Carel pCO3 series Technical Manual
Carel pCO3 series is an electronic controller designed in compliance with the European RoHS regulation and offers multiple applications in the air conditioning and refrigeration sector. It ensures the most absolute versatility, allowing the creation of specific products at the customer's request.
pCO3 is dedicated to executing the regulation program and is equipped with the set of terminals necessary for connection to the devices (compressors, fans, etc.). The program and parameters are stored on FLASH-MEMORY and E2prom, allowing them to be maintained even in the event of a power failure (without the need for a back-up battery).
Loading the program can be done via PC (28.8 kbps and 115.2 kbps) or with a special programming key. pCO3 allows the connection to the pLAN local area network (pCO Local Area Network) and can be connected, in addition to other pCO3s, also to all the other controllers of the pCO system and to all the terminals of the pGD family. Each controller in the pLAN network can exchange information (any variable, digital or analog, depending on the application program used) with high transmission speed. Up to 32 units, including pCO controllers and terminals, can be connected in order to share information effectively.
Advertisement
Advertisement
pCO 3 -
controllore elettronico / electronic controller
Foglio istruzioni
Technical leafl et
Betriebsanleitung
Mode d’emploi
LEGGI E CONSERVA
QUESTE ISTRUZIONI
READ AND SAVE
THESE INSTRUCTIONS
Indice / Contents / Inhalt / Sommaire
Foglio istruzioni
Technical leafl et
Foglio istruzioni
Mode d’emploi
ELECTRICAL CONNECTIONS
23
33
38
3
15
CARATTERISTICHE TECNICHE pCO 3 è un controllore elettronico a microprocessore compatibile sia a livello hardware che software con la famiglia pCO 2 . Sviluppato da
CAREL nel rispetto delle normativa europea RoHS, per offrire molteplici applicazioni nel settore del condizionamento dell’aria e della refrigerazione. Assicura la più assoluta versatilità di applicazione, consentendo di realizzare prodotti specifi ci su richiesta del cliente.
pCO 3 è dedicato all’esecuzione del programma di regolazione ed è dotato del set di morsetti necessari alla connessione verso i dispositivi (compressori, ventilatori..). Il programma e i parametri sono memorizzati su FLASH-MEMORY e su E 2 prom, consentendo il loro mantenimento anche in caso di mancanza di alimentazione (senza la necessità di una batteria di mantenimento).
Il caricamento del programma può essere eseguito tramite PC (28.8 kbps e 115.2 kbps) o con apposita chiave di programmazione.
pCO 3 permette la connessione alla rete locale pLAN (pCO Local Area Network) e può essere collegato, oltre che ad altri pCO 3 anche a tutti gli altri controllori del pCO sistema e a tutti i terminali della famiglia pGD. Ogni controllore in rete pLAN può scambiare informazioni (qualsiasi variabile, digitale o analogica, a seconda del programma applicativo utilizzato) con velocità di trasmissione elevata. Possono essere collegate fi no a 32 unità, tra controllori pCO e terminali, in modo da condividere le informazioni in maniera effi cace.
Il collegamento verso la linea seriale di supervisione/teleassistenza con il protocollo di comunicazione CAREL o Modbus™, secondo lo standard RS485, viene realizzato tramite l’inserimento sul pCO 3 di una scheda seriale opzionale.
È possibile, mediante altre schede opzionali, la connessione a supervisore con standard diversi da RS485. Infi ne la seriale fi eld bus, mediante scheda opzionale, offre la connessione verso dispositivi controllati di campo (ad esempio: valvole, espansioni I/O pCO e , driver per valvola elettronica..).
Versioni disponibili:
• SMALL, MEDIUM, LARGE, EXTRALARGE N.O. e EXTRALARGE N.C.;
• con o senza terminale built-in;
• con memoria fl ash aggiuntiva e pLAN optoisolata;
• con o senza uscite digitali relè a stato solido (SSR).
Nota: il programma applicativo può essere scaricato nella memoria fl ash attraverso la smart key PCOS00AKY0, si veda Fig. 6; o un PC mediante adattatore USB-485 “CVSTDUTLF0” e il programma “WINLOAD32” da richiedere a CAREL.
Alimentazione
Nell’installazione si consiglia di utilizzare un trasformatore di sicurezza in Classe II di 50 VA, per l’alimentazione di un solo controllore pCO 3 . Si raccomanda di separare l’alimentazione del controllo pCO 3 e terminale (o più pCO 3 e terminali) dall’alimentazione del resto dei dispositivi elettrici (contattori ed altri componenti elettromeccanici) all’interno del quadro elettrico. Qualora il secondario del trasformatore sia posto a terra, verifi care che il conduttore di terra sia collegato al morsetto G0. Attenersi a ciò per tutti i dispositivi connessi al pCO 3 . Se si alimentano più schede pCO 3 collegate in rete pLAN, assicurarsi che siano rispettati i riferimenti G e G0 (il riferimento G0 deve essere mantenuto per tutte le schede).
In caso di utilizzo della rete pLAN e per ulteriori specifi cazioni e notizie richiedere il manuale pCO 3 CAREL.
OpzionI Field Bus
485 opto isolata tLAN
MPbus Belimo modem
CAN idronica
PCO100FD10
PCO100TLN0
PCO100MPB0
PCOS00FD20
PCOS00HBF0
Opzioni BMS
CANbus
485/Modbus modem scheda Ethernet
LonWorks
LonWorks
LonWorks
PCOS00HBB0
PCOS004850
PCO100MDM0
PCO1000WB0
FTT10
FTT10 profi lo chiller standard
PCO10000F0
PCO10001F0
+050003290 - 1.4 - 29.09.2006 3 italiano
Connettori
Esempio di codifi ca: PCO3CON*** , vedi tabella seguente per descrizione:
PCO3CON *
0 = a vite
1 = a molla
*
S = small
M = medium
L = large
Z = extra large N.O.
C = extra large N.C.
0
CARATTERISTICHE TECNICHE
Caratteristiche meccaniche
dimensioni montaggio versione SMALL inseribile su 13 moduli DIN, 110 x 227.5 x 60 mm versione MEDIUM, LARGE e EXTRALARGE inseribili su 18 moduli DIN, 110 x 315 x 60 mm su guida DIN
Contenitore plastico
• agganciabile su guida DIN secondo norme DIN 43880 e CEI EN 50022;
• autoestinguenza: V0 (secondo UL94) e 960 °C (secondo IEC 695);
• prova biglia: 125 °C;
• resistenza alle correnti striscianti: ≥ 250 V;
Caratteristiche elettriche
alimentazione (controllore con terminale connesso) 28…36 Vdc +10/-20% e 24 Vac +10/-15% 50…60 Hz; morsettiera
CPU memoria (su FLASH MEMORY) memoria dati (RAM statica) memoria dati parametri durata ciclo utile (applicazioni media complessità) orologio con batteria assorbimento massimo P= 15 W (alimentazione Vdc), P= 40 VA (Vac) con connettori maschio/femmina estraibili, tensione max 250 Vac; sez. cavo: min. 0,5 mm 2 - max 2,5 mm 2
H8S2320, 16 bit, 24 MHz
2+2 MB; nelle versioni estese un ulteriore memoria di 32 MB o superiore
512 kB organizzata a 16 bit (296 kB Bios; 216 kB applicativo)
13 kB organizzata a 16 bit (limite max: 400.000 scritture per locazione di memoria) e ulteriori 32 kB di E 2 prom (non visibili dalla pLAN)
0,2 s (tipico) di serie
Ingressi digitali
tipo numero massimo optoisolati
8: SMALL; 14: MEDIUM e EXTRALARGE N.O e N.C.; 18: LARGE. Secondo le combinazioni riportate qui sotto: n. ingr. optoisolati a 24 Vac n. ingr. optoisolati a 24 Vac/Vdc o totale
SMALL
MEDIUM/EXTRALARGE
LARGE
50/60 Hz o 24 Vdc
8
12
14
230 Vac (50/60 Hz) nessuno
2
4 ingressi
8
14
18 classifi cazione dei circuiti di misura
(CEI EN 61010-1)
Categooria I (J5, J7, J20) 24 Vac/Vdc
Categoria III (J8, J19) 230 Vac
AVVERTENZE: - 230 Vac 50/60 Hz (10/-15%);
- i due ingressi a 230/24 Vac presenti su J8 e J12, hanno il medesimo polo comune e quindi saranno entrambi a
24 Vac/Vdc o 230 Vac. L’isolamento tra i due ingressi è principale;
- in caso di ingressi in continua (Vdc) collegare il polo negativo al morsetto comune.
Nota: separare quanto più possibile i cavi dei segnali delle sonde e degli ingressi digitali dai cavi relativi ai carichi induttivi e di potenza, per evitare possibili disturbi elettromagnetici.
+050003290 - 1.4 - 29.09.2006 4
Ingressi analogici
conversione analogica tipo
A/D converter a 10 bit CPU built-in universale: (ingressi B1, B2, B3, B6, B7, B8) sensore di temperatura NTC CAREL (-50T90 °C; R/T 10 k Ω a 25 °C), NTC HT 0T150 °C, tensione: 0…1 Vdc, 0…5 V raziometrici o 0…10 Vdc, corrente:
0…20 mA o 4…20 mA, selezionabili via software. Resistenza di ingresso in 0…20 mA= 100 Ω passivo: (ingressi B4, B5, B9, B10) sensore di temp. NTC CAREL (vedi tipo universale),
PT1000 (-100T200 °C; R/T 1000 Ω a 0°C) o input digitale pulito (5 mA), selezionabili via software;
5: SMALL; 8: MEDIUM e EXTRALARGE N.O.; 10: LARGE e EXTRALARGE N.C.
0,5 s numero massimo costante di tempo per ogni ingresso precisione classifi cazione dei circuiti di misura (CEI EN 61010-1)
± 0,3 % del fondo scala
Categoria I
AVVERTENZA: per l’alimentazione di eventuali sonde attive, è possibile utilizzare i 21 Vdc disponibili sul morsetto +Vdc (J2), la corrente massima erogabile è di 150 mA protetta termicamente contro i corti circuiti. Per l’alimentazione delle sonde raziometriche 0…5 V si utilizzano i +5V
REF
(Imax: 60 mA) presenti nel morsetto J24.
Uscite analogiche
tipo numero massimo alimentazione risoluzione carico massimo precisione
0…10 Vdc optoisolate
4: SMALL, MEDIUM e EXTRALARGE N.O./N.C.; 6: LARGE esterna 24 Vac/Vdc
8 bit
1 k Ω (10 mA)
± 2 % del fondo scala sulle uscite: Y1, Y2, Y3 e Y4
-2%/+5% del fondo scala sulle: Y5 e Y6
Uscite digitali
tipo relè numero massimo 8: SMALL; 13: MEDIUM; 18: LARGE; 27: EXTRALARGE N.C.; 29: EXTRALARGE N.O.
Per i collegamenti si fa riferimento alle Fig. 3…5 (riferimento NO*, NC* e C*). Si nota la presenza di uscite con contatto in scambio tenute separate (ovvero senza poli condivisi tra uscite distinte). I gruppi da 2 a 5 uscite prevedono 2 poli “comuni” per un facile assemblaggio.
Prestare attenzione alla corrente circolante nei morsetti comuni in quanto la stessa non deve superare la corrente nominale di un singolo morsetto, ovvero 8A.
Distanza isolamento
Composizione gruppi le uscite sono suddivisibili in gruppi. Tra gruppo e gruppo (cella-cella della tabella) vi è doppio isolamento.
Nota: i relè appartenenti ad uno stesso gruppo devono essere sottoposti alla stessa tensione di alimentazione (24 o 230 Vac).
versione
SMALL
Tipo di relè
MEDIUM
Tipo di relè
LARGE
Tipo di relè
EXTRALARGE N.O.
Tipo di relè
EXTRALARGE N.C.
Tipo di relè relè a pari isolamento
1…7 8
Tipo A Tipo A
-
1…7 8 9…13 -
Tipo A Tipo A Tipo A
-
-
1…7 8 9…13 14…18 -
Tipo A Tipo A Tipo A Tipo A
1…7 8 9…13 14…16 17…20 21…24 25…29
Tipo A Tipo A Tipo A Tipo B Tipo B Tipo B Tipo B
1…7 8 9…13 14…16 17…20 21…24 25…27
Tipo A Tipo A Tipo A Tipo C Tipo C Tipo C Tipo C
Contatti in scambio
Potenza commutabile
Uscite SSR
NOTA: i relè nelle singole celle della tabella hanno isolamento principale, mentre tra gruppi di cella hanno doppio isolamento.
1: SMALL (relè 8); 3: MEDIUM e EXTRALARGE N.O./N.C. (relè 8, 12 e 13); 5: LARGE (relè 8, 12, 13, 14 e 15) avvertenza: le uscite relè hanno caratteristiche diverse a seconda del modello di pCO 3 relè di tipo A relè di tipo B relè di tipo C t ipo relè: SPDT, 2000 VA, 250 Vac, 8 A resistivi omologazioni pCO 3 : UL873: 2,5 A resistivi, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 cicli)
EN 60730-1: 2 A resistivi, 2 A induttivi, cos ϕ = 0,6, 2(2) A (100000 cicli) t ipo relè: SPDT, 1250 VA, 250 Vac, 5 A resistivi omologazioni pCO 3 : UL873: 1 A resistivi, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cicli)
EN 60730-1: 1 A resistivi, 1 A induttivi, cos ϕ = 0,6, 1(1) A (100000 cicli) tipo relè: SPDT, 1250 VA, 250 Vac, 5 A resistivi omologazioni pCO 3 : UL873: 1 A resistivi, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cicli)
EN 60730-1: 1 A resistivi, 1 A induttivi, cos ϕ = 0,6, 1(1) A (100000 cicli)
1: SMALL (uscita 7); 2: MEDIUM e EXTRALARGE N.O./N.C. (uscite 7 e 12); 3: LARGE (uscite 7, 12 e 14) tensione di lavoro: 24 Vac/Vdc; potenza massima: 10 W
+050003290 - 1.4 - 29.09.2006 5 italiano
Corrispondenza AWG e sezione cavo
AWG
20
15
14
Sezione (mm
0,5
1,5
2,5
2 ) Corrente
2
6
8
Collegamento rete pLAN/terminale utente
tipo velocità di trasmissione connettore per terminale connettore rete pLAN/terminale grafi co/terminale aria asincrono half duplex RS485
62,5 Kbps o 115,2 Kbps selezionabili via software telefonico a 6 vie (J10) connettore estraibile 3 vie (J11)
La distanza massima tra pCO e terminale utente è riportata nella seguente tabella.
tipo cavo telefonico distanza alimentazione
50 m alimentazione prelevata da pCO (150 mA) cavo schermato AWG24 cavo schermato AWG20/22
200 m
500 m prelevata da pCO (150 mA) alimentazione separata tramite TCONN6J000
La distanza massima tra due pCO 3 con cavo schermato AWG20/22 è pari a 500 m.
