ProSoft Technology MVI56-EGD ProductsGE Ethernet Global Data Network Interface Module for ControlLogix User Manual
Add to my manuals112 Pages
advertisement
MVI56-EGD
ControlLogix ® Platform
GE Ethernet Global Data
Communication Module
USER MANUAL
March 3, 2021
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about our products, documentation, or support, please write or call us.
How to Contact Us
ProSoft Technology, Inc.
+1 (661) 716-5100
+1 (661) 716-5101 (Fax) www.prosoft-technology.com [email protected]
Copyright © 2021 ProSoft Technology, Inc. All rights reserved.
MVI56-EGD User Manual
March 3, 2021
ProSoft Technology ® , ProLinx ® , inRAx ® , ProTalk ® , and RadioLinx ® are Registered Trademarks of ProSoft
Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify products and services of, their respective owners.
ProSoft Technology
®
Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments. User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided at: www.prosoft-technology.com
For professional users in the European Union
If you wish to discard electrical and electronic equipment (EEE), please contact your dealer or supplier for further information.
Prop 65 Warning – Cancer and Reproductive Harm – www.P65Warnings.ca.gov
Important Installation Instructions
Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article
501-4 (b) of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-
1J2 of the Canadian Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction. The following warnings must be heeded:
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIV. 2;
WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
THIS DEVICE SHALL BE POWERED BY CLASS 2 OUTPUTS ONLY.
MVI (Multi Vendor Interface) Modules
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DÉCONNECTER L'ÉQUIPEMENT, COUPER
LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX.
Warnings
North America Warnings
Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article
501-4 (b) of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-
1J2 of the Canadian Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction. The following warnings must be heeded:
A Warning - Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
B Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or rewiring modules.
C Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Avertissement - Risque d'explosion - Avant de déconnecter l'équipement, couper le courant ou s'assurer que l'emplacement est désigné non dangereux.
D Suitable for use in Class I, Division 2 Groups A, B, C and D Hazardous Locations or Non-Hazardous
Locations.
ATEX Warnings and Conditions of Safe Usage
Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction.
A Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.
B Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
C These products are intended to be mounted in an IP54 enclosure. The devices shall provide external means to prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used only with ATEX certified backplanes.
D DO NOT OPEN WHEN ENERGIZED.
Battery Life Advisory
The MVI46, MVI56, MVI56E, MVI69, and MVI71 modules use a rechargeable Lithium Vanadium Pentoxide battery to backup the real-time clock and CMOS. The battery should last for the life of the module. The module must be powered for approximately twenty hours before the battery becomes fully charged. After it is fully charged, the battery provides backup power for the CMOS setup and the real-time clock for approximately 21 days. When the battery is fully discharged, the module will revert to the default BIOS and clock settings.
Note: The battery is not user replaceable.
Agency Approvals and Certifications
Please visit our website: www.prosoft-technology.com
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Contents
User Manual
Contents
Your Feedback Please ....................................................................................................................... 2
How to Contact Us .............................................................................................................................. 2
ProSoft Technology ® Product Documentation ................................................................................... 2
Important Installation Instructions ....................................................................................................... 3
MVI (Multi Vendor Interface) Modules ................................................................................................ 3
Warnings ............................................................................................................................................ 3
Battery Life Advisory ........................................................................................................................... 4
Guide to the MVI56-EGD User Manual 9
1 Start Here
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.7.1
1.8
1.9
1.7.2
1.7.3
1.10
1.10.1
11
System Requirements ............................................................................................ 12
Package Contents .................................................................................................. 13
Installing ProSoft Configuration Builder Software................................................... 13
Setting Jumpers ...................................................................................................... 14
Installing the Module in the Rack ............................................................................ 15
Connecting Your PC to the ControlLogix Processor .............................................. 16
Opening the Sample Ladder Logic ......................................................................... 17
Determining the Firmware Version of Your Processor ........................................... 17
Selecting the Slot Number for the Module .............................................................. 19
Configuring the RSLinx Driver for the PC COM Port .............................................. 20
Downloading the Sample Program to the Processor.............................................. 22
Connecting your PC to the Module ......................................................................... 23
Using the RSLogix 5000 v16 Add-On Instruction ................................................... 24
Creating a New RSLogix 5000 Project ................................................................... 24
2 Configuring the MVI56-EGD Module
2.1
2.1.1
2.2
2.1.2
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.2.6
2.3
2.2.7
2.3.1
2.3.2
2.3.3
2.3.4
2.4
2.4.1
2.4.2
34
Using ProSoft Configuration Builder ....................................................................... 35
Setting Up the Project ............................................................................................. 35
Renaming PCB Objects .......................................................................................... 37
[Module] .................................................................................................................. 39
Module Name.......................................................................................................... 39
Module Type ........................................................................................................... 39
Read Register Start ................................................................................................ 39
Read Register Count .............................................................................................. 39
Write Register Start ................................................................................................ 39
Write Register Count .............................................................................................. 39
Failure Flag Count .................................................................................................. 39
[SNTP Client] .......................................................................................................... 40
NTP Server IP Address .......................................................................................... 41
Time Zone ............................................................................................................... 41
Use Daylight Savings Time ..................................................................................... 41
Database Register .................................................................................................. 41
[EGD Exchanges] ................................................................................................... 42
Exch Type ............................................................................................................... 42
Cast Type ................................................................................................................ 43
ProSoft Technology, Inc. Page 5 of 112
Contents
User Manual
2.4.3
2.4.4
2.4.5
2.4.6
2.4.7
2.4.8
2.5
2.6
2.4.9
2.4.10
2.7
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
DB Reg ................................................................................................................... 43
Reg Count ............................................................................................................... 43
Swap Code ............................................................................................................. 44
P/C Time ................................................................................................................. 44
IP Address .............................................................................................................. 45
Exch ID ................................................................................................................... 45
CS Major, CS Minor ................................................................................................ 46
EGD Exchange Command List Example ................................................................ 47
[EGD Multicast Group List] ..................................................................................... 48
Ethernet Configuration ............................................................................................ 49
Downloading the Project to the Module Using a Serial COM Port ......................... 50
3 Ladder Logic
3.1
3.2
3.2.1
3.2.2
3.2.3
3.3
3.2.4
51
Controller Tags ....................................................................................................... 51
Module Status Data and Variables (ModuleDef) .................................................... 53
Backplane Object .................................................................................................... 53
User Data Objects (MNETDATA) ........................................................................... 54
Status Object (InStat) ............................................................................................. 54
Consumer/Producer Status .................................................................................... 56
Adding the Module to an Existing Project ............................................................... 57
4 Diagnostics and Troubleshooting
4.1
4.1.1
4.1.2
4.1.3
4.2
4.2.1
4.2.2
4.2.3
4.2.4
4.2.5
4.2.6
4.3
4.2.7
4.2.8
61
LED Status Indicators ............................................................................................. 62
Ethernet LED Indicators .......................................................................................... 62
Clearing a Fault Condition ...................................................................................... 63
Troubleshooting ...................................................................................................... 63
Using ProSoft Configuration Builder (PCB) for Diagnostics ................................... 64
Using the Diagnostic Window in ProSoft Configuration Builder ............................. 64
Navigation ............................................................................................................... 66
Main Menu .............................................................................................................. 67
Database View Menu .............................................................................................. 70
Network Menu ......................................................................................................... 72
EGD Menu .............................................................................................................. 73
Producer/Consumer List Menu ............................................................................... 75
Producer/Consumer Status Menu .......................................................................... 76
Reading Status Data from the Module ................................................................... 76
5 Reference
5.1
5.2
5.1.1
5.1.2
5.1.3
5.1.4
5.2.1
Page 6 of 112
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
77
Product Specifications ............................................................................................ 77
General Specifications ............................................................................................ 77
Hardware Specifications ......................................................................................... 78
Functional Specifications ........................................................................................ 79
SNTP Support ......................................................................................................... 80
Functional Overview ............................................................................................... 81
Ethernet Global Data Compatible Devices ............................................................. 81
EGD Command Server ........................................................................................... 82
EGD Data Producer ................................................................................................ 99
EGD Data Consumer ............................................................................................ 100
General Concepts ................................................................................................. 101
Normal Data Transfer ........................................................................................... 103
ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5.3
5.2.7
Contents
User Manual
Special Function Blocks ........................................................................................ 105
Exchange Configuration Form .............................................................................. 108
6 Support, Service & Warranty
6.1
6.2
109
Contacting Technical Support ............................................................................... 109
Warranty Information ............................................................................................ 109
111 Index
ProSoft Technology, Inc. Page 7 of 112
Contents
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Page 8 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Guide to the MVI56-EGD User Manual
Function
Introduction
(Must Do)
Diagnostic and
Troubleshooting
Start Here
User Manual
Section to Read Details
Start Here (page 11) This section introduces the customer to the
module. Included are: package contents, system requirements, hardware installation, and basic configuration.
Diagnostics and
Troubleshooting
This section describes Diagnostic and
Troubleshooting procedures.
Reference
Product Specifications
Support, Service, and
Warranty
Index
Product
Specifications (page
These sections contain general references associated with this product and its
Specifications..
Support, Service and Warranty (page
Index
This section contains Support, Service and
Warranty information.
Index of chapters.
ProSoft Technology, Inc.
March 3, 2021
Page 9 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Page 10 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Start Here
User Manual
1 Start Here
In This Chapter
System Requirements ........................................................................... 12
Installing ProSoft Configuration Builder Software .................................. 13
Installing the Module in the Rack ........................................................... 15
Connecting Your PC to the ControlLogix Processor .............................. 16
Opening the Sample Ladder Logic ........................................................ 17
Downloading the Sample Program to the Processor ............................. 22
Connecting your PC to the Module ........................................................ 23
Using the RSLogix 5000 v16 Add-On Instruction .................................. 24
To get the most benefit from this User Manual, you should have the following skills:
Rockwell Automation ® RSLogix™ software: launch the program, configure ladder logic, and transfer the ladder logic to the processor
Microsoft Windows: install and launch programs, execute menu commands, navigate dialog boxes, and enter data
Hardware installation and wiring: install the module, and safely connect GE
Ethernet Global Data and ControlLogix devices to a power source and to the MVI56-
EGD module’s application port(s)
ProSoft Technology, Inc. Page 11 of 112
Start Here
User Manual
1.1 System Requirements
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The MVI56-EGD module requires the following minimum hardware and software components:
Rockwell Automation ControlLogix™ processor, with compatible power supply and one free slot in the rack, for the MVI56-EGD module. The module requires 800 mA of available power.
Rockwell Automation RSLogix 5000 programming software version 2.51 or higher
Rockwell Automation RSLinx communication software
Pentium ® II 450 MHz minimum. Pentium III 733 MHz (or better) recommended
Supported operating systems: o Microsoft Windows 10 o Microsoft Windows 7 Professional (32-or 64-bit) o Microsoft Windows XP Professional with Service Pack 1 or 2 o Microsoft Windows Vista o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3 o Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
100 Mbytes of free hard disk space (or more based on application requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color 1024
768 recommended)
ProSoft Configuration Builder, HyperTerminal or other terminal emulator program.
Note: You can install the module in a local or remote rack. For remote rack installation, the module requires
EtherNet/IP or ControlNet communication with the processor.
Page 12 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.2 Package Contents
Start Here
User Manual
The following components are included with your MVI56-EGD module, and are all required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are present.
Qty. Part Name
1
1
1
MVI56-EGD Module
Cable
Cable
Part Number
MVI56-EGD
Part Description
GE Ethernet Global Data Communication
Module
Cable #15 - RS232
Null Modem
Cable #14 - RJ45 to DB9 Male
Adapter
For RS232 between a Personal Computer
(PC) and the CFG port of the module
For connecting the module’s port to Cable
#15 for RS-232 connections
If any of these components are missing, please contact ProSoft Technology Support for replacement parts.
1.3 Installing ProSoft Configuration Builder Software
You must install the ProSoft Configuration Builder (PCB) software to configure the module. You can always get the newest version of ProSoft Configuration Builder from the ProSoft Technology website.
To install ProSoft Configuration Builder from the ProSoft Technology website
1 Open your web browser and navigate to www.prosoft-technology.com
2 Click the D OWNLOAD H ERE link to download the latest version of ProSoft
Configuration Builder .
3 Choose S
AVE or S
AVE
F
ILE when prompted.
4 Save the file to your Windows Desktop , so that you can find it easily when you have finished downloading.
5 When the download is complete, locate and open the file, and then follow the instructions on your screen to install the program.
ProSoft Technology, Inc. Page 13 of 112
Start Here
User Manual
1.4 Setting Jumpers
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The Setup Jumper acts as "write protection" for the module’s flash memory. In "write protected" mode, the Setup pins are not connecte d, and the module’s firmware cannot be overwritten. Do not jumper the Setup pins together unless you are directed to do so by ProSoft Technical Support.
The following illustration shows the MVI56-EGD jumper configuration.
Note: If you are installing the module in a remote rack, you may prefer to leave the Setup pins jumpered.
That way, you can update the module’s firmware without requiring physical access to the module.
Page 14 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.5 Installing the Module in the Rack
Start Here
User Manual
If you have not already installed and configured your ControlLogix processor and power supply, please do so before installing the MVI56-EGD module. Refer to your Rockwell
Automation product documentation for installation instructions.
Warning: You must follow all safety instructions when installing this or any other electronic devices. Failure to follow safety procedures could result in damage to hardware or data, or even serious injury or death to personnel. Refer to the documentation for each device you plan to connect to verify that suitable safety procedures are in place before installing or servicing the device.
After you have checked the placement of the jumpers, insert MVI56-EGD into the
ControlLogix chassis. Use the same technique recommended by Rockwell Automation to remove and install ControlLogix modules.
Warning: When you insert or remove the module while backplane power is on, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Verify that power is removed or the area is non-hazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
1 Turn power OFF.
2 Align the module with the top and bottom guides, and slide it into the rack until the module is firmly against the backplane connector.
3 With a firm but steady push, snap the module into place.
4 Check that the holding clips on the top and bottom of the module are securely in the locking holes of the rack.
5 Make a note of the slot location. You must identify the slot in which the module is installed in order for the sample program to work correctly. Slot numbers are identified on the green circuit board (backplane) of the ControlLogix rack.
6 Turn power ON.
Note: If you insert the module improperly, the system may stop working, or may behave unpredictably.
ProSoft Technology, Inc. Page 15 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.6 Connecting Your PC to the ControlLogix Processor
There are several ways to establish communication between your PC and the
ControlLogix processor. The following steps show how to establish communication through the serial interface. It is not mandatory that you use the processor's serial interface. You may access the processor through whatever network interface is available on your system. Refer to your Rockwell Automation documentation for information on other connection methods.
