Advertisement
Advertisement
User Manual
Original Instructions
Guardmaster EtherNet/IP Network Interface
Catalog Numbers 440R-ENETR (Series B)
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Table of Contents
Product Overview
Installation
Set the IP Address
Download and Install the Addon Profile
Add the AOP to a Studio 5000
Project
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 1
Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Use of the Common Industrial Protocol (CIP) . . . . . . . . . . . . . . . . . . 10
Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . 11
Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . . 11
Support of Data Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 2
Removable Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Chapter 3
Use BootP/DHCP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Use Third-party DHCP and RSLinx Software. . . . . . . . . . . . . . . . . . . 22
Chapter 4
Chapter 5
Add Relays to the ENETR Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 3
4
Table of Contents
AOP Controller Tags
Chapter 6
General Instructions for Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Dual GuardLink (DG) Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
GuardLink Tap Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
GuardLink Tap Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
EM and EMD Fault Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 7
Diagnostic Status Indicators
Studio 5000 Example Logix
Code
Chapter 8
Lock and Unlock a Nonlocking Device. . . . . . . . . . . . . . . . . . . . . . 66
Fault Reset Command to All GuardLink Taps . . . . . . . . . . . . . . . 67
Guard Locking with Fault Reset Command . . . . . . . . . . . . . . . . . 69
Explicit Communication
Specifications
Regulatory Approvals
Chapter 9
Appendix A
440R-ENETR Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Appendix B
Index
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Who Should Use this
Manual
Summary of Changes
Preface
This user manual is a reference guide for the 440R-ENETR Guardmaster®
EtherNet/IP™ network interface, communications interface for Guardmaster safety relays. It describes the procedures that you use to install, wire, configure, troubleshoot, and use this module.
This user manual describes the following:
• The features of the 440R-ENETR interface.
• Examples of how to add the ENETR interface to an existing network.
• Information that can be gathered from the GSR safety relays.
• Information on the control signals that can be sent to the GSR relays.
• RSLogix™ examples of how to use the ENETR interface.
Use this manual if your responsibilities include the design, installation, programming, or troubleshooting of control systems that use the 440R-ENETR
Guardmaster EtherNet/IP network interface.
To add a catalog number 440R-ENETR EtherNet/IP network interface to an existing network successfully, you must be familiar with EtherNet/IP networks and the RSLinx® and BootP/DHCP utilities. You must also have a basic understanding of electrical circuitry and familiarity with safety-related control systems. If you do not, obtain the proper training before using this product.
This manual contains the following new and updated information.
Topic Page
Updated information for the Series B interface Throughout
Updated Additional Resources table
Updated Relay Arrangement text.
Added Important table after
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 5
6
Preface
Definitions
Publication AG-7.1
contains a glossary of terms and abbreviations that are used by Rockwell Automation to describe industrial automation systems. The following is a list of specific terms and abbreviations that are used in this manual.
Term/Abbreviation
AOP (Add-on Profile)
Definition
A collection of parameters of a device that can be added to the Controller Tags of a Rockwell Automation® controller in the Studio 5000® application
(and earlier versions that are called the RSLogix 5000® application).
A type of tap that interfaces with safety devices that have redundant voltage-free contacts. The tap generates pulse tests to detect short circuits to the
DC power supply, short circuits to the DC common, and shorts circuits between the two contacts.
Electrical Mechanical
Safety Switch (EMSS)
ENETR
GSR
The Guardmaster EtherNet/IP network interface (catalog number 440R-ENETR).
A Guardmaster safety relay.
N.C. (Normally Closed) An electrical contact whose normal state (that is, no pressure or electrical potential applied) is in the closed position.
N.O. (Normally Open) An electrical contact whose normal state (that is, no pressure or electrical potential applied) is in the open position.
OLink
PLC
Reaction Time
Recovery Time
Reset
Monitored Manual
Automatic/Manual
The optical communication bus between GSR relays.
A programmable logic controller or a programmable automation controller.
The time between the true states of one input to the ON state of the output.
The time required for the input to be in the LO state before returning to the HI state.
The GSR safety relay offers two types of reset: monitored manual and automatic/manual.
The GSR safety relay performs a reset function when the reset signal goes from OFF to ON and then back to OFF in a prescribed time-period. The reset occurs on the trailing edge.
The GSR safety relay performs a reset function if the reset input is ON. If the reset input is connected directly to 24V, the reset function is executed immediately when the inputs become closed or active. If a contact (push button or equivalent device) is used in the reset input, the reset function is executed on the leading edge of the reset signal (if the inputs are closed or active).
Response Time
Output Signal Switching
Device (OSSD)
The time between the trigger of one input to the OFF state of the output. Throughout this manual, the safety outputs can be described as turning OFF immediately, which means that the safety outputs turn OFF within the response time.
A pair of solid-state signals that are pulled up to the DC source supply. The signals are tested for short circuits to the DC power supply, short circuits to the DC common and shorts circuits between the two signals.
Single Wire Safety (SWS) A unique, safety-rated signal that is sent over one wire to indicate a safety status. The SWS can be used in safety systems that require Category 4,
Performance Level e, per ISO 13849-1 and safety integrity level (SIL) 3, per IEC 62061 and IEC 61508. When an SWS signal is present, this document describes this state as ACTIVE or ON. This signal is also referred to as the logic link signal.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
ENETR Declaration of Conformity, publication SAFETY-CT004
Allen-Bradley Industrial Automation Glossary, publication AG-7.1
Ethernet Design Considerations, publication ENET-RM002
RSLinx Classic Getting Results Guide, publication LINX-GR001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website: rok.auto/certifications
Description
Provides declarations of conformity, certificates, and other certification details.
A glossary of industrial automation terms and abbreviations.
An overview of the design considerations when designing an EtherNet/IP network.
Guides you with information on how to install and navigate the RSLinx Classic software.
Provides general guidelines for installing a
Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page
.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Chapter
1
Product Overview
About the Interface
The Guardmaster EtherNet/IP network interface is catalog number
440R-ENETR (referred to as ‘ENETR interface’ throughout this manual). The
ENETR interface provides connectivity to EtherNet/IP networks from the
Guardmaster safety relays (GSR).
This user manual describes the Series B version of the ENETR interface, which was released in mid-year 2018.
Two significant differences between the Series A and B interface include:
• Webpage was discontinued to meet Internet security requirements.
• A faster optical bus was added to accommodate the DG relay and
GuardLink® designs.
The ENETR interface communicates to the GSR safety relays over two optical buses that are on the side of the housing. EtherNet/IP connectivity is provided through two RJ45 connectors for 2-port pass-through support of daisy chain or ring, and the existing star and tree network topologies.
shows the key features of the ENETR interface and the locations of the two optical buses. Opto bus 3 communicates with the DG safety relay. Opto bus 2 communicates with the DI, DIS, EM, EMD, GLP, GLT, and SI safety relays.
Power Up a System
Each time the interface is powered up, the adapter compares the number of I/O modules present on its backplane to the chassis size value from nonvolatile memory. The adapter does not allow I/O connections until the number of I/O modules present equals the chassis size value minus one for the adapter itself.
On powerup, the interface assigns an address to every Guardmaster safety relay
(up to six) in the backplane. The addressing starts from left to right with the
Guardmaster safety relay to the immediate right of the interface taking the first address of 1.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 7
Chapter 1 Product Overview
RIUP Situations
You must observe the following rules for Guardmaster safety relay system construction and the removal and reinsertion of safety relays.
• Actual Guardmaster safety relay identification (such as, electronic keying) is done when connection establishment requests are received from the controller or controllers. The interface does not allow any I/O connections until the number and type of Guardmaster safety relays match the configuration in the connection request.
• A Guardmaster safety relay that is removed under power disrupts communication of the other Guardmaster safety relays in the system.
Connections to all safety relays are disallowed until power to the entire system, including the interface, is cycled to initiate readdressing the system.
• If safety relays of different types are removed and returned to the wrong locations, attempts to connect to these safety relays fails during verification of the electronic ID (providing that keying has not been disabled).
• If safety relays of the same type are removed and returned to the wrong locations, they accept connections from the controller or controllers once they pass their electronic keying check.
What the Interface Does
The interface performs the following primary tasks:
• Real-time input data (also known as implicit messaging) - the interface serves as a bridge between Guardmaster safety relays and the network
L
7
X
E
N
B
T
EtherNet/IP Network
E
T
E
N
R
Guardmaster
Safety
Relays
E
N
B
T
ControlLogix
I/O
Other
Network
Devices
• Support of messaging data for programming information (also known as
Explicit Messaging)
8 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Interface Features
Product Overview Chapter 1
Features of the interface include:
• Use of EtherNet/IP messages encapsulated within standard TCP/UDP/
IP protocol
• Common application layer with ControlNet and DeviceNet networks
• Interfacing via Category 5 rated twisted-pair cable
• Half/full duplex 10 Mbit or 100 Mbit operation
• DIN Rail mounting for 440R-ENETR interface
• Communication from Guardmaster safety relays on the same DIN rail
(mounted immediately to the right of the interface) as the ENETR interface to controllers on the EtherNet/IP network
IMPORTANT Each safety relay must be mounted to the right of the interface within
5 mm [0.2 in.] of the next safety relay.
• Communication supported by RSLinx software
• IP address that is assigned via standard BOOTP or DHCP tools
• Configuration via RSLogix 5000 software
• No network scheduling required
• No routing tables required
• Support of connections from multiple controllers simultaneously
You must use RSLogix 5000 software to configure these features. For more details on configuration, see
Figure 1 - Key Features of the 440R-ENETR Interface
4
5
2
3
1
6
7
8
2
3
Item Description
1 35 mm (1.38 in.) DIN rail mounting
4
Optical communications bus (OLink) 2.0
Optical communications bus (OLink) 3.0
Removable terminal block
6
7
Item Description
5 Status Indicators
8
EtherNet/IP address rotary switches
Two Ethernet network RJ45 connectors
22.5 mm (0.89 in.) wide housing
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 9
Chapter 1 Product Overview
Hardware/Software
Compatibility
The interface and the applications that are described in this manual are compatible with the following firmware revisions and software releases.
Contact your Rockwell Automation sales office or Allen-Bradley distributor if you need software or firmware updates to use this equipment.
Product Firmware Revision/ Software Release
440R-ENETR interface
1756-ENBT
Logix controller
RSLogix 5000 software
RSLinx software
GSR DI (Catalog number 440R-D22R2)
GSR DIS (Catalog number 440R-D22S2)
GSR EM (Catalog number 440R-EM4R3)
GSR EMD (Catalog number 440R-EM4R2D)
GSR GLP (Catalog number 440R-GL2S1P)
GSR GLT (Catalog number 440R-GL2S2T)
1.xx or later
2.3 or later
19 or later
19 or later
2.52 or later
2 or later
2 or later
2 or later
2 or later
2 or later
2 or later
Use of the Common
Industrial Protocol (CIP)
The adapter uses the Common Industrial Protocol (CIP). CIP is the application layer protocol that is specified for EtherNet/IP, the Ethernet Industrial Protocol, and for ControlNet and DeviceNet networks. It is a message-based protocol that implements a relative path to send a message from the producing device in a system to the consuming devices.
The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not store it.
This configuration has the following significant benefits:
• You do not need to configure routing tables in the bridging modules, which greatly simplify maintenance and module replacement.
• You maintain full control over the route that each message takes, which enables you to select alternative paths for the same end device.
10 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Product Overview Chapter 1
Understand the Producer/
Consumer Model
The CIP producer and consumer networking model replaces the old source and destination (master and slave) model. The producer and consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system, a controller does not poll input modules. Instead, they produce (multicast or unicast) their data either upon a change of state (COS) or periodically.
Multicast is the default mode for version 17 Logix and earlier controllers and unicast is the default for version 18 with multicast as a selectable option.
The frequency of update depends upon the options that are chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data, and the controller is a consumer of the data.
The controller also produces data for other controllers to consume. The produced and consumed data is accessible by multiple controllers and other devices over the EtherNet/IP network. This data exchange conforms to the producer and consumer model.
Specify the
Support of Data
Connections
Requested
Packet Interval (RPI)
The Requested Packet Interval or RPI is the update rate that is specified for a particular piece of data on the network. The RPI can be specified for the interface and includes all Guardmaster safety relays in the system.
When you add an interface to the I/O configuration of a controller, you must enter the RPI as a parameter. This value specifies how often to produce the data for that device. For example, if you specify an RPI of 50 ms, it means that every
50 ms the device should send its data to the controller and the controller should send the consumed (output) data to the device.
Use RPIs only for devices that exchange data. For example, a ControlLogix®
EtherNet/IP bridge in the same chassis as the controller does not require an RPI, because it is not a data-producing member of the system. Its use is only as a bridge to remote racks.
TheGuardmaster EtherNet/IP Network Interface supports data connections.
A data connection to the interface is a grouping of data from one or more
Guardmaster safety relays into one block of data that is sent over one connection at the same data rate.
See the EtherNet/IP Design Considerations Reference Manual, publication ENET-RM002 for more information on connections.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 11
Chapter 1 Product Overview
Notes:
12 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Chapter
2
Installation
Relay Arrangement
Mount on DIN Rail
shows a typical setup. The ENETR interface must be at the leftmost position. Up to a maximum of six GSR safety relays can be mounted to the right of the ENETR interface. When OLink 3.x devices (for example, Guardmaster
DG safety relays) are used, they must be located next to the ENETR interface.
