M ICRO F LOW -
I
NSTRUCTION
M
ANUAL
M ICRO F LOW (F IRST E DITION R EV 5)
May 2019
Part Number M-MFi-S-001-5P
C OPYRIGHT
© Pulsar Process Measurement Limited, 2017 - 2019. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form without the written permission of Pulsar Process Measurement Limited.
W ARRANTY AND L IABILITY
Pulsar Process Measurement Limited guarantee for a period of 2 years from the date of delivery that it will either exchange or repair any part of this product returned to Pulsar Process Measurement Limited if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication or negligence.
D ISCLAIMER
Pulsar Process Measurement Limited neither gives nor implies any process guarantee for this product and shall have no liability in respect of any loss, injury or damage whatsoever arising out of the application or use of any product or circuit described herein.
Every effort has been made to ensure accuracy of this documentation, but Pulsar Process Measurement
Limited cannot be held liable for any errors.
Pulsar Process Measurement Limited operates a policy of constant development and improvement and reserves the right to amend technical details as necessary.
The MicroFlow-i shown on the cover of this manual is used for illustrative purposes only and may not be representative of the actual MicroFlow-i supplied.
T ECHNICAL E NQUIRIES
Please contact Pulsar Process Measurement Limited for technical support.
C OMMENTS AND S UGGESTIONS
If you have any comments or suggestions about this product, then please contact:
Pulsar Process Measurement Limited
Cardinal Building
Enigma Commercial Centre
Sandy’s Road
Malvern
Worcestershire
WR14 1JJ
United Kingdom
Pulsar Process Measurement Inc.
PO Box 5177
Niceville
FL 32578-5177
USA
Tel: + 44 (0) 1684 891371 Tel: + 1 850 279 4882
Web Site: https://www.pulsar-pm.com Web Site: https://www.pulsar-pm.com e-mail: [email protected] (general information) e-mail: [email protected] (general information) e-mail: support@ pulsar-pm.com (product support) e-mail: support.usa@ pulsar-pm.com (product support)
Pulsar® is a registered trademark of Pulsar Process Measurement Ltd in the UK, USA and China.
Contents
Chapter 1 Start Here…
Congratulations on your purchase of a Pulsar MicroFlow-i . This quality system has been developed over many years and represents the latest in high technology flow monitoring.
It has been designed to give you years of trouble free performance, and a few minutes spent reading this operating manual will ensure that your installation is as simple as possible.
About this Manual
It is important that this manual is referred to for correct installation and operation.
There are various parts of the manual that offer additional help or information as shown.
Tips
TIP
At various parts of this manual you may find tips to help you.
Additional Information
Additional Information
At various parts of the manual, you will find sections like this that explain specific things in more detail.
References
See also text in Bold as these may be references to other parts of this or another manual.
Drawings
It should be noted that drawings or pictures shown in this manual may not be to scale.
Page 1
About the
MicroFlow-i
The MicroFlow-i is a 2-wire loop-powered non-contacting velocity sensor, with hazardous area approval. The sensor provides reliable flow velocity measurements using short pulses of micro-waves, which are transmitted by an enclosed antenna. When reflected off a moving surface, the signal experiences a shift in frequency characteristics. The reflected signal is captured by the onboard microprocessor via the antenna, and analysed to determine the velocity.
The MicroFlow-i’s compact and versatile design makes it easy to install and ideal for confined spaces. Housed in a robust enclosure coupled with a fully encapsulated microwave antenna, it provides an effective fit-and-forget flow velocity solution.
Perfect for remote monitoring or when there is no mains power available, due to its low power consumption. To access flow velocity data, use Pulsar’s
MicroFlow-i HART PC or HART protocol.
Overall the device has outstanding stability, accuracy and repeatability.
Page 2
Benefits
Combined with the ease of programming there are many other benefits to using the MicroFlow-i , these are listed below:
•
Non-contact velocity measurement.
•
Loop powered and ideal for remote monitoring.
•
Low-power consumption.
•
Hazardous area approval (Ex ia) for Zone 0.
• ‘See through’ capability for enclosed plastic pipes and concrete (not reinforced) channels.
•
Suitable for abrasive and aggressive materials.
•
Resilient to liquid vapour, wind or temperature.
•
No minimum liquid level required for measurement
•
Maintenance free.
•
No interruption to operational flow.
•
Can be installed in addition to existing in process contact measuring devices.
•
Easily setup using MicroFlow-i HART PC .
•
The sensor is capable of monitoring flow of very shallow liquid, mitigating the constraint associated with in-liquid techniques.
Page 3
Functional Description
Based upon state-of-the-art micro-wave sensing technology, the MicroFlow-i integrates Pulsar’s innovative and award winning DSP (Digital Signal Processing) platform, offering you a cost effective solution with excellent reliability and performance.
The Pulsar MicroFlow-i has been designed to provide maintenance free performance. The MicroFlow-i i is also intrinsically safe (Ex ia) for Zone 0.
The MicroFlow-i can be mounted via a rear 1” BSP to M20 thread adapter
(supplied with unit). The MicroFlow-i is loop powered and gives a 4 to 20mA output which is proportional to the flow velocity . A ‘fault condition’ alarm will give out a reading of either 3.8mA or 22mA.
The 2 wire sensor can either be used in digital HART mode or as 4-20mA loop powered device. The MicroFlow-i loop powered version can be set up using a
HART modem with either proprietary HART software such as Pact ware or Pulsar
MicroFlow-i HART PC software.
Boot up time from power up to stable reading: cold boot 8.5 seconds, warm boot
4 seconds (if within 12 hours from last start up).
