ABB motion control
User’s manual
MicroFlex e150 servo drive
MN1961WEN
List of related manuals
Drive hardware manuals and guides
MicroFlex e150 Quick Installation Guide
Safety Manual: Safe Torque Off (STO) function for
MicroFlex e150 drives
MicroFlex e150 wall chart
MicroFlex e150 flyer
Code (English)
LT0307
LT0313
LT0296
3AUA0000097609
You can find manuals and other product documents in PDF format on the Internet. See section
Document library on the Internet on the inside of the back cover. For manuals not available in the
Document library, contact your local ABB representative.
2013 ABB Oy. All Rights Reserved.
User’s manual
MicroFlex e150
Table of contents
1. Safety
4. Mechanical installation
6. Electrical installation:
AC input, motor and brake
9. Start-up
LT0291A04EN
EFFECTIVE: 2013-12-01
Table of contents 5
Table of contents
List of related manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1. Safety
Safety in installation and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Safe start-up and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
General safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2. Introduction to the manual
Safety
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Contents of this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Quick installation and start-up flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3. Hardware description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Connections - front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Connections - top panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Type designation label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4. Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Requirements for the installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mounting and cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Effects of mounting surface and proximity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5. Planning the electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Checking the compatibility of the motor and drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Selecting the supply disconnecting device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6 Table of contents
European Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Other regions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Emergency stop devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Implementing the STO function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Thermal overload and short circuit protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Selecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
General rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Protecting the contacts of relay outputs and attenuating inductive loads . . . . . . . . . . . . . . . . 38
Selecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Connection of a motor temperature sensor to the drive I/O . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Routing the cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Separate control cable ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6. Electrical installation: AC input, motor and brake
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Connecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Earthing / grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Input power conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Supplying input power from a variac (variable transformer) . . . . . . . . . . . . . . . . . . . . . . . 47
Power supply filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Harmonic suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Reversing the filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Power disconnect and protection devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Drive overload protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
24 V control circuit supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Motor connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Motor power cable shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Motor circuit contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Sinusoidal filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Motor brake connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Thermal switch connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Brake resistor (regeneration resistor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7. Electrical installation: input / output
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Analog inputs AIN0, AIN1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Analog output AOUT0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Digital I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Using a digital input as a drive enable input (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Using a digital input as a home switch input (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Digital inputs - Safe Torque Off (STO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Digital inputs - general purpose DIN0, DIN3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Digital inputs - general purpose DIN1, DIN2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Special functions on inputs DIN1, DIN2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Digital inputs - general purpose DIN4 - DIN9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Status output (DOUT0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Digital outputs DOUT1, DOUT2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Table of contents 7
Digital outputs DOUT3 - DOUT6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
USB interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
RS485 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Ethernet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Standard Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
EtherCAT® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
EtherCAT configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Ethernet connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
DIP switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Motor feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Incremental encoder interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
BiSS interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
SSI interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
EnDat interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Smart Abs interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
SinCos interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Extra incremental encoder interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
8. Installation checklist
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Safe Torque Off (STO) connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9. Start-up
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Connecting the MicroFlex e150 to the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Installing Mint WorkBench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Starting the MicroFlex e150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Preliminary checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Power on checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
USB driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Configuring the TCP/IP connection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Configuring the PC network adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mint Machine Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Starting MMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Mint WorkBench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Help file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Starting Mint WorkBench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Commissioning Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Further tuning - no load attached . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Further tuning - with load attached . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Optimizing the velocity response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Performing test moves - continuous jog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Performing test moves - relative positional move . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Further configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Configuration tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Parameters tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Spy window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Other tools and windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
