Trane Tracer AdaptiView User Manual

Trane Tracer AdaptiView User Manual

Add to My manuals
92 Pages

advertisement

Trane Tracer AdaptiView User Manual | Manualzz
User Guide
Tracer® AdaptiView™ Display for
CenTraVac™ Water-cooled Chillers
X39641071060
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
March 2020
CTV-SVU01G-EN
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required.Your personal safety and the proper
operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTIONs
Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
accidents.
NOTICE
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be
performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE
and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field
wiring installation and grounding as described in NEC and your local/state electrical codes.
Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well
as the instructions below:
©2020Trane
•
Before installing/servicing this unit, technicians MUST put on all PPE required for the work
being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard
hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to
appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
•
When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS
and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals)
guidelines for information on allowable personal exposure levels, proper respiratory
protection and handling instructions.
•
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE
in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash
protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC
FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
CTV-SVU01G-EN
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
•
All Trane personnel must follow the company’s Environmental, Health and Safety
(EHS) policies when performing work such as hot work, electrical, fall protection,
lockout/tagout, refrigerant handling, etc. Where local regulations are more
stringent than these policies, those regulations supersede these policies.
•
Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Factory Training
Factory training is available through Trane University™ to help you learn more about the
operation and maintenance of your equipment. To learn about available training opportunities
contact Trane University™.
Online: www.trane.com/traneuniversity
Phone: 855-803-3563
Email: [email protected]
Revision History
CTV-SVU01G-EN
•
Added LLID Binding section.
•
Updated “Evaporator settings and status points (Simplex)”, “Condenser settings and status
points (Simplex)”, “Motor settings and status points (Simplex)”, “Condenser data” and
“Evaporator data” tables in Appendix A — Data for CenTraVac Simplex Chillers.
3
Table of Contents
Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Equipment Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Touchscreen Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chiller Status Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Main Display Area/Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Main Display Area/Screen Saver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Component Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Main Menu Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Stopping/Restarting Chiller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Stopping the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Restarting the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
The Alarms Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Active and Historic Alarm Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sorting Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
21
21
21
Resetting Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Additional Alarm Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
The Reports Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Viewing the Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Viewing the ASHRAE Chiller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Creating and Viewing a Custom Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Editing a Custom Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
About this Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Viewing Chiller Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simplex Chillers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duplex Chillers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Purge Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
26
28
31
Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
The Data Graphs Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Viewing Data Graphs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Changing the Scales on Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Creating Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Creating a Custom Data Graph From a Default Data Graph. . . . . . . . . . . . . . . . . . 35
4
CTV-SVU01G-EN
Table of Contents
Creating a Custom Data Graph With No Previously Defined Data Graph
Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Editing Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Deleting a Custom Data Graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Equipment Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
The Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Viewing and Changing Equipment Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chiller Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Service Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Setpoint Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Setpoint Source Arbitration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Changing the Setpoint Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Setpoint Source Button in the Chiller Status Area. . . . . . . . . . . . . . . . .
From the Setpoint Source Button on the Chiller Settings Screen. . . . . . . . . . . . .
From an Arbitrated Setpoint Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
44
44
45
Feature Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chilled Water Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Purge Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Manual Control Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Changing a Manual Control Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Viewing and Changing Display Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Viewing and Changing the Language Preference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Viewing and Changing Date and Time Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Clean Touchscreen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Security Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Disabling Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Enabling Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Logging Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
LLID Binding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Appendix A: Data for CenTraVac Simplex Chillers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Component Screen Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
CTV-SVU01G-EN
5
Table of Contents
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASHRAE Chiller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Items Available to Include in Custom Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65
65
67
69
Data Graph Data Points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Data Points Used in Default Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Data Points in Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Appendix B: Data for CenTraVac Duplex Chillers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Component Screen Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASHRAE Chiller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Items Available to Include in Custom Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Graph Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
78
79
80
82
83
Data Points Used in Default Data Graphs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Data Points in Custom Data Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6
CTV-SVU01G-EN
Product Overview
The Tracer® AdaptiView™ display provides a means for viewing data and for making operational
changes on the following types of chillers:
•
Simplex (single compressor) CenTraVac™ chiller models
•
Duplex™ (dual compressor) CenTraVac™ chiller models
The purpose of this guide is to assist you in using the Tracer® AdaptiView™ display. This guide
describes how to access the screens and the types of information that appear on the screens.
Equipment Description
The basic equipment features of the Tracer® AdaptiView™ display are described here.
Hardware
The Tracer® AdaptiView™ display is mounted on or near the chiller control panel. It can be
attached to the chiller by an arm that can extend 11 inches. Five pivot points enable full
articulation as described in the following specifications and in the figure:
Figure 1. The Tracer AdaptiView mounting arm
•
Two horizontal pivots points 90º right or left (180º total)
•
Two vertical pivots points: 90º degrees up or down (180º total)
•
Rotation: 135º clockwise and 135º counterclockwise (270º total)
Screen Characteristics
The 12.1-inch color touch-screen display shows data in either inches and pounds (I-P) or standard
international (SI) units, and in one of twenty-seven available languages. Animated color graphics
indicate the status of the chiller and its components.
CTV-SVU01G-EN
7
Product Overview
DC Power
The Tracer® AdaptiView™ display receives 24 Vdc power through its power cable. The Tracer®
UC800 controller must be powered on.
Communication
A separate ethernet cable provides communication between the Tracer® AdaptiView™ display
and the Tracer® UC800 controller. Alarms are communicated immediately upon detection.
Touchscreen Guidelines
The touch screen registers the downward pressure of a touch. However, touching with increased
pressure has no effect.
Use your fingers to operate the touch screen. Do NOT use a pen or pencil point, or any other
sharp or pointed object that might scratch the screen surface.
If you apply and hold pressure at more than one point, the touch screen registers only the first
touch. For example, if you press a finger on an area of the screen that is not touch sensitive,
pressing a sensitive area with another finger will not register.
Holding on to the screen with your hand can cause unintended navigation, such as from thumb
or palm pressure.
Related Information
Additional information on CenTraVac™ chillers with Tracer® AdaptiView™ control can be found
in these documents:
•
CVHE-SVX02*-EN (Installation, Operation, and Maintenance: CVHE, CVHF, and CVHG WaterCooled CenTraVac Chillers with Tracer AdaptiView Control )
•
CDHF-SVX01*-EN (Installation, Operation, and Maintenance: CDHF and CDHG Water-Cooled
CenTraVac Chillers with Tracer AdaptiView Control )
•
CVHH-SVX001*-EN (Installation, Operation, and Maintenance: CVHH Water-Cooled
CenTraVac Chillers with Tracer AdaptiView Control )
•
CDHH-SVX001*-EN (Installation, Operation, and Maintenance: CDHH Water-Cooled
CenTraVac Chillers with Tracer AdaptiView Control)
•
PRGF-SVX001*-EN (Installation, Operation, and Maintenance: EarthWise Purge System with
Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-123 Refrigerant)
•
PRGG-SVX001*-EN (Installation, Operation, and Maintenance: Purge System with Tracer
AdaptiView Control for Water-cooled CenTraVac Chillers with R-514A Refrigerant)
•
CTV-SVD03*-EN (Diagnostics Manual: Diagnostic Descriptions, Troubleshooting Tables, and
Control Component Overview for Water-cooled CenTraVac Chillers with Tracer AdaptiView
Control)
•
CTV-SVP02*-EN (Programming Guide: Tracer TU Service Tool for Water-cooled CenTraVac
Chillers with Tracer AdaptiView Control)
•
TTU-SVN01*-EN (Getting Started Guide: Tracer TU Service Tool)
Screen Overview
The touch-sensitive areas of the Tracer® AdaptiView™ display screen are described in detail in
this section.
8
CTV-SVU01G-EN
Product Overview
Figure 2. Tracer AdaptiView display (Home screen for Simplex chillers is shown)
1
2
3
1. “Chiller Status Area,” p. 9
2. “Main Display Area/Home Screen,” p. 10 This area is different between the Simplex chiller
models and the Duplex™ chiller models. Table 2, p. 11 describes the differences.
3. “Main Menu Area,” p. 17
Chiller Status Area
The chiller status area (shown as Location 1 in “Screen Overview,” p. 8) remains visible from
every screen on the Tracer® AdaptiView™ display. Basic information about chiller status and
control appears on the face of the buttons and touch targets. When touched, the buttons and
touch targets open other screens that provide more information and control access. The
following table provides the details.
Table 1. Chiller status area
Button/Touch target
Chiller status button
Description
The top-level operating mode of the chiller appears on the chiller status button. Touch this button to
view the Chiller Operating Mode screen.
Note: For more information, refer to “Reports,” p. 65 .
Alarm indicator button
If an active alarm exists, the alarm indicator button appears with the alarm severity indicated on it. If
there is more than one alarm, the most severe appears. You can touch this button as an alternate way
to view the Alarms screen.
Note: For more information, refer to “Alarms,” p. 20.
Manual override button
If a manual override exists but no active alarm exists, a manual override button appears in the same
location as the alarm indicator button. If neither an alarm nor a manual override exist, no button
appears.
If a manual override exists, you can touch this button as an alternate way to view the Manual Control
Settings screen.
Note: For more information, refer to “Manual Control Settings,” p. 47.
CTV-SVU01G-EN
9
Product Overview
Table 1. Chiller status area (continued)
Button/Touch target
Description
The water temperature touch target shows one of the following, depending on whether the chiller is in
heating or cooling mode (also referred to as the Active Control Type):
Water temperature touch target
•
If the Active Control Type is chilled water, the Evaporator Leaving Water Temperature appears and
the touch target links to the evaporator component screen.
•
If the Active Control Type is hot water, the Condenser Leaving Water Temperature appears and the
touch target links to the condenser component screen.
•
If the Ice Building mode is Active, the Evaporator Entering Water Temperature appears and the
touch target links to the evaporator component screen.
Note: For more information on the evaporator and condenser component screens, refer to “Component
Screens,” p. 14.
Setpoint source touch target
The current setpoint source is highlighted in green on the setpoint source touch target. Touch this
target to view the Setpoint Source screen, where you can change the setpoint source.
Note: For more information, refer to “Changing the Setpoint Source,” p. 44 .
Auto/Stop buttons
Auto and Stop are toggle buttons: One appears raised when the other is appears depressed.
•
Touch Auto to activate the chiller startup process.
•
Touch Stop to active the chiller shutdown process.
Note: For more information, refer to “Stopping/Restarting Chiller Operation,” p. 18.
Main Display Area/Home Screen
All screens appear within the main display area (shown as Location 2 shown in the figure in
“Screen Overview,” p. 8).
Home screen: Chiller status information
The home screen (shown in “Screen Overview,” p. 8) provides the most frequently needed
chiller status information on “touch targets” (the entire white rectangular areas) for each chiller
component. Touching any touch target displays a screen containing more chiller status
information related to each component (refer to “Component Screens,” p. 14).
Each touch target that appears on the home screen is described in the following table, including
those for Simplex chillers, and those for Duplex™ chillers.
In the lower right corner of the home screen, you can view the date and time as well as additional
chiller information. For details, see the last three rows of the following table.
10
CTV-SVU01G-EN
Product Overview
Table 2. Home screen touch targets and buttons
Touch target
Description
Compressor for Simplex chillers
This compressor touch target chiller provides information on:
•
Compressor Running Status
•
Differential Oil Pressure
Touch anywhere on the touch target to view the Compressor component
screen.
Compressor for Duplex Chillers
This compressor touch target provides information on:
•
Compressor Running Status Ckt1
•
Compressor Running Status Ckt2
Touch anywhere on the Ckt1 side of the touch target to view the
Circuit 1 Compressor component screen.
Touch anywhere on the Ckt2 side of the tough target to view the Circuit 2
Compressor component screen.
Condenser for all chiller models
This condenser touch target provides information on:
•
Condenser Leaving Water Temperature
•
Condenser Entering Water Temperature
•
Active Hot Water Setpoint (if Hot Water Control is available)
•
Condenser Water Flow Status (animation in graphic indicates if
condenser is running)
Touch anywhere on the touch target to view the Condenser component
screen.
Evaporator for all chiller models
The evaporator touch target provides information on:
•
Evaporator Leaving Water Temperature
•
Evaporator Entering Water Temperature
•
Active Chilled Water Setpoint (if Chilled Water Control is available) or
Active Ice Termination Setpoint in Ice Building mode)
•
Evaporator Water Flow Status (animation in graphic indicates if
evaporator is running)
Touch anywhere on the touch target to view the Evaporator component
screen.
Motor for Simplex chillers
The motor touch target provides information on:
•
Average line current
•
Frequency (if adjustable-frequency drive is configured)
Touch anywhere on the touch target to view the Motor component screen.
CTV-SVU01G-EN
11
Product Overview
Table 2. Home screen touch targets and buttons (continued)
Touch target
Description
Motor for Duplex chillers
The motor touch target provides information on:
•
Average line current Ckt1
•
Average line current Ckt2
Touch anywhere on the Ckt1 side of the touch target to view the Circuit 1
Motor component screen.
Touch anywhere on the Ckt2 side of the tough target to view the Circuit 2
Motor component screen.
Purge for Simplex chillers
The purge touch target provides information on:
•
Purge top level mode
Touch anywhere on the touch target to view the Purge component screen.
Note: The Purge button is not displayed if Purge is not installed.
Purge for Duplex chillers
The purge touch target provides information on:
•
Purge top level mode Ckt1
•
Purge top level mode Ckt2
Touch anywhere on the Ckt1 side of the touch target to view the Circuit 1
Purge component screen.
Touch anywhere on the Ckt2 side of the tough target to view the Circuit 2
Purge component screen.
Note: The Purge button is not displayed if Purge is not installed.
Information button and chiller and display names
Touch the “i” or the chiller or display name to view the About this Chiller
screen.
Note: For more information, see “About this Chiller,” p. 26 .
Custom Report
Touch the Custom Report button to view the Custom Report screen.
Note: For more information, see “Creating and Viewing a Custom
Report,” p. 24.
Home screen: Animated Graphic
A graphic of a chiller appears on the home page. The graphic uses animation to indicate the
operational status of the chiller. If the chiller is running, animation appears within the cutaway
areas of the compressor, the evaporator, and the condenser, as shown in the figure in “Screen
Overview,” p. 8. If the chiller is not running, the components are enclosed and are not animated.
The chiller graphic that appears on the screen also indicates the type of chiller that the Tracer®
AdaptiView™ display is monitoring. One of the following graphics will appear in the display for
Simplex chillers:
12
•
2-stage compressor, cooling only (as shown in the figure in “Screen Overview,” p. 8)
•
2-stage compressor with auxiliary condenser
•
2-stage compressor with heat recovery
•
3-stage compressor, cooling only
•
3-stage compressor with auxiliary condenser
•
3-stage compressor with heat recovery
CTV-SVU01G-EN
Product Overview
One of the following graphics will appear on the display for Duplex™ chillers:
CTV-SVU01G-EN
•
2–stage compressor
•
3–stage compressor
13
Product Overview
Main Display Area/Screen Saver
After 30 minutes of inactivity, the screen dims and a screen saver appears in the main display
area as shown in the following figure. The screen saver also appears if you touch the animated
graphic on the home screen. Alternately, if you touch the screen saver, the home screen appears.
Figure 3. Screen saver
Component Screens
Each chiller component has a touch target, accessible from the home screen, that is illustrated in
“Screen Overview,” p. 8 (main display area/home screen) and described in “Main Display Area/
Home Screen,” p. 10.
Simplex Chillers
If you touch anywhere on a component touch target, a screen appears containing data that is
related to that component (see the example in the following figure). You can use the shortcut
buttons at the top of each of the component screens to view the other components screens.
“Appendix A: Data for CenTraVac Simplex Chillers,” p. 63 lists the settings and status points that
are accessible from each of the component screens. The chiller configuration determines which
of the settings and status points appear.
14
CTV-SVU01G-EN
Product Overview
Figure 4. Component screen example for Simplex chillers
1
2
1. Data Graph shortcut button
2. Component screen shortcut buttons
Duplex Chillers
Each component has a separate screen for circuit 1 and circuit 2.
•
If you touch anywhere on an evaporator or condenser component touch target, a screen
appears containing data related to circuit 1 of that component (refer to the following figure).
•
If you touch in the circuit 1 data area of a compressor, motor, or purge component touch
target, a screen appears containing data related to circuit 1 of that component. If you touch in
the circuit 2 data area of a compressor, motor, or purge component touch target, a screen
appears containing data related to circuit 2 of that component.
Circuit 1 and Circuit 2 buttons at the bottom of each component screen (see Location 4 in the
following figure) allow you to toggle between circuit 1 and circuit 2 component screens.