Page 4
Product Specification
Physical
Sensor body material
Mounting Connection
Mounting angle:
Sensor body dimensions
Sensor body weight
Transducer cable extensions
Maximum separation
Valox 357
Via
1” BSP back mounted thread, 45 o
Angled
Mounting bracket and M20 thread adaptor
(optional).
45° optimum and mounted at the centre line of the channel with clear uninterrupted view
Diameter 90mm x height 140mm (3.54in x 5.51in)
Nominal 0.7kg (1.54 lbs)
2 core screened
Up to 1000m (3280ft)
Environmental
Enclosure protection
Max. & min. temperature (electronics)
Approvals
ATEX
CE and Radar Approval
IP68
-20 ºC to +60 ºC (-4°F to +140°F)
CML 16ATEX2331X, IECEx CML 16.0105X
II 1 G Ex ia IIC T4 Ga
II 1 D Ex ia IIIC T135 0 C Da
See EU Declaration of Conformity
Performance
Velocity Range
Accuracy
Optimum installation
Maximum channel width per sensor
Radar
Transmitter Power
Beam width
Outputs
Communication
0.2 – 6.0 m/s (0.66 – 19.7 ft/s)
The greater of ± 1.5% or 0.05 m/s (0.1ft/s)
Install at an angle of 45° in line with flow. For more information, see ‘Locating the MicroFlow-i sensor’ section of this manual
1.5m (4.92ft)
K-Band (ISM)
<15 dBm
20° inclusive
HART compatible, 4-20mA loop powered
Programming
PC programming
Programming security
Programmed data integrity
PC setup and monitoring software
MicroFlow-i HART PC via passcode
Via non-volatile memory compatible Win 7, Win 8, Win 10
Supply
Operating Voltage
Power Consumption
10 – 28VDC
Start up = 20mA. Average current = 60µA per hour when one velocity measurement is performed every 15 minutes
Pulsar Process Measurement Limited operates a policy of constant development and improvement and reserve the right to amend technical details as necessary.
Page 5
EU Declaration of Conformity
Page 6
Chapter 2 Installation
Unpacking
Important Information
All shipping cartons should be opened carefully. When using a box cutter, do not plunge the blade deeply into the box, as it could potentially cut or scratch equipment components. Carefully remove equipment from each carton, checking it against the packing list before discarding any packing material. If there is any shortage or obvious shipping damage to the equipment, report it immediately to Pulsar Process Measurement Limited.
Power Supply Requirements
The MicroFlow-i can operate from a DC supply of 10 to 28V. In all cases the unit typically consumes 0.52W of power and will typically draw less than 22mA.
Cable Requirements
The MicroFlow-i comes with a fitted integral cable, if this cable is extended then the total capacitance must not exceed the limits for the voltage applied, and the hazardous area it is installed in.
The HART modem and PC or HART programmer are used to set up the operation parameters for the MicroFlow-i sensor. The output can either be as a
4-20mA current giving flow velocity or as a digital signal via a HART master.
The MicroFlow-i cable is a twisted pair with an overall cable screen. The twisted pair are red and black, connect the red to +ve and the black to the -ve.
The screen should go to signal ground.
Important Information
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
Page 7
Information specific to Hazardous Area Installation
(Reference European ATEX Directive 2014/34/EU )
The following instructions apply to equipment covered by certificate number CML
16ATEX2331X
1.
The equipment may be used with flammable gases and vapours with apparatus groups IIC, IIB, and IIA with temperature classes; T4 ambient temperature range -20 o C to +60 o C.
2.
The equipment is only certified for use in ambient temperatures in the range -
20 o C to +60 o C and should not be used outside this range.
3.
Installation shall be carried out in accordance with the applicable code of practise by suitably trained personnel.
4.
Repair of the equipment shall be carried out in accordance with the acceptable code of practise.
5.
Certification as detailed in drawing number D-804-1200 (Ex ia).
6.
If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised .
Aggressive Substances : e.g. such as acidic liquids or gases that may attack metals or solvents that may affect polymeric materials.
Suitable precautions : e.g. regular checks as part of routine inspections or establishing from the materials data sheet that it is resistant to specific chemicals.
7.
The certificate number has an ‘X’ suffix that indicates that the following special condition of certification applies. In the case of the MicroFlow-i sensor, due to the housing and labels being non-conductive plastic care needs to be taken with regards to electrostatic charge. The equipment shall not be installed if the conditions are conductive to the build-up of electrostatic charge.
Additionally, the equipment should only be cleaned with a damp cloth.
Limitations on use
1.
The MicroFlow-i must be routinely inspected to avoid the build-up of dust layers when installed in Zone 21 & Zone 22.
2.
Electrostatic hazard – The MicroFlow-i must only be wiped with a damp or antistatic cloth.
3.
The outer enclosure is made from Valox357U, consider the performance of this material with respect to chemicals that may be present in the hazardous area.
Page 8
Hazardous Area Specific Power Supply and barrier Requirements
The MicroFlow-i operates from a DC supply of 10 – 28VDC and will typically draw less than 22mA. When connecting sensor to the PC software with a HART modem, it is recommended to use a supply of at least 18VDC.
Important Information
In the case of the Ex ia version, the sensor must be powered from an approved I.S. safety barrier or approved I.S. power supply with the following limits:
Uo <= 28V, Io <= 162mA, Po <= 1.03W
The MicroFlow-i cable is a twisted pair with overall cable screen. The twisted pair is red and black, connect the red to +ve and the black to -ve. The screen should go to signal ground.
