Trane Tracer AdaptiView User Manual 92 Pages
Trane Tracer AdaptiView User Manual
advertisement
▼
Scroll to page 2
of
92
User Guide Tracer® AdaptiView™ Display for CenTraVac™ Water-cooled Chillers X39641071060 SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. March 2020 CTV-SVU01G-EN Warnings, Cautions, and Notices Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. The three types of advisories are defined as follows: WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTIONs Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices. Indicates a situation that could result in equipment or property-damage only accidents. NOTICE WARNING Proper Field Wiring and Grounding Required! Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. WARNING Personal Protective Equipment (PPE) Required! Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below: ©2020Trane • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE. • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions. • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE. CTV-SVU01G-EN WARNING Follow EHS Policies! Failure to follow instructions below could result in death or serious injury. • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies. • Non-Trane personnel should always follow local regulations. Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change. Trademarks All trademarks referenced in this document are the trademarks of their respective owners. Factory Training Factory training is available through Trane University™ to help you learn more about the operation and maintenance of your equipment. To learn about available training opportunities contact Trane University™. Online: www.trane.com/traneuniversity Phone: 855-803-3563 Email: [email protected] Revision History CTV-SVU01G-EN • Added LLID Binding section. • Updated “Evaporator settings and status points (Simplex)”, “Condenser settings and status points (Simplex)”, “Motor settings and status points (Simplex)”, “Condenser data” and “Evaporator data” tables in Appendix A — Data for CenTraVac Simplex Chillers. 3 Table of Contents Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Equipment Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Touchscreen Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Chiller Status Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Main Display Area/Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Main Display Area/Screen Saver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Component Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Main Menu Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Stopping/Restarting Chiller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Stopping the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Restarting the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 The Alarms Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm Icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Active and Historic Alarm Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sorting Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 21 21 21 Resetting Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Additional Alarm Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 The Reports Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Viewing the Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Viewing the ASHRAE Chiller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Creating and Viewing a Custom Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Editing a Custom Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 About this Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Viewing Chiller Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Simplex Chillers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duplex Chillers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Purge Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 26 28 31 Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 The Data Graphs Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Viewing Data Graphs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Changing the Scales on Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Creating Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Creating a Custom Data Graph From a Default Data Graph. . . . . . . . . . . . . . . . . . 35 4 CTV-SVU01G-EN Table of Contents Creating a Custom Data Graph With No Previously Defined Data Graph Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Editing Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Deleting a Custom Data Graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Equipment Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 The Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Viewing and Changing Equipment Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Chiller Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Service Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Setpoint Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Setpoint Source Arbitration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Changing the Setpoint Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using the Setpoint Source Button in the Chiller Status Area. . . . . . . . . . . . . . . . . From the Setpoint Source Button on the Chiller Settings Screen. . . . . . . . . . . . . From an Arbitrated Setpoint Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 44 44 45 Feature Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Chilled Water Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Purge Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Manual Control Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Changing a Manual Control Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Viewing and Changing Display Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Viewing and Changing the Language Preference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Viewing and Changing Date and Time Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Clean Touchscreen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Security Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Disabling Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Enabling Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Logging Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 LLID Binding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Appendix A: Data for CenTraVac Simplex Chillers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Component Screen Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 CTV-SVU01G-EN 5 Table of Contents Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASHRAE Chiller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Items Available to Include in Custom Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 65 67 69 Data Graph Data Points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Data Points Used in Default Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Data Points in Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Appendix B: Data for CenTraVac Duplex Chillers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Component Screen Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASHRAE Chiller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Items Available to Include in Custom Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data Graph Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 79 80 82 83 Data Points Used in Default Data Graphs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Data Points in Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 6 CTV-SVU01G-EN Product Overview The Tracer® AdaptiView™ display provides a means for viewing data and for making operational changes on the following types of chillers: • Simplex (single compressor) CenTraVac™ chiller models • Duplex™ (dual compressor) CenTraVac™ chiller models The purpose of this guide is to assist you in using the Tracer® AdaptiView™ display. This guide describes how to access the screens and the types of information that appear on the screens. Equipment Description The basic equipment features of the Tracer® AdaptiView™ display are described here. Hardware The Tracer® AdaptiView™ display is mounted on or near the chiller control panel. It can be attached to the chiller by an arm that can extend 11 inches. Five pivot points enable full articulation as described in the following specifications and in the figure: Figure 1. The Tracer AdaptiView mounting arm • Two horizontal pivots points 90º right or left (180º total) • Two vertical pivots points: 90º degrees up or down (180º total) • Rotation: 135º clockwise and 135º counterclockwise (270º total) Screen Characteristics The 12.1-inch color touch-screen display shows data in either inches and pounds (I-P) or standard international (SI) units, and in one of twenty-seven available languages. Animated color graphics indicate the status of the chiller and its components. CTV-SVU01G-EN 7 Product Overview DC Power The Tracer® AdaptiView™ display receives 24 Vdc power through its power cable. The Tracer® UC800 controller must be powered on. Communication A separate ethernet cable provides communication between the Tracer® AdaptiView™ display and the Tracer® UC800 controller. Alarms are communicated immediately upon detection. Touchscreen Guidelines The touch screen registers the downward pressure of a touch. However, touching with increased pressure has no effect. Use your fingers to operate the touch screen. Do NOT use a pen or pencil point, or any other sharp or pointed object that might scratch the screen surface. If you apply and hold pressure at more than one point, the touch screen registers only the first touch. For example, if you press a finger on an area of the screen that is not touch sensitive, pressing a sensitive area with another finger will not register. Holding on to the screen with your hand can cause unintended navigation, such as from thumb or palm pressure. Related Information Additional information on CenTraVac™ chillers with Tracer® AdaptiView™ control can be found in these documents: • CVHE-SVX02*-EN (Installation, Operation, and Maintenance: CVHE, CVHF, and CVHG WaterCooled CenTraVac Chillers with Tracer AdaptiView Control ) • CDHF-SVX01*-EN (Installation, Operation, and Maintenance: CDHF and CDHG Water-Cooled CenTraVac Chillers with Tracer AdaptiView Control ) • CVHH-SVX001*-EN (Installation, Operation, and Maintenance: CVHH Water-Cooled CenTraVac Chillers with Tracer AdaptiView Control ) • CDHH-SVX001*-EN (Installation, Operation, and Maintenance: CDHH Water-Cooled CenTraVac Chillers with Tracer AdaptiView Control) • PRGF-SVX001*-EN (Installation, Operation, and Maintenance: EarthWise Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-123 Refrigerant) • PRGG-SVX001*-EN (Installation, Operation, and Maintenance: Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-514A Refrigerant) • CTV-SVD03*-EN (Diagnostics Manual: Diagnostic Descriptions, Troubleshooting Tables, and Control Component Overview for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control) • CTV-SVP02*-EN (Programming Guide: Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control) • TTU-SVN01*-EN (Getting Started Guide: Tracer TU Service Tool) Screen Overview The touch-sensitive areas of the Tracer® AdaptiView™ display screen are described in detail in this section. 8 CTV-SVU01G-EN Product Overview Figure 2. Tracer AdaptiView display (Home screen for Simplex chillers is shown) 1 2 3 1. “Chiller Status Area,” p. 9 2. “Main Display Area/Home Screen,” p. 10 This area is different between the Simplex chiller models and the Duplex™ chiller models. Table 2, p. 11 describes the differences. 3. “Main Menu Area,” p. 17 Chiller Status Area The chiller status area (shown as Location 1 in “Screen Overview,” p. 8) remains visible from every screen on the Tracer® AdaptiView™ display. Basic information about chiller status and control appears on the face of the buttons and touch targets. When touched, the buttons and touch targets open other screens that provide more information and control access. The following table provides the details. Table 1. Chiller status area Button/Touch target Chiller status button Description The top-level operating mode of the chiller appears on the chiller status button. Touch this button to view the Chiller Operating Mode screen. Note: For more information, refer to “Reports,” p. 65 . Alarm indicator button If an active alarm exists, the alarm indicator button appears with the alarm severity indicated on it. If there is more than one alarm, the most severe appears. You can touch this button as an alternate way to view the Alarms screen. Note: For more information, refer to “Alarms,” p. 20. Manual override button If a manual override exists but no active alarm exists, a manual override button appears in the same location as the alarm indicator button. If neither an alarm nor a manual override exist, no button appears. If a manual override exists, you can touch this button as an alternate way to view the Manual Control Settings screen. Note: For more information, refer to “Manual Control Settings,” p. 47. CTV-SVU01G-EN 9 Product Overview Table 1. Chiller status area (continued) Button/Touch target Description The water temperature touch target shows one of the following, depending on whether the chiller is in heating or cooling mode (also referred to as the Active Control Type): Water temperature touch target • If the Active Control Type is chilled water, the Evaporator Leaving Water Temperature appears and the touch target links to the evaporator component screen. • If the Active Control Type is hot water, the Condenser Leaving Water Temperature appears and the touch target links to the condenser component screen. • If the Ice Building mode is Active, the Evaporator Entering Water Temperature appears and the touch target links to the evaporator component screen. Note: For more information on the evaporator and condenser component screens, refer to “Component Screens,” p. 14. Setpoint source touch target The current setpoint source is highlighted in green on the setpoint source touch target. Touch this target to view the Setpoint Source screen, where you can change the setpoint source. Note: For more information, refer to “Changing the Setpoint Source,” p. 44 . Auto/Stop buttons Auto and Stop are toggle buttons: One appears raised when the other is appears depressed. • Touch Auto to activate the chiller startup process. • Touch Stop to active the chiller shutdown process. Note: For more information, refer to “Stopping/Restarting Chiller Operation,” p. 18. Main Display Area/Home Screen All screens appear within the main display area (shown as Location 2 shown in the figure in “Screen Overview,” p. 8). Home screen: Chiller status information The home screen (shown in “Screen Overview,” p. 8) provides the most frequently needed chiller status information on “touch targets” (the entire white rectangular areas) for each chiller component. Touching any touch target displays a screen containing more chiller status information related to each component (refer to “Component Screens,” p. 14). Each touch target that appears on the home screen is described in the following table, including those for Simplex chillers, and those for Duplex™ chillers. In the lower right corner of the home screen, you can view the date and time as well as additional chiller information. For details, see the last three rows of the following table. 