ABB ACS 600 Startup Manual

Add to my manuals
10 Pages

advertisement

ABB ACS 600 Startup Manual | Manualzz

ACS 600

This manual includes:

• ACS 600 initialisation using the Control

Panel

• First start

• Rotation direction check

• Start through a digital input

• Speed control using the Control Panel and through an analogue input

Start-up Guide

ACS 600 Frequency Converters

equipped with Standard Application Program 5.x

This Guide describes the basic start-up procedure of the

ACS 600 frequency converter equipped with the Standard

Application Program 5.x.

See the

)LUPZDUH0DQXDOIRU$&66WDQGDUG$SSOLFDWLRQ

3URJUDP[ for more information on

• the use of the Control Panel,

• the control connections,

• the Parameters,

• the fault tracing.

1998 ABB Industry Oy. All Rights Reserved.

3BFE 64049224 R0125

EN

EFFECTIVE: 26.08.1998

SUPERSEDES: None

Start-up Guide

START-UP PROCEDURE

1 – SAFETY

The start-up procedure must only be carried out by a qualified electrician.

The safety instructions must be followed during the start-up procedure. See the appropriate hardware manual for the safety instructions.

The ACx 600 must not be powered up more than five times in ten minutes to avoid charging resistor overheating (no limitation for ACS 600 MultiDrive and ACx 607 units -0760-3, -0930-5, -0900-6 or above).

Check the installation before the start-up procedure. See the installation checklist from the appropriate hardware/installation manual.

Check that starting the motor does not cause any danger.

It is recommended having the driven equipment disengaged when first start is performed if there is the risk of damage to the driven equipment in case of incorrect rotation direction of the motor.

2 – POWER-UP

Apply mains power. The Control Panel first enters the panel identification data ...

CDP312 PANEL Vx.xx

.......

... then the Identification Display of the drive ...

ACS 600 xx kW

ID NUMBER 1

...and after a few seconds the Control Panel automatically enters the Actual Signal Display.

Drive set-up can be started.

1 -> 0.0 rpm O

FREQ 0.00 Hz

CURRENT 0.00 A

POWER 0.00 %

Standard Application Program 1

Start-up Guide

START-UP PROCEDURE

3 – START-UP DATA ENTERING (Parameter Group 99)

Select the language. The general parameter setting procedure is given below.

The general parameter setting procedure:

• Press PAR to select parameter mode.

• Press or to scroll Parameter Groups (10 to 99).

• Press or to scroll parameters within the

Parameter Group.

• Select a new value by ENTER (brackets appear around the parameter value) and or . (Fast change by or .)

1 -> 0.0 rpm O

99 START-UP DATA

01 LANGUAGE

ENGLISH

1 -> 0.0 rpm O

99 START-UP DATA

01 LANGUAGE

[ENGLISH] disappear).

Select the Application Macro. The general parameter setting procedure is given above.

The default value FACTORY is suitable in most cases. A detailed description of the Application Macros is included in Firmware Manual.

1 -> 0.0 rpm O

99 START-UP DATA

02 APPLICATION MACRO

[ ]

Select the motor control mode. The general parameter setting procedure is given above.

DTC is suitable in most cases. The SCALAR control mode is recommended

• for multimotor drives when the number of motors connected to the

ACS 600 is variable.

• when the nominal current of the motor is less than 1/6 of the nominal current of the inverter.

• when the inverter is used for test purposes with no motor connected.

1 -> 0.0 rpm O

99 START-UP DATA

04 MOTOR CTRL MODE

[DTC]

2 Standard Application Program

Start-up Guide

START-UP PROCEDURE

Enter the motor data from the motor nameplate.

ABB Motors

3 motor

V

690 Y

400 D

660 Y

380 D

415 D

440 D

Cat. no

M2AA 200 MLA 4

Hz

50

50

IEC 200 M/L 55 kW

30

30 r/min

1475

1475

No

Ins.cl. F

A

32.5

56 cos IA/IN t E/s

0.83

0.83

IP 55

50

50

50

60

30

30

30

35

1470

1470

1475

1770

34

59

54

59

0.83

0.83

0.83

0.83

380 V

Mains

Voltage

3GAA 202 001 - ADA

6312/C3 6210/C3

IEC 34-1

180

Note: Set the motor data exactly the same as on the motor nameplate. For example, if the motor nominal speed is

1440 rpm on the nameplate, setting the value of Parameter

99.08 MOTOR NOM SPEED to 1500 rpm results in wrong operation of the drive.

Nominal voltage. The general parameter setting procedure is given on Page 2.

Allowed range: 1/2 · U

N

... 2 · U

N of ACS 600. ( U

N

refers to the highest voltage in each of the nominal voltage ranges: 415 VAC for 400 VAC units, 500 VAC for 500 VAC units and 690 VAC for 600 VAC units.)

1 -> 0.0 rpm O

99 START-UP DATA

05 MOTOR NOM VOLTAGE

[ ]

Nominal current. The general parameter setting procedure is given on Page 2.

