Installation Instructions
Cat. No. 1792D-8BT8PE
Ground lug
43881
!
I/O module (Cat. No. 1792D-8BT8PE) is a
DeviceNet
!
network. The sealed housing of this module requires no enclosure.
This module has 8 inputs and 8 outputs accessed through Y splitter cables. Inputs are 24V dc devices. Eight self-protected 24V dc outputs can provide up to 0.5 amp each. Diagnostic features are short circuit, open wire, and no load detection reported to the connector level on included. An external lug exists to ground the block.
Publication 1792D-IN055A-EN-P - October 2004
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 3
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
Package Contents
Your package contains:
"
1 ArmorBlock MaXum module
" these installation instructions
(Note: Cable bases are ordered and shipped separately.)
Publication 1792D-IN055A-EN-P - October 2004
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 5 switches. Line up the small black dot on the switch with the number setting you wish to use.
The rotary switches are read at module power up only. Settings from
64 through 99 cause the module to use the last valid node address stored internally. For example, the last setting was 40. If a change is made to 68, and then you power up, the address will default to 40.
Refer to the following illustration of the node address.
NODE ADDRESS
(00-63 PGM)
8
9
7
6
0 1
5 4
2
3
MSD
8
9
7
6
0 1
5 4
2
3
LSD
Node Address is set at 62; see small black dots.
Bottom View of Module
41462
Install the Module
This module mounts to the following cable bases:
"
1792D-CBFM for KwikLink™ flat media installation
"
"
"
1792D-CB12 for 12mm drop cable installation other optional cable base assembly.
IMPORTANT more information about the cable base, see publication 1792D-IN036 (CB18P) or 1792D-IN009
(CBFM, CB12).
Publication 1792D-IN055A-EN-P - October 2004
6 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug
To install the module:
IMPORTANT
Proper alignment of the screws is necessary to contacts and the cable contacts.
1.
2.
Position the module over the mounted cable base. Align the receptacles in the base.
Tighten the screws with a torque of 8 inch-pounds to secure the module to the base.
Note: Dimensions change according to the cable base and module combination used.
2.7in. (68.6mm)
6.85in. (174mm)
1.9in. (48.26mm)
Cable Base 1792D-CBFM is used for this example.
Ground lug
WARNING
43875
Align the screws to properly secure the module to the base.
location, this equipment must be mounted in a complies with the governing electrical codes.
Publication 1792D-IN055A-EN-P - October 2004
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 7
Connect the Input / Output Cord Sets to the MaXum Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Eight micro caps cover the connectors on your module. Remove the caps and connect your cord sets to the appropriate ports. This product has two inputs or outputs per I/O connector. Use a “Y” splitter cable for access to all I/O connections.
Use the micro caps to cover and seal unused ports. The following illustration shows pinout diagrams for the connectors.
Input Micro-Connector
(view into socket)
#
Pin 1 Sensor Source voltage
#
Pin 2 Input B
#
Pin 3 Return Logic Ground 1
Pin 4 Input A
#
Pin 5 PE
#
Output Micro-Connector
(view into socket)
#
Pin 1 Not Used
#
Pin 2 Output B
#
Pin 3 Auxiliary Power Ground
#
Pin 4 Output A
#
Pin 5 PE
1 Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.
41452
WARNING with power applied to this module or any device on the explosion in hazardous location installations.
Publication 1792D-IN055A-EN-P - October 2004
8 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug
WARNING
Use supply wires suitable for 30°C above surrounding ambient.
IMPORTANT
ATTENTION connections require Class 2 power to operate, the powered by a Class 2 source.
"
"
" tightened to properly seal the connections against leaks and maintain IP67 requirements.
For maximum noise immunity, input and output cable return wires must be properly terminated.
When inputs and outputs are connected in loopback, return wires should be connected together.
I/O cable length should be less than 30 meters.
Publication 1792D-IN055A-EN-P - October 2004
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 9
I/O connectors for this module are shown below.
Connector A
Input 0
Input 1
I-0
I-1
O-0
O-1
Output 0
Output 1
Connector E
Connector B
Input 2
Input 3
I-2
I-3
O-2
O-3
Output 2
Output 3
Connector F
Connector C
Input 4
Input 5
I-4
I-5
O-4
O-5
Output 4
Output 5
Connector G
Connector D
Input 6
Input 7
I-6
I-7
O-6
O-7
Output 6
Output 7
Connector H
Auxilary Power
Logic Status Net/Mod Status
41517
WARNING
This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Output Power and DeviceNet Cables
Output power and DeviceNet cables are described in the installation publications for the cable base assembly of your choice. Refer to the following publications:
1792D-IN009 ArmorBlock MaXum Cable Base Installation
"
"
Instructions
DN-6.7.2 DeviceNet Cable Planning and Installation Manual
Publication 1792D-IN055A-EN-P - October 2004
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 15
The following table describes individual I/O status indicators.