10 CTV-SVU01G-EN Product Overview Table 2. Home screen touch targets and buttons Touch target Description Compressor for Simplex chillers This compressor touch target chiller provides information on: • Compressor Running Status • Differential Oil Pressure Touch anywhere on the touch target to view the Compressor component screen. Compressor for Duplex Chillers This compressor touch target provides information on: • Compressor Running Status Ckt1 • Compressor Running Status Ckt2 Touch anywhere on the Ckt1 side of the touch target to view the Circuit 1 Compressor component screen. Touch anywhere on the Ckt2 side of the tough target to view the Circuit 2 Compressor component screen. Condenser for all chiller models This condenser touch target provides information on: • Condenser Leaving Water Temperature • Condenser Entering Water Temperature • Active Hot Water Setpoint (if Hot Water Control is available) • Condenser Water Flow Status (animation in graphic indicates if condenser is running) Touch anywhere on the touch target to view the Condenser component screen. Evaporator for all chiller models The evaporator touch target provides information on: • Evaporator Leaving Water Temperature • Evaporator Entering Water Temperature • Active Chilled Water Setpoint (if Chilled Water Control is available) or Active Ice Termination Setpoint in Ice Building mode) • Evaporator Water Flow Status (animation in graphic indicates if evaporator is running) Touch anywhere on the touch target to view the Evaporator component screen. Motor for Simplex chillers The motor touch target provides information on: • Average line current • Frequency (if adjustable-frequency drive is configured) Touch anywhere on the touch target to view the Motor component screen. CTV-SVU01G-EN 11 Product Overview Table 2. Home screen touch targets and buttons (continued) Touch target Description Motor for Duplex chillers The motor touch target provides information on: • Average line current Ckt1 • Average line current Ckt2 Touch anywhere on the Ckt1 side of the touch target to view the Circuit 1 Motor component screen. Touch anywhere on the Ckt2 side of the tough target to view the Circuit 2 Motor component screen. Purge for Simplex chillers The purge touch target provides information on: • Purge top level mode Touch anywhere on the touch target to view the Purge component screen. Note: The Purge button is not displayed if Purge is not installed. Purge for Duplex chillers The purge touch target provides information on: • Purge top level mode Ckt1 • Purge top level mode Ckt2 Touch anywhere on the Ckt1 side of the touch target to view the Circuit 1 Purge component screen. Touch anywhere on the Ckt2 side of the tough target to view the Circuit 2 Purge component screen. Note: The Purge button is not displayed if Purge is not installed. Information button and chiller and display names Touch the “i” or the chiller or display name to view the About this Chiller screen. Note: For more information, see “About this Chiller,” p. 26 . Custom Report Touch the Custom Report button to view the Custom Report screen. Note: For more information, see “Creating and Viewing a Custom Report,” p. 24. Home screen: Animated Graphic A graphic of a chiller appears on the home page. The graphic uses animation to indicate the operational status of the chiller. If the chiller is running, animation appears within the cutaway areas of the compressor, the evaporator, and the condenser, as shown in the figure in “Screen Overview,” p. 8. If the chiller is not running, the components are enclosed and are not animated. The chiller graphic that appears on the screen also indicates the type of chiller that the Tracer® AdaptiView™ display is monitoring. One of the following graphics will appear in the display for Simplex chillers: 12 • 2-stage compressor, cooling only (as shown in the figure in “Screen Overview,” p. 8) • 2-stage compressor with auxiliary condenser • 2-stage compressor with heat recovery • 3-stage compressor, cooling only • 3-stage compressor with auxiliary condenser • 3-stage compressor with heat recovery CTV-SVU01G-EN Product Overview One of the following graphics will appear on the display for Duplex™ chillers: CTV-SVU01G-EN • 2–stage compressor • 3–stage compressor 13 Product Overview Main Display Area/Screen Saver After 30 minutes of inactivity, the screen dims and a screen saver appears in the main display area as shown in the following figure. The screen saver also appears if you touch the animated graphic on the home screen. Alternately, if you touch the screen saver, the home screen appears. Figure 3. Screen saver Component Screens Each chiller component has a touch target, accessible from the home screen, that is illustrated in “Screen Overview,” p. 8 (main display area/home screen) and described in “Main Display Area/ Home Screen,” p. 10. Simplex Chillers If you touch anywhere on a component touch target, a screen appears containing data that is related to that component (see the example in the following figure). You can use the shortcut buttons at the top of each of the component screens to view the other components screens. “Appendix A: Data for CenTraVac Simplex Chillers,” p. 63 lists the settings and status points that are accessible from each of the component screens. The chiller configuration determines which of the settings and status points appear. 14 CTV-SVU01G-EN Product Overview Figure 4. Component screen example for Simplex chillers 1 2 1. Data Graph shortcut button 2. Component screen shortcut buttons Duplex Chillers Each component has a separate screen for circuit 1 and circuit 2. • If you touch anywhere on an evaporator or condenser component touch target, a screen appears containing data related to circuit 1 of that component (refer to the following figure). • If you touch in the circuit 1 data area of a compressor, motor, or purge component touch target, a screen appears containing data related to circuit 1 of that component. If you touch in the circuit 2 data area of a compressor, motor, or purge component touch target, a screen appears containing data related to circuit 2 of that component. Circuit 1 and Circuit 2 buttons at the bottom of each component screen (see Location 4 in the following figure) allow you to toggle between circuit 1 and circuit 2 component screens. You can use the shortcut buttons at the top of each of the component screens (see Location 2 in the preceding figure) to view the other components screens. If you are viewing a circuit 1 component screen and touch a shortcut button, the circuit 1 screen for the component represented by that button appears; and likewise for circuit 2. “Appendix B: Data for CenTraVac Duplex Chillers ,” p. 77 lists the settings and status points that are accessible from each of the component screens. The chiller configuration determines which of the settings and status points appear. CTV-SVU01G-EN 15 Product Overview Figure 5. Component screen example for Duplex chillers 22 1 2 3 4 1. Data Graph shortcut button 2. Component screen shortcut buttons 3. Animated graphic 4. Circuit 1 and Circuit 2 components screen toggle buttons Component Screen Settings Some settings appear on the component screens as buttons. These buttons take you to another screen, where you can change the setting. (See, for example, the buttons on the evaporator component screen in the preceding two figures, which show the Active Chilled Water Setpoint and the Evaporator Water Pump Override). N o t e : For more information about changing settings, see “Equipment Settings,” p. 39. Data Graph Shortcut Button To view a data graph that is related to the component screen you are viewing, touch the Data Graph button at the top left of the component screen (Location 1 in the preceding two figures). Component Screen Graphics On the left side of each component screen is a graphic of the component. If the chiller is running, each graphic, except for the purge graphic, is animated. 16 CTV-SVU01G-EN Product Overview Main Menu Area The main menu area (shown in “Screen Overview,” p. 8) always remains visible at the bottom of the display. When touched, each of the buttons displays the main menu screen for the topic listed on the button. The following table provides a description of each button. Table 3. Main menu area Button Description Touch the Alarms button to view the Alarms screen. If there is an active alarm, the button flashes a color. The flashing color is determined by the highest severity of active alarms: • If an Immediate Shutdown alarm exists, the flashing color is red. • If a Normal Shutdown alarm exists, the flashing color is yellow. • If a Warning alarm exists, the flashing color is blue. Note: For more information, see “Alarms,” p. 20. Touch the Reports button to view the Reports screen. Note: For more information, see . “Reports,” p. 23. Touch the Data Graphs button to view the Data Graphs screen. Note: For more information, see “Data Graphs,” p. 32. Touch the Settings button to view the Settings screen, which is separated into the following three categories: • “Equipment Settings,” p. 39 • “Display Settings,” p. 51 • “Security Settings,” p. 58 Note: Refer to the page numbers for detailed information about each category. Touch the Language icon to view the Language screen. (This button is a shortcut. You can also view the Language screen by using the Settings button.) Note: For more information, see “Viewing and Changing the Language Preference,” p. 54. Touching the brightness button will cycle the display brightness from 30% to 60% to 90% brightness. CTV-SVU01G-EN 17 Stopping/Restarting Chiller Operation You can start or stop the chiller from the Tracer® AdaptiView™ display by using the Auto and Stop buttons. The buttons are located in upper right. Stopping the Chiller You can stop the chiller in two ways: • Normally, which involves stopping the various components sequentially in order to protect them from damage • Immediately, which shuts down all the components at once, and should be used only in an emergency To stop the chiller in either of these ways: 1. Touch the Stop button to initiate the chiller shutdown process. A confirmation screen appears as shown in the following figure. Figure 6. Stop the Chiller confirmation screen 2. Touch the Y e s button. The Shutting Down Chiller screen appears as shown in the following figure. 18 • To stop the chiller normally, no further action is required. You can observe the submodes change and the timers count down. • To stop the chiller immediately, touch the I m m e d i a t e S h u t d o w n button. • To cancel shutdown, touch the C a n c e l S h u t d o w n button. CTV-SVU01G-EN Stopping/Restarting Chiller Operation Figure 7. Shutting Down Chiller screen N o t e : If the chiller is a Duplex™, the screen shows top-level modes and submodes for both the chiller and the two circuits. Restarting the Chiller Touch the Auto button to initiate the chiller restart process. You can observe the mode change to Auto. The chiller will wait until cooling is needed before starting the compressor. When the chiller is running normally, it automatically starts and stops as needed to reach its setpoints. CTV-SVU01G-EN 19 Alarms You can use the Tracer® AdaptiView™ display to view alarms and to reset them. Alarms are communicated to the display immediately upon detection. The Alarms Screen Touch the A l a r m s button in the main menu area at the bottom of the screen to view the Alarms screen. A table of active alarms appears that is organized chronologically with the most recent at the top of the list, as shown in the following figure. This example shows the default view, which appears each time you return to the screen. Figure 8. Alarms screen (default view) 1 2 3 4 5 1. Reset Alarms button 2. Number of alarms 3. Sortable columns—The example is sorted by date/time. 4. Page controls N o t e : A page number appears in the lower right corner of the screen. If a screen contains more than one page, up/down arrows also appear for viewing the other pages. 5. Alarms categories—The example shows active alarms. 20 CTV-SVU01G-EN Alarms Alarm Icons Alarm icons, which appear in the left-most column of the alarms screen and on the alarms indicator button if there is an existing alarm, are distinguished by their shape and color. Their meaning is explained in the following table. Table 4. Alarm icons Active alarm icons Historic alarm icons Level of severity Immediate shutdown Red octagon Gray octagon Normal shutdown Yellow triangle Gray triangle Blue circle Gray circle Warning Active and Historic Alarm Categories You can view alarms by three different categories: • A c t i v e a l a r m s : These are alarms that require attention. All alarms that are currently active appear when you view this category. • H i s t o r i c a l a r m s : After an alarm condition has been resolved, the alarm is reclassified as historic. The 20 most recent historic alarms appear when you view this category. • A l l a l a r m s : All active alarms and the 20 most recent historic alarms appear when you view this category. The alarms are listed in chronological order. The Alarms screen defaults to active alarms, as in “The Alarms Screen,” p. 20. Note that the A c t i v e A l a r m s button in Location 5 appears shaded in the figure, which indicates that you are viewing active alarms. To view a different category, touch H i s t o r i c A l a r m s or A l l A l a r m s . The button you select becomes shaded and the list appears. Sorting Alarms To sort alarms by a category other than date and time, touch one of the other column headings in the table. The column heading responds by changing to blue, and the alarms table re-sorts according to the blue column heading. If you touch the blue column heading again, the column changes the order from ascending to descending. You can sort the alarms table by: CTV-SVU01G-EN • Date/Time (the default sort): Most recent alarms are at the top. • Severity: Active alarms are at the top (if you are viewing both active and historic alarms), followed by the most severe, followed by the most recent. • Description: Alarms are sorted alphanumerically by name, followed by the most recent. • Status: Alarms are sorted according to active/historic status (if you are viewing both active and historic alarms), followed by the most recent. 21 Alarms Resetting Alarms Some alarms require reset to move from the active to the historic state, even if the issue causing the alarm has been resolved. These manual reset alarms are sometimes referred to as latching alarms. Non-latching alarms change from the active to the historic state automatically, after the problem has been resolved. The Alarms screen does not directly state whether the alarms are latching or non-latching. However, their behavior indicates their type: • Reset latching alarms by touching the R e s e t A l a r m s button at the top of the Alarms screen (refer to “The Alarms Screen,” p. 20). Latching alarms respond by disappearing from the active alarms list and becoming a part of the historic alarms list. However, if the condition that caused the alarm persists, the alarm will re-appear in the active alarms list. • You do not have to reset non-latching alarms. Non-latching alarms automatically disappear from the active alarms list and re-appear in the historic alarms list when the conditions that caused them are resolved. Additional Alarm Indicators In addition to the Alarms screen, there are two buttons that indicate alarm conditions. These buttons are viewable from any screen on the display. You can touch either one to access the Alarms screen. 