Advertisement
Advertisement
FLEX I/O Frequency Input Module
Catalog Numbers 1794-IJ2, 1794-IJ2K, 1794-IJ2XT
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD
Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, FLEX I/O, RSLinx, RSLogix 5000 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
New and Updated
Information
Summary of Changes
This manual contains new and updated information. Changes throughout this revision are marked by change bars, as shown to the right of this paragraph.
This table contains the changes made to this revision.
Topic
Inclusion of two catalogs, 1794-IJ2K and 1794-IJ2XT
The first chapter has been updated with the following topics:
•The FLEX System
•Type of Modules
•The FLEX I/O Module in a Logix Control System
The wiring illustration for terminal base units has been updated.
The following topics have been added:
•Configure Your FLEX I/O Module with RSLogix 5000
(Chapter 3)
•Troubleshoot the Module (Chapter 5)
•Electronic Data Sheet (EDS) Files
The Specifications topic (Appendix A) has been updated to include specifications for 1794-IJ2K, and 1794-IJ2XT.
"Program Your Module" is now moved to the appendices section. It was previously Chapter 3 in the last revision.
69
Page
iii Publication 1794-6.5.11 - September 2011
iv Summary of Changes
Notes:
Publication 1794-6.5.11 - September 2011
v
Table of Contents
Summary of Changes
New and Updated Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Preface
Who Should Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Purpose of the Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
About the Vocabulary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . xii
Overview of the Frequency Input
Module
Chapter 1
Usage of the Frequency Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . 2
The FLEX I/O Module in a Logix Control System . . . . . . . . . . . . . . . 3
Selecting the Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Implementing Application Features . . . . . . . . . . . . . . . . . . . . . . . . . 7
How Frequency Is Calculated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Frequency Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Termination on Number of Pulses . . . . . . . . . . . . . . . . . . . . . . . . . 10
Missing Pulse Multiplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Direction Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Install Your FLEX I/O Frequency
Input Module
Chapter 2
Before You Install Your Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mount on a DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mount on a Panel or Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mount the Frequency Input Module on the Terminal Base
Wiring the Terminal Base Units (1794-TB3G shown) . . . . . . . . . 20
Wire the Terminal Base Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Connect Wiring to the FLEX I/O Frequency Input Module . . . . 21
Connecting Wiring Using a 1794-TB3G, 1794-TB3GK or
1794-TB3GS Terminal Base Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Resolution and Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Examples of Wiring to a 1794-TB3G Terminal Base Unit . . . . . . 27
Publication 1794-6.5.11 - September 2011
vi Table of Contents
Configure Your FLEX I/O Module with RSLogix 5000 Software
Chapter 3
Add and Configure the FLEX I/O Module. . . . . . . . . . . . . . . . . . . . . 29
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Troubleshoot the Module
Read and Write Configuration
Maps for the FLEX I/O Module
Specifications
Chapter 4
Diagnostic Bits in Word 5 of the BTR File . . . . . . . . . . . . . . . . . 37
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Chapter 5
Configure Your Frequency Input Module . . . . . . . . . . . . . . . . . . . . . . 39
Read Data From Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Map Data for the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Frequency Input Module Image Table Mapping . . . . . . . . . . . . . 40
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Appendix A
What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Appendix B
Electronic Data Sheet (EDS) Files
Updating EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
EDS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Schematics
Appendix C
What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Gate Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
DC to DC Converters – 24V DC Power Supplies . . . . . . . . . . . . 63
Programming Your Module with
PLC Processors
Appendix D
Enter Block Transfer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PLC-2 Family Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
PLC-3 Family Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
PLC-5 Family Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
PLC-5/250 Family Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Index
Publication 1794-6.5.11 - September 2011
ix
Who Should Use This
Manual
Purpose of the Manual
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
• terminology used in this manual
We assume that you have previously used an Allen-Bradley programmable controller, that you are familiar with its features, and that you are familiar with the terminology we use. If not, read the user manual for your processor before reading this manual.
This manual is a reference guide for the 1794 Frequency Input Modules. It describes the procedures for installing, configuring and troubleshooting your module.
For information on
Overview of the Frequency Input Module
Install Your FLEX I/O Frequency Input Module
Configure Your FLEX I/O Module with RSLogix 5000 Software
Read and Write Configuration Maps for the FLEX I/O Module
Electronic Data Sheet (EDS) Files
Program Your Module with PLC Processors
See
About the Vocabulary
In this manual, we refer to:
• the frequency input module as the “input module”
• the Programmable Controller as the “controller”
Publication 1794-6.5.11 - September 2011
x Preface
Related Documentation
The following documents contain additional information concerning Rockwell
Automation products. To obtain a copy, contact your local
Rockwell Automation office or distributor.
Resource Description
FLEX I/O Product Profile, publication 1794-PP019 xxxxx Comprehensive product profile for the FLEX I/O product line.
FLEX I/O ControlNet Redundant Media Adapter, publication 1794-5.18
x xxxx
FLEX I/O EtherNet/IP Adapter Module Installation
Instructions, publication 1794-IN082 x xxxx
FLEX I/O ControlNet Adapter Module Installation
Instructions, publication 1794-IN128 x xxxx
Information on how to install the FLEX I/O ControlNet Redundant Media
Adapter (1794-ACNR).
Information on how to install the FLEX I/O EtherNet/IP Adapter Module
(Catalog No. 1794-AENT).
Information on how to install the ControlNet Adapter Modules
(Catalog No. 1794-ACN15, 1794-ACN15K, 1794-ACNR15, 1794-ACNR15XT,
Series D).
FLEX I/O DeviceNet Adapter Module Installation
Instructions, publication 1794-IN099 x xxxxxxxxxxxxx
Remote I/O Adapter Modules Installation Instructions, publication 1794-IN098 x xxxxxxxxxxxxx
Remote I/O Adapter Module User Manual, publication
1794-UM009 x xxxxxxxxxxxxx
FLEX I/O PROFIBUS Adapter Module Installation
Instructions, publication 1794-IN087 x xxxxxxxxxxxxx
Information on how to install the FLEX I/O DeviceNet Adapter Modules
(Catalog No. 1794-ADN, 1794-ADNK).
Information on how to install the Remote I/O Adapter Modules
(Catalog No. 1794-ASB, 1794-ASB2, 1794-ASBK, 1794-ASB2K).
Information on how to use the Remote I/O Adapter Module
(Catalog No. 1794-ASB).
Information on how to install the FLEX I/O PROFIBUS Adapter
(Catalog No. 1794-APB).
FLEX I/O PROFIBUS Adapter Module User Manual, publication publication publication
1794-UM057
1794-IN093
1794-6.5.2
x xxxxxxxxxxxxx
Flex I/O Digital Input Modules Installation Instructions,
x xxxxxxxxxxxxx
Flex I/O Digital DC Sourcing Input and Sinking Output
Modules Installation Instructions, publication 1794-IN095 x xxxxxxxxxxxxx
Flex I/O Digital DC Sourcing Output Modules Installation
Instructions, publication 1794-IN094 x xxxxxxxxxxxxx
Flex I/O Input/ Output Module Installation Instructions, publication 1794-IN083 x xxxxxxxxxxxxx
Flex I/O 8 Output Relay Module Installation Instructions, publication 1794-IN019 x xxxxxxxxxxxxx
FLEX I/O Input, Output and Input/Output Analog Modules
Installation Instructions, publication 1794-IN100 xxxxxxx
FLEX I/O Analog Module User Manual,
x xxxxxxxxxxxxx
FLEX I/O Isolated Analog Output Module Installation
Instructions, publication 1794-IN037 x xxxxxxxxxxxxx
Information on how to use the FLEX I/O PROFIBUS Adapter Module
(Catalog No. 1794-APB).
Information on how to install the Flex I/O Digital Input Modules
(Catalog No. 1794-IB8, 1794-IB16, 1794-IB16K, 1794-IB32).
Information on how to install the Flex I/O Digital DC Sourcing Input and
Sinking Output Modules (Catalog No. 1794-IV16, 1794-OV16, 1794-OV16P).
Information on how to install the Flex I/O Digital DC Sourcing Output Modules
(Catalog No. 1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P, 1794-OB32P).
Information on how to install the Flex I/O Input/ Output Modules
(Catalog No. 1794-IB16XOB16P, 1794-IB10XOB6).
Information on how to install the Flex I/O 8 Output Relay Modules
(Catalog No. 1794-OW8, 1794-OW8K, 1794-OW8XT).
Information on how to install the FLEX I/O Input, Output and Input/Output
Analog Modules (Catalog No. 1794-IE8, 1794-IE4XOE2, 1794-OE4, 1794-IE8K,
1794-OE4K).
Information on how to install the FLEX I/O Analog Modules
(Catalog No. 794-OE4, 1794-IE8, 1794-IE12, 1794-OE12, 1794-IE4XOE2,
1794-IE8XOE4, 1794-IE4XOE2XT, 1794-IE8XT, 1794-OE4XT).
Information on how to install the FLEX I/O Isolated Analog Output Module
(Catalog No. 1794-OF4I).
Publication 1794-6.5.11 - September 2011
Preface xi
Resource
FLEX I/O 4 Isolated Input Module Installation Instructions, publication 1794-IN038 x xxxxxxxxxxxxx
Information on how to install the FLEX I/O 4 Isolated Input Module
(Catalog No. 1794-IF4I).
FLEX I/O 2 In/2 Out Isolated Analog Combo Module
Installation Instructions, publication xxxxxxxxxxxxx
1794-IN039
FLEX I/O Isolated Analog Modules User Manual, publication 1794-6.5.8
x xxxxxxxxxxxxx
x
Description
Information on how to install the FLEX I/O 2 In/2 Out Isolated Analog Combo
Module (Catalog No. 1794-IF2XOF2I).
Information on how to use the FLEX I/O Isolated Analog Modules
(Catalog No. 1794-IF4I, 1794-OF4I, 1794-IF2XOF2I, 1794-IF4IXT, 1794-IF4ICFXT,
1794-OF4IXT, 1794-IF2XOF2IXT).
FLEX I/O 8 Thermocouple Input Module Installation
Instructions, publication 1794-IN021 x xxxxxxxxxxxxx
FLEX I/O 8 Input RTD Module User Manual, publication 1794-6.5.4
x xxxxxxxxxxxxx
FLEX I/O Thermocouple/Millivolt Input Module User
Manual, publication 1794-6.5.7
x xxxxxxxxxxxxx
FLEX I/O Thermocouple/RTD Input Analog Module
Instructions, publication 1794-IN050 x xxxxxxxxxxxxx
2-Input Frequency Module Installation Instructions, publication 1794-IN049 x xxxxxxxxxxxxx
Information on how to install the FLEX I/O 8 Thermocouple Input Modules
(Catalog No. 1794-IT8, 1794-IR8).
Information on how to use the FLEX I/O 8 Input RTD Module
(Catalog No. 1794-IR8).
Information on how to use the Thermocouple and Millivolt Input Module
(Catalog No. 1794-IT8).
Information on how to install the Thermocouple/Millivolt Input Modules
(Catalog No. 1794-IRT8, 1794-IRT8K, 1794-IRT8XT).
Information on how to install the 2-Input Frequency Module
(Catalog No. 1794-IJ2, 1794-IJ2K, 1794-IJ2XT).
FLEX I/O Thermocouple, RTD, mV Input Modul, publication
1794-6.5.12
x xxxxxxxxxxxxx
24V FLEX I/O 2 Channel Incremental Encoder Module
Installation Instructions, publication xxxxxxxxxxxxx
1794-IN063 x
Information on how to use the FLEX I/O Thermocouple, RTD, mV Input Module
(Catalog No. 1794-IRT8, 1794-IRT8K, and 1794-IRT8XT).
Information on how to install the 24V FLEX I/O 2 Channel Incremental Encoder
Module (Catalog No. 1794-ID2).
FLEX Integra Analog Module User Manual, publication 1793-6.5.1
x xxxxxxxxxxxxx
FLEX I/O 4 Channel Pulse Counter Module Installation
Instructions, publication 1794-IN064 x xxxxxxxxxxxxx
FLEX I/O Very High Speed Counter Module Installation
Instruction, publication 1794-IN067 x xxxxxxxxxxxxx
Information on how to install the FLEX Integra Analog Module (Catalog No.
1793-IE2X0E1,1793-IE2XOE1S, 1793-IE4, 1793-IE4S, 1793-OE2, 1793-OE2S).
Information on how to install the 24V DC FLEX I/O 4-Channel Module
(Catalog No. 1794-IP4).
Information on how to install the Very High Speed Counter Module
(Catalog No. 1794-VHSC).
FLEX I/O 48V DC Input and Output Modules Installation
Instructions, publication 1794-IN105 x xxxxxxxxxxxxx
FLEX I/O AC Digital Input Modules Installation
Instructions, publication 1794-IN102 x xxxxxxxxxxxxx
FLEX I/O Digital AC Output Modules Installation
Instructions, publication 1794-IN103 x xxxxxxxxxxxxx
FLEX I/O 220V AC Input and Output Modules Installation
Instructions, publication 1794-IN104 x xxxxxxxxxxxxx
FLEX I/O Terminal Base Units Installation Instructions, publication 1794-IN092 x xxxxxxxxxxxxx
Interconnect Cable Installation Instructions, publication 1794-5.12
x xxxxxxxxxxxxx
Information on how to install the FLEX I/O 48V DC Input and Output Modules
(Catalog No. 1794-IC16, 1794-OC16).
Information on how to install the FLEX I/O AC Input Modules
(Catalog No. 1794-IA8, 1794-IA8I, 1794-IA16).
Information on how to install the FLEX I/O Digital AC Output Modules
(Catalog No. 1794-OA8, 1794-OA8K, 1794-OA8I, 1794-OA16).
