Advertisement
Advertisement
Compact I/O Analog
Modules
1769-IF4, -IF8, -OF2, -OF8C, and
-OF8V
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls (Publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
SHOCK HAZARD
Labels may be located on or inside the drive to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures.
Summary of Changes
The 1769-IF8, -OF8C, and -OF8V modules have been added to this manual since the last printing.
To help you find new and updated information in this release of the manual, we have included change bars as shown next to this paragraph.
1 Publication 1769-UM002B-EN-P - July 2005
Summary of Changes 2
Notes:
Publication 1769-UM002B-EN-P - July 2005
i
Overview
Installation and Wiring
Table of Contents
Preface
Who Should Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . Preface-1
How to Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preface-1
Manual Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preface-1
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . Preface-2
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . Preface-2
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . Preface-3
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preface-3
Technical Product Assistance . . . . . . . . . . . . . . . . . . . . . . . Preface-3
Your Questions or Comments on the Manual. . . . . . . . . . Preface-3
Chapter 1
How to Use Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Hardware Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General Diagnostic Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
System Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Module Field Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Chapter 2
Compliance to European Union Directives . . . . . . . . . . . . . . . . . . . . 2-1
EMC Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Hazardous Location Considerations. . . . . . . . . . . . . . . . . . . . . . . 2-3
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Remove Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Reducing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Protecting the Circuit Board from Contamination . . . . . . . . . . . 2-4
Minimum Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Replacing a Single Module within a System . . . . . . . . . . . . . . . . . . . . 2-9
External Power Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Publication 1769-UM002B-EN-P - July 2005
Table of Contents ii
Field Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
System Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Labeling the Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Removing the Finger-Safe Terminal Block . . . . . . . . . . . . . . . . 2-15
Wiring the Finger-Safe Terminal Block . . . . . . . . . . . . . . . . . . . 2-16
Wiring the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Terminal Door Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Analog Input Modules Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Analog Output Modules Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
Module Data, Status, and Channel
Configuration for the Input
Modules
Chapter 3
1769-IF4 Input Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
1769-IF4 Input Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
1769-IF4 Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
1769-IF4 Input Data File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
1769-IF4 Input Data Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
1769-IF4 Configuration Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Channel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Enable/Disable Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Input Filter Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Input Type/Range Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Input Data Selection Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Effective Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
1769-IF8 Input Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
1769-IF8 Input Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
1769-IF8 Output Image. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
1769-IF8 Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
1769-IF8 Input Data File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
1769-IF8 Input Data Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
1769-IF8 Output Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
1769-IF8 Configuration Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Channel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Enable/Disable Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Input Filter Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Input Type/Range Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
Input Data Selection Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
1769-IF8 Real Time Sampling. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-29
1769-IF8 Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-30
Publication 1769-UM002B-EN-P - July 2005
Table of Contents iii
Module Data, Status, and Channel
Configuration for the Output
Modules
Chapter 4
1769-OF2 Output Module Memory Map . . . . . . . . . . . . . . . . . . . . . . 4-1
1769-OF2 Output Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
1769-OF2 Input Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
1769-OF2 Diagnostic Bits (D0 and D1). . . . . . . . . . . . . . . . . . . . 4-2
1769-OF2 Hold Last State Bits (H0 and H1). . . . . . . . . . . . . . . . 4-2
1769-OF2 Over-Range Flag Bits (O0 and O1) . . . . . . . . . . . . . . 4-3
1769-OF2 Under-Range Flag Bits (U0 and U1). . . . . . . . . . . . . . 4-3
1769-OF2 General Status Bits (S0 and S1). . . . . . . . . . . . . . . . . . 4-3
1769-OF2 Output Data Loopback/Echo . . . . . . . . . . . . . . . . . . 4-4
1769-OF2 Configuration Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
1769-OF2 Channel Configuration . . . . . . . . . . . . . . . . . . . . . . . . 4-6
1769-OF2 Enable/Disable Channel . . . . . . . . . . . . . . . . . . . . . . . 4-7
1769-OF2 Output Data Format Selection . . . . . . . . . . . . . . . . . . 4-7
1769-OF2 Output Type/Range Selection . . . . . . . . . . . . . . . . . . 4-8
1769-OF2 Fault Mode (FM0 and FM1) . . . . . . . . . . . . . . . . . . . . 4-8
1769-OF2 Program/Idle Mode (PM0 and PM1). . . . . . . . . . . . . 4-9
1769-OF2 Program/Idle to Fault Enable (PFE0 and PFE1) . . 4-10
1769-OF2 Fault Value (Channel 0 and 1). . . . . . . . . . . . . . . . . . 4-11
1769-OF2 Program/Idle Value (Channel 0 and 1) . . . . . . . . . . 4-11
1769-OF2 Module Resolution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
1769-OF8C Output Module Memory Map . . . . . . . . . . . . . . . . . . . 4-16
1769-OF8V Output Module Memory Map . . . . . . . . . . . . . . . . . . . 4-17
1769-OF8C and -OF8V Output Data File . . . . . . . . . . . . . . . . . . . . 4-18
Channel Alarm Unlatch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
1769-OF8C and -OF8V Input Data File . . . . . . . . . . . . . . . . . . . . . 4-19
1769-OF8C and -OF8V Data Values . . . . . . . . . . . . . . . . . . . . . 4-19
1769-OF8C and -OF8V Output Data Loopback/Echo . . . . . . 4-21
1769-OF8C and -OF8V Configuration Data File . . . . . . . . . . . . . . 4-22
1769-OF8C and -OF8V Channel Configuration . . . . . . . . . . . . 4-24
1769-OF8C and -OF8V Enable/Disable Channel . . . . . . . . . . 4-25
Clamping/Limiting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Clamp/Limit Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
Ramping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
Hold for Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
Open Wire Detection (1769-OF8C Only) . . . . . . . . . . . . . . . . . 4-29
1769-OF8C and -OF8V Fault Mode (FM). . . . . . . . . . . . . . . . . 4-29
1769-OF8C and -OF8V Program/Idle Mode (PM) . . . . . . . . . 4-30
1769-OF8C and -OF8V Program/Idle to Fault Enable (PFE). 4-31
1769-OF8C and -OF8V Fault Value . . . . . . . . . . . . . . . . . . . . . 4-31
1769-OF8C and -OF8V Program/Idle Value . . . . . . . . . . . . . . 4-32
Publication 1769-UM002B-EN-P - July 2005
Table of Contents iv
Module Diagnostics and
Troubleshooting
Specifications
Module Addressing and
Configuration with MicroLogix
1500
Chapter 5
Safety Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Indicator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Activating Devices When Troubleshooting . . . . . . . . . . . . . . . . . 5-1
Stand Clear of the Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Program Alteration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Safety Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Module Operation vs. Channel Operation . . . . . . . . . . . . . . . . . . . . . 5-2
Power-up Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Channel Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Out-of-Range Detection (Input and Output Modules) . . . . . . . . 5-3
Open-Circuit Detection (Input Modules Only) . . . . . . . . . . . . . . 5-3
Output Wire Broken/High Load Resistance
(Output Modules Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Non-critical vs. Critical Module Errors. . . . . . . . . . . . . . . . . . . . . . . . 5-4
Module Error Definition Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Module Error Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Extended Error Information Field . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Module Inhibit Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Contacting Rockwell Automation . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Appendix A
1769-IF4 Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
1769-IF8 Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
1769-OF2 Output Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
1769-OF8C Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
1769-OF8V Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . A-11
Appendix B
Input Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Input Modules Input Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Input Modules’ Configuration File . . . . . . . . . . . . . . . . . . . . . . . . B-3
Configuring Analog I/O Modules in a MicroLogix 1500 System . . . B-4
Configuring the Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Configuring the Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Configuration Using the RSLogix
5000 Generic Profile for
CompactLogix Controllers
Appendix C
Configuring I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
Configuring Analog Output Modules. . . . . . . . . . . . . . . . . . . . . . C-7
Configuring Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . C-7
Publication 1769-UM002B-EN-P - July 2005
Table of Contents v
Configuring Modules in a Remote
DeviceNet System with a
1769-ADN DeviceNet Adapter
Appendix D
Add the DeviceNet Adapter to the Scanlist . . . . . . . . . . . . . . . . . . . D-2
Configure the 1769-IF4 Input Module Example . . . . . . . . . . . . . . . D-4
1769-IF4 Example of External Power . . . . . . . . . . . . . . . . . . . . D-6
Configure the 1769-OF8C Output Module Example . . . . . . . . . . . D-7
1769-OF8C Example of External Power . . . . . . . . . . . . . . . . . . D-8
1769-OF8C Example of Output Channels. . . . . . . . . . . . . . . . . D-9
Two’s Complement Binary
Numbers
Appendix E
Positive Decimal Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Negative Decimal Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-2
Glossary
Publication 1769-UM002B-EN-P - July 2005
Table of Contents vi
Publication 1769-UM002B-EN-P - July 2005
1
Preface
Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
• who should use this manual
• how to use this manual
• related publications
• conventions used in this manual
• Rockwell Automation support
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen-Bradley Compact™ I/O.
Who Should Use This
Manual
How to Use This Manual
As much as possible, we organized this manual to explain, in a task-by-task manner, how to install, configure, program, operate and troubleshoot a control system using the 1769 analog I/O modules.
Manual Contents
If you want...
An overview of the analog input and output modules
Installation and wiring guidelines
Input module addressing, configuration and status information
Output module addressing, configuration and status information
Information on module diagnostics and troubleshooting
Specifications for the input and output modules
Information on addressing and configuration using MicroLogix 1500 and
RSLogix 500
Information on configuring the module using CompactLogix and RSLogix
5000
Information on configuring the module using 1769-ADN DeviceNet
Adapter and RSNetWorx
Information on understanding two’s complement binary numbers
Definitions of terms used in this manual
See
Publication 1769-UM002B-EN-P - July 2005
2
Related Documentation
The table below provides a listing of publications that contain important information about MicroLogix 1500 systems.
For Read this document
A user manual containing information on how to install, use and program your MicroLogix 1500 controller.
MicroLogix™ 1500 User Manual
A user manual containing information on how to install, and use your 1769-ADN DeviceNet Adapter.
DeviceNet Adapter User Manual
A user manual containing information on how to install, use and program your CompactLogix controller.
CompactLogix User Manual
An overview of 1769 Compact Discrete I/O modules 1769 Compact Discrete Input/Output Modules Product
Data
MicroLogix™ 1500 System Overview An overview of the MicroLogix 1500 System, including
1769 Compact I/O.
In-depth information on grounding and wiring
Allen-Bradley programmable controllers.
Allen-Bradley Programmable Controller Grounding and
Wiring Guidelines
Document number
1764-UM001
1769-UM001
1769-UM007
1769-2.1
1764-SO001
1770-4.1
If you would like a manual, you can:
• download a free electronic version from the internet at www.ab.com/literature
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation representative
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574 (Outside
USA/Canada)
Conventions Used in This
Manual
The following conventions are used throughout this manual:
• Bulleted lists (like this one) provide information not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
• Text in this font indicates words or phrases you should type.
Publication 1769-UM002B-EN-P - July 2005
Rockwell Automation
Support
3
Rockwell Automation offers support services worldwide, with over
75 Sales/Support Offices, 512 authorized distributors and 260 authorized
Systems Integrators located throughout the United States alone, plus Rockwell
Automation representatives in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for:
• sales and order support
• product technical training
• warranty support
• support service agreement
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance, please
review the information in Chapter 5,
Module Diagnostics and Troubleshooting first.
Then call your local Rockwell Automation representative.
Your Questions or Comments on the Manual
If you find a problem with this manual, please notify us. If you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Rockwell Automation
Automation Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
Publication 1769-UM002B-EN-P - July 2005
4
Notes:
Publication 1769-UM002B-EN-P - July 2005
1
Chapter
1
Overview
How to Use Analog I/O
This chapter explains how analog data is used, and describes the 1769-IF4 and
-IF8 analog input modules and the 1769-OF2, -OF8C, and -OF8V analog output modules. Included is information about:
• the use of analog I/O
• the modules’ hardware and diagnostic features
• an overview of the 1769 analog input system operation
• an overview of the 1769 analog output system operation
Analog refers to the representation of numerical quantities by the measurement of continuous physical variables. Analog applications are present in many forms. The following application shows a typical use of analog data.
In this application, the processor controls the amount of fluid in a holding tank by adjusting the valve opening. The valve is initially open 100%. As the fluid level in the tank approaches the preset point, the processor modifies the output to close the valve 90%, 80%, and so on, continuously adjusting the valve to maintain the fluid level.
Figure 1.1 Analog I/O Application Example
Analog output wired to valve
Valve
Analog I/O
Module
Level Sensor
Controller
Analog input wired to tank
Publication 1769-UM002B-EN-P - July 2005
1-2 Overview
General Description
The 1769-IF4 and -IF8 analog input modules convert and digitally store analog data for retrieval by controllers, such as the CompactLogix™ or MicroLogix™
1500. The module supports connections from any combination of up to four voltage or current analog sensors for the 1769-IF4 and up to eight for the
1769-IF8. The high-impedance input channels can be wired as either single-ended or differential inputs.
The 1769-OF2 output module provides two single-ended analog output channels, each individually configurable for voltage or current. The
1769-OF8C and -OF8V output modules each provide eight single-ended analog output channels.
Both modules provide the following input/output types/ranges:
Table 1.1 Normal and Full Ranges
Normal Operating Input Range
±10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
0 to 20 mA
4 to 20 mA
Full Module Range
± 10.5V dc
0.5 - 5.25V dc
-0.5 - +5.25V dc
-0.5 - +10.5V dc
0 - 21 mA
3.2 - 21 mA
The data can be configured on board each module as:
• Engineering Units
• Scaled-for-PID
• Percent
• Raw/Proportional Data
Publication 1769-UM002B-EN-P - July 2005
Overview 1-3
Hardware Features
The modules contain removable terminal blocks. The 1769-IF4 and -IF8 channels can be wired as either single-ended or differential inputs. The
1769-OF2, -OF8C, and -OF8V channels are single-ended only. Module configuration is normally done via the controller’s programming software. In addition, some controllers support configuration via the user program. In either case, the module configuration is stored in the memory of the controller.
Refer to your controller’s user manual for more information.
Figure 1.2 1769-OF2, -OF8C, -OF8V and -IF4 Analog Module’s Hardware Features
1 2a
7a
10a
10
10b
8a
OK
Analog
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
ANLG
Com
I out 0 +
ANLG
Com
I out 1 +
ANLG
Com
I out 2 +
ANLG
Com
I out 3 +
ANLG
Com
I out 4 +
ANGL
Com
I out 5 +
ANLG
Com
I out 6 +
ANLG
Com
I out 7 + dc
NEUT
+24V dc
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
1769-OF8C
3
4
7a
2b
OK
Analog
5a
5b
9
6
7b
7b
8b
Table 1.2 1769-OF2, -OF8C, -OF8V, and -IF4 Feature Descriptions
8b
9
10
10a
10b
6
7a
7b
8a
3
4
5a
5b
Item
1
2a
2b
Description bus lever (with locking function) upper panel mounting tab lower panel mounting tab module status LEDs module door with terminal identification label movable bus connector with female pins stationary bus connector with male pins nameplate label upper tongue-and-groove slots lower tongue-and-groove slots upper DIN rail latch lower DIN rail latch write-on label for user identification tags removable terminal block (RTB) with finger-safe cover
RTB upper retaining screw
RTB lower retaining screw
Publication 1769-UM002B-EN-P - July 2005
1-4 Overview
Figure 1.3 1769-IF8 Analog Module’s Hardware Features
1
2a
7a
8a
10a
10b
10
7a
WARNING -Do Not
Remove RTB Unless
Area is Non-Hazardous
IN 1
IN 0
IN 17
IN 2
IN 3 IN 19
IN 4
IN 5 IN 21
IN 7
IN 9
IN 11
IN 13
IN 15
DC COM
IN 6
IN 23
DC COM
IN 25
IN 8
IN 27
IN 10
IN 29
IN 12
IN 31
IN 14
DC COM
IN 16
IN 18
IN 20
IN 22
DC COM
IN 24
IN 26
IN 28
IN 30
1769-IQ32
3
4
2b
5a
9
5b
6
7b 7b
8b
30538-M
Table 1.3 1769-IF8 Feature Descriptions
8b
9
10
10a
10b
6
7a
7b
8a
3
4
5a
5b
Item
1
2a
2b
Description bus lever (with locking function) upper panel mounting tab lower panel mounting tab
I/O diagnostic LEDs module door with terminal identification label movable bus connector with female pins stationary bus connector with male pins nameplate label upper tongue-and-groove slots lower tongue-and-groove slots upper DIN rail latch lower DIN rail latch write-on label for user identification tags removable terminal block (RTB) with finger-safe cover
RTB upper retaining screw
RTB lower retaining screw
Publication 1769-UM002B-EN-P - July 2005
System Overview
Overview 1-5
General Diagnostic Features
The analog modules contain diagnostic features that can help you identify the source of problems that may occur during power-up or during normal channel operation. These power-up and channel diagnostics are explained in chapter 6,
Module Diagnostics and Troubleshooting.
The modules communicate to the controller through the bus interface. The modules also receive 5 and 24V dc power through the bus interface. The
1769-IF4, -OF2, -OF8C, and -OF8V modules feature an external 24V dc power switch, providing you with the option of using an external power
supply. See External Power Switch on page 2-10 for details.
You can install as many analog modules as your power supply can support.
However, the modules have a power supply distance rating of 8, which means that they may not be located more than 8 modules away from the system power supply.
Figure 1.4 Determine Power Supply Distance
4 3 2 1
OR
1 2 3 Power Supply Distance
MicroLogix 1500 Controller with Integrated System
Power Supply
1 2 3 4 Power Supply Distance
Publication 1769-UM002B-EN-P - July 2005
1-6 Overview
System Operation
At power-up, the module performs a check of its internal circuits, memory, and basic functions. During this time, the module status LED remains off. If no faults are found during power-up diagnostics, the module status LED is turned on.
After power-up checks are complete, the module waits for valid channel configuration data. If an invalid configuration is detected, the module generates a configuration error. Once a channel is properly configured and enabled, it begins the analog-to-digital or digital-to-analog conversion process.
Input Modules
Each time a channel is read by the input modules, that analog data value is tested by the modules for an over-range or under-range condition. If such a condition is detected, a unique bit is set in the channel status word. The
channel status word is described in 1769-IF4 Input Data File on page 3-2 and
1769-IF8 Input Data File on page 3-18.
The controller reads the two’s complement binary converted analog data from the modules. This typically occurs at the end of the program scan or when commanded by the control program. If the controller and the modules determine that the bus data transfer was made without error, the data is used in your control program.
Output Modules
The output modules monitor channels for over-range and under-range conditions and also for broken output wires and high load resistance (in current mode only). If such a condition is detected, a unique bit is set in the
channel status word. The channel status word is described in 1769-OF2
Output Data File on page 4-2 and 1769-OF8C and -OF8V Output Data File on page 4-18.
The output module receives two’s complement binary values from the bus master. This typically occurs at the end of the program scan or when commanded by the control program. If the controller and the module determine that the bus transfer was completed without error, the output module converts the data to an analog output signal.
Publication 1769-UM002B-EN-P - July 2005
Overview 1-7
Input
Module Operation
Input Module Block Diagram
The input module’s input circuitry consists of four differential analog inputs multiplexed into a single analog-to-digital (A/D) converter. The
A/D converter reads the selected input signal and converts it to a digital value which is presented to the controller. The multiplexer sequentially switches each input channel to the module’s A/D converter.
Figure 1.5 1769-IF4 Block Diagram
Galvanic
Isolation
VA2 VA1 VS1
Vin+
CH0
Iin+
AIN+
A/D
AIN-
V/Iin-
COM
A-GND
Vref VREF
CH1
CH2
CH3 dc Neutral
+24V dc
Channel Select
VA3
(same as above)
TXD
MCU
RXD
VA2
VA1
DC/DC
Power
Supply
VA3
A-GND
ASIC
VS1
VS2
S-GND
Publication 1769-UM002B-EN-P - July 2005
1-8 Overview
CH4
CH5
CH6
CH7
Vin +
Iin +
V/I-
Com
Vin +
Iin +
V/I-
Com
Vin +
Iin +
V/I-
Com
Vin +
Iin +
V/I-
Com
CH0
CH1
CH2
CH3
Vin +
Iin +
V/I-
Com
Vin +
Iin +
V/I-
Com
Vin +
Iin +
V/I-
Com
Vin +
Iin +
V/I-
Com Select
Select
Figure 1.6 1769-IF8 Block Diagram
High
Impedance Gain
AD
Converter
Opto
Coupler
Opto
Coupler
Opto
Coupler
ASIC
Vref
CPU
High
Impedance Gain
AD
Converter
+15V
+5V
-15V
GND
DC/DC converter
EN0
A1
A0
EN1
EN1
CN2
(Out)
LED
+24V
GND
31542-M
CN1
(In)
Publication 1769-UM002B-EN-P - July 2005
Overview 1-9
Output
Output Module Block Diagram
The output module uses a digital-to-analog (D/A) converter to read the digital output data from the controller and convert it to an analog output signal.
Figure 1.7 1769-OF2 Block Diagram
Galvanic
Isolation
VA1 VS1
VA2
CH0
Iout+
A-GND
VA2
Analog Switch
Iout
D/A
Iout
Selec
Refout
Latch
Vout+
COM
A-GND
VA3
CH1
Latch
Selec
(same as above)
MCU
TXD
RXD
VA2
VA1
DC/DC
Power Supply
ASIC
VS1
VS2
VA3
A-GND S-GND dc Neutral
+24V dc
Figure 1.8 1769-OF8C and -OF8V Block Diagram
The following diagram shows only one of eight outputs. For each analog output, only one of the sections shown in broken-line boxes is implemented.
The 1769-OF8C module uses only the Current Out section while the
1769-OF8V module uses only the Voltage Out section.
Curent Out
OC
Detect
ASIC
CFU
64K Flash/
2K RAM
OPTOS
16 Bit
DAC
+24 VDC JP
GND
Voltage Out
EXT 24VDC
GND
Publication 1769-UM002B-EN-P - July 2005
1-10 Overview
Module Field Calibration
The 1769-IF4 and -IF8 input modules performs autocalibration when a channel is initially enabled. In addition, if a channel is configured differently than the previously scanned channel, an autocalibration cycle is run as part of the reconfiguration process.
The 1769-OF2, -OF8C, and -OF8V output modules’s calibration is guaranteed by its design. No field calibration is required.
Publication 1769-UM002B-EN-P - July 2005
Chapter
2
Installation and Wiring
This chapter tells you how to:
• determine the power requirements for the modules
• avoid electrostatic damage
• install the module
• wire the module’s terminal block
• wire input devices
• wire output devices
1
Compliance to European
Union Directives
This product is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
The analog modules are tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
• EN 50081-2
EMC – Generic Emission Standard, Part 2 - Industrial Environment
• EN 50082-2
EMC – Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers,
Part 2 – Equipment Requirements and Tests.
For specific information required by EN61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
• Industrial Automation, Wiring and Grounding Guidelines for Noise Immunity , publication 1770-4.1
• Automation Systems Catalog , publication B113
Publication 1769-UM002B-EN-P - July 2005
2-2 Installation and Wiring
Power Requirements
General Considerations
The modules receive power through the bus interface from the +5V dc/+24V dc system power supply. Some modules can also be supplied 24V dc power by an external power supply connected to the module’s terminal block.
Table 2.1 Maximum Current Draw
Module
1769-IF4 (Series A)
1769-IF4 (Series B)
1769-IF8 (Series A)
1769-OF2 (Series A)
1769-OF2 (Series B)
1769-OF8C (Series A)
1769-OF8V (Series A)
5V dc
120 mA
120 mA
145 mA
24V dc
Not applicable
60 mA
(1)
70 mA
Not applicable
120 mA
160 mA
125 mA
(1)
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Publication 1769-UM002B-EN-P - July 2005
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Installation and Wiring 2-3
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
ATTENTION
EXPLOSION HAZARD
• Substitution of components may impair suitability for
Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
• Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article 501-4(b).
Prevent Electrostatic Discharge
ATTENTION
Electrostatic discharge can damage integrated circuits or semiconductors if you touch analog I/O module bus connector pins or the terminal block on the input module.
Follow these guidelines when you handle the module:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• If available, use a static-safe work station.
• When it is not in use, keep the module in its static-shield box.
Publication 1769-UM002B-EN-P - July 2005
2-4 Installation and Wiring
System Assembly
Publication 1769-UM002B-EN-P - July 2005
Remove Power
ATTENTION
Remove power before removing or inserting this module.
When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices, causing unintended machine motion
• causing an explosion in a hazardous environment
• Electrical arcing causes excessive wear to contacts on both the module and its mating connector and may lead to premature failure.
Reducing Noise
Most applications require installation in an industrial enclosure to reduce the effects of electrical interference. Analog inputs and outputs are highly susceptible to electrical noise. Electrical noise coupled to the analog inputs will reduce the performance (accuracy) of the module.
Group your modules to minimize adverse effects from radiated electrical noise and heat. Consider the following conditions when selecting a location for the analog module. Position the module:
• away from sources of electrical noise such as hard-contact switches, relays, and AC motor drives
• away from modules which generate significant radiated heat, such as the
1769-IA16. Refer to the module’s heat dissipation specification.
In addition, route shielded, twisted-pair analog input and output wiring away from any high voltage I/O wiring.
Protecting the Circuit Board from Contamination
The printed circuit boards of the analog modules must be protected from dirt, oil, moisture, and other airborne contaminants. To protect these boards, the system must be installed in an enclosure suitable for the environment. The interior of the enclosure should be kept clean and the enclosure door should be kept closed whenever possible.
The module can be attached to the controller or an adjacent I/O module before or after
mounting. For mounting instructions, see Panel Mounting Using the
Dimensional Template on page 2-7, or DIN Rail Mounting on page 2-8. To
Installation and Wiring 2-5
Figure 2.1 Assemble the Compact I/O System
3
4
2
1
6
1
5
1.
Disconnect power.
2.
Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3.
Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or to a controller).
4.
Move the module back along the tongue-and-groove slots until the bus connectors (2) line up with each other.
5.
Push the bus lever back slightly to clear the positioning tab (3). Use your fingers or a small screwdriver.
Publication 1769-UM002B-EN-P - July 2005
2-6 Installation and Wiring
Mounting
Publication 1769-UM002B-EN-P - July 2005
6.
To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.
ATTENTION
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
7.
Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before.
8.
Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the bus.
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage at power up.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation.
Figure 2.2 Space Requirements
Top
Side Side
Host Controller
Bottom
Installation and Wiring 2-7
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Figure 2.3 Panel Mounting Using the Dimensional Template
For more than 2 modules: (number of modules-1) X 35 mm (1,38 in.).
Refer to host controller documentation for this dimension.
35
(1.38)
28.5
(1.12)
132
(5.197)
122.6±0.2
(4.826±0.008)
NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.04 mm (0.016 in.).
Figure 2.4 Panel Mounting for the 1769-IF8 Using the Dimensional Template
Spacing for single-wide modules 35 mm (1.378 in).
Spacing for one-and-a-half-wide modules 52.5 mm (2.067 in).
Refer to host controller documentation for this dimension.
NOTE: Overall hole spacing tolerance: ±0.4 mm (0.016 in.)
Locate holes every 17.5 mm (0.689 in) to allow for a mix of single-wide and one-and-a-half-wide modules
(e.g., 1769-OA16).
