ABB ARG600 ANSI is a wireless gateway that provides secure and reliable communication for industrial applications. It enables remote monitoring and control of field devices via cellular networks, making it ideal for use in remote locations or where wired communication is not feasible. With protocol conversion capabilities, the ARG600 ANSI can integrate legacy serial devices into modern TCP/IP-based control systems. It supports multiple communication protocols, including IEC 60870-5-101/104, DNP3, and Modbus, making it versatile for various industrial applications.
advertisement
—
Wireless Gateway
ARG600 ANSI
Product Guide
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
Contents
1. Description........................................................................ 3
2. Complete communication system...................................... 3
3. Application.........................................................................4
4. Physical interfaces............................................................. 6
5. Communication................................................................. 9
6. Technical data................................................................. 10
1MRS758866 B
7. Mounting......................................................................... 14
8. Ordering data...................................................................14
9. Accessories and ordering data.........................................14
10. Tools.............................................................................. 14
11. References..................................................................... 15
12. Document revision history...............................................16
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
© Copyright 2018 ABB.
All rights reserved.
Trademarks
ABB is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
2 ABB
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
Issued: 2018-06-29
Revision: B
1. Description
Wireless Gateway ARG600 provides wireless monitoring and control of field devices via cellular network from a central site or a control center. The devices offer industrial quality connectivity for the TCP/IP and serial port based protocols. Wireless Gateway
ARG600 exhibits integrated communication capability and seamless integration to the SCADA systems.
Wireless Gateway ARG600 is a member of ABB’s Arctic product family and part of its 600 Wireless Gateway product series.
By using Wireless Gateway ARG600, Ethernet and serial devices can be attached to a TCP/IP based control system. With Wireless
Gateway ARG600, conventional IEC60870-101 devices can be attached to a modern TCP/IP based IEC 60870-5-104 control system. This is made possible by the protocol conversion from
IEC 60870-5-101 to IEC 60870-104. ARG600 also supports
Modbus RTU to Modbus TCP protocol conversion.DNP3 serial devices can be attached to a DNP3 TCP SCADA system. In this case, the DNP3 protocol is transferred over TCP/IP communication (transparent serial gateway mode).
Wireless Gateway ARG600 can be utilized for various industrial and utility applications to maximize the benefits.
• Industrial grade TCP/IP router: several serial and TCP/IP based field devices can be integrated into a central supervisory and control system (SCADA)
• Integrated protocol conversion enables connecting the legacy serial-based devices into a TCP/IP-based supervisory control system (SCADA)
• Ideal for retrofitting by allowing the user to extend the life cycle of existing serial-based substation devices
• Remote access to field devices means less site visits for operations and maintenance
• Optimizing the cost of communication by using public cellular networks
• Possibility to upgrade from the existing legacy's private radio system to a higher bandwidth cellular network based solution. This enables to fully maximize the usage of the existing application. For example, the video surveillance of traffic can now be integrated into the same system.
2. Complete communication system
Wireless Gateway ARG600 is typically part of a complete communication system which consists of Arctic 600 series gateways and a central M2M Gateway ARM600 communication server. The M2M gateway is an essential part of the total communication solution and offers features that are needed to build a reliable end-to-end communication system.
• Static IP addressing for Arctic 600 series devices
• VPN Concentrator – Secure communication between a central location and remote sites
• Arctic Patrol – Centralized device management application for the Arctic 600 series devices monitoring and controlling
• Firewall – A network security system to control the incoming and outgoing network traffic
GUID-3B841385-0329-42A7-8320-824E1CFA0407 V1 EN
Figure 1.
Communication system overview with Wireless Gateway ARG600 and a protection relay
ABB 3
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
3. Application
Wireless Gateway ARG600 can be used in feeder automation and substation applications to automate distribution networks in cooperation with other ABB grid automation equipment. Further, the devices can be used in secondary substations for various monitoring and control applications.
ARG600 can be used in various industrial applications.
• Enables remote service and maintenance opportunities by allowing the service personnel to remotely access any type of field devices. For example, these field devices can securely report the condition monitoring information, which allows planning of preventative maintenance.
