Allen-Bradley 1794-IE12 is a FLEX I/O analog input module that provides 12 single-ended analog input channels. It is designed for use in industrial environments and offers features such as high accuracy, fast sampling rates, and the ability to convert analog signals to digital data for processing by a PLC or other control system. The module can be used for a variety of applications, including data acquisition, process monitoring, and machine control. With its rugged design and reliable performance, the 1794-IE12 is an ideal choice for demanding industrial applications.
Advertisement
Advertisement
Installation Instructions
FLEX I/O DC Input, Output, and
Input/Output Analog Modules
Catalog Numbers 1794-IE12, 1794-OE12, and 1794-IE8XOE4
Table of Contents
Topic
Important User Information
Environment and Enclosure
Prevent Electrostatic Discharge
North American Hazardous Location Approval
Install Your Analog Input/Output Module
Connect Wiring
Configuring Your Module
Data Table – 1794-IE12
Data Table – 1794-OE12
Data Table – 1794-IE8XOE4
Specifications
Page
2
5
6
3
3
6
11
11
13
14
15
2
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc., with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: identify a hazard, avoid a hazard, and recognize the consequences.
SHOCK HAZARD: Labels may be located on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be located on or inside the equipment (for example, drive or motor) to alert people that surfaces may be dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
3
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-IN041 , for additional installation requirements pertaining to this equipment.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1794-IN106D-EN-E - January 2014
4
FLEX I/O DC Input, Output, and Input/Output Analog Modules
WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: If you connect or disconnect wiring while the field side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (such as aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connections to this equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
5
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations:
Informations sur l’utilisation de cet équipement en environnements dangereux:
Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, hazardous locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent qu’à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
WARNING: EXPLOSION
HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I,
Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
WARNING: RISQUE
D’EXPLOSION
• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I,
Division 2.
• S’assurer que l’environnement est classé non dangereux avant de changer les piles.
Publication 1794-IN106D-EN-E - January 2014
6
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Install Your Analog Input/Output Module
7
3
1
2
6
4
5
45284
1
2
3
4
Description
Keyswitch
Terminal base
FLEXBus connector
Module
5
6
7
Description
Groove
Alignment bar
Latching mechanism
These modules mount on a 1794-TB3G or 1794-TB3GS terminal base.
1.
Rotate the keyswitch ( 1 ) on the terminal base ( 2 ) clockwise to position 3
(1794-IE12), 4 (1794-OE12), or 5 (1794-IE8XOE4) as required.
2.
Make certain the FLEXBus connector ( 3 ) is pushed all the way to the left to connect with the neighboring terminal base/adapter. You cannot install the module unless the connector is fully extended .
3.
Make sure the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base.
4.
Position the module ( 4 ) with its alignment bar ( 5 ) aligned with the groove ( 6 ) on the terminal base.
5.
Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism ( 7 ) is locked into the module.
ATTENTION: During mounting of all devices, be sure that all debris (such as metal chips, and wire strands) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
7
Connect Wiring
Connect the wiring for the 1794-TB3G and 1794-TB3GS terminal bases as shown in the following figure:
Terminal Base Wiring for the 1794-IE12/A Analog Input Module
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
I0 V0 I1 V1 I2 V2 I3 V3 I4 V4 I5 V5 I6 V6 I7 V7
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
B
Chassis
Ground
34
C0 C1 I8 V8 I9 V9 C2 C3 C4 C5 I10 V10 I11 V11 C6 C7 Chassis
Ground
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
+V COM
24V DC
Supply In
NC C8 NC
C
C9
Chassis Grounds for Shields
C10 NC C11 NC +V COM
24V DC
Supply Out
I = Current
V=Voltage
[1794-TB3G shown]
C-0...C-11 = Returns for I or V connections 0...11
+24V DC = Terminals C-34 and C-50
COM = Terminals C-35 and C-51
Chassis ground (CG) = Terminals B-16, B-33, C-38, C-40...C-45, C-47
NC = No connection
For daisy-chaining: Supply in – C-34 (+) and C-35 (-)
Supply out – C-50 (+) and C-51 (-)
ATTENTION: To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a length of
10 m (33 ft) for DC power or analog I/O cabling.
ATTENTION: Do not daisy-chain power or ground from this terminal base unit to any AC or DC digital module terminal base units.
