ABB Relion REQ650 Product Manual 72 Pages
advertisement
Relion ® 650 series
Breaker protection REQ650 2.1 IEC
Product guide
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Contents
1. Application..................................................................... 3
2. Available functions..........................................................5
3. Current protection........................................................ 12
4. Voltage protection........................................................ 13
5. Multipurpose protection................................................13
6. Secondary system supervision..................................... 13
7. Control......................................................................... 14
8. Logic............................................................................ 15
9. Monitoring.................................................................... 16
1MRK 505 358-BEN B
10. Metering......................................................................18
11. Human machine interface............................................18
12. Basic IED functions..................................................... 19
13. Station communication ...............................................19
14. Hardware description.................................................. 19
15. Connection diagrams.................................................. 22
16. Technical data............................................................. 23
17. Ordering for pre-configured IED...................................65
18. Ordering for Accessories............................................. 68
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2016 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
2 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Issued: June 2017
Revision: B
1. Application
GUID-3F024D79-D031-42DC-B0BC-1F3757B8D3E0 v3
Breaker protection REQ650 provides a standalone solution for applications where synchrocheck controlled closing of the circuit breaker is required, but the integration of the automatic reclosing function into the main line protection IED is not preferred or suitable. The advanced automatic reclosing, synchronizing, synchrocheck and energizing check functions of REQ650 provides an optimized standalone product.
REQ650 provides backup to the main protection with redundant protection and control functions.
One pre-configured package has been defined for the following application:
• A breaker bay connecting a transmission line to a busbar, with back-up protection functions enabling single or three phase trip (B11)
The backup protection is based on basic overcurrent and voltage based functions. In line protection applications, autoreclosing with or without synchrocheck is available.
The package is configured and ready for direct use. Analog and control circuits have been pre-defined and other signals need to be applied as required for each application. The preconfigured IED can be changed and adapted to suit specific applications with the graphical configuration tool.
Forcing of binary inputs and outputs is a convenient way to test wiring in substations as well as testing configuration logic in the IEDs. Basically it means that all binary inputs and outputs on the IED I/O modules (BOM, BIM and IOM) can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a secure solution for enforcing access control to IEDs and other systems within a substation.
This incorporates management of user accounts, roles and certificates and the distribution of such, a procedure completely transparent to the user.
The Flexible Product Naming allows the customer to use an
IED-vendor independent 61850 model of the IED. This customer model will be used as the IEC 61850 data model, but all other aspects of the IED will remain unchanged (e.g., names on the local HMI and names in the tools). This offers significant flexibility to adapt the IED to the customers system and standard solution
Description of B11
GUID-D9C6EAEB-A4EA-49BF-BE90-CC3CAF1CA476 v1
A breaker bay connecting a transmission line to a busbar, with back-up protection functions enabling single or three phase trip.
ABB 3
Breaker protection REQ650 2.1 IEC
Product version: 2.1
WA1
WA2
1MRK 505 358-BEN B
REQ650 B11
– Single breaker with single phase tripping
12AI (7I+5U)
QB1
QA1
QB9
QB2
WA2_VT
MET UN
VN MMXU
WA1_VT
MET UN
VN MMXU
79 5(0 →1)
SMB RREC
25 SC/VC
SES RSYN
3 Control
Q CBAY
LINE_CT
50BF 3I>BF
CC RBRF
50STB 3I>STB
STB PTOC
50 3I>>
PH PIOC
26 q>
LC PTTR
46 lub
BRC PTOC
50N IN>>
EF PIOC
51N_67N 4(IN>)
EF4 PTOC
MET P/Q
CV MMXN
U>/I<
FUF SPVC
46I2
NS4 PTOC
51_67 4(3I>)
OC4 PTOC
QC9
MET W/Varh
ETP MMTR
MET Isqi
C MSQI
MET I
C MMXU
LINE_VT
DFR/SER DR
DRP RDRE
27 2(3U<)
UV2 PTUV
59 3U>
OV2 PTOV
63
S SIMG
71
S SIML
27
LOV PTUV
MET U
V MMXU
59N 3U0
ROV2 PTOV
MET Usqi
V MSQI
MET UN
VN MMXU
Other Functions available from the function library
2(I>/U<)
CV GAPC
87 INd/I
CCS SPVC
26 θ>
LF PTTR
IEC10000323 V5 EN-US
Figure 1.
Configuration diagram for configuration B11
IEC10000323-5-en.vsd
4 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
2. Available functions
Back-up protection functions
IEC 61850 ANSI Function description
Current protection
PHPIOC
OC4PTOC
50 Instantaneous phase overcurrent protection
51_67 1) Four step phase overcurrent protection
EFPIOC
EF4PTOC
50N
51N
67N 2)
Instantaneous residual overcurrent protection
Four step residual overcurrent protection
NS4PTOC
LCPTTR
LFPTTR
CCRBRF
46I2
26
26
50BF
Four step directional negative phase sequence overcurrent protection
Thermal overload protection, one time constant, Celsius
Thermal overload protection, one time constant, Fahrenheit
Breaker failure protection
Stub protection
Broken conductor check
STBPTOC
BRCPTOC
Voltage protection
50STB
46
UV2PTUV
OV2PTOV
ROV2PTOV
LOVPTUV
27
59
59N
27
Multipurpose protection
CVGAPC
Two step undervoltage protection
Two step overvoltage protection
Two step residual overvoltage protection
Loss of voltage check
General current and voltage protection
1) 67 requires voltage
2) 67N requires voltage
1MRK 505 358-BEN B
GUID-A8D0852F-807F-4442-8730-E44808E194F0 v11
Breaker
REQ650 (B11)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
ABB 5
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Control and monitoring functions
IEC 61850 ANSI Function description
Control
SESRSYN
SMBRREC
QCBAY
LOCREM
LOCREMCTRL
SLGAPC
VSGAPC
DPGAPC
SPC8GAPC
AUTOBITS
Synchrocheck, energizing check and synchronizing
Autorecloser
Apparatus control
Handling of LRswitch positions
LHMI control of PSTO
Logic Rotating Switch for function selection and LHMI presentation
Selector mini switch
Generic communication function for Double Point indication
Single Point Generic Control 8 signals
AutomationBits, command function for DNP3.0
SINGLECMD
I103CMD
I103GENCMD
I103POSCMD
CCSSPVC
FUFSPVC
Logic
SMPPTRC
Single command, 16 signals
Function commands for IEC 60870-5-103
Function commands generic for IEC 60870-5-103
IED commands with position and select for IEC 60870-5-103
I103POSCMDV
I103IEDCMD
IED direct commands with position for IEC 60870-5-503
IED commands for IEC 60870-5-103
I103USRCMD
Secondary system supervision
Function commands user defined for IEC 60870-5-103
Current circuit supervison
Fuse failure supervision
TMAGAPC
ALMCALH
WRNCALH
INDCALH
AND, GATE, INV,
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Tripping logic
Trip matrix logic
Logic for group alarm
Logic for group warning
Logic for group indication
Basic configurable logic blocks (see Table
)
FXDSIGN
B16I
BTIGAPC
IB16
ITBGAPC
Fixed signal function block
Boolean 16 to Integer conversion
Boolean 16 to Integer conversion with Logic Node representation
Integer to Boolean 16 conversion
Integer to Boolean 16 conversion with Logic Node representation
6
1MRK 505 358-BEN B
GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v13
Breaker
REQ650 (B11)
6
1
1
5
5
12
5
40–420
4
50
1
4
1
50
50
1
1
15
20
1
1
1
16
5
3
1
18
16
18
16
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
IEC 61850
TEIGAPC
INTCOMP
REALCOMP
Monitoring
CVMMXN,
VMMXU, CMSQI,
VMSQI, VNMMXU
CMMXU
AISVBAS
SSIMG
SSIML
EVENT
DRPRDRE,
A1RADR-
A4RADR,
B1RBDR-B8RBDR
SPGAPC
SP16GAPC
MVGAPC
BINSTATREP
RANGE_XP
I103MEAS
I103MEASUSR
I103AR
I103EF
I103FLTPROT
I103IED
I103SUPERV
I103USRDEF
L4UFCNT
TEILGAPC
Metering
PCFCNT
ETPMMTR
ANSI Function description
Elapsed time integrator with limit transgression and overflow supervision
Comparator for integer inputs
Comparator for real inputs
Measurements
Measurements
Function block for service value presentation of secondary analog inputs
Gas medium supervision
Liquid medium supervision
Event function
Disturbance report
Generic communication function for Single Point indication
Generic communication function for Single Point indication 16 inputs
Generic communication function for Measured Value
Logical signal status report
Measured value expander block
Measurands for IEC 60870-5-103
Measurands user defined signals for IEC 60870-5-103
Function status auto-recloser for IEC 60870-5-103
Function status earth-fault for IEC 60870-5-103
Function status fault protection for IEC 60870-5-103
IED status for IEC 60870-5-103
Supervison status for IEC 60870-5-103
Status for user defined signals for IEC 60870-5-103
Event counter with limit supervision
Running hour-meter
Pulse-counter logic
Function for energy calculation and demand handling
1MRK 505 358-BEN B
12
12
12
6
Breaker
REQ650 (B11)
10
1
21
3
20
1
6
20
30
1
1
1
1
3
1
66
1
64
16
24
3
16
6
ABB 7
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 1. Total number of instances for basic configurable logic blocks
Basic configurable logic block
AND
GATE
INV
LLD
OR
PULSETIMER
RSMEMORY
SRMEMORY
TIMERSET
XOR
Total number of instances
280
40
40
40
60
280
40
420
40
40
1MRK 505 358-BEN B
8 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Communication
IEC 61850
DNPFREC
IEC 61850-8-1
GOOSEINTLKRCV
GOOSEBINRCV
GOOSEDPRCV
GOOSEINTRCV
GOOSEMVRCV
GOOSESPRCV
MULTICMDRCV/
MULTICMDSND
FRONT, LANABI,
LANAB, LANCDI,
LANCD, GATEWAY
OPTICAL103
RS485103
AGSAL
LD0LLN0
SYSLLN0
LPHD
PCMACCS
SECALARM
Station communication
LONSPA, SPA
ADE
HORZCOMM
PROTOCOL
RS485PROT
RS485GEN
DNPGEN
DNPGENTCP
CHSERRS485
CH1TCP, CH2TCP,
CH3TCP, CH4TCP
CHSEROPT
MSTSER
MST1TCP,
MST2TCP,
MST3TCP,
MST4TCP
ANSI
ABB
Function description
SPA communication protocol
LON communciation protocol
Network variables via LON
Operation selection between SPA and IEC 60870-5-103 for SLM
Operation selection for RS485
RS485
DNP3.0 communication general protocol
DNP3.0 communication general TCP protocol
DNP3.0 for EIA-485 communication protocol
DNP3.0 for TCP/IP communication protocol
DNP3.0 for TCP/IP and EIA-485 communication protocol
DNP3.0 for serial communication protocol
DNP3.0 for TCP/IP communication protocol
DNP3.0 fault records for TCP/IP and EIA-485 communication protocol
Parameter setting function for IEC 61850
Horizontal communication via GOOSE for interlocking
GOOSE binary receive
GOOSE function block to receive a double point value
GOOSE function block to receive an integer value
GOOSE function block to receive a measurand value
GOOSE function block to receive a single point value
Multiple command and transmit
Ethernet configuration
IEC 60870-5-103 Optical serial communication
IEC 60870-5-103 serial communication for RS485
Generic security application component
IEC 61850 LD0 LLN0
IEC 61850 SYS LLN0
Physical device information
IED configuration protocol
Component for mapping security events on protocols such as DNP3 and IEC103
GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v13
Breaker
REQ650 (B11)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
59
16
64
32
60
64
60/10
1
1
1
1
1
1
1
1
1
9
Breaker protection REQ650 2.1 IEC
Product version: 2.1
IEC 61850
FSTACCS,
FSTACCSNA
ACTIVLOG
ALTRK
SINGLELCCH
PRPSTATUS
PRP
ANSI Function description
Field service tool access via SPA protocol over ethernet communication
Activity logging parameters
Service Tracking
Single ethernet port link status
Dual ethernet port link status
IEC 62439-3 parallel redundancy protocol
1MRK 505 358-BEN B
1
Breaker
REQ650 (B11)
1
1
1
1
1-P03
10 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Basic IED functions
Table 2. Basic IED functions
IEC 61850 or function name
INTERRSIG
SELFSUPEVLST
TIMESYNCHGEN
BININPUT, SYNCHCAN,
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA,
SYNCHCMPPS
TIMEZONE
DSTBEGIN,
DSTENABLE, DSTEND
IRIG-B
SETGRPS
ACTVGRP
TESTMODE
CHNGLCK
SMBI
SMBO
SMAI1 - SMAI12
3PHSUM
ATHSTAT
ATHCHCK
AUTHMAN
FTPACCS
SPACOMMMAP
SPATD
DOSFRNT
DOSLANAB
DOSLANCD
DOSSCKT
GBASVAL
PRIMVAL
ALTMS
ALTIM
MSTSER
Description
Self supervision with internal event list
Self supervision with internal event list
Time synchronization module
Time synchronization
Time synchronization
GPS time synchronization module
Time synchronization
Number of setting groups
Parameter setting groups
Test mode functionality
Change lock function
Signal matrix for binary inputs
Signal matrix for binary outputs
Signal matrix for analog inputs
Summation block 3 phase
Authority status
Authority check
Authority management
FTP access with password
SPA communication mapping
Date and time via SPA protocol
Denial of service, frame rate control for front port
Denial of service, frame rate control for OEM port AB
Denial of service, frame rate control for OEM port CD
Denial of service, socket flow control
Global base values for settings
Primary system values
Time master supervision
Time management
DNP3.0 for serial communication protocol
ABB
1MRK 505 358-BEN B
GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v10
11
1MRK 505 358-BEN B
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 3. Local HMI functions
IEC 61850 or function name
LHMICTRL
LANGUAGE
SCREEN
FNKEYTY1–FNKEYTY5
FNKEYMD1–
FNKEYMD5
LEDGEN
OPENCLOSE_LED
GRP1_LED1–
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15
ANSI Description
Local HMI signals
Local human machine language
Local HMI Local human machine screen behavior
Parameter setting function for HMI in PCM600
General LED indication part for LHMI
LHMI LEDs for open and close keys
Basic part for CP HW LED indication module
3. Current protection
M12910-3 v12
The instantaneous two-phase overcurrent function PHPIOC has low transient overreach and short tripping times to allow use as a high set short-circuit protection function.