Publication 1769-UM002B-EN-P - July 2005
2-8 Installation and Wiring
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template provided on
page 2-7. Due to module mounting hole tolerance, it is important to follow
these procedures:
1.
On a clean work surface, assemble no more than three modules.
2.
Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel.
3.
Return the assembled modules to the clean work surface, including any previously mounted modules.
4.
Drill and tap the mounting holes for the recommended M4 or #8 screw.
5.
Place the modules back on the panel, and check for proper hole alignment.
6.
Attach the modules to the panel using the mounting screws.
TIP
If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
7.
Repeat steps 1 to 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-9
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or DIN rail). Follow these steps in order:
1.
Remove power. See important note on 2-4.
2.
On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches using a flat-blade or phillips-style screwdriver).
3.
Move the bus lever to the right to disconnect (unlock) the bus.
4.
On the right-side adjacent module, move its bus lever to the right
(unlock) to disconnect it from the module to be removed.
5.
Gently slide the disconnected module forward. If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
TIP
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
6.
Before installing the replacement module, be sure that the bus lever on the module to be installed and on the right-side adjacent module are in the unlocked (fully right) position.
7.
Slide the replacement module into the open slot.
8.
Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module.
9.
Replace the mounting screws (or snap the module onto the DIN rail).
Publication 1769-UM002B-EN-P - July 2005
2-10 Installation and Wiring
External Power Switch
The analog modules have an external 24V dc power switch which gives you the option of using an external power supply. The switch is located in on the lower left portion of the module’s circuit board, as shown below. With the switch pressed on the top (default), 24V dc power is drawn from the 1769 system power supply via the 1769 I/O bus. Pressed on the bottom, 24V dc power is drawn from the external power supply.
Wire the external power supply to the module via the module’s terminal block.
The external power supply must be Class 2 rated, with a 24V dc range of 20.4 to 26.4V dc and a minimum current rating that meets the needs of the modules
used in your application. Refer to Maximum Current Draw on page 2-2.
IMPORTANT
Only 1769-IF4 and -OF2 Series B modules have the 24V dc power switch.
Figure 2.5 External Power Switch
1769-IF4 and -OF2 Modules 1769-OF8C and -OF8V Modules
External Power
Supply Switch
External Power Switch
Pressed on the Top
Bus Power (default)
Pressed on the Bottom
External Power Bus Power (default)
External Power
Field Wiring Connections
Grounding
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding
Guidelines , Allen-Bradley publication 1770-4.1, for additional information.
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-11
System Wiring Guidelines
Consider the following when wiring your system:
General
• All module commons (ANLG COM) are connected in the analog module. The analog common (ANLG COM) is not connected to earth ground inside the module.
• Channels are not isolated from each other.
• Do not use the analog module’s NC terminals as connection points.
• To ensure optimum accuracy, limit overall cable impedance by keeping your cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit.
• Use Belden™ 8761, or equivalent, shielded wire.
• Keep shield connection to ground as short as possible.
• Under normal conditions, the drain wire and shield junction must be connected to earth ground via a panel or DIN rail mounting screw at the analog I/O module end.
(1)
1769-IF4 and -IF8 Input Modules
• If multiple power supplies are used with analog inputs, the power supply commons must be connected together.
• The 1769-IF4 and -IF8 modules do not provide loop power for analog inputs. Use a power supply that matches the input transmitter specifications.
• Differential analog inputs are more immune to noise than single-ended analog inputs.
• Voltages on Vin+, V/Iin-, and Iin+ of the 1769-IF4 and -IF8 modules must be within ±10V dc of analog common.
1769-OF2, -OF8C, and -OF8V Output Modules
• Voltage outputs (Vout 0+ and Vout 1+ for 1769-OF2, Vout 0+ through Vout 7+ for 1769-OF8V) of the output modules are referenced to ANLG COM. Load resistance for a voltage output channel must be equal to or greater than 1K Ω .
• Current outputs (Iout 0+ and Iout 1+ for 1769-OF2, Iout 0+ through
Iout 7+ for 1769-OF8C) of the output modules source current that returns to ANLG COM. Load resistance for a current output channel must remain between 0 and 500 Ω .
(1)
In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth at the module end and via a 0.1µF capacitor at the sensor end.
Publication 1769-UM002B-EN-P - July 2005
2-12 Installation and Wiring
Effect of Transducer/Sensor and Cable Length Impedance on Voltage Input
Accuracy
For voltage inputs, the length of the cable used between the transducer/sensor and the 1769-IF4 or -IF8 module can affect the accuracy of the data provided by the module.
Figure 2.6 Voltage Input Accuracy
Rs Rc
Vs
+
-
V in
Ri
Rc
Where:
Rc = DC resistance of the cable (each conductor) depending on
cable length
Rs = Source impedance of analog transducer/sensor input
Ri = Impedance of the voltage input
(220 K Ω for 1769-IF4 and -IF8)
Vs = Voltage source
(voltage at the transducer/sensor input device)
Vin = Measured potential at the module input
%Ai = Percent added inaccuracy in a voltage-based system due
to source and cable impedance.
Vin =
[
Rs +
[
(
Ri
2
×
×
Vs
Rc
)
]
+ Ri
]
For example, for Belden 8761 two conductor, shielded cable:
Rc = 16 Ω /1000 ft
Rs = 0 (ideal source)
% Ai =
⎛
⎝ 1
∠ ---------
Vs
⎞
âŽ
×
100
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-13
Table 2.2 Effect of Cable Length on Input Accuracy
Length of Cable (m)
50
100
200
300 dc resistance of the cable,
2.625
5.25
10.50
15.75
Rc (
Ω
)
Accuracy impact at the input module
0.00238%
0.00477%
0.00954%
0.0143%
As input source impedance (Rs) and/or resistance (dc) of the cable (Rc) get larger, system accuracy decreases. If you determine that the inaccuracy error is significant, implementing the following equation in the control program can compensate for the added inaccuracy error due to the impedance of the source and cable.
Vs = Vin
×
[
Rs + 2
×
Rc
Ri
)
+ Ri
]
TIP
In a current loop system, source and cable impedance do not impact system accuracy.
Effect of Device and Cable Output Impedance on Output Module Accuracy
The maximum value of the output impedance is shown in the example below, because it creates the largest deviation from an ideal voltage source.
Figure 2.7 Output Module Accuracy
Rs Rc
+
Vs
-
V in
Ri
Rc
Where:
Rc = DC resistance of the cable (each conductor)
depending on cable length
Rs = Source impedance
(15 Ω for 1769-OF2 and 1 Ω for 1769-OF8V)
Ri = Impedance of the voltage input
(220 K Ω for 1769-IF4)
Vs = Voltage at the output of 1769-OF2
Vin = Measured potential at the module input
%Ai = Percent added inaccuracy in a voltage-based
system due to source and cable impedance.
Vin =
[
Rs +
[
(
Ri
×
Vs
2
×
Rc
)
]
+ Ri
]
Publication 1769-UM002B-EN-P - July 2005
2-14 Installation and Wiring
For example, for Belden 8761 two conductor, shielded cable and a 1769-IF4 input module:
Rc = 16 Ω /1000 ft
Rs = 15 Ω
Ri = 220 K Ω
% Ai =
⎛
⎝ 1
∠ ---------
Vs
⎞
âŽ
×
100
Table 2.3 Effect of Output Impedance and Cable Length on Accuracy
Length of Cable (m)
50
100
200
300 dc resistance of the cable
Rc (
Ω
)
2.625
5.25
10.50
15.75
Accuracy impact at the input module
0.00919%
0.01157%
0.01634%
0.02111%
As output impedance (Rs) and/or resistance (dc) of the cable (Rc) get larger, system accuracy decreases. If you determine that the inaccuracy error is significant, implementing the following equation in the control program can compensate for the added inaccuracy error due to the impedance of the output module and cable.
Vs = Vin
×
[
Rs + 2
×
Rc
)
+ Ri
]
Ri
TIP
In a current loop system, source and cable impedance do not impact system accuracy.
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-15
Labeling the Terminals
A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
Figure 2.8 Terminal Labels upper retaining screw wiring the finger-safe terminal block lower retaining screw
Removing the Finger-Safe Terminal Block
When wiring field devices to the module, it is not necessary to remove the terminal block. If you remove the terminal block, use the write-on label on the side of the terminal block to identify the module slot location and type. RTB position can be indicated by circling either the ‘R’ for right side or ‘L’ for left side.
Figure 2.9 Finger-Safe Terminal Block
SLOT # _____
MODULE TYPE ______
To remove the terminal block, loosen the upper and lower retaining screws.
The terminal block will back away from the module as you remove the screws.
When replacing the terminal block, torque the retaining screws to 0.46 Nm
(4.1 in-lbs).
Publication 1769-UM002B-EN-P - July 2005
2-16 Installation and Wiring
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1.
Loosen the terminal screws to be wired.
2.
Begin wiring at the bottom of the terminal block and move up.
3.
Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals accept a 6.35 mm (0.25 in.) spade lug.
TIP
The terminal screws are non-captive. Therefore, it is possible to use a ring lug [maximum 1/4 inch o.d. with a
0.139 inch minimum i.d. (M3.5)] with the module.
4.
Tighten the terminal screw making sure the pressure plate secures the wire. Recommended torque when tightening terminal screws is 0.68 Nm
(6 in-lbs).
TIP
If you need to remove the finger-safe cover, insert a screwdriver into one of the square, wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires.
Table 2.4 Terminal Wire Considerations
Wire Type
Solid Cu-90°C (194°F)
Stranded Cu-90°C (194°F)
Wire Size Terminal Screw
Torque
Retaining Screw
Torque
#14 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
#16 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-17
Wiring the Modules
ATTENTION
To prevent shock hazard, care should be taken when wiring the module to analog signal sources. Before wiring any analog module, disconnect power from the system power supply and from any other source to the analog module.
After the analog module is properly installed, follow the wiring procedure below. To ensure proper operation and high immunity to electrical noise, always use Belden™ 8761 (shielded, twisted-pair) or equivalent wire.
ATTENTION
When wiring an analog input, take care to avoid connecting a voltage source to a channel configured for current input.
Improper module operation or damage to the voltage source can occur.
Never connect a voltage or current source to an analog output channel.
Figure 2.10 Belden 8761 Wire cable
Cut foil shield and drain wire signal wire signal wire drain wire foil shield signal wire signal wire
Publication 1769-UM002B-EN-P - July 2005
2-18 Installation and Wiring
To wire your module follow these steps.
1.
At each end of the cable, strip some casing to expose the individual wires.
2.
Trim the signal wires to 2-inch lengths. Strip about 3/16 inch (5 mm) of insulation away to expose the end of the wire.
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up.
3.
At one end of the cable, twist the drain wire and foil shield together.
Under normal conditions, this drain wire and shield junction must be connected to earth ground, via a panel or DIN rail mounting screw at the analog I/O module end. Keep the length of the drain wire as short as possible.
In environments where high frequency noise may be present, it may be necessary to ground the cable shields to earth at the module end via a
0.1 µF capacitor at the sensor end for analog inputs and at the load end for analog outputs.
4.
At the other end of the cable, cut the drain wire and foil shield back to the cable.
5.
Connect the signal wires to the terminal block as shown in Analog Input
output device.
6.
Repeat steps 1 through 5 for each channel on the module.
Terminal Door Label
A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-19
Analog Input Modules Wiring
Figure 2.11 1769-IF4 Terminal Layout
V/I in 0 -
ANLG Com
V/I in 1 -
ANLG Com
V/I in 2 -
ANLG Com
V/I in 3 -
ANLG Com dc NEUT
V in 0 +
I in 0 +
V in 1 +
I in 1 +
V in 2 +
I in 2 +
V in 3 +
I in 3 +
+24V dc
D A N G E R
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
V in 0 +
V/I in 0 -
ANLG
Com
I in 0+
V in 1 +
V/I in 1 -
ANLG
Com
I in 1+
V in 2 +
V/I in 2 -
ANLG
Com
I in 2+
V in 3 +
V/I in 3 -
ANLG
Com
I in 3+
+24V dc dc NEUT
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
1769-IF4
Figure 2.12 1769-IF4 Wiring Diagram Showing Differential Inputs
Belden 8761 cable (or equivalent)
–
1769-IF4
V/I in 0 -
V in 0 +
Analog
Source
+
I in 0+
ANLG Com
V in 1 +
V/I in 1 -
ANLG Com
I in 1+ earth ground shield locally at the module
V in 2 +
V/I in 2 -
I in 2+
ANLG Com
V in 3 +
V/I in 3 -
ANLG Com dc NEUT
I in 3+
+24V dc
-
+
External 24V dc
Power Supply
(1)
(optional)
(2)
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum for a single input module.
(2 ) Series B and later modules provide this option.
Publication 1769-UM002B-EN-P - July 2005
2-20 Installation and Wiring
Figure 2.13 1769-IF4 Wiring Single-ended Sensor/Transmitter Types
1769-IF4 Terminal Block
Sensor/
Transmitter
Supply
-
+
+
Current
+
Transmitter
Signal
+
Voltage
Transmitter
Ground
Signal
Voltage
Transmitter
Ground
Signal
V in 0 +
V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
+24V dc dc NEUT
External 24V dc
Power Supply
(1)
(optional)
(2)
+
-
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum for a single input module.
(2 ) Series B and later modules provide this option.
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-21
Figure 2.14 1769-IF4 Wiring Mixed Transmitter Types
Signal
Single-ended
–
Voltage
Transmitter
+
–
Differential
Voltage
Transmitter
Supply
+
+
Signal
–
–
Differential
Current
Transmitter
Supply
+
–
Signal
+
2-Wire Current
Transmitter
+
Signal
1769-IF4 Terminal Block
V in 0 +
V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
+24V dc dc NEUT
Sensor/Transmi tter Supply
+
–
External 24V dc
Power Supply
(optional)
(1)
+
–
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum for a single input module.
(2) Series B and later modules provide this option.
Publication 1769-UM002B-EN-P - July 2005
2-22 Installation and Wiring
Figure 2.15 1769-IF8 Terminal Layout
V/I in 0-
ANLG Com
V/I in 1-
ANLG Com
V/I in 2-
ANLG Com
V/I in 3-
ANLG Com
NC
V in 0+
I in 0
V/I in 4-
ANLG Com
V in 1+
V/I in 5-
I in 1
V in 2+
ANLG Com
V/I in 6-
I in 2
ANLG Com
V in 3+
V/I in 7-
I in 3
ANLG Com
NC
NC
V in 4+
I in 4
V in 5+
I in 5
V in 6+
I in 6
V in 7+
I in 7
NC
Figure 2.16 1769-IF8 Wiring Differential Inputs
Belden 8761 cable (or equivalent)
–
V/I in 0-
ANLG Com
V/I in 1-
ANLG Com
V/I in 2-
ANLG Com
V/I in 3-
ANLG Com
NC
V in 0+
I in 0+
V in 1+
I in 1+
V in 2+
I in 2+
V in 3+
I in 3+
NC
+
earth ground the shield locally at the module
V/I in 4-
ANLG Com
V/I in 5-
ANLG Com
V/I in 6-
ANLG Com
V/I in 7-
ANLG Com
NC
WARNING -Do Not
Remove RTB Unless
Area is Non-Hazardous
V in 0+
V/I in 0-
I in 0+
ANLG Com
V in 1+
V/I in 1-
I in 1+
ANLG Com
V/I in 2-
V in 2+
I in 2+
ANLG Com
V in 3+
V/I in 3-
I in 3+
ANLG Com
NC
NC
V/I in 4-
ANLG Com
V/I in 5-
ANLG Com
V/I in 6-
ANLG Com
V/I in 7-
ANLG Com
NC
V in 4+
I in 4+
V in 5+
I in 5+
V in 6+
I in 6+
V in 7+
I in 7+
NC
1769-IF8 analog source
V in 4+
I in 4+
V in 5+
I in 5+
V in 6+
I in 6+
V in 7+
I in 7+
NC
–
+
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-23
Figure 2.17 1769-IF8 Wiring Single-Ended Sensor/Transmitter Types
1769-IF8 Terminal Block
Sensor/Tran smitter
Supply
(1)
+
-
Current
Transmitter
+
Signal
+
+
Voltage
Transmitter
Ground
Signal
Voltage
Transmitter
Ground
Signal
V in 0 +
V/I in 0 -
I in 0 +
ANLG C om
V in 1 +
V/I in 1 -
I in 1 +
ANLG C om
V in 2 +
V/I in 2 -
I in 2 +
ANLG C om
V in 3 +
V/I in 3 -
I in 3 +
ANLG C om
NC
NC
Wiring for channels 4-7 are identical.
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum for a single input module.
Figure 2.18 1769-IF8 Wiring Mixed Transmitter Types
1769-IF8 Terminal Block
Single-ended
Voltage
Signal
V in 0 +
Transmitter (1)
– +
V/I in 0 -
Differential
Voltage
+
–
Signal
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
–
Transmitter
Supply +
I in 1 +
ANLG Com
Differential
Current
–
Transmitter
Supply +
–
Signal
+
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
2-Wire
Current
Transmitter
Signal
+
ANLG Com
NC
NC
Sensor/
Transmitter
Supply
+
–
Wiring for channels 4-7 are identical.
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum for a single input module.
Publication 1769-UM002B-EN-P - July 2005
2-24 Installation and Wiring
Analog Output Modules Wiring
Figure 2.19 1769-OF2 Terminal Layout
I out 0 +
NC
I out 1 +
NC dc Neutral
V out 0 +
ANLG Com
V out 1 +
ANLG Com
+24V dc
Figure 2.20 1769-OF2 Wiring Diagram
Voltage Load earth ground
Current Load
External 24V dc
Power Supply
(optional)
(1) -
+ earth ground
D A N G E R
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
V in 0 +
V in 0 -
ANLG
Com 0
I in 0
V out 0 +
I out 0 +
ANLG Com
NC
V out 1 +
I out 1 +
ANLG Com
NC
+24V dc dc NEUT
ANLG
Com 3
I in 3
NC
NC
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
1769-OF2
1769-OF2 Terminal Block
V out 0 +
I out 0 +
ANLG Com
NC
V out 1 +
I out 1 +
ANLG Com
NC
+24V dc dc NEUT
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 120 mA minimum per output module.
Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-25
Figure 2.21 1769-OF8C Terminal Layout
I out 0+
I out 1+
I out 2+
I out 3+
I out 4+
I out 5+
I out 6+
I out 7+
+24V dc
Figure 2.22 1769-OF8C Wiring Diagram
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com dc NEUT
D A N G E R
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
ANLG
I out 0+ C om
I out 1+
ANLG
C om
I out 2+
ANLG
C om
I out 3+
ANLG
C om
I out 4+
ANLG
C om
I out 5+
ANLG
C om
I out 6+
ANLG
C om
I out 7+
ANLG
C om
+24V dc dc NEUT
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
1769-OF8C
Current Load earth ground
External 24V dc Power +
Supply (optional)(1)
-
I out 0+
I out 1+
I out 2+
I out 3+
I out 4+
I out 5+
I out 6+
I out 7+
+24V dc
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com dc NEUT
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 120 mA minimum per output module.
Publication 1769-UM002B-EN-P - July 2005
2-26 Installation and Wiring
Figure 2.23 1769-OF8V Terminal Layout
V out 0+
V out 1+
V out 2+
V out 3+
V out 4+
V out 5+
V out 6+
V out 7+
+24V dc
Figure 2.24 1769-OF8V Wiring Diagram
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com dc NEUT
D A N G E R
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
V out 0+
ANLG
C om
V out 1+
ANLG
C om
V out 2+
ANLG
C om
ANLG
V out 3+
C om
V out 4+
ANLG
C om
V out 5+
ANLG
C om
V out 6+
ANLG
C om
V out 7+
ANLG
C om
+24V dc dc NEUT
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
1769-OF8V
Voltage Load earth ground
External 24V dc Power +
Supply (optional)(1)
-
V out 0+
V out 1+
V out 2+
V out 3+
V out 4+
V out 5+
V out 6+
V out 7+
+24V dc
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com
ANLG Com dc NEUT
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 120 mA minimum per output module.
Publication 1769-UM002B-EN-P - July 2005
1
Module Data, Status, and Channel
Configuration for the Input Modules
Chapter
3
1769-IF4 Input Module
Addressing
slot e
Input Image
Output Image
File slot e
Configuration
File
This chapter examines the analog input modules’ data table, channel status, and channel configuration word. The 1769-IF4 module information follows.
For 1769-IF8 module information, see page 3-16.
The 1769-IF4 memory map shows the input and configuration image tables for the 1769-IF4. Detailed information on the input image table can be found
in 1769-IF4 Input Data File on page 3-2.
Figure 3.1 1769-IF4 Memory Map
Memory Map
Channel 0 Data Word
Channel 1 Data Word
Channel 2 Data Word
Input Image
6 words
Channel 3 Data Word
General Status Bits
Over-/Under-range Bits
Word 0
Word 1
Word 2
Word 3
Word 4, bits 0 to 3
Word 5, bits 0 to 15
Configuration
File
4 words
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
Bit 15 Bit 0
Word 0
Word 1
Word 2
Word 3
Publication 1769-UM002B-EN-P - July 2005
3-2 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF4 Input Image
The 1769-IF4 input image file represents data words and status bits. Input words 0 through 3 hold the input data that represents the value of the analog inputs for channels 0 through 3. These data words are valid only when the channel is enabled and there are no errors. Input words 4 and 5 hold the status bits. To receive valid status information, the channel must be enabled.
TIP
You can access information in the input image file using the programming software configuration screen.
1769-IF4 Configuration File
The configuration file contains information that you use to define the way a specific channel functions. The configuration file is explained in more detail in
1769-IF4 Configuration Data File on page 3-4.
TIP
Not all controllers support program access to the configuration file. Refer to your controller’s user manual.
1769-IF4 Input Data File
Word/Bit
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
The input data table lets you access analog input module read data for use in the control program, via word and bit access. The data table structure is shown in table below.
Table 3.1 1769-IF4 Input Data Table
15
SGN
14 13 12 11 10 9 8 7 6 5
Analog Input Data Value Channel 0
4 3 2 1 0
SGN
SGN
SGN
Analog Input Data Value Channel 1
Analog Input Data Value Channel 2
Analog Input Data Value Channel 3
Not Used (Bits set to 0)
U0 O0 U1 O1 U2 O2 U3 O3
S3 S2 S1 S0
Set to zero
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-3
1769-IF4 Input Data Values
Words 0 through 3 contain the converted analog input data from the field device. The most significant bit (MSB) is the sign bit.
General Status Bits (S0 through S3)
Word 4, bits 0 through 3 contain the general operational status bits for input channels 0 through 3. If set (1), these bits indicate an error associated with that channel. The over- and under-range bits for channels 0 through 3 are logically
ORed to the appropriate general status bit.
Over-Range Flag Bits (O0 through O3)
Over-range bits for channels 3 through 0 are contained in word 5, bits 8, 10,
12, and 14. They apply to all input types. When set (1), this bit indicates input signals beyond the normal operating range. However, the module continues to convert analog data to the maximum full range value. The bit is automatically reset (0) by the module when the over-range condition is cleared and the data value is within the normal operating range.
Under-Range Flag Bits (U0 through U3)
Under-range bits for channels 3 through 0 are contained in word 5, bits 9, 11,
13, and 15. They apply to all input types. When set (1), this bit indicates input signals below the normal operating range. It may also indicate an open circuit condition, when the module is configured for the 4 to 20 mA range. However, the module continues to convert analog data to the minimum full range value.
The bit is automatically reset (0) by the module when the under-range condition is cleared and the data value is within the normal operating range.
Publication 1769-UM002B-EN-P - July 2005
3-4 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF4 Configuration Data
File
The configuration file lets you determine how each individual input channel will operate. Parameters such as the input type and data format are set up using this file. This data file is writable and readable. The default value of the configuration data table is all zeros. The structure of the channel configuration file is shown below.
Table 3.2 1769-IF4 Configuration Data Table
(1)
Word/Bit
Word 0
Word 1
Word 2
Word 3
15
Enable Channel 0
Enable Channel 1
Enable Channel 2
Enable Channel 3
14 13 12
Input Data Format
Select Channel 0
Input Data Format
Select Channel 1
Input Data Format
Select Channel 2
Input Data Format
Select Channel 3
11 10 9
Input Type/Range
Select Channel 0
8
Input Type/Range
Select Channel 1
Input Type/Range
Select Channel 2
Input Type/Range
Select Channel 3
7 6 5
Reserved
Reserved
Reserved
Reserved
4
(1)
The ability to change these values using your control program is not supported by all controllers. Refer to your controller manual for details.
3 2 1
Input Filter Select
Channel 0
0
Input Filter Select
Channel 1
Input Filter Select
Channel 2
Input Filter Select
Channel 3
The configuration file is typically modified using the programming software configuration screen. For information on configuring the module using
MicroLogix 1500 and RSLogix 500, see Appendix B; for CompactLogix and
RSLogix 5000, see Appendix C; for 1769-ADN DeviceNet Adapter and
The configuration file can also be modified through the control program, if supported by the controller. The structure and bit settings are shown in
Channel Configuration on page 3-5.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-5
Channel Configuration
Each channel configuration word consists of bit fields, the settings of which determine how the channel operates. See the table below and the descriptions that follow for valid configuration settings and their meanings. The default bit status of the configuration file is all zeros.
Table 3.3 Bit Definitions for Channel Configuration Words 0 through 3
Bit(s)
0 to 3
4 to 7
8 to
11
12 to
14
15
Reserved
Input Type/Range
Select
Define
Input Filter Select
Input Data
Format Select
Enable Channel 1
0
These bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Indicate this
0 0 0 0 60 Hz
0 0 0 1 50 Hz
0 0 1 0 Not Used
0 0 1 1 250 Hz
0 1 0 0 500 Hz
Not Used
(1)
Reserved
(2)
-10 to +10V dc 0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
Not Used
0
0
0
0
0
0
1
1
0
1
0
1
0 to 5V dc
0 to 10V dc
4 to 20 mA
1 to 5V dc
0 to 20 mA
Not Used
Raw/Proportional Data
Engineering Units
Scaled for PID
(3)
Percent Range
Not Used
Enabled
Disabled
(1)
(2)
If reserved bits are not equal to zero, a configuration error occurs.
(3)
This range is applicable to the PID function of the MicroLogix 1500 packaged controller, PLC, or SLC controllers. Logix controllers can use this or one of the other ranges for their PID functions.
Publication 1769-UM002B-EN-P - July 2005
3-6 Module Data, Status, and Channel Configuration for the Input Modules
Enable/Disable Channel
This configuration selection lets each channel to be individually enabled.
TIP
When a channel is not enabled (0), no voltage or current input is provided to the controller by the A/D converter.
Input Filter Selection
The input filter selection field lets you select the filter frequency for each channel and provides system status of the input filter setting for analog input channels 0 through 3. The filter frequency affects the noise rejection characteristics, as explained below. Select a filter frequency considering acceptable noise and step response time.
Noise Rejection
The 1769-IF4 uses a digital filter that provides noise rejection for the input signals. The filter is programmable, allowing you to select from four filter frequencies for each channel. The digital filter provides the highest noise rejection at the selected filter frequency. A lower frequency (60 Hz versus 250
Hz) can provide better noise rejection but it increases channel update time.
Transducer power supply noise, transducer circuit noise, or process variable irregularities may also be sources of normal mode noise.
