M-System R1C-GH is a thermocouple and DC input module designed for industrial automation. It offers 16-bit signed binary data output with high accuracy, making it suitable for precise temperature and voltage measurements. The module supports a variety of thermocouple types and DC input ranges, providing versatility for different applications. With its built-in cold junction compensation, it ensures accurate temperature readings. Additionally, R1C-GH can be easily integrated into CC-Link networks, allowing for efficient data exchange and remote monitoring.
Advertisement
Advertisement
INSTRUCTION MANUAL
THERMOCOUPLE & DC INPUT MODULE
( 16 points; CC-Link Ver.1.10 / Ver.2.00 )
MODEL
R1C-GH
Contents
2. GENERAL DESCRIPTION ........................................................................... 3
4. HARDWARE SPECIFICATIONS .................................................................. 4
5. COMPONENT IDENTIFICATIONS ............................................................... 5
7. TERMINAL CONNECTIONS ........................................................................ 6
8. INPUT RANGE SELECTING ........................................................................ 8
9. CONNECTING DATA LINK WIRES .............................................................. 9
10. SELECTING CC-LINK VERSION ................................................................. 9
12. PARAMETERS SETTING BY PLC PROGRAM ..........................................11
15. ADJUSTMENT PROCEDURE .....................................................................13
17. LIGHTNING SURGE PROTECTION ...........................................................13
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 1 / 13
R1C-GH
1. BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
This product is for use in general industrial environments, therefore may not be suitable for applications which require higher level of safety (e.g. safety or accident prevention systems) or of reliability (e.g. vehicle control or combustion control systems).
For safety, installation and maintenance of this product must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
Thermocouple & DC input module (body + CJC sensor) ...............................................................................(1)
Terminating resistor (110 Ω, 0.5 W) ................................................................................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
The R1C is programmable using the R1X Configurator Software (model: R1CON). For detailed information on the PC configuration, refer to the R1CON instruction manual. The R1CON PC Configurator Software is downloadable at M-System’s web site: http://www.m-system.co.jp.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 2 / 13
2. GENERAL DESCRIPTION
The model R1C-GH, Thermocouple & DC Input Module, is used as remote device for CC-Link.
Model number and suffix codes are designated as follows:
R1C−GH2T−x
MODEL
I / O TYPE
GH2 : Thermocouple or DC input, 16 points
FIELD TERMINAL TYPE
T : M3 screw terminals
POWER INPUT
M2 : 100 – 240V AC
R : 24V DC
R1C-GH
The R1C accepts 16 points of thermocouple and/or DC input signals. It converts analog inputs (0 – 100%) proportionally into 16-bit signed binary signals.
CC-Link Version 1.10 and 2.00 can be switched at the startup.
This instruction manual explains hardware specifications, component identification, and wiring instructions, etc.
3. POINTS OF CAUTION
■ GENERAL PRECAUTIONS
• Before you remove the module, turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the module inside proper housing with sufficient ventilation.
• Do not install the module where it is subjected to continuous vibration. Do not subject the module to physical impact.
• Environmental temperature must be within -5 to +60°C (23 to 140°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with cables, etc.
■ WIRING
• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tightly.
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The module is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 3 / 13
R1C-GH
4. HARDWARE SPECIFICATIONS
ITEM
Analog input
Sampling rate
Protocol
Digital output
Accuracy
CJC error
Number of inputs
Isolation
Required nodes
Power input, CC-Link
Input
Configurator
Noise immunity
Dielectric strength
Insulation resistance
Weight
Power input
Power consumption
SPECIFICATIONS
±20V DC, ±5V DC, ±0.8V DC, ±0.2V DC, ±50mV DC, ±10mV DC (input resistance 300 kΩ)
Approx. 150 msec. / 16 points
CC-Link, Ver.1.10 / Ver. 2.00
16-bit signed binary (14 bits for data)
Input Type
±20V
±5V
A/D Conversion Range (decimal)
±20000
±5000
±1V
±0.8V
±0.2V
±50mV
±10mV
Thermocouple
DC Input
±10000
±8000
±20000
±5000
±10000
Temperature × 10
±0.3%
T/C Type
Thermocouple (PR)
Usable Range
(°C)
0 to 1770
Accuracy
(%)
±0.5
Conformance Range
(°C)
400 to 1770
K (CA)
E (CRC)
J (IC)
T (CC)
-270 to +1370
-270 to +1000
-210 to +1200
-270 to +400
±0.3
±0.7
±0.7
±1.0
0 to 1370
0 to 1000
0 to 1200
0 to 400
B (RH)
R
S
C (WRe 5-26)
100 to 1820
-50 to +1760
-50 to +1760
0 to 2320
±0.7
±0.7
±0.7
±0.7
700 to 1820
400 to 1760
400 to 1760
0 to 2320
N
U
L
≤ ±3°C at 20°C ±10°C
P (Platinel II)
16
-270 to +1300
-200 to +600
-200 to +900
0 to 1395
±0.5
±0.5
±0.3
±0.5
0 to 1300
0 to 600
0 to 900
0 to 1395
Input to CC-Link (FG) to power
CC-Link Ver. 1.10 4 (RX/RY 32 points each, RWr/RWw each 16 points)
CC-Link Ver. 2.00 1 (RX/RY 64 points each, RWr/RWw each 16 points)
Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm 2 (AWG 24 to 12), stripped length 7 mm)
M3 screw terminals (torque: 0.6 N∙m)