Information on how to install the FLEX I/O 220V AC Input and Output Modules
(Catalog No. 1794-IM8, 1794-OM8).
Information on how to install the FLEX I/O Terminal Base Units
(Catalog No. 1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S, 1794-TB32,
1794-TB3G, 1794-TB3GK, 1794-TB3GS, 1794-TB3T, 1794-TB3TS, 1794-TBN,
1794-TBNK, 1794-TBNF).
Information on how to install the Interconnect Cable
(Catalog No. 1794-CE1, 1794-CE3).
Publication 1794-6.5.11 - September 2011
xii Preface
Resource
FLEX I/O DC Power Supply Installation Instructions, publication 1794-IN069 x xxxxxxxxxxxxx
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
x xxxxxxxxxxxxx
Rockwell Automation Industrial Automation Glossary,
AG-7.1
x xxxxxxxxxxxxx
Description
Information on how to install the FLEX I/O DC Power Supply
(Catalog No. 1794-PS13, 1794-PS3).
In-depth information on grounding and wiring Allen-Bradley programmable controllers.
A glossary of industrial automation terms and abbreviations.
Common Techniques Used in this Manual
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
Publication 1794-6.5.11 - September 2011
1
Overview
The FLEX System
Adapter
Chapter
1
Overview of the Frequency Input Module
This chapter provides a description of the application and capabilities of the
1794 FLEX I/O Frequency Input module. It also explains the general algorithm for calculating frequency.
Topic
Usage of the Frequency Input Module
The FLEX I/O Module in a Logix Control System
Page
FLEX I/O is a small, modular I/O system for distributed applications that performs all of the functions of rack-based I/O. The FLEX system contains the following components shown below:
Terminal base I/O module
2
+
2
+
1794-IRT8
45568
• Adapter – transfers read and write configuration data to and from the
I/O module
• terminal base – contains a terminal strip to terminate wiring for two- or three-wire devices
Publication 1794-6.5.11 - September 2011
2 Overview of the Frequency Input Module
• I/O module – contains the bus interface and circuitry needed to perform specific functions related to your application
The 1794 FLEX system consists of an adapter module, terminal base unit,
DIN rail, power supply, and adapter cabling components. You can use up to 8 terminal bases per adapter module.
For detailed instructions to set up and install your module, refer to the topic,
Install Your FLEX I/O Frequency Input Module, on page 13.
Type of Modules
The FLEX I/O Frequency Input modules refer to the following catalogs.
Catalog No.
Voltage Inputs Outputs Description
1794-IJ2 24V DC 2 2 Digital – 2-pt 24V DC input frequency module
1794-IJ2K 24V DC 2 2
1794-IJ2XT 24V DC 2 2
Digital – 2-pt 24V DC input frequency module, conformally coated.
Digital – 2-pt 24V DC input frequency module for extended temperature.
The frequency input module is an intelligent I/O module designed to perform high-speed frequency algorithms. The module provides:
• 2 Frequency Inputs,
• 2 Gate Inputs and
• 2 Outputs.
The Frequency Inputs can accept frequencies up to 32,767 Hz and it accepts and returns binary data.
Usage of the Frequency
Input Module
The FLEX I/O Frequency Input module is essentially a tachometer with the capability of reporting frequency, acceleration, and direction. Outputs are activated by alarms. Input devices range from magnetic pickup to flowmeters, to incremental encoders to proximity detectors. This intelligent I/O module is designed to perform high-speed frequency algorithms.
Power to the module is supplied from an external power supply. All power for input devices (24V DC) is supplied by the I/O module. Outputs are used to set alarms depending on the input conditions.
The module measures frequency over a user-specified time interval. A frequency calculation can start before the time interval has elapsed, if a user-specified number of frequency input pulses have occurred.
Publication 1794-6.5.11 - September 2011
I n p u ts
Mod u le
FlexB u s
Overview of the Frequency Input Module 3
The primary use of the module is accurate, high-speed frequency measurement. A high-speed internal clock is synchronized with the frequency input to count over a user-selected sampling time or a user-defined number of frequency input pulses.
All power for input devices (4 devices, 24 V DC @ 15 mA max) is supplied by the I/O module.
Gate input Frequency input
500/50 mV
50 mV
Select
GND
IEC 1+/Contact
24Vpower
Input
Magnetic 24V IEC 1+
IEC 1+/Contact
Input 24V Power
GND
50 mV
Select
500/50 mV
Vortex
3Vin 6Vin 24V power
24V IEC 1+ Magnetic VORTEX
Invert
Y/N
Inter-processor communication, uP system 0/1
Invert
Y/N uP system 0
Input control
Processing
Counter
Direction data
Frequency / count data
Output control
CRISP
Bus interface
Output 0 Output 1
From uP system 1
Data To/From FlexBus
45388
The FLEX I/O Module in a
Logix Control System
The frequency input module performs high-speed frequency and/or scaling calculation operations for various industrial applications. The module interfaces with a FLEX I/O family adapter which then communicates with a programmable controller processor that has block-transfer capability and external I/O devices.
The adapter transfers data to the module (block transfer write) and from the module (block transfer read) using BTW and BTR instructions in your ladder diagram program. These instructions let the adapter read input values and status from the module, and let you write output values and configure the module mode of operation. The following illustration describes the communication process.
Publication 1794-6.5.11 - September 2011
4 Overview of the Frequency Input Module
Typical Communication between a FLEX I/O Module and an Adapter
1794-ACN15
1794-ACNR15
1794-ACNR15K
1794-ADN
1794-AENT
1794-APBDPV1
1794-ASB
1794-APB
Adapter
1794-AENT shown
1
The adapter transfers your configuration data to the module using a BTW.
FlexBus
FREQUENCY INPUT 2 CHANNEL
4
Your ladder program instructs the adapter to perform a BTR of the values and stores them in a data table.
0
FREQ
F 0
GATE
F 1
FREQ
F 1
GATE
F
OUT
0
1794-IJ2
OUT
1
OK
1
2
External devices transmit frequency signals to the module.
5
The adapter module determines that the transfer was made without error and input values are within specified range.
6
Your ladder program can use and/or transmit the data (if valid) before it is overwritten by the transfer of new data in a subsequent transfer.
7
Your ladder program performs BTWs to the module when you power it up, and any time you wish to reconfigure the module.
3
The module converts frequency signals into integer format and stores these values until the adapter requests their transfer.
45339
Publication 1794-6.5.11 - September 2011
Typical Applications
Overview of the Frequency Input Module 5
A broader view of how the FLEX I/O module interfaces with the different elements in a Logix system is shown in the sample illustration below.
PC running controller and
Rockwell Automation configuration software
Panel V iew S tation
FLEX System
1794 Adapter
1794 FLEX I/O module
Bridge
Ethernet
45567
.
In this example, the FLEX I/O module communicates with the controller through the adapter. The controller can produce and consume tags. It can initiate MSG instructions that send and receive data or configure devices.
Configuration of devices and the network is done through the personal computer running the controller and configuration software.
To learn about the steps to configure your FLEX I/O module, see Configure
Your FLEX I/O Module with RSLogix 5000 Software on page 29.
ATTENTION
The following publications provide more information about
EtherNet/IP, and ControlNet modules in a Logix5000 system:
•EtherNet/IP Modules in Logix5000 Control Systems, publication ENET-UM001
•ControlNet Modules in Logix5000 Control Systems, publication CNET-UM001
You can use the frequency input modules in power management, automotive, food and beverage, and oil and gas industries for various flow and/or turbine metering applications. Some sample applications include:
• turbine shaft speed monitoring
• automotive paint booths
• brewery flow monitoring
• petrochemical flow and custody transfer
Publication 1794-6.5.11 - September 2011
6 Overview of the Frequency Input Module
Input Capabilities
The frequency module has 2 input channels (mode dependent). Each of the 2 input channels may accept these input signals:
• magnetic pickup – 500 mV…28V AC peak (optional 50 mV…28V AC peak for increased signal sensitivity)
• proximity probe inputs
– compatible with Bently Nevada 3300 – 5 mm (0.197 in.) and 8 mm
(0.315 in.) – proximity transducer systems
– provides 1 isolated 24V DC power supply (2 channels rated at 30 mA each) to power external devices
– vortex flowmeter – 6V and 3V
You configure the 2 input channels for your specific application(s). Each input channel has two input selections:
F r eq u e n cy I n p u t (F0-F1) – you connect your input device to this input (ac, proximity sensors switch, magnetic, vortex )
Gate I n p u t (G0-G1) – you connect your input device to this input (ac, proximity sensors switch, magnetic, vortex )
used to determine direction – CW or CCW
0
FREQ
F
Allen-Bradley
FREQUENCY INPUT 2 CHANNEL
0
GATE
F 1
FREQ
F 1
GATE
F
OUT
0
1794-IJ2
1
OUT
1
OK
2 input channels
Frequency Input (F0)
Gate Input (G0)
Channel 0
Frequency Input (F1)
Gate Input (G1)
Channel 1
45557
Publication 1794-6.5.11 - September 2011
Overview of the Frequency Input Module 7
Selecting the Modes of Operation
You configure the frequency input module for these modes of operation:
Modes of Operation
Mode Use this mode to
Frequency and
% Full Scale
•Monitor the frequency of an input with high accuracy (for example, shaft)
•Monitor the percentage of full scale frequency
•Operate frequency alarm (% full scale)
•Scale the frequency
•Monitor the direction of shaft rotation
•Wire-off alarm with DC devices
•Missing pulse alarm
Frequency and Acceleration •Monitor the frequency of an input with high accuracy (for example, shaft)
•Monitor the acceleration (rate of speed change)
•Operate acceleration alarm (rate of change)
•Scale the frequency
•Monitor the direction of shaft rotation
•Wire-off alarm with DC devices
•Missing pulse alarm
Indicators /
Alarms
Scaler /
Values x x x x x x x x
Output Capabilities
The frequency input module has 2 assignable outputs. These outputs are designed for applications that require fast response. The outputs:
• are current sourcing at 10…31.2V DC (1 A maximum per output)
• are electrically fused (current limited to 3 A)
• can be assigned to the associated input channel with user-selectable frequency and acceleration values
• are isolated – this lets you use two separate external power supplies if desired (one for output 0 and one for output 1)
Implementing Application Features
You can use the module to implement programmable application features that are usually initiated by your controller processor. This frees up the controller
Publication 1794-6.5.11 - September 2011
8 Overview of the Frequency Input Module processor to do other tasks and helps increase the overall throughput of your controller system.
Application Features
Feature
Frequency alarm
Acceleration alarm
Scaling
Mode
Frequency alarm selected
Acceleration alarm selected
% full scale and acceleration
Purpose
Activate alarm when calculated or scaled frequency is higher than user-specified frequency value.
Activate acceleration alarm when acceleration is greater than user-specified acceleration value.
Multiply and/or divide frequency by scalar
Alarm is ON when
Frequency > user-specified value
| Acceleration | > user-specified value
Frequency > User-specified scaled frequency value
How Frequency Is
Calculated
The following paragraphs explain the operation of the frequency input module algorithm and its modifying parameters.
Frequency Calculation
Frequency is determined by a general algorithm which can be modified by user-defined parameters. In its simplest form, the algorithm employs the user-defined Minimum Sampling Time to set a window in which to count pulses to determine the frequency. At least two pulses are required within the sample window. Frequency is determined by storing the time the first pulse occurred and then continually storing and updating the time of subsequent pulses, along with the number of pulses encountered. When the window expires, the frequency is calculated and the procedure repeats. The sequence and formula for determining frequency are shown below.
Publication 1794-6.5.11 - September 2011
Overview of the Frequency Input Module 9
Normal Mode Frequency Determination, at Least Two Pulses in Sampling Time
Missing pulse alarm would be reported after 2 s, if no pulse occurs
Frequency reported at end sampling time
=
Pulses counted
T2 - T1
Minimum sampling time
Frequency input pulses pulses counted
First pulse in window,
T1 time stored
T2, update as each pulse occurs
Last pulse in window
45340
If only one pulse occurs within the sampling window, when the sample time has expired, the window is extended to 2 s to allow for a second pulse to occur.
As soon as a second pulse occurs, the frequency is calculated and the procedures starts over. If no second pulse is detected, zero frequency is reported and a Missing Pulse Alarm is generated. The following figure depicts this scenario.
Normal Mode, Only One Pulse in Sampling Time,
Sampling Time Extended
Frequency reported at first pulse in extended Time
=
Missing pulse alarm is reported after 2 s, if no pulse occurs
2 - 1
T2 - T1
Minimum sampling time Frequency input pulses
2 = pulses counted Sampling time extended to 2 s
First pulse in window,
T1 time stored
First pulse after window extended,
T2 time stored
45341
Publication 1794-6.5.11 - September 2011
10 Overview of the Frequency Input Module
Termination on Number of Pulses
The normal mode is designed to provide wide bandwidth. However, it requires the full 2 seconds to report a missing pulse. Another user parameter, Number of Pulses to Terminate Sampling, is provided for scenarios where many pulses are expected within the sampling window, such that early determination of frequency is possible.
During normal operation, there is a sufficient number of pulses to prevent the module from entering the 2-second extension mode. Once the user-defined number of pulses is reached within the sampling window, the frequency is immediately reported.
If the sampling window has been extended to 2 seconds while waiting for a second pulse to occur, a situation which can occur during system startup, the module does not wait for the number of pulses to be reached. Instead, as soon as a second pulse occurs, the frequency is calculated based on the time between the 2 pulses, and the procedure starts over.