Common Mode Rejection is better than 60 dB at 50 and 60 Hz, with the 50 and 60 Hz filters selected, respectively. The module performs well in the presence of common mode noise as long as the signals applied to the user plus and minus input terminals do not exceed the common mode voltage rating (±
10 V) of the module. Improper earth ground may be a source of common mode noise.
Channel Step Response
The selected channel filter frequency determines the channel’s step response.
The step response is the time required for the analog input signal to reach
100% of its expected final value. This means that if an input signal changes faster than the channel step response, a portion of that signal will be attenuated by the channel filter.
Table 3.4 Filter Frequency and Step Response
Filter Frequency
50 Hz
60 Hz
250 Hz
500 Hz
Cut-off Frequency
13.1 Hz
15.7 Hz
65.5 Hz
131 Hz
Step Response
60 ms
50 ms
12 ms
6 ms
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-7
Channel Cut-Off Frequency
The -3 dB frequency is the filter cut-off frequency. The cut-off frequency is defined as the point on the frequency response curve where frequency components of the input signal are passed with 3 dB of attenuation. All input frequency components at or below the cut-off frequency are passed by the digital filter with less than 3 dB of attenuation. All frequency components above the cut-off frequency are increasingly attenuated as shown in the graphs below.
The cut-off frequency for each channel is defined by its filter frequency selection. Choose a filter frequency so that your fastest changing signal is below that of the filter’s cut-off frequency. The cut-off frequency should not be confused with the update time. The cut-off frequency relates to how the digital filter attenuates frequency components of the input signal. The update time defines the rate at which an input channel is scanned and its channel data word is updated.
0
–20
–40
–60
–80
–100
–120
–140
–160
–180
–200
0
13.1 Hz
–3 dB
Figure 3.2 Frequency Response Graphs
50 Hz Input Filter Frequency
0
–20
50 100 150
Frequency (Hz)
200 250 300
60 Hz Input Filter Frequency
–3 dB
–40
–60
–80
–100
–120
–140
–160
–180
–200
0
15.72 Hz
60 120 180
Frequency (Hz)
240 300 360
0
–20
–40
–60
–80
–100
–120
–140
–160
–180
–200
0
65.5 Hz
250 Hz Input Filter Frequency
–3 dB
250 500 750
Frequency (Hz)
900 1150 1300
–80
–100
–120
–140
–160
–180
0
–20
–40
–60
–200
0
131 Hz
500
500 Hz Input Filter Frequency
–3 dB
1000 1500
Frequency (Hz)
2000 2500 3000
Publication 1769-UM002B-EN-P - July 2005
3-8 Module Data, Status, and Channel Configuration for the Input Modules
Module Update Time and Scanning Process
The module update time is defined as the time required for the module to sample and convert the input signals of all enabled input channels and provide the resulting data values to the processor. Module update time can be calculated by adding the sum of all enabled channel times. Channel times include channel scan time, channel switching time, and reconfiguration time.
The module sequentially samples the channels in a continuous loop.
Figure 3.3 Sequential Sampling
Channel 1 Disabled Channel 2 Disabled Channel 3 Disabled Channel 0 Disabled
Enabled
Sample
Channel 0 Enabled
Sample
Channel 1 Enabled
Sample
Channel 2 Enabled
Sample
Channel 3
Table 3.5 shows the channel update times. The fastest module update time
occurs when only one channel is enabled with a 500 Hz filter (4 ms). If more than one channel is enabled, the update time is faster if both channels have the
same configuration. See the first example on page 3-9. The slowest module
update time occurs when all four channels are enabled with different
configurations. See the second example on page 3-9.
Table 3.5 Channel Update Time
Filter Frequency
50 Hz
60 Hz
250 Hz
500 Hz
Channel Update Time
22 ms
19 ms
6 ms
4 ms
Channel Switching and Reconfiguration Times
The table below provides the channel switching and reconfiguration times for a channel.
Channel Switching
Time
Channel-to-Channel
Reconfiguration Time
Description
Table 3.6 Channel Switching and Reconfiguration Times
50 Hz
46 ms
Duration
60 Hz 250 Hz 500 Hz
39 ms 14 ms 10 ms The time it takes the module to switch from one channel to another.
The time it takes the module to change its configuration settings for a difference in configuration between one channel and another.
116 ms 96 ms 20 ms 8 ms
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-9
Examples of Calculating Module Update Time
EXAMPLE
1. Two Channels Enabled with Identical Configurations
The following example calculates the 1769-IF4 module update time for two channels enabled with the same configuration and a 500 Hz filter.
Module Update Time = [Ch 0 Update Time + Ch 0 Switching Time] + [Ch 1 Update Time + Ch 1 Switching Time]
28 = [4 ms + 10 ms] + [4 ms + 10 ms]
EXAMPLE
2. Three Channels Enabled with Different Configurations
The following example calculates the module update time for three channels with the following configurations:
• Channel 0: ±10V dc with 60 Hz filter
• Channel 1: ±10V dc with 500 Hz filter
• Channel 2: 4 to 20 mA with 250 Hz filter
Module Update Time =[Ch 0 Reconfiguration Time + Ch 0 Update Time + Ch 0 Switching Time]
+
[Ch 1 Reconfiguration Time + Ch 1 Update Time + Ch 1 Switching Time]
+
[Ch 2 Reconfiguration Time + Ch 2 Scan Time + Ch 2 Switching Time]
216 =
[
96 ms + 19 ms + 39 ms
]
+
[
8 ms + 4 ms + 10 ms
]
+
[
20 ms + 6 ms + 14 ms
]
Input Type/Range Selection
This selection along with proper input wiring lets you configure each channel individually for current or voltage ranges and provides the ability to read the current range selections.
Publication 1769-UM002B-EN-P - July 2005
3-10 Module Data, Status, and Channel Configuration for the Input Modules
Input Data Selection Formats
This selection configures channels 0 through 3 to present analog data in any of the following formats:
• Raw/Proportional Data
• Engineering Units
• Scaled-for-PID
• Percent Range
Raw/Proportional Data
The value presented to the controller is proportional to the selected input and scaled into the maximum data range allowed by the bit resolution of the A/D converter and filter selected. The full range for a ±10Vdc user input is -32767
to +32767. See Table 3.7 Valid Input Data on page 3-11.
Engineering Units
The module scales the analog input data to the actual current or voltage values for the selected input range. The resolution of the engineering units is
dependent on the range selected and the filter selected. See Table 3.7 Valid
Scaled-for-PID
The value presented to the controller is a signed integer with zero representing the lower user range and 16383 representing the upper user range.
Allen-Bradley controllers, such as the MicroLogix 1500, use this range in their
PID equations. The amount over and under user range (full scale range -410 to
16793) is also included. See Table 3.7 Valid Input Data on page 3-11.
Percent Range
The input data is presented as a percentage of the user range. For example, 0V to 10V dc equals 0% to 100%.
TIP
The ±10V dc range does not support the percent user range data format.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-11
Valid Input Data Word Formats/Ranges
The following table shows the valid formats and min./max. data ranges provided by the module.
Table 3.7 Valid Input Data
1769-IF4 Input
Range
-10V to +10V dc
0V to 5V dc
Input Value
Over 10.5V dc
+10.5V dc
-10V to +10V dc
-10.5Vdc
Under -10.5V dc
Over 5.25V dc
5.25V dc 5.25V dc
0.0V dc to 5.0V dc 5.0V dc
-0.5V dc
0.0V dc
-0.5V dc
Example
Data
-10.0V dc
-10.5V dc
-11.0V dc
5.5V dc
Input
Range
Condition
+11.0V dc Over-range
+ 10.5V dc Over-range
+10.0V dc Normal
0.0V dc Normal
Normal
Under-range
Raw/Propor tional Data
Decimal
Range
Engineering
Unit
Decimal
Range
Scaled-for-
PID
Decimal
Range
32767 (max.) 10500 (max.) 16793 (max.)
32767 (max.) 10500 (max.) 16793 (max.)
31206
0
-31206
-32767 (min.)
10000
0
-10000
-10500 (min.)
16383
8192
0
-410 (min.)
Percent
Full Range
Decimal
Range
N/A
N/A
N/A
N/A
N/A
N/A
Under-range -32767 (min.) -10500 (min.) -410 (min.)
Over-range 32767 (max.) 5250 (max.) 17202 (max.)
N/A
10500 (max.)
Over-range
Normal
Normal
32767 (max.) 5250 (max.)
31206
0
Under-range -3121 (min.)
5000
0
-500 (min.)
17202 (max.)
16383
0
10500 (max.)
10000
0
-1638 (min.) -1000 (min.)
0V to 10V dc
4 mA to 20 mA
Under -0.5V dc
Over 10.5V dc
+10.5V dc 10.5V dc
0.0V dc to 10.0V dc 10.0V dc
-0.5V dc
Under -5.0V dc
Over 21.0 mA
21.0 mA
22.0 mA
21.0 mA
4.0 mA to 20.0 mA 20.0 mA
3.2 mA
Under 3.2 mA
-1.0V dc
11.0V dc
0.0V dc
-0.5V dc
-1.0V dc
4.0 mA
3.2 mA
0.0 mA
Under-range -3121 (min.)
Over-range 32767 (max.)
-500 (min.)
10500 (max.)
-1638 (min.)
17202 (max.)
-1000 (min.)
10500 (max.)
Over-range
Normal
32767 (max.)
31206
10500 (max.)
10000
17202 (max.)
16383
10500 (max.)
10000
Normal 0
Under-range -1560 (min.)
Under-range -1560 (min.)
Over-range
Over-range
Normal
0
-500 (min.)
-500 (min.)
0
-819 (min.)
-819 (min.)
0
-500 (min.)
-500 (min.)
32767 (max.) 21000 (max.) 17407 (max.) 10625 (max.)
32767 (max.) 21000 (max.) 17407 (max.) 10625 (max.)
31206 20000 16383 10000
Normal 6241
Under-range 4993 (min.)
Under-range 4993 (min.)
4000
3200 (min.)
3200 (min.)
0
-819 (min.)
-819 (min.)
0
-500 (min.)
-500 (min.)
Publication 1769-UM002B-EN-P - July 2005
3-12 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF4 Input
Range
1.0V to 5V dc
0 mA to 20 mA
Input Value
Over 5.25V dc
+5.25V dc
1.0V to 5.0V dc
0.5V dc
Under 0.5V dc
Over 21.0 mA
21.0 mA 21.0 mA
0.0 mA to 20.0 mA 20.0 mA
Under 0.0 mA
0.0 mA
0.0 mA
5.5V dc
5.25V dc
5.0V dc
1.0V dc
0.5V dc
0.0V dc
22.0 mA
Table 3.7 Valid Input Data
Example
Data
Input
Range
Condition
Raw/Propor tional Data
Decimal
Range
Engineering
Unit
Decimal
Range
32767 (max.) 5250 Over-range
Over-range
Normal
32767 (max.) 5250
31206 5000
Normal 6243
Under-range 3121 (min.)
1000
500
Under-range 3121 (min.)
Over-range 32767
Over-range
Normal
32767
31206
Normal 0
Under-range 0
500
21000
21000
20000
0
0
0
0
-2048
17202
17202
16383
Scaled-for-
PID
Decimal
Range
17407
17407
16383
1
-2048
0
0
-1250
10500
10500
10000
Percent
Full Range
Decimal
Range
10625
10625
10000
1
-1250
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-13
Effective Resolution
The effective resolution for an input channel depends upon the filter frequency selected for that channel. The following tables provide the effective resolution for the four frequencies for each of the range selections.
1769-IF4
Input
Range
Bits and
Engineering
Units
Resolution
Decimal
Range and
Count Value
-10 to
+10V dc
Sign +14
0.64 mV/
2 counts
0 to +5V dc Sign +13
0.64 mV/
4 counts
0 to +10V dc Sign +14
0.64 mV/
2 counts
+4 to
+20 mA
Sign +14
1.28 µA/
2 counts
+1 to +5V dc Sign +13
0.64 mV/
4 counts
0 to +20 mA Sign +14
1.28 µA/
2 counts
Raw/Proportional Data
Over the Full Input Range
±32767
Count by 2
-3121 to
+32767
Count by 4
-1560 to
+32767
Count by 2
+4993 to
+32767
Count by 2
+3121 to
+32767
Count by 4
0 to +32767
Count by 2
Table 3.8 50Hz / 60Hz Effective Resolution
Engineering Units Over the Full Input Range
Resolution Decimal
Range and
Count
Value
1.00 mV/
1 count
±10500
Count by 1
1.00 mV/
1 count
1.00 mV/
1 count
2.00 µA/
2 counts
1.00 mV/
1 count
2.00 µA/
2 counts
-500 to
+5250
Count by 1
-500 to
+10500
Count by 1
+3200 to
+2100
Count by 2
+500 to
+5250
Count by 1
0 to
+21000
Count by 2
Scaled-For-PID Over the Full Input Range
Resolution Decimal
Range and
Count
Value
1.22 mV/
1 count
-410 to
+16793
Count by 1
0.92 mV/
3 counts
1.22 mV/
2 counts
-1638 to
+17202
Count by 3
-819 to
+17202
Count by 2
1.95 µA/
2 counts
0.73 mV/
3 counts
2.44 µA/
2 counts
-819 to
+17407
Count by 2
-2048 to
+17407
Count by 3
0 to
+17202
Count by 2
Percent
Over the Full Input
Range
Resolution Decimal
Range and
Count
Value
Not
Applicable
Not
Applicable
1.00 mV/
2 counts
1.00 mV/
1 count
1.60 µA/
1 count
0.80 mV/
2 counts
2.00 µA/
1 count
-1000 to
+10500
Count by 2
-500 to
+10500
Count by 1
-500 to
+10625
Count by 1
-1250 to
+10625
Count by 2
0 to
+10500
Count by 1
Publication 1769-UM002B-EN-P - July 2005
3-14 Module Data, Status, and Channel Configuration for the Input Modules
-10 to
+10V dc
0 to
+5V dc
0 to
+10V dc
+4 to
+20 mA
+1 to
+5V dc
0 to
+20 mA
1769-IF4
Input
Range
Raw/Proportional Data
Over the Full Input Range
Bits and
Engineering
Units
Resolution
Sign +11
5.13 mV/
16 counts
Sign +10
5.13 mV/
32 counts
Sign +11
5.13 mV/
16 counts
Sign +11
10.25 µA/
16 counts
Sign +10
5.13 mV/
32 counts
Sign +11
10.25 µA/
16 counts
Decimal
Range and
Count
Value
±32767
Count by 16
-3121 to
+32767
Count by 32
-1560 to
+32767
Count by 16
+4993 to
+32767
Count by 2
+3121 to
+32767
Count by 32
0 to +32767
Count by 16
Table 3.9 250Hz Effective Resolution
Engineering Units Over the Full Input Range
Resolution Decimal
Range and Count
Value
6.00 mV/
6 counts
±10500
Count by 6
6.00 mV/
6 counts
6.00 mV/
6 counts
11.00 µA/
11 counts
6.00 mV/
6 counts
11.00 µA/
11 counts
-500 to
+5250
Count by 6
-500 to
+10500
Count by 6
+3200 to
+2100
Count by 11
+500 to
+5250
Count by 6
0 to +21000
Count by 11
Scaled-For-PID Over the
Full Input Range
Resolution Decimal
Range and Count
Value
6.10 mV/
5 counts
-410 to
+16793
Count by 5
5.19 mV/
17 counts
5.49 mV/
9 counts
-1638 to
+17202
Count by 17
-819 to
+17202
Count by 9
10.74 µA/
11 counts
5.37 mV/
22 counts
10.99 µA/
9 counts
-819 to
+17407
Count by 11
-2048 to
+17407
Count by 22
0 to +17202
Count by 9
Percent
Over the Full Input
Range
Resolution Decimal
Range and
Count
Value
Not
Applicable
Not
Applicable
5.50 mV/
11 counts
6.00 mV/
6 counts
11.20 µA/
7 counts
5.20 mV/
13 counts
12.00 µA/
6 counts
-1000 to
+10500
Count by 11
-500 to
+10500
Count by 6
-500 to
+10625
Count by 7
-1250 to
+10625
Count by 13
0 to +10500
Count by 6
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-15
1769-IF4
Input
Range
Raw/Proportional Data
Over the Full Input Range
-10 to
+10V dc
0 to
+5V dc
0 to
+10V dc
+4 to
+20 mA
+1 to
+5V dc
0 to
+20 mA
Bits and
Engineering
Units
Resolution
Sign +9
20.51 mV/
64 counts
Sign +8
20.51 mV/
128 counts
Sign +9
20.51 mV/
64 counts
Sign +9
41.02 µA/
64 counts
Sign +8
20.51 mV/
128 counts
Sign +9
41.02 µA/
64 counts
Decimal
Range and
Count
Value
±32767
Count by 64
-3121 to
+32767
Count by 128
-1560 to
+32767
Count by 64
+4993 to
+32767
Count by 64
+3121 to
+32767
Count by 128
0 to +32767
Count by 64
Table 3.10 500 Hz Effective Resolution
Engineering Units Over the Full Input Range
Resolution Decimal
Range and
Count
Value
21.00 mV/
21 counts
±10500
Count by 21
21.00 mV/
21 counts
21.00 mV/
21 counts
42.00 µA/
42 counts
21.00 mV/
21 counts
42.00 µA/
42 counts
-500 to
+5250
Count by 21
-500 to
+10500
Count by 21
+3200 to
+2100
Count by 42
+500 to
+5250
Count by 21
0 to +21000
Count by 42
Scaled-For-PID Over the
Full Input Range
Resolution Decimal
Range and
Count
Value
20.75 mV/
17 counts
-410 to
+16793
Count by 17
20.75 mV/
68 counts
20.75 mV/
34 counts
-1638 to
+17202
Count by 68
-819 to
+17202
Count by 34
41.02 µA/
42 counts
20.75 mV/
84 counts
41.51 µA/
-819 to
+17407
Count by 42
-2048 to
+17407
Count by 84
0 to +17202
Count by 34
34 counts
Percent
Over the Full Input
Range
Resolution Decimal
Range and
Count
Value
Not
Applicable
Not
Applicable
21.00 mV/
42 counts
21.00 mV/
21 counts
41.60 µA/
26 counts
20.8 mV/
52 counts
42.00 µA/
21 counts
-1000 to
+10500
Count by 42
-500 to
+10500
Count by 21
-500 to
+10625
Count by 26
-1250 to
+10625
Count by 52
0 to +10500
Count by 21
Publication 1769-UM002B-EN-P - July 2005
3-16 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF8 Input Module
Addressing
slot e
Input Image
File slot e
Output Image
File slot e
Configuration
File
The1769-IF8 memory map shows the output, input, and configuration tables for the 1769-IF8.
Figure 3.4 1769-IF8 Memory Map
Input Image
12 words
Memory Map
Channel 0 Data Word
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
Channel 4 Data Word
Channel 5 Data Word
Channel 6 Data Word
Channel 7 Data Word
Time Stamp Value Word
General Status Bits
High-/Low-Alarm & Over-/Under-Range
High-/Low-Alarm & Over-/Under-Range
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Word 9, bits 0-7
Word 10
Word 11
Output Image
1 word
Clear Latched Alarm Bits Word 0
Publication 1769-UM002B-EN-P - July 2005
Configuration File
50 words
Bit 15
Real Time Sample Rate
Enable Time Stamp
Channel 0 Configuration Words
Channel 1 Configuration Words
Channel 2 Configuration Words
Channel 3 Configuration Words
Channel 4 Configuration Words
Channel 5 Configuration Words
Channel 6 Configuration Words
Channel 7 Configuration Words
Bit 0
Word 0
Word 1, bit 15
Words 2-7
Words 8-13
Words 14-19
Words 20-25
Words 26-31
Words 32-37
Words 38-43
Words 44-49
Module Data, Status, and Channel Configuration for the Input Modules 3-17
1769-IF8 Input Image
The 1769-IF8 input image file represents data words and status bits. Input words 0 through 7 hold the input data that represents the value of the analog inputs for channels 0 through 7. These data words are valid only when the channel is enabled and there are no errors. Input words 9 and 11 hold the status bits. To receive valid status information, the channel must be enabled.
TIP
You can access information in the input image file using the programming software configuration screen.
1769-IF8 Output Image
The 1769-IF8 output image file contains the clear alarm control bits for the high- and low-alarm bits on each input channel. These bits are used to clear alarms when alarms are latched.
TIP
You can access information in the output image file using the programming software configuration screen.
1769-IF8 Configuration File
The configuration file contains information that you use to define the way a specific channel functions. The configuration file is explained in more detail in
1769-IF8 Configuration Data File on page 3-20.
TIP
Not all controllers support program access to the configuration file. Refer to your controller’s user manual.
Publication 1769-UM002B-EN-P - July 2005
3-18 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF8 Input Data File
The input data table lets you access analog input module read data for use in the control program, via word and bit access. The data table structure is shown in the table below. For each input module, slot x, words 0-7 in the input data file contain the analog values of the inputs.
Table 3.11 1769-IF8 Input Data Table
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 SGN Analog Input Data Channel 0
1 SGN
2 SGN
3 SGN
4 SGN
Analog Input Data Channel 1
Analog Input Data Channel 2
Analog Input Data Channel 3
Analog Input Data Channel 4
5 SGN
6 SGN
7 SGN
8 Nu
Analog Input Data Channel 5
Analog Input Data Channel 6
Analog Input Data Channel 7
Time Stamp Value
9 Nu Nu Nu Nu Nu Nu Nu Nu S7 S6 S5 S4 S3 S2 S1 S0
10 L3 H3 U3 O3 L2 H2 U2 O2 L1 H1 U1 O1 L0 H0 U0 O0
11 L7 H7 U7 O7 L6 H6 U6 O6 L5 H5 U5 O5 L4 H4 U4 O4
1769-IF8 Input Data Values
Words 0 through 7 contain the converted analog input data from the field device. The most significant bit (MSB) is the sign bit, which is in two’s complement format. (Nu indicates not used with the bit set to 0.)
General Status Bits (S0 through S7)
Word 9, bits 0 through 7 contain the general operational status bits for input channels 0 through 7. If set (1), these bits indicate an error associated with that channel. The over- and under-range bits and the high- and low-alarm bits for channels 0 through 7 are logically ORed to the appropriate general status bit.
Low Alarm Flag Bits (L0 through L7)
Word 10, bits 3, 7, 11, and 15 and Word 11, bits 3, 7, 11, 15 contain the low alarm flag bits for input channels 0 through 7. If set (1), these bits indicate the input signal is outside the user-defined range. The module continues to convert analog data to minimum full-range values. The bit is automatically reset (0) when the low alarm condition clears, unless the channel’s alarm bits are latched. If the channel’s alarm bits are latched, a set (1) low alarm flag bit clears via the corresponding Clear Alarm Latch bit in your output data file.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-19
High Alarm Flag Bits (H0 through H7)
Word 10, bits 2, 6, 10, 14 and Word 11, bits 2, 6, 10, 14 contain the high alarm flag bits for input channels 0 through 7 and applies to all input types. If set (1), the input signal is output the user-defined range. The module continues to convert analog data to maximum full-range values. The bit is automatically reset (0) when the high alarm condition clears, unless the channel’s alarm bits are latched. If the channel’s alarm bits are latched, a set (1) high alarm flag bit clears via the corresponding Clear Alarm Latch bit in your output data file.
Over-Range Flag Bits (O0 through O7)
Over-range bits for channels 0 through 7 are contained in Word 10, bits 0, 4, 8,
12 and Word 11, bits 0, 4, 8, 12. They apply to all input types. When set (1), this bit indicates input signals beyond the normal operating range. However, the module continues to convert analog data to the maximum full range value.
The bit is automatically reset (0) by the module when the over-range condition is cleared and the data value is within the normal operating range.
Under-Range Flag Bits (U0 through U7)
Under-range bits for channels 0 through 7 are contained in Word 10, bits 1, 5,
9, 13 and Word 11, bits 1, 5, 9, 13. They apply to all input types. When set (1), this bit indicates input signals below the normal operating range. It may also indicate an open circuit condition, when the module is configured for the 4 to
20 mA range. However, the module continues to convert analog data to the minimum full range value. The bit is automatically reset (0) by the module when the under-range condition is cleared and the data value is within the normal operating range.
Time Stamp Value (Word 8)
The 1769-IF8 supports a 15-bit rolling timestamp that is updated during each new sampling period of the analog inputs. The timestamp has a 1 ms resolution. The timestamp value is placed in the input image file, word 8, for each module input data update (if the timestamp function is enabled). Enable and/or disable this timestamp in the configuration file.
Publication 1769-UM002B-EN-P - July 2005
3-20 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF8 Output Data File
The output data table lets you access analog output module write data for use in the control program, via word and bit access. The data table structure is shown in the table below.
Table 3.12 1769-IF8 Output Data Table
0
15
CL
(1)
L7
Bit Position
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
CL
(2)
H7
CL
L6
CL
H6
CL
L5
CL
H5
CL
L4
CL
H4
CL
L3
CL
H3
CL
L2
CL
H2
CL
L1
CL
H1
CL
L0
CL
H0
(1)
CL Lx = Cancel Low Process Alarm Latch x. This lets you individually cancel each low process alarm latch.
Cancel = 1.
(2)
CL Hx = Cancel High Process Alarm Latch x. This lets you individually cancel each high process alarm latch.
These bits are written during run mode to clear any latched low- and high-process alarms. The alarm is unlatched when the unlatch bit is set (1) and the alarm condition no longer exists. If the alarm condition persists, then the unlatch bit has no effect until the alarm condition no longer exists. You need to keep the unlatch bit set until verification from the appropriate input channel status word that the alarm status bit has cleared (0). Then you need to reset (0) the unlatch bit. The module will not latch an alarm condition if a transition from no alarm to alarm occurs while a channel’s clear latch bit is set.
5
6
3
4
7
8
0
1
2
9
10
11
1769-IF8 Configuration Data
File
The configuration file lets you determine how each individual input channel will operate. Parameters such as the input type and data format are set up using this file. This data file is writable and readable. The default value of the configuration data table is all zeros. The structure of the channel configuration file is shown below.
15
ETS
EC
S
S
S
EC
S
S
14
Reserved
Reserved
Table 3.13 1769-IF8 Configuration Data Table
13 12 11 10
Bit Position
9 8 7 6
Reserved
Reserved
5
Real Time Sample Value
EA AL
Reserved
EI
(1) Reserved
Inpt Dta Fm Chl0 Reserved
Process Alarm High Data Value Channel 0
Process Alarm Low Data Value Channel 0
Alarm Dead Band Value Channel 0
Reserved
EA AL
Reserved
Inpt Dta Fm Chl1 Reserved
Process Alarm High Data Value Channel 1
Process Alarm Low Data Value Channel 1
4 3 2 1 0
Input Filter Sel Chl0
Inpt Tp/RngeSel Chl0
Inpt Filter Sel Chl1
Inpt Tp/RngeSel Chl1
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-21
39
40
41
42
43
44
33
34
35
36
37
38
45
46
47
48
49
27
28
29
30
31
32
21
22
23
24
25
26
15
16
17
18
19
20
12
13
14
S
EC
S
S
S
EC
S
S
S
EC
S
S
S
EC
S
S
S
EC
S
S
S
EC
S
S
S
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
(1)
CompactLogix L43 controllers will be able to support these interrupts.