1 Connect the right-angle connector end of the cable to your controller at the communications port.
2 Connect the straight connector end of the cable to the serial port on your computer.
Page 16 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.7 Opening the Sample Ladder Logic
Start Here
User Manual
The sample program for your MVI56-EGD module includes custom tags, data types and ladder logic for data I/O and status monitoring. For most applications, you can run the sample ladder program without modification, or, for advanced applications, you can incorporate the sample program into your existing application.
The ProSoft Technology website provides one or more versions of the sample ladder logic. The version number appended to the file name corresponds with the firmware version number of your ControlLogix processor. The firmware version and sample program version must match.
1.7.1 Determining the Firmware Version of Your Processor
Important: The RSLinx service must be installed and running on your computer in order for RSLogix to communicate with the processor. Refer to your RSLinx and RSLogix documentation for help configuring and troubleshooting these applications.
1 Connect an RS-232 serial cable from the COM (serial) port on your PC to the communication port on the front of the processor.
2 Start RSLogix 5000 and close any existing project that may be loaded.
3 Open the C OMMUNICATIONS menu and choose G O O NLINE . RSLogix will establish communication with the processor. This may take a few moments.
4 When RSLogix has established communication with the processor, the Connected
To Go Online dialog box will open.
ProSoft Technology, Inc. Page 17 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5 In the Connected To Go Online dialog box, click the G ENERAL tab. This tab shows information about the processor, including the Revision (firmware) version. In the following illustration, the firmware version is 17.2.
Page 18 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.7.2 Selecting the Slot Number for the Module
Start Here
User Manual
This sample application is for a module installed in Slot 1 in a ControlLogix rack. The ladder logic uses the slot number to identify the module. If you are installing the module in a different slot, you must update the ladder logic so that program tags and variables are correct, and do not conflict with other modules in the rack.
To change the slot number
1 In the Controller Organization list, select the module and then click the right mouse button to open a shortcut menu.
2 On the shortcut menu, choose P ROPERTIES . This action opens the Module Properties dialog box.
3 In the Slot field, use the spinners on the right side of the field to select the slot number where the module will reside in the rack, and then click OK .
RSLogix will automatically apply the slot number change to all tags, variables and ladder logic rungs that use the MVI56-EGD slot number for computation.
ProSoft Technology, Inc. Page 19 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.7.3 Configuring the RSLinx Driver for the PC COM Port
If RSLogix is unable to establish communication with the processor, follow these steps.
1 Open RSLinx.
2 Open the C OMMUNICATIONS menu, and choose C ONFIGURE D RIVERS .
This action opens the Configure Drivers dialog box.
Note: If the list of configured drivers is blank, you must first choose and configure a driver from the Available
Driver Types list. The recommended driver type to choose for serial communication with the processor is
RS-232 DF1 Devices.
Page 20 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Start Here
User Manual
3 Click to select the driver, and then click C ONFIGURE . This action opens the Configure
RS-232 DF1 Devices dialog box.
4 Click the A UTO -C ONFIGURE button . RSLinx will attempt to configure your serial port to work with the selected driver.
5 When you see the message Auto Configuration Successful , click the OK button to dismiss the dialog box.
Note: If the auto-configuration procedure fails, verify that the cables are connected correctly between the processor and the serial port on your computer, and then try again. If you are still unable to auto-configure the port, refer to your RSLinx documentation for further troubleshooting steps.
ProSoft Technology, Inc. Page 21 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.8 Downloading the Sample Program to the Processor
Note: The key switch on the front of the ControlLogix processor must be in the REM or PROG position.
1 If you are not already online with the processor, open the Communications menu, and then choose D
OWNLOAD
.
RSLogix 5000 will establish communication with the processor. You do not have to download through the processor's serial port, as shown here. You may download through any available network connection.
2 When communication is established, RSLogix 5000 will open a confirmation dialog box. Click the D OWNLOAD button to transfer the sample program to the processor.
3 RSLogix 5000 will compile the program and transfer it to the processor. This process may take a few minutes.
4 When the download is complete, RSLogix 5000 will open another confirmation dialog box. If the key switch is in the REM position, click OK to switch the processor from
PROGRAM mode to RUN mode.
Note: If you receive an error message during these steps, refer to your RSLogix documentation to interpret and correct the error.
Page 22 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.9 Connecting your PC to the Module
Start Here
User Manual
With the module securely mounted, connect your PC to the Configuration/Debug port using an RJ45-DB-9 Serial Adapter Cable and a Null Modem Cable.
1 Attach both cables as shown.
2 Insert the RJ45 cable connector into the Configuration/Debug port of the module.
3 Attach the other end to the serial port on your PC.
ProSoft Technology, Inc. Page 23 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1.10 Using the RSLogix 5000 v16 Add-On Instruction
Important: If you are using an older version of RSLogix 5000 (version 15 or older), please refer to Using the
Sample Program in a New Application or Using the Sample Program in an Existing Application.
If you have RSLogix 5000 version 16 or newer, you can use an Add-On Instruction to simplify the task of configuring the module, either as a new application, or within an existing application.
Download the manuals and sample program from the ProSoft Technology web site
You can always download the latest version of the sample ladder logic and user manuals for the MVI56-EGD module from the ProSoft Technology web site, at www.prosoft-technology.com/support/downloads
From that link, navigate to the download page for your module and choose the sample ladder program to download for your version of RSLogix 5000 and your processor.
1.10.1 Creating a New RSLogix 5000 Project
1 Open the F ILE menu, and then choose N EW .
2 Select your ControlLogix controller model.
3 Select R
EVISION
16 .
4 Enter a name for your controller, such as My_Controller .
5 Select your ControlLogix chassis type.
Page 24 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
6 Select S LOT 0 for the controller.
Start Here
User Manual
ProSoft Technology, Inc. Page 25 of 112
Start Here
User Manual
Creating the Module
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1 Add the MVI56-EGD module to the project.
In the C ONTROLLER O RGANIZATION window, select I/O C ONFIGURATION and click the right mouse button to open a shortcut menu. On the shortcut menu, choose N EW
M ODULE ...
This action opens the S ELECT M ODULE dialog box.
2 Select the 1756-M ODULE (G ENERIC 1756 M ODULE ) from the list and click OK.
This action opens the N EW M ODULE dialog box.
Page 26 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
3 In the N EW M ODULE dialog box, enter the following values.
Parameter Value
N
D
AME
ESCRIPTION
EGD
Enter a description for the module. Example: GE Ethernet
Global Data Communication Module
Select D ATA -INT C OMM F ORMAT
S LOT
I NPUT A SSEMBLY I NSTANCE
I NPUT S IZE
Enter the slot number in the rack where the MVI56-EGD module is located
1
250
O UTPUT A SSEMBLY
O UTPUT S IZE
I NSTANCE 2
248
C ONFIGURATION A SSEMBLY I NSTANCE 4
C ONFIGURATION S IZE 0
Start Here
User Manual
Important: You must select the C OMM F ORMAT as D ATA INT in the dialog box, otherwise the module will not communicate over the backplane of the ControlLogix rack.
4 Click OK to continue.
5 Edit the Module Properties.
Select the R EQUESTED P ACKET I NTERVA l value for scanning the I/O on the module.
This value represents the minimum frequency at which the module will handle scheduled events. This value should not be set to less than 1 millisecond. The default value is 5 milliseconds. Values between 1 and 10 milliseconds should work with most applications.
6 Save the project.
ProSoft Technology, Inc. Page 27 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
7 Click OK to close the dialog box. Notice that the module now appears in the
C ONTROLLER O RGANIZATION window.
Page 28 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Start Here
User Manual
Import the Ladder Rung
1 In the C
ONTROLLER
O
RGANIZATION
window, expand the T
ASKS folder and subfolders until you reach the M AIN P ROGRAM folder.
2 In the M
AIN
P
ROGRAM folder, double-click to open the M
AIN
R
OUTINE ladder.
3 Select an empty rung in the routine, and then click the right mouse button to open a shortcut menu. On the shortcut menu, choose I MPORT R UNG
…
ProSoft Technology, Inc. Page 29 of 112
Start Here
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
4 Navigate to the location on your PC where you saved the Add-On Instruction (for example, My Documents or Desktop ). Select the
MVI56EGD_A DD O N _R UNG _ V X_Y.L5X
file
This action opens the I
MPORT
C
ONFIGURATION
dialog box, showing the controller tags that will be created.
Page 30 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Start Here
User Manual
5 If you are using the module in a different slot (or remote rack), select the correct connection input and output variables that define the path to the module. If your module is located in Slot 1 of the local rack, this step is not required.
6 Click OK to confirm the import. RSLogix will indicate that the import is in progress:
When the import is completed, the new rung with the Add-On Instruction will be visible as shown in the following illustration.
The procedure has also imported new User Defined Data Types, Controller Tags, and the Add-On instruction for your project.
7 Save the application and then download the sample ladder logic into the processor.
ProSoft Technology, Inc. Page 31 of 112
Start Here
User Manual
Adjusting the Input and Output Array Sizes
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The module internal database is divided into two user-configurable areas:
Read Data
Write Data.
The Read Data area is moved from the module to the processor, while the Write Data area is moved from the processor to the module. You can configure the start register and size of each area in ProSoft Configuraton Builder (PCB). The size of each area you configure must match the Add-On Instruction controller tag array sizes for the R
EAD
D
ATA and W
RITE
D
ATA arrays.
The MVI56-EGD sample program is configured for 600 registers of R EAD D ATA and 600 registers of W RITE D ATA , which is sufficient for most application. This topic describes how to configure user data for applications requiring more than 600 registers of ReadData and WriteData.
Important: Because the module pages data in blocks of 200 registers at a time, you should configure your user data in multiples of 200 registers.
Caution: When you change the array size, RSLogix may reset the EGD tag values to zero. To avoid data loss, be sure to save your settings before continuing.
1 In the C ONTROLLER O RGANIZATION window, expand the D ATA T YPES and U SER -
D
EFINED
folders, and then double-click EGDDATA.
This action opens an edit window for the EGDDATA data type.
Note: If RSLogix resets your data values, refer to the backup copy of your program to re-enter your data.
2 To modify the W RITE D ATA array, follow the steps in this topic, but substitute
W RITE D ATA for ReadData throughout.
3 Save and download the sample program to the processor.
Page 32 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Start Here
User Manual
ProSoft Technology, Inc. Page 33 of 112
Configuring the MVI56-EGD Module
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2 Configuring the MVI56-EGD Module
In This Chapter
Using ProSoft Configuration Builder ...................................................... 35
[EGD Multicast Group List] .................................................................... 48
Downloading the Project to the Module Using a Serial COM Port ......... 50
Warning: When interfacing with a GE RX3i Controller, all reserved bits within the RX3i Controller must be set to 0 in order to communicate with the MVI56-EGD. Also, the use of a Configuration Server is not supported.
Page 34 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.1 Using ProSoft Configuration Builder
Configuring the MVI56-EGD Module
User Manual
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files customized to meet your application needs. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects.
2.1.1 Setting Up the Project
To begin, start P RO S OFT C ONFIGURATION B UILDER (PCB).
If you have used other Windows configuration tools before, you will find the screen layout familiar. PCB ’s window consists of a tree view on the left, and an information pane and a configuration pane on the right side of the window. When you first start PCB , the tree view consists of folders for Default Project and Default Location , with a Default
Module in the Default Location folder. The following illustration shows the PCB window with a new project.
ProSoft Technology, Inc. Page 35 of 112
Configuring the MVI56-EGD Module
User Manual
Adding the MVI56-EGD module to the project
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
1 Use the mouse to select D EFAULT M ODULE in the tree view, and then click the right mouse button to open a shortcut menu.
2 On the shortcut menu, choose C HOOSE M ODULE T YPE . This action opens the Choose
Module Type dialog box.
3 In the Product Line Filter area of the dialog box, select MVI56 . In the Select Module
Type dropdown list, select MVI56-EGD , and then click OK to save your settings and return to the ProSoft Configuration Builder window.
Page 36 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.1.2 Renaming PCB Objects
Configuring the MVI56-EGD Module
User Manual
Notice that the contents of the information pane and the configuration pane changed when you added the module to the project.
At this time, you may wish to rename the Default Project and Default Location folders in the tree view.
1 Select the object, and then click the right mouse button to open a shortcut menu.
From the shortcut menu, choose R ENAME .
2 Type the name to assign to the object.
3 Click away from the object to save the new name.
Configuring Module Parameters
1 Click the [+] sign next to the module icon to expand module information.
2 Click the [+] sign next to any icon to view module information and configuration options.
3 Double-click any icon to open an Edit dialog box.
4 To edit a parameter, select the parameter in the left pane and make your changes in the right pane.
5 Click OK to save your changes.
ProSoft Technology, Inc. Page 37 of 112
Configuring the MVI56-EGD Module
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Creating Optional Comment Entries
1 Click the [+] to the left of the
2 Double-click the icon. The
icon to expand the module comments.
Edit - Module Comment dialog box appears.
3 Enter your comment and click OK to save your changes.
Printing a Configuration File
1 Select the module icon, and then click the right mouse button to open a shortcut menu.
2 On the shortcut menu, choose V IEW C ONFIGURATION .
This action opens the View
Configuration window.
3 In the View Configuration window, open the F ILE menu, and choose P RINT .
This action opens the Print dialog box.
4 In the Print dialog box, choose the printer to use from the drop-down list, select printing options, and then click OK .
Page 38 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.2 [Module]
Configuring the MVI56-EGD Module
User Manual
This section designates database addresses for input and output on the module and on the processor, and identifies the method of failure for the communications for the module if the processor is not in run mode.
2.2.1 Module Name
0 to 80 characters
This parameter assigns a name to the module that can be viewed using the configuration/debug port. Use this parameter to identify the module and the configuration file.
2.2.2 Module Type
The part number for the module, for example MVI56-EGD
2.2.3 Read Register Start
0 to 3999
This parameter specifies the starting register address of a block of data registers to transfer from the module to the processor.
2.2.4 Read Register Count
0 to 4000
This parameter specifies the number of registers to transfer from the module to the processor.
2.2.5 Write Register Start
0 to 3999
This parameter specifies the starting register address of a module register block where data transferred from the processor will be stored.
2.2.6 Write Register Count
Range 0 to 4000
This parameter specifies the number of registers to transfer from the processor to the module. Valid entry for this parameter is 0 to 3999.
2.2.7 Failure Flag Count
0 through 65535
This parameter specifies the number of successive transfer errors that must occur before halting communication on the application port(s). If the parameter is set to 0 , the application port(s) will continue to operate under all conditions. If the value is set larger than 0 ( 1 to 65535 ), communications will cease if the specified number of failures occur.