ATTENTION: Do not exceed a length of 10 m (33 ft) for signal cabling.
Publication 1794-IN106D-EN-E - January 2014
8
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Wire Connections for the 1794-IE12/A Analog Input Module
Channel
Input 0
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
-V DC
Common
+V DC
Power
Chassis
Ground
(Shield)
Signal
Type
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Label
Marking
I0
V0
I1
V1
I2
V2
I3
V3
I4
V4
I5
V5
1794-TB3G or 1794-TB3GS
Input
A-0
Common Terminal
B-17
A-1
A-2
A-3
A-4
A-5
A-6
A-7
A-8
A-9
A-10
A-11
B-18
B-23
B-24
B-25
B-26
Current
Voltage
Current
Voltage
Current
I6
V6
I7
V7
I8
A-12
A-13
A-14
A-15
B-19
B-31
B-32
C-37
Voltage
Current
Voltage
Current
Voltage
Current
V8
I9
V9
I10
V10
I11
B-20
B.21
B-22
B-27
B-28
B-29
C-39
C-46
C-48
Voltage V11 B-30
1794-TB3G and 1794-TB3GS – Terminals C-35 and C-51 are internally connected in the terminal base unit.
1794-TB3G and 1794-TB3GS – Terminals C-34 and C-50 are internally connected in the terminal base unit.
1794-TB3G and 1794-TB3GS – Terminals B-16, B-33, C-38, C-40...C-45, and C-47 are internally connected to chassis ground.
ATTENTION: Connect only one current or voltage signal per channel. Do not connect both current and voltage on one channel.
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
9
Wire Connections for the 1794-OE12/A Analog Output Module
Channel
Output 0
Output 1
Output 2
Signal Type
Current
Voltage
Current
Voltage
Current
Label
Marking
I0
V0
I1
V1
I2
A-3
A-4
A-5
A-6
A-7
1794-TB3G or 1794-TB3GS
Output Common Terminal
B-17 A-0
A-1
A-2 B-18
B-23
B-24 Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
V2
I3
V3
I4
V4
I5
V5
I6
V6
I7
V7
I8
V8
I9
V9
I10
V10
A-8
A-9
A-10
A-11
A-12
A-13
A-14
A-15
B-19
B-20
B.21
B-22
B-27
B-28
B-25
B-26
B-31
B-32
C-37
C-39
C-46
Output 11 Current
Voltage
I11
V11
B-29
B-30
C-48
-V DC
Common
1794-TB3G and 1794-TB3GS – Terminals C-35 and C-51 are internally connected in the terminal base unit.
+V DC Power 1794-TB3G and 1794-TB3GS – Terminals C-34 and C-50 are internally connected in the terminal base unit.
Chassis
Ground
(Shield)
1794-TB3G and 1794-TB3GS – Terminals B-16, B-33, C-38, C-40...C-45, and
C-47 are internally connected to chassis ground.
ATTENTION: Use shielded cable for better noise immunity and easier connection to ground. Connect shield to designated ground points on the terminal base unit. Ground at the terminal base unit only.
Publication 1794-IN106D-EN-E - January 2014
10
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Wire Connections for the 1794-IE8XOE4/A Analog 8 Input/4 Output Module
Channel
Output 0
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Output 11
-V DC
Common
+V DC
Power
Chassis
Ground
(Shield)
Signal Type
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Label
Marking
I0
V0
I1
V1
I2
V2
I3
V3
I4
V4
I5
V5
I6
A-8
A-9
A-10
A-11
A-12
A-2
A-3
A-4
A-5
A-6
A-7
1794-TB3G or 1794-TB3GS
Output
A-0
A-1
Common Terminal
B-17
B-18
B-23
B-24
B-25
B-26
B-31
Voltage
Current
Voltage
Current
Voltage
Current
V6
I7
V7
I8
V8
I9
A-13
A-14
A-15
B-19
B-20
B.21
B-32
C-37
C-39
Voltage
Current
Voltage
Current
V9
I10
V10
I11
B-22
B-27
B-28
B-29
C-46
C-48
Voltage V11 B-30
1794-TB3G and 1794-TB3GS – Terminals C-35 and C-51 are internally connected in the terminal base unit.
1794-TB3G and 1794-TB3GS – Terminals C-34 and C-50 are internally connected in the terminal base unit.