Nota:
• su J10 è consentito il collegamento al massimo di un terminale (pCOT, pCOI, pGD0, pGD1) o di due terminali ma senza l’utilizzo
della retroilluminazione per il display. Esiste una versione di pCO 3 dove il collegamento alla rete pLAN è di tipo optoisolato.
• terminale grafi co e terminale aria vanno sempre alimentati con alimentazione separate.
• La tensione di 21Vdc presente sul morsetto +Vterm (J24) è utilizzabile per alimentare un terminale esterno con assorbimento
massimo 2W. È consentito collegare un solo terminale (ad esempio terminale PLD o terminale aria) oltre a quello connesso sul
Altre caratteristiche
condizioni di immagazzinamento condizioni di funzionamento grado di protezione inquinamento ambientale classe secondo la protezione contro le scosse elettriche
PTI dei materiali per isolamento periodo delle sollecitazioni elettriche delle parti isolanti tipo azioni tipo disconnessione o microinterruzione categoria di resistenza al calore e al fuoco immunità contro le sovratensioni caratteristiche di invecchiamento (ore di funzionamento) n. cicli di manovra operazioni automatiche classe e struttura del software categoria di immunità al surge (CEI EN 61000-4-5)
Il dispositivo non è destinato ad essere tenuto in mano
-40T70 °C, 90% UR non condensante
-25T70 °C, 90% UR non condensante
IP20, IP40 nel solo frontalino normale da integrare su apparecchiature di Classe I e/o II
250 V lungo
1C microinterruzione categoria D (UL94 - V0) categoria 1
80.000
100.000 (EN 60730-1); 30.000 (UL 873)
Classe A
Categoria III
•
•
•
•
•
•
•
AVVERTENZE per applicazioni soggette a forte vibrazioni (1,5 mm pk-pk 10/55 Hz) si consiglia di fi ssare tramite fascette i cavi collegati al pCO 3 a circa 3 cm di distanza dai connettori; se il prodotto è installato in ambiente industriale (applicazione della normativa EN 61000-6-2) la lunghezza dei collegamenti deve essere inferiore a 30 m; l’installazione deve essere eseguita secondo le normative e legislazioni vigenti nel paese di utilizzo dell’apparecchiatura; per motivi di sicurezza l’apparecchiatura deve essere alloggiata all’interno di un quadro elettrico, in modo che l’unica parte raggiungibile sia il display e la tastiera comando; tutte le connessioni in bassissima tensione (Ingressi analogici e digitali a 24 Vac/Vdc, uscite analogiche, connessioni bus seriali, alimentazioni) devono avere un isolamento rinforzato o doppio rispetto alla rete; per qualsiasi malfunzionamento non tentare di riparare l’apparecchio, ma rivolgersi al centro di assistenza CAREL; in ambiente domestico il cavo di collegamento tra il pCO3 e il terminale deve esser eschermato.
+050003290 - 1.4 - 29.09.2006 6
DIMENSIONI
Dimensioni pCO 3 MEDIUM, LARGE, EXTRALARGE N.O. e N.C.
Dimensioni pCO 3 SMALL
227,5
315
44
45 110
60 Fig. 2
44
45 110
60 Fig. 1
•
•
•
CERTIFICAZIONI DI PRODOTTO normativa CEI EN 50155: “Applicazioni ferroviarie, tramviarie, fi loviarie e metropolitane. Equipaggiamenti elettronici utilizzati sul materiale rotabile”; normative UL 873 e C22.2 No.24-93: “Temperature-indicating and regulating equipment”; regolamento CE 37/2005 del 12 Gennaio 2005; in particolare, se il controllo elettronico è equipaggiato con sonde NTC standard
CAREL, è conforme alla normativa EN13485 relativa ai “Termometri per la misurazione della temperatura dell’aria per applicazioni su unità di conservazione e di distribuzione di alimenti refrigerati, congelati, surgelati e dei gelati”.
Smaltimento del prodotto
L’apparecchiatura (o il prodotto) deve essere oggetto di raccolta separata in conformità alle vigenti normative locali in materia di smaltimento.
+050003290 - 1.4 - 29.09.2006 7 italiano
ELEMENTI STRUMENTO
4
7
1
3
15
4
5
2
14
6
7
8
G
G0
+V term
GND
+5 V
REF
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
ID13H
ID13
IDC13
ID14
ID14H
ID10
ID11
ID12
IDC9
B6
B7
B8
GND
ID9
Y3
Y4
ID1
Y1
Y2
VG
VG0
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
B9
BC9
B10
BC10
ID17
ID18
IDC17
8
6
5
7
+050003290 - 1.4 - 29.09.2006 8
11
12
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
E-
E+
GND
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
C7
NO7
C7
NO8
C8
NC8
C4
NO4
NO5
NO6
C4
C1
NO1
NO2
NO3
C1
Rx-/Tx-
Rx+/Tx+
GND
9
10
13
16
17
11
Fig. 3
Versione EXTRALARGE N.O.
C21
NO21
NO22
NO23
NO24
C21
C25
NO25
NO26
NO27
NO28
NO29
C25
11
Versione EXTRALARGE N.C.
12
C17
NO17
NO18
NO19
NO20
C17
E-
E+
GND
C14
NO14
NO15
NO16
C14
C21
NC21
NC22
NC23
NC24
C21
C14
NC14
NC15
NC16
C14
B9
B10
BC9
C25
NC25
NC26
NC27
C25
11
5
12
C17
NC17
NC18
NC19
NC20
C17
E-
E+
GND
Legenda (Fig. 3…5)
1.
connettore per l’alimentazione [G (+), G0 (-)];
2.
LED giallo indicazione presenza tensione di alimentazione e 3 LED per la rete locale pLAN;
3.
alimentazione aggiuntiva per terminale e sonde raziometriche 0…5 V;
4.
ingressi analogici universali NTC, 0…1 V, 0…5 V raziometrici, 0…10 V, 0…20 mA, 4…20 mA;
5.
ingressi analogici passivi NTC, PT1000, ON/OFF;
6.
uscite analogiche 0…10 V;
7.
ingressi digitali a 24 Vac/Vdc;
8.
ingressi digitali 230 Vac o 24 Vac/Vdc;
9.
connettore per il terminale sinottico (pannello esterno con segnalazioni dirette);
10.
connettore per tutti i terminali standard della serie pCO e per il download del programma applicativo;
11.
uscite digitali a relè;
12.
connettore per la connessione alla scheda di espansione I/O;
13.
connettore rete locale pLAN;
14.
sportello per l’inserimento dell’opzione serial card per supervisore;
15.
sportello per l’inserimento dell’opzione fi eld card;
16.
sportello per l’inserimento del’opzione service card;
17.
terminale built-in (LCD, tasti e LED).
+050003290 - 1.4 - 29.09.2006 9 italiano
NOTE PRELIMINARI PER L’INSTALLATORE: CONFRONTO TRA pCO 3 E pCO 2
• tutti i controlli della famiglia pCO 3 non sono provvisti del connettore per la programmazione tramite chiave PCO201KEY0. Per la
programmazione del controllo è necessario utilizzare la nuova Smart Key (PCOS00AKY0) disponibile da settembre 2005. Utilizzare
altrimenti il WinLoad vers. 3.35 e successive.
Fig. 6
Non è possibile eseguire un applicativo dalla Smart Key;
• a differenza del pCO 2 non è presente il fusibile tra J1 e J2. Tutti i controlli della famiglia pCO 3 hanno al loro interno una
protezione termica sull’alimentazione. Non è richiesto l’utilizzo di un fusibile esterno;
• è presente un ulteriore morsetto J24 (al posto del fusibile) che fornisce la tensione di alimentazione per le sonde raziomentriche
(+5
REF
) e una tensione continua di 20V per alimentare un terminale secondario, come il terminale aria (TAT***), in alternativa a
• i LED presenti vicino ai dip-switch di indirizzamento pLAN sono stati spostati tra i connettori J3 e J4;
• è stato eliminato il LED rosso di sovraccarico alimentazione sonde.
Simulatore pCO 3 :
Nel caso si volesse provare il pCO 3 con un simulatore si fa presente che non può essere usato quello del pCO 2 , ma serve il simulatore del pCO 3 . Chiedere disponibilità a CAREL.
Procedura di indirizzamento di controllo e terminale
Indirizzamento del controllo
Il controllore pCO 3 NON è provvisto di dip-switch per l’impostazione dell’indirizzo pLAN. L’indirizzo deve essere impostato con procedura software, come per il pCO 1/XS .
La procedura è la seguente:
1. disalimentare il pCO 3 ;
2. predisporre un terminale standard CAREL con indirizzo a 0 (non necessario se si utilizza il terminale Built-in del pCO 3 ). Per questa
operazione vedere il paragrafo successivo;
3. collegare il terminale al pCO 3 ;
4. scollegare dal pCO 3 eventuali altri dispositivi collegati in pLAN (terminale J11);
5. alimentare il pCO 3 premendo contemporaneamente i tasti UP + ALARM. La combinazione di tasti vale anche da terminale built in. In
alternativa, nei terminali PCOT, utilizzare la combinazione di tasti menu e .
6. dopo qualche secondo appare la seguente schermata:
PLAN ADDRESS: 0
UP: INCREASE
DOWN: DECREASE
ENTER: SAVE & EXIT
7. Se si vuole modifi care l’indirizzo basta agire sui tasti UP e DOWN e poi premere ENTER per confermare.
8. è necessario ora impostare l’indirizzo pLAN del terminale e la confi gurazione della rete pLAN.
Indirizzamento del terminale
Terminale di tipo pCOI/pCOT
L’indirizzamento del terminale avviene tramite i DIP_SWITCH presenti sul retro del terminale stesso.
Terminale di tipo pGD0/1/2/3
Il valore dell’indirizzo preimpostato in fabbrica è 32.
È possibile confi gurare l’indirizzo del terminale solo dopo aver fornito alimentazione allo stesso tramite il connettore telefonico.
Per entrare in modalità confi gurazione premere contemporaneamente i tasti ↓↑↵ (anche da terminale già acceso), sempre presenti in tutte le versioni, per almeno 5 secondi; verrà visualizzata la maschera della fi gura seguente qui sotto con il cursore lampeggiante nell’angolo in alto a sinistra:
Display address setting.........:nn
I/O Board address:xx
• per modifi care l’indirizzo del terminale (display address setting) premere una volta il tasto ↵ : il cursore si sposterà sul campo
+050003290 - 1.4 - 29.09.2006 10
• tramite i tasti ↓↑ selezionare il valore voluto, e confermare ripremendo il tasto ↵ . Se il valore selezionato è diverso da quello
memorizzato precedentemente apparirà la maschera di fi gura seguente e il nuovo valore verrà memorizzato nella memoria
permanente del display.
Display address changed
Se si imposta il campo nn al valore 0, il terminale comunicherà con il controllo pCO 3 usando il protocollo “punto-punto” (non pLAN) e il campo “I/O Board address: xx” scompare in quanto privo di signifi cato.
pCO
3
: assegnazione lista terminali privati e condivisi
A questo punto, se fosse necessario modifi care la lista dei terminali associata ad ogni singola scheda pCO 3 , si dovrà seguire la seguente procedura:
• entrare nella modalità confi gurazione con i tasti ↓↑↵ come descritto nel paragrafo precedente;
• premere il tasto ↵ fi no a che il cursore si posiziona sul campo xx (I/O board address) ;
• tramite i tasti ↓↑ scegliere l’indirizzo della scheda pCO 3 desiderata. I valori selezionabili saranno solo quelli delle schede pCO 3
effettivamente in linea. Se la rete pLAN non funziona correttamente, oppure non è presente nessuna scheda pCO 3 , non sarà possibile
modifi care il campo che mostrerà solo “—”;
• premendo ancora una volta il tasto ↵ verranno visualizzate in sequenza le maschere seguenti:
Terminal Config
Press ENTER to continue
P12:Adr Priv/Shared
Trm1 02 Sh
Trm2 03 Pr
Trm3 None --OK?NO
• anche qui il tasto ↵ muove il cursore da un campo all’altro e i tasti ↓↑ cambiano il valore del campo corrente. Il campo P:xx mostra
l’indirizzo della scheda selezionata; nell’esempio di fi gura è stata selezionata la 12;
• per uscire dalla procedura di confi gurazione e memorizzare i dati selezionare il campo “OK ?” impostare Yes e confermare con il
tasto .
I campi della colonna “Adr” rappresentano gli indirizzi dei terminali associati alla scheda pCO 3 di indirizzo 12, mentre la colonna
Priv/Shared indica il tipo di terminale.
Attenzione: i terminali della linea pGD non possono essere confi gurati come “Sp” (shared printer) in quanto privi dell’uscita stampante.
Se il terminale rimane inattivo (nessun tasto premuto) per più di 30 secondi esce automaticamente dalla procedura di confi gurazione senza memorizzare gli eventuali cambiamenti.
NOTE SULL’UTILIZZO DI WINLOAD, BOOT E BIOS
Si raccomanda di utilizzare sempre la versione più recente di WinLoad. La gestione del pCO 3 è supportata dalla versione WinLoad 3.35.
Dalla versione 3.36 la velocità di scaricamento di Bios e applicativo per il pCO3 passa a 115200 bit/s invece della velocità standard
28800 bit/s, questo cambiamento non comporta nessuna nuova impostazione da parte dell’utilizzatore.
