Eclipse 5602-91 Instruction Manual
Eclipse 5602-91 UV Scanner: Safeguard your combustion processes with continuous flame monitoring. Ideal for gas or oil flames, this scanner features a self-check mechanism that verifies flame presence every 10 seconds. Its high-quality fused silica quartz lens and durable construction ensure reliable operation. Suitable for use with Veri-Flames, Multi-Flame, Bi-Flame, and Peek-A-Flame controllers.
Advertisement
Advertisement
856 Instruction Manual
10/18/2010
Eclipse Self-Check
UV Scanner
Model 5602-91
Version 1
Introduction
The self-check UV Scanner is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly every ten seconds, at which time the scanner’s internal circuit checks for a flame signal. If a signal is present, indicating a failed sensor, the output signal to the flame safeguard is stopped and the system shuts down.
The scanner features a high quality fused silica quartz lens, machined alloy housing with seals and a long life push-pull electromagnetically driven photo shutter. This scanner operates with the series 5600 and VF56 series
Veri-Flames, the series 6000 Multi-Flame, Series 6500 Bi-
Flame controllers, and series 7000 Peek-A-Flame.
Factory Mutual (FM) recommends these scanners be used when any fired equipment is operated continuously
(more than 24 hours without shutdown).
Mechanical Specifications
Parameter
Overall Length
Specification
7-3/4" (197mm)
Diameter 3-1/4" (83mm)
Housing Material Aluminum
Finish Clear anodized
Sight Tube Entrance 1" NPT
Purge Air Entrance 1/4" NPT
Purge Air Flow 5 cfm, 10 psi maximum (140 lpm, 0.7mbar)
Electrical Specifications
Parameter
Supply Voltage
Supply Current
Output
Specification
120V +10/-15%, 50/60 Hz
0.04A
Pulse frequency modulated transistor
Required Accessory Cable with connector, 10 feet
(3m), model 5602-91-7, Part
49602-91-7
Wiring Extension Instrumentation cable with two pairs of individually shielded #18
AWG conductors, 300V minimum, BELDEN #9368 or equivalent.
Temperature Range 0°F to 140°F (-20° to +60°C) case temperature
Shipping Weight
Optical
4.5 lbs (2 kg)
Angle of view @ 2.5° depending on sight pipe size and length property damage. Be certain that the flame sensor detects only the pilot and/or main flame of the intended burner by testing the control system under varying operating conditions and firing rates. Follow the test procedures given in this manual and the equipment provider’s instructions after installation and at regularly scheduled maintenance intervals.
Sensor Wiring
Route sensor wiring a sufficient distance from ignition and other high voltage wiring to avoid electrical interference.
To reduce interference, ground both shields.
If sensor wiring is to extend beyond the supplied 10 ft
(305cm) lengths, use wiring extension as shown in specifications.
Tables 1 - 4 illustrate how the sensor should be wired to appropriate controls. Near the end of each of the four cable leads is a letter tag for identifications. The scanner is only available for 120V supply. Refer to Figure 1 to use with a 230 VAC supply.
NOTE: The shield wire terminals shown in the tables provide a convenient attachment point. A panel ground wire must also be run to these points.
Option
Sensor Installation
Spectral Sensitivity: 185 to 260 nanometers; scanner is solar blind
Non-Magnifying lens part 18165
CAUTION
CAUTION
■ Incorrect sensor installation may cause the sensor to generate a false flame signal. This can cause unburned fuel to collect in the combustion chamber, resulting in explosions, injuries, and
■ Cable lead "B" should only be connected to power
(120 VAC); connecting it to any other terminal will bypass the safe-start check of the scanner.