The other OLink 2.0 relays can be mounted in any order. The DG safety relay has both OLink 2.0 and 3.x, so it can pass information from OLink 2.0 devices to the
ENETR interface.
Figure 2 - Typical Arrangement of ENETR Interface and GSR Relays
A1 A2
LINK1
MS
LNK1
LNK2
NS
ENETR
C
A
B
S12 S22 S32 S42
A1 A2 S11 S21
S12 S22 S32 S42
A1 A2 S11 S21
PWR/Fault
OUT
IN 1
IN 2
OUT X
IN X
Reset
FB
PWR/Fault
OUT
IN 1
IN 2
OUT X
IN X
Reset
FB
Config/Set
DG
Reset
Sel./Save
8
9
7
6
0
5
1
2
4
3
Time
X1 X2 X3 X4
13 14 23 24
Config/Set
DG
Reset
Sel./Save
7
8
9
6
0
5
1
2
4
3
Time
X1 X2 X3 X4
13 14 23 24
LINK2
S12 S22 S32 S42
A1 A2 S11 S12
PWR/Fault
S12 S22 S32 S42
A1 A2 S11 S12
PWR/Fault
IN1
IN2
Logic IN
OUT
LOGIC
8
7
6 5
0 1
2
3
4
IN1
IN2
Logic IN
OUT
LOGIC
8
7
6 5
0 1
2
4
3
A1
33 34 43 44
A1 A2 S11 S12
PWR/Fault
Logic IN
OUT
33 34 43 44
37 38 47 48
A1 A2 B1 B2
PWR/Fault
B1
Logic IN
OUT
RANGE
9
8
7
TIME
6
10
9
8
7
0
4
1
2
3
5
6
1
2
5
3
4
13 14 23 24
DI
L12 L11 Y32 S34
13 14 23 24
34 44 14 24
DIS
L12 L11 Y32 S34
34 44 14 24
13 14 23 24
EM
L12 L11 X32
13 14 23 24
EMD
L12 L11 X32
17 18 27 28
Locate DG safety relays closest to the ENETR interface
Max separation between relays is 5 mm (0.2 in.).
Follow these steps to mount the ENETR interface on a DIN rail.
1.
Position the adapter vertically above an IEC standard (35x7.5x1 mm
[1.38x0.3x0.04 in.]) DIN rail at a slight angle (DIN rail catalog number
199-DR1; 46277-3).
DIN Rail
DIN Rail Latch
2.
Press down firmly to install the interface on the DIN rail.
To remove your interface from the DIN rail, pry the DIN rail latch downwards until there is separation from the latch and the DIN rail.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 13
Chapter 2 Installation
Removable Terminal Block
The ENETR interface has one removable terminal block. Use a screwdriver (or
your thumb) as a lever to remove the blocks. As shown in Figure 3
, insert the screwdriver into the slot and pry up.
Figure 3 - Terminal Block Removal
Power Connections
The ENETR interface requires only a 24V DC connection and common.
Connect 24V DC to terminal A1 and the 24V common to terminal A2 as shown
.
The 24V supply must provide power to the ENETR interface and the GSR relays that it is monitoring. If a power cycle is required to clear a fault on a GSR relay, then power also has to be cycled to the ENETR interface to re-establish the optical link communications. Having one power supply eliminates the need for two power cycles to clear a fault and re-establish the optical communications.
Figure 4 - Power Connections
Ethernet
RJ45 connector
A1 = +24V DC Supply
A2 = 24V Common
TOP VIEW
Wire Size
Each terminal accommodates copper wire with size from 0.14…2.5 mm2
(26…14 AWG). Use copper wire that withstands 60…75 °C (140…167 °F).
Each terminal can accommodate up to two wires.
Terminal Torque
Torque terminals to 0.4 N•m (4 lb•in).
14 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Network Connections
Installation Chapter 2
The ENETR interface has two network connections, using standard RJ45 connectors. The connection that is labeled LNK1 is on the top of the housing, and the LNK2 connection is on the bottom of the housing. Connection can be made to either LNK1 or LNK2. The network connection is a repeater; the signal
coming into one Link is repeated at the other Link. Figure 5
shows an example of a system with both LNK1 and LNK2 connections.
Figure 5 - Example Showing Link 1 and Link 2 Network Connections
Enclosure Considerations
Most applications require installation in an industrial enclosure to reduce the effects of electrical interference and environmental exposure. Pollution Degree 2 is an environment where normally only non-conductive pollution occurs except that occasionally temporary conductivity that is caused by condensation can be expected. Overvoltage Category II is the load level section of the electrical distribution system. At this level, transient voltages are controlled and do not exceed the impulse voltage capability of the product insulation.
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there can be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that are present and appropriately designed to help prevent personal injury that results from accessibility to live parts. The enclosure must have suitable flameretardant properties to help prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic.
The interior of the enclosure must be accessible only by use of a tool. Subsequent sections of this publication contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
Other helpful publications can be found in Additional Resources on page 6
.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 15
Chapter 2 Installation
Preventing Excessive Heat
For most applications, normal convective cooling keeps the ENETR interface and relays within the specified operating range. Confirm that the specified temperature range is maintained. Spacing of 50.8 mm (2 in.) above, below, and in front of components within an enclosure is usually sufficient for heat dissipation.
In some applications, other equipment inside or outside the enclosure produce a substantial amount of heat. In this case, place blower fans inside the enclosure to help air circulation and to reduce “hot spots” near the ENETR interface and safety relays.
Additional cooling provisions might be necessary when high ambient temperatures are encountered. Do not bring in unfiltered outside air. Place the controller in an enclosure to help protect it from a corrosive atmosphere.
Harmful contaminants or dirt could cause improper operation or damage to components. In extreme cases, the use air conditioning to help protect against heat buildup within the enclosure may be required.
16 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Chapter
3
Set the IP Address
Overview
Before using your ENETR interface in an EtherNet/IP network, you must configure it with an IP address, subnet mask, and optional Gateway address. The
ENETR interface must be assigned a fixed IP address to maintain continued communication with its network.
There are four ways of assigning a fixed IP address:
• Use the ABC rotary switches to set a ‘Private’ IP address (see
• Use the Rockwell BootP/DHCP tool, version 2.3 or later, that ships with
Studio 5000 (RSLogix 5000) or RSLinx software (see
).
• Use a third-party DHCP server and RSLinx software to set the IP address
(see Use Third-party DHCP and RSLinx Software on page 22 ).
• Have your network administrator configure the ENETR interface via the network DHCP server.
Upon power-up, the ENETR interface reads the switches to determine what actions to take.
Reset to Factory Default
At any time, the ENETR interface can be set to the factory default by setting the
ABC rotary switches to 888 and cycling the power. The ENETR interface is reset after 10 seconds. The indicators remain OFF during the reset process. You must then assign a new IP address by setting the ABC switches and cycling the power again. The ENETR interface comes up as DHCP enabled unless the ABC switches are set to a value of 001…254 or 888.
Set a Private IP Address
Use a small screwdriver to rotate the switches. Align the small arrow on the switch with the number setting you wish to use. Setting the ABC switches to a value of 001 to 254 assigns a fixed private IP address of 192.168.1.ABC.
Figure 6 on page 18 shows an example with the ABC switches set to 163. Upon
power-up, the ENETR interface assigns itself a fixed IP address of 192.168.1.163.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 17
Chapter 3 Set the IP Address
Figure 6 - Network Address Example
A
8
7
9
6
0
5
1
4
2
3
B
8
7
9
6
0
5
1
4
2
3
C
8
7
9
6
0
5
1
4
2
3
When you use the switches to assign an address and set it to 001, the gateway address of the ENETR interface is set to 0.0.0.0, and the subnet mask is
255.255.255.0. When you use the switches to assign an address and set it to a valid number between 002…254, the gateway address of the ENETR interface is set to 192.168.1.1, and the subnet mask is 255.255.255.0.
Since the IP address is fixed, the ENETR interface does not show up on the
DHCP/BootP Utility. The ENETR interface is listed on RSLinx program when a compatible driver is selected.
Use BootP/DHCP Server
When received from the factory, the ABC switches are set to 999, and the
ENETR interface is DHCP enabled. If the ENETR interface was previously assigned an IP address and you want to change it with the BootP/DHCP server, then set the ENETR interface back to its factory default setting. Set the ABC switches to 888 and cycle power and then set the ABC switches to 999 and cycle the power.
TIP The ENETR interface goes into DHCP mode for any switch settings except
1…254 and 888. Common practice is to set the switches to 999 or 000.
The following example uses BootP/DHCP Version 3.02.00. In this example, the network is 192.168.2.xxx.
1.
Upon opening, the BootP/DHCP server may prompt for a network interface similar to the window shown in
. This window does not appear if there is only one network connection available. For this example, the ‘USB2.0 to Fast Ethernet Adapter’ with IP address 192.168.2.10 is selected.
Figure 7 - Select the BootP/DHCP Network Interface
18 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Set the IP Address Chapter 3
2.
The first time the BootP/DHCP server is used, you must select the types of networks you can connect to.
is an example of this request in
Windows 10.
Select Public networks and click Allow Access.
IMPORTANT If the BootP/DHCP server is not functioning properly, check the firewall settings and adjust if necessary.
Figure 8 - Windows Firewall Settings
The BootP/DHCP window appears.
3.
Cycle the power to the ENETR interface and the discovery process begins
, the MAC address of the ENETR interface appears in the Discovery History window and the type of connection is
DHCP.
The # column shows the number of times the ENETR interface has requested an IP address. The Error and warnings section shows that it cannot service the request because you have not told it what address to use.
Double-click the listing to open the New Entry window.
Figure 9 - BootP/DHCP Commissioning Tool
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 19
Chapter 3 Set the IP Address
4.
As shown in
Figure 10 , the New Entry window opens showing the server
IP address and client MAC address. Type in the desired client IP address, hostname, and description.
At this point, only the client IP address is required. Although the other fields are optional, they are imported into the Studio 5000 program.
Click OK.
Figure 10 - New Entry — Set the IP Address
The Commissioning window is updated as shown in Figure 11 .
• The IP address and hostname appear in the Discovery History.
• The new entry appears the Entered Relations.
• The Error and Warning show the IP address as sent to the ENETR interface.
Figure 11 - IP Address Sent to ENETR Interface
20
5.
Right-click the Relation and click Disable BOOTP/DHCP, as shown in
.
IMPORTANT The Disable BOOTP/DHCP button does not work.
Figure 12 - Right-click Relation
In
Figure 13 , the Errors and Warnings show that the Disable command
was successful. Now, you can cycle power to the ENETR interface and this
IP address remains configured.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Set the IP Address Chapter 3
Figure 13 - Disable DHCP Command Successful
6.
Save the relation. This step is optional but highly recommended. This feature allows you to save your list of assigned IP address to help prevent duplicate IP addresses. Also, if you have to repeat this process, you can open the file, and the utility automatically sends the IP address to the device.
Click File and then Save As, as shown in
. Then, follow the instructions in each of the subsequent windows to save the file.
Figure 14 - Save the Relation
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 21
Chapter 3 Set the IP Address
Use Third-party DHCP and
RSLinx Software
To perform this process, the ENETR interface and your host computer must be connected to a third-party DHCP server. See publication LINX-GR001 for more information on RSLinx software.
In the following example, we want to add an ENETR interface to our network, and we want to assign it an IP address of 192.168.2.59.
1.
To reset the ENETR interface to the factory default setting, set the ABC switches to 888 and cycle the power. All indicators remain OFF after the power cycle. Leave the power ON for at least 10 seconds to allow the reset to finish.
2.
Set the ABC switches to 999 and cycle power.
3.
Open your RSLinx software and configure the driver. See
a. Uncheck the Autobrowse feature. (This step is optional.) b. Notice the two connections:
Connection Description
192.168.2.10
The FactoryTalk® Linx connection from your computer. This connection is a USB to
Ethernet adapter.
192.168.2.60
A L83E Logix controller.
4.
To configure the RSLinx drivers, click the icon.
5.
With AB_ETHIP-1 highlighted, click Configure.
6.
Highlight the IP address that is the DHCP server. In this example, the
DHCP server is 10.0.0.183.
7.
Click OK.
8.
Click Close to close the Configure Drives window.
Figure 15 - Configure Driver
22 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Set the IP Address Chapter 3
9.
Click Refresh to update the RSLinx window. After a short while,
shows the ENETR interface with its new IP address, and a new
FactoryTalk Linx connection. The 192.168.2.xx devices cannot be recognized, for now.
10.
Right-click the ENETR interface description.
11.
Select Module Configuration.
Figure 16 - ENETR Interface Assigned an IP Address
12.
In
Figure 17 , click the Port Configuration tab.
13.
Click the Manually configure IP settings.
14.
Enter the desired IP address. In this example, we want 192.168.2.59. Leave the Network Mask as 255.255.255.0 and clear out all other fields.
15.
Click OK.
16.
Click Yes at the next prompt (not shown).
Figure 17 - Reassign the IP Address
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 23
Chapter 3 Set the IP Address
17.
In
Figure 18 , click Refresh. The RSLinx window is updated, the ENETR
interface at 10.0.0.146 can no longer be found.
18.
Click the Configure Driver icon.
19.
With the ETHIP-1 highlighted, click Configure.
20.
Select the Ethernet adaptor with IP address 192.168.2.10.
21.
Click OK.
Figure 18 - Reconfigure the Driver
22.
In
23.