8 Table of contents
Safe Torque Off (STO) acceptance test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
10. Fault tracing
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Problem diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
SupportMe feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Power-cycling the MicroFlex e150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
MicroFlex e150 indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Ethernet LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Drive status display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Mint WorkBench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
11. Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Dimension drawing (all models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Electrical power network specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Effect of AC power supply voltage on DC-bus voltage . . . . . . . . . . . . . . . . . . . . . . . . . 130
Effect of AC power supply voltage on DC-bus ripple voltage . . . . . . . . . . . . . . . . . . . . . 130
Effect of output current on DC-bus ripple voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Derating characteristic for 3 A models (E152A03...): . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Derating characteristic for 6 A models (E152A06...): . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Derating characteristic for 9 A models (E152A09...): . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Overtemperature trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Heat dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Recommended fuses, circuit breakers and wire sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Input power-cycling and inrush . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Discharge period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Power supply filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
24 V control circuit supply (X2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Motor output power (X1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Brake (X1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Braking capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Brake resistor selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Braking energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Braking power and average power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Resistor choice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Resistor derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Duty cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Input / output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Analog inputs AIN0, AIN1 (X4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Analog output AOUT0 (X4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Digital inputs STO1, STO2 (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Digital inputs DIN0, DIN3 (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Digital inputs DIN1, DIN2 - high speed (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Table of contents 9
Digital inputs DIN4 - DIN9 (OPT1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Digital outputs DOUT0 (Status), DOUT1, DOUT2 (X3) . . . . . . . . . . . . . . . . . . . . . . . . . 147
Digital outputs DOUT3 - DOUT6 (OPT1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Incremental encoder interface (X8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
BiSS encoder interface (X8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
SSI encoder interface (X8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
SinCos / EnDat encoder interface (X8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Smart Abs encoder interface (X8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Ethernet interface (E1, E2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Design and test standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Environmental test standards: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Functional safety standards: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Compliance with the European EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Compliance with the EN 61800-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Category C2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Category C3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Compliance with the European Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Validating the operation of the Safe Torque Off function . . . . . . . . . . . . . . . . . . . . . . . . 155
CE Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
UL marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
UL checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Servo configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Torque servo configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
12. Accessories
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Fan tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Foot-mount filter (single phase only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
24 V power supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
EMC filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Brake resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Encoder breakout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Motor power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Feedback cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Ethernet cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
13. Appendix: Safe Torque Off (STO)
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Operation of the STO function and diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
10 Table of contents
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Validating the operation of the Safe Torque Off function . . . . . . . . . . . . . . . . . . . . . . . . 176
Technical data: Digital inputs STO1, STO2 (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
STO function: data related to safety standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
STO function: TüV certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
1
Safety 11
Safety
Safety in installation and maintenance
These warnings are intended for all who work on the drive, motor cable or motor.
Electrical safety
WARNING!
Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
Only qualified electricians are allowed to install and maintain the drive!
• Be sure the system is properly earthed/grounded before applying power. Do not apply AC power before earths/grounds are connected.
• Never work on the drive, motor cable or motor when input power is applied. After disconnecting the input power, always wait for 5 minutes to let the intermediate circuit capacitors discharge before you start working on the drive, motor or motor cable. Always ensure by measuring with a multimeter (impedance at least
1 Mohm) that there is no voltage between the drive input phases L1, L2 and L3 and the ground.
• Do not work on the control cables when power is applied to the drive or to the external control circuits. Externally supplied control circuits can carry dangerous voltage even when the input power of the drive is switched off.
• Do not make any insulation or voltage withstand tests on the drive.
• All ELV (extra low voltage) circuits connected to the drive must be used within a zone of equipotential bonding, i.e. within a zone where all simultaneously accessible conductive parts are electrically connected to prevent hazardous voltages appearing between them. This is accomplished by proper factory grounding.
12 Safety
• Even when the motor is stopped, dangerous voltage is present at the power circuit terminals L1, L2, L3, U, V, W, R1, R2 (connector X1).
• If a motor is driven mechanically, it can generate hazardous voltages that are conducted to its power terminals. The enclosure must be earthed/grounded to prevent possible shock hazard.
• To prevent equipment damage, be certain that the input power has correctly sized protective devices installed.
• To prevent equipment damage, be certain that input and output signals are powered and referenced correctly.
• To ensure reliable performance of this equipment be certain that all signals to/from the drive are shielded correctly.
• Do not tin (solder) exposed wires. Solder contracts over time and can cause loose connections. Use crimp connections where possible.
• If the drive is subjected to high potential (‘hipot') testing, only DC voltages may be applied. AC voltage hipot tests could damage the drive. For further information please contact your local ABB representative.
