Installation Instructions
1732E ArmorBlock 2-Port EtherNet/IP
Modules with QuickConnect
Catalog Numbers 1732E-12X4M12QCDR,
1732E-12X4M12P5QCDR, 1732E-16CFGM12QCR,
1732E-16CFGM12P5QCR, 1732E-16CFGM12QCWR,
1732E-16CFGM12P5QCWR
Table of Contents
Topic
Preventing Electrostatic Discharge
Connect the I/O, Network and Auxiliary Cables to the Module
Page
2
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ ) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
3
Environment and Enclosure
ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication.
Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
, for additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1732E-IN010C-EN-E - June 2013
4
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Additional Resources
Resource
ArmorBlock 2-Port EtherNet with Diagnostics and QuickConnect Wiring Diagrams, publication 1732E-WD004
ArmorBlock WeldBlock 2-Port Ethernet
Self-configurable with QuickConnect Wiring
Diagrams, publication 1732E-WD005
ArmorBlock 2-Port Ethernet Self-configurable with QuickConnect Wiring Diagrams, publication 1732E-WD006
Ethernet QuickConnect Application
Technique, publication ENET-AT001
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Description
Detailed description of how to wire your
1732E-12X4M12QCDR or 1732E-12X4M12P5QCDR module.
Detailed description of how to wire your
1732E-16CFGM12QCWR or
1732E-16CFGM12P5QCWR module.
Detailed description of how to wire your
1732E-16CFGM12QCR or
1732E-16CFGM12P5QCR module.
Detailed explanation on how to set up and use
QuickConnect ArmorBlock modules.
More information on proper wiring and grounding techniques.
If you would like a manual, you can:
• download a free electronic version from the internet: http://www.rockwellautomation.com/literature/
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
Overview
The 1732E-12X4M12QCDR, 1732E-12X4M12P5QCDR, 1732E-16CFGM12QCR,
1732E-16CFGM12P5QCR, 1732E-16CFGM12QCWR,
1732E-16CFGM12P5QCWR ArmorBlock
™
are I/O modules that communicate via
EtherNet/IP. The sealed IP65, IP66, IP67 and IP69K housing of these modules requires no enclosure. The I/O modules have dual Ethernet ports and use an embedded Ethernet switch.
The modules have Auxiliary power In and Out connectors. There is no need to house these modules in a secondary enclosure. The I/O modules support the QuickConnect feature, onboard nonvolatile memory for storing block-specific data such as Tool ID and counter value, and provide basic distributed I/O functionality.
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
5
Module Identification
LED status indicators
PORT 1
LINK 1
MOD
LINK 2
NET
PORT 2
1732E-16CFGM12QCWR shown
Function earth
(2)
EtherNet/IP D-code
M12 connector EtherNet/IP D-code
M12 connector
Node address switches
M12 style I/O connectors
M12 style
I/O connectors
Mini-style auxiliary power in
Protective earth
(1)
AUX POWER
Mini-style auxiliary power out
45758
(1) Protective Earth is provided for the grounding of field devices and is internally connected to each Pin 5 of the M12 I/O
connectors. See I/O Connectors on page 9.
(2) Functional Earth grounds the I/O block’s EtherNet/IP communication circuitry which is designed to mitigate the effect of
noise on the network. See EtherNet/IP Connector on page 11.
Catalog Number Explanation
Refer to the table for a description of the module catalog numbers.
Catalog Number Description
1732E-12X4M12QCDR
Network
Connector
Dual D-code
M12
1732E-12X4M12P5QCDR
1732E-16CFGM12QCR
Diagnostic 12-input/4 output 24V DC digital
I/O dual-port Ethernet module with
QuickConnect
Diagnostic 12-input/4 output 24V DC digital
I/O dual-port Ethernet module with
QuickConnect
16 channel 24V DC self-configurable digital
I/O dual-port Ethernet module with
QuickConnect
Dual D-code
M12
Dual D-code
M12
Auxiliary
Power
Dual 4-pin mini
Dual 5-pin mini
Dual 4-pin mini
Publication 1732E-IN010C-EN-E - June 2013
6
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Catalog Number Description
1732E-16CFGM12P5QCR
1732E-16CFGM12QCWR
16 channel 24V DC self-configurable digital
I/O dual-port Ethernet module with
QuickConnect
16 channel 24V DC self-configurable digital
I/O dual-port Ethernet metal WeldBlock module with QuickConnect
1732E-16CFGM12P5QCWR 16 channel 24V DC self-configurable digital
I/O dual-port Ethernet metal WeldBlock module with QuickConnect
Network
Connector
Dual D-code
M12
Dual D-code
M12
Dual D-code
M12
Auxiliary
Power
Dual 5-pin mini
Dual 4-pin mini
Dual 5-pin mini
Install the Module
To install the module:
• Set the network address
• Mount the module
• Connect the I/O, Network and Auxiliary cables to the module.