ProSoft Technology, Inc. Page 39 of 112
Configuring the MVI56-EGD Module
User Manual
2.3 [SNTP Client]
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The [SNTP CLIENT] section specifies the parameters for the Simple Network Time
Protocol (SNTP) Client, which keeps the internal clock set correctly. This version of the driver supports the unicast implementation of the SNTP Revision 3 and stratum between
1 and 14.
The module can be configured to periodically synchronize its clock with a remote SNTP server. Approximately every 6 minutes, the module sends 10 consecutive requests to the remote SNTP Client (at approximately 6-second intervals). You can check these requests and responses from the SNTP Client Configuration Menu (press the [N] key from the Configuration/Debug Main Menu). If the module receives a valid response from the SNTP server, the computations value will be also be incremented. After 10 consecutive successful requests and responses, the module will synchronize its internal clock (an average is performed based on all 10 responses for better accuracy). The
Time Set Cnt value is incremented every time the clock is synchronized.
After the synchronization is performed, the time valid register is set to Yes. If the module cannot connect to the remote SNTP server after 3 consecutive attempts, the time valid register is set to No. You can also configure the GMT settings to use, and the database address where the date and time information can be copied.
The following parameters in the configuration file set up the SNTP Client:
The database register parameter defines a database register where the SNTP time and date values are copied. It occupies four words as follows:
Word Offset
0 and 1
2 and 3
Description
Date and time in Unix format (long integer)
Microseconds (long integer)
Page 40 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.3.1 NTP Server IP Address
Configuring the MVI56-EGD Module
User Manual
Enter in dotted notation
This parameter sets the IP address of the NTP server to contact for time acquisition.
Select an NTP server with the greatest accuracy that is available all the time from your network. Set this IP address to 0.0.0.0 to disable SNTP server requests.
2.3.2 Time Zone
-11 to 11
This parameter sets the time zone offset from UTC. Positive values are for time zones west of UTC, and negative values are for time zones east of UTC. Set this value to 0 to use UTC in the module.
2.3.3 Use Daylight Savings Time
Y ES or N O
This parameter specifies if daylight savings time will be used in the time computation.
2.3.4 Database Register
-1 or 0 to 3992 as an even value
This parameter specifies if the NTP time computed by the driver is to be placed into the module’s database. If a value of -1 is specified, the time will not be placed into the database. If the value is between 0 and 3992, the time will be placed in the database.
The first 4 bytes represent the seconds since 1/1/1970, and the second 4 bytes represent the number of microseconds. An even value should be used for the register value in order for the data to be stored correctly.
ProSoft Technology, Inc. Page 41 of 112
Configuring the MVI56-EGD Module
User Manual
2.4 [EGD Exchanges]
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
In order to interface the module with EGD devices, you must construct an exchange list.
The exchanges specify messages that will be produced or consumed at a user-defined frequency using the module's internal database. Messages can be broadcast to all nodes on the network, sent to a multicast group on the network or associated with a single node on the network. Up to 100 exchanges can be defined for the driver. Up to
700 word registers can be produced or consumed in a single exchange.
The [EGD Exchanges] section defines the messages that will be produced and consumed by the driver. The UDP protocol on the IP network is used to transport these over Ethernet between all the EGD devices.
For the exchanges to operate correctly, the other EGD devices must be configured and correctly set up. The primary reason for user problems with the module is failure to provide devices that are correctly configured. Before trying to connect the module to the network, the remote device must be able to communicate with ProSoft Configuration
Builder. You must understand and document all parameters.
2.4.1 Exch Type
Producer: exchange will send data from the module's database to another station or stations
Consumer: exchange will receive data from another station
The Exchange Type field defines the direction data moves during the exchange.
Producer exchanges (P) are generated by the driver from data module’s database. This produced (transmitted) data will be available to any other stations on the network that wish to consume (receive) it.
Consumer exchanges (C) place data received from other producing EGD devices into the module’s database.
Page 42 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.4.2 Cast Type
Configuring the MVI56-EGD Module
User Manual
When the Exchange Type is Producer, the cast type field determines if the exchange is a unicast ("U" = point-to-point) exchange, multicast ("M"=multicast group) or a broadcast
("B" = all nodes) exchange.
Producer Unicast - produce message to another station
Producer Multicast - produce message to a group of stations. In order to use this option you need to configure the same Multicast IP address used in the exchange also at the EGD MULTICAST ADDRESS section.
Important: For Multicast mode, use transmit rates of 1 or 2 for best results.
Producer Broadcast - produce message to all stations (set exchange IP address to
255.255.255.255)
When the Exchange Type is Consumer, the cast type field determines how the local database area associated to this exchange will be updated in case an COMS Error
(timeout) occurs.
Consumer No DB Change on COMS Error
Consumer Set DB to -1 On COMS Error
Consumer Set DB to 0 On COMS Error
Consumer Set DB to 1 On COMS Error
2.4.3 DB Reg
The DB Reg field determines the starting register address of the module database area from which data will be produced (sent) or area into which data will be consumed
(received). The validity of the entry depends on the number of registers ( Reg Count ) to be produced or consumed. To be valid, the sum of the DB Reg and Reg Count values cannot exceed the range of the module’s database.
2.4.4 Reg Count
Number of database registers to send or receive in the exchange.
ProSoft Technology, Inc. Page 43 of 112
Configuring the MVI56-EGD Module
User Manual
2.4.5 Swap Code
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
0, 1, 2 or 3
The Swap Code field sets byte and word swapping of data produced or consumed.
Swapping of words and/or bytes in the message may be required for different protocol and operating systems as their representation of multi-byte values may not be the same as that of the module.
Swap Code
0
1
2
3
Description
None - No Change is made in the byte ordering (1234 = 1234)
Words - The words are swapped (1234=3412)
Words & Bytes - The words are swapped then the bytes in each word are swapped (1234=4321)
Bytes - The bytes in each word are swapped (1234=2143)
2.4.6 P/C Time
For a producer exchange, P/C Time sets the number of milliseconds between consecutive produced data exchanges (produced data update interval).
For a consumer exchange, P/C Time sets the number of milliseconds to wait for a new produced message before a timeout error will occur.
For produced exchanges, if this parameter is set to zero, the message will not be produced.
For consumed exchanges, setting this value to approximately 4 times the produced time set on the producer device will prevent the exchange from experiencing excessive timeout errors on a busy network. Setting this value to zero will turn off timeout error checking. A zero value can also be used for exchanges that will interface with the command service port (7937) to handle data read and write requests from another device.
Page 44 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.4.7 IP Address
Configuring the MVI56-EGD Module
User Manual
The IP Address field should be set to the IP address of destination station for produced data or source station for consumed data.
Producer Exchange IP address: If the cast type is set to "U" for a produced exchange, the address should be set to IP address of the specific node to receive (consume) the data. If the cast type is set to "B" for produced data, set the IP to either a network
(255.255.255.255) or subnet (192.168.0.255) broadcast address. If the cast type is set to
"M" for produced data, set the IP address to a valid multicast address.
Multicast Address Assignments
Important: Use Multicast whenever the module produces data to be consumed by at least two other modules. Using Unicast for these applications can cause data transmission delay when at least one of the consumer modules is powered down.
Multicast group addresses 224.0.7.1 to 224.0.7.32 are reserved to allow for designation of up to 32 multicast groups. The following table shows the relationship between multicast group parameters and IP addresses. Refer to Underlying Protocol
Requirements and Constraints for more detailed information on IP and UDP addresses limitations.
Parameter
Group 1
Group 2
…
Group 32
IP Address
224.0.7.1
224.0.7.2
…
224.0.7.32
Important: For Multicast mode, use transmit rates of 1 or 2 for best results.
Consumer Exchange IP address: For consumed messages, this parameter should be set to the IP address of the producer generating the specific exchange data. The combination of the IP address and the exchange ID uniquely identify the exchange to the system.
2.4.8 Exch ID
1 to 16383
The Exch ID field defines the Exchange ID for this message, and must be unique for each station.
For produced exchanges, the combination of the module IP address and the entered
Exchange ID uniquely define a specific exchange to the network.
For consumed exchanges, the Exchange ID and IP address in each message are compared to those defined in the Exchange List to determine which exchanges to consume. The other parameters defined in the Exchange List then determine how much data to receive and where to place that data in the module’s internal database.
ProSoft Technology, Inc. Page 45 of 112
Configuring the MVI56-EGD Module
User Manual
2.4.9 CS Major, CS Minor
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
This is an optional functionality that can be used to prevent unexpected results when changes are performed to existing producer and consumer exchanges.
The purpose of the Configuration Signature (CS) is to guarantee that the produced exchange will contain data in a format expected by a consumer. Therefore, it prevents the consumer from processing received data exchanges which may have an incompatible format due to producer configuration changes.
The Configuration Signature consists of two one-byte integer value (CS Major and CS
Minor). The CS Major must be equal for both Producer and Consumer exchanges. The
CS Minor reflects backward compatible modifications made to an exchange (for example: adding registers to the producer exchange count). Truncating data within an exchange (send less data than before) would not be backward-compatible and, therefore, would require a change in the major number to prevent processing errors.
Whenever a consumer receives an exchange message, it will look for a configured consumer exchange that contains the same Exchange ID. If it finds a matching produced exchange it will compare the Configuration Signature for validation. If the exchange is not validated, then the data will not be consumed.
By default, the <ModuleOrGateway > will perform validity checking but can be configured to ignore validity checking. To disable validity checking, configure all exchanges with both CS Major and CS Minor values equal to ZERO (0) .
When acting as a consumer, the following rules are used by the module to validate an exchange based on its Configuration Signature:
Page 46 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Rules for CS Validation
Configuring the MVI56-EGD Module
User Manual
An exchange will be considered valid if at least one of the following conditions is true:
Producer CS Major and CS Minor are both equal to 0
Consumer CS Major and CS Minor are both equal to 0
Producer CS Major is equal to Consumer CS Major AND Producer CS Minor is greater than or equal to Consumer CS Minor
1
2
1
1
The following table contains some examples that will help you to understand the consumer criteria to validate received exchanges based on the Configuration Signature:
Producer
CS Major
0
0
1
1
Producer
CS Minor
0
0
2
2
2
2
2
2
1
0
1
1
2
1
Consumer
CS Major
0
1
2
2
2
1
Consumer
CS Minor
0
2
0
3
Yes
No
No
Yes
Will Data be
Consumed?
Yes
Comment
Same CS value of 0.0 (Major.Minor) validates the exchange
Yes Producer CS value of 0.0 (Major.Minor) validates the exchange
Yes
No
Consumer CS value of 0.0 (Major.Minor) validates the exchange
Same CS value (1.2) validates the exchange
CS Major mismatch - exchange is not validated
CS Major mismatch - exchange is not validated
Same CS Major and Consumer CS Minor is less than Producer CS Minor - exchange is validated
Same CS Major but Consumer CS Minor is greater than Producer CS Minor - exchange is not validated
2.4.10 EGD Exchange Command List Example
The following is an example section from the [EGD Exchanges] section:
ProSoft Technology, Inc. Page 47 of 112
Configuring the MVI56-EGD Module
User Manual
2.5 [EGD Multicast Group List]
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
This section contains the list of multicast group addresses the EGD server should process (consumer messages for this server produced on other units). This list may contain up to 16 IP addresses. The reserved group addresses for the EGD protocol are
224.0.7.1 to 224.0.7.32. The module will support other group addresses than this data set.
Important: Use Multicast whenever the module produces data to at least two other modules. Using Unicast for these applications can cause data transmission delay when at least one of the consumer modules is powered down.
Page 48 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.6 Ethernet Configuration
Configuring the MVI56-EGD Module
User Manual
Use this procedure to configure the Ethernet settings for your module. You must assign an IP address, subnet mask and gateway address. After you complete this step, you can connect to the module with an Ethernet cable.
1 Determine the network settings for your module, with the help of your network administrator if necessary. You will need the following information: o o o
IP address (fixed IP required) _____ . _____ . _____ . _____
Subnet mask
Gateway address
_____ . _____ . _____ . _____
_____ . _____ . _____ . _____
Note: The gateway address is optional, and is not required for networks that do not use a default gateway.
2 Double-click the E THERNET C ONFIGURATION icon. This action opens the Edit dialog box.
3 Edit the values for my_ip , netmask (subnet mask) and gateway (default gateway).
4 When you are finished editing, click OK to save your changes and return to the
ProSoft Configuration Builder window.
ProSoft Technology, Inc. Page 49 of 112
Configuring the MVI56-EGD Module
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
2.7 Downloading the Project to the Module Using a Serial COM Port
For the module to use the settings you configured, you must download (copy) the updated Project file from your PC to the module.
To download the project file
1 In the tree view in ProSoft Configuration Builder , click once to select the module.
2 Right-click the module icon to open a shortcut menu. From the shortcut menu, choose D OWNLOAD FROM PC TO D EVICE . The program will scan your PC for a valid com port (this may take a few seconds). When PCB has found a valid COM port, the
Download dialog box will open.
3 Choose the COM port to use from the dropdown list, and then click the D
OWNLOAD button.
The module will perform a platform check to read and load its new settings. When the platform check is complete, the status bar in the Download dialog box will display the message Module Running .
Page 50 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Ladder Logic
User Manual
3 Ladder Logic
In This Chapter
Module Status Data and Variables (ModuleDef) .................................... 53
Adding the Module to an Existing Project .............................................. 57
Ladder logic is required for application of the MVI56-EGD module. Tasks that must be handled by the ladder logic are module data transfer, special block handling, and status data receipt. Additionally, a power-up handler may be needed to handle the initialization of the module’s data and to clear any processor fault conditions.
The sample ladder logic is extensively commented, to provide information on the purpose and function of each rung. For most applications, the sample ladder will work without modification.
3.1 Controller Tags
The MVI56-EGD module is defined in the example as EGD to hold all data related to the module. The tag name can be set to any valid tag name desired.