The ENETR interface now has a fixed IP address of 192.168.2.59. You can right-click and delete the two connections that are not used.
Figure 19 - Now Available
24 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Download the AOP
Download and Install the Add-on Profile
Chapter
4
When using Rockwell Automation controllers, an Add-on Profile (AOP) can be added to the Controller Tags to facilitate the use of the performance characteristics of the GSR relays.
To use the ENETR interface in a Logix Designer application, you must download and install the AOP. Download firmware, associated files (such as AOP, DTM, and EDS), and access product release notes from only the Product Compatibility and Download Center (PCDC): http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page
.
Complete the following steps after you go to the Compatibility and Downloads
): https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?crumb=112
1.
Type 440r in the ‘search…’ box.
2.
Click the box that contains the 440R-ENETR.
3.
Click the Downloads icon.
Figure 20 - Compatibility and Downloads Webpage
The available ENETER interface Add-on Profiles are shown ( Figure 21 ).
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 25
Chapter 4 Download and Install the Add-on Profile
4.
Check the v2 option.
5.
Click Downloads
Figure 21 - AOP Offerings – Select v2
The Download Cart window ( Figure 22
) appears.
6.
Click Download Now.
7.
Sign in (not shown)
8.
Accept the terms (not shown).
9.
Use the Managed Download or Direct Download option (not shown)
Figure 22 - Download Now
26
The downloaded file is named 440RAdapter_Rel_Ver_2.00.51.zip, and
shows the desired version ( Figure 23 ).
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
10.
Extract the file.
Figure 23 - ZIP File Downloaded
Download and Install the Add-on Profile Chapter 4
Install the AOP
In this example, the zip file was extracted to a directory with the same name.
1.
In
Figure 24 , expand that directory and expand the Install directory.
2.
To install the AOP, click the MPSetup.exe file.
Figure 24 - Run MPSetup
The installation begins with the Profile Setup Wizard (
).
3.
Click Next.
Figure 25 - Profile Setup Wizard
shows the License Agreement.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 27
Chapter 4 Download and Install the Add-on Profile
4.
Click “I accept...”
5.
Click Next.
Figure 26 - Accept License Agreement
28
shows the Program Maintenance window.
6.
To install from media, click Next.
Figure 27 - Install from Media
shows the module profiles to be installed.
7.
Click Install to begin the installation.
Figure 28 - Click Install to Begin
shows that the install was successful.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
8.
Click Next.
Figure 29 - Installation Succeeded
Download and Install the Add-on Profile Chapter 4
shows the completion of the setup.
9.
Check “Display RSLogix 5000...” to show the release notes after finishing.
10.
Click Finish.
Figure 30 - Finish
The release notes are displayed.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 29
Chapter 4 Download and Install the Add-on Profile
Notes:
30 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Add AOP
Chapter
5
Add the AOP to a Studio 5000 Project
This chapter describes how to add the ENETR Add-on Profile to a Studio 5000
Project. In this example, version 32 of Studio 5000 is used.
Figure 31 shows the Controller Organizer in Studio 5000.
1.
Right-click Ethernet and select New Module.
Figure 31 - New Module
The Select Module Type window opens.
2.
In the “Enter Search Text for Module Type…” field, type ‘440R’, as shown in
Figure 32 . The list of available catalog numbers is reduced to one
module.
3.
Click the 440R-ENETR (the selection is now highlighted in blue).
4.
Check the Close on Create box.
5.
Click Create.
Figure 32 - Select Module Type
Upon creation, the New Module window appears, as shown in
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 31
Chapter 5 Add the AOP to a Studio 5000 Project
6.
Type in the name of the module.
7.
Type in a description, if desired (optional).
8.
Type in the IP address.
9.
The Module Definition box shows the six safety relays as being undefined.
10.
To specify the safety relays, click Change.
IMPORTANT At least one safety relay must be specified.
Figure 33 - New Module – General Setup
shows the possible selections for electronic keying.
11.
Select the desired electronic keying.
• Compatible Module: The series letter must be correct, but the revision level is ignored.
• Disable Keying: The series letter and revision level are not used to determine if the module is correct.
• Exact Match: Both the series letter and revision level must be correct to use the module.
Figure 34 - Electronic Keying
32 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Add Relays to the ENETR
Interface
Add the AOP to a Studio 5000 Project Chapter 5
There are two ways to add relays to the ENETR interface.
• Upload Method
This preferred method requires the physical system to be complete, including relays, taps, and communications with the ENETR interface.
• Manual Method
This method can be used before the physical system being complete. This method requires you to select each relay in its specific location. If a DG safety relay is used, you must also select the type of tap and its specific location in the GuardLink circuit. For more information, see
Upload Method
The steps of the upload method follow steps 1
…
…
1.
).
Figure 35 - Module Definition
2.
To select the upload path, click the ENETR interface (
3.
Click OK.
Figure 36 - Select Path
The Upload Complete message (
Figure 37 on page 34 ) confirms the
operations.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 33
Chapter 5 Add the AOP to a Studio 5000 Project
4.
Click OK.
Figure 37 - Upload Complete
5.
Expand the Relay Bus and confirm the number of relays and type of relay is
correct for each slot ( Figure 38
).
6.
Expand the DG relay (440R-DG2R2T) and confirm how many
GuardLink circuits are used. In this example, a GuardLink circuit is used on input 1. Input 2 is a standard dual channel circuit.
7.
Expand the GuardLink circuit and confirm the number of taps and types of taps are correct for each location.
8.
Click OK.
Figure 38 - Confirm the Configuration
9.
Click Yes to confirm the change to the module definition (
Figure 39 - Confirm Module Definition Change
shows the results of the setup.
34 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Add the AOP to a Studio 5000 Project Chapter 5
10.
Verify the number and type of safety relays.
11.
To add the ENETR interface to the project, click OK.
Figure 40 - Confirm Setup
The ENETR interface is added to the project in the Controller Organizer
(
Figure 41 - ENETR Interface Added to the Controller Organizer
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 35
Chapter 5 Add the AOP to a Studio 5000 Project
Manual Method
The manual method follows steps
. The following steps
come after Figure 34 on page 32
.
In this method, the safety relays and GuardLink taps are manually added to the
ENETR interface.
1.
Right-click Relay Bus (
2.
Click Add Device.
3.
Click one of the devices in the list that appears. You can select multiple devices, but the DG safety relays must be together and closest to the
ENETR interface. For this example, click the DG safety relay.
Figure 42 - Module Definition - Add a DG Safety Relay
The DG relay is added and located in Slot 1 ( Figure 43
). The GuardLink circuits are added with the default status as disabled; both inputs are configured as standard dual-channel.
Figure 43 - DG Relay Added
36 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Add the AOP to a Studio 5000 Project Chapter 5
4.
To add taps to the GuardLink circuit (
[1]GuardLink.
5.
Click Add Device.
6.
Click one of the taps.
Figure 44 - Add a Tap
The tap is added to the GuardLink circuit ( Figure 45
).
IMPORTANT
…
to add more relays and taps. The number and location of the relays and taps must be the same as the physical setup.
7.
Click OK.
Figure 45 -
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 37
Chapter 5 Add the AOP to a Studio 5000 Project
8.
Confirm the change to the change in the module definition (
and click Yes.
Figure 46 - Change Module Definition
The ENETR interface is added to the project in the Controller Organizer
(
Figure 47 - ENETR Interface Added to the Controller Organizer
38 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Chapter
6
AOP Controller Tags
This chapter contains the controller tags and nonrecoverable fault codes for each the ENETR interface, the GSR safety relays, and the GuardLink taps.
The Controller tag names have a prefix, which is shown in the title of each table.
• The name that you have assigned to the ENETR interface replaces the
‘ENETRname’.
• Relay1…Relay6 replaces the ‘Relayx’.
• GuardLink1 or GuardLink2 replaces the ‘GuardLinkx’.
General Instructions for
Faults
The GSR relays have both recoverable and nonrecoverable. External events generally cause the recoverable faults, and most of the recoverable faults can be cleared by following the recommended actions. Internal events generally cause the nonrecoverable faults and require power to be cycled after the recommended action to clear the fault.
Follow these steps when trying to clear a fault:
1.
Perform the recommended action, if stated.
2.
Cycle power to the relay and GuardLink circuit to clear the fault.
3.
If the fault is not cleared, reconfigure the relay.
4.
If the fault continues, try to remove possible sources of electromagnetic interference in the grounding and wiring/cabling.
5.
If the fault persists, replace the relay or tap.
TIP The AOP in Studio 5000 sets the fault code style to Decimal. If a -1 appears as the fault code, change the style to Hexadecimal to get the value.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 39
Chapter 6 AOP Controller Tags
ENETR Input Tags
Table 1 - ENETR Input Tags (Tag name prefix: ENETRname:I.)
Name Data Type Definition
ConnectionFaulted BOOL Indicates whether the ENETR interface is communicating with an Ethernet network.
0 = No connection.
1 = Communication is active.
EthernetLink1Sts BOOL
EthernetLink2Sts BOOL
Indicates whether an Ethernet connection is communicating on LNK1.
0 = No communications.
1 = Communication is active.
Indicates whether an Ethernet connection is communicating on LNK2.
0 = No communications.
1 = Communication is active.
OpticalLinkSts BOOL
OpticalLink2Sts
OpticalLink3Sts
BOOL
BOOL
Indicates whether an ENETR interface is communicating to the GSR relays over Optical Link 2 and Optical Link 3. Cycling the power to an individual GSR relay causes this bit to go to 0. The Module Status (MS) indicator is flashing red. Cycle power to the ENETR interface to restore the communications.
0 = No communications on one or both optical links.
1 = Communication is active on both Optical Link 2 and 3.
Indicates whether an ENETR interface is communicating to the GSR relays over Optical Link 2.
0 = No communications.
1 = Communication is active.
Indicates whether an ENETR interface is communicating to the GSR relays over Optical Link 3.
0 = No communications.
1 = Communication is active.
Relay1Connected BOOL
Relay2Connected
Relay3Connected
Relay4Connected
Relay5Connected
Relay6Connected
BOOL
BOOL
BOOL
BOOL
BOOL
Indicates whether Relay 1 is connected (monitored by Optical Link 2 or 3)
0 = No relay connected.
1 = Relay is connected.
Indicates whether Relay 2 is connected (monitored by Optical Link 2 or 3)
0 = No relay connected.
1 = Relay is connected.
Indicates whether Relay 3 is connected (monitored by Optical Link 2 or 3)
0 = No relay connected.
1 = Relay is connected.
Indicates whether Relay 4 is connected (monitored by Optical Link 2 or 3)
0 = No relay connected.
1 = Relay is connected.
Indicates whether Relay 5 is connected (monitored by Optical Link 2 or 3)
0 = No relay connected.
1 = Relay is connected.
Indicates whether Relay 6 is connected (monitored by Optical Link 2 or 3)
0 = No relay connected.
1 = Relay is connected.
IMPORTANT If six relays are configured on the optical bus (for example, 1. DG, 2. DG, 3. DI, 4.
GLP, 5. EMD, 6. EM) and a FaultReset (or power cycle) is performed on an OLink
3.x device, the tags RelayxConnected behind the OLink 3.x device momentarily go to 0 and come back after the FaultReset (or power cycle).
40 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
ENETR Output Tags
Table 2 - ENETR Output Tags (Tag name prefix: ENETRname:O.Relayx.)
Name
Reset1
FaultReset
GuardLinkx.UnlockCmd
GuardLinkx.LockCmd
GuardLinkx.FaultResetCmd
Data Type Definition
BOOL Sends a reset command to the relay, which is equivalent to pressing a push button connected to the reset terminal on a relay.
The reset command only operates on Optical Link 3.
Those relays that have only Optical Link 2 cannot be reset by the command.
The duration of the reset signal must be between 0.25…3 s.
0 = The reset command is OFF.
1 = The reset command is ON.
BOOL
DINT
Sends a fault reset command to the relay, which is equivalent to cycling the power to the relay.
The reset command only operates on Optical Link 3.
Those relays that have only Optical Link 2 cannot be reset by the command.
0 = The fault reset command is OFF.
1 = The fault reset command is ON.
Sends an unlock command to one or more GuardLink taps.
-1 = sends an unlock command to all GuardLink taps.
0 = Clears the unlock command to all GuardLink taps.
DINT = sends lock command to one or more GuardLink taps.
For example, 23 = sends unlock command to taps 1, 2, 3, and 5.
DINT
DINT
Sends a lock command to one or more GuardLink taps.
-1 = sends a lock command to all GuardLink taps.
0 = Clears the lock command to all GuardLink taps.
DINT = sends lock command to one or more GuardLink taps.
For example, 23 = sends lock command to taps 1, 2, 3, and 5.
Equivalent to cycling the power to a GuardLink tap and also to the device connected to the tap. Use this command to clear a fault on the tap or a fault on a device that is connected to the tap.
Only one tap can be sent a fault reset command at a time.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 41
Chapter 6 AOP Controller Tags
Dual GuardLink (DG) Tags
DG safety relays have GuardLink input capability. The AOP includes tags that
are related to the DG relay (see Table 3 ) and tags related to the GuardLink
circuits (see
Table 3 - DG Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_DG.)
Name
SafetyInput01
SafetyInput02
PtS12
PtS22
PtS32
PtS42
PtS11
PtS21
PtX1
PtX2
PtX3
PtX4
Pt13_14
Pt23_24
ResetRequired1
Data Type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
Definition
Safety Input 1 Status - Indicates whether safety input circuit 1 is ON or OFF.