You can use the shortcut buttons at the top of each of the component screens (see Location 2 in
the preceding figure) to view the other components screens. If you are viewing a circuit 1
component screen and touch a shortcut button, the circuit 1 screen for the component
represented by that button appears; and likewise for circuit 2.
“Appendix B: Data for CenTraVac Duplex Chillers ,” p. 77 lists the settings and status points that
are accessible from each of the component screens. The chiller configuration determines which
of the settings and status points appear.
CTV-SVU01G-EN
15
Product Overview
Figure 5. Component screen example for Duplex chillers
22
1
2
3
4
1.
Data Graph shortcut button
2. Component screen shortcut buttons
3. Animated graphic
4. Circuit 1 and Circuit 2 components screen toggle buttons
Component Screen Settings
Some settings appear on the component screens as buttons. These buttons take you to another
screen, where you can change the setting. (See, for example, the buttons on the evaporator
component screen in the preceding two figures, which show the Active Chilled Water Setpoint
and the Evaporator Water Pump Override).
N o t e : For more information about changing settings, see “Equipment Settings,” p. 39.
Data Graph Shortcut Button
To view a data graph that is related to the component screen you are viewing, touch the Data
Graph button at the top left of the component screen (Location 1 in the preceding two figures).
Component Screen Graphics
On the left side of each component screen is a graphic of the component. If the chiller is running,
each graphic, except for the purge graphic, is animated.
16
CTV-SVU01G-EN
Product Overview
Main Menu Area
The main menu area (shown in “Screen Overview,” p. 8) always remains visible at the bottom of
the display. When touched, each of the buttons displays the main menu screen for the topic
listed on the button. The following table provides a description of each button.
Table 3. Main menu area
Button
Description
Touch the Alarms button to view the Alarms screen.
If there is an active alarm, the button flashes a color. The flashing color is determined by the highest
severity of active alarms:
•
If an Immediate Shutdown alarm exists, the flashing color is red.
•
If a Normal Shutdown alarm exists, the flashing color is yellow.
•
If a Warning alarm exists, the flashing color is blue.
Note: For more information, see “Alarms,” p. 20.
Touch the Reports button to view the Reports screen.
Note: For more information, see . “Reports,” p. 23.
Touch the Data Graphs button to view the Data Graphs screen.
Note: For more information, see “Data Graphs,” p. 32.
Touch the Settings button to view the Settings screen, which is separated into the following three
categories:
•
“Equipment Settings,” p. 39
•
“Display Settings,” p. 51
•
“Security Settings,” p. 58
Note: Refer to the page numbers for detailed information about each category.
Touch the Language icon to view the Language screen. (This button is a shortcut. You can also view the
Language screen by using the Settings button.)
Note: For more information, see “Viewing and Changing the Language Preference,” p. 54.
Touching the brightness button will cycle the display brightness from 30% to 60% to 90% brightness.
CTV-SVU01G-EN
17
Stopping/Restarting Chiller Operation
You can start or stop the chiller from the Tracer® AdaptiView™ display by using the Auto and
Stop buttons. The buttons are located in upper right.
Stopping the Chiller
You can stop the chiller in two ways:
•
Normally, which involves stopping the various components sequentially in order to protect
them from damage
•
Immediately, which shuts down all the components at once, and should be used only in an
emergency
To stop the chiller in either of these ways:
1. Touch the Stop button to initiate the chiller shutdown process. A confirmation screen appears
as shown in the following figure.
Figure 6. Stop the Chiller confirmation screen
2. Touch the Y e s button. The Shutting Down Chiller screen appears as shown in the following
figure.
18
•
To stop the chiller normally, no further action is required. You can observe the submodes
change and the timers count down.
•
To stop the chiller immediately, touch the I m m e d i a t e S h u t d o w n button.
•
To cancel shutdown, touch the C a n c e l S h u t d o w n button.
CTV-SVU01G-EN
Stopping/Restarting Chiller Operation
Figure 7. Shutting Down Chiller screen
N o t e : If the chiller is a Duplex™, the screen shows top-level modes and submodes for both
the chiller and the two circuits.
Restarting the Chiller
Touch the Auto button to initiate the chiller restart process. You can observe the mode change to
Auto. The chiller will wait until cooling is needed before starting the compressor.
When the chiller is running normally, it automatically starts and stops as needed to reach its
setpoints.
CTV-SVU01G-EN
19
Alarms
You can use the Tracer® AdaptiView™ display to view alarms and to reset them. Alarms are
communicated to the display immediately upon detection.
The Alarms Screen
Touch the A l a r m s button in the main menu area at the bottom of the screen to view the Alarms
screen. A table of active alarms appears that is organized chronologically with the most recent at
the top of the list, as shown in the following figure. This example shows the default view, which
appears each time you return to the screen.
Figure 8. Alarms screen (default view)
1
2
3
4
5
1. Reset Alarms button
2. Number of alarms
3. Sortable columns—The example is sorted by date/time.
4. Page controls
N o t e : A page number appears in the lower right corner of the screen. If a screen contains
more than one page, up/down arrows also appear for viewing the other pages.
5. Alarms categories—The example shows active alarms.
20
CTV-SVU01G-EN
Alarms
Alarm Icons
Alarm icons, which appear in the left-most column of the alarms screen and on the alarms
indicator button if there is an existing alarm, are distinguished by their shape and color. Their
meaning is explained in the following table.
Table 4. Alarm icons
Active alarm icons
Historic alarm icons
Level of severity
Immediate shutdown
Red octagon
Gray octagon
Normal shutdown
Yellow triangle
Gray triangle
Blue circle
Gray circle
Warning
Active and Historic Alarm Categories
You can view alarms by three different categories:
•
A c t i v e a l a r m s : These are alarms that require attention. All alarms that are currently active
appear when you view this category.
•
H i s t o r i c a l a r m s : After an alarm condition has been resolved, the alarm is reclassified as
historic. The 20 most recent historic alarms appear when you view this category.
•
A l l a l a r m s : All active alarms and the 20 most recent historic alarms appear when you view
this category. The alarms are listed in chronological order.
The Alarms screen defaults to active alarms, as in “The Alarms Screen,” p. 20. Note that the
A c t i v e A l a r m s button in Location 5 appears shaded in the figure, which indicates that you are
viewing active alarms. To view a different category, touch H i s t o r i c A l a r m s or A l l A l a r m s . The
button you select becomes shaded and the list appears.
Sorting Alarms
To sort alarms by a category other than date and time, touch one of the other column headings in
the table. The column heading responds by changing to blue, and the alarms table re-sorts
according to the blue column heading. If you touch the blue column heading again, the column
changes the order from ascending to descending.
You can sort the alarms table by:
CTV-SVU01G-EN
•
Date/Time (the default sort): Most recent alarms are at the top.
•
Severity: Active alarms are at the top (if you are viewing both active and historic alarms),
followed by the most severe, followed by the most recent.
•
Description: Alarms are sorted alphanumerically by name, followed by the most recent.
•
Status: Alarms are sorted according to active/historic status (if you are viewing both active
and historic alarms), followed by the most recent.
21
Alarms
Resetting Alarms
Some alarms require reset to move from the active to the historic state, even if the issue causing
the alarm has been resolved. These manual reset alarms are sometimes referred to as latching
alarms. Non-latching alarms change from the active to the historic state automatically, after the
problem has been resolved.
The Alarms screen does not directly state whether the alarms are latching or non-latching.
However, their behavior indicates their type:
•
Reset latching alarms by touching the R e s e t A l a r m s button at the top of the Alarms screen
(refer to “The Alarms Screen,” p. 20). Latching alarms respond by disappearing from the
active alarms list and becoming a part of the historic alarms list. However, if the condition
that caused the alarm persists, the alarm will re-appear in the active alarms list.
•
You do not have to reset non-latching alarms. Non-latching alarms automatically disappear
from the active alarms list and re-appear in the historic alarms list when the conditions that
caused them are resolved.
Additional Alarm Indicators
In addition to the Alarms screen, there are two buttons that indicate alarm conditions. These
buttons are viewable from any screen on the display. You can touch either one to access the
Alarms screen.
22
•
The A l a r m s button in the main menu area of the screen (refer to “Screen Overview,” p. 8)
flashes a color that represents the alarm level of the most severe active alarm. The three color
possibilities correspond to those of the active alarm icons shown in “Alarm Icons,” p. 21.
•
If an active alarm is present, the alarm indicator button (refer to “Chiller Status Area,” p. 9)
appears in the upper left of the screen, as shown in “The Alarms Screen,” p. 20. The icon on
this button indicates the level of the most severe active alarm.
CTV-SVU01G-EN
Reports
You can use the Tracer® AdaptiView™ display to view a variety of reports and to create and edit
a custom report. All reports contain live data that refreshes every 2–5 seconds.
The Reports Screen
Touch the R e p o r t s button in the main menu area (refer to “Screen Overview,” p. 8) to view the
Reports screen. The Reports screen contains the following buttons:
•
Log Sheet
•
ASHRAE Chiller Log
•
Custom Report
•
About This Chiller
•
Chiller Operating Modes
•
Purge Operating Modes
Each button links to the report named on the button.
Figure 9. Reports screen
Viewing the Log Sheet
On the Reports screen, touch L o g S h e e t to view the information that is itemized in “Log
Sheet,” p. 65 for Simplex chillers, and in “Log Sheet,” p. 79 for Duplex™ chillers. The items
included in the Log Sheet are those recommended by Trane. Refer to current Trane service
literature for more information.
CTV-SVU01G-EN
23
Reports
Viewing the ASHRAE Chiller Log
On the Reports screen, touch A S H R A E C h i l l e r L o g to view the information that is itemized in
“ASHRAE Chiller Log,” p. 67 for Simplex chillers, and in “ASHRAE Chiller Log,” p. 80 for
Duplex™ chillers.
Creating and Viewing a Custom Report
You can create a custom report in which you specify the type and order of data that it contains.
Items available to select for a custom report are grouped according to subsystem. (For Simplex
chillers, see “Items Available to Include in Custom Reports,” p. 69; for Duplex™ chillers, see
“Items Available to Include in Custom Reports,” p. 82.)
To create and view a custom report:
1. On the Reports screen, touch C u s t o m R e p o r t . The Custom Report screen appears.
2. On the Custom Report screen, touch E d i t . The Edit Custom Report screen appears in the
following figure.
Figure 10.
Edit Custom Report screen
3. Touch the up/down arrows at the top of the left box on this screen to scroll through the items
that are available to add to a custom report.
4. To set up a custom report by adding:
•
One item at a time, touch the item. It responds by changing to blue. Touch A d d to move
the selected item to the right box on the screen.
•
All of the items at once to the right box on the screen, touch A d d A l l .
N o t e : You can organize your selections in any order by using the down arrows that appears
in the right box, and by adding them one at a time in the order in which you want them
to appear in your report.
5. To save and view your custom report, touch S a v e . The Custom Reports screen appears,
containing the custom report you have just created as shown in the next figure.
24
CTV-SVU01G-EN
Reports
N o t e : A page number appears in the lower right corner of the screen. If a screen contains
more than one page, up/down arrows also appear for viewing the other pages, as in
the following figure.
Figure 11.
Custom Report screen
Editing a Custom Report
You can edit the custom report by adding, removing, or re-order data as follows:
1. On the Custom Report screen, touch E d i t . The E d i t C u s t o m R e p o r t screen appears.
2. Add, remove, or re-order as follows:
•
To add an item to the custom report, touch it. It responds by changing to blue. You an use
the arrows to scroll through the rest of the items that can be added to the custom report.
Then touch A d d to move the selected item to the box on the right side of the screen. To
add all of the remaining items in the left box to the custom report, touch A d d A l l .
•
To remove an item from the custom report, touch it. It responds by changing to blue. You
can use the arrows to scroll through the rest of the items that can be removed from the
custom report. Then touch R e m o v e to move the selected item to the box on the left side
of the screen.
•
To re-order items in the custom report, touch it. It responds by changing to blue. Use the
arrows to change the order of a highlighted item.
3. To save and view your edited custom report, touch S a v e . The Custom Reports screen
appears, containing the custom report you have just edited.
CTV-SVU01G-EN
25
Reports
About this Chiller
On the Reports screen, touch A b o u t T h i s C h i l l e r to view the following unit information:
•
Chiller Name
•
Chiller Model Number
•
Chiller Sales Order Number
•
Product Name
•
Controller Build Part Number
•
Chiller Serial Number
•
Display Firmware Build
•
Controller Hardware Serial Number
•
Controller Boot Part Number
•
Display Boot Code
Viewing Chiller Operating Modes
On the Reports screen, touch C h i l l e r O p e r a t i n g M o d e s to view the current operating status of
the chiller in terms of the top-level operating mode and submodes.
N o t e : You can also access the Chiller Operating Modes screen from the chiller status button in
the upper left corner of the screen.
Simplex Chillers
The following figure shows an example of a Chiller Operating Modes screen for a Simplex chiller.
Figure 12.
Chiller Operating Modes screen for Simplex chillers
Simplex chillers operate in one of the top-level operating modes shown in the following table.
The table gives a description of the top-level modes and lists the submodes that correspond to
each top-level mode.
26
CTV-SVU01G-EN
Reports
Submodes are dependent on the top-level mode. Their appearance on the Chiller Operating
Modes screen has the following characteristics:
•
The newest submode appears at the top of the submode list.
•
Submodes disappear when they no longer apply.
•
The screen displays up to six submodes.
•
If less than six submodes are active, the submode rows that do not apply are blank.
Table 5. Chiller top-level operating modes and corresponding submodes for Simplex chillers
Top-level mode
Description
Stopped
Chiller is inhibited from running and requires user action to go
to Auto.
Corresponding submodes
Local Stop
Immediate Stop
Diagnostic Shutdown—Manual Reset
Ice Building Is Complete
Run Inhibit
Unit is inhibited from running by building automation system
(BAS), external control source (Ext), or Auto Reset diagnostic
Tracer Inhibit
External Source Inhibit
Diagnostic Shutdown—Auto Reset
Waiting for Evaporator Water Flow
Waiting for a Need to Cool
Auto
Unit is determining if there is a need to run.
Waiting for a Need to Heat
Power Up Delay Inhibit (MIN:SEC)(a)
Waiting For Condenser Water Flow
Establishing Oil Pressure
Pre-Lubrication Time (MIN:SEC)(a)
Motor Temperature Inhibit: Motor Temperature/
Inhibit Temperature
Waiting to Start
Unit is waiting for tasks required prior to compressor start to be
completed.
Restart Time Inhibit (MIN:SEC)(a)
AFD Restart Inhibit
High Vacuum Inhibit: Oil Sump Press/Inhibit
Press
Low Oil Temperature Inhibit: Oil Temperature/
Inhibit Temperature
Waiting for Starter To Start (MIN:SEC)(a)
Starting Compressor
Unit is starting compressor.
No submode is shown
No submode is shown
Hot Water Control
Surge
Base Loaded
Running
Compressor is running with no limits in effect.
Hot Gas Bypass
Ice Building
Ice To Normal Transition
Current Control Soft Loading
CTV-SVU01G-EN
27
Reports
Table 5. Chiller top-level operating modes and corresponding submodes for Simplex chillers (continued)
Top-level mode
Description
Corresponding submodes
Current Limit
Phase Unbalance Limit
Condenser Pressure Limit
Running—Limit
Compressor is running with limits in effect.
Evaporator Temperature Limit
Evaporator Rfgt Temperature Higher Than
Selection
Minimum Capacity Limit
Maximum Capacity Limit
Opening Free Cooling Valves
Free Cooling
Unit is in Free Cooling mode and will not run the compressor.
Closing Free Cooling Limit
Preparing to Shutdown
Unit is closing inlet guide vanes prior to compressor shutdown.
Closing IGV (IGV Position %)(b)
Post-Lubrication Time (MIN:SEC)(a)
Evaporator Pump Off Delay (MIN:SEC(a)
Shutting Down
Compressor has been stopped and unit is performing shutdown
tasks.
Condenser Pump Off Delay (MIN:SEC)(a)
Satisfied Need to Minimum Capacity Timer (will
appear for only 10 seconds)
(a)
(b)
“MIN:SEC” refers to a count-down timer that appears on the screen to indicate how long the submode will remain active.
“IGV Position %” refers to a value that indicates the position of the inlet guide vane (IGV).
Duplex Chillers
The following figure shows an example of a Duplex Chiller Operating Modes screen.
Figure 13.