ProSoft Technology, Inc. Page 51 of 112
Ladder Logic
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Page 52 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
3.2 Module Status Data and Variables (ModuleDef)
Ladder Logic
User Manual
All status and variable data related to the MVI56-EGD is stored in a user-defined data type. An instance of the data type is required before the module can be used. This is accomplished by declaring a variable of the data type in the Controller Tags Edit Tags dialog box. The object has the following structure:
Name
InStat
ReadData
WriteData
BP
Data Type
InStat
INT[1000]
INT[1000]
Backplane
HaltBlk9250 BOOL
Blk9250GenStat Blk9250Stat
HaltBlk2000
CPmessage
BOOL
CPstat[17]
CPmessReq BOOL
CPmessReqQty INT
CPindxFirst INT
GenStatReq
CPmessResQty
CPindxResFirst
CPwordsQty
ColdBoot
WarmBoot
BOOL
INT
INT
INT
BOOL
BOOL
Description
Status information in each read block
Data read from module
Data to write to module
Data to handle backplane logic
Halts Block 9250
Halts Block 2000
Initiates Block 2000. C/P Messages
Quantity of Consumer/Producer Message
Index of the First Consumer/Producer Message
Initiates Block 9260 C/P Messages
Quantity of Consumer/Producer Message from Module
Index of the First Consumer/Producer Message from Module
Calculated words Qty CP messages x 14.
This object contains objects that define variables for the module and status data related to the module. Each of these object types is discussed in the following topics of the document.
3.2.1 Backplane Object
This data object stores the variables required for the data transfer between the processor and the MVI56-EGD module. The following illustration shows the structure of the object.
Name
LastRead
LastWrite
BlockIndex
StatusIndex
Data Type
INT
INT
INT
INT
Description
Index of last read block
Index of last write block
Computed block offset for data table
Computed block offset for status data
The LastRead tag stores the latest Read Block ID received from the module. The
LastWrite tag stores the latest Write Block ID to be sent to the module. The Block Index tag is an intermediate variable used during the block calculation.
ProSoft Technology, Inc. Page 53 of 112
Ladder Logic
User Manual
3.2.2 User Data Objects (MNETDATA)
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
These objects hold data to be transferred between the processor and the MVI56-EGD module. The user data is the read and write data transferred between the processor and the module as pages of data up to 200 words long.
Name
ReadData
WriteData
Data Type
INT[600]
INT[600]
Description
Data read from module. Set array equal to the size set in the Configuration file.
Data to write to module. Set array equal to the size set in the Configuration file.
The read data (R
EAD
D
ATA
) is an array set to match the value entered in the Read
Register Count parameter of the configuration file. For ease of use, this array should be dimensioned as an even increment of 200 words. This data is paged up to 200 words at a time from the module to the processor. The ReadData task places the data received into the proper position in the read data array. Use this data for status and control in the ladder logic of the processor.
The write data (W RITE D ATA ) is an array set to match the value entered in the Write
Register Count parameter of the configuration file. For ease of use, this array should be dimensioned as even increments of 200 words. This data is paged up to 200 words at a time from the processor to the module. The WriteData task places the write data into the output image for transfer to the module. This data is passed from the processor to the module for status and control information for use in other nodes on the network.
3.2.3 Status Object (InStat)
This object stores the status data of the module. The InStat object (shown in the following example) is updated each time a read block is received by the processor. Use this data to monitor the state of the module at a "real-time" rate.
Name
PassCnt
BlkCntr
SNTP
Data Type
INT
BlkStat
SNTPstat
Description
Program cycle/scan counter
Within the InStat objects are objects containing the status information for the EGD protocol. Refer to Status Data Area and Error Codes for a complete listing of the data stored in this object.
Page 54 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
General Status
Name
RevByte1
RevByte2
RevByte3
OpByte0
OpByte1
OpByte2
OpByte3
RunByte0
RunByte1
RunByte2
RunByte3
BlkXferStat
SNTPstats
SINT
BlkStat
SNTPstat
ProductCodeName DINT
RevisionLevel DINT
OpSysRevision
RunNumber
DINT
DINT
Data Type
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
Description
Revision byte 1 of 0 & 1
Revision byte 2 of 2 & 3
Revision byte 3 of 2 & 3
Op byte 0 of 0 & 1
Op byte 1 of 0 & 1
Op byte 2 of 2 & 3
Op byte 3 of 2 & 3
Run byte 0 of 0 & 1
Run byte 1 of 0 & 1
Run byte 2 of 2 & 3
Run byte 3 of 2 & 3
Block Status
Name
Write
Read
Parse
Error
Data Type
INT
INT
INT
INT
Ladder Logic
User Manual
Description
Total number of write block transfers. Block Write counter.
Total number of read block transfers. Block Read counter.
Total number of blocks parsed. Block Parse counter.
Total number of block transfer errors. Block Error Counter.
SNTP Status
Name
ValidTime
ReqCnt
RespCnt
CompCnt
SetCnt
TimeoutErrCnt
SecLSW
SecMSW micSecLSW micSecMSW
Sec micSec
ProSoft Technology, Inc.
Data Type
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
DINT
DINT
Description
SNTP valid time
SNTP request count
SNTP response count
SNTP computation count
SNTP set count
SNTP timeout error count
SNTP seconds (LSW)
SNTP seconds (MSW)
SNTP microseconds (LSW)
SNTP microseconds (MSW)
SNTP seconds
SNTP microseconds
Page 55 of 112
Ladder Logic
User Manual
3.2.4 Consumer/Producer Status
Name
Status
Data Type
INT
StatBit
CPnumTimesLSW
CPnumTimesMSW
MissCntLSW
MissCntMSW
RfrshCntErrLSW
RfrshCntErrMSW
InvErrBit
TimeSyncErr
ShrtMEsgErr
LngMEsgErr
PrtclPVN
CnfgSig
CPMessageCount
MissedCount
RefreshCountErr
INT
INT
INT
INT
INT
INT
DINT
DINT
DINT
INT
INT
INT
INT
INT
INT
INT
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Description
Status (0=invalid, 1=producing/healthy,
2=pending/unhealthy)
Status bit mapped (bit 0=error or invalid, bit 1=not time synchronized, bits 2 to 15 reserved)
Number of times C/P (LSW)
Number of times C/P (MSW)
Missed count (LSW)
Missed count (MSW)
Refresh count error (LSW)
Refresh count error (MSW)
Invalid error bit set by producer
Time sync error set by producer
Short message error in exchange
Long message error in exchange
Protocol PVN not set to 1
Configuration signature not set correctly
Number of times C/P
Missed count
Refresh count error
Page 56 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
3.3 Adding the Module to an Existing Project
Ladder Logic
User Manual
1 Select the I/O Configuration folder in the Controller Organization window of RSLogix
5000, and then click the right mouse button to open a shortcut menu. On the shortcut menu, choose N
EW
M
ODULE
.
This action opens the Select Module dialog box:
2 Select the 1756-M ODULE (G ENERIC 1756 M ODULE ) from the list and click OK . This action opens the New Module dialog box.
ProSoft Technology, Inc. Page 57 of 112
Ladder Logic
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
3 Enter the Name, Description and Slot options for your application. You must select the Comm Format as D ATA INT in the dialog box, otherwise the module will not communicate. Click OK to continue.
Parameter
Name
Description
Value
Enter a module identification string. Example: EGD_2
Enter a description for the module. Example: GE
E THERNET G LOBAL D ATA C OMMUNICATION M ODULE
Select D ATA -INT . Comm Format
Slot
Input Assembly Instance
Input Size
Output Assembly Instance
Output Size
Enter the slot number in the rack where the MVI56-EGD module is located.
1
2
248
Configuration Assembly Instance 4
Configuration Size 0
250
4 Select the Requested Packet Interval value for scanning the I/O on the module. This value represents the minimum frequency that the module will handle scheduled events. This value should not be set to less than 1 millisecond. The default value is 5 milliseconds. Values between 1 and 10 milliseconds should work with most applications.
Page 58 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Ladder Logic
User Manual
5 Save the module. Click OK to dismiss the dialog box. The Controller Organization window now displays the module's presence.
6 Copy the User-Defined Data Types from the sample program into your existing
RSLogix 5000 project.
7 Copy the Controller Tags from the sample program into your project.
8 Copy the Ladder Rungs from the sample program into your project.
ProSoft Technology, Inc. Page 59 of 112
Ladder Logic
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Page 60 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Diagnostics and Troubleshooting
User Manual
4 Diagnostics and Troubleshooting
In This Chapter
Using ProSoft Configuration Builder (PCB) for Diagnostics ................... 64
Reading Status Data from the Module ................................................... 76
The module provides information on diagnostics and troubleshooting in the following forms:
LED status indicators on the front of the module provide general information on the module's status.
Status data contained in the module can be viewed through the Configuration/Debug port, using the troubleshooting and diagnostic capabilities of ProSoft Configuration
Builder (PCB) .
Status data values can be transferred from the module to processor memory and can be monitored there manually or by customer-created logic.
ProSoft Technology, Inc. Page 61 of 112
Diagnostics and Troubleshooting
User Manual
4.1 LED Status Indicators
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The LEDs indicate the module’s operating status as follows:
LED
CFG
Color
Green
Status
On
APP
STATUS
BP ACT
OK
BATT
Off
Amber Off
On
Amber On
Red/
Green
Red
Off
Off
Green
Red
Off
On
Indication
Data is being transferred between the module and a remote terminal using the Configuration/Debug port.
No data is being transferred on the Configuration/Debug port.
The MVI56-EGD is working normally.
The MVI56-EGD module program has recognized a communication error on one of its ports.
The LED is on when the module is performing a write operation on the backplane.
The LED is off when the module is performing a read operation on the backplane. Under normal operation, the LED should blink rapidly on and off.
The card is not receiving any power and is not securely plugged into the rack.
The module is operating normally.
The program has detected an error or is being configured. If the LED remains red for over 10 seconds, the program has probably halted. Remove the card from the rack and re-insert the card to restart the module’s program.
The battery voltage is OK and functioning.
The battery voltage is low or battery is not present. Allow battery to charge by keeping module plugged into rack for 24 hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, call ProSoft
Technology support. There is a serious problem with the module, and it will have to be sent back to ProSoft.
4.1.1 Ethernet LED Indicators
LED
Data
Link
State
OFF
GREEN Flash
OFF
GREEN Solid
Description
No activity on the Ethernet port.
The Ethernet port is actively transmitting or receiving data.
No physical network connection is detected. No Ethernet communication is possible. Check wiring and cables.
Physical network connection detected. This LED must be ON solid for Ethernet communication to be possible.
Page 62 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
4.1.2 Clearing a Fault Condition
Diagnostics and Troubleshooting
User Manual
Typically, if the OK LED on the front of the module becomes illuminated red for more than ten seconds, a hardware problem has been detected in the module or the program has exited. To attempt to clear the condition:
1 Remove the card from the rack and re-insert the card in the rack
2 Verify the configuration data being transferred to the module from the ControlLogix processor
If the module's OK LED does not turn green, make sure the module is inserted completely into the rack. If this does not cure the problem, contact ProSoft Technology
Support.
4.1.3 Troubleshooting
Use the following troubleshooting steps if you encounter problems when the module is powered up. If these steps do not resolve your problem, please contact ProSoft
Technology Technical Support.
Processor Errors
Problem description Steps to take
Processor fault Verify that the module is plugged into the slot that has been configured for the module in the I/O Configuration of RSLogix.
Verify that the slot location in the rack has been configured correctly in the ladder logic.
Processor I/O LED flashes
This indicates a problem with backplane communications. A problem could exist between the processor and any installed I/O module, not just the MVI56-EGD. Verify that all modules in the rack are correctly configured in the ladder logic.
Module Errors
Problem description Steps to take
BP ACT LED (not present on MVI56E modules) remains OFF or blinks slowly
MVI56E modules with scrolling LED display:
<Backplane Status> condition reads ERR
This indicates that backplane transfer operations are failing. Connect to t he module’s Configuration/Debug port to check this.
To establish backplane communications, verify the following items:
The processor is in RUN or REM RUN mode.
The backplane driver is loaded in the module.
The module is configured for read and write data block transfer.
The ladder logic handles all read and write block situations.
The module is properly configured in the processor I/O configuration and ladder logic.
OK LED remains RED The program has halted or a critical error has occurred. Connect to the
Configuration/Debug port to see if the module is running. If the program has halted, turn off power to the rack, remove the card from the rack and re-insert it, and then restore power to the rack.
ProSoft Technology, Inc. Page 63 of 112
Diagnostics and Troubleshooting
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
4.2 Using ProSoft Configuration Builder (PCB) for Diagnostics
The Configuration and Debug menu for this module is arranged as a tree structure, with the Main menu at the top of the tree, and one or more submenus for each menu command. The first menu you see when you connect to the module is the Main menu.
Because this is a text-based menu system, you enter commands by typing the
[command letter] from your computer keyboard in the Diagnostic window in ProSoft
Configuration Builder (PCB) . The module does not respond to mouse movements or clicks. The command executes as soon as you press the [ COMMAND LETTER ] — you do not need to press [E NTER ].
When you type a [ COMMAND LETTER ] , a new screen will be displayed in your terminal application.
4.2.1 Using the Diagnostic Window in ProSoft Configuration Builder
Tip: You can have a ProSoft Configuration Builder Diagnostics window open for more than one module at a time.
To connect to the module’s Configuration/Debug serial port
1 Start PCB , and then select the module to test. Click the right mouse button to open a shortcut menu.
2 On the shortcut menu, choose D IAGNOSTICS .
This action opens the Diagnostics dialog box.
Page 64 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
3 Press [?] to open the Main menu.
Diagnostics and Troubleshooting
User Manual
If there is no response from the module, follow these steps:
1 Click to configure the connection. On the Connection Setup dialog box, select a valid com port or other connection type supported by the module.
2 Verify that the null modem cable is connected pro perly between your computer’s serial port and the module. A regular serial cable will not work.
3 On computers with more than one serial port, verify that your communication program is connected to the same port that is connected to the module.
If you are still not able to establish a connection, contact ProSoft Technology for assistance.
ProSoft Technology, Inc. Page 65 of 112
Diagnostics and Troubleshooting
User Manual
4.2.2 Navigation
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
All of the submenus for this module contain commands to redisplay the menu or return to the previous menu. You can always return from a submenu to the next higher menu by pressing [M] on your keyboard.
The organization of the menu structure is represented in simplified form in the following illustration:
The remainder of this section shows the menus available for this module, and briefly discusses the commands available to you.
Keystrokes
The keyboard commands on these menus are usually not case sensitive. You can enter most commands in lowercase or uppercase letters.
The menus use a few special characters ( ?
, , + , @ ) that must be entered exactly as shown. Some of these characters will require you to use the SHIFT , CTRL , or ALT keys to enter them correctly. For example, on US English keyboards, enter the ?
command as
SHIFT and / .
Also, take care to distinguish the different uses for uppercase letter "eye" ( I ), lowercase letter "el" ( L ), and the number one ( 1 ). Likewise, uppercase letter "oh" ( O ) and the number zero ( 0 ) are not interchangeable. Although these characters look alike on the screen, they perform different actions on the module and may not be used interchangeably.