Table 3.13 1769-IF8 Configuration Data Table
Alarm Dead Band Value Channel 1
Reserved
EA AL
Reserved
Inpt Dta Fm Chl2 Reserved
Process Alarm High Data Value Channel 2
Process Alarm Low Data Value Channel 2
Alarm Dead Band Value Channel 2
Reserved
EA AL
Reserved
Inpt Dta Fm Chl3 Reserved
Process Alarm High Data Value Channel 3
Process Alarm Low Data Value Channel 3
Alarm Dead Band Value Channel 3
Reserved
EA AL
Reserved
Inpt Dta Fm Chl4 Reserved
Process Alarm High Data Value Channel 4
Process Alarm Low Data Value Channel 4
Alarm Dead Band Value Channel 4
Reserved
EA AL
Reserved
Inpt Dta Fm Chl5 Reserved
Process Alarm High Data Value Channel 5
Process Alarm Low Data Value Channel 5
Alarm Dead Band Value Channel 5
Reserved
EA AL
Reserved
Inpt Dta Fm Chl6 Reserved
Process Alarm High Data Value Channel 6
Process Alarm Low Data Value Channel 6
Alarm Dead Band Value Channel 6
Reserved
EA AL
Reserved
Inpt Dta Fm Chl7 Reserved
Process Alarm High Data Value Channel 7
Process Alarm Low Data Value Channel 7
Alarm Dead Band Value Channel 7
Reserved
Input Filter Sel Chl2
Inpt Tp/RngeSel Chl2
Input Filter Sel Chl3
Inpt Tp/RngeSel Chl3
Input Filter Sel Chl4
Inpt Tp/RngeSel Chl4
Input Filter Sel Chl5
Inpt Tp/RngeSel Chl5
Input Filter Sel Chl6
Inpt Tp/RngeSel Chl6
Input Filter Sel Chl7
Inpt Tp/RngeSel Chl7
The configuration file is typically modified using the programming software configuration screen. For information on configuring the module using
MicroLogix 1500 and RSLogix 500, see Appendix B; for CompactLogix and
RSLogix 5000, see Appendix C; for 1769-ADN DeviceNet Adapter and
Publication 1769-UM002B-EN-P - July 2005
3-22 Module Data, Status, and Channel Configuration for the Input Modules
The configuration file can also be modified through the control program, if supported by the controller. The structure and bit settings are shown in
Channel Configuration on page 3-22.
Channel Configuration
Each channel’s configuration words consist of bit fields, the settings of which determine how the channel operates. See the table below and the descriptions that follow for valid configuration settings and their meanings. The default bit status of the configuration file is all zeros.
Table 3.14 Bit Definitions for Channel Configuration Words
Define
Input Filter
Selection/
-3 dB
Frequency
Enable
Interrupt
Process
Alarm
Latch
Enable
Process
Alarms
Enable
Channel
To Select
60 Hz
50 Hz
10 Hz
250 Hz
500 Hz
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Make these bit settings
15 14 13 12 11 10 9 8 7-4 3 2 1 0
1
0
1
0
1
0
1
0
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
Table 3.15 Bit Definitions for Input Range and Input Data
Define Indicate this These bit settings
15-11 10 9 8 7-4
Input
Range
Select
Input
Data
Format
Select
-10 to +10V dc
0 to 5V dc
0 to 10V dc
4 to 20 mA
1 to 5V dc
0 to 20 mA
Raw/Proportional
Counts
Engineering Units
Scaled for PID
Percent Range
0
0
0
0
0
0
1
1
0
1
0
1
3 2 1 0
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-23
Enable/Disable Channel
This configuration selection lets each channel to be individually enabled.
TIP
When a channel is not enabled (0), no voltage or current input is provided to the controller by the A/D converter.
Input Filter Selection
The input filter selection field lets you select the filter frequency for each channel and provides system status of the input filter setting for analog input channels 0 through 3. The filter frequency affects the noise rejection characteristics, as explained below. Select a filter frequency considering acceptable noise and step response time.
Noise Rejection
The 1769-IF8 uses a digital filter that provides noise rejection for the input signals. The filter is programmable, allowing you to select from four filter frequencies for each channel. The digital filter provides -3 db (50% amplitude) attenuation at the selected filter frequency. A lower frequency (60 Hz versus
250 Hz) can provide better noise rejection but it increases channel update time. Transducer power supply noise, transducer circuit noise, or process variable irregularities may also be sources of normal mode noise.
Common Mode Rejection is better than 60 dB at 50 and 60 Hz, with the 50 and 60 Hz filters selected, respectively. The module performs well in the presence of common mode noise as long as the signals applied to the user plus and minus input terminals do not exceed the common mode voltage rating (±
10 V) of the module. Improper earth ground may be a source of common mode noise.
Channel Step Response
The selected channel filter frequency determines the channel’s step response.
The step response is the time required for the analog input signal to reach
100% of its expected final value. This means that if an input signal changes faster than the channel step response, a portion of that signal will be attenuated by the channel filter.
Publication 1769-UM002B-EN-P - July 2005
3-24 Module Data, Status, and Channel Configuration for the Input Modules
Channel Cut-Off Frequency
The -3 dB frequency is the filter cut-off frequency. The cut-off frequency is defined as the point on the frequency response curve where frequency components of the input signal are passed with 3 dB of attenuation. All input frequency components at or below the cut-off frequency are passed by the digital filter with less than 3 dB of attenuation. All frequency components above the cut-off frequency are increasingly attenuated.
The cut-off frequency for each channel is defined by its filter frequency selection and is equal to the filter frequency setting. Choose a filter frequency so that your fastest changing signal is below that of the filter’s cut-off frequency. The cut-off frequency should not be confused with the update time. The cut-off frequency relates to how the digital filter attenuates frequency components of the input signal. The update time defines the rate at which an input channel is scanned and its channel data word is updated.
Module Update Time and Scanning Process
The module update time is defined as the time required for the module to sample and convert the input signals of all enabled input channels and provide the resulting data values to the processor. Module update time can be calculated by adding the sum of all enabled channel times. Channel times include channel scan time, channel switching time, and reconfiguration time.
The module sequentially samples the channels in a continuous loop.
The 1769-IF8 uses two parallel sampling loops as shown in Figure 3.5 to
update the entire module (all 8 channels) in an amount of time equal to only four channel update times. The module performs parallel channel sampling on pairs of inputs. Channels 0 and 4 are a pair. The other input channel pairs are
1 and 5, 2 and 6, and 3 and 7.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-25
Figure 3.5 Sequential Sampling
Disable Disable
Sample
Channel 0
Sample
Channel 1
Disable
Sample
Channel 4
Disable
Enable
Sample
Channel 5
Disable
Sample
Channel 2
Disable
Sample
Channel 6
Disable
Sample
Channel 3
Disable
Sample
Channel 7
Wait
RTS
Enable
Update
Input Data
Disable
Module update time is calculated as follows:
• Slowest channel update time of pair 0 and 4 (determined by the filter setting selected for each channel and the channel update times from
Table 3.16 - channel update time for a channel that is not enabled is
equal to 0)
PLUS
• Slowest channel update time of pair 1 and 5
PLUS
• Slowest channel update time of pair 2 and 6
PLUS
• Slowest channel update time of pair 3 and 7
Publication 1769-UM002B-EN-P - July 2005
3-26 Module Data, Status, and Channel Configuration for the Input Modules
If you use real-time sampling, the user-configured sample rate is used as the module update time.
Table 3.16 Filter Frequency and Update Times
Filter Frequency
10 Hz
50 Hz
60 Hz
250 Hz
500 Hz
Update Time per
Channel
100 ms
30 ms
30 ms
9 ms
6 ms
Update Time per
Module
(1)
400 ms
120 ms
120 ms
36 ms
24 ms
(1)
Module update time applies if you use all channel pairs and all enabled channels, and all the enabled channels use the filter frequency from the first column.
Examples of Calculating Module Update Time
EXAMPLE
1. Two Channels Enabled with Identical Filter Setting, But Not a Channel Pair
The following example calculates the 1769-IF8 module update time for two channels enabled with any configuration and a 500 Hz filter but the enabled channels are not a channel pair.
• Channel 0: ±10V dc with 500 Hz filter
• Channel 1: 0…10V dc with 500 Hz filter
Module Update Time = [Greater of Channel 0 Update Time or Channel 4 Update Time]
+ [Greater of Channel 1 Update Time or Channel 5 Update Time]
12 ms = [Greater of 6 ms or 0 ms] + [Greater of 6 ms or 0 ms]
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-27
EXAMPLE
2. Two Channels Enabled with Different Filter Settings, But are a Channel Pair
The following example calculates the 1769-IF8 module update time for two channels enabled with any configuration, with different filter settings, but are a channel pair.
• Channel 0: ±10V dc with 60 Hz filter
• Channel 4: 0…10V dc with 500 Hz filter
Module Update Time = [Greater of Channel 0 Update Time or Channel 4 Update Time]
30 ms = [Greater of 30 ms or 6 ms]
IMPORTANT
Configuring the 1769-IF8 module to take advantage of channel pairs can result in module update times that are significantly faster than configuring the 1769-IF8 modules without such channel assignment optimization.
Input Type/Range Selection
This selection along with proper input wiring lets you configure each channel individually for current or voltage ranges and provides the ability to read the configured range selections.
Input Data Selection Formats
This selection configures channels 0 through 3 to present analog data in any of the following formats:
• Raw/Proportional Data
• Engineering Units
• Scaled-for-PID
• Percent Range
Raw/Proportional Data
The value presented to the controller is proportional to the selected input and scaled into the maximum data range allowed by the bit resolution of the A/D converter and filter selected. The full range for a ±10Vdc user input is -32767
to +32767. See Table 3.17 Valid Input Data on page 3-28.
Publication 1769-UM002B-EN-P - July 2005
3-28 Module Data, Status, and Channel Configuration for the Input Modules
Engineering Units
The module scales the analog input data to the actual current or voltage values for the selected input range. The resolution of the engineering units is
dependent on the range selected and the filter selected. See Table 3.17 Valid
Scaled-for-PID
The value presented to the controller is a signed integer with zero representing the lower user range and 16383 representing the upper user range.
Allen-Bradley controllers, such as the MicroLogix 1500, use this range in their
PID equations. The amount over and under user range (full scale range -410 to
16793) is also included. See Table 3.17 Valid Input Data on page 3-28.
Percent Range
The input data is presented as a percentage of the user range. For example, 0V to 10V dc equals 0% to 100%.
Valid Input Data Word Formats/Ranges
The following table shows the valid formats and min./max. data ranges provided by the module.
1769-IF8
Normal
Operating
Input Range
-10V to
+10V dc
0V to 5V dc
0V to 10V dc
4 mA to
20 mA
3.2 mA to 21 mA
1.0V to 5V dc 0.5V to 5.25V
0 mA to
20 mA
Full Range
(Includes amounts
Over and Under
Normal Operating
Range)
+10.5V to -10.5V
0.0V to 5.25V
0.0V to 10.5V
0 mA to 21 mA
Table 3.17 Valid Input Data
Raw/Pro portional
Data
Engineering
Units
Full Range
-32767 to
+32767
-27068 to
+32767
-29788 to
+32767
-10500 to
+10500
0 to 5250
0 to 10500
Scaled-for-PID
Normal
Operating
Range
0 to 16383
Full Range
-410 to 16793 -100 to
+100%
0 to 17202
Percent
Normal
Operating
Range
Full Range
-105.00 to
105.00%
0 to
105.00%
-32767 to
+32767
3200 to
21000
500 to 5250
0 to 21000
-819 to
+17407
-2048 to
17407
0 to 17202
0 to 100%
-5.00 to
+106.25%
-12.50 to
+106.25%
0.00 to
105.00%
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-29
1769-IF8 Real Time Sampling
This parameter instructs the module how often to scan its input channels and obtain all available data. After the channels are scanned, the module places the data into the Input Data file. This feature is applied on a module-wide basis.
During module configuration, you specify a Real Time Sampling (RTS) period by entering a value into Word 0 of the Configuration Data file. This value entered in Word 0 can be in the range of 0 to 5000 and indicates the sampling rate the module will use in 1 ms increments.
If you enter a 0 for the Real Time Sample Rate, the module should scan its inputs at as fast a rate as possible, controlled by the number of enabled channels and the filter setting selected for those channels.
The module compares the Real Time Sample Rate value entered in Word 0 of the Configuration Data file with a calculated module update time, again based on the number of enabled channels and the filter setting selected for those channels. If the value entered for the Real Time Sample Rate is smaller than the calculated module update time, the module indicates a configuration error.
The longest Real Time Sample Rate supported by the 1769-IF8 is 5 s, the maximum value for Word 0 of the Configuration Data file is 5000 decimal.
Publication 1769-UM002B-EN-P - July 2005
3-30 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF8 Process Alarms
Process alarms alert you when the module has exceeded configured high or low limits for each channel . You can latch process alarms. These are set at two user configurable alarm trigger points:
• Process Alarm High
• Process Alarm Low
Each input channel’s process alarms are controlled by bits in the
Configuration Data file. Enable alarms for a channel by setting (1) the EA bit for that channel. Set the AL bit (1) for a channel to enable the alarm latching.
Each channel’s process alarm high data value and process alarm low data value are set by entering values in the corresponding words of the Configuration
Data file for that channel.
The values entered for a channel’s process alarm data values must be within the normal operating data range as set by the input Data Format selected for that channel. If a process alarm data value is entered that is outside the normal operating data range set for a channel, the module indicates a configuration error.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-31
Alarm Deadband
You may configure an Alarm Deadband to work with the process alarms.
The deadband lets the process alarm status bit to remain set, despite the alarm condition disappearing, as long as the input data remains within the deadband of the process alarm.
Figure 3.6 shows input data that sets each of the two alarms at some point
during module operation. In this example, Latching is disabled; therefore, each alarms turns OFF when the condition that caused it to set ceases to exist.
Figure 3.6 Alarm Deadbands
High
High alarm turns ON
Low
High alarm turns OFF
Low alarms turns ON
Normal input range
Low alarms turns OFF
Alarm deadbands
43153
The value entered for a channel’s alarm deadband value must be within the normal operating data range as set by the Input Data Format selected for that channel. If an alarm deadband value is entered that is outside the normal operating data range set for a channel, the module indicates a configuration error.
The module also checks for an alarm deadband value that is less than 0 or large enough to exceed one or both of the channel’s full range limits. When one of these conditions occurs, the module changes the alarm deadband value that is in violation to one that is allowed. A deadband value less than 0 is set at 0. A deadband value that when added to the process alarm low data value or subtracted from the process alarm high data value results in a value that exceeds the full range limits of the channel is adjusted to the first, smaller value that eliminates this full range violation.
Publication 1769-UM002B-EN-P - July 2005
3-32 Module Data, Status, and Channel Configuration for the Input Modules
Notes:
Publication 1769-UM002B-EN-P - July 2005
1
Module Data, Status, and Channel
Configuration for the Output Modules
Chapter
4
This chapter examines the analog output module’s output data file, input data file, channel status, and channel configuration words.
1769-OF2 Output Module
Memory Map
slot e
Input Image
File
The 1769-OF2 memory map shows the output, input, and configuration tables for the 1769-OF2.
Figure 4.1 1769-OF2 Memory Map
Memory Map
Input Image
Diagnostic and Status Bits
Over- and Under-range Bits
Channel 0 Output Data Echo
(1)
Channel 1 Output Data Echo
(1)
Word 0, bits 0-1, 12-15
Word 1, bits 12-15
Word 2
Word 3
Output Image Channel 0 Data Word
Channel 1 Data Word
Word 0
Word 1 slot e
Output Image
File slot e
Configuration
File
Configuration File
6 words
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 0 Fault Value Word
Channel 0 Program Idle Mode Word
Bit 15
Channel 1 Fault Value Word
Channel 1 Program Idle Mode Word
Bit 0
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Publication 1769-UM002B-EN-P - July 2005
4-2 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF2 Output Data File
The structure of the output data file is shown in the table below. Words 0 and
1 contain the converted analog output data for channels 0 and 1, respectively.
The most significant bit is the sign bit.
Table 4.1 1769-OF2 Output Data Table
Word/Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word 0 SGN
Word 1 SGN
Analog Output Data Channel 0
Analog Output Data Channel 1
1769-OF2 Input Data File
This data table file provides immediate access to channel diagnostic information and analog output data at the module for use in the control program. To receive valid data, you must enable the channel. The data table structure is described below.
Table 4.2 1769-OF2 Input Data Table
Word/Bi t
Word 0
15 14 13 12 11 10 9 8 7 6 5 4
D0 H0 D1 H1 Not Used (bits set to 0)
Word 1 U0 O0 U1 O1
Word 2 SGN
Bits 0 - 11 set to 0
Channel 0 - Output Data Loopback/Echo
Word 3 SGN Channel 1 - Output Data Loopback/Echo
3 2 1
S1
0
S0
1769-OF2 Diagnostic Bits (D0 and D1)
When set (1), these bits indicate a broken output wire or high load resistance
(not used on voltage outputs). Bit 15 represents channel 0; bit 13 represents channel 1.
1769-OF2 Hold Last State Bits (H0 and H1)
These bits indicate when channel 0 (bit 14) or channel 1 (bit 12) is in a hold last state condition. When one of these bits is set (1), the corresponding channel is in the hold state. Output data will not change until the condition which caused the hold last state to occur is removed. The bit is reset (0) for all other conditions.
TIP
MicroLogix 1500 controllers do not support the hold last state function. Refer to your controller’s user manual for details.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-3
1769-OF2 Over-Range Flag Bits (O0 and O1)
Over-range bits for channels 0 and 1 are contained in word 1, bits 14 and 12.
When set, the over-range bit indicates that the controller is attempting to drive the analog output above its normal operating range. However, the module continues to convert analog output data to a maximum full range value. The bit is automatically reset (0) by the module when the over-range condition is cleared (the output is within the normal operating range). The over-range bits
apply to all output ranges. Refer to Table 4.5 1769-OF2 Valid Output Data
Table on page 4-12 to view the normal operating and over-range areas.
1769-OF2 Under-Range Flag Bits (U0 and U1)
Under-range bits for channels 0 and 1 are contained in word 1, bits 15 and 13.
When set (1), the under-range bit indicates that the controller is attempting to drive the analog output below its normal operating range. However, the module continues to convert analog output data to a minimum full range value. The bit is automatically reset (0) by the module when the under-range condition is cleared (the output is within the normal operating range). The
under-range bits apply to all output ranges. Refer to Table 4.5 1769-OF2 Valid
Output Data Table on page 4-12 to view the normal operating and
under-range areas.
1769-OF2 General Status Bits (S0 and S1)
Word 0, bits 0 and 1 contain the general status information for output channels 0 and 1. If set (1), these bits indicate an error associated with that channel. The over-range and under-range bits and the diagnostic bit are logically ORed to this position.
Publication 1769-UM002B-EN-P - July 2005
4-4 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF2 Output Data Loopback/Echo
Words 2 and 3 provide output loopback/data echo through the input array for channels 0 and 1, respectively. The value of the data echo is the analog value currently being converted on-board the module by the D/A converter. This ensures that the logic-directed state of the output is true. Otherwise, the state of the output could vary depending on controller mode.
Under normal operating conditions, the data echo value is the same value that is being sent from the controller to the output module. Under abnormal conditions, the values may differ. For example:
1.
During run mode, the control program could direct the module to a value over or under the defined full range. In that case, the module raises the over- or under-range flag and continues to convert and data echo up to the defined full range. However, upon reaching either the maximum upper or lower full range value, the module stops converting and echoes back that maximum upper or lower full range value, not the value being sent from the controller.
2.
During program or fault mode with Hold Last State or User-Defined
Value selected, the module echoes the hold last value or alternate value you selected. For more information on the hold last and user-defined
values, see 1769-OF2 Fault Value (Channel 0 and 1) on page 4-11 and
1769-OF2 Program/Idle Value (Channel 0 and 1) on page 4-11.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-5
1769-OF2 Configuration
Data File
The configuration file lets you determine how each individual output channel will operate. Parameters such as the output type/range and data format are set up using this file. The configuration data file is writable and readable. The default value for the configuration data file is all zeros. The structure of the channel configuration file is explained below. Words 0 and 1 are the channel
configuration words for channels 0 and 1. They are described in 1769-OF2
Channel Configuration on page 4-6. Words 2 through 5 are explained
Table 4.3 1769-OF2 Configuration Data Table
(1)
Word/Bit 15 14
Word 0 E
13 12
Output Data Format
Select Channel 0
11 10 9 8
Output Type/Range
Select Channel 0
Word 1
Word 2
E Output Data Format
Select Channel 1
S
7 6 5
Not Used
(set to 0)
Output Type/Range
Select Channel 1
Not Used
(set to 0)
Fault Value - Channel 0
4
Word 3
Word 4
Word 5
S
S
S
Program (Idle) Value - Channel 0
Fault Value - Channel 1
Program (Idle) Value - Channel 1
3 2
FM0 PM0
FM1 PM1
(1)
The ability to change these values using your control program is not supported by all controllers. Refer to your controller manual for details.
1
Not Used
(set to 0)
Not Used
(set to 0)
0
PFE0
PFE1
The configuration file is typically modified using the programming software configuration screen. For information on configuring the module using
MicroLogix 1500 and RSLogix 500, see Appendix B; for CompactLogix and
RSLogix 5000, see Appendix C; for 1769-ADN DeviceNet Adapter and
The configuration file can also be modified through the control program, if supported by the controller. The structure and bit settings are shown in
1769-OF2 Channel Configuration on page 4-6.
Publication 1769-UM002B-EN-P - July 2005
4-6 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF2 Channel Configuration
Both channel configuration words (0 and 1) consist of bit fields, the settings of which determine how the corresponding channel operates. See the table below and the descriptions that follow for valid configuration settings and their meanings.
Table 4.4 1769-OF2 Bit Definitions for Channel Configuration Words 0 and 1
Bit(s)
0
1
2
3
4-7
8-11
12-14
15
Reserved
Program/Idle
Mode
Define
Program/Idle to
Fault Enable
Fault Mode
Reserved
Output
Type/Range Select
Output Data
Format Select
Enable Channel 1
0
These bit settings Indicate this
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Program Mode Data
Applied
1 Fault Mode Data Applied
0
0
0
0
0
0
0
0
0
1
0
0
1
1
0
0
1
0
1
0
0 1 0 1
Not Used
0
1
0
1
Reserved
Program Mode Hold Last
State
Program Mode
User-Defined Value
Fault Mode Hold Last
State
Fault Mode User-Defined
Value
Reserved
(1)
-10V dc to +10V dc
0 to 5V dc
0 to 10V dc
4 to 20 mA
1 to 5V dc
0 0 0
0 0 1
0 1 0
0 1 1
0 to 20 mA
Not Used
(2)
Raw/Proportional Data
Engineering Units
Scaled-for-PID
(3)
Percent Range
Not Used
Enabled
Disabled
(1)
If reserved bits are not equal to zero, a configuration error occurs.
(2)
(3)
This range is applicable to the PID function of the MicroLogix 1500 packaged controller, PLC, or SLC controllers. Logix controllers can use this or one of the other ranges for their PID functions.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-7
1769-OF2 Enable/Disable Channel
This configuration selection (bit 15) lets each channel to be individually enabled.
TIP
A channel that is not enabled has zero voltage or current at its terminal.
1769-OF2 Output Data Format Selection
This selection configures each channel to interpret data presented to it by the controller in any of the following formats:
• Raw/Proportional Data
• Engineering Units
• Scaled-for-PID
• Percent Full Range
1769-OF2 Raw/Proportional Data
The control program presents the maximum raw data value allowed by the bit resolution of the D/A converter. The full range for a ±10V dc user input is
-32767 to +32767. See Table 4.5 1769-OF2 Valid Output Data Table on page 4-12.
1769-OF2 Engineering Units
The control program presents an engineering data value to the module within the current or voltage range allowed by the D/A converter. The module then scales the data to the appropriate analog output value for the selected user
range. See Table 4.5 1769-OF2 Valid Output Data Table on page 4-12.
1769-OF2 Scaled-for-PID
The control program presents an integer value to the module, with zero representing the lower user range and 16383 representing the upper user range, for conversion by the D/A converter. The module then scales this data to the
approximate analog output value for the selected user range. See Table 4.5
1769-OF2 Valid Output Data Table on page 4-12.
TIP
Allen-Bradley controllers, such as the MicroLogix 1500, use this range in their PID equations for controlled process outputs.
Publication 1769-UM002B-EN-P - July 2005
4-8 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF2 Percent Full Range
The control program presents the analog output data to the module as a percent of the full analog output range (for example, valve 50% open). The module scales this data to the appropriate analog output value for the selected
user range. For example, 0 to 100% equals 0 to 10V dc. See Table 4.5
1769-OF2 Valid Output Data Table on page 4-12.
TIP
The ±10V dc range does not support percent full range.
1769-OF2 Output Type/Range Selection
This selection, along with proper output wiring, lets you configure each output channel individually for current or voltage ranges, and provides the ability to read the range selection.
1769-OF2 Fault Mode (FM0 and FM1)
This configuration selection provides individual fault mode selection for analog output channels 0 (word 0, bit 3) and 1 (word 1, bit 3). When this selection is disabled [the bit is reset (0)] and the system enters the fault mode, the module holds the last output state value. This means that the analog output remains at the last converted value prior to the condition that caused the system to enter the fault mode.
IMPORTANT
Hold last state is the default condition for the 1769-OF2 during a control system run-to-fault mode change.
TIP
MicroLogix 1500™ does not support the analog output module’s default hold last state function and resets analog outputs to zero when the system enters the fault mode.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-9
If this selection is enabled [the bit is set (1)] and the system enters the fault mode, it commands the module to convert the user-specified integer value from the channel’s fault value word (2 or 4) to the appropriate analog output for the range selected. If the default value, 0000, is entered, the output typically converts to the minimum value for the range selected.
EXAMPLE
• If the raw/proportional or engineering units data format is selected and zero (0000) is entered in the
±10V dc operating range, the resulting value would be
0V dc.
• If the raw/proportional or engineering units format is selected and zero is entered as the fault value in either a
1 to 5V dc or 4 to 20 mA range, a configuration error results.
•
See Table 4.5 1769-OF2 Valid Output Data Table on page 4-12 for more examples.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
1769-OF2 Program/Idle Mode (PM0 and PM1)
This configuration selection provides individual program/idle mode selection for the analog channels 0 (word 0, bit 2) and 1 (word 1, bit 2). When this selection is disabled [the bit is reset (0)], the module holds the last state , meaning that the analog output remains at the last converted value prior to the condition that caused the control system to enter the program mode.
IMPORTANT
Hold last state is the default condition for the 1769-OF2 during a control system run-to-program mode change.
TIP
MicroLogix 1500™ does not support the analog output module’s default hold last state function and resets analog outputs to zero when the system enters the program mode.
Publication 1769-UM002B-EN-P - July 2005
4-10 Module Data, Status, and Channel Configuration for the Output Modules
If this selection is enabled [the bit is set (1)] and the system enters the program mode, it commands the module to convert the user-specified value from the channel’s program/idle value word (3 or 5) to the appropriate analog output for the range selected.
EXAMPLE
• If the default value, 0000, is used and the range selected is 0 to 20 mA, the module will output 0 mA for all data formats.