M13667-3 v18
EF4PTOC can be set directional or non-directional independently for each of the steps.
IDir, UPol and IPol can be independently selected to be either zero sequence or negative sequence.
Four-step phase overcurrent protection OC4PTOC
M12846-3 v16
The four step three-phase overcurrent protection function
OC4PTOC has an inverse or definite time delay independent for step 1 to 4 separately.
All IEC and ANSI inverse time characteristics are available together with an optional user defined time characteristic.
Four step negative sequence overcurrent protection
NS4PTOC
GUID-485E9D36-0032-4559-9204-101539A32F47 v5
Four step negative sequence overcurrent protection
(NS4PTOC) has an inverse or definite time delay independent for each step separately.
The directional function needs voltage as it is voltage polarized with memory. The function can be set to be directional or non-directional independently for each of the steps.
A second harmonic blocking level can be set for the function and can be used to block each step individually.
Instantaneous residual overcurrent protection EFPIOC
M12701-3 v15
The Instantaneous residual overcurrent protection EFPIOC has a low transient overreach and short tripping times to allow the use for instantaneous earth-fault protection, with the reach limited to less than the typical eighty percent of the line at minimum source impedance. EFPIOC is configured to measure the residual current from the three-phase current inputs and can be configured to measure the current from a separate current input.
Four step residual overcurrent protection, zero sequence and negative sequence direction EF4PTOC
The directional function is voltage polarized.
NS4PTOC can be set directional or non-directional independently for each of the steps.
Thermal overload protection, one time constant
M12020-4 v13
The increasing utilization of the power system closer to the thermal limits has generated a need of a thermal overload protection for power lines.
A thermal overload will often not be detected by other protection functions and the introduction of the thermal overload protection can allow the protected circuit to operate closer to the thermal limits.
The three-phase current measuring protection has an I 2 t characteristic with settable time constant and a thermal memory. The temperature is displayed in either Celsius or
Fahrenheit, depending on whether the function used is
LCPTTR (Celsius) or LFPTTR (Fahrenheit).
12 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
An alarm level gives early warning to allow operators to take action well before the line is tripped.
Estimated time to trip before operation, and estimated time to reclose after operation are presented.
Breaker failure protection CCRBRF
M11550-6 v16
Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding breakers in case the own breaker fails to open. CCRBRF can be current-based, contact-based or an adaptive combination of these two conditions.
A current check with extremely short reset time is used as check criterion to achieve high security against inadvertent operation.
Contact check criteria can be used where the fault current through the breaker is small.
CCRBRF can be single- or three-phase initiated to allow use with single phase tripping applications. For the three-phase version of CCRBRF the current criteria can be set to operate only if two out of four for example, two phases or one phase plus the residual current start. This gives a higher security to the back-up trip command.
CCRBRF function can be programmed to give a single- or three-phase re-trip of its own breaker to avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to mistakes during testing.
Stub protection STBPTOC
M12902-3 v9
The primary line distance protection will thus not be able to operate and must be blocked.
The stub protection STBPTOC covers the zone between the current transformers and the open disconnector. The threephase instantaneous overcurrent function is released from a normally open, NO (b) auxiliary contact on the line disconnector.
Two step overvoltage protection OV2PTOV
M13798-3 v14
Overvoltages may occur in the power system during abnormal conditions such as sudden power loss, tap changer regulating failures, and open line ends on long lines.
OV2PTOV has a high reset ratio to allow settings close to system service voltage.
Two step residual overvoltage protection ROV2PTOV
M13808-3 v10
Residual voltages may occur in the power system during earth faults.
Two step residual overvoltage protection ROV2PTOV function calculates the residual voltage from the three-phase voltage input transformers or measures it from a single voltage input transformer fed from an open delta or neutral point voltage transformer.
Two step residual overvoltage protection ROV2PTOV function calculates the residual voltage from the two-phase voltage input transformers or measures it from a single voltage input transformer fed from a neutral point voltage transformer.
ROV2PTOV has two voltage steps, each with inverse or definite time delay.
ROV2PTOV has two voltage steps, each with definite time delay.
Loss of voltage check LOVPTUV
Loss of voltage check LOVPTUV is suitable for use in
SEMOD171457-5 v7 networks with an automatic system restoration function.
LOVPTUV issues a three-pole trip command to the circuit breaker, if all three phase voltages fall below the set value for a time longer than the set time and the circuit breaker remains closed.
The operation of LOVPTUV is supervised by the fuse failure supervision FUFSPVC.
Broken conductor check BRCPTOC
SEMOD171446-5 v2
The main purpose of the function Broken conductor check
(BRCPTOC) is the detection of broken conductors on protected power lines and cables (series faults). Detection can be used to give alarm only or trip the line breaker.
5. Multipurpose protection
General current and voltage protection CVGAPC
M13083-11 v9
The General current and voltage protection (CVGAPC) can be utilized as a negative sequence current protection detecting unsymmetrical conditions such as open phase or unsymmetrical faults.
4. Voltage protection
Two step undervoltage protection UV2PTUV
M13789-3 v11
Undervoltages can occur in the power system during faults or abnormal conditions. Two step undervoltage protection
(UV2PTUV) function can be used to open circuit breakers to prepare for system restoration at power outages or as longtime delayed back-up to primary protection.
UV2PTUV has a high reset ratio to allow settings close to system service voltage.
ABB
6. Secondary system supervision
Current circuit supervision CCSSPVC
M12444-3 v10
Open or short circuited current transformer cores can cause unwanted operation of many protection functions such as differential, earth-fault current and negative-sequence current functions.
Current circuit supervision (CCSSPVC) compares the residual current from a three phase set of current transformer cores
13
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B with the neutral point current on a separate input taken from another set of cores on the current transformer.
Current circuit supervision (CCSSPVC) compares the residual current from a two phase set of current transformer cores with the neutral point current on a separate input taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to block protection functions expected to give inadvertent tripping.
Fuse failure supervision FUFSPVC
SEMOD113820-4 v11
The aim of the fuse failure supervision function FUFSPVC is to block voltage measuring functions at failures in the secondary circuits between the voltage transformer and the IED in order to avoid inadvertent operations that otherwise might occur.
The fuse failure supervision function basically has three different detection methods, negative sequence and zero sequence based detection and an additional delta voltage and delta current detection.
A criterion based on delta current and delta voltage measurements can be added to the fuse failure supervision function in order to detect a three phase fuse failure, which in practice is more associated with voltage transformer switching during station operations.
difference, phase angle difference, slip frequency and frequency rate of change before issuing a controlled closing of the circuit breaker. Breaker closing time is a parameter setting.
M12390-3 v14
The autorecloser SMBRREC function provides high-speed and/or delayed auto-reclosing for single breaker applications.
Up to five three-phase reclosing attempts can be included by parameter setting.
autoreclosing function is configured to co-operate with the synchrocheck function.
The autorecloser SMBRREC function provides high-speed and/or delayed auto-reclosing for single or multi-breaker applications. The autoreclosing can be used for delayed busbar restoration. Two autoreclosers, one for each busbar, can be provided.
Up to five reclosing attempts can be included by parameter setting.
Each autoreclosing function is configured to co-operate with the synchrocheck function.
The autoreclosing function provides high-speed and/or delayed three pole autoreclosing.
Bay control QCBAY
M13447-3 v7
The Bay control QCBAY function is used together with Local remote and local remote control functions to handle the selection of the operator place per bay. QCBAY also provides blocking functions that can be distributed to different apparatuses within the bay.
7. Control
Synchrocheck, energizing check, and synchronizing
SESRSYN
M12480-3 v15
The Synchronizing function allows closing of asynchronous networks at the correct moment including the breaker closing time, which improves the network stability.
Synchrocheck, energizing check, and synchronizing
SESRSYN function checks that the voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that closing can be done safely.
The synchrocheck and energizing check function checks that the voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that closing can be done safely.
SESRSYN function includes a built-in voltage selection scheme for double bus and 1½ breaker or ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and can have different settings.
For systems, which are running asynchronous, a synchronizing function is provided. The main purpose of the synchronizing function is to provide controlled closing of circuit breakers when two asynchronous systems are going to be connected. The synchronizing function evaluates voltage
14
Local remote LOCREM/Local remote control LOCREMCTRL
M17086-3 v8
The signals from the local HMI or from an external local/ remote switch are connected via the function blocks
LOCREM and LOCREMCTRL to the Bay control QCBAY function block. The parameter
ControlMode
in function block
LOCREM is set to choose if the switch signals are coming from the local HMI or from an external hardware switch connected via binary inputs.
Logic rotating switch for function selection and LHMI presentation SLGAPC
SEMOD114908-4 v9
The logic rotating switch for function selection and LHMI presentation SLGAPC (or the selector switch function block) is used to get an enhanced selector switch functionality compared to the one provided by a hardware selector switch.
Hardware selector switches are used extensively by utilities, in order to have different functions operating on pre-set values. Hardware switches are however sources for maintenance issues, lower system reliability and an extended purchase portfolio. The selector switch function eliminates all these problems.
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Selector mini switch VSGAPC
The Selector mini switch VSGAPC function block is a
SEMOD158756-5 v8 multipurpose function used for a variety of applications, as a general purpose switch.
VSGAPC can be controlled from the menu, from a symbol on the single line diagram (SLD) on the local HMI or from Binary inputs
Generic communication function for Double Point indication
DPGAPC
SEMOD55850-5 v6
Generic communication function for Double Point indication
DPGAPC function block is used to send double indications to other systems, equipment or functions in the substation through IEC 61850-8-1 or other communication protocols. It is especially used in the interlocking station-wide logics.
Single point generic control 8 signals SPC8GAPC
SEMOD176462-4 v9
In this way, simple commands can be sent directly to the IED outputs, without confirmation. The commands can be pulsed or steady with a settable pulse time.
ABB
SEMOD158591-5 v7
Single command, 16 signals
M12446-6 v5
The IEDs can receive commands either from a substation automation system or from the local HMI. The command function block has outputs that can be used, for example, to control high voltage apparatuses or for other user defined functionality.
8. Logic
M12275-3 v10
A function block for protection tripping is always provided as basic for each circuit breaker involved in the tripping of the fault. It provides a settable pulse prolongation to ensure a trip pulse of sufficient length, as well as all functionality necessary for correct co-operation with autoreclosing functions.
The trip function block also includes a settable latch functionality for breaker lock-out.
Trip matrix logic TMAGAPC
M15321-3 v11
The trip matrix logic function has 3 output signals and these outputs can be connected to physical tripping outputs according to the specific application needs for settable pulse or steady output.
Group alarm logic function ALMCALH
GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v3
The group alarm logic function ALMCALH is used to route several alarm signals to a common indication, LED and/or contact, in the IED.
Group warning logic function WRNCALH
GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v3
The group warning logic function WRNCALH is used to route several warning signals to a common indication, LED and/or contact, in the IED.
Group indication logic function INDCALH
Basic configurable logic blocks
M11396-4 v15
The basic configurable logic blocks do not propagate the time stamp and quality of signals (have no suffix QT at the end of their function name). A number of logic blocks and timers are always available as basic for the user to adapt the configuration to the specific application needs. The list below shows a summary of the function blocks and their features.
These logic blocks are also available as part of an extension logic package with the same number of instances.
• AND function block. Each block has four inputs and two outputs where one is inverted.
GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v3
The group indication logic function INDCALH is used to route several indication signals to a common indication, LED and/or contact, in the IED.
• GATE function block is used for whether or not a signal should be able to pass from the input to the output.
• INVERTER function block that inverts one input signal to the output.
• LLD function block. Loop delay used to delay the output signal one execution cycle.
• OR function block. Each block has up to six inputs and two outputs where one is inverted.
• PULSETIMER function block can be used, for example, for pulse extensions or limiting of operation of outputs, settable pulse time.
• RSMEMORY function block is a flip-flop that can reset or set an output from two inputs respectively. Each block has two outputs where one is inverted. The memory setting controls if, after a power interruption, the flip-flop resets or returns to the state it had before the power interruption.
RESET input has priority.
• SRMEMORY function block is a flip-flop that can set or reset an output from two inputs respectively. Each block has two outputs where one is inverted. The memory setting controls if, after a power interruption, the flip-flop resets or returns to the state it had before the power interruption.
The SET input has priority.
• TIMERSET function has pick-up and drop-out delayed outputs related to the input signal. The timer has a settable time delay.
• XOR function block. Each block has two outputs where one is inverted.
Fixed signal function block
M15322-3 v11
The Fixed signals function FXDSIGN generates nine pre-set
(fixed) signals that can be used in the configuration of an IED, either for forcing the unused inputs in other function blocks to
15
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B a certain level/value, or for creating certain logic. Boolean, integer, floating point, string types of signals are available.
One FXDSIGN function block is included in all IEDs.