28
Chiller Operating Modes screen for Duplex chillers
CTV-SVU01G-EN
Reports
For Duplex™ chillers, the Chiller Operating Modes screen shows top-level modes and submodes
for the chiller (Table 6, p. 29) and for the circuits (Table 7, p. 30). Each table shows top-level
modes in the left column, a description in the middle column, and the corresponding submodes
in the right column.
Submodes are dependent on the top-level mode. They appear on the Chiller Operating Modes
screen with the following characteristics:
•
The newest submode appears at the top of the submode list.
•
Submodes disappear when they no longer apply.
•
The screen displays up to four submodes.
•
If less than four submodes are active, the submode rows that do not apply are blank.
Table 6. Chiller top-level operating modes and corresponding submodes for Duplex chillers
Top-level mode
Description
Stopped
The chiller is not running either circuit and cannot run without
intervention.
Corresponding submodes
Local Stop
Immediate Stop
Diagnostic Shutdown—Manual Reset
Ice Building Is Complete
Start Inhibited By BAS
Run Inhibit
The chiller is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or
diagnostic condition is cleared.
Waiting for BAS Communication
External Source Inhibit
Diagnostic Shutdown—Auto Reset
No Circuits Available
Waiting for Evaporator Water Flow
Auto
The chiller is not currently running but can be expected to start
at any moment given that the proper conditions and interlocks
are satisfied.
Waiting for a Need to Cool
Waiting for a Need to Heat
Power Up Display Inhibit (MIN:SEC)(a)
Waiting to Start
The chiller is going through the necessary steps to allow the
lead circuit to start.
The chiller will wait up to 4 minutes and 15
seconds in this mode for condenser water flow
to be established by means of the flow switch
hardwired input.
Hot Water Control
Base Loaded
Ice Building
Running
At least one circuit on the chiller is currently running.
Ice To Normal Transition (MIN:SEC)(a)
Current Control Softloading
Capacity Control Softloading
Minimum Capacity Limit
Running—Limit
CTV-SVU01G-EN
At least one circuit on the chiller is currently running, but the
operation of the chiller as a whole is being actively limited by
the controls. The submodes that apply the Running top modes
may be displayed along with the following limit-specific modes.
All of the chiller-level Running submodes apply.
There are no specific submodes associated with
Running—Limit.
29
Reports
Table 6. Chiller top-level operating modes and corresponding submodes for Duplex chillers (continued)
Top-level mode
Description
Corresponding submodes
Evaporator Pump Off Delay (MIN:SEC)(a)
Condenser Pump Off Delay (MIN:SEC)(a)
Shutting Down
The chiller is still running, but shutdown is imminent. The
chiller is going through a compressor run-unload.
Satisfied Need to Cool
Satisfied Need to Heat
Satisfied Need to Minimum Capacity Timer (will
display for only 10 seconds)
Evaporator Pump Off Override
Condenser Pump Override
Miscellaneous
These submodes may appear with most of the top-level chiller
modes.
Manual Capacity Override
IGV Manual Override(b)
Software Service Lock
(a)
(b)
“MIN:SEC” refers to a count-down timer that appears on the screen to indicate how long the submode will remain active.
“IGV Position %” refers to a value that indicates the position of the inlet guide vane (IGV).
Table 7. Circuit-level operating modes and corresponding submodes for Duplex chillers
Top-level mode
Description
Stopped
The circuit is not running, and cannot run without intervention.
Corresponding submodes
Diagnostic Shutdown—Manual Reset
Front Panel Circuit Lockout
Run Inhibit
Auto
The circuit is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or
diagnostic condition is cleared.
The circuit is currently not running but is expected to start at
any moment if the proper conditions are satisfied.
Diagnostic Shutdown—Auto Reset
External Circuit Lockout
No Circuit Submodes
Waiting for Low Oil Differential Pressure
Establishing Oil Pressure
Pre-Lubrication Time (MIN:SEC)(a)
Motor Temperature Inhibit: Motor Temperature/
Inhibit Temperature
Restart Time Inhibit (MIN:SEC)(a)
Waiting To Start
The chiller is going through the necessary steps to allow the
lead circuit to start.
High Vacuum Inhibit: Oil Sump Press/Inhibit
Press
Low Oil Temperature Inhibit: Oil Temperature/
Inhibit Temperature
Waiting for Starter To Start (MIN:SEC)(a)
Waiting for IGV Positioning to Complete(b)
Waiting for Starter Interlock
Starting Compressor
30
The circuit is going through the necessary steps to allow the
compressor on that circuit to start.
No submodes
CTV-SVU01G-EN
Reports
Table 7. Circuit-level operating modes and corresponding submodes for Duplex chillers (continued)
Top-level mode
Description
Corresponding submodes
Surge
Hot Gas Bypass
Current Limit
Running
The compressor on the circuit is currently running.
Phase Unbalance Limit
Evaporator Temperature Limit
High Compressor Discharge Temp Limit
Current Limit
Phase Unbalance Limit
Running—Limit
Compressor is running with limits in effect.
Condenser Pressure Limit
Evaporator Temperature Limit
High Compressor Discharge Temp Limit
Preparing to Shutdown
The circuit is preparing to de-energize the compressor.
Closing IGV(b)
Shutting Down
The chiller is going through the necessary steps after deenergizing the compressor.
Post-Lubrication Time (MIN:SEC)(a)
Miscellaneous
These submodes may appear with most of the top-level chiller
modes.
(a)
(b)
Overdrive IGV Closed(b)
Oil Pump Override
“MIN:SEC” refers to a count-down timer that appears on the screen to indicate how long the submode will remain active.
“IGV Position %” refers to a value that indicates the position of the inlet guide vane (IGV).
Purge Operating Modes
On the Reports screen, touch P u r g e O p e r a t i n g M o d e s to view the current operating status of
the purge system in terms of the top-level operating mode and submodes.
N o t e : For Duplex™ chillers, the operating status of purge system is shown in terms of the two
circuits.
The purge system operates in one of four top-level operating modes:
•
Stop
•
On
•
Auto
•
Adaptive
Submodes are dependent on the top-level mode. Their appearance on the Purge Operating
Modes screen has the following characteristics:
•
The newest submode appears at the top of the submode list.
•
Submodes disappear when they no longer apply.
•
The screen displays up to six submodes.
•
If less than six submodes are active, the submode rows that do not apply are blank.
For detailed information about purge operating modes and submodes, refer to PRGF-SVX001*EN (Installation, Operation, and Maintenance: EarthWise Purge System with Tracer AdaptiView
Control for Water-cooled CenTraVac Chillers with R-123 Refrigerant) or PRGG-SVX001*-EN
(Installation, Operation, and Maintenance: Purge System with Tracer AdaptiView Control for
Water-cooled CenTraVac Chillers with R-514A Refrigerant), as appropriate.
CTV-SVU01G-EN
31
Data Graphs
You can use the Tracer® AdaptiView™ display to view a variety of default data graphs and to
create up to six custom data graphs with up to eight data points per graph. The data sample rate
is 30 seconds, and the data storage duration is 48 hours. These rates cannot be adjusted.
The Data Graphs Screen
Touch the D a t a G r a p h s button in the main menu area to view the Data Graphs screen shown in
the following figure. Each button on the screen links to a data graph.
The buttons under the Default Graphs heading for Simplex chillers are:
•
•
•
•
•
•
•
•
•
•
Chiller Overview 1
Chiller Overview 2
Approach Temperature
Evaporator
Motor
Condenser
Motor Temperature
Compressor
Purge
Oil System or Lube System
When you create custom graphs, they appear under the Custom Graphs heading with names
such as “Custom 1” and “Custom 2,” as shown in the following figure.
Figure 14.
Data Graphs screen
The buttons under the Default Graphs heading for Duplex™ chillers are:
Chiller
•
32
Chiller Overview 1
CTV-SVU01G-EN
Data Graphs
•
•
•
Chiller Overview 2
Evaporator
Condenser
Circuit 1
•
•
•
•
•
•
Oil System
Approach Temperature
Compressor
Motor
Motor Temperature
Purge
Circuit 2
•
•
•
•
•
•
Oil System
Approach Temperature
Compressor
Motor
Motor Temperature
Purge
Viewing Data Graphs
On the Data Graphs screen, touch any of the buttons to view a live graph. (The following
figure shows Chiller Overview 1 as an example). For every graph, the X-axis shows time. The Yaxes presents data points specific to each graph. The data points are listed in “The Data Graphs
Screen,” p. 32.
Figure 15.
CTV-SVU01G-EN
Example of Data Graph (Chiller Overview 1 shown)
33
Data Graphs
Changing the Scales on Data Graphs
Changing the Scale of the X-axis
The X-axis scale defaults to the most recent 60 minutes with 15 minutes in between the time
labels that appear across the bottom of the graph. You can change the scale from the last 12
minutes to the last 2 days and increments in between, as follows:
•
•
•
•
•
•
•
12-minute graph with 3 minutes between time labels
40-minute graph with 10 minutes between time labels
60-minute graph with 15 minutes between time labels
4-hour graph with 1 hour between time labels
8-hour graph with 2 hours between time labels
1-day graph with 6 hours between time labels
2-day graph with 12 hours between time labels
To change the scale, touch the plus or minus button in the magnifying glass in the lower left
corner of a data graph that you want to edit (for an example, refer to the figure in “Viewing Data
Graphs,” p. 33). The slider scale moves to the right or left as you touch either the plus or minus
button. The time scale for the X-axis changes in response.
Changing the Scale of the Y-axes
The Y-axes scales have a default range that varies for each data graph. You can change the range
for each graph.
1. Touch the E d i t Y - A x i s button at the bottom of a data graph that you want to edit (for an
example, refer to the figure in “Viewing Data Graphs,” p. 33). The Set Axis Range screen
appears in the following figure. The screen shows the minimum and maximum values for
that particular graph.
Figure 16.
Set Axis Range screen
2. Touch the M a n u a l l y s e t v a l u e s button under either the Left Y-Axis or Right Y-Axis heading.
E n t e r n u m b e r buttons appear to the right of the minimum and maximum values.
3. Touch the E n t e r n u m b e r button for the value you want to change. A keypad appears on the
34
CTV-SVU01G-EN
Data Graphs
screen.
4. Touch the appropriate numbers to change the current value. The new value appears above
the keypad.
5. Touch the E n t e r button. The graph you were previously viewing appears with changed
maximum and/or minimum values.
6. Touch S a v e . The data graph appears with changed Y-axes scales.
Creating Custom Data Graphs
You can create a custom data graph in two ways:
•
By starting with a default data graph
•
By starting from a blank screen, with no previously defined data graph points
Creating a Custom Data Graph From a Default Data Graph
1. Touch the C r e a t e C u s t o m button at the top left of any default data graph screen (for an
example, refer to the figure in “Viewing Data Graphs,” p. 33). The Data Graph Points screen
appears as shown in the following figure.
Figure 17.
Data Graph Points screen
2. Touch the A d d / R e m o v e P o i n t s button at the top left of the screen. The Add/Remove screen
appears (refer to the following figure), pre-populated with data points from the default data
graph you chose.
N o t e : When you save the graph, a new custom graph is created; the default data graph is not
overwritten.
3. Touch the up/down arrows at the top of the left box on the Add/Remove screen to scroll
through a list of chiller components. The list of items in the box just below the up/down
arrows changes to correspond to the component choice. (For reference, these items are listed
in “Appendix A: Data for CenTraVac Simplex Chillers,” p. 63 and “Appendix B: Data for
CTV-SVU01G-EN
35
Data Graphs
CenTraVac Duplex Chillers ,” p. 77).
Figure 18.
Add/Remove screen example
4. To choose points to include in the custom data graph, you can do any of the following:
•
To add one item at a time, touch the item in the left box. It responds by changing to blue.
Touch A d d to move the selected item to the right box.
•
To add all of the items in the left box to the right box, touch A d d A l l .
•
To remove one item at a time, touch the item in the right box. It responds by changing to
blue. Touch R e m o v e to move the selected item to the left box.
•
To remove all of the items in the right box to the left box, touch R e m o v e A l l . A
confirmation screen appears, asking you to verify your request.
5. When you are finished choosing data points, touch S a v e . The Data Graph Points screen
appears. Touch the F i n i s h e d button to view the custom data graph you have just created
(refer to the following figure.
N o t e : To edit the appearance of data points in the graph, refer to “Editing Custom Data
Graphs,” p. 37.
36
CTV-SVU01G-EN
Data Graphs
Figure 19.
Custom data graph example
Creating a Custom Data Graph With No Previously Defined Data Graph Points
1. Touch the C r e a t e C u s t o m button at the top left of the Data Graphs screen (Figure 14, p. 32).
The Add/Remove screen appears (see ), but with no data on the screen.
2. Continue by following Step 3 through Step 5 in “Creating a Custom Data Graph From a
Default Data Graph,” p. 35.
Editing Custom Data Graphs
You can edit custom data graphs by:
•
Changing the scales of the X-axis and Y-axes (follow the procedures in “Changing the Scales
on Data Graphs,” p. 34 ).
•
Changing the:
–
Line style between bold and normal
–
Y-axis location between left and right
–
Line color
1. To edit a data point, touch the E d i t button in the row for the data point you want to edit. The
Edit Data Point screen appears (refer to the following figure).
2. Touch the button in each category—Line Style, Y-Axis, Color—that represents how you want
the graph to appear. The buttons you select become shaded.
3. Touch S a v e . The screen you were previously viewing appears with your changes reflected in
the table.
CTV-SVU01G-EN
37
Data Graphs
Figure 20.
Edit Data Point screen
Deleting a Custom Data Graph
Touch the D e l e t e button at the top of a custom graph screen to delete the custom graph.
38
CTV-SVU01G-EN
Equipment Settings
You can use the Tracer® AdaptiView™ display to monitor and change a variety of equipment
settings.
The Settings Screen
Touch the S e t t i n g s button in the main menu area (see “Main Menu Area,” p. 17) to view the
Settings screen. Equipment Settings identifies a column of buttons located on the screen. (Refer
to the outlined column in the following figure.) The buttons are:
•
Chiller Settings
•
Feature Settings
•
Chiller Water Reset
•
Purge Settings
•
Manual Control Settings
Each of these buttons provide access to a screen that contains additional buttons related to each
topic. This section provides detailed information about these screens.
Figure 21.
Settings screen with the Equipment Settings column highlighted
Viewing and Changing Equipment Settings
Each button in the Equipment Settings column on the Settings screen takes you to a menu
screen that contains a group of buttons. Each button displays the name of a setting and its
current value (refer to the following figure). Touch any button to view a screen where you can
change the setting for the feature shown on the button.
N o t e : A page number appears in the lower right corner of the screen. If a screen contains more
than one page, up/down arrows also appear for viewing the other pages, as in the
following figure.
CTV-SVU01G-EN
39
Equipment Settings
Figure 22.
Example equipment settings screen (Chiller Settings shown)
To change an equipment setting, follow this procedure:
1. Touch one of the buttons in the Equipment Settings column on the Settings screen, such as
Chiller Settings. The corresponding screen appears (in this case, the Chiller Settings screen).
2. Touch the button that shows the equipment setting you want to change. A screen that allows
you to change the equipment setting appears. There are two types of these screens:
•
40
For screens with button selections, touch the button that represents the setting you want.
The button becomes shaded, and a S a v e button appears at the bottom of the screen as
shown in the following figure.
CTV-SVU01G-EN
Equipment Settings
Figure 23.
•
Example equipment settings screen with buttons for changing setting
For screens with numerical keypads, touch the appropriate numbers to change the current
value as shown in the following figure. The new value appears above the keypad.
Figure 24.
Example equipment settings screen with keypad for changing setting
Keypad features:
CTV-SVU01G-EN
41
Equipment Settings
–
When you enter a new number, the value in the N e w v a l u e field is deleted and
replaced with the new entry.
–
The backspace (arrow) key deletes the characters you previously entered.
–
If the keypad is used to enter a setpoint that is out of range, an error dialog will
appear when you touch the S a v e button.
–
Keypads that allow negative numbers have positive and negative number (+/-)
keys.
3. Touch S a v e to complete the change. The current value is updated in the upper left side of the
screen, demonstrating that the change has been communicated to the Tracer UC800
controller. The screen you were previously viewing appears.
N o t e : Manual Control Settings screens have Apply buttons in addition to Save buttons. For
an example, refer to “Manual Control Settings,” p. 47. Touching Apply is the same as
touching Save, except that you remain at the current screen after the change is
communicated to the Tracer® UC800 controller.
Chiller Settings
The following table lists the settings that are available as buttons on the Chiller Settings menu
screen, along with their corresponding setting options. The chiller configuration determines
which of the settings appear.
