Installation Instructions
E300 / E200 Control Module
(Cat 193-EIO-_ _-_ _ _; 193-EIOGP-_ _-_ _ _)
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
Additional Resources:
1) Go to http://www.literature.rockwellautomation.com; 2) Go to Search. Type in publication number: 193-UM015
Features
193-EIO-22-24D 193-EIO-63- _ _ _ 193-EIOGP-42- _ _ _
Communication
Module Latch
A1
A1
A2
A1
A1
A2
IN2
IN3
IN4
IN5
A1
A1
A2
IN2
IN3
IT1
IT2
Power / PTC
Terminals
R13
R14
R13
R14
R23
R24
R13
R14
S1
S2
193-EIO-22-120 and
193-EIO-22-240
A1
A1
A2
193-EIO-43- _ _ _
A1
A1
A2
IN2
IN3
R13
R14
R13
R14
R23
R24
193-EIOGP-22- _ _ _
A1
A1
A2
IT1
IT2
R13
R14
S1
S2
Relay / Ground
Fault Terminals
Expansion Bus
Connector
Sensing Module
Latch
Installation
IN1
IN0
A2
R04
R03
A1
Input / Output
Terminals
IMPORTANT - Tightening screws while the 6 position connector is plugged in could result in damage to the connector.
1
2
3
Wiring Diagrams
193-EIO-_ _-_ _ _ 193-EIOGP-_ _-_ _ _
A1 R03 R04 A2 IN0 IN1
RELAY 0 Additional Inputs for 193-EIO-43-_ _ _ and 193-EIO-63-24D
Additional Inputs for 193-EIO-63-24D
A1 R03 R04 A2 IN0 IN1
RELAY 0
Additional Inputs for 193-EIOGP-42-24D
A1 A1 A2
(+) (-)
IN2 IN3 IN4 IN5
RELAY 1 RELAY 2
PE R13 R14 R23 R24
Additional Outputs for
193-EIO-43-_ _ _ and
193-EIO-63-24D
A1 A1 A2
(+) (-)
IN2 IN3 IT1
PTC
IT2 PE R13
RELAY 1
R14 S1
Ground
Fault
S2
+ t
Power Requirements
193-EIO-22-24D, 193-EIO-63-24D, 193-EIOGP-42-24D
Nominal Supply Voltage (Us)
Operating Range
Rated Supply Current
Maximum Surge Current at Power-Up
Maximum Power Consumption
Maximum Power Interruption Time @ 25 V DC
24V DC
11 - 30V DC
725mA @ 11V DC derated to 267mA @ 30V DC
6A for 1.25ms
6W
10ms at all environmental conditions
193-EIO-22-120, 193-EIO-43-120, 193-EIOGP-22-120
Rated Supply Voltage (Us)
Operating Range
120V AC
85 - 132V AC
Rated Supply Current
Maximum Surge Current at Power-Up
118mA @ 85V AC derated to 65mA @ 132V AC
5.2A for 1.00ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 120V AC 10ms at all environmental conditions
Input / Output Ratings
Inputs
Operating Voltage Range Cat No
193-EIO-22-24D
193-EIO-63-24D
193-EIOGP-42-24D
193-EIO-22-120
193-EIO-43-120
193-EIOGP-22-120
193-EIO-22-240
193-EIO-43-240
193-EIOGP-22-240
11 - 30V DC
74 - 132V AC
159 - 265V AC
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Cat No
ALL
193-EIO-22-240, 193-EIO-43-240, 193-EIOGP-22-240
Rated Supply Voltage (Us) 240V AC
Operating Range
Rated Supply Current
184 - 265V AC
58mA @ 172V AC derated to 33mA @ 310V AC
Maximum Surge Current at Power-Up 5.8A for 1.25ms
Maximum Power Consumption
Maximum Power Interruption Time @ 240V AC
6W
10ms at all environmental conditions
Rated Operating
Current (Ie)
5A @ 250V AC
0.25A @ 220V DC
Outputs
Output Current
Rating
Resistive (P.F. = 1.0) Inductive
5A @ 250V AC 2A @ 250V AC
5A @ 5-30V DC 2A @ 5-30V DC
Publication 193-IN058D-EN-P - June 2016
PN-356926
DIR 10000518534 (Version 03)