Elapsed time integrator with limit transgression and overflow supervision (TEIGAPC)
GUID-2D64874A-F266-4251-8EED-E813F40513D7 v2
The Elapsed time integrator function TEIGAPC is a function that accumulates the elapsed time when a given binary signal has been high.
The main features of TEIGAPC
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1
The function gives the possibility to monitor the level of integer values in the system relative to each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring, supervision, interlocking and other logics.
Comparator for real inputs REALCOMP
GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1
The function gives the possibility to monitor the level of real value signals in the system relative to each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring, supervision, interlocking and other logics.
• Applicable to long time integration (≤999 999.9
seconds).
• Supervision of limit transgression conditions and overflow.
• Possibility to define a warning or alarm with the resolution of 10 milliseconds.
• Retaining of the integration value.
• Possibilities for blocking and reset.
• Reporting of the integrated time.
Boolean 16 to Integer conversion B16I
SEMOD175725-4 v4
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical) signals into an integer.
Boolean 16 to Integer conversion with logic node representation BTIGAPC
Boolean 16 to integer conversion with logic node
SEMOD175781-4 v7 representation function BTIGAPC is used to transform a set of
16 binary (logical) signals into an integer. The block input will freeze the output at the last value.
• measured voltages, currents, frequency, active, reactive and apparent power and power factor
• primary phasors
Disturbance report DRPRDRE
M12153-3 v11.1.1
Complete and reliable information about disturbances in the primary and/or in the secondary system together with continuous event-logging is accomplished by the disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of all selected analog input and binary signals connected to the function block with a, maximum of
40 analog and 128 binary signals.
BTIGAPC can receive remote values via IEC 61850 depending on the operator position input (PSTO).
Integer to Boolean 16 conversion
SEMOD158373-5 v5
Integer to boolean 16 conversion function is used to transform an integer into a set of 16 binary (logical) signals.
Integer to Boolean 16 conversion with logic node representation ITBGAPC
SEMOD158421-5 v8
Integer to boolean conversion with logic node representation function ITBGAPC is used to transform an integer which is transmitted over IEC 61850 and received by the function to
16 binary coded (logic) output signals.
9. Monitoring
Measurements CVMMXN, CMMXU, VNMMXU, VMMXU,
CMSQI, VMSQI
The measurement functions are used to get on-line information from the IED. These service values make it
M12024-3 v8 possible to display on-line information on the local HMI and on the Substation automation system about:
The Disturbance report functionality is a common name for several functions:
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
The Disturbance report function is characterized by great flexibility regarding configuration, starting conditions, recording times, and large storage capacity.
ITBGAPC function can only receive remote values over IEC
61850 when the R/L (Remote/Local) push button on the front
HMI, indicates that the control mode for the operator is in position R (Remote i.e. the LED adjacent to R is lit ), and the corresponding signal is connected to the input PSTO
ITBGAPC function block. The input BLOCK will freeze the output at the last received value and blocks new integer values to be received and converted to binary coded outputs.
Comparator for integer inputs INTCOMP
A disturbance is defined as an activation of an input to the
AnRADR or BnRBDR function blocks, which are set to trigger the disturbance recorder. All connected signals from start of pre-fault time to the end of post-fault time will be included in the recording.
Every disturbance report recording is saved in the IED in the standard Comtrade format as a reader file HDR, a configuration file CFG, and a data file DAT. The same applies
16 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B to all events, which are continuously saved in a -buffer. The local HMI is used to get information about the recordings. The disturbance report files may be uploaded to PCM600 for further analysis using the disturbance handling tool.
Event list DRPRDRE
M12412-6 v8
Continuous event-logging is useful for monitoring the system from an overview perspective and is a complement to specific disturbance recorder functions.
The event list logs all binary input signals connected to the
Disturbance recorder function. The list may contain up to
1000 time-tagged events stored in a -buffer.
Indications DRPRDRE
To get fast, condensed and reliable information about a straightforward way.
the Disturbance recorder function (triggered).
M12030-3 v6 disturbances in the primary and/or in the secondary system it is important to know, for example binary signals that have changed status during a disturbance. This information is used in the short perspective to get information via the local HMI in
There are three LEDs on the local HMI (green, yellow and red), which will display status information about the IED and
The Indication list function shows all selected binary input signals connected to the Disturbance recorder function that have changed status during a disturbance.
Event recorder DRPRDRE
M12033-3 v8
Quick, complete and reliable information about disturbances in the primary and/or in the secondary system is vital, for example, time-tagged events logged during disturbances.
This information is used for different purposes in the short term (for example corrective actions) and in the long term (for example functional analysis).
The event recorder logs all selected binary input signals connected to the Disturbance recorder function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
The event recording information is an integrated part of the disturbance record (Comtrade file).
Trip value recorder DRPRDRE
M12128-3 v7
Information about the pre-fault and fault values for currents and voltages are vital for the disturbance evaluation.
The Trip value recorder calculates the values of all selected analog input signals connected to the Disturbance recorder function. The result is magnitude and phase angle before and during the fault for each analog input signal.
The trip value recorder information is available for the disturbances locally in the IED.
The trip value recorder information is an integrated part of the disturbance record (Comtrade file).
Disturbance recorder DRPRDRE
M12156-3 v10
The Disturbance recorder function supplies fast, complete and reliable information about disturbances in the power system. It facilitates understanding system behavior and related primary and secondary equipment during and after a disturbance. Recorded information is used for different purposes in the short perspective (for example corrective actions) and long perspective (for example functional analysis).
The Disturbance recorder acquires sampled data from selected analog- and binary signals connected to the
Disturbance recorder function (maximum 40 analog and 128 binary signals). The binary signals available are the same as for the event recorder function.
The function is characterized by great flexibility and is not dependent on the operation of protection functions. It can record disturbances not detected by protection functions. Up to ten seconds of data before the trigger instant can be saved in the disturbance file.
The disturbance recorder information for up to 100 disturbances are saved in the IED and the local HMI is used to view the list of recordings.
Event function
M12805-6 v10
When using a Substation Automation system with LON or
SPA communication, time-tagged events can be sent at change or cyclically from the IED to the station level. These events are created from any available signal in the IED that is connected to the Event function (EVENT). The EVENT function block is used for LON and SPA communication.
Analog and double indication values are also transferred through the EVENT function.
Generic communication function for Single Point indication
SPGAPC
SEMOD55713-5 v7
Generic communication function for Single Point indication
SPGAPC is used to send one single logical signal to other systems or equipment in the substation.
Measured value expander block translating the integer output signal from the measuring functions to 5 binary signals: below low-low limit, below low limit, normal, above high limit or above high-high limit. The output signals can be used as conditions in the configurable logic or for alarming purpose.
SEMOD52450-4 v7 are provided with measurement supervision functionality. All measured values can be supervised with four settable limits: low-low limit, low limit, high limit and high-high limit. The measure value expander block has been introduced to enable
ABB 17
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Event counter with limit supervison L4UFCNT
GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v5
The 30 limit counter L4UFCNT provides a settable counter with four independent limits where the number of positive and/or negative flanks on the input signal are counted against the setting values for limits. The output for each limit is activated when the counted value reaches that limit.
Overflow indication is included for each up-counter.
Running hour-meter (TEILGAPC)
GUID-464FB24F-B367-446C-963A-A14841943B87 v1
The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed time when a given binary signal has been high.
The main features of TEILGAPC are: time
tEnergy
. The integration of active and reactive energy values will happen in both forward and reverse directions.
These energy values are available as output signals and also as pulse outputs. Integration of energy values can be controlled by inputs (STARTACC and STOPACC) and
EnaAcc
setting and it can be reset to initial values with RSTACC input.
The maximum demand for active and reactive powers are calculated for the set time interval
tEnergy
and these values are updated every minute through output channels. The active and reactive maximum power demand values are calculated for both forward and reverse direction and these values can be reset with RSTDMD input.
• Applicable to very long time accumulation (≤ 99999.9
hours)
• Supervision of limit transgression conditions and rollover/ overflow
• Possibility to define a warning and alarm with the resolution of 0.1 hours
• Retain any saved accumulation value at a restart
• Possibilities for blocking and reset
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time
11. Human machine interface
Local HMI
AMU0600442 v14
10. Metering
Pulse-counter logic PCFCNT
Pulse-counter logic (PCFCNT) function counts externally
M13394-3 v7 generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values. The pulses are captured by the binary input module and then read by the PCFCNT function. A scaled service value is available over the station bus. The special Binary input module with enhanced pulse counting capabilities must be ordered to achieve this functionality.
Function for energy calculation and demand handling
(ETPMMTR)
GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v2
Measurements function block (CVMMXN) can be used to measure active as well as reactive power values. Function for energy calculation and demand handling (ETPMMTR) uses measured active and reactive power as input and calculates the accumulated active and reactive energy pulses, in forward and reverse direction. Energy values can be read or generated as pulses. Maximum demand power values are also calculated by the function. This function includes zero point clamping to remove noise from the input signal. As output of this function: periodic energy calculations, integration of energy values, calculation of energy pulses, alarm signals for limit violation of energy values and maximum power demand, can be found.
The values of active and reactive energies are calculated from the input power values by integrating them over a selected
18
IEC13000239 V2 EN-US
Figure 2.
Local human-machine interface
IEC13000239-2-en.vsd
The LHMI of the IED contains the following elements:
• Graphical display capable of showing a user defined single line diagram and provide an interface for controlling switchgear.
• Navigation buttons and five user defined command buttons to shortcuts in the HMI tree or simple commands.
• 15 user defined three-color LEDs.
• Communication port for PCM600.
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
The LHMI is used for setting, monitoring and controlling.
12. Basic IED functions
Time synchronization
M11344-3 v9
The time synchronization function is used to select a common source of absolute time for the synchronization of the IED when it is a part of a protection system. This makes it possible to compare events and disturbance data between all
IEDs within a station automation system and in between substations.
13. Station communication
Communication protocols
Each IED is provided with a communication interface,
• IEC 61850-8-1 communication protocol
• LON communication protocol
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol
M14815-3 v12 enabling it to connect to one or many substation level systems or equipment, either on the Substation Automation
(SA) bus or Substation Monitoring (SM) bus.
Available communication protocols are:
SEMOD120137-5 v3
DNP3.0 communication protocol
SEMOD153688-5 v1
An electrical RS485 and an optical Ethernet port is available for the DNP3.0 communication. DNP3.0 Level 2 communication with unsolicited events, time synchronizing and disturbance reporting is provided for communication to
RTUs, Gateways or HMI systems.
Multiple command and transmit
M14791-3 v3
When IEDs are used in Substation Automation systems with
LON, SPA or IEC 60870-5-103 communication protocols, the
Event and Multiple Command function blocks are used as the communication interface for vertical communication to station
HMI and gateway, and as interface for horizontal peer-to-peer communication (over LON only).
IEC 62439-3 Parallel Redundancy Protocol
GUID-A90FDBA7-D4D7-4CBD-9F05-13DCC9971779 v5
Redundant station bus communication according to IEC
62439-3 Edition 1 and IEC 62439-3 Edition 2 parallel redundancy protocol (PRP) are available as options when ordering IEDs. Redundant station bus communication according to IEC 62439-3 uses both port AB and port CD on the OEM module.
Several protocols can be combined in the same IED.
IEC 61850-8-1 communication protocol
M14787-3 v13
The IEC 61850-8-1 communication is also possible from the electrical Ethernet front port. IEC 61850-8-1 protocol allows intelligent electrical devices (IEDs) from different vendors to exchange information and simplifies system engineering. IEDto-IED communication using GOOSE and client-server communication over MMS are supported. Disturbance recording file (COMTRADE) uploading can be done over MMS or FTP.
The front port shall not be used due to interference.
14. Hardware description
Hardware modules
IP14529-1 v1
Power supply module PSM
The power supply module is used to provide the correct
M11595-3 v5 internal voltages and full isolation between the IED and the battery system. An internal fail alarm output is available.
Binary input module BIM
M1769-3 v4
The binary input module has 16 optically isolated inputs and is available in two versions, one standard and one with enhanced pulse counting capabilities on the inputs to be used with the pulse counter function. The binary inputs are freely programmable and can be used for the input of logical signals to any of the functions. They can also be included in the disturbance recording and event-recording functions. This enables extensive monitoring and evaluation of operation of the IED and for all associated electrical circuits.
LON communication protocol
SEMOD120140-5 v2
Existing stations with ABB station bus LON can be extended with use of the optical LON interface. This allows full SA functionality including peer-to-peer messaging and cooperation between the IEDs.
SPA communication protocol
SEMOD120134-5 v1
A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation
Monitoring Systems SMS.
IEC 60870-5-103 communication protocol
Binary output module BOM
M6938-3 v4
The binary output module has 24 independent output relays and is used for trip output or any signaling purpose.
Binary input/output module IOM
M6939-3 v6
The binary input/output module is used when only a few input and output channels are needed. The ten standard output channels are used for trip output or any signaling purpose.
The two high speed signal output channels are used for applications where short operating time is essential. Eight optically isolated binary inputs cater for required binary input information.
ABB 19
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
M2152-3 v5
Optical ethernet module OEM
M16073-3 v6
The optical fast-ethernet module is used for fast and interference-free communication of synchrophasor data over
IEEE C37.118 and/or IEEE 1344 protocols. It is also used to connect an IED to the communication buses (like the station bus) that use the IEC 61850-8-1 protocol (port A, B). The module has one or two optical ports with ST connectors.
Galvanic RS485 serial communication module
SEMOD158664-5 v3
The Galvanic RS485 communication module (RS485) is used for DNP3.0 and IEC 60870-5-103 communication. The module has one RS485 communication port. The RS485 is a balanced serial communication that can be used either in 2wire or 4-wire connections. A 2-wire connection uses the same signal for RX and TX and is a multidrop communication with no dedicated Master or slave. This variant requires however a control of the output. The 4-wire connection has separated signals for RX and TX multidrop communication with a dedicated Master and the rest are slaves. No special control signal is needed in this case.