• If the raw/proportional or engineering units format is selected and zero is entered as the program/idle value in either a 1 to 5V dc or 4 to 20 mA range, a configuration error results.
•
See Table 4.5 1769-OF2 Valid Output Data Table on page 4-12 for more examples.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
1769-OF2 Program/Idle to Fault Enable (PFE0 and PFE1)
If a system currently in program/idle mode faults, this setting (word 0, bit 0; word 1, bit 0) determines whether the program/idle or fault mode value is applied to the output. If the selection is enabled [the bit is set (1)], the module applies the fault mode data value. If the selection is disabled [the bit is reset
(0)], the module applies the program/idle mode data value. The default setting is disabled.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-11
1769-OF2 Fault Value (Channel 0 and 1)
Using words 2 and 4 for channels 0 and 1, you can specify the values the outputs will assume when the system enters the fault mode. The default value is 0. Valid values are dependent upon the range selected in the range selection field. If the value you entered is outside the normal operating range for the output range selected, the module generates a configuration error.
For example, if you select engineering units for the ±10V dc range and enter a fault value within the normal operating range (0 to 10000), the module will configure and operate correctly. However, if you enter a value outside the normal operating range (for example 11000), the module indicates a configuration error.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
1769-OF2 Program/Idle Value (Channel 0 and 1)
Use words 3 and 5 to set the integer values for the outputs to assume when the system enters the program mode. The values are dependent upon the range selected in the range selection field. If the value you entered is outside the normal operating range for the output range selected, the module generates a configuration error. The default value is 0.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
Publication 1769-UM002B-EN-P - July 2005
4-12 Module Data, Status, and Channel Configuration for the Output Modules
OF2
Output
Range
Input
Value
Example Data
1769-OF2 Valid Output Data Word Formats/Ranges
The following table shows the valid formats and data ranges accepted by the module.
Table 4.5 1769-OF2 Valid Output Data Table
Output
Range
State
Raw/Proportio nal Data
Engineering
Unit
Scaled-for-PID Percent Full
Range
Decimal Range Decimal Range Decimal
Range
Decimal
Range
±10V dc
0V to
5V dc
Over
10.5V dc
+10.5V dc
-10V to
+10V dc
+11.0V dc
+10.5V dc
+10.0V dc
0.0V dc
-10.0V dc
-10.5V dc -10.5V dc
+10.5V dc
+10.5V dc
Over
Over
N/A
32767
N/A
32767
11000
10500
10500
10500
17202
16793
16793
16793
N/A
N/A
+10.0V dc
Normal 31207
0.0V dc Normal 0
31207
0
10000
0
10000
0
16383
8192
16383
8192
N/A
N/A
Normal -31207 -31207 -10000 -10000 0 0 N/A -10.0V dc
-10.5V dc
Under -32767 -32767 -10500 -10500 -410 -410 N/A
N/A
N/A
N/A
N/A
N/A
N/A
Under
-10.5V dc
Over
5.25V dc
-11.0V dc
5.5V dc
-11.0V dc
+5.25V dc
Under
Over
N/A
N/A
N/A
N/A
-11000
5500
5.25V dc 5.25V dc +5.25V dc
Over 32767 32767 5250
0.0V dc to
5.0V dc
5.0V dc
0.0V dc
+5.0V dc
0.0V dc
Normal
Normal
31207
0
31207
0
5000
0
-0.5V dc -0.5V dc -0.5V dc Under -3121 -3121 -500
Under
-0.5V dc
-1.0V dc -0.5V dc Under -6241 -3121 -500
-10500
5250
5250
5000
0
-500
-500
-819
18021
17202
16383
0
-1638
-3277
-410
17202
17202
16383
0
-1638
-1638
N/A
11000
10500
10000
0
-1000
-2000
N/A
10500
10500
10000
0
-1000
-1000
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-13
OF2
Output
Range
Input
Value
Example Data
Table 4.5 1769-OF2 Valid Output Data Table
Output
Range
State
Raw/Proportio nal Data
Engineering
Unit
Scaled-for-PID Percent Full
Range
Decimal Range Decimal Range Decimal
Range
Decimal
Range
0V to
10V dc
4 mA to
20 mA
1.0V to
5V dc
Over
10.5V dc
11.0V dc +10.5V dc
+10.5V dc +10.5V dc +10.5V dc
0.0V dc to
10.0V dc
-0.5V dc
Under
-5.0V dc
Over
21.0 mA
21.0 mA
4.0 mA to
20.0 mA
+10.0V dc +10.0V dc
0.0V dc 0.0V dc
Normal 31207
Normal 0
-0.5V dc -0.5V dc Under
-1.0V dc -0.5V dc Under
-1560
-3121
31207
0
-1560
-1560
10000
0
-500
-1000
10000
0
-500
-500
16383
0
-819
-1638
16383
0
-819
-819
10000
0
-500
-1000
10000
0
-500
-500
+22.0 mA
+21.0 mA
+21.0 mA
+21.0 mA
+20.0 mA +20.0 mA
Over
Over
Over
Over
Normal
N/A
32767
N/A
32767
31207
N/A
32767
N/A
32767
31207
11000
10500
22000
21000
20000
10500
10500
21000
21000
20000
18021
17202
18431
17407
16383
17202
17202
17407
17407
16383
11000
10500
11250
10625
10000
10500
10500
10625
10625
10000
4000
3200
3200
0
-819
0
-819
-4096 -819
0
-500
0
-500
-2500 -500
3.2 mA
Under 3.2 mA
1.0V to
5.0V dc
0.5V dc
Under
0.5V dc
+4.0 mA +4.0 mA Normal 6241
+3.2 mA
0.0 mA
Over
5.25V dc
+5.5V dc +5.25V dc
+5.25V dc +5.25V dc +5.25V dc
+5.0V dc
+3.2 mA
+3.2 mA
+5.0V dc
Under
Under
Over
Over
Normal
4993
0
N/A
32767
31207
+1.0V dc +1.0V dc Normal 6241
+0.5V dc +0.5V dc Under
0.0V dc 0.0V dc Under
3121
0
6241
4993
4993
N/A
32767
31207
6241
3121
3121
4000
3200
0
5500
5250
5000
1000
500
0
5250
5250
5000
1000
500
500
18431
17407
16383
0
17407
17407
16383
0
11250
10625
10000
0
10625
10625
10000
0
-2048 -2048 -1250 -1250
-4096 -2048 -2500 -1250
Publication 1769-UM002B-EN-P - July 2005
4-14 Module Data, Status, and Channel Configuration for the Output Modules
OF2
Output
Range
Input
Value
Example Data
Table 4.5 1769-OF2 Valid Output Data Table
Output
Range
State
Raw/Proportio nal Data
Engineering
Unit
Scaled-for-PID Percent Full
Range
Decimal Range Decimal Range Decimal
Range
Decimal
Range
0 mA to
20 mA
Over
21.0 mA
21.0 mA
0.0 mA to
20.0 mA
Under 0.0 mA
+22.0 mA +21.0 mA
21.0 mA +21.0 mA
20.0 mA +20.0 mA
0.0 mA
-1.0 mA
0.0 mA
0.0 mA
Over
Over
N/A N/A 22000 21000 18201 17202 11000 10500
32767 32767 21000 21000 17202 17202 10500 10500
Normal 31207 31207 20000 20000 16383 16383 10000 10000
Normal 0
Under -1560
0
0
0
0
0
-1000
0
-819
0
0
0
-500
0
0
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-15
1769-OF2 Module
Resolution
The resolution of an analog output channel depends on the output type/range
and data format selected. Table 4.6 provides detailed resolution information
for the 1769-OF2.
1769-OF
2 Output
Range
-10 to
+10V dc
0 to
+5V dc
0 to
+10V dc
+4 to
+20 mA
+1 to
+5V dc
0 to
+20 mA
Raw/Proportional Data
Over the Full Input Range
Bits and
Engineering
Units
Resolution
Decimal
Range and Count
Value
±32767
Count by 2
Sign +14
0.64 mV/
2 counts
Sign +13
0.64 mV/
4 counts
Sign +14
0.64 mV/
2 counts
Sign +14
1.28 µA/
2 counts
-3121 to
+32767
Count by 4
-1560 to
+32767
Count by 2
+4993 to
+32767
Count by 2
Sign +13
0.64 mV/
4 counts
Sign +14
1.28 µA/
2 counts
+3121 to
+32767
Count by 4
0 to
+32767
Count by 2
Table 4.6 1769-OF2 Output Resolution
Engineering Units Over the Full Input Range
Resolution Decimal
Range and Count
Value
2.00 mV/
2 counts
±10500
Count by 2
2.00 mV/
2 counts
2.00 mV/
2 counts
2.00 µA/
2 counts
2.00 mV/
2 counts
2.00 µA/
2 counts
-500 to
+5250
Count by 2
-500 to
+10500
Count by 2
+3200 to
+2100
Count by 2
+500 to
+5250
Count by 2
0 to
+21000
Count by 2
Scaled-For-PID Over the
Full Input Range
Resolution Decimal
2.44 mV/
2 counts
0.92 mV/
3 counts
1.22 mV/
2 counts
1.95 µA/
2 counts
0.73 mV/
3counts
2.44 µA/
2 counts
Range and Count
Value
-410 to
+16793
Count by 2
-1638 to
+17202
Count by 3
-819 to
+17202
Count by 2
-819 to
+17407
Count by 2
-2048 to
+17407
Count by 3
0 to
+17202
Count by 2
Percent
Over the Full Input Range
Resolution Decimal
Range and
Count
Value
Not
Applicable
Not
Applicable
1.00 mV/
2 counts
2.00 mV/
2 counts
3.20 µA/
2 counts
0.80 mV/
2 counts
4.00 µA/
2 counts
-1000 to
+10500
Count by 2
-500 to
+10500
Count by 2
-500 to
+10625
Count by 2
-1250 to
+10625
Count by 2
0 to +10500
Count by 2
Publication 1769-UM002B-EN-P - July 2005
4-16 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C Output Module
Memory Map
slot e
Input Image
File slot e
Output Image
File slot e
Configuration
File
The 1769-OF8C memory map shows the output, input, and configuration tables for the 1769-OF8C.
Figure 4.2 1769-OF8C Memory Map
Memory Map
General Status Bits
Open-circuit, Output-held, Over-/Under-range
Input Image
11 words
Word 0, bits 0-8
Word 1
Open-circuit, Output-held, Over-/Under-range Word 2
Channel 0 Data Word
Channel 1 Data Word
Word 3
Word 4
Channel 2 Data Word
Channel 3 Data Word
Word 5
Word 6
Channel 4 Data Word
Channel 5 Data Word
Channel 6 Data Word
Channel 7 Data Word
Word 7
Word 8
Word 9
Word 10
Output Image
9 words
Channel 0 Data Word
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
Channel 4 Data Word
Channel 5 Data Word
Channel 6 Data Word
Channel 7 Data Word
Unlatch Over- and Under-range Bits
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Configuration File
64 words
Bit 15
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
Channel 4 Configuration Word
Channel 5 Configuration Word
Channel 6 Configuration Word
Channel 7 Configuration Word
Bit 0
Words 0-7
Words 8-15
Words 16-23
Words 24-31
Words 32-39
Words 40-47
Words 48-55
Words 56-63
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-17
1769-OF8V Output Module
Memory Map
slot e
Input Image
File slot e
Output Image
File slot e
Configuration
File
The 1769-OF8V memory map shows the output, input, and configuration tables for the 1769-OF8V.
Figure 4.3 1769-OF8V Memory Map
Memory Map
General Status Bits
Open-circuit, Output-held, Over-/Under-range
Input Image
11 words
Word 0, bits 0-8
Word 1
Open-circuit, Output-held, Over-/Under-range Word 2
Channel 0 Data Word
Channel 1 Data Word
Word 3
Word 4
Channel 2 Data Word
Channel 3 Data Word
Word 5
Word 6
Channel 4 Data Word
Channel 5 Data Word
Channel 6 Data Word
Channel 7 Data Word
Word 7
Word 8
Word 9
Word 10
Output Image
9 words
Channel 0 Data Word
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
Channel 4 Data Word
Channel 5 Data Word
Channel 6 Data Word
Channel 7 Data Word
Unlatch Over- and Under-range Bits
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Configuration File
64 words
Bit 15
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
Channel 4 Configuration Word
Channel 5 Configuration Word
Channel 6 Configuration Word
Channel 7 Configuration Word
Bit 0
Words 0-7
Words 8-15
Words 16-23
Words 24-31
Words 32-39
Words 40-47
Words 48-55
Words 56-63
Publication 1769-UM002B-EN-P - July 2005
4-18 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V
Output Data File
The structure of the output data file is shown in the table below. Words 0 through 7 contain the commanded analog output data for channels 0 through
7, respectively. The most significant bit is the sign bit. Word 8 contains the control bits for unlatching alarms.
Table 4.7 1769-OF8C and -OF8V Output Data Table
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 SGN
1 SGN
Analog Output Data Channel 0
Analog Output Data Channel 1
2 SGN
3 SGN
4 SGN
5 SGN
Analog Output Data Channel 2
Analog Output Data Channel 3
Analog Output Data Channel 4
Analog Output Data Channel 5
6 SGN
7 SGN
Analog Output Data Channel 6
Analog Output Data Channel 7
8 UU7 UO7 UU6 UO6 UU5 UO5 UU4 UO4 UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0
Channel Alarm Unlatch
These bits are written during run mode to clear any latched low- and high-clamps and under- and over-range alarms. The alarm is unlatched when the unlatch bit is set (1) and the alarm condition no longer exists. If the alarm condition persists, then the unlatch bit has no effect. You need to keep the unlatch bit set until verification from the appropriate input channel status word says that the alarm status bit has cleared (0). Then you need to reset (0) the unlatch bit. The module will not latch an alarm condition when a transition from a no alarm condition to an alarm condition occurs while a channel’s clear latch bit is set.
Table 4.8 Channel Alarm Unlatch
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 UU7 (1)
UO7
(2) UU6 UO6 UU5 UO5 UU4 UO4 UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0
(1)
Unlatch channel x under-range or low-clamp exceeded alarm.
(2)
Unlatch channel x over-range or high-clamp exceeded alarm.
Publication 1769-UM002B-EN-P - July 2005
1769-OF8C and -OF8V
Input Data File
Module Data, Status, and Channel Configuration for the Output Modules 4-19
This data table file provides immediate access to channel diagnostic information and analog output data at the module for use in the control program. To receive valid data, you must enable the channel. The data table structure is described below.
Table 4.9 1769-OF8C and -OF8V Input Data Table
8
9
6
7
10
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 PF S7 S6 S5 S4 S3 S2 S1 S0
1 D3 H3 U3 O3 D2 H2 U2 O2 D1 H1 U1 O1 D0 H0 U0 O0
4
5
2 D7 H7 U7 O7 D6 H6 U6 O6 D5 H5 U5 O5 D4 H4 U4 O4
3 Channel 0 Data Value
Channel 1 Data Value
Channel 2 Data Value
Channel 3 Data Value
Channel 4 Data Value
Channel 5 Data Value
Channel 6 Data Value
Channel 7 Data Value
1769-OF8C and -OF8V Data Values
Words 3 through 10 contain the data echo of the analog data presently commanded by the module for each output.
1769-OF8C and -OF8V Power Fail Bit (PF)
Word 0, bit 8, contains the analog power fail information for the output channels (which is isolated from the system backplane power). If set (1), this bit indicates that the analog power on the isolated output channel has failed. If external user power is selected for the module, the external power supply may be wired incorrectly or not supplying power. If internal (backplane) power is desired, be sure the selector switch on the module is in the internal power position.
1769-OF8C and -OF8V General Status Bits (S0 through S7)
Word 0, bits 0 through 7 contain the general status information for output channels 0 through 7. If set (1), these bits indicate an error associated with that channel. The over-range and under-range bits and the diagnostic bit are logically ORed to this position.
Publication 1769-UM002B-EN-P - July 2005
4-20 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V Over-Range Flag Bits (O0 through O7)
Word 1, bits 0, 4, 8, and 12, and Word 2, bits 0, 4, 8, and 12 contain the over-range bits for channels 0 through 7. When set, the over-range bit indicates that the controller is attempting to drive the analog output above its normal operating range or above the channel’s High Clamp level (if clamp limits are set for the channel). However, the module continues to convert analog output data to a maximum full range value if clamp levels are not set for the channel.
If alarm latching is not enabled for the channel, the bit is automatically reset
(0) by the module when the over-range condition is cleared or the commanded value no longer exceeds the high clamp (the output is commanded to return to within the normal allowed range). The over-range bits apply to all output
ranges. Refer to Table 4.17 1769-OF8C Valid Output Data Table on page 4-33
and Table 4.18 1769-OF8V Valid Output Data Table on page 4-34 to view the
normal operating and over-range areas.
1769-OF8C and -OF8V Under-Range Flag Bits (U0 through U7)
Word 1, bits 1, 5, 9, and 13, and Word 2, bits 1, 5, 9, and 13 contain the under-range bits for channels 0 through 7. When set (1), the under-range bit indicates that the controller is attempting to drive the analog output below its normal operating range or below the channel’s Low Clamp level (if clamp limits are set for the channel). However, the module continues to convert analog output data to a minimum full range value if clamp levels are not set for the channel.
If alarm latching is not enabled for the channel, the bit is automatically reset
(0) by the module when the under-range condition is cleared or the commanded value no longer exceeds the low clamp (the output is commanded to return to within the normal allowed range). The under-range bits apply to all
output ranges. Refer to Table 4.17 1769-OF8C Valid Output Data Table on
page 4-33 and Table 4.18 1769-OF8V Valid Output Data Table on page 4-34
to view the normal operating and under-range areas.
1769-OF8C and -OF8V Diagnostic Bits (D0 through D7)
Word 1, bits 3, 7, 11, and 15, and Word 2, bits 3, 7, 11, and 15 contain the open-circuit diagnostic bits for input channels 0 through 7. When set (1), these bits indicate a broken output wire or high load resistance. These bits are always cleared (0) for the 1769-OF8V module since open-circuit diagnostics do not apply for analog voltage outputs.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-21
1769-OF8C and -OF8V Output Held Bits (H0 through H7)
Word 1, bits 2, 6, 10, and 14, and Word 2, bits 2, 6, 10, and 14 contain the output held bits for input channels 0 through 7. When one of these bits is set
(1), the corresponding channel is in the hold state. Output data will not change until value commanded by the controller matches the value being held by the module for any held output channel.
When the value commanded for a channel by the controller matches the value being held by the module, the Output Held bit for that channel is cleared (0).
The output channel can again be directly controlled by the values commanded in the Output Data file by the controller. The control can determine the output value being held by the module for any channel whose Output Held bit is set (1) by reading words 3 to 10 of the Input Data file.
1769-OF8C and -OF8V Output Data Loopback/Echo
Words 3 through 10 provide output loopback/data echo through the input array for channels 0 through 7. The value of the data echo is the analog value currently being converted on-board the module by the D/A converter. This ensures that the logic-directed state of the output is true. Otherwise, the state of the output could vary depending on controller mode.
Under normal operating conditions, the data echo value is the same value that is being sent from the controller to the output module. Under abnormal conditions, the values may differ. For example:
1.
During run mode, the control program could direct the module to a value over or under the defined full range. In that case, the module raises the over- or under-range flag and continues to convert and data echo up to the defined full range. However, upon reaching either the maximum upper or lower full range value, the module stops converting and echoes back that maximum upper or lower full range value, not the value being sent from the controller.
2.
During program or fault mode with Hold Last State or User-Defined
Value selected, the module echoes the hold last value or alternate value you selected. For more information on the hold last and user-defined
values, see 1769-OF8C and -OF8V Fault Value on page 4-31 and
1769-OF8C and -OF8V Program/Idle Value on page 4-32.
3.
When one or more of the output channel’s Output Held bits are set (1).
See 1769-OF8C and -OF8V Output Held Bits (H0 through H7) on page 4-21.
Publication 1769-UM002B-EN-P - July 2005
4-22 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V
Configuration Data File
The configuration file lets you determine how each individual output channel will operate. Parameters such as the output type/range and data format are set up using this file. The configuration data file is writable and readable. The default value for the configuration data file is all zeros. The structure of the channel configuration file is explained below. The channel configuration
words, the first two words of each eight word group, are described in Table
4.10 1769-OF8C and -OF8V Configuration Data File on page 4-22.
Table 4.10 1769-OF8C and -OF8V Configuration Data File
15
16
17
18
19
20
21
22
23
11
12
13
14
7
8
9
10
5
6
3
4
1
2
Word Description
0 Channel 0 Configuration Word 0
Channel 0 Configuration Word 1
Channel 0 Fault Value Word
Channel 0 Program Idle Mode Word
Channel 0 Low Clamp
Channel 0 High Clamp
Channel 0 Ramp Rate
27
28
29
30
Word Description
24 Channel 3 Configuration Word 0
25
26
Channel 3 Configuration Word 1
Channel 3 Fault Value Word
Channel 3 Program Idle Mode Word
Channel 3 Low Clamp
Channel 3 High Clamp
Channel 3 Ramp Rate
Channel 0 Spare
Channel 1 Configuration Word 0
Channel 1 Configuration Word 1
Channel 1 Fault Value Word
Channel 1 Program Idle Mode Word 35
Channel 1 Low Clamp
Channel 1 High Clamp
Channel 1 Ramp Rate
31
32
33
34
36
37
38
Channel 3 Spare
Channel 4 Configuration Word 0
Channel 4 Configuration Word 1
Channel 4 Fault Value Word
Channel 4 Program Idle Mode Word
Channel 4 Low Clamp
Channel 4 High Clamp
Channel 4 Ramp Rate
Channel 1 Spare
Channel 2 Configuration Word 0
Channel 2 Configuration Word 1
Channel 2 Fault Value Word 42
Channel 2 Program Idle Mode Word 43
Channel 2 Low Clamp
Channel 2 High Clamp
Channel 2 Ramp Rate
Channel 2 Spare
39
40
41
44
45
46
47
Channel 4 Spare
Channel 5 Configuration Word 0
Channel 5 Configuration Word 1
Channel 5 Fault Value Word
Channel 5 Program Idle Mode Word
Channel 5 Low Clamp
Channel 5 High Clamp
Channel 5 Ramp Rate
Channel 5 Spare
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-23
51
52
53
54
55
Word Description
48 Channel 6 Configuration Word 0
49
50
Channel 6 Configuration Word 1
Channel 6 Fault Value Word
Channel 6 Program Idle Mode Word
Channel 6 Low Clamp
Channel 6 High Clamp
Channel 6 Ramp Rate
Channel 6 Spare
59
60
61
62
63
Word Description
56 Channel 7 Configuration Word 0
57
58
Channel 7 Configuration Word 1
Channel 7 Fault Value Word
Channel 7 Program Idle Mode Word
Channel 7 Low Clamp
Channel 7 High Clamp
Channel 7 Ramp Rate
Channel 7 Spare
Table 4.11 1769-OF8C and -OF8V Word 0 and 1 Bit Descriptions
Word/
Bit
15
Word 0 E
14 13 12 11
Reserved
10 9 8 7 6
SIU SIO
5
LA
4
ER
3
FM
2
PM
1
HI
0
PFE
Word 1 Reserved Output Data
Format Select
Reserved Output
Type/Range
The configuration file is typically modified using the programming software configuration screen. For information on configuring the module using
MicroLogix 1500 and RSLogix 500, see Appendix B; for CompactLogix and
RSLogix 5000, see Appendix C; for 1769-ADN DeviceNet Adapter and
The configuration file can also be modified through the control program, if supported by the controller. The structure and bit settings are shown in
1769-OF8C and -OF8V Channel Configuration on page 4-24.
Publication 1769-UM002B-EN-P - July 2005
4-24 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V Channel Configuration
The first two words of each eight word group in the configuration file allow you to change the parameters of each channel independently. For example, words 8 and 9 correspond to channel 1 while words 56 and 57 correspond to channel 7.
Table 4.12 1769-OF8C Channel Configuration
(1)
Define Indicate this These bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Program (Idle) to
Fault Enable
Hold for
Initialization
Program (Idle)
Mode Data
Applied
(2)
Fault Mode
Disabled
Enabled
Program (Idle)
Mode
Hold Last
State
User-Defined
Value
Fault Mode Hold Last
State
User-Defined
Fault Value
Enable Ramping Disabled
Enable Clamp/
Alarm Latching
Enabled
Disabled
Enabled
Enable High
Clamp/ Alarm
Interrupt
Enable Low
Clamp/ Alarm
Interrupt
Disabled
Enabled
Disabled
Enabled
Enable Channel Disabled
Enabled
(1)
0
1
Refer to the 1769-OF8C and -OF8V Output Channel Configuration table.
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
(2)
These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method. Refer to your controller manual for details.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-25
Table 4.13 1769-OF8C and -OF8V Output Channel Configuration
Define Indicate this
Output
Range
Select
Output
Data
Select
Output
Range
Select
Output
Data
Select
0 to 20 mA dc
4 to 20 mA dc
Raw/Proportion al Counts
Engineering
Units
Scaled for PID
Percent Range
-10…+10V dc
0…5V dc
0…10V dc
1…5V dc
Raw/Proportion al Counts
Engineering
Units
Scaled for PID
Percent Range
These bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0
0 0 1
0
0
0
0
0
0
0
0
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0 0 0
0 0 1
0 1 0
0 1 1
1769-OF8C and -OF8V Enable/Disable Channel
This configuration selection (bit 15) allows each channel to be individually enabled.
TIP
A channel that is not enabled has zero voltage or current at its terminal.
Clamping/Limiting
Clamping limits the output from the analog module to remain within a range configured by the controller, even when the controller commands an output outside that range. This safety feature sets a high clamp and a low clamp.
Once clamps are determined for a module, any data received from the controller that exceeds those clamps sets an appropriate limit alarm and transitions the output to that limit but not beyond the requested value.
Publication 1769-UM002B-EN-P - July 2005
4-26 Module Data, Status, and Channel Configuration for the Output Modules
For example, an application may set the high clamp on a 1769-OF8C module for 15 mA and the low clamp for 5 mA. If a controller sends a value corresponding to 16 mA to the module, the module will only apply 15 mA to its screw terminals.
Clamping is disabled on a per channel basis by entering a 0 value for both the high and low clamps in the Configuration Data file. Interrupts are generated on a high- or low-alarm by setting (1) the SIO bit (for high-clamp or over-range alarm) or setting (1) the SIU bit (for low-clamp or under-range alarm). Alarms caused by exceeding over-/under-range or clamp limits can be latched by setting (1) a channel’s LA bit on a per channel basis.
Clamp/Limit Alarms
This function works directly with clamping. When a module receives a data value from the controller that exceeds clamping limits, it applies signal values at the clamping limit but also sends a status bit to the controller notifying it that the value sent exceeds the clamping limits.
With reference to the example in the Clamping/Limiting section, if a
1769-OF8C module has clamping limits of 15 mA and 5 mA but then receives data to apply 16 mA, only 15 mA is applied to the screw terminals. The module sends a status bit back to the controller informing it that the 16 mA value exceeds the module’s clamping limits.
Ramping
Ramping limits the speed at which an analog output signal can change. This prevents fast transitions in the output from damaging the devices that an output module controls.
Table 4.14 Ramping Types
Ramping Type
Ramp to Fault Mode
Description
This type of ramping occurs when the present output value changes to the Fault
Value after a communications fault occurs.
