Allen-Bradley PowerFlex 70 is a powerful AC drive that offers precise motor control and a wide range of features for a variety of applications. With its compact design and easy-to-use interface, the PowerFlex 70 is ideal for controlling pumps, fans, conveyors, and other industrial machinery. Some of its key capabilities include:
-
Precise motor control: The PowerFlex 70 uses advanced algorithms to provide precise speed and torque control, even for demanding applications.
-
Built-in intelligence: The PowerFlex 70 is equipped with a variety of built-in functions, including PID control, programmable logic, and data logging.
Advertisement
Advertisement
PowerFlex 70 Power Jumpers
Installation Instructions
The PowerFlex 70 drive contains protective MOVs and Common Mode
Capacitors referenced to ground (see below). To guard against unstable operation and/or damage, the drive must be properly configured as shown in
MOV and AC EMI Capacitor Phase to Ground Common Mode Capacitor to Ground
R/L1
S/L2
T/L3
DC+
DC–
Jumper-Wire
Jumper-Wire
Important: All PowerFlex 70 drives are shipped with the DC bus common mode capacitors referenced to ground.
The information in this document supersedes the MOV and Common Mode
Capacitor material in the following:
Title
PowerFlex 70 User Manual
PowerFlex 70 Installation Instructions
Publication
20A-UM001M
20A-IN009B
For additional general information, refer to:
Title
PowerFlex 70 User Manual
Publication
20A-UM001
Wiring and Grounding Guidelines for PWM AC Drives DRIVES-IN001
Guarding Against Electrostatic Damage 8000-4.5.2
Available Online at … www.rockwellautomation.com/ literature
Before proceeding, ensure that all power to the drive has been removed.
!
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly.
Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection guide.
Publication 20A-IN010B-EN-P
2 PowerFlex 70 Power Jumpers
!
!
!
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should perform maintenance/repair of the system. Failure to comply may result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the following points (refer to the User Manual for locations):
•
+DC terminal of the Power Terminal Block and the -DC test point
(Frames A…D) or the -DC terminal of the Power Terminal Block
(Frame E)
•
+DC terminal of the Power Terminal Block and the chassis
•
-DC test point (Frames A…D) or the -DC terminal of the Power
Terminal Block (Frame E) and the chassis
The voltage must be zero for all three measurements.
ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
Table A Recommended Power Jumper Configurations
Power Source Type
Solid Ground
(1)
•
AC fed, solidly grounded
•
DC fed from passive rectifier which has an AC source and solid ground
MOV/Input
Filter Caps
Connected
(2)
DC Bus
Common Mode
Caps
Connected
Benefits Of Correct
Configuration on Power Source
Type
•
UL compliance,
•
Reduced electrical noise,
•
Most stable operation,
•
EMC compliance,
•
Reduced voltage stress on components and motor bearings
•
Helps avoid severe equipment damage when ground fault occurs
Non-Solid Ground
•
AC fed ungrounded
•
Impedance grounded
•
High resistive ground
•
B phase ground
•
Regenerative unit such as common DC bus supply & brake
•
DC fed from an active converter
(1)
(2)
Disconnected Disconnected
It is highly recommended to accurately determine the power source type and then configure appropriately.
When MOVs are disconnected, the power system must have its own transient protection to ensure known and controlled voltages.
To connect or disconnect these devices, refer to pages
5 .
Important: Common mode capacitors are used to conform with the EMC directives. Removing these devices may withdraw the associated directive.
Publication 20A-IN010B-EN-P
PowerFlex 70 Power Jumpers 3
In addition, on an ungrounded distribution system where the line-to-ground voltages on any phase could exceed 125% of the nominal line-to-line voltage, an isolation transformer should be installed. See Wiring and Grounding Guidelines for PWM AC Drives, publication DRIVES-IN001 for more information on impedance grounded and ungrounded systems.
Jumper Installation, Removal and Storage
PowerFlex 70 drives utilize plug-in style jumpers. Most drives will have a jumper storage area inside the front cover. Extra jumpers or jumpers that have been removed should be stored in this location for use at a later time.
In some cases a protective cover may be present over the jumper pins that extend from the board. If present, simply remove the protective cover, install (or remove) jumper and replace cover.