IEC04000448 V2 EN-US
Figure 3.
Case without rear cover
IRIG-B Time synchronizing module
SEMOD141113-4 v7
The IRIG-B time synchronizing module is used for accurate time synchronizing of the IED from a station clock.
Transformer input module TRM
M14875-3 v9
The transformer input module is used to galvanically separate and adapt the secondary currents and voltages generated by the measuring transformers. The module has twelve inputs in different combinations of currents and voltage inputs.
Alternative connectors of Ring lug or Compression type can be ordered.
High impedance resistor unit
M16727-3 v2
The high impedance resistor unit, with resistors for pick-up value setting and a voltage dependent resistor, is available in a single phase unit and a three phase unit. Both are mounted on a 1/1 19 inch apparatus plate with compression type terminals.
Layout and dimensions
Dimensions
IP14539-1 v1
IP14826-1 v1
IEC04000464 V2 EN-US
Figure 4.
Case without rear cover with 19” rack mounting kit
M15243-12 v8
Case size
(mm)/(inches)
A B C D E F
6U, 1/2 x 19” 265.9/
10.47
223.7/
8.81
242.1/
9.53
255.8/
10.07
205.7/
8.10
The H and K dimensions are defined by the 19” rack mounting kit.
190.5/
7.50
G
203.7/
8.02
-
H J
228.6/
9.00
-
K
Mounting alternatives
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
20
M16079-3 v13
– 1/2 case size (h) 254.3 mm/10.01” (w) 210.1 mm/
8.27”
• Wall mounting kit
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
See ordering for details about available mounting alternatives.
1MRK 505 358-BEN B
ABB 21
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
15. Connection diagrams
Connection diagrams
GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v4
The connection diagrams are delivered on the IED
Connectivity package DVD as part of the product delivery.
The latest versions of the connection diagrams can be downloaded from http://www.abb.com/substationautomation .
650 series ver. 2.1, IEC symbols 1MRK006501-AF
650 series ver. 2.1, ANSI symbols 1MRK006502-AF
Connection diagram, REQ650 2.1, B11 1MRK006505-QA
22 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
16. Technical data
General
M10993-1 v3 IP11376-1 v2
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its intended functions according to the specified requirements
IP15765-1 v2
Energizing quantities, rated values and limits
ABB 23
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Analog inputs
M16988-1 v10
Table 4. TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Current
Operative range
Permissive overload
Burden
AC voltage
Operative range
Permissive overload
Burden
Frequency
*) max. 350 A for 1 s when COMBITEST test switch is included.
SEMOD55310-2 v9
Table 5. OEM - Optical ethernet module
Rated value
I r
= 1 or 5 A
(0-100) x I r
4 × I r
cont.
100 × I r
for 1 s *)
< 150 mVA at I r
= 5 A
< 20 mVA at I r
= 1 A
U r
= 110 V
(0–340) V
420 V cont.
450 V 10 s
< 20 mVA at 110 V f r
= 50/60 Hz
Quantity
Number of channels
Standard
Type of fiber
Wave length
Optical connector
Communication speed
Rated value
1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118)
IEEE 802.3u 100BASE-FX
62.5/125 m m multimode fibre
1300 nm
Type ST
Fast Ethernet 100 Mbit/s
Table 6. PSM - Power supply module
Quantity
Auxiliary DC voltage, EL (input)
Power consumption
Auxiliary DC power in-rush
Binary inputs and outputs
M50609-2 v6
Rated value
EL = (24-60) V
EL = (90-250) V
32 W typically
< 10 A during 0.1 s
Nominal range
-
-
EL ± 20%
EL ± 20%
1MRK 505 358-BEN B
IP15842-1 v1
Nominal range
(0.2-40) × I r
0.5–288 V
±5%
IP15844-1 v1
24 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Table 7. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
Debounce filter
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V max. 0.05 W/input max. 0.1 W/input max. 0.2 W/input max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range.
-
-
Nominal range
-
-
RL ± 20%
RL ± 20%
RL ± 20%
RL ± 20%
M12441-1 v8
Table 8. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Test voltage across open contact, 1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
Making capacity at inductive load with L/R > 10 ms
0.2 s
1.0 s
Breaking capacity for AC, cos j > 0.4
Breaking capacity for DC with L/R < 40 ms
Trip and Signal relays
24
250 V AC, DC
1000 V rms
8 A
10 A
12 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
ABB 25
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Influencing factors
Table 9. Temperature and humidity influence
Parameter
Ambient temperature, operate value
Relative humidity
Operative range
Storage temperature -
Reference value
+20°C
10-90%
0-95%
M16705-1 v10
Nominal range
-20°C to +55°C
10-90% -
Influence
0.02%/°C
-40°C to +70°C -
Table 10. Auxiliary DC supply voltage influence on functionality during operation
Dependence on Reference value Within nominal range
15% of EL Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate value
Interrupted auxiliary DC voltage
Interruption interval
0–50 ms
0–∞ s
Restart time max. 2%
Full wave rectified
±20% of EL
24-60 V DC ± 20%
90-250 V DC ± 20%
Influence
0.01%/%
0.01%/%
No restart
Correct behaviour at power down
< 300 s
Table 11. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Frequency dependence for broken conductor
Within nominal range f f r r
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz f f r r
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
Harmonic frequency dependence (20% content) 2 nd , 3 rd and 5 th harmonic of f r
Harmonic frequency dependence for broken conductor (20% content) 2nd, 3rd and 5 th harmonic of f r
Influence
±1.0%/Hz
±2.0%/Hz
±1.0%
±2.0%
IP15846-1 v1
Type tests according to standards
M16706-1 v9 IP15778-1 v1
26 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 12. Electromagnetic compatibility
Test
1 MHz burst disturbance
100 kHz slow damped oscillatory wave immunity test
Ring wave immunity test, 100 kHz
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity test
Conducted common mode immunity test
Power frequency magnetic field test
Pulse magnetic field immunity test
Damped oscillatory magnetic field test
Radiated electromagnetic field disturbance
Radiated electromagnetic field disturbance
Conducted electromagnetic field disturbance
Radiated emission
Radiated emission
Conducted emission
Table 13. Insulation
Test
Dielectric test
Impulse voltage test
Insulation resistance
1MRK 505 358-BEN B
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
2-4 kV, 1.2/50 m s high energy
150-300 V, 50 Hz
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
1000 A/m
100 A/m
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m
80-1000 MHz
10 V, 0.15-80 MHz
30-5000 MHz
30-5000 MHz
0.15-30 MHz
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V
IEC 61000–4–9, Class V
IEC 61000-4-10, Class V
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEEE/ANSI C63.4, FCC
IEC 60255-26
Type test values
2.0 kV AC, 1 min.
5 kV, 1.2/50 m s, 0.5 J
> 100 M W at 500 VDC
Reference standard
IEC 60255-27
ANSI C37.90
ABB 27
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Table 14. Environmental tests
Test
Cold operation test
Cold storage test
Dry heat operation test
Dry heat storage test
Change of temperature test
Damp heat test, steady state
Damp heat test, cyclic
Table 15. CE compliance
Test
Immunity
Emissivity
Low voltage directive
Table 16. Mechanical tests
Test
Vibration response test
Vibration endurance test
Shock response test
Shock withstand test
Bump test
Seismic test
Type test value
Test Ad for 16 h at -25°C
Test Ab for 16 h at -40°C
Test Bd for 16 h at +70°C
Test Bb for 16 h at +85°C
Test Nb for 5 cycles at -25°C to +70°C
Test Ca for 10 days at +40°C and humidity 93%
Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle =
24 hours)
Reference standard
IEC 60068-2-1
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-2
IEC 60068-2-14
IEC 60068-2-78
IEC 60068-2-30
Type test values
Class II
Class I
Class I
Class I
Class I
Class II
According to
EN 60255–26
EN 60255–26
EN 60255–27
Reference standards
IEC 60255-21-1
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-3
28 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Current protection
Table 17. PHPIOC
Function
Operate current
Reset ratio
Operate time at 0 to 2 x I set
Reset time at 2 to 0 x I set
Critical impulse time
Operate time at 0 to 10 x I set
Reset time at 10 to 0 x I set
Critical impulse time
Dynamic overreach
M12336-1 v12
Range or value
(5-2500)(5–1200)% of lBase
> 95% at (50–2500)% of IBase
> 95% at (5–1200)% of IBase
Min. = 15 ms40 ms
Max. = 25 ms50 ms
Min. = 15 ms45 ms
Max. = 25 ms65 ms
10 ms35 ms typically at 0 to 2 x I set
Min. = 5 ms10 ms
Max. = 15 ms20 ms
Min. = 25 ms80 ms
Max. = 40 ms100 ms
2 ms typically at 0 to 10 x I set
7 ms typically at 0 to 10 x I set
< 5% at t = 100 ms
1MRK 505 358-BEN B
-
-
-
-
-
-
-
Accuracy
-
± 1.0% of I r
at I ≤ I r
± 1.0% of I at I > I r
ABB 29
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 18. Four-step phase overcurrent protection OC4PTOC
Function
Operate current, step 1-4
Setting range
(5-2500)% of lBase
M12342-1 v18
Reset ratio > 95% at (50–2500)% of lBase
Minimum operate current, step 1-4 (1-10000)% of lBase
Relay characteristic angle (RCA)
Relay operating angle (ROA)
Second harmonic blocking
Independent time delay at 0 to 2 x
I set
, step 1-4
Minimum operate time for inverse curves , step 1-4
Inverse time characteristics, see table
Operate time, start non-directional at 0 to 2 x I set
(40.0–65.0) degrees
(40.0–89.0) degrees
(5–100)% of fundamental
(0.000-60.000) s
(0.000-60.000) s
16 curve types
Reset time, start non-directional at
2 to 0 x I set
Operate time, start non-directional at 0 to 10 x I set
Reset time, start non-directional at
10 to 0 x I set
Critical impulse time
Impulse margin time
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
10 ms typically at 0 to 2 x I set
15 ms typically
M12340-2 v8
Table 19. Instantaneous residual overcurrent protection EFPIOC
Function
Operate current
Range or value
(5-2500)% of lBase
Reset ratio
Operate time at 0 to 2 x I
Reset time at 2 to 0 x I
Critical impulse time set set
Operate time at 0 to 10 x I
Reset time at 10 to 0 x I
Critical impulse time
Dynamic overreach
30 set set
> 95% at (50–2500)% of lBase
Min. = 15 ms
Max. = 25 ms
Min. = 15 ms
Max. = 25 ms
10 ms typically at 0 to 2 x I set
Min. = 5 ms
Max. = 15 ms
Min. = 25 ms
Max. = 35 ms
2 ms typically at 0 to 10 x I set
< 5% at t = 100 ms
1MRK 505 358-BEN B
-
-
-
-
-
-
Accuracy
-
-
±1.0% of I r
at I ≤ I r
±1.0% of I at I > I r
-
-
-
-
Accuracy
-
± 1.0% of I r
at I ≤ I r
± 1.0% of I at I > I r
± 1.0% of I r
at I ≤ I r
± 1.0% of I at I > I r
-
± 2.0 degrees
± 2.0% of I r
± 0.2% or ± 35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
-
See table
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
M15223-1 v16
Table 20. Four step residual overcurrent protection EF4PTOC technical data
Function
Operate current, step 1-4
Range or value
(1-2500)% of IBase
Reset ratio
Relay characteristic angle
(RCA)
Operate current for directional release
> 95% at (10-2500)% of IBase
(-180 to 180) degrees
(1–100)% of IBase
Independent time delay at 0 to 2 x I set
, step 1-4
Minimum operate time for inverse curves, step 1-4
Inverse time characteristics, see
and Table
Second harmonic blocking
Minimum polarizing voltage
Minimum polarizing current
Real part of source Z used for current polarization
Imaginary part of source Z used for current polarization
Operate time, start nondirectional at 0 to 2 x I set
Reset time, start non-directional at 2 to 0 x I set
Operate time, start nondirectional at 0 to 10 x I set
Reset time, start non-directional at 10 to 0 x I set
Critical impulse time
Impulse margin time
(0.000-60.000) s
(0.000 - 60.000) s
16 curve types
(5–100)% of fundamental
(1–100)% of UBase
(2-100)% of IBase
(0.50-1000.00) W /phase
(0.50–3000.00) W /phase
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
10 ms typically at 0 to 2 x I set
15 ms typically
1MRK 505 358-BEN B
-
-
-
-
-
-
-
Accuracy
±1.0% of I r
at I ≤ I r
±1.0% of I at I > I r
-
±2.0 degrees
For RCA ±60 degrees:
±2.5% of I r
at I ≤ I
±2.5% of I at I > I r r
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
and
±2.0% of I r
-
±0.5% of U r
±1.0% of I r
ABB 31
Breaker protection REQ650 2.1 IEC
Product version: 2.1
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v5
Table 21. Four step negative sequence overcurrent protection NS4PTOC
Function
Operate current, step 1 - 4
Range or value
(1-2500)% of lBase
Reset ratio
Independent time delay at 0 to
2 x I set
, step 1 - 4
Minimum operate time for inverse curves, step 1 - 4
Inverse time characteristics, see table
table
Minimum operate current, step
1 - 4
Relay characteristic angle
(RCA)
Operate current for directional release
> 95% at (10-2500)% of IBase
(0.000-60.000) s
(0.000 - 60.000) s
16 curve types
(1.00 - 10000.00)% of IBase
(-180 to 180) degrees
(1–100)% of IBase
Minimum polarizing voltage
Minimum polarizing current
Real part of negative sequence source impedance used for current polarization
Imaginary part of negative sequence source impedance used for current polarization
Operate time, start nondirectional at 0 to 2 x I set
Reset time, start nondirectional at 2 to 0 x I set
Operate time, start nondirectional at 0 to 10 x I set
Reset time, start nondirectional at 10 to 0 x I set