0 = The input channel is OFF.
1 = The input channel is ON.
Safety Input 2 Status - Indicates whether safety input circuit 2 is ON or OFF.
0 = The input channel is OFF.
1 = The input channel is ON.
S12 Status - Indicates whether terminal S12 of circuit IN01 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S22 Status - Indicates whether terminal S22 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S32 Status - Indicates whether terminal S32 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S42 Status - Indicates whether terminal S42 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S11 Status - Indicates whether terminal S11 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S21 Status - Indicates whether terminal S21 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
X1 Status - Indicates whether terminal X1 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
X2 Status - Indicates whether terminal X2 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
X3 Status - Indicates whether terminal X3 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
X4 Status - Indicates whether terminal X4 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
13/14 Status - Indicates whether output relays contacts at terminals 13/14 are closed or open.
0 = The contacts are open.
1 = The contacts are closed.
23/24 Status - Indicates whether output relays contacts at terminals 23/24 are closed or open.
0 = The contacts are open.
1 = The contacts are closed.
Reset Required Indication – Indicates whether the DG relay shows all monitored input conditions (both IN1 and IN2, as configured) are ON and the safety relay Output is OFF (0).
0 = No reset required.
1 = Waiting for reset signal at terminal X4.
42 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
Table 3 - DG Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_DG.)
Name
ResetHeldOn1
NonRecoverableFault
Fault
FaultCode
Config
ValueRotarySwitch
GuardLink1
GuardLink2
Data Type
BOOL
BOOL
BOOL
INT
INT
Definition
Reset Held On Fault - Indicates that the reset signal at terminal X4 was held ON (1) for longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault
Nonrecoverable Fault Status - Indicates whether the DG safety relay has detected unexpected internal operation.
0 = No fault
1 = Fault
Fault Status - Indicates whether the DG safety relay has detected unexpected operation of a monitored safety device.
0 = No fault
1 = Fault
Fault Code - When a nonrecoverable fault occurs, the DG safety relay generates a value to help indicate the potential cause of the
for a list of DG fault codes.
Configuration ID - Each configuration of the DG safety relay has a unique ID. You can use this tag to determine if the configuration changed.
SINT Value of Rotary Switch - The DG safety relay provides a unique value of each position of the timer rotary switch.
AB:GSR_DG_GL:I:0 GuardLink1 Input and Output
AB:GSR_DG_GL:I:0 GuardLink2 Input and Output
DG Fault Codes
Table 4 - DG Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
01 (01)
02 (02)
03 (03)
04 (04)
06 (06)
10 (0A)
13 (0D)
16 (10)
17 (11)
19 (13)
Description
21 (15)
23 (17)
64 (40)
65 (41)
66 (42)
67 (43)
Recommended Action
Pulse test output A stuck at 24V or 0V Check the wiring and voltage at terminal S11.
Pulse test output B stuck at 24V or 0V Check the wiring and voltage at terminal S21.
Power Fault
Internal VCC (3.3V) is out of range
Terminal A1 is over 27V or under 20V. Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
Internal fault
Internal relay feedback error
Pulse test output cross fault
Terminal fault S11
Terminal fault S21
Terminal fault S22
Follow the general instructions for faults.
The internal force-guided relay has a feedback error. Replace unit.
Check for a short circuit between ChA S11/S12 and ChB S21/S22.
Terminal issue when configured as output like Test Pulse Output A. Check the wiring at terminal S11.
Terminal issue when configured as output like Test Pulse Output B. Check the wiring at terminal S21.
Terminal issue when configured as GuardLink.
Check wiring on terminal S22.
Terminal fault S42
Terminal fault X2
GuardLink-CH[0] no termination
Terminal issue when configured as GuardLink.
Check wiring on terminal S22.
Terminal issue when configured as OSSD/SWS. Check the wiring at terminal X2.
Check and install terminator at end of GuardLink[0] circuit.
GuardLink-CH[1] no termination Check and install terminator at end of GuardLink[1] circuit.
GuardLink-CH[0] no communication Check wiring - brown wire is connected to 24V, blue wire is connected to ground, white wire is connected to S12, and black wire is connected to S22.
GuardLink-CH[1] no communication Check wiring - brown wire is connected to 24V, blue wire is connected to ground, white wire is connected to S32, and black wire is connected to S42.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 43
Chapter 6 AOP Controller Tags
Table 4 - DG Relay Nonrecoverable Fault Codes
277 (115)
278 (116)
279 (117)
280 (118)
281 (119)
282 (11A)
283 (11B)
284 (11C)
269 (10D)
270 (10E)
271 (10F)
272 (110)
273 (111)
274 (112)
275 (113)
276 (114)
285 (11D)
286 (11E)
287 (11F)
261 (105)
262 (106)
263 (107)
264 (108)
265 (109)
266 (10A)
267 (10B)
268 (10C)
Fault Code
Decimal (Hex)
68 (44)
69 (45)
257 (101)
258 (102)
259 (103)
260 (104)
Description
GuardLink-CH[0] more than 32 taps
GuardLink-CH[1] more than 32 taps
GuardLink-CH[0] Tap 1 comm error
GuardLink-CH[0] Tap 2 comm error
GuardLink-CH[0] Tap 3 comm error
GuardLink-CH[0] Tap 4 comm error
GuardLink-CH[0] Tap 5 comm error
GuardLink-CH[0] Tap 6 comm error
GuardLink-CH[0] Tap 7 comm error
GuardLink-CH[0] Tap 8 comm error
GuardLink-CH[0] Tap 9 comm error
GuardLink-CH[0] Tap 10 comm error
GuardLink-CH[0] Tap 11 comm error
GuardLink-CH[0] Tap 12 comm error
GuardLink-CH[0] Tap 13 comm error
GuardLink-CH[0] Tap 14 comm error
GuardLink-CH[0] Tap 15 comm error
GuardLink-CH[0] Tap 16 comm error
GuardLink-CH[0] Tap 17 comm error
GuardLink-CH[0] Tap 18 comm error
GuardLink-CH[0] Tap 19 comm error
GuardLink-CH[0] Tap 20 comm error
GuardLink-CH[0] Tap 21 comm error
GuardLink-CH[0] Tap 22 comm error
GuardLink-CH[0] Tap 23 comm error
GuardLink-CH[0] Tap 24 comm error
GuardLink-CH[0] Tap 25 comm error
GuardLink-CH[0] Tap 26 comm error
GuardLink-CH[0] Tap 27 comm error
GuardLink-CH[0] Tap 28 comm error
GuardLink-CH[0] Tap 29 comm error
GuardLink-CH[0] Tap 30 comm error
GuardLink-CH[0] Tap 31 comm error
Recommended Action
Reduce the number of taps on the GuardLink circuit to no more than 32.
No or corrupted GuardLink channel communications from the specified Tap.
Check the tap and the wiring that is located before the tap.
44 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Table 4 - DG Relay Nonrecoverable Fault Codes
310 (136)
311 (137)
312 (138)
313 (139)
314 (13A)
315 (13B)
316 (13C)
317 (13D)
302 (12E)
303 (12F)
304 (130)
305 (131)
306 (132)
307 (133)
308 (134)
309 (135)
318 (13E)
319 (13F)
320 (140)
512 (200)
513 (201)
294 (126)
295 (127)
296 (128)
297 (129)
298 (12A)
299 (12B)
300 (12C)
301 (12D)
Fault Code
Decimal (Hex)
288 (120)
289 (121)
290 (122)
291 (123)
292 (124)
293 (125)
Description
GuardLink-CH[0] Tap 32 comm error
GuardLink-CH[1] Tap 1 comm error
GuardLink-CH[1] Tap 2 comm error
GuardLink-CH[1] Tap 3 comm error
GuardLink-CH[1] Tap 4 comm error
GuardLink-CH[1] Tap 5 comm error
GuardLink-CH[1] Tap 6 comm error
GuardLink-CH[1] Tap 7 comm error
GuardLink-CH[1] Tap 8 comm error
GuardLink-CH[1] Tap 9 comm error
GuardLink-CH[1] Tap 10 comm error
GuardLink-CH[1] Tap 11 comm error
GuardLink-CH[1] Tap 12 comm error
GuardLink-CH[1] Tap 13 comm error
GuardLink-CH[1] Tap 14 comm error
GuardLink-CH[1] Tap 15 comm error
GuardLink-CH[1] Tap 16 comm error
GuardLink-CH[1] Tap 17 comm error
GuardLink-CH[1] Tap 18 comm error
GuardLink-CH[1] Tap 19 comm error
GuardLink-CH[1] Tap 20 comm error
GuardLink-CH[1] Tap 21 comm error
GuardLink-CH[1] Tap 22 comm error
GuardLink-CH[1] Tap 23 comm error
GuardLink-CH[1] Tap 24 comm error
GuardLink-CH[1] Tap 25 comm error
GuardLink-CH[1] Tap 26 comm error
GuardLink-CH[1] Tap 27 comm error
GuardLink-CH[1] Tap 28 comm error
GuardLink-CH[1] Tap 29 comm error
GuardLink-CH[1] Tap 30 comm error
GuardLink-CH[1] Tap 31 comm error
GuardLink-CH[1] Tap 32 comm error
DG not configured.
DG needs firmware update.
Recommended Action
No or corrupted GuardLink channel communications from the specified Tap.
Check the tap and the wiring that is located before the tap.
Configure the DG relay as stated in publication 440R-UM015 .
Follow the general instructions for faults.
AOP Controller Tags Chapter 6
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 45
Chapter 6 AOP Controller Tags
Table 4 - DG Relay Nonrecoverable Fault Codes
534 (216)
535 (217)
536 (218)
537 (219)
538 (21A)
539 (21B)
540 (21C)
541 (21D)
542 (21E)
543 (21F)
Fault Code
Decimal (Hex)
528 (210)
529 (211)
530 (212)
531 (213)
532 (214)
533 (215)
Description
Rotary switch mismatch (0)
Rotary switch mismatch (1)
Rotary switch mismatch (2)
Rotary switch mismatch (3)
Rotary switch mismatch (4)
Rotary switch mismatch (5)
Rotary switch mismatch (6)
Rotary switch mismatch (7)
Rotary switch mismatch (8)
Rotary switch mismatch (9)
Rotary switch mismatch (10)
Rotary switch mismatch (11)
Rotary switch mismatch (12)
Rotary switch mismatch (13)
Rotary switch mismatch (14)
Rotary switch mismatch (15)
Recommended Action
Wrong rotary switch position detected during startup.
Turn the rotary switch back to the specified position.
GuardLink Tap Tags
Table 5 - GuardLink Taps (Tag name prefix: ENETRname:I.Relayx_GSR_DG.GuardLinkx.)
Name
Active
Trip
DiagnosticActive
Fault
DiagnosticCode
FaultCode
Data Type Definition
BOOL Active Status - Indicates whether the GuardLink circuit is used on IN1.
0 = IN1 is used for standard OSSD or EMSS inputs. When the Active value is zero, all remaining GuardLink tags are zero.
1 = IN1 is used as a GuardLink input.
BOOL
BOOL
Tripped Status - Indicates whether the GuardLink circuit is operational or in a tripped state.
0 = Operational
1 = Tripped
Diagnostic Active - Indicates whether the GuardLink circuit is in a diagnostic state.
0 = All GuardLink taps are not in a faulted (diagnostic) state.
1 = One or more GuardLink taps are in a faulted (diagnostic) state. The tap indicators are flashing red.
BOOL
SINT
SINT
Fault - Indicates whether the GuardLink circuit is in a fault state.
0 = No fault
1 = Fault
Diagnostic Code - See
Table 6 on page 47 for more information.
Fault Code - Indicates the fault code when the GuardLink circuit is faulted. See Table 7 on page 48
.
46 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
Table 5 - GuardLink Taps (Tag name prefix: ENETRname:I.Relayx_GSR_DG.GuardLinkx.)
Name
DeviceTrip
Data Type Definition
DINT Device Trip - When all nodes are operational, DeviceTrip is the same as DeviceCount. When nodes are tripped, DeviceTrip shows a value that reflects all nodes that remain operational. Bit values of zero indicate the nodes that are tripped.
With four operational nodes, the decimal value is 15.
• If nodes 1 and 3 are tripped, the decimal value is 10.
• If only node 2 is tripped, the decimal value is 13.
Status
All Operational
Nodes 1 and 3 tripped 10
Node 2 tripped 13
Decimal Bit 3
15 1
1
1
Bit 2
1
0
1
Bit 1
1
1
0
Bit 0
1
0
1
DeviceDiagnostic
DeviceFault
DeviceCount
DINT
DINT
DINT
Device Diagnostic - Indicates the nodes whose diagnostics are active.
0 = No nodes are in diagnostics.
DINT = one or more taps with active diagnostics
Device Fault - Indicates the nodes that are faulted.
0 = No nodes are faulted.
For example, with four nodes, a 6 means that node 1 and node 4 are faulted.
Device Count - Provides the number of nodes in the GuardLink1 circuit. For example, a 15 means the GuardLink system has four nodes.
GuardLink Tap Diagnostic Codes
Table 6 - Tap Diagnostic Codes
Diagnostic Code
Decimal (Hex)
Description
00 (00)
01 (01)
02 (02)
No diagnostic
Safety signal timeout
Safety signal invalid
03 (03)
04 (04)
64 (40)
65 (41)
Reset input is held ON
Power low warning
Device startup functional test
Device fault functional test
Recommended Action
No action needed
Check status of downstream (furthest away from the DG relay) device.