1794-TB3G and 1794-TB3GS – Terminals B-16, B-33, C-38, C-40...C-45, and C-47 are internally connected to chassis ground.
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
11
Configuring Your Module
You configure your output/input module by setting bits in the configuration word.
Data Table – 1794-IE12
Dec.
Oct.
Read Words
0 - Input 0
1 - Input 1
2 - Input 2
3 - Input 3
4 - Input 4
5 - Input 5
6 - Input 6
7 - Input 7
8 - Input 8
9 - Input 9
10 - Input 10
11 - Input 11
12 - Status
15
17
PU
14
16
FP
13
15
GF
12
14
11
13
10
12
9
11
NU R11 R10 R9
8
10
R8
7
7
Signed 2’s Complement data Value of Channel 0
Signed 2’s Complement data Value of Channel 1
Signed 2’s Complement data Value of Channel 2
Signed 2’s Complement data Value of Channel 3
Signed 2’s Complement data Value of Channel 4
Signed 2’s Complement data Value of Channel 5
Signed 2’s Complement data Value of Channel 6
Signed 2’s Complement data Value of Channel 7
Signed 2’s Complement data Value of Channel 8
Signed 2’s Complement data Value of Channel 9
Signed 2’s Complement data Value of Channel 10
Signed 2’s Complement data Value of Channel 11
6
6
5
5
4
4
3
3
2
2
1
1
0
0
R7 R6 R5 R4 R3 R2 R1 R0
Write Words
0 - Reserved EN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 - Configuration QS 0 0 0 CAB C89 C67 C45 C23 C01
Where:
PU = Power up bit
FP = Field power fault
GF = General fault
NU = Not used
Rx = Out of range (x = associated channel)
EN = Enable
QS = Quick step bit – allows input filter to be reduced during rapid signal changes.
Cxx = Configuration
Publication 1794-IN106D-EN-E - January 2014
12
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Range Selection Bits for the 1794-IE12, 1794-OE12, and 1794-IE8XOE4
Range
-10...+10V DC < -10.0V or > 10.0V
4...20 mA
Out of Range
< 4.0mA or > 20.0 mA
Range Setting Cxx
Set bits for each channel pair
00 = off
01 = 0...20 mA
10 = 4...20 mA
11 = +10V
(1)
Channel Configuration
C01 for channels 0 and 1
C23 for channels 2 and 3
C45 for channels 4 and 5
C67 for channels 6 and 7
C89 for channels 8 and 9
CAB for channels 10 and 11
0...20 mA < 0.0 mA or > 20.0 mA
(1) xx = associated channel pair
Safe State Selection Bits for the 1794-OE12 and 1794-IE8XOE4
When EN = 0, these bits designate the source of the safe state data for all outputs in the module.
S1/S0 Safe State
Select Source
Safe State Mode Safe State Output Behavior
S1
0
S0
0 Outputs will use Safe State value
0
1
1
1
0
1
Safe State value is in the output words
Reserved (Safe State value is in the output words)
Clear/Reset the outputs, based on range selected
Hold output at its present level
Reserved (Outputs will use Safe State value)
+10V range – Output set to 0V
4...20 mA range – Output set to 4 mA
0...20 mA range – Output set to 0 mA
Outputs will Hold Last State
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
13
Data Table – 1794-OE12
Dec.
Oct.
Read Words
0 - Status
Write Words
0 - Reserved
1 - Output 0
2 - Output 1
3 - Output 2
4 - Output 3
5 - Output 4
6 - Output 5
7 - Output 6
15
17
PU
14
16
FP
13
15
GF
12
14
11
13
10
12
9
11
8
10
7
7
6
6
5
5
4
4
3
3
2
2
1
1
0
0
NU W11 W10 W9 W8 W7 W6 W5 W4 W3 W2 W1 W0
EN S1 S0 WR 0 0 0 0 0 0 0 0 0 0 0 0
Signed 2’s Complement data Value of Channel 0
Signed 2’s Complement data Value of Channel 1
Signed 2’s Complement data Value of Channel 2
Signed 2’s Complement data Value of Channel 3
Signed 2’s Complement data Value of Channel 4
Signed 2’s Complement data Value of Channel 5
Signed 2’s Complement data Value of Channel 6
8 - Output 7
9 - Output 8
Signed 2’s Complement data Value of Channel 7
Signed 2’s Complement data Value of Channel 8
10 - Output 9 Signed 2’s Complement data Value of Channel 9
11 - Output 10 Signed 2’s Complement data Value of Channel 10
12 - Output 11 Signed 2’s Complement data Value of Channel 11
13 - Configuration 0 0 0 0 CAB C89 C67 C45 C23 C01
Where:
PU = Power up bit
FP = Field power fault
GF = General fault
NU = Not used
Wx = Wire off (x = associated channel)
EN = Enable outputs
S1/S0 = Safe state source – When EN = 0, these bits indicate source of safe state output.