Termination on Number of Pulses
Frequency reported at number of pulses to terminate reached
=
Pulses to terminate - 1
T2 - T1
Missing pulse alarm would be reported after 2 seconds, if no pulse occurs
Minimum sampling time pulses to terminate
Frequency input pulses
45342
First pulse in window,
T1 time stored
T2, update as each pulse occurs
Number of pulses to terminate reached
Missing Pulse Multiplier
The last user parameter which is provided to modify the frequency algorithm is the Missing Pulse Multiplier. In this case, the user can set the number of
Minimum Frequency Sampling Time windows allowed to extend the time to capture a second pulse, before reporting a Missing Pulse Alarm. The intent with this parameter is to allow a tradeoff of the bandwidth available with the response time to report a missing pulse. This mechanism is shown in the following figure.
Publication 1794-6.5.11 - September 2011
Overview of the Frequency Input Module 11
Missing pulse multiplier
Frequency reported at first pulse in extended time
=
2 - 1
T2 - T1
Missing pulse alarm would be reported after last window, if no pulse occurs
Extended windows added one at time, until pulse occurs or multiplied windows exceeded
Minimum sampling time
2 = pulses counted
Possible extended window
Frequency input pulses
First pulse in window,
T1 time stored
First pulse in an extended window, T2 time stored
45343
Direction Detection
Direction detection is accomplished by using the Frequency input, Gate input, and two sensors. The module expects to see a Low to High transition on the
Frequency input, followed by a Low to High transition on the Gate input. This assumes both input polarity select bits are the same selection.
This corresponds to clockwise rotation. See illustration, Direction Detection –
Principle of Operation, on page 12. If a Low to High transition occurs on the
Gate input, followed by one on the Frequency input, the rotation is counterclockwise.
Publication 1794-6.5.11 - September 2011
12 Overview of the Frequency Input Module
M
2 x M
Direction Detection – Principle of Operation
Clockwise rotation
Sensor 0
Sensor 1
Gate input
IJ2 module
Frequency input
Sensor 0 (F)
Sensor 1 (G)
Clockwise
Rotation
Sensor 0 (F)
Sensor 1 (G)
Counter
Clockwise
Rotation
Chapter Summary
45344
In this chapter, you learned about the frequency input module, block transfer communication, and details of how the module functions.
Publication 1794-6.5.11 - September 2011
Chapter
2
Install Your FLEX I/O Frequency Input Module
Overview
Before You Install
Your Module
This chapter provides you with pre-installation requirements and instructions on how to install your FLEX I/O Frequency Input modules.
Topic
Before You Install Your Module
Mount the Frequency Input Module on the Terminal Base Unit
Connect Wiring to the FLEX I/O Frequency Input Module
Connecting Wiring Using a 1794-TB3G, 1794-TB3GK or 1794-TB3GS
Examples of Wiring to a 1794-TB3G Terminal Base Unit
Page
Before installing your frequency input module in the FLEX I/O system, you need to:
• calculate the power requirements of all modules in each FLEX I/O system, and
• position the keyswitch on the terminal base.
ATTENTION
This FLEX I/O module does not receive primary operational power from the backplane. 24V DC power must be applied to your module before installation. If power is not applied, the module position may appear to the adapter as an empty slot in your chassis.
Power Requirements
13
The wiring of the terminal base unit is determined by the current draw through the terminal base. Make certain that the current draw does not exceed 10 A.
Publication 1794-6.5.11 - September 2011
14 Install Your FLEX I/O Frequency Input Module
ATTENTION
Total current draw through the terminal base unit is limited to 10 A.
Separate power connections may be necessary.
The frequency input module requires 30 mA at 5V DC from the FlexBus backplane.
Methods of wiring the terminal base units are shown in the illustration below.
ATTENTION
Do not daisychain power or ground from the terminal base unit to any
AC or DC digital module terminal base unit.
Install the Module
Installation of the frequency input module consists of:
• mounting the terminal base unit
• installing the module into the terminal base unit
• installing the connecting wiring to the terminal base unit
Mount on a DIN Rail
ATTENTION
Do not remove or replace a terminal base unit when power is applied.
Interruption of the FlexBus can result in unintended operation or machine motion.
Install the Terminal Base Unit
1.
Remove the cover plug in the male connector of the unit to which you are connecting this terminal base unit.
Publication 1794-6.5.11 - September 2011
Install Your FLEX I/O Frequency Input Module 15
2.
Check to make sure that the 16 pins in the male connector on the adjacent device are straight and in line so that the mating female connector on this terminal base unit will mate correctly.
7
8
9
6
0
4
1
2
3
7
2
+
2
+
45319
Make certain that the female FlexBus connector is fully retracted into the base unit.
3.
Position the terminal base at a slight angle and hooked over the top of the 35 x 7.5 mm DIN rail A (Allen Bradley part number 199-DR1;
46277-3).
2
+
2
+
45320
4.
Slide the terminal base over tight against the adapter, or proceeding terminal base. Make sure the hook on the terminal base slides under the edge of the adapter, or proceeding terminal base, and the FlexBus connector is fully retracted.
5.
Rotate the terminal base onto the DIN rail with the top of the rail hooked under the lip on the rear of the terminal base.
Use caution to make sure that the female FlexBus connector does not strike any of the pins in the mating male connector.
Publication 1794-6.5.11 - September 2011
16 Install Your FLEX I/O Frequency Input Module
6.
Press down on the terminal base unit to lock the terminal base on the
DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place.
2 2
+ +
45321
Gently push the FlexBus connector into the side of the adapter, or proceeding terminal base to complete the backplane connection.
Publication 1794-6.5.11 - September 2011
2
+
2
+
45322
For specific wiring information, refer to the installation instructions for the module you are installing in this terminal base unit.
7.
Repeat the above steps to install the next terminal base unit.
Ensure that the cover of the FlexBus connector on the last terminal base unit is in place.
Mount on a Panel or Wall
Installation of a FLEX I/O system on a wall or panel consists of:
• laying out the drilling points on the wall or panel.
• drilling the pilot holes for the mounting screws.
• mounting the adapter mounting plate.
Install Your FLEX I/O Frequency Input Module 17
• installing the terminal base units and securing them to the wall or panel.
Use the mounting kit Cat. No. 1794-NM1 for panel or wall mounting.
1794-NM1 Mounting Kit
Millimeters
(inches)
1
35.5
(1.4)
Millimeters
(Inches)
4
2
9
7
8
6
0
1
4
2
3
7
2
+
2
+
3
45323
1
2
Description
Mounting plate for adapter
#6 Self-tapping screws
3
4
To install the mounting plate on a wall or panel:
1.
Lay out the required points on the wall or panel as shown in the drilling dimension drawing.
Drilling Dimensions for Panel or Wall Mounting
Description
Terminal base unit (not included)
Adapter module (not included)
35.5
(1.4)
58.5
(2.3)
35.5
(1.4)
58.5
(2.3)
35.5
(1.4)
21 (0.83)
45327
Publication 1794-6.5.11 - September 2011
18 Install Your FLEX I/O Frequency Input Module
2.
Drill the necessary holes for the #6 self-tapping mounting screws.
3.
Mount the mounting plate for the adapter module using two #6 self-tapping screws – 18 screws are included for mounting up to 8 modules and the adapter.
IMPORTANT
Make certain that the mounting plate is properly grounded to the panel. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
.
4.
Hold the adapter at a slight angle and engage the top of the mounting plate in the indention on the rear of the adapter module.
5.
Press the adapter down flush with the panel until the locking lever locks.
6.
Position the terminal base unit up against the adapter and push the female bus connector into the adapter.
7.
Secure to the wall with two #6 self-tapping screws.
8.
Repeat for each remaining terminal base unit.
Mount the Frequency Input Module on the Terminal Base Unit
The Frequency Input module mounts on a 1794-TB3G or 1794-TB3GS terminal base unit.
1.
Rotate keyswitch (3) on terminal base unit (4) clockwise to position 1 as required for the module.
Do not change the position of the keyswitch after wiring the terminal base unit.
Publication 1794-6.5.11 - September 2011
1
Install Your FLEX I/O Frequency Input Module 19
2
3
4
5
6
8
7
40231
Label here or under here
Description
1 FlexBus connector
2 Latching mechanism
3 Keyswitch
4 Cap plug
Description
5 Base unit
6 Alignment groove
7 Alignment bar
8 Module
2.
Make certain the FlexBus connector (1) is pushed all the way to the left to connect with the neighboring terminal base or adapter.
You cannot install the module unless the connector is fully extended.
3.
Make sure the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base unit.
ATTENTION
If you remove or insert the module while the backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
4.
Position the module (8) with its alignment bar (7) aligned with the groove (6) on the terminal base.
5.
Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism is locked into the module.
6.
Remove cap plug and attach another terminal base unit to the right of this terminal base unit if required.
Make sure the last terminal base has the cap plug in place.
Publication 1794-6.5.11 - September 2011
20 Install Your FLEX I/O Frequency Input Module
IMPORTANT
The adapter is capable of addressing eight modules. Do not exceed a maximum of eight terminal base units in your system.
Wiring Information
This section provides essential wiring information for the 1794-TB3G,
1794-TB3GK, and 1794-TB3GS terminal base units. It also includes instructions for connecting wiring to the FLEX I/O module.
Wiring the Terminal Base Units (1794-TB3G shown)
Daisy-chai n i n g
Frequency input module
Frequency input module
Analog module
Frequency input module
I n divid u al
24V DC
Wiring when total current draw is 10 A.
Digital input module
Frequency input module
Digital input module
Digital output module
24V DC
24V DC
24V DC
Combi n atio n
Wiring when total current draw is greater than 10 A.
Analog
module
Frequency input module
Frequency Input module
Frequency input module
24V DC
24V DC
Total current draw through any base must not be greater than 10 A.
Publication 1794-6.5.11 - September 2011
45556
Install Your FLEX I/O Frequency Input Module 21
ATTENTION
Take note of the following considerations when wiring your terminal base units:
•AIl modules must be frequency or analog modules for the daisychain configuration.
•Use the individual type of configuration for any "noisy" DC digital I/O modules in your system.
•All modules powered by the same power supply must be frequency or analog modules for the combination type of configuration.
Wire the Terminal Base Units
Wiring the FLEX I/O Frequency Input module is done using the 1794-TB3G,
1794-TB3GK or the 1794-TB3GS terminal base unit.
1794-TB3G, 1794-TB3GK and 1794-TB3GS Wiring Connections
1794-TB 3 GS
1794-TB 3 G o r 1794-TB 3 GK
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0
16
34
1 2 3
17
4 5 6 7
18 19 20 21 22 23
35 36 37 38
8 9 10 11 12 13 14 15
24 25 26 27 28 29 30 31 32
39 40 41 42 43 44 45 46 47 48 49 50
33
51
Label placed at top of wiring area
A 0...15
A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
B 16...33
B
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
C 34...51 C
34 and 50 = 24V DC
35 and 51 = common
16 and 33 = chassis
40…45 = chassis ground
35 and 51 = common
34 and 50 = 24V DC
16 and 33 = chassis ground
40…45 = chassis ground
45328
Connect Wiring to the FLEX I/O Frequency Input Module
Wiring to the Frequency Input module is made through the terminal base unit on which the module mounts.
The module is compatible with the 1794-TB3G, 1794-TB3GK and
1794-TB3GS terminal base units.
Publication 1794-6.5.11 - September 2011
22 Install Your FLEX I/O Frequency Input Module
Connecting Wiring Using a 1794-TB3G, 1794-TB3GK or
1794-TB3GS Terminal Base Unit
1.
Connect individual signal wiring to numbered terminals on the 0…15 row (A) and 17…32 row (B) on the terminal base unit as indicated in the table below.
2.
Connect output signal and supply wiring to the numbered terminals on
rows B and C, as shown in the figure, 1794-TB3G, 1794-TB3GK and
1794-TB3GS Wiring Connections, on page 21.
3.
Terminate shields to terminals 16 or 33 on row B, or 40…45 on row C.
4.
Connect +24V DC to terminal 34 on the 34…51 row (C), and 24V common to terminal 35 on the 34…51 row (C).
ATTENTION
To reduce susceptibility to noise, power frequency modules and digital modules from separate power supplies. Do not exceed a length of
10 m (33 ft) for DC power cabling.
5.
If daisychaining the +24V DC power to the next 1794-TB3G or
1794-TB3GS base unit, connect a jumper from terminal 50 (+24V) on this base unit to terminal 34 and from terminal 51 (24V DC common) to terminal 35 on the next 1794-TB3G or 1794-TB3GS base unit.
ATTENTION
Use extreme care when connecting wiring to an adjacent terminal base unit. Wiring for the 1794-TB3G and 1794-TB3GS terminal base units is different from other 1794 terminal base units.
ATTENTION
Do not daisychain power or ground from the 1794-TB3G or
1794-TB3GS terminal base unit to any AC or DC digital module terminal base unit.
ATTENTION
24V DC power must be applied to your module before operation. If power is not applied, the module position will appear to the adapter as an empty slot in your chassis. If the adapter does not recognize your module after installation is completed, cycle power to the adapter.
Publication 1794-6.5.11 - September 2011
Install Your FLEX I/O Frequency Input Module 23
Wiring Connections for the Frequency Input Module
Types of Inputs
Frequency
24V DC IEC1+ Proximity
(1) (2)
24V DC Contact Switch
(3)
500mV AC Magnetic Pickup
Channel 0 Terminals
(5)
Power Input RET
7
7
6
6
3
3
(7)
Channel 1 Terminals
(5)
Power Input
8
8
9
9
50mV AC Magnetic Pickup
(4)
6V AC Vortex
3V AC Vortex
Gate
24V DC IEC1+ Proximity
(1) (2)
24V DC Contact Switch
(3)
500mV AC Magnetic Pickup
50mV AC Magnetic Pickup
(4)
7
(6)
7
2
2
24
24
24
24
5
5
1
0
23
23
22
22
3
3
3
3
20
20
20
20
8
8
13
13
25
25
25
25
10
10
14
15
26
26
27
27
(1)
As defined by standard IEC 1131-2.