Page 66 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
4.2.3 Main Menu
Diagnostics and Troubleshooting
User Manual
When you first connect to the module from your computer, your terminal screen will be blank. To activate the main menu, press the [?] key on your computer’s keyboard. If the module is connected properly, the following menu will appear.
Caution: Some of the commands available to you from this menu are designed for advanced debugging and system testing only, and can cause the module to stop communicating with the processor or with other devices, resulting in potential data loss or other failures. Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff. Some of these command keys are not listed on the menu, but are active nevertheless. Please be careful when pressing keys so that you do not accidentally execute an unwanted command.
Redisplaying the Menu
Press [?] to display the current menu. Use this command when you are looking at a screen of data, and want to view the menu choices available to you.
Viewing Block Transfer Statistics
Press [B] to view the Block Transfer Statistics screen.
Use this command to display the configuration and statistics of the backplane data transfer operations between the module and the processor. The information on this screen can help determine if there are communication problems between the processor and the module.
Tip: Repeat this command at one-second intervals to determine the number of blocks transferred each second.
Viewing Module Configuration
Press [C] to view the Module Configuration screen.
Use this command to display the current configuration and statistics for the module.
ProSoft Technology, Inc. Page 67 of 112
Diagnostics and Troubleshooting
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Opening the Database View Menu
Press [D] to open the Database View menu.
Use this menu command to view the current contents of the module’s database. For
more information about this submenu, see Database View Menu (page 70).
Opening the EGD Menu
Press [E] to open the EGD Menu. Use this command to view the configuration and status of EGD Producer/Consumer Exchanges.
Viewing SNTP Status
Press [I] to view configuration information about the SNTP client.
Refer to SNTP Support (page 80) for more information on configuring and using this
function.
Transferring the Configuration File from the PC to the Module
On the Diagnostics Menu this is referred to as Receive Module Configuration .
Press [R] to receive (download) the configuration file from your PC to the module and store the file on the module’s Compact Flash Card (Personality Module) or Flash RAM.
Press [Y] to confirm the file transfer, and then follow the instructions on the terminal screen to complete the file transfer process.
After the file has been successfully downloaded, the module will restart the program and load the new configuration information. Review the new configuration using menu commands [6] and [0] to verify that the module is configured correctly.
Transferring the Configuration File from The Module to the PC
On the Diagnostics Menu this is referred to as Send Module Configuration .
Press [S] to send (upload) the configuration file from the module to your PC.
Press [Y] to confirm the file transfer, and then follow the instructions on the terminal screen to complete the file transfer process.
After the file has been successfully uploaded, you can open and edit the file to change the module’s configuration.
Resetting Diagnostic Data
Press [U] to reset the status counters for the Client and/or server(s) in the module.
Page 68 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Viewing Version Information
Press [V] to view version information for the module.
Diagnostics and Troubleshooting
User Manual
Use this command to view the current version of the software for the module, as well as other important values. You may be asked to provide this information when calling for technical support on the product.
Values at the bottom of the display are important in determining module operation. The
Program Scan Counter value is incremented each time a module’s program cycle is complete.
Tip: Repeat this command at one-second intervals to determine the frequency of program execution.
Warm Booting the Module
Press [W] from the Main menu to warm boot (restart) the module.
This command will cause the program to exit and reload, refreshing configuration parameters that must be set on program initialization. Only use this command if you must force the module to reboot.
Opening the Network Menu
Press [@] to open the Network menu.
The Network menu allows you to send, receive and view the WATTCP.CFG file that contains the IP, gateway and other network specification information. For more
information about this submenu, see Network Menu (page 72).
Exiting the Program
Press [ESC] to restart the module and force all drivers to be loaded. The module will use the configuration stored in the module's flash memory to configure the module.
ProSoft Technology, Inc. Page 69 of 112
Diagnostics and Troubleshooting
User Manual
4.2.4 Database View Menu
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Press [D] from the Main menu to open the Database View menu. Use this menu command to view the current contents of the module database. Press [?] to view a list of commands available on this menu.
Viewing Register Pages
To view sets of register pages, use the keys described below:
Command
[0]
[1]
[2]
Description
Display registers 0 to 99
Display registers 1000 to 1099
Display registers 2000 to 2099
And so on. The total number of register pages available to view depends on your module’s configuration.
Displaying the Current Page of Registers Again
Press [S] from the Database View menu to show the current page of registers again.
This screen displays the current page of 100 registers in the database.
Page 70 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Diagnostics and Troubleshooting
User Manual
Moving Back Through 5 Pages of Registers
Press [-] from the Database View menu to skip five pages back in the database to see the 100 registers of data starting 500 registers before the currently displayed page.
Moving Forward (Skipping) Through 5 Pages of Registers
Press [+] from the Database View menu to skip five pages ahead in the database to see the 100 registers of data starting 500 registers after the currently displayed page.
Viewing the Previous Page of Registers
Press [P] from the Database View menu to display the previous page of data.
Viewing the Next Page of Registers
Press [N] from the Database View menu to display the next page of data.
Viewing Data in Decimal Format
Press [D] from the Database View menu to display the data on the current page in decimal format.
Viewing Data in Hexadecimal Format
Press [H] from the Database View menu to display the data on the current page in hexadecimal format.
Viewing Data in Floating-Point Format
Press [F] from the Database View menu to display the data on the current page in floating-point format. The program assumes that the values are aligned on even register boundaries. If floating-point values are not aligned as such, they are not displayed properly.
Viewing Data in ASCII (Text) Format
Press [A] from the Database View menu to display the data on the current page in ASCII format. This is useful for regions of the database that contain ASCII data.
Returning to the Main Menu
Press [M] to return to the Main menu.
ProSoft Technology, Inc. Page 71 of 112
Diagnostics and Troubleshooting
User Manual
4.2.5 Network Menu
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
From the IEC-870-5-104 Server menu press [@] to display the IEC-870-5-104 Network menu screen. The Network menu allows you to send, receive, and view the
WATTCP.CFG file that contains the IP and module addresses, and other network information.
Transferring WATTCP.CFG to the Module
Press [R] to transfer a new WATTCP.CFG file from the PC to the module. Use this command to change the network configuration for the module (for example, the module’s
IP address).
Press [Y] to confirm the file transfer, and then follow the instructions on the terminal screen to complete the file transfer process.
Transferring WATTCP.CFG to the PC
Press [S] to transfer the WATTCP.CFG file from the module to your PC.
Press [Y] to confirm the file transfer, and then follow the instructions on the terminal screen to complete the file transfer process.
After the file has been successfully transferred, you can open and edit the file to change the module’s network configuration.
Page 72 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Diagnostics and Troubleshooting
User Manual
Viewing the WATTCP.CFG File on the module
Press [V] to view the module’s WATTCP.CFG file. Use this command to confirm the module’s current network settings.
Returning to the Main Menu
Press [M] to return to the Main menu.
4.2.6 EGD Menu
Press [E] to open the EGD Menu. Use this command to view configuration and status for the EGD protocol.
Opening the Producer/Consumer List Menu
Press [C] to open the Producer/Consumer List menu. Use this command to view the status of producers and consumers currently communicating on the network.
Viewing the Multicast Group List
Press [G] to view the Multicast Group List. Use this command to see a list of IP addresses in the radio’s configured multicast group.
ProSoft Technology, Inc. Page 73 of 112
Diagnostics and Troubleshooting
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Opening the Status Data Menu
Press [S] to open the Producer/Consumer Status Data menu. Use this command to view communication status for each of the configured producers and consumers.
Redisplaying the Menu
Press [?] to display the current menu. Use this command when you are looking at a screen of data, and want to view the menu choices available to you.
Returning to the Main Menu
Press [M] to return to the Main menu.
Page 74 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
4.2.7 Producer/Consumer List Menu
Diagnostics and Troubleshooting
User Manual
Press [C] to open the Producer/Consumer List menu. Use this command to view a list of the configured producers and consumers.
Redisplaying the Menu
Press [?] to display the current menu. Use this command when you are looking at a screen of data, and want to view the menu choices available to you.
Redisplaying the Current Page
Press [S] to display the current page of data.
Going Back Two Pages of Data
Press [-] from the Database View menu to skip back to the previous 200 registers of data.
Viewing the Previous Page of Data
Press [P] to display the previous page of data.
Going Ahead Two Pages of Data
Hold down [Shift] and press [=] to skip forward to the next 200 registers of data.
Viewing the Next Page of Data
Press [N] to display the next page of data.
Returning to the Previous Menu
Press [M] to return to the Previous Menu.
ProSoft Technology, Inc. Page 75 of 112
Diagnostics and Troubleshooting
User Manual
4.2.8 Producer/Consumer Status Menu
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Press [S] to open the Producer/Consumer Status menu. Use this command to view communication status for each of the configured producers and consumers.
Redisplaying the Menu
Press [?] to display the current menu. Use this command when you are looking at a screen of data, and want to view the menu choices available to you.
Redisplaying the Current Page
Press [S] to display the current page of data.
Going Back Two Pages of Data
Press [-] from the Database View menu to skip back to the previous 200 registers of data.
Viewing the Previous Page of Data
Press [P] to display the previous page of data.
Going Ahead Two Pages of Data
Hold down [Shift] and press [=] to skip forward to the next 200 registers of data.
Viewing the Next Page of Data
Press [N] to display the next page of data.
Returning to the Previous Menu
Press [M] to return to the Previous Menu.
4.3 Reading Status Data from the Module
The MVI56-EGD module returns a 20-word Status Data block that can be used to determine the module’s operating status. This data can be located in the module’s database at registers at the location specified in the configuration. This data is transferred to the ControlLogix continuously with each read block.
Page 76 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Reference
User Manual
5 Reference
In This Chapter
Exchange Configuration Form ............................................................. 108
5.1 Product Specifications
The Ethernet Global Data (EGD) module can be used to interface many different protocols with EGD devices. The EGD driver supports both the producer/consumer service port (18246) and the command service port (7937) using the UDP protocol over an IP network. The user defines the data to be produced and consumed in a configuration file downloaded to the module.
GE Fanuc Automation and GE Drive Systems developed an Ethernet Global Data, or
EGD, exchange for PLC and computer data in 1998. Ethernet Global Data (EGD) offers versatility where a mix of control devices requires cooperation with each other. This involves sharing of information across the applications regardless of device or network type, often at high speed, and with high reliability. High reliability means fewer communication failures and having the ability to detect failures upon occurrence.
Particular emphasis is delivered for applications requiring periodic or frequent updates and time synchronization of devices. The protocol supports Unicast, Broadcast and
Multicast group messaging. Efficiency is based on the fact that each device on the network can produce these types of messages and each device determines which of these messages to consume.
5.1.1 General Specifications
Single Slot - 1756 backplane compatible
The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module.
Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
Configuration data obtained from configuration text file downloaded to module.
Sample configuration file included
Local or remote rack
ProSoft Technology, Inc. Page 77 of 112
Reference
User Manual
5.1.2 Hardware Specifications
Specification
Backplane Current Load
Operating Temperature
Storage Temperature
Shock
Relative Humidity
LED Indicators
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Description
800 mA @ 5 Vdc
3 mA @ 24 Vdc
32°F to 140°F (0° C to 60°C)
-40°F to 185°F (-40° C to 85°C)
30 g operational
50 g non-operational
Vibration: 5 g from 10 Hz to 150 Hz
5% to 95% (with no condensation)
Module Status
Backplane Transfer Status
Application Status
Serial Activity
Application port (Ethernet)
Ethernet Port (Ethernet modules)
Shipped with Unit
10/100 Base-T
RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to
5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable
Debug/Configuration port (CFG)
CFG Port (CFG) RJ45 (DB-9M with supplied cable)
No hardware handshaking
Page 78 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5.1.3 Functional Specifications
Reference
User Manual
The driver interfaces with a common internal database in the module. This permits the sharing of data across many different networks.
The module supports UDP of service port 7927 (0x1F01) to handle all requests made of the module. The module will only service the requests and generate response messages. It will not generate command requests. The module supports the following functions specified in the EGD protocol:
32
33
34
35
36
37
8
9
10
15
16
18
Code
3
4
7
Description
Retrieve Configuration Request
Retrieve Configuration Response
Summary Request
Summary Response
Capabilities Request
Capabilities Response
Statistics Request
Statistics Response
Command NAK
Read Request
Read Response
Write Request
Write Response
Masked Write Request
Masked Write Response
The producer functionality provided in the EGD protocol is used to transfer portions of the module’s database to other EGD nodes on the network. The consumer functionality is used to transfer data from other nodes on the network into the module’s database.
The EGD module generates produced data as defined in the user configuration exchange list, from the module’s internal database, and is produced at the frequency defined in the exchange list. This data can be broadcast to all nodes or to a specific node on the network.
The EGD module consumes data as defined in the user configuration exchange list. This data is derived from other nodes on the network and is placed in the module’s internal database. If a consumer exchange is not received at the specified timeout, the driver will update the status of the exchange. When the driver again receives the exchange, the status will be updated.
ProSoft Technology, Inc. Page 79 of 112
Reference
User Manual
5.1.4 SNTP Support
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
SNTP is used for time synchronization of produced and consumed commands. When an exchange occurs the driver compares time stamps from the previous exchange. When the new exchange time is less than the previous exchange, the exchange is ignored.
This can occur when the Ethernet packets are routed and delayed. Time synchronization provides for data integrity. The following table lists the parameters defined in this section:
The SNTP driver will compute a new clock value every 5 minutes using the average value of 10 samples each collected over an approximate 6-second period. This new value will be used to adjust the clock maintained by the SNTP driver and used by the application. If a valid database register is specified, the driver will place the time value into the module’s database. The first two registers will contain the number of seconds and the next two registers will contain the number of microseconds since January 1,
1970.
A list of some of the common NTP servers can be obtained at http://www.ntp.org/, http://www.eecis.udel.edu/~mills/ntp/servers.html, along with the appropriate IP address.
Other server lists can be found on the Internet by searching on "NTP Servers" with your browser.
Page 80 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5.2 Functional Overview
Reference
User Manual
GE Fanuc Automation and GE Drive Systems developed an Ethernet Global Data, or
EGD, exchange for PLC and computer data in 1998. GE Ethernet Global Data (EGD) offers versatility where a mix of control devices requires cooperation with each other.
This involves sharing of information across the applications regardless of device or network type, often at high speed, and with high reliability. Bandwidth utilization is optimized by using efficient communication methods. High reliability means fewer communication failures and having the ability to detect failures upon occurrence.
Particular emphasis is delivered for applications requiring periodic or frequent updates and time synchronization of devices. The protocol supports Unicast, Broadcast and
Multicast group messaging. Efficiency is based on the fact each device on the network can produce these types of messages and each device determines which of these messages to consume.