Typical wiring for the MicroFlow-i :
SAFE AREA
PSU/SENSE
LOAD/SENSE
+
V
24VDC
-
Ex ia Version 4-20mA mode
HAZARDOUS
AREA
I.S. EARTH
Ui<=28V
Li<=162mA
Pi<=1.03W
SINGLE ZENNER BARRIER
SINGLE ZENNER BARRIER
CURENT SENSED IN +ve
Page 9
Ex ia Version 4-20mA mode
SAFE AREA
PSU/SENSE
HAZARDOUS
AREA
+
V
24VDC
-
LOAD/SENSE
I.S. EARTH
Ui<=28V
Li<=162mA
Pi<=1.03W
DUAL ZENNER BARRIER
DOUBLE ZENNER BARRIER
CURENT SENSED IN +ve
Ex ia Version 4-20mA mode
SAFE AREA
PSU/SENSE
HAZARDOUS
AREA
CURRENT
SENSE
Page 10
V
+
-
GALVANIC ISOLATOR
GALVANIC ISOLATOR
Ui<=28V
Li<=162mA
Pi<=1.03W
Location
All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
When choosing a location to mount the bracket and MicroFlow-i , note the following:
•
For optimum readings, it is recommended that the MicroFlow-i should be positioned at a 45° angle to the surface of the material being measured.
•
The mounting surface must be vibration-free.
•
The ambient temperature should be between -20ºC and 60ºC.
Important Information
When installing the MicroFlow-i it is recommended that it is mounted at least 1m away from moving persons or machinery.
Mounting
For the best results it is highly recommended to use the MicroFlow-i angled bracket, which is available from your Pulsar distributor, which will ensure that the
MicroFlow-i can be correctly installed. The bracket can be used if the MicroFlowi sensor is to be mounted on its own in a specific location or along with a Pulsar dBi or dB level transducer. Please see ‘ Angled Mounting Bracket ’ for dimensions of this bracket, please note that the drawing is not to scale.
‘ Mounting sensor to a bracket ’ illustrates how you would install the sensor to one of Pulsar’s angled brackets.
The MicroFlow-i angled bracket should be mounted by marking and drilling the holes suitable for fixing your screws/bolts (length to suit your application) and then fixing the bracket in place.
Page 11
Angled Mounting Bracket
Part number: dBA0008MF
176mm
45 o
Side view
100mm
22mm
22mm
R20mm
12mm
90mm
130mm
Top view
Page 12
100mm
60mm 20mm
14mm
100mm
60mm
26mm
4 off 12mm
20mm
R20mm
Rear view
Important Information
Using a spirit level, ensure that the Mounting Bracket is level before attaching the sensor to the bracket.
Page 13
MicroFlow-i sensor
The dimensions of the sensor body are shown below in Fig.1 and Fig.2:
78 mm
1” BSP
73 mm
M i
Page 14
90 mm
BOTTOM
Fig.1
Green ‘Dot’ to be positioned on top of sensor.
45°
Surface of measurement
Fig.2
To obtain the most accurate results, ensure the device is mounted at a 45° angle to the surface being measured.
Mounting sensor to a bracket
Mounting the sensor to the 45° angled bracket is done via an adapter and M20 nut, as shown in Fig.3:
Bracket
M20 Nut
Green dot to be displayed on top
Adapter
Cable
Fig.3
For correct installation, we recommend that the adapter is threaded on the cable, and carefully screwed onto the MicroFlow-i before fitting to the bracket. This will reduce the risk of any ’twisting’ in the cable.
Ensure that the sensor is tightened and the dot is in the correct position.
Important Information
When fixing the sensor to the adapter, ensure that care is taken when pulling the sensor cable through. And once attached to the adapter, and the M20 nut is tightened, the green dot should be central to the movement of flow as shown in Fig.4.
Page 15
M i
Fig.4
Central to the movement of flow in channel.
Care should be taken not to overtighten the sensor when everything is connected, as seen in Fig.5 below, as this could cause damage to the housing.
305mm
215mm
129mm
Fig.5
Page 16
When the sensor is mounted on the bracket with dB or dBi series level transducer, you can position the bracket in a way where the MicroFlow-i is obtaining measurements following the direction of the flow, or facing the direction of flow. Fig.6 and Fig.7 illustrate the correct positioning of the devices according to the direction of flow:
Green dot to be displayed on top
Direction of flow
Fig.6
Green dot to be displayed on top
Fig.7
Direction of flow
Page 17
Terminal Connection Details
Terminal Connections
Power
The MicroFlow-i operates from a DC voltage supply of 10-28 volts, and should be installed and connected in accordance with ‘ Chapter 2–Power supply requirements ’ and the instructions below. When wiring the MicroFlow-i you should use a twisted pair cable. The wire coding is shown below for ease of use when connecting the MicroFlow-i to monitor flow velocity:
MicroFlow-i cable
Bootlace
Ferrules
Power +10-28 VDC (Red cable)
Heat Shrink
110 mm
0 Volts (Black cable)
Screen (Green cable)
You can also use Pulsar’s
MicroFlow-i HART PC software to interrogate and obtain readings from the device. Please refer to Chapter 6 MicroFlow-i HART
PC for more details on how to use it.
Important Information
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
Page 18
Chapter 3 Locating the MicroFlow-i sensor
For optimum accuracy install the MicroFlow-i where the flow is not turbulent.
An ideal location for the sensor is in the centre of a long straight channel.
Vertical drops, baffles, curves or junctions can cause the velocity profile to be distorted.
To obtain optimum results in velocity readings, the MicroFlow sensor requires surface ripples to be present to provide a reliable measurement. If there are not any surface ripples within the sensors field of view under ant flow conditions, then an alternative measurement point should be found, or ripples created.