Il BIOS e il BOOT del pCO 3 sono fi le specifi ci, diversi dai fi le di BIOS e BOOT del pCO 1 e del pCO 2 . Non è possibile quindi il caricamento di questi sul pCO 3 , e, ovviamente, non è possibile caricare i fi le di BOOT e BIOS per il pCO 3 sul pCO 1 e pCO 2 .
AVVERTENZE IMPORTANTI
Il prodotto CAREL è un prodotto avanzato, il cui funzionamento è specifi cato nella documentazione tecnica fornita col prodotto o scaricabile, anche anteriormente all’acquisto, dal sito internet www.carel.com.
Il cliente (costruttore, progettista o installatore dell’equipaggiamento fi nale) si assume ogni responsabilità e rischio in relazione alla fase di confi gurazione del prodotto per il raggiungimento dei risultati previsti in relazione all’installazione e/o equipaggiamento fi nale specifi co.
La mancanza di tale fase di studio, la quale è richiesta/indicata nel manuale d’uso, può generare malfunzionamenti nei prodotti fi nali di cui
CAREL non potrà essere ritenuta responsabile.
Il cliente fi nale deve usare il prodotto solo nelle modalità descritte nella documentazione relativa al prodotto stesso.
La responsabilità di CAREL in relazione al proprio prodotto è regolata dalle condizioni generali di contratto CAREL editate nel sito www.
carel.com e/o da specifi ci accordi con i clienti.
+050003290 - 1.4 - 29.09.2006 11 italiano
Note: ______________________________________________________________________
_____________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
GENERAL CHARACTERISTICS pCO 3 is a microprocessor-based electronic controller compatible in both hardware and software terms with the pCO 2 family. Developed by CAREL in compliance with the European RoHS directives, it provides a solution for many applications in the air-conditioning and refrigeration sectors. It ensures absolute versatility, allowing specifi c products to be created to customer request.
pCO 3 runs the control program, and is fi tted with the set of terminals required for connection to the devices (compressors, fans…). The program and the parameters are saved to FLASH-MEMORY and E 2 prom, ensuring they are stored even in the event of power failures
(without requiring a backup battery).
The program can be loaded using a PC (28.8 kbps and 115.2 kbps) or the special programming key.
pCO 3 also allows connection to the pLAN (pCO Local Area Network) and can be connected, as well as to other pCO 3 controllers, to all the other controllers in the pCO sistema and all the pGD family terminals. All the controllers in the pLAN can exchange information
(variables, digital or analogue, depending on the application software used) at high transmission speed. Up to 32 units can be connected, including pCO controllers and terminals, so as to share the information effectively.
The connection to the supervisor/telemaintenance serial line, via the CAREL or Modbus™ communication protocol over the RS485 standard, is performed by inserting an optional serial board in the pCO 3 .
Other optional cards can be used to connect to a supervisor via standards other than RS485. Finally, the serial fi eld bus interface, using the optional board, ensures connection to the fi eld devices controlled (for example: valves, pCOe I/O expansions, electronic valve drivers...).
Versions available:
• SMALL, MEDIUM, LARGE, EXTRALARGE N.O. and EXTRALARGE N.C.;
• with or without Built-In terminal;
• with additional fl ash memory and optically-isolated pLAN;
• with or without solid state relay (SSR) digital outputs.
Note: the application software can be downloaded to the fl ash memory using the smart key PCOS00AKY0, see Fig. 6; or a PC using the
USB-485 adapter “CVSTDUTLF0” and the “WINLOAD32” program, to be ordered from CAREL.
Power supply
A Class II safety transformer with a minimum rating of 50 VA must be used in the installation to supply just one pCO 3 controller. The power supply to the µ pCO 3 controller and terminal (or pCO 3 controllers and terminals) should be separated from the power supply to the other electrical devices (contactors and other electromechanical components) inside the electrical panel. If the secondary of the transformer is earthed, make sure that the earth wire is connected to terminal G0. This is true for all the devices connected to the pCO 3 .
If powering more than one pCO 3 board connected in the pLAN network, make sure that the references G and G0 are observed (the reference G0 must be maintained for all the boards).
If using the pLAN network and for further explanations and information, please refer to the CAREL manual pCO 3 .
Field Bus options optically isolated 485 PCO100FD10 tLAN PCO100TLN0
Belimo MPbus modem
CAN hydronic
PCO100MPB0
PCOS00FD20
PCOS00HBF0
BMS options
CANbus
485/Modbus modem
Ethernet board
LonWorks
LonWorks
LonWorks
PCOS00HBB0
PCOS004850
PCO100MDM0
PCO1000WB0
FTT10
FTT10 standard chiller profi le
PCO10000F0
PCO10001F0
+050003290 - 1.4 - 29.09.2006 13 english
Connettori
Example of coding: PCO3CON*** , see the following table for the description:
PCO3CON *
0 = screw
1 = spring
*
S = small
M = medium
L = large
Z = extra large N.O.
C = extra large N.C.
0
TECHNICAL SPECIFICATIONS
Mechanical characteristics
dimensions installation
SMALL version fi tted on 13 DIN rail modules, 110 x 227.5 x 60 mm
MEDIUM, LARGE and EXTRALARGE version fi tted on 18 DIN rail modules, 110 x 315 x 60 mm
DIN rail
Plastic case
• fi tted on DIN rail according to DIN 43880 and CEI EN 50022 standards;
• material: technopolymer;
• fl ame retardancy: V0 (UL94) and 960°C (IEC 695);
• ball pressure test: 125°C;
• resistance to creeping current: ≥ 250 V;
• colour: grey RAL7035;
Electrical specifi cations
power supply (controller with terminal connected) 28 TO 36 Vdc +10/-20% and 24 Vac +10/-15% 50 to 60 HZ maximum power input P= 15 W (24 Vdc power supply), P= 40 VA
(24 Vac) with plug-in male/female connectors, max voltage 250 Vac; terminal block
CPU memory (FLASH MEMORY) data memory (static RAM) parameter data memory cable cross-section: min. 0.5 mm 2 - max 2.5 mm 2
H8S2320, 16 bit, 24 MHz
2+2 MB; in the extended versions further memory of 32 MB or higher
512 kB at 16 bit (296 kB BIOS; 216 application sw)
13 kB at 16 bit (max. limit: 400,000 writes per memory location) and a further 32 kB E 2 prom (not available to the pLAN) working cycle duration (applications of average complexity) 0.2 s (typical) clock with battery standard
Digital inputs
type maximum number optically-isolated
8, 14, 18, respectively on the SMALL, MEDIUM and EXTRALARGE N.O and N.C., LARGE boards, according to the combinations shown below: optoinsulated input no. to 24 Vac optoinsulated input no. to
24 Vac/Vdc or 230 Vac (50/60 Hz) inputs
SMALL
MEDIUM/
50/60 Hz or 24 Vdc
8
12 none
2
8
14
EXTRALARGE
LARGE 14 4 18
Category I (J5, J7, J20) 24 Vac/Vdc
Category III (J8, J19) 230 Vac classifi cation of the measuring circuits
(CEI EN 61010-1)
WARNINGS: - 230 Vac 50/60 Hz (10/-15%);
- the two 230/24 Vac inputs present on J8 and J12 have the same common pole and consequently will be both
24 Vac/Vdc or both 230 Vac. Basic insulation between the two inputs;
- for DC inputs, connect the negative pole to the common terminal.
Note: separate as much as possible the probe and digital input signal cables from the cables carrying the inductive loads and the power cables, to avoid possible electromagnetic disturbance.
+050003290 - 1.4 - 29.09.2006 14
Analogue inputs
analogue conversion type maximum number time constant for each input precision classifi cation of the measuring circuits (CEI EN 61010-1)
10 bit A/D converter in the CPU universal: (inputs B1, B2, B3, B6, B7, B8) CAREL NTC temperature sensor (-50T90°C; R/T 10 k Ω at 25°C),
HT NTC 0T150°C, voltage: 0 to 1 Vdc, 0 to 5 V ratiometric or 0 to 10 Vdc, current: 0 to 20 mA or 4 to 20 mA, selectable via software. Input resistance in 0 to 20 mA= 100 Ω passive: (inputs B4, B5, B9, B10) CAREL NTC temp. sensor (see universal type),
PT1000 (-100T200°C; R/T 1000 Ω at 0°C) or voltage-free digital input (5 mA), selectable via software;
5, 8, 10, on the SMALL, MEDIUM and EXTRALARGE N.O., LARGE and EXTRALARGE N.C. boards respectively
0.5 s
± 0.3 % of full scale
Category I
WARNING: the 21 Vdc available at the +Vdc terminal (J2) can be used to power any active probes, the maximum current is 150 mA, thermally protected against short-circuits. To supply the ratiometric 0 to 5 V probes, use the +5V
REF
(Imax: 60 mA) present at terminal J24.
Analogue outputs
type maximum number power supply resolution maximum load precision
0 to 10 Vdc optically-isolated
4, 4, 6, on the SMALL, MEDIUM and EXTRALARGE N.O./N.C., LARGE boards respectively external 24 Vac/Vdc
8 bit
1 k Ω (10 mA)
± 2 % of end scale on outputs: Y1, Y2, Y3 and Y4
-2%/+5% of end scale on: Y5 and Y6
Digital outputs
type relay maximum number 8: SMALL; 13: MEDIUM; 18: LARGE; 27: EXTRALARGE N.C.; 29: EXTRALARGE N.O.
For the requirements refer to Figs. 3 to 5 (reference NO*, NC* and C*). Note the presence of outputs with changeover contacts kept separately (that is, without the poles shared between different outputs). Groups from 2 to 5 outputs have 2 “common” poles for easy assembly.
Make sure that the current running through the common terminals does not exceed the rated current of each individual terminal, that is 8A.
Insulation distance
Makeup of the groups the outputs can be divided into groups. There is double insulation between groups (between cells in the table).
Note: the relays in the same group must have the same power supply (24 or 230 Vac).
version
SMALL
Type of relay
MEDIUM
Type of relay
LARGE
Type of relay
EXTRALARGE N.O.
Type of relay
EXTRALARGE N.C.
Type of relay relays with same insulation
1…7 8 -
A type A type
-
1…7 8 9…13 -
A type A type A type
1…7 8 9…13 14…18 -
A type A type A type A type
-
1…7 8 9…13 14…16 17…20 21…24 25…29
A type A type A type B type B type B type B type
1…7 8 9…13 14…16 17…20 21…24 25…27
A type A type A type C type C type C type C type
Note: the relays in the individual cells of the table have basic insulation between them, while between groups (cell-cell) there is double insulation.
Changeover contacts 1: SMALL (relè 8); 3: MEDIUM e EXTRALARGE N.O./N.C. (relè 8, 12 e 13); 5: LARGE (relè 8, 12, 13, 14 e 15)
Switchable power warning: the relay outputs have different characteristics according to the model of pCO relay type of relay: SPDT, 2000 VA, 250 Vac, 8 A resistive
3 type A relay type B relay type C pCO 3 approval: UL873: 2.5 A resistive, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 cycles)
EN 60730-1: 2 A resistive, 2 A inductive, cos ϕ = 0.6, 2(2) A (100000 cycles) type of relay: SPDT, 1250 VA, 250 Vac, 5 A resistive pCO 3 approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cos ϕ = 0.6, 1(1) A (100000 cycles) type of relay: SPDT, 1250 VA, 250 Vac, 5 A resistive pCO 3 approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cos ϕ = 0.6, 1(1) A (100000 cycles)
SSR outputs 1: SMALL (output 7); 2: MEDIUM - EXTRALARGE N.O./N.C. (outputs 7, 12); 3: LARGE (OUTPUTS 7, 12, 14) operating voltage 24 Vac/Vdc; maximum power: 10 W
+050003290 - 1.4 - 29.09.2006 15 english
Relation between AWG and wire cross-section
AWG Cross-section (mm 2 ) Current
20
15
14
0.5
1.5
2.5
2
6
8
pLAN network/user terminal connection
type transmission speed terminal connector pLAN network/graphic terminal/aria terminal connector
RS485 half-duplex asynchronous
62.5 Kbps or 115.2 Kbps, selectable via software
6 pin telephone (J10)
3 pin plug-in connector (J11)
The maximum distance between the pCO and user terminal is shown in the following table.
cable type telephone
AWG24 shielded cable
AWG20/22 shielded cable power supply distance
50 m
200 m
500 m power supply taken from the pCO (150 mA) taken from the pCO (150 mA) separate power supply via TCONN6J000
The maximum distance between two pCO 3 controllers with AWG20/22 shielded cable is 500 m.
Note:
• a maximum of one terminal (pCOT, pCOI, pGD0, pGD1) can be connected, or two terminals but without using use the backlighting on display. One version of the pCO 3 features optically-isolated connection to the pLAN network.
• the graphic terminal and aria terminal should be always powered with a separate power supply.
• the 21 Vdc present at +Vterm (J24) can be used to power an external terminal with a maximum input of 2 W. Only one terminal
can be connected (for example PLD terminal or ARIA terminal) in addition to the one connected to terminal J10.
Other specifi cations
storage conditions operating conditions index of protection environmental pollution class according to protection against electric shock
PTI of the insulating materials period of stress across the insulating parts type of action type of disconnection or microswitching
-40T70 °C, 90% RH non-condensing
-25T70 °C, 90% RH non-condensing
IP20, IP40 front panel only normal to be incorporated into Class I and/or II appliances
250 V long
1C microswitching category of resistance to heat and fi re immunity against voltage surges ageing characteristics (operating hours) no. of automatic operating cycles category D (UL94 - V0) category 1
80,000
100,000 (EN 60730-1); 30,000 (UL 873) software class and structure Class A category of immunity to voltage surges (CEI EN 61000-4-5) Category III
The device is not designed to be hand-held
WARNING
• for applications subject to strong vibrations (1.5 mm pk-pk 10/55 Hz), secure the cables connected to the µ pCO 3 using clamps
placed around 3 cm from the connectors
• If the product is installed in industrial environments (application of the EN 61000-6-2 standard) the length of the output connections must be less than 30 m.