2.5 dia. miniature jack; RS-232-C level
1000 Vp-p, 1 µsec.
2000V AC @ 1 minute (input to CC-Link [FG] to power to ground [FG1])
≥100 MΩ with 500V DC (input to CC-Link [FG] to power)
400 g (0.88 lb)
R1C-GH2T-M2
R1C-GH2T-R
R1C-GH2T-M2
R1C-GH2T-R
85 – 264V AC, 47 – 66 Hz
24V DC ±10%
Approx. 10VA
Approx. 7W
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 4 / 13
R1C-GH
5. COMPONENT IDENTIFICATIONS
A B C D E F G
T8 T7 T6 DA DB DG FG SLD
H
NAME FUNCTIONS
A Power terminal block For power input
B Network terminal block For wiring to CC-Link
SETTING
C Baud rate setting
D
E
F
G
H
Station No. setting
Status indicator LED
Power LED
Configurator jack
Specifications
BAUD RATE
2
3
0
1
4
Other than 0 – 4
156 kbps (factory default)
625 kbps
2.5 Mbps
5 Mbps
10 Mbps
Not valid; L ERR. turns on as a transmission error.
Ver. 1.10: Selectable within 1 – 61. (factory set to: 00)
Ver. 2.00: Selectable within 1 – 64. (factory set to: 00)
ID (color)
L RUN (red)
L ERR. (red)
FUNCTIONS
ON:
Blinking :
OFF:
ON :
Blinking :
OFF:
ON when transmitting
Normal communication
Transmission data error
Communication down (time-out error)
Transmission data error
Transmission data error
Normal transmission
SD (red)
RD (red)
ID (color)
PWR (green)
ON when receiving
FUNCTIONS
ON:
Blinking, high speed:
Blinking, low speed:
Abnormality
CC-Link Ver. 1.10
CC-Link Ver. 2.00
Master Version 2.00 with long ON time
Master Version 1.10 with long OFF time
2.5 dia. miniature jack; RS-232-C level
Display(s) serial No., model No., etc.
6. INSTALLATION
■ DIN RAIL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor.
Position the upper hook at the rear side on the DIN rail and push in the lower. Push back the DIN rail adaptor.
DIN Rail
35mm wide
■ WALL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor.
Refer to “EXTERNAL DIMENSIONS.” DIN Rail Adaptor
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 5 / 13
R1C-GH
7. TERMINAL CONNECTIONS
Connect the module referring to the connection diagram.
Attach the CJC sensor together with input wiring to the input screw terminals. The sensor is calibrated for the particular module and not interchangeable with another. Check the serial numbers of the module and sensor.
7.1. EXTERNAL DIMENSIONS
175 (6.89)
165 (6.50) 15.5 (.61)
3–5 (.20) dia.
MTG HOLES
DIN RAIL
35 mm wide
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
163 (6.42)
6.2 (.24)
36–M3 INPUT TERMINALS
FOR WALL MOUNT.
CJC SENSOR (model: CJM)
3 (.12)
40 (1.57) [6 (.24)] unit: mm (inch)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 6 / 13
7.2. CONNECTION DIAGRAM
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
INPUT 16
DC INPUT
+
–
CJC
Sensor
CC-Link VERSION SELECTOR INPUT
+
–
34
35
36
30
31
32
33
25
26
27
28
29
21
22
23
24
16
17
18
19
20
13
14
15
10
11
12
1
2
3
4
5
6
7
8
9
–
+
–
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
T/C INPUT
+ ext. wire
+
–
–
+
–
+
Comm.
