Carlo Gavazzi EM11DINAV81XR1X Datasheet
Advertisement
Advertisement
Energy Management
Energy Analyzer
Type EM11 DIN
• Other versions available (not certified, option X):
see “how to order” on the next page
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Class 2 (kvarh) according to EN62053-23
• Accuracy ±0.5 RDG (current/voltage)
• Energy analyzer
• Instantaneous variables readout: 4 DGT
• Energies readout: 6 DGT
• Instantaneous variables: V, A, W, Wdmd, Wdmd max, var,
PF, Hz
• Single phase variables: VLL, VLN, A, VA, W, var, PF
• Energy measurements: total kWh and kvarh
• TRMS measurements of distorted sine waves
(voltages/currents)
• Self power supply
• Dimensions: 1-DIN module
• Protection degree (front): IP40
• 1 pulse output on request
• 1 alarm output on request
• Certified according to MID Directive (option PF only):
see “how to order” below
Product Description
One-phase energy analyzer with built-in configuration push button and LCD data displaying; particularly indicated for active and reactive energy metering and for cost allocation. Housing for DIN-rail mounting, IP40
(front) protection degree.
Direct connection up to
32A. Moreover the meter can be provided with either pulse output proportional to the active energy being measured or alarm control on the available instantaneous variables.
MID Certified according to MID Directive, Module B and Module D of Annex II, for legal metrology relevant to active electrical energy meters (see Annex V, MI003, of
MID). Can be used for fiscal (legal) metrology.
How to order EM11 DIN AV8 1 X O1 PF
Model
Range code
System
Power supply
Output
Option
Type Selection
Range code
AV8: 230V
LN
AC - 5(32)A †††
††††† (direct connection)
System
1: ††
Output
1-phase
O1: Pulse type (open collector output)
Power supply
X: Self power supply
(from 48 to 62Hz).
The instrument works on the range from -20% to +20% of the measuring input nominal voltage.
Option
PF: Certified according to
MID Directive. Can be used for fiscal
(legal) metrology.
Range System
AV8 1 X O1
Option
PF
Specifications are subject to change without notice EM11DIN DS ENG 130117
NOTE: please check the availability of the needed code on the verification path diagram on left before order.
1
EM11 DIN
STANDARD
Not certified according to MID directive. Cannot be used for fiscal (legal) metrology.
How to order EM11 DIN AV8 1 X O1 X
Model
Range code
System
Power supply
Output
Option
Type Selection
Range code
AV7: 120V
LN
AC - 5(32)A †††
††††† (direct connection)
AV8: 230V
LN
AC - 5(32)A †††
††††† (direct connection)
System
1: ††
Output
1-phase
O1: Pulse type (open collector output)
R1: Alarm type (relay output)
Power supply
X: Self power supply
(from 48 to 62Hz).
The instrument works on the range from -20% to +20% of the measuring input nominal voltage.
Option
X: none
NOTE: please check the availability of the needed code on the verification path diagrams below before order.
Range System
AV7 1 X O1
Option
X
Range System
AV8 1 X O1
R1
Option
X
2 Specifications are subject to change without notice EM11DIN DS ENG 130117
EM11 DIN
Input specifications
Rated inputs
Current range (by shunt)
Voltage range
Accuracy (Display)
(@25°C ±5°C, R.H. ≤60%, 48 to 62Hz)
AV7 model
System: 1
AV7 and AV8: 5(32)
A
AV7: 120 VLN AC
AV8: 230 VLL AC
AV8 model
Current
Voltage
Frequency
Active power
Reactive power
Active energy
Reactive energy
Reference values
Start up current:
Ib: 5A, Imax: 32A;
Un: 120VLN (-20% +20%)
Ib: 5A, Imax: 32A;
Un: 230VLN (-20% +20%)
From 0.04Ib to 0.2Ib, PF=1:
±(0.5% RDG +3DGT)
From 0.2Ib to Imax, PF=1:
±(0.5% RDG +1DGT).
In the Un range: ±(0.5%
RDG +2DGT)
±0.1Hz (48 to 62Hz)
±(1%RDG +2DGT)
±(2%RDG +2DGT)
Class 1 according to
EN62053-21 and Class B according to EN50470-3.
Class 2 according to
EN62053-23.
Ib: 5A, Imax: 32A,
0.1 Ib: 0.5A
20mA
Energy additional errors
Influence quantities
Temperature drift
Sampling rate
Display refresh time
Display
According to EN62053-21,
EN62053-23
≤200ppm/°C
4096 samples/s @ 50Hz
4096 samples/s @ 60Hz
1 sec.
