Installation Instructions
1732E ArmorBlock Dual-Port
EtherNet/IP 4-Point Thermocouple and
RTD Input Modules
Catalog Numbers 1732E-IT4IM12R, 1732E-IR4IM12R
Table of Contents
Topic
Preventing Electrostatic Discharge
Connect the I/O, Network and Auxiliary Cables to the Module
Page
2 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ ) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 3
Environment and Enclosure
ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication.
Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
, for additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1732E-IN005B-EN-E - September 2012
4 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Additional Resources
Resource
1732E ArmorBlock™ Dual-Port EtherNet/IP 4-Point
Analog Modules Wiring Diagrams 1732E-WD003
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point
Thermocouple and RTD Input Modules User Manual
1732E-UM004
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Description
Pinout guide wiring diagram for the ArmorBlock dual-port EtherNet/IP 4-Point Analog modules
(1732E-IF4M12R, 1732E-OF4M12R,
1732E-IT4IM12R, 1732E-IR4IM12R).
A detailed description of module functionality, configuration, installation procedure and information on how to use the ArmorBlock dual-port EtherNet/IP 4-Point Thermocouple and
RTD modules (1732E-IT4IM12R,
1732E-IR4IM12R).
More information on proper wiring and grounding techniques.
If you would like a manual, you can:
• download a free electronic version from the internet: http://rockwellautomation.com/literature
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
Overview
The EtherNet/IP ArmorBlock is a 24V DC I/O module that communicates via
EtherNet/IP. The sealed IP65, IP67 and IP69K housing of these modules requires no enclosure. Note that environmental requirements other than IP65, IP67 and IP69K may require an additional appropriate enclosure. I/O connectors are micro M12 style.
EtherNet/IP networks use advanced network technology, for example, producer/consumer communication, to increase network functionality and throughput.
To learn more about features, configuration requirements, and calibration process for the
1732E-IT4IM12R and 1732E-IR4IM12R modules, see the 1732E ArmorBlock
Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules User Manual, publication 1732E-UM004 .
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 5
Module Identification
EtherNet/IP D-code
M12 connector
Function earth
(1)
EtherNet/IP D-code
M12 connector
Link 1 status indicator
Module status indicator
Link 2 status indicator
Network status indicator
Node address switches
I/O status indicators
M12 style
I/O connectors
Auxiliary power status indicator
Micro-style power in Micro-style power out
45871
(1) Function Earth grounds the I/O block’s EtherNet/IP communication circuitry which is designed to mitigate the effect of noise on the network. The device requires a solid earth ground connection, either through a metal screw to a grounded
metal panel or through a wire. See Ethernet Connector on page 11 for connections.
Publication 1732E-IN005B-EN-E - September 2012
6 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Optional Accessories
The following table identifies optional accessories that you can use with the modules that have to be ordered separately.
Option
Snap-in individual marker card
(1)
Cold Junction Compensation Terminal Chamber
(with embedded thermistor)
(2)
Catalog Number
1492-MD6X9
871A-TS4CJC-DM or 871A-TR4CJC-DM
(1)
Provides labelling for the terminal blocks to allow for easy identification and description.
(2)
Recommended for use with the 1732E-IT4IM12R module.
Catalog Number Explanation
Refer to the table for a description of the module catalog numbers.
Catalog Number
1732E-IT4IM12R
1732E-IR4IM12R
Description
24V DC power, 4-Point Isolated Thermocouple
Input, Dual-Port EtherNet/IP Module
24V DC power, 4-Point Isolated RTD Input,
Dual-Port EtherNet/IP Module
Network
Connector
Dual D-code
M12
Power
Connector
Dual 4-pin micro
Install the Module
To install the module:
• Set the network address
• Mount the module
• Connect the Functional Ground and Module power/Auxiliary power cables
• Connect the I/O and Network cables to the module
Set the Network Address
The I/O block ships with the rotary switches set to 999 and DHCP enabled.