Circuit
DA
DB
DG
SLD
FG
To Other
CC-Link Devices
Power
Circuit
T6
T7
T8
U (+)
V (–)
FG1
POWER
Input
Circuit
JACK CONFIGURATOR
Note 1: This device is not designed to cancel noise included in the input signals.
Be careful to eliminate such noise by using shielded cables.
Note 2: Be sure to maintain the same potential at all the common negative terminals for DC input.
Note 3: CC-Link version selector input is valid only at the moment of the power turned on.
Firmware version 0B.00 or higher. Use the R1X Configurator Software (model: R1CON)
or consult M-System to confirm the firmware version.
Caution: FG1 terminal is NOT a protective conductor terminal.
R1C-GH
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 7 / 13
R1C-GH
8. INPUT RANGE SELECTING
Select switches to match the input signal according to the table below. For fine range setting, the R1X
Configurator Software (model: R1CON) including a dedicated cable is required.
7
8
5
6
3
4
1
2
SW411
O
N
SW401 SW308 SW307 SW306
SW408 SW407 SW406
7
8
5
6
3
4
1
2
SW311 SW305 SW304 SW303 SW302
O
N
SW301
SW405 SW404 SW403 SW402
INPUT
Thermocouple
Voltage input, 0.8V or less
Voltage input, above 0.8V (*)
SWITCHES
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SETTING
Set to position “1”
OFF
Set to position “1”
ON
Set to position “3”
ON
(*) Factory setting unless specific input types and ranges are specified when ordering
NOTES
Attenuation OFF
Attenuation OFF
Attenuation ON
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 8 / 13
9. CONNECTING DATA LINK WIRES
The following explanations apply to the wires connecting the R1C to the Master Unit.
9.1. TWISTED-PAIR CABLE
The following types of wire are recommended for connecting the R1C to the Master Unit.
KURAMO ELECTRIC FANC-SB 0.5 mm 2 × 3 or equivalent
Sheath
DA blue white yellow
Shielding
Aluminum Tape
DB
DG
Grounding
9.2. POINTS OF CAUTION IN HANDLING WIRES
DO NOT apply extraordinary forces to the wires as explained in the following:
1) DO NOT SQUEEZE the wires with a sharp-edged tool.
2) DO NOT TWIST the wires extraordinarily.
3) DO NOT PULL the wires extraordinarily tight.
4) DO NOT TRAMPLE on the wires.
5) DO NOT PUT objects onto the wires.
6) DO NOT DAMAGE the insulation tube of wires.
9.3. WIRING DIAGRAM
Connect the R1C to the Master Unit as shown below.
MASTER UNIT
TERMINATOR
DA blue
DB white
DG yellow
SLD
FG
R1C
DA
DB
DG
SLD
FG
I/O UNIT
DA
DB
DG
SLD
FG
R1C-GH
10. SELECTING CC-LINK VERSION
The R1C-GH is usable both for CC-Link Ver. 1.10 and Ver. 2.00. The contact status of the version selector input at the moment of the power supplied determines the CC-Link version. Required node numbers depends upon the version No as shown below. For use with Ver. 2.00, set the cyclic expansion to ‘4’ at the
Master Unit.
VERSION SELECTOR INPUT
ON
OFF
CC-LINK VERSION
Ver. 2.00
Ver. 1.10
REQUIRED NODES
1
4
SELECTABLE STATION NO.
1 through 64
1 through 61
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 9 / 13
R1C-GH
11. DATA LIST
11.1. REMOTE I/O
For CC-Link Ver.1.10, the R1C occupies 4 nodes according to the number of I/O channels, for CC-Link
Ver.2.00, it occupies 1 node. Regardless of the number of nodes, for CC-Link Ver.1.10, 32 bits are assigned to each of input and output for sending to/receiving from the Master Unit, for CC-Link Ver.2.00, 64 bits are assigned. One (1) bit among RXxB* is used as remote device (R1C) READY signal, turned ON when the
R1C is in normal operation.
• CC-Link Ver.1.10
*x = (Station No. × 2 – 1) H
[example] Station No. = 9
9 × 2 – 1 = 17 ➡ 11H
READY signal is input at RX11B.
• CC-Link Ver.2.00
*x = (Station No. × 4 – 1) H
[example] Station No. = 9
9 × 4 – 1 = 35 ➡ 23H
READY signal is input at RX23B.
11.2. ASSIGNING REMOTE REGISTERS
The R1C does not use the remote registers for the direction from the Master to Remote (RWwn to RWwn+15).
The table below shows the data assignment of those for the direction from the Remote to Master.