22 • The A l a r m s button in the main menu area of the screen (refer to “Screen Overview,” p. 8) flashes a color that represents the alarm level of the most severe active alarm. The three color possibilities correspond to those of the active alarm icons shown in “Alarm Icons,” p. 21. • If an active alarm is present, the alarm indicator button (refer to “Chiller Status Area,” p. 9) appears in the upper left of the screen, as shown in “The Alarms Screen,” p. 20. The icon on this button indicates the level of the most severe active alarm. CTV-SVU01G-EN Reports You can use the Tracer® AdaptiView™ display to view a variety of reports and to create and edit a custom report. All reports contain live data that refreshes every 2–5 seconds. The Reports Screen Touch the R e p o r t s button in the main menu area (refer to “Screen Overview,” p. 8) to view the Reports screen. The Reports screen contains the following buttons: • Log Sheet • ASHRAE Chiller Log • Custom Report • About This Chiller • Chiller Operating Modes • Purge Operating Modes Each button links to the report named on the button. Figure 9. Reports screen Viewing the Log Sheet On the Reports screen, touch L o g S h e e t to view the information that is itemized in “Log Sheet,” p. 65 for Simplex chillers, and in “Log Sheet,” p. 79 for Duplex™ chillers. The items included in the Log Sheet are those recommended by Trane. Refer to current Trane service literature for more information. CTV-SVU01G-EN 23 Reports Viewing the ASHRAE Chiller Log On the Reports screen, touch A S H R A E C h i l l e r L o g to view the information that is itemized in “ASHRAE Chiller Log,” p. 67 for Simplex chillers, and in “ASHRAE Chiller Log,” p. 80 for Duplex™ chillers. Creating and Viewing a Custom Report You can create a custom report in which you specify the type and order of data that it contains. Items available to select for a custom report are grouped according to subsystem. (For Simplex chillers, see “Items Available to Include in Custom Reports,” p. 69; for Duplex™ chillers, see “Items Available to Include in Custom Reports,” p. 82.) To create and view a custom report: 1. On the Reports screen, touch C u s t o m R e p o r t . The Custom Report screen appears. 2. On the Custom Report screen, touch E d i t . The Edit Custom Report screen appears in the following figure. Figure 10. Edit Custom Report screen 3. Touch the up/down arrows at the top of the left box on this screen to scroll through the items that are available to add to a custom report. 4. To set up a custom report by adding: • One item at a time, touch the item. It responds by changing to blue. Touch A d d to move the selected item to the right box on the screen. • All of the items at once to the right box on the screen, touch A d d A l l . N o t e : You can organize your selections in any order by using the down arrows that appears in the right box, and by adding them one at a time in the order in which you want them to appear in your report. 5. To save and view your custom report, touch S a v e . The Custom Reports screen appears, containing the custom report you have just created as shown in the next figure. 24 CTV-SVU01G-EN Reports N o t e : A page number appears in the lower right corner of the screen. If a screen contains more than one page, up/down arrows also appear for viewing the other pages, as in the following figure. Figure 11. Custom Report screen Editing a Custom Report You can edit the custom report by adding, removing, or re-order data as follows: 1. On the Custom Report screen, touch E d i t . The E d i t C u s t o m R e p o r t screen appears. 2. Add, remove, or re-order as follows: • To add an item to the custom report, touch it. It responds by changing to blue. You an use the arrows to scroll through the rest of the items that can be added to the custom report. Then touch A d d to move the selected item to the box on the right side of the screen. To add all of the remaining items in the left box to the custom report, touch A d d A l l . • To remove an item from the custom report, touch it. It responds by changing to blue. You can use the arrows to scroll through the rest of the items that can be removed from the custom report. Then touch R e m o v e to move the selected item to the box on the left side of the screen. • To re-order items in the custom report, touch it. It responds by changing to blue. Use the arrows to change the order of a highlighted item. 3. To save and view your edited custom report, touch S a v e . The Custom Reports screen appears, containing the custom report you have just edited. CTV-SVU01G-EN 25 Reports About this Chiller On the Reports screen, touch A b o u t T h i s C h i l l e r to view the following unit information: • Chiller Name • Chiller Model Number • Chiller Sales Order Number • Product Name • Controller Build Part Number • Chiller Serial Number • Display Firmware Build • Controller Hardware Serial Number • Controller Boot Part Number • Display Boot Code Viewing Chiller Operating Modes On the Reports screen, touch C h i l l e r O p e r a t i n g M o d e s to view the current operating status of the chiller in terms of the top-level operating mode and submodes. N o t e : You can also access the Chiller Operating Modes screen from the chiller status button in the upper left corner of the screen. Simplex Chillers The following figure shows an example of a Chiller Operating Modes screen for a Simplex chiller. Figure 12. Chiller Operating Modes screen for Simplex chillers Simplex chillers operate in one of the top-level operating modes shown in the following table. The table gives a description of the top-level modes and lists the submodes that correspond to each top-level mode. 26 CTV-SVU01G-EN Reports Submodes are dependent on the top-level mode. Their appearance on the Chiller Operating Modes screen has the following characteristics: • The newest submode appears at the top of the submode list. • Submodes disappear when they no longer apply. • The screen displays up to six submodes. • If less than six submodes are active, the submode rows that do not apply are blank. Table 5. Chiller top-level operating modes and corresponding submodes for Simplex chillers Top-level mode Description Stopped Chiller is inhibited from running and requires user action to go to Auto. Corresponding submodes Local Stop Immediate Stop Diagnostic Shutdown—Manual Reset Ice Building Is Complete Run Inhibit Unit is inhibited from running by building automation system (BAS), external control source (Ext), or Auto Reset diagnostic Tracer Inhibit External Source Inhibit Diagnostic Shutdown—Auto Reset Waiting for Evaporator Water Flow Waiting for a Need to Cool Auto Unit is determining if there is a need to run. Waiting for a Need to Heat Power Up Delay Inhibit (MIN:SEC)(a) Waiting For Condenser Water Flow Establishing Oil Pressure Pre-Lubrication Time (MIN:SEC)(a) Motor Temperature Inhibit: Motor Temperature/ Inhibit Temperature Waiting to Start Unit is waiting for tasks required prior to compressor start to be completed. Restart Time Inhibit (MIN:SEC)(a) AFD Restart Inhibit High Vacuum Inhibit: Oil Sump Press/Inhibit Press Low Oil Temperature Inhibit: Oil Temperature/ Inhibit Temperature Waiting for Starter To Start (MIN:SEC)(a) Starting Compressor Unit is starting compressor. No submode is shown No submode is shown Hot Water Control Surge Base Loaded Running Compressor is running with no limits in effect. Hot Gas Bypass Ice Building Ice To Normal Transition Current Control Soft Loading CTV-SVU01G-EN 27 Reports Table 5. Chiller top-level operating modes and corresponding submodes for Simplex chillers (continued) Top-level mode Description Corresponding submodes Current Limit Phase Unbalance Limit Condenser Pressure Limit Running—Limit Compressor is running with limits in effect. Evaporator Temperature Limit Evaporator Rfgt Temperature Higher Than Selection Minimum Capacity Limit Maximum Capacity Limit Opening Free Cooling Valves Free Cooling Unit is in Free Cooling mode and will not run the compressor. Closing Free Cooling Limit Preparing to Shutdown Unit is closing inlet guide vanes prior to compressor shutdown. Closing IGV (IGV Position %)(b) Post-Lubrication Time (MIN:SEC)(a) Evaporator Pump Off Delay (MIN:SEC(a) Shutting Down Compressor has been stopped and unit is performing shutdown tasks. Condenser Pump Off Delay (MIN:SEC)(a) Satisfied Need to Minimum Capacity Timer (will appear for only 10 seconds) (a) (b) “MIN:SEC” refers to a count-down timer that appears on the screen to indicate how long the submode will remain active. “IGV Position %” refers to a value that indicates the position of the inlet guide vane (IGV). Duplex Chillers The following figure shows an example of a Duplex Chiller Operating Modes screen. Figure 13. 28 Chiller Operating Modes screen for Duplex chillers CTV-SVU01G-EN Reports For Duplex™ chillers, the Chiller Operating Modes screen shows top-level modes and submodes for the chiller (Table 6, p. 29) and for the circuits (Table 7, p. 30). Each table shows top-level modes in the left column, a description in the middle column, and the corresponding submodes in the right column. Submodes are dependent on the top-level mode. They appear on the Chiller Operating Modes screen with the following characteristics: • The newest submode appears at the top of the submode list. • Submodes disappear when they no longer apply. • The screen displays up to four submodes. • If less than four submodes are active, the submode rows that do not apply are blank. Table 6. Chiller top-level operating modes and corresponding submodes for Duplex chillers Top-level mode Description Stopped The chiller is not running either circuit and cannot run without intervention. Corresponding submodes Local Stop Immediate Stop Diagnostic Shutdown—Manual Reset Ice Building Is Complete Start Inhibited By BAS Run Inhibit The chiller is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared. Waiting for BAS Communication External Source Inhibit Diagnostic Shutdown—Auto Reset No Circuits Available Waiting for Evaporator Water Flow Auto The chiller is not currently running but can be expected to start at any moment given that the proper conditions and interlocks are satisfied. Waiting for a Need to Cool Waiting for a Need to Heat Power Up Display Inhibit (MIN:SEC)(a) Waiting to Start The chiller is going through the necessary steps to allow the lead circuit to start. The chiller will wait up to 4 minutes and 15 seconds in this mode for condenser water flow to be established by means of the flow switch hardwired input. Hot Water Control Base Loaded Ice Building Running At least one circuit on the chiller is currently running. Ice To Normal Transition (MIN:SEC)(a) Current Control Softloading Capacity Control Softloading Minimum Capacity Limit Running—Limit CTV-SVU01G-EN At least one circuit on the chiller is currently running, but the operation of the chiller as a whole is being actively limited by the controls. The submodes that apply the Running top modes may be displayed along with the following limit-specific modes. All of the chiller-level Running submodes apply. There are no specific submodes associated with Running—Limit. 29 Reports Table 6. Chiller top-level operating modes and corresponding submodes for Duplex chillers (continued) Top-level mode Description Corresponding submodes Evaporator Pump Off Delay (MIN:SEC)(a) Condenser Pump Off Delay (MIN:SEC)(a) Shutting Down The chiller is still running, but shutdown is imminent. The chiller is going through a compressor run-unload. Satisfied Need to Cool Satisfied Need to Heat Satisfied Need to Minimum Capacity Timer (will display for only 10 seconds) Evaporator Pump Off Override Condenser Pump Override Miscellaneous These submodes may appear with most of the top-level chiller modes. Manual Capacity Override IGV Manual Override(b) Software Service Lock (a) (b) “MIN:SEC” refers to a count-down timer that appears on the screen to indicate how long the submode will remain active. “IGV Position %” refers to a value that indicates the position of the inlet guide vane (IGV). Table 7. Circuit-level operating modes and corresponding submodes for Duplex chillers Top-level mode Description Stopped The circuit is not running, and cannot run without intervention. Corresponding submodes Diagnostic Shutdown—Manual Reset Front Panel Circuit Lockout Run Inhibit Auto The circuit is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared. The circuit is currently not running but is expected to start at any moment if the proper conditions are satisfied. Diagnostic Shutdown—Auto Reset External Circuit Lockout No Circuit Submodes Waiting for Low Oil Differential Pressure Establishing Oil Pressure Pre-Lubrication Time (MIN:SEC)(a) Motor Temperature Inhibit: Motor Temperature/ Inhibit Temperature Restart Time Inhibit (MIN:SEC)(a) Waiting To Start The chiller is going through the necessary steps to allow the lead circuit to start. High Vacuum Inhibit: Oil Sump Press/Inhibit Press Low Oil Temperature Inhibit: Oil Temperature/ Inhibit Temperature Waiting for Starter To Start (MIN:SEC)(a) Waiting for IGV Positioning to Complete(b) Waiting for Starter Interlock Starting Compressor 30 The circuit is going through the necessary steps to allow the compressor on that circuit to start. No submodes CTV-SVU01G-EN Reports Table 7. Circuit-level operating modes and corresponding submodes for Duplex chillers (continued) Top-level mode Description Corresponding submodes Surge Hot Gas Bypass Current Limit Running The compressor on the circuit is currently running. Phase Unbalance Limit Evaporator Temperature Limit High Compressor Discharge Temp Limit Current Limit Phase Unbalance Limit Running—Limit Compressor is running with limits in effect. Condenser Pressure Limit Evaporator Temperature Limit High Compressor Discharge Temp Limit Preparing to Shutdown The circuit is preparing to de-energize the compressor. Closing IGV(b) Shutting Down The chiller is going through the necessary steps after deenergizing the compressor. Post-Lubrication Time (MIN:SEC)(a) Miscellaneous These submodes may appear with most of the top-level chiller modes. (a) (b) Overdrive IGV Closed(b) Oil Pump Override “MIN:SEC” refers to a count-down timer that appears on the screen to indicate how long the submode will remain active. “IGV Position %” refers to a value that indicates the position of the inlet guide vane (IGV). Purge Operating Modes On the Reports screen, touch P u r g e O p e r a t i n g M o d e s to view the current operating status of the purge system in terms of the top-level operating mode and submodes. N o t e : For Duplex™ chillers, the operating status of purge system is shown in terms of the two circuits. The purge system operates in one of four top-level operating modes: • Stop • On • Auto • Adaptive Submodes are dependent on the top-level mode. Their appearance on the Purge Operating Modes screen has the following characteristics: • The newest submode appears at the top of the submode list. • Submodes disappear when they no longer apply. • The screen displays up to six submodes. • If less than six submodes are active, the submode rows that do not apply are blank. For detailed information about purge operating modes and submodes, refer to PRGF-SVX001*EN (Installation, Operation, and Maintenance: EarthWise Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-123 Refrigerant) or PRGG-SVX001*-EN (Installation, Operation, and Maintenance: Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-514A Refrigerant), as appropriate. CTV-SVU01G-EN 31 Data Graphs You can use the Tracer® AdaptiView™ display to view a variety of default data graphs and to create up to six custom data graphs with up to eight data points per graph. The data sample rate is 30 seconds, and the data storage duration is 48 hours. These rates cannot be adjusted. The Data Graphs Screen Touch the D a t a G r a p h s button in the main menu area to view the Data Graphs screen shown in the following figure. Each button on the screen links to a data graph. The buttons under the Default Graphs heading for Simplex chillers are: • • • • • • • • • • Chiller Overview 1 Chiller Overview 2 Approach Temperature Evaporator Motor Condenser Motor Temperature Compressor Purge Oil System or Lube System When you create custom graphs, they appear under the Custom Graphs heading with names such as “Custom 1” and “Custom 2,” as shown in the following figure. Figure 14. Data Graphs screen The buttons under the Default Graphs heading for Duplex™ chillers are: Chiller • 32 Chiller Overview 1 CTV-SVU01G-EN Data Graphs • • • Chiller Overview 2 Evaporator Condenser Circuit 1 • • • • • • Oil System Approach Temperature Compressor Motor Motor Temperature Purge Circuit 2 • • • • • • Oil System Approach Temperature Compressor Motor Motor Temperature Purge Viewing Data Graphs On the Data Graphs screen, touch any of the buttons to view a live graph. (The following figure shows Chiller Overview 1 as an example). For every graph, the X-axis shows time. The Yaxes presents data points specific to each graph. The data points are listed in “The Data Graphs Screen,” p. 32. Figure 15. CTV-SVU01G-EN Example of Data Graph (Chiller Overview 1 shown) 33 Data Graphs Changing the Scales on Data Graphs Changing the Scale of the X-axis The X-axis scale defaults to the most recent 60 minutes with 15 minutes in between the time labels that appear across the bottom of the graph. You can change the scale from the last 12 minutes to the last 2 days and increments in between, as follows: • • • • • • • 12-minute graph with 3 minutes between time labels 40-minute graph with 10 minutes between time labels 60-minute graph with 15 minutes between time labels 4-hour graph with 1 hour between time labels 8-hour graph with 2 hours between time labels 1-day graph with 6 hours between time labels 2-day graph with 12 hours between time labels To change the scale, touch the plus or minus button in the magnifying glass in the lower left corner of a data graph that you want to edit (for an example, refer to the figure in “Viewing Data Graphs,” p. 33). The slider scale moves to the right or left as you touch either the plus or minus button. The time scale for the X-axis changes in response. Changing the Scale of the Y-axes The Y-axes scales have a default range that varies for each data graph. You can change the range for each graph. 