Cycle the device between safe and active state. Measure the voltage of the safety signals; verify that they are at the switch concurrently.
Check the reset signal duration. Reset must be 250…3000 s.
Evaluate supply voltage. Supply voltage must be 20.4…26.4V at all taps under all electrical load conditions.
Functionally test the monitored device. Cycle the device between safe and active state.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 47
Chapter 6 AOP Controller Tags
GuardLink Tap Fault Codes
Table 7 - GuardLink Tap Nonrecoverable Fault Codes
05 (05)
06 (06)
07 (07)
08 (08)
09 (09)
10 (0A)
11 (0B)
12 (0C)
13 (0D)
14 (0E)
15 (0F)
Fault Code
Decimal (Hex)
00 (00)
01 (01)
02 (02)
Description
No fault.
Short circuit is detected on Channel A of the monitored field device
Short circuit is detected on Channel B of the monitored field device
Recommended Action
No action necessary.
Check wiring. Functionally test the monitored device. Cycle the device between safe and active state.
Power error
Internal memory fault
Failure to detect monitored field device type
Internal memory (ROM) fault
Evaluate supply voltage. Supply voltage must be 20.4… 26.4V at all taps under all electrical load conditions.
Follow the general instructions for faults. See General Instructions for Faults on page 39
.
Runtime memory (RAM) fault.
Internal memory(CPU) fault
Internal test fault
Voltage fault Evaluate supply voltage. Supply voltage must be 20.4…26.4V at all taps under all electrical load conditions.
Channel A and Channel B (OSSD) cross fault Check for a short circuit condition between ChA and ChB of the monitored device.
Internal memory fault
No response on GuardLink
Follow the general instructions for faults. See General Instructions for Faults on page 39
.
Check GuardLink wiring - brown wire is connected to 24V, blue wire is connected to ground, white wire is connected to S12, and black wire is connected to S22.
DI and DIS Tags
Due to similar functionality, the DI and DIS safety relays have the same tags. The
DI safety relay has voltage-free electromechanical outputs, and the DIS safety relay has solid-state outputs.
Table 8 - DI and DIS Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_DI. or ENETRname:I.Relayx_GSR_DIS.)
Name
IN01
IN02
SingleWireSafetyIn
ResetRequired
CrossLoopOK
SafetyOutput
Data Type Definition
BOOL IN01 Status - Indicates whether input circuit 1 is ON or OFF.
0 = The input channel is OFF.
1 = The input channel is ON.
BOOL
BOOL
BOOL
BOOL
IN02 Status - Indicates whether input circuit 2 is ON or OFF.
0 = The input channel is OFF.
1 = The input channel is ON.
Single Wire Safety Input Status - Indicates whether the Single Wire Safety input (L12) is ON or OFF.
0 = The Single Wire Safety input signal is OFF.
1 = The Single Wire Safety input signal is ON.
Reset Required Indication - Turns ON (1) when all monitored input conditions are ON and the safety relay Output is OFF (0).
BOOL
Cross Loop OK - Indicates whether the safety relay is detecting a cross loop fault on one of the input circuits.
0 = Cross loop fault
1 = No fault
Safety Output Status – Indicates whether the safety output channels are ON or OFF.
0 = The safety output channels are OFF.
1 = The safety input channels are ON.
48 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
Table 8 - DI and DIS Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_DI. or ENETRname:I.Relayx_GSR_DIS.)
Name
RecoverableFault
NonRecoverableFault
S12
S22
S32
S42
L12
S34
NonRecoverableFault_A
NonRecoverableFault_B
S12OpenWire
S22OpenWire
S32OpenWire
S42OpenWire
CrossLoopFault
Data Type Definition
BOOL Recoverable Fault Status – Toggles ON (1) for one scan when the DI/DIS safety relay has detected an unexpected operation.
• S12 OpenWire
• S22 OpenWire
• S32 OpenWire
• S42 OpenWire
• Cross Loop Fault
• Invalid Switch Setting
• Reset Held ON
Toggles back to OFF (0), when the unexpected operation status goes to ON (1)
0 = No fault
1 = Fault
BOOL Nonrecoverable Fault Status – Toggles ON (1) for one scan when the DI/DIS safety relay has detected an unexpected internal operation or failed a pulse check. Toggles back to OFF (0), when the nonrecoverable fault tags are assigned a value.
See
NonRecoverableFault_A and NonRecoverableFault_B
fault tags for values.
0 = No fault
1 = Fault
BOOL
BOOL
BOOL
BOOL
S12 Status – Indicates whether terminal S12 of circuit IN01 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S22 Status – Indicates whether terminal S22 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S32 Status – Indicates whether terminal S32 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S42 Status – Indicates whether terminal S42 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
BOOL
BOOL
SINT
SINT
BOOL
BOOL
BOOL
BOOL
BOOL
L12 Status – Indicates whether terminal L12 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S34 Status – Indicates whether terminal S34 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
list of nonrecoverable fault codes.
list of nonrecoverable fault codes.
S12 Open Wire - Indicates S12 open (0) and closed (1) while S22 remained closed (1).
S22 Open Wire - Indicates S22 open (0) and closed (1) while S12 remained closed (1).
S32 Open Wire - Indicates S32 open (0) and closed (1) while S42 remained closed (1).
S42 Open Wire - Indicates S42 open (0) and closed (1) while S32 remained closed (1).
InvalidSwitchSetting
ResetHeldOn
BOOL
BOOL
Cross Loop Fault – Indicates whether the safety relay has detected a cross loop fault on one of the input circuits.
0 = No fault
1 = Cross loop fault
Invalid Switch Settings – Indicates the switch settings changed after power-up of the safety relay.
0 = No fault
1 = Fault
Reset Held On Fault – Indicates the reset signal ON (1) for longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 49
Chapter 6 AOP Controller Tags
DI and DIS Fault Codes
Table 9 - DI and DIS Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
06 (06)
Description Recommended Action
07 (07)
09 (09)
11 (0B)
12 (0C)
13 (0D)
14 (0E)
15 (0F)
16 (10)
17 (11)
32 (20), 33 (21) Internal program fault
34 (22), 35 (23) Rotary switch read error
36 (24)
37 (25)
Cross fault at processor pins for safety outputs
Under voltage detected
38 (26)
Safety mat wiring detected on one of the input pairs while the safety relay is configured for ‘OR’ logic
Mismatch between current switch settings and setting stored in EEPROM during power-up
If there are no safety mats, check the input wiring (safety mat wiring is crossed from normal dual-channel device wiring).
Change the safety relay to ‘AND’ logic.
Change the switch settings to the correct values or reconfigure the relay.
SPI compare fault
ROM test failure
Terminal S12 hardware input fault
Terminal S22 hardware input fault
Fault detected in the other Processor
Follow the general instructions for faults.
Terminal S32 hardware input fault
Terminal S42 hardware input fault
Terminal S34 hardware input fault
Pulse test fault on main transistor
18 (12)
19 (13)
Pulse test fault of transistor for safety output channel 1 (DIS terminal 14, 34)
Pulse test fault of transistor for safety output channel 2 (DIS terminal 24, 44)
20 (14)…30 (1E) Internal plausibility test fault
31 (1F) Different Single Wire Safety input signal is detected at Processor A than
Processor B
At the specified terminal, check the wiring for short circuits to 24V, 0V, or other channels.
Validate the electrical installation and appropriate measures to reduce noise and suppress surges are taken.
Follow the general instructions for faults. See General Instructions for Faults on page 39 .
Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
Follow the general instructions for faults. See General Instructions for Faults on page 39 .
50 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
EM Tags
lists the tags used by the EM expansion module.
Table 10 - EM Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_EM.)
Name
SingleWireSafetyIn
SafetyOutput
Recoverable_Fault
NonRecoverable_Fault
NonRecoverableFault_A
NonRecoverableFault_B
Data Type Definition
BOOL Single Wire Safety Input Status – Indicates whether the Single Wire Safety input (L12) is ON or OFF.
0 = The Single Wire Safety input signal is OFF.
1 = The Single Wire Safety input signal is ON.
BOOL
BOOL
Safety Output Status – Indicates whether the safety output channels are ON or OFF.
0 = The safety output channels are OFF.
1 = The safety input channels are ON.
Recoverable Fault Status – Toggles ON (1) for one scan when the EM has detected an unexpected operation. Toggles back to OFF (0), when the unexpected operation status goes to ON (1).
0 = No fault
1 = Fault
BOOL
SINT
SINT
Nonrecoverable Fault Status – Toggles ON (1) for one scan when the safety relay has detected unexpected internal operation or failed a pulse check. Toggles back to OFF (0), when the nonrecoverable fault tags are assigned a value. See
and
for details.
0 = No fault
1 = Fault
Nonrecoverable Fault Processor A – Indicates that Safety Processor A has recorded a nonrecoverable fault. See
a list of nonrecoverable fault codes.
for a list of nonrecoverable fault codes.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 51
Chapter 6 AOP Controller Tags
EMD Tags
lists the tags that are used by the EMD module with delayed outputs.
Table 11 - EMD Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_EMD.)
Name
SingleWireSafetyIn
B1State
SafetyOutput
Recoverable_Fault
NonRecoverable_Fault
NonRecoverableFault_A
NonRecoverableFault_B
Data Type Definition
BOOL Single Wire Safety Input Status – Indicates whether the Single Wire Safety input (L12) is ON or OFF.
0 = The Single Wire Safety input signal is OFF.
1 = The Single Wire Safety input signal is ON.
BOOL
BOOL
B1 Status – Only when the Safety Output is ON, this tag indicates whether input B1 is ON (connected to 24V DC or to B2) or OFF. When the SafetyOutput tag is 0, B1 State is 0.
0 = The input is OFF.
1 = The input is ON.
Safety Output Status – Indicates whether the safety output channels are ON or OFF.
0 = The safety output channels are OFF.
1 = The safety input channels are ON.
BOOL
BOOL
SINT
SINT
Recoverable Fault Status – Toggles ON (1) for one scan when the EMD has detected an unexpected operation.
0 = No fault
1 = Fault
Nonrecoverable Fault Status – Toggles ON (1) for one scan when the EMD has detected unexpected internal operation or failed a pulse check. See
NonRecoverableFault_A and NonRecoverableFault_B for details.
0 = No fault
1 = Fault
Nonrecoverable Fault Processor A – Indicates that Safety Processor A has recorded a nonrecoverable fault. See
a list of nonrecoverable fault codes.
Nonrecoverable Fault Processor B – Indicates that Safety Processor B has recorded a nonrecoverable fault. See
a list of nonrecoverable fault codes.
Input_Retrigger
InvalidSwitchSetting
B1_B2_Setting_Change
BOOL
BOOL
BOOL
Input Retrigger – Indicates whether a retrigger event occurred when the EMD is configured for non-retriggerable OFF-delay. If the
SWS input at terminal L12 turns ON during the timing period, this tag is set to 1 and the PWR/Fault indicator is green with flashing red
4X. Turn the SWS input OFF during the timing cycle to clear the fault condition.
0 = No fault
1 = Retrigger event occurred.
Invalid Switch Setting – Indicates that either the Range or Time (or both) switch settings have been changed after configuration. The
Recoverable Fault tag changes from 0 to 1 for one scan and then the InvalidSwitchSetting value changes from 0 to 1 and remain at 1 until the switches are returned to their original configured values. The PWR/Fault indicator is green with flashing red 2X when this tag has a value of 1.
0 = No changes
1 = One or both switches have changed
While the Safety Output tag is On, this tag indicates whether the connection between terminals B1 and B2 has changed from its original configuration.
Example: The EMD is configured for OFF-delay with B1/B2 connected (retriggerable). If the B1/B2 connection opens while the safety output is ON, the following events happen:
1. The Recoverable Fault tag changes from 0 to 1.
2. The B1 State tag changes from 1 to 0.
3. The B1_B2_Setting_Change tag changes from 0 to 1.
4. The Recoverable Fault tag changes back from 1 to 0.
5. The PWR/Fault indicator is green with flashing red 3X.
If the B1/B2 connection is remade while the safety output is ON, the same steps happen with the values reversed, and the PWR/Fault indicator changes to solid green.
When the SafetyOutput tag is 0, the B1_B2_Setting_Change tag has a value of 0.
0 = Connection has not changed.
1 = Connection changed.
52 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
EM and EMD Fault Codes
Table 12 - EM and EMD Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
00 (00)
01 (01)
02 (02)
03 (03)
04 (04)
05 (05)
06 (06)
07 (07)
08 (08)
09 (09)
11 (0B)
17 (11)
18 (12)
Description
No fault
RAM test
Stack over-/under-flow
Configuration mismatch between
Processors A and B
Internal timing
EEPROM read/write failure
B1 configuration
Mismatch between current switch settings (switch 1: Range) and setting stored during power-up.
Mismatch between current switch settings (switch 2: Time) and setting stored during power-up.
SPI compare fault
ROM test failure
Pulse test fault on main transistor
Pulse test fault of transistor for safety output channel 1
19 (13) Pulse test fault of transistor for safety output channel 2
20 (14)…24 (18) Internal plausibility test fault
25 (19) Relay contact K1
26 (1A)
27 (1B)
Relay contact K2
Relay contact K3
28 (1C) Relay contact K4
29 (1D), 30 (1E) Internal plausibility test.