• installation must be performed according to the standards and legislation in force in the country where the appliance is used;
• for safety reasons the appliance must be housed inside an electrical panel, so that the only accessible part is the display and the
• all the very low voltage connections (analogue and digital inputs at 24 Vac/Vdc, analogue outputs, serial bus connections, power)
must have reinforced or double insulation from the mains;
• in the event of malfunctions do not attempt to repair the appliance, but rather contact the CAREL service centre;
• in domestic environments, the connection cable between the pCO 3 and the terminal must be shielded.
+050003290 - 1.4 - 29.09.2006 16
DIMENSIONS
Dimensions pCO 3 MEDIUM, LARGE, EXTRALARGE N.O. and N.C.
Dimensions pCO 3 SMALL
315
227,5
44
45 110
60
Fig. 5
44
45 110
60
Fig. 4
•
•
•
PRODUCT CERTIFICATION
CEI EN 50155 standard: “Railway applications − Electronic equipment used on rolling stock”;
UL 873 and C22.2 No. 24-93: “Temperature-Indicating and -Regulating Equipment”;
EC regulations 37/2005 of 12 January 2005; in particular, if the electronic controller is fi tted with standard Carel NTC probes, it is compliant with standard EN13485 on “Thermometers for measuring the air temperature in applications on units for the conservation and sale of refrigerated, frozen and deep-frozen food and ice cream”.
Disposal of the product
The appliance (or the product) must be disposed of separately in accordance with the local waste disposal legislation in force.
+050003290 - 1.4 - 29.09.2006 17 english
INSTRUMENT ELEMENTS
4
7
1
3
15
4
5
2
14
6
7
8
G
G0
+V term
GND
+5 V
REF
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
ID13H
ID13
IDC13
ID14
ID14H
ID10
ID11
ID12
IDC9
B6
B7
B8
GND
ID9
Y3
Y4
ID1
Y1
Y2
VG
VG0
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
B9
BC9
B10
BC10
ID17
ID18
IDC17
8
6
5
7
+050003290 - 1.4 - 29.09.2006 18
11
12
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
E-
E+
GND
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
C7
NO7
C7
NO8
C8
NC8
C4
NO4
NO5
NO6
C4
C1
NO1
NO2
NO3
C1
Rx-/Tx-
Rx+/Tx+
GND
9
10
13
16
17
11
Fig. 3
EXTRALARGE N.O. version
C21
NO21
NO22
NO23
NO24
C21
C25
NO25
NO26
NO27
NO28
NO29
C25
11
12
C17
NO17
NO18
NO19
NO20
C17
E-
E+
GND
C14
NO14
NO15
NO16
C14
EXTRALARGE N.C. version
C21
NC21
NC22
NC23
NC24
C21
B9
B10
BC9
C25
NC25
NC26
NC27
C25
11
5
12
C17
NC17
NC18
NC19
NC20
C17
E-
E+
GND
C14
NC14
NC15
NC16
C14
Key (Figs. 3 to 5)
1 .
power supply connector [G (+), G0 (-)];
2.
yellow power LED and 3 LEDs for the pLAN networks;
3.
additional power supply (max. 200 mA) for the terminal and 0 to 5 V ratiometric probes;
4.
universal NTC, 0 to 1 V, 0 to 5 V ratiometric, 0 to 10 V,
0 to 20 mA, 4 to 20 mA analogue inputs;
5.
passive NTC, PT1000, ON/OFF analogue inputs;
6.
0 to 10 V analogue outputs;
7.
24 Vac/Vdc digital inputs;
8.
230 Vac or 24 Vac/Vdc digital inputs;
9.
connector for terminal display (external panel with direct signals);
10.
connector for all the standard pCO series terminals and for downloading the application software;
11.
digital relay outputs;
12.
connector for the I/O board expansion;
13.
pLAN connector;
14.
cover for inserting the optional supervisor serial board;
15.
cover for inserting the optional fi eld board;
16.
cover for inserting the optional service board;
+050003290 - 1.4 - 29.09.2006 19 english
PRELIMINARY NOTES FOR THE INSTALLER: COMPARISON BETWEEN pCO 3 AND pCO 2
• the pCO 3 family controllers do not have the connector using the programming key code PCO201KEY0. To program the controller,
use the new Smart Key (PCOS00AKY0) available from September 2005. Otherwise use WinLoad ver. 3.35 and higher:
Fig. 6
An application cannot be run from the Smart Key;
• unlike the pCO 2 , there is no fuse between J1 and J2. All pCO 3 family controllers have an internal thermal protector on the power
supply. No external fuse is required;
• a further terminal J24 (in place of the fuse) is provided for the power supply to the ratiometric probes (+5 VREF), as well as 20 Vdc to supply a secondary terminal, such as the aria terminal (TAT***), in alternative to the standard one;
• the terminal J11 (connection to the pLAN network) in the fi rst prototypes of the pCO 3 only has a pitch of 3.81, rather than the 5.08
on the pCO 2 ;
• the LEDs near the dipswitches for setting the pLAN address have been moved between connectors J3 and J4;
• the red probe power supply overload LED has been removed.
pCO 3 simulator:
If testing the pCO 3 with a simulator, note that the pCO 2 simulator cannot be used in place of the pCO 3 simulator. Contact CAREL for the availability of the latter.
Procedure for setting the address of the controller and terminal
Setting the address of the controller
The pCO 3 controller does NOT have dipswitches for setting the pLAN address. The address must be set by software, as for the pCO 1/XS .
The procedure is as follows:
1. switch the pCO 3 off;
2. prepare a standard Carel terminal with the address set to 0 (not necessary if the pCO 3 Built-In terminal is used). For this operation, see the following paragraph;
3. connect the terminal to the pCO 3 ;
4. disconnect any other devices connected in the pLAN from the pCO 3 (terminal J11);
5. switch the pCO 3 on, pressing the UP + ALARM buttons at the same time. This combination of buttons is the same on the built in
terminal. Alternatively, on the PCOT terminals, use the combination of the menu and
6. after a few seconds, the following screen will be displayed:
PLAN ADDRESS: 0
UP: INCREASE
DOWN: DECREASE
ENTER: SAVE & EXIT
buttons.
7. to modify the address simply use the UP and DOWN buttons and then press ENTER to confi rm.
8. now set the pLAN address of the terminal and confi gure the pLAN network.
Setting the address of the terminal pCOI/pCOT terminal
The address of the terminal is set using the DIPSWITCHES on the rear of the terminal.
pGD0/1/2/3 terminal
The default value of the address is 32.
The address of the terminal can only be set after having connected the power supply via the telephone connector.
To enter confi guration mode, press the ↓↑↵ buttons at the same time (even when the terminal is already on), in all the versions, for at least 5 seconds; the following screen will be displayed, with the cursor fl ashing in the top left corner:
Display address setting.........:nn
I/O Board address:xx
• to modify the address of the terminal (display address setting) press the ↵ button once: the cursor will move to the address fi eld
(nn).
+050003290 - 1.4 - 29.09.2006 20
• use the ↓↑ buttons to select the desired value, and confi rm by pressing the ↵ button. If the value selected is different than the value saved previously, the screen shown below will be displayed, and the new value will be saved to permanent memory.
Display address changed
If the fi eld nn is set to the value 0, the terminal will communicate with the pCO 3 controller using the “point-to-point” protocol (not pLAN) and the “I/O Board address: xx” fi eld will not be displayed, as it no longer has meaning.
pCO
3
: assigning the list of private and shared terminals
At this stage, to modify the list of terminals associated with each individual pCO 3 board, proceed as follows:
• enter confi guration mode by pressing the ↓↑↵ buttons, as described in the previous paragraph;
• press the ↵ button until the cursor reaches the fi eld xx (I/O board address) ;
• use the ↓↑ buttons to select the desired address of the pCO 3 board. The values that can be selected refer to the pCO 3 boards that
are effectively on line. If the pLAN network is not operating correctly, or alternatively no pCO 3 board is connected, the fi eld will not
be able to be modifi ed and will only show “—”;
• pressing the ↵ button again displays the following screens in sequence:
Terminal Config
Press ENTER to continue
P12:Adr Priv/Shared
Trm1 02 Sh
Trm2 03 Pr
Trm3 None --OK?NO
• here too the ↵ button moves the cursor from one fi eld to another, and the ↓↑ buttons change the value of the current fi eld.
The fi eld P:xx shows the address of the board selected; in the example shown in fi gure, the address 12 has been selected;
• to exit the confi guration procedure and save the data, select the fi eld “OK ?” and set to Yes, then confi rm by pressing the ↵ button.
The fi elds in the “Adr” column represent the addresses of the terminals associated with the pCO3 board address 12, while the Priv/
Shared column indicates the type of terminal.
Important: the pGD terminals cannot be confi gured as “Sp” (shared printer), as they do not have the printer output.
If the terminal remains inactive (no button pressed) for more than 30 seconds, the confi guration procedure is automatically ended without saving any changes.
NOTES ON USING WINLOAD, BOOT AND BIOS
The most recent version of WinLoad should always be used. Management of the pCO 3 is supported by WinLoad version 3.35, available at http://ksa.carel.com.
From version 3.36, the download speed for the Bios and the application to the pCO 3 has been increased to 115200 bit/s from the standard speed of 28800 bit/s, however this change does not require any new settings by the user.
The pCO 3 BIOS and the BOOT are specifi c fi les, and different from the pCO 1 and pCO 2 BIOS and BOOT fi les. Consequently, these cannot be loaded onto the pCO 3 , and, obviously, the pCO 1 and pCO 2 BOOT and BIOS cannot be loaded onto the pCO 3 .
IMPORTANT WARNINGS
The CAREL product is a state-of-the-art product, whose operation is specifi ed in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
The client (builder, developer or installer of the fi nal equipment) assumes every responsibility and risk relating to the phase of confi guration the product in order to reach the expected results in relation to the specifi c fi nal installation and/or equipment. The lack of such phase of study, which is requested/indicated in the user manual, can cause the fi nal product to malfunction of which CAREL can not be held responsible.
The fi nal client must use the product only in the manner described in the documentation related to the product itself.
The liability of CAREL in relation to its own product is regulated by CAREL’s general contract conditions edited on the website www.carel.
com and/or by specifi c agreements with clients.
+050003290 - 1.4 - 29.09.2006 21 english
Note: ______________________________________________________________________
_____________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
ALLGEMEINE BESCHREIBUNG pCO 3 ist eine elektronische Mikroprozessorsteuerung, deren Hardware- und Softwareausstattung mit der pCO 2 -Produktserie kompatibel ist. Sie wurde von CAREL in Übereinstimmung mit den europäischen RoHS-Normen entwickelt und liefert die ideale Lösung für zahlreiche
Anwendungen in der Klima- und Kältetechnik. Sie gewährleistet extreme Flexibilität und kann entsprechend den Anforderungen des
Kunden personalisiert werden. pCO 3 führt das Steuerprogramm aus und ist mit einem Klemmen-Set für den Anschluss der Stellglieder
(Verdichter, Ventilatoren...) ausgerüstet. Das Programm und die Parameter sind im FLASH-Speicher und im E 2 prom gespeichert, wo sie auch bei Spannungsausfall (ohne Notstrombatterie) erhalten bleiben.
Das Programm kann mit einem PC (28.8 kbps und 115.2 kbps) oder mit dem speziellen Programmierschlüssel geladen werden.
pCO 3 ist für die Einbindung in das lokale pLAN-Netzwerk (pCO Local Area Network) ausgelegt und kann auch an andere pCO 3 sowie an alle pCO sistema-Steuerungen und pGD-Bedienteile angeschlossen werden. Alle pLAN-Steuerungen tauschen Informationen (Digital- oder Analogvariablen nach dem jeweiligen Anwendungsprogramm) mit hoher Übertragungsgeschwindigkeit aus. Für einen effi zienten
Informationsaustausch können bis zu 32 Geräte (pCO-Steuerungen und Bedienteile) vernetzt werden.
Der Anschluss an das serielle Überwachungs-/Fernwartungssystem per CAREL- oder Modbus-Kommunikationsprotokoll über RS485 erfolgt anhand einer seriellen, optionalen Platine.
Für den Anschluss an das Überwachungsgerät mit anderen Standards als RS485 werden zusätzliche optionale Platinen verwendet.
Über die serielle Field bus-Schnittstelle werden mit der optionalen Platine die vor Ort gesteuerten Vorrichtungen (z. B. Ventile, E/O-
Erweiterungen, Ventiltreiber ...) verbunden.
Verfügbare Versionen:
• SMALL, MEDIUM, LARGE, EXTRALARGE N.O. und EXTRALARGE N.C.;
• mit oder ohne Built-in-Bedienteil;
• mit zusätzlichem Flash-Speicher und opto-isoliertem pLAN-Netzwerk;
• mit oder ohne digitale Festkörperrelaisausgänge (SSR).
Anmerkung: Das Anwendungsprogramm kann mit dem Smart Key PCOS00AKY0 in den Flashspeicher (siehe Abb. 6) oder auf einen
PC mittels USB-485-Adapter “CVSTDUTLF0” und Programm “WINLOAD32” (bei CAREL anzufordern) geladen werden.
Spannungsversorgung
Für die Versorgung einer einzigen pCO 3 -Steuerung wird die Verwendung eines Sicherheitstrafos der Klasse II von 50 VA empfohlen.
Die Versorgung der pCO 3 -Steuerung und des Bedienteils (oder mehrerer pCO 3 und Bedienteile) muss von der Versorgung der anderen elektrischen Geräte (Schaltschütze und elektromechanische Komponenten) in der Schalttafel getrennt werden. Im Fall einer
Erdung der Trafo-Sekundärwicklung ist zu überprüfen, dass der Erdleiter mit der Klemme G0 verbunden ist. Dies gilt für alle an pCO 3 angeschlossenen Geräte. Werden mehrere, pLAN-vernetze pCO 3 -Platinen versorgt, sind die Massen G und G0 zu beachten (die Masse
G0 muss für alle Platinen beibehalten werden).