1. Touch the E d i t Y - A x i s button at the bottom of a data graph that you want to edit (for an example, refer to the figure in “Viewing Data Graphs,” p. 33). The Set Axis Range screen appears in the following figure. The screen shows the minimum and maximum values for that particular graph. Figure 16. Set Axis Range screen 2. Touch the M a n u a l l y s e t v a l u e s button under either the Left Y-Axis or Right Y-Axis heading. E n t e r n u m b e r buttons appear to the right of the minimum and maximum values. 3. Touch the E n t e r n u m b e r button for the value you want to change. A keypad appears on the 34 CTV-SVU01G-EN Data Graphs screen. 4. Touch the appropriate numbers to change the current value. The new value appears above the keypad. 5. Touch the E n t e r button. The graph you were previously viewing appears with changed maximum and/or minimum values. 6. Touch S a v e . The data graph appears with changed Y-axes scales. Creating Custom Data Graphs You can create a custom data graph in two ways: • By starting with a default data graph • By starting from a blank screen, with no previously defined data graph points Creating a Custom Data Graph From a Default Data Graph 1. Touch the C r e a t e C u s t o m button at the top left of any default data graph screen (for an example, refer to the figure in “Viewing Data Graphs,” p. 33). The Data Graph Points screen appears as shown in the following figure. Figure 17. Data Graph Points screen 2. Touch the A d d / R e m o v e P o i n t s button at the top left of the screen. The Add/Remove screen appears (refer to the following figure), pre-populated with data points from the default data graph you chose. N o t e : When you save the graph, a new custom graph is created; the default data graph is not overwritten. 3. Touch the up/down arrows at the top of the left box on the Add/Remove screen to scroll through a list of chiller components. The list of items in the box just below the up/down arrows changes to correspond to the component choice. (For reference, these items are listed in “Appendix A: Data for CenTraVac Simplex Chillers,” p. 63 and “Appendix B: Data for CTV-SVU01G-EN 35 Data Graphs CenTraVac Duplex Chillers ,” p. 77). Figure 18. Add/Remove screen example 4. To choose points to include in the custom data graph, you can do any of the following: • To add one item at a time, touch the item in the left box. It responds by changing to blue. Touch A d d to move the selected item to the right box. • To add all of the items in the left box to the right box, touch A d d A l l . • To remove one item at a time, touch the item in the right box. It responds by changing to blue. Touch R e m o v e to move the selected item to the left box. • To remove all of the items in the right box to the left box, touch R e m o v e A l l . A confirmation screen appears, asking you to verify your request. 5. When you are finished choosing data points, touch S a v e . The Data Graph Points screen appears. Touch the F i n i s h e d button to view the custom data graph you have just created (refer to the following figure. N o t e : To edit the appearance of data points in the graph, refer to “Editing Custom Data Graphs,” p. 37. 36 CTV-SVU01G-EN Data Graphs Figure 19. Custom data graph example Creating a Custom Data Graph With No Previously Defined Data Graph Points 1. Touch the C r e a t e C u s t o m button at the top left of the Data Graphs screen (Figure 14, p. 32). The Add/Remove screen appears (see ), but with no data on the screen. 2. Continue by following Step 3 through Step 5 in “Creating a Custom Data Graph From a Default Data Graph,” p. 35. Editing Custom Data Graphs You can edit custom data graphs by: • Changing the scales of the X-axis and Y-axes (follow the procedures in “Changing the Scales on Data Graphs,” p. 34 ). • Changing the: – Line style between bold and normal – Y-axis location between left and right – Line color 1. To edit a data point, touch the E d i t button in the row for the data point you want to edit. The Edit Data Point screen appears (refer to the following figure). 2. Touch the button in each category—Line Style, Y-Axis, Color—that represents how you want the graph to appear. The buttons you select become shaded. 3. Touch S a v e . The screen you were previously viewing appears with your changes reflected in the table. CTV-SVU01G-EN 37 Data Graphs Figure 20. Edit Data Point screen Deleting a Custom Data Graph Touch the D e l e t e button at the top of a custom graph screen to delete the custom graph. 38 CTV-SVU01G-EN Equipment Settings You can use the Tracer® AdaptiView™ display to monitor and change a variety of equipment settings. The Settings Screen Touch the S e t t i n g s button in the main menu area (see “Main Menu Area,” p. 17) to view the Settings screen. Equipment Settings identifies a column of buttons located on the screen. (Refer to the outlined column in the following figure.) The buttons are: • Chiller Settings • Feature Settings • Chiller Water Reset • Purge Settings • Manual Control Settings Each of these buttons provide access to a screen that contains additional buttons related to each topic. This section provides detailed information about these screens. Figure 21. Settings screen with the Equipment Settings column highlighted Viewing and Changing Equipment Settings Each button in the Equipment Settings column on the Settings screen takes you to a menu screen that contains a group of buttons. Each button displays the name of a setting and its current value (refer to the following figure). Touch any button to view a screen where you can change the setting for the feature shown on the button. N o t e : A page number appears in the lower right corner of the screen. If a screen contains more than one page, up/down arrows also appear for viewing the other pages, as in the following figure. CTV-SVU01G-EN 39 Equipment Settings Figure 22. Example equipment settings screen (Chiller Settings shown) To change an equipment setting, follow this procedure: 1. Touch one of the buttons in the Equipment Settings column on the Settings screen, such as Chiller Settings. The corresponding screen appears (in this case, the Chiller Settings screen). 2. Touch the button that shows the equipment setting you want to change. A screen that allows you to change the equipment setting appears. There are two types of these screens: • 40 For screens with button selections, touch the button that represents the setting you want. The button becomes shaded, and a S a v e button appears at the bottom of the screen as shown in the following figure. CTV-SVU01G-EN Equipment Settings Figure 23. • Example equipment settings screen with buttons for changing setting For screens with numerical keypads, touch the appropriate numbers to change the current value as shown in the following figure. The new value appears above the keypad. Figure 24. Example equipment settings screen with keypad for changing setting Keypad features: CTV-SVU01G-EN 41 Equipment Settings – When you enter a new number, the value in the N e w v a l u e field is deleted and replaced with the new entry. – The backspace (arrow) key deletes the characters you previously entered. – If the keypad is used to enter a setpoint that is out of range, an error dialog will appear when you touch the S a v e button. – Keypads that allow negative numbers have positive and negative number (+/-) keys. 3. Touch S a v e to complete the change. The current value is updated in the upper left side of the screen, demonstrating that the change has been communicated to the Tracer UC800 controller. The screen you were previously viewing appears. N o t e : Manual Control Settings screens have Apply buttons in addition to Save buttons. For an example, refer to “Manual Control Settings,” p. 47. Touching Apply is the same as touching Save, except that you remain at the current screen after the change is communicated to the Tracer® UC800 controller. Chiller Settings The following table lists the settings that are available as buttons on the Chiller Settings menu screen, along with their corresponding setting options. The chiller configuration determines which of the settings appear. Table 8. Chiller Settings menu screen: Buttons and available setting options Page 1 of 2 Setpoint Source BAS/Ext/FP Ext/FP Front Panel Front Panel Control Type Cooling/ Heating Front Panel Chilled Water Setpoint XX.X °F/C Front Panel Hot Water Setpoint XXX.X °F/C Front Panel Ice Building Command Auto/On Front Panel Ice Termination Setpoint XX.X °F/C Ice to Normal Cooling Timer Setpoint XX Min Front Panel Current Limit Setpoint XXX.X % Front Panel Base Loading Setpoint XXX.X % Front Panel Base Loading Command Auto/On Page 2 of 2 Differential to Start XX.X °F/C Differential to Stop XX.X °F/C Front Panel Free Cooling Command Auto/On Condenser Water Pump Off Delay XX Min Evaporator Water Pump Off Delay XX Min Evap Low Water Flow Warning SetpointXXXX.X gpm/lpm Power-Up Start Delay XXX Sec Starter Power Demand Time Period XXX Min 42 CTV-SVU01G-EN Equipment Settings Service Settings The following table lists the settings that are available as buttons on the Service Settings menu screen, along with their corresponding setting options. The chiller configuration determines which of the settings appear. Table 9. Service Settings menu screen: Buttons and available settings options Page 1 of 2 Evaporator Leaving Water Temp Cutout XX.X °F/C Low Refrigerant Temperature Cutout XX.X °F/C Local Atmospheric Pressure XX.X PSI/kPa Maximum Capacity Limit XXX.X % Minimum Capacity Limit XXX.X % (Formerly in Chiller Settings) BAS Setpoint Power Loss Store Enable Enable/Disable Check Oil Filter Setpoint XX.XX PSID/kPaD -orCheck Lube Filter Setpoint XX.XX PSID/kPaD (CVHS Only) Startup Lube Diff Pressure Threshold XX.XX PSID/kPaD (CVHS Only) Capacity Control Softload Time XXX Sec Current Limit Control Softload Time XXX Sec Current Limit Softload Start Point XXX.X % Page 2 of 2 Condenser Limit Setpoint XXX.X % Head Pressure Control Pre-Position Setpoint XXX.X % Staging On Boundary XXX.X % (Duplex Only) Staging Off Boundary XXX.X % (Duplex Only) Head Pressure Control Pre-Position Setpoint XXX.X % Setpoint Sources Some setpoints can be controlled from more than one source; these are referred to as arbitrated setpoints. Arbitrated setpoints can be: • Communicated from a building automation system (BAS)—Refers to a Trane or other BAS that can communicate with chiller controls over a network. • Set by an external control source (Ext)—Refers to inputs that are hard-wired directly to local chiller controls, carrying low-voltage binary (On/Off) or analog (0–10 Vdc, 4–20 mA) signals. • Set at the front panel (FP)—Refers to inputs that are entered by an operator using the Tracer® AdaptiView™ display or by a technician using the Tracer® TU service tool. Setpoint Source Arbitration The Tracer® UC800 uses a process referred to as setpoint source arbitration to prioritize the selection of the setpoint source. The following table provides an explanation of how this process works. Table 10. Setpoint source choices and corresponding arbitration Priority BAS/Ext/FP Ext/FP First Setpoint from the BAS is used. Setpoint from a external control source is used. Second If no BAS setpoint is available (for example, BAS communication has never been established), a setpoint from an external control source is used. Front Panel Setpoint from the front panel is used. CTV-SVU01G-EN If no externally controlled setpoint is available, a setpoint from the front panel is used. Note: Any setpoint from a BAS or external control source is ignored. None Note: Any setpoint from a BAS is ignored. 43 Equipment Settings Table 10. Setpoint source choices and corresponding arbitration (continued) Priority BAS/Ext/FP Ext/FP Front Panel Third If no BAS nor external setpoint is available (for example, BAS communication has never been established), a setpoint from the front panel is used. None None Notes: 1. 2. For service or troubleshooting, it may be helpful to set the setpoint source to front panel to isolate the chiller from other control sources. If BAS communication was established and then lost, in most instances the BAS values remain and can be used by the chiller controller. Changing the Setpoint Source There are three ways to access the Setpoint Source screen. To change the setpoint source, follow one of these procedures: Using the Setpoint Source Button in the Chiller Status Area 1. Touch the S e t p o i n t S o u r c e button in the chiller status area (refer to “Screen Overview,” p. 8). The Setpoint Source screen appears as shown in the following figure. 2. Touch the appropriate source button on the Setpoint Source screen. 3. Touch S a v e to complete the change. N o t e : The change applies to all arbitrated setpoints. Figure 25. Setpoint Source screen From the Setpoint Source Button on the Chiller Settings Screen 1. Touch the S e t t i n g s button in the main menu area (refer to “Screen Overview,” p. 8). The Settings screen appears. 44 CTV-SVU01G-EN Equipment Settings 2. From the Settings screen, touch the C h i l l e r S e t t i n g s button. The Chiller Settings screen appears. 3. From the Chiller Settings screen, touch the button that is labeled “Setpoint Source” and displays the current source. The Setpoint Source screen appears (refer to the preceding figure). 4. Touch the button the appropriate source button on the Setpoint Source screen. 