Table 8. Chiller Settings menu screen: Buttons and available setting options
Page 1 of 2
Setpoint Source
BAS/Ext/FP
Ext/FP
Front Panel
Front Panel Control Type
Cooling/ Heating
Front Panel Chilled Water Setpoint
XX.X °F/C
Front Panel Hot Water Setpoint
XXX.X °F/C
Front Panel Ice Building Command
Auto/On
Front Panel Ice Termination Setpoint
XX.X °F/C
Ice to Normal Cooling Timer Setpoint
XX Min
Front Panel Current Limit Setpoint
XXX.X %
Front Panel Base Loading Setpoint
XXX.X %
Front Panel Base Loading Command
Auto/On
Page 2 of 2
Differential to Start
XX.X °F/C
Differential to Stop
XX.X °F/C
Front Panel Free Cooling Command
Auto/On
Condenser Water Pump Off Delay
XX Min
Evaporator Water Pump Off Delay
XX Min
Evap Low Water Flow Warning
SetpointXXXX.X gpm/lpm
Power-Up Start Delay
XXX Sec
Starter Power Demand Time Period
XXX Min
42
CTV-SVU01G-EN
Equipment Settings
Service Settings
The following table lists the settings that are available as buttons on the Service Settings menu
screen, along with their corresponding setting options. The chiller configuration determines
which of the settings appear.
Table 9. Service Settings menu screen: Buttons and available settings options
Page 1 of 2
Evaporator Leaving Water Temp Cutout
XX.X °F/C
Low Refrigerant Temperature Cutout
XX.X °F/C
Local Atmospheric Pressure
XX.X PSI/kPa
Maximum Capacity Limit
XXX.X %
Minimum Capacity Limit
XXX.X %
(Formerly in Chiller Settings)
BAS Setpoint Power Loss Store Enable
Enable/Disable
Check Oil Filter Setpoint
XX.XX PSID/kPaD
-orCheck Lube Filter Setpoint
XX.XX PSID/kPaD
(CVHS Only)
Startup Lube Diff Pressure Threshold
XX.XX PSID/kPaD
(CVHS Only)
Capacity Control Softload Time
XXX Sec
Current Limit Control Softload Time
XXX Sec
Current Limit Softload Start Point
XXX.X %
Page 2 of 2
Condenser Limit Setpoint
XXX.X %
Head Pressure Control Pre-Position Setpoint
XXX.X %
Staging On Boundary
XXX.X %
(Duplex Only)
Staging Off Boundary
XXX.X %
(Duplex Only)
Head Pressure Control Pre-Position Setpoint
XXX.X %
Setpoint Sources
Some setpoints can be controlled from more than one source; these are referred to as arbitrated
setpoints. Arbitrated setpoints can be:
•
Communicated from a building automation system (BAS)—Refers to a Trane or other BAS
that can communicate with chiller controls over a network.
•
Set by an external control source (Ext)—Refers to inputs that are hard-wired directly to local
chiller controls, carrying low-voltage binary (On/Off) or analog (0–10 Vdc, 4–20 mA) signals.
•
Set at the front panel (FP)—Refers to inputs that are entered by an operator using the Tracer®
AdaptiView™ display or by a technician using the Tracer® TU service tool.
Setpoint Source Arbitration
The Tracer® UC800 uses a process referred to as setpoint source arbitration to prioritize the
selection of the setpoint source. The following table provides an explanation of how this process
works.
Table 10.
Setpoint source choices and corresponding arbitration
Priority
BAS/Ext/FP
Ext/FP
First
Setpoint from the BAS is used.
Setpoint from a external control source is
used.
Second
If no BAS setpoint is available (for
example, BAS communication has
never been established), a setpoint
from an external control source is
used.
Front Panel
Setpoint from the front panel is used.
CTV-SVU01G-EN
If no externally controlled setpoint is
available, a setpoint from the front panel
is used.
Note: Any setpoint from a BAS or external
control source is ignored.
None
Note: Any setpoint from a BAS is ignored.
43
Equipment Settings
Table 10.
Setpoint source choices and corresponding arbitration (continued)
Priority
BAS/Ext/FP
Ext/FP
Front Panel
Third
If no BAS nor external setpoint is
available (for example, BAS
communication has never been
established), a setpoint from the front
panel is used.
None
None
Notes:
1.
2.
For service or troubleshooting, it may be helpful to set the setpoint source to front panel to isolate the chiller from other control sources.
If BAS communication was established and then lost, in most instances the BAS values remain and can be used by the chiller controller.
Changing the Setpoint Source
There are three ways to access the Setpoint Source screen. To change the setpoint source, follow
one of these procedures:
Using the Setpoint Source Button in the Chiller Status Area
1. Touch the S e t p o i n t S o u r c e button in the chiller status area (refer to “Screen Overview,” p.
8).
The Setpoint Source screen appears as shown in the following figure.
2. Touch the appropriate source button on the Setpoint Source screen.
3. Touch S a v e to complete the change.
N o t e : The change applies to all arbitrated setpoints.
Figure 25.
Setpoint Source screen
From the Setpoint Source Button on the Chiller Settings Screen
1. Touch the S e t t i n g s button in the main menu area (refer to “Screen Overview,” p. 8). The
Settings screen appears.
44
CTV-SVU01G-EN
Equipment Settings
2. From the Settings screen, touch the C h i l l e r S e t t i n g s button. The Chiller Settings screen
appears.
3. From the Chiller Settings screen, touch the button that is labeled “Setpoint Source” and
displays the current source. The Setpoint Source screen appears (refer to the preceding
figure).
4. Touch the button the appropriate source button on the Setpoint Source screen.
5. Touch S a v e to complete the change.
N o t e : The change applies to all arbitrated setpoints.
From an Arbitrated Setpoint Screen
1. Touch the S e t t i n g s button in the main menu area (Figure 2, p. 9). The Settings screen
appears.
2. From the Settings screen, touch the C h i l l e r S e t t i n g s button. The Chiller Settings screen
appears.
3. From the Chiller Settings screen, touch an arbitrated setpoint. The setpoint screen for that
specific arbitrated setpoint appears (see the following figure for an example).
4. On the arbitrated setpoint screen, touch the Setpoint Source button. The Setpoint Source
screen appears (refer to the preceding figure).
5. Touch the button the appropriate source button on the Setpoint Source screen.
6. Touch S a v e to complete the change.
N o t e : The change applies to all arbitrated setpoints.
Figure 26.
CTV-SVU01G-EN
Changing the setpoint source from an arbitrated setpoint screen
45
Equipment Settings
Feature Settings
The following table lists the settings that are available as buttons on the Feature Settings menu
screen, along with their corresponding setting options. The chiller configuration determines
which of the settings appear.
Table 11.
Feature Settings menu screen: Buttons and available setting options
Ext Chilled Wtr Setpt
Enable/Disable
Ext Current Limit Setpt
Enable/Disable
Ice Building
Enable/Disable
Ext Chilled Wtr Setpt
Enable/Disable
Ext Current Limit Setpt
Enable/Disable
Ice Building
Enable/Disable
Hot Gas Bypass Feature
Enable/Disable
Hot Gas Bypass Maximum Timer
Enable
Enable/Disable
Security
Enable/Disable
LCI-C Diagnostic Encoding
Text/Code
External Base Loading Setpoint
Enable/Disable
Check Oil Filter Diagnostic Ckt1
Enable/Disable
-orCheck Lube Filter Diagnostic
Enable/Disable
(CVHS Only)
Check Oil Filter Diagnostic Ckt2
Enable/Disable
Chilled Water Reset
The following table lists the settings that are available as buttons on the Chilled Water Reset
menu screen, along with their corresponding setting options. The chiller configuration
determines which of the settings appear.
Table 12.
Chilled Water Reset menu screen: Buttons and available setting options
Buttons
Chilled Water Reset Type
Available setting options
•
Disable
•
Return
•
Outdoor Air
•
Constant
Return Reset Ratio
Valid numerical range appears on screen.
Return Start Reset
Valid numerical range appears on screen.
Return Maximum Reset
Valid numerical range appears on screen.
Outdoor Reset Ratio
Valid numerical range appears on screen.
Outdoor Start Reset
Valid numerical range appears on screen.
Outdoor Maximum Reset
Valid numerical range appears on screen.
46
CTV-SVU01G-EN
Equipment Settings
Purge Settings
The following table lists the settings that are available as buttons on the Purge Settings menu
screen, along with their corresponding setting options. The chiller configuration determines
which of the settings appear.
Table 13.
Purge Settings menu screen: Buttons and available setting options
Available setting options
Buttons
•
Stop
Purge Operating Mode
•
Auto
Note: Ckt1 and Ckt2 for Duplex chillers
•
Adaptive
•
On
Daily Pumpout Limit
Valid numerical range appears on screen.
Note: Ckt1 and Ckt2 for Duplex chillers
Disable Daily Pumpout Limit
Valid numerical range appears on screen.
Note: Ckt1 and Ckt2 for Duplex chillers
Purge Liquid Temperature Inhibit
•
Enable
Note: Ckt1 and Ckt2 for Duplex chillers
•
Disable
Purge Liquid Temperature Limit
Valid numerical range appears on screen.
Note: Ckt1 and Ckt2 for Duplex chillers
Manual Control Settings
The following table lists the settings that are available as buttons on the Manual Control Settings
menu screen, along with their corresponding setting options. The chiller configuration
determines which of the settings appear.
Table 14.
Manual Control settings menu screen: Buttons, available setting options, and status points
Feature
Chiller Control Signal
Evaporator Pump Override
Condenser Pump Override
CTV-SVU01G-EN
Current
value
Auto/Manual
On/Off
On/Off
Available setting
options
Manual mode: Up/down
arrows for changing the
setpoint
•
Auto
•
On
•
Auto
•
On
Status points
•
IGV1 Position (Simplex chillers only)
•
IGV2 Position (Simplex chillers only)
•
Average Line Current (Ckt1 and Ckt2 for Duplex
chillers
•
AFD Frequency (Ckt1 and Ckt2 for Duplex
chillers
•
Active Chilled Water Setpoint (Active Hot Water
Setpoint if in Heating mode)
•
Evap Leaving Water Temp (Cond Leaving Water
Temp if in Heating mode)
•
Evaporator Pump Manual Override Time
Remaining
•
Evap Water Flow Switch Status
•
Active Chilled Water Setpoint
•
Evap Leaving Water Temp
•
Condenser Pump Manual Override Time
Remaining
•
Cond Water flow Switch Status
•
Active Hot Water Setpoint
•
Cond Leaving Water Temp
47
Equipment Settings
Table 14.
Manual Control settings menu screen: Buttons, available setting options, and status points (continued)
Feature
Clear Energy Consumption
Current
value
XXXX kWh
Oil Pump Control
Note: Ckt1 and Ckt2 for Duplex
chillers
On/Off
Available setting
options
•
Simplex chillers only:
Clear
•
Duplex chillers only:
Energy Consumption
Resettable Ckt1, Ckt2
XX:XX min:sec
Purge Exhaust Circuit Test
Note: Ckt1 and Ckt2 for Duplex
chillers
Auto/On
Purge Regen Cycle
Note: Ckt1 and Ckt2 for Duplex
chillers
On/Off
Front Panel Lockout
Note: Duplex chillers only; for Ckt1
and Ckt2.
Head Pressure Control Override
48
Cond Entering
Water Temp
XXX.X °F/C
•
Starter Energy Consump. Resettable
•
Starter Energy Consump. Last Reset
•
Starter Energy Consump. NonReset
•
Oil Pump Manual Override Time Remaining
•
Auto
•
Oil Differential Pressure
•
On
•
Oil Pump Discharge Pressure
•
Oil Tank Pressure
•
Motor Temperature
•
Motor Winding Temp #1
•
Motor Winding Temp #2
•
Motor Winding Temp #3
•
MTC Switch
•
Motor Coolant Temperature
Clear Restart Inhibit
Note: Ckt1 and Ckt2 for Duplex
chillers
Status points
•
Clear
•
Enable
•
Purge Rfgt Cprsr Suction Temp
•
Disable
•
Purge Liquid Temp
•
Auto
•
Carbon Tank Temp
•
On
•
Chiller Top Level Mode
•
Locked Out
•
Top Level Operating Mode Ckt1
•
Not Locked Out
•
Top Level Operating Mode Ckt2
Cond Leaving Water Temp
Cond Rfgt Pressure
CTV-SVU01G-EN
Equipment Settings
Changing a Manual Control Setting
To change a manual control setting, follow this procedure:
1. In the Equipment Settings column on the Settings screen, touch M a n u a l C o n t r o l S e t t i n g s .
The Manual Control Settings screen appears as shown in the following figure.
Figure 27.
Manual Control Settings screen
2. Touch the button that shows the manual control setting you want to change. A screen for
changing the manual control setting appears as shown in the following figure.
3. Touch the button that represents the setting you want. The button becomes shaded and
A p p l y and S a v e buttons appear at the bottom of the screen.
N o t e : The Compressor Control Signal screen provides up/down arrow keys and numerical
fields for selecting a value.
4. To save your change, do one of the following:
CTV-SVU01G-EN
•
Touch A p p l y . The change is communicated to the Tracer® UC800 controller. You can
observe the status points in the lower half of the screen change in response to the setting
change you just made. Also, a Manual Override button appears in the upper left corner of
the screen (refer to the following figure).
•
Touch S a v e . The change is communicated to the Tracer® UC800 controller. The screen
you were previously viewing appears.
49
Equipment Settings
Figure 28.
50
Manual Control Settings screen (Evaporator Pump Override shown)
CTV-SVU01G-EN
Display Settings
You can use the Tracer® AdaptiView™ display to change the format of the information that
appears on the display, and to clean the touch screen.
Settings Screen
Touch the S e t t i n g s button in the main menu area (refer to “Screen Overview,” p. 8) to view the
Settings screen. Display Settings identifies a column of buttons located on the screen as shown
in the following figure. The buttons are:
•
Display Preferences
•
Language
•
Date and Time
•
Clean Display
Each button provides access to a screen that is related to the button name.
Figure 29.
Settings screen with the Display Settings column highlighted
Viewing and Changing Display Preferences
On the Settings screen, touch D i s p l a y P r e f e r e n c e s to view a screen containing the following
buttons.
CTV-SVU01G-EN
•
Date Format
•
Date Separator
•
Time Format
•
Brightness
•
Unit System
•
Pressure Units
•
Backlight Timeout
51
Display Settings
Figure 30.
Display Preferences screen
Each of the buttons in the previous figure shows the name of a display preference and its format
(current value). Touch any of these buttons to view a screen where you can change the format.
(Refer to the following figure for an example.) The button representing the format currently used
is shaded (see the “MMDDYYYY” button.
52
CTV-SVU01G-EN
Display Settings
Figure 31.
Example of a display preference screen
To change the format:
1. Touch the button that shows that format you prefer.
2. Touch S a v e to confirm your selection and to return to the Display Preferences screen.
Date Format
Use the Date Format screen to choose from the following date formats:
•
MMDDYYYY (default)
•
YYYYMMDD
•
DDMMYYYY
Date Separator
Use the Date Separator screen to choose from the following date formats:
•
None
•
Slash ( \ ) (default)
•
Hyphen ( – )
•
Period ( . )
•
Underscore ( _ )
Time Format
Use the Time Format screen to choose from the following time formats:
•
12 hour (default)
•
24 hour
Brightness
Use the numerical keypad on the Brightness screen to change the brightness of the screen. (The
default is 90%.)
CTV-SVU01G-EN
53
Display Settings
Display Units
Use the Display Units screen to choose from the following display units:
•
SI
•
Inch-Pounds (default)
Pressure Units
Use the Pressure Units screen to choose from the following pressure units:
•
kPaA (default if “SI” is chosen for display units)
•
kPaG
•
psia (default if “Inch-Pound” is chosen for display units)
•
psig
Backlight Timeout
Use the numerical keypad on the Backlight Timeout screen to change the number of minutes of
inactivity that pass until the screen dims. (The default is 60 minutes.)
Viewing and Changing the Language Preference
On the Settings screen, touch L a n g u a g e s to view a screen containing the following buttons
(refer to the following figure):
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
54
Arabic (Gulf Regions)
Chinese—China
Chinese—Taiwan
Czech
Dutch
English
French
French (Canada)
German
Greek
Hebrew
Hungarian
Indonesian
Italian
Japanese
Korean
Norwegian
Polish
Portuguese (Portugal)
Portuguese (Brazil)
Russian
Romanian
Spanish (Europe)
Spanish (Latin America)
Swedish
Thai
Turkish
CTV-SVU01G-EN
Display Settings
Figure 32.