5602-91
Scanner
Connector
Pin
A
B
C
D
-
Table 1 - Wiring to Multi-Flame
Multi-Flame
J4 Terminal
Multi-Flame
J5 Terminal
5602-91-7
Cable
Wire red white black UV green Gnd Return shields
Function
Neutral
Scanner
#1
Scanner
#3
Scanner
#2
Scanner
#4
Neutral Neutral Neutral Neutral
120 VAC 120 VAC 120 VAC 120 VAC 120 VAC
Ground
3
2
4
9
8
10
3
2
4
9
8
10
Expansion Board
J3, J4, J5, J6 Terminals
Scanner #5, 6, 9,
10 (also #13, 14,
17, 18)
Scanner #7, 8,
11, 12 (also #15,
16, 19 20)
Neutral
120 VAC
3
2
4
Neutral
120 VAC
9
8
10
2 Eclipse Self-Check UV Scanner, V1, Instruction Manual 856, 10/18/2010
5602-91 Scanner
Connector Pin
A
B
C
D
-
5602-91 Scanner
Connector Pin
A
B
C
D
-
Table 2 - Wiring to Bi-Flame
5602-91-7
Cable Wire red white black green shields
Function
Neutral
120 VAC
UV
Gnd Return
Ground
Table 3 - Wiring to Veri-Flame
5602-91-7
Cable Wire red white black green shields
Function
Neutral
120 VAC
UV
Gnd Return
Ground
J4 Terminal
Scanner #1
Neutral
120 VAC
3
2
4
Bi-Flame
J5 Terminal
Scanner #2
Neutral
120 VAC
1
2
4
Veri-Flame
Terminal
2
1
S1
S2
Gnd
5602-91 Scanner
Connector Pin
A
B
C
D
-
Sensor Installation
Table 4 - Wiring to Peek-A-Flame
5602-91-7
Cable Wire red white black green shields
Function
Neutral
120 VAC
UV
Gnd Return
Ground
In most cases, the location for this scanner will be predetermined by the burner manufacturer. However, proper application of this scanner requires knowledge of the burner, the combustion chamber, and the process.
Opposing burners, flame swirl patterns, and substance in the line-of-sight may require special mounting techniques.
CAUTION
■ The UV tube is fragile. Handle carefully and avoid dropping or sharp blows.
Consult the burner manufacturer’s instructions for mounting location. The scanner should view the intersection of the pilot and main flames. It typically should be aimed at the first third of the flame closest to the burner nozzle, see Figure 2. Certain unburned hydrocarbons, oil mist, recirculated flue gas or other contaminants may mask and absorb the ultraviolet radiation.
Peek-A-Flame
Terminal
1
3
7
8
2
Position the scanner within 30 inches (762 mm) of the flame.
For temperatures higher than specified, provide clean cooling air to the 1/4" NPT purge tap on the housing.
Maximum furnace pressure is 60 psig.
To assist in sighting the scanner, a swivel mount
(#10042584) may be used.
Keep the scanner lens and line-of-sight free of contamination. Be aware that scanners looking up are susceptible to dirt and dust settling. Soot, steam, and unburned hydrocarbons may reduce or even mask the radiation from the flame. A purging assembly as described above may alleviate these problems.
Some burners have an open construction allowing the scanner to view into a furnace. Avoid sighting background sources of UV light. If necessary, mask the offending background source by use of an orifice.
Eclipse Self-Check UV Scanner, V1, Instruction Manual 856, 10/18/2010 3
2
1
S1
S2
Wiring with a Transformer for 230V Supply
T1
240V 120V
A
B
C
D
T1 Third party transformer required. Must be at least 25 VA.
Figure 1.
Main
Burner
One-Third of
Flame Length
Scanner
Sight Line
Figure 2. UV Scanner Sighting
Test Procedures
Perform the following tests for every new installation and at periodic maintenance intervals. Depending on the burner equipment (such as pilot versus direct spark), some of the tests may not be possible.
Measuring Flame Signal Strength
Insert the positive probe of a 0-15 VDC voltmeter (100k ohm minimum input impedance) into the test point on the control cover. Connect the negative probe to the GND or terminal for the "D" (green) wire. Readings greater than 4
VDC are adequate.
Minimum Pilot Test
Run this test on pilot ignited burners to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame.
1. Manually shut off the fuel supply to the burner, but not to the pilot.
2. Put the control in the pilot test mode. On the Veri-Flame push the Test/Reset button in the Test position (button in). On the Bi-Flame and Multi-Flame press the Reset and Enter buttons together then release the Reset and after a few seconds release the Enter.
3. Start the system normally. The control will hold the operating sequence at the pilot flame step.
4. Measure the flame signal strength as described above.
5. Slowly reduce the pilot fuel until the signal drops out.
Increase the pilot fuel slightly and restart the system.
Observe the flame signal and adjust the pilot fuel as required to prevent flame failure. This is the minimum pilot.
6. Take the control out of the pilot test mode and begin the start-up sequence again. On the Veri-Flame push the
Test/Reset button again so that it pops out to the Run position. On the Bi-Flame and Multi-Flame press the
Reset button.
7. When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to the main burner. If the main burner does not light within five seconds, immediately shut off the burner fuel supply, stop the control and purge the system. Attempt to light the burner again before proceeding with adjustments in the next step.