This is the only type of ramping for the
1769-OF8C and -OF8V modules.
The ramp rate is defined in terms of the selected range/format in units per second. For example, in the 0 to 20 mA range and percent of full scale format, a ramp rate of 1000 is 10%/second (since 1000 is 10% of the total number of counts in the full scale of the 0 to 20 mA range) or a maximum of 2 mA per
second. Table 4.15 and Table 4.16 describes how ramp rate is defined for all
output range/types and output data formats.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-27
Table 4.15 1769-OF8C Output Range/Types and Output Data Formats
Output Data
Format Output
Range/Type
Proportional Counts
Total Counts in
Full Scale
65534 0…20 mA
4…20 mA
Engineering Units
0…20 mA 21000
17800 4…20 mA
Scaled for PID
0…20 mA
4…20 mA
16383
Percent of Full Scale
0…20 mA 10000
4…20 mA
Number of Counts for Every 1% of
Ramp Rate
655
210
178
164
100
Real Units/Second for Every 1% of
Ramp Rate
0.2 mA/s
0.16 mA/s
0.2 mA/s
0.16 mA/s
0.2 mA/s
0.16 mA/s
0.2 mA/s
0.16 mA/s
Table 4.16 1769-OF8V Output Range/Types and Output Data Formats
Output Data
Format Output
Range/Type
Proportional Counts
Total Counts in
Full Scale
65534 -10…+10V
0…5V
0…10V
1…5V
Engineering Units
-10…+10V
0…5V
0…10V
1…5V
Scaled for PID
-10…+10V
0…5V
0…10V
1…5V
21000
5750
11000
4750
16383
Number of Counts for Every 1% of
Ramp Rate
655
210
58
110
48
164
Real Units/Second for Every 1% of
Ramp Rate
0.2V/s
0.05V/s
0.1V/s
0.04V/s
0.2V/s
0.05V/s
0.1V/s
0.04V/s
0.2V/s
0.05V/s
0.1V/s
0.04V/s
Publication 1769-UM002B-EN-P - July 2005
4-28 Module Data, Status, and Channel Configuration for the Output Modules
Table 4.16 1769-OF8V Output Range/Types and Output Data Formats
Output Data
Format Output
Range/Type
Total Counts in
Full Scale
Percent of Full Scale
-10…+10V 10000
0…5V
0…10V
1…5V
Number of Counts for Every 1% of
Ramp Rate
100
Real Units/Second for Every 1% of
Ramp Rate
0.2V/s
0.05V/s
0.1V/s
0.04V/s
Ramping only takes place, if configured, when the output is being commanded to go to a fault state. Ramping is not done in normal run operation. The ramp rate values are entered in the Configuration Data file and are accepted as valid only if:
• The number of counts entered for a channel’s ramp rate is greater than or equal to a minimum of 1% of the total number of full scale counts
for the channel’s selected data format (see Table 4.14 and Table 4.15 for
minimum values).
OR
• The number of counts entered for a channel’s ramp rate may be equal to
0 if ramping is not enabled for the channel.
Hold for Initialization
Hold for Initialization causes outputs to hold present state until the value commanded by the controller matches the value held by the module providing a bumpless transfer.
If Hold for Initialization is selected, outputs hold if any of these three conditions occur:
• initial connection is established after power-up
• new connection is established after a communications fault occurs
• transition to Run Mode from Program state
The Output Held bit (see the Input Data file) for a channel indicates that the channel is holding.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-29
Open Wire Detection (1769-OF8C Only)
This feature detects when current flow is not present on an output channel that is enabled and has a non-zero output value commanded.
When an open wire condition occurs channel, the diagnostic bit (D bit in
Input Data file status words) is set for that channel.
1769-OF8C and -OF8V Fault Mode (FM)
This configuration selection provides individual fault mode selection for the analog channels. When this selection is disabled [the bit is reset (0)], the module holds the last state , meaning that the analog output remains at the last converted value prior to the condition that caused the control system to enter the program mode.
IMPORTANT
Hold last state is the default condition for the 1769-OF8C and -OF8V during a control system run-to-program mode change.
TIP
MicroLogix 1500™ does not support the analog output module’s default hold last state function and resets analog outputs to zero when the system enters the program mode.
If this selection is enabled [the bit is set (1)] and the system enters the program mode, it commands the module to convert the user-specified value from the channel’s Fault mode word to the appropriate analog output for the range selected.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
Publication 1769-UM002B-EN-P - July 2005
4-30 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V Program/Idle Mode (PM)
This configuration selection provides individual program/idle mode selection for the analog channels 0. When this selection is disabled [the bit is reset (0)], the module holds the last state , meaning that the analog output remains at the last converted value prior to the condition that caused the control system to enter the program mode.
IMPORTANT
Hold last state is the default condition for the 1769-OF8C and -OF8V during a control system run-to-program mode change.
TIP
MicroLogix 1500™ does not support the analog output module’s default hold last state function and resets analog outputs to zero when the system enters the program mode.
If this selection is enabled [the bit is set (1)] and the system enters the program mode, it commands the module to convert the user-specified value from the channel’s Program/Idle mode word to the appropriate analog output for the range selected.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-31
1769-OF8C and -OF8V Program/Idle to Fault Enable (PFE)
If a system currently in program/idle mode faults, this setting determines whether the program/idle or fault value is applied to the output. If the selection is enabled [the bit is set (1)], the module applies the fault value. If the selection is disabled [the bit is reset (0)], the module applies the program/idle mode data value. The default setting is disabled.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
1769-OF8C and -OF8V Fault Value
Using words each channel’s Fault Value word, you can specify the values the outputs will assume when the system enters the fault mode. The default value is 0. Valid values are dependent upon the range selected in the range selection field. If the value you entered is outside the normal operating range for the output range selected, the module generates a configuration error.
For example, if you select engineering units for the 0 to 20 mA range and enter a fault value within the normal operating range (0 to 20000), the module will configure and operate correctly. However, if you enter a value outside the normal operating range (for example 21000), the module indicates a configuration error.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
EXAMPLE
• If the default value, 0000, is used and the range selected is 0 to 20 mA, the module will output 0 mA for all data formats.
• If the raw/proportional or engineering units format is selected and zero is entered as Program/Idle mode word in the 4 to 20 mA range (for 1769-OF8C) or the
1 to 5V range (for 1769-OF8V), a configuration error results.
•
See Table 4.17 1769-OF8C Valid Output Data Table
on page 4-33 and Table 4.18 1769-OF8V Valid Output
Data Table on page 4-34for more examples.
Publication 1769-UM002B-EN-P - July 2005
4-32 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V Program/Idle Value
Use each channel’s Program/Idle Mode word to set the integer values for the outputs to assume when the system enters the program mode. The values are dependent upon the range selected in the range selection field. If the value you entered is outside the normal operating range for the output range selected, the module generates a configuration error. The default value is 0.
For example, if you select engineering units for the 0 to 20 mA range and enter a program/idle value within the normal operating range (0 to 20000), the module will configure and operate correctly. However, if you enter a value outside the normal operating range (for example 21000), the module indicates a configuration error.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
EXAMPLE
• If the default value, 0000, is used and the range selected is 0 to 20 mA, the module will output 0 mA for all data formats.
• If the raw/proportional or engineering units format is selected and zero is entered as Program/Idle mode word in the 4 to 20 mA range (for 1769-OF8C) or the
1 to 5V range (for 1769-OF8V), a configuration error results.
•
See Table 4.17 1769-OF8C Valid Output Data Table
on page 4-33 and Table 4.18 1769-OF8V Valid Output
Data Table on page 4-34 for more examples.
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-33
OF8C
Normal
Operating
Range
Input
Value
1769-OF8C Valid Output Data Word Formats/Ranges
The following table shows the valid formats and data ranges accepted by the module.
Example Data
Table 4.17 1769-OF8C Valid Output Data Table
Output
Range
State
Raw/Proportio nal Data
Engineering
Unit
Scaled-for-PID Percent Full
Range
Decimal Range Decimal Range Decimal
Range
Decimal
Range
4 mA to
20 mA
0 mA to
20 mA
Over
21.0 mA
21.0 mA
4.0 mA to
20.0 mA
+22.0 mA +21.0 mA
+21.0 mA +21.0 mA
Over
Over
N/A
32767
N/A
32767
22000
21000
21000
21000
18431
17407
17407
17407
11250
10625
10625
10625
+20.0 mA +20.0 mA
Normal 29085 29085 20000
+4.0 mA +4.0 mA Normal -29822 -29822 4000
20000
4000
16383
0
16383
0
10000
0
10000
0
+3.2 mA +3.2 mA Under
0.0 mA +3.2 mA Under
-32767 -32767 3200
N/A N/A 0
3200
3200
-819 -819
-4096 -819
-500 -500
-2500 -500
3.2 mA
Under 3.2 mA
Over
21.0 mA
21.0 mA
0.0 mA to
20.0 mA
Under 0.0 mA
+22.0 mA +21.0 mA
21.0 mA +21.0 mA
20.0 mA +20.0 mA
0.0 mA
-1.0 mA
0.0 mA
0.0 mA
Over
Over
Normal
Normal
Under
N/A
32767
29646
-32767
N/A
N/A
32767
29646
-32767
N/A
22000
21000
20000
0
-1000
21000
21000
20000
0
0
18201
17202
16383
0
-819
17202
17202
16383
0
0
11000
10500
10000
0
-500
10500
10500
10000
0
0
Publication 1769-UM002B-EN-P - July 2005
4-34 Module Data, Status, and Channel Configuration for the Output Modules
OF8V
Normal
Operating
Output
Range
Input
Value
1769-OF8V Valid Output Data Word Formats/Ranges
The following table shows the valid formats and data ranges accepted by the module.
Example Data
Table 4.18 1769-OF8V Valid Output Data Table
Output
Range
State
Raw/Proportio nal Data
Decimal Range
Engineering
Unit
Decimal Range
Scaled-for-PID Percent Full
Range
Decimal
Range
Decimal Range
±10V dc
0V to
5V dc
Over
10.5V dc
+10.5V dc
+11.0V dc
+10.5V dc
+10.5V dc
+10.5V dc
Over
Over
N/A
32767
N/A
32767
11000
10500
10500
10500
17202
16793
16793
16793
11000
10500
10500
10500
-10V to
+10V dc
Under
-0.5V dc
0.0V dc
-10.0V dc
-10.5V dc -10.5V dc
-11.0V dc
0.0V dc Normal 0
-10.0V dc
0 0 0 8192
Normal -31207 -31207 -10000 -10000 0
Under -32767 -32767 -10500 -10500 -410 -10.5V dc
-11.0V dc
Under N/A N/A -11000 -10500 -819
Over
5.25V dc
5.5V dc +5.25V dc
5.25V dc 5.25V dc +5.25V dc
Over
Over
N/A
32767
N/A
32767
5500
5250
5250
5250
8192
0
0
-10000
0
-10000
18021 17202 11000 10500
17202
-410
-410
17202
-10500
-11000
10500
-10500
-10500
10500
0.0V dc to
5.0V dc
+10.0V dc
5.0V dc
0.0V dc
+10.0V dc
+5.0V dc
0.0V dc
Normal
Normal
Normal
-0.5V dc -0.5V dc -0.5V dc Under
Under
-0.5V dc
-1.0V dc -0.5V dc Under
31207
29918
-27068
-32767
N/A
31207
29918
-27068
-32767
N/A
10000
5000
0
-500
-1000
10000
5000
0
-500
-500
16383
16383 16383 10000 10000
0 0 0 0
-1638
-3277
16383
-1638
-1638
10000
-1000
-2000
10000
-1000
-1000
Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules 4-35
OF8V
Normal
Operating
Output
Range
Input
Value
Example Data
Table 4.18 1769-OF8V Valid Output Data Table
Output
Range
State
Raw/Proportio nal Data
Decimal Range
Engineering
Unit
Decimal Range
Scaled-for-PID Percent Full
Range
Decimal
Range
Decimal Range
0V to 10V dc
1.0V to
5V dc
Over
10.5V dc
11.0V dc +10.5V dc
+10.5V dc +10.5V dc +10.5V dc
0.0V dc to
10.0V dc
-0.5V dc
+10.0V dc
0.0V dc
-0.5V dc
+10.0V dc
0.0V dc
Over
Over
Normal
Normal -29788 -29788 0
-0.5V dc Under
N/A
32767
29788
-32767
N/A
32767
29788
-32767
11000
10500
10000
-500
10500
10500
10000
0
-500
18021
17202
16383
0
-819
17202
17202
16383
0
-819
11000
10500
10000
0
-500
10500
10500
10000
0
-500
N/A N/A -1000 -500 -1638 -819 -1000 -500 Under
-5.0V dc
Over
5.25V dc
-1.0V dc -0.5V dc
+5.5V dc +5.25V dc
+5.25V dc +5.25V dc +5.25V dc
Under
Over
Over
N/A
32767
N/A
32767
5500
5250
5250
5250
18431
17407
17407
17407
11250
10625
10625
10625
1.0V to
5.0V dc
0.5V dc
Under
0.5V dc
+5.0V dc +5.0V dc Normal
+1.0V dc +1.0V dc Normal -25869 -25869 1000
+0.5V dc +0.5V dc Under
0.0V dc 0.0V dc Under
29318 29318 5000
-32767 -32767 500
N/A N/A 0
5000
1000
500
500
16383
0
16383
0
10000
0
-2048 -2048 -1250
-4096 -2048 -2500
10000
0
-1250
-1250
Publication 1769-UM002B-EN-P - July 2005
4-36 Module Data, Status, and Channel Configuration for the Output Modules
Notes:
Publication 1769-UM002B-EN-P - July 2005
1
Chapter
5
Module Diagnostics and Troubleshooting
Safety Considerations
This chapter describes troubleshooting the analog input and output modules.
This chapter contains information on:
• safety considerations when troubleshooting
• module vs. channel operation
• the module’s diagnostic features
• critical vs. non-critical errors
• module condition data
Safety considerations are an important element of proper troubleshooting procedures. Actively thinking about the safety of yourself and others, as well as the condition of your equipment, is of primary importance.
The following sections describe several safety concerns you should be aware of when troubleshooting your control system.
ATTENTION
Never reach into a machine to actuate a switch because unexpected motion can occur and cause injury.
Remove all electrical power at the main power disconnect switches before checking electrical connections or inputs/outputs causing machine motion.
Indicator Lights
When the green LED on the analog module is illuminated, it indicates that power is applied to the module.
Activating Devices When Troubleshooting
When troubleshooting, never reach into the machine to actuate a device.
Unexpected machine motion could occur.
Publication 1769-UM002B-EN-P - July 2005
5-2 Module Diagnostics and Troubleshooting
Module Operation vs.
Channel Operation
Stand Clear of the Machine
When troubleshooting any system problem, have all personnel remain clear of the machine. The problem could be intermittent, and sudden unexpected machine motion could occur. Have someone ready to operate an emergency stop switch in case it becomes necessary to shut off power to the machine.
Program Alteration
There are several possible causes of alteration to the user program, including extreme environmental conditions, Electromagnetic Interference (EMI), improper grounding, improper wiring connections, and unauthorized tampering. If you suspect a program has been altered, check it against a previously saved program on an EEPROM or UVPROM memory module.
Safety Circuits
Circuits installed on the machine for safety reasons, like over-travel limit switches, stop push buttons, and interlocks, should always be hard-wired to the master control relay. These devices must be wired in series so that when any one device opens, the master control relay is de-energized, thereby removing power to the machine. Never alter these circuits to defeat their function. Serious injury or machine damage could result.
The module performs operations at two levels:
• module level
• channel level
Module-level operations include functions such as power-up, configuration, and communication with a bus master, such as a MicroLogix 1500 controller.
Channel-level operations describe channel related functions, such as data conversion and over- or under-range detection.
Internal diagnostics are performed at both levels of operation. When detected, module error conditions are immediately indicated by the module status LED.
Both module hardware and channel configuration error conditions are reported to the controller. Channel over-range or under-range conditions are reported in the module’s input data table. Module hardware errors are typically reported in the controller’s I/O status file. Refer to your controller manual for details.
Publication 1769-UM002B-EN-P - July 2005
Power-up Diagnostics
Channel Diagnostics
Module Diagnostics and Troubleshooting 5-3
At module power-up, a series of internal diagnostic tests are performed. These diagnostic tests must be successfully completed or the module status LED remains off and a module error results and is reported to the controller.
Table 5.1 Diagnostics
If module status
LED is:
On
Off
Blinking
(1)
Indicated condition:
Proper
Operation
Corrective action:
No action required.
Module Fault Cycle power. If condition persists, replace the module. Call your local distributor or Rockwell
Automation for assistance.
Isolated 24V
Power Not
Present
Check external power switch setting. Check wiring to external power supply terminals. Check external power supply.
(1)
1769-OF8V and -OF8C only.
When an input or output module channel is enabled, the module performs a diagnostic check to see that the channel has been properly configured. In addition, the module checks each channel on every scan for configuration errors, over-range and under-range, open-circuit (input module in 4 to 20 mA range only) and output wire broken/high load resistance (output module only) conditions.
Out-of-Range Detection (Input and Output Modules)
For input modules, whenever the data received at the channel word is out of the defined operating range, an over-range or under-range error is indicated in the Input Data file.
For output modules, whenever the controller is driving data over or under the defined operating range, an over-range or under-range error is indicated in the
Input Data file.
Open-Circuit Detection (Input Modules Only)
The module performs an open-circuit test on all enabled channels configured for 4 to 20 mA inputs. Whenever an open-circuit condition occurs, the under-range bit for that channel is set in the Input Data file.
Possible causes of an open circuit include:
• the sensing device may be broken
• a wire may be loose or cut
• the sensing device may not be installed on the configured channel
Publication 1769-UM002B-EN-P - July 2005
5-4 Module Diagnostics and Troubleshooting
Output Wire Broken/High Load Resistance (Output Modules Only)
A check is performed on all enabled channels to determine if an output wire is broken, or if the load resistance is high, in the case of current mode outputs.
Whenever one of these conditions is present, the diagnostic bit for that channel is set in the Input Data file.
Non-critical vs. Critical
Module Errors
Non-critical module errors are typically recoverable. Channel errors
(over-range or under-range errors) are non-critical. Non-critical error conditions are indicated in the module input data table. Non-critical
configuration errors are indicated by the extended error code. See Table 5.4
1769-IF4 and -OF2 Extended Error Codes on page 5-6.
Critical module errors are conditions that prevent normal or recoverable operation of the system. When these types of errors occur, the system typically leaves the run or program mode of operation until the error can be dealt with.
Critical module errors are indicated in Table 5.4 1769-IF4 and -OF2 Extended
Module Error Definition
Table
15
0
14
0
“Don’t Care” Bits
13
0
Hex Digit 4
12
0
Analog module errors are expressed in two fields as four-digit Hex format with the most significant digit as “don’t care” and irrelevant. The two fields are
“Module Error” and “Extended Error Information”. The structure of the module error data is shown below.
Table 5.2 Module Error Table
11
0
Module Error
10
0
9
0
Hex Digit 3
8
0
7
0
6
0
Extended Error Information
5
0
Hex Digit 2
4
0
3
0
2
0
1
0
Hex Digit 1
0
0
Publication 1769-UM002B-EN-P - July 2005
Module Diagnostics and Troubleshooting 5-5
Module Error Field
The purpose of the module error field is to classify module errors into three distinct groups, as described in the table below. The type of error determines what kind of information exists in the extended error information field. These types of module errors are typically reported in the controller’s I/O status file.
Refer to your controller manual for details.
Table 5.3 Module Error Types
Error
Type
No Errors
Module Error
Field Value
Bits 11 through 09
(Bin)
000
Description
Hardware
Errors
Configurat ion Errors
001
010
No error is present. The extended error field holds no additional information.
General and specific hardware error codes are specified in the extended error information field.
Module-specific error codes are indicated in the extended error field. These error codes correspond to options that you can change directly. For example, the input range or input filter selection.
Extended Error Information Field
Check the extended error information field when a non-zero value is present in the module error field. Depending upon the value in the module error field, the extended error information field can contain error codes that are module-specific or common to all 1769 analog modules.
TIP
If no errors are present in the module error field, the extended error information field will be set to zero.
Hardware Errors
General or module-specific hardware errors are indicated by module error
code 2. See Table 5.4 1769-IF4 and -OF2 Extended Error Codes on page 5-6,
Table 5.5 1769-IF8 Extended Error Codes on page 5-7, and Table 5.6
1769-OF8C and -OF8V Extended Error Codes on page 5-10.
Publication 1769-UM002B-EN-P - July 2005
5-6 Module Diagnostics and Troubleshooting
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values, the module ignores the invalid configuration, generates a non-critical error, and keeps operating with the previous configuration.
Each type of analog module has different features and different error codes.
See Table 5.4 1769-IF4 and -OF2 Extended Error Codes on page 5-6, Table
Error Codes
Error codes can help troubleshoot your module.
Table 5.4 1769-IF4 and -OF2 Extended Error Codes
Error Type Hex
Equivalent
(1)
No Error
General Common
Hardware Error
Hardware-
Specific Error
1769-IF4 Specific
Configuration
Error
X000
X200
X201
X300
X301
X400
X401
X402
X403
X404
X405
X406
X407
X408
X409
X40A
X40B
X40C
010
010
010
010
010
001
010
010
010
010
010
010
010
010
Module
Error
Code
Binary
000
001
001
001
Extended Error
Information
Code
Binary
Error Description
0 0000 0000 No Error
0 0000 0000 General hardware error; no additional information
0 0000 0001 Power-up reset state
0 1000 0000 General hardware error, loss of external 24V dc power
0 1000 0001 Microprocessor hardware error
0 0000 0000 General configuration error; no additional information
0 0000 0001 invalid input range selected (channel 0)
0 0000 0010 invalid input range selected (channel 1)
0 0000 0011 invalid input range selected (channel 2)
0 0000 0100 invalid input range selected (channel 3)
0 0000 0101 invalid input filter selected (channel 0)
0 0000 0110 invalid input filter selected (channel 1)
0 0000 0111 invalid input filter selected (channel 2)
0 0000 1000 invalid input filter selected (channel 3)
0 0000 1001 invalid input format selected (channel 0)
0 0000 1010 invalid input format selected (channel 1)
0 0000 1011 invalid input format selected (channel 2)
0 0000 1100 invalid input format selected (channel 3)
Publication 1769-UM002B-EN-P - July 2005
Module Diagnostics and Troubleshooting 5-7
Table 5.4 1769-IF4 and -OF2 Extended Error Codes
Error Type
1769-OF2 Specific
Configuration
Error
Hex
Equivalent
(1)
X400
X401
X402
X403
X404
X405
X406
X407
X408
(1)
X represents the “Don’t Care” digit.
Module
Error
Code
Binary
010
010
010
010
010
010
010
010
010
Extended Error
Information
Code
Error Description
Binary
0 0000 0000 General configuration error; no additional information
0 0000 0001 invalid output range selected (channel 0)
0 0000 0010 invalid output range selected (channel 1)
0 0000 0011 invalid output data format selected (channel 0)
0 0000 0100 invalid output data format selected (channel 1)
0 0000 0101 invalid fault value entered for data format selected (channel 0)
0 0000 0110 invalid fault value entered for data format selected (channel 1)
0 0000 0111 invalid program value entered for data format selected (channel 0)
0 0000 1000 invalid program value entered for data format selected (channel 1)
Table 5.5 1769-IF8 Extended Error Codes
Error Type Hex
Equivalent
(1)
No Error
General Common
Hardware Error
Hardware-
Specific Error
X000
X200
X201
X300
X301
X302
Module
Error
Code
Binary
000
001
001
001
001
001
Extended Error
Information
Code
Error Description
Binary
0 0000 0000 No Error
0 0000 0000 General hardware error; no additional information
0 0000 0001 Power-up reset state
0 1000 0000 General hardware error, loss of external 24V dc power
0 1000 0001 Microprocessor hardware error
1 0000 0010 A/D converter communication error
Publication 1769-UM002B-EN-P - July 2005
5-8 Module Diagnostics and Troubleshooting
Table 5.5 1769-IF8 Extended Error Codes
Error Type Hex
Equivalent
(1)
1769-IF8 Specific
Configuration
Error
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
Module
Error
Code
Binary
010
010
010
010
010
010
010
010
010
X407
X408
X409
X40A
X40B
X40C
X40D
X40E
X400
X401
X402
X403
X404
X405
X406
X413
X414
X415
X416
X417
X40F
X410
X411
X412
X418
X419
X41A
Extended Error
Information
Code
Error Description
Binary
0 0000 0000 General configuration error; no additional information
0 0000 0001 invalid input range selected (channel 0)
0 0000 0010 invalid input range selected (channel 1)
0 0000 0011 invalid input range selected (channel 2)
0 0000 0100 invalid input range selected (channel 3)
0 0000 0101 invalid input range selected (channel 4)
0 0000 0110 invalid input range selected (channel 5)
0 0000 0111 invalid input range selected (channel 6)
0 0000 1000 invalid input range selected (channel 7)
0 0000 1001 invalid input filter selected (channel 0)
0 0000 1010 invalid input filter selected (channel 1)
0 0000 1011 invalid input filter selected (channel 2)
0 0000 1100 invalid input filter selected (channel 3)
0 0000 1101 invalid input filter selected (channel 4)
0 0000 1110 invalid input filter selected (channel 5)
0 0000 1111 invalid input filter selected (channel 6)
0 0001 0000 invalid input filter selected (channel 7)
0 0001 0001 invalid input format selected (channel 0)
0 0001 0010 invalid input format selected (channel 1)
0 0001 0011 invalid input format selected (channel 2)
0 0001 0100 invalid input format selected (channel 3)
0 0001 0101 invalid input format selected (channel 4)
0 0001 0110 invalid input format selected (channel 5)
0 0001 0111 invalid input format selected (channel 6)
0 0001 1000 invalid input format selected (channel 7)
0 0001 1001 alarm not enabled (channel 0)
0 0001 1010 alarm not enabled (channel 1)
Publication 1769-UM002B-EN-P - July 2005
Module Diagnostics and Troubleshooting 5-9
Table 5.5 1769-IF8 Extended Error Codes
Error Type Hex
Equivalent
(1)
1769-IF8 Specific
Configuration
Error
X426
X427
X428
X429
X422
X423
X424
X425
X41B
X41C
X41D
X41E
X41F
X420
X421
(1)
X represents the “Don’t Care” digit.