Language screen
The language that is currently in use on the display is expressed as the current value on the
Language screen. The button that displays the current value is shaded (refer to the “English”
button in the previous figure as an example).
To change the language:
1. Touch the button that identifies the language you prefer.
2. Touch S a v e to confirm your selection and to return to the Settings screen.
CTV-SVU01G-EN
55
Display Settings
Viewing and Changing Date and Time Preferences
On the Settings screen, touch D a t e a n d T i m e to view the Date and Time screen, shown in the
following figure.
Figure 33.
Date and Time screen
The current date and time for the display is expressed as the current value. The current value
appears below the center line on the screen.
Above the center line, the following date and time attributes appear:
•
Month
•
Day
•
Year
•
Hour
•
Minute
•
AM/PM
To change the date or time:
1. Touch the square presenting the attribute you want to change. The square becomes
highlighted.
2. Touch the up or down arrow key on the screen until the your desired selection appears.
Repeat the process for any other attributes you want to change.
3. Touch S a v e to confirm your selection and return to the Settings screen.
56
CTV-SVU01G-EN
Display Settings
Clean Touchscreen
On the Settings screen, touch C l e a n T o u c h s c r e e n to disable the Tracer® AdaptiView™ display
screen for 15 seconds so that you can clean the screen without it responding to touch. During this
time, the screen is black with a number in the center that counts down the seconds. After 15
seconds, the Settings screen re-appears.
Figure 34.
CTV-SVU01G-EN
Countdown screen
57
Security Settings
If security if enabled, the Tracer® AdaptiView™ display requires that you log in with a four-digit
security PIN to make setting changes that are protected by security. This feature prevents
unauthorized personnel from doing so. There are two levels of security, each allowing specific
changes to be made.
You can view all data without logging in. The log-in screen appears only when you try to change
a setting that is protected by security, or when you touch the L o g i n button from the Settings
screen.
Settings Screen
Touch the S e t t i n g s button in the main menu area (refer to “Screen Overview,” p. 8) to view the
Settings screen. Security Settings identifies a column on the right side of the screen that contains
two buttons (see the outlined column in the following figure):
•
Security
•
Log in (Log out)
Figure 35.
Equipment Settings screen with the Security Settings column highlighted
N o t e : If security is disabled, the Log in/Log out button is not visible. Refer to “Disabling
Security,” p. 58 and “Enabling Security,” p. 59.
Disabling Security
You can disable the security feature that allows a user to log in and log out.
1. From the Settings screen, touch the S e c u r i t y button. The Security screen appears as shown
in the following figure.
N o t e : If you are logged out, the Log In screen appears. You must first log in to proceed.
58
CTV-SVU01G-EN
Security Settings
Figure 36.
Security screen
2. Touch the D i s a b l e button. The button becomes shaded.
3. Touch S a v e . The Settings screen appears with only the Security button visible. The Log in/
Log out button is gone.
Enabling Security
To enable security, perform the following steps:
1. From the Settings screen, touch the S e c u r i t y button. The Security screen appears as shown
in “Disabling Security,” p. 58.
2. Touch the E n a b l e button. The button becomes shaded.
3. Touch S a v e . The Settings screen appears with a Log out button in addition to the Security
button.
Logging In
There are two levels of security:
•
Security Level 1 allows users to change a limited group of secure settings. The default
security PIN is 1111.
•
Security Level 2 allows users to change all secure settings. The default security PIN is 7123.
A technician must use the Tracer® TU service tool to change a PIN.
To log in:
1. Touch the L o g I n button. The Log In screen appears as shown in the following figure.
CTV-SVU01G-EN
59
Security Settings
Figure 37.
Log In screen
2. Use the keypad to enter your PIN.
•
The PIN is a four-digit number, which was configured for your system with the Tracer®
TU service tool.
•
As you enter the number, the PIN remains hidden by asterisks.
N o t e : If you enter an invalid PIN, an error message appears on the Log in screen.
3. Touch S a v e .
•
If you viewed the Log In screen from touching L o g I n on the Settings screen, the Settings
screen appears with a L o g O u t button on it.
•
If the Log In screen appeared when you tried to change a setting, you return to that setting
screen.
N o t e : The PIN is valid until 30 minutes of inactivity passes, or until you log out.
60
CTV-SVU01G-EN
Security Settings
Logging Out
To log out:
1. Touch the L o g O u t button. A confirmation screen appears as shown in the following figure.
Figure 38.
Log Out confirmation screen
2. Touch Y e s to confirm that you want to log out. The Settings screen appears with a L o g I n
button on it.
LLID Binding
LLID binding screen provides the capability to bind and unbind LLIDs, similar to Tracer® TU. It
can be disabled in the configuration.
I m p o r t a n t : LLID binding screen should ONLY be used by experienced service personnel.
CTV-SVU01G-EN
61
Troubleshooting
The following table contains information to help troubleshoot the Tracer® AdaptiView™
displays.
Table 15.
Common error messages with possible causes and solutions
Issue
Possible Causes/Solutions
The screen only partially displays; the Auto and Stop buttons
appear, but there is no text.
The UC800 configuration is invalid.
Download a valid configuration using the Tracer TU service tool.
The following error message appears:
UC800 Configuration is Invalid
UC800 configuration must be updated with the Tracer TU
technician utility
Follow the error message instructions.
The following error message appears:
Communication lost with UC800
•
Check power and communication cables
•
Update the UC800 software with the Tracer TU technician
utility
The following error message appears:
Display Failed to Establish Communication
•
Check power and communication cables
•
Re-attempting connection in X seconds
Communication has been established and then lost, or the UC800
configuration is invalid.
Follow the error message instructions.
Communication is not established.
•
The Ethernet cable and/or the power cable may be disconnected.
Check the connections.
•
The UC800 may have an invalid configuration. Download a valid
configuration using the Tracer TU service tool.
A file is missing.
The following error message appears:
[*Missing file name]
UC800 software must be updated with the Tracer TU technician
utility
62
•
The Tracer TU service tool is connected and the LLID binding screen is
displayed.
•
UC800 has an invalid configuration. Download a valid configuration
using the Tracer TU service tool.
•
Cycle power to the display and the UC800. Disconnect the USB cable
and wait approximately 10 seconds before reconnecting the USB
cable.
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
The following lists contain all of the data available for viewing on a Tracer® AdaptiView™
display that is connected to a CenTraVac™ Simplex chiller.
Component Screen Data
Chiller configuration determines which of the following settings and status points appear on the
display. For more information, refer to “Component Screens,” p. 14.
Table 16.
Evaporator settings and status points (Simplex)
Active Chilled Water Setpoint (button links to the Active Chiller Water
Setpoint screen)
Evaporator Rfgt Pressure
Evaporator Pump Override (button links to Evaporator Pump Override
screen)
Evap Approach Temp
Evap Water Flow Status
Approx Evap Water Flow
Evap Leaving Water Temp
Evap Differential Wtr Press
Evap Entering Water Temp
Evaporator Entering Water Pressure
Calculated Chiller Capacity
Evaporator Leaving Water Pressure
Evaporated Saturated Rfgt Temp
Table 17.
Condenser settings and status points (Simplex)
Active Hot Water Setpoint (button links to the Active Hot Water
Setpoint screen)
Approx Cond Water Flow
Cond Condenser Pump Override (button links to the Condenser Pump
Override screen)
Cond Differential Wtr Press
Cond Water Flow Status
Second Condenser Lvg Wtr Temp
Cond Entering Water Temp
Second Condenser Ent Wtr Temp
Cond Leaving Water Temp
Head Pressure Control Status
Outdoor Air Temp
Differential Refrigerant Pressure
Condenser Sat Rfgt Temp
Refrigerant Monitor
Condenser Refrigerant Pressure
Condenser Entering Water Pressure
Condenser Refrigerant Liquid Level
Condenser Leaving Water Pressure
Condenser Approach Temperature
Economizer Bypass Valve Position
Table 18.
Compressor settings and status points (Simplex)
Compressor Running Status
IGV 2 Percent Open
Chiller Control Signal
IGV 2 Position (Steps)
Oil Pump Control
Compressor Rfgt Discharge Temp
Average Line Current (%RLA)
HGBP Time
Oil Pump Status
Oil Differential Pressure Switch (CVG, CVR Only)
Oil Differential Pressure
Lube Differential Pressure (CVHS Only)
Compressor Starts
Lube Pump Discharge Pressure (CVHS Only)
Compressor Running Time
Lube Pump Suction Pressure (CVHS)
Oil Pump Discharge Pressure
Cond Rfgt Pressure
CTV-SVU01G-EN
63
Appendix A: Data for CenTraVac Simplex Chillers
Table 18.
Compressor settings and status points (Simplex) (continued)
Oil Tank Pressure
Lube Pump Command (CVHS)
Oil Tank Temperature
Lube Flow First Stage Bearing (CVHS)
Inboard Bearing Temperature
Lube Flow Second Stage Bearing (CVHS)
Outboard Bearing Temperature
Outboard Bearing Pad Temperature #1 (CVHH Only)
IGV 1 Percent Open
Outboard Bearing Pad Temperature #2 (CVHH)
IGV 1 Position (Steps)
Outboard Bearing Pad Temperature #3 (CVHH)
Table 19.
Motor settings and status points (Simplex)
Active Current Limit Setpoint (button links to Active Current Limit
Setpoint screen)
AFD Motor Current U % RLA
Average Motor Current (%RLA)
AFD Motor Current V % RLA
ADF Frequency or Generator Frequency Command (based on
configuration)
AFD Motor Current W % RLA
Starter Motor Current L1 (%RLA)
AFD Motor Current U
Starter Motor Current L2 (%RLA)
AFD Motor Current V
Starter Motor Current L3 (%RLA)
AFD Motor Current W
Starter Motor Current L1 (A)
AFD Input Current L1
Starter Motor Current L2 (A)
AFD Input Current L2
Starter Motor Current L3 (A)
AFD Input Current L3
Starter Input Voltage Phase AB
AFD Average Motor Voltage
Starter Input Voltage Phase BC
AFD Average Input Voltage
Starter Input Voltage Phase CA
AFD Motor Voltage UV
Motor Winding Temp 1
AFD Motor Voltage VW
Motor Winding Temp 2
AFD Motor Voltage WU
Motor Winding Temp 3
AFD DC Bus Voltage
AFD Speed
AFD DC Bus Current
AFD Transistor Temp
AFD Calculated Input Voltage
Starter Energy Consumption Resettable
AFD Output Power
Starter Energy Consumption Last Reset
AFD Average Input Current
Starter Energy Consump Non Reset
Motor Speed
Starter Power Demand
Motor Frequency
Starter Load Power Factor
Table 20.
Purge settings and status points (Simplex)
Purge Top Level Mode (button links to Purge Operating Modes screen
Pumpout Chiller On—7 days
Purge Regen Cycle (button links to Purge Regen Cycle screen)
Pumpout Chiller Off—7 days
Purge Fault Indicator (button links to Alarms screen)
Time Until Next Purge Run
Daily Pumpout—24 Hours
Purge Rfgt Compressor Suction Temp
Average Daily Pumpout—7 Days
Purge Liquid Temperature
64
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
Table 20.
Purge settings and status points (Simplex) (continued)
Daily Pumpout Limit/Alarm
Pumpout—Life
Chiller On—7 Days
Purge Carbon Tank Temp
Reports
The following data can be viewed on the Reports screen. For more information, refer to
“Reports,” p. 23.
Log Sheet
Table 21.
Evaporator report data
Report item
Unit
Evaporator Entering Water Temperature
XXX.X °F/°C
Evaporator Leaving Water Temp
XXX.X °F/°C
Evaporator Sat Rfgt Temp
XXX.X °F/°C
Evaporator Rfgt Pressure
XXX.X PSI/kPa
Evaporator Approach Temp
XXX.X °F/°C
Evaporator Water Flow Switch Status
Flow/No Flow
Table 22.
Condenser report data
Report item
Unit
Cond Entering Water Temp
XXX.X °F/°C
Cond Leaving Water Temp
XXX.X °F/°C
Cond Sat Rfgt Temp
XXX.X °F/°C
Cond Rfgt Pressure
XXX.X PSI/kPa
Cond Approach Temp
XXX.X °F/°C
Cond Water Flow Switch Status
Flow/No Flow
Cond Rfgt Liquid Level
XX.XX in/mm
Table 23.
Compressor report data
Report item
Unit
Starts
XXXX Starts
Running Time
XX:XX Hr:Min
Oil Tank Pressure
XXX.X PSI/kPa
Oil Pump Discharge Pressure
XXX.X PSI/kPa
Oil Differential Pressure
XXX.X PSI/kPa
Oil Tank Temperature
XXX.X °F/°C
IGV 1 Position
XXX.X %
Oil Diff Pressure Switch (CVGF, CVR)
XXX.X PSI/kPa
Lube Pump Discharge Pressure (CVHS)
XXX.X PSI/kPa
Cond Rfgt Pressure (visible only with CVHS)
XXX.X PSI/kPa
IGV 1 Position
Steps
CTV-SVU01G-EN
65
Appendix A: Data for CenTraVac Simplex Chillers
Table 23.
Compressor report data (continued)
Report item
Unit
IGV 2 Position
XXX.X %
IGV 2 Position
Steps
Table 24.
Motor report data
Report item
Unit
Starter Current L1
XXX.X %
Starter Current L2
XXX.X %
Starter Current L3
XXX.X %
Starter Current L1
XXXX A
Starter Current L2
XXXX A
Starter Current L3
XXXX A
Starter Voltage AB
XXXXX.X V
Starter Voltage BC
XXXXX.X V
Starter Voltage CA
XXXXX.X V
Starter Power Demand
XXXX kW
Starter Load Power Factor
XX.X
Motor Winding Temp 1
XXX.X °F/°C
Motor Winding Temp 2
XXX.X °F/°C
Motor Winding Temp 3
XXX.X °F/°C
AFD Frequency
XX Hz
AFD Speed
XXXX RPM
AFD Transistor Temp
XXX.X °F/°C
AFD Motor Current U % RLA
XXX.X %RLA
AFD Motor Current V % RLA
XXX.X %RLA
AFD Motor Current W % RLA
XXX.X %RLA
AFD Motor Current U
XXXX Amps
AFD Motor Current V
XXXX Amps
AFD Motor Current W
XXXX Amps
AFD Motor Voltage UV
XXXXX.X Volts
AFD Motor Voltage VW
XXXXX.X Volts
AFD Motor Voltage WU
XXXXX.X Volts
Starter Input Power Consumption
XXXXX kWh
Starter Motor Power Factor
XXX.X
Table 25.
Purge report data
Report item
Unit
Time Until Next Purge Run
XXX.X min
Daily Pumpout—24 Hours
XXX.X min
66
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
Table 25.
Purge report data (continued)
Report item
Unit
Average Daily Pumpout—7 Days
XXX.X min
Daily Pumpout Limit
XXX.X min
Chiller On—7 Days
XXX.X min
Pumpout Chiller On—7 Days
XXX.X min
Pumpout Chiller Off—7 Days
XXX.X min
Pumpout—Life
XXX.X min
Purge Rfgt Compressor Suction Temp
XXX.X °F/°C
Purge Liquid Temp
XXX.X °F/°C
Purge Carbon Tank Temp
XXX.X °F/°C
ASHRAE Chiller Log
N o t e : The ASHRAE Chiller Log contains those items recommended by ASHRAE Std 147 Standard
147-2002, Reducing Release of Halogenated Refrigerants from Refrigeration and AirConditioning Equipment and Systems.
Table 26.
ASHRAE Chiller Log data
Data Name
Value
Current Date/Time
User-selected date/time format
Chiller Top Level Mode
Running /Stopped / Run Inhibit / Auto / etc.
Starter Motor Current L1
XXX.X A
Starter Motor Current L2
XXX.X A
Starter Motor Current L3
XXX.X A
AFD Motor Current U
XXXX A
AFD Motor Current V
XXXX A
AFD Motor Current W
XXXX A
AFD Motor Voltage UV
XXXX v
AFD Motor Voltage VW
XXXX v
AFD Motor Voltage WU
XXXX v
Starter Input Voltage AB
XXXX.X v
Starter Input Voltage BC
XXXX.X v
Starter Input Voltage CA
XXXX.X v
Active Chilled Water Setpoint
XXX.X °F/C
Active Current Limit Setpoint
XXX.X %
Refrigerant Type
XXXXX
Refrigerant Monitor
XXX ppm
Daily Pumpout - 24 Hours
XX:XX Min:Sec
Daily Pumpout Limit
XXX Min
Pumpout - Life
XXX:XX Min:Sec
Purge Top Level Mode
On/Auto/Adaptive/Stop
CTV-SVU01G-EN
67
Appendix A: Data for CenTraVac Simplex Chillers
Table 26.