5.2.1 Ethernet Global Data Compatible Devices
Devices that support the Ethernet Global Data protocol:
GE Series 90-70 PLC CPU (CMM742 with EGD support)
GE Series 90-30 PLC CPU 364 (with EGD support)
VersaMax CPU E05
Several drives and turbines
Ethernet Global Data Service for NT
CIMPLICITY HMI software
Several HMI products
ProSoft Technology, Inc. Page 81 of 112
Reference
User Manual
5.2.2 EGD Command Server
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The module supports UDP service port 7937 (0x1F01) to handle all command requests.
The module will only service requests and generate response messages. It will not generate command requests. The module supports the following functions specified in the EGD protocol:
9
10
15
16
18
32
33
34
35
36
37
Code
3
4
7
8
Description
Retrieve Configuration Request (page 83) (example provided)
Retrieve Configuration Response (page 83) (example provided)
Capabilities Request (page 86)
Capabilities Response (page 86)
Masked Write Request (page 97)
Masked Write Response (page 97)
The module only supports address type 0 for the read and write commands. Therefore, the data requested is relative to the EGD exchange delimited in the request. In order to use these functions, an exchange must first exist in the module's exchange list defining the database and register count. If the production/consumption time is set to zero, the exchange will never be produced or consumed and will only be valid for command processing. These functions should be used for data that is not time critical and does not require periodic updating. The maximum length of the message is 1400 bytes.
The module supports the masked write request command to alter one or more bits.
Multiple cells can be provided in the request to alter more than one byte of data. The maximum length of the message is 1400 bytes.
Refer to EGD Protocol Specific Configuration for information on the data structures required for each command. Command support is usually not available in most EGD devices or drivers. Most devices only support the producer/consumer services.
Therefore, this service may not be utilized by those devices.
Page 82 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Retrieve Configuration PDUs Example
PDU Type = 3
Reference
User Manual
Retrieve Configuration Request
The Retrieve Configuration Request PDU command permits an application program to request the configuration details associated with a matching Producer and Exchange ID.
A Retrieve Configuration Request sent from a requesting node must be followed by a
Retrieve Configuration Response message from the responding node.
Description Data Packet
Info
Ethernet
II
IPv4
UDP
Destination MAC:
Source MAC:
Type:
Version:
Header Size:
Type of service:
000----0:
---0---0:
----0-—0:
-----0-0:
------00:
00:0D:8D:00:13:83
00:12:3F:AE:5C:AE
0x0800 - Ipv4
0x4
20 bytes
Routine
Normal Delay
Normal throughput (0x 00)
Total Length:
Identification:
Flags:
Fragment Offset:
Time to Live:
Protocol:
Source Port:
Length:
Checksum:
EGD:
00-:
0-0:
Source Address:
Destination Port:
Header Checksum:
Destination Address:
Normal reliability
Normal Monetary cost
44 bytes (0x002C)
2645 (0x0A55)
EGD's PDU Field: Offset
PDU Type: 0
Message Flag: 1
Request ID: 2
PVN1: 4
Reserved:
Message
Length:
5
6
Producer ID: 8
Exchange ID: 12
May Fragment
Last Fragment
0 bytes (0x0000)
64 (0x40)
17 (0x11) [UDP]
39947 correct (0x9C0B)
(0x 00)
105.102.0.200 (0x 69 66 00 C8)
105.102.0.205 (0x 69 66 00
7937 (0x 1F01)
7937 (0x 1F01)
24 bytes (0x 00 18)
32236 - correct (0x 7DEC)
Bytes
1
1
2
1
1
Hex code
0x 03
0x 00
0x 11 11
0x 01
0x 00
2
4
4
0x 10 00
0x 69 66 00 C8
0x E0 2E 00 00
This is an example of an EGD Configuration Request Command Production Data Unit.
ProSoft Technology, Inc. Page 83 of 112
Reference
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
This is the hexadecimal representation of the Retrieve Configuration Request from the above table. It includes the Ethernet II, IPv4, UDP, and within UDP, the EGD Command
PDU Type 3 depicted in bold font.
00 0D 8D 00 13 83 00 12 3f AE 5C AE 08 00 45 00
00 2C 0A 55 00 00 40 11 9C 0b 69 66 00 C8 69 66
00 CD 1F 01 1F 01 00 18 7D EC 03 00 11 11 01 00
10 00 69 66 00 C8 E1 2E 00 00
PDU Type = 4
Retrieve Configuration Response
The Retrieve Configuration Response PDU supports the retrieval of exchange configurations for Ethernet Global Data. This message packet will be sent in response to a Retrieve Configuration Request message.
Description Data (Hex) Packet
Info
Ethernet
II
IPv4
UDP
Source MAC:
Destination MAC:
Type:
Version:
00:12:3F:AE:5C:AE (0x 00 12 3F AE 5C AE)
00:0D:8D:00:13:83 (0x 00 0D 8D 00 13 83)
0x0800 - IPv4 (0x 08 00)
0x45 (0x 45)
Header Size:
Type of service:
000----0:
---0---0:
----0-—0:
-----0-0:
------00:
Routine
Normal Delay
Normal throughput
(0x 00)
Total Length:
Identification:
Flags:
00-:
0-0:
Normal reliability
Normal Monetary cost
104 bytes (0x00 68)
2645 (0x00 04)
May Fragment
(0x 00)
Fragment Offset:
Time to Live:
Protocol:
Header Checksum:
Source Address:
Destination Address:
Source Port:
Destination Port:
Length:
Checksum:
EGD:
Last Fragment
0 bytes (0x00 00)
254 (0x FE)
17 [UDP] (0x 11)
8168 correct (0x E8 1F)
105.102.0.200 (0x 69 66 00 C8)
105.102.0.205 (0x 69 66 00 CD)
1025 (0x 04 01)
7937 (0x 1F 01)
84 bytes (0x 00 54)
62188- correct (0x EC F2)
EGD's PDU
Field:
PVN1:
Status:
Offset
PDU Type: 0
Message Flag:
1
Request ID:
2
4
5
Bytes
1
1
2
1
1
Hex code
0x 04
0x 00
0x 11 11
0x 01
0x 00
Page 84 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Message
Length:
6
Producer ID:
Destination
Type:
8
Exchange ID:
12
Production
Period:
16
Reserved:
20
22
Destination address
24
2
4
4
4
2
2
0x 4C 00
0x 00 00
0x 01 00
Reference
User Manual
0x 69 66 00 C8
0x E1 2E 00 00
0x 40 06 00 00
Configuration
State:
Exchange
Length:
Reserved:
UDP/IP Port
Configuration
Type:
Configuration
Sig.:
Mode:
Reserved:
Configuration
Data:
56
58
60
64
66
68
70
72
74
32
2
2
2
2
2
2
4
2
2
0x 69 66 00 C8
00 00 00 00 00
00 00 00 00 00
00 00 00 00 00
00 00 00 00 00
00 00 00 00 00
00 00 00
0x 02 00
0x 78 05
0x 00 00 00 00
0x 46 47
0x 00 00
0x 00 00
0x 02 00
0x 00 00
0x 00 00
This is an example of the module's EGD Configuration Response to the Command
Production Data Unit.
This is the hexadecimal representation of the Retrieve Configuration Response from the above table. It includes the Ethernet II, IPv4, UDP, and within UDP, the EGD Server's
Reply PDU Type 4 depicted in bold font.
00 12 3F AE 5C AE 00 0D 8D 00 13 83 08 00 45 00
00 68 00 04 00 00 FE 11 E8 1F 69 66 00 CD 69 66
00 C8 04 01 1F 01 00 54 EC F2 04 00 11 11 01 00
4C 00 69 66 00 C8 E1 2E 00 00 40 06 00 00 00 00
01 00 69 66 00 C8 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 02 00 78 05 00 00 00 00 46 47 00 00 00 00
02 00 00 00 00 00
ProSoft Technology, Inc. Page 85 of 112
Reference
User Manual
Capabilities PDUs
PDU Type = 9
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Capabilities Request
The Capabilities Request PDU command permits an application program to request the supported capabilities of the EGD implementation on the destination node. A
Capabilities Request sent from a requesting node must be followed by a Capabilities
Response message from the responding node.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD: EGD's PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Reserved:
Message Length:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
Offset
0
1
2
4
5
6
Bytes Hex code
1
1
2
1
1
2
0x 09
0x HH
0x 01
0x HH
0x HH HH
0x HH HH
Page 86 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
PDU Type = 10
Reference
User Manual
Capabilities Response
The Capabilities Response command PDU is sent in response to a Capabilities
Request . This message returns the functional capabilities and limits of the supported
EGD implementation on the responding controller.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD: EGD's PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Status:
Message Length:
Producer ID:
Reserved:
Maximum Exchanges:
Capabilities Bit Mask:
Reserved:
Configuration Type:
Identification String
(up to 80 characters):
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
12
16
20
24
26
28
2
4
5
6
8
Offset
0
1
4
4
4
2
2
XX
2
1
1
2
4
Bytes Hex code
1 0x 0A
1 0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH
0x HH HH
0x HH . . . HH
ProSoft Technology, Inc. Page 87 of 112
Reference
User Manual
Summary PDUs
PDU Type = 7
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Summary Request
The Summary Request PDU command permits an application program to request a summary of the exchanges configured on a given node. This allows a user to get a complete list of all exchanges defined. The Index field is normally 0 and is used to request a block of summaries in nodes which contain a large number of exchanges. A
Summary Request sent from a requesting node must be followed by a Summary
Response message from the responding node.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD: EGD’s PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Reserved:
Message Length:
Index:
Reserved:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
4
5
6
8
9
Offset
0
1
2
Bytes Hex code
1
1
2
1
1
2
1
3
0x 07
0x HH
0x HH HH
0x 01
0x HH
0x HH
0x HH HH
0x 00 00 00
Page 88 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
PDU Type = 8
Reference
User Manual
Summary Response
The Summary Response PDU is used to respond to a Summary Request . This PDU returns a list of exchanges which are currently defined on the responding node. This message is of variable length; the number of summaries, or cells, included in the message is returned in the header of the message. If the number of cells returned is less than the total number of cells, remaining summaries can be retrieved by subsequent requests with a larger index variable.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
EGD’s PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Reserved:
Message Length:
Index:
2
4
5
6
Offset
0
1
8
9
13
2
1
1
2
1
4
2
Bytes
1
1
Hex code
0x 08
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH
0x HH HH HH HH
0x HH HH
Producer ID:
Total Cells:
(Qty of exchange cells defined for this node)
Cells contained in the message:
15 2 0x HH HH
The following six items are referred to as the exchange Cell. Each Cell targets one [EGD Excha nge] command line present in the EGD module’s configuration file. Cell Qty is limited to [EGD Exchange] command lines present in the module’s configuration file.
Producer ID:
17 4 0x HH HH HH HH
Exchange ID:
Mode:
21
25
4
1
0x HH HH HH HH
0x HH
Reserved:
State:
26
27
1
2
0x HH
0x HH HH
Production Period:
29 4 0x HH HH HH HH
ProSoft Technology, Inc. Page 89 of 112
Reference
User Manual
Statistics PDUs
PDU Type = 15
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Statistics Request
The Statistics Request PDU command permits an application program to obtain the current operating statistics of the specified exchange. The exchange must be valid on the destination node. A Statistics Request sent from a requesting node must be followed by a Statistics Response message from the responding node.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD: EGD's PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Reserved:
Message Length:
Producer ID:
Exchange ID:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
Offset
0
1
2
4
5
6
8
12
Bytes Hex code
1
1
2
1
1
2
4
4
0x 0F
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH HH HH
0x HH HH HH HH
Page 90 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
PDU Type = 16
Reference
User Manual
Statistics Response
The Statistics Response PDU command returns the operating statistics for the Producer and Exchange ID specified in the request message.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD: EGD's PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Status:
Message Length:
Producer ID:
Exchange ID:
Configuration Time:
Due Time:
State:
Exchange Length:
Message Count:
Missed Count:
Refresh Error Count:
Reserved:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
8
12
16
20
24
28
32
4
5
6
Offset
0
1
2
36
40
44
4
4
4
4
4
4
4
4
4
4
1
1
2
Bytes Hex code
1
1
2
0x 10
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH HH HH
ProSoft Technology, Inc. Page 91 of 112
Reference
User Manual
Command NAK PDU PDU Type = 18
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Command NAK Response
The Command NAK Response may be sent by a responder to any command received on the command port that is in error. Use of the Command NAK allows the responder to give more precise and detailed information about the nature of the error to the requester.
The Command NAK shall not be sent in response to a NAK message.
The NAK message is returned to indicate a syntactic error in a request message. It should only be used if the request is unintelligible. Thus, whenever possible, the corresponding response to a received request message shall be returned.
Packet
Info
Description
UDP
Data
Source Port:
Destination Port:
Length:
Checksum:
EGD:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
EGD's PDU Field: Offset
PDU Type:
0
Message Flag:
Request ID:
1
2
PVN1:
Producer ID:
4
Status: 5
Message Length:
6
8
Exchange ID:
Error Code:
12
16
Reserved:
Offending
Message:
18
20
36 Error String:
(up to 80 characters)
XX
4
2
2
16
1
2
4
Bytes
1
1
2
1
Hex code
0x 12
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH HH HH
0x HH HH HH HH
0x HH HH
0x HH HH
0x HH . . . HH
0x HH . . . HH
Page 92 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Read PDUs
PDU Type = 32
Reference
User Manual
Read Request
The Read Request PDU is used to request the contents of one or more contiguous groups of memory from a specific peer controller. The header defines parameters which apply to all of the individual cell references in the message. Each cell reference specifies an offset into the specified exchange or target-specific address and the number of bytes to read. Based on the address type, the Domain ID must contain an Exchange and
Producer ID or target-specific address which is valid on the destination node. A Read
Request sent from a requesting node must be followed by a Read Response message from the responding node.
Description Data Packet
Info
UDP Source Port:
7937 (0x 1F01)
Destination Port:
Length:
Checksum:
EGD:
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
EGD’s PDU Field:
PDU Type:
Offset
0
Message Flag:
Exchange ID:
1
Request ID:
PVN1:
2
4
Option Length:
Address Type:
5
Message Length: 6
Configuration Signature:
8
10
Cell Count:
Producer ID:
11
12
16
Time Stamp:
Reserved:
20
28
Bytes
1
1
2
1
1
2
2
1
1
4
4
8
4
Hex code
0x 20
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH
0x HH
0x HH
0x HH HH HH HH
0x HH HH HH HH
0x HH . . . HH
0x HH HH HH HH
The following two items are referred to as the exchange Cell. Each Cell ta rgets one [EGD Exchange] command line present in the EGD module’s configuration file.
Offset: reads the DB Register specified in the Command.
Length: is Bytes count, not Words.
Multiple Cells may be requested dependent on the Cell Count field specified above.
Offset:
Length:
32
34
2
2
0x HH HH
0x HH HH
ProSoft Technology, Inc. Page 93 of 112
Reference
User Manual
PDU Type = 33
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Read Response
The Read Response PDU (Read_Resp) is used to return the contents of one or more contiguous groups of memory from the local node to the requesting controller. The header defines parameters which apply to the all of the individual cell references in the message. Each cell reference specifies an offset into the specified exchange, the number of bytes of data, and the data itself. All data returned must be padded to the nearest 4-byte boundary.
Description Data Packet
Info
UDP Source Port:
7937 (0x 1F01)
7937 (0x 1F01)
Destination Port:
Length:
Checksum:
EGD: xx bytes (0x 00 XX) xxxxx (0x XX XX)
EGD’s PDU Field:
Time Stamp:
Reserved:
Offset
PDU Type:
Message Flag:
0
1
Request ID:
PVN1:
2
4
Option Length:
Address Type:
5
Message Length: 6
Configuration Signature:
8
10
Cell count:
Producer ID:
11
12
Exchange ID:
16
20
28
Bytes
1
1
2
1
1
2
2
1
1
4
4
8
4
Hex code
0x 20
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH
0x HH
0x HH
0x HH HH HH HH
0x HH HH HH HH
0x HH . . . HH
0x HH HH HH HH
The following four items are referred to as the exchange Cell. Each Cell contains data from one [EGD Exchange] command line present in the EGD module’s configuration file.
Offset: reads the DB Register specified in the [EGD Exchange] command.
Length: is Bytes Qty, not Words.
Multiple Cells may be returned dependent on the Cell Count: field specified in the requesting PDU.
Offset: 32 2 0x HH HH
Length:
Data (depends on length requested):
34
36
2
XX
0x HH HH
0x HH . . . HH
Padding (to 32-bit boundary):
XX XX 0x HH HH
Page 94 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Write PDUs
PDU Type = 34
Reference
User Manual
Write Request
The Write Request PDU is used to change the contents of one or more contiguous groups of memory on a specific peer controller. The header defines parameters which apply to all of the individual cell references in the message. Each cell reference specifies an offset into the specified exchange or target-specific address, the number of bytes to write, and the data. Each data field must be padded to the nearest 4-byte boundary.
Based on the address type, the Domain ID must contain an Exchange and Producer ID or target-specific address which is valid on the destination node. A Write Request sent from a requesting node must be followed by a Write Response message from the responding node. See the discussion in the section entitled Exchange Data Handling for information about coherency in the write.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
EGD’s PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Option Length:
Message Length:
5
6
Configuration Signature:
8
Offset
0
1
2
4
Bytes Hex code
1
1
2
1
1
2
2
0x 22
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH
Address Type:
Cell Count:
Producer ID:
Exchange ID:
Time Stamp:
10
11
12
16
20
28
4
8
4
1
1
4
0x HH
0x HH
0x HH HH HH HH
0x HH HH HH HH
0x HH . . . HH
0x HH HH HH HH
Reserved:
The following two items are referred to as the exchange Cell. Each Cell targets one [EGD Exchange] command line present in the EGD module’s configuration file.
Offset: reads the DB Register specified in the Command.
Length: is Bytes count, not Words.
Multiple Cells may be requested dependent on the Cell Count field specified above.
Offset:
32 2 0x HH HH
Length:
Data (depends on length requested):
34
36
2
XX
0x HH HH
0x HH . . . HH
Padding (to 32-bit boundary):
XX XX 0x HH HH
ProSoft Technology, Inc. Page 95 of 112
Reference
User Manual
PDU Type = 35
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Write Response
The Write Response is returned from a destination controller in response to a Write
Request message. It serves as an acknowledgment for the original request. A positive response indicates that all of the data has been written to the responding device. An error response indicates that one or more of the transfers to the responding device failed. Responders shall use all available means to assure that a write is performed in its entirety or not performed at all. Requesting applications are advised that if partial failures of the write can cause problems with the control algorithm, they should include only one cell in each write to assure complete knowledge of the disposition of the Write Request .
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD: EGD’s PDU Field:
PDU Type:
Message Flag:
Request ID:
PVN1:
Option Length:
Message Length:
Configuration
Signature:
Address Type:
Cell count:
Producer ID:
Exchange ID:
Time Stamp:
Reserved:
10
11
12
16
20
28
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
2
4
5
Offset
0
1
6
8
Bytes Hex code
1
1
2
1
1
2
2
0x 23
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH
1
1
4
4
8
4
0x HH
0x HH
0x HH HH HH HH
0x HH HH HH HH
0x HH . . . HH
0x HH HH HH HH
Page 96 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Masked Write PDUs
PDU Type = 36
Reference
User Manual
Masked Write Request
The Masked Write Request PDU is used to change individual bits in one or more bytes in the destination controller. The header defines parameters which apply to all of the individual cell references in the message. Each cell reference specifies which bits to change in the byte specified by the offset given. Based on the address type, the Domain
ID must contain an Exchange and Producer ID or target-specific address which is valid on the destination node. A Masked Write Request sent from a requesting node must be followed by a Masked Write Response message from the responding node. Some devices may not support writing individual bits and others may support writing only one bit at a time. Such devices shall return a status of MEMORY_ACCESS_ERROR for masked write attempts that they do not support.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
EGD’s PDU Field: Offset
PDU Type:
0
Message Flag:
Request ID:
1
2
PVN1: 4
Option Type: 5
Message Length:
6
Configuration
Signature:
8
Address Type:
10
Cell Count:
Producer ID:
11
12
Exchange ID:
16
Time Stamp:
Reserved:
20
28
1
1
4
4
8
4
1
2
2
Bytes
1
1
2
1
Hex code
0x 24
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH
0x HH
0x HH
0x HH HH HH HH
0x HH HH HH HH
0x HH . . . HH
0x HH HH HH HH
The following three items are referred to as the exchange Cell. Each Cell targets one [EGD Exchange] command line present in the EGD module’s configuration file.
Offset: writes into the DB Register specified in the [EGD Exchange] command line.
Mask: example 0x AA AA. Bin 1010101010101010
Data: is ANDed with the Mask Bytes on the target server.
Offset:
Mask:
Data:
32
36
38
4
2
2
0x HH HH HH HH
0x HH HH
0x HH HH
ProSoft Technology, Inc. Page 97 of 112
Reference
User Manual
PDU Type = 37
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Masked Write Response
The Masked Write Response provides an acknowledgment to the Masked Write
Request message. A positive response indicates that all of the data has been written to the responding device. An error response indicates that one or more of the transfers to the responding device failed. Responders shall use all available means to assure that a write is performed in its entirety or not performed at all. Requesting applications are advised that if partial failures of the write can cause problems with the control algorithm, they should include only one cell in each write to assure complete knowledge of the disposition of the write request. Requesters should be aware that some responding devices are not capable of setting more than one bit in a request. Before sending a mask with more than one bit set, the requester should assure that the responding device supports multiple bit writes.
Description Data Packet
Info
UDP Source Port:
Destination Port:
Length:
Checksum:
EGD:
7937 (0x 1F01)
7937 (0x 1F01) xx bytes (0x 00 XX) xxxxx (0x XX XX)
EG
D’s PDU Field:
Time Stamp:
Reserved:
Offset
PDU Type:
Message Flag:
0
1
Request ID:
PVN1:
2
4
Status:
Address Type:
5
Message Length: 6
Configuration Signature:
8
10
Cell count:
Producer ID:
11
12
Exchange ID: 16
20
28
Bytes
1
1
2
1
1
2
2
1
1
4
4
8
4
Hex code
0x 25
0x HH
0x HH HH
0x 01
0x HH
0x HH HH
0x HH HH
0x HH
0x HH
0x HH HH HH HH
0x HH HH HH HH
0x HH . . . HH
0x HH HH HH HH
Page 98 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5.2.3 EGD Data Producer
Reference
User Manual
The EGD driver will generate produced data as defined in the user configuration exchange list. This data is derived from the module’s internal database and is produced at the set frequency defined in the exchange list. The data can be broadcast to all nodes or to a specific node on the network. Up to 700 database registers can be transferred in a single produced message. Therefore, to transfer the whole database would only require 6 messages (4000 word registers in the module’s database).
The internal database is central to the functionality of the module. This database is shared between all the drivers in the module and is used as a conduit to pass information from one device on one network to one or more devices on another network.
This permits data from devices on one communication port to be viewed and controlled by devices on another port.
The producer functionality provided in the EGD driver is used to transfer portions of the module’s database to other EGD nodes on the network. The following diagram describes the flow of data between the producer, the internal database and the remote EGD devices:
ProSoft Technology, Inc. Page 99 of 112
Reference
User Manual
5.2.4 EGD Data Consumer
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
The EGD driver will consume data as defined in the user configuration exchange list.
This data is derived from other nodes on the network and is placed in th e module’s internal database. If a consumer exchange is not received at the specified timeout, the driver will update the status of the exchange. When the driver again receives the exchange, the status will be updated. Exchanges received by the consumer driver that are not defined in the exchange list will be discarded. Up to 700 words of data can be consumed in a single message. Therefore, to fill the whole database with values would only require 6 exchanges (4000 word registers in the module’s database).
The internal database is central to the functionality of the module. This database is shared between all the drivers in the module and is used as a conduit to pass information from one device on one network to one or more devices on another network.
This permits data from devices on one communication port to be viewed and controlled by devices on another port.
The consumer functionality provided in the EGD driver is used to transfer data from other nodes on the network into the module’s database. The following diagram describes the flow of data between the consumer, the internal database and the remote EGD devices:
Page 100 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5.2.5 General Concepts
Reference
User Manual
The following topics describe several concepts that are important for understanding the operation of the MVI56-EGD module.
On power up the module begins performing the following logical functions:
1 Initialize hardware components o o o
Initialize ControlLogix backplane driver
Test and Clear all RAM
Initialize the serial communication ports
2 Reads configuration from Compact Flash Disk
3 Initialize Module Register space
4 Enable Slave Driver on selected ports
After the module has received the Module Configuration, the module will begin communicating with other nodes on the network, depending on the configuration.
Main Logic Loop
Upon completing the power up configuration process, the module enters an infinite loop that performs the functions shown in the following diagram.
ControlLogix Processor Not in Run
Whenever the module detects that the processor has gone out of the Run mode (that is,
Fault or PGM), backplane communications will halt between processor and module but not on the EGD network. When the processor is returned to a running state, the module will resume communication with the Processor.
ProSoft Technology, Inc. Page 101 of 112
Reference
User Manual
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Backplane Data Transfer
The MVI56-EGD module communicates directly over the ControlLogix backplane. Data is paged between the module and the ControlLogix processor across the backplane using the module's input and output images. The update frequency of the images is determined by the scheduled scan rate defined by the user for the module and the communication load on the module. Typical updates are in the range of 1 to 10 milliseconds.
This bi-directional transference of data is accomplished by the module filling in data in the module's input image to send to the processor. Data in the input image is placed in the Controller Tags in the processor by the ladder logic. The input image for the module is set to 250 words. This large data area permits fast throughput of data between the module and the processor.
The processor inserts data into the module's output image to transfer to the module. The module's program extracts the data and places it in the module's internal database. The output image for the module is set to 248 words. This large data area permits fast throughput of data from the processor to the module
The following illustration shows the data transfer method used to move data between the
ControlLogix processor and the MVI56-EGD module.
All data transferred between the module and the processor over the backplane is through the input and output images. Ladder logic must be written in the ControlLogix processor to interface the input and output image data with data defined in the Controller
Tags. All data used by the module is stored in its internal database. The following illustration shows the layout of the database:
Module’s Internal Database Structure
4000 registers for user data 0
Register Data
3999
Page 102 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Reference
User Manual
Data contained in this database is paged through the input and output images by coordination of the ControlLogix ladder logic and the MVI56-EGD module's program. Up to 248 words of data can be transferred from the module to the processor at a time. Up to 247 words of data can be transferred from the processor to the module. The read and write block identification codes in each data block determine the function to be performed or the content of the data block. The block identification codes used by the module are listed in the following table.
Block Range
-1 or 0
1 to 20
2000
9250
9998
9999
Descriptions
Empty Data Blocks
Data Read or Write Blocks
CP Status Data
General Status Data
Warm-boot control block
Cold-boot control block
Each image has a defined structure depending on the data content and the function of the data transfer.
5.2.6 Normal Data Transfer
Normal data transfer includes the paging of the user data found in the module’s internal database in registers 0 to 3999 and the status data. These data are transferred through read (input image) and write (output image) blocks. Refer to the Module Configuration and Ladder Logic sections for a description of the data objects used with the blocks and the ladder logic required. The structure and function of each block is discussed in the following topics.
Block Request from the Processor to the Module
These blocks of data transfer information from the ControlLogix processor to the module and source the input (monitored) data to be used by the remote master. The following table describes the structure of the output image.
Words
0
Description
Block write ID
1 to 200 Output data
201 to 247 Reserved
The Write Block ID is an index value used to determine the location in the module’s database where the data will be placed. Each transfer can move up to 200 words (block offsets 1 to 200) of data.
ProSoft Technology, Inc. Page 103 of 112
Reference
User Manual
Block Response from the Module to the Processor
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
These blocks of data transfer information from the module to the ControlLogix processor and transfer output (control) data sent to the module from the remote master unit. The following table describes the structure of the input image.
204
205
206
207
208
209
210
Words
0
1
2 to 201
202
203
211
212
213
214
215
216
217 to 248
249
Description
Reserved
Block write ID requested
Input data
Program scan counter
Block write counter
Block read counter
Block parse counter
Block error counter
SNTP valid time
SNTP request count
SNTP response count
SNTP computation count
SNTP set count
SNTP timeout error count
SNTP seconds (LSW)
SNTP seconds (MSW)
SNTP microseconds (LSW)
SNTP microseconds (MSW)
Reserved
Block read ID
The Read Block ID is an index value used to determine the location of where the data will be placed in the ControlLogix processor controller tag array of module read data.
Each transfer can move up to 200 words (block offsets 2 to 201) of data. In addition to moving user data, the block also contains status data for the module. This last set of data is transferred with each new block of data and can be used for module diagnostics.
The Write Block ID associated with the block requests data from the ControlLogix processor. Under normal program operation, the module sequentially sends read blocks and requests write blocks. For example, if the application uses three read and two write blocks, the sequence will be as follows:
R1W1 R2W2 R3W1 R1W2 R2W1 R3W2 R1W1
This sequence will continue until interrupted by other write block numbers sent by the controller or operator control through the module’s Configuration/Debug port.