Locating the MicroFlow-i
•
If the width of the channel exceeds 1.5m. Multiple MicroFlow-i sensors are required to be used in conjunction with the Ultimate Controller with firmware version 1.5.2 and later.
•
When a level measurement transducer is used and mounted on the same bracket as the MicroFlow-i . Take into account, the ‘blanking’ distance of the transducer when mounting the bracket for the application.
•
Ensure that there is an unobstructed path between the sensor and the surface of the moving liquid being measured.
•
Position the sensor at a height of 250mm above maximum liquid level or up to two times the channel width from the minimum liquid level, whichever is greater. As shown in Fig.8 below:
MicroFlow
A
Max Liquid
Level
Min Liquid
Level
•
A = Minimum 250mm above Maximum Liquid level.
•
B = Maximum 3m above Minimum Liquid Level.
B
Fig.8
Important Information
If the maximum water height exceeds 2x width of the channel OR
If the maximum water height in channel is less than 50% of the width of the channel. Please consult Pulsar product support for assistance.
Page 19
•
In the instance where there are vertical drops, baffles, curves or junctions. The sensor should then be positioned on a straight part of the channel, at a minimum distance that is at least five times the width of the channel before a bend, in order to obtain optimal velocity readings.
Examples of positioning the sensor are shown in diagrams 1 - 4 below:
Diagram 1
Distance
Distance
Diagram 2
Page 20
Diagram 3
Distance Distance
Diagram 4
Distance Distance
Page 21
Installing the Sensor
• The sensor is supplied with a 1” BSP to M20 thread adapter. The Sensor housing is designed to accept a 1” BSP female threaded coupler for pipe or conduit.
•
Ensure that the sensor is positioned at a 45° angle to the surface of the measured application, as this will achieve the best results. An example of this is shown in the diagram below:
Green dot to be displayed on top
45°
Surface of measurement
•
When using one of the Pulsar Angled Mounting Brackets, secure the bracket using the correct size screws/bolts/U-bolts (12mm diameter thread).
•
Tighten the sensor into the bend, and then screw the thread adapter onto the bracket using the nut supplied. CAUTION: extreme over-tightening may crack or cause damage to the unit or bracket.
•
Position the sensor so the green ‘dot’ that is shown on the label between the two green arrows is on the top of the device, and is central to the movement of flow in the channel.
•
If desired, the sensor cable may be extended up to a maximum of 1000m.
Install the sensor cables in grounded metal conduit. Do not run in cable trays or duct banks with variable frequency drives or other high voltage sources.
•
When extending cable for a MicroFlow-i sensor, ensure that all wiring in any junction /connector boxes are correct.
•
Attention should also be taken, when mounting the unit, to ensure that strong windy conditions are avoided wherever possible to prevent abnormal operation.
•
The sensor can be positioned to obtain readings following the direction of the flow. Or it can be positioned to measure the oncoming flow as seen below:
Page 22
MicroFlow-i obtaining readings following the direction of the flow.
MicroFlow-i obtaining readings from the oncoming direction of the flow.
Preparation for Operation
Before switching on, ensure that the following is checked:
✓
The MicroFlow-i is mounted correctly and is secure as outlined in
Chapter 3 – Locating the MicroFlow-i sensor .
✓
All wiring is correct.
✓
The power supply is correctly installed.
General Maintenance
There are no user serviceable parts inside MicroFlow-i . If you experience any problems with the unit, then please contact Pulsar Process Measurement for advice.
To clean the equipment, wipe with a damp cloth. Do not use any solvents on the enclosure.
Page 23
Sensor Maintenance.
Procedure for the Removal of a MicroFlow-i Sensor
From time to time it may be necessary to remove the sensor for cleaning or maintenance purposes, the below procedure is to ensure that this is done carefully with regard for the health and safety of the operator involved, and without damage to the sensor.
Important Information
Before attempting to remove the sensor for cleaning or any other purpose, the power to the unit should be disconnected.
If it is necessary to replace the sensor for any reason, the following procedure should be followed:
•
Disconnect the power supply to the sensor.
•
Remove any fittings that the sensor may be attached to, allowing the cable to be pulled through with ease.
•
If using a Pulsar angled bracket, the sensor head is mounted onto the end of the bend via its process fitting, this should be carefully unscrewed in an anticlockwise direction. Ensure that the sensor is not dropped or knocked as this can cause damage to the unit.
•
When replacing the sensor, care must be taken not to over tighten the unit as this can cause damage. Hand tight is sufficient.
•
Ensure that the green dot has been positioned in the direction of the flow of the vessel, this will obtain optimum velocity readings that are available.
Please refer to ‘ Fig.3
’ in ‘ Chapter 2-Installation ’ section on how to do this.
•
When the sensor has been replaced for the application, and re-connected to a controller and the power re-applied, the unit will re-initialise and will begin the process of acquiring flow and velocity readings.
•
When refitting or replacing a sensor, ensure that it is installed in accordance with ‘
Chapter 2-Mounting a sensor to a bracket
’.
•
When replacing the sensor for a new one, you can use MicroFlow-i HART
PC to upload any changed parameters from your old sensor to the new sensor.
Allowing continued use of the sensor which is setup for your application.
The correct PPE should be worn on site when performing maintenance on the system, if in doubt please contact your site Health and Safety Officer for further advice.
Page 24
Important Information
Care should be taken when removing and cleaning so as to not damage the device.
To remove the sensor, first loosen any glands, couplers etc. that may connect it to the Mounting Bracket, and then lift the sensor body onto a safe place. Taking care not to damage the sensor housing or cable whilst performing this removal.
The sensor can then be safely inspected for damage or material fouling and can be carefully cleaned with a damp cloth to remove any foreign debris.