Set the Network Address
The I/O block ships with the rotary switches set to 999 and DHCP enabled.
To change the network address, you can do one of the following:
• adjust the switch on the front of the module.
• use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell
Automation BootP/DHCP.
• retrieve the IP address from nonvolatile memory.
The I/O block reads the switches first to determine if the switches are set to a valid number. To set the network address:
1. Rotate the three (3) switches on the front of the module using a small blade screwdriver.
2. Line up the small notch on the switch with the number setting you wish to use.
Valid settings range from 001…254.
3. Cycle power.
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
7
Set Network Address
Example shows default node address set at 163.
45759
When the switches are set to a valid number, the I/O block’s IP address is 192.168.1.xxx
(where xxx represents the number set on the switches). The I/O block’s subnet mask is
255.255.255.0 and the gateway address is set to 0.0.0.0. When the I/O block uses the network address set on the switches, the I/O block does not have a host name assigned to it or use any Domain Name Server.
If the switches are set to an invalid number (for example, 000 or a value greater than 254 excluding 888), the I/O block checks to see if DHCP is enabled. If DHCP is enabled, the
I/O block asks for an address from a DHCP server. The DHCP server also assigns other
Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the I/O block uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.
Mount the Module
Two sets of mounting holes are used to mount the module directly to a panel or machine.
Mounting holes accommodate #8 (M4) pan head screws. The torque specification is
1.13 Nm (10 in-lb).
Product Dimensions
Refer to the mounting dimensions illustration to help you mount the module.
Publication 1732E-IN010C-EN-E - June 2013
8
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Module Dimensions
60.4 mm
(2.38 in.)
45 mm
(1.77 in.)
28 mm
(1.1 in.)
LINK 1
PORT 1
MOD
LINK 2
NET
PORT 2
200 mm
(7.87 in.)
189.6 mm
(7.46 in.)
AUX POWER
Front view
Mount the Module in High Vibration Areas
Side view
45760
If you mount the module in an area that is subject to shock or vibration, we recommend you use a flat and a lock washer to mount the module. Mount the flat and the lock washer as shown in the mounting illustration. Torque the mounting screws to 1.13 Nm (10 in-lb).
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
9
High Vibration Area Mounting
Lock washer
Flat washer
Connect the I/O, Network and Auxiliary Cables to the Module
The ArmorBlock EtherNet/IP family has 5-pin micro-style connectors. We provide caps to cover the unused connectors on your module. Connect the quick-disconnect cord sets you selected for your module to the appropriate ports.
I/O Connectors
44766
Micro-style 5-Pin Input Female Connector
1
4
5
2
3
44807
For 1732E-12X4M12QCDR and 1732E-12X4M12P5QCDR only
(View into connector)
Pin 1 Sensor source voltage
Pin 2 Input B
Pin 3 Return
Pin 4 Input A
Pin 5 PE
ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment and all connected I/O must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Publication 1732E-IN010C-EN-E - June 2013
10
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Micro-style 5-Pin Output Female Connector
1
4
5
2
3
44807
For 1732E-12X4M12QCDR and 1732E-12X4M12P5QCDR only
(View into connector)
Pin 1 Not used
Pin 2 Output B
Pin 3 Return
Pin 4 Output A
Pin 5 PE
Self-configuring Modules
The 1732E-16CFGM12QCR, 1732E-16CFGM12P5QCR,
1732E-16CFGM12QCWR, and 1732E-16CFGM12P5QCWR self-configuring modules contain both input and output functionality.
• If an I/O point is to be an output, dedicate that point as an output with a wired load and energize it through a control program.
• Energized outputs show an associated active input that can be used as a feedback mechanism to make certain that the output is on.
• If an I/O point is to be an input, wire the input device as normal and leave the associated output de-energized at all times.
Micro-style 5-Pin Selectable Point Connector
1
4
5
2
3
(View into connector)
Pin 1 Sensor source voltage
Pin 2 Input or Output B
Pin 3 Return
Pin 4 Input or Output A
Pin 5 PE
44807
ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure and
NEMA type requirements.