31 (1F) Different Single Wire Safety input signal is detected at Processor A than
Processor B
32 (20), 33 (21) Internal program
34 (22), 35 (23) Rotary switch read error
36 (24) Cross fault at processor pins for safety outputs.
37 (25)
38 (26)
42 (30)
Under voltage detected
Fault detected in the other Processor
Capacitor short detected
Recommended Action
No action necessary.
Follow the general instructions for faults. See General Instructions for Faults on page 39 .
Check the wiring to terminal B1.
Change the switch settings to the correct values.
Follow the general instructions for faults. See General Instructions for Faults on page 39 .
Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
Follow the general instructions for faults. See General Instructions for Faults on page 39 .
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 53
Chapter 6 AOP Controller Tags
GLP Tags
lists the tags that are used by the GLP safety relay.
Table 13 - GLP Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_GLP.)
Name
S12_S22_Status
SingleWireSafetyIn
LockRequest_S44
UnLockRequest_S54
RecoverableFault
NonRecoverableFault
OSSD_51
L61
Y32
S11
S21
L11
NonRecoverableFault_A
NonRecoverableFault_B
Data Type Definition
BOOL S12, S22 Status – Indicates whether two channel input channel S12/S22 is ON or OFF.
0 = The two-channel input is OFF.
1 = The two-channel input is ON.
BOOL
BOOL
Single Wire Safety Input Status – Indicates whether the Single Wire Safety input (L12) is ON or OFF.
0 = The Single Wire Safety input signal is OFF.
1 = The Single Wire Safety input signal is ON.
Lock Request S44 Indication – This indication whether the Lock Request input (S44) is ON or OFF.
0 = The Lock Request input is OFF.
1 = the Lock Request input is ON.
BOOL
BOOL
Unlock Request S54 Indication – This indication whether the Unlock Request input (S54) is ON or OFF.
0 = The Unlock Request input is OFF.
1 = the Unlock Request input is ON.
Recoverable Fault Status – Toggles ON (1) for one scan when the GLP safety relay has detected unexpected operation for the following:
• Gate Open Fault
• Invalid Switch Setting
• Lock Request Gate Open Fault
• Overspeed SL2
• Overspeed SL1
• Lock Request Held ON
• Unlock Request Held ON
Toggles back to OFF (0), when the unexpected operation status goes to ON (1).
0 = No fault
1 = Fault
BOOL
BOOL
BOOL
BOOL
Nonrecoverable Fault Status – Toggles ON (1) for one scan when the safety relay has detected unexpected internal operation or failed a pulse check. Toggles back to OFF (0), when the nonrecoverable fault tags are assigned a value. See
NonRecoverableFault_A and NonRecoverableFault_B tags for details.
0 = No fault
1 = Fault
51 Status – Indicates whether terminal 51 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
L61 Status – Indicates whether terminal L61 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
Y32 Status – Indicates whether terminal Y32 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
BOOL
BOOL
BOOL
SINT
SINT
S11 Status – Indicates whether terminal S11 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S21 Status – Indicates whether terminal S21 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
L11 Status – Indicates whether terminal L11 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
Nonrecoverable Fault Processor A – Indicates that Safety Processor A has recorded a nonrecoverable fault. See
for a list of nonrecoverable fault codes.
for a list of nonrecoverable fault codes.
54 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
Table 13 - GLP Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_GLP.)
Name
GateOpenFault
Data Type Definition
BOOL Gate Open Fault - Indicates the Gate inputs, S12, S22, unexpectedly opened.
0 = No Fault
1 = Fault
InvalidSwitchSetting BOOL
LockRequestGateOpenFault BOOL
Invalid Switch Setting Fault – The rotatory switch configuration does not match the configuration that is stored in the safety relay.
Lock Request/Reset Gate Open Fault - Indicates that the gate was open during a lock or reset request.
0 = No fault
1 = Fault
Overspeed_SL2 BOOL
Overspeed_SL1
LockRequestHeldOn
UnLockRequestHeldOn
BOOL
BOOL
BOOL
Overspeed SL2 Fault - Indicates that the monitored speed exceeded the configured maximum speed limit settings for SL2 with the safety gate locked. PWR/Fault indicator is green with red flashing 4X. Reduce the speed to below SL2 and press the reset button to clear the fault.
0 = No fault
1 = Fault
Overspeed SL1 Fault - Indicates that the monitored speed exceeded the configured maximum speed limit settings for SL1 when the gate is unlocked with Logic setting = 3 or 4. Reduce speed below the SL1 setting and press reset to clear the fault.
0 = No fault
1 = Fault
Lock Request Held On Fault – Indicates the lock request signal ON (1) for longer than the maximum time of 3000 ms. The fault is cleared when the signal is removed.
0 = No fault
1 = Fault
Unlock Request Held On Fault – Indicates the unlock request signal ON (1) for longer than the maximum time of 3000 ms. The fault is cleared when the signal is removed.
0 = No fault
1= Fault
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 55
Chapter 6 AOP Controller Tags
GLP Fault Codes
Table 14 - GLP Relay Nonrecoverable Fault Codes
04 (04)
05 (05)
06 (06)
07 (07)
08 (08)
09 (09)
10 (0A)
11 (0B)
15 (0F)
16 (11)
18 (13)
21 (16)
23 (18)
24 (19)
30 (1E)
31 (1F)
32 (20)
33 (21)
Fault Code
Decimal (Hex)
00 (00)
02 (02)
03 (03)
12 (0C)
13 (0D)
14 (0E)
34 (22)
35 (23)
S54 Auto-start fault
Prox sensor cross fault
40 (28)…57 (39) ROM Fault
250 (FA)
Description
No fault
Reserved
Jitter fault
Proximity speed exceeds SL1 when safety gate is unlocked with logic setting = 1
Recommended Action
No action needed.
Follow the general instructions for faults. See
General Instructions for Faults on page 39
.
Check the movement of the sensor targets. Movement must not cause one sensor to turn ON and OFF while the other sensor does not change state.
Proximity Sensor 1 (P12) stuck at High fault.
Proximity Sensor 2 (P22) stuck at High fault.
Proximity Sensors cross fault.
Self-test of terminal 51 failed.
Self-test of terminal L61 failed.
Proximity Input Fault: Both Proximity inputs are Low simultaneously.
Proximity Input Fault: Both Proximity inputs stuck at HIGH simultaneously.
SPI compare fault
Check the alignment and functionality of the specified proximity sensor.
Check the wiring at the specified terminal for short circuits to 24V.
Check connection for short circuit from P12 and P22.
Check connection of 51 or L61 against shorts to 24V or 0V and cross loop shorts from 51 to L61.
Check the alignment and functionality of the Proximity Sensors.
Self-test of Single Wire Safety output at L11.
Current configuration does not agree with the safety relay memory:
Switch settings do not match required initial configuration or X14 and X24 are connected to inputs S12, S22 but they are configured as safety outputs or
L61 and 51 connection has changed after configuration.
Mismatch between current switch settings and setting stored during powerup.
EEPROM read/write Fault
Compare State Fault
L52 Fault
Cross Tran Fault
Gate Open Fault: Indicates the Gate inputs, S12, S22, unexpectedly opened.
Over Speed 1
Terminal S12 hardware input fault
Terminal S22 hardware input fault
Pulse test fault on main transistor
Over voltage detected
Follow the general instructions for faults. See
General Instructions for Faults on page 39
.
Check connection of L11 for short circuits to 24V or 0V.
Change the current configuration back to the stored configuration.
Change the switch settings to the correct values.
Follow the general instructions for faults. See
General Instructions for Faults on page 39
.
Check wiring for shorts to 24V or other channels.
Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
Processor A shows FF. Processor B shows 21.
Check for a short circuit from P12 to P22 while safety outputs are ON.
Follow the general instructions for faults. See
General Instructions for Faults on page 39
.
Reduce the speed to below the SL1 setting. Cycle power.
Processor A shows 00. Processor B shows FA.
PWR/Fault indicator is flashing red 7X.
56 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
GLT Tags
lists the controller tags for the guard locking with time delay safety relay.
Table 15 - GLT Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_GLT.)
Name
S12_S22_Status
SingleWireSafetyIn
LockRequest_S44
UnlockRequest_S54
Recoverable_Fault
NonRecoverable_Fault
OSSD_51
L61_Door_Cntrl
Y32
OSSD_14
OSSD_24
L61_OSSD
L11
NonRecoverableFault_A
NonRecoverableFault_B
Data Type Definition
BOOL S12, S22 Status – Indicates whether two channel input channel S12/S22 is ON or OFF.
0 = The two-channel input is OFF.
1 = The two-channel input is ON.
BOOL
BOOL
Single Wire Safety Input Status – Indicates whether the Single Wire Safety input (L12) is ON or OFF.
0 = The Single Wire Safety input signal is OFF.
1 = The Single Wire Safety input signal is ON.
Lock Request – Indicates whether the lock request input at terminal S44 is ON (24V) or OFF (0V).
0 = The Lock Request input is OFF.
1 = The Lock Request input is ON.
BOOL
BOOL
Unlock Request – Indicates whether the lock request input at terminal S54 is ON (24V) or OFF (0V).
0 = The Unlock Request input is OFF.
1 = The Unlock Request input is ON.
Recoverable Fault Status – Toggles ON (1) for one scan when the GLT safety relay has detected unexpected operation of the following:
• Gate Open Fault
• Cross Loop Fault
• Lock Request Gate Open
• S12 Open Wire
• S22 Open Wire
• Logic, Range, or Time switch settings changed
Toggles back to OFF (0), when the unexpected operation status goes to ON (1).
0 = No fault
1 = Fault
BOOL
BOOL
BOOL
BOOL
Nonrecoverable Fault Status – Toggles ON (1) for one scan when the GLT safety relay has detected an unexpected internal operation or failed a pulse check. Toggles back to OFF (0), when the nonrecoverable fault tags are assigned a value. See
NonRecoverableFault_A and NonRecoverableFault_B tags for details.
0 = No fault
1 = Fault
51 Status – Indicates whether terminal 51 is ON or OFF.
0 = The terminal is OFF. The 51/L61 indicator is ON.
1 = The terminal is ON. The 51/L61 indicator is OFF.
L61 Door Control Status –Indicates whether terminal L61 is ON or OFF.
0 = The terminal is OFF. The 51/L61 indicator is ON.
1 = The terminal is ON. The 51/L61 indicator is OFF.
Y32 Status – Indicates whether terminal Y32 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
BOOL
BOOL
BOOL
BOOL
SINT
SINT
S11 Status – Indicates whether terminal S11 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S21 Status – Indicates whether terminal S21 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
Not used.
L11 Status – Indicates whether terminal L11 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
Nonrecoverable Fault Processor A – Indicates that Safety Processor A has recorded a nonrecoverable fault. See
a list of nonrecoverable fault codes.
Nonrecoverable Fault Processor B – Indicates that Safety Processor B has recorded a nonrecoverable fault. See
a list of nonrecoverable fault codes.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 57
Chapter 6 AOP Controller Tags
Table 15 - GLT Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_GLT.)
Name
CrossLoopFault
S12OpenWire
S22OpenWire
Data Type Definition
BOOL Cross Loop Fault – Indicates that a short circuit is present from terminal S11 to terminal S21, or short circuit from S11 to 24V or from
S21 to 24V.
• Case 1: The input circuit is open (gate is open)
The PWR/Fault indicator is solid green.
Close the gate and press the reset button to clear the fault.
• Case 2: The input circuit is closed (gate is locked)
The PWR/Fault indicator is green with red flashing 5X.
Remove the fault and cycle power to the GLP to clear the fault.
• Case 3: The input circuit is open (E-stop pushed).
The PWR/Fault indicator is solid green.
Remove the fault and release the E-stop to clear the fault.
• Case 4. The input circuit is closed (E-stop released)
The PWR/Fault indicator is solid green.
Remove the fault and cycle the E-stop to clear the fault.
0 = No fault
1 = Fault
BOOL
BOOL
S12 Open Wire Fault – Indicates that the circuit to terminal S12 opened when it was expected to be closed. The PWR/Fault indicator is green with red flashing 5X. Check the wiring at S12 and its source. Open and close the gate to clear the fault.
If the Logic setting is 5…8, then a short circuit from S12 to 0V also sets this bit to 1. The PWR/Fault indicator is solid green. Remove the short circuit and cycle the E-stop button to clear the fault.
0 = No fault
1 = Fault
S22 Open Wire Fault – Indicates that the circuit to terminal S22 opened when it was expected to be closed. The PWR/Fault indicator is green with red flashing 5X. Check the wiring at S22 and its source. Open and close the gate to clear the fault.
If the Logic setting is 5…8, then and a short circuit from S22 to 0V sets this bit. Remove the short circuit and cycle the E-stop to clear the fault.
0 = No fault
1 = Fault
LockRequest_GateOpen BOOL
Gate_Retrigger_Fault
GateOpen_Fault
BOOL
BOOL
Lock Request/Reset Gate Open Fault - Indicates that the gate was open during a lock or reset request. The PWR/Fault indicator is green with red flashing 3X. Close the gate and press the unlock button to clear the fault.
0 = No fault
1 = Fault
Gate Retrigger Fault – With the GLP configured for non-retriggerable delay, the E-stop was released before the time delay expired.
The PWR/Fault indicator is green with red flashing 4X. After the timing cycle expires, cycle the E-stop button to clear the fault.
0 = No fault
1 = Fault
Gate Open Fault - Indicates the gate inputs, S12 and S22, unexpectedly opened, or a cross loop fault occurred when the gate was locked. The PWR/Fault indicator is green with red flashing 5X. Close the gate and press the reset button to clear the fault.
0 = No Fault
1 = Fault
GLT Fault Codes
Table 16 - GLT Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
00 (00)
05 (05)
06 (06)
07 (07)
Description
No Fault
S11 Pulse Test
S21 Pulse Test
OSSD1
Recommended Action
No action needed.
Follow the general instructions for faults. See
General Instructions for Faults on page 39 .
Check for short circuits at terminal 14 to 24V and 0V.
Processor A shows 07. Processor B shows 07 (24V short).
Processor A shows 07. Processor B shows 02 (0V short).
58 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
Table 16 - GLT Relay Nonrecoverable Fault Codes
15 (0F)
17 (21)
19 (13)
20 (14)
21 (15)
22 (16)
23 (17)
24 (18)
25 (19)
29 (1D)
30 (1E)
31 (1F)
32 (20)
33 (21)
40 (28)
50 (32)
51 (33)
52 (34)
53 (35)
54 (36)
55 (37)
56 (38)
57 (39)
58 (40)
Fault Code
Decimal (Hex)
08 (08)
Description
09 (09)
10 (0A)
11 (0B)
12 (0C)
13 (0D)
14 (0E)
Recommended Action
OSSD2
Low Side
High Side
SPI
L11
Locking configuration different from
EEPROM
Switch setting different from EEPROM
Check for short circuits at terminal 24 to 24V and 0V.
Processor A shows FF. Processor B shows 08 (24V short).
Processor A shows 82. Processor B shows 08 (0V short).
Check for short circuits at terminal 51 and L61 to 24V and 0V.
Processor A shows 09. Processor B shows 0A.
Follow the general instructions for faults. See
General Instructions for Faults on page 39 .
Check for short circuits at terminal L11 to 24V and 0V.
Processor A shows FF. Processor B shows 0C.
The connections at terminals 51 and L61 differ from the configuration that is stored in the EEPROM. Return to the previous connections or reconfigure the GLP.
Processor A shows FF. Processor B shows 0C.
Logic, Range, or Time switch setting was incorrect on power-up.
Processor A shows FF. Processor B shows 0E (24V short).
Set switch back to appropriate setting or reconfigure the GLP.
EEPROM
Compare State
L52
Switch 3
CASE 000
Cross Tran
B2 Value Different from EPROM
Follow the general instructions for faults. See
General Instructions for Faults on page 39 .
In Logic Setting 5…8: Upon power-up, the connection to B2 is not as originally configured. Either reconnect 24V or remove 24V from B2 and cycle power to the GLP.
IN1 is open while guard switch is locked
Switch overflow
B2
S12
S22
Main Output Transistor
Overvoltage detected
Follow the general instructions for faults. See
General Instructions for Faults on page 39 .
Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
Processor A shows FF. Processor B shows 21.
ROM
CASE
RAM
Flow control
Unused interrupt
Stack
Wrong revision number (Processor B only)
Array overflow
ADC
Input not equal to other processor
Follow the general instructions for faults. See
General Instructions for Faults on page 39 .
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 59
Chapter 6 AOP Controller Tags
SI Tags
lists the controller tags for the single input safety relay.
Table 17 - SI Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_SI)
Name
IN01
ResetRequired
CrossLoopOK
SafetyOutput
RecoverableFault
NonRecoverableFault
S12
S22
S34
NonRecoverableFault_A
NonRecoverableFault_B
S12OpenWire
S22OpenWire
CrossLoopFault
Data Type Definition
BOOL IN01 Status - Indicates whether input circuit 1 is ON or OFF.
0 = The input channel is OFF.
1 = The input channel is ON.
BOOL
BOOL
Reset Required Indication - This indication turns ON (1) when all monitored input conditions are ON and the safety relay Output is OFF
(0).
Cross Loop OK - Indicates whether the safety relay is detecting a cross loop fault on one of the input circuits.
0 = Cross loop fault
1 = No fault
BOOL
BOOL
BOOL
Safety Output Status – Indicates whether the safety output channels are ON or OFF.
0 = The safety output channels are OFF.
1 = The safety input channels are ON.
Recoverable Fault Status – Toggles ON (1) for one scan when the SI safety relay has detected an unexpected operation for the following:
• S12 OpenWire
• S22 OpenWire
• Cross Loop Fault
• Invalid Switch Setting
• Reset Held ON
Toggles back to OFF (0), when the unexpected operation status goes to ON (1).
0 = No fault
1 = Fault
Nonrecoverable Fault Status – Toggles ON (1) for one scan when the safety relay has detected unexpected internal operation or failed a pulse check. Toggles back to OFF (0), when the nonrecoverable fault tags are assigned a value. See
and
tags for details.
0 = No fault
1 = Fault
BOOL
BOOL
BOOL
SINT
SINT
BOOL
BOOL
BOOL
S12 Status – Indicates whether terminal S12 of circuit IN01 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S22 Status – Indicates whether terminal S22 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S34 Status – Indicates whether terminal S34 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
Nonrecoverable Fault Processor A – Indicates that Safety Processor A has recorded a nonrecoverable fault. See
for a list of nonrecoverable fault codes.
nonrecoverable fault codes.
S12 Open Wire - Indicates S12 open (0) and closed (1) while S22 remained closed (1).
S22 Open Wire - Indicates S22 open (0) and closed (1) while S12 remained closed (1).
InvalidSwitchSetting
ResetHeldOn
BOOL
BOOL
Cross Loop Fault – Indicates whether the safety relay has detected a cross loop fault on one of the input circuits.
0 = No fault
1 = Cross loop fault
Invalid Switch Settings – Indicates the switch settings changed after power-up of the safety relay.
0 = No fault
1 = Fault
Reset Held On Fault – Indicates the reset signal ON (1) for longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault
60 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
AOP Controller Tags Chapter 6
SI Fault Codes
Table 18 - SI Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
00 (00)
01 (01)
02 (02)
03 (03)
04 (04)
05 (05)
06 (06)
07 (07)
16 (10)
17 (11)
18 (12)
19 (13)
20 (14)
21 (15)
22 (16)
23 (17)
08 (08)
09 (09)
10 (0A)
11 (0B)
12 (0C)
13 (0D)
14 (0E)
15 (0F)
Description
No fault
Reserved
Stack over or underflow Fault
Different configuration at Processor A + B
Timing Fault
EEPROM Read or Write Fault
Reserved
Mismatch between current Reset setting and setting stored in EEPROM during power-up
Current Safety Mats configuration unequal the stored value
SPI Compare Fault
Reserved
ROM Test Fault
Terminal S12 hardware input fault
Terminal S22 hardware input fault
Reserved
Reserved
Terminal S34 hardware input fault
Pulse Test Fault of main transistor
Pulse Test Fault of transistor for safety output channel 1
Pulse Test Fault of transistor for safety output channel 2
Plausibility Test Fault of relay channel 1 feedback contact
Plausibility Test Fault of relay channel 2 feedback contact
Plausibility Test Fault of main transistor
Plausibility Test Fault of transistor for safety output channel 1
24 (18)
25 (19)
26 (1A)
27 (1B)
28 (1C)
29 (1D)
30 (1E)
31 (1F)
Plausibility Test Fault of transistor for safety output channel 2
Reserved
Reserved
Reserved
Reserved
Plausibility Fault of Single Wire Safety Output (should be ON, but is OFF)
Plausibility Fault of Single Wire Safety Output (should be OFF, but is ON)
Different Single Wire Safety Input Signal at Processor A + B
32 (20)
33 (21)
34 (22)
35 (23)
Switch / Case Fault
Logical program flow control fault
ADC Fault (reading Potentiometer values)
Fault by reading the Potentiometer values
36 (24)
37 (25)
Cross Fault at processor pins for safety outputs
Fault of voltage reduction of the relay voltage
38 (26) The other Processor has a Fault only
39 (27)…255 (FF) Reserved
Recommended Action
No action needed.
Follow the general instructions for faults. See General Instructions for Faults on page 39
.
Change the switch settings to the correct values or reconfigure the relay.
Follow the general instructions for faults. See General Instructions for Faults on page 39
.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 61
Chapter 6 AOP Controller Tags
Notes:
62 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Indicator Location
Chapter
7
Diagnostic Status Indicators
Figure 48 shows the four diagnostic status indicators on the front face of the
ENETR interface.
Figure 48 - Diagnostic Status Indicators
Module Status
Link 1 Activity/Status
Link 2 Activity/Status
Network Status
Indicator Description
Table 19 on page 64 describes each of the indicators and recommended actions
for each status.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 63
Chapter 7 Diagnostic Status Indicators
Table 19 - Diagnostic Status Indicator Descriptions
Indicator
Module status
Network status
Link 1 or Link 2 Activity / Status
Status
OFF
Solid green
Flashing green
Flashing red/green Module self-test on power-up.
No action necessary.
Flashing red Recoverable fault.
Complete firmware update.
Verify address switches.
Check for monitored safety relay fault - PWR/Fault indicator may be red or Device Fault bit may be 1.
Power was cycled to one of the monitored safety relays.
Cycle power.
Solid red
OFF
Unrecoverable fault; may require device replacement.
Cycle power.
Device is not online.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Flashing green
Solid green
Flashing red
Device is online but has no CIP connections in the established state.
Device online and has CIP connections in the established state.
One or more CIP connections in timed-out state.
Check for Guardmaster safety relay failure and controller operation.
Solid red
OFF
Solid green
Flashing green
Solid yellow
Flashing yellow
Description and Recommended Actions
No power is applied to device.
AOP: ConnectionFaulted = 0
Check the voltage at terminals A1/A2.
Device operating normally.
AOP: ConnectionFaulted = 0
No action necessary.
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Update module configuration (See Upload Method on page 33
).
Check for missing IP address.
Check if automation controller is in program mode.
Cycle power.
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
No link established. Check RJ45 connections at top or bottom of ENETR interface.
One of the following conditions exists:
• A 100 Mbps (full or half-duplex) link exists.
• The ring network is operating normally.
No action necessary.
Transmit or receive activity present on indicated port @ 100 Mbps.
AOP: EthernetLinkxSts = 1 if ConnectionFaulted = 0
AOP: EthernetLinkxSts = 0 if ConnectionFaulted = 1.
No action necessary.
One of the following conditions exists:
• A 10 Mbps (full or half-duplex) link exists.
• The ring network is operating normally.
• AOP: EthernetLinkxSts = 1 if ConnectionFaulted = 0.
• AOP: EthernetLinkxSts = 0 if ConnectionFaulted = 1.
No action necessary.
Transmit or receive activity present on indicated port @ 10 Mbps.
AOP: EthernetLinkxSts = 1 if ConnectionFaulted = 0.
AOP: EthernetLinkxSts = 0 if ConnectionFaulted = 1.
No action necessary.
64 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Chapter
8
Studio 5000 Example Logix Code
GuardLink Commands
This chapter shows sample code for GuardLink commands.
Lock and Unlock
Figure 49 shows sample code to lock and unlock guard locking switches. Rung 9
uses an HMI input to unlock all switches in the GuardLink circuit. First, we move a zero into the LockCmd to clear out any previous lock commands. Then, we move a -1 into the UnlockCmd. The -1 is converted to a 1 for each tap.
Rung 10 uses an HMI input to lock all switches in the GuardLink circuit. First, we move a zero into the UnlockCmd to clear out any previous unlock commands.
Then, we move a -1 into the LockCmd. The -1 is converted to a 1 for each tap.
Rungs 11 and 12 provide an example of unlocking and locking a specific switch.
In this case, we move a 4, which is the third tap, instead of a -1.
Figure 49 - Unlock and Lock Commands
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 65
Chapter 8 Studio 5000 Example Logix Code
Lock and Unlock a Nonlocking Device
When an unlock command is sent to a tap connected to a non-locking device
(like an E-stop), the GuardLink safety signal turns OFF. When a lock command is sent to a tap connected to a non-locking device, the tap turns ON. The following events occur when an unlock command is issued to an individual tap that is not connected to a locking switch.
Figure 50 , an unlock command is sent to tap 4 on Relay 1, GuardLink1. Tap 4 is
an E-stop.
Figure 50 - Unlock Tap 4
1.
The GuardLink safety signal turns OFF.
• The Link indicator on all taps changes to solid red.
• The Device indicator on all taps changes to blinking green. Tap 4 blinks green because the E-stop has not been pressed.
• The DG IN1 indicator changes to solid red.
• The DG output turns OFF.
2.
The following occurs in the Studio 5000 AOP:
• The GuardLink1.DeviceTrip.4 bit remains HI because the E-stop is not pressed.
• The GuardLink1.Trip bit remains LO, because no devices are tripped.
• The Relay1_GSR_DG.PtS12 is LO, because the GuardLink Safety signal is OFF.
• The Relay1_GSR_DG.SafetyInput01 is LO.
The unlock command for tap 4 must be cleared (set to 0), and a lock command must be sent to tap 4 to restore the GuardLink safety signal (
Figure 51 - Lock Tap 4
66 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Studio 5000 Example Logix Code Chapter 8
Fault Reset Command to All GuardLink Taps
The fault reset command is used to power cycle a tap. In GuardLink 1.0, the DG relay does not know if a device connected to a tap is in a faulted state; the DG relay only knows that the tap is OFF. If the tap remains OFF, this state can indicate a device fault. A fault reset command can be sent to the tap to power cycle the tap and the device that is connected to the tap. This action can clear the fault in the device.