• The safe integration of the drive into a machine system is the responsibility of the machine designer. Be sure to comply with the local safety requirements at the place where the machine is to be used. In Europe these are the Machinery
Directive, the ElectroMagnetic Compatibility Directive and the Low Voltage
Directive. In the United States this is the National Electrical code and local codes.
• To comply with CE directive 2004/108/EC an appropriate AC filter must be installed.
• Motor overtemperature sensing is required to satisfy UL 508C. The drive has no provisions for motor overtemperature protection, so external provisions are required.
• Both the AC supply and the 24 V DC supply must be fused.
• The 24 V DC control circuit supply must be installed so that the 24 V DC supplied to the unit is isolated from the AC supply using double or reinforced insulation, or by using basic insulation with a protective earth.
• The input of the control circuit must be limited to Safety Extra Low Voltage circuits.
Permanent magnet motor drives
These are additional warnings concerning permanent magnet motor drives. Ignoring the instructions can cause physical injury or death, or damage to the equipment.
WARNING!
Do not work on the drive when the permanent magnet motor is rotating. Also, when the supply power is switched off and the inverter is stopped, a rotating permanent magnet motor feeds power to the intermediate circuit of the drive and the supply connections become live.
Before installation and maintenance work on the drive:
Safety 13
• Stop the motor.
• Ensure that there is no voltage on the drive power terminals according to step 1 or
2, or if possible, according to the both of the following steps:
1. Disconnect the motor from the drive with a safety switch or by other means.
Measure that there is no voltage present on the drive input (L1, L2, L3), motor output (U, V, W), or brake terminals (R1, R2).
2. Ensure that the motor cannot rotate during work. Make sure that no other system, like a hydraulic crawling drive, is able to rotate the motor directly or through any mechanical connection like felt, nip, rope, etc. Measure that there is no voltage present on the drive input (L1, L2, L3), output (U, V, W), or brake
/ regeneration terminals (R1, R2). Ground the drive output terminals temporarily by connecting them together as well as to the PE.
General safety
WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
• The drive is not field repairable. Never attempt to repair a malfunctioning drive; contact your local ABB representative or Authorized Service Center for replacement.
• When operating a rotary motor with no load coupled to its shaft, remove the shaft key to prevent it flying out when the shaft rotates.
• Operating the MicroFlex e150 in torque mode with no load attached to the motor can cause the motor to accelerate rapidly to excessive speed.
• Make sure that dust from drilling does not enter the drive during the installation.
Electrically conductive dust inside the drive can cause damage or lead to malfunction.
• Drives must be installed inside an electrical cabinet that provides environmental control and protection. Installation information for the drive is provided in this manual. Motors and controlling devices that connect to the drive should have specifications compatible with the drive. If not installed in an electrical cabinet, barriers around the equipment are required.
• Avoid locating the drive immediately above or beside heat generating equipment, directly below water or steam pipes, or in the vicinity of corrosive substances or vapors, metal particles and dust.
• Ensure sufficient cooling. Failure to meet cooling air flow requirements will result in reduced product lifetime and/or drive overtemperature trips.
• The metal heat sink on the left side of the MicroFlex e150 can become very hot during normal operation.
14 Safety
Safe start-up and operation
These warnings are intended for all who plan to start-up or operate the drive.
General safety
WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
• Before adjusting the drive and putting it into service, make sure that the motor and all driven equipment are suitable for operation throughout the speed range provided by the drive. The drive can be adjusted to operate the motor at speeds above and below the speed provided by connecting the motor directly to the power line.
• Improper operation or programming of the drive can cause violent motion of the motor and driven equipment. Be certain that unexpected motor movement will not cause injury to personnel or damage to equipment.
• Do not activate automatic fault reset functions if dangerous situations can occur.
When activated, these functions will reset the drive and resume operation after a fault.
• Do not control the motor with an AC contactor or disconnecting device
(disconnecting means); use instead external commands (I/O or fieldbus).
• If a drive enable signal is already present when power is applied to the
MicroFlex e150, the motor could begin to move immediately.
• The metal heat sink on the left side of the MicroFlex e150 can become very hot during normal operation.