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Limited Voltage
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
11
I/O Self-configure Circuitry
43601
EtherNet/IP Connector
D-Code Micro Network Female Connector
4
1
3
2
5
(View into connector 1)
Pin 1 M12_Tx+
Pin 2 M12_Rx+
Pin 3 M12_Tx-
Pin 4 M12_Rx-
Pin 5 Connector shell shield GND
45793
2
3
1
4
(View into connector 2)
Pin 1 M12_Rx+
Pin 2 M12_Tx+
Pin 3 M12_Rx-
Pin 4 M12_Tx-
Pin 5 Connector shell shield GND
5
45794
IMPORTANT Use the 1585D–M4DC–H: Polyamide small body unshielded or the
1585D–M4DC–SH: Zinc die-cast large body shielded mating connectors for the D-Code M12 female network connector.
Publication 1732E-IN010C-EN-E - June 2013
12
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Enable QuickConnect
To enable QuickConnect for the Ethernet ports, use the RSLogix 5000 software Module
QuickConnect tab and check the Enable QuickConnect option. For more information on the QuickConnect system set up, refer to Ethernet QuickConnect Application Technique, publication ENET-AT001 .
After the QuickConnect feature is set to "on", the module must be power cycled.
QuickConnect is active during the next connection.
Once active, the QuickConnect feature automatically sets all Ethernet ports to:
• Speed = 100 Mbps
• Duplex = Full
• Auto-negotiate = Off
• Automatic Cross-over Cable Detection (Auto-MDIX) = Off
If you configure BootP or DHCP, QuickConnect changes the configuration to retain the current IP address. Disabling the QuickConnect feature automatically sets all Ethernet ports to Automatic Cross-over Cable Detection (Auto-MDIX) = On.
To reset the Ethernet ports to Auto-negotiate or the IP address to DHCP request, you can:
• change the setting on the module web page
• change the setting in the RSLogix 5000 software
• perform a factory reset
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
13
Auxiliary Power Connector
The 1732E-12X4M12QCDR, 1732E-16CFGM12QCR, and
1732E-16CFGM12QCWR modules use 4-pin auxiliary power connections. Attach the mini-style 4-pin connector to the mini-style 4-pin receptacle as shown below.
Mini-style 4-Pin Receptacle
Male Input
4
3
2
1
(View into receptacle)
Pin 1 Output power+
Pin 2 Sensor/MDL power+
Pin 3 Sensor/MDL power-
Pin 4 Output power-
44809
Female Output
2
1
4
3
45677
The 1732E-12X4M12P5QCDR, 1732E-16CFGM12P5QCR, and
1732E-16CFGM12P5QCWR modules use 5-pin auxiliary power connections. Attach the mini-style 5-pin connector to the mini-style 5-pin receptacle as shown below.
Mini-style 5-Pin Receptacle
Male Input
2
1
3
5
4
(View into receptacle)
Pin 1 Output power-
Pin 2 Sensor/MDL power-
Pin 3 Protective Earth
Pin 4 Sensor/MDL power+
Pin 5 Output power+
46199
TIP
Female Output
4
5
3
The ground for both module power and output power are shared.
1
2
46200
ATTENTION: This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbance.
Publication 1732E-IN010C-EN-E - June 2013
14
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Auxiliary Power is based on a 4-pin and 5-pin connector system and is used to provide 24V
DC power to I/O modules and other devices. Running separate power to these devices is most typically used for I/O devices with output connections to prevent power supply interruption due to switching of outputs. However, some devices require separate auxiliary power to power them regardless of the presence of outputs.
Depending on the devices used, it may be possible to provide power through only one pair of the four available pins, and in this case the other available pair may be used for single channel E-stop through the use of special E-stop drop or power T-ports and shorting plugs. Allen-Bradley E-stop T-ports and shorting plugs are red in color for easy identification.
Configure the Module
Refer to the illustration for configuration operations.
Configure Operations
1732E-16CFGM12QCR shown
EtherNet/IP D-code
M12 connector
Node address switches
LINK 1
PORT 1
MOD
LINK 2
NET
PORT 2
EtherNet/IP D-code
M12 connector
M12 style
I/O connectors
M12 style
I/O connectors
Mini-style auxiliary power in
AUX POWER
Mini-style auxiliary power out
45761
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
15
Refer to On-Machine Connectivity Catalog, publication M117-CA001 , for Rockwell
Automation cable and cord set offerings or use the configuration tools available at www.rockwellautomation.com/en/e-tools/ .