Drive Identification
Refer to the drive nameplate and locate the “Voltage Code,” “Frame” and
“Internal EMC Option” (Frame B drives). Use this information to locate the proper procedure in the following tables.
Voltage Code Internal EMC Option
Frame
Cat No. 20A D xxx x x xxx x xxx
UL TYPE 1/IP20 and 50C (122F) Ambient Limit
See Manual for additional ratings
Normal Duty Power
Heavy Duty Power
400V Class xxx kW xxx kW
Input: 3 Phase, 47-63Hz
AC Voltage Range
Amps
Output: 3 Phase, 0-400 Hz
AC Voltage Range
Base Frequency (default)
Continuous Amps
3 Sec / 60 Sec Ovld Amps
Mfd. in 2008 on Jan 19
342-440 xxx
Series: A
Frame: A
480V Class xxx HP xxx HP
432-528 xxx
0-400
50 Hz xxx xxx
0-460
60 Hz x xxx / xx
Serial No. xxxxxxx
Original Firmware No. x.xxx
Mfg. in U.S.A. (FAC1J) c
U
®
L
US
LISTED INDUCTRIAL
CONTROL EQUIPMRNT
966X
.
.
Rheinland
Product Safety
W
E C
Production inspected
EN 50178
N223
Publication 20A-IN010B-EN-P
4 PowerFlex 70 Power Jumpers
A B
C
D
E
Jumper Settings and Locations
Factory Default Jumper Settings
MOV/Input Filter
Caps
DC Bus Common
Mode Caps
JP2/JP3
Installed
Not Applicable
Power Source Type
Solid Ground
Insert jumper at the “JP2/JP3” location.
Non-Solid Ground
Remove the jumper at “JP2/JP3.”
B B
C
D
E
JP2/JP3
Installed
C B
C
D
E
JP2/JP3
Installed
JP5/JP6
Installed
JP3A/JP3B
Installed
JP3
JP2
Important: The Internal EMC Filter (input filter) is a factory installed option on Frame B drives. If the option is installed, the drive cannot be used on a non-solid ground power source.
To verify: an extra “R, S, T” terminal block will be present if the option is installed (as shown).
Additionally, the 13th character of the nameplate catalog number will be an “A” (see
).
Input Filter
Option
Solid Ground
Jumpers should be installed at both locations
(JP2/JP3 and JP5/JP6).
L1
R
L2
S
L3
T
L1
R
L2
S
L3
T
BR1
+DC
Non-Solid Ground
Remove the jumpers at “JP2/JP3” and “JP5/
JP6.” In addition, verify that the Input Filter option is not installed.
L1
R
L2
S
L3
T
L1
R
L2
S
L3
T
BR1
+DC
MOV
CM Cap or
JP6 JP5
JP2
JP3
MOV
CM Cap
JP6
JP2
JP5
JP3
Input Filter
Option
Solid Ground
Jumpers should be installed at both locations
(JP2/JP3 and JP3A/JP3B).
Non-Solid Ground
Remove the jumpers at “JP2/JP3” and “JP3A/
JP3B.”
JP3B
JP3A
MOV
CM Cap
JP3 JP2
MOV / Filter Cap
Publication 20A-IN010B-EN-P
D B
C
D
E
Factory Default Jumper Settings
MOV/Input Filter
Caps
DC Bus Common
Mode Caps
JP2/JP3
Installed
JP3A/JP3B
Installed
Power Source Type
Solid Ground
Jumpers should be installed at both locations
(JP2/JP3 and JP3A/JP3B).
Non-Solid Ground
Remove the jumpers at “JP2/JP3” and “JP3A/
JP3B.”
E B
C
D
E
JP1/JP2
Installed
JP3/JP4
Installed
Solid Ground
Jumpers should be installed at both locations
(JP1/JP2 and JP3/JP4).
Non-Solid Ground
Remove the jumpers at “JP1/JP2” and “JP3/
JP4.”
S HLD
PowerFlex 70 Power Jumpers 5
JP 3 B
JP 3 A
CM C a p
JP 3
JP2
MOV / Filter C a p
JP4
JP1 JP2
JP3
CM Cap
MOV /
Filter Cap
Publication 20A-IN010B-EN-P
*PN-73465*
PN-73465
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 20A-IN010B-EN-P – March 2010
Supersedes 20A-IN010A-EN-P –June 2009
PN-73465
Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in USA.
Advertisement