• Provides a fast, reliable and secure wireless link between
Ethernet devices, such as a Distribution Automation
Controller COM600F and 615 series protection relays
• Offers backup connectivity for any communication link
• Supports weather monitoring stations, live video streaming, building automation and smart traffic management system
• Connects IEC-101, DNP or Modbus RTU protocol based meters and fault passage indicators into an upper-level system
Key features
• Protocol converter for IEC-101 to IEC-104 protocol
• Wireless monitoring and control of IEC-101, IEC-104, DNP and Modbus field devices via cellular network
• Always-on TCP/IP routing and serial over TCP/IP based twoway communication
• Arctic Patrol connectivity supervision of the communication system
• Secure communication with VPN and Firewall
• OpenVPN client and server enable direct connection of one to five Arctic 600 series devices to a single Arctic 600 series device
• Static IP addressing with Arctic M2M Gateway ARM600
4 ABB
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
Power generation Distribution substation
Control room
SCADA / DMS
ARM600
Internet
VPN
GPRS/3G/LTE
Cellular network
VPN
Secondary substation
Consumers
GUID-E9E4368B-4014-4974-A662-C50D01401F02 V1 EN
Figure 2.
Communication solution in distribution automation overview
Reclosers
1MRS758866 B
ABB 5
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
4. Physical interfaces
Wireless Gateway ARG600 has two serial ports (RS-232, RS-485) and one LAN/WAN port (RJ-45) for device connectivity. For communication to an upper-level system, ARG600 provides 4G
LTE cellular network connectivity, but is also compatible with 3G
(WCDMA) and GPRS networks.
LED panel
The LED panel of the device contains LEDs to indicate the complete operational status of the device.
1 2 3 4 5
6 7 8 9 10
GUID-BE410203-7AA3-4ED7-947A-7FD2CACF86FA V2 EN
Figure 3.
LEDs
1 Batt.
2 Status
3 Power/Error
4 Function
5 Eth 1
6 Eth 2
7 Led 1
8 Led 2
9 Led 3
10 Cellular
6 ABB
8
9
6
7
10
3
4
5
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
Table 1. Description of available LEDs
LED
1
2
Label
Batt
Status
Power/Error
Function
Eth 1
Eth 2
Led 1
Led 2
Led 2
Cellular
State
-
On
Flashing
Off
On
Off
On
Flashing
Off
On
-
-
Flashing
Off
-
-
Flashing
Off
Description
LED unassigned
VPN connection is up
VPN connection is starting
VPN connection is disabled
Operating power is turned on
Operating power is turned off
Device is starting
Device is operating normally
Device is not operational
Ethernet link is up
Ethernet link is transferring data
Ethernet link down
LED reserved for future use
LED reserved for future use
LED reserved for future use
LED reserved for future use
Cellular connections up and active
Cellular connection is inactive
1MRS758866 B
ABB 7
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
Front panel
1 2 3 4
5
GUID-FD7297D1-5F9C-49CF-82F0-AF5D989D035D V2 EN
Figure 4.
Front panel
1 Power supply 12...48 VDC
2 Console/serial port
3 Application serial ports
4 LAN/WAN port
5 Power switch
6 Console/serial port switch
7 DIP switches
Back panel
6 7
1
2
GUID-BB2AF55E-76F0-4C5D-87C2-EACC9F0088BA V1 EN
Figure 5.
Back panel
1 Antenna connector SMA (female)
2 SIM card slot
8
1MRS758866 B
ABB
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
Antenna panel
The SIM card slot and antenna connector can be found on the antenna panel.
5. Communication
Wireless Gateway ARG600 provides a complete solution for integrating remote serial (RS-232/RS-485) or Ethernet devices with a central management system over a GPRS, 3G or LTE connection. Industrial protocols IEC-104, DNP-TCP and Modbus
TCP are supported for the SCADA connectivity. With the ARG600 protocol conversion feature, conventional IEC-101 and Modbus serial devices can be connected in a reliable way to modern
TCP/IP based IEC-104 and Modbus TCP control systems.
for multiple field devices' connectivity by serial and Ethernet ports, ARG600 Wireless Gateway is the ideal solution for the monitoring and controlling of field devices when a reliable and secure communication with high data bandwidth is required.
ARG600 provides a secure and reliable communication solution with support for secure VPN communication, static IP routing, an intelligent self-testing system, NAT, port forwarding and a firewall for monitoring IP traffic and blocking unwanted connections.
ARG600 makes it possible to have a cost-effective communication networks over long distances and at high data rates (up to 100 Mbps). When this is combined with the possibility
More information is available in the Technical data section of this product guide or technical manual available at www.abb.com/mediumvoltage .