ASHRAE Chiller Log data (continued)
Data Name
Value
Purge Mode
On/Auto/Adaptive/Stop
Compressor Starts
XXXX
Compressor Running Time
XX:XX Hr:Min
Compressor Refrigerant Discharge Temperature*
XXX.X °F/C
Oil Pump Discharge Pressure
XXX.X PSIA/kPaA
Oil Tank Pressure
XXX.X PSIA/kPaA
Oil Differential Pressure
XXX.XX PSID/kPaD
Oil Diff Pressure Switch
(CVGF, CVR only)
Flow/No Flow
Lube Pump Discharge Pressure
(CVHS)
XXX.X PSIA/kPaA
Cond Rfgt Pressure
(visible only with CVHS)
XXX.X PSIA/kPaA
Lube Differential Pressure
(CVHS)
XXX.XX PSID/kPaD
Lube Pump Suction Pressure
(CVHS)
XXX.X PSIA/kPaA
Oil Tank Temperature
XXX.X °F/C
Inboard Bearing Temp
XXX.X °F/C
Outboard Bearing Temp
XXX.X °F/C
Daily Pumpout - 24 Hours
XX:XX Min:Sec
Daily Pumpout Limit
XXX Min
Pumpout - Life
XXX:XX Min:Sec
Purge Top Level Mode
On/Auto/Adaptive/Stop
Purge Mode
On/Auto/Adaptive/Stop
Compressor Starts
XXXX
Compressor Running Time
XX:XX Hr:Min
Compressor Refrigerant Discharge Temperature*
XXX.X °F/C
Oil Pump Discharge Pressure
XXX.X PSIA/kPaA
Oil Tank Pressure
XXX.X PSIA/kPaA
Oil Differential Pressure
XXX.XX PSID/kPaD
Oil Diff Pressure Switch
(CVGF, CVR only)
Flow/No Flow
Lube Pump Discharge Pressure
(CVHS)
XXX.X PSIA/kPaA
Cond Rfgt Pressure
(visible only with CVHS)
XXX.X PSIA/kPaA
Lube Differential Pressure
(CVHS)
XXX.XX PSID/kPaD
Lube Pump Suction Pressure
(CVHS)
XXX.X PSIA/kPaA
Oil Tank Temperature
XXX.X °F/C
68
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
Table 26.
ASHRAE Chiller Log data (continued)
Data Name
Value
Inboard Bearing Temp
XXX.X °F/C
Outboard Bearing Temp
XXX.X °F/C
Evaporator Entering Water Temperature
XXX.X °F/C
Evaporator Leaving Water Temperature
XXX.X °F/C
Evap Sat Rfgt Temp
XXX.X °F/C
Evap Rfgt Pressure
XXX.X PSIA/kPaA
Evap Approach Temp
XXX.X °F/C
Evap Water Flow Status
Flow/No Flow
Evap Differential Wtr Press
XXX.XX PSID/kPaD
Approx Evap Water Flow
XXX.X gpm/lpm
Calculated Chiller Capacity
XXX.X tons/kW
Cond Entering Water Temp
XXX.X °F/C
Cond Leaving Water Temp
XXX.X °F/C
Cond Sat Rfgt Temp
XXX.X °F/C
Cond Rfgt Pressure
XXX.X PSIA/kPaA
Cond Approach Temp
XXX.X °F/C
Cond Water Flow Status:
Flow/No Flow
Cond Differential Wtr Press
XXX.XX PSID/kPaD
Approx Cond Water Flow
XXX.X gpm/lpm
Second Condenser Ent Wtr Temp
XXX.X °F/C
Second Condenser Lvg Wtr Temp
XXX.X °F/C
Items Available to Include in Custom Reports
Table 27.
Chiller data
Controller Build Part Number
Ice Building Active
Version
Refrigerant Monitor
Chiller Heating or Cooling Mode
Chiller Top Level Mode
Chiller Heating or Cooling Mode
Table 28.
Evaporator data
Active Chilled Water Setpoint
Evaporator Leaving Water Temperature
Active Chilled Water Setpoint Source
Evaporator Pump Override
Active Ice Termination Setpoint
Evaporator Pump Override Time Remaining
Active Ice Termination Setpoint Source
Evap Rfgt Pressure
Calculated Chiller Capacity
Evap Sat Rfgt Temp
Approx Evap Water Flow
Evap Water Flow Status
BAS Chilled Water Setpoint
Ext Chilled Wtr Setpt
CTV-SVU01G-EN
69
Appendix A: Data for CenTraVac Simplex Chillers
Table 28.
Evaporator data (continued)
Evap Approach Temp
Front Panel Ice Building Command
Evap Differential Wtr Press
Evaporator Entering Water Pressure
Evaporator Entering Water Temperature
Evaporator Leaving Water Pressure
Table 29.
Condenser data
Active Hot Water Setpoint
Second Condenser Lvg Wtr Temp
Active Hot Water Setpoint Source
Condenser Pump Override Time Remaining
Approx Cond Water Flow
Condenser Pump Override
Cond Approach Temp
Differential Refrigerant Pressure
Cond Differential Wtr Press
Head Pressure Control Status
Cond Entering Water Temp
Condenser Entering Water Pressure
Cond Leaving Water Temp
Condenser Leaving Water Pressure
Cond Rfgt Pressure
Condenser Refrigerant Liquid Level Ckt1
Cond Sat Rfgt Temp
Economizer Bypass Valve Position Ckt1
Cond Water Flow Status
Condenser Refrigerant Liquid Level Ckt2
Outdoor Air Temp
Economizer Bypass Valve Position Ckt2
Second Condenser Ent Wtr Temp
Table 30.
Compressor data
Chiller Control Signal
Oil Pump Control
Active Base Loading Setpoint
Oil Pump Command
Active Base Loading Setpoint Source
Oil Pump Discharge Pressure
Compressor Refrigerant Discharge Temperature
Oil Pump Override Time Remaining
Compressor Running
Lube Differential Pressure
(CVHS)
Compressor Running Time
Lube Pump Control
(CVHS)
Compressor Starts
Lube Pump Command
(CVHS)
Hot Gas Bypass Total Time
Lube Pump Discharge Pressure
(CVHS)
IGV1 Position
Lube Pump Override Time Remaining
(CVHS)
IGV1 Position Steps
Lube Pump Suction Pressure
(CVHS)
IGV2 Position
Oil Tank Temperature
IGV2 Position Steps
Lube Flow First Stage Bearing
(CVHS)
IGV Closed Switch
Lube Flow Second Stage Bearing
(CVHS)
Oil Tank Pressure
Inboard Bearing Temp
Oil Differential Pressure
Outboard Bearing Temp
70
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
Table 30.
Compressor data (continued)
Oil Differential Pressure Switch
(CVGF, CVR only)
Outboard Bearing Pad Temperature #1
Oil Heater Command
Outboard Bearing Pad Temperature #2
Oil Heater Command 4E1
Outboard Bearing Pad Temperature #3
Oil Heater Command 4E2
Compressor Vibration
Table 31.
Motor data
Active Current Limit Setpoint
Motor Winding Temp #1
Active Current Limit Setpoint Source
Motor Winding Temp #2
BAS Current Limit Setpoint
Motor Winding Temp #3
Starter Input Power Consumption
AFD Average Input Current
Starter Power Demand
AFD Input Current L1
Starter Motor Power Factor
AFD Input Current L2
Motor Speed
AFD Input Current L3
Motor Frequency
AFD Input Frequency
Speed Command RPM
AFD Average Motor Voltage
Speed Command (CVHS)
AFD Calculated Input Voltage
Average Motor Current % RLA
AFD DC Bus Voltage
Electro-Mech. Phase Unbalance
AFD DC Bus Current
Ext Current Limit Setpt
AFD Output Power
Frequency Command
AFD Ground Current
Speed Signal
AFD Inverter Base Temp
Motor Coolant Temperature
AFD Rectifier Base Temp
MTC Switch
AFD Transistor Temp
Restart Inhibit Time (MP)
AFD Motor Current U % RLA
Starter Average Phase Voltage
AFD Motor Current V % RLA
Starter Motor Current L1 % RLA
AFD Motor Current W % RLA
Starter Motor Current L1
AFD Motor Current U
Starter Motor Current L2 % RLA
AFD Motor Current V
Starter Motor Current L2
AFD Motor Current W
Starter Motor Current L3 % RLA
AFD Motor Voltage UV
Starter Motor Current L3
AFD Motor Voltage VW
Starter Energy Consump. NonReset
AFD Motor Voltage WU
Starter Energy Consump. Resettable
AFD Average Input Voltage
Starter Energy Consump. Last Reset
AFD Inverter Module Temp U
Starter Input Voltage AB
AFD Inverter Module Temp V
Starter Input Voltage BC
AFD Inverter Module Temp W
Starter Input Voltage CA
AFD Total Demand Distortion
Motor Temperature
CTV-SVU01G-EN
71
Appendix A: Data for CenTraVac Simplex Chillers
Table 32.
Purge data
Average Daily Pumpout-7 Days
Carbon Tank Temp
Carbon Regen Cycles
Purge Liquid Temp
Chiller On-7 Days
Purge Rfgt Cprsr Suction Temp
Daily Pumpout-24 Hours
Time at Last Regeneration
Pumpout Chiller Off-7 Days
Time Until Next Purge Run
Pumpout Chiller On-7 Days
Purge Top Level Mode
Pumpout-Life
Data Graph Data Points
This subsection contains:
•
Data points used in the default data graphs, organized by graph
•
Data points available to include in custom data graphs, organized by component
Data Points Used in Default Data Graphs
Table 33.
Chiller overview 1
Graph data point
Axis
Active Chilled Water Setpoint
Left Y-axis
Active Hot Water Setpoint
Left Y-axis
Evaporator Leaving Evaporator Temperature
Left Y-axis
Evaporator Entering Water Temperature
Left Y-axis
Condenser Leaving Water Temperature
Left Y-axis
Condenser Entering Water Temperature
Left Y-axis
Calculated Chiller Capacity
Right Y-axis
Table 34.
Chiller overview 2
Graph data point
Axis
Average Motor Current % RLA
Left Y-axis
Motor Frequency
Left Y-axis
Oil Differential Pressure
Left Y-axis
Frequency Command
Left Y-axis
Lube Differential Pressure
(CVHS)
Left Y-axis
Speed Command
(CVHS)
Right Y-axis
Table 35.
Approach temperature
Graph data point
Axis
Evaporator Approach Temperature
Left Y-axis
Condenser Approach Temperature
Left Y-axis
Approximate Evaporator Water Flow
Right Y-axis
72
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
Table 35.
Approach temperature (continued)
Graph data point
Axis
Approximate Condenser Water Flow
Right Y-axis
Average Motor Current % RLA
Right Y-axis
Table 36.
Evaporator
Graph data point
Axis
Active Chilled Water Setpoint
Left Y-axis
Evaporator Leaving Water Temperature
Left Y-axis
Evaporator Entering Water Temperature
Left Y-axis
Evaporator Saturated Refrigerant Temperature
Left Y-axis
Approximate Evaporator Water Flow
Right Y-axis
Table 37.
Motor
Graph data point
Axis
Starter Motor Current L1 % RLA
Left Y-axis
Starter Motor Current L2 % RLA
Left Y-axis
Starter Motor Current L3 % RLA
Left Y-axis
Average Motor Current % RLA
Left Y-axis
Starter Input Voltage AB
Right Y-axis
Starter Input Voltage BC
Right Y-axis
Starter Input Voltage CA
Right Y-axis
AFD Motor Current U % RLA
Left Y-axis
AFD Motor Current V % RLA
Left Y-axis
AFD Motor Current W % RLA
Left Y-axis
AFD Motor Voltage UV
Right Y-axis
AFD Motor Voltage VW
Right Y-axis
AFD Motor Voltage WU
Right Y-axis
Table 38.
Motor temperature
Graph data point
Axis
Motor Winding Temperature 1
Left Y-axis
Motor Winding Temperature 2
Left Y-axis
Motor Winding Temperature 3
Left Y-axis
AFD Transistor Temperature
Left Y-axis
Table 39.
Condenser
Graph data point
Axis
Active Hot Water Setpoint
Left Y-axis
Condenser Leaving Water Temperature
Left Y-axis
Condenser Entering Water Temperature
Left Y-axis
CTV-SVU01G-EN
73
Appendix A: Data for CenTraVac Simplex Chillers
Table 39.
Condenser (continued)
Graph data point
Axis
Condenser Saturated Refrigerant Temperature
Left Y-axis
Approximate Condenser Water Flow
Right Y-axis
Table 40.
Compressor
Graph data point
Axis
Average Line Current
Left Y-axis
Active Current Limit Setpoint
Left Y-axis
AFD Frequency
Left Y-axis
IGV 1 Position
Left Y-axis
Chiller Control Signal
Left Y-axis
Compressor Refrigerant Discharge Temperature
Right Y-axis
Table 41.
Purge
Graph data point
Axis
Daily Pumpout—24 Hours
Left Y-axis
Pumpout Chiller On—7 Days
Left Y-axis
Pumpout Chiller Off—7 Days
Left Y-axis
Purge Average Daily Pumpout—7 Days
Right Y-axis
Purge Refrigerant Compressor Suction Temperature
Right Y-axis
Purge Liquid Temperature
Right Y-axis
Table 42.
Oil system
Graph data point
Axis
Oil Differential Pressure
Left Y-axis
Oil Tank Pressure
Left Y-axis
Oil Pump Discharge Pressure
Left Y-axis
Oil Tank Temperature
Right Y-axis
Outboard Bearing Temperature
Right Y-axis
Inboard Bearing Temperature
Right Y-axis
Table 43.
Lube system
Graph data point
Axis
Lube Differential Pressure
Left Y-axis
Lube Pump Discharge Pressure
Left Y-axis
Cond Rfgt Pressure
Left Y-axis
Lube Pump Suction Pressure
Left Y-axis
Lube Flow First Stage Bearing
Right Y-axis
Lube Flow Second Stage Bearing
Right Y-axis
74
CTV-SVU01G-EN
Appendix A: Data for CenTraVac Simplex Chillers
Data Points in Custom Data Graphs
Table 44.
Evaporator
Active Chilled Water Setpoint
Approx Evap Water Flow
Evaporator Leaving Water Temperature
Evap Differential Wtr Press
Evaporator Entering Water Temperature
Calculated Chiller Capacity
Evap Sat Rfgt Temp
Evap Approach Temp
Evap Rfgt Pressure
Active Ice Termination Setpoint
Table 45.
Compressor
Chiller Control Signal
Inboard Bearing Temp
Oil Tank Pressure
Outboard Bearing Temp
Oil Pump Discharge Pressure
Outboard Bearing Pad Temperature #1
Oil Differential Pressure
Outboard Bearing Pad Temperature #2
Lube Pump Suction Pressure
(CVHS)
Outboard Bearing Pad Temperature #3
Lube Pump Discharge Pressure
(CVHS)
IGV1 Position (%)
Lube Differential Pressure
(CVHS)
IGV2 Position (%)
Oil Tank Temperature
Compressor Refrigerant Discharge Temperature
Lube Flow First Stage Bearing
(CVHS)
Compressor Vibration
Lube Flow Second Stage Bearing
(CVHS)
Table 46.
Condenser
Active Hot Water Setpoint
Cond Approach Temp
Cond Leaving Water Temp
Approx Cond Water Flow
Cond Entering Water Temp
Cond Differential Wtr Press
Cond Sat Rfgt Temp
Second Condenser Lvg Wtr Temp
Outdoor Air Temp
Second Condenser Ent Wtr Temp
Refrigerant Monitor
Differential Refrigerant Pressure
Cond Rfgt Pressure
Head Pressure Control Status
Table 47.
Motor
Active Current Limit Setpoint
AFD Input Current L1
Average Motor Current %RLA
AFD Input Current L2
Motor Frequency
AFD Input Current L3
Speed Command
(CVHS)
AFD Input Frequency
Starter Motor Current L1 % RLA
AFD Average Motor Voltage
Starter Motor Current L2 % RLA
AFD DC Bus Voltage
Starter Motor Current L3 % RLA
AFD DC Bus Current
CTV-SVU01G-EN
75
Appendix A: Data for CenTraVac Simplex Chillers
Table 47.