(2)
RET not used on 2-wire devices.
(3)
Add external resistor from 24V to F or G for wire-off detection (0.4 mA) – (
≈
50 K
Ω
).
(4)
Add a jumper between 50 mV and RET (Frequency – channel 0 = 3…4; channel 1 = 11…12)
(Gate – channel 0 = 21…20; channel 1 = 28…29).
(5)
Connect cable shields to GND terminals.
(6)
24V terminal may not be used on 2-wire magnetic devices.
(7)
All 4 RET terminals (ch 0 and 1, Freq, Gate) are internally connected together.
RET
12
12
12
12
12
12
29
29
29
29
(7)
GND
(5)
ATTENTION
Total current draw through the terminal base unit is limited to 10 A.
Separate power connections to the terminal base unit may be necessary.
Publication 1794-6.5.11 - September 2011
24 Install Your FLEX I/O Frequency Input Module
0 1 2
Co nn ectio n s fo r Te r mi n al Base 1794-TB 3 G show n
3 4 5 6 7 8 9 10 11 12 13 14 15
3V 6V 24V
Pwr
RET 50 mV
Sel
500/50 mV
Channel 0 Frequency Input
F 24V
Pwr
24V
Pwr
F 500/50 mV
50 mV
Sel
RET 24V
Pwr
6V
Channel 1 Frequency Input
3V
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
Out 0 Out 0
Ret
Chassis Gnd
RET 50 mV
Sel
500/50 mV
Channel 0 Gate Input
G 24V
Pwr
24V
Pwr
G 500/50 mV
50 mV
Sel
Channel 1 Gate Input
RET Out 1 Out 1
Ret
Chassis Gnd
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
+V COM
24V DC
Supply In
Sply 0
Gnd
Sply 0
Ret
Channel 0 Output Supply
6 Chassis Ground for Shields
+24V DC = Terminals C-34 and C-50
COM = C-35 and C-51
Chassis Ground = Terminals B-16, B-33, C-38, C-40…45, and C-47
NC = No connection
Sply 1
Gnd
Sply 1
Ret
+V COM
Channel 1 Output Supply
24V DC
Supply Out
45346
For daisychaining:
Supply in – C-34 (+) and C-35 (-)
Supply out – C-50 (+) and C-51 (-)
Output Alarm Connections
Output Alarm
Connections
Channel 0 Terminals
(1)
Supply
+
C-37
Supply
RET
C-39
Out + Out
RET
Supply
Output
(1)
Connect cable shields to GND connections.
B-17 B-18
Channel 1 Terminals
(1)
Supply
+
C-46
Supply
RET
C-48
Out + Out
RET
B-31 B-32
Resolution and Accuracy
1 Hz or 0.1 Hz (depending on frequency range bit setting), or + accuracy specification listed below, whichever is greater.
Publication 1794-6.5.11 - September 2011
Install Your FLEX I/O Frequency Input Module 25
Resolution % is defined as:
% Resolution =
100
Count frequency x minimum frequency sample time
Accuracy % is defined as:
% Accuracy = 100 1 -
Minimum frequency sample time
2
Minimum frequency sample
+ time
1 count frequency
2
4
5
10
20
50
100
200
500
1000
Resolution and Accuracy
Accuracy
Minimum
Frequency
Sample
Time (ms)
Sampling
Accuracy
Time
Base
Accuracy
0.02%
0.01%
0.008%
0.004%
0.002%
0.0002%
0.00008%
0.00004%
0.0225%
0.0225%
0.0225%
0.0225%
0.0225%
0.0008% 0.0225%
0.0004% 0.0225%
0.0225%
0.0225%
0.0225%
0.0425
0.0325
0.0305
0.0265
0.0245
0.0233
0.0229
0.0227
0.02258
0.02254
Worst
Case
Total
Accuracy
Deviation in Hz Due to
Total Accuracy
1.0…3276.7
Frequency
Range
(in Hz)
0.1…1.4
1…32767
Frequency
Range
(in Hz)
1…14
Resolution
0.01%
0.1…1.1
0.1…1.0
0.1…0.9
0.1…0.8
1…11
1…10
1…9
1…8
0.005%
0.004%
0.002%
0.001%
0.1…0.8
0.1…0.8
0.1…0.7
0.1…0.7
0.1…0.7
1…8
1…8
1…7
1…7
1…7
0.0004%
0.0002%
0.0001%
0.00004%
0.00002%
Input Map
2
3
4
0
1
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word Read
Frequency 0…32,767 or 0.0…3,276.7 Channel 0
% Full Scale 0.0…3,276.7% Channel 0 or Acceleration -32,768…32,767 Channel 0
Frequency 0…32,767 or 0.0…3,276.7 Channel 1
% Full Scale 0.0…3,276.7% Channel 1 or Acceleration -32,768…32,767 Channel 1
R R Direction
Ch 0
GS
Ch 0
F/A
Ch 0
WO
Ch 0
MPA
Ch 0
R R Direction
Ch 1
GS
Ch 1
F/A
Ch 1
WO
Ch 1
MPA
Ch 1
Publication 1794-6.5.11 - September 2011
26 Install Your FLEX I/O Frequency Input Module
Output Map
Dec
Oct
0
1
2
15
17
CF
14
16
13
15
SSM FR
Ch0
12 11 10
14 13 12
Number of pulses to terminate sampling
0…7 Ch 0
Maximum Frequency 0…32.767 or 0.0…3,276.7 - or -
Absolute Value of Acceleration - 0…32767 Channel 0
Frequency Scaling Divisor 0…255 Channel 0
09 08
11 10
MPM 0…3
Ch 0
3
4
5
Input Map
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word Read
5 Reserved Diagnostic Status
Channel 0
Reserved Diagnostic Status
Channel 1
6
Where:
Reserved
R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm
WOFG
Ch0
WOFF
Ch0
IGI
Ch0
IFI
Ch0
Minimum Frequency
Sample Time 0…15
Ch 0
Maximum Frequency 0…32,767 or 0.0…3,276.7 - or -
Absolute Value of Acceleration – 0…32,767 Channel 1
Frequency Scaling Divisor 0…255 Channel 1
07
07
R
06 05 04
06 05 04
LF FR
Ch 1
03
03
02
02
Number of pulses to terminate sampling
0…7 Ch 1
Frequency Scaling Multiplier 0…255
Channel 0
Init St
Up
Ch 0
ACT 0…3
Ch 0
F/AA
S Ch0
MPDM
0…3 Ch 0
01 00
01 00
MPM
0…3
Ch 1
WOFM
0…3 Ch0
6 WOFG
Ch1
WOFF
Ch1
IGI
Ch 1
IFI
Ch 1
Minimum Frequency
Sample Time 0…15 Ch 1
Frequency Scaling Multiplier 0…255
Channel 1
Init St
Up
Ch 1
ACT 0…3
Ch 1
F/AAS
Ch 1
MPDM
0…3 Ch 1
WOFM
0…3 Ch 1
7 Reserved
Where: CF = Communication fault
SSM = Safe state mode
FR = Frequency range
R = Reserved
MPM = Missing pulse multiplier
LF = Local Fault mode
F/AAS = Frequency/Accel alarm select
WOFF = Wire-off fault frequency
WOFG = Wire-off fault gate
WOFM = Wire-off fault mode
IGI = Invert gate input
IFI = Invert frequency input
ACT = Acceleration calculation time
MPDM = Missing pulse delay multiplier
Publication 1794-6.5.11 - September 2011
Chapter Summary
Install Your FLEX I/O Frequency Input Module 27
Examples of Wiring to a 1794-TB3G Terminal Base Unit
Sta n da r d Mag n etic Pick u p
500 mV threshold (F0)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Sta n da r d Mag n etic Pick u p
50 mV threshold (F0)
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
Impo r ta n t: When using a channel for 50 mV sensor, jumper the
50/500 mV pin to the appropriate
RET.
Magnetic
Input
Device -
+
5
3
40
10
12
41
-
+ Magnetic
Input
Device
24V DC IEC 1+ P r oximity
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
6V Vo r tex Flowmete r
Power
+
-
Input
Device
+
-
In
Sta n da r d O u tp u t (O0)
External
Power Supply #1
10-31.2V DC @ 1A
+
-
LOAD 0
+
-
6
3
42
3
7
42
14
12
13
12
45
+
-
6V Vortex
+
Flowmeter
-
17
18
16
37
39
38
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
24V DC Co n tact Switch
Add external resistor from 24V to F or G for wire-off detection.
Powe r
9
8
44
In
45347
This chapter provided you with instructions on how to install the input module in an existing programmable controller system and how to wire to a terminal base unit.
Publication 1794-6.5.11 - September 2011
28 Install Your FLEX I/O Frequency Input Module
Notes:
Publication 1794-6.5.11 - September 2011
29
Configure Your FLEX I/O Module with
RSLogix 5000 Software
Chapter
3
Overview
Add and Configure the
FLEX I/O Module
This chapter describes how to configure the 1794-IJ2 module for the
ControlLogix and CompactLogix system. The module can communicate through different networks such as ControlNet, Ethernet, Profibus, among others. In the examples below, the Ethernet adapter is used for communication between the Logix processor and the FLEX I/O bus.
ATTENTION
If using an SLC controller with ControlNet, refer to the associated I/O scanner documentation.
If using a PLC 5 controller, refer to the PLC 5 controller documentation for ControlNet configuration information.
You need to follow these series of steps to fully configure your FLEX I/O module in the RSLogix 5000 software.
1.
Add and configure the new local bridge module, such as 1756-ENBT, to your project. This user manual assumes you have already properly configured this module. Refer to the associated documentation.
2.
Add and configure the new adapter module, such as a FLEX I/O
EtherNet Adapter (1794-AENT). This user manual assumes you have already properly configured this module. Refer to the associated documentation.
3.
Add and configure your FLEX I/O module. See the steps provided below.
4.
Download the configuration to the controller.
To be able to add your FLEX I/O Frequency Input module, you should have already added and configured your Ethernet bridge and adapter.
Publication 1794-6.5.11 - September 2011
30 Configure Your FLEX I/O Module with RSLogix 5000 Software
1.
Select New Module for the I/O Configuration.
Right-click the local communication module.
Select New Module.
2.
The Select Module dialog appears.
Select the FLEX I/O module from the Specialty module type. Click OK
3.
The New Module dialog appears.
Publication 1794-6.5.11 - September 2011
Configure Your FLEX I/O Module with RSLogix 5000 Software 31
Complete the following fields and click OK.
• Name
• Description
• Comm Format
• Electronic Keying
4.
On the Connection tab, specify a value for the Requested Packet
Interval(RPI).
5.
On the Fault Action tab, specify the following:
• Fault Mode
• Communication Fault Behavior
Publication 1794-6.5.11 - September 2011
32 Configure Your FLEX I/O Module with RSLogix 5000 Software
6.
On the Configuration tab, specify the following:
• Channel
• Frequency or Acceleration
Publication 1794-6.5.11 - September 2011
If you choose Frequency, go to step 8. Go to step 9 if you choose
Acceleration.
7.
For Frequency mode, specify the following:
• Maximum Frequency
• Frequency Range
• Minimum Frequency Sample Time
8.
For Acceleration mode, specify the following:
• Maximum Frequency
• Frequency Range
• Minimum Frequency Sample Time
• Acceleration Calculation Time
9.
Click the Alarms tab and specify the following:
• Missing Pulse Multiplier
• Missing Pulse Delay Multiplier
• Pulses to Terminate Sampling
• Wire-off/Missing Pulse Fault Select Mode
10.
Click OK on the Module Properties dialog after you have configured the different parameters.
The following options are available for each parameter on the Configuration and Alarms tabs of the Module Properties dialog.
Configure Your FLEX I/O Module with RSLogix 5000 Software 33
Configuration Parameters
Module Property
Maximum Frequency
Frequency Range
Minimum Frequency Sample Time
Acceleration Calculation Time
Missing Pulse Multiplier
Pulses to Terminate Sampling
Wire-off/Missing Pulse Fault Select
Mode
Configuration Options
0 Hz (default)
1…32767
1.0…3276.7
2…100
Rolling Average
8
16
32
None
2
8
32
4
8
Minimum Frequency Sample Time
2
16
32
Disabled
Alarm Only
Alarm/Maximum Frequency
Alarm/Minimum Frequency
You should now see the 1794-IJ2 module added to your
I/O Configuration tree.
Chapter Summary
To be able to check if your configured parameters are acceptable and the configuration is successful, you need to go online.
Refer to the RSLogix 5000 Online Help for detailed descriptions of the configuration parameters.
This chapter provided instructions and required parameters for setting up your
FLEX I/O module on an EtherNet/IP network.
Publication 1794-6.5.11 - September 2011
34 Configure Your FLEX I/O Module with RSLogix 5000 Software
Notes:
Publication 1794-6.5.11 - September 2011
35
Chapter
4
Read and Write Configuration Maps for the
FLEX I/O Module
Overview
This chapter describes how to configure, read data from, and map data to your
Frequency Input module.
Topic
Configure Your Frequency Input Module
Frequency Input Module Image Table Mapping
Page
Configure Your Frequency
Input Module
The frequency module is configured using a group of data table words that are transferred to the module using a block transfer write instruction.
The software features available for configuration are:
• frequency range
• number of pulses to sample
• sampling time
• safe states
• fault modes
• alarms
Configure your module for its intended operation by means of your programming terminal and write block transfers.
During normal operation, the processor transfers from 1…8 words to the module when you program a BTW instruction to the module address.
Read Data From Your
Module
Read programming transmits status and data from the frequency input module to the processor data table in one I/O scan. The processor user program initiates the request to transfer data from the frequency input module to the processor.