• MEDICAL DEVICE / PACEMAKER DANGER: Magnetic and electromagnetic fields in the vicinity of current carrying conductors and industrial motors can result in a serious health hazard to persons with cardiac pacemakers, internal cardiac defibrillators, neurostimulators, metal implants, cochlear implants, hearing aids, and other medical devices. To avoid risk, stay away from the area surrounding a motor and its current carrying conductors.
• When operating a rotary motor with no load coupled to its shaft, remove the shaft key to prevent it flying out when the shaft rotates.
• A brake resistor can generate enough heat to ignite combustible materials. To avoid fire hazard, keep all combustible materials and flammable vapors away from brake resistors.
Introduction to the manual 15
2
Introduction to the manual
What this chapter contains
The chapter describes applicability, target audience and purpose of this manual. It describes the contents of this manual and refers to a list of related manuals for more information. The chapter also contains a flowchart of steps for checking the delivery and installing and commissioning the drive. The flowchart refers to chapters/sections in this manual.
Applicability
The manual is applicable to the MicroFlex e150 drive.
Target audience
The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. The manual is written for readers worldwide. Both SI and imperial units are shown.
Purpose of the manual
This manual provides information needed for planning the installation, installing, commissioning, using and servicing the drive.
16 Introduction to the manual
Contents of this manual
The manual consists of the following chapters:
• Safety (page 11 ) gives safety instructions you must follow when installing, commissioning, operating and servicing the drive.
• Introduction to the manual (this chapter, page 15 ) describes applicability, target audience, purpose and contents of this manual. It also contains a quick installation and commissioning flowchart.
•
Hardware description
(page
21
) describes the operation principle, connector layout, type designation label and type designation information in short.
•
Mechanical installation
(page
27
) describes how to check the installation site, unpack, check the delivery and install the drive mechanically.
•
Planning the electrical installation
(page
33
) describes the requirements for the
AC supply, cabling and RCDs.
•
Electrical installation: AC input, motor and brake
(page
43
) describes the installation of high power connections including the AC supply, motor output, and brake resistor.
• Electrical installation: input / output (page 59 ) describes the installation of low power connections, including analog and digital input/outputs (including Safe
Torque Off), motor feedback and Ethernet.
• Installation checklist (page 87 ) provides a list of checks to confirm that the physical installation has been completed correctly.
• Start-up (page 89 ) describes the steps for applying power to the drive, installing the Mint Machine Center software, and tuning and optimizing the motor/drive combination.
•
Fault tracing
(page
117
) describes the drive’s LED indicators and provides solution to common problems encountered during installation.
•
Technical data
(page
127
) contains the technical specifications of the drive, e.g. the dimensions, ratings, technical specifications, and provisions for fulfilling the requirements for CE and other markings.
•
Appendix: Safe Torque Off (STO)
(page
173
) describes STO features, installation, and technical data.
• Accessories (page 163 ) describes optional accessories.
Related documents
See List of related manuals on page 2 (inside the front cover).
Introduction to the manual 17
Quick installation and start-up flowchart
Task
Plan the electrical installation and acquire the accessories needed (cables, fuses, etc.).
Check the ratings, required cooling air flow, input power connection, compatibility of the motor, motor connection, and other technical data.
See
Planning the electrical installation
(page 43 )
Technical data (page 119 )
Check the installation site.
Unpack and check the units (only intact units may be started up).
Check that all necessary optional modules and equipment are present and correct.
Mount the drive.
Requirements for the installation site
(page 27 )
Checking the delivery (page 28 ).
Mounting and cooling (page 29 ).
Route the cables.
Connect the power cable.
Connect the motor cable.
Connect the control cables.
Routing the cables (page 39 )
Check the insulation of the supply cable, the motor and the motor cable.
Checking the insulation of the assembly
(page 44 )
Connecting the power cables
Motor connections
Electrical installation: input / output
(page 59 ).
(page
(page
52 ).
Installation checklist (page 87 ).
45 ).
Check the installation.
Start the drive.
Start-up (page 89 )
18 Introduction to the manual
Terms and abbreviations
The following units and abbreviations might appear in this manual.
General terms
cu.ft
lbf-in
N·m
ADC
ASCII
AWG
CDROM
CiA
CTRL+E
DAC
DS402
EDS
EMC
HMI
ISO
Kbit/s
LCD
Mbit/s
MB
MMC
Unit / term / abbreviation
W
A
Ω
μ F pF mH mm m in ft
Φ ms
μ s ns
Description
Watt
Ampere
Ohm microfarad picofarad millihenry phase millisecond microsecond nanosecond millimeter meter inch feet cubic feet pound force inch (torque)
Newton meter (torque)
Analog to Digital Converter
American Standard Code for Information Interchange
American Wire Gauge
Compact Disc Read Only Memory
CAN in Automation International Users and Manufacturers Group e.V.
on the PC keyboard, press Ctrl and E at the same time.
Digital to Analog Converter
CiA Device Profile for Drives and Motion Control
Electronic Data Sheet
Electromagnetic Compatibility
Human Machine Interface
International Standards Organization kilobits per second
Liquid Crystal Display megabits per second megabytes
Mint Machine Center
Introduction to the manual 19
Unit / term / abbreviation
(NC)
RF
SSI
TCP/IP
UDP
Description
Not Connected
Radio Frequency
Synchronous Serial Interface
Transmission Control Protocol / Internet Protocol
User Datagram Protocol
See also page 177 for safety related abbreviations.
Trademarks
EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
Windows XP, Windows Vista and Windows 7 are registered trademarks of the
Microsoft Corporation.
20 Introduction to the manual
Hardware description
Hardware description 21
3
What this chapter contains
The chapter briefly describes the operation principle, layout, type designation label and type designation information. It also shows a general diagram of power connections and control interfaces.
Features
The MicroFlex e150 is a versatile servo drive, providing a flexible and powerful motion control solution for rotary and linear motors. Standard features include:
• Single axis drive for AC brushless servo motors. Can also control induction motors.
• Range of models with continuous current ratings of 3 A, 6 A or 9 A.
• Direct connection to 115 V AC or 230 V AC single-phase, or 230 V AC threephase supplies.
• Universal feedback interface supporting incremental encoder, BiSS, SSI, EnDat,
SinCos or Smart Abs feedback.
• Position, velocity and current control.
• 10 optically isolated general purpose digital inputs. Two inputs have ‘fast input' capability, providing real-time position capture.
• 2 dedicated Safe Torque Off (STO) digital inputs.
• 7 optically isolated general purpose digital outputs.
• 2 analog inputs (±10 V) and 1 analog output (±10 V).
• USB serial port (compatible with USB 2.0 and USB 3.0).
• EtherCAT support.
• Programmable in Mint (except models E152AxxEI N A).
22 Hardware description
Operating principle
The figure below shows the simplified main circuit diagram of the drive. The rectifier converts three-phase AC voltage to DC voltage. The capacitor bank of the intermediate circuit stabilizes the DC voltage. The inverter converts the DC voltage back to AC voltage for the AC motor. The brake chopper connects the external brake resistor to the intermediate DC circuit when the voltage in the circuit exceeds its maximum limit.
AC supply
L1
L2
L3
Rectifier Capacitor bank
Brake chopper
R1 R2
Inverter
U
V
W
AC motor
Hardware description 23
Product overview
Connections - front panel
X1 Power LEDs
Earth/Ground
Earth/Ground
(NC)
L1 AC Phase 1/L
L2 AC Phase 2 / N
L3 AC Phase 3
U Motor U
V Motor V
W Motor W
R1 Brake
R2 Brake
The seven-segment display and the two EtherCAT
LEDs are described in MicroFlex e150 indicators on page 119 .
DIP switches
These switches select the Ethernet mode and
RS485 settings. See DIP switches on page 79 .
U1 USB
1 +5 V
2 Data-
3 Data+
4 GND
X6 RS485 serial port
2-wire 4-wire
1 TXA(+)/RXA(+) TXA(+)
2 TXB(-)/RXB(-) TXB(-)
3 GND
4 7 V out
5 (NC)
6 (NC)
GND
7 V out
RXA(+)
RXB(-)
X3 Input / Output
1 Status-
2 DOUT2-
3 DOUT1-
4 DIN2-
5 DIN3-
6 DIN1-
7 DIN0-
8 SREF
9 SREF
10 Shield
11 Status+
12 DOUT2+
13 DOUT1+
14 DIN2+
15 DIN3+
16 DIN1+
17 DIN0+
18 STO1
19 STO2
20 Shield
X4 Input / Output
1 AOUT0
2 AIN1+
3 AIN0+
4 Shield
5 AGND
6 AIN1-
7 AIN0-
8 Shield
X2 Control circuit power
0 V
+24V
(NC) = Not Connected. Do not make a connection to this pin.
X8 Feedback in
1
2
Pin Incremental BiSS/SSI/ Smart Abs EnDat 2.1 SinCos
EnDat 2.2
7
8
9
10
5
6
3
4
11
12
13
14
CHA+
CHB+
CHZ+
Sense
Hall U-
Hall U+
Hall V-
Hall V+
CHA-
CHB-
CHZ-
+5 V out
DGND
Hall W-
15 Hall W+
Shell Shield
Data+
Clock+
(NC)
Sense
(NC)
(NC)
(NC)
(NC)
Data-
Clock-
DGND
(NC)
(NC)
Shield
Data+
(NC)
(NC)
Sense
(NC)
(NC)
(NC)
(NC)
Data-
(NC)
Data+
Clock+
(NC)
Sense
Sin-*
Sin+*
Cos-*
Cos+*
(NC)
(NC)
(NC)
Sense
Sin-
Sin+
Cos-
Cos+
(NC) (NC) (NC) (NC)
+5 V out +5 V out +5 V out +5 V out
DGND
(NC)
(NC)
Shield
Data-
Clock-
DGND
(NC)
(NC)
Shield
(NC)
(NC)
DGND
(NC)
(NC)
Shield
* EnDat v2.1 only. EnDat v2.2 does not use the Sin and Cos signals.
Tightening torque for terminal block connections X1 & X2 is 0.5-0.6 N·m (4.4-5.3 lb-in).
Maximum wire sizes: X1: 2.5 mm
2
; X3: 0.5 mm
2
.
Connector X3 is designed to accept bare wires only; do not use ferrules.
24 Hardware description
Connections - top panel
OPT1: Input / Output
14 Shield
13 CREF1
12 DIN8
11 DIN9
10 USRV+
9 DOUT5
8 DOUT6
7 DIN4
6 DIN5
5 DIN6
4 DIN7
3 CREF0
2 DOUT3
1 DOUT4
E2
E1
E1 / E2 EtherCAT®
EtherCAT
IN
EtherCAT
OUT
E1 is also used for standard
Ethernet if DIP switch 4 is in the
ON position (see page
79
).
1 TX+
2 TX-
3 RX+
4 (NC)
5 (NC)
6 RX-
7 (NC)
8 (NC)
Both connectors have identical pinouts.
See chapter Electrical installation: AC input, motor and brake on page 43 for installation in general.
Hardware description 25
Type designation label
A description of the product’s catalog numbering system is shown below:
F
CAT.
S/No.
E152A09EIOA
U0316010002
Desc.
INPUT 105-250 AC 50/60 Hz 1 3
OUTPUT
Made in the UK
9A Cont/18A Pk 0-250V 3 Ø, 3kW
A 0 3 T R E N 2 3
U0316010002
Typical label shown.
Actual appearance may differ.
E
I
O
A xxx
E15
2A
09
E 1 5 2 A 0 9 E I O A x x x
MicroFlex e150.
115 - 230 V AC supply input.
Rated amps: 03 = 3 A, 06 = 6 A, 09 = 9 A.
Feedback: E = Universal Encoder (connector X8, see page 23 ).
Extra digital inputs / outputs present (connector OPT1).
Build option: O = Programmable, N = Not programmable.*
Hardware revision.
(Optional) Custom variant.
* Note: Model ..EI
N A.. cannot store or run a Mint program, but it does support individual Mint commands entered in the Mint WorkBench Command window.
Commands received from a host application using the Mint ActiveX control are also supported, although the application cannot be used to download a program file to the drive.
26 Hardware description
Mechanical installation 27
Mechanical installation
4
What this chapter contains
The chapter describes the mechanical installation procedure of the drive.