5. Touch S a v e to complete the change. N o t e : The change applies to all arbitrated setpoints. From an Arbitrated Setpoint Screen 1. Touch the S e t t i n g s button in the main menu area (Figure 2, p. 9). The Settings screen appears. 2. From the Settings screen, touch the C h i l l e r S e t t i n g s button. The Chiller Settings screen appears. 3. From the Chiller Settings screen, touch an arbitrated setpoint. The setpoint screen for that specific arbitrated setpoint appears (see the following figure for an example). 4. On the arbitrated setpoint screen, touch the Setpoint Source button. The Setpoint Source screen appears (refer to the preceding figure). 5. Touch the button the appropriate source button on the Setpoint Source screen. 6. Touch S a v e to complete the change. N o t e : The change applies to all arbitrated setpoints. Figure 26. CTV-SVU01G-EN Changing the setpoint source from an arbitrated setpoint screen 45 Equipment Settings Feature Settings The following table lists the settings that are available as buttons on the Feature Settings menu screen, along with their corresponding setting options. The chiller configuration determines which of the settings appear. Table 11. Feature Settings menu screen: Buttons and available setting options Ext Chilled Wtr Setpt Enable/Disable Ext Current Limit Setpt Enable/Disable Ice Building Enable/Disable Ext Chilled Wtr Setpt Enable/Disable Ext Current Limit Setpt Enable/Disable Ice Building Enable/Disable Hot Gas Bypass Feature Enable/Disable Hot Gas Bypass Maximum Timer Enable Enable/Disable Security Enable/Disable LCI-C Diagnostic Encoding Text/Code External Base Loading Setpoint Enable/Disable Check Oil Filter Diagnostic Ckt1 Enable/Disable -orCheck Lube Filter Diagnostic Enable/Disable (CVHS Only) Check Oil Filter Diagnostic Ckt2 Enable/Disable Chilled Water Reset The following table lists the settings that are available as buttons on the Chilled Water Reset menu screen, along with their corresponding setting options. The chiller configuration determines which of the settings appear. Table 12. Chilled Water Reset menu screen: Buttons and available setting options Buttons Chilled Water Reset Type Available setting options • Disable • Return • Outdoor Air • Constant Return Reset Ratio Valid numerical range appears on screen. Return Start Reset Valid numerical range appears on screen. Return Maximum Reset Valid numerical range appears on screen. Outdoor Reset Ratio Valid numerical range appears on screen. Outdoor Start Reset Valid numerical range appears on screen. Outdoor Maximum Reset Valid numerical range appears on screen. 46 CTV-SVU01G-EN Equipment Settings Purge Settings The following table lists the settings that are available as buttons on the Purge Settings menu screen, along with their corresponding setting options. The chiller configuration determines which of the settings appear. Table 13. Purge Settings menu screen: Buttons and available setting options Available setting options Buttons • Stop Purge Operating Mode • Auto Note: Ckt1 and Ckt2 for Duplex chillers • Adaptive • On Daily Pumpout Limit Valid numerical range appears on screen. Note: Ckt1 and Ckt2 for Duplex chillers Disable Daily Pumpout Limit Valid numerical range appears on screen. Note: Ckt1 and Ckt2 for Duplex chillers Purge Liquid Temperature Inhibit • Enable Note: Ckt1 and Ckt2 for Duplex chillers • Disable Purge Liquid Temperature Limit Valid numerical range appears on screen. Note: Ckt1 and Ckt2 for Duplex chillers Manual Control Settings The following table lists the settings that are available as buttons on the Manual Control Settings menu screen, along with their corresponding setting options. The chiller configuration determines which of the settings appear. Table 14. Manual Control settings menu screen: Buttons, available setting options, and status points Feature Chiller Control Signal Evaporator Pump Override Condenser Pump Override CTV-SVU01G-EN Current value Auto/Manual On/Off On/Off Available setting options Manual mode: Up/down arrows for changing the setpoint • Auto • On • Auto • On Status points • IGV1 Position (Simplex chillers only) • IGV2 Position (Simplex chillers only) • Average Line Current (Ckt1 and Ckt2 for Duplex chillers • AFD Frequency (Ckt1 and Ckt2 for Duplex chillers • Active Chilled Water Setpoint (Active Hot Water Setpoint if in Heating mode) • Evap Leaving Water Temp (Cond Leaving Water Temp if in Heating mode) • Evaporator Pump Manual Override Time Remaining • Evap Water Flow Switch Status • Active Chilled Water Setpoint • Evap Leaving Water Temp • Condenser Pump Manual Override Time Remaining • Cond Water flow Switch Status • Active Hot Water Setpoint • Cond Leaving Water Temp 47 Equipment Settings Table 14. Manual Control settings menu screen: Buttons, available setting options, and status points (continued) Feature Clear Energy Consumption Current value XXXX kWh Oil Pump Control Note: Ckt1 and Ckt2 for Duplex chillers On/Off Available setting options • Simplex chillers only: Clear • Duplex chillers only: Energy Consumption Resettable Ckt1, Ckt2 XX:XX min:sec Purge Exhaust Circuit Test Note: Ckt1 and Ckt2 for Duplex chillers Auto/On Purge Regen Cycle Note: Ckt1 and Ckt2 for Duplex chillers On/Off Front Panel Lockout Note: Duplex chillers only; for Ckt1 and Ckt2. Head Pressure Control Override 48 Cond Entering Water Temp XXX.X °F/C • Starter Energy Consump. Resettable • Starter Energy Consump. Last Reset • Starter Energy Consump. NonReset • Oil Pump Manual Override Time Remaining • Auto • Oil Differential Pressure • On • Oil Pump Discharge Pressure • Oil Tank Pressure • Motor Temperature • Motor Winding Temp #1 • Motor Winding Temp #2 • Motor Winding Temp #3 • MTC Switch • Motor Coolant Temperature Clear Restart Inhibit Note: Ckt1 and Ckt2 for Duplex chillers Status points • Clear • Enable • Purge Rfgt Cprsr Suction Temp • Disable • Purge Liquid Temp • Auto • Carbon Tank Temp • On • Chiller Top Level Mode • Locked Out • Top Level Operating Mode Ckt1 • Not Locked Out • Top Level Operating Mode Ckt2 Cond Leaving Water Temp Cond Rfgt Pressure CTV-SVU01G-EN Equipment Settings Changing a Manual Control Setting To change a manual control setting, follow this procedure: 1. In the Equipment Settings column on the Settings screen, touch M a n u a l C o n t r o l S e t t i n g s . The Manual Control Settings screen appears as shown in the following figure. Figure 27. Manual Control Settings screen 2. Touch the button that shows the manual control setting you want to change. A screen for changing the manual control setting appears as shown in the following figure. 3. Touch the button that represents the setting you want. The button becomes shaded and A p p l y and S a v e buttons appear at the bottom of the screen. N o t e : The Compressor Control Signal screen provides up/down arrow keys and numerical fields for selecting a value. 4. To save your change, do one of the following: CTV-SVU01G-EN • Touch A p p l y . The change is communicated to the Tracer® UC800 controller. You can observe the status points in the lower half of the screen change in response to the setting change you just made. Also, a Manual Override button appears in the upper left corner of the screen (refer to the following figure). • Touch S a v e . The change is communicated to the Tracer® UC800 controller. The screen you were previously viewing appears. 49 Equipment Settings Figure 28. 50 Manual Control Settings screen (Evaporator Pump Override shown) CTV-SVU01G-EN Display Settings You can use the Tracer® AdaptiView™ display to change the format of the information that appears on the display, and to clean the touch screen. Settings Screen Touch the S e t t i n g s button in the main menu area (refer to “Screen Overview,” p. 8) to view the Settings screen. Display Settings identifies a column of buttons located on the screen as shown in the following figure. The buttons are: • Display Preferences • Language • Date and Time • Clean Display Each button provides access to a screen that is related to the button name. Figure 29. Settings screen with the Display Settings column highlighted Viewing and Changing Display Preferences On the Settings screen, touch D i s p l a y P r e f e r e n c e s to view a screen containing the following buttons. CTV-SVU01G-EN • Date Format • Date Separator • Time Format • Brightness • Unit System • Pressure Units • Backlight Timeout 51 Display Settings Figure 30. Display Preferences screen Each of the buttons in the previous figure shows the name of a display preference and its format (current value). Touch any of these buttons to view a screen where you can change the format. (Refer to the following figure for an example.) The button representing the format currently used is shaded (see the “MMDDYYYY” button. 52 CTV-SVU01G-EN Display Settings Figure 31. Example of a display preference screen To change the format: 1. Touch the button that shows that format you prefer. 2. Touch S a v e to confirm your selection and to return to the Display Preferences screen. Date Format Use the Date Format screen to choose from the following date formats: • MMDDYYYY (default) • YYYYMMDD • DDMMYYYY Date Separator Use the Date Separator screen to choose from the following date formats: • None • Slash ( \ ) (default) • Hyphen ( – ) • Period ( . ) • Underscore ( _ ) Time Format Use the Time Format screen to choose from the following time formats: • 12 hour (default) • 24 hour Brightness Use the numerical keypad on the Brightness screen to change the brightness of the screen. (The default is 90%.) CTV-SVU01G-EN 53 Display Settings Display Units Use the Display Units screen to choose from the following display units: • SI • Inch-Pounds (default) Pressure Units Use the Pressure Units screen to choose from the following pressure units: • kPaA (default if “SI” is chosen for display units) • kPaG • psia (default if “Inch-Pound” is chosen for display units) • psig Backlight Timeout Use the numerical keypad on the Backlight Timeout screen to change the number of minutes of inactivity that pass until the screen dims. (The default is 60 minutes.) Viewing and Changing the Language Preference On the Settings screen, touch L a n g u a g e s to view a screen containing the following buttons (refer to the following figure): • • • • • • • • • • • • • • • • • • • • • • • • • • • 54 Arabic (Gulf Regions) Chinese—China Chinese—Taiwan Czech Dutch English French French (Canada) German Greek Hebrew Hungarian Indonesian Italian Japanese Korean Norwegian Polish Portuguese (Portugal) Portuguese (Brazil) Russian Romanian Spanish (Europe) Spanish (Latin America) Swedish Thai Turkish CTV-SVU01G-EN Display Settings Figure 32. Language screen The language that is currently in use on the display is expressed as the current value on the Language screen. The button that displays the current value is shaded (refer to the “English” button in the previous figure as an example). To change the language: 1. Touch the button that identifies the language you prefer. 2. Touch S a v e to confirm your selection and to return to the Settings screen. CTV-SVU01G-EN 55 Display Settings Viewing and Changing Date and Time Preferences On the Settings screen, touch D a t e a n d T i m e to view the Date and Time screen, shown in the following figure. Figure 33. Date and Time screen The current date and time for the display is expressed as the current value. The current value appears below the center line on the screen. Above the center line, the following date and time attributes appear: • Month • Day • Year • Hour • Minute • AM/PM To change the date or time: 1. Touch the square presenting the attribute you want to change. The square becomes highlighted. 2. Touch the up or down arrow key on the screen until the your desired selection appears. Repeat the process for any other attributes you want to change. 3. Touch S a v e to confirm your selection and return to the Settings screen. 56 CTV-SVU01G-EN Display Settings Clean Touchscreen On the Settings screen, touch C l e a n T o u c h s c r e e n to disable the Tracer® AdaptiView™ display screen for 15 seconds so that you can clean the screen without it responding to touch. During this time, the screen is black with a number in the center that counts down the seconds. After 15 seconds, the Settings screen re-appears. Figure 34. CTV-SVU01G-EN Countdown screen 57 Security Settings If security if enabled, the Tracer® AdaptiView™ display requires that you log in with a four-digit security PIN to make setting changes that are protected by security. This feature prevents unauthorized personnel from doing so. There are two levels of security, each allowing specific changes to be made. You can view all data without logging in. The log-in screen appears only when you try to change a setting that is protected by security, or when you touch the L o g i n button from the Settings screen. Settings Screen Touch the S e t t i n g s button in the main menu area (refer to “Screen Overview,” p. 8) to view the Settings screen. Security Settings identifies a column on the right side of the screen that contains two buttons (see the outlined column in the following figure): • Security • Log in (Log out) Figure 35. Equipment Settings screen with the Security Settings column highlighted N o t e : If security is disabled, the Log in/Log out button is not visible. Refer to “Disabling Security,” p. 58 and “Enabling Security,” p. 59. Disabling Security You can disable the security feature that allows a user to log in and log out. 1. From the Settings screen, touch the S e c u r i t y button. The Security screen appears as shown in the following figure. N o t e : If you are logged out, the Log In screen appears. You must first log in to proceed. 58 CTV-SVU01G-EN Security Settings Figure 36. Security screen 2. Touch the D i s a b l e button. The button becomes shaded. 3. Touch S a v e . The Settings screen appears with only the Security button visible. The Log in/ Log out button is gone. Enabling Security To enable security, perform the following steps: 1. From the Settings screen, touch the S e c u r i t y button. The Security screen appears as shown in “Disabling Security,” p. 58. 2. Touch the E n a b l e button. The button becomes shaded. 3. Touch S a v e . The Settings screen appears with a Log out button in addition to the Security button. Logging In There are two levels of security: • Security Level 1 allows users to change a limited group of secure settings. The default security PIN is 1111. • Security Level 2 allows users to change all secure settings. The default security PIN is 7123. A technician must use the Tracer® TU service tool to change a PIN. To log in: 1. Touch the L o g I n button. The Log In screen appears as shown in the following figure. CTV-SVU01G-EN 59 Security Settings Figure 37. Log In screen 2. Use the keypad to enter your PIN. • The PIN is a four-digit number, which was configured for your system with the Tracer® TU service tool. • As you enter the number, the PIN remains hidden by asterisks. N o t e : If you enter an invalid PIN, an error message appears on the Log in screen. 