Im Fall der Verwendung des pLAN-Netzwerkes und für weitere Details siehe das pCO3-Benutzerhandbuch von CAREL.
Field Bus-Optionen opto-isoliert 485 tLAN
PCO100FD10
PCO100TLN0
Belimo MPbus PCO100MPB0
Modem PCOS00FD20
CAN hydronic PCOS00HBF0
BMS-Optionen
CANbus PCOS00HBB0
485/Modbus PCOS004850
Modem PCO100MDM0
Ethernet-Karte PCO1000WB0
LonWorks
LonWorks
LonWorks
FTT10
FTT10
Chiller Standard-Profi l
PCO10000F0
PCO10001F0
+050003290 - 1.4 - 29.09.2006 23 deutsch
Steckverbinder
Aufschlüsselungsbeispiel: PCO3CON***, siehe folgende Tabelle für die Beschreibung:
PCO3CON *
0 = Schrauben
1 = Feder
*
S = small
M = medium
L = large
Z = extra large N.O.
C = extra large N.C.
0
TECHNISCHE DATEN
Mechanische Daten
Abmessungen SMALL-Version auf 13 DIN-Modulen, 110 x 227.5 x 60 mm
MEDIUM-, LARGE- und EXTRALARGE-Version auf 18 DIN- Modulen, 110 x 315 x 60 mm
Kunststoffgehäuse
• Montage nach DIN-Norm gemäß DIN 43880 und CEI EN 50022;
• selbstlöschend: V0 (gemäß UL94) und 960 °C (gemäß IEC 695);
• Kriechstromwiderstand: 250 V;
• Farbe: grau RAL7035;
Elektrische Daten
Versorgung (Steuerung mit angeschlossenem Bedienteil 28…36 Vdc +10/-20% und 24 Vac +10/-15% 50…60 Hz;
Klemmleiste max. Leistungsaufnahme P= 15 W (Versorgung Vdc), P= 40 VA (Vac) mit abnehmbaren Steckverbindern (Kontaktstifte/Steckerhülsen), max.
CPU
Speicher (FLASH MEMORY)
Datenspeicher (statischer RAM)
Parameterspeicher
Spannung 250 Vac;
Kabeldurchmesser: min. 0,5 mm 2 - max. 2,5 mm 2
H8S2320, 16 bit, 24 MHz
2+2 MB; in den erweiterten Versionen Zusatzspeicher von 32 MB oder höher
512 kB 16 bit (296 kB Bios; 216 kB Anwendungsprogramm)
13 kB 16 bit (max. Grenzwert: 400.000 Schreibvorgänge pro Speicherplatz) und weitere 32 kB E2prom (für pLAN nicht zugänglich)
Dauer der Arbeitszyklen (mittelkomplexe Anwendungen 0,2 s (typisch)
Uhr mit Batterie serienausstattung
Digitale Eingänge
Typ max. Anzahl opto-isoliert
8: SMALL; 14: MEDIUM und EXTRALARGE N.O und N.C.; 18: LARGE. nach den unten angeführten Kombinationen: opto-isolierte Eingänge zu 24 opto-isolierte Eingänge zu 24 Vac/Vdc Eingänge
SMALL
MEDIUM/EXTRALARGE
LARGE
Vac 50/60 Hz oder 24 Vdc
8
12
14 oder 230 Vac (50/60 Hz) nessuno
2
4 insgesamt
8
14
18
Klassifi kation der
Messleitungen
(CEI EN 61010-1)
Kategorie I (J5, J7, J20) 24 Vac/Vdc
Kategorie III (J8, J19) 230 Vac
WICHTIGER HINWEIS: - 230 Vac 50/60 Hz (10/-15%);
- die beiden 230/24 Vac-Eingänge auf J8 und J12 haben denselben gemeinsamen Pol und werden also beide
mit 24 Vac/Vdc oder 230 Vac versorgt. Grundisolierung zwischen den beiden Eingängen;
- für DC-Eingänge den negativen Pol an die gemeinsame Klemme anschließen.
Anmerkung: Die Kabel der Fühlersignale und digitalen Eingänge soweit wie möglich von den Kabeln der induktiven und
Leistungslasten zur Vermeidung von möglichen elektromagnetischen Störungen trennen.
+050003290 - 1.4 - 29.09.2006 24
Analoge Eingänge
Analoge Umsetzung
Typ
A/D Konverter 10 bit in Built-in-CPU universal: (Eingänge B1, B2, B3, B6, B7, B8) CAREL NTC-Temperaturfühler (-50T90 °C; R/T 10 k Ω bei 25 °C),
NTC HT 0T150 °C, Spannung: 0…1 Vdc, 0…5 V ratiometrisch oder 0…10 Vdc, Strom:
0…20 mA oder 4…20 mA, über Software wählbar. Eingangswiderstand in 0…20 mA= 100 Ω passiv: (Eingänge B4, B5, B9, B10) CAREL NTC-Temperaturfühler (siehe universale Eingänge), max. Anzahl
Zeitkonstante pro Eingang
Präzision
Klassifi kation der Messleitungen
PT1000 (-100T200 °C; R/T 1000 Ω bei 0°C) oder potenzialfreier digitaler Eingang (5 mA), über Software wählbar;
5: SMALL; 8: MEDIUM und EXTRALARGE N.O.; 10: LARGE und EXTRALARGE N.C.
0,5 s
± 0,3 % des Endwertes
Kategorie I
(CEI EN 61010-1)
HINWEIS: Für die Versorgung eventueller aktiver Fühler können die 21 Vdc der Klemme +Vdc (J2) verwendet werden; die max. lieferbare
Stromstärke beträgt 150 mA p und ist thermisch gegen Kurzschlüsse geschützt. Für die Versorgung der ratiometrischen 0…5 Vdc-Fühler werden die
+5VREF (Imax: 60 mA) auf der Klemme J24 verwendet.
Analoge Ausgänge
Typ max. Anzahl
Versorgung extern
Aufl ösung max. Belastung
Genauigkeit
0…10 Vdc opto-isoliert
4: SMALL, MEDIUM und EXTRALARGE N.O./N.C.; 6: LARGE
24 Vac/Vdc
8 bit
1 k Ω (10 mA)
± 2 % des Endwertes auf den Ausgängen: Y1, Y2, Y3 und Y4
-2%/+5% des Endwertes auf: Y5 und Y6
Digitale Ausgänge
Typ max. Anzahl
Relais
8: SMALL; 13: MEDIUM; 18: LARGE; 27: EXTRALARGE N.C.; 29: EXTRALARGE N.O.
Für die Anschlüsse siehe Abb. 3 bis 5 (NO*, NC* und C*). Die Ausgänge mit Wechselkontakt werden getrennt gehalten (natürlich ohne gemeinsam verwendete Pole zwischen verschiedenen Ausgängen). Die Gruppen mit 2 bis 5 Ausgängen sehen 2 „gemeinsame“ Pole für eine einfache Montage vor. Achtung: Der Strom der gemeinsamen Klemmen darf den Nennstrom einer einzelnen Klemme, d.h. 8A nicht überschreiten.
Isolierungsabstand Die Ausgänge können in Gruppen gegliedert werden. Zwischen den einzelnen Gruppen (Zelle-Zelle der Tabelle) besteht eine doppelte Isolierung.
Anmerkung: Die Relais einer selben Gruppe mit Grundisolierung müssen mit derselben Versorgungsspannung (24 oder
230 Vac) versorgt werden.
Gruppenkomposition
Version
SMALL
Relais
Relais mit gleicher Isolierung
1…7 8 -
Realais A Realais A
-
MEDIUM
Relais
LARGE
Relais
EXTRALARGE N.O.
Relais
EXTRALARGE N.C.
Relais
1…7
Realais A
1…7
Realais A
1…7
Realais A
1…7
Realais A
8
Realais A
8
Realais A
8
Realais A
8
Realais A
9…13
Realais A
-
9…13 14…18 -
Realais A Realais A
-
9…13 14…16 17…20 21…24 25…29
Realais A Realais B Realais B Realais B Realais B
9…13 14…16 17…20 21…24 25…27
Realais A Realais C Realais C Realais C Realais C
Wechselkontakte
N.B.: Die Relais jeder einzelnen Tabellenzelle besitzen untereinander eine Grundisolierung, zwischen den Zellengruppen besteht jedoch eine Doppelisolierung.
1: SMALL (Relais 8); 3: MEDIUM und EXTRALARGE N.O./N.C. (Relais 8, 12 und 13); 5: LARGE (Relais 8, 12, 13, 14 und
15)
Umschaltbare Leistung Hinweis: Die Relaisausgänge haben in Abhängigkeit des pCO3-Modells jeweils andere Merkmale pCO 3
Relais A Relaistyp: SPDT, 2000 VA, 250 Vac, 8 A ohmsch pCO 3 -Zulassungen: UL873: 2,5 A ohmsch, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 Zyklen)
EN 60730-1: 2 A ohmsch, 2 A induktiv, cos ϕ = 0,6, 2(2) A (100000 Zyklen)
Relais B Relaistyp: SPDT, 1250 VA, 250 Vac, 5 A ohmsch pCO 3 -Zulassungen: UL873: 1 A ohmsch, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 Zyklen)
EN 60730-1: 1 A ohmsch, 1 A induktiv, cos ϕ = 0,6, 1(1) A (100000 Zyklen)
Relais C Relaistyp: SPDT, 1250 VA, 250 Vac, 5 A ohmsch pCO 3 -Zulassungen: UL873: 1 A ohmsch, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 Zyklen)
EN 60730-1: 1 A ohmsch, 1 A induktiv, cos ϕ = 0,6, 1(1) A (100000 Zyklen)
SSR-Ausgänge 1: SMALL (Ausgang 7); 2: MEDIUM und EXTRALARGE N.O./N.C. (Ausgänge 7 und 12); 3: LARGE (Ausgänge 7,
12 und 14); Arbeitsspannung: 24 Vac/Vdc; max. Leistung: 10 W
+050003290 - 1.4 - 29.09.2006 25 deutsch
AWG und Kabeldurchmesser
AWG
20
15
14
Durchmesser (mm
0,5
1,5
2,5
2 ) Strom
2
6
8
pLAN-Netzwerk/Bedienteil-Anschluss
Typ
Übertragungsgeschwindigkeit
Bedienteil-Steckverbinder
Steckverbinder für pLAN/graphisches Bedienteil/aria-Bedienteil asynchron half duplex RS485
62,5 Kbps oder 115,2 Kbps, über Software wählbar
6-drahtiger Telefonstecker (J10) abnehmbarer 3-drahtiger Steckverbinder (J11)
Der max. Abstand zwischen pCO und dem Benutzerbedienteil ist in der folgenden Tabelle enthalten.
Kabeltyp
Telefonkabel
Versorgungsabstand
50 m
Versorgung
über pCO (150 mA) abgeschirmtes AWG24-Kabel 200 m abgeschirmtes AWG20/22-Kabel 500 m
über pCO (150 mA) separate Versorgung über TCONN6J000
Der max. Abstand zwischen zwei pCO3 mit abgeschirmtem AWG20/22-Kabel beträgt 500 m.
Sonstige Daten:
• An J10 können max. ein Bedienteil (pCOT, pCOI, pGD0, pGD1) oder zwei Bedienteile ohne Displayhinterleuchtung angeschlossen
werden. Eine pCO 3 -Version besitzt einen opto-isolierten Anschluss an das pLAN-Netzwerk.
• Das graphische Bedienteil und das aria-Bedienteil müssen immer getrennt versorgt werden.
• Die 21Vdc-Spannung auf der Klemme +Vterm (J24) kann für die Versorgung eines externen Bedienteils mit max. Aufnahme von
2 W verwendet werden. Es kann nur ein Bedienteil (z.B. PLD oder aria) zusätzlich zu dem mit der Klemme J10 verbundenen
Altre caratteristiche
Lagerungsbedingungen
Betriebsbedingungen
-40T70 °C, 90% rF nicht kondensierend
-25T70 °C, 90% rF nicht kondensierend
Schutzart IP20, IP40 nur Frontteil
Umweltbelastung normal
Schutzklasse gegen Stromschläge in Geräte der Klasse I und/oder II zu integrieren
PTI der Isoliermaterialien
Isolation gegen elektrische Beanspruchung
Art der Schaltung
Ausschaltung oder Mikrounterbrechung
Wärme- und Brandschutzkategorie
250 V lang
1C
Mikrounterbrechung
Kategorie D (UL94 - V0)
Schutz gegen Überspannung
Alterung (Betriebsstunden)
Anzahl der automatischen Arbeitszyklen
Softwareklasse und -struktur
Schutz gegen Stoßspannung (CEI EN 61000-4-5)
Das Gerät ist nicht als Handgerät gedacht
Kategorie 1
80.000
100.000 (EN 60730-1); 30.000 (UL 873)
Klasse A
Kategorie III
WICHTIGER HINWEIS
• Für Anwendungen, die starken Vibrationen ausgesetzt sind (1,5 mm pk-pk 10/55 Hz), empfi ehlt sich die Festigung der pCO 3 -Kabel
mit Kabelschellen im Abstand von ca. 3 cm von den Steckverbindern;
• Wird das Produkt in einer industriellen Anwendung installiert (Anwendung der EN 61000-6-2-Normen), muss die Länge der
Anschlüsse unter 30 m betragen;
• Die Installation muss nach den im Verwendungsland geltenden Bestimmungen und Vorschriften erfolgen;
• Aus Sicherheitsgründen muss das Gerät in der Schalttafel montiert sein, sodass die einzigen zugänglichen Teile das Display und die
• Alle Niedrigstspannungsanschlüsse (analoge und digitale 24 Vac/Vdc-Eingänge, analoge Ausgänge, serielle Bus-Anschlüsse,
Versorgung) müssen eine verstärkte oder Doppelisolierung aufweisen;
• Bei Betriebsstörungen darf das Gerät nicht repariert werden: bitte den CAREL-Service kontaktieren;
• Bei Privatanwendungen muss das Verbindungskabel zwischen pCO 3 und dem Bedienteil abgeschirmt sein.