8. For burners with an adjustable scanner sighting assembly, adjust the sighting assembly further away from the nozzle of the pilot flame thus requiring a larger minimum pilot for adequate signal strength. For burners with fixed sighting, increase the pilot flame. Repeat steps 1 through 8 until the main burner lights off smoothly and reliably.
Ignition Interference Test
Test the effect of the ignition system (transformer, spark plug, wiring and grounding) on the flame signal and control. Ignition interference can decrease or increase the flame signal strength or can cause erratic operation of the control. The scanner placement on some burners allows direct sighting of the spark, creating a strong but false flame signal. The Eclipse flame control sequence does not interrupt the spark upon flame detection until after the trial for ignition period. Therefore spark detection is not a problem; however ignition interference should still be reduced or eliminated where possible.
1. Manually shut off the fuel supply to the burner.
2. Start the system normally. Observe the flame signal during ignition to see if it responds during the spark.
Readings above 2 VDC indicate spark interference or spark sighting.
3. On pilot ignited burners, manually shut off the fuel supply to the main burner. For direct spark burners, lock the burner firing-rate at the start position.
4. Put the control in the pilot test mode (see step 2 of
Minimum Pilot Test above).
4 Eclipse Self-Check UV Scanner, V1, Instruction Manual 856, 10/18/2010
5. Start the system normally. Observe the flame signal during spark and after the trial for ignition. Spark interference causes the signal during the spark to differ more than 2 VDC from the signal after the spark.
6. If spark interference is observed, try to minimize its affect: a. Ensure proper grounding for the ignition circuit.
b. Isolate the scanner from ground and/or remove the shield connection from ground.
c. Check for proper spark gap.
d. Clean, repair, or replace faulty wiring and connectors.
e. Separate or shield the scanner wiring from the ignition wiring.
f. Reverse the wires feeding the primary to the ignition transformer.
g. Move the location of the ignition transformer.
Pilot Flame Failure Test
1. Put the control in the pilot test mode (see step 2 of
Minimum Pilot Test above).
2. Start the system normally.
3. After the pilot has lit, manually turn off the fuel supply.
The controller should lock out of flame failure. If not, then the controller is detecting a false flame signal.
Find the problem and correct it before resuming normal operation.
Main Flame Failure Test
1. Put the control in the "Run" position (see step 6 of
Minimum Pilot Test above).
2. Start the system normally.
3. After the sequence lights the main flame, manually shut off the fuel supply. If the control does not shut down in less than 4 seconds after visually observing that the flame extinguished, it may be detecting a false flame signal. Find the problem and correct it before resuming normal operation.
Process Conditions Test
1. Start the system normally.
2. Observe the flame signal as the system operates at various firing rates under process (at temperature) conditions.
3. Perform the Main Flame Failure Test under these conditions and verify that the control shuts down in less than 4 seconds after visually observing that the flame extinguished.
Limit & Interlock Tests
Periodically check all interlock and limit switches by manually tripping them during burner operation to make sure they cause a system to lock out.
WARNING
■ Never operate a system that is improperly adjusted or has faulty interlocks or limit switches.
Always replace faulty equipment with new equipment before resuming operation. Operating a system with defective safety equipment can cause explosions, injuries, and property damage.
Maintenance
CAUTION
■ High voltage, turn off power before disconnecting or installing sensors or controls.
All burner systems must be maintained to ensure their safe operation. The operator of this equipment must be trained in safe operating procedures. The owner and operator must set a regularly scheduled maintenance interval based on recommendations from the equipment manufacturers, environmental conditions, and their own operational history.
System Checks
Periodically test the sensors as described in the Test
Procedure section.
Sensor Lens
Clean the glass lens regularly with a soft, damp cloth. The presence of foreign material will measurably reduce the flame signal strength.
Rotation
To ensure operability of stored items and to reduce the possibility of extended down-time, periodically swap spare sensors and control units with active ones.
Eclipse Self-Check UV Scanner, V1, Instruction Manual 856, 10/18/2010 5
Dimensions in inches (mm)
Ø3.2 (81.3)
1-3/8" - 18 EXT
7.5 (190.5)
6.8 (172.7)
1.8 (45.7)
Ø2.0 (50.8)
1.7 (43.2)
1/4" - 18 NPT
1" NPT INTERNAL
856 Instruction Manual, 10/18/2010
Advertisement