Vents BOOST / BOOST EC User Manual

Add to My manuals
16 Pages

advertisement

Vents BOOST / BOOST EC User Manual | Manualzz

USER'S MANUAL

Boost 355

Boost 400

Inline mixed-flow fan

Boost

CONTENTS

Safety requirements ..................................................................................................................................................................... 3

Purpose ................................................................................................................................................................................................ 5

Delivery set ........................................................................................................................................................................................ 5

Designation key .............................................................................................................................................................................. 5

Technical data .................................................................................................................................................................................. 6

Mounting and set-up .................................................................................................................................................................. 7

Connection to power mains .................................................................................................................................................. 9

Technical maintenance .............................................................................................................................................................. 10

Troubleshooting ......................................................................................................................................................................................................11

Storage and transportation regulations .......................................................................................................................... 11

Manufacturer’s warranty ........................................................................................................................................................... 12

Certificate of acceptance .......................................................................................................................................................... 13

Seller information .......................................................................................................................................................................... 13

Installation certificate .................................................................................................................................................................. 13

Warranty card ................................................................................................................................................................................... 13

This user’s manual is a main operating document intended for technical, maintenance, and operating staff.

The manual contains information about purpose, technical details, operating principle, design, and installation of the Boost unit and all its modifications.

Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.

2 www.ventilation-system.com

SAFETY REQUIREMENTS

All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.

Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.

Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation and maintenance. The present user’s manual should be carefully read before beginning works.

• Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.

• While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.

• Misuse of the unit and any unauthorised modifications are not allowed.

• Do not expose the device to adverse atmospheric agents (rain, sun, etc.).

• Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.

• Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.

• Do not close or block the intake or extract vents in order to ensure the efficient air flow.

• Do not sit on the unit and do not put objects on it.

• The information in this user’s manual was correct at the time of the document’s preparation.

• The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.

WARNING! Similar to the use of any other household electrical appliances when operating this fan, the following basic rules must be followed:

• Never touch the unit with wet or damp hands.

• Never touch the unit when barefoot.

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be supervised to ensure that they do not play with the appliance.

The connection to the supply mains must be made through a means of disconnection, which is incorporated in the fixed wiring in accordance with the wiring rules, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.

www.ventilation-system.com

3

Boost

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.

CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.

Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

Ensure that the appliance is switched off from the supply mains before removing the guard.

WARNING: If unusual oscillating movements is observed, immediately stop using the appliance and contact the manufacturer, its service agent or suitably qualified persons.

The replacement of parts of the safety suspension system device shall be performed by the manufacturer, its service agent or suitably qualified persons.

4

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.

DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

www.ventilation-system.com

PURPOSE

The product described herein is a mixed-flow inline fan for supply or extract ventilation of premises.

The fan is designed for connection to ø 355 and 400 mm air ducts.

Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

DELIVERY SET

Name

Fan

User’s manual

Packing box

Number

1 pc.

1 pc.

1 pc.

DESIGNATION KEY

Boost 355 EC X

Options

R : power cord with a mains plug

V : three-position speed switch

S : high-powered motor

Electric motor type

_: asynchronous

EC: electronically commutated

Air duct diameter [mm]

355, 400

Unit series

Inline mixed-flow fan www.ventilation-system.com

5

6

Boost

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to

80 % at 25 °C. Ingress protection rating against access to hazardous parts and water ingress is IPX4.

The unit is rated as a class I electric appliance. The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

Parameter

Speed

Voltage [V] at 50 Hz

Power [W]

Current [A]

Maximum air flow [m 3 /h]

RPM [min -1 ]

Maximum transported air temperature [°C]

Ingress protection rating

Low

126

0.60

2090

1350

Boost 355

Medium

131

0.58

2296

1400

High Low

1~ 230

150

0.66

197

0.91

2485

1470

-25...+55

IPX4

2677

1320

Voltage [V] at 50 Hz

Parameter

Power [W]

Current [A]

Maximum air flow [m 3 /h]

RPM [min -1 ]

Maximum transported air temperature [°C]

Ingress protection rating

Boost 355 EC

346

1,54

3685

2470

Boost 355 EC S

1~ 230

701

3,10

4630

3175

-25...+55

IPX4

Overall dimensions of the unit [mm]

Boost 400

Medium

204

0.90

3136

1390

ød

A

High

224

0.98

3350

1446

Boost 400 EC

726

3,23

5700

2580

øD

B1

ød

B

Model

Boost 355

Boost 400

D

406

451 d

350

395

A

451

496

Dimensions [mm]

L

372

415

B

468

513

B1

566

623

C

437

482

C1

439

484

Weight

[kg]

15

18.5

www.ventilation-system.com

MOUNTING AND SET-UP

READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.