+050003290 - 1.4 - 29.09.2006 26
ABMESSUNGEN
Abmessungen pCO3 MEDIUM, LARGE, EXTRALARGE N.O. und N.C.
Abmessungen pCO 3 SMALL
315
227,5
44
45 110
60 Abb. 2
44
45 110
60 Abb. 1
•
•
•
PRODUKTZERTIFIZIERUNG
Norm CEI EN 50155: “Anwendungen im Eisenbahn-, Straßenbahn-, Oberleitungsomnibus- und U-Bahn- Bereich. Elektronische
Anlagen für rollendes Material”;
Normen UL 873 und C22.2 No.24-93: “Temperature-indicating and regulating equipment”;
CE-Verordnung 37/2005 vom 12. Januar 2005; ist die Steuerung mit dem Standard-NTC-Fühler von CAREL ausgerüstet, entspricht sie der Norm EN13485 über die “Thermometer zur Lufttemperaturmessung für Anwendungen in Konservierungs- und
Verteilungsgeräten von gekühlten und tiefgekühlten Lebensmitteln sowie Speiseeis”.
Entsorgung des Produktes
Das Gerät (oder Produkt) muss im Mülltrennungsverfahren in Übereinstimmung mit den örtlichen Entsorgungsnormen entsorgt werden.
+050003290 - 1.4 - 29.09.2006 27 deutsch
GERÄTEKOMPONENTEN
4
7
1
3
15
4
5
2
14
6
7
8
G
G0
+V term
GND
+5 V
REF
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
ID13H
ID13
IDC13
ID14
ID14H
ID10
ID11
ID12
IDC9
B6
B7
B8
GND
ID9
Y3
Y4
ID1
Y1
Y2
VG
VG0
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
B9
BC9
B10
BC10
ID17
ID18
IDC17
8
6
5
7
+050003290 - 1.4 - 29.09.2006 28
11
12
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
E-
E+
GND
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
C7
NO7
C7
NO8
C8
NC8
C4
NO4
NO5
NO6
C4
C1
NO1
NO2
NO3
C1
Rx-/Tx-
Rx+/Tx+
GND
9
10
13
16
17
11
Abb. 3
Version EXTRALARGE N.O.
C21
NO21
NO22
NO23
NO24
C21
C25
NO25
NO26
NO27
NO28
NO29
C25
11
Version EXTRALARGE N.C.
12
C17
NO17
NO18
NO19
NO20
C17
E-
E+
GND
C14
NO14
NO15
NO16
C14
B9
B10
BC9
C25
NC25
NC26
NC27
C25
C21
NC21
NC22
NC23
NC24
C21
11
5
12
C17
NC17
NC18
NC19
NC20
C17
E-
E+
GND
C14
NC14
NC15
NC16
C14
Legende (Abb. 3…5)
1.
Versorgungsstecker [G (+), G0 (-)];
2.
gelbe Versorgungs-LED und 3 LEDs für das lokale pLAN-Netzwerk;
3.
zusätzliche Versorgung für Bedienteil und ratiometrische 0…5 V-Fühler;
4.
universale analoge NTC-, 0…1 V-, 0…5 V, ratiometrische 0…10 V-, 0…20 mA-, 4…20 mA-
Eingänge;
5.
passive analoge NTC-, PT1000-, EIN/AUS-Eingänge;
6.
analoge 0…10 V-Ausgänge;
7.
digitale 24 Vac/Vdc-Eingänge;
8.
digitale 230 Vac- oder 24 Vac/Vdc-Eingänge;
9.
Steckverbinder für das synoptische Display
(externe Tafel mit direkten Anzeigen);
10.
Steckverbinder für alle Standard-Bedienteile der pCO-Serie und für das Download des
Anwendungsprogramms;
11.
digitale Relaisausgänge;
12.
Steckverbindung für den Anschluss an die E/A-
13.
Erweiterungsplatine;
Steckverbinder für pLAN;
14.
Klappe für das Einstecken der optionalen seriellen
Überwachungsgerät-Karte;
15.
Klappe für das Einstecken der optionalen Field-
Karte;
16.
Klappe für das Einstecken der optionalen Service-
Karte;
17.
Built-in-Bedienteil (LCD, Tasten und LEDs).
+050003290 - 1.4 - 29.09.2006 29 deutsch
ANMERKUNGEN FÜR DEN INSTALLATEUR: VERGLEICH ZWISCHEN PCO 3 UND PCO 2
• Nicht alle Steuerungen der pCO3-Serie sind mit dem Steckverbinder für den Programmierschlüssel PCO201KEY0 ausgerüstet. Für
die Programmierung der Steuerung muss der neue Smart Key (PCOS00AKY0) (verfügbar seit September 2005) verwendet werden.
Ansonsten ist die WinLoad-Version 3.35 oder höher zu verwenden.
Abb. 6
Das Anwendungsprogramm kann nicht vom Smart Key aus ausgeführt werden;
• Im Unterschied zu pCO 2 ist zwischen J1 und J2 keine Sicherung vorhanden. Alle pCO 3 -Steuerungen besitzen einen internen
Thermoschutz auf der Spannungsversorgung. Die Verwendung einer externen Sicherung ist also nicht erforderlich;
• Eine zusätzliche Klemme J24 liefert (anstelle der Sicherung) die Versorgungsspannung für die ratiometrischen Fühler (+5 VREF) und
eine Gleichspannung von 20V für die Versorgung eines zweiten Bedienteils wie aria (TAT***) alternativ zum Standard-Bedienteil;
• Die LEDs in der Nähe der Dipschalter für die pLAN-Adressierung wurden zwischen die Steckverbinder J3 und J4 versetzt;
• Die rote LED für die Versorgungsüberlast der Fühler ist nicht mehr vorhanden.
pCO 3 -Simulator:
Soll die pCO3-Steuerung mit einem Simulator getestet werden, muss berücksichtigt werden, dass der pCO2-Simulator nicht anstelle des pCO3-Simulators verwendet werden kann. Für die Verfügbarkeit des pCO3-Simulators bitte CAREL kontaktieren.
Adressierung der Steuerung und des Bedienteils
Adressierung der Steuerung
Die pCO3-Steuerung ist NICHT mit Dipschaltern für die Einstellung der pLAN-Adresse ausgerüstet. Die Adresse muss über ein
Softwareverfahren wie für pCO 1/XS eingestellt werden.
Verfahren:
1. pCO 3 von der Spannung abtrennen;
2. ein Standard-Bedienteil von CAREL mit der Adresse 0 konfi gurieren (nicht nötig, wenn ein Built-in-Bedienteil der pCO 3 -Steuerung
verwendet wird). Für diesen Schritt siehe nächsten Absatz;
3. das Bedienteil an pCO 3 anschließen;
4. pCO 3 von eventuellen anderen pLAN-vernetzten Geräten abtrennen (Bedienteil J11);
5. pCO 3 mit Spannung versorgen und gleichzeitig die UP- und ALARM-Tasten drücken. Diese Tasten-Kombination gilt auch für das
Built-in-Bedienteil. Für die PCOT-Bedienteile hingegen die Kombination der Tasten menu und verwenden.
6. nach einigen Sekunden erscheint das Fenster:
PLAN ADDRESS: 0
UP: INCREASE
DOWN: DECREASE
ENTER: SAVE & EXIT
7. die Adresse kann mit den UP- und DOWN-Tasten geändert werden. Mit ENTER bestätigen.
8. die pLAN-Adresse des Bedienteils einstellen und das pLAN-Netzwerk konfi gurieren.
Adressierung des Bedienteils pCOI/pCOT-Bedienteil
Die Adresse des Bedienteils wird anhand der DIPSCHALTER auf der Rückseite des Bedienteils eingestellt.
pGD0/1/2/3-Bedienteil
Die werkseingestellte Adresse ist 32.
Die Adresse des Bedienteils kann nur nach der Versorgung des Bedienteils über den Telefonstecker konfi guriert werden.
Für den Zugriff auf den Konfi gurationsmodus in allen Versionen die Tasten ↓↑↵ für mindestens 5 Sekunden gleichzeitig drücken (auch bei bereits eingeschaltetem Bedienteil); es erscheint die Maske der folgenden Abbildung mit dem blinkenden Cursor links oben:
Display address setting.........:nn
I/O Board address:xx
• Zur Änderung der Bedienteiladresse (display address settino) die Taste ↵ : einmal drücken: der Cursor verlagert sich auf das Feld der Adresse (nn).
+050003290 - 1.4 - 29.09.2006 30
• mit den Tasten ↓↑ den gewünschten Wert wählen und mit der Taste …. bestätigen. Ist der gewählte Wert ein anderer als der vorher
gespeicherte, erscheint die Maske der folgenden Abbildung; der neue Wert wird im Permanentspeicher des Displays gespeichert.
Display address changed
Wird das Feld nn auf den Wert 0 eingestellt, kommuniziert das Bedienteil mit der pCO3-Steuerung über das „Punkt-zu-Punkt“-Protokoll
(nicht pLAN); das Feld “I/O Board address: xx” wird ausgeblendet, weil es keine Bedeutung mehr hat.
pCO
3
: Zuweisung der Liste der privaten und gemeinsamen Bedienteile
Soll die Liste der jeder pCO3-Platine zugewiesenen Bedienteile geändert werden, siehe folgendes Verfahren:
• den Konfi gurationsmodus mit den Tasten ↓↑↵ wie im vorigen Absatz beschrieben betreten;
• die Taste ↵ drücken, bis sich der Cursor auf das Feld xx verlagert (I/O board address);
• mit den Tasten ↓↑ die Adresse der gewünschten pCO3-Platine wählen; es können nur die Werte der effektiv verbundenen
pCO 3 -Platinen eingestellt werden. Arbeitet das pLAN-Netzwerk nicht korrekt oder ist keine pCO3-Platine vorhanden, kann das Feld
nicht geändert werden; es wird nur “—” angezeigt;
• drückt man die Taste ↵ erneut, werden die folgenden Masken angezeigt:
Terminal Config
Press ENTER to continue
P12:Adr Priv/Shared
Trm1 02 Sh
Trm2 03 Pr
Trm3 None --OK?NO
• auch hier verlagert die Taste ↵ den Cursor von einem Feld zur anderen, und die Tasten ↓↑ ändern den Wert des aktuellen Feldes.
Das Feld P:xx zeigt die Adresse der gewählten Platine an; im abgebildeten Beispiel wurde die Zahl 12 gewählt;
• zum Verlassen des Konfi gurationsverfahrens und zum Speichern der Daten das Feld “OK ?” wählen, Yes einstellen und mit der Taste
↵ bestätigen.
Die Felder der Spalte “Adr” stellen die Adressen der Bedienteile dar, die der pCO 3 -Platine mit der Adresse 12 zugewiesen wurden; die
Spalte Priv/Shared gibt die Art des Bedienteils an.
Achtung: Die pGD-Bedienteile können nicht als “Sp” (shared printer) konfi guriert werden, da sie keinen Druckeranschluss besitzen.
Bleibt das Bedienteil für länger als 30 Sekunden inaktiv (kein Tastendruck), wird das Konfi gurationsverfahren automatisch beendet, ohne die angebrachten Änderungen zu speichern.
ANMERKUNGEN ZUR VERWENDUNG VON WINLOAD, BOOT UND BIOS
Es sollte immer die neueste WinLoad-Version verwendet werden. pCO 3 unterstützt die WinLoad-Version 3.35, die auf der Webseite http://ksa.carel.com heruntergeladen werden kann.
Ab der Version 3.36 erhöht sich die Downloadgeschwindigkeit des Bios und Anwendungsprogramms für pCO 3 auf 115200 bit/s anstatt auf die Standardgeschwindigkeit von 28800 bit/s; diese Änderung bringt für den Benutzer jedoch keine neuen Einstellungen mit sich.
Das pCP3-BIOS und BOOT sind spezifi sche Dateien, die sich vom pCO 1 - und pCO 2 -BIOS und BOOT unterscheiden. Somit können diese nicht auf pCO 3 geladen werden, und umgekehrt auch nicht die pCO 3 -BOOT- und BIOS-Dateien auf pCO 1 und pCO 2 .
WICHTIGE HINWEISE KURZFASSUNG
Das CAREL Produkt ist ein Produkt nach dem neuesten Stand der Technik, dessen Betriebsanleitungen in den dem Produkt beiliegenden technischen Spezifi kationen enthalten sind oder - auch vor dem Kauf - von der Internetseite www.carel.com heruntergeladen werden können.
Der Kunde (Hersteller, Planer oder Installateur der Endausstattung) übernimmt jede Haftung und Risiken in Bezug auf die
Produktkonfi guration zur Erzielung der bei der Installation und/oder spezifi schen Endausstattung vorgesehenen Resultate.
Die Unterlassung dieser Phase, die im Benutzerhandbuch verlangt/angegeben ist, kann zu Funktionsstörungen der Endprodukte führen, für welche CAREL nicht verantwortlich gemacht werden kann.
Der Endkunde darf das Produkt nur auf die in den Produktspezifi kationen beschriebenen Weisen verwenden.
Die Haftung CARELS für die eigenen Produkte ist von den allgemeinen CAREL Vertragsbedingungen (siehe Internetseite www.carel.com) und/oder durch spezifi sche Vereinbarungen mit den Kunden geregelt.
+050003290 - 1.4 - 29.09.2006 31 deutsch
Note: ______________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
CARACTÉRISTIQUES TECHNIQUES pCO 3 est un contrôleur électronique à microprocesseur compatible tant au niveau de l’équipement informatique et du logiciel qu’avec la famille pCO 2 . Développé par CAREL dans le respect de la norme européenne, pour offrir de nombreuses applications dans le secteur du conditionnement de l’air et de la réfrigération. Il garantit la polyvalence d’applications la plus absolue en permettant de réaliser des produits spécifi ques sur demande du client. pCO 3 est destiné à l’exécution du programme de réglage et il est doté du groupe de bornes nécessaires à la connexion vers les dispositifs (compresseurs, ventilateurs..), le programme et les paramètres sont mémorisés sur FLASH-
MEMORY et sur E2prom, en permettant leur maintien même en cas de manque d’alimentation (sans qu’une batterie de maintien ne soit nécessaire).