WR = Wire-off reset
Cxx = Configuration
Publication 1794-IN106D-EN-E - January 2014
14
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Data Table – 1794-IE8XOE4
Dec.
Oct.
Read Words
0 - Input 0
1 - Input 1
2 - Input 2
3 - Input 3
4 - Input 4
5 - Input 5
6 - Input 6
7 - Input 7
8 - Status
Write Words
15
17
PU
14
16
FP
13
15
GF
12
14
11
13
10
12
9
11
8
10
7
7
Signed 2’s Complement data Value of Channel 0
Signed 2’s Complement data Value of Channel 1
Signed 2’s Complement data Value of Channel 2
Signed 2’s Complement data Value of Channel 3
Signed 2’s Complement data Value of Channel 4
Signed 2’s Complement data Value of Channel 5
Signed 2’s Complement data Value of Channel 6
Signed 2’s Complement data Value of Channel 7
6
6
5
5
4
4
3
3
2
2
1
1
0
0
NU W3 W2 W1 W0 R7 R6 R5 R4 R3 R2 R1 R0
0 - Reserved
1 - Output 0
2 - Output 1
3 - Output 2
EN S1 S0 WR 0 0 0 0 0
Signed 2’s Complement data Value of Channel 0
Signed 2’s Complement data Value of Channel 1
Signed 2’s Complement data Value of Channel 2
4 - Output 3 Signed 2’s Complement data Value of Channel 3
5 - Configuration QS 0 0 0 CAB C89 C67
0 0
C45
0 0
C23
0 0
C01
0
Where:
PU = Power up bit
FP = Field power fault
GF = General fault
NU = Not used
Wx = Wire off (x = associated channel)
Rx = Out of range (x = associated channel)
EN = Enable outputs
S1/S0 = Safe state source – When EN = 0, these bits indicate source of safe state output.
WR = Wire-off reset
QS = Quick step bit – allows input filter to be reduced during rapid signal changes.
Cxx = Channel Configuration (xx = associated channel pair)
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
15
Specifications
General Specifications for the 1794-IE12, 1794-OE12, and 1794-IE8XOE4 Modules
(1)
Attribute
Indicators
Recommended terminal base
Calibration
Isolation voltage
1794-IE12
1 red/green power/status indicator
1794-TB3G or 1794-TB3GS
FLEXBus current
Power supply
Voltage, nom.(nom)
Specification
Certification
Voltage, range
Supply current
Specification
Certification
80 mA
24V DC
(2)
24V DC
10.5...31.2V DC
30 mA @ 24V DC;
45 mA @ 10.0V DC
60 mA
1794-OE12
24V DC
24V DC
10.0...31.2V DC
320 mA @ 24V DC;
720 mA @ 10.0V DC
320 mA
(2)
1794-IE8XOE4
24V DC
(2)
24V DC
10.0...31.2V DC
140 mA @ 24V DC;
280 mA @ 10.0V DC
140 mA
None required – factory calibrated
50V (continuous), Basic Insulation Type,
No isolation between individual channels
Type tested @ 850V AC for 60 s between field and system
Power dissipation, max 1.2 W @ 31.2V DC
Thermal dissipation
Terminal base screw torque
0.8 Nm (7 lb-in.)
1.0 Nm (9 lb-in.) –
7.68 W @ 24V DC
1794-TBN only
3.4 W @ 24V DC
4.1 BTU/hr @ 31.2V DC 26.2 BTU/hr @ 24V DC 11.6 BTU/hr @ 24V DC
Shielded Wire type
Wire size
Wiring category
(1)
Determined by installed terminal base
2 – on signal ports
2 – on power ports
North American temperature code
Dimensions (approx.)
(HxWxD)
T4A
46 x 94 x 54 mm
(1.81 x 3.7 x 2.1 in.)