To change the network address, you can do one of the following:
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 7
• adjust the switches on the front of the module.
• use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• retrieve the IP address from nonvolatile memory.
The I/O block reads the switches first to determine if the switches are set to a valid number. To set the network address:
1.
Remove power.
2.
Remove the switch dust caps.
3.
Rotate the three (3) switches on the front of the module using a small blade screwdriver.
4.
Line up the small notch on the switch with the number setting you wish to use.
Valid settings range from 001…254.
5.
Replace switch dust caps. Make sure not to over tighten.
6.
Reapply power.
7.
Record IP address on product label found on the side of enclosure.
Set Network Address
2
Example shows the node address switches at 163 , which sets the module IP address to 192.168.1.163.
0
4
8 6
2 2
4
Note: You need to remove the protective switch dust caps before you can adjust the address settings.
0
8
6
0
8 6
4
44233
When the switches are set to a valid number, the I/O block’s IP address is 192.168.1.xxx, where xxx represents the number set on the switches. The I/O block’s subnet mask is
255.255.255.0 and default gateway address is set to 192.168.1.1.
When the I/O block uses the network address set on the switches, the I/O block does not have a host name assigned to it or use any Domain Name Server.
If the switches are set to an invalid number (for example, 000 or a value greater than 254 excluding 888), the I/O block checks to see if DHCP is enabled. If DHCP is enabled, the
I/O block asks for an address from a DHCP server. The DHCP server also assigns other
Transport Control Protocol (TCP) parameters. The modules are shipped with the network switches set to 999.
Publication 1732E-IN005B-EN-E - September 2012
8 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
If DHCP is not enabled, the I/O block uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.
Network Address Switch value 001
The module IP address cannot be the same as the gateway address. If the address switches are set to 001, the module IP address becomes 192.168.1.1, which is the same as the default gateway address. In this case, the module gateway address will be set to 0.0.0.0.
Default Factory Configuration
The switch value 888 resets the module to default factory configuration on power up. The module will not operate properly when powered up with this setting. The switches must be set to a different (and valid) value and then power cycled after a reset.
While in reset state, the module LED flashes red and the network LED goes off.
Mount the Module
Two sets of mounting holes are used to mount the module directly to a panel or machine.
Mounting holes accommodate #6 (M3) pan head screws. The torque specification is
0.68 Nm (6 lb-in.).
Product Dimensions
Refer to the mounting dimensions illustration to help you mount the module.
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 9
Module Dimensions
37 (1.46)
16.2 (0.64)
19.8
(0.78)
166.5 (6.56)
179 (7.05)
168.6 (6.64)
32
(1.26)
)URQW0RXQWLQJ
18
(0.71)
27
(1.06)
6LGH0RXQWLQJ
Measurements are in
millimeters (inches)
45870
Publication 1732E-IN005B-EN-E - September 2012
10 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Mount the Module in High Vibration Areas
If you mount the module in an area that is subject to shock or vibration, we recommend you use a flat and a lock washer to mount the module. Mount the flat and the lock washer as shown in the mounting illustration. Torque the mounting screws to 0.68 Nm (6 lb-in.).
High Vibration Area Mounting
Lock washer
Flat washer
45768
Connect the I/O, Network and Auxiliary Cables to the Module
The 1732E-IT4IM12R and 1732E-IR4IM12R modules have 5-pin micro-style M12 I/O connectors. We provide caps to cover the unused connectors on your module. Connect the quick-disconnect cord sets you selected for your module to the appropriate ports.
