M-system MXS is a self-synch transmitter that can be used for a variety of applications. It has a wide input range of -180.0 to 360.0 degrees, and an output range of -1 to +1V, -10 to +10V, or 0 to 20mA. The MXS also has a number of features that make it easy to use, including a loop test output, a 0° (%) input fine adjustment, and a power-saving mode.
Here are some of the possible use cases for the MXS:
- Position control: The MXS can be used to control the position of a motor or other device.
- Speed control: The MXS can be used to control the speed of a motor or other device.
- Flow control: The MXS can be used to control the flow of a liquid or gas.
Advertisement
Advertisement
INSTRUCTION MANUAL
SELF-SYNCH TRANSMITTER
(front configurable)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket) .............................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
85 – 132V AC rating: 85 – 132V, 47 – 66 Hz, approx. 6VA
170 – 264V AC rating: 170 – 264V, 47 – 66 Hz, approx. 6VA
■ GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
MODEL
MXS
COMPONENT IDENTIFICATION
Connection Diagram
Specifications
Base Socket
Body
Input Setting
Instructions
INSTALLATION
Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the DIN rail adaptor utilizing a minus screwdriver and pull.
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■ WALL MOUNTING
Refer to “EXTERNAL DI-
MENSIONS.”
Shape and size of the base socket are slightly different with various socket types.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 1 / 7
MXS
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.
■ EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
20 (.79)
DIN RAIL
35mm wide
6 5
7.8 (.31)
4 3
50 (1.97) 103 (4.06)
123 (4.84)
2 – 4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8 – M3.5
SCREW
7 8 1 2
40 (1.57)
50 (1.97) [3.3 (.13)]
• When mounting, no extra space is needed between units.
■ CONNECTION DIAGRAM
*
S1
SELF-
SYNCH
R2
POWER
S2
R1
**
S3
U
V
3
4
5
7
8
1
2
+
–
OUTPUT
* The output increases when the self-synch rotates clockwise
For changing the operation to counterclockwise, reverse the
connection of S2 and S3.
** Be sure that the polarity of the power input to the signal conditioner
matches to the self-synch input polarity. When the connetion is
reversed, the signal conditioner output will be shifted by 180°.
FRONT PANEL CONFIGURATION & PROGRAMMING
■ PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.
1: Data indication only.
2: All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value you need on DATA display.
5) Repeat above 3 and 4. (Entered data is stored 1 sec. after the operation has been complete.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input. You can now check data setting by choosing ITEM No.
Note: DO NOT press UP and DOWN keys simultaneously.
Polarity LED
Programming
Error LED
DATA
ITEM
PL1
PL2
ITEM
PL3
PL4
DATA
DATA Display
ITEM No. Display
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 2 / 7
MXS
ITEM
P
MDF.
CODE
N/A
DATA
-180.0 – 360.0
CONTENTS
Input display in angle ---
DEFAULT
01
02
03
04
05
06
07
08
09
10/L
11
12
13
14
23
24
:
83
84
85
86
87
15
16
17
18
17
18
17
18
19
20
21
22
N/A
2
2
2
2
2
N/A
N/A
2
2
2
2
2
2
3
N/A
2
2
:
2
2
2
2
2
2
2
2
2
2
N/A
2
2
2
1, 2, 3
0 – 99
0, 1
0, 1
Modification code 1: Data indication only.
2: All parameters are modifiable.
3: Only ITEM 19 is modifiable.
Status indication (“0” is normally indicated.)
0° (%) input setting by actual position input * 1
100% input setting by actual position input * 1
(canceled by ITEM 06 setting)
0° (%) input angle adjustment (fine adj. of the value set in ITEM 03) * 2
100% input angle adjustment (canceled by ITEM 04 setting)
-180.0 – 180.0
0.0 – 360.0
0, 1
0, 1, 2
Rotating direction * 3 0: CW (clockwise) * 2
1: CCW (counterclockwise)
Output range code 0: V1 (-1 – +1V)
1: V2 (-10 – +10V)
2: Z1 (0 – 20mA)
-15.0 – 115.0
Input indicated in % (of the range set in ITEM 03/04/05/06)
-15.0 – 115.0
Output indicated in % with ITEM 01 DATA 1 (of the range set in ITEM 17/18)
Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
(Use DATA UP/DOWN key to set the output signal.)