Requirements for the installation site
The safe operation of this equipment depends upon its use in the appropriate environment. The following points must be considered:
• The MicroFlex e150 must be installed indoors, permanently fixed and located so that it can only be accessed by service personnel using tools. When installed in a cabinet, the cabinet must have a volume of at least 0.19 m
3
(6.84 cu.ft). If not installed in a cabinet, barriers around the equipment are required.
• The MicroFlex e150 must be secured by the slots in the flange. The protective earth/ground (the threaded hole on the top of the MicroFlex e150) must be bonded to a safety earth/ground using either a 25 A conductor or a conductor of three times the peak current rating - whichever is the greater.
• Avoid locating the MicroFlex e150 immediately above or beside heat generating equipment, or directly below water steam pipes.
• Avoid locating the MicroFlex e150 in the vicinity of corrosive substances or vapors, metal particles and dust.
• Failure to meet cooling air flow requirements will result in reduced product lifetime and/or drive overtemperature trips.
• The maximum suggested operating altitude is 1000 m (3300 ft).
• The MicroFlex e150 must be installed where the pollution degree according to
EN 60664 shall not exceed 2.
• The atmosphere must not contain flammable gases or vapors.
• There must not be abnormal levels of nuclear radiation or X-rays.
28 Mechanical installation
• The threaded holes in the top and bottom of the case are for cable clamps. The holes are threaded for M4 bolts no longer than 11 mm (0.43 in).
• The D-type connectors on the front panel of the MicroFlex e150 are secured using two hexagonal jack screws (sometimes known as “screwlocks”). If a jack screw is removed accidentally or lost it must be replaced with a #4-40 UNC jack screw with an external male threaded section no longer than 10 mm (0.4 in).
Required tools
• A small slot screwdriver(s) with a blade width of 3 mm or less for connector X1, and 2 mm (1/10 in) or less for connectors X3 and X4.
• A drill, and M5 screws or bolts for mounting the MicroFlex e150.
• Wire stripper.
• For UL installations, use UL listed closed loop connectors that are of appropriate size for the wire gauge being used.
• Connectors are to be installed using only the crimp tool specified by the manufacturer of the connector.
Checking the delivery
Check that there are no signs of damage. Notify the shipper immediately if damaged components are found.
If MicroFlex e150 is to be stored for several weeks before use, be sure that it is stored in a location that conforms to the storage humidity and temperature specifications shown in Ambient conditions on page 150 .
Before attempting installation and operation, check the information on the type designation label of the drive to verify that the drive is of the correct type. See section
Type designation label
on page
25
.
Mechanical installation 29
Mounting and cooling
Ensure you have read and understood Requirements for the installation site on page
27 . Mount the MicroFlex e150 vertically on its rear side, the side opposite the front panel. M5 bolts or screws should be used to mount the MicroFlex e150. Detailed dimensions are shown in Dimension drawing (all models) on page 128 .
For effective cooling, the MicroFlex e150 must be mounted upright on a smooth vertical metal surface. The MicroFlex e150 is designed to operate in an ambient temperature of 0 °C to 45 °C (32 °F to 113 °F). Output current must be derated between 45 °C (113 °F) and the absolute maximum ambient temperature of 55 °C
(131 °F). Within the ambient temperature range:
• The 3 A model is designed to operate without any additional cooling methods.
• The 6 A and 9 A models require a forced air flow, passing vertically from the bottom to the top of the MicroFlex e150 case, to allow full rated current at 45 °C
(113 °F).
Temperature derating characteristics are shown in Temperature derating on page
132 .
Failure to meet cooling air flow requirements will result in reduced product lifetime and/or drive overtemperature trips. It is recommended to check periodically the operation of the cooling equipment. Optional fan tray FAN001-024, mounted exactly as shown in Fan tray on page 164 , ensures that correct cooling is provided and allows the MicroFlex e150 to be UL listed.
30 Mechanical installation
Effects of mounting surface and proximity
The proximity of the MicroFlex e150 to other components could affect cooling efficiency. If the
MicroFlex e150 is mounted beside another
MicroFlex e150 (or other obstruction), there should be a minimum space of 15 mm (0.6 in) to maintain effective cooling.
If the MicroFlex e150 is mounted above or below another MicroFlex e150 (or other obstruction), there should be a minimum space of 90 mm
(3.5 in) to maintain effective cooling. Remember that a MicroFlex e150 will be receiving air that has been already heated if it is mounted above another MicroFlex e150 or heat source. Multiple
MicroFlex e150 units mounted above each other should be aligned, not offset, to promote air flow across the heat sinks.