Allowed range: 1/6 · I

2hd

... 2 · I

2hd of ACS 600

1 -> 0.0 rpm O

99 START-UP DATA

06 MOTOR NOM CURRENT

[ ]

Nominal frequency. The general parameter setting procedure is given on Page 2.

Range: 8 ... 300 Hz

1 -> 0.0 rpm O

99 START-UP DATA

07 MOTOR NOM FREQ

[ ]

Nominal speed. The general parameter setting procedure is given on Page 2.

Range: 1 ... 18000 rpm

1 -> 0.0 rpm O

99 START-UP DATA

08 MOTOR NOM SPEED

[ ]

Standard Application Program 3

Start-up Guide

START-UP PROCEDURE

Nominal power. The general parameter setting procedure is given on Page 2.

Range: 0... 9000 kW

1 -> 0.0 rpm O

99 START-UP DATA

09 MOTOR NOM POWER

[ ]

When the motor data has been entered a warning appears.

It indicates that the motor parameters have been set, and the ACS 600 is ready to start the motor identification

(ID magnetisation or ID Run).

1 -> 0.0 rpm O

** WARNING **

ID MAGN REQ

Select the motor identification. The general parameter setting procedure is given on Page 2.

The default value NO is suitable for most applications. It is applied in this basic start-up procedure.

The ID Run (STANDARD or REDUCED) should be selected instead if:

• Operation point is near zero speed.

• Operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder (i.e. without any measured speed feedback) is required.

See the Firmware Manual for the ID Run procedure.

1 -> 0.0 rpm O

99 START-UP DATA

10 MOTOR ID RUN

[NO]

4 – IDENTIFICATION MAGNETISATION with Motor ID Run selection NO

Press the LOC/REM key to change to local control (L shown on the first row).

Press the to start the magnetisation. The motor is magnetised at zero speed for 20 to 60 s. Two warnings are displayed:

• The upper warning is displayed while the magnetisation is on.

• The lower warning is displayed after the magnetisation is completed.

1 L-> 0.0 rpm I

** WARNING **

ID MAGN

1 L-> 0.0 rpm O

** WARNING **

ID DONE

4 Standard Application Program

Start-up Guide

START-UP PROCEDURE

5 – ROTATION DIRECTION OF THE MOTOR

Check the rotation direction of the motor.

• Press ACT to get the status row visible.

• Increase the speed reference from zero to a small value by pressing REF and then or ( or ).

• Press (Start) to start the motor.

• Check that the motor is running in the desired direction.

• Stop the motor by pressing .

1 L->[xxx] rpm I

FREQ xxx Hz

CURRENT xx A

POWER xx %

To change the rotation direction of the motor:

• Disconnect mains power from the ACx 600, and wait 5 minutes for the intermediate circuit capacitors to discharge. Measure the voltage between each input terminal (U1, V1 and W1) and earth with a multimeter to ensure that the frequency converter is discharged.

• Exchange the position of two motor cable phase conductors at the motor terminals or at the motor connection box.

• Verify your work by applying mains power and repeating the check as described above.

forward direction reverse direction

6 – SPEED LIMITS AND ACCELERATION/DECELERATION TIMES

Set the minimum speed. The general parameter setting procedure is given on Page 2.

1 L-> 0.0 rpm O

20 LIMITS

01 MINIMUM SPEED

[ ]

Set the maximum speed. The general parameter setting procedure is given on Page 2.

1 L-> 0.0 rpm O

20 LIMITS

02 MAXIMUM SPEED

[ ]

Set the acceleration time 1. The general parameter setting procedure is given on Page 2.

Note: Check also acceleration time 2, if two acceleration times will be used in the application.

1 L-> 0.0 rpm O

22 ACCEL/DECEL

02 ACCELER TIME 1

[ ]

Set the deceleration time 1. The general parameter setting procedure is given on Page 2.

Note: Set also deceleration time 2, if two deceleration times will be used in the application.

1 L-> 0.0 rpm O

22 ACCEL/DECEL

03 DECELER TIME 1

[ ]

Standard Application Program 5

Start-up Guide

START-UP PROCEDURE

7 – STARTING THE DRIVE THROUGH THE I/O INTERFACE

As default the external start/stop signal is read from the digital input DI1, and the external speed reference from the analogue input AI1.

Valid if the factory macro is selected. See Parameter

99.02 APPLICATION MACRO.

Starting through a digital input:

• Press the LOC/REM key to change to external control

(no L visible on the first row of the panel display).

• Switch on digital input DI1.

Drive starts. The motor is accelerated to a speed determined by the voltage level of analogue input AI1.

8 – STOPPING THE MOTOR

Stopping when in local control: Press .

Stopping when in external control: Switch off digital input

DI1.

Valid if the factory macro is selected. See Parameter

99.02 APPLICATION MACRO.

Press the LOC/REM key to change between local and external control.

6 Standard Application Program

ABB Industry Oy

Drives

P.O.Box 184

FIN-00381 HELSINKI

FINLAND

Telephone: +358-10 22 2000

Telefax: +358-10-22 22681

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement