Advertisement
Advertisement
Heos
User manual
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
I n t e g r a t e d C o n t r o l S o l u t i o n s & E n e r g y S a v i n g s
WARNINGS
CAREL bases the development of its products on decades of experience in HVAC, on the continuous investments in technological innovations to products, procedures and strict quality processes with in-circuit and functional testing on 100% of its products, and on the most innovative production technology available on the market. CAREL and its subsidiaries nonetheless cannot guarantee that all the aspects of the product and the software included with the product respond to the requirements of the fi nal application, despite the product being developed according to start-of-theart techniques. The customer (manufacturer, developer or installer of the fi nal equipment) accepts all liability and risk relating to the confi guration of the product in order to reach the expected results in relation to the specifi c fi nal installation and/or equipment. CAREL may, based on specifi c agreements, acts as a consultant for the positive commissioning of the fi nal unit/application, however in no case does it accept liability for the correct operation of the fi nal equipment/system.
The CAREL product is a state-of-the-art product, whose operation is specifi ed in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
Each CAREL product, in relation to its advanced level of technology, requires setup/confi guration/programming/commissioning to be able to operate in the best possible way for the specifi c application. The failure to complete such operations, which are required/indicated in the user manual, may cause the fi nal product to malfunction; CAREL accepts no liability in such cases.
Only qualifi ed personnel may install or carry out technical service on the product.
The customer must only use the product in the manner described in the documentation relating to the product.
In addition to observing any further warnings described in this manual, the following warnings must be heeded for all CAREL products:
• prevent the electronic circuits from getting wet. Rain, humidity and all types of liquids or condensate contain corrosive minerals that may damage the electronic circuits. In any case, the product should be used or stored in environments that comply with the temperature and humidity limits specifi ed in the manual.
• do not install the device in particularly hot environments. Too high temperatures may reduce the life of electronic devices, damage them and deform or melt the plastic parts. In any case, the product should be used or stored in environments that comply with the temperature and humidity limits specifi ed in the manual.
• do not attempt to open the device in any way other than described in the manual.
• do not drop, hit or shake the device, as the internal circuits and mechanisms may be irreparably damaged.
• do not use corrosive chemicals, solvents or aggressive detergents to clean the device.
• do not use the product for applications other than those specifi ed in the technical manual.
All of the above suggestions likewise apply to the controllers, serial boards, programming keys or any other accessory in the CAREL product portfolio.
CAREL adopts a policy of continual development. Consequently, CAREL reserves the right to make changes and improvements to any product described in this document without prior warning.
The technical specifi cations shown in the manual may be changed without prior warning.
The liability of CAREL in relation to its products is specifi ed in the CAREL general contract conditions, available on the website www.carel.com and/or by specifi c agreements with customers; specifi cally, to the extent where allowed by applicable legislation, in no case will CAREL, its employees or subsidiaries be liable for any lost earnings or sales, losses of data and information, costs of replacement goods or services, damage to things or people, downtime or any direct, indirect, incidental, actual, punitive, exemplary, special or consequential damage of any kind whatsoever, whether contractual, extra-contractual or due to negligence, or any other liabilities deriving from the installation, use or impossibility to use the product, even if CAREL or its subsidiaries are warned of the possibility of such damage.
ENG
IMPORTANT
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
Separate as much as possible the probe and digital input cables from the cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance.
Never run power cables (including the electrical panel cables) and signal cables in the same conduits.
DISPOSAL
INFORMATION FOR USERS ON THE CORRECT HANDLING OF WASTE
ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
In reference to European Union directive 2002/96/EC issued on 27 January
2003 and the related national legislation, please note that:
• WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately;
• the public or private waste collection systems defi ned by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment;
• the equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative eff ects on human health and on the environment;
• the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately;
• in the event of illegal disposal of electrical and electronic waste, the penalties are specifi ed by local waste disposal legislation.
Warranty on materials: 2 years (from the date of production, excluding the consumable parts.
Certifi cation: the quality and safety of CAREL S.p.A. products are guaranteed by the ISO 9001 certifi ed design and production system.
3 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
4
ENG
C
ontent
1. INTRODUCTION 7
1.2 Components and accessories ...................................................................7
2. INSTALLATION 8
2.1 Main board: connctor’s description .......................................................8
2.2 Inverter monofase 10A ..................................................................................9
2.3 16 A 1PH and 18-24 A 3PH inverter ....................................................10
2.4 E 2 V unipolar valves.........................................................................................11
2.5 Pressure probe (SPKT00**P0) ..................................................................11
2.7 General connection diagram ..................................................................12
3. USER INTERFACE 15
3.1 pGDe and pLDPRO Keypad .....................................................................15
4. MENU DESCRIPTION 16
5. STARTUP 17
5.1 Guided commissioning procedure .....................................................17
6. FUNCTIONS 18
6.1 Probes (analogue inputs) ..........................................................................18
6.9 Electronic valve ..............................................................................................30
6.10 Protection functions .....................................................................................31
6.11 Anti-sweat heater or fan modulation ................................................32
6.12 Condenser control .........................................................................................33
6.13 Anti-sweat on inverter with cold plate .............................................34
6.14 “Dual temperature” management ......................................................35
7. PARAMETER TABLE 36
8. SIGNALS AND ALARMS 49
8.3 EEV valve protector alarms .......................................................................49
9. SOFTWARE UPDATE 52
9.1 Setting the controller’s address .............................................................52
9.2 Setting the terminal’s address and connecting the controller to the terminal .................................................................52
9.3 Uploading/updating the software ......................................................53
9.4 pCO Manager: operating instructions ..............................................54
9.5 History of software revisions ...................................................................56
5 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
1. INTRODUCTION
Heos is a control system for the complete management of showcases or cold rooms in which the compressor (variable speed or on/off ) is cooled by a water loop.
The control board is ready for DIN rail assembly, is fi tted with plug-in screw terminals and comes with a built-in electronic expansion valve driver.
In order to manage multiplexed showcases, Heos can manage a local
Master-Slave network comprising a maximum of 6 units (1 Master and 5
Slave). Each controller can be fi tted with its own display (PLD) and/or user terminal (pGDe), for service or commissioning.
Main features:
• board with built-in driver for CAREL single-pole valve;
• modulating management of cooling capacity by inverter on BLDC compressor;
• stand-alone or multi-evaporator management;
• automatic balancing of cooling capacity in multi-evaporator confi guration;
• COP calculation and management;
• advanced superheat control with protection against low superheat
(LowSH), low evaporation temperature (LOP), high evaporation temperature (MOP) and low suction temperature (LSA);
• defrosts can be activated from the keypad, digital input, via network from the Master, or supervisor;
• various types of defrost available: electric heater, reverse cycle, hot gas;
• smart defrost functions;
• coordination of network defrosts;
• management of lights and curtains;
• anti-sweat heater modulation;
• evaporator fan speed modulation;
• possibility to display and set Slave parameters from the Master;
• sharing of one or more network probes (e.g. network pressure probe);
• HACCP alarm management;
• RS485 serial for BMS inside.
1.2 Components and accessories
Part number Description
UP2AH030302SK Heos for cabinets with cover - 230 Vac power supply
UP2BH030302SK Heos for cabinets with cover - 24 V power supply
PGDEH00FZ0
PLDH0GFP00 pGDE Heos display, for panel mounting, with buzzer pLDpro Heos display, for panel mounting, with buzzer
S90CONN000
S90CONN001
PLDH0SF400
PLDCON03B0
PLDCON05B0
PSD10102BA
PSD10162A0
Connector for pGD evolution display, 1.5 m long
Connector for pGD evolution display, 3 m long
PLD small Heos, green display
3 m cable for PLD display
5 m cable for PLD display
POWER+ 10 A, 200-240 Vac 1PH, IP00 with COLDPLATE
POWER+ 16 A, 200-240 Vac 1PH, IP20/IP44 with COLDPLATE
PSD101021A
PSD1016200
PSD1018400
PSD1024400
PSD10184A0
PSD10244A0
PSACH10100
PSACH10200
E2V**FSFC0
E2VSTA0320
NTC030HP00
NTC030HF01
NTC030HT41
SPKT0043P0
SPKT00B6P0
SPKC002310
POWER+ 10 A, 200-240 Vac 1PH, IP00
POWER+ 16 A, 200-240 Vac 1PH, IP20/IP44
POWER+ 18 A, 380-480 Vac 3PH, IP20/IP44
POWER+ 24 A, 380-480 Vac 3PH, IP20/IP44
POWER+ 18 A, 380-480 Vac 3PH, IP20/IP44 with COLDPLATE
POWER+ 24 A, 380-480 Vac 3PH, IP20/IP44 with COLDPLATE
Coils for POWER+ 18 A
Coils for POWER+ 24 A
Exp valve - E2V* 12-12 ODF
E2V unipolar stator with 2m cable
NTC temp. probe, HP IP67, -50T50, 3 m long
NTC temp. probe, HF IP67, -50T90, strap-on, lung. 3m. 10 pz
NTC temp. probe,, HT IP55, 0T150, lungh. 3 m, 10 pz
Pressure probe, 0-5V 0...17,3 barg (0...250 psig)
Pressure probe, 0-5V 0...45 barg (0…650 psig)
3-wire cable, 2 m long, for SPKT pressure probes, IP67 Packard connector
Tab. 1.a
Example of stand-alone system
Supervisor network
BMS
Master/Slave network
M S1 .... S5
Fig. 1.a
Example of multi-evaporator system
BMS
Fig. 1.b
7 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
2.1 Main board: connctor’s description
For further details on the electrical and mechanical specifi cations, see instruction sheet +050001590
1 G
G0
J1
- for UP2A*: 230 Vac 50/60 Hz, +10%/-15%;
- for UP2B*: 24 Vac +10%/-15% 50/60 Hz,
28 to 36 Vdc +10%/-15%;
J10
J9
J11
Vout
RX-/TX-
RX+/TX+
GND
RX-/TX-
RX+/TX+
GND
14
12
11
13
15 J13 J12 5a
2
3
4
U6
U7
+Vdc
+5VR
GND
U8
U9
U10
+Vdc
+5VR
GND
U1
U2
U3
GND
U4
U5
+Vdc
+5VR
GND
GND
Y1
Y2
Y3
DI1
DI2
DI3
DI4
GND
J2
J3
J4
J5
J6
J7 J8
J15
J14
J16
J17
J18
J19
J20
J21
J22
J23
J24
RX-/TX-
RX+/TX+
GND
Out5
C2
C2
V-IN
Out6
C6
Out7
C7
Out8
C8
N01
NC1
C1
Out2
C2
Out3
C2
Out4
C2
16
10
9
8
7
6
5b
Fig. 2.a
Key:
1 Power supply 230Vac for version with trasformer (UP2A*********)
Power supply 24Vac for version without trasformer (UP2B*********)
2 Universal channel 9 Alarm digital output
3 Analog outputs
4 Digital inputs
5a Valve output 1
5b Valve output 2
10 Serial line pLAN
11 Serial line BMS2
12 Serial line Fieldbus
13 PLD terminal connector
6 Relay digital output switch type 14 Dipswitch for selection
7 Voltage inputs for digital output 2, 3, 4, 5 15 Serial card RS485 BMS1
8 Voltage digital outputs 16 Power supply - Green Led
Digital inputs
Analogue outputs
Universal channels
Digital outputs
Singlepole valve outputs
Type: digital inputs with voltage-free contacts
Number of digital inputs (DI): 4
Type: 0 to 10 Vdc cont., PWM 0 to 10 V 50 Hz synch. with power supply,
PWM 0 to 10 V frequency 100 Hz, PWM 0 to 10 V frequency 2 kHz
Number of analogue outputs (Y): 3
Analogue/digital conversion bits: 14
Type of input selectable from application: NTC, PT1000, PT500, PT100, 4 to
20 mA, 0 to 1 V, 0 to 5 V, 0 to 10 V, voltage-free contact digital input
Type of output selectable from application: PWM 0/3.3 V 100 Hz synchronous with power supply PWM 0/3.3 V 100 Hz, PWM 0/3.3 V 2 kHz,
0 to 10 V analogue output Maximum current 2 mA
Number of universal channels (U): 10
Precision of passive probe reading: ± 0.5 C across entire temperature range; Precision of active probe reading: ± 0.3% across entire voltage range; Output precision: ± 2%
Group 1, Switchable power R1: NO 1(1)A
Group 2, Switchable power R3, R4, R5: NO NO 2(2)A
Group 3, Switchable power R6, R7, R8: NO 6(6)A
Maximum switchable voltage: 250 Vac
Switchable power R2 (SSR case mounting): 15 VA 110/230 Vac
The relays in the same group have basic insulation between each other and therefore must have the same power supply
Relays belonging to diff erent groups have reinforced insulation and consequently a diff erent power supply can be used
Maximum output for each valve: 7 W
Type of control: single-pole
Valve connector: 6-pin, fi xed sequence
Power supply: 12 Vdc ±5%
Maximum current: 0.3 A for each winding
Minimum winding resistance: 40 Ω
Maximum cable length: 2 m
Tab. 2.a
2. INSTALLATION
Mechanical and Electrical specifi cations
Power supply :
230 Vac, +10…-15% UP2A*********;
24 Vac +10%/-15% 50/60 Hz,
28 to 36 Vdc +10…-15% UP2B*********;
Max power input: 25 VA
Insulation between power supply and instrument
• mod. 230Vac: reinforced
• mod. 24Vac: reinforced ensured by power supply of safety transformer
Max voltage connectors J1 and from J16 to J24: 250 Vac;
Minimum section of the wires - digital outputs: 1,5 mm 2
Minimum section of wires of all others connectors: 0,5mm 2
Power supplied
Type: +Vdc, +5VR, Vout for external power supply
+Vdc: 26 Vdc ±15% models 230Vac power supply (UP2A*********),
21 Vdc ±5% models 24 Vac power supply (UP2B*********)
Max current available +Vdc: 100mA, total taken from all connectors, protected against short-circuits
+5 VR: 5 Vdc ±2%; Max current available 100 mA, total taken from all connectors, protected against short-circuits
Vout: 26 Vdc ±15% for models 230 Vac power supply (UP2A*********),
21 Vdc ±5% Max current available (J9): 100 mA
Product specifi cations
Program memory: (FLASH): 4 MB
Log memory: 2 MB
Internal clock precision: 100 ppm
Removable battery : Lithium button, CR2430, 3 Vdc
Battery lifetime : minimum 8 years
User interface available
Type: all the pGD terminals with connector J15, PLD terminal with connector
J10
Max distance for pGDe terminal: 2m by telephone connector J15, 50m by shield-cable AWG24
Maximun number of user interface: One user interface pGDe on the connector J15 or J14. One PLD user interface choosing tLAN protocol on the on board dip switch
Communication lines available
Type: RS485, Master for FieldBus1, Slave for BMS 2, pLAN
Number and type of available linees:
1 line not optoinsulated on J11 connector (BMS2).
1 line not optoinsulated on J9 connector (FieldBus), if not used from PLD user interface on J10 connector.
1 line not optoinsulated on J14 connector (pLAN), if not used from pGDe user interface on J115 connector.
1 optional line (J13), selectable from Carel optionals
Maximum connection cable-lenght: 2m without shield-cable, 500m by shield-cable AWG24
Maximum connections lenght
Universal digital inputs and everything without diff erent specifi cation: less than 10m
Digital outputs: less than 30m
Serial Lines: check indication on relevant section
Operating conditions
Storage: -40T70 °C, 90% rH non-condensing
Operating: -40T70 °C, 90% rH non-condensing
Mechanical specifi cations
Dimensions: 13 DIN rail modules, 228 x 113 x 55 mm
Ball pressure test: 125 °C
Other specifi cations
Environmental pollution: 2 level
Index of protection: IP00
Class according to protection against electric shock: to be incorporated into Class I and/or II appliances
PTI of the insulating materials PCB: PTI250; insulation material: PTI 175
Period of stress across the insulating parts: long
Type of action: 1C; 1Y for SSR versions
Type of disconnection or microswitching: microswitching category of resistance to heat and fi re: category D (UL94 - V2)
Immunity against voltage surges: category II software class and structure: Class A
To not touch or maintenance the product when power supply is applied
Heos +0300078EN - rel. 1.6 - 23.11.2017
8
ENG
2.2 Inverter monofase 10A
For further details on the electrical and mechanical specifi cations, see instruction sheet +0500076IE
-DC
+DC
J1 J2 J3
1 2 3 4 5 6 7
Fig. 2.b
Description of the terminals:
Ref.
L, N
earth (*)
U, V, W
earth (*)
-DC
+DC
J1-1
J1-2
J2-3
J2-4
J2-5
J3-6
J3-7
E
F (Led)
Description
Single-phase power supply input
Motor output
DC bus output
C
NO
0 V
Tx/Rx+
Tx/Rx-
PTC
24 Vdc
DC bus output
RS485/ModBus®connection
PTC input (black connector)
PE
POWER (green) drive powered
RUN/FAULT (green/red) drive running / drive alarm
DATA (yellow) communication active
Tab. 2.c
(*) The earth connections inside the drive are electrically connected together and to PE.
Important: before carrying out any maintenance work, disconnect the drive and the external control circuits from the power supply by moving the main system switch to “off ”. Once power has been disconnected from the drive, wait at least 5 minutes before disconnecting the electrical cables.
Coldplate with cooling adapter
The Coldplate with cooling adapter version (PSD10102BA) is provided with four threaded holes M5 on the aluminum plate for fi xing.
Assembly
Technical specifi cations
Operating temperature
Humidity
Pollution degree
Input voltage
Output voltage
Output frequency
Maximum length
Switching frequency
Protection functions
Frequency resolution
-20T60°C
<95% U.R. non-condensing
Max 2
200 - 240V ± 10%, 50 - 60Hz, 1~
0 - Input voltage
0 - 500 Hz
5 m
4, 6, 8 kHz
Drive: short-circuit, overcurrent, ground fault, overvoltage and undervoltage, overtemperature
Motor: overtemperature and overload (150% rated current for 1 minute)
System: short-circuit
0,1 Hz
1 motor protector input: PTC temp. probe or voltage-free contact max source current 10 mA, Inputs
Outputs
Serial data connection
RS485, Modbus® protocol, max. transmission speed
19200 bit/s.
24Vdc auxiliary power supply Double insulation, precision 10%, 50mA max
Maximum length
Index of protection
100m shielded cable
IP00
Tab. 2.d
CE conformity: max. length 25 m
1 relay: Programmable output, voltage-free contact: 240 Vac, 1 A
2006/95/EC
EN 61800-5-1: Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
2004/108/EC
EN 61800-3, ed.2.0.: Adjustable speed electrical power drive systems. EMC requirements and specifi c test methods.
EN61000-3-2: Electromagnetic compatibility (EMC) Part 3-2: Limits for harmonic currents (equipment connected with input current > 16 A per phase).
EN61000-3-12: Electromagnetic compatibility (EMC) Part 3-12: Limits - Limits for harmonic currents (equipment connected with input current > 16 A and <= 75 A per phase).
Rated values
The table below shows the rated input and output values, as well as the specifi cations for sizing the cables (cross-section, maximum length) and the fuses. The values refer to an operating temperature of 60 °C and a switching frequency of 8 kHz, unless otherwise specifi ed.
PSD10102BA
Rated input current at 230V
Fuse or type B circuit breaker
Power cable cross-section
Rated output current
Rated output power at 230V
Max. total dissipation
Max. heatsink dissipation
Minimum motor cable cross-section
Maximum motor cable length
17 A
25 A
4 mm 2
10 A
3,8 kW
270 W
150 W
2,5 mm 2
5 m
Tab. 2.e
Dimensions
1
3
2
4,8
4,8
102,8
138
88
39,3
Ø5
M5
4
Key:
1 Coldplate cooling device (example)
2
Holes/screws for fastening the coldplate from rear of drive (4 x M5 holes, max.
14mm deep)
3 Holes/screws for fastening the coldplate from front of drive
4 Power+ plate
Note: the air-cooled heat sink is shown in grey in the dimensioned drawing.
12,6 113,4 4
9 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
2.3 16 A 1PH and 18-24 A 3PH inverter
For further details on the electrical and mechanical specifi cations, see instruction sheet +0500048IE
C 1
C2
F
E
L 1 /L L2/N L3 U V W
1 2 3 4 5 6 7 8 9 1 0
Fig. 2.f
1,2
3
4
7
8
5
6
9
10
Description of the terminals:
Ref.
Description
L1/L, L2/N, L3
earth (*)
L1/L, L2/N
earth (*)
U, V, W
earth (*)
Three-phase power supply input
Single-phase power supply input
Motor output
C1, C2
Terminal block not used in PSD10**2**. For optional external
DC Choke in PSD10184** e PSD10244**
Relay output
0 V
Tx/Rx+
Tx/Rx-
PTC input
24 Vdc
0V
STOa
STOb
RS485/ModBus® connection
Auxiliary voltage
Safe Torque Off digital input (**)
E
F (Led)
PE
POWER (green) drive powered
RUN/FAULT (green/red) drive running / drive alarm
DATA (yellow) communication active
Tab. 2.g
(*) The earth connections inside the drive are electrically connected together and to PE.
(**) To enable the drive for operation, apply a voltage of 24 Vac/Vdc to the Safe
Torque Off digital input. The polarity is indiff erent for direct current power supply.
Coldplate with cooling adapter
The Power+ Coldplate (PSD10***A0) models are the same as respective standard Power+ models, with the unique diff erence that the fi nned heatsink and fan are replaced by a fl at aluminium plate.
The plate has threaded holes M5 for fi xing an additional device with cooling function (coldplate), typically using liquid refrigerant. The coldplate is the user’s responsibility and is not supplied by Carel.
Assembly
Technical specifi cations
Operating temperature
Humidity
Pollution degree
Input voltage
Output voltage
Output frequency
Maximum length
Switching frequency
Protection functions
Frequency resolution
-20T60°C
<95% U.R. non-condensing
Max 2
200 - 240Vac ±10%, 50/60 Hz, 1~ (P/N PSD1***2**)
380 - 480Vac ±10%, 50/60 Hz, 3~ (P/N PSD10**4*0)
0 - Input voltage
0 - 500 Hz
5 m
4, 6, 8 kHz
Drive: short-circuit, overcurrent, ground fault, overvoltage and undervoltage, overtemperature
Motor: overtemperature and overload (150% Inom for 1 minute)
System: Safe Torque OFF input, loss of communication
0,1 Hz
1 motor protector input: PTC temp. probe or voltage-free contact max source current 10mA, max. Inputs
Outputs
Serial input
24 Vdc auxiliary power
Maximum length
Index of protection length 25 m
1 relay: progr. output, voltage-free contact: 240Vac, 1A
RS485, Modbus® protocol, max trasmission speed
19200 bit/s
Double insulation, precision 10%, 50mA max
100m shielded cable
IP20
Tab. 2.h
CE conformity:
2006/95/EC
EN 61800-5-1: Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
2004/108/EC
EN 61800-3, ed.2.0.: Adjustable speed electrical power drive systems. EMC requirements and specifi c test methods.
EN61000-3-2: Electromagnetic compatibility (EMC) Part 3-2: Limits for harmonic currents (equipment connected with input current > 16 A per phase).
EN61000-3-12: Electromagnetic compatibility (EMC) Part 3-12: Limits - Limits for harmonic currents (equipment connected with input current > 16 A and <= 75 A per phase).
Rated values
The table below shows the rated input and output values, as well as the specifi cations for sizing the cables (cross-section, maximum length) and the fuses. The values refer to an operating temperature of 60 °C and a switching frequency of 8 kHz, unless otherwise specifi ed.
Models
Rated input current at 230V (400V 3PH)
Fuse or type B circuit breaker
Power cable cross-section
Rated output current
Rated output power at 230V (400V 3PH)
Max. total dissipation
Max. heatsink dissipation
Minimum motor cable cross-section
Maximum motor cable length
16A 1PH 18A 3PH 24A 3PH
28 A 23 A 30 A
40 A
6 mm 2
32 A
4 mm 2
40 A
6 mm 2
16A
6 kW
450 W
250 W
2,5 mm 2
5 m
18A
10,5 kW
320 W
250 W
4 mm
5 m
2
24A
14 kW
485 W
380 W
4 mm
5 m
2
Tab. 2.i
Dimensions (mm)
173
127
2
Key:
1 Coldplate cooling device (example)
Holes/screws for fastening the
2 coldplate
3 Power+ plate
Note: the air-cooled heat sink is shown in grey in the dimensioned drawing.
1
131
M5
3
94
98
96
86
Heos +0300078EN - rel. 1.6 - 23.11.2017
84
71
Ø 5
10
26 75 26
80
192,3
ENG
2.4 E
2
V unipolar valves
B
47,75 Ø 35
G
F
G
Valve
B
C type
A
D
E
E2V**FSF** copper 12-
12mm ODF
133.5mm (5.26inch)
85.4 mm (3.36 inch)
55.1 mm (2.17 inch)
57.5 mm (2.26 inch)
In 12 / Out 14 mm (In 0.47/
Out 0.55 inch)
In 12 / Out 14 mm (In 0.47/
Out 0.55 inch)
10 mm (0.39 inch)
Ø E in
Ø E out
CAREL E 2 V-U operating specifi cations (+ 050001440 )
Compatibility Group 1: R1234yf, R290, R600, R600a
Group 2: R22, R134a, R404A, R407C, R410A, R417A,
R507A, R744, R1234ze, R448A, R449A, R450A, R513A
Maximum operating pressure (MOP) CE approval: 60 bars (870psi).
Maximum operating PD (MOPD)
P.E.D.
Refrigerant temperature
Ambiente temperature
UL approval: 45 bars (652 psi)
35 bars (508 psi); for E2V35 unipolar: 26 bars (377psi)
Gr 1 & 2, art. 4, par. 3.
-40T70 °C (-40T158 °F)
-30T70 °C (-22T158 °F)
C
CAREL E2V-U stator (+ 050001440 )
Power supply voltage
Drive frequency
Phase resistance (25 °C)
Ingress protection
Step angle
Linear movement/step
Connections
Complete closing /control steps
12 V
50 Hz
40 Ohm ± 10%
IP67
15°
0.03 mm (0,0012 inch)
6 pin (AWG 18-22) with 1; 2; 0.3 m cable included
500 / 480
Tab. 2.j
2.5 Pressure probe (SPKT00**P0)
Ø 21
Ch 14
Reference technical document
Power supply
Output
Connector thread
Operating conditions
Protection degree
Environmental pollution level
Material in contact with the fl uid
Separation with plastic
Clamping force
7/16”-20UNF
+050000598
4,5...5,5 Vdc
0,5...4,5 Vdc
7/16” 20 UNF
-40T135 °C
IP65 with mechanical protection; IP67 with electrical connector plugged in
Normal
Brass or plated steel
Compatible with fl uids R12, R22, R134A, R404A, R407C, R410A, R502, R507, R744, HFO 1234ze
Not compatible with R717 (ammonia), not to be used with water and glycol.
12...16 Nm
Models
Reference technical document
Operating range
Connections
Sensor
Dissipation factor (in air)
Thermal constant over time (in air)
Sensitive element index of protection
Sensitive element housing
Classifi cation according to protection against electric shock
Category of resistance to heat and fi re
NTC***HP00
+030220655
-50T105 °C in air - -50T50 °C in fl uid
Stripped ends, dimensions: 5±1 mm
NTC 10 kΩ ±1% a 25 °C Beta 3435 ca. 3 mW/°C ca. / approx. 25 s
IP67
Polyolefi n
Basic insulation for 250 Vac
Flame retardant
NTC***HT41
+030220655
0T150 °C in air
Stripped ends, dimensions: 6±1mm
NTC 50 kΩ ±1% a 25 °C Beta 3977 ca. / approx. 3 mW
NTC***HF01
+030220655
-50T105 °C
Stripped ends, dimensions: 6±1mm
R(25 °C)= 10 kOhm 1%; Beta 3435
3 mW ca. / approx. 30 s ca. 50 s
IP55 IP67
High temperature polyester dim. 20x5 mm Thermoplastic with fastening clamp
Basic insulation for 250 Vac Basic insulation for 250 Vac
In accordance with CEI 20-35 UL/HB cable
Tab. 2.k
for inside showcase temperature for outlet temperature
11 for evaporation temperature
Tab. 2.l
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
2.7 General connection diagram
Inverter 12/16A Inverter 10A
L1/L L2/N L3 U V W
K
High press switch
L N
PE
Fuse or
MCB
3
M
1 2
GND +
3 4 5
-
6 7 8 9 10
PTC Klixon to HEOS controller
PAY ATTENTION
TO THE POWER SUPPLY!
Power supply
- for UP2A*: 230 Vac 50/60 Hz, +10%/-15%;
- for UP2B*: 24 Vac +10%/-15% 50/60 Hz,
28 to 36 Vdc +10%/-15%;
G
G0
J1
HEOS configuration
DIP2=OFF
DIP1=ON
PE
K
L
N
U V W
DC
+DC
1 2
GND + -
3 4 5 6 7
PTC Klixon
High press switch
L N
Fuse or
MCB
3
M to HEOS controller to power+
2
1
J10
ON OFF
J9
J11
Vout
RX-/TX-
RX+/TX+
GND
RX-/TX-
RX+/TX+
GND
Air OFF (supply) probe (CAREL NTC)
Defrost probe (CAREL NTC)
Air ON (return) probe (CAREL NTC)
Suction temp. probe (CAREL NTC)
LP Probe (*)
Discharge temp. probe (CAREL NTC-HT)
HP Probe (*)
Analog Input
Analog Output (0-10V)
Digital Input (free voltage)
White
Black
Green
White
Black
Green
U6
U7
+Vdc
+5VR
GND
U8
U9
U10
+Vdc
+5VR
GND
GND
(A01) Y1
(A02) Y2
(A03) Y3
U1
U2
U3
GND
U4
U5
+Vdc
+5VR
GND
DI1
DI2
DI3
DI4
GND
J2
J3
J4
J5
J6
J7
J8
RS485 serial card to connect supervisory system
Liquid
Injection
(optional)
J13
J12
J14
RX-/TX-
RX+/TX+
GND
BUS pLAN for
Master/Slave
Expansion
Valve
J16
J17
J18
J19
J20
J21
J22
J23
J24 pLD Terminal
Out5
C2
C2
V-IN
N06
C6
N07
C7
N08
C8
N01
NC1
C1
Out2
C2
Out3
C2
Out4
C2
Alarm
L N pGDe Terminal
Rail Heaters (**)
Evap Fan
Lights
Digital Output
(POWERED)
Defrost
Digital Output
(NOT POWERED) pLD PRO
Fig. 2.m
(*) The 4-20 mA pressure probes are connected as follows: white to Ux and black to +Vdc, green not used
(**) 230 Vac SSR output, maximum switchable power 15VA
Important: Class A software: the safety devices providing overload and high pressure protection must control the compressor directly, and consequently need to be wired in series with compressor contactor control signal. For the type of cable to use, refer to power+ manual (cod. +0300048IT).
I/O selection table
/FI
/FL
/FM
/FW
/FY
/FG
/FH
Par.
/FA
/Fb
/Fc
/P3
/P4
/P1
/P2
/Fq
Description ( A nalogue inputs)
Air outlet temperature (default U1)
Defrost temperature (default U2)
Air intake temperature (default U3)
Condensing pressure (default U7)
Suction pressure (default U5)
Discharge temperature (default U6)
Suction temperature (default U4)
Liquid temperature
Room temperature
Room humidity
Glass temperature
Condenser water inlet temperature
Condenser water outlet temperature
Auxiliary probe 1
Auxiliary probe 2
/b8
/b9
/bA
/bb
/bC
/A9
/bl
Par.
/b1
/b2
/b3
/b4
/b5
/b6
/b7
Description ( D igital inputs)
Remote alarm
Delayed remote alarm
Enable defrost
Start network defrost
Door switch
Remote ON/OFF
Curtain/light switch - day/night
Continuous cycle
Cold room maintenance
Showcase cleaning
Inverter alarm
Lights
Virtual input
Dual temperature
/EN
/Eo
/Er
/ES
/EY
Par.
/EA
/EC
/Ed
/EE
/EF
/EG
/EM
Par.
/LA
/Lb
/Lc
/Ld
/LE
/LF
/LG
Description ( A nalogue outputs)
EC evaporator fans
Anti-sweat heaters
Water control valves
Condenser pump
Auxiliary output
Water-cooled condenser output
Air-cooled condenser output
Description ( D igital outputs)
Fans 1 (default DO6)
Lights (default DO7)
Defrost heaters (default DO8)
Alarms
Auxiliary output
Anti-mist heaters
Liquid injection solenoid
Curtain contact
ON/OFF compressor
Inverter valve output
Fan/condenser output
Dual temperature output
Heos +0300078EN - rel. 1.6 - 23.11.2017
12
There are two possible showcase/cold/room confi gurations. The fi rst involves the various units being fi tted individually with their own compressor and condenser, meaning the showcase is completely independent, and shares the cooling water loop with the rest of the system. In the second case, the condenser is shared and consequently the
Slave showcases are only fi tted with the evaporator and corresponding electronic expansion valve, while the compressor is controlled by the
Master board.
The system confi gurations can be set from a terminal (pGDe) as illustrated in the chapter on Commissioning; while on the showcase itself a PLD is normally used to display the temperature and any alarm signals.
Defrosts can be coordinated via the pLAN that controls a maximum of 6 units, or alternatively by the supervisor
1. Stand-alone confi guration
In this case, each showcase/cold room has its own compressor, controlled by the corresponding board, which manages all system devices
(expansion valve, showcase temperature control, alarms….).
The Master/Slave network is used for to coordinate defrosts, lights and curtain switch; otherwise these functions must be managed by the supervisor.
BMS
Waterloop
ENG
2. Multi-evaporator Master/ Slave network
The Master controller manages the compressor and coordinates the functions of the 5 Slave controllers connected via the pLAN. Each Slave controller manages the individual showcase and has a PLD user terminal for temperature monitoring. Each controller, both Master and Slave, is connected to the supervisor network. The Master only shares the evaporation pressure, and not the corresponding temperature.
BMS
Waterloop
Conden. Unit
T P
Cabinet
T
T
T
T
P
Master
Slave1
Cabinet
T
T
T
Conden. Unit
T P
Cabinet
T
T
T
P
T
Master
Conden. Unit
T P
Cabinet
T
T
T
P
T
Slave1
Slave2
Cabinet
T
T
T
T
Fig. 2.o
3. RS485 supervisor network
A maximum of 199 number Heos controllers (Master or Slave) can be connected to the supervisor network (via CAREL or Modbus® protocol).
BMS
Conden. Unit
T P
Cabinet
Slave2
1
T
T
T
P
T
2...
Fig. 2.n
Note: For the electrical connections, see the general connection diagram in par. 2.9. If a master/slave network or multi-evaporator pLAN is confi gured, the controller addresses should be set following the procedure shown in chapter 9.1 or using the Wizard (chap. 5
“Commissioning”)
...199
13
Fig. 2.p
Supervisor network layout with various Heos controllers connected,
1-199
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
2.9 Installation
For installation, proceed as follows, with reference to the wiring diagrams:
• before performing any operations on the control board, disconnect the main power supply by turning the main switch in the electrical panel OFF.
• avoid touching the control board with bare hands, as any electrostatic discharges may damage the electronic components;
• suitable electrical protection must be ensured by the manufacturer of the showcase or by appropriate installation of the controller;
• for safety devices (e.g.: residual current circuit breakers), comply with the following requirements:
IEC 60364-4-41
-
Normative in vigore nel paese standards in force in the country where the product is installed
connection technical requirements established by the electricity company
• if use a B or B+ residual current circuit breaker when the compressors are controlled by inverter; these protection devices must always be installed always upstream of the AC/A/F (see the fi gure below)
Wh
OK
Type
AC/A/F
I
Δn
≥300 mA S
NO
Type
AC/A/F
I
Δn
≤100 mA
Type
B/B+ kHz
I
Δn
≥30 mA
Fig. 2.q
The diff erential protection device, inside a TT,TN network, can be used for several showcases as shown in the example below.
Fig. 2.r
Attention: the size and the tripping current of the diff erential switch must be properly sized in accordance with the network type (TT,
TN-C, TN-S) and the number of inverters connected.
• connect any digital inputs, Lmax=10 m;
• connect the temperature and pressure probe, Lmax=10 m;
• connect the electronic expansion valve cable to connector J12;
• connect the inverter serial communication cable (if used) to terminal
J11;
• connect the optional PGDe terminal (needed for commissioning) to connector J15;
• connect the optional PLD terminal to connector J10;
• connect power supply to controller and the inverter, if used;
• program the controller using the guided commissioning procedure: see the chapter on Commissioning”.
• Program the individual controllers using the Wizard (also used to assign the pLAN address) and then connect the controllers in the same pLAN
Master/Slave group together, using connector J14. For connection, use a shielded cable and make sure that the maximum distance between consecutive controllers is 100 m (minimum cable size AWG22);
• connect the electrical loads to the relay outputs only after having programmed the controller. Always carefully evaluate the maximum capacity of the output relays, as specifi ed in the Technical specifi cations;
• connect the supervisor serial line to the card inserted on connector
J13.
Important: avoid installing the controllers in environments with the following characteristics:
• relative humidity greater than 90% or with condensation;
• strong vibrations or knocks;
• exposure to water sprays;
• exposure to aggressive and polluting atmospheres (e.g.: sulphur and ammonia fumes, saline mist, smoke) to avoid corrosion and/or oxidation;
• strong magnetic and/or radio frequency interference (therefore avoid installing the devices near transmitting antennae);
• exposure of the controllers to direct sunlight and to the elements in general.
Important: the following warnings must be observed when connecting the controllers:
• incorrect power connections may seriously damage the controller;
• use cable ends suitable for the corresponding terminals. Loosen each screw and insert the cable ends, then tighten the screws and gently
• separate as much as possible the probe and digital input cables from cables to inductive loads and power cables, so as to avoid possible electromagnetic disturbance. Never run power cables (including the electrical panel cables) and probe signal cables in the same conduits;
• do not run probe signal cables in the immediate vicinity of power devices (contactors, circuit breakers, etc.);
• reduce the path of probe cables as much as possible, and avoid spiral paths that enclose power devices.
Important: Class A software: the safety devices providing overload and high pressure protection must control the compressor directly, and consequently need to be wired in series with compressor contactor control signal.
Note: when connecting the serial network:
• connect the shield to the GND terminals on all controllers;
• do not earth the shield on the electrical panel;
• use a shielded twisted cable AWG20-22 (e.g. Belden 8761 or, in the event of particularly demanding environments from a point of view of electromagnetic disturbance, Belden 3106A);
• For the supervisor serial network (J13): connect a 120 Ω terminating resistor between the Tx/Rx+ and Tx/Rx- terminals on the last controller in the network (the one furthest away from the supervisor). Do connect any resistors to the pLAN Master/Slave network connectors (J14).
Heos +0300078EN - rel. 1.6 - 23.11.2017
14
ENG
The Heos system can be used with two types of display: one, the pGDe, for commissioning and/or to access all the control parameters; the other,
PLD, for displaying the cabinet temperature and any alarms.
Note: the PLD terminal can only be used if the pGDE terminal is disconnected (both cannot be used at the same time).
pLDPRO Keypad
Below are some examples of the INFO screens, directly accessible from the main screen:
3
4
1
2
7
8
5
6
Ref.
1
2
3
4
Button Function
Alarm displays the list of active alarms
Prg used to enter the main menu tree
Esc returns to the higher level screen
Up
Down scrolls a list upwards or increases the value highlighted by the cursor from the “main” screen, accesses the INFO screens scrolls a list downwards or decreases the value highlighted by the cursor from the “main” screen, accesses the INFO screens
Enter enters the selected submenu or confi rms the set value from the main screen, accesses the “DIRECT COMMANDS” screens
(index: Ab01-03)
Fig. 3.a
Function
Active Master/Slave board;
Control temperature;
Defrost probe temperature
Output status:
• compressor
• evaporator fan
• light
• continuous cycle
• anti-sweat heaters
Serial address;
Active set point;
% of electronic expansion opening valve;
% of compressor speed
8
5
6
7
Fig. 3.b
Button
UP
DOWN
SEL / ALM
Function scroll a list upwards or increases the value shown on the display; scrolls a list downwards or decreases the value shown on the display; accesses the set point for modifi cation and mutes the buzzer if an alarm is active.
Switch system on/off : hold the , fbutton for a few seconds, until the system status parameter (“oFF” / on”) is shown;
- to switch on/off , press .
- to exit the parameter, press and .
Change set point and switch lights on/off : from the main screen, press and hold and together for a few seconds, until “SET” is shown; then use or to select the parameter, “LIG” or “SET” and press to change the setting (again using and ) . To exit the menu, press
and .
Start a defrost: press and hold for a few seconds; when the button backlighting comes on, the defrost starts.
15 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
To access the menu tree, press from the main screen; the “enter password” screen is displayed.
Once having entered the correct password (default value 123), the fi rst main menu screen will be displayed.
Important:
• the password U ser; S ervice; M anufacturer is set in branch Ee01-03;
• if no button is pressed while navigating the menu tree, after 5 minutes the main screen is automatically displayed again.
To navigate inside the menu tree, use the following buttons:
• and : navigate around the submenus, screens and change values and settings;
• : confi rm and save the changes made;
• : to return to the previous menu a.On/Off b.Direct Commands a.Configuration
b.Manual Management a.Setpoint
b.Night regulation c.Setpoint config.
a.Compressor
b.EEV
c.Defrost
d.Fans
e.Rail Heaters f.Generic Functions a.Communication
b.M/S-Multievaporator c.Display
d.Clock
e.Password
f.Default
a.Compressor
b.EEV Safeties c.Temperature
d.History
a.Compressor
b.EEV
a.Analog In.
b.Analog Out c.Dig.In.
d.Dig.Out
a.Regulation
b.Scheduler
a.Regulation
b.Configurazion
c.Power+ d.Alarms
e.Diagnostic
a.Regolation
b.Configuration
c.Safety Procedures d.Diagnostic
a.Configuration
b.Scheduler
c.Special Functions
U
U
M
M
M
S
S
S
M
S
M
M
M
M
M
M
U
S
M
M
U
U
M
M
M
M
U
M
M
M
M
S
U
M
M
S
M
S
Tab. 4.a
Aa01-03
Ab01-03
Baa01-21
Bab01-07
Bac01-20
Bad01-20
Bb01-06
Ca01-05
Cba01
Cbb01-03
Cc01-02
Daa01-12
Dab01-13
Dac01-22
Dad01-07
Dae01-08
Dba01-02
Dbb01-03
Dbc01-08
Dbd01
Dca01-12
Dcb01-04
Dcc01-04
Dd01-05
De01-07
Df01
Ea01-03
Eb01-07
Ec01-04
Ed01-02
Ee01-03
Ef01-04
Dad01-07
Dbc01-08
Fc01-05
Fd00-50
Dae01-08
Dbd01
Heos +0300078EN - rel. 1.6 - 23.11.2017
16
ENG
5. STARTUP
5.1 Guided commissioning procedure
The Heos controllers can be setup the fi rst time from the pGDe user terminal connected to J15. After programming, the terminal can be removed or remain connected.
If the controller has not yet been confi gured, the user terminal shows the language selection and than the fi rst screen in a guided confi guration procedure, called the “wizard”. Otherwise, the same menu can be accessed from branch.
E.Confi guration>>f.default
.
The main parameters needed for general confi guration are shown one at a time. The wizard screens are all numbered in the top right corner; the following explanations refer to this number. To go from one screen to the next press , while to return to previous screen press .
Screen WZ09: set point and virtual probe composition. This screen is used to set the control set point and the weight of the outlet and intake temperature probes in the average for calculating the control temperature. When the parameter is set to 0%, the virtual probe coincides with the outlet probe, if set to 100% the virtual probe coincides with the intake probe.
Important: at the end of the procedure, exit by powering the unit OFF, after having exited screen WZ19 by pressing .
Screen WZ01: this shows the code of the application loaded on the controller (FLSTDmWL0M) and the revision. Pressing starts the guided procedure.
x.x xxx
Screen WZ02: select multi-evaporator/individual compressor confi guration. A group of controllers is called “multi-evaporator” when multiple controllers (up to 6) are connected in a Master/Slave network, and share the same compressor, controlled by the Master. If setting “Y” for the parameter on this screen, the unit will be part of a multi-evaporator group. Setting “NO”, the unit is confi gured as stand-alone or part of a
Master/Slave group with an individual compressor on each unit.
Screen WZ03 : unit address. The unit can be confi gured as the Master or as one of the Slaves, setting the parameter to MASTER or SLAVE1, SLAVE2,
… SLAVE 5. Setting this parameter also sets the controller pLAN address as a consequence: 1 for the Master, 2 for Slave 1, 3 for Slave 2, and so on up to 6 for Slave 5.
Screen WZ04: this is only shown if the controller is set as the Master and the multi-evaporator confi guration has been selected. This specifi es the number of evaporators connected to the Master. The default value is the number of Slaves connected.
Screen WZ05: this is only shown if the controller is set as the Master and the multi-evaporator confi guration has not been selected. specifi es the number of Slaves connected to the Master.
Screen WZ06: evaporator capacity. If the unit is confi gured as part of a multi-evaporator group, this screen is used to set the rated evaporator cooling capacity. This data is used to adjust the compressor speed based on demand from the various units served.
Screen WZ07: select type of unit. The type of unit can be selected as
SHOWCASE or COLD ROOM. If COLD ROOM is selected, other parameters are proposed: the position of the door switch and enable/disable the three temperature probes: outlet, defrost and intake.
Screen WZ08: select type of unit of measure (SI or Imperial) for temperature and pressure.
Screen WZ10: select type of compressor: BLDC, ON/OFF (single) or ON/
OFF (multiple).
Screen WZ11: select the digital input for multi compressors.
Screen WZ12: select compressor and inverter programming. For the
Compressor parameter, any one of the compressors managed by
Heos can be selected. Under the type of compressor, if the inverter is connected and on, the model of Power+ can be read. If the inverter is off or not connected, the last row of the screen displays the message
Power+ not connected. After having confi rmed the type of compressor, if communication with the inverter is active, Write parameters is displayed; choosing Y starts writing some of the parameters to the inverter, so as to ensure correct operation with the selected compressor. During the write procedure, the display shows Installing parameters…, replaced by a confi rmation message when the write procedure has ended. If the control is fi tted on a Slave on a multi-evaporator unit, this screen is not displayed.
Screen WZ13: select type and limits of the suction and condensing pressure probes.
Screen WZ14: with on-board compressor, if confi guring a Slave in on a multi-evaporator unit, only the suction probe is proposed.
Screen WZ15: select the type of outlet, defrost, intake, compressor suction and compressor discharge temperature probes. If is a Slave unit being confi gured, the compressor discharge temperature probe is not displayed.
Screen WZ16: select the type defrost and main defrost parameters.
Screen WZ17: select the operating mode for the evaporator fans.
Screen WZ18: set the parameters for connecting the supervisor.
Screen WZ19: end the wizard procedure. Pressing ENTER ends the procedure, and starts confi guring the system with the chosen options.
At the end of the confi guration, the controller needs to reset the unit to confi rm the data ( WZ20 ). Power down the controller for a few seconds and power on again.
WZ19
17 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
6. FUNCTIONS
detailed, the I/Os can be confi gured individually in branch B.a.xx
(inputs/outputs).
Note: many parameter codes, for uniformity, are the same as used on the MPXpro controller (manual +0300055EN). In this case, the pGDE shows a complete description of the parameters.
6.1 Probes (analogue inputs)
Heos features 10 universal analogue inputs (U1, U2, … U10) which can be confi gured for the functions shown in the following table. The fi rst seven
(U1-U7) relate to the main probes and are confi gured by default; the other three inputs are optional, and can be associated with other functions.
List of selectable functions
/Fq
/FI
/FL
/FM
/FW
/FY
/FG
/FH
/FE
/FF
/FN
/FP
/Fr
Par.
/FA
/Fb
/Fc
/P3
/P4
/P1
/P2
Description
Air outlet temperature (default U1)
Defrost temperature (default U2)
Air intake temperature (default U3)
Condensing pressure (default U7) (*)
Suction pressure (default U5) (*)
Discharge temperature (default U6) (*)
Suction temperature (default U4)
Liquid temperature
Room temperature (SA)
Room humidity (SU)
Glass temperature
Condenser water inlet temperature
Condenser water outlet temperature
Auxiliary probe 1
Auxiliary probe 2
Discharge temperature comp. 1
Discharge temperature comp. 2
Discharge temperature comp. 3
Discharge temperature comp. 4
Discharge temperature comp. 5
(*) Slave units in a multi-evaporator system do not have their own compressor.
Consequently, the discharge pressure and temperature probes are not used.
These inputs can be connected to temperature, pressure and humidity probes, as shown in the table below:
Temperature
NTC (-50T90°C; R/T 10 kΩ±1% @ 25°C)
NTC HT (0T150°C)
PT1000 (-100T400°C)
PT500 (-100T400°C)
PT100 (-100T200°C)
PTC (600Ω ...2200Ω)
Pressure
4-20mA
0-5V ratiometric
Humidity
4-20mA
0-1V
0-10V
Tab. 6.a
Active probes (voltage or current) can be powered directly by Heos (see the chapter on connections). For all these probes, the range of measurement needs to be confi gured on the corresponding screen.
Heos can modify the values read by the probes by applying a settable off set directly in the screen used to associate the function to the input.
Serial probes cannot be calibrated, while probes that are shared with the Master (such as the common pressure probe for multi-evaporator systems) are calibrated on the Master. Only one pressure probe can be shared across the Master/Slave network in multi-evaporator mode, and must only be connected to the Master. Simply correctly confi gure the probe in the corresponding screen and then on the Slaves, in the same screen, select the “shared” probe option. In this way, the Slaves will automatically look for the pressure value shared by the Master and use this to calculate local superheat. This saves the cost of installing a pressure probe on each evaporator, assuming that the pressure drop on of line in the corresponding section is negligible.
The room temperature and humidity probes must not be positioned too far from the corresponding showcases. At times it is better to install more than one if the supermarket is divided into zones with diff erent temperature and humidity (frozen foods, meat, fruit and vegetables, etc.): glass temperature probe: NTC060WG00. The glass temperature probe is connected at the coldest point of the glass on the showcase, so as to optimise operation of the anti-sweat device (heaters or fans). See instruction sheet +050002005.
Master/Slave system (see functional diagram for stand-alone confi guration on page 3)
Up to 6 units can be connected together in a Master/Slave confi guration, where the Master synchronises the defrosts and the night/day transition for the entire group, and shares the suction pressure reading.
Communication between units in the same Master/Slave group is managed over a pLAN sub-network connected to terminal J14 on each controller.
Multi-evaporator system (see functional diagram for multi-evaporator
Master/Slave network on page 13)
In a Master/Slave system, just one compressor can be used, connected to the Master, to serve the evaporators on the Slaves. This is called a multievaporator system. One condensing unit can be connected to up to six evaporators (including the Master). Each evaporating unit will be fi tted with a controller, electronic expansion valve, air temperature probes, refrigerant superheat temperature probe (evaporator outlet) and evaporator outlet pressure probe. On the controllers, the cooling capacity of each unit needs to be set (parameter PE2) and multi-evaporator mode must be activated on both the Master and the Slaves (parameter PE1 > 1). On multi-evaporator systems, the Master suction pressure probe reading can be shared and used to calculate the superheat on the Slaves (confi gured by default).
Heos manages four physical digital inputs, which can be selected as shown below. There is also the possibility to use a virtual digital input, propagated via pLAN from Master to Slaves. This is useful, for example, for a curtain switch, as the units can switch from daytime to night-time operation and vice-versa without needing additional wiring between the
Master and the Slaves. The virtual digital input can be set on the Master, using parameter A9, and will be propagated to the Slaves by selecting
“Virtual DI”.
For example, if there is a Heos confi gured as Master and another as Slave,
DI1 on the Master will be connected to the door switch, and its status will be shared with the Slave:
• on the Master, set parameter A9 to DI1;
• on the Slave, on the Door switch input confi guration screen, select
“Virtual DI”.
Heos +0300078EN - rel. 1.6 - 23.11.2017
18
Functions available for the digital inputs
For each function, there is a confi guration screen used to associate it with an available digital input. The same screen is used to select the input confi guration (normally open or normally closed). The status (Open or
Closed) displayed is the eff ective position of the input, while the function is associated with the selected logic. When the input is in the physical status specifi ed as “normal” in the logic, the function is “Not active”, when the input is in the opposite physical status, the corresponding function is “Active”.
List of selectable functions
/b8
/b9
/bA
/bb
/bC
A9
/bE
/bF
/bG
/bH
/bI
/bl
Parameter Description
/b1 Remote alarm
/b2
/b3
Delayed remote alarm
Enable defrost
/b4
/b5
/b6
/b7
Start network defrost
Door switch
Remote ON/OFF
Curtain/light switch - day/night
Continuous cycle
Cold room maintenance
Showcase cleaning
Inverter alarm
Lights
Virtual input
Compressor 1 alarm
Compressor 2 alarm
Compressor 3 alarm
Compressor 4 alarm
Compressor 5 alarm
Select dual temperature
Remote alarm (immediate)
Activation of the input causes:
• alarm message shown on the display
• activation of the buzzer
• activation of the alarm relays (if confi gured, see digital outputs);
• deactivation of the compressor.
Note: When the compressor is shut down due to a remote alarm the minimum compressor ON time (parameter c3) is ignored.
Remote alarm with activation delay
Operation of this alarm depends on the setting of parameter A7 (delay time for delayed remote alarm):
A7=0: signal only alarm on the display, normal operation of the controller is not aff ected (default);
A7≠0: alarm similar to the remote alarm (immediate), activation is delayed by the time set for A7.
Enable defrost
Used to disable any defrost calls. When the contact is open, all defrost calls are ignored. Parameter d5 can be used to delay activation.
Start network defrost
Closing the digital contact starts the defrost, if enabled. In the event of
Master/Slave network connection, if the controller is the Master, the defrost will be a network defrost (i.e. will also involve all the Slaves), while if it is a Slave, it will only be a local defrost. The defrost digital input can be used eff ectively to perform real time defrosts. Simply connect a timer to the multifunction digital input on the Master and use d5 to delay the defrosts on the various Slaves and thus avoid current overloads.
ENG
Door switch
With the door open (switch active) the following occur:
• Lights on
• Fans off
• The delayed alarm counter starts (parameter d8)
• The message “DOR” is shown on the PLD display
For stand-alone evaporator units:
• Compressor off (without deactivation ramp, cooling demand is not reset, but continues to be calculated)
For multi-evaporator units:
• Compressor cooling demand continues to be calculated, however the component relating to the unit with the door open is reset
• Expansion valve closed
When the door is closed:
• Lights off
• Fans on
For stand-alone evaporator units:
• The compressor is restarted as normal
For multi-evaporator units:
• The component of demand relating to the unit whose door was open is used again in the calculation
• The expansion valve resumes operation (pre-positioning as at start-up)
Note:
• when resuming control, the compressor protection times are observed;
• if the door remains open for a time greater than the value set for parameter d8, control is resumed in any case. The light remains on, the buzzer and the alarm relay are activated, and the temperature alarms are enabled, with the delay Ad.
Par.
Description d8 High temperature alarm bypass time after defrost and door open
Def Min Max UOM
30 1 240 min
Remote ON/OFF
Switches the controller off via the digital input. The PLD displays the value measured by the selected probe (parameter /t2) alternating with the message OFF; switch ON commands from the keypad or supervisor are ignored.
Note:
• if more than one input is confi gured as the remote ON/OFF, the off status of one any of these switches the controller OFF;
• the OFF control from digital input has priority over the keypad and the supervisor;
• if the controller remains OFF for longer than the value set for basic parameter (time between consecutive defrosts), when the controller is switched back on a defrost is performed.
Curtain/light switch
The curtain switch is used to control night/day status via a digital input.
When the switch is active (open if NC, closed if NO), the status is set to
NIGHT, when the switch is not active, the status is DAY.
• During Night status, the night-time set point Stn is used for control, calculated based on the set point St plus the off set defi ned by parameter r4 (Stn = St + r4). If r4 is negative, during Night status the eff ective set point is decreased from the Day set point.
• In addition, if necessary the control probe is changed based on the setting of parameter r6 (0 = virtual probe, 1= intake probe); the light is switched off .
• During Day status: normal operation resumes, set point = St, the virtual probe used as the control probe; the light output is activated.
19 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Cold room maintenance
The logic is the same as the door switch, and activation is as follows:
• Door opens: stop control in the same way as the door switch.
• Door closed again: ignored
• Door opened again: control resumes, same as when closing the door switch
• Door closed again: ignored
Showcase cleaning
When the contact closes, control stops, while the lights and probe alarms are enabled. When the contact opens again, or after a maximum time
(parameter bA1 - screen Df01), control resumes.
On screen Df02, a second type of logic can be set for the digital input. If set to Y, it works as described above. If set to N, the function is activated by pressing the button, and is deactivated after the timeout set for Df01.
Inverter alarm
This has the same functions as the remote alarm, and is connected to the inverter alarm output.
Lights
Lights On/Off , if the lights are controlled by time band, or day/night status, this function has higher priority.
List of selectable functions
/EM
/EN
/Eo
/Er
/ES
/Et
/Eu
/EV
Par.
/EA
/Eb
/EC
/Ed
/EE
/EF
/EG
/EW
/EX
/EY
Description
Fans 1 (default DO6)
Fans 2
Lights (default DO7)
Defrost heaters (default DO8)
Alarms
Auxiliary output
Anti-sweat heaters
Liquid injection solenoid
Curtain contact
ON/OFF Compressor
Inverter valve output
Fan/condenser output
Compressor output 1
Compressor output 2
Compressor output 3
Compressor output 4
Compressor output 5
Dual temperature valve output
Normally de-energised/normally energised alarm
A relay confi gured as an alarm may be set as: normally de-energised: the relay is energised when an alarm occurs; normally energised: the relay is de-energised when an alarm occurs.
Note: operation with the relay de-energised when an alarm occurs ensures maximum safety when the alarm is due to a power failure or disconnection of the power cables.
Heos features three analogue outputs (0-10 V), which can be associated with the following functions.
List of selectable functions
Par.
/LA
/Lb
/Lc
/Ld
/LE
/LF
/LG
Description
EC evaporator fans
Anti-sweat heaters
Water control valves (not enabled)
Condenser pump (not enabled)
Auxiliary output (not enabled)
Water-cooled condenser output
Air-cooled condenser output
6.5 Control
There are various modes for controlling air temperature for the conservation of foodstuff s in cold rooms and showcases. The following fi gure shows the position of the intake probe Sr and the outlet probe
Sm. The virtual probe Sv is a weighted average of these two, based on parameter /4, according to the following formula:
Sv =
Sm • (100 - /4) + Sr • (/4)
100
Par. Description
/4 Virtual probe composition
(weighted average Sr, Sm)
Def U.M. Min Max
0 % 0 100
For example if /4=50, Sv=(Sm+Sr)/2 represents the average value of the air temperature.
Example: vertical showcase
Waterloop
Sm
Heos features eight digital outputs, confi gurable as shown in the following table.
Sv = (Sm+Sr)/2
Heos +0300078EN - rel. 1.6 - 23.11.2017
Sr
20
Key
Sm Outlet probe
Fig. 6.a
Sr Intake probe Sv Virtual probe
During the day most of the load of the showcase is due to the warm air that enters from the outside and mixes with the cool air inside.
Control based on the intake probe, due to high temperature outside the showcase and the mixing of the air, may not manage to reach the set point. Displaying the intake temperature would show a temperature that is too high. Setting a set point that is too low for the intake probe Sr may cause the food to freeze. On the other hand, displaying the outlet temperature would show a temperature that is too low. Consequently, the display (on the PLD) of the control probe, set point or virtual probe can be confi gured using parameter /t2.
Temp.
Setpoint
Setpoint
ON-OFF P+I time
Fig. 6.b
Temperature control of the refrigeration unit is managed using a proportional + integral (P+I) algorithm. Based on the diff erence between control temperature and set point (proportional error) and the trend in this diff erence over time (integral error), the controller varies the request for cooling capacity on a scale from 0 to 100%. Depending on the model of compressor installed, this percentage is converted to an operating speed, expressed in revolutions per second (rps).
To adapt control to the characteristics of the refrigeration unit, the proportional gain (Kp) and integral time (tI) can be adjusted.
Kp represents the percentage of increase in cooling request according to the deviation from the set point [%/°C], tI represents the time interval to evaluate the variation and the trend in the integral error. High values of
Kp lead to higher variations in request for the same variation in control temperature (Treg), high values of tI lead to smaller variations in request over time.
Par.
Description
Kp Temperature control diff erential tI Compressor control integral time
Def U.M. Min Max
10 %/°C 1
500 s 0
200
999
Night-time operation
During night-time operation, the curtain on the showcase is closed and consequently less cold inside air is mixed with warm outside air. The thermal load decreases. The temperature of the air that cools the produce is near the outlet temperature, and therefore to avoid excessively low temperatures and reduce energy consumption, the set point needs to be increased at night, by setting parameter r4. Parameter r6 can then be used to assign the virtual probe Sv or intake probe Sr as the control probe.
The change to night-time operation must be signalled externally. This is done using the curtain switch (set using the parameters relating to the digital inputs) or by setting time bands (S1…S3), or from the supervisor, or using a command from the Master via the Master/Slave network. Nighttime status is activated by the transition of the assigned digital input from
“Not active” to “Active”. Vice-versa, a transition from “Active” to “Not active” changes back to daytime status. If, when the digital input is active, the signal is sent to change to daytime status by the supervisor or one of the other possible sources, the controller switches to daytime status. In other words, none of the sources has higher priority than the others, rather the status depends on the most recent command.
Par.
r4
Description
Set point off set in night mode
Def U.M.
Min Max
3.0 °C (°F) -50.0 50.0
(5.4) r6 Enable night-time control on intake probe (Sr) 0 hS1/mS1 Start time band 1 (hours/minutes) hE1/mE1 End time band 1 (hours/minutes) -
-
-
-
--
-
-
(-90.0)
0
-
-
(90.0)
1
During daytime status: Set point= St control on virtual probe Sv (Treg)
During night-time status: Set point= St + r4 control on Sr (se r6= 1) or Sv (if r6= 0)
ENG
Minimum and maximum set point value (parameters r1 and r2)
A parameter can be used to defi ne the minimum and maximum possible values for the set point.
Par.
Description r1 Minimum control set point limit r2 Maximum control set point limit
Def U.M. Min Max
-50.0 °C -50.0 max
(-58.0)
50.0
(°F)
°C
(-58.0) min 50.0
(122.0) (°F) (122.0)
ON/OFF
Parameter O/F is used to switch the controller ON/OFF. Any digital input confi gured as the remote ON/OFF signal has higher priority than the signal from the supervisor or the parameter.
Par.
Description
O/F Select unit status
Def U.M. Min Max
0 -0 1
If more than one digital input is selected as ON/OFF, ON status will be activated when all the digital inputs are inactive. The unit is OFF even if just one of the contacts is activated. When switching from ON to OFF and vice-versa, the compressor protector times are observed.
When OFF, the following are possible:
• access all the confi guration parameters;
• activate remote ON/OFF.
When OFF, the following alarms are reset:
• high and low temperature;
• open door (dor);
• expansion valve alarms LSA, LowSH, MOP).
Control off set with probe error (parameter r0)
By default, Heos uses the virtual probe Sv for control, that is, the weighted average of the outlet and intake probe (see parameter /4). If one of the two probes making up the virtual probe is broken or has an error, parameter r0 is used to continue normal control in controlled conditions, without the need for an immediate response by maintenance personnel.
Par.
Description r0 Control off set with probe error
Def U.M. Min Max
5.0 °C 0.0 20.0
(9.0) (°F) (0.0) (36.0)
The recommended value of r0 is the temperature diff erence between the outlet probe and intake probe reading in steady refrigeration unit operating conditions: r0 = Sr-Sm
The following two cases may occur: outlet probe Sm error: starts control based on the intake probe Sr alone, considering a new set point (St*) determined by the formula:
St* = St + r0 •
(100 - /4)
100 intake probe Sr error: Heos starts control based on the outlet probe Sm alone, considering a new set point (St*) determined by the formula:
St* = St - r0 •
(100 - /4)
100
If night-time operation has been set with the intake probe as the control probe, the controller considers /4=100 and uses the outlet probe. The new set point becomes:
St* = St-r0
Note:
• if an error occurs on both probes, the controller switches to duty setting operation, see below.
Example: Sm fault in daytime operation, with /4=50, St=-4, Sr=0, Sm=-8, r0 (recommended) = 0-(-8) =8. Then the new control probe will be Sr with:
St*= -4+8 •(100-50)/100=0
If the fault is on Sr, the new control probe will be Sm with:
St*= -4-8 •50/100=-8.
21 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Duty setting operation (parameter c4)
Duty setting is a special function used to maintain control in emergency situations with errors in the temperature control probes, until a service callout is possible. In the event of a temperature probe error, Heos uses the other probe available and adjusts the set point according to the setting of parameter r0. In the event of errors on both probes, Heos switches to duty setting mode. The controller is activated at regular intervals, operating for a time equal to the value set for the duty setting parameter c4, and off for a time equal to c5. Compressor speed is fi xed, at the value set for cI3.
Par. Description cI3 Compressor capacity percentage with probe alarm c4 Comp. on time in duty setting from probe alarm c5 Comp. off time in duty setting from probe alarm
5
5
Def U.M. Min Max
50 % 0 100 min 0 100 min 0 100 speed cl3
6.6 Compressor
6.6.1 Inverter compressor control
The compressor can be selected during the wizard (commissioning).
Before selecting the compressor installed on the unit, make sure that the
Power+ inverter is connected to the Heos controller. In screen Dab01, select one of the compressors available for the application.
• TOSHIBA DA91A1F-230V
• TOSHIBA DA130A1F-230V
• TOSHIBA DA220A2F-230V
• TOSHIBA DA330A3F-230V
• TOSHIBA DA420A3F-230V
Other models can be implemented by contacting Carel HQs directly. c4 c5 time
Fig. 6.c
Important: during duty setting, the compressor protection times are not observed.
The table below describes the possible fault situations relating to the control probes and the function that is activated.
Type of system Control probe fault
1 probe Sm
Sr
2 probes
* r0 must be >0.
Control
Duty setting
Duty setting control with Sr control with Sm
Duty setting
Parameter c4 c4 r0(*) r0(*) c4
Multi-evaporator system control
Each evaporating unit has its own cooling capacity (parameter PE2).
Compressor speed is calculated based on the average between the diff erence between the control temperature and the set point on each unit, weighed according to the cooling capacity of each evaporator. If there are three evaporators, the total error E_TOT that the P+I control algorithm will use to calculate the output depends on the cooling capacities of the three units (PM, PS1, PS2).
The E_TOT calculated in this way is applied to a P+I algorithm so as to determine the required percentage of cooling capacity, which translates into the required compressor speed.
Superheat modulation (multi-evaporator)
On showcases where active, the superheat set point varies between the user setting (P3) and an off set (PE7) with P+I logic, so as to correctly manage the control temperature. As the control temperature approaches the set point, the superheat set point is increased, so as to further close the expansion valve. To activate this function, set the off set PE7 to a value greater than 0.
Duty setting with multi-evaporator
Activation of duty setting mode on the Master controller implies that the compressor management times set for the Master controller are also used by all the connected Slaves. The Slaves will activate and deactivate control of the expansion valve according to compressor operation (ON or OFF). If a Slave is in duty setting mode (due to a probe error), the proportional component corresponding to the unit with the error will be equal to the value of parameter cI3, weighted according to the cooling capacity (PE2).
Heos +0300078EN - rel. 1.6 - 23.11.2017
22
The thermodynamic parameters and times are part of the Heos controller software: these are used to control the compressor, making sure that normal operating conditions are always within the limits set by the manufacturer. The electrical parameters are written in the Power+ inverter fi rmware: these are the parameters that allow the sensorless controller to eff ectively manage the compressor. Selecting the compressor involves confi guring all the thermodynamic parameters and times on the Heos controller; writing the parameters (last item on the screen) initialises the electrical parameters on Power+. Once the model has been selected and the parameters downloaded to Power+, no other compressor parameters are required to start the unit.
Envelope management
The envelope defi nes the operating range in which the compressor can safely work for an indefi nite time. This can be represented graphically by plotting several limits, inside which normal operating conditions need to be kept. The fi gure shows the envelope for the Toshiba DA series horizontal compressors.
Min 50 rps
Max Cond T 55°C
Min 30 rps
Min
30 rps
Min 15 rps
CR = 2
Min Cond T 10°C
Evaporation temp.
Fig. 6.d
The limits of the envelope consist of:
• Minimum and maximum condensing temperature
• Minimum and maximum evaporation temperature
• Minimum and maximum compression ratio (CR)
• Maximum compressor current draw
Normal operating conditions are defi ned by:
• Evaporation pressure (or saturated temperature)
• Condensing pressure (or saturated temperature)
• Discharge temperature
• Rotation speed (rps)
The form of the envelope may change according to compressor speed, and with this the normal operating conditions considered as being safe for the compressor. Consequently, a certain pair of operating pressures may be considered safe (within the envelope) at a certain speed, and unsafe (outside the envelope) at another speed.
With reference to the Toshiba envelope shown above: the conditions
Tcond = 40°C Tevap = -10°C are inside the envelope at a speed of 30 rps, but are outside at a speed of 15 rps.
The set point depends on the outside conditions (fl uid temperature at the heat exchangers) and on unit operation: compressor speed, expansion valve opening. Consequently, the set point can be shifted, increasing or decreasing the condensing and evaporation pressures by adjusting compressor speed and valve opening.
If operating conditions are near the limit of the envelope or outside of it, the controller will implement corrective actions so as to keep the set point within the limits allowed by the manufacturer. In these cases, therefore, eff ective compressor speed may not correspond to the cooling capacity required by the temperature controller and superheat may diff er from the value set by the user. If operating conditions remain outside of the envelope for a time exceeding the alarm threshold (default 180 s), the compressor will be stopped and an alarm signal will be activated, indicating the zone where operation was outside of the envelope.
2
3
Min Speed = 30 rps
1
4
9 5
1
Min Speed = 15 rps
6
7
8
Evaporation pressure
Fig. 6.e
The control actions are (see fi g. 6.e):
1. Inside envelope
2. High compression ratio
3. High condensing pressure
4. High current
5. High evaporation pressure
6. Low compression ratio
7. Low diff erential pressure
8. Low condensing pressure
9. Low evaporation pressure
Heos also features the following parameters for managing the compressor
ON/OFF times
Par. Description c0 Start control delay at power on c1 Minimum time between successive compressor calls 6 min 0 c2 Minimum compressor off time 3 min 0 c3 Minimum on compressor time
Def U.M. Min Max
0 min 0 15
3 min 0
15
15
15 c0 is used to delay the start of control when powering on This is useful in the event of power failures, so that the controllers (in the network) don’t all start at the same time, avoiding potential problems of electrical overload. c1 sets the minimum time between two successive starts of the compressor, irrespective of the request. This parameter can be used to limit the maximum number of starts per hour; c2 sets the minimum compressor off time. The compressor is not started again until the minimum time set has elapsed; c3 sets the minimum compressor running time.
ON
CMP
OFF c3 c2 c1
Fig. 6.f
time
ENG
On/off
The compressor starts whenever the request is equal to the minimum speed in the allowed range. For example, if the compressor has a range from 20 to 80 rps, it will be started when the request is equal to 25%.
The compressor is stopped when the request is equal to 0%.
Start-up procedure
When the compressor starts, a special startup procedure is applied. The compressor speed value depends on the model (cIA) and is kept constant, irrespective of the request from the controller, for a minimum time corresponding to the minimum ON time (c3). Once this time has elapsed, the compressor speed will refl ect the temperature control request rps cIA cIE
(decrease ramp) c3 min rps
Req
Req = min rps time
Fig. 6.g
Acceleration/deceleration ramps (screen Dab08)
According to the model of compressor, acceleration, deceleration and stopping ramps are defi ned. These are expressed in rps/s, and represent the maximum speed variation allowed each second to increase or decrease operating speed or stop the compressor. When the request varies more quickly, the compressor speed will change according to the set ramps.
Par.
Description cId Maximum speed increase (control) cIE Maximum speed decrease (control)
CIF Maximum speed decrease (shutdown)
Def U.M. Min Max
1.0
rps/s 0.1
Type comp
1.0
rps/s 0.1
Type comp
1.0
rps/s 0.1
Type comp rps
Speed ref.
Strat-up
Speed
Min
Speed
Acc. ramp
Very fast
Acc. ramp
Dec. ramp
Switch off ramp
Min ON time
Req time
Fig. 6.h
Equalising procedure (screen Daa02, Dab05)
If, when the compressor is requested to start, the diff erence between discharge pressure and suction pressure is greater than the maximum allowed for start-up (cI5), the equalising procedure (cE1) can be activated:
• using the expansion valve; this procedure involves opening the valve by a set percentage (cE3) and for a set time (cE2);
• using an equalising solenoid valve;
• When the pressure diff erential is less than (cI5), the expansion valve is positioned at the initial opening set for CP1, while if equalising by solenoid is set, this is closed and the compressor can be started.
Par. Description cE1 Select equalising procedure mode cE2 Maximum EEV opening time during equalisation cE3 EEV pre-opening percentage during equalisation
Def U.M. Min Max
0 --
90 s
0
0
1
999
60 % 20 99.9
Key:
CMP compressor
23 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG rps
Disch P
Pressure
Suct P
EEV rps
Req time
Control increase in ΔP when starting (screen Dab05)
To verify correct compressor rotation and a correct increase in pressure diff erential, the latter is checked whenever the compressor is started. This involves measuring the increase in ΔP after a set time (cI7). If the increase is less than the settable threshold (cI6), the compressor is stopped and the failed start alarm is signalled.
Par. Description Def U.M. Min Max cI5 Maximum pressure delta for compressor start 0.5 bar/ 0.0 120
(7.3) cI6 Minimum pressure delta for compressor start 0.2 psi bar/
(0.0)
0.1
(1762.8)
2.0 cI7 Pressure delta control delay to check comp. start-up
(2.9)
10 psi s
(1.5)
1
(29.4)
99
Start failure management (screen Dab06)
If the compressor fails to start, the controller will make several attempts to start it again.
Par. Description cI8 Activation delay after failed start cI9 Number of restart attempts after failed start
Def U.M. Min Max
30 s 1 360
5 -0 9
Oil recovery procedure (screen Dab11, 12)
In the event of operation a low speed, with low refrigerant fl ow-rate and solution to this problem involves a momentary acceleration (at speed cIV) of the compressor for a time cIS whenever operating speed is below a certain threshold (cIu) for a set time (cIr).
rps cIV - speed during procedure
CMP speed cIb cIA
PEV
EEV
M
EEV
S1
EEV
S2 close close
PEV close close
PEV close close
OIL cIS cIS
Fig. 6.j
cIS time
• The total procedure lasts cIS x no. of evap., and is divided into equal sections corresponding to the number of evaporators.
• In each section, the valve on that evaporator is active (PEV), while the others are closed.
• When the valves start normal control again at the end of the procedure, these return to the last position saved at the start.
• The compressor speed varies between StartUp (cIA) and cIb (keeping envelope control active), based on the weight of the evaporator.
• If Treg falls below the set point minus a set delta, the procedure ends, without a delay, for the cabinet/showcase in question.
The changeover from one section to the next occurs as follows:
• showcase 1 ends the procedure;
• the valve on showcase 2 opens;
• the valve on showcase 1 closes after a 5 second delay.
High discharge temperature control (screen Daa03, Daa04, Daa05)
Discharge temperature is an important indicator of the compressor’s health: by continuously monitoring this value, a procedure can be implemented to keep the temperature under control.
Envelope control involves actions to adjust compressor speed and expansion valve opening, so as to keep discharge temperature within the allowed limits. In addition, a liquid injection procedure can also be confi gured:
1. by an ON/OFF liquid injection valve activated when the discharge temperature exceeds a threshold, and deactivated when it returns below the threshold minus a diff erential.
2. by an electronic valve (connected to connector J8 - see Fig. 2.d); in this case there will be continuous modulation of operation with P+I control set by parameter LII.
Temp.
T inj
Diff cIu - Threshold time at high speed time cIr - time below threshold cIS
Fig. 6.i
Par. Description cIP Enable oil recovery management cIr Oil recovery procedure activation time
Def
1
30
U.M. Min Max
-0 min 1
1
480 cIS Compressor override time during procedure 2 min 1 cIu Min. comp. output to activate oil recovery procedure Comp %
10
10.0 99.9
cIV Comp. speed during oil recovery procedure 100 % 0 100
Oil recovery procedure in multi-evaporator system
If the system is confi gured as multi-evaporator, the oil recovery procedure will be:
• cIS Compressor override time: multiplied by the number of evaporators.
• The procedure is performed as shown in the fi gure:
EV
ON
OFF time
Fig. 6.k
Par. Description
LIV Type of liquid injection valve 0
LIt Liquid injection function activation threshold 95.0
(203.0)
LII Liquid injection control integral time
LId Liquid injection diff erential
LIc Duty Cycle
LIS Duty Cycle period
Def U.M. Min Max
5.0
(9.0)
30
--
°C
(°F)
--
100 s
°C
(°F)
100 % s
0
50.0
(122.0)
1
1
0.1
(0.2)
0
0
1
150.0
(302.0)
200
999
20.0
(36.0)
100
60
Heos +0300078EN - rel. 1.6 - 23.11.2017
24
ENG
Compression ratio control
When normal operating conditions mean the compressor works at a compression ratio below the limit allowed by the envelope, two procedures can be activated:
• MOP procedure using EEV: the valve closes, increasing the pressure diff erential and consequently the compression ratio
• compressor acceleration: increasing the speed, the compressor increases the pressure diff erential and consequently the compression ratio.
Compressor shutdown for pump down
The pump down procedure is used to improve compressor restarts without the risk of liquid on the suction side. In this case, the following actions are carried out:
• the EEV closes;
• the compressor continues operating and speeds up (or down), after the time cPL from when the function starts, based on the distance from the threshold, and stops when the pressure reaches cPt, or when the maximum time cPM has elapsed;
• during the procedure, the LP alarm is disabled.
6.6.2 ON/OFF compressor control
In the branch used to confi gure the type of compressor, ON/OFF compressors can also be selected; in this case, control is based on temperature too.
The PID remain parameters the same (kp and ti), with the same meaning for both inverter-controlled and on/off compressors.
The compressor is started when the request exceeds 98% and stops when it falls below 2%..
In multi-evaporator confi gurations, the suction valves close when the compressor is OFF.
Pressure control with ON/OFF compressor
If a multi-evaporator system is confi gured, control can be performed based on pressure rather than temperature. In this case, the control sequence is as follows:
• the compressor is started (based on pressure) by one of thermostats on the cabinet/showcase, with active envelope control;
• the individual EEV valves strive to maintain the desired controlled temperature inside the cabinet/showcase, as set on screen Ca02.
6.6.3 ON/OFF control with multi compressors
On screen Dab13, a delay time can be selected for activation (or deactivation) between one compressor and the next.
6.6.4 Propane (R290) inverter compressor control
Propane compressors can be selected for the specifi c part numbers listed below.
P/N Description
UP2AH610302SK Heos for propane cabinet - 230 Vac power supply
UP2BH610302SK Heos for propane cabinet - 24 V power supply
UP2AH630302SK Heos for propane cabinet with door - 230 Vac power supply
UP2BH630302SK Heos for propane cabinet with door - 230 Vac power supply
Tab. 6.a
As for the HFC models, the compressor is selected during the wizard to be completed when commissioning the unit
(see Commissioning). Before selecting the installed compressor, make sure that the Power+ inverter is connected to the Heos controller.
On screen Dab01, the compressors available for the application can be selected; currently this is:
• SIAM SPB 172
Other models can be implemented on request by contacting Carel HQ directly.
In the same way as for the other types of compressor, the thermodynamic and timing parameters are an integral part of the Heos controller software, so as to control the compressor while verifying that its operating conditions are always within the limits allowed by the manufacturer.
The electrical parameters are written into the Power+ inverter fi rmware, allowing sensorless control to manage the compressor eff ectively.
Furthermore, when selecting the compressor, all the thermodynamic and timing parameters are automatically confi gured.
Therefore, no other parameters need to be set before starting the compressor.
All of the compressor management functions (envelope, on/off ramps, equalisation, oil recovery, discharge temperature...) are the same as for HFC compressors.
Note: for this type of compressor, multi-evaporator management is
NOT available, rather the compressor can only be combined with a single evaporator.
The pressure probes must be suitable for use with propane (e.g.
SPKT***P**) ,
The confi guration for on/off compressor control (up to 5 compressors in
5 circuits) also allows the selection of propane compressors. In this case, there are no analogue inputs for managing the high and low pressure, but rather only the possibility to manage a digital alarm (for example, thermal overload) selected from the digital or/and universal channels (on screens Bac15 to Bac19); alarm discharge temperature management by probes selectable (Baa17 ... 21) with threshold setting on the mask Dad07.
The position of the digital outputs is selected on screens Dad15 to Dad19.
25 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
6.7 Defrost
Scheduling
Screens Dcb01-Dcb04 can be used to set up to 8 defrost events managed by the clock (RTC) on the controller, and activate Power Defrost. The screen for setting the fi rst two events is shown below:
For Master/Slave networks with synchronised end defrost, control resumes on all units when the last of these reaches dt1 or the time dP1 has elapsed.
The units in standby remain in the dripping stage: fans off and cooling deactivated (or at minimum capacity without heater defrost).
Heater defrost (d0 = 0, 2, 4):
W
aterloop
Heos can manage the following types of defrost, depending on the setting of parameter d0: electric heater, hot gas, reverse cycle. The defrost can end based on temperature, in which case the defrost probe Sd needs to be installed, or after a set time. In the fi rst case, the defrost ends when the defrost probe Sd reading exceeds the end defrost value dt1 or the time dP1 has elapsed, while in the second case, only when the time dP1 has elapsed. If end defrost by temperature is selected, an alarm can be activated if the defrost ends when exceeding the maximum time. At the end of the defrost, a dripping stage can be activated (if the dripping time dd is greater than 0), in which the cooling cycle is not active and the fans are off , and then a further post-dripping stage, if the time Fd
(screen Dd02) is greater than 0, during which the cooling cycle restarts with the fans off . Parameter d6 (screen Ec02) can be used to select what is displayed on the PLD during the defrost.
Par. Description d0 Type of defrost/end defrost
0: electric/ temp-timeout
1: reverse cycle/ temp-timeout
2: electric/ timeout only
3: reverse cycle/ timeout only
4: electric/ time with temp. control
5: hot gas bypass/ temp-timeout
6: hot gas bypass/ timeout only dt1 End defrost temperature
Def U.M. Min Max
0 -0 6 dP1 Maximum defrost duration dd Dripping time after defrost (fans off )
0 = no dripping d9 Disable evaporation pressure alarm in defrost
Fd Fan off time in post-dripping
8.0 °C -50.0
(46.4) (°F) (-58.0)
40 min 1
120 s 0
50.0
(122.0)
240
600
0
60
-s
0
0
1
240
Dripping time after defrost (param. dd)
This parameter is used to stop the compressor and the evaporator fans following a defrost so as to allow the evaporator to drip. The value of the parameter indicates the off time in minutes. If dd=0 no dripping time is enabled, and at the end of the defrost control resumes immediately, without stopping the compressor and the fan, if active.
The standard defrost cycle is illustrated below.
Normal reg.
Defrost state Drip Post drip Normal reg.
CMP speed
EEV
FAN
DEF
Key
CMP Compressor
EEV Expansion valve
FAN Fan
DEF Defrost
Fig. 6.l
Drip Dripping time
Post drip Post-dripping time time
Heos +0300078EN - rel. 1.6 - 23.11.2017
26
Fig. 6.m
When starting the defrost, the compressor stops, following the stopping ramp. The heaters are activated, the fans switch off and the expansion valve closes. At the end of the defrost, the heaters are deactivated, and the dripping time elapses with the compressor, valve and fans off . This is followed by the post-dripping stage, with the compressor and valve reactivated while the fans remain off . At the end of the post-dripping stage, normal control resumes.
Normal reg.
Defrost state Drip Post drip Normal reg.
CMP speed
EEV
FAN
DEF time
Fig. 6.n
Key
CMP Compressor
EEV Expansion valve
FAN Fan
DEF Defrost
Drip Dripping time
Post drip Post-dripping time
The heater defrost by time with temperature control (d0=4) activates the defrost output only if the evaporator temperature (Sd) is less than the value of parameter dt1, and ends after the time defi ned by dP1. This function is useful for energy saving.
Hot gas defrost (d0 = 5, 6)
W
aterloop
Fig. 6.o
ENG
When starting the defrost, the compressor is controlled at the defrost speed (parameter dH2). The bypass valve (HGV) is activated, the fans switch off and the expansion valve operates as normal. At the end of the defrost, the HGV is deactivated, the dripping period elapses with compressor operating at minimum capacity, the expansion valve operating and the fans off . This is followed by the post-dripping stage, with the compressor reactivated and the fans off . At the end of the postdripping stage, normal control resumes.
Key
CMP speed
EEV
FAN
HGV
DEF
Normal reg.
Defrost state
CMP Compressor
EEV Expansion valve
FAN Fan
DEF Defrost
Drip
Min
Speed
Post drip Normal reg.
Fig. 6.p
HGV
Drip
Hot gas bypass valve
Dripping time
Post drip Post-dripping time time
Defrost by reversing the cycle (d0 = 1, 3)
W
aterloop
Fig. 6.q
When starting the defrost, the compressor decelerates to minimum speed, and after a delay (dG5) the 4-way valve is activated.
After 5 seconds, the compressor accelerates to the defrost speed dG2, until the defrost ends. After the time dG6 elapses, the 4-way valve is deactivated and control resumes after a delay (dG7). During the defrost, the expansion valve can be set to operate as normal or remain in a stable, set position (parameters dG8, dG9, dG10)
Par.
Description Def U.M. Min Max dG2 Compressor speed (defrost by reversing the cycle) 50.0 rps cIc cIb dG3 Maximum acceleration in defrost (reverse cycle) 1.0
rps cId cIE dG4 Out of envelope alarm delay (defrost by reversing cycle) 600 s 0 999 dG5 4-way valve changeover delay on defrost dG6 4-way valve changeover delay after defrost
10
10 s s
0
0
99
99 dG7 End defrost delay (defrost by reversing cycle) dG8 EEV mode at start defrost dG9 EEV mode during defrost dG10 EEV mode at end defrost
60
1
1
1 s
--
--
--
0
0
0
0
180
1
1
1
CMP speed
EEV
FAN
4 WV
DEF
Min Speed
Fixed
Defrost Speed
Fixed
Min Speed time
Fig. 6.r
Key
CMP Compressor
EEV Expansion valve
FAN Fan
DEF Defrost
4WV Reversing valve
Maximum time between consecutive defrosts (parameter dI)
Parameter dI (screen Dca03) is a safety parameter used to perform cyclical defrosts every “dI” hours, even without the Real Time Clock (RTC). It is also useful if the pLAN or RS485 serial network is disconnected, when defrosts are controlled by the supervisor. At the start of each defrost, irrespective of the duration, an interval starts being counted. If this interval exceeds dI without a defrost being performed, one is started automatically.
The count is always active even if the controller is OFF. If set on Master controller, the parameter has eff ect on all the sub-LANs connected, if set on a Slave controller, it only has an eff ect locally.
Par. Description Def U.M. Min Max dI Interval between two consecutive defrosts 0=disabled 8 h 0 500 d4 Enable defrost at start-up
0: disabled (NO); 1: enabled (YES)
0 -0 1 d5 Defrost delay at start-up or from digital input 0 min 0 240
Defrost at start-up (parameter d4)
Defrost at start-up has priority over the control request. On the Master controller the defrost at start-up will be a network defrost, while on the
Slave controllers it will be local.
Defrost delay at start-up (parameter d5)
Also active when d4=0. If the digital input is set to enable or start a defrost via an external contact, parameter d5 represents the delay between enabling or calling the defrost and when it eff ectively starts. In a Master/
Slave network, to activate the heater defrost via a digital input on the
Master, it is suggested to use parameter d5 to delay the various defrosts on the Slaves, thus avoiding current overloads.
Example: if due to an RTC fault, the scheduled defrost (td3) is not performed, after the safety time dI, a new defrost starts.
dl
ON
DEF
OFF td1 time td2 td3
Fig. 6.s
Key dI Maximum time between consecutive defrosts td1…td3 Scheduled defrosts
DEF Defrost
27 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Pump Down
With a heater defrost, the pump down cycle is always performed, in which the evaporator is emptied of liquid refrigerant immediately before the defrost starts. When starting the defrost, the expansion valve is immediately closed, and the compressor stops with a deceleration ramp lasting a few seconds. In this stage, the refrigerant is pumped to the high pressure section of the unit.
Other defrost management parameters concern the activation delays, synchronisation between Master and Slave, defrost stages such as pump down and dripping, and advanced functions, including
• Running time;
• Sequential stops;
• Skip defrost;
• Power defrost.
End defrost synchronised by Master (parameter d2)
This parameter determines whether or not, in a local network, at the end of the defrost Heos waits for an end defrost signal from the Master before restarting the cooling cycle.
Par. Description d2 End defrost synchronised by Master
0 = local only;
1 = start;
2 = start and end.
Def U.M. Min Max
1 -0 2
In the event of synchronised end defrosts (d2=1), after the post-dripping time (if set), control resumes when the last unit has ended defrosting. The units that end the defrost before the last wait in the dripping stage (see the following fi gure); in this case parameter dd (dripping time) must be
≠ 0.
Normal reg.
Defrost state Drip Post drip Normal reg.
CMP speed
DEF
Drip
CMP speed
DEF
Drip
CMP speed
DEF time
Fig. 6.t
Defrost ended by timeout signal (parameter r3)
For defrosts that end at a set temperature, this enables an alarm to signal the end of the defrost by timeout.
Par. Description r3 Enable end defrost signal for maximum time
0: disabled (NO); 1: enabled (YES)
Def U.M. Min Max
0 -0 1
Running time defrost (parameters d10, d11, dA1)
Running time is a special function that determines when the refrigeration unit needs defrosting. In particular, it is assumed that if the evaporator temperature measured by probe Sd remains continuously below a certain set threshold (d11) for a certain time (d10), the evaporator may be frozen and a defrost is activated. The time is reset if the temperature returns above the threshold. The probe used is set by parameter dA1. In addition, at start-up the time dA2 must elapse before the running time procedure is activated.
Par. Description Def U.M.
Min Max d11 Defrost Running Time temperature threshold -4.0 °C -50.0 30.0 d10 Defrost time in Running Time mode
(24.8)
0
(°F) min
(-58.0)
0
(86.0)
240
0 = function disabled dt1 End defrost temperature (read by Sd) dA1 Select probe for activation (Sd or Tsat) dA2 Delay at start-up before activating Running
Time
8.0
(46.4)
0
30
°C
(°F)
-0 min 0
-50.0
(-58.0)
50.0
(122.0)
1
480
Temp.
dt1
T sat
/Sd d11
ON
DEF
OFF time dA2 d10
Fig. 6.u
Key
Sd Defrost probe
Tsat Saturation temperature converted from suction pressure
DEF Defrost
Running time defrost in a Master/Slave system
The defrost is activated, based on the selected probe reading, on the individual unit, independently of the others; if the Master starts a defrost in running time mode, this will be a network defrost, otherwise it will be local.
Sequential stops (parameters dS1, dS2)
Par. Description dS0 Enable defrost by Sequential Stops dS1 Compressor operating time for Sequential
Stops defrost dS2 Compressor off time for Sequential Stops defrost”
Def U.M.
Min Max
0 -0 1
180 min 0 999
10 min 0 999
Sequential stop mode is especially useful for high-normal temperature refrigeration units, and is based on intelligently stopping control to allow the evaporator to defrost naturally by the fl ow of ambient air only, without activating the defrost output.
If the function is enabled (parameter dS0), during normal control two countdown timers are started:
• OFFTIME: counts down when control has stopped and paused during control;
• ONTIME: counts down during control and paused when control has stopped.
Two events may occur, with reference to the following fi gure:
• OFFTIME reaches zero (instant C): OFFTIME and ONTIME are reset with the values of dS1 and dS2 and the defrost is considered as having already been completed. Control resumes;
• ONTIME reaches zero (instant A): OFFTIME is reset with the value of dS1 and the natural defrost cycle starts, which lasts for the time dS1. At the end of the defrost (instant B), OFFTIME and ONTIME are reset with the values of dS1 and dS2 and control resumes.
Heos +0300078EN - rel. 1.6 - 23.11.2017
28
ENG
1
OFFTIME = 0 regulation regulation
ON
CMP
OFF
2 time
C
ONTIME = 0 regulation defrost regulation
ON
CMP
OFF d5 time
A B
Fig. 6.v
Key
CMP Compressor
The purpose is to stop control and allow natural defrosts only when necessary.
Skip defrost (parameters d7, dn, do)
The function applies to defrosts that end by temperature, otherwise it has no eff ect. The Skip defrost function evaluates whether the defrost duration is less than a certain threshold (dn) and based on this establishes whether or not the subsequent defrosts will be skipped.
Par. Description d7 Enable skip defrost
0: disabled (NO); 1: enabled (YES) dn Nominal defrost duration for skip defrost do Number of defrosts to be performed when starting before activating skip def.
Def U.M. Min Max
0 -0 1
45 min 0
7 -1
240
9
The algorithm keeps a counter of the defrosts to be skipped:
• if the defrost ends in a time less than dn1, the counter of the defrosts to be skipped is increased by 1;
• if the defrost ends normally, the next defrost is performed;
• when the counter reaches 3, three defrosts are skipped;
• at start-up, the defrost is performed “do” two times without increasing the counter.
Power defrost (parameters ddt, ddP)
Power defrost is used to increase the end defrost threshold dt1 and/or the maximum defrost duration dP1. These increases allow longer and more eff ective defrosts. Power defrosts are performed on each defrost call during night-time status or when suitably confi gured by the RTC parameters (sub-parameter P of parameters td1 to td8), so as to allow the user to choose the conditions that are most suitable for this special procedure. Power Defrost is activated when at least one of the increases, ddt or ddP, has any value other than zero.
Par. Description ddt Additional defrost temperature delta in Power
Defrost mode ddP Additional maximum defrost time delta in Power
Defrost mode
Def U.M. Min Max
0.0 °C -20.0 20.0
(0.0)
0
(°F) min
(-36.0)
0
(36.0)
60
Note: in Power Defrost mode, the maximum defrost duration dP1 is increased by the value of parameter ddP.
The evaporator fans can be set to operate always, or be managed according to the temperature measured by the defrost and control probes. Fan behaviour is set by par. F0:
Note: during the dripping time and post-dripping time, if set, the evaporator fans are always OFF.
Fixed speed fans
Below are the parameters involved in managing fi xed speed fans, related by default to relay 6, and an example of the trend based on the diff erence between the evaporator temperature and the value of the virtual probe
(F0=1). If F0=2, activation depends solely on the evaporator probe temperature.
Par. Description
F0 Fan management confi guration
F1 Fan activation threshold
Def U.M. Min Max
0 -0 2
-5.0 °C -50.0 50.0
(23.0)
0
(°F)
--
(-58.0)
0
(122.0)
1 F2 Enable fans off with controller off (OFF); 0: see
F0; 1: always off
F3 Enable fans off during defrost
0: fans always ON
1: fans always OFF
2: fans ON, OFF in dd
Fd Fan Off time in post-dripping
0: no dripping
Frd Fan diff erential
0
60
-s
0
0
2
240 dd Dripping time after defrost (fans off )
2.0 °C
(3.6) (°F)
120 s
0.1
(0.2)
0
20.0
(36.0)
600
Sd-Sv
(F0 = 1)
Temp.
F1
Frd
ON
FAN
OFF time
Fig. 6.w
Key
Sd
Sv
F1
Evaporator probe
Virtual probe
Fan activation speed setting
Frd Control diff erential
FAN Evaporator fans
The fans can be turned off in the following situations:
• when the compressor is off (parameter F2);
• during defrost (parameter F3).
During the dripping period (parameter dd > 0) and the post-dripping period (parameter Fd > 0) the evaporator fans are always off . This is useful to allow the evaporator to return to temperature after defrosting, thus avoiding blowing warm hot and moist air into the refrigerated environment.
Variable speed fans
The installation of variable speed fans may be useful in optimising energy consumption. In this case, the fans are powered by the mains, while the control signal may come from a PWM or 0-10 V output. The maximum and minimum fan speed can be set using parameters F6 and F7. Frd in this case represents the variation in temperature for switching fan speed from minimum to maximum. If using the fan speed controller, F5 represents the temperature below which the fans are activated. There is a fi xed hysteresis of 1°C for deactivation.
Par. Description
F5 Evaporator fan cut-off temperature
(hysteresis 1°C)
F6 Maximum fan speed
F7 Minimum fan speed
F8 Fan peak time
0: function disabled (NO);
F9 Override fan output to 100% every:
0: function disabled (NO);
Def U.M.
Min Max
0.0 °C -50.0 50.0
(32.0)
80
10
10
(°F)
%
% s
(-58.0) min 100
0
0
(122.0) max
240
0 min 0 240
29 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Overview screen (screen Dbd01)
Temp.
Sd-Sv
(F0 = 1)
F5
F1
F1-Frd
F6
FAN
F7
0%
Key
Sd Evaporator probe
Sv Virtual probe
F5 Fan cut-off temperature
Fig. 6.x
time
F1 Evaporator fan activation threshold
Frd Fan activation diff erential
F6 is the maximum fan speed, expressed as a % of the output. For 0 to
10 V outputs, it represents the output voltage at maximum speed as a percentage. The same is true for the minimum speed set for F7. The fan peak time F8 represents the operating time at maximum speed set using parameter F6 to overcome the mechanical inertia of the motor.
F9 represents the time the fan is operated at maximum speed for the peak time (F8). If the fan is kept operating too long at low speed, ice may form on the blades; to avoid this, every F9 minutes the fan is operated at maximum speed for the time set for parameter F8.
Fan Speed
F6
F7
0%
Frd
F1
F5
Fig. 6.y
1°C
Sd
(Sd-Sv)
6.9 Electronic valve
Heos can manage Carel E2V single-pole valves (with 6-wire cable).
Double-pole valves (with 4-wire cable) are incompatible with Heos.
To manage the electronic expansion valve, two additional probes must be installed and suitably confi gured:
• temperature probe for measuring the superheated gas temperature at the evaporator outlet;
• pressure probe for measuring the saturated evaporation pressure/ temperature at the evaporator outlet
Installation notes:
Heos is designed to manage one electronic expansion valve that controls the fl ow of refrigerant inside an individual evaporator. Two evaporators in parallel cannot be managed with just one electronic expansion valve.
The NTC/PTC/PT1000 temperature probe must be installed near the evaporator outlet, according to the standard installation methods (see the installation notes on the E2V instruction sheet). Suitable thermal insulation is recommended. CAREL off ers special types of probes designed to simplify installation in contact with the refrigerant pipe:
• NTC030HF01 for Retail use IP67, 3m, -50T90 °C, 10 pcs
• NTC060HF01 for Retail use IP67, 6m, -50T90 °C, 10 pcs
To measure the saturated evaporation temperature, diff erent types of probes can be used; in particular, the following can be installed:
0 to 5 V ratiometric pressure probe (recommended by CAREL);
4 to 20 mA active pressure probes .
Conversion of the pressure to a temperature value is performed automatically once the refrigerant has been selected (see the paragraph on the compressor)
Heos manages the proportional opening of the electronic expansion valve, adjusting the fl ow of refrigerant in the evaporator, so as to maintain the superheat around the value set for advanced parameter P3 (superheat set point). The opening of the valve is controlled simultaneously yet independently from normal temperature control. When there is a refrigeration call (the compressor is operating), control of the electronic valve is also activated and then managed independently of compressor speed. If the superheat value read by the probes is greater than the set point, the valve is opened proportionally to the diff erence between the values. The speed of variation and the percentage of opening depend on the PID parameters set. The opening is continuously modulated based on the superheat value, with PID control.
Superheat set point (parameter P3)
This is used to set the reference superheat value for the control of the electronic valve. It does not determine the actual superheat value, but rather the desired value. Heos, with PID control, tends to maintain the actual superheat, calculated based on the probe readings, around the value set for this parameter. This is done by gradually varying the opening of the valve based on the diff erence between the actual superheat and the set point.
Par. Description
P3 Setpoint superheat
Def U.M.
Min Max
10.0 (36.0) °C (°F) 0.0 (0.0) 30.0 (54.0)
Important: the set point value calculated depends on the quality of the installation, the position of the probes and other factors.
Consequently, depending on the installation, the set point read may deviate from the actual value. Set point values that are too low (2...4 K), albeit ideally usable, may cause problems involving the return of liquid refrigerant to the compressor.
Valve position at start control (parameter cP1)
This is used to set the position of the valve as a percentage when control starts. High values ensure intense and immediate cooling of the evaporator when each call is sent, however may cause problems if the valve is oversized with reference to the cooling capacity of the controller.
Low values, on the other hand, allow a more gradual and slower action.
The values set should be coherent with compressor start-up speed.
Par. Description
Psb Enable EEV opening in standby
CP1 EEV opening at start-up cP2 EEV pre-positioning delay
Def U.M.
Min Max
0 -0 1
50
6
% s
0
0
100
300.0
PID control of the expansion valve (parameters P4, P5, P6)
The opening of the electronic valve is controlled based on the diff erence between the superheat set point and the actual superheat calculated by the probes. The speed of variation, the reactivity and the ability to reach the set point depend on three parameters:
• Kp = proportional gain, parameter P4;
• Ti = integral time, parameter P5;
• Td = derivative time, parameter P6;
The ideal values to be set vary depending on the applications and the utilities managed, nonetheless default values are proposed that allow good control in the majority of cases. For further details, refer to classic
PID control theory.
Heos +0300078EN - rel. 1.6 - 23.11.2017
30
ENG
Par. Description
P4 PID: EEV proportional gain
P5 PID: EEV integral time
0 = function disabled (NO);
P6 PID: EEV derivative time
0 = function disabled (NO);
Def U.M.
Min Max
15.0
0.0
100.0
150 s 0 999
5.0
s 0.0
100.0
P4: this represents the amplifi cation factor. It determines an action that is directly proportional to the diff erence between the set point and the actual superheat value. It acts on the speed of the valve, in terms of steps/°K. The valve moves P4 steps for every degree variation in the superheat, opening or closing whenever the superheat increases or decreases respectively. It also acts on the other control factors, and is valid in both normal control and with all emergency control functionsa.
• High values ==> fast and reactive valve
• Low values ==> slow and less reactive valve.
P5: this represents the time required by the controller to balance the diff erence between the set point and the actual superheat. It practically limits the number of steps that the valve completes each second. It is only valid during normal control, the special functions in fact have their own integral time.
• High values ==> slow and less reactive valve
• Low values ==> fast and reactive valve
• P5 = 0 ==> integral action disabled
P6: this represents the reaction of the valve to variations in the superheat.
It amplifi es or reduces variations in the superheat value.
• High values ==> rapid variations
• Low values ==> limited variations
• P6 = 0 ==> diff erential action disabled
6.10 Protection functions
LowSH Low superheat
To prevent too low superheat values that may cause the return of liquid to the compressor or system instability (swings), a low superheat threshold can be defi ned, below which a special protection function is activated. When the superheat falls below the threshold, the system immediately enters low superheat status and activates a control action, in addition to normal control, with the aim of closing the electronic valve more quickly. In practice, the intensity of system “reaction” is increased.
If the device remains in low superheat status for a certain period, a low superheat alarm is activated, with the display showing the message ‘LSh’.
The low superheat signal features automatic reset, when the condition is no longer present or the controller is switched off (standby).
Par. Description
P7 LowSH: low superheat threshold
Def U.M. Min Max
2.0 °C 0.0 30.0
(35.6)
10
(°F) s
(32.0) (86.0)
0.0
999 P8 LowSH: EEV low superheat integral time
0 = function disabled (NO);
P9 LowSH: EEV low superheat alarm delay
0 = function disabled (NO);
120 s 0 300.0
TempSH P7
ON
LowSH
OFF
ON
ALARM
OFF time
P9
Key
SH Superheat
LowSH Low superheat protection
ALARM Alarm
Fig. 6.z
P7 Low SH protection threshold
P9 Alarm delay
MOP Maximum evaporation pressure
When starting or restarting a system, the compressors may not be able to satisfy cooling demand. This may cause an excessive increase in the evaporation pressure and consequently the corresponding saturated temperature. When the evaporation pressure, expressed in degrees
(saturated), rises above the threshold, after a certain settable time the system enters MOP protection status: PID superheat control is stopped and the controller starts gradually closing the valve with an integration action to return the evaporation pressure below the threshold. The protection function has been designed to allow a gradual return to normal operating conditions, that is, when the critical conditions have ended, the controller temporarily operates with a higher superheat set point until the function is automatically reset.
Par.
Description
PM1 MOP
Def U.M. Min Max
15.0 °C LOP 30.0
(59.0) (°F)
20.0
s 0.0
(86.0)
999 PM2 MOP: High evaporation temperature integral time
PM3 MOP: High evaporation temperature alarm delay 240 s
0 = function disabled (NO);
0 300.0
T evap
PM1
MOP
ON
OFF
ON
ALARM
OFF time
PM3
Key
T_EVAP Evaporation temperature
MOP MOP protection
ALARM Alarm
Fig. 6.aa
PM1 MOP threshold
PM3 Alarm delay
PM1 represents the maximum evaporation pressure, expressed in degrees (saturated), above which the MOP protection and alarm are activated (each with its own delay times). There is a gradual return to normal operation, to avoid the critical situations arising again.
31 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
PM2 represents the integration time for the maximum evaporation pressure protection function. This replaces normal PID control during
MOP status.
• PM2 = 0 ==> MOP protection and alarm disabled
PM3 represents the alarm activation delay after exceeding the MOP threshold. When the alarm is activated, the following occur:
Message ‘MOP’ shown on the display
The buzzer is activated
The alarm features automatic reset when the evaporation pressure falls below the threshold PM1.
LSA - Low suction temperature
When the suction temperature falls below the threshold, the alarm is activated after the set delay, closing the electronic valve. The alarm is reset when the suction temperature exceeds the set threshold plus the hysteresis. Reset is automatic for a maximum of four times in a two hour period. Upon the fi fth activation in such period, the alarm is saved and requires manual reset from the user terminal or supervisor.
Par. Description
P11 LSA: low suction temperature threshold
P12 Low suction temperature alarm delay
0: alarm disabled (NO);
Def U.M. Min Max
-40.0 °C -50.0 30.0
(-40.0) (°F)
120 s
(-58.0)
0
(86.0)
300
P11 represents the suction temperature below which the alarm is activated, after the corresponding delay. The threshold for resetting the alarm is represented by this threshold plus a 3°C hysteresis.
P12 represents the alarm activation delay after exceeding the threshold
P11. When the alarm is activated, the following occur:
• message ‘LSA’ shown on the display;
• the buzzer is activated
The alarm features automatic reset for the fi rst four activations over a two hour period, then becomes manual reset.
• P12 = 0 ==> LSA alarm disabled
PL1 represents the evaporation pressure, expressed in degrees
(saturated), below which the LOP protection is activated. The protection is deactivated immediately when the pressure exceeds this threshold.
PL2 represents the integral constant used during the activation of the
LOP protection. This integral time is summed to normal PID control.
• PL2 = 0 ==> LOP protection and alarm disabled
PL3 represents the alarm activation delay after exceeding the LOP threshold. When the alarm is activated, the following occur: message ‘LOP’ shown on the display; the buzzer is activated.
The alarm features automatic reset when the evaporation pressure rises above the threshold PL1.
PL3 = 0 ==> LOP alarm disabled
High superheat
To avoid excessively high superheat values, an alarm threshold and activation delay can be set.
When superheat exceeds the threshold, the system immediately enters high superheat status and activates a function that closes the electronic valve more quickly. If the device remains in high superheat status for a certain period, an alarm is activated, with the display showing the message
‘HSh’. The high superheat signal features automatic reset, when the condition is no longer present or the controller is switched off (standby).
Par. Description
Pa High superheat threshold
Def U.M. Min Max
35.0 °C 0.0 50.0
(95.0) (°F)
600 s
(32.0)
0
(122.0)
999 Pb High superheat alarm delay
Manual valve positioning (screen Bb05)
PMP is used to enable/disable manual valve positioning.
PMP = 0: manual positioning disabled;
PMP = 1: manual positioning enabled.
If manual positioning is enabled, PMu is used to set the manual opening of the electronic valve. The value is expressed in steps.
Par.
Description
PMP Enable manual expansion valve positioning
0 = disabled (NO); 1 = enabled (YES)
PMu Manual expansion valve position
Def U.M. Min Max
0 -0 1
0 steps 0 480 T suct
P11
3°C
ON
LSA
OFF
ON
ALARM
OFF
P12 time
Fig. 6.ab
Key
T_SUCT Suction temperature
P11
LSA LSA protection
LSA: low suction temperature threshold ALARM Alarm
P12 LSA: LSA alarm delay
LOP Minimum evaporation pressure
This function is used to prevent the evaporation pressure from remaining excessively low for too long. When the evaporation pressure, expressed in degrees (saturated), falls below the threshold, the LOP protection is activated, which adds an integration action to normal PID control, specifi cally devised to be more reactive as regards the opening of the valve. PID control remains active, as the superheat must continue to be monitored as to avoid fl ooding the compressor. The LOP alarm is delayed from the activation of the protection function, both are reset automatically when the pressure value, in degrees (saturated), exceeds the threshold.
Par. Description Def U.M. Min Max
(-40.0)
PL2 LOP: Low evaporation temperature integral time 10
PL3 LOP: Low evaporation temperature alarm delay 120 s
(°F) s
(-58.0)
0.0
0
999
300.0
6.11 Anti-sweat heater or fan modulation
IAnti-sweat heaters are controlled by comparing dew point calculated based on the room temperature and humidity, and the temperature of the showcase glass, measured by a probe or estimated using the showcase outlet, intake and room temperature. Two types of anti-sweat heater control are available:
• PI (proportional, integral);
• fi xed activation (manual control).
The conditions for activation of the algorithms are as follows:
PI fi xed activation (manual control) rHd > 0 rHd = 0; rHt >0
If the glass probe temperature is estimated (not read), PI control becomes proportional only. Based on a series of conditions, the PI algorithm ceases and, if activated, control with fi xed activation commences. In this case, alarm ACE is signalled on the display.
Condition
Glass temperature probe not valid
Cause physical probe not confi gured or error; the estimate of the glass temperature probe cannot be used because the outlet probe or intake probe is not confi gured or has an error or the room probe is broken or missing
Dew point not valid room humidity and/or temperature probe are not confi gured and operating; the serial dew point value is not available .
Heos +0300078EN - rel. 1.6 - 23.11.2017
32
PI control
Inputs
The room humidity (SU) and temperature (SA) probes can be (see parameters /FL, /FI):
• connected to the Master, which automatically shares them with the Slaves;
• connected locally to each controller;
• sent from the supervisor via the serial probes.
Alternatively, the supervisor can directly supply the dew point value
(Sdp) using the serial probes. The glass temperature probe (Svt) can be connected directly to each controller (see parameter /FM), or estimated.
The estimate of the glass temperature probe reading is performed internally when: room temperature (SA), outlet temperature (Sm) and intake temperature (Sr) are available, and depends on parameters Ga, Gb and Gc. Parameters rHo, rHd determine the modulating output.
Par.
Description
Ga Coeffi
Def U.M. Min Max
2.0 °C -20.0 20.0
Gb Coeffi
(35.6)
22
Gc Coeffi 80 rHo Anti-sweat modulation off set from dew point 2.0
(°F)
%
%
°C
(-4.0)
0
0
-20.0
(68.0)
100
100
20.0 rHd Anti-sweat heater diff erential modulation
(3.6)
0.0
(0.0)
(°F)
°C
(°F)
(-36.0)
0.0
(0.0)
(36.0)
20.0
(36.0)
Svt = (SA - Ga -3) - Gb • (SA - Ga - Ti)
100 dove:
Ti = Sm • Gc + Sr • (100 - Gc)
100
If one of the probes is not available (SA or either Sm or Sr), only fi xed activation control will be possible, based on parameters rHu and rHt.
Outputs
The analogue output for the anti-sweat function can be 0-10 VDC
(analogue output Y1, Y2, Y3) or PWM (SSR output OUT2).
If using the 0 to 10 Vdc output, the output voltage will vary based on the anti-sweat control activation percentage (see Fig. 6.ad). This output can be used to directly control an FCS controller, for example.
If using SSR output Out2, the output will be active for a time that is proportional to the function activation percentage (see Fig. 6.ad), with a period equal to rHt (manual anti-sweat activation time, settable between
1 min and 30 min).
The anti-sweat control activation percentage (OUT) depends on the diff erence between the dew point calculated and the glass temperature probe value (measured or estimated), on the value of parameter rHo
(off set), the value of parameter rHd (diff erential), the Cutoff (rhB) and the hysteresis (rHC) (see the following fi gure).
Out
Max rHC
Min
0%
Sdp rHo rHd rHB
Cutoff
Svt
Fig. 6.ac
Key
Sdp Dew point rHo Anti-sweat heater modulation off set
Svt Glass temperature probe
Min Minimum anti-sweat output value rHd Anti-sweat heater modulation diff erential Max Maximum anti-sweat output value
OUT Anti-sweat controller
ENG
Min: minimum output fi xed at 10%; Max: maximum output fi xed at 100%.
The action is only proportional if the estimate of the glass temperature is used, and proportional and integral (Tint=240 s, constant) if the actual glass temperature probe is used. The aim of the integral action is to bring the glass temperature towards the set point (Sdp+rHo).
Important: if using supervisor serial probes to propagate the room temperature, humidity or dew point values, the Heartbeat on the
“Dew point propagation plugin” needs to be set appropriately. This is used by the HEOS controller to understand whether the supervisor is continuing to send new values. If Heos does not receive any new values for more than 30 minutes, alarm ACE is signalled and manual control
(fi xed activation) is activated. This is useful in the event of power failures on the supervisor.
The probe not updated alarms are normally displayed when the unit is fi rst started, i.e. when the variables have yet to be initialised.
Fixed activation control (manual control)
Control depends only on parameters rHu and rHt and follows the trend shown in the fi gures.
Par.
Description rHt Anti-sweat heater activation period rHu Manual activation anti-sweat heaters percentage 0: disabled (NO);
Def U.M. Min Max
30
70 min
%
10
0
180
100
Out
10 Vdc
(ON)
0
(OFF) rHu rHt
Fig. 6.ad
Key: rHu Manual anti-sweat activation percentage rHt Manual anti-sweat activation time
OUT Anti-sweat controller time
6.12 Condenser control
Heos can also optimise the condenser control (generally water-cooled) the condensing pressure/temperature, however can also use the water temperature; there are two main types of valves, two-way or threeway mixing valves. In certain special cases (for example, when ambient heat can be recovered from), air-cooled condensers can also be used; in this case, control is performed based on the condensing pressure/ temperature. Consequently, two types of condenser can be chosen on screen Daa06 (displayed only if both analogue outputs have been activated): water-cooled and air-cooled
Water-cooled condenser
Below is the water connection diagram with two-way valve. In this case, the fl ow-rate is modulated so as to stabilise the condensing temperature.
M
0...10V
T water in
T water out
T cond
Hot GAS
Cooled GAS
Fig. 6.ae
Note : a variable fl ow-rate pump must be used in the water loop so as to respond to the variations required by the various cabinets/ showcases.
33 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Below is the control diagram based on condensing temperature; the same also applies when using the diff erential between water inlet and outlet temperature.
Output
100%
Fan Speed
100%
Diff.
Temp. cond.
or Temp. water
Setpoint
Fig. 6.af
Note : on screens Bab01-07 for selecting the analogue outputs, the minimum and maximum values can be set for the output voltage. For example, to select the 2-10 Vdc standard, simply set the minimum voltage to 2V.
Screen Daa07 is used to select the type of control (condensing temperature or water inlet/outlet temperature or diff erential), the corresponding set point, diff erential and integral time.
If control is selected based on water temperature, screen Daa10 is displayed for setting a maximum safety threshold for the condensing temperature/ pressure.
Diff.
Setpoint
Fig. 6.ah
Par.
Description co4 Condensing temp. set point co5 Cond. control proportional coeffi co6 Cond. control integral time
Temp. cond.
Def UoM Min Max
20.0 °C 10.0 55.0
(68.0)
40
(°F)
100 s
(50.0)
%/°C 1
0
(131.0)
999
999
6.13 Anti-sweat on inverter with cold plate
If the inverter is water-cooled, condensation may form when the water temperature is lower than the dew point in the environment where the inverter is installed. This may potentially occur on low temperature units, when the cooling water is normally lower than room temperature.
There are basically two types of connection for inverter cooling circuits:
• Parallel connection to the condenser
• Serial connection to the condenser
Par.
Description co3 Type of water-cooled condenser control
0: COND. TEMP.
1: W OUTIN TEMP.
2: W OUT TEMP.
3: W IN TEMP.
co4 Condensing temp. set point
Def
0
UoM Min Max
0 3
Condenser water temp. diff . set point co5 Cond. control proportional coeffi co6 Cond. control integral time coA Cond. control safety set point cob Cond. control safety diff erential
20.0
(68.0)
5.0
(9.0)
40
100
42.0
(107.6)
5.0
(9.0)
°C
(°F)
°C
10.0
(50.0)
0.1
(°F) (0.18)
%/°C 1 s
°C
0
30.0
(°F)
°C
(86.0)
0.0
(°F) (0.0)
55.0
(131.0)
20.0
(36.0)
999
999
55.0
(131.0)
9.9
(17.8)
At compressor start-up, in order to improve the response of the condensing stage control valve, parameters can be set (screens Daa08 and Daa13) to allow pre-opening.
Parallel connection
Below is the inverter water connection diagram. In this case, there is an on/off valve controlled based on the temperature read near the inverter’s microprocessor. The set point and corresponding diff erential (fi xed at
1 °C) must be set, keeping in consideration that the cooler parts of the board are below the controlled temperature and depend on the type of heat exchanger used to cool the inverter.
M
ON/OFF
T cond
Fig. 6.ai
The on/off valve is selected in confi guration branch Bad13, while the parameters are set on screen Dad06, used to select a minimum operating temperature threshold for the valve, below which the valve closes.
Air-cooled condenser
Below is the air-cooled condenser connection diagram. In this case, air fl ow-rate is modulated by controlling the fan (0-10 Vdc or by digital output, set in the I/O confi guration menu) so as to stabilise the condensing temperature.
0...10 V
T cond
Hot GAS Cooled GAS
Fig. 6.ag
Below is the control diagram based on condensing temperature/ pressure.
Note : If a digital output is selected (Bad13), the confi guration is automatically set to “Parallel connection”, while if the other confi guration is required, no output must be selected for Bad13.
Heos +0300078EN - rel. 1.6 - 23.11.2017
34
Serial connection
Below is the inverter water connection diagram. In this case, there is a modulating controlled based not on the temperature inside the inverter, but rather giving priority to the condensing pressure. For further control
(temperature inside the inverter), a minimum condensing temperature threshold is set, below which the valve is progressively closed.
T cond
M
0...10V
Fig. 6.aj
The modulating valve is selected in confi guration branch Bab06 for condensing pressure control, the same for the control parameters. In addition, screen Daa10 is used to set and enable this safety threshold so that when the compressor is off , the valve is deactivated.
Note: The minimum inverter temperature with the compressor running is around ten degrees lower than the value read, and consequently the corresponding threshold should be set accordingly. In addition, special care should be paid to the values set, when need to be checked on the specifi c application. Otherwise, on low temperature showcases, air-cooled inverters can be used.
Par.
Description coE Enable inverter anti-sweat
0= NO
Def
0
1= YES coc Inverter anti-sweat temperature threshold 15.0
(59.0) cod Inverter anti-sweat temperature diff erential 3.0
(5.4)
UoM Min
°C
(°F)
°C
(°F)
0
0.0
(32.0)
0.0
(0.0)
Max
1
50.0
(122.0)
10.0
(18.0)
ENG
6.14 “Dual temperature” management
This procedure provides “2 sets” (setA and setB) of parameters for managing both a low temperature (setB) and medium temperature cabinet (setA).
The set of parameters (setA or setB) can be selected either via the digital input set on screen Bac20 or on the keypad via screen Df04; the function is enabled and the type of selection (keypad/supervisor or digital input) is set on screen Df03.
In the event of changes to the cabinet circuit, a digital output set on screen Bad20 can be used; the active set used (A or B) for the digital output is always selected on screen Df03.
The parameters (setA and setB) are programmed on screens Df05-13 for setA and screens Df14-22 for setB; if the active set is “A”, then only the parameters in setB will be visible; vice versa if the active set is “B” only the parameters in setA will be visible. This is because if set “A” is active, the corresponding operating settings are currently selected in the respective control loops, while setB can be set on screens Df14-22; switching the sets swaps the parameter settings.
The aff ected parameters are listed below:
"Dual temp." screen
Df05/14
Par. Description
Df06/15
Df07…10/
16…19
Df11/20
Df12/21
Df13/22 st User temperature set point d0 Type of defrost/end defrost dt1 End defrost temperature dP1 Maximum defrost duration dI Interval between two consecutive defrosts
0=disabled d2 Defrost control in pLAN
/10 Select probe used for end defrost (d0=4) td1…8 Defrost schedule day tt1…8 Defrost schedule hours tt1…8 Defrost schedule minutes d11 Temperature set point for running time d10 Defrost time for running time dA2 Delay at start-up to start Running time
F1 Fan activation threshold
F3 Enable fans off during defrost 0
AH High temperature alarm threshold Al.1
AL Low temperature alarm threshold Al.1
AH2 High temperature alarm threshold Al.2
AL2 Low temperature alarm threshold Al.2
PE2 Evaporator capacity screen
Ca02
Dca01
Dca02
Dca02
Dca03
Dca04
Dca05
Dcb01…4
Dcb01…4
Dcb01…4
Dcc02
Dcc02
Dcc02
Dd01
Dd02
Fc01
Fc01
Fc04
Fc04
Eb04
Tab. 6.ak
35 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Mask index” : iindicates the unique address of each screen and consequently the path needed to reach the parameters available on this screen; for example, to reach the parameters corresponding to the suction pressure probe with mask index Bab01, proceed as follows:
Main menu B.In./Out.
Î a.Status
Î b.Analog.in.
Below is the table of the parameters that can be displayed on the terminal. The values indicated with ‘---‘ are not signifi cant or are not set, while the values indicated with ‘…’ may vary according to the confi guration, with the possible options visible on the user terminal. A row of ‘…’ means that there are a series of parameters similar to the previous ones.
Note : not all the screens and parameters shown in the table are always visible or can be set, the screens and parameters that are visible or can be set depend on the confi guration and the access level .
R/W = Read / Write
Mask index Par.
Aa01
Aa02
Ab01
Ab03
Ab04
O/F
H2
H3
J1
J2
J4
J5
Description
Select unit status
Select unit status
Enable On/Off from supervisor
Enable On/Off from keypad
Run local defrost from keypad
Run network defrost from keypad
Defrost temperature
Management of light digital input
Enable force water valve
0
0
0
1
Default
0
0
0
0
UOM
--
--
--
--
--
--
°C (°F)
--
--
Min
0
0
0
0
0
0
0
0
Max
13
1
1
1
1
1
1
1
Possible value descr.
0: ON
1: UNIT OFF FROM ALARM
2: UNIT OFF FROM SUPERVIS .
3: UNIT OFF FROM TIME-BAND
4: UNIT OFF FROM DIG. INPUT
5: UNIT OFF FROM KEYPAD
6: DEFROST - 7: DRIPPING
8: POST DRIPPING
9: DOOR OPEN
10: CONTINUOS CYCLE
11: UNIT OFF FROM START-UP
12: MAINTENANCE
13: UNIT OFF FROM MASTER
14: OIL RECOVERY
0: UNIT OFF
1: UNIT ON
2: UNIT FORCED OFF
0: NO; 1: YES
0: NO; 1: YES
0: NO; 1: YES
0: NO; 1: YES
0: SWITCH LIGHTS ON
1: SWITCH LIGHTS OFF
0: NO
1: YES
R/W
R
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
Baa01
J6
/FA
Maximum valve forcing time
Select outlet temperature probe position (Sm)
480
1 min
--
0
0
999
10
R/W
R/W
Select type of outlet temperature probe (Sm) 0 -0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: PT1000
R/W
Baa02 /Fb
Outlet temperature reading (Sm)
Outlet temperature probe off set (Sm)
Select defrost temperature probe position (Sd)
Select type of defrost temperature probe (Sd)
0.0 (0.0)
2
0
°C (°F)
°C (°F)
--
--
-50.0 (-90.0) 50.0 (90.0)
0 10
0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: PT1000
R
R/W
R/W
R/W
Baa03 /Fc
Defrost temperature reading (Sd)
Defrost temperature probe off set (Sd)
Select intake temperature probe position (Sr)
0.0 (0.0)
3
°C (°F)
°C (°F)
--
-50.0 (-90.0) 50.0 (90.0)
0 10
R
R/W
R/W
Select type of intake temperature probe (Sr) 0 -0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: PT1000
R/W
Baa04 /P3
Intake temperature reading (Sr)
Intake temperature probe off set (Sr)
Select condensing pressure probe position
Select type of condensing pressure probe
0.0 (0.0)
7
0
°C (°F)
°C (°F)
--
--
-50.0 (-90.0) 50.0 (90.0)
0 10
0 3
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: RAT.0-5V
1: 4-20MA
2: 4-20MA REM
3: 4-20MA EXT
R
R/W
R/W
R/W
Condensing pressure probe reading
Maximum condensing pressure probe value
Minimum condensing pressure probe value
Condensing pressure probe off set
0.0 (0.0) barg/psig
45.0 (650.0) barg/psig
0.0 (0.0)
0.0 (0.0) barg/psig bar/psi min 200.0 (2938.0)
-1.0 (-14.7) max
-10.0 (-146.9) 10.0 (146.9)
R
R/W
R/W
R/W
Heos +0300078EN - rel. 1.6 - 23.11.2017
36
Mask index Par.
Baa05 /P4
Description
Select evaporation pressure probe position
Select type of evaporation pressure probe
Baa06 /P1
Evaporation pressure probe value
Maximum evaporation pressure probe value
Minimum evaporation pressure probe value
Evaporation pressure probe off set
Select discharge temperature probe position
Select type of discharge temperature probe
Baa07 /P2
Discharge temperature reading
Discharge temperature probe off set
Select suction temperature probe position
Select type of suction temperature probe
Baa08 /Fq
Suction temperature reading
Suction temperature probe off set
Select liquid temperature probe position
Baa09 /FI
Select type of liquid temperature probe
Liquid temperature probe reading
Liquid temperature probe off set
Select room temperature probe position
Baa10 /FL
Select type of room temperature probe
Room temperature probe reading
Room temperature probe off set
Select room humidity probe position
Baa11 /FM
Select type of room humidity probe
Room humidity probe reading
Maximum room humidity probe value
Minimum room humidity probe value
Room humidity probe off set
Select glass temperature probe position
Baa11
Baa12 /FW
Baa13 /FY
Select type of glass temperature probe
Glass temperature probe reading
Glass temperature probe off set
Select water inlet temperature probe position
Select type of water inlet temperature probe
Water inlet temperature probe reading
Water inlet temperature probe off set
Select water outlet temperature probe position
Select type of water outlet temperature probe
Water outlet temperature probe reading
Water outlet temperature probe off set
Default
5
0
UOM
17.3 (250.0) barg/psig
0.0 (0.0) barg/psig
0.0 (0.0)
0.0 (0.0)
6 barg/psig bar/psi
1
0.0 (0.0)
4
°C (°F)
°C (°F)
0
--
--
--
0.0 (0.0)
8
°C (°F)
°C (°F)
0
0.0 (0.0)
0
--
°C (°F)
°C (°F)
0
0.0 (0.0)
0
--
°C (°F)
°C (°F)
0
100.0
0.0
0.0
0
--
%rH
%rH
%rH
%rH
0 --
°C (°F)
°C (°F) 0.0 (0.0)
0
0
0.0 (0.0)
0
0
--
°C (°F)
°C (°F)
0.0 (0.0)
--
°C (°F)
°C (°F)
Min
0
0
Max
15
3
Possible value descr.
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: RAT.0-5V
1: 4-20MA
2: 4-20MA REM
3: 4-20MA EXT min 200.0
-1.0 (-14.7)
(2938.0) max
-10.0 (-146.9) 10.0 (146.9)
0 10
0 5
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: CAREL NTC
1: CAREL NTC-HT
2: NTC SPKP**T0
3: TEMP.CUSTOM1
4: PT500
-50.0 (-90.0) 50.0 (90.0)
0 10
0 5
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: NTC SPKP**T0
3: 0-10V EXT.
4: TEMP.CUSTOM1
5: PT500
-50.0 (-90.0) 50.0 (90.0)
0 10
0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: PT1000
-50.0 (-90.0) 50.0 (90.0)
0 15
0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: PT1000
-50.0 (-90.0) 50.0 (90.0)
0 15
0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: 4-20MA
1: 0-1V
2: 0-10V min
0.0
-20.0
0
100.0
max
20.0
15
0 2
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: NTC-HT
2: PT1000
-50.0 (-90.0) 50.0 (90.0)
0 14
0 2
0: --
1: U01…10: U10
11: SPV
0: NTC
1: NTC-HT
2: PT1000
-50.0 (-90.0) 50.0 (90.0)
0 14
0 2
0: --
1: U01…10: U10
11: SPV
0: NTC
1: NTC-HT
2: PT1000
-50.0 (-90.0) 50.0 (90.0)
ENG
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
37 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Mask index Par.
Baa14
Baa14
/FG
Description
Select position of auxiliary probe 1
Select type of auxiliary probe 1
Select function of auxiliary probe 1
Baa15 /FH
Auxiliary probe 1
Minimum value of range for auxiliary probe 1
Maximum value of range for auxiliary probe 1
Auxiliary probe 1 off set
Select position of auxiliary probe 2
Select type of auxiliary probe 2
Select function of auxiliary probe 2
Baa16 /FO
Baa17
Baa18
Baa19
Baa20
/FE
/FF
/FN
/FP
Auxiliary probe 2
Minimum value of range for auxiliary probe 2
Maximum value of range for auxiliary probe 2
Auxiliary probe 2 off set
Condenser air outlet temperature
Select type of condenser air outlet temperature
Condenser air outlet temperature
Condenser air outlet temperature probe off set
Select discharge temperature probe position comp 1
Select type of discharge temperature probe comp 1
Discharge temperature reading comp 1
Discharge temperature probe off set comp 1
Select discharge temperature probe position comp 2
Select type of discharge temperature probe comp 2
Discharge temperature reading comp 2
Discharge temperature probe off set comp 2
Select discharge temperature probe position comp 3
Select type of discharge temperature probe comp 3
Discharge temperature reading comp 3
Discharge temperature probe off set comp 3
Select discharge temperature probe position comp 4
Select type of discharge temperature probe comp 4
Discharge temperature reading comp 4
Discharge temperature probe off set comp 4
Default
0
0
0
UOM
--
--
--
Min
0
0
0
Max
15
16
3
°C (°F) /%rH/ barg
0.0 (32.0) °C (°F) /%rH/ barg
0.0 (32.0) °C (°F) /%rH/
0.0 (0.0) barg
°C (°F) /%rH/
0 barg
--
-999.9
min
-999.9
0
0
0
--
--
0
0
16
3
°C (°F) /%rH/ barg
0.0 (32.0) °C (°F) /%rH/ barg
0.0 (32.0) °C (°F) /%rH/
0.0 (0.0) barg
°C (°F) /%rH/ barg
0
-999.9
min
-999.9
0
0
0.0 (0.0)
6
1
0.0 (0.0)
6
1
--
°C (°F)
°C (°F)
--
°C (°F)
°C (°F)
-max
999.9
999.9
14
0 2
-50.0 (-90.0) 50.0 (90.0)
0 10
0 2
0: --
1: U01…10: U10
11: SPV
0: NTC
1: NTC-HT
2: PT1000
-50.0 (-90.0) 50.0 (90.0)
0 10
0 2
0: --
1: U01…10: U10
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
0: --
1: U01…10: U10
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
°C (°F)
°C (°F)
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: PT1000
2: 0/1V
3: 0/10V
4: 4/20MA
5: 0/20MA
6: ON/OFF
?8: 0/5V RAT.
9: NTC HT
13: PTC
14: PT500
15: PT100
0: TEMPERATURE
1: PRESSURE
2: HUMIDITY
3: GENERIC
0.0 (0.0)
6
1 -max
999.9
999.9
15
-50.0 (-90.0) 50.0 (90.0)
0 10
0 2
0: --
1: U01…10: U10
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
°C (°F)
°C (°F) 0.0 (0.0)
6
1 --
-50.0 (-90.0) 50.0 (90.0)
0 10
0 2
0: --
1: U01…10: U10
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
0.0 (0.0)
°C (°F)
°C (°F) -50.0 (-90.0) 50.0 (90.0)
Possible value descr.
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
0: NTC
1: PT1000
2: 0/1V
3: 0/10V
4: 4/20MA
5: 0/20MA
6: ON/OFF
?8: 0/5V RAT.
9: NTC HT
13: PTC
14: PT500
15: PT100
0: TEMPERATURE
1: PRESSURE
2: HUMIDITY
3: GENERIC
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
Heos +0300078EN - rel. 1.6 - 23.11.2017
38
Mask index Par.
Baa21 /Fr
Bab01 /LA
Bab02 /Lb
Bab05 /LE
Bab06 /LF
Bab07 /LG
Bac01 /b1
Bac02 /b2
Bac03 /b3
Bac04 /b4
Bac05 /b5
Bac06 /b6
Bac07 /b7
Bac09 /b9
Description
Select discharge temperature probe position comp 5
Select type of discharge temperature probe comp 5
Discharge temperature reading comp 5
Discharge temperature probe off set comp 5
Select modulating fan output position
Modulating fan output % reading
Analogue output voltage
Maximum voltage
Minimum voltage
Select anti-sweat heater output position
Anti-sweat heater output % reading
Analogue output voltage
Maximum voltage
Minimum voltage
Select auxiliary output position
Auxiliary output % reading
Analogue output voltage
Maximum voltage
Minimum voltage
Select water-cooled condenser output position
Water-cooled condenser output % reading
Analogue output voltage
Maximum voltage
Minimum voltage
Select air-cooled condenser output position
Air-cooled condenser output % reading
Analogue output voltage
Maximum voltage
Minimum voltage
Select remote alarm input position
Remote alarm input status
Select remote alarm input logic
Remote alarm input function
Select delayed remote alarm input position
Delayed remote alarm input status
Select delayed remote alarm input logic
Delayed remote alarm input function
Select enable defrost input position
Enable defrost input status
Select enable defrost input logic
Enable defrost input function
Select start network defrost input position
Start network defrost input status
Select start network defrost input logic
Start network defrost input function
Select door sensor input position
Door sensor input status
Select door sensor input logic
Door sensor input function
Select remote on/off input position
Remote on/off input status
Select remote on/off input logic
Remote on/off input function
Select Day/Night input position
Day/Night input status
Select Day/Night input logic
Day/Night input function
Select curtain contact output position
Curtain contact output status
Select curtain contact output logic
Curtain contact output function
Default
6
1
UOM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
V
--
V
V
--
%
V
V
%
V
V
--
V
V
V
--
%
V
V
--
%
V
V
%
V
°C (°F)
°C (°F)
--
--
--
--
--
--
--
--
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-
10
0
0
-
10
0
0
0
10
0
-
0
0.0 (0.0)
0
0
0
0
0
-
10
-
0
10
0
0
0
0
0
0
0
0
39
ENG
Min
0
0
Max
10
2
Possible value descr.
0: --
1: U01…10: U10
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.0
min
0.0
0
0
0.0
min
0.0
0
0.0
min
0.0
0
0
0.0
min
0.0
0
-50.0 (-90.0) 50.0 (90.0)
0 3
0
0.0
100
10.0
0
0 min
0.0
10.0
max
3
100
10.0
10.0
max
3
100
10.0
10.0
max
3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0: --; 1: Y1; 2: Y2; 3: Y3
0: --; 1: Y1; 2: Y2; 3: Y3
0: --; 1: Y1; 2: Y2; 3: Y3
0: --; 1: Y1; 2: Y2; 3: Y3
100
10.0
10.0
max
3
100
10.0
10.0
0: --; 1: Y1; 2: Y2; 3: Y3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 max
MaxPosDin 0: --
1: DI1, ..., 4: DI4
5: MST
1
5
1
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
0: NOT ACTIVE
1: ACTIVE
Heos +0300078EN - rel. 1.6 - 23.11.2017
R/W
R/W
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R/W
R
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R
R/W
R/W
R/W
R
R
R/W
R/W
R/W
R
R
R/W
R/W
R
R
R/W
R/W
R
R/W
R
R/W
R
R/W
R
ENG
Mask index Par.
Bac10 /bA
Bac11 /bb
Bac12 /bC
Bac14 A9
Description
Select showcase cleaning input position
Showcase cleaning input status
Select showcase cleaning input logic
Showcase cleaning input function
Select inverter alarm input position
Inverter alarm input status
Select inverter alarm input logic
Inverter alarm input function
Select showcase light input position
Showcase light input status
Select showcase light input logic
Showcase light input function
Select virtual digital input
Display type of virtual digital input
Bac15
Bac16
Bac17 /bG
Bac18
Bac19
Bac20
Bad01
/bE
/bF
/bH
/bI
/bI
/EA
Select position of alarm input on compressor 1
Status of alarm input on compressor 1
Select alarm input logic on compressor 1
Alarm input function on compressor 1
Select position of alarm input on compressor 2
Status of alarm input on compressor 2
Select alarm input logic on compressor 2
Alarm input function on compressor 2
Select position of alarm input on compressor 3
Status of alarm input on compressor 3
Select alarm input logic on compressor 3
Alarm input function on compressor 3
Select position of alarm input on compressor 4
Status of alarm input on compressor 4
Select alarm input logic on compressor 4
Alarm input function on compressor 4
Select position of alarm input on compressor 5
Status of alarm input on compressor 5
Select alarm input logic on compressor 5
Alarm input function on compressor 5
Select dual temperature valve output position
Dual temperature valve output status
Select dual temperature valve output logic
Dual temperature valve output function
Select fan output 1 position
Fan output 1 status
Select fan output 1 logic
Fan output 1 function
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6
0
0
0
0
0
0
0
--
--
--
--
--
--
--
--
--
--
--
--
--
UOM
--
0
0
0
0
0
0
0
0
0
0
0
0
0
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Min
0
Max
5
Possible value descr.
0: --
1: DI1, ..., 4: DI4
5: MST
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5
1
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DI1, ..., 4: DI4
5: MST
0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
1
1
1
1
0: NOT ACTIVE
1: ACTIVE
MaxPosDin 0: --
1: DI1, ..., 4: DI4
5: MST
1 0: CLOSED
1: OPEN
0: N.C.; 1: N.A.
0: NOT ACTIVE
1: ACTIVE
4
13
5
1
0: --
1: REMOTE ALARM
2: DELAYED REMOTE ALARM
3: ENABLE DEFROST
4: START NETWORK DEF.
5: DOOR CONTACT
6: REMOTE ON/OFF
7: DAY/NIGHT
9: COLD ROOM MAINT.
10: SHOWCASE CLEANING
11: INVERTER ALARM
12: SHOWCASE LIGHTS
13: CURTAIN CONTACT
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.O.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.O.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.O.
5
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.O.
5
1
5
1
8
1
0: NOT ACTIVE
1: ACTIVE
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.O.
0: NOT ACTIVE
1: ACTIVE
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
0: CLOSED
1: OPEN
0: N.C.; 1: N.O.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
R/W
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
Heos +0300078EN - rel. 1.6 - 23.11.2017
40
Mask index Par.
Bad03 /EC
Description
Select light output position
Bad04 /Ed
Light output status
Select light output logic
Light output function
Select defrost output position
Bad05 /EE
Defrost output status
Select defrost output logic
Defrost output function
Select alarm output position
Bad06 /EF
Alarm output status
Select alarm output logic
Alarm output function
Select auxiliary output position
Bad07 /EG
Auxiliary output status
Select auxiliary output logic
Auxiliary output function
Select anti-sweat heater output position
Bad08 /EM
Anti-sweat heater output status
Select anti-sweat heater output logic
Anti-sweat heater output function
Select liquid injection solenoid output position
Bad09 /EN
Liquid injection solenoid output status
Select liquid injection solenoid output logic
Liquid injection solenoid output function
Select curtain contact output position
Bad10 /Eo
Curtain contact output status
Select curtain contact output logic
Curtain contact output function
Select position of ON/OFF compressor output
Bad13 /Er
Status of ON/OFF compressor output
Select logic of ON/OFF compressor output
ON/OFF compressor output function
Select inverter valve output position
Bad14 /ES
Inverter valve output status
Select inverter valve output logic
Inverter valve output function output
Select condenser fan output position
Condenser fan output status
Select condenser fan output logic
Condenser fan output function
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Default
7
UOM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
41
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Min
0
1
1
1
8
1
1
1
8
1
1
1
8
1
1
1
8
1
1
1
1
1
1
8
1
1
1
8
1
1
1
8
1
1
1
8
1
1
1
3
Max
8
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: --
2: DO2
3: DO3
0: OPEN
1: CLOSED
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: CLOSED
1: OPEN
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: CLOSED
1: OPEN
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: CLOSED
1: OPEN
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
Possible value descr.
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.A; 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.A; 1: N.C.
ENG
R/W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Mask index Par.
Bad15 /Et
Description
Select position of compressor output 1
Bad16 /Eu
Status of compressor output 1
Select logic of compressor output 1
Function of compressor output 1
Select position of compressor output 2
Bad17 /EV
Status of compressor output 2
Select logic of compressor output 2
Function of compressor output 2
Select position of compressor output 3
Bad18 /EW
Status of compressor output 3
Select logic of compressor output 3
Function of compressor output 3
Select position of compressor output 4
Bad19 /EX
Status of compressor output 4
Select logic of compressor output 4
Function of compressor output 4
Select position of compressor output 5
Bad20 /EY
Status of compressor output 5
Select logic of compressor output 5
Function of compressor output 5
Select dual temperature valve output position
Bb01 J5
Dual temperature valve output status
Select dual temperature valve output logic
Dual temperature valve output function
Enable manual procedure
Select status of DO1-DO4
Bb02 J6
Manual management status of DO1-DO4
Display confi guration of DO5-DO8
Manual management status of DO5-DO8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Min
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Default
0
UOM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
0
0
--
--
0 --
0
0
0
Max
8
1
1
1
8
1
1
1
1
24
1
1
1
8
1
1
1
8
1
1
1
8
1
1
1
8
1
24
1
Possible value descr.
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
0: OPEN
1: CLOSED
0: N.O. 1: N.C.
0: NOT ACTIVE
1: ACTIVE
0: NO; 1: YES
0: NOT CONFIGURED
1: FANS 1
3: LIGHTS
4: DEFROST
5: ALARM
6: AUX. OUTPUT
7: ANTI-SWEAT HEAT.
13: LIQ. INJ. SOLEN.
14: CURTAIN CONTACT
15: ON/OFF COMP.
16: HEAT RECOVERY
17: COND. BYPASS.
18: INV. WATER SOL. VALVE
19: COND. AIR ON/OFF
20...24: COMPRESSOR 1...5
0: NO; 1: YES
0: NOT CONFIGURED
1: FANS 1
3: LIGHTS
4: DEFROST
5: ALARM
6: AUX. OUTPUT
7: ANTI-SWEAT HEAT.
13: LIQ. INJ. SOLEN.
14: CURTAIN CONTACT
15: ON/OFF COMP.
16: HEAT RECOVERY
17: COND. BYPASS.
18: INV. WATER SOL. VALVE
19: COND. AIR ON/OFF
20...24: COMPRESSOR 1...5
0: NO; 1: YES
R/W
R/W
R/W
R
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R/W
W
R/W
R
R
R/W
W
R/W
R
R/W
W
R/W
Heos +0300078EN - rel. 1.6 - 23.11.2017
42
ENG
Mask index Par.
Bb03 J7
Description
Display analogue output confi guration AO1-AO3
Bb03
Bb04
Bb05
Bb06
Ca01
Ca02
Ca03
Ca04
Ca05
Ca06
Cba01
Cbb01
/4
Kp tI
StP
KpP tiP r0
Enc cof r4 r6
HL
S1
J8
J9
PMP
PMu
PME
PMV tPS tPU
St
% analogue outputs in manual mode
Enable compressor in manual mode
Compressor capacity percentage in manual mode
Enable manual expansion valve positioning (A)
Manual expansion valve position (A)
Enable man. expansion valve positioning (B)
Manual expansion valve position (B)
Type of set point in multi-evaporator confi guration
Pressure set point set as:
User temperature set point
Current temperature set point (read-only)
Virtual probe composition (weighted average Sr, Sm)
Temperature control diff erential
Compressor control integral time
Pressure control set point
Pressure control proportional coeff .
Compressor control integral time
Control off set with probe error (intake, outlet)
Enable cut-off
Cut-off off set
Set point off set in night mode
Pressure set point off set in night mode
Enable night-time control on intake probe (Sr)
Enable lights off at night
Night time band 1
Cbb02 hS1 mS1 hE1 mE1
S2
Night start hours
Night start minutes
Night end hours
Night end minutes
Night time band 2
Cbb03 hS2 mS2 hE2 mE2
S3
Night start hours
Night start minutes
Night end hours
Night end minutes
Night time band 3
Cc01
Cc02 hS3 mS3 hE3 mE3 r1 r2
Pr1
Pr2
Night start hours
Night start minutes
Night end hours
Night end minutes
Minimum control set point limit
Maximum control set point limit
Minimum pressure control set point limit
Maximum pressure control set point limit
Default
0
0
0
0
0
0
0
0
0
0
0
UOM
--
0
0
0.0
0
0
0
0.0
0
0
--
--
--
-steps
-steps
2.0 (35.6) °C (°F)
0
°C (°F)
%
10
500
%/°C s
5.8 (84.1) barg (psig)
10 %/bar
500
5.0 (9.0)
0 s
°C (°F)
--
1
0
0
0
2,0 (3.6)
3.0 (5.4)
--
--
°C (°F)
°C (°F) bar (psi)
-h min h min
-h min h min
--
0
0
0
0
0
0
0
0
0
0
Min
0
0 r1
0
0
0.0
0
0
0
0.0
0
Max
7
1 r2
100.0
1
100.0
1
480
1
480
1
0
1
0
1.2 (17.3)
1
0
0.0 (0.0)
0
100
200
999
8.3 (121.9)
200
999
20.0 (36.0)
1
0
0
0 99,9 (179.8)
-50.0 (-90.0) 50.0 (90.0)
-99.9 (-1.449) 99.9 (1.449)
0 1
1
11
0: NO; 1: YES
0: NO; 1: YES
0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
Possible value descr.
0: NOT CONFIGURED
8: FAN (DO)
10: LIGHT (DO)
11: DEFROST (DO)
12: ALARM (DO)
13: AUXILIARY (DO)
14: SOFT GAS SOLENOID
15: LIQUID SOLENOID
16: EQUALIZATION SOLENOID
17: SUCCTION SOLENOID
18: RAIL HEATERS
19: HOT GAS SOLENOID
20: LIQUID INJECTION
21: CIRTAIN SWITCH (DO)
22: COMP. ON/OFF (DO)
23: HEAT RECLAIM
24: CONDENSER BYPASS
25: INVERTER WATER SOLEN.
26: AIR CONDENSER
27...31: COMPR. 1...5 (DO)
R/W
R
0: NO; 1: YES
0: AUTO; 1: MAN.
0: AUTO; 1: MAN.
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W 0: TEMPERATURE
1: PRESSURE
0: TEMPERATURE
1: PRESSURE
R/W
0: NO
1: YES
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
23
59
23
59
11
R/W
R/W
R/W
R/W
R/W 0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
23
59
23
59
11
R/W
R/W
R/W
R/W
R/W 0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
0
0
0
0 h min h min
0
0
0
0
23
59
23
59
-50.0 (-58.0) °C (°F) -50.0 max
50.0 (122.0) °C (°F)
1.2 (17.3) barg (psig)
8.3 (121.9) barg (psig) min
1.2 (17.3)
1.2 (17.3)
50.0 (122.0)
8.3 (121.9)
8.3 (121.9)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
43 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Mask index Par.
Daa01 Kp
Daa02 tI cE1
Daa03
Daa04
Daa05 cE2 cE3
LIV
LIt
LIP
LII
LId
LIc
LIS dts dtd dto cH1 cH2 cH3 cH4
Daa06
Daa07 cH5 co1 co3
Dab03
Dab04
Dab05
Dab06 c0 c1 c2 c3 cI3 c4 c5 cI5 cI6 cI7 cI8 cI9
Description
Compressor control integral time
Select equalising procedure mode
Maximum EEV opening time during equalisation
EEV pre-opening percentage during equalisation
Type of liquid injection valve
Default
10
500
0
90
60
0 s
--
UOM
%/°C s
%
--
Liquid injection function activation threshold
Liquid injection control integral time
Liquid injection diff erential
Duty Cycle
Duty Cycle period
Discharge temperature set point managed by EEV
Discharge temperature diff erential managed by EEV
Discharge temperature off set managed by EEV
Discharge temperature limit (red. comp. speed)
Discharge temperature alarm
Discharge temperature activation diff erential (red. comp. speed)
Pause in speed reduction over discharge temperature limit 90
(red. comp. speed)
Speed reduction percent over discharge temperature limit
Type of condenser cooling
95.0 (203.0) °C (°F)
5
100
-s
5.0 (9.0)
100
°C (°F)
%
30 s
100.0 (212) °C (°F)
0.1 (0.2) °C (°F)
0.1 (0.2) °C (°F)
100.0 (212) °C (°F)
105.0 (221.0) °C (°F)
20.0 (36.0) °C (°F)
3.0
0 s
%
Type of water-cooled condenser control 0
Daa08
Daa10
Daa11
Daa12
Daa13
Daa14 coc cod com con coo cor cPE cPt cPd cPM cPP cPL co4 co4 co5 co6 cot cov coA cob coE
Dab01
Dab02
Condensing temp. set point
Condenser water temp. diff . set point
Cond. control integral time
Valve pre-positioning at start-up
Pre-opening duration
Cond. control safety set point
Cond. control safety diff erential
Enable inverter anti-sweat
Inverter anti-sweat temperature threshold
Inverter anti-sweat temperature diff erential
Minimum % fan/valve output
Maximum % fan/valve output
Valve closing delay on compressor shutdown
Pre-opening duration at compressor start-up
Enable pump down
Activation threshold
Diff erential
Maximum time to complete procedure
Maximum speed in pump down
Delay in changing compressor speed
Compressor model used
Type of ON/OFF compressor
Number of ON/OFF multi compressors
Model of compressor used
Refrigerant type
Power supply
Write parameters for the selected compressor
Start control delay at power on
Minimum time between successive compressor calls
Minimum compressor off time
Minimum on compressor time
Compressor capacity percentage with probe alarm
Comp. on time in duty setting from probe alarm
Comp. off time in duty setting from probe alarm
Maximum pressure delta for compressor start ?
Minimum pressure delta for compressor start ?
Pressure delta control delay to check comp. start-up
Restart delay after failed start
Number of restart attempts after failed start
20.0 (68.0) °C (°F)
5.0 (9.0) °C (°F)
40
100
%/°C s
50
6
42.0 (107.6) °C (°F)
5.0 (9.0) °C (°F)
0
% s
5
0
1.7
2.0
120
50
0
0
52
10
10
1
15.0 (59.0) °C (°F)
3.0 (5.4) °C (°F)
0.0
100
%
% s s
-
--
s
-barg (psig) barg (psig) s
%
2 --
0
6
3
1
0
3
3
3
50
0.5 (7.3)
0.2 (2.9)
10
30
5
--
-min min min min
% min min bar/psi s
-bar/psi s
0.5
0
0
0
0
0
0
0
0
0
0
0
0.0 (0.0)
1
0
0.1 (1.5)
1
1
0
10.0 (50.0)
0.1 (0.18)
0
0
30.0 (86.0)
0.0 (0.0)
0
0
0
0
0.0 (32.0)
0.0 (0.0)
0.0
0.0
-
0
0
0
0
0
0 (0)
0.1 (1.45)
0
Min
1
Max
200
Possible value descr.
0
0
999
1 0: EEV PRE-OPENING
1: EQUAL. VALVE
0
20
0
999
99.9
1 0: ON-OFF
1: EEV
50.0 (122.0) 150.0 (302.0)
1
1
200
999
WITH LIV = 1
WITH LIV = 1
0.1 (0.2)
0
0
20.0 (36.0) WITH LIV = 0
100 WITH LIV = 0
60
50.0 (122.0) 150.0 (302.0)
WITH LIV = 0
0.1 (0.2) 20.0 (36.0)
0.0 (0.0) 99.9 (179.8)
50.0 (122.0) 150.0 (302.0)
50.0 (122.0) 150.0 (302.0)
0.1 (0.2) 30.0 (48.0)
1 300
0
20
1
3
0: WATER
1: AIR
0: COND. TEMP.
1: W OUTIN TEMP.
2: W OUT TEMP.
3: W IN TEMP.
55.0 (131.0)
20.0 (36.0)
999
999
100
999
55.0 (131.0)
9.9 (17.8)
1 0: NO
1: YES
50.0 (122.0)
10.0 (18.0)
100
100
999
999
1 0: NO
1: YES
-
5
10 (145)
10 (145)
999
100
99
1
1
13
1
0: BLDC
1: ON/OFF
0: SINGLE
1: MULTIPLE
-
50: TOSHIBA DA91A1F-230V
51: TOSHIBA DA130A1F-230V
52: TOSHIBA DA220A2F-230V
53: TOSHIBA DA330A3F-230V
54: TOSHIBA DA420A3F-230V
0: R22
1: R134A
2: R404A
3: R407C
4: R410A
5: R507A
6: R290 (PROPANE)
7: R600 (BUTANE)
8: R600A (ISOBUTANE)
9: R717 (AMMONIA)
10: R744
11: R728 (NITROGEN)
12: R1270 (PROPILENE)
13: R417A
0: 230V
1: 400V
0: NO; 1: YES 1
15
15
15
15
100
100
100
120 (1762.8)
2.0 (29.4)
99
360
9
0: ALWAYS ON
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Heos +0300078EN - rel. 1.6 - 23.11.2017
44
ENG
Mask index Par.
Dab07 cIA
Dab08
Dab09
Dab10
Dab11
Dab12
Dab13
Dad01
Dad02
Dad03 cIS cIu cIV c6 c7 cIn cIo cIP cIr cIb cIc cId cIE
CIF cIH cII cIJ cIL
AI1
AI2
AI3
AI4
AI5
AI6
AI7
Dad04
Dad05
Dad06
Dad07
AI8
AIA
AIb
AI9
AIC
AId dtt dtE
Hdt
Hdd dHd
Dae08
Dba01
Dba02
Dbb01
Dbb02
P3
P4
P5
P6
EVP
PH
Description
Compressor speed when starting
Default
50.0
UOM rps
Maximum compressor speed
Minimum compressor speed
Maximum speed increase (control)
Maximum speed decrease (control)
Maximum speed decrease (shutdown)
Acceleration decrease (to return inside envelope)
Minimum comp. speed to remain inside envelope
Out of envelope alarm delay
Low compression ratio alarm delay
Enable low compression ratio management by closing EEV 1
Enable increase comp. speed with low compression ratio 1
Enable oil recovery management
Oil recovery procedure activation time
1
30
Compressor override time during procedure 2
Minimum comp. output to activate oil recovery procedure Comp
Comp. speed during oil recovery procedure
ON delay between two compressors
OFF delay between two compressors
100
10
10
Comp
Comp
1.0
1.0
1.0
0.5
Comp
180
180
Set high compressor pressure
High compressor pressure diff erential
Set low compressor pressure
Low pressure compressor diff erential
Low compressor pressure alarm delay at start-up
Low compressor pressure alarm delay in steady operation
Type of low compressor pressure alarm reset
33.0 (484.7) barg/psig
3.0 (44.1) bar/psi
0.5 (7.3) barg/psig
2.0 (29.4) bar/psi
30
5
0 s s
--
--
--
-min min
%
% s s rps rps rps/s rps/s rps/s s s rps/s rps
Type of envelope alarm reset
Time range
No. of attempts performed
Type of Power+ alarm reset
Time range
No. of attempts performed
Low inverter temperature threshold
Inverter temperature diff erential
Threshold high alarm discharge temperature comp
Diff erential discharge temperature
Delay alarm discharge temperature
Operating hours, compressor 1-5
Superheat set point
PID: EEV proportional gain
PID: EEV integral time
PID: EEV derivative time
EEV present
Refrigerant type (depends on selected compressor)
0 --
60
5
0 min
--
--
60
5 min
--
2.0 (3.6)
3.0 (5.4)
°C (°F)
°C (°F)
90.0 (194.0) °C (°F)
5.0 (9.0) °C (°F)
30
0 s h
10.0 (36.0) °C (°F)
15.0
150
5.0
1 s s
Comp --
Dbb03
Dbc01
Dbc02
Dbc03
Dbc04
Dbc05
Dbc06
Dbc07
Dbc08
Dca01
PL3
PM1
PM2
PM3
P11
P12
Pa
Pb
CP1
Psb cP2
P7
P8
P9
PL1
PL2
Pb1
Pb2
Pb3
Pb4
P15 d0
EEV opening at power on
Enable EEV opening in standby
EEV pre-positioning delay
Low superheat threshold
LowSH: EEV low superheat integral time
LowSH: EEV low superheat alarm delay
LOP
LOP: Low evaporation temperature integral time
LOP: Low evaporation temperature alarm delay
MOP
MOP: High evaporation temperature integral time
MOP: High evaporation temperature alarm delay
Low suction temperature alarm threshold
Low suction temperature alarm delay
High superheat threshold
High superheat alarm delay
Valve threshold position warning
Alarm delay
Superheat off set setpoint for low refrigerant charge warning
Alarm delay
Off set for LP calculation
Type of defrost/end defrost
50
0
6
%
-s
2.0 (3.6)
10
°C (°F) s
120 s
-50.0 (-58.0) °C (°F)
10 s
120 s
15.0 (59.0) °C (°F)
20.0
240 s s
-40.0 (-40.0) °C (°F)
120 s
35.0 (95.0) °C (°F)
600 s
99
10
3.0 (5.4)
% min
°C (°F)
10
3.0 (5.4)
0 min
°C (°F)
--
0
0
0
Min cIc
Max cIb
0
1
0
0
0
0
1
10.0
0 cIc Type comp
Type comp cIb
0.1
0.1
0.1
Type comp
Type comp
Type comp
0
1
0.1
Type comp
Type comp cIb
600
600
1
1
1
480
10
99.9
100
999
999
0
0
0
-1.0 (-14.7)
0.0 (0.0)
-1.0 (-14.7)
0.0 (0.0)
200.0 (2938.0)
20.0 (293.8)
200.0 (2938.0)
20.0 (293.8)
999
999
1
0 1
Possible value descr.
0: NO; 1: YES
0: NO; 1: YES
0: NO; 1: YES
0: 5 ATTEMPTS
1: 0 ATTEMPTS
0: SEMIAUT.
1: MANUAL
999
10
1 0: SEMIAUT.
1: MANUAL
0
0
999
10
-99.9 (-147,8) 99.9 (212.0)
0.0 (0.0) 10.0 (18.0)
0.0 (32)
0.0 (0.0)
200.0 (392.0)
20.0 (36.0)
0
0
0.0 (0.0)
0.0
0
0.0
0
999
99999
30.0 (54.0)
100.0
999
100.0
1
0 13
0: NO PRESENT
1: PRESENT
0: R22
1: R134A
2: R404A
3: R407C
4: R410A
5: R507A
6: R290 (PROPANE)
7: R600 (BUTANE)
8: R600A (ISOBUTANE)
9: R717 (AMMONIA)
10: R744
11: R728 (NITROGEN)
12: R1270 (PROPILENE)
13: R417A
0
0
0
100
1
300.0
0.0 (0.0)
0.0
30.0 (54.0)
999
0 300.0
-50.0 (-58.0) MOP
0.0
999
0
LOP
0.0
0
300.0
30.0 (86.0)
999
300.0
-50.0 (-58.0) 30.0 (86.0)
0 300
0.0 (32.0)
0
50.0 (122.0)
999
0
0
0 (0)
100
999
20.0 (36.0)
0
0 (0)
0
0: NO; 1: YES
R
999
68.0 (122.4)
6 0: ELECTR./ TEMP-TIMEOUT
1: INV. CYCLE/ TEMP-TIMEOUT
2: ELECTR./ ONLY TIMEOUT
3: INV. CYCLE/ ONLY TIMEOUT
4: ELECTRICAL/
REGUL. TEMPERAT. TIME
5: BYPASS HOT-GAS /
TEMP-TIMEOUT
6: BYPASS HOT-GAS/
ONLY TIMEOUT
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
45 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Mask index Par.
Dca02 dt1
Dca03
Dca04 dP1 dd d9 dI d4 d5 r3 d2
Dca05 d8 d13 dR1
/10
Description
End defrost temperature
Maximum defrost duration
Dripping time after defrost (fans off )
Disable evaporation pressure alarm in defrost
Interval between two consecutive defrosts 0=disabled
Enable defrost at start-up
Defrost delay at start-up or from digital input
Enable end defrost signal for maximum time
Defrost control in pLAN
Default UOM
8.0 (46.4) °C (°F)
0
0
1
0
8
40
120
0
-h min s
-min
--
--
High temperature alarm bypass time after defrost and/or door open
Restart control delay during maintenance 0=disabled
Enable compressor OFF in defrost
Select probe used for end defrost (d0=4)
30
0
0
2 min min
--
--
Dca06
Dca07
Dca08
Dca09 dG2 dG3 dG4 dG5 dG6 dG7 dG8
Compressor speed (defrost by reversing cycle)
Maximum acceleration in defrost by reversing cycle
Out of envelope alarm delay (defrost by reversing cycle)
4-way valve changeover delay in Defrost
4-way valve changeover delay after defrost
End defrost delay (defrost by reversing cycle) dG9
EXV mode at start defrost
Manual EXV opening at start defrost
EXV mode during defrost
Manual EXV opening during defrost dG10 EXV mode at end defrost
Manual EXV opening at end defrost dH2 dH4
Compressor speed (hot gas defrost)
Out of envelope alarm delay (hot gas defrost)
Dca10
Dca11
Dca12 dH5 dH6 dH7 dH8 dH9
Bypass valve opening delay (hot gas defrost)
Bypass valve closing delay (hot gas defrost)
Enable manual (hot gas defrost)
Manual positioning (hot gas defrost)
Defrost duration threshold (hot gas defrost) dH10 Alarm delay after defrost (hot gas defrost)
Dcb01…4 td1…8 Scheduled defrost day
1
50
1
50
1
50
80.0
600
50.0
1.0
600
10
10
60
2
0
0
0
10
10
s s
%
-2.0 (28.4) °C (°F) min
--
--
%
% s
--
%
--
% s s s rps rps s
Dd05
De01
De02
De03
De04
Dcc01
Dcc02
Dcc03
Dcc04
Dd01 d11 d10 dA2 ddt ddP dS0 dS1 dS2
F0 tt1…8 Scheduled defrost hours tt1…8 Scheduled defrost minutes tP1…8 Enable Power Defrost d7 Enable skip defrost dn do
Nominal defrost duration for skip defrost
Number of defrosts to be performed when starting before dA1 activating skip def.
Probe used for Running Time
0
0
0
0
45
7
0
Running Time temperature set point
Defrost duration in Running Time mode
Delay at start-up before activating Running Time
Additional temperature for power defrost
Additional defrost duration in power defrost
Enable Sequential Stops
Compressor ON time for Sequential Stop defrost
Compressor OFF time for sequential Stop defrost
Confi gure fan management
--
--
--
-min
--
--
-4.0 (24.8) °C (°F)
0 min
120
0.0 (0.0) min
°C (°F)
0
0
180
10
0 min
-min min
--
Dd02
Dd03
Dd04
F1
F2
F3
F9
F10
F11 rHo rHd rHB rHC rHt rHu rH6 rH7
Fd
Frd
F6
F7
F5
F8
Fan activation threshold
Enable fans off with controller off (OFF)
Enable fans off during defrost
Fan off time in post-dripping
Fan diff erential
Maximum fan speed
Minimum fan speed
Fan cut-off temperatures
Fan peak time
Override fan output to 100% every:
OFF time during curtain closing
OFF time during curtain opening
Anti-sweat modulation off set from dew point
Anti-sweat heater diff erential modulation
Anti-sweat modulation cut-off
Anti-sweat heater modulation cut-off diff erential
Anti-sweat heater activation period
Manual activation anti-sweat heaters percentage
Minimum anti-sweat heater output
Maximum anti-sweat heater output
-5.0 (23.0) °C (°F)
0 --
0 --
60
2.0 (3.6) s
°C (°F)
80
10
%
%
0.0 (32.0) °C (°F)
10 s
0
50
50
2.0 (3.6) min s s
°C (°F)
0.0 (0.0) °C (°F)
10.0 (18.0) °C (°F)
1.0 (1.8)
30
70
°C (°F) min
%
10
100
%
%
Heos +0300078EN - rel. 1.6 - 23.11.2017
46
0
0
0
0
0
1
0
0
Min Max
-50.0 (-58.0) 50.0 (122.0)
240
600
1
500
1
240
1
2
Possible value descr.
0: NO; 1: YES
0: NO; 1: YES
0: NO; 1: YES
0: START ONLY
1: START & END
2: LOCAL ONLY
0 240
0
0
0
240
1
3
0: NO; 1: YES
0: CONTROL PROBE
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
0
0 cIc
0
0
0
0
0
0
0
0 cIc cId
0
0
0
0
0
0
0
-5.0 (-23.0)
1
100
1
100
1
100 cIb
999 cIb cIE
999
99
99
180
99
99
1
100
10.0 (50.0)
99
11
0: REG; 1: MAN
0: REG; 1: MAN
0: REG; 1: MAN
0: NO; 1: YES
0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
0
0
0
0
0
1
1
1
23
59
240
9
0: NO; 1: YES
0: NO; 1: YES
0 1
0
0
0
0
0
-50.0 (-58.0) 30.0 (86.0)
0 240
0 480
-20.0 (-36.0) 20.0 (36.0)
60
1
999
999
2
0: DEFROST
1: TEMP.SAT.EVAP.
0 = DISABLED
0: NO; 1: YES
0: ALWAYS ON
1: BY SD -SV DIFFERENCE
2: BY. DEFROST TEMP.
-50.0 (-58.0) 50.0 (122.0)
0 1
0 2
0: NO; 1: YES
0: ALWAYS ON
1: ALWAYS OFF
2: ALWAYS ON, OFF IN dd
0
0.1 (0.2)
240
20.0 (36.0) min
0
100 max
-50.0 (-58.0) 50.0 (122.0)
0 240
0
0
240
999
0 999
-20.0 (-36.0) 20.0 (36.0)
0.0 (0.0)
0.0 (0.0)
0.0 (0.0)
10
0
0 min
20.0 (36.0)
20.0 (36.0)
10.0 (18.0)
180
100 max
100
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
Mask index Par.
De05 rH8
De06
De07
Df01
Df02 rH9
Ga
Gb
Gc bA1 bA3
Df03 bA4 bA5
Df04 bA6 bA7
St
Df05/14 d0
Description
Type of anti-sweat heater modulation
Anti-sweat heater integral time
Showcase/cold room cleaning duration
Showcase cleaning with end via DI
Enable dual temperature
Enable digital input
EPR activated by DO
Change status
User temperature set point
Type of defrost/end defrost dt1 dP1
Df06/15 dI d2
/10
End defrost temperature
Maximum defrost duration
Interval between two consecutive defrosts
Defrost control in pLAN
Select probe used for end defrost
Df07…10
Df16…19 td1…8 Scheduled defrost day tt1…8 Scheduled defrost hours tt1…8 Scheduled defrost minutes
Df11/20 d11 d10 dA2
Temperature set point for running time
Defrost time for running time
Delay at start-up to start Running time
Df12/21 F1
F3
Fan activation threshold
Enable fans off during defrost
Df13/22 AH
Ea01
AL
AH2
AL2
PE2
H0
H6
High temperature alarm threshold Al.1
Low temperature alarm threshold Al.1
High temperature alarm threshold Al.2
Low temperature alarm threshold Al.2
Evaporator capacity
Serial address for supervisor (BMS)
BMS communication speed
H7 BMS communication protocol
Ea02 Modbus master protocol baud rate 4 --
Ea03
Eb01
Eb02
Eb03
Eb04
Eb05
Eb06
Eb07
Sn
PE1
PES
PE2
PE5
PE6
PE7
PEA
PEB
PEV
Modbus master protocol Stop bits
Modbus master protocol parity
Timeout
Master/Slave unit address
Multi-evaporator unit with single compressor
Number of slaves
Number of evaporators (for multi-evaporator)
Enable modulating superheat
Evaporator capacity
Multi-evaporator superheat control proportional gain
Multi-evaporator superheat control integral time
Multi-evaporator superheat control off set
Change unit delay in SuperHeat mode
Modulating SuperHeat mode
Valve opening during oil recovery
1
0
--
--
500
1 ms
--
0
0
1
0
500
4.0
120
--
--
--
W
-s
20.0 (36.0) °C (°F)
180 s
0
80
--
%
47
0
0
-4.0 (24.8) °C (°F)
0 min
120 min
-5.0 (23.0) °C (°F)
0
10.0 (50.0) °C (°F)
10.0 (18.0) °C (°F)
4.0 (39.2) °C (°F)
4.0 (7.2) °C (°F)
10.0 (50.0) °C (°F)
10.0 (18.0) °C (°F)
4.0 (39.2) °C (°F)
4.0 (7.2) °C (°F)
500
194
4
W
--
--
0 --
Default
0
60
2.0 (3.6)
22
80
240
0
0
0
0
0
2.0 (35.6) °C (°F)
0
UOM
-s
°C (°F)
%
% min
--
8
1
8.0 (46.4) °C (°F)
40 min h
2
0
ENG
Min
0
0
0
0
0 r1
0
0
0
-50.0 (-58.0) 50.0 (122.0)
1 240
500
2
0
0
Max
1
0
0
0
0
0 999
-20.0 (-36.0) 20.0 (36.0)
100
100
360
1
1
1
1
1 r2
6
3
11
0
0
23
59
-50.0 (-58.0) 30.0 (86.0)
0 240
0 480
-50.0 (-58.0) 50.0 (122.0)
0 2
2: ALWAYS ON, OFF IN dd
-50.0 (-58.0) 50.0 (122.0) if A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) if A1= 0: RELATIVE
-50.0 (-58.0) 50.0 (122.0) if A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) if A1= 0: RELATIVE
-50.0 (-58.0) 50.0 (122.0) if A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) if A1= 0: RELATIVE
0
0
1
0
0
-50.0 (-58.0) 50.0 (122.0) if A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) if A1= 0: RELATIVE
0
15000
199
4
0
0
0
0
2
4
1
2
0: 1200 BAUD
1: 2400 BAUD
2: 4800 BAUD
3: 9600 BAUD
4: 19200 BAUD
0: CAREL
1: MODBUS
2: WINLOAD
3: MODEM GSM
4: RS232
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
0: 1; 1: 2
0: NO
1: EVEN
2: ODD
100
1
5000
6 1: MASTER
2: SLAVE 1...6: SLAVE 5
0: NO; 1: YES 1
5
6
0: NO; 1: YES 0
0
1.0
0
0
0
0.0 (0.0)
0
1
15000
99.9
999
40.0 (72.0)
999
1
100
0: BEST UNIT; 1: ALL
Possible value descr.
0: P; 1: P+I
R/W
R/W
R/W
R/W
R/W
R/W
0: YES
1: NO
0: NO ; 1:YES
0: NO ; 1:YES
0: set A ; 1:set B
0: set A ; 1:set B
R/W
R/W
R/W
R/W
R/W
R/W
0: ELECTR./ TEMP-TIMEOUT
1: REV. CYCLE/TEMP-TIME-
OUT
2: ELECTR./ TIMEOUT ONLY
3: REV. CYCLE/TIMEOUT ONLY
4: ELECTRIC/TIMEOUT +
TEMP. CONTROL
5: HOT GAS BYPASS/ TEMP-TI-
MEOUT
6: HOT GAS BYPASS/ TIME-
OUT ONLY
R/W
R/W
R/W
R/W
R/W
R/W 0: START ONLY
1: START AND END
2: LOCAL ONLY
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
R/W
R/W
0 = DISABLED
0: ALWAYS ON
R/W
R/W
R/W
R/W
R/W
R/W
R/W
1: ALWAYS OFF
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Mask index Par.
Eb08
Ec01
Ec02
Ec03
Ec04
Ed02
Ed03
Ee01
Ee02
Ee03
Ef01
Ef02
Ef03
Ef04
Fc01
Fc02
Fc03
Fc04
Fc05
Fd00
P15
Description
Off set on control T when LP probe is broken or disconnected
Type of showcase display
Default
3.0 (5.4)
UOM
°C (°F)
Min
0 (0)
Max
68.0 (122.4)
Possible value descr.
R/W
R/W
/7
/t2
/t d6
H4
Ut
UP cLK cKu
Y0
Y1
Y2
PP
PD
Y3
Aa
AH
AL
A1
A0
Ad
Ar
A7
Aa2
AH2
AL2
A2
AdE
As rF
Value shown on showcase display
Enable show alarms on showcase display
Display management during defrost
Enable buzzer
Temperature unit of measure
Pressure unit of measure
Select language used on pGDe
Clock "hour" setting
Clock "minutes" setting
Clock "day" setting
Clock "month" setting
Clock "year" setting
Read current day of the week
Type of clock update
User password
Service password
Manufacturer password
Login Password
Menu access time without re-entering password
Install Carel default parameters
Save confi guration
Load the saved confi guration
Delete previous confi guration
Select probe for high and low temperature alarm Al.1
High temperature alarm threshold Al.1
Low temperature alarm threshold Al.1
Type of alarm thresholds, relative to control set point or absolute
Temperature alarm diff erential
High and low temperature alarm delay
Enable alarm propagation from Slaves to Master
Delay time for delayed external alarm
Select probe for high and low temperature alarm Al.2
High temperature alarm threshold Al.2
Low temperature alarm threshold Al.2
Type of alarm thresholds, relative to control set point or absolute
Alarm delayed external delay priority
Serial probe alarm delay
Reset alarm log
0
12
1
0
0
1
0
1
0
0
0
0
0
0
0
000
123
123
0
15
0
0
0
0
1
10.0 (50.0) °C (°F)
10.0 (18.0) °C (°F)
4.0 (39.2) °C (°F)
4.0 (7.2)
0
°C (°F)
--
0
1
0
2.0 (3.6)
120
--
--
--
-min
--
--
--
-h
--
--
°C (°F) min
-min
--
10.0 (50.0) °C (°F)
10.0 (18.0) °C (°F)
4.0 (39.2) °C (°F)
4.0 (7.2) °C (°F)
0 --
0
30
0
--
--
--
--
--
--
--
--
--
--
--
--
--
-min
--
0
0
0
0
1
13
1
2
0: PLD WITH BUTTONS
1: PLD DISPLAY
0: NONE
1: U01, ..., 10: U10
11: REGULATION PROBE
12: VIRTUAL PROBE
13: SETPOINT
0: NO; 1: YES
0: VALUE TEMP. AND DEF
1: VALUE TEMP. FROZEN
2: ALWAYS DEF
0: NO; 1: YES 0
0
0
1
1
1
1
2
0: °C; 1: °F
0: BARG
1: PSIG
0: ITALIAN
1: ENGLISH
1
0
0
0
0
1
23
59
31
12
99
0
0 1
0: ***
1: MONDAY
2: TUESDAY
3: WEDNESDAY
4: THURSDAY
5: FRIDAY
6: SATURDAY
7: SUNDAY
0: FROM BMS
1: FROM MASTER.
0
0
0
0
0
0
999
999
999
999
90
1
0
0
0
0
1
1
1
9
0:
1: DEFAULT. INSTALLATION
0:
1: SAVE
0:
1: SAVE
0:
1: DELETE
0: VIRTUAL PROBE
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
4: SUCTION PROBE
5: SATURATION PROBE
7: AUX.1 PROBE
8: AXU.2 PROBE
9: TEMP.DEWP.PROBE
-50.0 (-58.0) 50.0 (122.0) if A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) if A1= 0: RELATIVE
-50.0 (-58.0) 50.0 (122.0) if A1= 1: ABSOLUTE
0.0 (0.0)
0
50.0 (90.0) if A1= 0: RELATIVE
1 0: RELATIVE
1: ABSOLUTE
0,1.0 (0,18.0) 20.0 (36.0)
0 240
0
0
0
1
240
9
0: NO; 1: YES
0: VIRTUAL PROBE
1: SOUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
4: SUCTION PROBE
5: SATURATION PROBE
7: AUX.1 PROBE
8: AXU.2 PROBE
9: TEMP.DEWP.PROBE.
-50.0 (-58.0) 50.0 (122.0) se A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) se A1= 0: RELATIVE
-50.0 (-58.0) 50.0 (122.0) se A1= 1: ABSOLUTE
0.0 (0.0) 50.0 (90.0) se A1= 0: RELATIVE
0 1 0: RELATIVE
1: ABSOLUTE
0 1 0: LOW
1: HIGH
10
0
500
1 0: NO; 1: YES
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
Tab. 7.al
These parameters can only be set by Carel HQ, depending on the compressor model. Changing the settings may aff ect compressor life, as they have been agreed on with the compressor manufacturer. For any settings, please contact Carel.
Heos +0300078EN - rel. 1.6 - 23.11.2017
48
ENG
8. SIGNALS AND ALARMS
Heos can manage both alarms relating to the status of the digital inputs and to system operation. For each alarm, the following are controlled:
• actions on the devices, if required
• output relays
• red LED on the terminal and buzzer
• any activation delay
The complete list of alarms, with the related information as described above, is available in the “Alarm table”.
Note : A maximum of 50 alarms can be logged; after this limit any new events overwrite the oldest ones, which are therefore deleted.
3
4
Alarms history Fd01 rE 15:49 05/06/14
Regulation probe failure
Value Setpoint
Treg. : 05.0°C 04.0°C
SuperH. : 05.0°C 04.0°C
Tdisch. : 05.0°C
Temp. : HP05.0°C LP04.0°C
1
2
5
All alarms feature the following behaviour:
• When an alarm is activated, the red LED fl ashes and the buzzer and alarm relay are activated (when confi gured)
• Pressing the button, the red LED stays on steady, the buzzer is muted and the alarm screen is shown
• If there is more than one active alarm, these can be scrolled using and
• Pressing the button again for at least 3 seconds manually resets the alarms, which are cleared from the display unless others are active
(they are saved in the log)
The compressor high and low pressure alarms can be set in branch
Dad01-04. In addition to the high and low pressure alarm thresholds, with corresponding delays for the low pressure alarms, this screen can also be used to set the type of reset when exiting the envelope. For the delay and type of reset, also see the alarm table (par. 8.5).
8.3 EEV valve protector alarms
The alarms corresponding to the LowSH, LOP, MOP and High Tcond protectors are only activated during control when the corresponding activation threshold is exceeded, and only when the timeout defi ned by the corresponding parameter has elapsed. If a protector is not enabled
(integration time= 0 s), no alarm will be signalled. If before the expiry of the timeout, the protector control variable returns back inside the corresponding threshold, no alarm will be signalled.
Note: this is a likely event, as during the timeout, the protection function will have an eff ect.
If the timeout relating to the control alarms is set to 0 s, the alarm is disabled. The protectors are still active, however. The alarms are reset automatically.
Reset
Alarms can be reset manually or automatically:
• Manual: the alarm is reset by pressing the button twice, the fi rst time displays the corresponding alarm screen and mutes the buzzer, the second (extended, for at least 3 seconds) cancels the alarm (which is saved in the log). If the alarm is still active, the reset has no eff ect and the signal is shown again.
• Automatic: when the alarm condition ceases, the alarm is automatically reset, the LED comes on steady and the corresponding screen remains displayed until the button is pressed and held; the alarm is saved in the log.
For manual reset, the functions associated with the alarm will not be reactivated until the alarm is reset, while for automatic reset, the functions are reactivated as soon as the alarm condition ceases.
Log
The alarm log can be accessed:
• from branch F.d of the main menu
• pressing and then when there are no active alarms
The alarm log screens show:
1. the chronological number of the event (no. 01 is the oldest alarm)
2. time and date of the alarm
3. the alarm code (see the table in par. 8.5)
4. short description of the logged alarm
5. control probe reading and set point, superheat reading and set point, discharge temperature value, envelope zone, evaporation and condensing pressure values converted to temperature.
The last screen displayed is used to reset the log.
49
Assign probe for high and low temperature alarms
(parameters Aa, Aa2)
Aa selects the probe to be used for measuring the high and low temperature alarms with reference to thresholds AL and AH. Aa2 is the same as Aa for thresholds AL2 e AH2.
Par Description Def Min Max UM
Aa Assign probe for high (AH) and low (AL) tempera1 0 9 ture alarm
0: VIRTUAL PROBE
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
4: SUCTION PROBE
5: SATURATED PROBE
7: AUX. PROBE 1
8: AUX. PROBE 2
9: DEWP. TEMP. PROBE
Aa2 Assign probe for high (AH2) and low (AL2) temperature alarm - see Aa
0 0 9 -
Tab. 8.a
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Alarm parameters and activation
AL (AH) is used to determine the activation threshold for the low (high) temperature alarm LO (HI). The value set for AL (AH) is continuously compared against the value measured by the probe defi ned by parameter
AA. Parameter Ad represents the alarm activation delay, in minutes; the low temperature alarm (LO) is activated only if the temperature remains below the value of AL for a time greater than Ad. The thresholds may be relative or absolute, depending on the value of parameter A1. In the former case (A1=0), the value of AL indicates the deviation from the set point and thus the activation point for the low temperature alarm is: set point - AL. If the set point changes, the activation point also changes automatically. In the latter case (A1=1), the value of AL indicates the low temperature alarm threshold. The low temperature alarm is signalled by the buzzer and error code LO on the display. The same applies to the high temperature alarm (HI), with AH instead of AL. I
The meaning of parameters AL2, AH2, Aa2 and A2 is similar to AL, AH, Aa,
A1, relative to the second set point.
Par Description
AH High temperature alarm threshold Al.1
AL Low temperature alarm threshold Al.1
Def UM Min Max
10.0 °C -50.0 50.0
(50.0)
10.0
(18.0)
4.0
(39.2)
(°F)
°C
(°F)
°C
(-58.0)
0.0
(0.0)
-50.0
(122.0)
50.0
(90.0)
50.0
0
(°F)
°C
(°F)
--
(-58.0)
0.0
(0.0)
0
(122.0)
50.0
(90.0)
1 A1 Type of alarm thresholds, relative to the control set point or absolute
0: RELATIVE
1: ABSOLUTE
A0 Temperature alarm diff erential
Ad High and low temperature alarm delay
Ar Enable propagation of alarms from Slaves to Master
0: NO; 1: YES
A7 Delay time for delayed external alarm
AH2 High temperature alarm threshold Al.2
AL2 Low temperature alarm threshold Al.2
2.0 °C
(3.6) (°F)
120 min
0 --
0.1
(0.2)
0
0
20.0
(36.0)
240
1
1
10.0
(50.0)
10.0
(18.0)
4.0
(39.2)
0 min
°C
(°F)
°C
(°F)
°C
(°F)
°C
(°F)
--
0
-50.0
(-58.0)
0.0
(0.0)
-50.0
(-58.0)
0.0
(0.0)
0
240
50.0
(122.0)
50.0
(90.0)
50.0
(122.0)
50.0
(90.0)
1 A2 Type of alarm thresholds, relative to the control set point or absolute
0: RELATIVE
1: ABSOLUTE
AdE Delayed external alarm delay priority
0: LOW (compressor not stopped)
1: HIGH (compressor stopped)
As Serial probe alarm delay
0
30
-min
0 1
10 500
Tab. 8.b
Note:
• alarms LO(LO2) and HI(HI2) have automatic reset. A0 represents the hysteresis between the alarm activation value and deactivation value.
LO HI
ON
OFF
ON
AL
A0
LO2
OFF
AL2
A0
Key
LO, LO2 Low temperature alarms
HI, HI2 High temperature alarms
Fig. 8.a
A0
HI2
A0
AH
AH2
Ux
Ux
Ux Probes selected
Heos +0300078EN - rel. 1.6 - 23.11.2017
50
ENG
Eb
Ec
EG
EH u5 n1 n2 n3 u1 u2 u3 u4
Code Description rE Control probe broken or disconnected
SLP
EA
Serial probe broken or disconnected
Outlet probe broken or disconnected
EI
EL
EM
IA dA
Lo
Lo2
HI
Defrost probe 1 broken or disconnected
Air intake probe broken or disconnected
Auxiliary probe 1 broken or disconnected
Auxiliary probe 2 broken or disconnected
Humidity probe t broken or disconnected
Temperature probe to calc. dew point broken or disconnected
Glass temperature probe broken or disconnected
Immediate external alarm
Delayed external alarm
Low temperature alarm
Low temperature alarm 2
High temperature alarm
HI2
Ed1
High temperature alarm 2
Defrost ended after maximum time
MOP MOP alarm
LOP LOP alarm
LSh Low superheat alarm
HSh High SH temperature alarm tC
MA
RTC invalid or fl at battery
Communication lost with Master n4 n5 dr
LSA
Communication lost with Slave 1
Communication lost with Slave 2
Communication lost with Slave 3
Communication lost with Slave 4
Communication lost with Slave 5
Alarm on Slave 1
Alarm on Slave 2
Alarm on Slave 3
Alarm on Slave 4
Alarm on Slave 5
Door open timeout
Low suction temperature alarm (*)
Mnt Crt Cold room maintenance timeout
UI
GAI
ISF
AEI
UIE Power+ no (*)
Failed compressor start (att.: / max.: ) (*)
Envelope zone alarm (*)
Hid dLP
Pnr
LP
HP
ELP
ESt
EHP
Edt
LqP
High discharge temperature (*)
Power+ not recognised
Low pressure alarm (*)
High pressure alarm (*)
Suction pressure probe S1 alarm
Suction temperature probe S2 alarm
Discharge pressure probe S3 alarm
Discharge temperature probe S4 alarm
Liquid probe broken or disconnected
WiP HIP Water inlet probe broken or disconnected
WoP HoP Water outlet probe broken or disconnected dtA
VPA
LCA
CSF
Low Power + driver temperature
Valve position warning
Low refrigerant charge warning
Compressor start failed
GEA Envelope alarm with shutdown
GIA Inverter alarm with shutdown
AC1...5 Compressors alarm 1...5
Hd1...5 High temperature discharge compressors 1...5
ACE Check room probe confi guration to calculate dew point
CPC Check compressor probe confi guration
NCM Master confi gured without pLAN network
Log x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Man
Auto
AI8
Auto
AI7
AI7
Auto
Auto
Auto
Man
Man
Auto
Auto
Auto
Auto
Auto
Imm.
Imm.
Imm.
Imm.
Imm.
Pb2
Pb4
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
Imm.
dHd
Imm.
Imm.
Imm.
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
AI9
Auto
AI8
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Reset Delay Alarm relay Action
Auto Imm.
ON
Auto
Auto
Imm.
Imm.
OFF
ON Safety control
Auto
Auto
Auto
Auto
Imm.
Imm.
Imm.
Imm.
OFF
ON
OFF
OFF
Safety control
Imm.
Imm.
Imm.
Imm.
A7
Ad
Ad
Ad
OFF
OFF
OFF
ON
ON
ON
ON
ON
Compressor OFF
Compressor OFF
Ad
Imm.
PM3
PL3
P9
Pb
-
15s
15s
15s
15s
15s
15s
15s
15s
15s
15s
15s d8
P12
Imm.
Imm.
Imm.
Imm.
Imm.
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
Compressor OFF
Compressor OFF
Compressor OFF
Fans ON
Compressor OFF
Compressor OFF
Compressor OFF
Compressor may stay OFF if occurs more than once in
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON set time
See Al_Envelop
See Al_Envelop
Compressor does not start
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor 1...5 OFF
Compressor 1...5 OFF
Compressor OFF
Note: in the event of alarms, the evaporator fan behaves as set (with control active) for parameter F2 (screen Dd01).
(*) Manual or semi-automatic reset
51 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
9.1 Setting the controller’s address
The controller’s pLAN address set by default in the factory is 1. The controller’s address can be set via a terminal connected in the pLAN network. The controller is assigned a private (Pr) or shared (Sh) terminal with address 32. The address of the external terminal can be set in the range between 0 and 32; addresses between 1 and 32 are used by the pLAN protocol, while address 0 identifi es the Local terminal protocol, used for point-to-point connections and to confi gure the controller (this procedure is only possible with a pGD terminal and one pCO only).
If the controller with the default setting (address=1) is connected to an external terminal (address=32), communication is established and the display on the external terminal replicates the display on the built-in terminal, if featured. If, on the other hand, the controller has a diff erent address (e.g. 7) and the terminal is not set to communicate with the controller with this address, once the connection has been established, the terminal displays a blank screen.
In this case, proceed as follows.
Procedure:
1. Press the UP, DOWN and Enter buttons together to access the screen for setting the terminal’s address.
Display address setting............:02
I/O Board address..:07
4. Power on the controller while holding the Alarm and Up buttons together, until the following screen is shown.
selftest please wait...
5. Use UP and DOWN to set the controller’s pLAN address to 7 and confi rm by pressing Enter.
pLAN address: 7
UP: increase
DOWN: decrease
ENTER: save & exit
2. Set the address of the display, 0 for point-to-point connections.
Confi rm by pressing Enter.
Display address setting............:00
9.2 Setting the terminal’s address and connecting the controller to the terminal
After setting the controller’s network address (see previous paragraph), to establish connections between the controller and the terminal, the terminal’s address needs to be set.
Procedure:
1. Press the UP, DOWN and Enter buttons together. The screen is displayed for setting the terminal’s address. Set the address to 2 and confi rm by pressing Enter.
Display address setting............:02
3. Power off the controller.
Fig. 9.a
Slave1
2. Press the UP, DOWN and Enter buttons together. Press Enter twice and set the controller’s address to 7. Confi rm by pressing Enter.
Display address setting............:02
I/O Board address..:07
3. Confi rm by pressing Enter.
Terminal config press ENTER to continue
Heos +0300078EN - rel. 1.6 - 23.11.2017
52
ENG
4. Set terminal 1 (Trm1) with address 2 as private (Priv) or shared
(Shared) according to the application, and confi rm to exit. After a few seconds, the connection will be established.
5. To add a second terminal, repeat steps 1 to 4.
9.3 Uploading/updating the software
The following methods can be used to update the fi rmware and acquire the log fi les on pCO controllers:
• SmartKey programming key;
• pCO manager tool, installable on a PC.
Smart key
The PCOS00AKY0 key is an electronic device used to program and service the pCO sistema family controllers. PCOS00AKY0 simplifi es data transfer between the controllers installed and a personal computer by exploiting the high capacity fl ash memory for storing software applications, BIOS and variable logs. The pCO is connected directly via the telephone connector using the cable supplied, while to transfer the data to a personal computer, the USB adapter code PCOS00AKC0 is required. The power supply comes either via the USB port on the PC or from the controller, therefore no external power supply is needed.
start mode
P:07 Adr Priv/Shared
Trm1 02 Pr
Trm2 None --
Trm3 None -- Ok? Yes
telephone cable
Fig. 9.b
For the steps in the procedure, see par. 9.1.
Operating instructions start mode
USB
PCOS00AKC0
USB
Fig. 9.c
start mode
53
Programming the Smart Key via Personal Computer
The operating modes described in the table below can be confi gured using a program on the PC. The program can also load the software to the key or transfer logged data from the controller to disk.
Type Function
B Update software from key to pCO (BIOS, application, parameters, etc.)
C* Copy software from pCO to pCO (BIOS,
D
E application, parameters, etc.)
Read logs
Read logged data and software from
Mode button
Disabled
Switches the key from write mode to read mode
Disabled
Disabled
F
G pCO (BIOS, application, parameters, etc.)
Read logged data Disabled
Copy from pCO to pCO and read logs Switches the key to write mode, read mode and read logs mode
*: Default mode
Tab. 9.d
The key is factory-programmed in read/write mode (type C) so that it can be used immediately to transfer software from one controller to another.
When the key is connected to the personal computer, the symbols have the following meanings:
Flashing Waiting for connection to PC
Alternating When connected to PC indicates data transfer in progress
The programming key is compatible starting from BIOS version 3.43 and
BOOT version 3.01. For more detailed information on programming the key, see the pCO Manager program manual.
Using the Smart Key with the pCO/μPC
Switch off the pCO, remove any peripherals connected in the pLAN and plug the key into the telephone connector on the controller. When switching on again, all the symbols light up momentarily and the buzzer emits a beep. A few seconds later the key becomes operational. During this period the symbols will fl ash. The controller then enters programming mode and the start button lights up steadily. Press the button to start data transfer.
Important:
• If the key is type B, C or G (in write mode) pressing the start button will immediately delete the software already loaded on the pCO.
• Do not remove the key while data is being transferred to the key itself, as the fi le being transferred will be lost and the corresponding space will not be restored. To restore the original capacity all the fi les will need to be deleted. If the key is type “C” or “G”, simply perform a new application read operation.
Meanings of Buttons/Symbols start start+ start+ start+ mode
Flashing: the key is connecting to the pCO. During this phase, which may last a few seconds, the start button is disabled.
Flashing: The key has detected the pCO and is checking the access rights.
On steady: Pressing the start button will start writing the software to the pCO.
On steady: Pressing the start button will start reading the software from the pCO.
On steady: Pressing the start button will start reading the logs from the pCO.
On steady: In case of C or G keys, pressing the button for 1 second switches from read to write.
Tab. 9.b
If the key is type C of G, pressing the “mode” button for 1 second switches from read to read logs (G only) or to write. The symbols (write to pCO),
(read from pCO), (read logs) refl ect the selected status. If the key is not type “C” or “G”, the “mode” button is disabled and off . The “start” button starts the read or write operation, indicated by the fl ashing of the corresponding symbol ( or ) at a frequency proportional to the progress of the operation.
When the operation is completed, the buzzer will sound intermittently for 2 seconds. Pressing the start button again will make the buzzer sound without repeating the operation. To repeat the operation, the key must fi rst be unplugged. In case of error the symbol will light up together with the other LEDs. The following table can help you fi nd the cause of the problem.
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
Errors before pressing the START button
+ +
Symbols fl ashing
Communication error: No response from the pCO or: Key fi rmware version is incompatible
Symbols steady Password error
+mode
Symbols fl ashing Type of key is incompatible
+mode
+
+ +start
+ +mode
Symbols steady The key is missing one or more required fi -
Symbols steady + fl ashing start les (memory empty; no kit for the type of pCO connected)
Incompatibility between the software on the key and the pCO HW
Symbols steady + Incompatibility between pCO application fl ashing mode and HW (application size)
Symbols steady No logged data present on the pCO
+ +
Steady Type of key not programmed.
Tab. 9.e
Errori dopo la pressione del tasto START
+start+
+start+ +buzzer
+start+
+buzzer
+buzzer
Symbols fl ashing and buzzer sounding intermittently
Symbols fl ashing and buzzer sounding intermittently
Symbols fl ashing and buzzer sounding intermittently
Write operation failed
Read operation failed
Read logs operation failed
+ +
Symbols steady + fl ashing
Incompatibility between log confi guration and pCOHW (no fl ash memory). This error does not prevent writing other fi les.
Steady
+
Flashing Generic error
Tab. 9.f
As for the port number, follow the Wizard’s instructions for the port to be identifi ed automatically (e.g. COM4).
Fig. 9.h
Switch the controller off and then on again and use the Connect command to establish the connection. When the connection is established the fl ashing message “ONLINE” will appear at the bottom left of the screen.
Fig. 9.i
Installing the application program
• Select the directory containing the application program fi les and click
“Upload” to upload the program to the pCO controller.
9.4 pCO Manager: operating instructions
pCO Manager is a program that lets you manage all the confi guration, debugging and maintenance operations on pCO Sistema devices. pCO
Manager can be installed by itself or as part of the 1Tool programming environment.
Installing pCO Manager
Go to http://ksa.carel.com and, in section pCO Sistema, select pCO_manager.
After you accept the general conditions of the software’s free use licence, a window will open from which you can download the fi le pCO_manager.
zip. Install the program on your computer.
Connecting the PC to the pCO controller
Connect a cable with USB/RS485 converter to the USB port on the computer, and connect the converter to a telephone cable plugged into the pLAN port of the pCO.
USB
CVSTDUTLF0
USB
Fig. 9.j
Commissioning
• Using the mouse, select “Commissioning” at the bottom left. A new work environment will appear.
power supply
Fig. 9.g
Upon launching, pCO Manager will display a screen showing the connection settings in the upper right-hand corner. Choose:
1. “connessione locale” [local connection];
2. baud rate: Auto;
3. “ricerca dispositivo” [fi nd device]: Auto (pLAN).
Heos +0300078EN - rel. 1.6 - 23.11.2017
54
Fig. 9.k
• Click on “confi gura dispositivo” [confi gure device] to display all the application variables. The variables can be selected according to the categories that appear at the bottom.
Fig. 9.l
ENG
Changing a parameter
Select the parameter category and then the parameter that you want to edit. The parameter (e.g. recovery.recovery_type) will be highlighted in blue.
Fig. 9.m
1. Double-click on the column marked “letto” [read]. A window will appear in which you can enter the new value for the parameter.
Fig. 9.n
2. Enter the new value (e.g. 3) and click OK. The new value will appear in the column marked “scritto” [written]. To write the parameter to the pCO controller, right-click and select “scrivi selezionate” [write selected].
The new value will appear in the column marked “scritto” [written], meaning that the parameter has been written to the controller.
Fig. 9.o
Click on “Salva” [Save] to generate the project’s “.2cw” fi le.
Commissioning: basic concepts
Note: The following paragraphs are from the online help of pCO
Manager, to which the user is referred for further details.
Commissioning is a confi guring and real-time monitoring software that can be used to supervise the performance of an application program installed on a pCO, to start up the pCO and to perform debugging and maintenance. With this software the user can set the confi guration parameters, edit the values of volatile and permanent variables, save on fi le the trends of the unit’s main quantities, manually manage the unit’s I/O using simulation fi les and monitor/reset the alarms of the unit on which the device is installed.
Work carried out with Commissioning is preceded by confi guring the work environment, which is typically done by the project designer. The active project in 1Tool is automatically loaded by pCO Manager.
The project designer can use the confi guration functions of Commissioning to decide which variables should be subjected to monitoring, logging, trend-monitoring and event-monitoring, to organize variables into categories and to create sets of confi guration parameters.
55
Operators using Commissioning for maintenance will be able to see the necessary variables and to draw from preset confi guration values.
Support fi les
Once the design of the application is completed, 1Tool generates a number of fi les in the compiling stage, two of which are required by Commissioning:
• <nomeApplicativo>.2CF [<ApplicationName>.2CF] (variable descriptor)
• <nomeApplicativo>.2CD [<ApplicationName>.2CD] (category and access profi le descriptor)
In addition to these fi les, the software also manages the <nome applicativo>.
DEV [<Application Name>.DEV] fi le, which contains the unit’s preset parameters. When the user has fi nished using Commissioning, whether for confi guration or monitoring purposes, the following fi les can be generated:
• <nomeApplicativo>.2CW [<ApplicationName>.2CW] (descriptor for categories, access profi les, monitoring groups);
• <nomefi leCommissioningLog>.CSV [<FilenameCommissioningLog>.
CSV] (fi le used for the commissioning log, containing data of the variables logged during monitoring).
Therefore, to confi gure Commissioning the following fi les are required:
.2CF, 2CD and, if necessary, the .DEV fi le, which can be imported or exported. For monitoring purposes, in addition to the fi les above, it might also be necessary to have the .2CW fi le, containing the defi nition of the work environment. The commissioning log fi le is a simple output fi le.
pCO Load: basic concepts
pCOLoad is the module that manages:
• uploading to the fl ash memory (of the device or of the ProgKeyX key installed on the pCO);
• uploading to the NAND memory of certain devices;
• downloading the log fi le, .DEV fi le and P memory (from the fl ash memory);
• downloading fi les from the NAND memory, if present.
The fi les exchanged with the Flash memories of pCO controllers are:
• BOOT.BIN (download reserved, upload enabled from menu)
• BIOS.BIN (download reserved)
• <nomeApplicativo>.BLB [<ApplicationName>.BLB] (download reserved)
• <nomeApplicativo>.BIN [<ApplicationName>.BIN] (download reserved)
• <nomeApplicativo>.DEV [<ApplicationName>.DEV]
• <nomeApplicativo>.GRT [<ApplicationName>.GRT] (upload only, from which the .GRP fi le is extracted)
• <nomeApplicativo>.IUP [<ApplicationName>.IUP]
• <nomeApplicativo>.LCT [<ApplicationName>.LCT]
• <nomeApplicativo>.PVT [<ApplicationName>.PVT]
• <nomepCOlog>.BIN, <nomepCOlog>.CSV, <nomepCOlog_GRAPH>.CSV
[<pCOlogName>.BIN, <pCOlogName>.CSV, <pCOlog_GRAPHName>.
CSV] (only if log fi les have been confi gured, download only).
The fi les exchanged with the NAND memories of pCO controllers are:
• any fi le that the pCO can independently copy to fl ash memory (see list);
• external fi les (e.g. .pdf or .doc fi les for documentation).
LogEditor: basic concepts
LogEditor is the module used to confi gure the log fi les of pCO devices
(pCO logs). Confi guring pCO logs consists in defi ning a number of sets of variables in which to specify which variables should be logged, the logging method (by frequency or by event) and the minimum number of loggings required. Confi guration is based on a binary fi le (.PVT – Public
Variable Table), which is generated by 1Tool and contains the descriptive data of the variables that can be logged.
All the log confi gurations so defi ned are saved in the .LCT (Log
Confi guration Table) binary fi le, which must be uploaded to the pCO together with the .PVT fi le. Log confi guration data is also saved in a fi le that can be used only by LogEditor – the .LEF fi le, which must be saved to be edited with LogEditor as necessary.
LogEditor can be used even when the device is not connected. Once the fi les for logging are uploaded to the pCO, the pCO saves the logged data in the following fi les:
• .BIN fi le containing all the data in binary format;
• .CSV fi le containing the same data in a generic format with values separated by commas;
• *_GRAPH.CSV containing the same data to be used for charting purposes.
Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
9.5 History of software revisions
New version 1.1
• Water- or air-cooled condenser control added
• Anti-sweat control added for water-cooled inverters
• Oil recovery management modifi ed for multi-evaporator systems
• Pressure control added for ON/OFF compressors in multi-evaporator systems
• Control adapted for extension of envelope on Toshiba compressors
New version 1.1018
• New warning
• Modify alarms management
New version 1.1027
• Added management of ON/OFF multi-compressors
New version 1.2
• Added pump down management
New version 1.3
• Defrost on multi-evaporator changed
• Various updates
New version 1.4
• Dual temp function added
• Some default values changed
• Various updates
Heos +0300078EN - rel. 1.6 - 23.11.2017
56
N
otes:
ENG
57 Heos +0300078EN - rel. 1.6 - 23.11.2017
ENG
N
otes:
Heos +0300078EN - rel. 1.6 - 23.11.2017
58
CAREL INDUSTRIES - Headquarters
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 - Fax (+39) 049.9716600
e-mail: [email protected] - www.carel.com
Agenzia / Agency:
Advertisement