-99.99 – 99.99
-99.99 – 99.99
0, 1, 2, 3, 4
Output zero adjustment (%) (fine adj. of the value set in ITEM 17)
Output span adjustment (%) (fine adj. of the value set in ITEM 18)
Moving average (sampling cycle: 150 msec.)
0: No 1: 4 samples 2: 8 samples 3: 16 samples 4: 32 samples
0, 1 – 60
-15.0 – 0.0
100.0 – 115.0
-1.00 – 1.00
-1.00 – 1.00
-10.0 – 10.0
-10.0 – 10.0
0.0 – 20.0
0.0 – 20.0
---
0, 1
-15.0 – 115.0
-15.0 – 115.0
Power-saving mode 0: Continuous display
1 – 60: Time before display turned off (minutes)
Overrange output below 0%
Overrange output exceeding 100%
Output code V1 0% output voltage (V) * 4
100% output voltage (V) * 4
Output code V2
Output code Z1
---
Linearization table
Point 1 input setting (%)
Point 1 output setting (%)
0% output voltage (V) * 4
100% output voltage (V) * 4
0% output current (mA) * 4
100% output current (mA) * 4
0: Disable 1: Enable * 5
-15.0 – 115.0
-15.0 – 115.0
:
-15.0 – 115.0
-15.0 – 115.0
0, 1
0, 1
---
:
Point 2 input setting (%)
Point 2 output setting (%)
Point 32 input setting (%)
Point 32 output setting (%)
Inverted output
Reset all settings * 6
ROM version
0: Non-inverted 1: Inverted
1
---
0
0
0.0
270.0
0
V1: 0
V2: 1
Z1: 2
---
---
0.00
0.00
0
10
0
0
---
:
0.0
0.0
0.0
0.0
---
0
0.0
0.0
-15.0
115.0
-1.00
1.00
-10.0
10.0
4.0
20.0
*1. Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the setting is complete.
*2. Relative to absolute 0° for the device which is determined with the 0° (%) input setting (ITEM 03).
*3. Rotating direction (ITEM 07) must be determined before setting the 0° (%) input setting (ITEM 03).
*4. ITEM 17 < ITEM 18.
*5. Linearization is disabled with the loop test output.
*6. Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the initialization is complete.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 3 / 7
MXS
■ SELECTING INPUT ANGLE RANGE
START
Go to the PROGRAM mode
• Press ITEM or key until the display shows ITEM 01
• Press DATA or key until the display shows DATA 2
Set the current position to 0° (%)
0 ° (%) Input Angle (Position) Setting * 1
• Fix the self-synch motor to the desired 0° position
• Press ITEM or key until the display shows ITEM 03
• Press DATA key to show DATA 1 and double-click DATA key
(The display returns to DATA 0 when the setting is complete)
Span angle value is known?
NO
YES
Set 100% angle
100% Input Angle Setting
[e.g.] 270.0
• Press ITEM or key until the display
shows ITEM 06
• Press DATA or key until the DATA
display shows 270.0 (0.1° increments)
Set the current position to 100%
100% Input Position Setting
• Fix the self-synch motor to the desired 100% position
• Press ITEM or key until the display shows ITEM 04
• Press DATA key to show DATA 1 and double-click DATA key
(The display returns to DATA 0 when the setting is complete)
(ITEM 06 shows the span angle)
Go to the MONITOR mode
• Press ITEM or key until the display shows ITEM 01
• Press DATA or key until the display shows DATA 1
COMPLETE
* The Rotating Angle (ITEM 07) must be determined before the 0° (%) Input Angle (Position) Setting (ITEM 03).
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 4 / 7
■ 0° (%) INPUT FINE ADJUSTMENT
ITEM 05 shows deviation in angle between the MXS’s absolute 0° and 0° (%) Input Angle setting with ITEM 03.
Since the MXS’s absolute 0° cannot be changed, fine adjustment of the 0° (%) setting with ITEM 03 is performed by adding/subtracting the deviation with ITEM 05.