I/O Status Indicators
Function Module Status Indicator Point
Outputs Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
Inputs Green
Green
Module Status blink red
Module Status blink red
Indicator 1
None
Yellow
Orange
Red
Orange
Red
None
Yellow
Red
Blink red
Status
Output not energized
Output energized
Output shorted - auto restart
Output shorted - latching
Output no load - auto restart
Output no load - latching
No valid input
Valid input
Short on input connector 1
Off wire on input connector
1 Only the first LED of each input connector will light as red when twin inputs are used.
Specifications
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE
Input Specifications Maximum Minimum
Inputs per block 8 - 3 wire or dry contact PNP devices or 4 - 4 wire PNP devices
Sensor Source Current (per connector) 100mA total -
Off-wire Sense Current
On-state Voltage
0.5mA
25V dc
-
10V dc
On-state Current
Off-state Voltage
10mA
5V dc -
2mA
Off-state Current
Output Specifications
-
Maximum
1.5mA
Minimum
Outputs per block 8 sourcing outputs labeled O0 through O7
Off Peak Blocking Voltage 30V
On-state Voltage Drop
On-state Current
1V
0.5A
Off-state Leakage
Module Current (all outputs)
1.5mA
4.0A
2.4A
-
-
-
-
-
10V
No Load Sense Current (On-state) 0.18A
-
Publication 1792D-IN055A-EN-P - October 2004
16 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE
General Specifications Maximum
DeviceNet Power Voltage
Current
25V dc max
150mA max (no sensors)
Auxiliary Power
Indicators
Communication Rate
Dimensions (assembled to base) inches - (Millimeters)
Operational Temperature
Storage Temperature
Relative Humidity
Vibration
Minimum
11V dc min
50mA per sensor)
Logic Status - green
Point LED - yellow/orange/red
"
"
"
125Kbps @ 500 meters(1600 feet) for thick cable, flat media length 375 meters (1230 feet)
250Kbps @ 200 meters(600 feet) for thick cable, flat media length 150 meters (492 feet)
500Kbps @ 100 meters (330 feet) for thick cable, flat media length 75 meters (246 feet)
1.9H x 2.7W x 6.9D
(48)H x (69)W x (174)D
IEC 60068-2-1 (Test Ad, Operating Cold),
#
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-25 to 60 ° (-13 to 140 ° F)
#
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
#
#
Shock):
#
-25 to 80 ° (-13 to 176 ° F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):
#
5 to 95% non-condensing
IEC 60068-2-6 (Test Fc, Operating):
#
10g @ 10-500 Hz
Publication 1792D-IN055A-EN-P - October 2004
ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 17
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE
General Specifications (continued)
Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
#
30g
Non-Operating Shock
Emissions
ESD Immunity
Radiated RF Immunity
EFT/B Immunity
Surge Transient Immunity
Conducted RF Immunity
Conductors
Enclosure
Supply Voltages/Voltage Ranges
Supply Power/Current Ratings
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
#
50g
CISPR 11:
#
Group 1, Class A
IEC 61000-4-2:
#
6kV contact discharges
#
8kV air discharges
IEC 61000-4-3:
#
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
#
10V/m with 200Hz 50% Pulse 100%AM at 900MHz|
#
10V/m with 200Hz 50% Pulse 100%AM at 1890MHz
IEC 61000-4-4:
#
±2kV at 5kHz on power ports
#
±2kV at 5kHz on signal ports
#
±2kV at 5kHz on communications ports
IEC 61000-4-5:
#
±1kV line-line(DM) and ±2 line-earth(CM) on power ports
#
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
#
±2kV line-earth(CM) on communications ports
IEC 61000-4-6:
#
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Publication DN-6.7.2
Meets IP67
DNet Power: 11V dc to 25V dc;
#
Auxiliary Power: 10V dc to 30V dc
DNet current:1.6A;
#
Input current: 50mA;
#
Output power: 60VA DC-13/SQ;
Auxiliary current:4A
#
Tested to withstand 750V dc for 60 seconds
Wire Size
Wiring Category 1 2 - on signal ports
#
#
2 - on communications ports
Publication 1792D-IN055A-EN-P - October 2004
18 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE
General Specifications (continued)
Certifications: 2
#
(when product is marked)
CSA CSA Certified Process Control Equipment
#
CSA CSA Certified Process Control Equipment for
#
CE
Class I, Division 2 Group A,B,C,D Hazardous
#
Locations
European Union 89/336/EEC EMC Directive,
# compliant with:
#
EN 50082-2; Industrial Immunity
#
EN 61326; Meas./Control/Lab., Industrial
#
Requirements
#
EN 61000-6-2; Industrial Immunity
#
EN 61000-6-4; Industrial Emissions
#
EN 61131-2; Programmable Controllers
#
(Clause 8, Zone A & B)
#
C-Tick Australian Radiocommunications Act,
# compliant with:
#
AS/NZS CISPR 11; Industrial Emissions
#
ODVA ODVA conformance tested to DeviceNet
# specifications
1. Use this Conductor Category information for planning conductor routing. Refer to Publication
1770-4.1, "Industrial Automation Wiring and Grounding Guidelines".
2. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
This product has been tested at an Open DeviceNet Vendor
Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test. Please contact the by ODVA independent test labs for further details.
Publication 1792D-IN055A-EN-P - October 2004