Page 25
This page is left blank intentionally
Page 26
Chapter 4 Understanding how the MicroFlow-i operates
In order to initially set up the MicroFlow-i (if required) to obtain readings from your application, it is advised to do this using MicroFlow-i HART PC .
Once the MicroFlow-i has been powered up, you can now begin to obtain flow velocity from the sensor.
MicroFlow-i HART compatible
The MicroFlow-i uses a unique protocol which enables it to be compatible to any
HART controller that it is connected to, the HART address is ‘0’.
To enable the MicroFlow-i to work successfully, ensure that the power is disconnected prior to a connection being made.
4 – 20 mA Device
The MicroFlow-i can be used as an ‘out of the box’ 4 – 20mA device, this is the case, by default when you switch the sensor on. The 4 – 20mA output is proportional to the flow velocity being seen, with respect to the maximum range of the sensor up to 6 m/s (19.7 ft/s).
Important Information
For further information on how to set up the sensor as a mA device, please contact your local Pulsar distributor.
Page 27
Page 28
This page is left blank intentionally
Chapter 5 MicroFlow-i HART PC
The software that accompanies the MicroFlow-i can be used to access and change all parameters via the HART modem, test, obtain and record trace readings from a sensor. To utilise the features of the software, a USB HART modem which is available from Pulsar (as shown in Fig.9 below), is required to communicate between the sensor and your machine.
Fig.9
Software installation
Insert the CD that accompanies the MicroFlow-i sensor into your PC/Laptop. If you do not have a CD drive on your laptop, then this software can be downloaded from the Pulsar Process Measurement website: www.pulsarpm.com/support/downloads/software.aspx
and choose to download MicroFlow-i
HART PC from the list which will then be downloaded onto your machine.
When setting up the HART modem for the first use, you will need to install the necessary drivers for it to operate correctly with your OS. These drivers can be installed from your installation disc. Run the MicroFlow-i HART PC Setup.exe from the CD, or from the downloaded file from our website to install the
MicroFlow-i HART PC software correctly, which will automatically install the necessary drivers for your HART modem. Once downloaded, a shortcut icon will be created onto your Desktop for ease of use. Double click on this icon to launch the program.
Important Information
For optimum installation insert your HART modem to your PC whilst installing MicroFlow-i HART PC , where your PC should then assign the modem to a Com Port. Or if you have an internet connection, upon inserting the USB of the HART modem for the first time,
Windows updates should install this onto your computer for you.
Once the driver’s installation has completed, remove the HART modem from your machine. Your modem is ready to be used when a connection to MicroFlow-i PC is required.
Page 29
Connecting to MicroFlow-i HART PC
When connecting to the software using the HART modem, power to the sensor can be obtained from a 10-28VDC source.
Important Information
Ensure that power to the sensor is switched ‘OFF’ before removing cables and any connection is made.
To enable the MicroFlow-i to work correctly please ensure that the sensor is wired as shown in the picture below:
0V from supply
(Black cable)
0V to MicroFlow-I (Black cable)
Power (+) from supply
(Red cable)
Connector from
Connector from
Power (+) to MicroFlow-i
(Red cable)
250 Ohm resistor
To enable the sensor to work correctly, the power (red) cables from the supply and to the MicroFlow-i must be wired in series with the 250 Ohm resistor (as seen in the above picture).
Once the sensor is connected to the HART modem, insert the USB into the
PC/laptop ready for use. You can now use MicroFlow-i HART PC to change settings of the sensor to suit your application.
To make a connection to the MicroFlow-i sensor, supply power to the sensor and then select the button which will change to ‘Scanning’ and the following pop-up windows will appear during an initial connection:
Page 30
Once the MicroFlow-i parameters have been retrieved successfully, the status condition will then appear as below:
Page 31
If the sensor fails to connect to the software, please check that the Comport has been correctly set (details of how to do this is outlined in this chapter). After launching the program and connecting to the MicroFlow-i , the device’s parameters will be automatically extracted once a connection is established.
Once connected you can now view the information received from the sensor on the Software’s individual tabs: Flow , Configuration and Trace .
appears after a connection is established, selecting this will then disconnect the MicroFlow-i .
Flow Tab
The above picture is an example of the default screen of MicroFlow-i HART PC , which is the Flow tab. The dial on the left displays the linear flow velocity of a maximum up to 6m/s (19.7 ft/s). While the numerical display on the right shows the velocity flow rate and the current mA reading.
Signal Strength
The signal strength gives an indication of the actual strength of the velocity signal detected. A level of higher than 70% is desired for reliable operation.
Page 32
Stability
The stability level is an indication of the consistency of flow reading, as derived from the combination of signal strength and statistical fluctuations of the flow reading. A high level of stability would indicate optimum condition, and relatively healthy flow within the channel and indicate higher levels of repeatability and better flow tracking. The stability does not necessarily indicate the accuracy of the flow reading, as this is subject to calibration.
Configuration Tab
Parameter Get/Set
This feature allows you to obtain and change parameter values from the list available. Further information of these parameters and their values can be found in Chapter 7 – Parameter Listing and Descriptions .
Get:
This will read and display the current ‘Value’ of the parameter selected, along with
‘Units’ of measurement where used, and a brief description of the parameter selected. Select the desired parameter from the drop down ‘Parameter’ box and select ‘Get’
Page 33
Default:
When selected, this will display the current parameters default value. Selecting
‘Set’ will change the parameters value to that of its default value.
Set:
Allows the value of the selected parameter to be changed. Select the desired parameter from the drop down ‘Parameter’ box, enter the required value and select
‘Set’. The value box will turn green when the change of parameter value has been successfully carried out.