3. Touch S a v e . • If you viewed the Log In screen from touching L o g I n on the Settings screen, the Settings screen appears with a L o g O u t button on it. • If the Log In screen appeared when you tried to change a setting, you return to that setting screen. N o t e : The PIN is valid until 30 minutes of inactivity passes, or until you log out. 60 CTV-SVU01G-EN Security Settings Logging Out To log out: 1. Touch the L o g O u t button. A confirmation screen appears as shown in the following figure. Figure 38. Log Out confirmation screen 2. Touch Y e s to confirm that you want to log out. The Settings screen appears with a L o g I n button on it. LLID Binding LLID binding screen provides the capability to bind and unbind LLIDs, similar to Tracer® TU. It can be disabled in the configuration. I m p o r t a n t : LLID binding screen should ONLY be used by experienced service personnel. CTV-SVU01G-EN 61 Troubleshooting The following table contains information to help troubleshoot the Tracer® AdaptiView™ displays. Table 15. Common error messages with possible causes and solutions Issue Possible Causes/Solutions The screen only partially displays; the Auto and Stop buttons appear, but there is no text. The UC800 configuration is invalid. Download a valid configuration using the Tracer TU service tool. The following error message appears: UC800 Configuration is Invalid UC800 configuration must be updated with the Tracer TU technician utility Follow the error message instructions. The following error message appears: Communication lost with UC800 • Check power and communication cables • Update the UC800 software with the Tracer TU technician utility The following error message appears: Display Failed to Establish Communication • Check power and communication cables • Re-attempting connection in X seconds Communication has been established and then lost, or the UC800 configuration is invalid. Follow the error message instructions. Communication is not established. • The Ethernet cable and/or the power cable may be disconnected. Check the connections. • The UC800 may have an invalid configuration. Download a valid configuration using the Tracer TU service tool. A file is missing. The following error message appears: [*Missing file name] UC800 software must be updated with the Tracer TU technician utility 62 • The Tracer TU service tool is connected and the LLID binding screen is displayed. • UC800 has an invalid configuration. Download a valid configuration using the Tracer TU service tool. • Cycle power to the display and the UC800. Disconnect the USB cable and wait approximately 10 seconds before reconnecting the USB cable. CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers The following lists contain all of the data available for viewing on a Tracer® AdaptiView™ display that is connected to a CenTraVac™ Simplex chiller. Component Screen Data Chiller configuration determines which of the following settings and status points appear on the display. For more information, refer to “Component Screens,” p. 14. Table 16. Evaporator settings and status points (Simplex) Active Chilled Water Setpoint (button links to the Active Chiller Water Setpoint screen) Evaporator Rfgt Pressure Evaporator Pump Override (button links to Evaporator Pump Override screen) Evap Approach Temp Evap Water Flow Status Approx Evap Water Flow Evap Leaving Water Temp Evap Differential Wtr Press Evap Entering Water Temp Evaporator Entering Water Pressure Calculated Chiller Capacity Evaporator Leaving Water Pressure Evaporated Saturated Rfgt Temp Table 17. Condenser settings and status points (Simplex) Active Hot Water Setpoint (button links to the Active Hot Water Setpoint screen) Approx Cond Water Flow Cond Condenser Pump Override (button links to the Condenser Pump Override screen) Cond Differential Wtr Press Cond Water Flow Status Second Condenser Lvg Wtr Temp Cond Entering Water Temp Second Condenser Ent Wtr Temp Cond Leaving Water Temp Head Pressure Control Status Outdoor Air Temp Differential Refrigerant Pressure Condenser Sat Rfgt Temp Refrigerant Monitor Condenser Refrigerant Pressure Condenser Entering Water Pressure Condenser Refrigerant Liquid Level Condenser Leaving Water Pressure Condenser Approach Temperature Economizer Bypass Valve Position Table 18. Compressor settings and status points (Simplex) Compressor Running Status IGV 2 Percent Open Chiller Control Signal IGV 2 Position (Steps) Oil Pump Control Compressor Rfgt Discharge Temp Average Line Current (%RLA) HGBP Time Oil Pump Status Oil Differential Pressure Switch (CVG, CVR Only) Oil Differential Pressure Lube Differential Pressure (CVHS Only) Compressor Starts Lube Pump Discharge Pressure (CVHS Only) Compressor Running Time Lube Pump Suction Pressure (CVHS) Oil Pump Discharge Pressure Cond Rfgt Pressure CTV-SVU01G-EN 63 Appendix A: Data for CenTraVac Simplex Chillers Table 18. Compressor settings and status points (Simplex) (continued) Oil Tank Pressure Lube Pump Command (CVHS) Oil Tank Temperature Lube Flow First Stage Bearing (CVHS) Inboard Bearing Temperature Lube Flow Second Stage Bearing (CVHS) Outboard Bearing Temperature Outboard Bearing Pad Temperature #1 (CVHH Only) IGV 1 Percent Open Outboard Bearing Pad Temperature #2 (CVHH) IGV 1 Position (Steps) Outboard Bearing Pad Temperature #3 (CVHH) Table 19. Motor settings and status points (Simplex) Active Current Limit Setpoint (button links to Active Current Limit Setpoint screen) AFD Motor Current U % RLA Average Motor Current (%RLA) AFD Motor Current V % RLA ADF Frequency or Generator Frequency Command (based on configuration) AFD Motor Current W % RLA Starter Motor Current L1 (%RLA) AFD Motor Current U Starter Motor Current L2 (%RLA) AFD Motor Current V Starter Motor Current L3 (%RLA) AFD Motor Current W Starter Motor Current L1 (A) AFD Input Current L1 Starter Motor Current L2 (A) AFD Input Current L2 Starter Motor Current L3 (A) AFD Input Current L3 Starter Input Voltage Phase AB AFD Average Motor Voltage Starter Input Voltage Phase BC AFD Average Input Voltage Starter Input Voltage Phase CA AFD Motor Voltage UV Motor Winding Temp 1 AFD Motor Voltage VW Motor Winding Temp 2 AFD Motor Voltage WU Motor Winding Temp 3 AFD DC Bus Voltage AFD Speed AFD DC Bus Current AFD Transistor Temp AFD Calculated Input Voltage Starter Energy Consumption Resettable AFD Output Power Starter Energy Consumption Last Reset AFD Average Input Current Starter Energy Consump Non Reset Motor Speed Starter Power Demand Motor Frequency Starter Load Power Factor Table 20. Purge settings and status points (Simplex) Purge Top Level Mode (button links to Purge Operating Modes screen Pumpout Chiller On—7 days Purge Regen Cycle (button links to Purge Regen Cycle screen) Pumpout Chiller Off—7 days Purge Fault Indicator (button links to Alarms screen) Time Until Next Purge Run Daily Pumpout—24 Hours Purge Rfgt Compressor Suction Temp Average Daily Pumpout—7 Days Purge Liquid Temperature 64 CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers Table 20. Purge settings and status points (Simplex) (continued) Daily Pumpout Limit/Alarm Pumpout—Life Chiller On—7 Days Purge Carbon Tank Temp Reports The following data can be viewed on the Reports screen. For more information, refer to “Reports,” p. 23. Log Sheet Table 21. Evaporator report data Report item Unit Evaporator Entering Water Temperature XXX.X °F/°C Evaporator Leaving Water Temp XXX.X °F/°C Evaporator Sat Rfgt Temp XXX.X °F/°C Evaporator Rfgt Pressure XXX.X PSI/kPa Evaporator Approach Temp XXX.X °F/°C Evaporator Water Flow Switch Status Flow/No Flow Table 22. Condenser report data Report item Unit Cond Entering Water Temp XXX.X °F/°C Cond Leaving Water Temp XXX.X °F/°C Cond Sat Rfgt Temp XXX.X °F/°C Cond Rfgt Pressure XXX.X PSI/kPa Cond Approach Temp XXX.X °F/°C Cond Water Flow Switch Status Flow/No Flow Cond Rfgt Liquid Level XX.XX in/mm Table 23. Compressor report data Report item Unit Starts XXXX Starts Running Time XX:XX Hr:Min Oil Tank Pressure XXX.X PSI/kPa Oil Pump Discharge Pressure XXX.X PSI/kPa Oil Differential Pressure XXX.X PSI/kPa Oil Tank Temperature XXX.X °F/°C IGV 1 Position XXX.X % Oil Diff Pressure Switch (CVGF, CVR) XXX.X PSI/kPa Lube Pump Discharge Pressure (CVHS) XXX.X PSI/kPa Cond Rfgt Pressure (visible only with CVHS) XXX.X PSI/kPa IGV 1 Position Steps CTV-SVU01G-EN 65 Appendix A: Data for CenTraVac Simplex Chillers Table 23. Compressor report data (continued) Report item Unit IGV 2 Position XXX.X % IGV 2 Position Steps Table 24. Motor report data Report item Unit Starter Current L1 XXX.X % Starter Current L2 XXX.X % Starter Current L3 XXX.X % Starter Current L1 XXXX A Starter Current L2 XXXX A Starter Current L3 XXXX A Starter Voltage AB XXXXX.X V Starter Voltage BC XXXXX.X V Starter Voltage CA XXXXX.X V Starter Power Demand XXXX kW Starter Load Power Factor XX.X Motor Winding Temp 1 XXX.X °F/°C Motor Winding Temp 2 XXX.X °F/°C Motor Winding Temp 3 XXX.X °F/°C AFD Frequency XX Hz AFD Speed XXXX RPM AFD Transistor Temp XXX.X °F/°C AFD Motor Current U % RLA XXX.X %RLA AFD Motor Current V % RLA XXX.X %RLA AFD Motor Current W % RLA XXX.X %RLA AFD Motor Current U XXXX Amps AFD Motor Current V XXXX Amps AFD Motor Current W XXXX Amps AFD Motor Voltage UV XXXXX.X Volts AFD Motor Voltage VW XXXXX.X Volts AFD Motor Voltage WU XXXXX.X Volts Starter Input Power Consumption XXXXX kWh Starter Motor Power Factor XXX.X Table 25. Purge report data Report item Unit Time Until Next Purge Run XXX.X min Daily Pumpout—24 Hours XXX.X min 66 CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers Table 25. Purge report data (continued) Report item Unit Average Daily Pumpout—7 Days XXX.X min Daily Pumpout Limit XXX.X min Chiller On—7 Days XXX.X min Pumpout Chiller On—7 Days XXX.X min Pumpout Chiller Off—7 Days XXX.X min Pumpout—Life XXX.X min Purge Rfgt Compressor Suction Temp XXX.X °F/°C Purge Liquid Temp XXX.X °F/°C Purge Carbon Tank Temp XXX.X °F/°C ASHRAE Chiller Log N o t e : The ASHRAE Chiller Log contains those items recommended by ASHRAE Std 147 Standard 147-2002, Reducing Release of Halogenated Refrigerants from Refrigeration and AirConditioning Equipment and Systems. Table 26. ASHRAE Chiller Log data Data Name Value Current Date/Time User-selected date/time format Chiller Top Level Mode Running /Stopped / Run Inhibit / Auto / etc. Starter Motor Current L1 XXX.X A Starter Motor Current L2 XXX.X A Starter Motor Current L3 XXX.X A AFD Motor Current U XXXX A AFD Motor Current V XXXX A AFD Motor Current W XXXX A AFD Motor Voltage UV XXXX v AFD Motor Voltage VW XXXX v AFD Motor Voltage WU XXXX v Starter Input Voltage AB XXXX.X v Starter Input Voltage BC XXXX.X v Starter Input Voltage CA XXXX.X v Active Chilled Water Setpoint XXX.X °F/C Active Current Limit Setpoint XXX.X % Refrigerant Type XXXXX Refrigerant Monitor XXX ppm Daily Pumpout - 24 Hours XX:XX Min:Sec Daily Pumpout Limit XXX Min Pumpout - Life XXX:XX Min:Sec Purge Top Level Mode On/Auto/Adaptive/Stop CTV-SVU01G-EN 67 Appendix A: Data for CenTraVac Simplex Chillers Table 26. ASHRAE Chiller Log data (continued) Data Name Value Purge Mode On/Auto/Adaptive/Stop Compressor Starts XXXX Compressor Running Time XX:XX Hr:Min Compressor Refrigerant Discharge Temperature* XXX.X °F/C Oil Pump Discharge Pressure XXX.X PSIA/kPaA Oil Tank Pressure XXX.X PSIA/kPaA Oil Differential Pressure XXX.XX PSID/kPaD Oil Diff Pressure Switch (CVGF, CVR only) Flow/No Flow Lube Pump Discharge Pressure (CVHS) XXX.X PSIA/kPaA Cond Rfgt Pressure (visible only with CVHS) XXX.X PSIA/kPaA Lube Differential Pressure (CVHS) XXX.XX PSID/kPaD Lube Pump Suction Pressure (CVHS) XXX.X PSIA/kPaA Oil Tank Temperature XXX.X °F/C Inboard Bearing Temp XXX.X °F/C Outboard Bearing Temp XXX.X °F/C Daily Pumpout - 24 Hours XX:XX Min:Sec Daily Pumpout Limit XXX Min Pumpout - Life XXX:XX Min:Sec Purge Top Level Mode On/Auto/Adaptive/Stop Purge Mode On/Auto/Adaptive/Stop Compressor Starts XXXX Compressor Running Time XX:XX Hr:Min Compressor Refrigerant Discharge Temperature* XXX.X °F/C Oil Pump Discharge Pressure XXX.X PSIA/kPaA Oil Tank Pressure XXX.X PSIA/kPaA Oil Differential Pressure XXX.XX PSID/kPaD Oil Diff Pressure Switch (CVGF, CVR only) Flow/No Flow Lube Pump Discharge Pressure (CVHS) XXX.X PSIA/kPaA Cond Rfgt Pressure (visible only with CVHS) XXX.X PSIA/kPaA Lube Differential Pressure (CVHS) XXX.XX PSID/kPaD Lube Pump Suction Pressure (CVHS) XXX.X PSIA/kPaA Oil Tank Temperature XXX.X °F/C 68 CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers Table 26. ASHRAE Chiller Log data (continued) Data Name Value Inboard Bearing Temp XXX.X °F/C Outboard Bearing Temp XXX.X °F/C Evaporator Entering Water Temperature XXX.X °F/C Evaporator Leaving Water Temperature XXX.X °F/C Evap Sat Rfgt Temp XXX.X °F/C Evap Rfgt Pressure XXX.X PSIA/kPaA Evap Approach Temp XXX.X °F/C Evap Water Flow Status Flow/No Flow Evap Differential Wtr Press XXX.XX PSID/kPaD Approx Evap Water Flow XXX.X gpm/lpm Calculated Chiller Capacity XXX.X tons/kW Cond Entering Water Temp XXX.X °F/C Cond Leaving Water Temp XXX.X °F/C Cond Sat Rfgt Temp XXX.X °F/C Cond Rfgt Pressure XXX.X PSIA/kPaA Cond Approach Temp XXX.X °F/C Cond Water Flow Status: Flow/No Flow Cond Differential Wtr Press XXX.XX PSID/kPaD Approx Cond Water Flow XXX.X gpm/lpm Second Condenser Ent Wtr Temp XXX.X °F/C Second Condenser Lvg Wtr Temp XXX.X °F/C Items Available to Include in Custom Reports Table 27. Chiller data Controller Build Part Number Ice Building Active Version Refrigerant Monitor Chiller Heating or Cooling Mode Chiller Top Level Mode Chiller Heating or Cooling Mode Table 28. Evaporator data Active Chilled Water Setpoint Evaporator Leaving Water Temperature Active Chilled Water Setpoint Source Evaporator Pump Override Active Ice Termination Setpoint Evaporator Pump Override Time Remaining Active Ice Termination Setpoint Source Evap Rfgt Pressure Calculated Chiller Capacity Evap Sat Rfgt Temp Approx Evap Water Flow Evap Water Flow Status BAS Chilled Water Setpoint Ext Chilled Wtr Setpt CTV-SVU01G-EN 69 Appendix A: Data for CenTraVac Simplex Chillers Table 28. Evaporator data (continued) Evap Approach Temp Front Panel Ice Building Command Evap Differential Wtr Press Evaporator Entering Water Pressure Evaporator Entering Water Temperature Evaporator Leaving Water Pressure Table 29. Condenser data Active Hot Water Setpoint Second Condenser Lvg Wtr Temp Active Hot Water Setpoint Source Condenser Pump Override Time Remaining Approx Cond Water Flow Condenser Pump Override Cond Approach Temp Differential Refrigerant Pressure Cond Differential Wtr Press Head Pressure Control Status Cond Entering Water Temp Condenser Entering Water Pressure Cond Leaving Water Temp Condenser Leaving Water Pressure Cond Rfgt Pressure Condenser Refrigerant Liquid Level Ckt1 Cond Sat Rfgt Temp Economizer Bypass Valve Position Ckt1 Cond Water Flow Status Condenser Refrigerant Liquid Level Ckt2 Outdoor Air Temp Economizer Bypass Valve Position Ckt2 Second Condenser Ent Wtr Temp Table 30. Compressor data Chiller Control Signal Oil Pump Control Active Base Loading Setpoint Oil Pump Command Active Base Loading Setpoint Source Oil Pump Discharge Pressure Compressor Refrigerant Discharge Temperature Oil Pump Override Time Remaining Compressor Running Lube Differential Pressure (CVHS) Compressor Running Time Lube Pump Control (CVHS) Compressor Starts Lube Pump Command (CVHS) Hot Gas Bypass Total Time Lube Pump Discharge Pressure (CVHS) IGV1 Position Lube Pump Override Time Remaining (CVHS) IGV1 Position Steps Lube Pump Suction Pressure (CVHS) IGV2 Position Oil Tank Temperature IGV2 Position Steps Lube Flow First Stage Bearing (CVHS) IGV Closed Switch Lube Flow Second Stage Bearing (CVHS) Oil Tank Pressure Inboard Bearing Temp Oil Differential Pressure Outboard Bearing Temp 70 CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers Table 30. Compressor data (continued) Oil Differential Pressure Switch (CVGF, CVR only) Outboard Bearing Pad Temperature #1 Oil Heater Command Outboard Bearing Pad Temperature #2 Oil Heater Command 4E1 Outboard Bearing Pad Temperature #3 Oil Heater Command 4E2 Compressor Vibration Table 31. Motor data Active Current Limit Setpoint Motor Winding Temp #1 Active Current Limit Setpoint Source Motor Winding Temp #2 BAS Current Limit Setpoint Motor Winding Temp #3 Starter Input Power Consumption AFD Average Input Current Starter Power Demand AFD Input Current L1 Starter Motor