If ITEM 04 or 06 (100% input angle) is already set, the
100% angle is also affected by this adjustment.
[Example] Shifting (adjusting) +10.0° from ITEM 03 setting
START
Go to the PROGRAM mode
Shift 0° (%) input
0° (%) Input Fine Adjustment
• Press ITEM or key until the display
shows ITEM 05
• Press DATA or key until the DATA
display shows +10.0
(Deviation from the absolute 0)
Go to the MONITOR mode
MXS
■ LOOP TEST OUTPUT
The loop test output is enabled when ITEM L (10) is selected in the PROGRAM mode.
[Example] Loop test output 90.0%
START
Go to the PROGRAM mode
Set Loop Test Output
Loop Test Output
• Press ITEM or key until the display
shows ITEM 10
• Press DATA or key until the DATA
display shows 90.0
Confirm the Output Signal
• Check the output across the terminals
1 – 2
Cancel Loop Test Output
Go to the MONITOR mode
COMPLETE COMPLETE
■ SELECTING OUTPUT RANGE
[Example] Output range -10.0 to 0.0V
START
Go to the PROGRAM mode
Set 0% output
0% Output
• Press ITEM or key until the display
shows ITEM 17
• Press DATA or key until the DATA
display shows -10.0
(PL1 turns on with minus (–) sign indicated)
Set 100% output
100% Output
• Press ITEM or key until the display
shows ITEM 18
• Press DATA or key until the DATA
display shows 0.0
Go to the MONITOR mode
COMPLETE
Selected range is available after the power supply is reset.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 5 / 7
MXS
■ LINEARIZATION TABLE
Max. 32 calibration points defined by sets of input and output values can be programmed. Use only necessary number of points, arranged in order from the smallest input value.
+100% Y05
Y04
Y03
Y02
-15% X01
-5%
0
Y01
X02 X03
INPUT
X04 X05 +115%
START
Go to the PROGRAM mode
Need Linearization?
NO
YES
Enable Linearization Table
• Press ITEM or key until the display
shows ITEM 20
• Press DATA or key until the display
shows DATA 1
Disable Linearization Table
• Press ITEM or key until the display
shows ITEM 20.
• Press DATA or key until the display
shows DATA 0.
Create Linearization Table
• Set the 1st calibration point (input & output) to ITEM 21/22
• Set the 2nd calibration point (input & output) to ITEM 23/24
[e.g.] Set the 2nd input point to 50.0%, output point to 20.0%
• Press ITEM or key until the display shows ITEM 23
• Press DATA or key until the DATA display shows 50.0
• Press ITEM or key until the display shows ITEM 24
• Press DATA or key until the DATA display shows 20.0
Go to the MONITOR mode
COMPLETE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 6 / 7
■ RESET ALL SETTINGS
START
Go to the RESET mode
• Press ITEM or key until the display shows ITEM 01
• Press DATA or key until the display shows DATA 3
MXS
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Input signal and power input voltage: Check wiring across MXS and self-synch as follows; terminal 3 – S1, terminal 4 – S2, terminal 5 – S3, terminal 7 – R1, and terminal 8 – R2.
Be sure that the connection for R1 and R2 of the selfsynch. When the connection is reversed, the signal conditioner output will be shifted by 180°.
3) Output: Check that the load resistance meets the described specifications.
Reset All Settings
• Press ITEM or key until the display shows ITEM 86
• Press DATA key to show DATA 1 and double-click DATA key
(The display returns to DATA 0 when the setting is complete)
Go to the MONITOR mode
COMPLETE
■ PROGRAMMING ERROR LED, PL2
When the PL2 is turned on, identify the cause or error with
ITEM 02 (Status Indication)
REF. ERROR
0 Normal status
17 Output range setting: 0% Setting > 100% Setting
See ITEM 17 / 18.
99 Memory error: Initialize all the settings of the unit by operating ITEM 86 and program the unit again.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of tolerance, recalibrate the unit as explained earlier (ITEM
11 and 12).
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for protection against induced lightning surges. Please contact
M-System to choose appropriate models.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1739 Rev.4 P. 7 / 7