MicroFlow-i Manual Setting
The option for manually setting the parameters can be done by utilising the Manual
Setting terminal, as shown below:
This feature is also available when the sensor has been set into ‘Program mode’, where all if the MicroFlow-i parameters can be queried by entering the parameter address in the Parameter field and then clicking on the ‘Get’ button. The
MicroFlow-i will then reply with the current value of that parameter.
Selecting ‘Get’ will read and display the current value of the MicroFlow-i parameter selected. When ‘selected, within the terminal box you will see a command appear, example <</p102 as the software queries the chosen parameter.
The unit will reply with the parameter and its current value, example: ==/p102:120
Selecting ‘Set’ allows the value of the selected
MicroFlow-i parameter to be changed, both the address and value must be entered before clicking on the button.
<</p102:100 will show the parameter number and the value you have changed in the manual setting box. And ==/p102:140 will appear when the change of the parameter and its value is complete. The appropriate access levels are required for setting parameters.
The values need to be valid and within the allowed range for that particular parameter for the change to be successful. Please refer to ‘ Chapter 7 Parameter listing and Descriptions ’ in this manual, on the parameters available and the range each one can be set between. If a parameter has been incorrectly set, choose the parameter from the options in ‘Parameter Get/Set’ and select the default button to display the default value for that parameter. Pressing set will revert the parameter to its default value.
Page 34
4 – 20mA Trim
This feature is only available to use when the sensor has been set to ‘Run mode’, the options will then no longer be greyed out and will now be available to use.
If the device connected to the mA output is out of calibration, and is unable to be calibrated. Then the low and high current levels can be calibrated by altering ‘ Set
4mA ’ (Low Trim) and ‘ Set 20mA ’ (High Trim). It is advised that to carry out calibration, that a Digital Multi Meter (DMM) is used, so that 4mA or 20mA respectively are shown on the device.
Calibrating 4mA
To calibrate the 4mA, type in ‘4’ in the ‘Constant mA’ value box and press ‘Send’.
If the low value reading is incorrect, then it can be trimmed using the ‘Set 4mA’ option. Enter the offset directly into the value box and then select the ‘Set 4mA’ button to enable you to get the expected result (reading).
Calibrating 20mA
To calibrate the 20mA, type in ‘20’ in the ‘Constant mA’ value box and press
‘Send’. If the high value reading is incorrect, then it can be trimmed using the
‘Set 20mA’ option. Enter the offset directly into the value box and then select ‘Set
20mA’ button to enable you to get the expected result (reading).
Resume mA
When calibration is complete, to release the constant mA reading select ‘Resume mA’ which will return you to normal measurement/mA output readings. If this is not selected when calibration is complete, then your mA output will not be updated.
Page 35
Trace Tab
Upon opening the trace tab, the information at the bottom of the screen will scroll through Measurement in progress, Updating mA, Updating Trace. Once the trace has updated the diagnostic traces from the sensor will be displayed. You are also able to see the current velocity measurement obtained by the sensor.
The vertical axis is related to the signal strength, while the horizontal axis is related to the detected flow.
When a signal is received, the ‘ green square indicator ’ will move down from 10 on the vertical axis. The further the ‘ green square indicator ’ moves from 10, the larger the strength of the received signal. During flow condition, the ‘ green square indicator ’ will normally be within the range of 30 to 70. Under no-flow conditions the ‘ green square indicator ’ will remain at 10.
When flow is detected, the ‘ red circle indicator ’ will move horizontally to indicate flow detection. The ‘ red circle indicator ’ should stay at 0 under no-flow conditions, and move along the horizontal axis when flow is detected.
Under flow condition, the line should still approach and flatten out at just below the signal index 10 line. If the trace remains flat or the indicators struggle to remain stable during flow, then increase the ‘Gain’ (P102) setting.
Page 36
You can zoom in by clicking and holding the mouse to draw a box over the region to zoom in on. Zooming out can be done by right clicking on the chart and selecting “Undo All Zoom”.
Record Traces
To record traces and the current velocity, select the
Record
button and enter a site ID when prompted to do so. The record button will then change to green whilst the software is recording the data from the sensor. A new trace will be recorded when Updating Trace….
is shown in the status box.
Replay Traces
To replay trace and velocity data, the sensor needs to be disconnected from the software. Select the
Replay
button and a prompt will appear to choose the data file you wish to play. The replay button will change to green whilst the software is replaying the data. During replay select the replay button again to stop.
Important Information
Traces will only be recorded whilst the trace screen is displayed.
Upon leaving the trace screen, a message will appear to inform you of this. Returning to the trace screen will resume recording of the trace data.
Page 37
Comport
If MicroFlow-i PC fails to connect to the sensor, the status condition will appear as below:
You will need to change the communications port that is being used. To do this, select ‘Comport’ from the top menu bar and the Comm Port setup window will appear, as seen below:
From the drop down box select the Comport that has been assigned to your HART modem, then press select and then close. Comport assignments can be viewed in the Device Manager area of Microsoft Windows.
Your Comport information will then appear at the bottom of the MicroFlow-i
HART PC
Language
:
COM 8 1200 8 Odd
.
This menu allows you to select the language you wish to view the information on the software in the language option selected.
Tools menu
This menu option allows you to choose the following options:
Convert Logs to CSV
This allows you to export a saved data file (.MLG only) into CSV format. And once opened in Excel, the information recorded in this file can be viewed and each section is labelled at the top of the row: Date , Time , Velocity (m/s) , Signal
Strength and Stability . This information from the MicroFlow-i can then be placed into a chart/graph format.
Page 38
Change Work Folder
This will allow you to select the default folder for where the trace data files are to be saved to.