Le téléchargement du programme peut être exécuté via PC (28.8 kbps et 115.2 kbps) ou avec une clef de programmation prévus à cet effet. pCO3 permet la connexion au réseau local pLAN (pCO Local Area Network) et peut être connecté à d’autres pCO 3 ainsi qu’à tous les autres contrôleurs du pCO sistema et à tous les terminaux de la famille pGD. Chaque contrôleur en réseau pLAN peut échanger des informations (toute variable, numérique ou analogique, selon le programme d’application utilisé) avec une vitesse de transmission élevée.
Il est possible de connecter jusqu’à 32 unités, entre contrôleurs pCO et terminaux, afi n de partager les informations de manière effi cace.
La connexion vers la ligne sérielle de supervision/téléassistance avec le protocole de communication CAREL ou Modbus™, selon le standard RS485, est réalisée en introduisant une carte sérielle optionnelle sur le pCO 3 .
La connexion au superviseur avec des standards différents de RS485 est possible par l’intermédiaire d’autres cartes optionnelles. Et enfi n la communication sérielle fi eld bus, par carte optionnelle, offre la connexion vers des dispositifs contrôlés de champ (par exemple: vanne
à détente E/S pCOe, gestionnaire pour vanne électronique..).
Versions disponibles:
• SMALL, MEDIUM, LARGE, EXTRALARGE N.O. et EXTRALARGE N.F.;
• avec ou sans terminal incorporé;
• avec une mémoire fl ash supplémentaire et pLAN optoisolée;
• avec ou sans sorties numériques relais à l’état solide (SSR).
Remarque: le programme d’application peut être téléchargé de la mémoire fl ash via la smart key PCOS00AKY0, voir Fig. 6; ou un PC via un adaptateur USB-485 “CVSTDUTLF0” et le programme “WINLOAD32” à demander à CAREL.
Alimentation
Pour l’installation, nous conseillons d’utiliser un transformateur de sécurité en Classe II de 50 VA, pour l’alimentation d’un seul contrôleur pCO 3 . Il est recommandé de séparer l’alimentation du contrôle pCO 3 et le terminal (ou plusieurs pCO 3 et terminaux) de l’alimentation du reste des dispositifs électriques (compteurs et autres composants électromécaniques) à l’intérieur du tableau
électrique. Si le secondaire du transformateur est positionné au sol, vérifi er que le conducteur de terre est bien connecté à la borne
G0. Il en est de même pour tous les dispositifs connectés au pCO 3 . Si l’on alimente plusieurs cartes pCO 3 connectées au réseau pLAN, s’assurer que soient respectées les références G et G0O (la référence G0 doit être maintenue pour toutes les cartes).
En cas d’utilisation du réseau pLAN pour toutes spécifi cations et informations supplémentaires demander le manuel pCO 3 CAREL.
Options Field Bus
485 optoisolée tLAN
MPbus Belimo modem
CAN hydronique
PCO100FD10
PCO100TLN0
PCO100MPB0
PCOS00FD20
PCOS00HBF0
Options BMS
CANbus
485/Modbus modem carte Ethernet
LonWorks
LonWorks
LonWorks
PCOS00HBB0
PCOS004850
PCO100MDM0
PCO1000WB0
FTT10
FTT10 profi l chiller standard
PCO10000F0
PCO10001F0
+050003290 - 1.4 - 29.09.2006 33 français
Connecteurs
Exemple de codage : PCO3CON***, voir tableau suivant pour la description:
PCO3CON *
0 = à vis
1 = à ressort
*
S = small
M = medium
L = large
Z = extra large N.O.
C = extra large N.C.
0
CARACTÉRISTIQUES TECHNIQUES
Caractéristiques mécaniques
dimensions montage version SMALL pouvant être insérée sur 13 modules DIN, 110 x 227.5 x 60 mm version MEDIUM, LARGE et EXTRALARGE pouvant être insérée sur 18 modules DIN, 110 x 315 x 60 mm sur rail DIN
Boîtier en plastique
• accrochable sur rail DIN selon les normes DIN 43880 et CEI EN 50022;
• autoextinctible: V0 (selon UL94) et 960 °C (selon IEC 695);
• essai bille: 125 °C;
• résistant aux courants de cheminement: ≥ 250 V;
Caractéristiques électriques
Alimentation (contrôleur avec terminal connecté) 28…36 Vcc +10/-20% e 24 Vca +10/-15% 50…60 Hz; bornier
CPU mémoire (sur FLASH MEMORY) mémoire données (RAM statique) mémoire données paramètres absorption maximale P= 15 W (alimentation Vcc), P= 40 VA (Vac) avec connecteurs mâle/femelle extractibles, tension max 250 Vac; sec. câble: min. 0,5 mm 2 - max 2,5 mm 2
H8S2320, 16 bit, 24 MHz
2+2 MB; dans les versions étendues une mémoire supplémentaire de 32 MB ou sup
512 kB organisée à 16 bits (296 kB Bios; 216 kB d’application)
13 kB organisée à 16 bits (limite max: 400.000 écritures pour emplacement de mémoire) et 32 kB de E2prom supplémentaires(non visibles du pLAN) durée cycle utile (applications moyennes complexité) 0,2 s (typique) horloge avec batterie de série
Entrées numériques
type optoisolées nombre maximal 8: SMALL; 14: MEDIUM et EXTRALARGE N.O e N.C.; 18: LARGE. Selon les combinaisons mentionnées ci-après:
N. ent. Optoisolées à 24 Vac N. ent.optoisolées à 24 Vac/Vdc ou total
SMALL
MEDIUM/EXTRALARGE
LARGE
50/60 Hz ou 24 Vdc
8
12
14
230 Vac (50/60 Hz) nessuno
2
4 entréesi
8
14
18 classifi cation des circuits de mesure
(CEI EN 61010-1)
Catégorie I (J5, J7, J20) 24 Vac/Vdc
Catégorie III (J8, J19) 230 Vac
AVERTISSEMENT: - 230 Vac 50/60 Hz (10/-15%);
- les deux entrées à 230/24 Vca présentes sur J8 et J12, ont le même pôle commun, elles seront donc toutes deux
à 24 Vca/Vcc ou 230 Vca. L’isolation entre les deux entrées est principale;
- en cas d’entrées en continue (Vcc) connecter le pôle négatif à la borne commune.
Remarque: séparer au maximum les câbles des signaux des sondes et des entrées numériques des câbles relatifs aux charges inductives et de puissance pour éviter tous brouillages électromagnétiques possibles.
+050003290 - 1.4 - 29.09.2006 34
Entrées analogiques
Conversion analogique type
A/D convertisseur à 10 bits UC incorporée universel: (entrées B1, B2, B3, B6, B7, B8) détecteur de température NTC CAREL (-50T90 °C; R/T 10 k Ω à 25
°C), NTC HT 0T150 °C, tension: 0…1 Vcc, 0…5 V ratiométriques ou 0…10 Vcc, courant:
0…20 mA o 4…20 mA, sélectionnables via logiciel. Résistance d’entrées en 0…20 mA= 100 Ω passif: (entrées B4, B5, B9, B10) détecteur de temp. NTC CAREL (voir type universel), nombre maximal
Constante de temps pour chaque entrée
Précision
Classifi cation des circuits de
PT1000 (-100T200 °C; R/T 1000 Ω à 0°C) ou entrée numérique sans tension (5 mA); sélectionnables via logiciel
5: SMALL; 8: MEDIUM e EXTRALARGE N.O.; 10: LARGE e EXTRALARGE N.C.
0,5 s
± 0,3 % du fond d’échelle
Catégorie I mesure(CEI EN 61010-1)
AVERITSSEMENT: pour l’alimentation de sondes actives éventuelles, il est possible d’utiliser les 21 Vdc disponibles sur la borne +Vdc (J2), le courant maximal pouvant être fourni est de 150 mA protégé thermiquement contre les courts-circuits. Pour l’alimentation des sondes ratiométriques 0…5 V on utilise les +5VREF (max: 60 mA) présents dans la borne J24.
Sorties analogiques
type nombre maximal alimentation résolution charge maximale précision
0…10 Vdc optoisolées
4: SMALL, MEDIUM e EXTRALARGE N.O./N.C.; 6: LARGE externe 24 Vac/Vdc
8 bits
1 k Ω (10 mA)
± 2 % du plein d’échelle des sorties: Y1, Y2, Y3 e Y4
-2%/+5% du plein d’échelle sur: Y5 et Y6
Sorties numériques
type nombre maximal relais
8: SMALL; 13: MEDIUM; 18: LARGE; 27: EXTRALARGE N.C.; 29: EXTRALARGE N.O.
Pour les connexions faire référence aux Fig. 3…5 (référence NO*, NF* et C*). Remarquer la présence de sorties avec contact en échange tenues séparées (à savoir sans pôles partagés entre sorties distinctes). Les groupes de 2 à 5 sorties prévoient 2 pôles “communs” pour un assemblage facile.
Prêter attention au courant circulant dans les bornes communes car il ne doit pas dépasser le courant nominal d’une seule borne, soit 8A .
Distance isolation
Composition groupes les sorties peuvent être réparties en groupes. Entre groupe et groupe (cellule-cellule du tableau) il y a un double isolement.
Remarque: les relais appartenant à un même groupe doivent être soumis à la même tension d’alimentation (24 ou 230 Vac).
version
SMALL
Relais de type
MEDIUM
Relais de type
LARGE
Relais de type
EXTRALARGE N.O.
Relais de type
EXTRALARGE N.C.
Relais de type relais à isolation égale
1…7 8 type A type A
-
1…7 type A
1…7 type A
1…7 type A
1…7 type A
8 type A
8 type A
8 type A
8 type A
-
9…13 type A
9…13 14…18 type A type A
-
-
9…13 14…16 17…20 21…24 25…29 type A type B type B type B type B
9…13 14…16 17…20 21…24 25…27 type A type C type C type C type C
Remarque: Les relais dans les singles chambres du tableau sont pourvus d’isolement principale, tandis qu’entre les groupes de chambres ils sont pourvus d’isolement double.
1: SMALL (relais 8); 3: MEDIUM e EXTRALARGE N.O./N.C. (relais 8, 12 e 13); 5: LARGE (relais 8, 12, 13, 14 e 15) Contact en
échange
Puissance commutable
Sorties SSR avertissement: les sorties relais ont des caractéristiques différentes selon le modèle de pCO 3 relais de type relais: SPDT, 2000 VA, 250 Vca, 8 A résistifs type A relais de type B homologations pCO 3 : UL873 : 2,5 A résistifs, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 cycles)
EN 60730-1 : 2 A résistifs, 2 A inductifs, cos ϕ = 0,6, 2(2) A (100000 cycles) type relais SPDT, 1250 VA, 250 Vca, 5 A résistifs homologations pCO 3 : UL873 : 1 A résistifs, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles) relais de type C
EN 60730-1 : 1 A résistifs, 1 A inductifs, cos ϕ = 0,6, 1(1) A (100000 cycles) type relais: SPDT, 1250 VA, 250 Vca, 5 A résistifs homologations pCO 3 : UL873 : 1 A résistifs, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1 : 1 A résistifs, 1 A inductifs, cos ϕ = 0,6, 1(1) A (100000 cycles)
1: SMALL (uscita 7); 2: MEDIUM et EXTRALARGE N.O./N.C. (sorties 7 e 12); 3: LARGE (sorties 7, 12 e 14)
Tension de travail : 24 Vca/Vxc; puissance maximale: 10 W
+050003290 - 1.4 - 29.09.2006 35 français
Correspondance AWG et section câble
AWG
20
15
14
Section (mm
0,5
1,5
2,5
2 ) Courant
2
6
8
Connexion réseau pLAN/terminal utilisateur
type vitesse de transmission asynchrone half duplex RS485
62,5 Kbps ou 115,2 Kbps selectionnables via logiciel connecteur pour terminal téléphonique à 6 voies (J10) connecteur réseau pLAN/terminal graphique/terminal air connecteur extractible 3 voies (J11)
La distance maximale entre pCO et terminal utilisateur est reportée dans le tableau suivant.
type câble téléphonique distance alimentation
50 m alimentation prélevée de pCO (150 mA) câble blindé AWG24 câble blindé AWG20/22
200 m
500 m prélevée de pCO (150 mA) alimentation séparée via TCONN6J000
La distance maximale entre deux pCO 3 avec câble blindé AWG20/22 est égale à 500 m.
Remarque:
• sur J10 est admise la connexion d’un terminal au maximum (pCOT, pCOI, pGD0, pGD1) ou de deux terminaux mais sans
l’utilisation du rétro-éclairage pour l’affi cheur. Il existe une version de pCO3 où la connexion au réseau pLAN est de type optoisolé.
• terminal graphique et terminal air doivent toujours être alimentés avec une alimentation séparée.
• La tension de 21Vcc présente sur la borne +Vterm (J24) est utilisable pour alimenter un terminal externe avec une absorption
maximale de 2W. La connexion à un seul terminal est admise (par exemple terminal PLD ou terminal air) en plus de celui
connecté sur la borne J10.
Autres caractéristiques
Conditions de stockage
Conditions de fonctionnement degré de protection pollution environnementale classe selon la protection contre les chocs électriques
PTI des matériaux pour isolation période des sollicitations électriques des parties isolantes type actions type déconnexion ou micro-interruption catégorie de résistance à la chaleur et au feu
-40T70 °C, 90% HR non condensante
-25T70 °C, 90% HR non condensante
IP20, IP40 uniquement sur le bandeau frontal normale
à intégrer sur des appareils de Classe I et/ou II
250 V longue
1C micro-interruption catégorie D (UL94 - V0) immunité contre les surtensions catégorie 1 caractéristiques de vieillissement (heures de fonctionnement) 80.000
n° cycles de manœuvre opérations automatiques classe et structure du logiciel
100.000 (EN 60730-1); 30.000 (UL 873)
Classe A catégorie d’immunité à l’onde de choc (CEI EN 61000-4-5) Categoria III
Le dispositif n’est pas destiné à être tenu en main
AVERTISSEMENTS
• Pour des applications sujettes à de fortes vibrations (1,5 mm pk-pk 10/55 Hz) nous conseillons de fi xer à l’aide de bandes les câbles
connectés au pCO 3 à environ 3 cm de distance des connecteurs;
• si le produit est installé dans un milieu industriel (application de la norme EN 61000-6-2) la longueur des connexions doit être
inférieure à 30 m;
• l’installation doit être exécutée selon les normes et les lois en vigueur dans le pays d’utilisation de l’appareil;
• pour des motifs de sécurité, l’appareil doit être logé dans un tableau électrique, de façon à ce que la seule partie accessible soit
l’affi cheur et le clavier de commande;
• toutes les connexions en très basse tension (entrées analogiques et numériques à 24 Vac/Vdc, sorties analogiques, connexions bus
sérielles, alimentations) doivent avoir une isolation renforcée ou double par rapport au réseau;
• pour tout dysfonctionnement, ne pas essayer de réparer l’appareil, mais s’adresser au service après-vente CAREL;
• dans un milieu domestique le câble de connexion entre le pCO 3 et le terminal doit être blindé.