1 line (max: 6 DGT)
Type LCD, h 7mm
Instantaneous variables read-out 4 DGT (V and A)
3 DGT (W, var, Wdmd,
Wdmd max, Hz, PF)
Min. Max. indication
Energies
LEDs
Measurements
Method
Max. 9 999;
Min. 0 (0.0)
Total: 6 DGT
Red LED (Energy consumption), 1000 pulses/kWh
(Max Frequency 16 Hz) according to EN62053-11
See “Measuring variables and Min. Max. indications”
TRMS measurements of distorted wave forms
Direct
Ib 5A ≤4 (45A max. peak)
Coupling type
Crest factor
Current Overload
Continuous
For 10ms
Voltage Overload
Continuous
For 500ms
Input impedance
120VL-N (AV7)
230VL-N (AV8)
5(32) A (AV7-AV8)
32A, @ 50Hz
960A, @ 50Hz
1.2 Un
2 Un
>720KΩ
>720KΩ
< 0.5VA
Frequency
Key-pad
48 to 62 Hz
1 push-button for variable selection and programming of the instrument working parameters.
Not available in case of
“PF” option.
Output specifications
Digital output
Number of outputs
X Option
PF option
Signal
Pulse duration
Insulation
Alarm output
Number of outputs
Type
1, open collector programmable, from 0.001 to 1 kWh for each pulse.
Fixed, 0,001 kWh/pulse
V
V
ON
OFF
1.2 VDC/ max. 100 mA
30 VDC max.
≥100ms < 120msec (ON),
≥120ms (OFF), according to EN62052-31
By means of optocouplers,
4000 VRMS output to measuring inputs
Not available in case of PF option.
1
Relay, SPST type
AC 1-5A @ 250VAC
DC 12-5A @ 24VDC
AC 15-1.5A @ 250VAC
Alarm modes
Controlled variables
Set-point adjustment
Hysteresis
On-time delay
Off-time delay
Min. response time
Insulation
DC 13-1.5A @ 24VDC
Up alarm or down alarm kW, kWdmd, kvar, PF, A,
V, Hz
Programmable on all the measuring range (see
“Measuring variables and
Min. Max. indications”) programmable on all the measuring range (see
“Measuring variables and
Min. Max. indications”)
0 to 9999s (166min)
0 to 9999s (166min)
1s, set-point on-time delay:
“0 s”
4000 VRMS output to measuring inputs
Specifications are subject to change without notice EM11DIN DS ENG 130117
3
EM11 DIN
Software functions (Not available in case of PF option)
Password
1st level
2nd level
Numeric code of max. 4 digits; 2 protection levels of the programming data:
Password “0”, no protection;
Password from 1 to 9999, all data are protected
Displaying
Reset
1 variable per page (See
«Measuring variables and
Min. Max. indications»)
By means of the front key-pad:
- W dmd max;
- energies: kWh, kvarh
General specifications
Operating temperature
Storage temperature
Installation category
Insulation (for 1 minute)
Dielectric strength
CMRR Noise rejection
EMC
Electrostatic discharges
Immunity to irradiated
electromagnetic fields
Burst
Immunity to conducted
disturbances
-25°C to +55°C (-13°F to
131°F) (R.H. from 0 to 90% non-condensing @ 40°C) according to EN62053-21,
EN50470-1 and EN62053-
23
-30°C to +70°C (-22°F to
140°F) (R.H. < 90% noncondensing @ 40°C)
according to EN62053-21,
EN50470-1 and EN62053-
23
Cat. III (IEC60664,
EN60664)
4000 VRMS between measuring inputs and digital output (O1 and R1).
4000 VRMS for 1 minute
100 dB, 48 to 62 Hz
According to EN62052-11
8kV air discharge;
Test with applied current:
10V/m from 80 to 2000MHz;
Test without any applied current: 30V/m from 80 to
2000MHz;
On current and voltage measuring input circuits:
4kV
10V/m from 150KHz to
Surge
80MHz
On current and voltage measuring input circuits:
4kV;
Radio frequency suppression According to CISPR 22
Standard compliance
Safety
Metrology
Pulse output
Approvals
Connections
Cable cross-section area
IEC60664, IEC61010-1
EN60664, EN61010-1
(EN62052-11) EN50470-1.
EN62053-21, EN62053-23,
EN50470-3.
DIN43864, IEC62053-31
CE, cULus (X option)
MID (PF option)
Screw-type
Measuring inputs: min. 2.5 mm 2 , max. 10 mm 2 ;
Min./Max. screws tightening torque: 0.5 Nm / 1.1 Nm
Other terminals: 1.5 mm 2 .