Critical impulse time
Impulse margin time
Transient overreach
(1–100)% of UBase
(2-100)% of IBase
(0.50-1000.00) W /phase
(0.50–3000.00) W /phase
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
10 ms typically at 0 to 2 x I
15 ms typically
<10% at τ = 100 ms set
1MRK 505 358-BEN B
-
-
-
-
-
-
-
-
Accuracy
-
±1.0% of I r
at I £ I
±1.0% of I at I > I r r
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
and table
±1.0% of I r at I ≤ I
±1.0% of I at I > I r r
± 2.0 degrees
For RCA ±60 degrees:
±2.5% of I r
at I ≤ I
±2.5% of I at I > I r r
±0.5% of U r
-
±1.0% of I r
32 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
M12352-1 v13
Table 22. Thermal overload protection, one time constant LCPTTR/LFPTTR
Function
Reference current
Reference temperature
Operate time:
Range or value
(2-400)% of IBase
(0-300)°C, (0 - 600)°F
Time constant t = (1–1000) minutes t = t ln
ê
ê
é
ê
ê
I 2 I 2 p
-
I 2 I 2 p
T
Trip
T
Amb
T ref
× I 2 ref
ú
ú
ù
ú
EQUATION13000039 V2 EN-US
(Equation 1)
T
Trip
T
Amb
= set operate temperature
= ambient temperature
T ref
= temperature rise above ambient at I ref
I ref
= reference load current
I
I = actual measured current p
= load current before overload occurs
Alarm temperature
Operate temperature
Reset level temperature
(0-200)°C, (0-400)°F
(0-300)°C, (0-600)°F
(0-300)°C, (0-600)°F
M12353-1 v12
Table 23. Breaker failure protection CCRBRF
Function
Operate phase current
Range or value
(5-200)% of lBase
Accuracy
±1.0% of I r
± 1.0°C, ±2.0°F
IEC 60255-149, ±5.0% or ±200 ms whichever is greater
±2.0°C, ±4.0°F
±2.0°C, ±4.0°F
±2.0°C, ±4.0°F
Reset ratio, phase current
Operate residual current
Reset ratio, residual current
Phase current level for blocking of contact function
Reset ratio
Operate time for current detection
Reset time for current detection
Time delay for re-trip at 0 to 2 x I set
Time delay for back-up trip at 0 to 2 x I set
Time delay for back-up trip at multi-phase start at 0 to 2 x I set
Additional time delay for a second back-up trip at 0 to 2 x I set
Time delay for alarm for faulty circuit breaker
> 95%
(2-200)% of lBase
> 95%
(5-200)% of lBase
> 95%
10 ms typically
15 ms maximum
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
Accuracy
±1.0% of I r
at I £ I r
±1.0% of I at I > I r
-
±1.0% of I r
at I £ I r
±1.0% of I at I > I r
-
-
-
±1.0% of I r
at I £ I
±1.0% of I at I > I r r
-
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±20 ms whichever is greater
±0.2% or ±20 ms whichever is greater
±0.2% or ±15 ms whichever is greater
ABB 33
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
M12350-1 v11
Table 24. Stub protection STBPTOC
Function
Operating current
Reset ratio
Independent time delay at 0 to 2 x I
Operate time, start at 0 to 2 x I
Reset time, start at 2 to 0 x I
Critical impulse time
Impulse margin time set set set
Range or value
(5-2500)% of
Table 25. Broken conductor check BRCPTOC
Function
Minimum phase current for operation
Unbalance current operation
Independent operate time delay
Independent reset time delay
Start time at current change from I r
to 0
Reset time at current change from 0 to I r
Range or value
(5–100)% of IBase
(50–90)% of maximum current
(0.000-60.000) s
(0.010-60.000) s
Min. = 25 ms
Max. = 35 ms
Min. = 5 ms
Max. = 20 ms
-
-
IBase
> 95% at (50-2500)% of
(0.000-60.000) s
Accuracy
±1.0% of I
±1.0% of I r r
IBase
Min. = 10 ms
Max. = 20 ms
Min. = 10 ms
Max. = 20 ms
10 ms typically at 0 to 2 x I set
15 ms typically
SEMOD175200-2 v7
-
-
-
Accuracy
-
± 1.0% of I r
at I ≤ I r
± 1.0% of I at I > I r
-
± 0.2% or ± 30 ms whichever is greater
±0.2% or ±45 ms whichever is greater
±0.2% or ±30 ms whichever is greater
34 ABB
1MRK 505 358-BEN B
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Voltage protection
Table 26. Two step undervoltage protection UV2PTUV
Function
Operate voltage, low and high step
Absolute hysteresis
Internal blocking level, step 1 and step 2
Inverse time characteristics for step 1 and step 2, see table
Definite time delay, step 1 at 1.2 to 0 x U set
M13290-1 v14
Range or value
(1.0–100.0)% of UBase
(0.0–50.0)% of UBase
(1–50)% of UBase
-
(0.00-6000.00) s
(0.000-60.000) s Definite time delay, step 2 at 1.2 to 0 x U set
Minimum operate time, inverse characteristics (0.000–60.000) s
Operate time, start at 2 to 0 x U set
Reset time, start at 0 to 2 x U set
Operate time, start at 1.2 to 0 x U set
Reset time, start at 0 to 1.2 x U set
Critical impulse time
Impulse margin time
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
Max. = 25 ms
Min. = 15 ms
Max. = 35 ms
5 ms typically at 1.2 to 0 x U set
15 ms typically -
-
-
-
-
Accuracy
±0.5% of U r
±0.5% of U r
±0.5% of U r
±0.2% or ±40ms whichever is greater
±0.2% or ±40ms whichever is greater
-
±0.5% or ±40ms whichever is greater
ABB 35
1MRK 505 358-BEN B
Breaker protection REQ650 2.1 IEC
Product version: 2.1
M13304-1 v13
Table 27. Two step overvoltage protection OV2PTOV
Function
Operate voltage, step 1 and 2
Absolute hysteresis
Range or value
(1.0-200.0)% of UBase
(0.0–50.0)% of UBase
Inverse time characteristics for steps 1 and 2, see table
Definite time delay, low step (step 1) at 0 to 1.2 x U
Minimum operate time, Inverse characteristics
Operate time, start at 0 to 2 x U
Reset time, start at 2 to 0 x U
Operate time, start at 0 to 1.2 x U
Reset time, start at 1.2 to 0 x U
Critical impulse time
Impulse margin time set set set set set
Definite time delay, high step (step 2) at 0 to 1.2 x U set
"" -
(0.00 - 6000.00) s
(0.000-60.000) s
(0.000-60.000) s
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 20 ms
Max. = 35 ms
Min. = 5 ms
Max. = 25 ms
10 ms typically at 0 to 2 x U set
15 ms typically
M13317-2 v13
Table 28. Two step residual overvoltage protection ROV2PTOV
Function
Operate voltage, step 1 - step 2
Range or value
(1.0-200.0)% of UBase
Absolute hysteresis (0.0–50.0)% of UBase
Inverse time characteristics for low and high step, see table "" -
Definite time delay low step (step 1) at 0 to 1.2 x U set
(0.00–6000.00) s
(0.000–60.000) s Definite time delay high step (step 2) at 0 to 1.2 x U set
Minimum operate time (0.000-60.000) s
Operate time, start at 0 to 2 x U
Reset time, start at 2 to 0 x U
Critical impulse time
Impulse margin time set set
Operate time, start at 0 to 1.2 x U
Reset time, start at 1.2 to 0 x U set set
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 20 ms
Max. = 35 ms
Min. = 5 ms
Max. = 25 ms
10 ms typically at 0 to 2 x U set
15 ms typically
36
-
-
-
-
-
Accuracy
±0.5% of U r
at U ≤ U r
±0.5% of U at U > U r
±0.5% of U r
at U ≤ U r
±0.5% of U at U > U r
See table ""
±0.2% or ±45 ms whichever is greater
±0.2% or ±45 ms whichever is greater
-
±0.2% or ±45 ms whichever is greater
-
-
-
-
-
Accuracy
± 0.5% of U r
at U ≤ U r
± 0.5% of U at U > U r
± 0.5% of U r
at U ≤ U r
± 0.5% of U at U > U r
See table ""
± 0.2% or ± 45 ms whichever is greater
± 0.2% or ± 45 ms whichever is greater
-
± 0.2% or ± 45 ms whichever is greater
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Table 29. Two step residual overvoltage protection ROV2PTOV
Function
Operate voltage, step 1 - step 2
Range or value
(1.0-200.0)% of UBase
Definite time delay low step (step 1) at 0 to 1.2 x U set
Definite time delay high step (step 2) at 0 to 1.2 x U set
Operate time, start at 0 to 1.2 x U set
Reset time, start at 1.2 to 0 x U set
Critical impulse time
Impulse margin time
Table 30. Loss of voltage check LOVPTUV
Function
Operate voltage
Pulse timer when disconnecting all three phases
Time delay for enabling the functions after restoration
Operate time delay when disconnecting all three phases
Time delay to block when all three phase voltages are not low
Range or value
(1–100)% of UBase
(0.050–60.000) s
(0.000–60.000) s
(0.000–60.000) s
(0.000–60.000) s
(0.000–60.000) s
(0.000–60.000) s
Min. = 50 ms
Max. = 60 ms
Min. = 10 ms
Max. = 30 ms
45 ms typically at 0 to 1.2 x U set
10 ms typically
SEMOD175210-2 v6
Accuracy
±0.5% of U r
±0.2% or ±15 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
-
-
-
Accuracy
± 0.5% of U r
at U ≤ U r
± 0.5% of U at U > U r
Maximum up to 130v secondary at
16.7Hz
± 0.2% or ± 65 ms whichever is greater
-
± 0.2% or ± 65 ms whichever is greater
ABB 37
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Multipurpose protection
M13095-2 v7
1MRK 505 358-BEN B
38 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Table 31. General current and voltage protection CVGAPC
Function
Measuring current input
Measuring voltage input
Start overcurrent, step 1 - 2
Start undercurrent, step 1 - 2
Independent time delay, overcurrent at 0 to 2 x I
Overcurrent (non-directional):
Start time at 0 to 2 x I
Reset time at 2 to 0 x I
Start time at 0 to 10 x I
Reset time at 10 to 0 x I
Undercurrent:
Start time at 2 to 0 x I
Overcurrent: set set
Reset time at 0 to 2 x I
Overcurrent: set set set set
Inverse time characteristics, see table
Voltage level where voltage memory takes over
Start overvoltage, step 1 - 2
Start undervoltage, step 1 - 2 set
Independent time delay, undercurrent at 2 to 0 x I
, step 1 - 2 set
Minimum operate time for inverse curves, step 1 - 2
, step 1 - 2
Independent time delay, overvoltage at 0.8 to 1.2 x U set
, step 1 -
2
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
16 curve types
Range or value phase1, phase2, phase3, PosSeq, -
NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph phase1, phase2, phase3, PosSeq, -
NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph
(2 - 5000)% of IBase
-
-
Accuracy
(2 - 150)% of IBase
(0.00 - 6000.00) s
(0.00 - 6000.00) s
±1.0% of I r
at I ≤ I
±1.0% of I at I > I r r
±1.0% of I r
at I ≤ I
±1.0% of I at I > I r r
±0.2% or ±35 ms whichever is greater
-
±0.2% or ±35 ms whichever is greater
(0.00 - 6000.00) s
(0.0 - 5.0)% of UBase
(2.0 - 200.0)% of UBase
(2.0 - 150.0)% of UBase
(0.00 - 6000.00) s
-
-
-
-
-
See table
and table
±0.2% or ±35 ms whichever is greater
±0.5% of U r
±0.5% of U r
at U ≤ U
±0.5% of U at U > U r r
±0.5% of U r
at U ≤ U
±0.5% of U at U > U r r
±0.2% or ±35 ms whichever is greater
ABB 39
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Directional function
Relay characteristic angle
Relay operate angle
Reset ratio, overcurrent
Reset ratio, undercurrent
Reset ratio, overvoltage
Reset ratio, undervoltage
Overcurrent:
Critical impulse time
Impulse margin time
Undercurrent:
Critical impulse time
Impulse margin time
Overvoltage:
Critical impulse time
Impulse margin time
Undervoltage:
Critical impulse time
Impulse margin time
Table 31. General current and voltage protection CVGAPC , continued
Function Range or value
(0.00 - 6000.00) s Independent time delay, undervoltage at 1.2 to 0.8 x U set
, step 1
- 2
Overvoltage:
Start time at 0.8 to 1.2 x U set
Reset time at 1.2 to 0.8 x U
Undervoltage:
Start time at 1.2 to 0.8 x U
Reset time at 1.2 to 0.8 x U
Overvoltage: set set set
Inverse time characteristics, see table
Undervoltage:
Inverse time characteristics, see table
2
""
High and low voltage limit, voltage dependent operation, step 1 -
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
4 curve types
3 curve types
(1.0 - 200.0)% of UBase
Settable: NonDir, forward and reverse
(-180 to +180) degrees
(1 to 90) degrees
> 95%
< 105%
> 95%
< 105%
10 ms typically at 0 to 2 x I set
15 ms typically
10 ms typically at 2 to 0 x I set
15 ms typically
10 ms typically at 0.8 to 1.2 x U set
15 ms typically
10 ms typically at 1.2 to 0.8 x U set
15 ms typically
-
-
Accuracy
±0.2% or ±35 ms whichever is greater
-
-
-
-
-
-
-
-
-
-
-
-
-
See table ""
±1.0% of U r
at U ≤ U
±1.0% of U at U > U r r
-
±2.0 degrees
-
±2.0 degrees
40 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
SEMOD175176-2 v5
Table 32. Rotor earth fault protection
Function
For machines with:
• rated field voltage up to
• static exciter with rated supply voltage up to
Supply voltage 120 or 230 V
Operate earth fault resistance value
Influence of harmonics in the DC field voltage
Permitted leakage capacitance
Permitted shaft earthing resistance
Protective resistor
Range or value
350 V DC
700 V 50/60 Hz
50/60 Hz
Approx. 1–20 kΩ
Negligible influence of 50 V, 150
Hz or 50 V, 300 Hz
(1–5) μF
Maximum 200 Ω
220 Ω, 100 W, plate
(the height is 160 mm (6,2 inches) and width 135 mm (5,31 inches))
1MRK 505 358-BEN B
ABB 41
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Secondary system supervision
Table 33. Current circuit supervision CCSSPVC
Function
Operate current
Range or value
(10-200)% of IBase
Reset ratio, Operate current
Block current
Reset ratio, Block current
>90%
(20-500)% of IBase
>90% at (50-500)% of IBase
M12358-1 v8
Accuracy
±10.0% of I r
at I ≤ I r
±10.0% of I at I > I r
±5.0% of I r
at I ≤ I r
±5.0% of I at I > I r
Table 34. Current circuit supervision CCSSPVC
Function
Operate current
Block current
Range or value
(10-200.00)% of lBase
(20-500.00)% of lBase
M16069-1 v11
Table 35. Fuse failure supervision FUFSPVC
Function
Operate voltage, zero sequence
Operate current, zero sequence
Operate voltage, negative sequence
Operate current, negative sequence
Operate voltage change level
Operate current change level
Operate phase voltage
Operate phase current
Operate phase dead line voltage
Operate phase dead line current
Operate time, start, 1 ph, at 1 to 0 x U r
Reset time, start, 1 ph, at 0 to 1 x U r
Range or value