Publication 1794-6.5.11 - September 2011
36 Read and Write Configuration Maps for the FLEX I/O Module
Map Data for the Module
The following read and write words and bit/word descriptions describe the information written to and read from the frequency input module. The module uses up to 6 words of input data and up to 7 words of output data.
Each word is composed of 16 bits.
Frequency Input Module Image Table Mapping
I/O Image
I n p u t size
1...6 Words
O u tp u t size
0...7 Words
R
DIR
0
Mod u le Image
Frequency Channel 0
% Full Scale or Acceleration Channel 0
Frequency Channel 1
% Full Scale or Acceleration Channel 1
GS
0
F/A
0
WO
0
MPA
0
Reserved
R R
DIR
1
GS
1
F/A
1
WO
1
MPA
1
Diagnostics
CF SSM
FR
0
NOPTS
0
MPM
0
R LF
FR
1
NOPTS
1
Minimum Freq or Absolute Value of Acceleration Channel 0
MPM
1
Frequency Scaling Divisor Channel 0 Frequency Scaling Multiplier Channel 0
WOFG
0
WOFF
0
IGI
0
IFI
0
MFST
0
IS
UP0
ACT 0
F/A
AS0
MPDM
0
Minimum Freq or Absolute Value of Acceleration Channel 1
WOFM
0
WOFG
1
Frequency Scaling Divisor Channel 1
WOFF
1
IGI
1
IFI
1
MFST
1
IS
UP1
Frequency Scaling Multiplier Channel 1
ACT 1
F/A
AS1
MPDM
1
WOFM
1
45351
Block Transfer Read Word Assignments
2
3
0
1
(Octal Bit) 17 16 15
Decimal Bit 15 14 13
14
12
13
11
12
10
11
09
Frequency 0…32,767 or 0.0…3,276.7 Channel 0
10
08
07
07
06
06
05
05
04
04
% Full Scale 0.0%…3,276.7% Channel 0 or Acceleration -32,768…+32,767 Channel 0
Frequency 0…32,767 or 0.0…3,276.7 Channel 1
% Full Scale 0.0%…3,276.7% Channel 1 or Acceleration -32,768…+32,767 Channel 1
03
03
02
02
01
01
00
00
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 37
Block Transfer Read Word Assignments
(Octal Bit) 17 16 15 14
Decimal Bit 15 14 13
4 R R
12
Direction
Ch 0
5 Reserved
Where:
13
R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm
12 11
11 10 09
GS
Ch 0
F/A
Ch 0
WO
Ch 0
10
08
MPA
Ch 0
07
07
R
06
06
R
05
05
04
04
Direction
Ch 1
03
03
GS
Ch 1
02
02
F/A
Ch 1
01
01
WO
Ch 1
Diagnostic Status
00
00
MPA
Ch 1
Word 2
Word 3
Bit 00…15
(00…17)
Bit 00…15
(00…17)
Bit/Word Definitions for Block Transfer Read Words
Word
Read
Word 0
Word 1
Bit
Bit 00…15
(00…17)
Bit 00…15
(00…17)
Definition
Calculated value of frequency (channel 0) – frequency can be reported down to 1 or 1.0 Hz, depending on the Frequency Range bit setting:
Below a 1 Hz value, 0 is reported
Below a 1.0 Hz value, 0.0 is reported.
Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier.
% of Full Scale or Acceleration (channel 0) – Value of the calculated frequency scaled by the Maximum
Frequency, or Calculated Value of Acceleration in Hz/s, depending on the state of the Frequency or
Acceleration Alarm Select bit.
Note : Percentage Full scale is calculated accurately up to a maximum of 3,276.7%. Beyond this maximum, the value of 3,276.7% will be returned, and a Calculation Failure (9) will be set in the Diagnostic Status byte.
Calculated value of Frequency (channel 1) – Frequency can be reported down to 1 or 1.0 Hz, depending on the Frequency Range bit setting; below a 1 Hz value, 0 is reported; below a 1.0 Hz value, 0.0 is reported.
Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier.
Percentage of Full Scale or Acceleration (channel 1) – Value of the calculated Frequency scaled by the
Maximum Frequency, or Calculated Value of Acceleration in Hz/s, depending on the state of the Frequency or Acceleration Alarm Select bit. Percentage full scale will be calculated accurately up to a maximum of
3,276.7%. Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in the Diagnostic Status byte.
Publication 1794-6.5.11 - September 2011
38 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for Block Transfer Read Words
Word
Word 4
Bit
Bits 00
Bit 01
Definition
Missing Pulse Alarm (channel 1) – Indicates that no Frequency input pulse has occurred within the period determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is given to the Missing Pulse Multiplier to determine when this bit is set. However, if the Missing Pulse
Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics will determine when this bit is set.
Wire Off Fault Alarm (channel 1) – when set, indicates that 24V DC Input (IEC 1+ or Switch Contact with shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the
Wire Off Fault Select = 1.
Bit 02
Bit 03
Frequency or Acceleration Alarm (channel 1) – Changes state from 0…1 if the calculated Frequency (actual or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated
Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Gate Input State (channel 1) – Indicates if there is a valid signal on the gate input. This parameter is only determined once every 0.5…2 s.
Bits 04…05 Direction (channel 1) – Indicates the current Direction of Rotation, using both the Frequency and Gate inputs. (Frequency leads Gate = Clockwise; Gate leads Frequency = CounterClockwise). Used for slow speed detection from 1…1,500Hz. No or Stopped rotation can be determined by the state of the Missing Pulse
Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse Alarm, a missing Gate
Input only generates a No Sensor Present/Detected status (3).
Bits 06…07 Not used
Bits 08 (10) Missing Pulse Alarm (channel 0) – Indicates that no frequency input pulse has occurred within the period determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is given to the Missing Pulse Multiplier to determine when this bit is set. However, if the Missing Pulse
Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics determines when this bit is set.
Bit 09 (11)
Bit 10 (12)
Wire Off Fault Alarm (channel 0) – When set, indicates that 24V DC Input (IEC 1+ or Switch Contact with shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the
Wire Off Fault Select = 1.
Frequency or Acceleration Alarm (channel 0) – Changes state from 0…1 if the calculated Frequency (actual or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated
Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Bit 11 (13)
Bits 12…13
(14…15)
Gate Input State (channel 0) – Indicates if there is a valid signal on the gate input. This parameter is only determined once every 0.5…2 s.
Direction (channel 0) – Indicates the current Direction of Rotation, using both the Frequency and Gate inputs.
Frequency leads Gate = Clockwise
Gate leads Frequency = CounterClockwise
Bits 14…15
(16…17)
Used for slow speed detection from 1…1,500Hz. No or Stopped rotation can be determined by the state of the Missing Pulse Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse
Alarm, a missing Gate Input only generates a No Sensor Present/Detected status (3).
Not used
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 39
Bit/Word Definitions for Block Transfer Read Words
Word
Word 5
Bit
Bits 00…03 Diagnostic Status – indicates the response from the module; a normal or non-normal
Bits 04…15
(04…17)
Definition operating condition.
Bit
Reserved
03
0
0
1
1
0
0
0
0
0
0
02
0
0
0
0
1
1
1
1
0
0
1010…1111
01
0
0
1
1
0
0
1
1
0
0
00
0
1
0
1
0
1
0
1
0
1
0 = Normal Operation (No Failure)
1 = Calibration Failure
2 = Configuration Failure
A Minimum Frequency Sample Time value other than 0…9 was selected.
3 = Message Failure
4 = Lead Break Detection Hardware Failure
5 = Major Hardware Failure
6 = EEPROM Failure
7 = RAM Failure
8 = ROM Failure
9 = Calculation Failure
The actual Frequency is greater than 32,767 Hz. or 3,276.7 Hz.
(overange).
The scaled Frequency is greater than 32,767 Hz. or 3,276.7 Hz.
(overange).
The % Full Scale calculation (based on Maximum Frequency) is
> 3,276.7%.
10…15 = Not Used
Block Transfer Write Word Assignments
1
2
3
(Octal Bit) 17
Dec. Bit
0
15
CF
4
05
05
FR
Ch 1
Maximum Frequency 0…32,767 or 0.0…3,276.7 or Absolute Value of Acceleration 0…32,767 – Channel 0
Frequency Scaling Divisor 0…255 Ch 0 Frequency Scaling Multiplier 0…255 Ch 0
WOFG
Ch 0
16
14
SSM FR
Ch 0
WOFF
Ch 0
15
13
IGI
Ch 0
14
12
Number Of Pulses
To Terminate
Sampling Ch 0
IFI
Ch 0
13 12 11
11 10 09
MPM
Ch 0
Minimum Frequency
Sample Time Ch 0
10
08
07
07
R
Init
St Up
Ch 0
06
06
LF
ACT Ch 0
04
04 03
Number Of Pulses To
Terminate Sampling
Ch 1
02 01 00
MPM
Ch 1
F/A AS
Ch 0
03
MPDM
Ch 0
02 01 00
Maximum Frequency 0…32,767 or 0.0…3,276.7 or Absolute Value of Acceleration 0…32,767 – Channel 1
WOFM
Ch 0
Publication 1794-6.5.11 - September 2011
40 Read and Write Configuration Maps for the FLEX I/O Module
Block Transfer Write Word Assignments
(Octal Bit) 17
Dec. Bit
5
6
15
16
14
15
13
14
12
13
11
Frequency Scaling Divisor 0…255 Ch 1
12
10
11
09
Where:
10
08
07
07
06
06
05
05
04
04
03
03
Frequency Scaling Multiplier 0…255 Ch 1
WOFG
Ch 1
WOFF
Ch 1
IGI
Ch 1
IFI
Ch 1
CF = Communication fault
SSM = Safe state mode
FR = Frequency Range
Ch = Channel
MPM = Missing Pulse Multiplier
R = Reserved
LF = Local fault mode
WOFF = Wire-off fault frequency
Minimum Frequency
Sample Time Ch 1
Init
St Up
Ch 1
ACT Ch 1 F/A AS
Ch 1
WOFG = Wire-off fault gate
IGI = Invert gate input
IFI = Invert frequency input
ACT = Acceleration Calculation Time
F/AAS = Frequency/Accel alarm select
MPDM = Missing pulse delay multiplier
WOFM = Wire-off fault mode
MPDM
Ch 1
02 01
WOFM
Ch 1
00
02 01 00
Bit/Word Definitions for the Block Transfer Write Words
Word Bit
Write Word 0 Bits 00…01
Definition
Missing pulse multiplier bits (channel 1) – used to modify the Minimum Frequency
Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Bits 02…04
Default = No multiplier; alarm generated immediately
Bit 01 00 Missing Pulse Multiplier
0 0 No Multiplier, normal mode with 2 s delay
0 1 X2
1 0 X8
1 1 X32
Number of pulses to terminate sampling (channel 1) – Lets you calculate Frequency when a specified number of input pulses have occurred. This allows earlier reporting of the frequency than the Minimum Frequency Sampling Time, when many input pulses are occurring. Accurate frequency determination is possible without waiting for the full
Minimum Frequency Sampling Time to expire.
Default = Minimum frequency sampling time
Bit 04 03 02 Number of pulses to terminate sampling
0 0 0
0 0 1
Use minimum frequency sampling time
2
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
4
8
16
32
64
128
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 41
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 0
(con’t.)
Bit
Bits 05
Definition
Frequency range bits (channel 1) – Specifies the Frequency Range of the Frequency input.
Bits 06
Bits 07
Bits 08…09
(10…11)
0 = 1…32767 (below 1 Hz reports 0);
1 = 1.0…3276.7 (below 1.0 Hz reports 0.0).
Default = 0
Local fault mode selection – determines how the Module Safe State data is used to control alarm outputs for bus communication and internal module faults.
Local Fault = Wire Off Fault or Missing Pulse Alarm.
0 = Safe states activated by bus communication only;
1 = Safe states activated by any failure (bus communication, internal module faults, and so on.)
Default = 0, safe states activated by bus communication only
Not used
Missing pulse multiplier bits (channel 0) – used to modify the Minimum Frequency
Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Bits 10…12
(12…14)
Default = No multiplier; alarm generated immediately
Bit 09
(11)
08
(10)
Minimum frequency sampling time
0 0
0 1
No Multiplier, alarm generated immediately (normal mode with 2 s delay)
X2
1 0
1 1
X8
X32
Number of pulses to terminate sampling (channel 0) – Lets you calculate Frequency when a specified number of input pulses have occurred. This allows earlier reporting of the frequency than the Minimum Frequency Sampling Time, when many input pulses are occurring. Accurate frequency determination is possible without waiting for the full
Minimum Frequency Sampling Time to expire.
Default = Minimum frequency sampling time.
Bit 12
(14)
11
(13)
10
(12)
Number of pulses to terminate sampling
0 0 0 Use minimum frequency sampling time
0 0
0 1
0 1
1 0
1
0
1
0
2
4
8
16
1 0
1 1
1 1
1
0
1
32
64
128
Publication 1794-6.5.11 - September 2011
42 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
Word Bit
Bit 13 (15)
Definition
Frequency range bits (channel 0) – Specifies the Frequency Range of the Frequency input.
Word 1
Word 2
Bit 14 (16)
Bit 15 (17)
Bits 00…15
(00…17)
Bits 00…07
Bits 08…15
(10…17)
0 = 1…32767 (below 1 Hz reports 0);
1 = 1.0…3276.7 (below 1.0 Hz reports 0.0).
Default = 0
Safe state mode bit – selection determines how module alarm outputs react to bus communication and internal module faults
Local fault = Wire Off Fault or Missing Pulse Alarm
0 = Reset outputs
1 = Hold last state
Default = 0 (reset outputs)
Communication fault – Signals that communication has been interrupted on the network. The adapter signals that the module should execute its fault routine or go to the Safe State and control any Alarm Outputs accordingly. During normal startup, this bit must be set (1) by the user program to begin normal module operation of Alarm Outputs
(in effect, an output enable). When the adapter communication link is broken, the adapter will reset this bit (0). Adapter dependent.