External Repository for Random Data (ERRD)
The QuickConnect modules provide onboard nonvolatile memory, of up to 6 Kbytes, for storing block-specific data such as Tool ID and counter value. You can read from and write to the module memory.
To read from the module
1. Send an EtherNet/IP Explicit Message with the following information:
Service Code 4C (hex)
Class ID 6E (hex)
Instance ID
Attribute ID
1
1
Request Data Data Payload (total 8 bytes):
Offset Description
0x00 Address to Read from
0x04 Number of bytes to read (max. 472 bytes)
To write to the module
2. Send the following three EtherNet/IP Explicit Messages:
Start command
Service Code
Class ID
Instance ID
Attribute ID
06 (hex)
6E (hex)
1
1
Write command
Service Code 4D (hex)
Class ID 6E (hex)
Instance ID
Attribute ID
1
1
Request Data Data Payload (max 8+ 472 bytes):
Offset Description
0x00 Address to Write to
0x04 Number of bytes to write (max. 472 bytes)
0x08 User Data (Array of USINT)
Publication 1732E-IN010C-EN-E - June 2013
16
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Stop command
Service Code
Class ID
Instance ID
Attribute ID
1
1
07 (hex)
6E (hex)
Interpret LED Indicators
This module has the following indicators:
• Network, Module, and Link status indicators for EtherNet/IP
• Module Power indicator
• Individual I/O status indicators for inputs and outputs
Link status indicator
Module status indicator
1732E-16CFGM12QCR/
1732E-16CFGM12QCWR
LINK 1
PORT 1
MOD
LINK 2
NET
PORT 2
Network status indicator
Module status indicator
1732E-12X4M12QCDR
LINK 1
PORT 1
MOD
LINK 2
NET
PORT 2
Link status indicator
Network status indicator
Input status indicator
I/O status indicator
AUX POWER
Power status indicator
AUX POWER
Output status indicator
45762
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
17
Link status indicator
Module status indicator
1732E-16CFGM12P5QCR/
1732E-16CFGM12P5QCWR
LINK 1
PORT 1
MOD
LINK 2
NET
PORT 2
Network status indicator
Module status indicator
1732E-12X4M12P5QCDR
LINK 1
PORT 1
MOD
LINK 2
NET
PORT 2
Link status indicator
Network status indicator
Input status indicator
I/O status indicator
AUX POWER
Power status indicator
AUX POWER
Output status indicator
46201
Indicator Status for Modules
Module status
Status
Off
Flashing red/green
Green
Flashing red
Red
Description
No power applied to device.
Device is in self-test.
Device operating normally.
Recoverable fault.
Unrecoverable fault — may require device replacement.
Publication 1732E-IN010C-EN-E - June 2013
18
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Indicator Status for Modules
Network status
Network link status
Power status
Digital output status
Digital input status
Status
Off
Flashing green
Green
Flashing red
Red
Flashing red/green
Off
Green
Flashing green
Yellow
Flashing yellow
Off
Green
Off
Yellow
Flashing yellow
Red
(1)
Flashing red
Off
Yellow
Red
(1)
Flashing red
Description
The device is not initialized or the module does not have an IP address.
The device has no CIP connections.
The device has an IP address, but no CIP connections are established.
The device is online, has an IP address, and CIP connections are established.
One or more connections have timed out.
The module has detected that its IP address is already in use.
The module is performing a powerup self-test.
No link established.
Link established on indicated port at 100 Mbps.
Link activity present on indicated port at 100 Mbps.
Link established on indicated port at 10 Mbps.
Link activity present on indicated port at 10 Mbps.
No power to device or input not valid.
Power applied to device.
Output not energized.
Output energized and output power applied.
Output energized and no output power.
Output shorted.
Output open load.
No valid input.
Valid input.
Sensor source voltage shorted.
Sensor source open wire.
(1)
Only diagnostic modules 1732E-12X4M12QCDR and 1732E-12X4M12P5QCDR have red I/O status LED indicators.
IMPORTANT In non-QuickConnect mode, the Module Status LED indicator flashes red and green for a maximum 5 s while the module completes its POST
(Power-On Self Test).