(1-100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1–100)% of IBase
Min. = 10 ms
Max. = 25 ms
Min. = 15 ms
Max. = 30 ms
Accuracy
±10.0% of I r
at I ≤ I r
±10.0% of I at I > I r
±5.0% of I r
at I ≤ I r
±5.0% of I at I > I r
-
Accuracy
±0.5% of U r
±0.5% of I r
±0.5% of U r
±0.5% of I r
±10.0% of U r
-
±10.0% of I r
±0.5% of U r
±0.5% of I r
±0.5% of U r
1MRK 505 358-BEN B
42 ABB
1MRK 505 358-BEN B
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Control
M12359-1 v13
Table 36. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Phase shift, j line
j bus
Voltage high limit for synchronizing and synchrocheck
Range or value
(-180 to 180) degrees
(50.0-120.0)% of UBase
Reset ratio, synchrocheck
Frequency difference limit between bus and line for synchrocheck
Phase angle difference limit between bus and line for synchrocheck
Voltage difference limit between bus and line for synchronizing and synchrocheck
Time delay output for synchrocheck when angle difference between bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees
Frequency difference minimum limit for synchronizing
Frequency difference maximum limit for synchronizing
Breaker closing pulse duration
> 95%
(0.003-1.000) Hz
(5.0-90.0) degrees
(0.02-0.5) p.u
(0.000-60.000) s
(0.003-0.250) Hz
(0.050-0.500) Hz
(0.050-60.000) s
(0.000-6000.00) s tMaxSynch, which resets synchronizing function if no close has been made before set time
Minimum time to accept synchronizing conditions
Voltage high limit for energizing check
(0.000-60.000) s
(50.0-120.0)% of UBase
Reset ratio, voltage high limit
Voltage low limit for energizing check
Reset ratio, voltage low limit
Maximum voltage for energizing
> 95%
(10.0-80.0)% of UBase
< 105%
(50.0-180.0)% of UBase
Time delay for energizing check when voltage jumps from 0 to 90% of
Urated
Operate time for synchrocheck function when angle difference between bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees
Operate time for energizing function when voltage jumps from 0 to 90% of Urated
(0.000-60.000) s
Min. = 15 ms
Max. = 30 ms
Min. = 70 ms
Max. = 90 ms
-
Accuracy
±0.5% of U r
at U ≤ U r
±0.5% of U at U > U r
-
±2.5 mHz
±2.0 degrees
±0.5% of U r
±0.2% or ±35 ms whichever is greater
±2.5 mHz
±2.5 mHz
±0.2% or ±15 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.5% of U r
at U ≤ U r
±0.5% of U at U > U r
-
-
±0.5% of U r
±0.5% of U r
at U ≤ U
±0.5% of U at U > U r r
±0.2% or ±100 ms whichever is greater
–
–
ABB 43
1MRK 505 358-BEN B
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 37. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Phase shift, j line
j bus
Voltage high limit for synchronizing and synchrocheck
Range or value
(-180 to 180) degrees
(10.0-120.0)% of Ubase
Frequency difference limit between bus and line for synchrocheck
Phase angle difference limit between bus and line for synchrocheck
Voltage difference limit between bus and line for synchronizing and synchrocheck
Time delay output for synchrocheck when angle difference between bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees
Frequency difference minimum limit for synchronizing
Frequency difference maximum limit for synchronizing
Maximum allowed frequency rate of change
(0.003-1.000) Hz
(5.0-90.0) degrees
(0.02-0.50) p.u
(0.000-60.000) s
(0.003-1.000) Hz
(0.050-1.000) Hz
(0.000-0.500) Hz/s
Breaker closing pulse duration tMaxSynch, which resets synchronizing function if no close has been made before set time
Minimum time to accept synchronizing conditions
Voltage high limit for energizing check
(0.050-2.000) s
(0.000-6000.000) s
(0.000-60.000) s
(10.0-120.0)% of Ubase
Voltage low limit for energizing check
Maximum voltage for energizing
(10.0-80.0)% of Ubase
(50.0-180.0)% of Ubase
Time delay for energizing check when voltage jumps from 0 to 90% of
Urated
Operate time for synchrocheck function when angle difference between bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees
Operate time for energizing function when voltage jumps from 0 to 90% of Urated
(0.000-60.000) s
Min. = 35 ms
Max. = 65 ms
Min. = 100 ms
Max. = 125 ms
-
Accuracy
±0.5% of U r
at U ≤ U
±0.5% of U at U > U r r
±5 mHz
±2.0 degrees
±0.5% of U r
±0.2% or ±70 ms whichever is greater
±5 mHz
±5 mHz
±5% or ±10.0 mHz/s whichever is greater
±0.2% or ±10 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±60 ms whichever is greater
±0.5% of U r
at U ≤ U r
±0.5% of U at U > U r
±0.5% of U r
±0.5% of U r
at U ≤ U
±0.5% of U at U > U r r
±0.2% or ±125 ms whichever is greater
–
–
44 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
M12379-1 v12
Table 38. Autorecloser SMBRREC
Function
Number of autoreclosing shots
Autoreclosing open time: shot 1 - t1 1Ph shot 1 - t1 2Ph shot 1 - t1 3PhHS shot 1 - t1 3Ph shot 2 - t2 3Ph shot 3 - t3 3Ph shot 4 - t4 3Ph shot 5 - t5 3Ph
Extended autorecloser open time
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle
Maximum operate pulse duration
Reclaim time
Circuit breaker closing pulse length
Wait for master release
Inhibit reset time
Autorecloser maximum wait time for sync
CB check time before unsuccessful
Wait time after close command before proceeding to next shot
Range or value
1-5
(0.000-120.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
1MRK 505 358-BEN B
Accuracy
-
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±45 ms whichever is greater
±0.2% or ±45 ms whichever is greater
±0.2% or ±45 ms whichever is greater
±0.2% or ±45 ms whichever is greater
ABB 45
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 39. Autorecloser SMBRREC
Function
Number of autoreclosing shots
Autoreclosing open time: shot1 - t1_HS, high speed reclosing without synchrocheck shot1 - t1, delayed reclosing shot 2 - t2 shot 3 - t3 shot 4 - t4 shot 5 - t5
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle
Maximum operate pulse duration
Reclaim time
Circuit breaker closing pulse length
Inhibit reset time
Autorecloser maximum wait time for sync
CB check time before unsuccessful
Range or value
1-5
(0.000-20.000) s
(0.000-200.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-600.00) s
(0.00-6000.00) s
1MRK 505 358-BEN B
Accuracy
-
±0.2% or ±20 ms whichever is greater
±0.2% or ±20 ms whichever is greater
±0.2% or ±20 ms whichever is greater
±0.2% or ±20 ms whichever is greater
±0.2% or ±10 ms whichever is greater
±0.2% or ±10 ms whichever is greater
±0.2% or ±10 ms whichever is greater
±0.2% or ±20 ms whichever is greater
±0.2% or ±25 ms whichever is greater
±0.2% or ±25 ms whichever is greater
46 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Logic
Table 40. Tripping logic common 3-phase output SMPPTRC
Function
Trip action
Minimum trip pulse length
3-pole trip delay
Evolving fault delay
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
M12380-1 v10
-
Accuracy
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
Table 41. Number of SMPPTRC instances
Function
SMPPTRC
Quantity with cycle time
3 ms
6
Table 42. Tripping logic SMPPTRC
Function
Trip action
Minimum trip pulse length
Range or value
2 phase
(0.000-60.000) s
Accuracy
–
±0.2% or ±30 ms whichever is greater
Table 43. Number of SMPPTRC instances
Function
SMPPTRC
3 ms
6
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
Table 44. Number of TMAGAPC instances
Function
TMAGAPC
3 ms
6
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
Table 45. Number of ALMCALH instances
Function
ALMCALH -
3 ms
Quantity with cycle time
-
8 ms
Quantity with cycle time
Quantity with cycle time
8 ms
6
-
100 ms
-
100 ms
100 ms
5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
Table 46. Number of WRNCALH instances
Function
WRNCALH -
3 ms
Quantity with cycle time
-
8 ms 100 ms
5
1MRK 505 358-BEN B
ABB 47
Breaker protection REQ650 2.1 IEC
Product version: 2.1
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
Table 47. Number of INDCALH instances
Function
INDCALH -
3 ms
Quantity with cycle time
8 ms
5
Table 51. Number of LLD instances
Logic block
LLD
3 ms
10
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v1
Table 48. Number of AND instances
Logic block
AND
3 ms
60
Table 50. Number of INV instances
Logic block
INV
3 ms
90
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v1
Table 49. Number of GATE instances
Logic block
GATE
3 ms
10
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v1
Quantity with cycle time
8 ms
10
Quantity with cycle time
8 ms
90
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v1
Quantity with cycle time
8 ms
60
Quantity with cycle time
8 ms
10
Table 52. Number of PULSETIMER instances
Logic block
PULSETIMER
3 ms
10
Quantity with cycle time
8 ms
10
100 ms
20
GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v1
Table 53. Number of RSMEMORY instances
Range or Value
(0.000–90000.000) s
Logic block
RSMEMORY
3 ms
10
Table 54. Number of SRMEMORY instances
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v1
Quantity with cycle time
8 ms
10
Logic block
SRMEMORY
3 ms
10
Quantity with cycle time
8 ms
10
48
100 ms
20
100 ms
20
-
100 ms
100 ms
160
100 ms
20
100 ms
240
100 ms
20
1MRK 505 358-BEN B
Accuracy
±0.5% ±10 ms
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
GUID-C6C98FE0-F559-45EE-B853-464516775417 v1
Table 55. Number of TIMERSET instances
Logic block
TIMERSET
3 ms
15
Quantity with cycle time
8 ms
15
100 ms
30
GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1
Table 56. Number of XOR instances
Range or Value
(0.000–90000.000) s
Logic block
XOR
3 ms
10
Quantity with cycle time
8 ms
10
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v1
Table 57. Number of B16I instances
Function
B16I
3 ms
6
Quantity with cycle time
8 ms
4
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v1
Table 58. Number of BTIGAPC instances
Function
BTIGAPC
3 ms
4
Quantity with cycle time
8 ms
4
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v1
Table 59. Number of IB16 instances
Function
IB16
3 ms
6
Quantity with cycle time
8 ms
4
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v1
Table 60. Number of ITBGAPC instances
Function
ITBGAPC
3 ms
4
Quantity with cycle time
8 ms
4
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Table 61. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
Function
Elapsed time integration 3
Cycle time (ms) Range or value
0 ~ 999999.9 s
8
100
0 ~ 999999.9 s
0 ~ 999999.9 s
100 ms
20
100 ms
8
100 ms
8
100 ms
8
100 ms
8
1MRK 505 358-BEN B
Accuracy
±0.5% ±10 ms
Accuracy
±0.2% or ±20 ms whichever is greater
±0.2% or ±100 ms whichever is greater
±0.2% or ±250 ms whichever is greater
ABB 49
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Table 62. Number of TEIGAPC instances
Function
TEIGAPC
3 ms
4
Quantity with cycle time
8 ms
4
Table 63. Running hour-meter TEILGAPC
Function
Time limit for alarm supervision, tAlarm
Time limit for warning supervision, tWarning
Time limit for overflow supervision
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
Range or value
(0 - 99999.9) hours
(0 - 99999.9) hours
Fixed to 99999.9 hours
±0.1% of set value
±0.1% of set value
±0.1%
100 ms
4
Accuracy
50 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Monitoring
Table 64. Measurements CVMMXN
Function
Frequency
Current
Range or value
(0.95-1.05) x f r
(0.1-4.0) x I r
Active power, P (10 to 300) V
(0.1-4.0) x I r
(100 to 220) V
(0.5-2.0) x I r cos φ < 0.7
M12386-1 v14
Accuracy
± 2.0 mHz
± 0.8% of I at 0.1 x I r
< I < 0.2 x I r
± 0.5% of I at 0.2 x I r
< I < 0.5 x I r
± 0.2% of I at 0.5 x I r
< I < 4.0 x I r
± 0.5% of S r
at S ≤ 0.5 x S r
± 0.5% of S at S > 0.5 x S r
± 0.2% of P
Table 65. Measurements CVMMXN
Function
Frequency
Active power, P
Reactive power, Q
Apparent power, S
Power factor, cos ( φ )
Range or value
(0.90-1.10) x f r
Accuracy
± 3.0 mHz
0.1 x U r
≤ U ≤ 1.2 x U r
0.2 x I r
≤ I ≤ 1.2 x I r
Where U r
= 100 V
± 2.5% of S
GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v5
± 0.04
r
where S r
= VT prim
x CT prim
Table 66. Phase current measurement CMMXU
Function
Current at symmetrical load
Phase angle at symmetrical load
Range or value
(0.1-4.0) × I r
(0.1-4.0) × I r
Accuracy
±0.3% of I r
at I ≤ 0.5 × I r
±0.3% of I at I > 0.5 × I r
±1.0 degrees at 0.1 × I r
< I ≤ 0.5 × I r
±0.5 degrees at 0.5 × I r
< I ≤ 4.0 × I r
Table 67. Phase current measurement CMMXU
Function
Current magnitude
Phase angle
Range or value
(0.2 - 2.0) × I
(0.2 - 2.0) × I r r
GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v4
Accuracy
±1.0% of I r
at I ≤ I r
±1.0% of I at I > I r
±2.0 degrees at 0.2 × I r
≤ I < 1.0 × I r
±1.5 degrees at 1.0 × I r
≤ I ≤ 2.0 × I r
Table 68. Phase-phase voltage measurement VMMXU
Function
Voltage
Phase angle
Range or value
(10 to 300) V
(10 to 300) V
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
1MRK 505 358-BEN B
ABB 51
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 69. Phase-phase voltage measurement VMMXU
Function
Voltage magnitude
Phase angle
Range or value
(10 to 130) V
(10 to 130) V
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v5
Table 70. Phase-neutral voltage measurement VNMMXU
Accuracy
±0.5% of U
±1.0 degrees at 10 V ≤ U ≤ 110 V
±2.0 degrees at 110 V < U ≤ 130 V
Function
Voltage
Phase angle
Range or value
(5 to 175) V
(5 to 175) V
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
Table 71. Phase-neutral voltage measurement VNMMXU
Function
Voltage magnitude
Phase angle
Range or value
(10 to 130) V
(10 to 130) V