ABB 9
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
6. Technical data
Table 2. Dimensions
Description
Width × Height × Depth
Table 3. Hardware
Description
Processor environment
Power
Other
Approvals
Environmental conditions
Processor
Memory
Power supply
Power consumption
Internal clock
Temperature range
Humidity
Protection class
Table 4. Supported protocols
Master protocol
IEC 60870-5-104
Modbus TCP
TCP/IP, UDP/IP (DNP3)
Value
108 × 45 × 175 mm (without antenna)
Value
32 bit RISC
128 MB Flash
128 MB RAM
12...48 VDC (nominal)
1...5 W
Real time
CE and FCC
-30...+70°C (operating)
-40...+85°C (storage)
5...85% RH (non condensing)
IP30
Slave protocol
IEC 60870-5-101
Modbus RTU/ASCII
Serial gateway - serial port data stream (such as DNP3)
1MRS758866 B
10 ABB
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
Table 5. Network interfaces (single SIM variants)
Description
Ethernet ports
Serial ports
Ethernet/LAN
Serial 1/Console
Serial 2
Table 6. Variant codes
Variant
ARG600A1270NA
ARG600A1290NA
Table 7. Wireless network interfaces (WAN)
Product
ARG600A1270NA
ARG600A1290NA
Cellular operator
AT&T (operator approved)
North America and Mexico generic
Air interface
GPRS/EDGE
WCDMA/HSPA+
LTE
Value
10/100 Base-T. Shielded RJ-45
1.5 kV isolation transformer
Ethernet IEEE 802-3, 802-2
RS-232 DTE
Male DB-9 connector
IEC 60870-5-101 protocol support
Full serial and modem signals
300...460 800 bps
Data bits: 7 or 8
Stop bits: 1 or 2
Parity: None, Even, Odd
Flow control: None, RTS/CTS
Protection: 15 kV ESD and short circuit
Console: RS-232, 19200 bps, 8 data bits, 1 stop bit, no parity (8N1)
RS-232 DTE, RS-422, RS-485 (selectable)
Male DB-9 connector
IEC 60870-5-101 protocol support
Full serial and modem signals
300...460 800 bps
Data bits: 7 or 8
Stop bits: 1 or 2
Parity: None, Even, Odd
Flow control: None, RTS/CTS
Protection: 15 kV ESD and short circuit
FCC ID
N7NMC7355
N7NMC7355
Maximum data rate
100 Mbit/s
ABB 11
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
Table 8. LTE frequency band support
Band Frequency Variant code
Band 2
Band 4
Band 5
Band 13
Band 17
Tx
1850...1910 MHz
1710...1755 MHz
824...849 MHz
777...787 MHz
704...716 MHz
Rx
1930...1990 MHz
2110...2155 MHz
869...894 MHz
746...756 MHz
734...746 MHz
ARG600A1270NA,
ARG600A1290NA
ARG600A1270NA,
ARG600A1290NA
ARG600A1290NA
ARG600A1290NA
ARG600A1270NA,
ARG600A1290NA
Band 25 1850...1915 MHz 1930...1995 MHz ARG600A1290NA
All listed LTE bands and frequencies are supported by the integrated radio module. See the cellular operator compatibility and LTE frequency bands used by operators in Table 6 .