Screws tightening torque:
0.5 Nm
DIN Housing
Dimensions (WxHxD)
Material
17.5 (+0.5 -0) x 90 x 67.5 mm
Nylon PA66, self-extinguishing: UL 94 V-0
DIN-rail Mounting
Protection degree
Front
Screw terminals
Weight
IP40
IP20
Approx. 100 g (packing included)
Power supply specifications
Self supplied version 120VLN (AV7), 230 VLN
(AV8) (-20% +20%)
48-62Hz
Power consumption ≤ 3VA
4 Specifications are subject to change without notice EM11DIN DS ENG 130117
EM11 DIN
Accuracy (according to EN50470-3 and EN62053-23)
kWh , accuracy (RDG) depending on the current
Percentage error limits for class index B kvarh , accuracy (RDG) depending on the current
Error
+1.5%
+1%
+2.5%
+2%
0%
-1%
-1.5%
0%
-2%
-2.5%
PF=1
PF=L0.5
or C0.8
0.25A
(0.5Iref)
0.5A
(0,1Iref)
0.5A
(0,1Iref)
5A (Iref)
5A (Iref)
32A (Imax)
32A (Imax)
Class 1 accuracy limits (Active energy)
5(32)A Start-up current: 20mA sin j =1 sin j =0.5
0.25A
(0.05Ib)
0.5A
(0.1Ib)
0.5A
(0.1Ib)
1A
(0.25Ib)
5A (Ib)
5A (Ib)
32A (Imax)
32A (Imax)
Class 2 accuracy limits (Reactive energy)
5(32)A Start-up current: 20mA
MID compliance (PF option only)
Accuracy
Operating temperature
0.9 Un ≤ U ≤ 1.1 Un;
0.98 fn ≤ f ≤ 1.02 fn; fn: 50 or 60Hz; cos j : 0.5 inductive to 0.8 capacitive.
Class
I st: 0.02A; I min: 0.25A;
I tr: 0.5A; I ref: 5A;
I max: 32A.
-25°C to +55°C (-13°F to
131°F) (R.H. from 0 to 90% non-condensing @ 40°C)
EMC compliance
Mechanical compliance
Protection degree
Used calculation formulas
Phase variables
Instantaneous effective voltage
Energy metering
E2
M2 in order to achieve the protection against dust and water required by the norms harmonized to MID, the meter must be used only installed in IP51 (or better) cabinets.
Instantaneous active power
Instantaneous power factor
Instantaneous effective current
Instantaneous apparent power
Instantaneous reactive power t
Where:
P = active power;
Q = reactive power;
1
, t
2
=starting and ending time points of consumption recording; nj = time unit;
∆ t = time interval between two successive power consumptions; n
1
, n
2
= starting and ending discrete time points of consumption recording
Where: n = sample number
Specifications are subject to change without notice EM11DIN DS ENG 130117
5
EM11 DIN
Measuring variables and Min. Max. indications
Page number Variable Min. Max. Indication Notes
1
2
3
4
8
9
10
5
6
7 kWh kvarh kW kW dmd kW dmd max
V
A
Hz
PF (cos j) kvar from 0.01 to 999999, autoranging.
from 0.0 to 99999.9
from 0.00 to 9.99
from 0.00 to 9.99
from 0.00 to 9.99
from 0.0 to 999.9
from 0.0 to 32.00
from 48.0 to 62.0
from L/C. 00 to L/C. 99 from 0.00 to 9.99
Total (only consumed energy)
Total (only consumed energy)
Integration time progammable from 1 to
30 minutes
Max value with data storage (in EEprom)
Note: In case of X option all the variables above can be scrolled using the front push button, in case of PF option the push button is not available and the variables are automatically scrolled.
Insulation between inputs and outputs
Measuring inputs
Relay output
Measuring inputs
-
4kV
4kV
0kV
Relay output
4kV
-
4kV
4kV AC self-power supply
Wiring diagrams and relay output (R1)
4kV
4kV
-
4kV
AC self-power supply
0kV
4kV
4kV
-
1-phase connection Fig. 1 1 relay output Fig. 2
NOTE: The 3 and 4 terminals, in the instrument, are wired together
6 Specifications are subject to change without notice EM11DIN DS ENG 130117
EM11 DIN
Wiring diagrams and open collector output (O1)
1-phase connection Fig. 1 1 open collector output Fig. 2
VDC VDC
VDC Reference GND Reference
NOTE: The 3 and 4 terminals, in the instrument, are wired together
Frontal panel description
The load resistances (RC) must be designed so that the close contact current is lower than 100mA; the VDC voltage must be lower than or equal to 30VDC.
3
2 1
1. Push button
†† To program the configuration parameters and the display
†† of the variables.
†† Not available in case of PF option.
2. LED
†† Red LED to show the consumed energy.
3. Display
†† LCD-type with alphanumeric indication to:
†† - display configuration parameters;
†† - display all the measured variables.
Dimensions and panel cut-out
18mm
44mm
67.5mm
17.5 +0.5/-0mm
Specifications are subject to change without notice EM11DIN DS ENG 130117