I/O Connectors
Micro-style M12 5-Pin Input Female Connector – 1732E-IT4IM12R
2
1
5
3
4
(View into connector)
Pin 1 CJC +
Pin 2 TC +
Pin 3 CJC -
Pin 4 TC -
Pin 5 No Connect
45868
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 11
Micro-style M12 5-Pin Input Female Connector – 1732E-IR4IM12R
2
1
5
3
4
(View into connector)
Pin 1 No Connect
Pin 2 A
Pin 3 B
Pin 4 C
Pin 5 No Connect
A
B
C
45868
Ethernet Connector
D-Code Micro Network Female Connector
4
1
3
2
5 (View into connector 1)
Pin 1 M12_Tx+
Pin 2 M12_Rx+
Pin 3 M12_Tx-
Pin 4 M12_Rx-
Pin 5 Connector shell shield GND
44808
IMPORTANT Use the 1585D–M4DC–H: Polyamide small body unshielded mating connectors for the D-Code M12 female network connector.
Note that the distance between the center of each Ethernet connector is
16.2 mm (see Module Dimensions on page 9). Rockwell Automation
recommends the use of suitable cable based on this measurement. Some of the recommended cables are 1585D-M4TBJM-x and 1585D-M4TBDM-x for daisychains.
Publication 1732E-IN005B-EN-E - September 2012
12 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
IMPORTANT Use two twisted pair CAT5E UTP or STP cables.
3
4
1
2
D-Code
M12 Pin
Wire Color
White-orange
White-green
Orange
Green
Signal
TX+
RX+
TX-
RX-
2
6
1
3
8-way Modular
RJ45 Pin
ATTENTION: The device does not provide bonding or grounding terminal.
Customer shall provide own bonding or grounding.
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 13
Configure the Module
Refer to the illustration for configuration operations.
Configure Operations
Functional ground
EtherNet/IP D-code
M12 connector
EtherNet/IP D-code
M12 connector
Network address switches
M12 style
I/O connectors
Power connector Power connector
45871
Refer to On-Machine Connectivity Catalog, publication M117-CA001 , for
Rockwell Automation cable and cord set offerings or use the configuration tools available at www.ab.com/e-tools/ .
Publication 1732E-IN005B-EN-E - September 2012
14 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Power Connectors
Attach the micro-style 4-pin connector to the micro-style 4-pin receptacle as shown below.
Micro-style 4-Pin Input Male Receptacle
Male Input Female Output
3
2
4
1
(View into receptacle)
Pin 1 Auxiliary power+
Pin 2 Module power+
Pin 3 Module power-
Pin 4 Auxiliary power-
1
2
4
3
45764 45763
The power required by the module is based on a 4-pin micro-style connector system.
Power can be daisy chained through the module either left to right or right to left. The standard configuration is with Module/Auxiliary power entering the module on the left connector.
Both modules require two 24V DC (nominal) supplies. These supplies are called the
Module Power and the Auxiliary Power. The Module power supplies the microprocessor and Ethernet portions of the module, while the Auxiliary power supplies the I/O circuits.
Internally, the Module Power and Auxiliary Power are electrically isolated.
IMPORTANT The maximum current that any pin on the power connectors can
carry is 4 A.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment and all connected I/O must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Limited Voltage/Limited Current.
ATTENTION: The device meets UL Type 1 Enclosure rating.
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 15
Interpret LED Indicators
This module has the following indicators:
• Network, Module, and Link status indicators for EtherNet/IP
• Auxiliary power status indicator
• Individual I/O status indicators for inputs
Status Indicators
Link 1 status indicator
Module status indicator
Link 2 status indicator
Network status indicator
I/O status indicators
Auxiliary power
status indicator
45871
Publication 1732E-IN005B-EN-E - September 2012
16 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Indicator Status for the Modules
Indicator
Module status
Status
Off
Flashing red/green
Network status
Network link status
(Link 1/Link 2)
Auxiliary
Power status
Green
Flashing red
Red
Off
Flashing green
Green
Flashing red
Red
Flashing red/green
Off
Green
Flashing green
Yellow
Flashing yellow
Off
Green
Description
No power applied to the device.
The module is performing POST (Power-On Self Test), which completes within 30 s.
Device operating normally.
Module has experienced a recoverable fault. Possible minor faults include the following:
• IP Address switches do not match configuration in use.
• The device has completed a reset to factory default request due to the switches being set to 888 at power up, and a power cycle is required.