DIRECTION
R1C
Master
ADDRESS
RWrn + 0
RWrn + 1
RWrn + 2
RWrn + 3
RWrn + 4
RWrn + 5
RWrn + 6
RWrn + 7
RWrn + 8
RWrn + 9
RWrn + 10
RWrn + 11
RWrn + 12
RWrn + 13
RWrn + 14
RWrn + 15
CONTENTS
Ch. 1 digital output
Ch. 2 digital output
Ch. 3 digital output
Ch. 4 digital output
Ch. 5 digital output
Ch. 6 digital output
Ch. 7 digital output
Ch. 8 digital output
Ch. 9 digital output
Ch. 10 digital output
Ch. 11 digital output
Ch. 12 digital output
Ch. 13 digital output
Ch. 14 digital output
Ch. 15 digital output
Ch. 16 digital output
DEFAULT
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11.3. A/D CONVERSION
1) OUTPUT IN NORMAL CONDITIONS
Analog input signal (0 – 100%) from signal conditioners is converted proportionally into digital data, provided to the Master Unit.
2) OUTPUT IN AN ABNORMALITY
When an abnormality such like CPU error, STOP, time-out occurs at the PLC, the output signal of the R1C is maintained as HOLD (no clearing output signal, keeping the value just before the abnormality).
When the PLC recovers to normal operation and the R1C receives new data, the output restarts changing.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 10 / 13
R1C-GH
12. PARAMETERS SETTING BY PLC PROGRAM
12.1. GENERAL DESCRIPTION
The ladder diagram below shows a program example assuming that the master station’s first I/O number is X/Y20 to 3F.
For detailed information, refer to users manuals for the PLC CPU and the Master Unit.
X0020 X002F
PLS M0
M0
SET M1
M1
MOV
MOV
D0
D1
MOV D2
T0 H0002 H0001 D0 K3
MOV D3
T0 H0002 H0006 D3 K1
Number of connected modules
Number of retries
Number of automatic return modules
Operation specification when the CPU is down
M1
Only when required
M1
MOV
MOV
MOV
MOV
MOV
MOV
MOV
MOV
D8
D9
D10
D11
T0 H0002 H0010 D4 K8
D4
D5
D6
D7
MOV
* 1
D13
Reserved station specification
Invalid station specification
Station information
(set for the number of connected modules.)
MOV D
T0 H0002 H0020 D13 K
RST M1
* 1. 14xx
where xx = R1C Station No.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 11 / 13
13. TROUBLESHOOTING
Basic troubleshooting methods are explained in this section.
For problems concerning the PLC CPU and Master Unit, consult users manuals for these units.
R1C-GH
13.1. L ERR. INDICATOR BLINKING
CHECK
Have you changed the station No. and/or baud rate settings during normal operation?
TROUBLESHOOTING
Return these settings to the state when the unit operated normally.
13.2. L ERR. INDICATOR ON
CHECK
Are the station No. and/or baud rate settings correct?
TROUBLESHOOTING
Set them correctly.
13.3. L RUN INDICATOR OFF
Consult the users manual for the Master Unit.
13.4. UNABLE TO READ/WRITE DIGITAL VALUES?
CHECK
Is the L RUN indicator OFF?
Is the L ERR. indicator blinking or ON?
Is the RUN indicator on the PLC CPU blinking or OFF?
Is the RUN indicator on the Master Unit OFF?
Are the RD/SD indicators on the Master Unit ON?
Are the wires for analog I/O properly connected to respective terminals? No wire breakdown?
Remove analog input wires and apply test voltage to the terminals (e.g. Use a dry cell). Try to read out digital value.
TROUBLESHOOTING
Refer to Section “13.3. L RUN INDICATOR OFF”.
Consult the users manual for the Master Unit.
Consult the users manual for the CPU.
Consult the users manual for the Master Unit.
Consult the users manual for the Master Unit.
Check these wires visually or check conductivity for each pair of wires.
If the digital value is read out normally, there are possibilities of noise interference via external wires. Check wiring and grounding.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 12 / 13
R1C-GH
14. CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input: Check supply voltage across the terminals T6 – T7.
3) Input: Check that the input is within 0 – 100% of full-scale.
4) DIP SW setting: Check that all switches are set correctly.
15. ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered specifications, therefore you usually do not need any calibration.
16. MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the module for at least 10 minutes. Apply 0%, 25%, 50%, 75% and 100% input signal. Check that the A/D conversion data for the respective input signal remains within accuracy described in the data sheet. When the A/D conversion data is out of tolerance, contact Factory or M-System’s local representative.
17. LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for protection against induced lightning surges.
Please contact M-System to choose appropriate models.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 13 / 13