Default = 0
Maximum frequency or absolute value acceleration/deceleration (channel 0) – Specifies the highest Frequency or absolute Acceleration/Deceleration value allowed on the
Frequency input. 0…32,767, 0.0…3,276.7 Hz. or 0…32,767 Hz/s depending on the
Frequency Range and Frequency/Acceleration Alarm Select bits.
Frequency scaling multiplier (channel 0) – Specifies a multiplier to scale the incoming
Frequency value, 0…255.
Default = 0 – no scaling multiplication performed (x1)
Frequency scaling divisor (channel 0) – Specifies divisor to scale the incoming Frequency value, 0…255.
Default = 0 – no scaling division performed (divided by 1)
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 43
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 3
Bit
Bits 00…01
Bits 02…03
Definition
Wire-Off/Missing Pulse fault select mode (channel 0) – Sets the mode for 24V DC IEC 1+
Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or
Gate). The Maximum Frequency is determined by Frequency Range bit and the
Maximum Frequency value, and the Minimum Frequency is determined by Frequency
Range bit. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum.
Bit 01 00 Channel wire-off/missing pulse detection mode
0 0 Disabled
0
1
1
0
Alarm only (frequency unchanged)
Alarm and force frequency to maximum frequency value
(32767 or 3276.7 or maximum frequency value, 0).
Alarm and force frequency to minimum frequency value (0 or 0.0).
1 1
Missing pulse delay multiplier bits (channel 0) – Specifies the number of Missing Pulse
Alarms periods (Minimum Frequency Sampling Times) which is permitted before the alarm is raised, if enabled. Used to defeat the Missing Pulse Alarm during a system startup.
Bit 04
Bits 05…06
Default = 0 – No multiplier; alarm generated immediately (normal mode with 2 s extension delay)
Bit 03 02 Alarm periods before alarm generated
0 0
0
1
1
0
No multiplier; alarm generated immediately (normal mode with 2 s extension delay)
2 sample periods + 2 s delay before alarm
8 sample periods + 2 s delay before alarm
1 1 32 sample periods + 2 s delay before alarm
Frequency or Acceleration Alarm Select (channel 0) – Determines if the value in the
Maximum Frequency or Acceleration write word is a Frequency (actual or scaled) or
Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = Frequency alarm
1 = Acceleration alarm
Default = 0 – frequency alarm
Acceleration Calculation Time (channel 0) – Specifies the number of Frequency Sample
Times over which the module calculates acceleration.
Bit 07
Default = 0 – Rolling Average (previous 4 samples)
Bit 06 05 Acceleration Calculation Time in Frequency Sample Times
0 0 Rolling Average (previous 4 samples)
0 1
1 0
8
16
1 1 32
Initiate Startup Select (channel 0) – Alerts a channel that if process start up is in progress to defeat the missing pulse alarm for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default = 0 – Normal Run Mode
Publication 1794-6.5.11 - September 2011
44 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 3
Bit
Bit 07
Bits 08…11
(10…13)
Bit 12 (14)
Definition
Minimum Frequency Sampling Time (channel 0) – Specifies the minimum time (in ms) the module spends collecting pulses to determine the Frequency.
Bit 11
(13)
10
(12)
09
(11)
0 0 0
0 0 0
0 0 1
0 0 1
0 1 0
08
(10)
0
1
0
1
0
Minimum Frequency Sampling Time (in ms)
2
4
5
10
20
0 1 0
0 1 1
0 1 1
1 0 0
1
0
1
0
50
100
200
500
1 0 0 1 1000
1010…1111 not used – 2 ms default sample time used
Invert Select – Frequency Input (channel 0) – Selects whether to invert the Frequency input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally
Open relay or switch contact on the 24V DC Frequency Input terminal. Allows compatibility with an Active Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed relay contact on the 24V DC Frequency Input terminal.
Bit 13 (15)
Bit 14 (16)
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default = 0 – Normal (Active High, 24V = On)
Invert Select – Gate Input (channel 0) – Selects whether to invert the Gate input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally Open relay or switch contact on the 24V DC Gate Input terminal. Allows compatibility with an Active
Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed relay contact on the 24V DC
Gate Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On)
Default = 0 – Normal (Active High, 24V = On)
Wire Off Fault Select – Frequency Input (channel 0) – Selects whether to turn On or Off the 24V DC Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default: = 0 – Disable
Bit 15 (17)
Note : Customer devices must draw more than 0.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
Wire Off Fault Select – Gate Input (channel 0) – Selects whether to turn On or Off the
24V DC Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default = 0 – Disable
Note : Customer devices must draw more than.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 45
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 4
Word 5
Bit
Bits 00…15
(00…17)
Bits 00…07
Definition
Maximum frequency or absolute value acceleration/deceleration (channel 1) – Specifies the highest Frequency or absolute Acceleration/Deceleration value allowed on the
Frequency input. 0…32,767 Hz, 0.0…3,276.7 Hz. or 0…32,767 Hz/s depending on the
Frequency Range and Frequency/Acceleration Alarm Select bits.
Frequency scaling multiplier (channel 1) – Specifies a multiplier to scale the incoming
Frequency value, 0…255.
Bits 08…15
(10…17)
Default = 0 – no scaling multiplication performed (x1)
Frequency scaling divisor (channel 1) – Specifies divisor to scale the incoming Frequency value, 0…255.
Default = 0 – no scaling division performed (divided by 1)
Publication 1794-6.5.11 - September 2011
46 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 6
Bit
Bits 00…01
Bits 02…03
Definition
Wire-Off/Missing Pulse fault select (channel 1) – Sets the mode for 24V DC IEC 1+ Wire
Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate).
The Maximum Frequency is determined by Frequency Range bit and the Maximum
Frequency value, and the Minimum Frequency is determined by Frequency Range bit.
The Wire Off detect time (in mode 1, 2, and 3) is 2 seconds maximum.
Bit 01 00 Channel wire-off or missing pulse fault mode
0 0 Disabled
0 1 Alarm only (frequency unchanged)
1 0 Alarm and force frequency to maximum frequency value (32767 or
3276.7 or maximum frequency value, 0).
1 1 Alarm and force frequency to minimum frequency value (0 or 0.0).
Missing pulse delay multiplier bits (channel 1) – Specifies the number of Missing Pulse
Alarms periods (Minimum Frequency Sampling Times) which will be tolerated before the alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during a system startup.)
Bit 04
Bits 05…06
Default = 0 – No multiplier; alarm generated immediately (normal mode with 2 s extension delay)
Bit 03 02 Alarm periods before alarm generated
0 0 No multiplier; alarm generated immediately (normal mode with 2 s extension delay)
0 1 2 sample periods + 2 s delay before alarm
1 0 8 sample periods + 2 s delay before alarm
1 1 32 sample periods + 2 s delay before alarm
Frequency or Acceleration Alarm Select (channel 1) – Determines if the value in the
Maximum Frequency or Acceleration write word is a Frequency (actual or scaled) or
Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = Frequency alarm
1 = Acceleration alarm
Default = 0 – frequency alarm
Acceleration Calculation Time (channel 1) – Specifies the number of Frequency Sample
Times over which the module calculates acceleration.
Default = 0 – Rolling Average (previous 4 samples)
Bit 06 05 Acceleration Calculation Time in Frequency Sample Times
0 0 Rolling Average (previous 4 samples)
0 1 8
1 0 16
1 1 32
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 47
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 6
Bit
Bit 07
Definition
Initiate Startup Select (channel 1) – Alerts a channel that if process startup is in progress to defeat the missing pulse alarm for a time determined by the missing pulse delay multiplier.
Bits 08…11
(10…13)
Bit 12 (14)
0 = Normal run mode,
1 = Startup Mode – Defeat/delay Missing Pulse Alarm
Default = 0 – Normal run mode
Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms) the module will spend collecting pulses to determine the Frequency.
Bit 11 10 09 08 Minimum Frequency Sampling Time (in ms)
0 0 0 0 2
0 0
0 0
0
1
1
0
4
5
0 0
0 1
0 1
0 1
0
1
1
0
1
0
1
0
10
20
50
100
0 1
1 0
1
0
1
0
200
500
1 0 0 1 1000
1010…1111 not used – 2 ms default sample time used
Invert Select – Frequency Input (channel 1) – Selects whether to invert the Frequency input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally
Open relay or switch contact on the 24V DC Frequency Input terminal. Allows compatibility with an Active Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed relay contact on the 24V DC Frequency Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default = 0 – Normal (Active High, 24V = On)
Publication 1794-6.5.11 - September 2011
48 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
Word
Word 6
Bit
Bit 13 (15)
Definition
Invert Select – Gate Input (channel 1) – Selects whether to invert the Gate input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or “Normally Open” relay or switch contact on the 24V DC Gate Input terminal. Allows compatibility with an Active
Low (0V = On) 24 V DC IEC 1+ sensor or “Normally Closed” relay contact on the 24V DC
Gate Input terminal.
Bit 14 (16)
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On)
Default = 0 – Normal (Active High, 24V = On)
Wire Off Fault Select – Frequency Input (channel 1) – Selects whether to turn On or Off the 24V DC Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default: = 0 – Disable
Bit 15 (17)
Note : Customer devices must draw more than 0.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
Wire Off Fault Select – Gate Input (channel 1) – Selects whether to power On or Off the
24V DC Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default = 0 – Disable
Note : Customer devices must draw more than 4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
Input Map
3
4
1
2
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word Read
0 Frequency 0…32,767 or 0.0…3,276.7 Channel 0
5
6
Where:
% Full Scale 0.0…3,276.7% Channel 0 or Acceleration -32,768…32,767 Channel 0
Frequency 0…32,767 or 0.0…3,276.7 Channel 1
% Full Scale 0.0…3,276.7% Channel 1 or Acceleration -32,768…32,767 Channel 1
R R Direction
Ch 0
GS
Ch 0
F/A
Ch 0
WO
Ch 0
MPA
Ch 0
R R Direction
Ch 1
Reserved
Reserved
Diagnostic Status
Channel 0
R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm
Reserved
GS
Ch 1
F/A
Ch 1
WO
Ch 1
Diagnostic Status
Channel 1
MPA
Ch 1
Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 49
4
5
Output Map
Dec
Oct
0
1
2
15
17
CF
14
16
13
15
SSM FR
Ch0
12 11 10
14 13 12
Number of pulses to terminate sampling
0…7 Ch 0
Maximum Frequency 0…32.767 or 0.0…3,276.7 - or -
Absolute Value of Acceleration - 0…32767 Channel 0
Frequency Scaling Divisor 0…255 Channel 0
09 08
11 10
MPM 0…3
Ch 0
3 WOFG
Ch0
WOFF
Ch0
IGI
Ch0
IFI
Ch0
Minimum Frequency
Sample Time 0…15
Ch 0
Maximum Frequency 0…32,767 or 0.0…3,276.7 - or -
Absolute Value of Acceleration – 0…32,767 Channel 1
Frequency Scaling Divisor 0…255 Channel 1
6 WOFG
Ch1
WOFF
Ch1
IGI
Ch 1
IFI
Ch 1
Minimum Frequency
Sample Time 0…15 Ch 1
7 Reserved
Where: CF = Communication fault
SSM = Safe state mode
FR = Frequency range
R = Reserved
MPM = Missing pulse multiplier
LF = Local Fault mode
F/AAS = Frequency/Accel alarm select
07
07
R
06 05
IGI = Invert gate input
04
06 05 04
LF FR
Ch 1
WOFF = Wire-off fault frequency
WOFG = Wire-off fault gate
WOFM = Wire-off fault mode
IFI = Invert frequency input
03
03
Number of pulses to terminate sampling
0…7 Ch 1
Frequency Scaling Multiplier 0…255
Channel 0
Init St
Up
Ch 0
ACT 0…3
Ch 0
F/AA
S Ch0
MPDM
0…3 Ch 0
WOFM
0…3 Ch0
Frequency Scaling Multiplier 0…255
Channel 1
Init St
Up
Ch 1
ACT 0…3
Ch 1
F/AAS
Ch 1
MPDM
ACT = Acceleration calculation time
02
02
0…3 Ch 1
MPDM = Missing pulse delay multiplier
01
01 00
MPM
0…3
Ch 1
WOFM
00
0…3 Ch 1
Chapter Summary
This chapter provided the user with data and instructions to configure and map FLEX I/O Frequency Input module data.
Publication 1794-6.5.11 - September 2011
50 Read and Write Configuration Maps for the FLEX I/O Module
Notes:
Publication 1794-6.5.11 - September 2011
Overview
35
Status Indicators
Chapter
5
Troubleshoot the Module
This chapter provides a description of the different status indicators for the frequency input module to help you troubleshoot.
Topic
Diagnostic Bits in Word 5 of the BTR File
Page
The module has indicators for the following:
• Frequency and Gate Inputs
• Frequency and Gate Wire-Off Faults
• Alarm Outputs
FREQUENCY INPUT 2 CHANNEL
1794-IJ2
1
0
FREQ
F 0
GATE
F 1
FREQ
F 1
GATE
F
OUT
0
OUT
1
OK
45348
A B C D E
A = Input indicator
B = Insertable label for writing individual I/O assignments
C = Wire-off fault indicator
D = Output indicator
E = Power/status indicator – indicates power applied to module and status of module
When an input indicator (yellow) is lighted, it indicates that a valid signal
(active high or active low) is present at one of the input terminals.