+050003290 - 1.4 - 29.09.2006 36
DIMENSIONS
Dimensions pCO 3 MEDIUM, LARGE, EXTRALARGE N.O. et N.C.
315
44
45 110
60 Fig. 1
Dimensions pCO 3 SMALL
44
45 110
227,5 60 Fig. 2
•
•
•
CERTIFICATIONS DE PRODUIT
Norme CEI EN 50155 : “Applications ferroviaires. Équipements électroniques utilisés sur le matériel roulant”.
Norme UL 873 et C22.2 N°.24-93: “Temperature-indicating and regulating equipment”;
Règlement CE 37/2005 du 12 janvier 2005; en particulier, si le contrôle électronique est équipé de sondes NTC standard CAREL, il est conforme à la norme EN13485 relative aux “Thermomètres pour mesurer la température de l’air pour des applications sur des unités de conservation et de distribution d’aliments réfrigérés, congelés, surgelés et des glaces”.
Élimination du produit
L’équipement (ou le produit) doit faire l’objet d’un ramassage particulier en conformité avec les normes en vigueur locales en matière d’élimination des déchets.
+050003290 - 1.4 - 29.09.2006 37 français
ÉLÉMENTS INSTRUMENTS
4
7
1
3
15
4
5
2
14
6
7
8
G
G0
+V term
GND
+5 V
REF
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
ID13H
ID13
IDC13
ID14
ID14H
ID10
ID11
ID12
IDC9
B6
B7
B8
GND
ID9
Y3
Y4
ID1
Y1
Y2
VG
VG0
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
B9
BC9
B10
BC10
ID17
ID18
IDC17
8
6
5
7
+050003290 - 1.4 - 29.09.2006 38
11
12
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
E-
E+
GND
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
C7
NO7
C7
NO8
C8
NC8
C4
NO4
NO5
NO6
C4
C1
NO1
NO2
NO3
C1
Rx-/Tx-
Rx+/Tx+
GND
9
10
13
16
17
11
Fig. 3
Version EXTRALARGE N.O.
C21
NO21
NO22
NO23
NO24
C21
C25
NO25
NO26
NO27
NO28
NO29
C25
11
Version EXTRALARGE N.C.
12
C17
NO17
NO18
NO19
NO20
C17
E-
E+
GND
C14
NO14
NO15
NO16
C14
B9
B10
BC9
C25
NC25
NC26
NC27
C25
C21
NC21
NC22
NC23
NC24
C21
11
5
12
C17
NC17
NC18
NC19
NC20
C17
E-
E+
GND
C14
NC14
NC15
NC16
C14
Légende (Fig. 3…5)
1.
connecteur pour l’alimentation [G (+), G0 (-)];
2.
LED jaune indication présence tension d’alimentation et 3 LED pour le réseau local pLAN;
3.
alimentation supplémentaire terminale et sondes ratiométriques 0…5 V;
4.
entrées analogiques universelles NTC, 0…1 V
0…5 V ratiométriques 0…10 V, 0…20 mA,
4…20 mA;
5.
entrées analogiques passives NTC, PT1000,
ON/OFF;
6.
sorties analogiques 0…10 V;
7.
entrées numériques 24 Vac/Vdc;
8.
entrées numériques 230 Vac ou 24 Vac/Vdc;
9.
connecteur pour le terminal synoptique(panneau externe avec signalisations directes);
10.
connecteur pour tous les terminaux standard de la série pCO et pour le téléchargement du programme d’app;
11.
sorties numériques à relais;
12.
connecteur pour la connexion à la carte
13.
connecteur réseau local pLAN;
14.
volet pour l’insertion de l’option serial card pour superviseur;
15.
volet pour l’insertion de l’option fi eld card;
16.
volet pour l’insertion de l’option service card;
17.
terminal incorporé (LCD, touches et LED).
+050003290 - 1.4 - 29.09.2006 39 français
NOTES PRÉLIMINAIRES POUR L’INSTALLATEUR : COMPARAISON ENTRE pCO 3 ET pCO 2
• tous les contrôles de la famille pCO 3 ne sont pas dotés du connecteur pour la programmation par clef PCO201KEY0. Pour la
programmation du contrôle, il faut utiliser la nouvelle Smart Key (PCOS00AKY0) disponible à partir de septembre 2005. Sinon utiliser
le WinLoad ver, 3.35 et suivantes.
Fig. 6
Il n’est pas possible d’exécuter un programme à partir de la Smart Key;
• contrairement au pCO 2 il n’y a pas le fusible entre J1 et J2. Tous les contrôles de la famille pCO 3 ont à l’intérieur une protection
thermique sur l’alimentation. L’utilisation d’un fusible externe n’est pas requise;
• il y a une borne J24 supplémentaire (à la place du fusible) qui fournit la tension d’alimentation pour les sondes ratiométriques.
(+5 VREF) et une tension continue de 20V pour alimenter un terminal secondaire. Comme le terminal air (TAT***), comme
alternative au standard;
• les LED présents à côté du commutateur d’adressage pLAN ont été déplacés entre les connecteurs J3 et J4;
• le LED rouge de surcharge alimentation sondes a été éliminé.
Simulateur pCO 3 :
Si l’on souhaite essayer le pCO 3 avec un simulateur, nous soulignons que l’on ne peut pas utiliser celui du pCO 2 , mais le simulateur du pCO 3 . Demander à CAREL la disponibilité.
Procédure d’adressage de contrôle et terminal
Adressage du contrôle
Le contrôleur pCO3 N’EST PAS équipé de commutateur pour la programmation de l’adresse pLAN. L’adresse doit être programmée avec une procédure logiciel comme pour le pCO 1/XS .
La procédure est la suivante:
1. couper la tension au pCO 3 ;
2. préparer un terminal standard CAREL avec adresse à 0 (pas nécessaire si l’on utilise le terminal Incorporé du pCO3). Pour cette opération voir le paragraphe suivant;
3. connecter le terminal au pCO 3 ;
4. déconnecter du pCO3 tous éventuels dispositifs connectés en pLAN (terminal J11);
5. alimenter le pCO3 en appuyant simultanément sur les touches UP + ALARM. La combinaison de touches fait également offi ce de
terminal incorporé. Comme alternative, dans les terminaux PCOT, utiliser la combinaison de touches menu et .
6. après quelques secondes la page-écran suivantes’affi che:
PLAN ADDRESS: 0
UP: INCREASE
DOWN: DECREASE
ENTER: SAVE & EXIT
7. Si l’on souhaite modifi er l’adresse, il suffi t d’agir sur les touches UP et DOWN puis appuyer sur ENTER pour confi rmer.
8. paramétrer ensuite l’adresse pLAN du terminal puis confi gurer le réseau pLAN.
Adressage du terminal
Terminal de type pCOI/pCOT
L’adressage du terminal se fait via les commutateurs présents à l’arrière du terminal même.
Terminal de type pGD0/1/2/3
La valeur de l’adresse programmée en usine est 32.
Il est possible de confi gurer l’adresse du terminal uniquement après avoir alimenté celui-ci par l’intermédiaire du connecteur téléphonique.
Pour entrer en modalité confi guration appuyer simultanément sur les touches ↓↑↵ (même du terminal déjà allumé), toujours présentes dans toutes les versions, pendant 5 secondes au moins; le masque de la fi gure suivante ci-dessous s’affi chera avec le pointeur clignotant dans le coin en haut à gauche:
Display address setting.........:nn
I/O Board address:xx
• pour modifi er l’adresse du terminal (display address setting)appuyer une fois sur la touche ↵ : le pointeur se déplacera sur le champ
+050003290 - 1.4 - 29.09.2006 40
• à l’aide des touches ↓↑ sélectionner la valeur voulue, et confi rmer en appuyant de nouveau sur la touche ↵ . Si la valeur sélectionnée
est différente de celle mémorisée auparavant, le masque de la fi gure suivante s’affi chera et la nouvelle valeur sera mémorisée dans la
mémoire permanente de l’affi cheur.
Display address changed
Si l’on programme le champ nn à la valeur 0, le terminal communiquera avec le contrôle pCO3 en utilisant le protocole “point-point”
(pas pLAN) et le champ “E/S Board address: xx” disparaît car sans signifi cation.
pCO
3
: attribution liste terminaux privés et partagés
À ce point, s’il était nécessaire de modifi er la liste des terminaux associés à chaque cart pCO 3 , il faudra suivre la procédure suivante:
• entrer dans la modalité confi guration avec les touches ↓↑↵ comme décrit au paragraphe précédent;
• appuyer sur ↵ jusqu’à ce que le pointeur se positionne sur le champ (E/S board address);
• à l’aide des touches ↓↑ choisir l’adresse de la carte pCO 3 souhaitée. Les valeurs sélectionnables seront uniquement celles des cartes
pCO 3 effectivement en ligne. Si le réseau pLAN ne fonctionne pas correctement ou si aucune carte pCO 3 n’est présente, il ne sera pas
possible de modifi er le champ qui montrera uniquement “—”;
• en appuyant encore une fois sur la touche ↵ les séquences de masques suivantes seront affi chées:
Terminal Config
Press ENTER to continue
P12:Adr Priv/Shared
Trm1 02 Sh
Trm2 03 Pr
Trm3 None --OK?NO
• ici aussi la touche ↵ déplace le pointeur d’un champ à l’autre et les touches ↓↑ changent la valeur du champ courant. Le champ
P:xx montre l’adresse de la carte sélectionnée; dans l’exemple de la fi gure la 12 a été sélectionnée;
• pour quitter la procédure de confi guration et mémoriser les données sélectionner “OK ?” programmer Yes et confi rmer avec la
touche .
Les champs de la colonne “Adr” représentent les adresses des terminaux associés à la carte pCO 3 d’adresse 12, alors que la colonne
Priv/Shared indique le type de terminal.
Attention: les terminaux de la ligne pGD ne peuvent pas être confi gurés comme “Sp” (shared printer) car sans sortie imprimante. Si le terminal reste inactif (aucune touche enfoncée) pendant plus de 30 secondes, il quitte automatiquement la procédure de confi guration sans mémoriser les changements éventuels.
NOTES SUR L’UTILISATION DE WINLOAD, BOOT ET BIOS
Nous recommandons de toujours utiliser la version la plus récente de WinLoad. La gestion du pCO 3 est supportée par la version
WinLoad 3.35, disponible sur le site http://ksa.carel.com.
De la version 3.36 la vitesse de téléchargement de Bios et du programme d’application pour l pCO 3 passe à 115200 bits/s à la place de la vitesse standard.
28800 bits/s, ce changement ne détermine aucune nouvelle programmation de la part de l’utilisateur.
Le BIOS et le BOOT du pCO 3 sont des fi chiers spéciaux, différents de BIOS et de BOOT du pCO 1 et du pCO 2 . Il n’est donc pas possible de télécharger ces derniers sur le pCO 3 , et, il n’est bien entendu pas possible de télécharger les fi chiers de BOOT et BIOS pour le pCO 3 sur pCO 1 et pCO 2 .
AVERTISSEMENTS IMPORTANTS BREFS
Le produit CAREL est un produit avancé dont le fonctionnement est spécifi é dans la documentation technique fournie avec le produit ou téléchargeable, même avant l’achat, du site Internet www.carel.com.
Le client (constructeur, concepteur ou installateur de l’équipement fi nal) assume toutes les responsabilités et risques quant à la confi guration du produit pour l’obtention des résultats prévus quant à l’installation et/ou à l’équipement fi nal spécifi que.
L’absence de cette phase d’étude qui est requise/indiquée dans le manuel d’instructions peut provoquer des dysfonctionnements des produits fi nals dont CAREL ne pourra en aucun cas être jugée responsable
Le client fi nal doit utiliser le produit exclusivement selon les modes décrits dans la documentation correspondant au produit.
La responsabilité de CAREL en ce qui concerne son produit est réglée par les conditions générales de contrat CAREL publiées sur le site www.carel.com et/ou par des accords spécifi ques stipulés avec les clients.
+050003290 - 1.4 - 29.09.2006 41 français
EXAMPLE GENERAL DIAGRAM OF THE ELECTRICAL CONNECTIONS
SMALL
J9 J10 service card input: 24 V / ; 50 to 60 Hz max. power: 40 VA/15W
J1 J24 J2 field card
J3 serial card
+050003290 - 1.4 - 29.09.2006 42
MEDIUM LARGE
+050003290 - 1.4 - 29.09.2006 43
Note: ______________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
Note: ______________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
Note: ______________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
____________________________________________________________________________________________________
CAREL S.p.A.
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 - Fax (+39) 049.9716600
e-mail: CAREL @ CAREL .
com - www .
CAREL .
com
Agenzia / Agency :
Advertisement
Key features
- Connection to the local pLAN network
- Can be connected to other pCO3s and pCO system controllers
- Can exchange information with other controllers on the network
- Up to 32 units can be connected to the network
- Allows for the creation of specific products at the customer's request
- Dedicated to executing the regulation program
- Equipped with the set of terminals necessary for connection to devices
- Program and parameters are stored on FLASH-MEMORY and E2prom
- Loading the program can be done via PC or programming key