Table 9. WCDMA frequency band support
Band Frequency
Tx
1920...1980 MHz
Rx
2110...2170 MHz Band 1
WCDMA 2100
Band 2
WCDMA 1900
Band 4
AWS 1700/2100
Band 5
WCDMA 850
Band 8
WCDMA 900
Table 10. GSM frequency band support
Band
1850...1910 MHz
1710...1755 MHz
824...849 MHz
880...915 MHz
1930...1990 MHz
2110...2155 MHz
869...894 MHz
925...960 MHz
GSM 850
EGSM 900
DCS 1800
PCS 1900
Frequency
Tx
824...849 MHz
880...915 MHz
1710...1785 MHz
1850...1910 MHz
Rx
869...894 MHz
925...960 MHz
1710...1785 MHz
1930...1990 MHz
12 ABB
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
Table 11. Supported RF data bandwidth
Technology
LTE
UMTS, HSDPA, HSUPA, HSPA+
GSM, GPRS, EDGE
Table 12. Antenna connectors
Description
Antenna connector
Table 13. Electromagnetic compatibility tests
Description
Emission tests according to the test specification IEC 61850-3 (Edition
2.0 2013-12)
Immunity tests according to the test specification IEC 61850-3 (Edition
2.0 2013-12)
Radiated disturbance
Conducted disturbance
Electrostatic discharge (ESD)
Radiated radiofrequency electromagnetic field
Electrical fast transient (EFT)
Surge
Conducted radiofrequency electromagnetic field
Power frequency magnetic field
Table 14. RoHS and REACH compliancy
Description
Directive
Data rate
Category 3 downlink: 100 Mbps and uplink 50 Mbps (20 MHz bandwidth)
HSPA+ rates, Downlink up to 42 Mbps (category 24) and uplink up to 5.76
Mbps (category 6)
GPRS throughput up to 85.2 kbps, EDGE throughput up to 236 kbps
Type
SMA (female, 50 Ω)
Reference
CISPR 16-2-3
CISPR 16-2-1
EN 61000-4-2 (2008-12)
EN 61000-4-3 (2006-02)
EN 61000-4-4 (2012-04)
EN 61000-4-5 (2005-11)
EN 61000-4-6 (2008-10)
EN 61000-4-8 (2009-09)
Reference
RoHS directive 2002/95/EC
REACH directive 2006/1907/EC
Table 15. FCC compliancy
Description
Standard
Reference
FCC 47 CFR FCC Part 15
ANSI C63.4-2014
ABB 13
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
1MRS758866 B
7. Mounting
The devices have been equipped with mounting arrangements that are specially designed for DIN rail mounting. A set of DIN rail mounting clips is recommended to be used when mounting. The device should be mounted preferably inside a robust, locked and weatherproof control cabinet.
As the device uses a cellular radio for data transmission, the surrounding environment can negatively affect the efficacy of these radio signals. Therefore, if a device with the antenna is mounted on the antenna connector, the unit should not be placed in a location where the radio signal might be shadowed, and therefore deteriorated by nearby obstacles or enclosures.
The large metallic surfaces, racks or walls with metallic structures
(cabling, concrete iron, and so on) may degrade the antenna performance to a very high extent. In this case, it is highly recommended to use the optional external antenna with appropriate cable. This allows for better positioning of the devices, antennas and thus optimal performance.
Another restriction to the positioning of the device during installation is that it should be mounted in such a way that the required environmental conditions that are set in the Technical data section of this product guide are met.
8. Ordering data
The product label contains basic information about the unit such as product name, serial number and Ethernet MAC address.
The product label is found at the bottom of the device.
Table 16. Ordering data
Description
Cellular operator
Radio IF
Data speed max
LAN/WAN
RS-232/RS-485
SIM card
Supply voltage
ARG600A1270NA
AT&T (operator approved)
LTE
100 Mbps
1
2
1
12...48 VDC
ARG600A1290NA
North America and Mexico generic
LTE
100 Mbps
1
2
1
12...48 VDC
9. Accessories and ordering data
Table 17. Accessories
Description
DIN rail mounting kit
3G puck antenna (SMA male)
Accessory kit
SMA(m)/FME(m) adapter 1)
Laird LTE antenna 700...2700 MHz (SMA male)
America power supply single SIM variants
1) Needed for single SIM Arctic products, if the third party antenna's connector type is FME female
Order code
2RCA028234
2RCA037240
2RCA037645
2RCA037659
2RCA037660
2RCA041791
10. Tools
The devices can be configured using a graphical user interface via a Web based browser. A conventional console interface is also provided. Software updates or configuration adjustments for the
14 devices can be made remotely by uploads over the network from the central control center.
ABB
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
11. References
The www.abb.com/substationautomation portal provides information on the entire range of distribution automation products and services.
1MRS758866 B
ABB 15
Wireless Gateway
ARG600 ANSI
Product version: 3.4.5
12. Document revision history
Document revision/date
A/2017-09-22
B/2018-06-29
Product version
3.4
3.4.5
1MRS758866 B
History
First release
Content updated to correspond to the product version
16 ABB
17
—
ABB Inc.
4300 Coral Ridge Drive
Coral Springs, Florida 33065, USA
Phone
Fax
+1 954 752 6700
+1 954 345 5329
Phone
Service 24/7)
+1 800 222 1946 (Customer www.abb.com/mediumvoltage www.abb.com/substationautomation
© Copyright 2018 ABB. All rights reserved.
advertisement