Module
Error
Code
Binary
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
Extended Error
Information
Code
Error Description
Binary
0 0001 1011 alarm not enabled (channel 2)
0 0001 1100 alarm not enabled (channel 3)
0 0001 1101 alarm not enabled (channel 4)
0 0001 1110 alarm not enabled (channel 5)
0 0001 1111 alarm not enabled (channel 6)
0 0010 0000 alarm not enabled (channel 7)
0 0010 0001 invalid alarm data selected (channel 0)
0 0010 0010 invalid alarm data selected (channel 1)
0 0010 0011 invalid alarm data selected (channel 2)
0 0010 0100 invalid alarm data selected (channel 3)
0 0010 0101 invalid alarm data selected (channel 4)
0 0010 0110 invalid alarm data selected (channel 5)
0 0010 0111 invalid alarm data selected (channel 6)
0 0010 1000 invalid alarm data selected (channel 7)
0 0010 1001 invalid real time sample rate value
Publication 1769-UM002B-EN-P - July 2005
5-10 Module Diagnostics and Troubleshooting
Table 5.6 1769-OF8C and -OF8V Extended Error Codes
Error Type
No Error
General Common
Hardware Error
Hex
Equivalent
(1)
X000
X200
X201
X216
X220
X221
Module
Error
Code
Binary
000
001
001
001
001
001
X300 001
Extended Error
Information
Code
Error Description
Binary
0 0000 0000 No Error
0 0000 0000 General hardware error; no additional information
0 0000 0001 Power-up reset state
0 0001 0110 Microprocessor watchdog error
0 0010 0000 Firmware corrupt (checksum failure)
0 0010 0001 Firmware checksum error in NVRAM (calibration data checksum failure)
1 0000 0000 General hardware error (ASIC) Hardware-
Specific Error
1769-OF8C and
-OF8V Specific
Configuration
Error
X409
X40A
X40B
X40C
X40D
X40E
X40F
X410
X411
X412
X405
X406
X407
X408
X401
X402
X403
X404
X413
X414
X415
X416
X417
X418
X419
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
0 0000 0001 invalid input range selected (channel 0)
0 0000 0010 invalid input range selected (channel 1)
0 0000 0011 invalid input range selected (channel 2)
0 0000 0100 invalid input range selected (channel 3)
0 0000 0101 invalid input range selected (channel 4)
0 0000 0110 invalid input range selected (channel 5)
0 0000 0111 invalid input range selected (channel 6)
0 0000 1000 invalid input range selected (channel 7)
0 0000 1001 invalid data format selected (channel 0)
0 0000 1010 invalid data format selected (channel 1)
0 0000 1011 invalid data format selected (channel 2)
0 0000 1100 invalid data format selected (channel 3)
0 0000 1101 invalid data format selected (channel 4)
0 0000 1110 invalid data format selected (channel 5)
0 0000 1111 invalid data format selected (channel 6)
0 0001 0000 invalid data format selected (channel 7)
0 0001 0001 invalid fault value (channel 0)
0 0001 0010 invalid fault value (channel 1)
0 0001 0011 invalid fault value (channel 2)
0 0001 0100 invalid fault value (channel 3)
0 0001 0101 invalid fault value (channel 4)
0 0001 0110 invalid fault value (channel 5)
0 0001 0111 invalid fault value (channel 6)
0 0001 1000 invalid fault value (channel 7)
0 0001 1001 invalid idle value (channel 0)
Publication 1769-UM002B-EN-P - July 2005
Module Diagnostics and Troubleshooting 5-11
Table 5.6 1769-OF8C and -OF8V Extended Error Codes
Error Type Hex
Equivalent
(1)
1769-OF8C and
-OF8V Specific
Configuration
Error
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
010
Module
Error
Code
Binary
010
010
010
010
010
010
010
010
010
X435
X436
X437
X438
X439
X43A
X429
X42A
X42B
X42C
X42D
X42E
X42F
X430
X431
X432
X433
X434
X425
X426
X427
X428
X421
X422
X423
X424
X41A
X41B
X41C
X41D
X41E
X41F
X420
Extended Error
Information
Code
Error Description
Binary
0 0001 1010 invalid idle value (channel 1)
0 0001 1011 invalid idle value (channel 2)
0 0001 1100 invalid idle value (channel 3)
0 0001 1011 invalid idle value (channel 4)
0 0001 1100 invalid idle value (channel 5)
0 0001 1101 invalid idle value (channel 6)
0 0010 0000 invalid idle value (channel 7)
0 0010 0001 invalid clamps (channel 0)
0 0010 0010 invalid clamps (channel 1)
0 0010 0011 invalid clamps (channel 2)
0 0010 0100 invalid clamps (channel 3)
0 0010 0101 invalid clamps (channel 4)
0 0010 0110 invalid clamps (channel 5)
0 0010 0111 invalid clamps (channel 6)
0 0010 1000 invalid clamps (channel 7)
0 0010 1001 invalid ramp rate (channel 0)
0 0010 1010 invalid ramp rate (channel 1)
0 0010 1011 invalid ramp rate (channel 2)
0 0010 1100 invalid ramp rate (channel 3)
0 0010 1101 invalid ramp rate (channel 4)
0 0010 1110 invalid ramp rate (channel 5)
0 0010 1111 invalid ramp rate (channel 6)
0 0011 0000 invalid ramp rate (channel 7)
0 0011 0001 configuration word 0 illegal bits set (channel 0)
0 0011 0010 configuration word 0 illegal bits set (channel 1)
0 0011 0011 configuration word 0 illegal bits set (channel 2)
0 0011 0100 configuration word 0 illegal bits set (channel 3)
0 0011 0101 configuration word 0 illegal bits set (channel 4)
0 0011 0110 configuration word 0 illegal bits set (channel 5)
0 0011 1011 configuration word 0 illegal bits set (channel 6)
0 0011 1000 configuration word 0 illegal bits set (channel 7)
0 0011 1001 configuration word 1 illegal bits set (channel 0)
0 0011 1010 configuration word 1 illegal bits set (channel 1)
Publication 1769-UM002B-EN-P - July 2005
5-12 Module Diagnostics and Troubleshooting
Table 5.6 1769-OF8C and -OF8V Extended Error Codes
Error Type
1769-OF8C and
-OF8V Specific
Configuration
Error
Hex
Equivalent
(1)
X43B
X43C
X43D
X43E
X43F
X440
(1)
X represents the “Don’t Care” digit.
Module
Error
Code
Binary
010
010
010
010
010
010
Extended Error
Information
Code
Error Description
Binary
0 0011 1011 configuration word 1 illegal bits set (channel 2)
0 0011 1100 configuration word 1 illegal bits set (channel 3)
0 0011 1101 configuration word 1 illegal bits set (channel 4)
0 0011 1110 configuration word 1 illegal bits set (channel 5)
0 0011 1111 configuration word 1 illegal bits set (channel 6)
0 0100 0000 configuration word 1 illegal bits set (channel 7)
Module Inhibit Function
CompactLogix controllers support the module inhibit function. See your controller manual for details.
Whenever the output modules are inhibited, the modules enter the program mode and the output channel is changed to the state configured for the program mode. Whenever the input modules are inhibited, the modules continue to provide information about changes at its inputs to the 1769
Compact Bus Master (for example, a CompactLogix controller).
Contacting Rockwell
Automation
If you need to contact Rockwell Automation for assistance, please have the following information available when you call:
• a clear statement of the problem, including a description of what the system is actually doing. Note the LED state; also note input and output image words for the module.
• a list of remedies you have already tried
• processor type and firmware number (See the label on the processor.)
• hardware types in the system, including all I/O modules
• fault code if the processor is faulted
Publication 1769-UM002B-EN-P - July 2005
Appendix
A
Specifications
1
General Specifications for
1769-IF4, -IF8, -OF2, -OF8C, and -OF8V Modules
Table A.1 General Specifications
Specification
Dimensions
Approximate Shipping Weight
(with carton)
Storage Temperature
Operating Temperature
Operating Humidity
Operating Altitude
Vibration
Shock
System Power Supply Distance
Rating
Optional 24V dc Class 2 Power
Supply Voltage Range
(1)
Recommended Cable
Maximum Cable Length
Agency Certification
Hazardous Environment Class
Radiated and Conducted
Emissions
Value
118 mm (height) x 87 mm (depth) x 35 mm (width)
[52.5 mm (width) for 1769-IF8]
Height including mounting tabs is 138 mm
4.65 in (height) x 3.43 in (depth) x 1.38 in (width)
[2.07 in (width) for 1769-IF8]
Height including mounting tabs is 5.43 in
300g (0.65 lbs.)
1769-IF8 - 450g (0.99 lbs.)
-40°C to +85°C (-40°F to +185°F)
0°C to +60°C (32°F to +140°F)
5% to 95% non-condensing
2000 meters (6561 feet)
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G
Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
8 (The module may not be more than 8 modules away from a system power supply.)
20.4 V to 26.4V dc
Belden™ 8761 (shielded)
1769-IF4 and -IF8: See “Effect of
Transducer/Sensor and Cable Length Impedance on Voltage Input Accuracy” on page 2-12
1769-OF2, -OF8C, and -OF8V: See “Effect of Device and Cable Output Impedance on Output Module
•
C-UL certified (under CSA C22.2 No. 142)
•
UL 508 listed
•
CE compliant for all applicable directives
Class I, Division 2, Hazardous Location, Groups A,
B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
EN50081-2 Class A
Publication 1769-UM002B-EN-P - July 2005
A-2 Specifications
Specification
Electrical /EMC:
Value
The module has passed testing at the following levels:
•
4 kV contact, 8 kV air, 4 kV indirect
•
ESD Immunity
(IEC1000-4-2)
•
Radiated Immunity
(IEC1000-4-3)
•
Fast Transient Burst
(IEC1000-4-4)
•
Surge Immunity
(IEC1000-4-5)
•
Conducted Immunity
(IEC1000-4-6)
•
•
•
•
10 V/m , 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
2 kV, 5kHz
1kV galvanic gun
10V, 0.15 to 80MHz
(2)
(1)
Failure to use a Class 2 power supply without regulation within these limits could result in improper module operation.
(2)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is
30 MHz to 1000 MHz.
Publication 1769-UM002B-EN-P - July 2005
1769-IF4 Input
Specifications
Specifications A-3
Table A.2 1769-IF4 Specifications
Specification
Analog Normal Operating
Ranges
Full Scale
(1)
Analog Ranges
1769-IF4 (Series B and later)
Voltage: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA
Voltage: ± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc,
0.5 to 5.25V dc
Current: 0 to 21 mA, 3.2 to 21 mA
4 differential or single-ended
120 mA at 5V dc
Number of Inputs
Bus Current Draw (max.)
Heat Dissipation
Converter Type
Response Speed per
Channel
Resolution (max.)
60 mA at 24V dc
(7)
2.63 Total Watts (The Watts per point, plus the minimum
Watts, with all points energized.)
Delta Sigma
Input filter and configuration dependent. See “Channel
14 bits (unipolar)
14 bits plus sign (bipolar)
See “Effective Resolution” on page 3-13.
30V ac/30V dc
±10V maximum per channel
Rated Working Voltage
(2)
Common Mode Voltage
Range
(3)
Common Mode Rejection
Normal Mode Rejection
Ratio
Input Impedance greater than 60 dB at 50 and 60 Hz with the 50 or 60 Hz filter selected, respectively
-50 dB at 50/60 Hz with the 50 or 60 Hz filter selected, respectively
Voltage Terminal: 220K
Ω
(typical)
Current Terminal: 250
Ω
Voltage Terminal: ±0.2% full scale at 25°C
Overall Accuracy
(4)
Accuracy Drift with
Temperature
Current Terminal: ±0.35% full scale at 25°C
Voltage Terminal: ±0.003% per °C
Calibration
Non-linearity (in percent full scale)
Repeatability
(5)
Module Error over Full
Temperature Range
(0 to +60°C [+32°F to
+140°F])
Current Terminal: ±0.0045% per °C
The module performs autocalibration on channel enable and on configuration change between channels.
±0.03%
±0.03%
Voltage: ±0.3%
Current: ±0.5%
Publication 1769-UM002B-EN-P - July 2005
A-4 Specifications
Specification
Input Channel Configuration via configuration software screen or the user program
(by writing a unique bit pattern into the module’s configuration file). Refer to your controller manual to determine if user program configuration is supported.
Module OK LED
1769-IF4 (Series B and later)
On: module has power, has passed internal diagnostics, and is communicating over the bus.
Channel Diagnostics
Maximum Overload at Input
Terminals
(6)
Off: Any of the above is not true.
Over or under range by bit reporting
Voltage Terminal: ±30V continuous, 0.1 mA
Input Group to Backplane
Isolation
Current Terminal: ±32 mA continuous, ±7.6 V
500V ac or 710V dc for 1 minute (qualification test)
Vendor I.D. Code
Product Type Code
Product Code
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
1
10
35
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
(2)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above ground).
(3)
For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common.
(4)
Includes offset, gain, non-linearity and repeatability error terms.
(5)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(6)
Damage to the input circuit may occur if this value is exceeded.
(7)
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
Publication 1769-UM002B-EN-P - July 2005
1769-IF8 Input
Specifications
Specifications A-5
Table A.3 1769-IF8 Specifications
Specification 1769-IF8
Analog Normal Operating
Ranges
(1)
Voltage: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA
Full Scale Analog
Ranges
Voltage: ± 10.5V dc, 0 to 10.5V dc, 0 to 5.25V dc, 0.5 to 5.25V dc
Current: 0 to 21 mA, 3.2 to 21 mA
Number of Inputs
Heat Dissipation
8 differential or single-ended
Bus Current Draw (max.) 120 mA at 5V dc
70 mA at 24V dc
3.24 Total Watts (The Watts per point, plus the minimum
Watts, with all points energized.)
Converter Type Delta Sigma
Response Speed per
Channel
Resolution (max.)
(2)
Input filter and configuration dependent. See your user’s manual.
16 bits (unipolar)
15 bits plus sign (bipolar)
Rated Working Voltage
(3)
Common Mode Voltage
Range
(4)
30V ac/30V dc
±10V dc maximum per channel
Common Mode Rejection greater than 60 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively.
Normal Mode Rejection
Ratio
Input Impedance
-50 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively.
Voltage Terminal: 220K
Current Terminal: 250
Ω
Ω ( typical)
Overall Accuracy
(5) Voltage Terminal: ±0.2% full scale at 25°C
Current Terminal: ±0.35% full scale at 25°C
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
(2)
Resolution is dependent upon your filter selection. The maximum resolution is achieved with the 10 Hz filter selected. For resolution with other filter selections, refer to the user manual, publication 1769-UM002.
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above ground).
(4)
For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common.
(5)
Includes offset, gain, non-linearity and repeatability error terms.
Publication 1769-UM002B-EN-P - July 2005
A-6 Specifications
Specification
Accuracy Drift with
Temperature
Calibration
1769-IF8
Voltage Terminal: ±0.003% per °C
Current Terminal: ±0.0045% per °C
The module performs autocalibration on channel enable and on a configuration change between channels.
±0.03% Non-linearity (in percent full scale)
Repeatability
(1) ±0.03%
Module Error over Full
Temperature Range
(0 to +60°C [+32°F to
+140°F])
Voltage: ±0.3%
Current: ±0.5%
Input Channel Configuration via configuration software screen or the user program (by writing a unique bit pattern into the module’s configuration file). Refer to your controller’s user manual to determine if user program configuration is supported.
Module OK LED On: module has power, has passed internal diagnostics, and is communicating over the bus.
Off: Any of the above is not true.
Channel Diagnostics Over- or under-range by bit reporting, process alarms
Maximum Overload at Input
Terminals
(2)
Voltage Terminal: ±30V dc continuous, 0.1 mA
Current Terminal: ±32 mA continuous, ±7.6 V dc
System Power Supply
Distance Rating
Recommended Cable
8 (The module may not be more than 8 modules away from the system power supply.)
Belden™ 8761 (shielded)
Input Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code 1
Product Type Code
Product Code
10
38
(1)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(2)
Damage may occur to the input circuit if this value is exceeded.
Publication 1769-UM002B-EN-P - July 2005
1769-OF2 Output
Specifications
Specifications A-7
Table A.4 1769-OF2 Specifications
Specification
Analog Ranges
(1)
Full Scale Analog Ranges
1769-OF2 (Series B and later)
Voltage: ±10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA
Voltage: ±10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc,
0.5 to 5.25V dc
Number of Outputs
Bus Current Draw (max.)
Heat Dissipation
Current: 0 - 21 mA, 3.2 - 21 mA
2 single-ended
120 mA at 5V dc
120 mA at 24V dc
(7)
2.52 Total Watts (The Watts per point, plus the minimum Watts, with all points energized.)
Sigma-Delta Converter Type
Analog Data Format
Digital Resolution Across Full
Range
14-bit, two’s complement. The Most Significant Bit is the sign bit.
14 bits (unipolar)
14 bits plus sign (bipolar)
See “1769-OF2 Module Resolution” on page 4-15.
2.5 ms Conversion Rate (all channels) max.
Step Response to 63%
(2) 2.9 ms
Current Load on Voltage Output 10 mA max.
Resistive Load on Current
Output
0 to 500
Ω
(includes wire resistance)
Load Range on Voltage Output >1 k
Ω at 10V dc
0.1 mH Max. Inductive Load
(Current Outputs)
Max. Capacitive Load
(Voltage Outputs)
Overall Accuracy
(3)
1 µF
Voltage Terminal: ±0.5% full scale at 25°C
Current Terminal: ±0.35% full scale at 25°C
Accuracy Drift with Temperature Voltage Terminal: ±0.0086% FS per °C
Current Terminal: ±0.0058% FS per °C
±0.05%
Output Ripple;
(4) range 0 - 50 kHz
(referred to output range)
Calibration
Non-linearity
(in percent full scale)
Repeatability
(5)
(in percent full scale)
None required (guaranteed by hardware design).
±0.05%
±0.05%
Publication 1769-UM002B-EN-P - July 2005
A-8 Specifications
Publication 1769-UM002B-EN-P - July 2005
Specification
Output Error Over Full
Temperature Range
(0 to 60°C [32 to +140°F])
Output Offset Error
(0 to 60°C [32 to +140°F])
Output Impedance
1769-OF2 (Series B and later)
Voltage: ±0.8%
Current: ±0.55%
±0.05%
Open and Short-Circuit
Protection
15
Ω
(typical)
Yes
Maximum Short-Circuit Current 21 mA
Output Overvoltage Protection Yes
Time to Detect Open Wire
Condition (Current Mode)
Output Response at Power Up and Power Down
Rated Working Voltage
(6)
Module OK LED
10 ms typical
13.5 ms maximum
±0.5 V spike for <5 ms
30V ac/30V dc
On: module has power, has passed internal diagnostics, and is communicating over the bus.
Channel Diagnostics
Off: Any of the above is not true.
Over or under range by bit reporting output wire broken or load resistance high by bit reporting (current mode only)
500V ac or 710V dc for 1 minute (qualification test) Output Group to Backplane
Isolation
Vendor I.D. Code
Product Type Code
Product Code
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
1
10
32
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
(2)
Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range. Time applies to one or both channels.
(3)
Includes offset, gain, non-linearity and repeatability error terms.
(4)
Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(5)
Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively, under the same conditions and in the same direction.
(6)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above ground).
(7)
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
1769-OF8C Output
Specifications
Specifications A-9
Table A.5 1769-OF8C Specifications
Specification 1769-OF8C
Analog Normal Operating
Ranges
(1)
0 to 20 mA, 4 to 20 mA
0 to 21 mA, 3.2 to 21 mA
Number of Outputs
Bus Current Draw (max.)
Heat Dissipation
Digital Resolution Across Full
Range
8 single-ended
145 mA at 5V dc
160 mA at 24V dc
(2)
2.69 Total Watts (All points - 21 mA into 250
Ω
- worst case calculated.)
16 bits (unipolar)
Conversion Rate (all channels) max.
+4 to +20 mA: 15.59 bits, 0.323 µA/bit
0 to +20 mA: 15.91 bits, 0.323 µA/bit
5 ms
Step Response to 63%
Resistive Load on Current
Output
(3) <2.9 ms
0 to 500
Ω
(includes wire resistance)
Max. Inductive Load
Field Calibration
Overall Accuracy
(4)
0.1 mH
None required
±0.35% full scale at 25°C
(1)
(2)
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
(3)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range unless configured to latch.
Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.
(4)
Includes offset, gain, drift, non-linearity and repeatability error terms.
Publication 1769-UM002B-EN-P - July 2005
A-10 Specifications
Specification
Accuracy Drift with
Temperature
Output Ripple
(1) range 0 to 50 kHz
(referred to output range)
1769-OF8C
±0.0058% FS per °C
±0.05%
Non-linearity (in percent full scale)
Repeatability
(2)
(in percent full scale)
±0.05%
±0.05%
Output Error Over Full
Temperature Range
(0 to 60°C [+32 to +140°F])
Output Offset Error
(0 to 60°C [+32 to +140°F])
Output Impedance
Time to Detect Open Wire
Condition
Output Response at System
Power Up and Power Down
Current: ±0.55%
±0.05%
Open and Short-Circuit
Protection
>1 M
Ω
Yes
Maximum Short-Circuit Current 21 mA
Output Overvoltage Protection Yes
5 ms
± 0.5V dc spike for < 5 ms
Rated Working Voltage
(3) 30V ac/30V dc
Output Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification test)
Module OK LED
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
On: module has power, has passed internal diagnostics, and is communicating over the bus.
Flashing: external power failure.
Channel Diagnostics
Off: Any of the above is not true.
Over- or under-range by bit reporting output wire broken or load resistance high by bit reporting
(1)
Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(2)
Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively, under the same conditions and in the same direction.
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above ground).
Publication 1769-UM002B-EN-P - July 2005
1769-OF8V Output
Specifications
Specifications A-11
Table A.6 1769-OF8V Specifications
Specification 1769-OF8V
Analog Normal Operating
Ranges
(1)
± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Number of Outputs
± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc,
0.5 to 5.25V dc
8 single-ended
Bus Current Draw (max.)
Heat Dissipation
Digital Resolution Across Full
Range
145 mA at 5V dc
125 mA at 24V dc
(2)
2.16 Total Watts (All points - 10.5V into 1 k
Ω
- worst case calculated.)
16 bits plus sign (bipolar)
±10V dc: 15.89 bits, 330 µV/bit
0 to +5V dc: 13.89 bits, 330 µV/bit
0 to +10V dc: 14.89 bits, 330 µV/bit
+1 to +5V dc: 13.57 bits, 330 µV/bit
5.0 ms Conversion Rate (all channels) max.
Step Response to 63%
(3)
Current Load Output
Load Range Output
Max. Capacitive Load
Field Calibration
Overall Accuracy
(4)
<2.9 ms
10 mA max.
> 1 k
1 µF
Ω at 10V dc
None required
±0.5% full scale at 25°C
(1)
(2)
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
(3)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.
(4)
Includes offset, gain, drift, non-linearity and repeatability error terms.
Publication 1769-UM002B-EN-P - July 2005
A-12 Specifications
Specification
Accuracy Drift with
Temperature
Output Ripple
(1) range 0 to 50 kHz
(referred to output range)
1769-OF8V
±0.0086% FS per °C
±0.05%
Non-linearity (in percent full scale)
Repeatability
(2)
(in percent full scale)
±0.05%
±0.05%
Output Error Over Full
Temperature Range
(0 to 60°C [+32 to +140°F])
Output Offset Error
(0 to 60°C [+32 to +140°F])
Output Impedance
±0.8%
±0.05%
Open and Short-Circuit
Protection
<1
Ω
Yes
Maximum Short-Circuit Current 30 mA
Output Overvoltage Protection Yes
Output Response at System
Power Up and Power Down
± 0.5V dc spike for < 5 ms
Rated Working Voltage
(3) 30V ac/30V dc
Output Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification test)
Module OK LED
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
On: module has power, has passed internal diagnostics, and is communicating over the bus.
Flashing: external power failure.
Channel Diagnostics
Off: Any of the above is not true.
Over- or under-range by bit reporting
(1)
Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(2)
Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively, under the same conditions and in the same direction.
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above ground).
Publication 1769-UM002B-EN-P - July 2005
1
Appendix
B
Module Addressing and Configuration with
MicroLogix 1500
This chapter examines the analog modules’ addressing scheme and describes module configuration using RSLogix 500 and MicroLogix 1500.
Input Module Addressing
In the following example, the 1769-IF4 is used. Detailed information on the
input image table can be found in 1769-IF4 Input Data File on page 3-2.
slot e
Input Image
Input Image
6 words
Figure B.1 1769-IF4 Memory Map Including Configuration
Memory Map
Channel 0 Data Word
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
General Status Bits
Over-/Under-range Bits
Word 0
Word 1
Word 2
Word 3
Word 4, bits 0 to 3
Word 5, bits 0 to 15
Output Image
FIle
Configuration
File
4 words
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
Bit 15 Bit 0
Word 0
Word 1
Word 2
Word 3
Refer to your controller manual for the addresses.
slot e
Configuration
File
Publication 1769-UM002B-EN-P - July 2005
B-2 Module Addressing and Configuration with MicroLogix 1500
Input Modules Input Image
The input modules’ input image file represents data words and status bits.
Input words 0 through 3 hold the input data that represents the value of the analog inputs for channels 0 through 3. These data words are valid only when the channel is enabled and there are no errors. Input words 4 and 5 hold the status bits. To receive valid status information, the channel must be enabled.
For example, to obtain the general status of channel 2 of the analog module located in slot 3, use address I:3.4/2.
Slot
Word
Bit
Input File Type
I:3.4/2
Element Delimiter Word Delimiter
Bit Delimiter
TIP
0 1 2
Slot Number
3
The end cap does not use a slot address.
Publication 1769-UM002B-EN-P - July 2005
Module Addressing and Configuration with MicroLogix 1500 B-3
Input Modules’ Configuration File
The configuration file contains information that you use to define the way a specific channel functions. The configuration file is explained in more detail in chapter 4.
The configuration file is modified using the programming software configuration screen. For an example of module configuration using RSLogix
500, see Configuring Analog I/O Modules in a MicroLogix 1500 System on page B-4.
TIP
The RSLogix 500 configuration default is to enable each analog input channel. For improved analog input module performance, disable any unused channels.
Table B.1 Software Configuration Channel Defaults
1769-IF4 and -IF8
Parameter
Enable/Disable Channel
(1)
Default Setting
Enabled
Filter Selection
Input Range
Data Format
60 Hz
±10V dc
Raw/Proportional
1769-OF2, -OF8C, and -OF8V
Parameter
Enable/Disable Channel
Output Range Selection
Data Format
Default Setting
Enabled
±10V dc
Raw/Proportional
(1)
The 1769-IF4, -IF8, -OF2, -OF8C, and -OF8V modules are disabled by default. You will need to enable the channels.
Publication 1769-UM002B-EN-P - July 2005
B-4 Module Addressing and Configuration with MicroLogix 1500
Configuring Analog I/O
Modules in a MicroLogix
1500 System
This example takes you through configuring your 1769 analog input and output modules with RSLogix 500 programming software. This application example assumes your input and output modules are installed as expansion
I/O in a MicroLogix 1500 system, and that RSLinx™ is properly configured and a communications link has been established between the MicroLogix processor and RSLogix 500.
Start RSLogix and create a MicroLogix 1500 application. The following screen appears:
While offline, double-click on the IO Configuration icon under the controller folder and the following IO Configuration screen appears.
Publication 1769-UM002B-EN-P - July 2005
This screen allows you to manually enter expansion modules into expansion slots, or to automatically read the configuration of the controller. To read the existing controller configuration, click on the Read IO Config button.
Module Addressing and Configuration with MicroLogix 1500 B-5
A communications dialog appears, identifying the current communications configuration so that you can verify the target controller. If the communication settings are correct, click on Read IO Config.
The actual I/O configuration is displayed. In this example, a second tier of
I/O is attached to the MicroLogix 1500 processor.
Publication 1769-UM002B-EN-P - July 2005
B-6 Module Addressing and Configuration with MicroLogix 1500
Configuring the Input Modules
For this example, the 1769-IF4 analog input module is installed in slot 1. To configure the module, double-click on the module/slot.