• The device is performing a firmware flash update.
• Channel fault
• No auxiliary power
Unrecoverable fault – may require device replacement.
The device is not initialized or the module does not have an
IP address.
The device has no CIP connections. The device has an IP address, but no CIP connections are established.
Device is online, has an IP address. CIP connections are established.
One or more connections have timed out.
The module has detected that its IP address is
already in use.
The module is performing a power-on self test (POST).
No link established.
Link established on indicated port at 100 Mbps.
Link activity present on indicated port at 100 Mbps.
Link established on indicated port at 10 Mbps.
Link activity present on indicated port at 10 Mbps.
Auxiliary power off or not connected.
Auxiliary Power applied to device.
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 17
Indicator Status for the Modules
Indicator
I/O status
Status
Off
Flashing Green
Green
Flashing Yellow
Flashing Red
Red
Description
The input channel is inactive, can be calibrated.
Channel is calibrating.
Normal operation, inputs being scanned.
Thermistor fault.
Fault. Overrange, underrange, or process alarm is present.
No power is detected.
IMPORTANT The Module Status LED indicator will flash red and green for a maximum
30 s while the module completes its POST (Power-On Self Test).
Specifications
General Specifications
Attributes
Voltage, power, max
Voltage, power, min
Module power
Power consumption
Isolation voltage
Communication rate
Value
30V DC
12V DC
12…30V DC @ 300 mA
3 W @ 24V DC, typical
3.5 W, max (module unloaded)
50V (continuous), Basic Insulation Type
Type tested @ 707V DC for 60 s
EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment
Publication 1732E-IN005B-EN-E - September 2012
18 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
General Specifications
Attributes
Status indicators
Dimensions, approx., HxWxD
Weight, approx.
Wiring category
(1)
Value
Module status – red/green
Network status – red/green
Link status – green/yellow
Auxiliary power status – green
I/O LED – red/green
179 x 37 x 27 mm (7.05 x 1.46 x 1.06 in.)
0.34 kg (0.75 lb)
1 – on signal ports
1 – on power ports
1 – on communication ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to publication 1770-4.1
, Industrial
Automation Wiring and Grounding Guidelines.
Input Specifications – 1732E-IT4IM12R
Attributes
Number of inputs
Resolution, min
Data format
Value
4, isolated
16 bits
Signed integer
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 19
Input Specifications – 1732E-IT4IM12R
Attributes
Thermocouple types
Value
Type
B
C
Material Temperature
Range °C (°F)
Pt /30% Rh vs. Pt/5% Rh 40…1820
(104…3308)
W/5% Re vs. W/26% Re 0…2320
(32…4208)
E
J
Ni/Cr vs. Cu/Ni
Ni/Cr vs. Cu/Ni
-270…1000
(-454…1832)
-210…1200
(-346…2192)
K
N
R
S
T
Ni/Cr vs. Ni/Al
Ni/14.2%Cr/1.4%Si vs.
Ni/4.4%Si/0.1%Mg
Pt/13%Rh vs. Pt
Pt/10%Rh vs. Pt
Cu vs. Cu/Ni
-270…1372
(-454…2501.6)
-270…1300
(-454…2372)
-50…1768
(-58…3214.4)
-50…1768
(-58…3214.4)
-270…400
(-454…752)
Voltage
Range (mV)
0…13.820
0…37.107
-9.835…76.373
-8.095…69.553
-6.458…54.886
-4.345…47.513
-0.226…21.101
-0.236…18.693
-6.258…20.872
Rockwell Automation 871A-TS4CJC-DM, 871A-TR4CJC-DM CJC Terminal Chamber recommended
Cold junction compensation range
Cold junction compensation modes
Thermistor types supported
Input voltage range
Accuracy
Accuracy drift with temperature
Calibration
0…70 °C (32…158 °F) for 302 type thermistors
Average Selected, Channel Independent, and CJC Offset
(For more information, see the User Manual, publication 1732E-UM004 )
Thermometrics MF65F302V/W or DC95F302V/W
±78.125 mV
0…78.125 mV
0.1% Full Scale @ 25 °C (77 °F)
30 ppm % Full Scale /°C @ 25 °C (77 °F)
Factory calibrated. Calibration is also supported through RSLogix 5000.