Power Factor AFD Input Current L2 Motor Speed AFD Input Current L3 Motor Frequency AFD Input Frequency Speed Command RPM AFD Average Motor Voltage Speed Command (CVHS) AFD Calculated Input Voltage Average Motor Current % RLA AFD DC Bus Voltage Electro-Mech. Phase Unbalance AFD DC Bus Current Ext Current Limit Setpt AFD Output Power Frequency Command AFD Ground Current Speed Signal AFD Inverter Base Temp Motor Coolant Temperature AFD Rectifier Base Temp MTC Switch AFD Transistor Temp Restart Inhibit Time (MP) AFD Motor Current U % RLA Starter Average Phase Voltage AFD Motor Current V % RLA Starter Motor Current L1 % RLA AFD Motor Current W % RLA Starter Motor Current L1 AFD Motor Current U Starter Motor Current L2 % RLA AFD Motor Current V Starter Motor Current L2 AFD Motor Current W Starter Motor Current L3 % RLA AFD Motor Voltage UV Starter Motor Current L3 AFD Motor Voltage VW Starter Energy Consump. NonReset AFD Motor Voltage WU Starter Energy Consump. Resettable AFD Average Input Voltage Starter Energy Consump. Last Reset AFD Inverter Module Temp U Starter Input Voltage AB AFD Inverter Module Temp V Starter Input Voltage BC AFD Inverter Module Temp W Starter Input Voltage CA AFD Total Demand Distortion Motor Temperature CTV-SVU01G-EN 71 Appendix A: Data for CenTraVac Simplex Chillers Table 32. Purge data Average Daily Pumpout-7 Days Carbon Tank Temp Carbon Regen Cycles Purge Liquid Temp Chiller On-7 Days Purge Rfgt Cprsr Suction Temp Daily Pumpout-24 Hours Time at Last Regeneration Pumpout Chiller Off-7 Days Time Until Next Purge Run Pumpout Chiller On-7 Days Purge Top Level Mode Pumpout-Life Data Graph Data Points This subsection contains: • Data points used in the default data graphs, organized by graph • Data points available to include in custom data graphs, organized by component Data Points Used in Default Data Graphs Table 33. Chiller overview 1 Graph data point Axis Active Chilled Water Setpoint Left Y-axis Active Hot Water Setpoint Left Y-axis Evaporator Leaving Evaporator Temperature Left Y-axis Evaporator Entering Water Temperature Left Y-axis Condenser Leaving Water Temperature Left Y-axis Condenser Entering Water Temperature Left Y-axis Calculated Chiller Capacity Right Y-axis Table 34. Chiller overview 2 Graph data point Axis Average Motor Current % RLA Left Y-axis Motor Frequency Left Y-axis Oil Differential Pressure Left Y-axis Frequency Command Left Y-axis Lube Differential Pressure (CVHS) Left Y-axis Speed Command (CVHS) Right Y-axis Table 35. Approach temperature Graph data point Axis Evaporator Approach Temperature Left Y-axis Condenser Approach Temperature Left Y-axis Approximate Evaporator Water Flow Right Y-axis 72 CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers Table 35. Approach temperature (continued) Graph data point Axis Approximate Condenser Water Flow Right Y-axis Average Motor Current % RLA Right Y-axis Table 36. Evaporator Graph data point Axis Active Chilled Water Setpoint Left Y-axis Evaporator Leaving Water Temperature Left Y-axis Evaporator Entering Water Temperature Left Y-axis Evaporator Saturated Refrigerant Temperature Left Y-axis Approximate Evaporator Water Flow Right Y-axis Table 37. Motor Graph data point Axis Starter Motor Current L1 % RLA Left Y-axis Starter Motor Current L2 % RLA Left Y-axis Starter Motor Current L3 % RLA Left Y-axis Average Motor Current % RLA Left Y-axis Starter Input Voltage AB Right Y-axis Starter Input Voltage BC Right Y-axis Starter Input Voltage CA Right Y-axis AFD Motor Current U % RLA Left Y-axis AFD Motor Current V % RLA Left Y-axis AFD Motor Current W % RLA Left Y-axis AFD Motor Voltage UV Right Y-axis AFD Motor Voltage VW Right Y-axis AFD Motor Voltage WU Right Y-axis Table 38. Motor temperature Graph data point Axis Motor Winding Temperature 1 Left Y-axis Motor Winding Temperature 2 Left Y-axis Motor Winding Temperature 3 Left Y-axis AFD Transistor Temperature Left Y-axis Table 39. Condenser Graph data point Axis Active Hot Water Setpoint Left Y-axis Condenser Leaving Water Temperature Left Y-axis Condenser Entering Water Temperature Left Y-axis CTV-SVU01G-EN 73 Appendix A: Data for CenTraVac Simplex Chillers Table 39. Condenser (continued) Graph data point Axis Condenser Saturated Refrigerant Temperature Left Y-axis Approximate Condenser Water Flow Right Y-axis Table 40. Compressor Graph data point Axis Average Line Current Left Y-axis Active Current Limit Setpoint Left Y-axis AFD Frequency Left Y-axis IGV 1 Position Left Y-axis Chiller Control Signal Left Y-axis Compressor Refrigerant Discharge Temperature Right Y-axis Table 41. Purge Graph data point Axis Daily Pumpout—24 Hours Left Y-axis Pumpout Chiller On—7 Days Left Y-axis Pumpout Chiller Off—7 Days Left Y-axis Purge Average Daily Pumpout—7 Days Right Y-axis Purge Refrigerant Compressor Suction Temperature Right Y-axis Purge Liquid Temperature Right Y-axis Table 42. Oil system Graph data point Axis Oil Differential Pressure Left Y-axis Oil Tank Pressure Left Y-axis Oil Pump Discharge Pressure Left Y-axis Oil Tank Temperature Right Y-axis Outboard Bearing Temperature Right Y-axis Inboard Bearing Temperature Right Y-axis Table 43. Lube system Graph data point Axis Lube Differential Pressure Left Y-axis Lube Pump Discharge Pressure Left Y-axis Cond Rfgt Pressure Left Y-axis Lube Pump Suction Pressure Left Y-axis Lube Flow First Stage Bearing Right Y-axis Lube Flow Second Stage Bearing Right Y-axis 74 CTV-SVU01G-EN Appendix A: Data for CenTraVac Simplex Chillers Data Points in Custom Data Graphs Table 44. Evaporator Active Chilled Water Setpoint Approx Evap Water Flow Evaporator Leaving Water Temperature Evap Differential Wtr Press Evaporator Entering Water Temperature Calculated Chiller Capacity Evap Sat Rfgt Temp Evap Approach Temp Evap Rfgt Pressure Active Ice Termination Setpoint Table 45. Compressor Chiller Control Signal Inboard Bearing Temp Oil Tank Pressure Outboard Bearing Temp Oil Pump Discharge Pressure Outboard Bearing Pad Temperature #1 Oil Differential Pressure Outboard Bearing Pad Temperature #2 Lube Pump Suction Pressure (CVHS) Outboard Bearing Pad Temperature #3 Lube Pump Discharge Pressure (CVHS) IGV1 Position (%) Lube Differential Pressure (CVHS) IGV2 Position (%) Oil Tank Temperature Compressor Refrigerant Discharge Temperature Lube Flow First Stage Bearing (CVHS) Compressor Vibration Lube Flow Second Stage Bearing (CVHS) Table 46. Condenser Active Hot Water Setpoint Cond Approach Temp Cond Leaving Water Temp Approx Cond Water Flow Cond Entering Water Temp Cond Differential Wtr Press Cond Sat Rfgt Temp Second Condenser Lvg Wtr Temp Outdoor Air Temp Second Condenser Ent Wtr Temp Refrigerant Monitor Differential Refrigerant Pressure Cond Rfgt Pressure Head Pressure Control Status Table 47. Motor Active Current Limit Setpoint AFD Input Current L1 Average Motor Current %RLA AFD Input Current L2 Motor Frequency AFD Input Current L3 Speed Command (CVHS) AFD Input Frequency Starter Motor Current L1 % RLA AFD Average Motor Voltage Starter Motor Current L2 % RLA AFD DC Bus Voltage Starter Motor Current L3 % RLA AFD DC Bus Current CTV-SVU01G-EN 75 Appendix A: Data for CenTraVac Simplex Chillers Table 47. Motor (continued) Starter Motor Current L1 AFD Output Power Starter Motor Current L2 AFD Ground Current Starter Motor Current L3 AFD Inverter Base Temp Starter Input Voltage AB AFD Rectifier Base Temp Starter Input Voltage BC AFD Transistor Temp Starter Input Voltage CA AFD Motor Current U % RLA Motor Winding Temp #1 AFD Motor Current V % RLA Motor Winding Temp #2 AFD Motor Current W % RLA Motor Winding Temp #3 AFD Motor Voltage UV Motor Temperature AFD Motor Voltage VW Motor Coolant Temperature AFD Motor Voltage WU Starter Input Power Consumption AFD Average Input Voltage Starter Power Demand AFD Inverter Module Temp U Starter Motor Power Factor AFD Inverter Module Temp V Starter Average Phase Voltage AFD Inverter Module Temp W Frequency Command AFD Total Demand Distortion AFD Average Input Current Table 48. Purge Daily Pumpout—24 Hours Purge Rfgt Cprsr Suction Temp Pumpout Chiller On—7 Days Purge Liquid Temp Pumpout Chiller Off—7 Days Carbon Tank Temp Purge Average Daily Pumpout—7 Days 76 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers The following lists contain all of the data available for viewing on a Tracer® AdaptiView™ display that is connected to a CenTraVac™ Duplex™ chiller. Component Screen Data Chiller configuration determines which of the following settings and status points appear on the display. For more information, refer to “Component Screens,” p. 14. Table 49. Evaporator settings and status points Active Chilled Water Setpoint (button links to the Active Chiller Water Setpoint screen) Evaporator Rfgt Pressure (Ckt1 and Ckt2) Evaporator Pump Override (button links to Evaporator Pump Override screen) Evap Approach Temp (Ckt1 and Ckt2) Evap Water Flow Status Approx Evap Water Flow Evap Leaving Water Temp Evap Differential Wtr Press Evap Entering Water Temp Evap Entering Water Press Calculated Chiller Capacity Evap Leaving Water Press Evaporator Saturated Rfgt Temp (Ckt1 and Ckt2) Table 50. Condenser settings and status points Active Hot Water Setpoint (button links to the Active Hot Water Setpoint screen) Condenser Approach Temperature (Ckt1 and Ckt2) Condenser Pump Override (button links to the Condenser Pump Override screen) Approx Cond Water Flow Cond Water Flow Status Cond Differential Wtr Press Cond Entering Water Temp Second Condenser Lvg Wtr Temp Cond Leaving Water Temp Second Condenser Ent Wtr Temp Outdoor Air Temp Cond Entering Water Press Condenser Refrigerant Pressure (Ckt1 and Ckt2) Cond Leaving Water Press Table 51. Compressor settings and status points Compressor Running (Ckt1 and Ckt2) Inboard Bearing Temperature (Ckt1 and Ckt2) Chiller Control Signal Outboard Bearing Temperature (Ckt1 and Ckt2) Oil Pump Control (Ckt1 and Ckt2) IGV 1 Percent Open (Ckt1 and Ckt2) Average Motor Current %RLA (Ckt1 and Ckt2) IGV 1 Position (Steps) (Ckt1 and Ckt2) Compressor Starts (Ckt1 and Ckt2) IGV 2 Percent Open (Ckt1 and Ckt2) Oil Pump Status (Ckt1 and Ckt2) IGV 2 Position (Steps) (Ckt1 and Ckt2) Oil Differential Pressure (Ckt1 and Ckt2) Compressor Rfgt Discharge Temp (Ckt1 and Ckt2) Compressor Running Time (Ckt1 and Ckt2) Outboard Bearing Pad Temperature #1 CktX (for CDHH) Oil Pump Discharge Pressure (Ckt1 and Ckt2) Outboard Bearing Pad Temperature #2 CktX (for CDHH) Oil Tank Pressure (Ckt1 and Ckt2) Outboard Bearing Pad Temperature #3 CktX (for CDHH) Oil Tank Temperature (Ckt1 and Ckt2) CTV-SVU01G-EN 77 Appendix B: Data for CenTraVac Duplex Chillers Table 52. Motor settings and status points Active Current Limit Setpoint Starter Input Voltage BC CktX Average Motor Current % RLA CktX Starter Input Voltage CA Ck Motor Frequency CktX Motor Winding Temperature 1 CktX Frequency Command CktX Motor Winding Temperature 2 CktX Starter Motor Current L1 % RLA CktX Motor Winding Temperature 3 CktX Starter Motor Current L2 % RLA CktX Motor Temperature CktX Starter Motor Current L3 % RLA CktX Motor Speed CktX Starter Motor Current L1 CktX Starter AFD Transistor Temperature CktX Motor Current L2 CktXStarter AFD Input Frequency Motor Current L3 CktX Starter Input Power Consumption CktX AFD Input Current L1 CktX Starter Power Demand CktX Starter Motor Power Factor CktX AFD Input Current L2 CktXAFD AFD Output Power CktX Input Current L3 CktX AFD Average Input Current CktX AFD Output Voltage CktX Starter Energy Consump. Resettable CktX AFD DC Bus Voltage CktX Starter Energy Consump. Non Reset CktX AFD DC Bus Current CktX Starter Energy Consump. Time of Last Reset CktX Starter Input Voltage AB CktX Table 53. Purge settings and status points Purge Top Level Mode (button links to Purge Operating Modes screen) (Ckt1 and Ckt2) Pumpout Chiller On—7 days (Ckt1 and Ckt2) Purge Regen Cycle (button links to PUrge Regen Cycle) (Ckt1 and Ckt2) Pumpout Chiller Off—7 days (Ckt1 and Ckt2) Purge Fault Indicator (button links to Alarms screen) (Ckt1 and Ckt2) Time Until Next Purge Run (Ckt1 and Ckt2) Daily Pumpout—24 Hours (Ckt1 and Ckt2) Purge Rfgt Compressor Suction Temp (Ckt1 and Ckt2) Average Daily Pumpout—7 Days (Ckt1 and Ckt2) Purge Liquid Temperature (Ckt1 and Ckt2) Daily Pumpout Limit (Ckt1 and Ckt2) Pumpout—Life (Ckt1 and Ckt2) Chiller On—7 Days (Ckt1 and Ckt2) Purge Carbon Tank Temp (Ckt1 and Ckt2) Reports The following data can be viewed on the Reports screen. For more information, refer to “Reports,” p. 23. 78 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers Log Sheet Table 54. Evaporator Report item Unit Evaporator Entering Water Temperature XXX.X °F/°C Evaporator Leaving Water Temp XXX.X °F/°C Evaporator Water Flow Status Flow/No Flow Evaporator Sat Rfgt Temp (Ckt1 and Ckt2) XXX.X °F/°C Evaporator Rfgt Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Evaporator Approach Temp (Ckt1 and Ckt2) XXX.X °F/°C Table 55. Condenser Report item Unit Cond Entering Water Temp Cond Entering Water Temp Cond Leaving Water Temp Cond Leaving Water Temp Cond Water Flow Status Cond Water Flow Status Cond Sat Rfgt Temp (Ckt1 and Ckt2) Cond Sat Rfgt Temp (Ckt1 and Ckt2) Cond Rfgt Pressure (Ckt1 and Ckt2) Cond Rfgt Pressure (Ckt1 and Ckt2) Cond Approach Temp (Ckt1 and Ckt2) Cond Approach Temp (Ckt1 and Ckt2) Table 56. Motor Report item Unit Starter Current L1 %RLA (Ckt1 and Ckt2) XXX.X % Starter Current L2 %RLA (Ckt1 and Ckt2) XXX.X % Compressor Starts (Ckt1 and Ckt2) XXXX Starts Compressor Running Time (Ckt1 and Ckt2) XX:XX Hr:Min Oil Tank Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Oil Pump Discharge Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Oil Differential Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Oil Tank Temperature (Ckt1 and Ckt2) XXX.X °F/°C IGV 1 Percent Open (Ckt1 and Ckt2) XXX.X % IGV 1 Position (Ckt1 and Ckt2) Steps IGV 2 Percent Open (Ckt1 and Ckt2) XXX.X % IGV 2 Position (Ckt1 and Ckt2) Steps Starter Current L3 %RLA (Ckt1 and Ckt2) XXX.X % Starter Current L1 (Ckt1 and Ckt2) XXXX A Starter Current L2 (Ckt1 and Ckt2) XXXX A Starter Current L3 (Ckt1 and Ckt2) XXXX A Starter Voltage Phase AB (Ckt1 and Ckt2) XXXXX.X V Starter Voltage Phase BC (Ckt1 and Ckt2) XXXXX.X V Starter Voltage Phase CA (Ckt1 and Ckt2) XXXXX.X V CTV-SVU01G-EN 79 Appendix B: Data for CenTraVac Duplex Chillers Table 56. Motor (continued) Report item Unit Starter Power Demand (Ckt1 and Ckt2) XXXX kW Starter Load Power Factor (Ckt1 and Ckt2) XX.X Motor Winding Temp 1 (Ckt1 and Ckt2) XXX.X °F/°C Motor Winding Temp 2 (Ckt1 and Ckt2) XXX.X °F/°C Motor Winding Temp 3 (Ckt1 and Ckt2) XXX.X °F/°C AFD Frequency (Ckt1 and Ckt2) XX Hz AFD Speed (Ckt1 and Ckt2) XXXX RPM AFD Transistor Temp (Ckt1 and Ckt2) XXX.X °F/°C Table 57. Purge Report item Unit Time Until Next Purge Run (Ckt1 and Ckt2) XXX.X min Daily Pumpout—24 Hours (Ckt1 and Ckt2) XXX.X min Average Daily Pumpout—7 Days (Ckt1 and Ckt2) XXX.X min Daily Pumpout Limit (Ckt1 and Ckt2) XXX.X min Chiller On—7 Days (Ckt1 and Ckt2) XXX.X min Pumpout Chiller On—7 Days (Ckt1 and Ckt2) XXX.X min Pumpout Chiller Off—7 Days (Ckt1 and Ckt2) XXX.X min Pumpout—Life (Ckt1 and Ckt2) XXX.X min Purge Rfgt Compressor Suction Temp (Ckt1 and Ckt2) XXX.X °F/°C Purge Liquid Temp (Ckt1 and Ckt2) XXX.X °F/°C Purge Carbon Tank Temp (Ckt1 and Ckt2) XXX.X °F/°C ASHRAE Chiller Log N o t e : The ASHRAE Chiller Log contains those items recommended by ASHRAE Std 147 Standard 147-2002, Reducing Release of Halogenated Refrigerants from Refrigeration and AirConditioning Equipment and Systems. Table 58. ASHRAE Chiller Log data Data name Value Current Date/Time User-selected date/time format Chiller Top Level Mode Dependent on chiller type Evap Entering Water Temp XXX.X °F/C° Evap Leaving Water Temp XXX.X °F/C° Evap Water Flow Status Flow/No Flow Evap