When wire-off detection is enabled, and a wire-off fault is detected (24V DC
IEC 1+ input terminal only), a fault indicator (red) flashes at a rate of 1 Hz to signal a fault condition. A wire-off fault signal is also sent to the backplane. A flashing red fault indication means a valid wire-off condition for a 24V DC
IEC 1+ Input or a 24V DC contact switch input with a shunt resistor.
Publication 1794-6.5.11 - September 2011
36 Troubleshoot the Module
Diagnostics
When an output indicator is yellow, the logic is driving an output alarm On.
After detecting a fault, the internal circuitry sets the output data to the appropriate safe state, as defined by the module data table. Safe state control may be adapter-dependent.
The input and output indicators are on the field side of the isolation path, and display the logic state of the actual microcontroller input and output.
The status indicator initially powers up as solid green, indicating the power supply is operating and internal diagnostic tests are being performed. After a successful power up test, the indicator remains green. The indicator turns red in about 1.5 s if there is an internal diagnostics error.
The module is operating correctly when the green OK indicator is on.
A red OK indicator shows that the module is in a Faulted condition, indicating an internal error.
Indicator
Input (0, 1)
Condition
Off (Dark)
(Freq. or Gate) On (Yellow)
Fault (F)
Output Alarm
(0, 1)
Status (OK)
Off (Dark)
(Freq. or Gate) On (Red
Flashing)
Off (Dark)
On (Yellow)
Off (Dark)
Solid Green
Solid Red
Operating Description
Input Turned Off, Input Not Used, or
Wire Disconnected
Input Turned On
(Active High or Active Low if Inverted)
Wire connected, normal operation or detection disabled
Wire disconnected, fault condition
(for IEC1 + Proximity switch or switch contacts with shunt resistor)
Output alarm turned off
Output alarm turned on (Logic Drive On)
24V Power Turned Off, or 5V Logic Power Problem
Module OK, Normal Operating Mode
Module Fault, Outputs Disabled
The frequency input module returns diagnostics to the PLC processor in Word
5 of the BTR file. These diagnostics give you information on the status or condition of the module.
Publication 1794-6.5.11 - September 2011
Troubleshoot the Module 37
Diagnostic Bits in Word 5 of the BTR File
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 word 5
See table, Diagnostic Bits in Word 5, for diagnostics
45375
Diagnostic Bits in Word 5
Word 5 Bits 00…03 Diagnostic Status – indicates the response from the module; a normal or non-normal operating condition.
Bit 03 02 01 00 Decimal equivalent and condition
0 0 0 0 0 = Normal operation (no failure)
0
0
0
0
0
1
1
0
1 = Calibration failure
2 = Configuration failure – a Minimum Frequency
Sample Time value other than 0…9 was selected
3 = Message failure
1
1
0
0
0
0
0
0
1
1
1
1
0
0
1
0
0
1
1
0
0
1
0
1
0
1
0
1
4 = Lead break detection hardware failure
5 = Major hardware failure
6 = EEPROM failure
7 = RAM failure
1010…1111
8 = ROM failure
9 = Calculation failure
The actual frequency is greater than 32,767 Hz or
3,276.7 Hz (overrange).
The scaled Frequency is greater than 32,767 Hz or
3,276.7 Hz (overrange).
The % Full Scale calculation (based on Maximum
Frequency) is > 3,276.7%.
10…15 = Not used
Chapter Summary
This chapter explained how to interpret the status indicators of the frequency input module and the internal diagnostics that indicates the condition of the module.
Publication 1794-6.5.11 - September 2011
38 Troubleshoot the Module
Notes:
Publication 1794-6.5.11 - September 2011
55
Appendix
A
Specifications
What This Appendix
Contains
This appendix contains the frequency accuracy and general specifications of the Frequency Input module (1794-IJ2, 1794-IJ2K, and 1794-IJ2XT).
Input Specifications
Attribute Value
Number of input channels 2
Number of inputs per channel
2 – Frequency and Gate
(gate used to establish direction)
Input frequency, max
Frequency value, max
Input pulse width
32 kHz
32,767 Hz or 3,276.7 Hz (dependent on range)
20
μ s
See table,
Resolution and Accuracy , on page 24
Resolution and accuracy
On-state voltage, min
On-state voltage, nom
(selected by terminal base connections)
10V (24V IEC+1 proximity, encoder input or switch inputs)
50 mV AC, 28V AC peak – Extended magnetic pickup
500 mV AC, 28V AC peak – Magnetic pickup
< 3V – Vortex flowmeter low range
> 6V – Vortex flowmeter high range
24V DC IEC+1 proximity or encoder input
24V DC Contact switch input
Limited to isolated 24V DC power supply On-state voltage, max
On-state current
Off-state current min nom max
2.0 mA
9.0 mA
10.0 mA
<1.5mA into 24V DC IEC+ terminal
Off-state voltage, max 5.0V DC on 24V DC IEC+1 terminal
Wire-off detection
Gate input impedance
0.4 mA for proximity, encoder or contact switch with
50 k
Ω
shunt resistor
Frequency input impedance >5 K
Ω
for 50 mV Extended magnetic pickup
>5 K
Ω
for 500 mV Magnetic pickup
>10 K
Ω
for 3V Vortex flowmeter low range
>10 K
Ω
for 6V Vortex flowmeter high range
>2.5 K
Ω
for 24V DC IEC+1 proximity or encoder input
>2.5 K
Ω
for 24V DC Contact switch input
>5 K
Ω
for 50 mV Extended magnetic pickup
>5 K
Ω
for 500 mV Magnetic pickup
>2.5 K
Ω
for 24V DC IEC+1 proximity or encoder input
>2.5 K
Ω
for 24V DC Contact switch input
Publication 1794-6.5.11 - September 2011
56 Specifications
Publication 1794-6.5.11 - September 2011
Output Specifications
(1)
Attribute
Number of outputs
Output voltage source
Output voltage min nom max
On-state current, min
On-state current, max
Surge current
Off-state leakage, max
On-state voltage drop
Output control
Output switching time
Value
2 – isolated
Customer supplied
10V DC
24V DC
31.2V DC
1 mA per output
1.0 A per channel sourced out of module
Current Limited – All outputs can be On simultaneously without derating
2 A for 50 ms, repeatable every 2 s
Less than 300
μ
A @ 31.2V DC
0.9V DC @ 1 A
Outputs individually assignable to:
Frequency, % Full scale or acceleration alarm
Triggered by frequency alarm or acceleration alarm
Turn on: Less than 0.5 ms
Turn off: Less than 1 ms
(1)
Meets IEC 1A 24V DC output specifications.
General Specifications
Attribute
Module location
External DC power
Voltage range
Supply voltage, nom
Supply current
Isolated DC power
Voltage range
Supply voltage, nom
Supply current, max
Peak AC ripple, max
Dimensions (with module installed in base) HxWxD
Isolation voltage
Processing time
FlexBus current
Value
Cat. No. 1794-TB3G and 1794-TB3GS terminal base units
(Input for +5V logic and 24V DC/DC converters)
19.2…31.2V DC (includes 5% AC ripple)
24V DC
220 mA @ 19.2V DC
180 mA @ 24V DC
140 mA @ 31.2V DC
(Output to sensors and encoders)
21.6…26.4V DC
24V DC
0…60 mA @ 24V DC
(4 devices @ 15 mA = 60 mA)
100 mV
94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)
50V (continuous), Basic Insulation Type
Type tested @ 1365V AC for 60 s, between field side and system and individual channels
<4 ms
30 mA @ 5V DC
Specifications 57
General Specifications
Attribute
Power dissipation, max
Thermal dissipation, max
Indicators (field side driven, logic side indication)
Keyswitch position
Wire size
Wiring category
(1)
Wire type
Terminal screw torque
Enclosure type rating
North American temp code
IEC temp code
Value
4.6W @ 31.2V DC
15.6 BTU/hr @ 31.2V DC
1 green/red power/status indicator
4 yellow status indicators (Freq 0, 1, Gate 0, 1)
4 red wire-off indicators (Freq 0, 1, Gate 0, 1)
2 yellow status indicators (Out 0, Out 1) – logic side
1
Determined by installed terminal base
2 – on signal ports
3 – on power ports
Shielded on signal ports
Determined by installed terminal base
None (open-style)
T4A
T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F) – 1794-IJ2 and 1794-IJ2K
-20…70 °C (-4…158 °F) – 1794-IJ2XT
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating
Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
Vibration
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
Shock, non-operating
Emissions
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
CISPR 11:
Group 1, Class A (with appropriate enclosure)
Publication 1794-6.5.11 - September 2011
58 Specifications
Environmental Specifications
Attribute
ESD immunity
Value
IEC 61000-4-2:
4 kV contact discharges – 1794-IJ2 and 1794-IJ2K
6 kV contact discharges – 1794-IJ2XT
8 kV air discharges
EFT/B immunity
Surge transient immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on shielded signal ports
IEC 61000-4-5:
±2 kV line-earth(CM) on shielded signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz on shielded signal ports
Certifications
Certifications when product is marked
(1) c-UL-us
Value
UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
CSA
(1794-IJ2, 1794-IJ2K)
CE
C-Tick
Ex
TÜV
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2
Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
(II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
TÜV Certified for Functional Safety: up to and including SIL 2
(1)
See the Product Certification link at http://www.ab.com
for Declaration of Conformity, Certificates, and other certification details.
Publication 1794-6.5.11 - September 2011
59
Overview
Appendix
B
Electronic Data Sheet (EDS) Files
EDS provides the definition for a device's configurable parameters and public interfaces to those parameters:
• Every type of configurable device has its own unique EDS.
• EDS is a simple text file that allows product-specific information to be made available to third-party vendors.
This makes updating of configuration tools easier without having to constantly revise the configuration software tool.
Beginning with the following revisions, EDS files are required for RSNetworx for Devicenet and ControlNet, RSLinx, RSLogix5, and RSLogix 5000 to recognize a device:
RSNetworx
RSLinx
RSLogix 5
RSLogix 5000
Version 2.21
Version 1.10.176
Version 4.0
Version 5.12
Updating EDS File
Most EDS files are installed with RSLinx, RSNetworx, and other RSI software as long as you enable the option during installation.
There are instances where you will need to acquire and register EDS files on your own even after all software is installed.
• If you go online with RSNetworx and it shows a device with a "?" mark icon, a globe, or a message that says the device is unrecognized, this means the EDS file for that device does not exist on your PC.
• If RSLinx can see a processor but going online, uploading or downloading is not possible.
With ControlLogix modules the backplane does not show after expanding the tree or ControlLogix modules in the backplane show up as a yellow question mark without a red X sign.
An EDS file is also required if a bridge module such as a 1756-CNB or DNB does not show the "+" sign to expand the tree to show its network.
Publication 1794-6.5.11 - September 2011
60 Electronic Data Sheet (EDS) Files
To acquire EDS files for Rockwell Automation and Allen-Bradley devices, go to Tools & Resources EDS Files at www.ab.com/networks/eds . It allows you to search for devices by the type of network and their catalog number.
ATTENTION
•Make sure to match the major firmware revision of the device as each major firmware revision is associated with a specific
EDS file.
•Download the EDS file and place it in any folder, except the
/Program Files/Rockwell Software/RSCommon/EDS folder where your Rockwell Automation software is installed.
•Register EDS files with RSNetworx by selecting Tools EDS
Wizard.
•Select Register an EDS File, then click the Browse button on the Next page to find your file.
EDS Installation
You can register EDS files with the EDS Hardware Installation tool.
1.
In Windows, go to Rockwell Software → RSLinx Tools → EDS
Hardware Installation Tool.
2.
Click Add to register an EDS file.
When an EDS file is registered, a copy of the file is made and placed in the /RSCommon/EDS folder where your Rockwell Automation software is installed and your Windows registry is updated. Once the registration is complete you can move, copy, or delete the original files.
Publication 1794-6.5.11 - September 2011
61
Appendix
C
Schematics
What This Appendix
Contains
Use this appendix to understand the internal logic of the FLEX I/O
Frequency Input module.
Follow the wiring practices described in Industrial Automation Wiring and
Grounding Guidelines for Noise Immunity, publication 1770-4.1
, when wiring your I/O devices. This includes:
• routing conductors
• grounding practices
• use of shielded cables
• input circuits
The frequency input module input logic consists of:
• frequency input circuits
• gate input circuits
• Frequency Inputs
The frequency input circuit uses a comparator to determine when the input voltage threshold is exceeded. When exceeded, it provides logic pulses internal to the 1794 Frequency Input module. The circuit is designed to interface with both active or passive sensor inputs by accepting any pulse output device (such as vortex flowmeter, magnetic pickup or digital pickup).
Gate Inputs
Gate inputs are similar to frequency inputs and are used for determining direction. There is one gate associated with each frequency input circuit (G0 corresponds to F0). The circuit is designed to interface with both active or passive sensor inputs by accepting any pulse output device (such as magnetic pickup or digital pickup).
Publication 1794-6.5.11 - September 2011
62 Schematics
Isolated 24V power (F and G,
15 mA each)
24V
IEC 1+ or
24V DC
Switch input
50/500 mV
Input
2.5 KW
5.11 KW
2.15 KW
6V Vortex input
Frequency only, not on gate
8.25 KW 100 KW
100 pF
3V Vortex input
8.25 KW 46.4 KW
100 pF
2.15 KW
100pF
Internal 500 mV
Ref. Voltage
50 mV Select jumper
825 W
Return
215 W
Lead breakage
Reference voltage
-
+
10 KW
100 pF
Frequency lead break
(Gate lead break)
47 pF
(Gate) input
-
+
Invert frequency
Ex
Nor
10 KW
100 pF
Frequency input
(Gate input)
45354
Output Circuits
The Frequency Input module output logic consists of digital outputs.