Motor (continued)
Starter Motor Current L1
AFD Output Power
Starter Motor Current L2
AFD Ground Current
Starter Motor Current L3
AFD Inverter Base Temp
Starter Input Voltage AB
AFD Rectifier Base Temp
Starter Input Voltage BC
AFD Transistor Temp
Starter Input Voltage CA
AFD Motor Current U % RLA
Motor Winding Temp #1
AFD Motor Current V % RLA
Motor Winding Temp #2
AFD Motor Current W % RLA
Motor Winding Temp #3
AFD Motor Voltage UV
Motor Temperature
AFD Motor Voltage VW
Motor Coolant Temperature
AFD Motor Voltage WU
Starter Input Power Consumption
AFD Average Input Voltage
Starter Power Demand
AFD Inverter Module Temp U
Starter Motor Power Factor
AFD Inverter Module Temp V
Starter Average Phase Voltage
AFD Inverter Module Temp W
Frequency Command
AFD Total Demand Distortion
AFD Average Input Current
Table 48.
Purge
Daily Pumpout—24 Hours
Purge Rfgt Cprsr Suction Temp
Pumpout Chiller On—7 Days
Purge Liquid Temp
Pumpout Chiller Off—7 Days
Carbon Tank Temp
Purge Average Daily Pumpout—7 Days
76
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
The following lists contain all of the data available for viewing on a Tracer® AdaptiView™
display that is connected to a CenTraVac™ Duplex™ chiller.
Component Screen Data
Chiller configuration determines which of the following settings and status points appear on the
display. For more information, refer to “Component Screens,” p. 14.
Table 49.
Evaporator settings and status points
Active Chilled Water Setpoint (button links to the Active Chiller Water
Setpoint screen)
Evaporator Rfgt Pressure (Ckt1 and Ckt2)
Evaporator Pump Override (button links to Evaporator Pump Override
screen)
Evap Approach Temp (Ckt1 and Ckt2)
Evap Water Flow Status
Approx Evap Water Flow
Evap Leaving Water Temp
Evap Differential Wtr Press
Evap Entering Water Temp
Evap Entering Water Press
Calculated Chiller Capacity
Evap Leaving Water Press
Evaporator Saturated Rfgt Temp (Ckt1 and Ckt2)
Table 50.
Condenser settings and status points
Active Hot Water Setpoint (button links to the Active Hot Water
Setpoint screen)
Condenser Approach Temperature (Ckt1 and Ckt2)
Condenser Pump Override (button links to the Condenser Pump
Override screen)
Approx Cond Water Flow
Cond Water Flow Status
Cond Differential Wtr Press
Cond Entering Water Temp
Second Condenser Lvg Wtr Temp
Cond Leaving Water Temp
Second Condenser Ent Wtr Temp
Outdoor Air Temp
Cond Entering Water Press
Condenser Refrigerant Pressure (Ckt1 and Ckt2)
Cond Leaving Water Press
Table 51.
Compressor settings and status points
Compressor Running (Ckt1 and Ckt2)
Inboard Bearing Temperature (Ckt1 and Ckt2)
Chiller Control Signal
Outboard Bearing Temperature (Ckt1 and Ckt2)
Oil Pump Control (Ckt1 and Ckt2)
IGV 1 Percent Open (Ckt1 and Ckt2)
Average Motor Current %RLA (Ckt1 and Ckt2)
IGV 1 Position (Steps) (Ckt1 and Ckt2)
Compressor Starts (Ckt1 and Ckt2)
IGV 2 Percent Open (Ckt1 and Ckt2)
Oil Pump Status (Ckt1 and Ckt2)
IGV 2 Position (Steps) (Ckt1 and Ckt2)
Oil Differential Pressure (Ckt1 and Ckt2)
Compressor Rfgt Discharge Temp (Ckt1 and Ckt2)
Compressor Running Time (Ckt1 and Ckt2)
Outboard Bearing Pad Temperature #1 CktX (for CDHH)
Oil Pump Discharge Pressure (Ckt1 and Ckt2)
Outboard Bearing Pad Temperature #2 CktX (for CDHH)
Oil Tank Pressure (Ckt1 and Ckt2)
Outboard Bearing Pad Temperature #3 CktX (for CDHH)
Oil Tank Temperature (Ckt1 and Ckt2)
CTV-SVU01G-EN
77
Appendix B: Data for CenTraVac Duplex Chillers
Table 52.
Motor settings and status points
Active Current Limit Setpoint
Starter Input Voltage BC CktX
Average Motor Current % RLA CktX
Starter Input Voltage CA Ck
Motor Frequency CktX
Motor Winding Temperature 1 CktX
Frequency Command CktX
Motor Winding Temperature 2 CktX
Starter Motor Current L1 % RLA CktX
Motor Winding Temperature 3 CktX
Starter Motor Current L2 % RLA CktX
Motor Temperature CktX
Starter Motor Current L3 % RLA CktX
Motor Speed CktX
Starter Motor Current L1 CktX Starter
AFD Transistor Temperature CktX
Motor Current L2 CktXStarter
AFD Input Frequency
Motor Current L3 CktX
Starter Input Power Consumption CktX
AFD Input Current L1 CktX
Starter Power Demand CktX Starter Motor Power Factor CktX
AFD Input Current L2 CktXAFD
AFD Output Power CktX
Input Current L3 CktX
AFD Average Input Current CktX
AFD Output Voltage CktX
Starter Energy Consump. Resettable CktX
AFD DC Bus Voltage CktX
Starter Energy Consump. Non Reset CktX
AFD DC Bus Current CktX
Starter Energy Consump. Time of Last Reset CktX
Starter Input Voltage AB CktX
Table 53.
Purge settings and status points
Purge Top Level Mode (button links to Purge Operating Modes screen)
(Ckt1 and Ckt2)
Pumpout Chiller On—7 days (Ckt1 and Ckt2)
Purge Regen Cycle (button links to PUrge Regen Cycle) (Ckt1 and
Ckt2)
Pumpout Chiller Off—7 days (Ckt1 and Ckt2)
Purge Fault Indicator (button links to Alarms screen) (Ckt1 and Ckt2)
Time Until Next Purge Run (Ckt1 and Ckt2)
Daily Pumpout—24 Hours (Ckt1 and Ckt2)
Purge Rfgt Compressor Suction Temp (Ckt1 and Ckt2)
Average Daily Pumpout—7 Days (Ckt1 and Ckt2)
Purge Liquid Temperature (Ckt1 and Ckt2)
Daily Pumpout Limit (Ckt1 and Ckt2)
Pumpout—Life (Ckt1 and Ckt2)
Chiller On—7 Days (Ckt1 and Ckt2)
Purge Carbon Tank Temp (Ckt1 and Ckt2)
Reports
The following data can be viewed on the Reports screen. For more information, refer to
“Reports,” p. 23.
78
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
Log Sheet
Table 54.
Evaporator
Report item
Unit
Evaporator Entering Water Temperature
XXX.X °F/°C
Evaporator Leaving Water Temp
XXX.X °F/°C
Evaporator Water Flow Status
Flow/No Flow
Evaporator Sat Rfgt Temp (Ckt1 and Ckt2)
XXX.X °F/°C
Evaporator Rfgt Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Evaporator Approach Temp (Ckt1 and Ckt2)
XXX.X °F/°C
Table 55.
Condenser
Report item
Unit
Cond Entering Water Temp
Cond Entering Water Temp
Cond Leaving Water Temp
Cond Leaving Water Temp
Cond Water Flow Status
Cond Water Flow Status
Cond Sat Rfgt Temp (Ckt1 and Ckt2)
Cond Sat Rfgt Temp (Ckt1 and Ckt2)
Cond Rfgt Pressure (Ckt1 and Ckt2)
Cond Rfgt Pressure (Ckt1 and Ckt2)
Cond Approach Temp (Ckt1 and Ckt2)
Cond Approach Temp (Ckt1 and Ckt2)
Table 56.
Motor
Report item
Unit
Starter Current L1 %RLA (Ckt1 and Ckt2)
XXX.X %
Starter Current L2 %RLA (Ckt1 and Ckt2)
XXX.X %
Compressor Starts (Ckt1 and Ckt2)
XXXX Starts
Compressor Running Time (Ckt1 and Ckt2)
XX:XX Hr:Min
Oil Tank Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Oil Pump Discharge Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Oil Differential Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Oil Tank Temperature (Ckt1 and Ckt2)
XXX.X °F/°C
IGV 1 Percent Open (Ckt1 and Ckt2)
XXX.X %
IGV 1 Position (Ckt1 and Ckt2)
Steps
IGV 2 Percent Open (Ckt1 and Ckt2)
XXX.X %
IGV 2 Position (Ckt1 and Ckt2)
Steps
Starter Current L3 %RLA (Ckt1 and Ckt2)
XXX.X %
Starter Current L1 (Ckt1 and Ckt2)
XXXX A
Starter Current L2 (Ckt1 and Ckt2)
XXXX A
Starter Current L3 (Ckt1 and Ckt2)
XXXX A
Starter Voltage Phase AB (Ckt1 and Ckt2)
XXXXX.X V
Starter Voltage Phase BC (Ckt1 and Ckt2)
XXXXX.X V
Starter Voltage Phase CA (Ckt1 and Ckt2)
XXXXX.X V
CTV-SVU01G-EN
79
Appendix B: Data for CenTraVac Duplex Chillers
Table 56.
Motor (continued)
Report item
Unit
Starter Power Demand (Ckt1 and Ckt2)
XXXX kW
Starter Load Power Factor (Ckt1 and Ckt2)
XX.X
Motor Winding Temp 1 (Ckt1 and Ckt2)
XXX.X °F/°C
Motor Winding Temp 2 (Ckt1 and Ckt2)
XXX.X °F/°C
Motor Winding Temp 3 (Ckt1 and Ckt2)
XXX.X °F/°C
AFD Frequency (Ckt1 and Ckt2)
XX Hz
AFD Speed (Ckt1 and Ckt2)
XXXX RPM
AFD Transistor Temp (Ckt1 and Ckt2)
XXX.X °F/°C
Table 57.
Purge
Report item
Unit
Time Until Next Purge Run (Ckt1 and Ckt2)
XXX.X min
Daily Pumpout—24 Hours (Ckt1 and Ckt2)
XXX.X min
Average Daily Pumpout—7 Days (Ckt1 and Ckt2)
XXX.X min
Daily Pumpout Limit (Ckt1 and Ckt2)
XXX.X min
Chiller On—7 Days (Ckt1 and Ckt2)
XXX.X min
Pumpout Chiller On—7 Days (Ckt1 and Ckt2)
XXX.X min
Pumpout Chiller Off—7 Days (Ckt1 and Ckt2)
XXX.X min
Pumpout—Life (Ckt1 and Ckt2)
XXX.X min
Purge Rfgt Compressor Suction Temp (Ckt1 and Ckt2)
XXX.X °F/°C
Purge Liquid Temp (Ckt1 and Ckt2)
XXX.X °F/°C
Purge Carbon Tank Temp (Ckt1 and Ckt2)
XXX.X °F/°C
ASHRAE Chiller Log
N o t e : The ASHRAE Chiller Log contains those items recommended by ASHRAE Std 147 Standard
147-2002, Reducing Release of Halogenated Refrigerants from Refrigeration and AirConditioning Equipment and Systems.
Table 58.
ASHRAE Chiller Log data
Data name
Value
Current Date/Time
User-selected date/time format
Chiller Top Level Mode
Dependent on chiller type
Evap Entering Water Temp
XXX.X °F/C°
Evap Leaving Water Temp
XXX.X °F/C°
Evap Water Flow Status
Flow/No Flow
Evap Differential Wtr Press
XXX.X PSI/kPa
Approx Evap Water Flow
XXX.X gpm/lpm
Calculated Chiller Capacity
XXXX tons/kW
Refrigerant Type
R123
80
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
Table 58.
ASHRAE Chiller Log data (continued)
Data name
Value
Refrigerant Monitor
XXX.X ppm
Active Chilled Water Setpoint
XXX.X F°/C°
Active Current Limit Setpoint
XXX.X %
Cond Entering Water Temp
XXX.X °F/C°
Cond Leaving Water Temp
XXX.X °F/C°
Cond Water Flow Status
Flow/No Flow
Cond Differential Wtr Press
XXX.X PSI/kPa
Approx Cond Water Flow
XXXX gpm/lpm
Top Level Operating Mode (Ckt1 and Ckt2)
Dependent on chiller type
Evaporator Saturated Rfgt Temp (Ckt1 and Ckt2)
XXX.X °F/C°
Evaporator Refrigerant Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Evaporator Approach Temp (Ckt1 and Ckt2)
XXX.X °F/C°
Condenser Saturated Rfgt Temp (Ckt1 and Ckt2)
XXX.X °F/C°
Condenser Refrigerant Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Condenser Approach Temperature (Ckt1 and Ckt2)
XXX.X °F/C°
Compressor Starts (Ckt1 and Ckt2)
XXXX
Compressor Running Time (Ckt1 and Ckt2)
XX:XX Hr:Min
Compressor Refrigerant Discharge Temperature (Ckt1 and Ckt2)
XXX.X °F/C°
Oil Pump Discharge Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Oil Tank Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Oil Differential Pressure (Ckt1 and Ckt2)
XXX.X PSI/kPa
Oil Tank Temperature (Ckt1 and Ckt2)
XXX.X °F/C°
Inboard Bearing Temp (Ckt1 and Ckt2)
XXX.X °F/C°
Outboard Bearing Temp (Ckt1 and Ckt2)
XXX.X F°/C°
Daily Pumpout—24 Hrs (Ckt1 and Ckt2)
XXX.X Min
Daily Pumpout Limit (Ckt1 and Ckt2)
XXX.X Min
Pumpout—Life (Ckt1 and Ckt2)
XXXXXX.X Hours
Purge Top Level Mode (Ckt1 and Ckt2)
On/Auto/Adaptive/Stop
Purge Operating Mode (Ckt1 and Ckt2)
On/Auto/Adaptive/Stop
Starter Current L1 (Ckt1 and Ckt2)
XXXX A
Starter Current L2 (Ckt1 and Ckt2)
XXXX A
Starter Current L3 (Ckt1 and Ckt2)
XXXX A
Starter Voltage Phase AB (Ckt1 and Ckt2)
XXXX V
Starter Voltage Phase BC (Ckt1 and Ckt2)
XXXX V
Starter Voltage Phase CA (Ckt1 and Ckt2)
XXXX V
CTV-SVU01G-EN
81
Appendix B: Data for CenTraVac Duplex Chillers
Items Available to Include in Custom Reports
Table 59.
Chiller
Active Base Loading Setpoint
Version
Active Base Loading Setpoint Source
Chiller Heating or Cooling Mode
Application Part Number
Chiller Top Level Mode
Table 60.
Evaporator
Active Chilled Water Setpoint
Evaporator Saturated Refrigerant Temperature (Ckt1 and Ckt2)
Active Chilled Water Setpoint Source
Evaporator Water Flow Status
BAS Chilled Water Setpoint
Active Ice Termination Setpoint
Evaporator Approach Temperature (Ckt1 and Ckt2)
Active Ice Termination Setpoint Source
Evaporator Entering Water Temperature
Calculated Chiller Capacity
Evaporator Leaving Water Temperature
Approx Evap Water Flow
Evaporator Pump Override
Evap Differential Wtr Pressure
Evaporator Pump Override Time Remaining
External Chilled Water Setpoint
Evaporator Refrigerant Pressure (Ckt1 and Ckt2)
Front Panel Ice Building Command
Table 61.
Compressor
Chiller Control Signal
Oil Differential Pressure (Ckt1 and Ckt2)
Active Base Loading Setpoint
Oil Heater Command (Ckt1 and Ckt2)
Active Base Loading Setpoint Source
Oil Pump Control (Ckt1 and Ckt2)
Compressor Refrigerant Discharge Temperature (Ckt1 and Ckt2)
Oil Pump Command (Ckt1 and Ckt2)
Compressor Running Status (Ckt1 and Ckt2)
Oil Pump Discharge Pressure (Ckt1 and Ckt2)
Compressor Running Time (Ckt1 and Ckt2)
Oil Pump Override Time Remaining
Compressor Starts (Ckt1 and Ckt2)
Oil Tank Pressure (Ckt1 and Ckt2)
Inboard Bearing Temperature (Ckt1 and Ckt2)
Oil Tank Temperature (Ckt1 and Ckt2)
IGV1 Position (Ckt1 and Ckt2)
Oil Pump Override Time Remaining (Ckt1 and Ckt2)
IGV1 Percent Open (Ckt1 and Ckt2)
Outboard Bearing Temperature (Ckt1 and Ckt2)
IGV2 Position (Ckt1 and Ckt2)
Inboard Bearing Temperature (Ckt1 and Ckt2)
IGV2 Percent Open (Ckt1 and Ckt2)
Table 62.
