INSTRUCTION MANUAL
DEVIATION ALARM
MODEL
AYDV
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) ..(1)
Input resistor is provided only with current input type.
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
COMPONENT IDENTIFICATION
Body
Specifications
SET MONITOR
-5–+5V(-50–+50
%)
M•UNIT
Model
AYDV
No.1
No.2
No.1
SET
No.2
SET
COM
Base Socket
Input Resistor
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
■ FRONT PANEL CONFIGURATION
Setpoint 1 Monitor
Setpoint 2 Monitor
COM.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
AC power : Rating ±10%, 50/60 ±2 Hz, approx. 2VA
DC power : Rating ±10%, approx. 1.3W or 85 – 150V, approx. 1.3W for 110V rating
Setpoint 1 Adj. & LED
Setpoint 2 Adj. & LED
■ GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.
• Explanations
Setpoint 1 and Setpoint 2 Adjustments are used to set the alarm setpoints.
A -5 – +5V DC is output at the setpoint monitor jacks across the COM jack, proportional to the setpoint -50 – +50%.
The LEDs turn on when the coil for each relay is energized.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
• Examples
For setting the setpoint 1 relay to trip above 20% deviation, turn Setpoint 1 Adj. until you read 2.0V at Setpoint 1
Monitor.
INSTALLATION
Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket.
■ WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the DIN rail adaptor utilizing a minus screwdriver and pull.
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■ WALL MOUNTING
Refer to “EXTERNAL DI-
MENSIONS.”
Shape and size of the base socket are slightly different with various socket types.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1615 Rev.7 P. 1 / 3
AYDV
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the front of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
■ EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
20 (.79)
DIN RAIL
35mm wide
8 7 6 5
4
50 (1.97)
■ CONNECTION DIAGRAM
INPUT 2 (ref)
INPUT 1 (meas)
+
–
R
+ 4
*
5
6
**
**
11 HI
10 LO
9 COM
OUTPUT 1
3 HI
2 LO OUTPUT 2
1 COM
7
8
U(+)
POWER
V(–)
* Input shunt resistor attached for current input.
** Relay status for output code “1”, at power OFF.
103 (4.06)
132 (5.20)
2 – 4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11 – M3.5
SCREW
[3.3 (.13)]
9
10 11
40 (1.57)
50 (1.97)
3
1 2
• When mounting, no extra space is needed between units.
■ TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
8 7 6 5
4
9
10 11
3
1 2
Input shunt resistor attached for current input.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1615 Rev.7 P. 2 / 3
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of the full-scale.
4) Alarm operations: Check the alarm operations referring to the figure below.
5) Output load: Check that the output load is 380 V AC/120
VA or 125 V DC/30 W at the maximum. For maximum relay life with inductive load, external protection is recommended.
AYDV
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Setpoint
Increase the input signal from a value lower than the setpoint and check that the trip point remains within the accuracy described in the data sheet.
• Lo Setpoint
Decrease the input signal from a value higher than the setpoint and check that the trip point remains within the accuracy described in the data sheet.
When the trip points are out of tolerance, contact M-System’s Sales Office or local representatives.
ALARM RELAY OPERATIONS
Output 1
(9–10)ON
(9–11)ON
Output 2
(1–2)ON
(1–3)ON
Deviation
(%) –50 ▲
Output 2
Setpoint
0 ▲
Output 1
Setpoint
Trip Operation in Power Failure
• Output 1 : (9 – 10) turn ON with code 1
(9 – 11) turn ON with code 2
• Output 2 : (1 – 2) turn ON with code 1
(1 – 3) turn ON with code 2
+50
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for protection against induced lightning surges. Please contact
M-System to choose appropriate models.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1615 Rev.7 P. 3 / 3