Analog Input Configuration
Each of the four analog input words (channels) are enabled by default. To enable a channel, click its Enable box so that a check mark appears in it. For optimum module performance, disable any channel that is not hardwired to a real input. Then, choose your Filter Frequency, Input Range, and Data Format for each channel.
Publication 1769-UM002B-EN-P - July 2005
TIP
For maximum noise immunity, choose 50 Hz. For the highest speed (fastest signal detection), choose 250 Hz.
Module Addressing and Configuration with MicroLogix 1500 B-7
Configuring the Output Modules
For this example, the 1769-OF2 analog output module is installed in slot 2. To configure the 1769-OF2, double-click on the module/slot.
The following general configuration screen appears for the 1769-OF2, -OF8C, and -OF8V output modules.
Publication 1769-UM002B-EN-P - July 2005
B-8 Module Addressing and Configuration with MicroLogix 1500
Analog Output Configuration
Both of the output words (channels) are enabled by default. To enable a channel, click its Enable box so that a check mark appears in it. For optimum module performance, disable any channel that is not hardwired to a real input.
Then, choose your Filter Frequency, Input Range, and Data Format for each channel.
Publication 1769-UM002B-EN-P - July 2005
Module Addressing and Configuration with MicroLogix 1500 B-9
Publication 1769-UM002B-EN-P - July 2005
B-10 Module Addressing and Configuration with MicroLogix 1500
Notes:
Publication 1769-UM002B-EN-P - July 2005
Appendix
C
Configuration Using the RSLogix 5000 Generic
Profile for CompactLogix Controllers
To configure a 1769 analog I/O module for a CompactLogix Controller in
RSLogix 5000 using the Generic Profile, you must first begin a new project in
RSLogix 5000. Click on the new project icon or on the FILE pull down menu and select NEW. The following screen appears:
1 Publication 1769-UM002B-EN-P - July 2005
C-2 Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers
Choose your controller type and enter a name for your project, then click OK.
The following main RSLogix 5000 screen appears:
The last entry in the controller organizer on the left of the screen shown above is a line labeled “[0] CompactBus Local”. Right click on this line, select “New
Module” and the following screen appears:
Publication 1769-UM002B-EN-P - July 2005
Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers C-3
This screen narrows your search for I/O modules to configure into your system. Click the OK button and the following default Generic Profile screen appears:
This is the default Generic Profile screen. The first area to fill in for the
Generic Profile screen is the name. This helps to easily identify the module type configured on your local Compact Bus. The “Description” field is optional and may be used to provide more details concerning this I/O module in your application.
The next parameter to configure is the “Comm Format”. Click the down arrow for this parameter to reveal the choices. For the 1769-OF8C and -OF8V modules, “Data – INT” is used. “Input Data –INT” is used for the 1769-IF8 module.
The slot number must be selected next, even though it begins with the first available slot number, 1, and increments automatically for each subsequent
Generic Profile you configure.
Publication 1769-UM002B-EN-P - July 2005
C-4 Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers
Use the following table for the “Comm Format”, “Assembly Instance” and
“Size” values for the 1769-IF8, -OF8C, and -OF8V modules if you have an earlier version of RSLogix5000, version 15.
1769 I/O
Modules
(1)
Comm Format Parameter
IF8
OF8C and OF8V
Input Data – INT
Data – INT
Input
Output
Config
Input
Output
Config
(1)
1769-OF2 and -IF4 modules do not use the generic profile.
Assembly
Instance
101
100
102
101
100
102
Note the Comm Format, Assembly Instance numbers and their associated sizes for each analog I/O module type and enter them into the Generic
Profile.
Size
(16-bit)
12
1
50
11
9
64
Publication 1769-UM002B-EN-P - July 2005
Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers C-5
At this point, you may click “Finish” to complete the configuration of your
I/O module. If you click “Next”, the following screen appears:
You may choose to inhibit the module or have the controller fault if the connection to this I/O module fails. The defaults for these two parameters are not to inhibit the module and not to fault the controller should an I/O module connection fail.
TIP
Refer to the Help screens in RSLogix 5000, under
“Connection Tab Overview” for a complete explanation of these features.
You may now click “Finish” to complete the configuration of your analog output module. If you click “Next”, you will see the Module Information screen, which is only filled in when you are online with your controller. If you clicked “Next” to get the Module Information screen, click “Finish” to complete the configuration of your I/O module.
Configure each analog I/O module in this manner.
Publication 1769-UM002B-EN-P - July 2005
C-6 Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers
Configuring I/O Modules
Once you have created Generic Profiles for each analog I/O module in your system, you must then enter configuration information into the Tag database that has been automatically created from the Generic Profile information you entered for each of these modules. This configuration information is downloaded to each module at program download, going to run, and at power up.
This section shows how and where to enter configuration data for each analog
I/O module, once Generic Profiles have been created for them.
You must first enter the Controller Tag database, by double-clicking on
“Controller Tags” in the upper portion of the controller organizer. The example to follow demonstrates entering configuration data for 1769-OF2 and
-IF4 modules.
For demonstration purposes, Generic Profiles have been created for 1769-IF8,
-OF8C, and -OF8V modules. The Controller Tags screen looks like the following:
Publication 1769-UM002B-EN-P - July 2005
Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers C-7
Tag addresses are automatically created for configured I/O modules. All local
I/O addresses are preceded by the word Local. These addresses have the following format:
• Input Data: Local:s.I
• Output Data: Local:s.O
• Configuration Data: Local:s.C
where s is the slot number assigned the I/O modules in the Generic
Profiles.
In order to configure an I/O module, you must open up the configuration tag for that module by clicking on the plus sign to the left of its configuration tag in the tag data base.
Configuring Analog Output Modules
To configure the 1769-OF8C or -OF8V module in slot 1, click on the plus sign left of Local:1.C. Configuration data is entered under the Local:1.C.Data tag. Click the plus sign to the left of Local:1.C.Data to reveal the 8 integer data words where configuration data may be entered for the 1769-OF8C or -OF8V module.
Configuring Analog Input Modules
To configure the input modules in slot 2, click on the plus sign left of
Local:2.C. Click on the plus sign to the left of Local:2.C.Data to reveal the 4 integer data words where the configuration data may be entered for the module. The tag addresses for these 4 words are Local:2.C.Data[0] through
Local:2.C.Data[3].
Publication 1769-UM002B-EN-P - July 2005
C-8 Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers
Notes:
Publication 1769-UM002B-EN-P - July 2005
1
Overview
Appendix
D
Configuring Modules in a Remote DeviceNet
System with a 1769-ADN DeviceNet Adapter
In this example, the 1769-IF4 and 1769-OF8C modules are in a remote
DeviceNet system controlled by a 1769-ADN DeviceNet adapter.
RSNetWorx for DeviceNet software, version 2.23 or later, is used to configure the network and the I/O modules.
The configuration method described here must be done prior to configuring the DeviceNet adapter in the DeviceNet scanner’s scanlist. This applies if you are configuring an I/O module offline, then downloading to the adapter, or if you do the configuration online. After the adapter is placed in the scanner’s scanlist, you can only configure or re-configure the I/O module using explicit messages or by removing the adapter from the scanner’s scanlist, modifying the configuration of the I/O module, and then adding the adapter back into the scanner’s scanlist.
For additional information on configuring DeviceNet scanners and adapters, refer to the documentation for those products. The DeviceNet Adapter User
Manual, publication 1769-UM001, contains examples on modifying I/O module configurations with explicit messages while the system is running.
IMPORTANT
You must use a Series B 1769-ADN adapter with the
1769-IF8, -OF8C, and -OF8V modules.
TIP
After setting up each slot, be sure to choose Apply.
Publication 1769-UM002B-EN-P - July 2005
D-2 Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter
Add the DeviceNet Adapter to the Scanlist
In this part of the example, the 1769-ADN adapter is added to the DeviceNet scanner’s scanlist.
1.
Start the RSNetWorx for DeviceNet software.
2.
In the left column under Category, click the + sign next to
Communication Adapters.
3.
In the list of products, double-click the 1769-ADN to place it on the network.
Publication 1769-UM002B-EN-P - July 2005
TIP
If 1769-ADN is not an option, you have an earlier version of RSNetWorx for DeviceNet software.
Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter D-3
4.
To configure I/O for the adapter, double-click the adapter icon that appears on the network.
5.
Click the Module Configuration tab.
TIP
The I/O Summary tab provides the configured sized and format of the I/O data.
The Transaction tab lets you send services supported by the device. The Clear/Reset Memory transaction returns the module’s configuration to the factory defaults, that is, empty. This operation cannot be undone.
Publication 1769-UM002B-EN-P - July 2005
D-4 Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter
Configure the 1769-IF4 Input
Module Example
The 1769-ADN adapter appears in slot 0. Your I/O modules, power supplies, end caps, and interconnect cables must be entered in the proper order, following the 1769 I/O rules contained in the DeviceNet Adapter User
Manual, publication 1769-UM001A. To simplify this example, we placed the
1769-IF4 in slot 1 to show how it is configured.
1.
To place the input module into slot 1, click Module Configuration.
A list of all possible 1769 products appears.
2.
Select the 1769-IF4/B.
Slot 1 appears to the right of the 1769-IF4.
3.
Under the General tab, select the appropriate bank.
Bank 1 was selected in this example.
Publication 1769-UM002B-EN-P - July 2005
Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter D-5
4.
Double-click this slot 1 box.
By default, the 1769-IF4 module contains six input words and no output words.
5.
Click the Data Description button to see what the six input words represent.
The first four words are the actual analog input data, while the last two words contain status and over- and under-range bits for the four channels.
6.
Click OK or Cancel to exit this screen and return to the Configuration screen.
7.
If your application requires only four data words and not the status information, click the Set for I/O only button
The input size changes to four words. The revision number for the series B 1769-IF4 module is two. With this setting, you may leave the electronic keying to Exact Match. It is not recommended to disable keying, but if you are not sure of the exact revision of your module, selecting Compatible Module allows your system to operate, while still requiring a 1769-IF4 module in slot 1.
The series B 1769-IF4 module differs from the series A module only in that it allows external 24V dc power. The external power connection allows you to draw 24V dc power for the module from your external source, should your 1769 power supply not provide enough 24V dc power for your particular set of 1769 I/O modules.
Publication 1769-UM002B-EN-P - July 2005
D-6 Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter
If you are using external 24V dc power for your 1769-IF4 module, you must click the white box to the left of “Using External +24v Power
Source”, so that a check mark appears in the box. Do not click on the box if you are not using external 24V dc power.
Each of the four analog input channels are disabled by default. To enable a channel, click its Enable box, so that a check mark appears in it.
Then, choose your Filter frequency, Input Range, and Data Format for each channel. See chapter 4 of this manual for a complete description of each of these configuration categories.
1769-IF4 Example of External Power
In this example, channels 0 through 4 are used and external power is being supplied from an external 24V dc power source. In addition, channels 0 and 1 are driven by 4 to 20 mA transducers, while channels 2 and 3 are driven by devices generating 0 to 10V dc analog signals.
Throughput is not a concern for this application. However, noise immunity is.
Therefore, the filter frequency for maximum noise immunity, 50 Hz, has been chosen. The analog input on channel 0 is used as the PV (input) value for a
PID loop. Therefore, the Data Format for this channel is Scaled-for-PID.
Channels 1 through 3 are not being used with a PID loop and have been configured for the Raw/Proportional Data Format for maximum resolution.
Publication 1769-UM002B-EN-P - July 2005
Click OK, and your configuration for the 1769-IF4 analog input module is complete.
Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter D-7
Configure the 1769-OF8C
Output Module Example
After leaving the 1769-IF4 configuration screen, the I/O Bank 1 screen for the
1769-ADN adapter should look like the following:
1.
Just as you did for the 1769-IF4 module, click on the drop-down arrow next to the empty slot and this time choose the 1769-OF8C.
2.
Click on the Slot 2 button that appears to the right of the 1769-OF8C module.
By default, the 1769-OF8C module contains eleven input words and nine output words.
Publication 1769-UM002B-EN-P - July 2005
D-8 Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter
3.
Click on the Configuration Settings button to see what the eleven input and nine output words represent.
The eleven input words contain channel diagnostic data for the eight channels. The nine output words contain the actual analog output data for the eight channels along with one additional word containing the control bits for unlatching alarms.
4.
Click OK or Cancel to exit this screen and return to the Configuration screen.
5.
Select No Input Data under Input Data Size if your application requires only the data words and not the status information.
The Input Size changes to 0, while the Output Size remains at nine words. The Revision number for the series B 1769-OF8C module is two. With this, you may leave the Electronic Keying to Exact Match. It is not recommended to disable keying, but if you are unsure of the exact revision of your module, selecting Compatible Module allows your system to operate, while still requiring a 1769-OF8C module in slot 2.
1769-OF8C Example of External Power
The series B 1769-OF8C module differs from the series A module only in that it allows external 24V dc power. The external power connection allows you to draw 24V dc power for the module from your external source, should your
1769 power supply not provide enough 24V dc power for your particular set of 1769 I/O modules.
If you are using external 24V dc power for your 1769-OF8C module, you must click the white box to the left of “Using External +24v Power Source”, so that a check mark appears in the box. Do not click on the box if you are not using external 24V dc power.
Publication 1769-UM002B-EN-P - July 2005
Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter D-9
1769-OF8C Example of Output Channels
Each of the two analog output channels are disabled by default. To enabled a channel, click its Enable box so that a check mark appears in it. Then, choose your Output Range, Data Format, and the state or your outputs should the controlling processor be placed into the program mode, fault, or lose communications.
Program State and Fault State each have two options:
• Hold Last State
Hold last state will hold the analog output at the last value received before the processor was placed in program mode or before it faulted.
• User-defined State
When selecting user-defined state, you must specify a value for the analog output to revert to should the processor be placed in program mode or fault. The values used for user-defined state must be valid values determined by the selected Data Format and Output Range. If communications fail, you may also choose whether your Program State or Fault State options take place for each channel.
In this example, channels 0 and 1 are enabled and configured for 4 to 20 mA
Output Ranges. The Data Format for channel 0 is Scaled-for-PID, because it is the CV (output) value from your PID instruction. Hold last state was chosen for all possible conditions other than Run mode for channel 0.
Channel 1 is also enabled and configured for 4 to 20 mA Output Range.
Raw/Proportional Data Format was chosen for maximum resolution. In addition, a requirement of the system is that this analog output must always be at 4 mA if the system is not in control of it.
Publication 1769-UM002B-EN-P - July 2005
D-10 Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter
Therefore, a value of 6241 (decimal) must be used in the event the controlling processor is placed into program mode, faults, or loses communications. The decimal number 6241 represents 4 mA, when using the Raw/Proportional
Data Format.
Click OK, and your configuration for the 1769-OF8C analog output module is complete.
Publication 1769-UM002B-EN-P - July 2005
IMPORTANT
Be sure to add appropriate power supplies and end caps.
Two’s Complement Binary Numbers
Appendix
E
1
The processor memory stores 16-bit binary numbers. Two’s complement binary is used when performing mathematical calculations internal to the processor. Analog input values from the analog modules are returned to the processor in 16-bit two’s complement binary format. For positive numbers, the binary notation and two’s complement binary notation are identical.
As indicated in the figure on the next page, each position in the number has a decimal value, beginning at the right with 2
0 and ending at the left with 2
15
.
Each position can be 0 or 1 in the processor memory. A 0 indicates a value of
0; a 1 indicates the decimal value of the position. The equivalent decimal value of the binary number is the sum of the position values.
Positive Decimal Values
The far left position is always 0 for positive values. This limits the maximum positive decimal value to 32767 (all positions are 1 except the far left position).
Figure E.1 Positive Decimal Values
2
1
32767
8
4
128
64
32
16
16384
8192
4096
2048
1024
512
256
0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
This position is always 0 for positive numbers.
EXAMPLE
0000 1001 0000 1110 = 2
11+
2
8+
2
3+
2
2+
2
1
=
2048+256+8+4+2 = 2318
0010 0011 0010 1000 = 2
13+
2
9+
2
8+
2
5+
2
3
=
8192+512+256+32+8 = 9000
Publication 1769-UM002B-EN-P - July 2005
E-2 Two’s Complement Binary Numbers
Negative Decimal Values
In two’s complement notation, the far left position is always 1 for negative values. The equivalent decimal value of the binary number is obtained by subtracting the value of the far left position, 32768, from the sum of the values
of the other positions. In Figure E.2 all positions are 1 and the value is 32767 -
32768 = -1.
Figure E.2 Negative Decimal Values
16384
8192
4096
2048
64
32
16
8
1024
512
256
128
1
32767
4
2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
This position is always 1 for negative numbers.
EXAMPLE 1111 1000 0010 0011 = (2
14+
2
13+
2
12+
2
11+
2
5+
2
1+
2
0
) - 2
15
=
(16384+8192+4096+2048+32+2+1) - 32768 =
30755 - 32768 = -2013
Publication 1769-UM002B-EN-P - July 2005
1
Glossary
The following terms and abbreviations are used throughout this manual. For definitions of terms not listed here refer to Allen-Bradley’s Industrial Automation
Glossary , Publication AG-7.1
.
A/D Converter – Refers to the analog to digital converter inherent to the module. The converter produces a digital value whose magnitude is proportional to the magnitude of an analog input signal.
alternate last state – A configuration selection that instructs the module to convert a user-specified value from the channel fault or program/idle word to the output value when the module enters the fault or program mode.
analog input module – A module that contains circuits that convert analog voltage or current input signals to digital values that can be manipulated by the processor.
attenuation – The reduction in the magnitude of a signal as it passes through a system. bus connector – A 16-pin male and female connector that provides electrical interconnection between the modules.
channel – Refers to analog input or output interfaces available on the module’s terminal block. Each channel is configured for connection to a variable voltage or current input or output device, and has its own data and diagnostic status words.
channel update time – The time required for the module to sample and convert the input signals of one enabled input channel and update the channel data word.
common mode rejection – For analog inputs, the maximum level to which a common mode input voltage appears in the numerical value read by the processor, expressed in dB.
common mode rejection ratio – The ratio of a device’s differential voltage gain to common mode voltage gain. Expressed in dB, CMRR is a comparative measure of a device’s ability to reject interference caused by a voltage common to its input terminals relative to ground. CMRR=20 Log
10 (V1/V2) common mode voltage – For analog inputs, the voltage difference between the negative terminal and analog common during normal differential operation.
common mode voltage range – For analog inputs, the largest voltage difference allowed between either the positive or negative terminal and analog common during normal differential operation.
Publication 1769-UM002B-EN-P - July 2005
2
Publication 1769-UM002B-EN-P - July 2005 configuration word – Contains the channel configuration information needed by the module to configure and operate each channel.
D/A Converter – Refers to the digital to analog converter inherent to the output module. The converter produces an analog dc voltage or current signal whose instantaneous magnitude is proportional to the magnitude of a digital value.
dB – (decibel) A logarithmic measure of the ratio of two signal levels.
data echo – The analog value currently being converted by the D/A converter and shown in words 2 and 3 of the output module’s input data file. Under normal operating conditions, the data echo value is the same value that is being sent from the bus master to the output module.
data word – A 16-bit integer that represents the value of the analog input or output channel. The channel data word is valid only when the channel is enabled and there are no channel errors. When the channel is disabled the channel data word is cleared (0).
differential operation – The difference in voltage between a channel’s positive terminal and negative terminal.
digital filter – A low-pass filter incorporated into the A/D converter. The digital filter provides very steep roll-off above it’s cut-off frequency, which provides high frequency noise rejection.
filter – A device that passes a signal or range of signals and eliminates all others.
filter frequency – (-3 dB frequency) The user-selectable frequency.
full scale – The magnitude of voltage or current over which normal operation is permitted.
full scale error – (gain error) The difference in slope between the actual and ideal analog transfer functions.
full scale range – (FSR) The difference between the maximum and minimum specified analog input values.
hold last state – A configuration selection that instructs the module to keep the outputs at the last converted value prior to the condition that caused the control system to enter the fault or program mode.
input image – The input from the module to the controller. The input image contains the module data words and status bits.
3
LSB – (Least Significant Bit) The bit that represents the smallest value within a string of bits. For analog modules, 16-bit, two’s complement binary codes are used in the I/O image in the card.
For analog inputs, the LSB is defined as the rightmost bit, bit 0, of the 16-bit field. For analog outputs, the three rightmost bits are not significant, and the
LSB is defined as the third bit from the right, bit 2, of the 16-bit field.
linearity error – An analog input or output is composed of a series of voltage or current values corresponding to digital codes. For an ideal analog input or output, the values lie in a straight line spaced by a voltage or current corresponding to 1 LSB. Any deviation of the converted input or actual output from this line is the linearity error of the input or output. The linearity is expressed in percent of full scale input or output. See the variation from the straight line due to linearity error (exaggerated) in the example below.
Actual Transfer
Function
Ideal Transfer number of significant bits – The power of two that represents the total number of completely different digital codes an analog signal can be converted into or generated from.
module scan time – same as module update time module update time – For input modules, the time required for the module to sample and convert the input signals of all enabled input channels and make the resulting data values available to the processor. For output modules, the time required for the module to receive the digital code from the processor, convert it to the analog output signal, and send it to the output channel.
multiplexer – An switching system that allows several signals to share a common A/D or D/A converter.
normal mode rejection – (differential mode rejection) A logarithmic measure, in dB, of a device’s ability to reject noise signals between or among circuit signal conductors.
normal operating range – Input or output signals are within the configured
range. See page 1-2 for a list of input and output types/ranges.
Publication 1769-UM002B-EN-P - July 2005
4 overall accuracy – The worst-case deviation of the output voltage or current from the ideal over the full output range is the overall accuracy. For inputs, the worst-case deviation of the digital representation of the input signal from the ideal over the full input range is the overall accuracy. this is expressed in percent of full scale.
Gain error, offset error, and linearity error all contribute to input and output channel accuracy.
output accuracy – The difference between the actual analog output value and what is expected, when a given digital code is applied to the d/a converter. Expressed as a ± percent of full scale. The error will include gain, offset and drift elements, and is defined at 25°C, and also over the full operating temperature range (0 to 60°C).
output image – The output from the controller to the output module. The output image contains the analog output data. analog output module – An I/O module that contains circuits that output an analog dc voltage or current signal proportional to a digital value transferred to the module from the processor.
repeatability – The closeness of agreement among repeated measurements of the same variable under the same conditions.
resolution – The smallest detectable change in a measurement, typically expressed in engineering units (e.g. 1 mV) or as a number of bits. For example a 12-bit system has 4096 possible output states. It can therefore measure 1 part in 4096.
status word – Contains status information about the channel’s current configuration and operational state. You can use this information in your ladder program to determine whether the channel data word is valid.
step response time – For inputs, this is the time required for the channel data word signal to reach a specified percentage of its expected final value, given a large step change in the input signal.
update time – see “module update time”
Publication 1769-UM002B-EN-P - July 2005
Index
Numerics
1769-ADN configuration example
A
A/D
definition
abbreviations
alarms process alarm analog input data
analog input module definition
attenuation cut-off frequency
definition
B
bus connector definition
C
channel definition
channel diagnostics
3-8, 3-24 channel scan time 3-8, 3-24
channel switching time
channel update time definition
CMRR. See common mode rejection ratio
common mode rejection 3-6, 3-23, A-3
definition
common mode rejection ratio definition
common mode voltage
common mode voltage range
common mode voltage rating 3-6, 3-23
configuration errors
configuration word
1769-OF2
contacting Rockwell Automation
current draw
1769-OF2
cut-off frequency
D
D/A converter
data loopback
data echo.
data word
dB
DeviceNet adapter configuration example
user manual publication number
differential mode rejection. See normal mode rejection.
differential operation
E
electrical noise
end cap terminator
Publication 1769-UM002B-EN-P - July 2005
2 Index errors
critical
extended error information field
module error field
extended error information field
F
fault condition at power-up
fault value
filter
and channel step response and channel update time
finger-safe terminal block 2-16
frequency
cut-off frequency 3-7, 3-24 response graphs 3-7, 3-24
full scale
full scale error
full scale range
1769-IF4 specifications
G
gain error. See full scale error.
generic profile
H
hold last state
program/idle mode
I
input data file
input data formats engineering units percent range
3-10, 3-28 raw/proportional data 3-10, 3-27
scaled for PID
valid formats/ranges
input filter selection
input image
input module
enable channel
input module status
over-range flag bits
under-range flag bits
input type/range selection 3-9, 3-27
grounding
heat and noise considerations
L
least significant bit. See LSB.
Publication 1769-UM002B-EN-P - July 2005
Index 3
M
module error field
module scan time
mounting
multiplexer
multiplexing
N
negative decimal values
normal mode rejection
number of significant bits
O
open-circuit detection
operation system
out-of-range detection
over-range flag bits
under-range flag bits
output data formats engineering units
percent full range
raw/proportional data
output image
output module channel configuration
output module status diagnostic bits
hold last state bits 4-2, 4-21
over-range flag bits
under-range flag bits
output range selection
overall accuracy
P
positive decimal values
process alarms
1769-IF8 modules
program/idle mode
program/idle to fault enable 4-10, 4-31
program/idle value
R
reconfiguration time 3-8, 3-24
removing terminal block
replacing a module
resolution
RSLogix 500
RSLogix 5000
RSNetworx
S
safety circuits
scan time
spacing
specifications
input
1769-IF8
output
1769-OF8C
1769-OF8V
status word
step response
step response time
system operation
Publication 1769-UM002B-EN-P - July 2005
4 Index
T
terminal block
wiring
terminal door label
terminal screw torque
troubleshooting safety considerations
two’s complement binary numbers
U
under-range flag bits
update time. See channel update time.
update time. See module update time.
W
wire size
differential inputs
input terminal layout mixed transmitter type
modules
ouput terminal layout
single-ended sensor/transmitter types
terminal block
Publication 1769-UM002B-EN-P - July 2005
How Are We Doing?
Your comments on our technical publications will help us serve you better in the future.
Thank you for taking the time to provide us feedback.
You can complete this form and mail (or fax) it back to us or email us at
Pub. Title/Type Compact I/O Analog Modules
Cat. No.
1769-IF4, -IF8, -OF2,
-OF8C, and -OF8V
Pub. No.
1769-UM002B-EN-P Pub. Date July 2005 Part No.
Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding).
Overall Usefulness 1 2 3 How can we make this publication more useful for you?
Completeness
(all necessary information is provided)
1 2 3 Can we add more information to help you?
procedure/step illustration example explanation guideline definition feature other
Technical Accuracy
(all provided information is correct)
1 2 3 Can we be more accurate?
text illustration
Clarity
(all provided information is easy to understand)
1 2 3 How can we make things clearer?
Other Comments You can add additional comments on the back of this form.
Your Name
Your Title/Function
Location/Phone
Would you like us to contact you regarding your comments?
___No, there is no need to contact me
___Yes, please call me
___Yes, please email me at _______________________
___Yes, please contact me via _____________________
Return this form to: Rockwell Automation Technical Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705
Fax: 440-646-3525 Email: [email protected]
Publication CIG-CO521C-EN-P- May 2003 PN 957782-91
Other Comments
PLEASE FASTEN HERE (DO NOT STAPLE)
PLEASE FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
1 ALLEN-BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
Publication 1769-UM002B-EN-P - July 2005 1
Supersedes Publication 1769-UM002A-EN-P - October 2000 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.