Publication 1732E-IN005B-EN-E - September 2012
20 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Input Specifications – 1732E-IT4IM12R
Attributes
Common mode rejection rate
Normal mode rejection rate
Sample Rate Filters
(1)
Value
120 dB @ 50/60 Hz
100 dB @ 50/60 Hz
50 Hz
60 Hz
250 Hz
500 Hz
(1)
Sample Rate/Notch Filter Frequency, selectable per channel.
Input Specifications – 1732E-IR4IM12R
Attributes
Number of inputs
Resolution, min
Data format
Sensors supported
Sensor Types
Value
4, isolated
16 bits
16-bit sign magnitude
100…200 =0.00385/0.003916 Pt RTD
100/120
Ni RTD
10
Cu
=0.00427 RTD
100
Pt 385
200
Pt 385
100 Pt 3916
200
Pt 3916
10
Cu 427
120
Ni 672
100
Ni 618
120
Ni 618
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 21
Input Specifications – 1732E-IR4IM12R
Attributes
Input range
Value
RTD type Temperature
Range (°C)
100
Pt 385
200
Pt 385
0…390.48
-200…850 °C
0…781
-200…850 °C
100
Pt 3916 0…337.03
-200…630 °C
200
Pt 3916 0…674.06
-200…630 °C
10
Cu 427
120
Ni 672
100
Ni 618
120
Ni 618
0…19.116
0…445.10
0…198.88
0…238.65
-320…500 °C
-70…445 °C
-60…180 °C
-90…140 °C
0.1% Full Scale @ 25 °C (77 °F)
30 ppm % Full Scale /°C @ 25 °C (77 °F)
Voltage Range
Accuracy
Accuracy drift with temperature
Calibration
Sample Rate
Filters
(1)
Factory calibrated. Calibration is also supported through RSLogix 5000.
50 Hz
60 Hz
250 Hz
500 Hz
120 dB @ 50/60 Hz Common Mode
Rejection Ratio
Normal Mode
Rejection Ratio
100 dB @ 50/60 Hz
(1)
Sample rate filter selectable on a module basis only.
0…156.25 mV
0…312.5 mV
0…156.25 mV
0…312.5 mV
0…19.53 mV
0…156.25 mV
0…78.125 mV
0…78.125mV
Publication 1732E-IN005B-EN-E - September 2012
22 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Environmental Specifications
Attribute
Temperature, operating
Temperature, nonoperating
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Temperature, ambient, max
60 °C (140 °F)
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
Emissions
ESD immunity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
CISPR 11:
Group 1, Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
EFT/B immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports
±3 kV at 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from150 kHz…80 MHz
Enclosure type rating Meets IP65/66/67/69K (when marked)
Publication 1732E-IN005B-EN-E - September 2012
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 23
Certifications
Certification (when product is marked)
(1) c-UR-us
CE
C-Tick
KC
EtherNet/IP
Value
UL Recognized Component Industrial Control Equipment, certified for US and Canada. See UL File E322657.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Korean Registration of Broadcasting and Communications
Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
ODVA conformance tested to EtherNet/IP specifications.
(1)
See the Product Certification link at http://www.ab.com
for Declarations of Conformity, Certificates, and other certification details.
Publication 1732E-IN005B-EN-E - September 2012
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ , you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/ .
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
contact your local Rockwell Automation representative.
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
Allen-Bradley, Rockwell Automation, ArmorBlock, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1732E-IN005B-EN-E - September 2012
Supersedes Publication 1732E-IN005A-EN-E - July 2012 Copyright © 2012 Rockwell Automation, Inc. All rights reserved.