Run HART Bootloader Control
This function allows you to reprogram the sensor with HART firmware, and should only be accessed by service personnel or under the guidance of Pulsar service engineers.
Run Bootloader Control
This function allows you to reprogram the sensor with MicroFlow-i firmware, and should only be accessed by service personnel or under the guidance of Pulsar service engineers.
Set Program mode
This allow you to interrogate the sensor and make changes to its parameters, and also view traces from the sensor. Whilst in program mode, the mA output will automatically change to high (20mA) allowing the change of parameters to be completed quickly and efficiently. However, the MicroFlow-i will continue to monitor and display any change in velocity and mA readings on the Flow tab.
Set Run mode
This mode is used once the MicroFlow-i has been set up in program mode. It is also the default mode that the sensor is in when a connection is made for the first time to a device, or after a power failure. In run mode no parameters can be changed and all current readings are reported, and you are able to adjust the 4 –
20mA Trim.
Info
This menu option allows you to choose the following options:
PC Software
This allows you to view the current version of MicroFlow-i HART PC being used.
MicroFlow-i Firmware
When connected to a MicroFlow-i sensor, the information regarding the firmware.
Hardware and serial number currently connected is displayed here.
Exit
Disconnects the sensor (leaving it in program mode) and closes MicroFlow-i
HART PC .
Page 39
Chapter 6 Parameter Listing and Descriptions
Parameter Access
All of the MicroFlow-i parameters have factory default values which the user receives upon first use, or when the sensor is reset. The parameters consist of two main types: Device information and Processing parameters.
Device parameters are read only and cannot be set by the user, such as the serial number of the sensor. Processing parameters can be queried and set, there is also an associated access level required for setting, either ‘User’ or ‘Service’. Upon connection to a MicroFlow-i , the access level is defaulted to ‘User’.
The parameters are always stored and entered as whole numbers, please refer to the individual parameter for its individual value range.
Device Information Parameters
These parameters are read-only.
Name Parameter
No.
Serial Number
Firmware ID
Hardware ID
240
&
241
261
262
Description
Registers 240 & 241 form a 32-bit number.
Register 240 = Most significant 16-bit.
Register 241 = Least significant 16-bit.
A number associated with the version of firmware that is currently programmed onto the sensor.
A number associated with the version of hardware that is currently used with the sensor.
Page 40
Processing Parameters
Gain
These parameters relate to the detection and processing of the flow velocity signal.
Name
Parameter
No.
Options Default Notes
Quick response
Damping Factor
Cal Factor
High/Main
Damping
102
104
108
109
100 - 1600
10 – 999
1 – 500
0 - 28
120
750
100
0
Used to enter a fixed gain
(sensitivity) value, a higher number means higher gain.
When P113=1, this damping factor will be applied. When
P113=0, measurement will only be damped by P109 the main damping factor.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
This sets the damping factor by adding to P104. A higher number represents more damping.
Step Response
Mode
113
0 = Off
1 = On
1
Low Damping
Persist
High Damping
Persist
No Signal
Persist
Signal Present
Persist
115
116
117
118
1 – 100
1 - 100
1 – 100
1 - 100
2
1
2
2
When turned off, no damping by pass will be performed.
This is the number of measurements that the sensor acquires, before switching into damping mode.
This is the number of measurements that the sensor acquires, before switching into Step Response Mode.
This is the number of nonmeasurement to persist before the sensor sees a state of no signal.
This is the number of measurements that need to persist for there to be a signal present state.
Page 41
Multipoint
Calibration @
0.2 m/s
Multipoint
Calibration @
0.4 m/s
Multipoint
Calibration @
0.8 m/s
Multipoint
Calibration @
1.5 m/s
Multipoint
Calibration @
3.0 m/s
Multipoint
Calibration @
5.0 m/s
Multipoint calibration mode
Page 42
Minimum Flow
Cut Off
Response
120
125
152
153
154
155
156
157
158
10-4000 150
0=Instant
1=Moderate
2=Damped
Instant
5 - 500
5 - 500
5 - 500
5 - 500
5 - 500
5 - 500
100
100
100
100
100
100
In units of mm/s velocity for user input, to set the minimum flow velocity present.
Changing this to ‘Instant’ will automatically calibrate parameters in the sensor to track measurements faster.
This is recommended for
Pumped flow. ‘Damped’ is recommended when there is natural flow, as measurements will be tracked at a slower pace.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
In percentage terms, default is 100, for 100%. 50% would half and 200% would double.
0 = Off
1 = On
Off
Turns Multipoint calibration on and off.
Simulated Flow
Mode
Simulated Flow
Velocity mm/s
Sensor Reset
288
289
297
0 = Off
1 = On
0 – 4000
7 = Default
Off
0
0
Switch simulated flow on or off.
This sets the flow velocity in mm/s, which can be used to simulate velocity and mA readings.
This resets all MicroFlow-i parameters to their default values. (It does not affect any mA Trims applied).
Both P834 and P835 are used for spanning the mA output, by default the 4-20 mA output span is 0 – 6 m/s. Below are some examples of the parameters use:
Example 1 : 0 – 3m/s span over 4 – 20 mA.
Set P835 to 3 (m/s).
0 – 6m/s span over 4 – 12mA. Set P835 to 12 (m/s). Example 2 :
Example 3 : 0 – 6m/s span over 20 – 4 mA. Set P834 to 6 (m/s) and set P835 to 0 (m/s).
Example 4: 0 – 6m/s over 8 – 20 mA. Set P834 to -2 (m/s).
Important Information
After using simulated flow, ensure that simulation mode (P288) is switched ‘OFF’ before disconnecting the sensor from the software and power cycling the unit.