Page 104 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
5.2.7 Special Function Blocks
Reference
User Manual
Special Function blocks are special blocks used to control the module. The current version of the software supports the following blocks.
Code
-1 or 0
1 to 20
2000
9250
9998
9999
Description
Empty data blocks
Data read or write blocks
C/P status data
General status data
Warm boot module
Cold boot module
C/P Status Data Block (2000)
Block 2000 Request
Words
0
1
2
3 to 247
Description
2000 Command Block ID
Number of C/P messages (1 to 17)
First C/P index (0 to 99)
Reserved
Block 2000 Response
Words
0
1
2
3
4 to 17
18 to 31
32 to 45
46 to 59
60 to 73
74 to 87
88 to 101
102 to 115
116 to 129
130 to 143
144 to 157
158 to 171
172 to 185
186 to 199
200 to 213
214 to 227
228 to 241
242 to 248
Description
Reserved
Block write ID requested
Number of C/P messages (0 to 17) Will be set to 0 if error in request.
First C/P index (0 to 99)
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
C/P Status Data
Reserved
ProSoft Technology, Inc. Page 105 of 112
Reference
User Manual
Words
249
Description
2000 Command Block ID
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
9
10
11
12
13
6
7
8
2
3
4
5
Block 2000 C/P Status Data Format
Words
0
1
Description
Status (0=invalid, 1=producing/healthy, 2=pending/unhealthy)
Status bit mapped (bit0=error or invalid, bit1=not time synchronized, bits 2 to 15 reserved)
Number of times C/P (LSW)
Number of times C/P (MSW)
Missed count (LSW)
Missed count (MSW)
Refresh count error (LSW)
Refresh count error (MSW)
Invalid error bit set by producer
Time sync error set by producer
Short message error in exchange
Long message error in exchange
Protocol PVN not set to 1
Configuration signature not set correctly
General Status Block (9250)
Block 9250 Request Block (General Status)
Words
0
1
2 to 63
64 to n
Description
Command/Control Sequence Trigger
9250 Command code value
Command/Control data
Output data
Page 106 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Block 9250 Response Block (General Status)
17
18
19
20
21
22
23
10
11
12
13
14
15
16
24
25 to 248
249
7
8
9
3
4
5
6
Words
0
1
2
Description
Command/Control Sequence Trigger
9250 Command code value
Program scan counter
Product code bytes 0 & 1
Product code bytes 2 & 3
Revision bytes 0 & 1
Revision bytes 2 & 3
Op bytes 0 & 1
Op bytes 2 & 3
Run bytes 0 & 1
Run bytes 2 & 3
Block write counter
Block read counter
Block parse counter
Block error counter
SNTP valid time
SNTP request count
SNTP response count
SNTP computation count
SNTP set count
SNTP timeout error count
SNTP seconds (LSW)
SNTP seconds (MSW)
SNTP microseconds (LSW)
SNTP microseconds (MSW)
Reserved
9250 Command Code Value
Reference
User Manual
Software Reset Block (9998/9999)
This block is sent from the ControlLogix processor to the module (output image) when the module is required to perform a warm-boot (software reset) operation. This block is commonly sent to the module any time configuration data modifications are made. This will cause the module to read the new configuration information and to restart. The following table describes the format of the control block.
Offset
0
1 to 247
Description
9998 or 9999
Spare
Length
1
247
Because many of the parameters set in the configuration file require the program to restart, this function works the same as the cold-boot function. It will cause the module to exit and restart the program.
ProSoft Technology, Inc. Page 107 of 112
Reference
User Manual
5.3 Exchange Configuration Form
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Use this form to design the exchange list for an application.
1
Exchange
Type (C/P)
2
Cast Type
(B/M/U)
3
Database
Address
4
Register
Count
5
Swap
Code
6
Prod/Cons
Time
7
IP
Address
8
Exchange
ID
9 10
CFG Signature
Version
Major Minor
Page 108 of 112 ProSoft Technology, Inc.
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Support, Service & Warranty
User Manual
6 Support, Service & Warranty
6.1 Contacting Technical Support
ProSoft Technology, Inc. is committed to providing the most efficient and effective support possible. Before calling, please gather the following information to assist in expediting this process:
1 Product Version Number
2 System architecture
3 Network details
If the issue is hardware related, we will also need information regarding:
1 Module configuration and associated ladder files, if any
2 Module operation and any unusual behavior
3 Configuration/Debug status information
4 LED patterns
5 Details about the interfaced serial, Ethernet or Fieldbus devices
Note: For technical support calls within the United States, ProSoft’s 24/7 after-hours phone support is available for
urgent plant-down issues.
North America (Corporate Location)
Phone: +1.661.716.5100 [email protected]
Languages spoken: English, Spanish
REGIONAL TECH SUPPORT [email protected]
Latin America Regional Office
Phone: +52.222.264.1814 [email protected]
Languages spoken: Spanish, English
REGIONAL TECH SUPPORT [email protected]
Europe / Middle East / Africa Regional Office
Phone: +33.(0)5.34.36.87.20 [email protected]
Languages spoken: French, English
REGIONAL TECH SUPPORT [email protected]
Asia Pacific Regional Office
Phone: +60.3.2247.1898 [email protected]
Languages spoken: Bahasa, Chinese, English,
Japanese, Korean
REGIONAL TECH SUPPORT [email protected]
For additional ProSoft Technology contacts in your area, please visit: https://www.prosoft-technology.com/About-Us/Contact-Us .
6.2 Warranty Information
For complete det ails regarding ProSoft Technology’s TERMS & CONDITIONS OF SALE,
WARRANTY, SUPPORT, SERVICE AND RETURN MATERIAL AUTHORIZATION
INSTRUCTIONS, please see the documents at: www.prosoft-technology/legal
ProSoft Technology, Inc. Page 109 of 112
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Guide to the MVI56-EGD User Manual
User Manual
ProSoft Technology, Inc.
March 3, 2021
Page 110 of 112
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
Index
[
[EGD Exchanges] • 42
[EGD Multicast Group List] • 48
[Module] • 39
[SNTP Client] • 40
A
Adding the Module to an Existing Project • 57
Adjusting the Input and Output Array Sizes • 32
B
Backplane Data Transfer • 102
Backplane Object • 53
Battery Life Advisory • 4
Block Request from the Processor to the Module • 103
Block Response from the Module to the Processor • 104
Block Status • 55
C
C/P Status Data Block (2000) • 105
Capabilities PDUs • 82, 86
Cast Type • 43
Clearing a Fault Condition • 63
Command NAK PDU • 82, 92
Configuring Module Parameters • 37
Configuring the MVI56-EGD Module • 34
Configuring the RSLinx Driver for the PC COM Port • 20
Connecting Your PC to the ControlLogix Processor • 16
Connecting your PC to the Module • 23
Consumer/Producer Status • 56
Contacting Technical Support • 109
Controller Tags • 51
ControlLogix Processor Not in Run • 101
Creating a New RSLogix 5000 Project • 24
Creating Optional Comment Entries • 38
Creating the Module • 26
CS Major, CS Minor • 46
D
Database Register • 41
Database View Menu • 68, 70
DB Reg • 43
Determining the Firmware Version of Your Processor • 17
Diagnostics and Troubleshooting • 9, 61
Displaying the Current Page of Registers Again • 70
Downloading the Project to the Module Using a Serial COM
Port • 50
Downloading the Sample Program to the Processor • 22
ProSoft Technology, Inc.
Index
User Manual
E
EGD Command Server • 82
EGD Data Consumer • 100
EGD Data Producer • 99
EGD Exchange Command List Example • 47
EGD Menu • 73
Ethernet Configuration • 49
Ethernet Global Data Compatible Devices • 81
Ethernet LED Indicators • 62
Exch ID • 45
Exch Type • 42
Exchange Configuration Form • 108
Exiting the Program • 69
Failure Flag Count • 39
Functional Overview • 81
Functional Specifications • 79
F
G
General Concepts • 101
General Specifications • 77
General Status • 55
General Status Block (9250) • 106
Going Ahead Two Pages of Data • 75, 76
Going Back Two Pages of Data • 75, 76
Guide to the MVI56-EGD User Manual • 9
Hardware Specifications • 78
How to Contact Us • 2
H
I
Import the Ladder Rung • 29
Important Installation Instructions • 3
Installing ProSoft Configuration Builder Software • 13
Installing the Module in the Rack • 15
IP Address • 45
K
Keystrokes • 66
L
Ladder Logic • 51
LED Status Indicators • 62
M
Main Logic Loop • 101
Main Menu • 67
Masked Write PDUs • 82, 97
Module Name • 39
Module Status Data and Variables (ModuleDef) • 53
Module Type • 39
Moving Back Through 5 Pages of Registers • 71
Moving Forward (Skipping) Through 5 Pages of Registers •
71
Page 111 of 112
Index
User Manual
MVI (Multi Vendor Interface) Modules • 3
Navigation • 66
Network Menu • 69, 72
Normal Data Transfer • 103
NTP Server IP Address • 41
N
O
Opening the Database View Menu • 68
Opening the EGD Menu • 68
Opening the Network Menu • 69
Opening the Producer/Consumer List Menu • 73
Opening the Sample Ladder Logic • 17
Opening the Status Data Menu • 74
P
P/C Time • 44
Package Contents • 13
Pinouts • 3
Printing a Configuration File • 38
Producer/Consumer List Menu • 75
Producer/Consumer Status Menu • 76
Product Specifications • 9, 77
ProSoft Technology® Product Documentation • 2
R
Read PDUs • 82, 93
Read Register Count • 39
Read Register Start • 39
Reading Status Data from the Module • 76
Redisplaying the Current Page • 75, 76
Redisplaying the Menu • 67, 74, 75, 76
Reference • 9, 77
Reg Count • 43
Renaming PCB Objects • 37
Resetting Diagnostic Data • 68
Retrieve Configuration PDUs Example • 82, 83
Returning to the Main Menu • 71, 73, 74
Returning to the Previous Menu • 75, 76
Rules for CS Validation • 47
S
Selecting the Slot Number for the Module • 19
Setting Jumpers • 14
Setting Up the Project • 35
SNTP Status • 55
SNTP Support • 68, 80
Software Reset Block (9998/9999) • 107
Special Function Blocks • 105
Start Here • 9, 11
Statistics PDUs • 82, 90
Status Object (InStat) • 54
Summary PDUs • 82, 88
Support, Service & Warranty • 9, 109
Swap Code • 44
System Requirements • 12
Page 112 of 112
MVI56-EGD ♦ ControlLogix Platform
GE Ethernet Global Data Communication Module
T
Time Zone • 41
Transferring the Configuration File from The Module to the
PC • 68
Transferring the Configuration File from the PC to the
Module • 68
Transferring WATTCP.CFG to the Module • 72
Transferring WATTCP.CFG to the PC • 72
Troubleshooting • 63
U
Use Daylight Savings Time • 41
User Data Objects (MNETDATA) • 54
Using ProSoft Configuration Builder • 35
Using ProSoft Configuration Builder (PCB) for Diagnostics •
64
Using the Diagnostic Window in ProSoft Configuration
Builder • 64
Using the RSLogix 5000 v16 Add-On Instruction • 24
V
Viewing Block Transfer Statistics • 67
Viewing Data in ASCII (Text) Format • 71
Viewing Data in Decimal Format • 71
Viewing Data in Floating-Point Format • 71
Viewing Data in Hexadecimal Format • 71
Viewing Module Configuration • 67
Viewing Register Pages • 70
Viewing SNTP Status • 68
Viewing the Multicast Group List • 73
Viewing the Next Page of Data • 75, 76
Viewing the Next Page of Registers • 71
Viewing the Previous Page of Data • 75, 76
Viewing the Previous Page of Registers • 71
Viewing the WATTCP.CFG File on the module • 73
Viewing Version Information • 69
W
Warm Booting the Module • 69
Warnings • 3
Warranty Information • 109
Write PDUs • 82, 95
Write Register Count • 39
Write Register Start • 39
Y
Your Feedback Please • 2
ProSoft Technology, Inc.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 74 Your Feedback Please
- 74 How to Contact Us
- 74 Product Documentation
- 75 Important Installation Instructions
- 75 MVI (Multi Vendor Interface) Modules
- 75 Warnings
- 76 Battery Life Advisory
- 84 System Requirements
- 85 Package Contents
- 85 Installing ProSoft Configuration Builder Software
- 86 Setting Jumpers
- 87 Installing the Module in the Rack
- 88 Connecting Your PC to the ControlLogix Processor
- 89 Opening the Sample Ladder Logic
- 89 Determining the Firmware Version of Your Processor
- 91 Selecting the Slot Number for the Module
- 92 Configuring the RSLinx Driver for the PC COM Port
- 94 Downloading the Sample Program to the Processor
- 95 Connecting your PC to the Module
- 96 Using the RSLogix 5000 v16 Add-On Instruction
- 96 Creating a New RSLogix 5000 Project
- 107 Using ProSoft Configuration Builder
- 107 Setting Up the Project
- 109 Renaming PCB Objects
- 111 [Module]
- 111 Module Name
- 111 Module Type
- 111 Read Register Start
- 111 Read Register Count
- 111 Write Register Start
- 111 Write Register Count
- 111 Failure Flag Count
- 112 [SNTP Client]
- 111 Database Register
- 111 [EGD Exchanges]
- 111 Exch Type
- 111 Cast Type
- 109 DB Reg
- 109 Reg Count
- 110 Swap Code
- 110 P/C Time
- 111 IP Address
- 111 Exch ID
- 112 CS Major, CS Minor
- 111 EGD Exchange Command List Example
- 111 [EGD Multicast Group List]
- 111 Ethernet Configuration
- 111 Downloading the Project to the Module Using a Serial COM Port
- 111 Controller Tags
- 111 Module Status Data and Variables (ModuleDef)
- 111 Backplane Object
- 111 Consumer/Producer Status
- 111 Adding the Module to an Existing Project
- 111 LED Status Indicators
- 111 Ethernet LED Indicators
- 111 Clearing a Fault Condition
- 111 Troubleshooting
- 111 Main Menu
- 111 Database View Menu
- 111 EGD Menu
- 111 General Specifications
- 111 Hardware Specifications
- 111 Functional Specifications
- 111 Functional Overview
- 111 Ethernet Global Data Compatible Devices
- 111 EGD Command Server
- 111 EGD Data Producer
- 111 EGD Data Consumer
- 111 General Concepts
- 112 Normal Data Transfer