Enclosure type rating None (open-style)
Keyswitch position 3 4 5
(2)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-IN041 .
includes 5 % AC ripple
Publication 1794-IN106D-EN-E - January 2014
16
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Environmental Specifications
Attribute 1794-IE12 1794-OE12 1794-IE8XOE4
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
Relative humidity
Vibration
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
Shock, operating
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity
IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
EC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave
80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse
100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse
100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave
80% AM from 2000...2700 MHz
EFT/B immunity IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±4 kV @ 5 kHz on shielded signal ports
IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on shielded signal ports
IEC 61000-4-3:
10V/m with 1 kHz sine-wave
80% AM from 80...2000 MHz
100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse
100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave
IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±4 kV @ 5 kHz on shielded signal ports
10V/m with 200 Hz 50% Pulse
80% AM from 2000...2700 MHz
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Publication 1794-IN106D-EN-E - January 2014
FLEX I/O DC Input, Output, and Input/Output Analog Modules
17
Output Specifications – 1794-OE12 and 1794-IE8XOE4 Modules
Attribute 1794-OE12 1794-IE8XOE4
Number of outputs
Output voltage terminal
Output current terminal
Output resolution
Voltage terminal
Current terminal
Data format
12 single-ended, nonisolated 4 single-ended, nonisolated
0V output until module is configured
+10V (user configurable)
0 mA output until module is configured
4...20 mA (user configurable)
0...20 mA (user configurable)
16 bit
320
μ
V/cnt
0.641
μ
A/cnt
16 bit
Output conversion type
Step response to 63% of full scale, output terminal
Absolute accuracy
(1)
Voltage terminal
Current terminal
Accuracy drift with temperature
Voltage terminal
Current terminal
Load on output current
Load on voltage output, max
Digital-to-analog converter
~70% 1st convert;
96% 2nd convert;
100% 3rd convert
0.1% full scale @ 25 °C
0.1% full scale @ 25 °C
0.004% full scale/°C
0.004% full scale/°C
0...750
Ω
3.0 mA
(1)
Includes offset, gain, nonlinearity, and repeatability error terms.
Input Specifications – 1794-IE12 and 1794-IE8XOE4 Modules
Attribute
Number of inputs
Input resolution
Voltage terminal
Current terminal
Data format
Input conversion type
Input conversion rate
1794-IE12 1794-IE8XOE4
12 single-ended, nonisolated from channel to channel
16 bits
320
μ
V/cnt
0.641
μ
A/cnt
8 single-ended, nonisolated from channel to channel
Left-justified 16-bit
Successive approximation
8.0 ms all channels
Publication 1794-IN106D-EN-E - January 2014
18
FLEX I/O DC Input, Output, and Input/Output Analog Modules
Input Specifications – 1794-IE12 and 1794-IE8XOE4 Modules
Attribute 1794-IE12 1794-IE8XOE4
Input voltage terminal
Input current terminal
Specification
Certification
Input impedance, nom. (nom)
Voltage terminal
Current terminal
Normal mode rejection ratio
+10V (user configurable)
4...20 mA (user configurable)
0...20 mA (user configurable)
> 1 M
Ω
< 100
Ω (2)
Voltage/current terminal:
-3 dB @ 0.05 Hz; -20 dB/decade
-52 dB @ 50 Hz;
-54 dB @ 60 Hz
Voltage/current terminal with Quick Step:
-3 dB @ 1.5 Hz; -20 dB/decade
-29 dB @ 50 Hz;
-31 dB @ 60 Hz
Step response to 63% of full scale Voltage/current terminal:
1.3 s
Voltage/current terminal with Quick Step:
0.09 s
Absolute accuracy
(1)
Voltage input
Current input
0.1% full scale @ 25 °C
0.1% full scale @ 25 °C
Accuracy drift with temperature
Voltage terminal
Current terminal 0.004% Full Scale/°C
0.004% Full Scale/°C
Voltage overload, max
Current overload, max
30V continuous, one channel at a time
32 mA continuous, one channel at a time
(1)
(2)
Includes offset, gain, nonlinearity, and repeatability error terms.
If 24V DC is removed from the module, input resistance is < 100 is 24V DC.
Ω
. This is also true at 0 mA current input even if there
If there is an input current applied, input impedance is > 1 M
Ω
.
Publication 1794-IN106D-EN-E - January 2014