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v4
Table 72. Current sequence component measurement CMSQI
Accuracy
±0.5% of U
±1.0 degrees at 10 V ≤ U ≤ 110 V
±2.0 degrees at 110 V < U ≤ 130 V
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Range or value
(0.1–4.0) × I r
(0.1–1.0) × I
(0.1–1.0) × I
(0.1–4.0) × I r r r
Accuracy
± 0.3% of I r
at I ≤ 0.5 × I r
± 0.3% of I at I > 0.5 × I r
± 0.3% of I r
at I ≤ 0.5 × I r
± 0.3% of I at I > 0.5 × I r
± 0.3% of I r
at I ≤ 0.5 × I r
± 0.3% of I at I > 0.5 × I r
± 1.0 degrees at 0.1 × I r
< I ≤ 0.5 × I r
± 0.5 degrees at 0.5 × I r
< I ≤ 4.0 × I r
Table 73. Positive and zero sequence current measurement CMSQI
Function
Current magnitude
Range or value
(0.2 - 2.0) × I r
Phase angle (0.2 - 2.0) × I r
Accuracy
±1.0% of I r
at I ≤ I r
±1.0% of I at I > I r
±2.0 degrees at 0.2 × I r
≤ I < 1.0 × I r
±1.5 degrees at 1.0 × I r
≤ I ≤ 2.0 × I r
1MRK 505 358-BEN B
52 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v5
Table 74. Voltage sequence measurement VMSQI
Function
Voltage positive sequence, U1
Range or value
(10 to 300) V
Voltage zero sequence, 3U0
Voltage negative sequence, U2
Phase angle
(10 to 300) V
(10 to 300) V
(10 to 300) V
Accuracy
± 0.5% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
± 0.5% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
± 0.5% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
± 0.5 degrees at U ≤ 50 V
± 0.2 degrees at U > 50 V
Table 75. Positive and zero sequence voltage measurement VMSQI
Function
Voltage magnitude
Phase angle
Range or value
(10 to 130) V
(10 to 130) V
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
Accuracy
±0.5% of U
±1.0 degrees at 10 V ≤ U ≤ 110 V
±2.0 degrees at 110 V < U ≤ 130 V
Table 76. Limit counter L4UFCNT
-
-
Accuracy Function
Counter value
Max. count up speed
Table 77. Disturbance report DRPRDRE
Range or value
0-65535
30 pulses/s (50% duty cycle)
M12760-1 v9.1.1
Function
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the Trip Value recorder per recording
Maximum number of indications in a disturbance report
Maximum number of events in the Event recording per recording
Maximum number of events in the Event list
Maximum total recording time (3.4 s recording time and maximum number of channels, typical value)
Sampling rate
Recording bandwidth
Range or value
(0.05–9.90) s
(0.1–10.0) s
(0.5–10.0) s
100, first in - first out
1 ms
30 + 10 (external + internally derived)
128
30
96
150
1000, first in - first out
340 seconds (100 recordings) at
50 Hz, 280 seconds (80 recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
-
-
-
-
-
-
-
-
-
-
-
-
-
Accuracy
ABB 53
Breaker protection REQ650 2.1 IEC
Product version: 2.1
GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v6
Table 78. Insulation gas monitoring function SSIMG
Function
Pressure alarm level
Pressure lockout level
Temperature alarm level
Temperature lockout level
Time delay for pressure alarm
Reset time delay for pressure alarm
Time delay for pressure lockout
Time delay for temperature alarm
Reset time delay for temperature alarm
Time delay for temperature lockout
Range or value
1.00-100.00
1.00-100.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v6
Table 79. Insulation liquid monitoring function SSIML
Function
Oil alarm level
Oil lockout level
Temperature alarm level
Temperature lockout level
Time delay for oil alarm
Reset time delay for oil alarm
Time delay for oil lockout
Time delay for temperature alarm
Reset time delay for temperature alarm
Time delay for temperature lockout
Range or value
1.00-100.00
1.00-100.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v7
Table 80. Breaker monitoring SSCBR
Function
Alarm level for open and close travel time
Alarm level for number of operations
Independent time delay for spring charging time alarm
Range or value
(0 – 200) ms
(0 – 9999)
(0.00 – 60.00) s
Independent time delay for gas pressure alarm (0.00 – 60.00) s
Independent time delay for gas pressure lockout
(0.00 – 60.00) s
CB Contact Travel Time, opening and closing
Remaining Life of CB
Accumulated Energy
54
1MRK 505 358-BEN B
Accuracy
±10.0% of set value
±10.0% of set value
±2.5% of set value
±2.5% of set value
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
Accuracy
±10.0% of set value
±10.0% of set value
±2.5% of set value
±2.5% of set value
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
±0.2% or ±250ms whichever is greater
Accuracy
±3 ms
-
±0.2% or ±30 ms whichever is greater
±0.2% or ±30 ms whichever is greater
±0.2% or ±30 ms whichever is greater
±3 ms
±2 operations
±1.0% or ±0.5 whichever is greater
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Table 81. Breaker monitoring SSCBR
Function
Alarm level for open and close travel time
Alarm level for number of operations
Independent time delay for spring charging time alarm
Independent time delay for gas pressure alarm
Independent time delay for gas pressure lockout
CB Contact Travel Time opening and closing
Remaining Life of CB
Accumulated energy
Range or value
(0 – 200) ms
(0 – 9999)
(0.00 – 60.00) s
(0.00 – 60.00) s
(0.00 – 60.00) s
M12700-1 v4
Accuracy
-
±3 ms
±0.2% or ±30 ms whichever is greater
±0.2% or ±30 ms whichever is greater
±0.2% or ±30 ms whichever is greater
±3 ms
±2 operations
±1.0% or ±0.5 whichever is greater
Table 82. Event list
Function
Buffer capacity
Resolution
Accuracy
Maximum number of events in the list
Value
1000
1 ms
Depending on time synchronizing
M13765-1 v4
Table 83. Indications
Function
Buffer capacity Maximum number of indications presented for single disturbance
Maximum number of recorded disturbances
M12702-1 v4
Table 84. Event recorder
Function
Buffer capacity Maximum number of events in disturbance report
Maximum number of disturbance reports
Resolution
Accuracy
M13747-1 v5
Table 85. Trip value recorder
Function
Buffer capacity Maximum number of analog inputs
Maximum number of disturbance reports
Value
100
Value
150
100
1 ms
Depending on time synchronizing
Value
100
ABB 55
Breaker protection REQ650 2.1 IEC
Product version: 2.1
M12384-1 v6.1.1
Table 86. Disturbance recorder
Function
Buffer capacity Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports
Maximum total recording time (3.4 s recording time and maximum number of channels, typical value)
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
Table 87. Limit counter L4UFCNT
Function
Counter value
Max. count up speed
Range or value
0-65535
30 pulses/s (50% duty cycle) -
-
Accuracy
Value
40
128
100
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
1MRK 505 358-BEN B
56 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Metering
Table 88. Pulse-counter logic PCFCNT
Function
Cycle time for report of counter value
Setting range
(1–3600) s
Table 89. ETPMMTR
Function
Energy metering
M13404-2 v5
SEMOD153707-2 v4
-
Accuracy
Range or value kWh Export/Import, kvarh Export/
Import
Accuracy
Input from MMXU. No extra error at steady load
1MRK 505 358-BEN B
ABB 57
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Station communication
Table 90. LON communication protocol
Function
Protocol
Communication speed
Value
LON
1.25 Mbit/s
M11901-1 v2
Table 91. SPA communication protocol
Function
Protocol
Communication speed
Slave number
Table 92. IEC 60870-5-103 communication protocol
Function
Protocol
Communication speed
Value
IEC 60870-5-103
9600, 19200 Bd
M12589-1 v4
Table 93. SLM – LON port
Value
SPA
300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
1 to 899
M11921-1 v4
Quantity Range or value
Optical connector
Fiber, optical budget
Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Glass fiber: 11 dB (1000m/3000 ft typically *)
Plastic fiber: 7 dB (10m/35ft typically *)
Fiber diameter Glass fiber: 62.5/125 m m
Plastic fiber: 1 mm
*) depending on optical budget calculation
SEMOD117441-2 v5
Table 94. SLM – SPA/IEC 60870-5-103/DNP3 port
Quantity
Optical connector
Fiber, optical budget
Range or value
Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Glass fiber: 11 dB (1000m/3000ft m typically *)
Plastic fiber: 7 dB (25m/80ft m typically *)
Fiber diameter Glass fiber: 62.5/125 m m
Plastic fiber: 1 mm
*) depending on optical budget calculation
SEMOD158710-2 v2
Table 95. Galvanic RS485 communication module
Quantity
Communication speed
External connectors
Range or value
2400–19200 bauds
RS-485 6-pole connector
Soft ground 2-pole connector
58
1MRK 505 358-BEN B
ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
GUID-8651FF22-C007-4D53-B7E3-686A30F37CB6 v4
Table 96. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function
Communication speed
Value
100 Base-FX
1MRK 505 358-BEN B
ABB 59
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Hardware
IED
M12327-1 v3
Table 97. Water and dust protection level according to IEC 60529
Front
Sides, top and bottom
Rear side
IP40 (IP54 with sealing strip)
IP20
IP20 with screw compression type
IP10 with ring lug terminals
SEMOD53385-1 v1
Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v1
Table 98. Electrical safety according to IEC 60255-27
Equipment class
Overvoltage category
Pollution degree
GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
I (protective earthed)
III
2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected)
Connection system
M12583-1 v5 SEMOD53371-1 v1
Table 99. Auxiliary power supply connectors
Connector type
Screw compression type
Terminal blocks suitable for ring lug terminals
Rated voltage
250 V AC
300 V AC
Maximum conductor area
2.5 mm 2 (AWG14)
2 × 1 mm 2 (2 x AWG18)
3 mm 2 (AWG14)
Table 100. Binary I/O connectors
Connector type
Screw compression type
Rated voltage
250 V AC
Maximum conductor area
2.5 mm 2 (AWG14)
2 × 1 mm 2 (2 x AWG18)
60 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Basic IED functions
M11963-1 v5
Table 101. Self supervision with internal event list
Data
Recording manner
List size
Value
Continuous, event controlled
40 events, first in-first out
SEMOD141136-2 v8
Table 102. IRIG-B
Quantity
Number of channels IRIG-B
Number of optical channels
Electrical connector:
Electrical connector IRIG-B
Optical connector IRIG-B
Type of fibre
Supported formats
Accuracy
Rated value
1
1
BNC
Type ST
62.5/125 μm multimode fibre
IRIG-B 00x
+/- 1μs
1MRK 505 358-BEN B
ABB 61
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Inverse characteristic
M12388-1 v19
Table 103. ANSI Inverse time characteristics
Function
Operating characteristic:
Range or value
0.10 ≤ k ≤ 3.00
1.5 x I set
≤ I ≤ 20 x I set t =
ç
è
(
I
P
A
1
)
ö
+ B k tDef
ø
EQUATION1249-SMALL V2 EN-US
Reset characteristic: t =
I tr
( ) × k
EQUATION1250-SMALL V1 EN-US
I = I measured
/I set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
A=28.2, B=0.1217, P=2.0 , tr=29.1
A=19.61, B=0.491, P=2.0 , tr=21.6
A=0.0086, B=0.0185, P=0.02, tr=0.46
A=0.0515, B=0.1140, P=0.02, tr=4.85
A=64.07, B=0.250, P=2.0, tr=30
A=28.55, B=0.712, P=2.0, tr=13.46
A=0.086, B=0.185, P=0.02, tr=4.6
1MRK 505 358-BEN B
Accuracy
ANSI/IEEE C37.112 ,
±2.0% or ±40 ms whichever is greater
62 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 104. IEC Inverse time characteristics
Function
Operating characteristic:
Range or value
0.10 ≤ k ≤ 3.00
1.5 x I set
≤ I ≤ 20 x I set t t =
æ
ç
I
A
(
P
1
)
ö
÷
× k
EQUATION1251-SMALL V1 EN-US
I = I measured
/I set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
=
æ
ç
I
(
P
A
C
) + B
ö
÷ × k
EQUATION1370-SMALL V1 EN-US
Reset characteristic:
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
k = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
t = (
I
PR
TR
CR
) × k
EQUATION1253-SMALL V1 EN-US
I = I measured
/I set
Table 105. RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1 t =
0.339
-
0.236
I
EQUATION1137-SMALL V1 EN-US
I = I measured
/I set
× k
RD type logarithmic inverse characteristic
Range or value
0.10 ≤ k ≤ 3.00
1.5 x I set
≤ I ≤ 20 x I set t = 5.8
-
æ
1.35
× In
I k
EQUATION1138-SMALL V1 EN-US
I = I measured
/I set
ABB
1MRK 505 358-BEN B
Accuracy
IEC 60255-151, ±2.0% or ±40 ms whichever is greater
Accuracy
IEC 60255-151, ±2.0% or ±40 ms whichever is greater
63
Breaker protection REQ650 2.1 IEC
Product version: 2.1
SEMOD116978-2 v9
Table 106. Inverse time characteristics for undervoltage protection
Function
Type A curve:
Range or value k = (0.05-1.10) in steps of 0.01
t =
U k
< U
U <
EQUATION1431-SMALL V1 EN-US
U< = U set
U = U measured
Type B curve: k × 480 t =
32 ×
U < -
U <
U
EQUATION1432-SMALL V1 EN-US
U< = U set
U = U measured
0.5
ö 2.0
+ 0.055
Programmable curve:
ê
ê
é
ê t =
B ×
U
U
< U
<
EQUATION1433-SMALL V1 EN-US
C
P
÷ ú
ú
ú
ù
ú
+ D
U< = U set
U = U measured k = (0.05-1.10) in steps of 0.01
k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of 0.001
B = (0.50-100.00) in steps of 0.01
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in steps of 0.001
P = (0.000-3.000) in steps of 0.001
1MRK 505 358-BEN B
Accuracy
±5.0% or ±45 ms whichever is greater
64 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
17. Ordering for pre-configured IED
GUID-A24820AA-D198-4429-8F9F-DEF7609B9B85 v2.1.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REQ650*2.1-B11X00- P03-B1A12-AC-MP-B-A3X0-D1AB1N1-GXFX-AX. Using the code of each position #1-13 specified as REQ650*1-2 2-3-4
4-5-6-7 8-9-10 10 10 10-11 11 11-12 12 12 12-13 13
REQ650*
# 1 - 2
-
- 3
-
- 4
-
- 5
-
6 - 7
-
8 - 9
-
10 - 11
-
- 12
.