Condenser
Condenser Approach Temperature (Ckt1 and Ckt2)
Condenser Pump Override
Condenser Entering Water Temperature (Ckt1 and Ckt2)
Active Hot Water Setpoint
Condenser Leaving Water Temperature (Ckt1 and Ckt2)
Active Hot Water Setpoint Source
Condenser Refrigerant Pressure (Ckt1 and Ckt2)
Approx Cond Water Flow
Condenser Saturated Refrigerant Temperature (Ckt1 and Ckt2)
Cond Differential Wtr Press
Condenser Water Flow Status
Outdoor Air Temperature
Condenser Pump Override Time Remaining
82
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
Table 63.
Motor
Active Current Limit Setpoint
Phase Unbalance (Ckt1 and Ckt2)
Active Current Limit Setpoint Source
Restart Inhibit Time (MP) (Ckt1 and Ckt2)
BAS Current Limit Setpoint
Starter Average Phase Voltage (Ckt1 and Ckt2)
External Current Limit Setpoint
Starter Current L1 %RLA (Ckt1 and Ckt2)
AFD DC Bus Voltage (Ckt1 and Ckt2)
Starter Current L1 (Ckt1 and Ckt2)
AFD Output Power (Ckt1 and Ckt2)
Starter Current L2 %RLA (Ckt1 and Ckt2)
AFD Transistor Temperature (Ckt1 and Ckt2)
Starter Current L2 (Ckt1 and Ckt2)
Starter Power Consumption (Ckt1 and Ckt2)
Starter Current L3 %RLA (Ckt1 and Ckt2)
Starter Load Power Factor (Ckt1 and Ckt2)
Starter Current L3 (Ckt1 and Ckt2)
Speed (Ckt1 and Ckt2)
Starter Energy Consumption Not Resettable (Ckt1 and Ckt2)
Frequency (Ckt1 and Ckt2)
Starter Energy Consumption Resettable (Ckt1 and Ckt2)
Generator Frequency Command (Ckt1 and Ckt2)
Starter Energy Consumption Last Reset (Ckt1 and Ckt2)
Generator Speed Signal (Ckt1 and Ckt2)
Starter Power Demand (Ckt1 and Ckt2)
Average Line Current %RLA (Ckt1 and Ckt2)
Starter Voltage Phase AB (Ckt1 and Ckt2)
Motor Winding Temperature 1 (Ckt1 and Ckt2)
Starter Voltage Phase BC (Ckt1 and Ckt2)
Motor Winding Temperature 2 (Ckt1 and Ckt2)
Starter Voltage Phase CA (Ckt1 and Ckt2)
Motor Winding Temperature 3 (Ckt1 and Ckt2)
Table 64.
Purge
Purge Top Level Mode (Ckt1 and Ckt2)
Pumpout—Life (Ckt1 and Ckt2)
Average Daily Pumpout—7 Days (Ckt1 and Ckt2)
Purge Carbon Tank Temp (Ckt1 and Ckt2)
Carbon Regen Cycles (Ckt1 and Ckt2)
Purge Liquid Temperature (Ckt1 and Ckt2)
Chiller On—7 Days (Ckt1 and Ckt2)
Purge Refrigerant Compressor Suction Temp (Ckt1 and Ckt2)
Daily Pumpout—24 Hours (Ckt1 and Ckt2)
Time at Last Regeneration (Ckt1 and Ckt2)
Pumpout Chiller Off—7 Days (Ckt1 and Ckt2)
Time Until Next Purge Run (Ckt1 and Ckt2)
Pumpout Chiller On—7 Days (Ckt1 and Ckt2)
Data Graph Data Points
This subsection contains:
•
Data points used in the default data graphs, organized by graph
•
Data points available to include in custom data graphs, organized by component
Data Points Used in Default Data Graphs
Table 65.
Chiller Overview 1
Graph data point
Axis
Active Chilled Water Setpoint
Left Y-axis
Active Hot Water Setpoint
Left Y-axis
Evaporator Leaving Evaporator Temperature
Left Y-axis
Evaporator Entering Water Temperature
Left Y-axis
CTV-SVU01G-EN
83
Appendix B: Data for CenTraVac Duplex Chillers
Table 65.
Chiller Overview 1 (continued)
Graph data point
Axis
Condenser Leaving Water Temperature
Left Y-axis
Condenser Entering Water Temperature
Left Y-axis
Calculated Chiller Capacity
Right Y-axis
Table 66.
Chiller Overview 2
Graph data point
Axis
Average Motor Current % RLA Ckt1 1st y-axis
Left Y-axis
Average Motor Current % RLA Ckt2 1st y-axis
Left Y-axis
Motor Frequency Ckt1 1st y-axis
Left Y-axis
Motor Frequency Ckt2 1st y-axis
Left Y-axis
Oil Differential Pressure Ckt1 1st y-axis
Left Y-axis
Oil Differential Pressure Ckt2 1st y-axis
Left Y-axis
Table 67.
Evaporator
Graph data point
Axis
Active Chilled Water Setpoint
Left Y-axis
Evaporator Leaving Water Temperature
Left Y-axis
Evaporator Entering Water Temperature
Left Y-axis
Evaporator Saturated Refrigerant Temperature (Ckt1 and Ckt2)
Left Y-axis
Approximate Evaporator Water Flow
Right Y-axis
Table 68.
Condenser
Graph data point
Axis
Active Hot Water Setpoint
Left Y-axis
Condenser Leaving Water Temperature
Left Y-axis
Condenser Entering Water Temperature
Left Y-axis
Condenser Saturated Refrigerant Temperature (Ckt1 and Ckt2)
Left Y-axis
Approximate Condenser Water Flow
Right Y-axis
Table 69.
Compressor
Graph data point
Axis
Average Motor Current % RLA (Ckt1 and Ckt2)
Left Y-axis
Active Current Limit Setpoint
Left Y-axis
AFD Frequency (Ckt1 and Ckt2)
Left Y-axis
IGV 1 Percent Open (Ckt1 and Ckt2)
Left Y-axis
Chiller Control Signal (Ckt1 and Ckt2)
Left Y-axis
Compressor Refrigerant Discharge Temperature (Ckt1 and Ckt2)
Right Y-axis
84
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
Table 70.
Oil System
Graph data point
Axis
Oil Differential Pressure (Ckt1 and Ckt2)
Left Y-axis
Oil Tank Pressure (Ckt1 and Ckt2)
Left Y-axis
Oil Pump Discharge Pressure (Ckt1 and Ckt2)
Left Y-axis
Oil Tank Temperature (Ckt1 and Ckt2)
Right Y-axis
Outboard Bearing Temperature (Ckt1 and Ckt2)
Right Y-axis
Inboard Bearing Temperature (Ckt1 and Ckt2)
Right Y-axis
Table 71.
Oil System
Graph data point
Axis
Oil Differential Pressure (Ckt1 and Ckt2)
Left Y-axis
Oil Tank Pressure (Ckt1 and Ckt2)
Left Y-axis
Oil Pump Discharge Pressure (Ckt1 and Ckt2)
Left Y-axis
Oil Tank Temperature (Ckt1 and Ckt2)
Right Y-axis
Outboard Bearing Temperature (Ckt1 and Ckt2)
Right Y-axis
Inboard Bearing Temperature (Ckt1 and Ckt2)
Right Y-axis
Table 72.
Motor
Graph data point
Axis
Average Motor Current %RLA CktX
Left Y-axis
Starter Motor Current L1 % RLA CktX
Left Y-axis
Starter Motor Current L2 % RLA (CktX)
Left Y-axis
Starter Motor Current L3 % RLA (CktX)
Left Y-axis
Starter Input Voltage Phase AB (CktX)
Right Y-axis
Starter Input Voltage Phase BC (CktX)
Right Y-axis
Starter Input Voltage Phase CA (CktX)
Right Y-axis
Table 73.
Motor Temperature
Graph data point
Axis
Motor Winding Temperature 1 (Ckt1 and Ckt2)
Left Y-axis
Motor Winding Temperature 2 (Ckt1 and Ckt2)
Left Y-axis
Motor Winding Temperature 3 (Ckt1 and Ckt2)
Left Y-axis
AFD Transistor Temperature (Ckt1 and Ckt2)
Left Y-axis
Table 74.
Purge
Graph data point
Axis
Daily Pumpout—24 Hours (Ckt1 and Ckt2)
Left Y-axis
Pumpout Chiller On—7 Days (Ckt1 and Ckt2)
Left Y-axis
Pumpout Chiller Off—7 Days (Ckt1 and Ckt2)
Left Y-axis
CTV-SVU01G-EN
85
Appendix B: Data for CenTraVac Duplex Chillers
Table 74.
Purge (continued)
Graph data point
Axis
Average Daily Pumpout—7 Days (Ckt1 and Ckt2)
Right Y-axis
Purge Refrigerant Compressor Suction Temperature (Ckt1 and Ckt2)
Right Y-axis
Purge Liquid Temperature (Ckt1 and Ckt2)
Right Y-axis
Table 75.
Approach Temperature
Graph data point
Axis
Evaporator Approach Temperature (Ckt1 and Ckt2)
Left Y-axis
Condenser Approach Temperature (Ckt1 and Ckt2)
Left Y-axis
Approximate Evaporator Water Flow (Ckt1 and Ckt2)
Right Y-axis
Approximate Condenser Water Flow (Ckt1 and Ckt2)
Right Y-axis
Average Line Current %RLA (Ckt1 and Ckt2)
Right Y-axis
Data Points in Custom Data Graphs
Table 76.
Evaporator
Active Chilled Water Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
Approx Evap Water Flow
Evap Differential Wtr Press
Calculated Chiller Capacity
Active Ice Termination Setpoint
Evaporator Saturated Rfgt Temp Ckt1
Evaporator Refrigerant Pressure Ckt1
Evaporator Approach Temperature Ckt1
Evaporator Saturated Rfgt Temp Ckt2
Evaporator Refrigerant Pressure Ckt2
Evaporator Approach Temperature Ckt2
Evaporator Entering Water Pressure
Evaporator Leaving Water Pressure
Table 77.
Condenser
Active Hot Water Setpoint
Condenser Leaving Water Temperature
Condenser Entering Water Temperature
Outdoor Air Temperature
Refrigerant Monitor
Approx Cond Water Flow
86
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
Table 77.
Condenser (continued)
Cond Differential Wtr Press
Head Pressure Control Status
Condenser Saturated Rfgt Temp Ckt1
Condenser Refrigerant Pressure Ckt1
Condenser Approach Temperature Ckt1
Differential Refrigerant Pressure Ckt1
Condenser Saturated Rfgt Temp Ckt2
Condenser Refrigerant Pressure Ckt2
Condenser Approach Temperature Ckt2
Differential Refrigerant Pressure Ckt2
Condenser Entering Water Pressure
Condenser Leaving Water Pressure
Table 78.
Compressor
Chiller Control Signal
Oil Tank Pressure Ckt1
Oil Pump Discharge Pressure Ckt1
Oil Differential Pressure Ckt1
Oil Tank Temperature Ckt1
Inboard Bearing Temperature Ckt1
Outboard Bearing Temperature Ckt1
Outboard Bearing Pad Temperature #1 Ckt1
*Added for CDHH
Outboard Bearing Pad Temperature #2 Ckt1
*Added for CDHH
Outboard Bearing Pad Temperature #3 Ckt1
*Added for CDHH
IGV 1 Percent Open Ckt1
IGV 1 Position Ckt1
IGV 2 Percent Open Ckt1
IGV 2 Position Ckt1
Compressor Rfgt Discharge Temp Ckt1
Oil Tank Pressure Ckt2
Oil Pump Discharge Pressure Ckt2
Oil Differential Pressure Ckt2
Oil Tank Temperature Ckt2
Inboard Bearing Temperature Ckt2
Outboard Bearing Temperature Ckt2
Outboard Bearing Pad Temperature #1 Ckt2
*Added for CDHH
Outboard Bearing Pad Temperature #2 Ckt2
*Added for CDHH
CTV-SVU01G-EN
87
Appendix B: Data for CenTraVac Duplex Chillers
Table 78.
Compressor (continued)
Outboard Bearing Pad Temperature #3 Ckt2
*Added for CDHH
IGV 1 Percent Open Ckt2
IGV 1 Position Ckt2
IGV 2 Percent Open Ckt2
IGV 2 Position Ckt2
Compressor Rfgt Discharge Temp Ckt2
Table 79.
Motor
Active Current Limit Setpoint
Motor Frequency Ckt1
Frequency Command Ckt1
Average Motor Current % RLA Ckt1
Starter Motor Current L1 % RLA Ckt1
Starter Motor Current L2 % RLA Ckt1
Starter Motor Current L3 % RLA Ckt1
Starter Motor Current L1 Ckt1
Starter Motor Current L2 Ckt1
Starter Motor Current L3 Ckt1
Starter Average Phase Voltage Ckt1
Starter Input Voltage AB Ckt1
Starter Input Voltage BC Ckt1
Starter Input Voltage CA Ckt1
Motor Winding Temperature 1 Ckt1
Motor Winding Temperature 2 Ckt1
Motor Winding Temperature 3 Ckt1
Motor Temperature Ckt1
Starter Input Power Consumption Ckt1
Starter Power Demand Ckt1
Starter Motor Power Factor Ckt1
AFD Average Input Current Ckt1
AFD Input Current L1 Ckt1
AFD Input Current L2 Ckt1
AFD Input Current L3 Ckt1
AFD Input Frequency Ckt1
AFD Output Voltage Ckt1
AFD DC Bus Voltage Ckt1
AFD DC Bus Current Ckt1
(Note: Added per CR 51244, 5/2/14)
88
CTV-SVU01G-EN
Appendix B: Data for CenTraVac Duplex Chillers
Table 79.
Motor (continued)
AFD Output Power Ckt1
AFD Ground Current Ckt1
AFD Inverter Base Temp Ckt1
AFD Rectifier Base Temp Ckt1
AFD Transistor Temperature Ckt1
Motor Frequency Ckt2
Frequency Command Ckt2
Average Motor Current % RLA Ckt2
Starter Motor Current L1 % RLA Ckt2
Starter Motor Current L2 % RLA Ckt2
Starter Motor Current L3 % RLA Ckt2
Starter Motor Current L1 Ckt2
Starter Motor Current L2 Ckt2
Starter Motor Current L3 Ckt2
Starter Average Phase Voltage Ckt2
Starter Input Voltage AB Ckt2
Starter Input Voltage BC Ckt2
Starter Input Voltage CA Ckt2
Motor Winding Temperature 1 Ckt2
Motor Winding Temperature 2 Ckt2
Motor Winding Temperature 3 Ckt2
Motor Temperature Ckt2
Starter Input Power Consumption Ckt2
Starter Power Demand Ckt2
Starter Motor Power Factor Ckt2
AFD Average Input Current Ckt2
AFD Input Current L1 Ckt2
AFD Input Current L2 Ckt2
AFD Input Current L3 Ckt2
AFD Input Frequency Ckt2
AFD Output Voltage Ckt2
AFD DC Bus Voltage Ckt2
AFD DC Bus Current Ckt1
(Note: Added per CR 51244, 5/2/14)
AFD Output Power Ckt2
AFD Ground Current Ckt2
AFD Inverter Base Temp Ckt2
CTV-SVU01G-EN
89
Appendix B: Data for CenTraVac Duplex Chillers
Table 79.
Motor (continued)
AFD Rectifier Base Temp Ckt2
AFD Transistor Temperature Ckt2
Table 80.
Purge
Daily Pumpout-24 hours Ckt1
Pumpout Chiller On 7 Days Ckt1
Pumpout Chiller Off 7 Days Ckt1
Average Daily Pumpout 7 days Ckt1
Purge Rfgt Compressor Suction Temp Ckt1
Purge Liquid Temperature Ckt1
Purge Carbon Tank Temp Ckt1
Daily Pumpout-24 hours Ckt2
Pumpout Chiller On 7 Days Ckt2
Pumpout Chiller Off 7 Days Ckt2
Average Daily Pumpout 7 days Ckt2
Purge Rfgt Compressor Suction Temp Ckt2
Purge Liquid Temperature Ckt2
Purge Carbon Tank Temp Ckt2
90
CTV-SVU01G-EN
Notes
CTV-SVU01G-EN
91
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy
efficient indoor environments for commercial and residential applications. For more information,
please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.
CTV-SVU01G-EN 21 Mar 2020
Supersedes CTV-SVU01F-EN (Apr 2017)
©2020 Trane

advertisement

Related manuals

Download PDF

advertisement