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
19
Specifications
1732E ArmorBlock 2-Port EtherNet Module Input
Attribute
Number of inputs
Input type
Voltage, off-state input, max
Voltage, on-state input, max
Voltage, on-state input, nom
Voltage, on-state input, min
Current, off-state input, max
Current, on-state input, max
Voltage, sensor source, max
Voltage, sensor source, min
Input delay time
ON to OFF
OFF to ON
Value
12 – 1732E-12x4M12QCDR, 1732E-12x4M12P5QCDR
16 – all other modules
Sink, 24V DC
5V DC
30V DC
24V DC
12V DC
1.5 mA @ 5V DC
5 mA @ 30V DC
30V DC
10V DC
0, 1, 2, 4, 8, 16 ms
1732E ArmorBlock 2-Port EtherNet Module Output
Attribute
Number of outputs
Value
4 – 1732E-12x4M12QCDR, 1732E-12X4M12P5QCDR
16 – all other modules
Output type Source, 24V DC
Voltage drop, on-state output, max 0.5V DC
Voltage off-peak blocking, min
Voltage, on-state output, max
Voltage, on-state output, min
Voltage, on-state output, nom
Current on-state output, max
30V DC
30V DC
12V DC
24V DC
0.5 A
Publication 1732E-IN010C-EN-E - June 2013
20
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
1732E ArmorBlock 2-Port EtherNet Module Output
Attribute
Current per module, max
Leakage current, off-state output, max
Surge current per output, min
Value
2.0 A – 1732E-12X4M12QCDR, 1732E-12X4M12P5QCDR
8.0 A – all other modules
0.5 mA – 1732E-12X4M12QCDR, 1732E-12X4M12P5QCDR
50
μ
A – all other modules
1.2 A for 10 ms, repeatable every 2 s
General Specifications
Attribute
Voltage, auxiliary power, max
Value
30V DC
Voltage, auxiliary power, min 12V DC
Current, Ethernet system power, max (pins 2, 3 sensor source/module power)
1 A
Current, auxiliary power, max per output module (pins 2, 3 sensor source/module power plus pins
1, 4 for output loads)
2 A – 1732E-12X4M12QCDR, 1732E-12X4M12P5QCDR
8 A – all other modules
Current, auxiliary power connector, max per module
10 A
Current, sensor source, per input, max
50 mA
100 mA Current, sensor source, per connector, max
Communication rate
Isolation voltage
LED indicators
Dimensions (HxWxD), approx.
Weight, approx.
EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment
50V (continuous), Basic Insulation Type, I/O to Ethernet,
Power to Ethernet
Type tested at 707V DC for 60 s
Module Status - red/green
Network Status - red/green
Link Status - green/yellow
Auxiliary Power - green
I/O LED - yellow
I/O LED - yellow/red – 1732E-12X4M12QCDR, 1732E-12X4M12P5QCDR
200 x 60.4 x 45 mm (7.87 x 2.38 x 1.77 in.)
0.51 kg (1.12 lb) – 1732E-16CFGM12QCWR, 1732E-16CFGM12P5QCWR
0.43kg (0.95 lb) – all other modules
Publication 1732E-IN010C-EN-E - June 2013
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
21
General Specifications
Attribute
Enclosure type rating
Wiring category
(1)
Value
Meets IP65/66/67/69K (when marked), and Type 4X Indoor Use Only, with receptacle dust caps or cable termination
1 - on signal ports
1 - on power ports
1 - on communications port
Onboard memory type Ferroelectric Nonvolatile RAM (FRAM)
Onboard memory, capacity, max 6 Kbytes
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
Environmental Specifications
Attribute
Temperature, operating
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, ambient, max.
60 °C (140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
Vibration
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10... 500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
ESD immunity
CISPR 11
Group 1, Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Publication 1732E-IN010C-EN-E - June 2013
22
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Environmental Specifications
Attribute Value
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 Mhz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on signal ports
±3 kV @ 5 kHz on communications ports
Surge transient immunity
Conducted RF immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when product is marked)
(1) c-UR-us
Value
CE
C-Tick
EtherNet/IP
KC
UL Recognized Component Industrial Control Equipment, certified for US and
Canada. See UL File E322657.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
ODVA conformance tested to EtherNet/IP specifications.
Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
(1)
See the Product Certification link at http://www.ab.com
for Declaration of Conformity, Certificates, and other certification details.
Publication 1732E-IN010C-EN-E - June 2013
Notes:
1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
23
Publication 1732E-IN010C-EN-E - June 2013
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ , you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/ .
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
contact your local Rockwell Automation representative.
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
Allen-Bradley, Rockwell Automation, ArmorBlock, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1732E-IN010C-EN-E - June 2013
1732E-IN010B-EN-E - December 2011 Copyright © 2013 Rockwell Automation, Inc. All rights reserved.