Differential Wtr Press XXX.X PSI/kPa Approx Evap Water Flow XXX.X gpm/lpm Calculated Chiller Capacity XXXX tons/kW Refrigerant Type R123 80 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers Table 58. ASHRAE Chiller Log data (continued) Data name Value Refrigerant Monitor XXX.X ppm Active Chilled Water Setpoint XXX.X F°/C° Active Current Limit Setpoint XXX.X % Cond Entering Water Temp XXX.X °F/C° Cond Leaving Water Temp XXX.X °F/C° Cond Water Flow Status Flow/No Flow Cond Differential Wtr Press XXX.X PSI/kPa Approx Cond Water Flow XXXX gpm/lpm Top Level Operating Mode (Ckt1 and Ckt2) Dependent on chiller type Evaporator Saturated Rfgt Temp (Ckt1 and Ckt2) XXX.X °F/C° Evaporator Refrigerant Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Evaporator Approach Temp (Ckt1 and Ckt2) XXX.X °F/C° Condenser Saturated Rfgt Temp (Ckt1 and Ckt2) XXX.X °F/C° Condenser Refrigerant Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Condenser Approach Temperature (Ckt1 and Ckt2) XXX.X °F/C° Compressor Starts (Ckt1 and Ckt2) XXXX Compressor Running Time (Ckt1 and Ckt2) XX:XX Hr:Min Compressor Refrigerant Discharge Temperature (Ckt1 and Ckt2) XXX.X °F/C° Oil Pump Discharge Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Oil Tank Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Oil Differential Pressure (Ckt1 and Ckt2) XXX.X PSI/kPa Oil Tank Temperature (Ckt1 and Ckt2) XXX.X °F/C° Inboard Bearing Temp (Ckt1 and Ckt2) XXX.X °F/C° Outboard Bearing Temp (Ckt1 and Ckt2) XXX.X F°/C° Daily Pumpout—24 Hrs (Ckt1 and Ckt2) XXX.X Min Daily Pumpout Limit (Ckt1 and Ckt2) XXX.X Min Pumpout—Life (Ckt1 and Ckt2) XXXXXX.X Hours Purge Top Level Mode (Ckt1 and Ckt2) On/Auto/Adaptive/Stop Purge Operating Mode (Ckt1 and Ckt2) On/Auto/Adaptive/Stop Starter Current L1 (Ckt1 and Ckt2) XXXX A Starter Current L2 (Ckt1 and Ckt2) XXXX A Starter Current L3 (Ckt1 and Ckt2) XXXX A Starter Voltage Phase AB (Ckt1 and Ckt2) XXXX V Starter Voltage Phase BC (Ckt1 and Ckt2) XXXX V Starter Voltage Phase CA (Ckt1 and Ckt2) XXXX V CTV-SVU01G-EN 81 Appendix B: Data for CenTraVac Duplex Chillers Items Available to Include in Custom Reports Table 59. Chiller Active Base Loading Setpoint Version Active Base Loading Setpoint Source Chiller Heating or Cooling Mode Application Part Number Chiller Top Level Mode Table 60. Evaporator Active Chilled Water Setpoint Evaporator Saturated Refrigerant Temperature (Ckt1 and Ckt2) Active Chilled Water Setpoint Source Evaporator Water Flow Status BAS Chilled Water Setpoint Active Ice Termination Setpoint Evaporator Approach Temperature (Ckt1 and Ckt2) Active Ice Termination Setpoint Source Evaporator Entering Water Temperature Calculated Chiller Capacity Evaporator Leaving Water Temperature Approx Evap Water Flow Evaporator Pump Override Evap Differential Wtr Pressure Evaporator Pump Override Time Remaining External Chilled Water Setpoint Evaporator Refrigerant Pressure (Ckt1 and Ckt2) Front Panel Ice Building Command Table 61. Compressor Chiller Control Signal Oil Differential Pressure (Ckt1 and Ckt2) Active Base Loading Setpoint Oil Heater Command (Ckt1 and Ckt2) Active Base Loading Setpoint Source Oil Pump Control (Ckt1 and Ckt2) Compressor Refrigerant Discharge Temperature (Ckt1 and Ckt2) Oil Pump Command (Ckt1 and Ckt2) Compressor Running Status (Ckt1 and Ckt2) Oil Pump Discharge Pressure (Ckt1 and Ckt2) Compressor Running Time (Ckt1 and Ckt2) Oil Pump Override Time Remaining Compressor Starts (Ckt1 and Ckt2) Oil Tank Pressure (Ckt1 and Ckt2) Inboard Bearing Temperature (Ckt1 and Ckt2) Oil Tank Temperature (Ckt1 and Ckt2) IGV1 Position (Ckt1 and Ckt2) Oil Pump Override Time Remaining (Ckt1 and Ckt2) IGV1 Percent Open (Ckt1 and Ckt2) Outboard Bearing Temperature (Ckt1 and Ckt2) IGV2 Position (Ckt1 and Ckt2) Inboard Bearing Temperature (Ckt1 and Ckt2) IGV2 Percent Open (Ckt1 and Ckt2) Table 62. Condenser Condenser Approach Temperature (Ckt1 and Ckt2) Condenser Pump Override Condenser Entering Water Temperature (Ckt1 and Ckt2) Active Hot Water Setpoint Condenser Leaving Water Temperature (Ckt1 and Ckt2) Active Hot Water Setpoint Source Condenser Refrigerant Pressure (Ckt1 and Ckt2) Approx Cond Water Flow Condenser Saturated Refrigerant Temperature (Ckt1 and Ckt2) Cond Differential Wtr Press Condenser Water Flow Status Outdoor Air Temperature Condenser Pump Override Time Remaining 82 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers Table 63. Motor Active Current Limit Setpoint Phase Unbalance (Ckt1 and Ckt2) Active Current Limit Setpoint Source Restart Inhibit Time (MP) (Ckt1 and Ckt2) BAS Current Limit Setpoint Starter Average Phase Voltage (Ckt1 and Ckt2) External Current Limit Setpoint Starter Current L1 %RLA (Ckt1 and Ckt2) AFD DC Bus Voltage (Ckt1 and Ckt2) Starter Current L1 (Ckt1 and Ckt2) AFD Output Power (Ckt1 and Ckt2) Starter Current L2 %RLA (Ckt1 and Ckt2) AFD Transistor Temperature (Ckt1 and Ckt2) Starter Current L2 (Ckt1 and Ckt2) Starter Power Consumption (Ckt1 and Ckt2) Starter Current L3 %RLA (Ckt1 and Ckt2) Starter Load Power Factor (Ckt1 and Ckt2) Starter Current L3 (Ckt1 and Ckt2) Speed (Ckt1 and Ckt2) Starter Energy Consumption Not Resettable (Ckt1 and Ckt2) Frequency (Ckt1 and Ckt2) Starter Energy Consumption Resettable (Ckt1 and Ckt2) Generator Frequency Command (Ckt1 and Ckt2) Starter Energy Consumption Last Reset (Ckt1 and Ckt2) Generator Speed Signal (Ckt1 and Ckt2) Starter Power Demand (Ckt1 and Ckt2) Average Line Current %RLA (Ckt1 and Ckt2) Starter Voltage Phase AB (Ckt1 and Ckt2) Motor Winding Temperature 1 (Ckt1 and Ckt2) Starter Voltage Phase BC (Ckt1 and Ckt2) Motor Winding Temperature 2 (Ckt1 and Ckt2) Starter Voltage Phase CA (Ckt1 and Ckt2) Motor Winding Temperature 3 (Ckt1 and Ckt2) Table 64. Purge Purge Top Level Mode (Ckt1 and Ckt2) Pumpout—Life (Ckt1 and Ckt2) Average Daily Pumpout—7 Days (Ckt1 and Ckt2) Purge Carbon Tank Temp (Ckt1 and Ckt2) Carbon Regen Cycles (Ckt1 and Ckt2) Purge Liquid Temperature (Ckt1 and Ckt2) Chiller On—7 Days (Ckt1 and Ckt2) Purge Refrigerant Compressor Suction Temp (Ckt1 and Ckt2) Daily Pumpout—24 Hours (Ckt1 and Ckt2) Time at Last Regeneration (Ckt1 and Ckt2) Pumpout Chiller Off—7 Days (Ckt1 and Ckt2) Time Until Next Purge Run (Ckt1 and Ckt2) Pumpout Chiller On—7 Days (Ckt1 and Ckt2) Data Graph Data Points This subsection contains: • Data points used in the default data graphs, organized by graph • Data points available to include in custom data graphs, organized by component Data Points Used in Default Data Graphs Table 65. Chiller Overview 1 Graph data point Axis Active Chilled Water Setpoint Left Y-axis Active Hot Water Setpoint Left Y-axis Evaporator Leaving Evaporator Temperature Left Y-axis Evaporator Entering Water Temperature Left Y-axis CTV-SVU01G-EN 83 Appendix B: Data for CenTraVac Duplex Chillers Table 65. Chiller Overview 1 (continued) Graph data point Axis Condenser Leaving Water Temperature Left Y-axis Condenser Entering Water Temperature Left Y-axis Calculated Chiller Capacity Right Y-axis Table 66. Chiller Overview 2 Graph data point Axis Average Motor Current % RLA Ckt1 1st y-axis Left Y-axis Average Motor Current % RLA Ckt2 1st y-axis Left Y-axis Motor Frequency Ckt1 1st y-axis Left Y-axis Motor Frequency Ckt2 1st y-axis Left Y-axis Oil Differential Pressure Ckt1 1st y-axis Left Y-axis Oil Differential Pressure Ckt2 1st y-axis Left Y-axis Table 67. Evaporator Graph data point Axis Active Chilled Water Setpoint Left Y-axis Evaporator Leaving Water Temperature Left Y-axis Evaporator Entering Water Temperature Left Y-axis Evaporator Saturated Refrigerant Temperature (Ckt1 and Ckt2) Left Y-axis Approximate Evaporator Water Flow Right Y-axis Table 68. Condenser Graph data point Axis Active Hot Water Setpoint Left Y-axis Condenser Leaving Water Temperature Left Y-axis Condenser Entering Water Temperature Left Y-axis Condenser Saturated Refrigerant Temperature (Ckt1 and Ckt2) Left Y-axis Approximate Condenser Water Flow Right Y-axis Table 69. Compressor Graph data point Axis Average Motor Current % RLA (Ckt1 and Ckt2) Left Y-axis Active Current Limit Setpoint Left Y-axis AFD Frequency (Ckt1 and Ckt2) Left Y-axis IGV 1 Percent Open (Ckt1 and Ckt2) Left Y-axis Chiller Control Signal (Ckt1 and Ckt2) Left Y-axis Compressor Refrigerant Discharge Temperature (Ckt1 and Ckt2) Right Y-axis 84 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers Table 70. Oil System Graph data point Axis Oil Differential Pressure (Ckt1 and Ckt2) Left Y-axis Oil Tank Pressure (Ckt1 and Ckt2) Left Y-axis Oil Pump Discharge Pressure (Ckt1 and Ckt2) Left Y-axis Oil Tank Temperature (Ckt1 and Ckt2) Right Y-axis Outboard Bearing Temperature (Ckt1 and Ckt2) Right Y-axis Inboard Bearing Temperature (Ckt1 and Ckt2) Right Y-axis Table 71. Oil System Graph data point Axis Oil Differential Pressure (Ckt1 and Ckt2) Left Y-axis Oil Tank Pressure (Ckt1 and Ckt2) Left Y-axis Oil Pump Discharge Pressure (Ckt1 and Ckt2) Left Y-axis Oil Tank Temperature (Ckt1 and Ckt2) Right Y-axis Outboard Bearing Temperature (Ckt1 and Ckt2) Right Y-axis Inboard Bearing Temperature (Ckt1 and Ckt2) Right Y-axis Table 72. Motor Graph data point Axis Average Motor Current %RLA CktX Left Y-axis Starter Motor Current L1 % RLA CktX Left Y-axis Starter Motor Current L2 % RLA (CktX) Left Y-axis Starter Motor Current L3 % RLA (CktX) Left Y-axis Starter Input Voltage Phase AB (CktX) Right Y-axis Starter Input Voltage Phase BC (CktX) Right Y-axis Starter Input Voltage Phase CA (CktX) Right Y-axis Table 73. Motor Temperature Graph data point Axis Motor Winding Temperature 1 (Ckt1 and Ckt2) Left Y-axis Motor Winding Temperature 2 (Ckt1 and Ckt2) Left Y-axis Motor Winding Temperature 3 (Ckt1 and Ckt2) Left Y-axis AFD Transistor Temperature (Ckt1 and Ckt2) Left Y-axis Table 74. Purge Graph data point Axis Daily Pumpout—24 Hours (Ckt1 and Ckt2) Left Y-axis Pumpout Chiller On—7 Days (Ckt1 and Ckt2) Left Y-axis Pumpout Chiller Off—7 Days (Ckt1 and Ckt2) Left Y-axis CTV-SVU01G-EN 85 Appendix B: Data for CenTraVac Duplex Chillers Table 74. Purge (continued) Graph data point Axis Average Daily Pumpout—7 Days (Ckt1 and Ckt2) Right Y-axis Purge Refrigerant Compressor Suction Temperature (Ckt1 and Ckt2) Right Y-axis Purge Liquid Temperature (Ckt1 and Ckt2) Right Y-axis Table 75. Approach Temperature Graph data point Axis Evaporator Approach Temperature (Ckt1 and Ckt2) Left Y-axis Condenser Approach Temperature (Ckt1 and Ckt2) Left Y-axis Approximate Evaporator Water Flow (Ckt1 and Ckt2) Right Y-axis Approximate Condenser Water Flow (Ckt1 and Ckt2) Right Y-axis Average Line Current %RLA (Ckt1 and Ckt2) Right Y-axis Data Points in Custom Data Graphs Table 76. Evaporator Active Chilled Water Setpoint Evaporator Leaving Water Temperature Evaporator Entering Water Temperature Approx Evap Water Flow Evap Differential Wtr Press Calculated Chiller Capacity Active Ice Termination Setpoint Evaporator Saturated Rfgt Temp Ckt1 Evaporator Refrigerant Pressure Ckt1 Evaporator Approach Temperature Ckt1 Evaporator Saturated Rfgt Temp Ckt2 Evaporator Refrigerant Pressure Ckt2 Evaporator Approach Temperature Ckt2 Evaporator Entering Water Pressure Evaporator Leaving Water Pressure Table 77. Condenser Active Hot Water Setpoint Condenser Leaving Water Temperature Condenser Entering Water Temperature Outdoor Air Temperature Refrigerant Monitor Approx Cond Water Flow 86 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers Table 77. Condenser (continued) Cond Differential Wtr Press Head Pressure Control Status Condenser Saturated Rfgt Temp Ckt1 Condenser Refrigerant Pressure Ckt1 Condenser Approach Temperature Ckt1 Differential Refrigerant Pressure Ckt1 Condenser Saturated Rfgt Temp Ckt2 Condenser Refrigerant Pressure Ckt2 Condenser Approach Temperature Ckt2 Differential Refrigerant Pressure Ckt2 Condenser Entering Water Pressure Condenser Leaving Water Pressure Table 78. Compressor Chiller Control Signal Oil Tank Pressure Ckt1 Oil Pump Discharge Pressure Ckt1 Oil Differential Pressure Ckt1 Oil Tank Temperature Ckt1 Inboard Bearing Temperature Ckt1 Outboard Bearing Temperature Ckt1 Outboard Bearing Pad Temperature #1 Ckt1 *Added for CDHH Outboard Bearing Pad Temperature #2 Ckt1 *Added for CDHH Outboard Bearing Pad Temperature #3 Ckt1 *Added for CDHH IGV 1 Percent Open Ckt1 IGV 1 Position Ckt1 IGV 2 Percent Open Ckt1 IGV 2 Position Ckt1 Compressor Rfgt Discharge Temp Ckt1 Oil Tank Pressure Ckt2 Oil Pump Discharge Pressure Ckt2 Oil Differential Pressure Ckt2 Oil Tank Temperature Ckt2 Inboard Bearing Temperature Ckt2 Outboard Bearing Temperature Ckt2 Outboard Bearing Pad Temperature #1 Ckt2 *Added for CDHH Outboard Bearing Pad Temperature #2 Ckt2 *Added for CDHH CTV-SVU01G-EN 87 Appendix B: Data for CenTraVac Duplex Chillers Table 78. Compressor (continued) Outboard Bearing Pad Temperature #3 Ckt2 *Added for CDHH IGV 1 Percent Open Ckt2 IGV 1 Position Ckt2 IGV 2 Percent Open Ckt2 IGV 2 Position Ckt2 Compressor Rfgt Discharge Temp Ckt2 Table 79. Motor Active Current Limit Setpoint Motor Frequency Ckt1 Frequency Command Ckt1 Average Motor Current % RLA Ckt1 Starter Motor Current L1 % RLA Ckt1 Starter Motor Current L2 % RLA Ckt1 Starter Motor Current L3 % RLA Ckt1 Starter Motor Current L1 Ckt1 Starter Motor Current L2 Ckt1 Starter Motor Current L3 Ckt1 Starter Average Phase Voltage Ckt1 Starter Input Voltage AB Ckt1 Starter Input Voltage BC Ckt1 Starter Input Voltage CA Ckt1 Motor Winding Temperature 1 Ckt1 Motor Winding Temperature 2 Ckt1 Motor Winding Temperature 3 Ckt1 Motor Temperature Ckt1 Starter Input Power Consumption Ckt1 Starter Power Demand Ckt1 Starter Motor Power Factor Ckt1 AFD Average Input Current Ckt1 AFD Input Current L1 Ckt1 AFD Input Current L2 Ckt1 AFD Input Current L3 Ckt1 AFD Input Frequency Ckt1 AFD Output Voltage Ckt1 AFD DC Bus Voltage Ckt1 AFD DC Bus Current Ckt1 (Note: Added per CR 51244, 5/2/14) 88 CTV-SVU01G-EN Appendix B: Data for CenTraVac Duplex Chillers Table 79. Motor (continued) AFD Output Power Ckt1 AFD Ground Current Ckt1 AFD Inverter Base Temp Ckt1 AFD Rectifier Base Temp Ckt1 AFD Transistor Temperature Ckt1 Motor Frequency Ckt2 Frequency Command Ckt2 Average Motor Current % RLA Ckt2 Starter Motor Current L1 % RLA Ckt2 Starter Motor Current L2 % RLA Ckt2 Starter Motor Current L3 % RLA Ckt2 Starter Motor Current L1 Ckt2 Starter Motor Current L2 Ckt2 Starter Motor Current L3 Ckt2 Starter Average Phase Voltage Ckt2 Starter Input Voltage AB Ckt2 Starter Input Voltage BC Ckt2 Starter Input Voltage CA Ckt2 Motor Winding Temperature 1 Ckt2 Motor Winding Temperature 2 Ckt2 Motor Winding Temperature 3 Ckt2 Motor Temperature Ckt2 Starter Input Power Consumption Ckt2 Starter Power Demand Ckt2 Starter Motor Power Factor Ckt2 AFD Average Input Current Ckt2 AFD Input Current L1 Ckt2 AFD Input Current L2 Ckt2 AFD Input Current L3 Ckt2 AFD Input Frequency Ckt2 AFD Output Voltage Ckt2 AFD DC Bus Voltage Ckt2 AFD DC Bus Current Ckt1 (Note: Added per CR 51244, 5/2/14) AFD Output Power Ckt2 AFD Ground Current Ckt2 AFD Inverter Base Temp Ckt2 CTV-SVU01G-EN 89 Appendix B: Data for CenTraVac Duplex Chillers Table 79. Motor (continued) AFD Rectifier Base Temp Ckt2 AFD Transistor Temperature Ckt2 Table 80. Purge Daily Pumpout-24 hours Ckt1 Pumpout Chiller On 7 Days Ckt1 Pumpout Chiller Off 7 Days Ckt1 Average Daily Pumpout 7 days Ckt1 Purge Rfgt Compressor Suction Temp Ckt1 Purge Liquid Temperature Ckt1 Purge Carbon Tank Temp Ckt1 Daily Pumpout-24 hours Ckt2 Pumpout Chiller On 7 Days Ckt2 Pumpout Chiller Off 7 Days Ckt2 Average Daily Pumpout 7 days Ckt2 Purge Rfgt Compressor Suction Temp Ckt2 Purge Liquid Temperature Ckt2 Purge Carbon Tank Temp Ckt2 90 CTV-SVU01G-EN Notes CTV-SVU01G-EN 91 Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. CTV-SVU01G-EN 21 Mar 2020 Supersedes CTV-SVU01F-EN (Apr 2017) ©2020 Trane
advertisement