If using the MicroFlow-i on an application where Flow type is changed to ‘Fast’, this will reduce the damping to obtain better results. If there is natural flow and ‘Slow’ is chosen, then damping is increased to obtain better results.
Page 43
MicroFlow-i Firmware Upgrade
Firmware upgrades are performed in ‘Bootloader’ mode, and require service level access. Note: It is advised that reprogramming is carried out by Pulsar service personnel. Also all flow measurement and output operation will be halted when the sensor is in the ‘Bootloader’.
Please follow these steps to reprogram a sensor MicroFlow-i firmware:
1.
Please ensure that the sensor is connected to a PC via the HART modem.
Prior to reprogramming, you will need the MicroFlow-i firmware file, and the COM port number of the modem.
2.
Establish a connection to the sensor.
3.
You will require Service access to Run Bootloader Control.
4.
Select Tools > Run Bootloader Control, which will then open up the
Bootloader control interface window as seen in Fig.10.
5.
Once connected click ‘Load Hex file’, and choose the firmware file you are using to upgrade the sensor.
6.
Click ‘Erase-Program-Verify’, and wait for the process to finish.
7.
When the ‘Verification Successful’ message is displayed, click ‘Run firmware’ and the Bootloader Interface will close down.
8.
Select the ‘Search’ button on the software, and the sensor will reconnect to
MicroFlow-i HART PC with the new HART firmware installed.
Important Information
It is important to know that it takes approximately 60 minutes to reprogram a sensor with MicroFlow-i firmware successfully.
Page 44
Fig.10
Important Information
Do not switch off supply to the unit or close the software down during the firmware upgrade.
Page 45
MicroFlow-i HART Firmware Upgrade
1.
Please ensure that the sensor is connected to a PC via the HART modem.
Prior to reprogramming, you will need the HART firmware file, and the
COM port number of the modem.
2.
Establish a connection to the sensor.
3.
You will require Service access to Run HART Bootloader Control.
4.
Select Tools > Run HART Bootloader Control, which will then open the
Bootloader control interface window as seen in Fig.11.
5.
Once connected click File’, and choose the firmware file you are using to upgrade the sensor.
6.
Click ‘Re-Program’, turn the sensor off and on again when prompted to do so by the Bootloader control and then wait for the process to finish.
7.
When the ‘Program File OK now rebooting’ message is displayed, you can close the HART Bootloader and reconnect to the PC software.
8.
Select the ‘Search’ button on the software, and the sensor will reconnect to
MicroFlow-i HART PC with the new HART firmware installed.
Page 46
Fig.11
Important Information
Do not switch off supply to the unit or close the software down during the firmware upgrade.
Page 47
Chapter 7 Troubleshooting
This section describes many common symptoms, with suggestions as to what to do to resolve them.
Symptom
Current velocity reads zero, but you know that there is flow movement.
Current velocity reading is higher/lower than known movement of flow.
Unable to connect to
MicroFlow-i HART PC .
What to Do
Ensure that the sensor is mounted correctly in accordance with Chapter
2.
Check that the sensor is mounted correctly. Adjust the Gain (P102) or
Damping (P109) parameters to obtain correct measurements.
Check that wiring to the modem is correct. Close MicroFlow-i HART
PC software, cycle power on the sensor and re-open the software.
Ensure that the correct Com port has been set and retry connection.
Sensor remains at a high mA out reading (20mA)
Ensure that Simulation mode (P288) is set to 0 = Off
Ensure that ‘Resume mA’ has been selected if in Run mode.
Important Information
If you experience any issues with our equipment, then please contact your local Pulsar Distributor for assistance.
Page 48
Chapter 8 Parameter record
Device Information Parameters
Parameter Details
No. Description
P240
&
P241
Serial No.
P261 Firmware ID
P262 Hardware ID
Processing Parameters
Default
Read Only
Read Only
Read Only
Entered Values
1 2 3 4 5
Parameter Details
No. Description
P102 Gain
Default
120
P104 Quick Resp Damp Factor 800
P108 Cal Factor
P109 High/Main damping
100
0
P113
P115
P116
P117
P118
P120
Step response
Low damping persist
High damping persist
No signal persist
Signal present persist
Minimum Flow cut off
0 = Off
2
1
2
2
150 (mm/s)
Entered Values
1 2 3
P125 Response 0 = Slow
P152 Multi Cal point 1 at 0.2 m/s 100
P153 Multi Cal point 2 at 0.4 m/s 100
P154 Multi Cal point 3 at 0.8 m/s 100
P155 Multi Cal point 4 at 1.5 m/s 100
P156 Multi Cal point 5 at 3.0 m/s 100
P157 Multi Cal point 6 at 5.0 m/s 100
P158 Multi Cal mode On/Off 0 = Off
P834 Low velocity for mA Span 0
P835 High velocity for mA Span 6
4
Page 49
5
Chapter 9 Disposal
Incorrect disposal can cause adverse effects to the environment.
Dispose of the device components and packaging material in accordance with regional environmental regulations including regulations for electrical \ electronic products.
Transducers
Remove power, disconnect the Transducer, cut off the electrical cable and dispose of cable and Transducer in accordance with regional environmental regulations for electrical \ electronic products.
Controllers
Remove power, disconnect the Controller and remove battery (if fitted). Dispose of
Controller in accordance with regional environmental regulations for electrical \ electronic products.
Dispose of batteries in accordance with regional environmental regulations for batteries.
EU WEEE Directive Logo
This symbol indicates the requirements of Directive 2012/19/EU regarding the treatment and disposal of waste from electric and electronic equipment.
Page 50