BEFORE MOUNTING, MAKE SURE THERE ARE NO VISIBLE DEFECTS ON THE UNIT, SUCH

AS MECHANICAL DAMAGES, MISSING PARTS, IMPELLER JAMMING ETC.

WHEN MOUNTING THE UNIT, IT IS NECESSARY TO PROVIDE PROTECTION AGAINST

CONTACT WITH HAZARDOUS ZONES OF THE FAN BY INSTALLING AIR DUCTS OF THE

NECESSARY LENGTHS AND PROTECTIVE GRILLES.

MOUNTING MUST BE PERFORMED BY QUALIFIED SPECIALISTS ONLY, PROPERLY

TRAINED AND QUALIFIED TO INSTALL AND MAINTAIN VENTILATION EQUIPMENT.

The unit is intended for mounting with round air ducts. The fan is installed between the air ducts.

The fan casing is equipped with fixing brackets for suspended mounting or for mounting on a horizontal or vertical surface.

While installing the unit ensure convenient access for subsequent maintenance and repair. Fasteners for fan mounting are not included in the delivery set and should be ordered separately. While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical data section. Fasteners for unit mounting should be selected by a service technician.

The unit can be mounted in two operation positions, which makes mounting easier. For this, dismantle the fan handle first or set it to another position.

After choosing one of two positions, securely mount the brackets to the fan.

1.

2.

SUSPENDED MOUNTING

Install the fan on the threaded rods (not included in the delivery set).

WARNING! When mounting the fan on threaded rods, it is necessary to provide protection of the nuts against self-loosening.

Nut

Washer

Vibration absorbing rubber

Washer

Nut and lock nut

Threaded rod www.ventilation-system.com

7

SURFACE MOUNTING

Fasten the fan to the surface using the screws with the dowels of appropriate size (not included in the delivery set).

Make sure the fan is fastened securely.

Boost

Connect the air ducts of the appropriate diameter to the fan (connections must be airtight).

Air motion in the system must be in compliance with the direction of the arrow on the fan label.

To attain the best performance of the fan and to minimise turbulence-induced air pressure losses, it is recommended to connect the straight air duct section to the spigots on both sides of the unit while mounting.

Minimum recommended straight air duct section length is equal to 3 fan diameters (see the "Technical data" section).

If the air ducts are shorter than 1 m or not connected, the internal parts of the unit must be protected from ingress of foreign objects.

To prevent uncontrollable access to the fans, the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12.5 mm.

3xD 3xD

ELECTRONICS OPERATION ALGORITHM

The EC motor is controlled by sending of an external control signal from 0 to 10 V to the X2 terminal block or by the R1 internal speed controller. Control method selection is carried out by means of the SW DIP switch:

- DIP switch in IN position. The control signal is set by the R1 internal speed controller, which allows turning the fan on and off, smoothly regulating the fan motor rotation speed (air flow) in the range from minimum to maximum speed.

Rotations are controlled from the minimum (extreme left position) to the maximum (extreme right position).

When rotating clockwise, the rotations increase.

- DIP switch in EXT position. The control signal is set by the S1 external control unit.

8 www.ventilation-system.com

CONNECTION TO POWER MAINS

POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.

THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.

THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE

MANUFACTURER’S LABEL.

ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED

AND WILL VOID THE WARRANTY.

Any tampering with the internal connections is prohibited and will void the warranty.

The fan is rated for connection to single-phase AC 220-240 V/50 Hz power mains. The connection must be made using durable, insulated and heat-resistant conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.

The fan connection shall be made on the terminal block mounted inside the terminal box in strict accordance with the wiring diagram and terminal designations.

L

N

Low speed

~220-240V

S

N

High

Med

Low

L

N

~220-240V

Boost ... V

QF

N

L

X

L

N

Medium speed

~220-240V

S

N

High

Med

Low

WIRING DIAGRAM

Boost ...

