ABB FCAN-01 Quick Installation And Start-Up Manual

Add to My manuals
2 Pages

ABB FCAN-01 is a CANopen adapter module that provides a gateway between CANopen networks and ABB drives. It enables communication between the drive and other CANopen devices, such as PLCs, HMIs, and sensors.

Key features and benefits

  • Easy installation: The module can be quickly and easily installed into an option module slot of the drive.
  • Automatic parameter setting: When the module is connected to the drive, the drive control program automatically sets the applicable parameters.
  • Flexible configuration: The module supports a variety of CANopen communication profiles, allowing it to be used with a wide range of devices.

advertisement

ABB FCAN-01 Quick Installation And Start-Up Manual | Manualzz

Options for ABB drives, converters and inverters

Quick installation and start-up guide

FCAN-01 CANopen adapter module

Safety instructions

WARNING ! Obey the safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. See the user’s manual.

Mechanical installation

1. Pull out the lock.

2. Install the module carefully to an option module slot of the drive. See the drive hardware manual.

3. Push in the lock.

4. Tighten the screw to torque 0.8 N·m using a Torx TX10 screwdriver.

WARNING ! Do not use excessive force, or leave the screw too loose. Overtightening can damage the screw or module. A loose screw decreases the EMC performance, and can even cause an operation failure.

Electrical installation

Layout of the module

1

1

2

3

No.

Description

1 Lock

4

Mounting and grounding screw

Bus connector [X1]

Diagnostic LEDs

4

3

4

2

3

Pin allocation for [X1]

1 5

SUB-D9

(male)

6 9

According to CANopen specification CiA 301 .

Pin

1

2

-

CAN_L

Description

Not in use

CAN_L bus line

8

9

6

7

3

4

5

CAN_GND

-

CAN_SHLD

GND

CAN_H

-

CAN_V+

CAN ground

Not in use

Optional CAN shield

Optional ground

CAN_H bus line

Not in use

Not supported.

Bus termination

Bus termination is required to prevent signal reflections from the bus cable ends. The module is not equipped with internal bus termination. Therefore, the first and last nodes of the bus must be included with bus termination.

In the this diagram, the built-on terminations of the D-SUB connectors at the first and last nodes are switched on.

CANopen

ON

CANopen CANopen CANopen

ON

Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters.

See the appropriate drive manual.

Basic parameter settings

Index

20.01

22.11

28.11

50.01

50.02

51.02

51.03

51.05

Name

Ext1 commands

Value

Fieldbus A

Speed ref1 source FBA A ref 1

Frequency ref1 source FBA A ref 1

FBA A enable Enable (or select the option slot in which the module is installed)

FBA A comm loss func Fault

Node ID

Bi t rate

Profile

Set the node address of the device.

Set the bit rate for the CANopen interface.

The ABB Drives communication profile is the default value.

To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh .

Further information

See the latest version of FCAN-01 CANopen adapter module user's manual (3AFE68615500 [English]) in ABB library ( www.abb.com/drives/documents ) .

For more information on fieldbus options and protocols provided by ABB Drives, see the fieldbus communications web page

( new.abb.com/drives/connectivity/fieldbus-connectivity ).

Fieldbus communications web page FCAN-01 manual