- 13
-
-
-
SOFTWARE
Version number
Version no
Configuration alternatives
Single breaker, double busbar, 1/3 phase tripping
ACT configuration
ABB Standard configuration
Software options
No option
IEC 62439-3 parallel redundancy protocol
First local HMI user dialogue language
HMI language, English IEC
Additional local HMI user dialogue language
No additional HMI language
HMI language, English US
Casing
1/2 x 19" case
Mounting details with IP40 of protection from the front
No mounting kit included
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6
19" rack mounting kit for 1/1 x 19" case
Wall mounting kit
Flush mounting kit
Flush mounting kit + IP54 mounting seal
Selection for position #1.
#1
2.1
Selection for position #2.
B11
#2
X00
Selection for position #3
X00
#3
P03
B1
#4
X0
A12
Selection for position #4.
A
Selection for position #5. A
#5
#6
B
C
X
A
D
Selection for position #6.
E
F
Notes and Rules
Notes and Rules
Notes and Rules
All fields in the ordering form do not need to be filled in
Note: Requires 2-channel OEM
Notes and Rules
Notes and Rules
Notes and Rules
Note: Wall mounting not recommended with communication modules with fibre connection (SLM, OEM,
LDCM)
ABB 65
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Connection type
Connection type for Power supply module
Compression terminals
Ringlug terminals
Connection type for input/output modules
Compression terminals
Auxiliary power supply
24-60 VDC
90-250 VDC
Human machine hardware interface
Medium size - graphic display, IEC keypad symbols
Medium size - graphic display, ANSI keypad symbols
Connection type for Analog modules
Compression terminals
Ringlug terminals
Analog system
TRM, 7I+5U 1A
TRM, 7I+5U 5A
TRM, 6I, 5A + 1I, 1A + 5U
TRM, 3I, 5A + 4I, 1A + 5U
Selection for position #7.
Selection for position #10.
A
B
M
N
#7
Selection for position #8.
Selection for position #9.
#9
B
C
#10
12
13
14
15
P
P
#8
A
B
Binary input/output module, mA and time synchronization boards.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1 BIM and 1 BOM always included.
Slot position (rear view)
#11
1/2 Case with 1 TRM
No board in slot
Binary output module 24 output relays (BOM)
BIM 16 inputs, 24-30 VDC, 50mA
BIM 16 inputs, 48-60 VDC, 50mA
BIM 16 inputs, 110-125 VDC, 50mA
BIM 16 inputs, 220-250 VDC, 50mA
BIM 16 inputs, 220-250 VDC, 120mA
BIMp 16 inputs, 24-30 VDC, 30mA, for pulse counting
BIMp 16 inputs, 48-60 VDC, 30mA, for pulse counting
BIMp 16 inputs, 110-125 VDC, 30mA, for pulse counting
BIMp 16 inputs, 220-250 VDC, 30mA, for pulse counting
IOM 8 inputs 10+2 output relays, 24-30 VDC, 50mA
IOM 8 inputs 10+2 output relays, 48-60 VDC, 50mA
IOM 8 inputs 10+2 output relays, 110-125 VDC, 50mA
IOM 8 inputs 10+2 output relays, 220-250 VDC, 50mA
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA
IOM with MOV 8 inputs ,10 out, 2 high-speed, 24-30 VDC, 30mA
IOM with MOV 8 inputs 10 out, 2 high-speed, 48-60 VDC, 30mA
IOM with MOV 8 inputs 10 out, 2 high-speed, 110-125 VDC, 30mA
IOM with MOV 8 inputs 10 out, 2 high-speed, 220-250 VDC, 30mA
Selection for position #11.
C1
D1
E1
E2
█
B1
A
█
P2
U
V
L1
M1
N1
P1
H
K
F
G
W
Y
C1
D1
E1
E2
█
X
A
B1
Notes and Rules
Notes and Rules
Notes and Rules
Notes and Rules
Notes and Rules
Note: Max 3 positions in
1/2 rack.
66 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
Remote end communication, DNP serial comm. and time synchronization modules
Slot position (rear view)
Available slots
No remote communication board included
IRIG-B Time synchronization module
Galvanic RS485 communication module
Selection for position #12.
F
G
█
X
Serial communication unit for station communication
Slot position (rear view)
No communication board included
Serial SPA/LON/DNP/IEC 60870-5-103 plastic interface
Serial SPA/LON/DNP/IEC 60870-5-103 plastic/glass interface
Serial SPA/LON/DNP/IEC 60870-5-103 glass interface
Optical ethernet module, 1 channel glass
Optical ethernet module, 2 channel glass
█
X
F
G
#12
Selection for position #13.
B
C
X
A
F
G
█
X
#13
D
E
X
F
G
█
X
Notes and Rules
Notes and Rules
ABB 67
Breaker protection REQ650 2.1 IEC
Product version: 2.1
1MRK 505 358-BEN B
18. Ordering for Accessories
Accessories
IP15151-1 v1
Test switch
SEMOD111888-5 v11
The test system COMBITEST intended for use with the IEDs is described in 1MRK 512 001-BEN and 1MRK 001024-CA.
Please refer to the website: www.abb.com/substationautomation for detailed information.
Due to the high flexibility of our product and the wide variety of applications possible the test switches needs to be selected for each specific application.
Select your suitable test switch based on the available contacts arrangements shown in the reference documentation.
However our proposals for suitable variants are:
Protection cover
RK926 315-AV is provided with one three-phase CT input with current shorting and with sixteen trip output blocking contacts. It is suitable when external CT grounding is required both for the three-phase version and single-phase versions.
One such switch is then used per bay. With such arrangement the best possible test facilities for BBP & integrated BFP are available
Test switches type RTXP 24 is ordered separately. Please refer to Section
for references to corresponding documents.
RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and the on/off switch for dc-supply are ordered separately. Please refer to Section
for references to corresponding documents.
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity:
M15040-3 v5
1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Combiflex
Key switch for settings
Key switch for lock-out of settings via LCD-HMI
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
SEMOD130267-5 v6
Mounting kit
Side-by-side mounting kit
Configuration and monitoring tools
Front connection cable between LCD-HMI and PC
M15042-3 v3
SEMOD131414-4 v3
LED Label special paper A4, 1 pc
LED Label special paper Letter, 1 pc
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
IP15161-1 v1
SEMOD130356-4 v5
1MRK 000 611-A
Ordering number
1MRK 002 420-Z
IP15162-1 v2
1MRK 001 665-CA
1MRK 002 038-CA
1MRK 002 038-DA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,
Installation manual, Commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label template is always included for each IED.
M15161-3 v12
68 ABB
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Rule: Specify additional quantity of IED Connect CD requested.
User documentation
Rule: Specify the number of printed manuals requested
Application manual
Technical manual
Commissioning manual
Communication protocol manual, IEC 61850 Edition 1
Communication protocol manual, IEC 61850 Edition 2
Communication protocol manual, IEC 60870-5-103
Communication protocol manual, LON
Communication protocol manual, SPA
Communication protocol manual, DNP
Point list manual, DNP
Operation manual
Installation manual
Engineering manual
Cyber security guideline
IEC Quantity:
IEC Quantity:
IEC Quantity:
IEC Quantity:
IEC Quantity:
IEC Quantity:
IEC Quantity:
IEC Quantity:
ANSI Quantity:
ANSI Quantity
IEC Quantity:
IEC Quantity:
IEC Quantity:
IEC Quantity:
Quantity:
1MRK 505 358-BEN B
1MRK 002 290-AD
1MRK 505 355-UEN
1MRK 505 356-UEN
1MRK 505 357-UEN
1MRK 511 375-UEN
1MRK 511 376-UEN
1MRK 511 377-UEN
1MRK 511 378-UEN
1MRK 511 379-UEN
1MRK 511 374-UUS
1MRK 511 380-UUS
1MRK 500 125-UEN
1MRK 514 025-UEN
1MRK 511 381-UEN
1MRK 511 382-UEN
ABB 69
Breaker protection REQ650 2.1 IEC
Product version: 2.1
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country:
Station name:
End user:
Voltage level:
Related documents
GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v3
Documents related to REQ650
Application manual
Commissioning manual
Product guide
Technical manual
Type test certificate
Document numbers
1MRK 505 355-UEN
1MRK 505 357-UEN
1MRK 505 358-BEN
1MRK 505 356-UEN
1MRK 505 358-TEN
650 series manuals
Operation manual
Engineering manual
Installation manual
Communication protocol manual,
DNP3
Communication protocol manual,
IEC 60870-5-103
Communication protocol manual,
IEC 61850 Edition 1
Communication protocol manual,
IEC 61850 Edition 2
Communication protocol manual,
LON
Communication protocol manual,
SPA
Point list manual, DNP3
Accessories guide
Document numbers
1MRK 500 125-UEN
1MRK 511 381-UEN
1MRK 514 025-UEN
1MRK 511 374-UUS
1MRK 511 377-UEN
1MRK 511 375-UEN
1MRK 511 376-UEN
1MRK 511 378-UEN
1MRK 511 379-UEN
1MRK 511 380-UUS
IEC: 1MRK 514 012-UEN
ANSI: 1MRK 514 012-UUS
1MRK 511 382-UEN Cyber security deployment guideline
Connection and Installation components
Test system, COMBITEST
1MRK 513 003-BEN
1MRK 512 001-BEN
1MRK 505 358-BEN B
M2175-3 v4 kV
70 ABB
71
Contact us
For more information please contact:
ABB AB
Substation Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00 www.abb.com/protection-control
Note:
We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained herein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in part – is forbidden without prior written consent of ABB AB.
© Copyright 2016 ABB.
All rights reserved.
Scan this QR code to visit our website
advertisement
Related manuals
advertisement
Table of contents
- 2 Contents
- 3 Application
- 5 Available functions
- 12 Current protection
- 13 Voltage protection
- 13 Multipurpose protection
- 13 Secondary system supervision
- 14 Control
- 15 Logic
- 16 Monitoring
- 18 Metering
- 18 Human machine interface
- 19 Basic IED functions
- 19 Station communication
- 19 Hardware description
- 22 Connection diagrams
- 23 Technical data
- 65 Ordering for pre-configured IED
- 68 Ordering for Accessories