X High speed

~220-240V

S

L

N

High

Med

Low

N

Boost ... EC

X1

X

N

L

High-Med-Low speed

S S1

~220-240V

High

Med

Low

N

R1

X1

N

L

N

~220-240V

L

SW

High — high speed

Med — medium speed

Low — low speed

N — neutral

L — line

— grounding

S — ON\OFF switch

S1 — switch

QF — automatic circuit breaker

R1 — internal speed controller

SW — DIP switch www.ventilation-system.com

X

9

Boost

TECHNICAL MAINTENANCE

DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE

OPERATIONS!

ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE

REMOVING THE GUARD.

Clean the product surfaces regularly (once in 6 months) from dust and dirt.

Disconnect the fan from power mains prior to any maintenance operations.

Disconnect the air ducts from the fan.

Clean the fans with a soft brush, cloth, vacuum cleaner or compressed air.

Do not use water, aggressive solvents, or sharp objects as they may damage the impeller.

It is forbidden to remove or change the location of the balancers on the impeller, as this can lead to increased level of vibration, noise and reduce the service life of the unit.

During technical maintenance, make sure that there are no visible defects on the unit, the mounting brackets are securely fastened to the fan casing and the unit is securely mounted.

10 www.ventilation-system.com

TROUBLESHOOTING

Problem

No power supply.

Possible reasons

The fan(s) do(es) not start.

Jammed motor.

The fan has overheated.

Automatic circuit breaker tripping following the fan turning on.

High current consumption due to short circuit in power line.

Noise, vibration.

The fan impeller is soiled.

The fan or casing screw connection is loose.

The ventilation system components (air ducts, diffusers, louvre shutters, grilles) are clogged or damaged.

Troubleshooting

Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.

Disconnect the fan from power supply. Troubleshoot the motor jamming. Restart the fan.

Disconnect the fan from power supply. Eliminate the cause of overheating. Restart the fan.

Turn the fan off. Contact the Seller.

Clean the impellers.

Tighten the screw connection of the fan or the casing against stop.

Clean or replace the ventilation system components

(air ducts, diffusers, louvre shutters, grilles).

STORAGE AND TRANSPORTATION REGULATIONS

• Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.

• Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.

• Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.

• Follow the handling requirements applicable for the particular type of cargo.

• The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.

• Avoid sharp blows, scratches, or rough handling during loading and unloading.

• Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

www.ventilation-system.com

11

Boost

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European

Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking

Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.

The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:

• routine technical maintenance

• unit installation/dismantling

• unit setup

To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases:

• User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.

• Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user's manual.

• User’s failure to ensure timely technical maintenance of the unit.

• External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.

• Redesign or engineering changes to the unit.

• Replacement and use of any assemblies, parts and components not approved by the manufacturer.

• Unit misuse.

• Violation of the unit installation regulations by the user.

• Violation of the unit control regulations by the user.

• Unit connection to power mains with a voltage different from the one stated in the user's manual.

• Unit breakdown due to voltage surges in power mains.

• Discretionary repair of the unit by the user.

• Unit repair by any persons without the manufacturer’s authorization.

• Expiration of the unit warranty period.

• Violation of the unit transportation regulations by the user.

• Violation of the unit storage regulations by the user.

• Wrongful actions against the unit committed by third parties.

• Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).

• Missing seals if provided by the user’s manual.

• Failure to submit the user’s manual with the unit purchase date stamp.

• Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND

TROUBLE-FREE OPERATION OF THE UNIT.

USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION

OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE

PURCHASE DATE STAMP.

12 www.ventilation-system.com

CERTIFICATE OF ACCEPTANCE

Unit Type

Model

Serial Number

Manufacture Date

Quality Inspector’s

Stamp

Inline mixed-flow fan

Boost_________

SELLER INFORMATION

Seller

Address

Phone Number

E-mail

Purchase Date

This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.

Customer’s Signature

INSTALLATION CERTIFICATE

The Boost_________ unit is installed pursuant to the requirements stated in the present user's manual.

Company name

Address

Phone Number

Installation

Technician’s Full Name

Installation Date: Signature:

The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.

Signature:

WARRANTY CARD

Unit Type

Model

Serial Number

Manufacture Date

Purchase Date

Warranty Period

Seller

Inline mixed-flow fan

Boost_________

Seller’s Stamp

Installation Stamp

Seller’s Stamp www.ventilation-system.com