The fault reset command cannot be sent to all taps with a rung of code like the lock all and unlock all commands. By using timers, logic can be written to execute the fault reset command to all taps.
Figure 52 on page 68 shows example logic for Studio 5000. A reset command is
sent to a tap. After 3 seconds, the reset command is sent to the next tap. The process is repeated until all taps are reset.
In this example, a momentary push button is used to initiate the subroutine. The
FRC_0 output is latched; this output is for the first tap (Tap 0). The output starts a timer. The timer value is set to 3000 ms; enough time for the tap to execute its startup self-test. After timer is done, the FRC_0 output is unlatched, and the FRC_1 output is latched. The steps are repeated for each tap.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 67
Chapter 8 Studio 5000 Example Logix Code
Figure 52 - Jump to Fault Reset Subroutine
68 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Studio 5000 Example Logix Code Chapter 8
Guard Locking with Fault Reset Command
Figure 53 on page 70 shows an example of how the lock, unlock, and fault reset
commands can be used. In this example, a guard locking interlock switch (like the
TLS-ZR or 440G-LZ) is connected to tap 4. Momentary, normally open push buttons initiate the lock and unlock commands. The logic initiates the fault reset command automatically.
The safety outputs of the guard locking switch can be OFF for various reasons:
• The switch is unlocked.
• The gate is not closed.
• The switch has faulted.
If the gate is not closed and a lock command is issued to the tap, the tap and switch do not fault. If the gate is then closed, the tap does not automatically lock the gate. The operator must issue an unlock command, followed by a lock command.
The GuardLink taps only know that the safety outputs of the switch are OFF.
The example logic allows an operator to attempt to lock the switch twice. If on the third attempt, the switch does not lock, the logic automatically sends a fault reset command to the tap. The fault reset command cycles power to the switch, in an attempt to clear a faulted state. If on the fourth unsuccessful attempt to lock the switch, an inspect flag is set. This flag can be used to inform the operator to inspect the tap, the switch, and its cabling.
You can change the number of attempts and the delay that is allowed before determining the lock command does not work. The delay must be set for at least
200 ms.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 69
Chapter 8 Studio 5000 Example Logix Code
Figure 53 - Logix
70 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Setup
Chapter
9
Explicit Communication
Explicit communication is used when status information is requested from the
ENETR interface or control signals are sent to the ENETR interface only when needed.
This communication method is also used by non-Rockwell Automation controllers.
The examples in this chapter show how to use the explicit communications when the AOP is not loaded into the Project. In this example, a generic Ethernet device is added to the project and the Get Message block is used.
1.
shows the start of the process of adding a new module. In the controller organizer, right-click the Ethernet connection and select New
Module.
Figure 54 - New Module
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 71
Chapter 9 Explicit Communication
2.
In
Figure 55 , scroll down to find the ETHERNET-BRIDGE.
3.
Check Close on Create.
4.
Click Create.
Figure 55 - Select Ethernet-Bridge
72
5.
In
6.
Enter a description (optional).
7.
Enter an IP address.
8.
Click OK.
Figure 56 - New Module Name and IP Address
9.
Create three message type controller tags; one for the configuration, a second for the input and a third for the output.
10.
Create three SINT data type. These data types must be arrays with the values as shown.
Figure 57 - Create Controller Tags
shows an example logic program. Add three rungs with the message block tags. When the program is running, toggle the
HMI control to execute the message function.
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Explicit Communication Chapter 9
11.
Add a rung to read the configuration of the ENETR interface.
12.
Add a rung to read the input values of the ENETR interface.
13.
Add a rung to write control signals to the ENETR interface.
14.
To configure each of the message blocks, click the ellipsis.
Figure 58 - Example Logic Program
15.
In
Figure 59 , click the Communication tab.
16.
Click Browse.
17.
Scroll down to find the Ethernet-Bridge.
18.
Click OK.
IMPORTANT Repeat these steps for each of the message controls.
Figure 59 - Communication Tab
19.
Populate the five fields as shown in Figure 60 to read the ENETR interface
configuration and click OK.
Figure 60 - Config Message Configuration
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 73
Chapter 9 Explicit Communication
20.
Populate the five fields as shown in Figure 61 to read the ENETR interface
input values and click OK.
Figure 61 - Input Message Configuration
21.
Populate the six fields as shown in Figure 62
to write the ENETR interface output values and click OK.
Figure 62 - Output Message Configuration
Configuration Data
The Configuration data can occupy an array of up to a maximum of 390 bytes.
Table 20 on page 75 describes the bytes. The Relay ID shows up in the first
six(0…5) bytes. Since the ENETR interface can only monitor a maximum of six relays, each relay is identified by one byte. Byte 0 is the relay closest to the
ENETR interface (called Slot 1).
Each DG relay can have a maximum of 32 GuardLink taps on each input and each DG relay as two inputs. Therefore, the Slot 1 GuardLink 1 taps are identified with bytes 6…37. Each GuardLink circuit occupies 32 bytes.
IMPORTANT See Knowledgebase article 1087826 for additional configuration information: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1087826
74 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Explicit Communication Chapter 9
Table 20 - Start and End Bytes
Description
Relay ID
Slot 1 GuardLink 1 ID
Slot 1 GuardLink 2 ID
Slot 2 GuardLink 1 ID
Slot 2 GuardLink 2 ID
Slot 3 GuardLink 1 ID
Slot 3 GuardLink 2 ID
Slot 4 GuardLink 1 ID
Slot 4 GuardLink 2 ID
Slot 5 GuardLink 1 ID
Slot 5 GuardLink 2 ID
Slot 6 GuardLink 1 ID
Slot 6 GuardLink 2 ID
198
230
262
294
326
358
Start Byte
0
6
38
70
102
134
166
229
261
293
325
357
389
End Byte
5
37
69
101
133
165
197
shows the IDs in hexadecimal and decimal format for each of the relays and taps.
Table 21 - Config IDs
Type
Relay
Taps
EMD
SI
GLP
GLT
Name
DIS
DI
EM
DG
OSSD 5-pin
OSSD 8-pin
EMSS 5-pin
EMSS 8-pin
Cat. No.
440R-D22S2
440R-D22R2
440R-EM4R2
440R-EM4R2D
440R-S12R2
440R-GL2S2P
440R-GL2S2P
440R-DG2R2T
440S-SF5D
440S-SF8D
440S-MF5D
440S-MF8D
8
9
4
6
Hex
1
2
3
82
83
A
81
84
8
9
4
6
2
3
Dec
1
10
129
130
131
132
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 75
Chapter 9 Explicit Communication
Notes:
76 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Appendix
A
Specifications
440R-ENETR Specifications
Attribute 440R-ENETR
Indicators
Power consumption, max
Power dissipation, max
Thermal dissipation, max
Dimensions (HxWxD), approx.
Enclosure type rating
Terminal screw torque
Weight, approx.
Wiring category
Wire size
Two red/green status indicators:
• Module status
• Network status (Ports 1 and 2 combined)
2.2 W @ 26.4V DC
0.8 W @ 26.4V DC
2.7 BTU/hr @ 26.4V DC
111.4 x 22.5 x 113.6 mm (4.39 x 0.89 x 4.47 in.)
None (open-style)
0.4 N•m (4 lb•in)
180 g (0.4 lb)
– on power ports
– on communications ports
Power connections:
0.34…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated @ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max
Two green/yellow status indicators:
• Link 1 status
• Link 2 status
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702.
North American temp code
IEC temp code
Temperature, operating IEC 60068-2-1 (Test Ad, operating cold), IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock): -20…+55 °C (-4…+131 °F)
Temperature, surrounding air, max 55 °C (131 °F)
Temperature, nonoperating
T6
T6
IEC60068-2-1 (Test Ab, unpackaged nonoperating cold) IEC60068-2-2 (Test Bb, unpackaged nonoperating dry heat), IEC60068-2-14 (Test Na, unpackaged nonoperating thermal shock):
-40…+85 °C (-40…+185 °F)
IEC 60068-2-30 (Test Db, unpackaged damp heat): 5...95% noncondensing Relative humidity
Vibration
Shock, operating
Emissions
ESD immunity
Radiated RF immunity
IEC 60068-2-6 (Test Fc, operating): 5 g @ 10...500 Hz
IEC60068-2-27 (Test Ea, unpackaged shock): 15 g
CISPR 11: Group 1, Class A
IEC61000-4-2: 6 kV contact discharges 8 kV air discharges
EFT/B immunity
IEC 61000-4-3:
• 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse
100% AM @ 900 MHz
• 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4:
• ±4 kV @ 5 kHz on power ports
• ±2 kV @ 5 kHz on communications ports
Surge transient immunity
Conducted RF immunity
IEC 61000-4-5:
• ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
• ±2 kV line-earth (CM) on communications ports
IEC61000-4-6:
• 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 77
Appendix A Specifications
Notes:
78 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Certifications
Appendix
B
Regulatory Approvals
The ENETR interface is not a safety rated device and does not meet the standard requirements of machine safety devices. The ENETR interface is a monitoring device that reports the status of the safety relays. It also monitors to the machine control system so you can take appropriate actions and sends non-safety related commands.
c-UL-us
CE
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
• ENETR Interface Declaration of Conformity
• European Union 2004/108/EC EMC Directive, compliant with:
– EN 61326-1; Meas./Control/Lab., Industrial Requirements
– EN 61000-6-2; Industrial Immunity
– EN 61000-6-4; Industrial Emissions
– EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 79
Appendix B Regulatory Approvals
Notes:
80 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
A
about interface
add
AOP
relays to ENETR
Add-on Profile download
install
AOP add
controller tags
download
install
approval regulatory
arrangement relay
B
BootP/DHCP server
bridge interface
C
certification
CIP
command
GuardLink
Common Industrial Protocol
communication explicit
compatibility hardware
software
configuration data
consumer model
controller tags
AOP
D
daisy chain
data messaging
data connection support
description status indicator
destination device model
consuming
producing
DG fault code
tag
DHCP software third-party
DI fault code
tag
diagnostic code
GuardLink tap
diagnostic status indicator
DIN rail mount
DIS fault code
tag
download
Add-on Profile (AOP)
dual GuardLink fault code
tag
E
EM fault code
tag
EMD fault code
tag
enclosure consideration
ENETR add relays
Ethernet Industrial Protocol
EtherNet/IP
example
Logix code
excessive heat
explicit communication
configuration data
setup
Index
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 81
Index
82
F
factory default reset
fault general instruction
fault code
DI
DIS
dual GuardLink (DG)
EM
EMD
GLP
GLT
GuardLink tap
SI
fault reset command guard locking
GuardLink taps
features interface
firmware version
G
general instruction fault
GLP fault code
tag
GLT fault code
tag
guard locking fault reset command
GuardLink command
GuardLink tap diagnostic code
fault code
fault reset command
tag
H
hardware compatibility
heat excessive
I
implicit messaging
information configuration
programming
input data real-time
input tag
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 install
Add-on Profile (AOP)
installation
interface about
bridge
features
primary tasks
what it does
IP address set
set private
L
location status indicator
lock
nonlocking device
Logix code example
M
manual method
messaging implicit
model destination master and slave
model
master and slave
producer/consumer
mount
DIN rail
multicast
N
network connection
nonlocking device lock/unlock
O
output tag
P
power connection
power up
primary tasks interface
private IP address set
producer model
protocol message-based
R
regulatory approval
reinsertion safety relay
relative path
relay arrangement
removable terminal block
removal safety relay
requested packet interval
reset factory default
RIUP situation
RJ45 connectors
RPI
RSLinx software third-party
S
safety relay reinsertion
removal
set setup
IP address
private IP address
explicit communication
SI fault code
tag
software compatibility
third-party DHCP/RSLinx
software releases
specifications
star
status indicator description
diagnostic
location
Studio 5000 example Logix code
support data connection
system power up
T
tag
DI
DIS
dual GuardLink (DG)
EM
EMD
GLP
GLT
GuardLink tap
input
output
SI
tags controller
terminal block removable
terminal torque
third-party tree
DHCP and RSLinx software
U
unicast
unlock
nonlocking device
upload method
V
version firmware
wire size
W
Index
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019 83
Index
Notes:
84 Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
.
Rockwell Automation Support
Use the following resources to access support information.
Technical Support Center
Local Technical Support Phone
Numbers
Direct Dial Codes
Literature Library
Product Compatibility and Download
Center (PCDC)
Knowledgebase Articles, How-to Videos, FAQs, Chat,
User Forums, and Product Notification Updates.
Locate the phone number for your country.
https://rockwellautomation.custhelp.com/ http://www.rockwellautomation.com/global/support/get-supportnow.page
Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
Installation Instructions, Manuals, Brochures, and
Technical Data.
Get help determining how products interact, check features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/direct-dial.page
http://www.rockwellautomation.com/global/literature-library/ overview.page
http://www.rockwellautomation.com/global/support/pcdc.page
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/ documents/du/ra-du002_-en-e.pdf
.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
.
Allen-Bradley, ControlLogix, FactoryTalk, GuardLink, Guardmaster, Rockwell Automation, Rockwell Software, RSLinx, RSLogix, RSLogix 5000, and Studio 5000 are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 440R-UM009C-EN-P - July 2019
Supersedes Publication 440R-UM009B-EN-P - February 2014 Copyright © 2019 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Advertisement