Digital Outputs
The module output is comprised of an isolated power MOSFET. This device operates in current sourcing mode, and is capable of delivering up to
1 A @ 10…31.2V DC.
Publication 1794-6.5.11 - September 2011
Schematics 63
.
Output channel
3.83 KW
10 KW
3.83 KW
Supply
D5
6.8V
Q1 s
D6
Output
TEMPFET
Output 0
RT1
Alarm
10-31.2V
DC
R load
1A max
Supply return
Customer supplied power, ranging from 10V…31.2V DC, is connected internally to the power output transistor.
When an output is turned on, current flows into the source, out of the drain, through the load connected to the ground of the customer supply (customer return). Diode D6 protects the power output transistors from damage due to inductive loads.
45355
Output Q1 is a thermally protected FET and will turn off @ 3A, approximately. After an output goes into thermal shutdown, you must fix the cause of the shutdown and toggle the outputs ON and OFF to reenergize the output.
RT1 protects D6 and Q1 if power supply polarity is reversed.
24V DC from terminal base
DC to DC Converters – 24V DC Power Supplies
The module provides two 24V (±10%) power sources rated at 15 mA each.
Each power source can power one Bently Nevada 3300 – 5 mm (0.197 in.) or
8 mm (0.315 in.) – Proximity Transducer.
DC/DC converter
Channel 0 current limit
Channel 1 current limit
Frequency 0 15 mA
Gate 0 15 mA
30 mA max
To customer devices
Frequency 1 15 mA
Gate 1 15 mA
30 mA max
45356
The frequency input module isolated power supply consists of 1 isolated 24V DC power supply that provides 2 current limited outputs of 30 mA max (1 for each channel).
Publication 1794-6.5.11 - September 2011
64 Schematics
Notes:
Publication 1794-6.5.11 - September 2011
65
Appendix
D
Program Your Module with PLC Processors
Overview
Enter Block Transfer
Instructions
This Appendix serves as a reference to users of the PLC-* Family Processors to program their modules.
To initiate communication between the frequency input module and your PLC processor, you must enter block transfer instructions into your ladder logic program. Use this chapter to enter the necessary block transfer instructions into your ladder logic program.
The frequency input module communicates with the PLC processor through bidirectional block transfers. This is the sequential operation of both read and write block transfer instructions.
Before you configure the module, you need to enter block transfer instructions into your ladder logic. The following example programs illustrate the minimum programming required for communication to take place between the module and a PLC processor. These programs can be modified to suit your application requirements.
A configuration block transfer write (BTW) is initiated when the frequency module is first powered up, and subsequently only when the programmer wants to enable or disable features of the module. The configuration BTW sets the bits which enable the programmable features of the module, such as scalars and alarm values, and so on. Block transfer reads are performed to retrieve information from the module.
Block transfer read (BTR) programming moves status and data from the module to the processor data table. The processor user program initiates the request to transfer data from the module to the processor. The transferred words contain module status, channel status and input data from the module.
Your program should monitor status bits, block transfer read and block transfer write activity.
Publication 1794-6.5.11 - September 2011
66 Program Your Module with PLC Processors
PLC-2 Family Processor
The 1794 Frequency I/O module is not recommended for use with PLC-2 family programmable controllers due to the number of digits needed for high resolution.
IMPORTANT
The frequency input module functions with reduced performance in PLC-2 systems. Because the module does not support BCD and the PLC-2 processor is limited to values of
4095 (12 bit binary), many values returned in the BTR file may not provide meaningful data to the PLC-2 processor.
PLC-3 Family Processor
Block transfer instructions with the PLC-3 processor use a control file and a data file. The block transfer control file contains the data table section for module location, the address of the block transfer data file and other related data. The block transfer data file stores data that you want transferred to the module (when programming a BTW) or from the module (when programming a BTR).
The programming terminal prompts you to create a control file when a block transfer instruction is being programmed. The same block transfer control file is used for both the read and write instructions for your module. A different block transfer control file is required for every module.
Publication 1794-6.5.11 - September 2011
Program Your Module with PLC Processors 67
PLC-3 Processor
Program Example
Rung M:0
The IJ2 module is located in rack 3, I/O group 2, slot 0. The control file is a 10 word file starting at B17:0 that is shared by the BTR/BTW. The data obtained by the PLC3 processor is placed in memory starting at location N18:101, and with the default length of 0, is 7 words long.
IJ2 BTR
Done Bit
B17:0
15
IJ2 BTR/BTW
Control Block
BTR
BLOCK TRANSFER READ
Rack 3
Group
Slot
Control
2
0
B17:0
Data File
Length
N18:101
0
EN
DN
ER
IJ2 BTR
Error Bit
B17:0
13
IJ2 BTR
Error Bit
B17:0
U
13
The IJ2 module is located in rack 3, I/O group 2, slot 0. The control file is a 10 word file starting at B17:0 that is shared by the BTR/BTW. The data sent by the PLC-3 processor to the
IJ2 module is from PLC memory starting at N18:1, and with the default length of 0, is 8 words long.
IJ2 BTW
Done Bit
B17:0
5
IJ2 BTR/BTW
Control Block
BTW
BLOCK TRANSFER WRITE
Rack
Group
Slot
3
2
0
Control
Data
Length
B17:0
N18:1
0
EN
DN
ER
IJ2 BTW
Error Bit
B17:0
3
IJ2 BTW
Error Bit
B17:0
U
3
45563
PLC-5 Family Processor
Block transfer instructions with the PLC-5 processor use a control file and a data file. The block transfer control file contains the data table section for module location, the address of the block transfer data file and other related data. The block transfer data file stores data that you want transferred to the module (when programming a BTW) or from the module (when programming a BTR).
The programming terminal prompts you to create a control file when a block transfer instruction is being programmed. A different block transfer control file is used for the read and write instructions for your module.
Publication 1794-6.5.11 - September 2011
68 Program Your Module with PLC Processors
PLC-5 Processor
Program Example
Rung 2:0
The IJ2 module is located in rack 1, I/O group 2, slot 0. The integer control file starts at N22:200, is 5 words long and is compatible with all PLC-5 family members.
The data obtained by the PLC-5 processor from the IJ2 module is placed in memory starting at N22:101, and with the default length of 0, is 7 words long. The length
1 can be any number between 0 and 7. In enhanced PLC-5 processors, the block transfer data type may be used as a control file.
IJ2 BTR
Enable Bit
N22:200
15
IJ2 BTW
Enable Bit
N22:205
15
IJ2 BTR
Control File
BTR
BLOCK TRANSFER READ
Rack
Group
Slot
Control
Data File
Length
01
2
0
N22:200
N22:101
0
Continuous N
EN
DN
ER
Rung 2:1
The IJ2 module is located in rack 1, group 2, slot 0. The integer control file starts at N22:205, is a 5 words long and is compatible will all PLC-5 family members. The data sent by the PLC-5 processor to the IJ2 module starts at N22:1, and with the default length of 0, is 8 words long. Valid BTW lengths can be any may be used as a control file.
IJ2 BTR
Enable Bit
N22:200
IJ2 BTW
Enable Bit
N22:205
15 15
IJ2 BTW
Control File
BTW
BLOCK TRANSFER WRITE
Rack
Group
01
2
Slot
Control
Data File
Length
Continuous
0
N22:205
N22:1
0
N
EN
DN
ER
1 Enhanced PLC-5 processors include: PLC-5/11, -5/20, -5/3x, -5/4x, and -5/6x.
45564
PLC-5/250 Family Processor
Block transfer instructions with the PLC-5/250 processor use a control file and a data file. The block transfer control file contains the data table section for module location, the address of the block transfer data file and other related data. The block transfer data file stores data that you want transferred to the module (when programming a BTW) or from the module (when programming a BTR).
The programming terminal automatically selects the control file based on rack, group and module, and whether it is a read or write. A different block transfer control file is used for the read and write instructions for your module. A different block transfer control file is required for every module.
Publication 1794-6.5.11 - September 2011
Program Your Module with PLC Processors 69
PLC-5/250 P r ocesso r
Program Example
R un g 1STEPO:1
The IJ2 module is located in rack 14, I/O group 1, slot 0. The data obtained by the PLC-5/250 processor from the
IJ2 module is placed in the data table starting at 2BTD5 : 101, and with the default length of 0, is 7 words long. The length can be any number between 0 and 7.
IJ2 BTR
Enable Bit
BR141 : 0
EN
IJ2 BT W
Enable Bit
B W 141 : 0
EN
IJ2 BTR
Control File
BTR
BLOCK TRAN S FER READ
Rack
Group
S lot
Control Block
Data File
BT Length
Continuous
BT Timeout
14
1
0
BR141 : 0
2BTD5 : 101
0
NO
4
EN
DN
ER
R un g 1STEPO:1
The IJ2 module is located in rack 14, I/O group 1, slot 0. The data sent to the IJ2 module from the PLC-5/250 processor is from the data table starting at 2BTD5 : 1, and with a default length of 0, is 8 words long.
V alid BT W lengths can be any number between 0 and 8.
IJ2 BTR
Enable Bit
BR141 : 0
EN
IJ2 BT W
Enable Bit
B W 141 : 0
EN
IJ2 BT W
Control File
BT W
BLOCK TRAN S FER W RITE
Rack
Group
S lot
Control Block
Data File
BT Length
Continuous
BT Timeout
14
B W 141 : 0
2BTD5 : 1
1
0
0
NO
4
EN
DN
ER
45565
Publication 1794-6.5.11 - September 2011
70 Program Your Module with PLC Processors
Notes:
Publication 1794-6.5.11 - September 2011
Numerics
1794-ACN15
1794-ACNR15K
1794-ADN
1794-APB
1794-APBDPV1
1794-ASB
1794-IJ2
1794-IJ2K
1794-TB3GK
1794-TB3GS
A
acceleration
1, 3, 5, 15, 16, 17, 18, 22, 52
alarm
missing pulse 9, 26, 38, 46, 47
pulses to terminate sampling 33
Index
B
backplane
bandwidth
bits words
frequency alarm 46 frequency range 42, 46
pulses
block transfer read (BTR)
octal bits 36 word assignments 36
block transfer write (BTW)
bit definition 40 communication fault 40
invert frequency 40 invert gate 40 local fault 40
wire-off 40 missing pulse multiplier 40 safe state mode 40
C
cabling
Publication 1794-6.5.12 - September 2011
72 Index calibration
communication
configuration
alarms 35 block transfer write 35
connector
contact switch
controller
current draw
D
data table
device
diagnostic
calibration 39, 53 configuration 39
Publication 1794-6.5.12 - September 2011 dimensions
DIN rail
direction detection
E
EEPROM
F
failure
calculation 53 calibration 53 configuration 53
fault
female connector
FLEX I/O
components 1
frequency input 13, 21 module 13 system 1, 2, 13
FlexBus
frequency
minimum sample time (ms) 8, 25, 44
minimum sample time 32, 33, 41, 47
G
gate input
H
hardware
hazardous location
I
I/O module
IEC 1131-2
indicator
output 51 power 51 wire-off fault 51
input
Index 73
installation
instructions 13 module position 13
J
K
L
local fault mode
location
Logix system 5
M
manuals
common techniques xii conventions xii
message
missing pulse
module
Publication 1794-6.5.12 - September 2011
74 Index
O
operation
output map
missing pulse multiplier 26, 49 safe state mode 26, 49
wire-off fault frequency 26, 49 wire-off fault gate 26, 49
outputs
capabilities
P
panel
PLC
processor 63, 69
PLC-2 64, 70
PLC-3 64, 70
PLC-5/250 66, 72 power
Publication 1794-6.5.12 - September 2011
programming
PLC-2 64, 70
PLC-3 64, 70
PLC-5/250 66, 72 proximity probe
publication
pulse
missing 10, 38, 40, 41, 43, 46, 47
R
RAM
read words
Requested Packet Interval (RPI) 31
resistor
ROM
rotation
clockwise 11 counterclockwise 11
S
safe state
sampling time
sensors
specification
status
T
tags
terminal base
installation 14 mount 14 replace 14 wiring 14, 21 wiring methods 14
troubleshoot
turbine metering
V
W
wire off
wiring
1794-TB3G, 1794-TB3GS, 1794-TB3GK 21 frequency module 21
illustration 14, 20 methods 14
write word
Z
zero frequency
Index 75
Publication 1794-6.5.12 - September 2011
76 Index
Notes:
Publication 1794-6.5.12 - September 2011
Rockwell Automation Support
Roc kw ell Automation provides technical information on the Web to assist you in using its products .
At http:// www.
roc kw ellautomation .
com/support/ , you can find technical manuals, a k no w ledge base of FAQs, technical and application notes, sample code and lin k s to soft w are service pac k s, and a MySupport feature that you can customize to ma k e the best use of these tools .
For an additional level of technical phone support for installation, configuration, and troubleshooting, w e offer TechConnect support programs .
For more information, contact your local distributor or Roc kw ell Automation representative, or visit http:// www.
roc kw ellautomation .
com/support/ .
Installation Assistance
If you experience a problem w ithin the first 24 hours of installation, revie w the information that is contained in this manual .
You can contact Customer Support for initial help in getting your product up and running .
United States or Canada
Outside United States or
Canada
1.440.646.3434
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
, or contact your local Rockwell Automation representative.
New Product Satisfaction Return
Roc kw ell Automation tests all of its products to ensure that they are fully operational w hen shipped from the manufacturing facility .
Ho w ever, if your product is not functioning and needs to be returned, follo w these procedures .
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments w ill help us serve your documentation needs better .
If you have any suggestions on ho w to improve this document, complete this form, publication RA-DU002 , available at http:// www.
roc kw ellautomation .
com/literature/ .
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 1794-6.5.11 - September 2011 77
Supersedes publication 1794-6.5.11 - November 1997 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.
Advertisement