It is recommended to allow approximately 60 mm
(2.4 in) at the front to accommodate wiring and connectors.
Metal backplane
90 mm
Fan Fan
Mechanical installation 31
Installing
1. Mark the hole locations. See
Dimension drawing (all models) on page 128 for complete dimensions.
63.5 mm (2.5 in)
167.7 mm (6.6 in)
2. Position the drive and check the hole positions are correct.
3. Drill the holes, mount the drive and tighten all four screws until the drive is secure.
32 Mechanical installation
Planning the electrical installation 33
Planning the electrical installation
5
What this chapter contains
The chapter contains the instructions that you must follow when checking the compatibility of the motor and drive, selecting cables, protective devices, and cable routing.
Note: The installation must always be completed according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations. Furthermore, if the recommendations given by ABB are not followed, the drive might experience problems that are not covered by the warranty.
The installation methods described in this chapter will improve the reliability of the system, reduce troubleshooting time, and optimize the EMC (electromagnetic compatibility) behavior of the control system.
Checking the compatibility of the motor and drive
Check that the 3-phase AC motor and the drive are compatible according to the
Motor output power (X1) on page 139 .
Selecting the supply disconnecting device
Install a hand-operated supply disconnecting device (disconnecting means) between the AC power source and the drive. The disconnecting device must be of a type that can be locked to the open position for installation and maintenance work.
34 Planning the electrical installation
European Union
To meet the European Union Machinery Directive, according to standard
EN 60204-1, Safety of Machinery, the disconnecting device must be one of the following types:
• a switch-disconnector of utilization category AC-23B (EN 60947-3)
• a disconnector having an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector (EN 60947-3)
• a circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions
The disconnecting device must conform to the applicable safety regulations.
Emergency stop devices
For safety reasons, install emergency stop devices at each operator control station and at other operating stations where emergency stop might be needed.
Implementing the STO function
See Appendix: Safe Torque Off (STO) on page 173 .
Planning the electrical installation 35
Thermal overload and short circuit protection
Thermal overload protection
The drive protects itself and the input and motor cables against thermal overload when the cables are dimensioned according to the nominal current of the drive. No additional thermal protection devices are needed.
WARNING!
If the drive is connected to multiple motors, a separate thermal overload switch or a circuit breaker must be used for protecting each cable and motor. These devices might require a separate fuse to cut off the short circuit current.
Protection against short circuit in motor cable
The drive protects the motor and motor cable in a short circuit situation when the motor cable is dimensioned according to the nominal current of the drive. No additional protection devices are needed. The drive trips on a motor phase short circuit and will not restart unless AC power is removed. Remove all power from the drive, correct the short circuit and restart the drive. The motor outputs are fully short circuit proof according to EN 61800-5-1.
Protecting against short circuit in the supply cable or drive
Protect the supply cable with fuses or circuit breakers. Size the fuses according to instructions given in Technical data on page 136 . The fuses protect the input cable in short circuit situations, restrict drive damage and prevent damage to adjoining equipment in case of a short circuit inside the drive.
Fuses
Recommended fuses are listed in
Recommended fuses, circuit breakers and wire sizes
on page
136
. Alternative fuses must be compatible fast acting types.
Circuit breakers
It is highly recommended that fuses are used instead of circuit breakers. Circuit breakers should only be used when absolutely necessary. UL compliance can only be achieved when using the recommended fuses.The use of circuit breakers does not guarantee UL compliance and provides protection for the wiring only, not the
MicroFlex e150. Your local ABB representative can help you in selecting the breaker type when the supply network characteristics are known.
Motor thermal protection
According to regulations, the motor must be protected against thermal overload and the current must be switched off when overload is detected. The drive can be configured to include a motor temperature input that protects the motor and switches off the current when necessary. For more information about motor thermal protection, see
Thermal switch connection
on page
57
, and the Mint keyword
MOTORTEMPERATUREINPUT
in the Mint WorkBench help file.
Brake output short circuit protection
The brake resistor output is fully short circuit proof according to EN 61800-5-1.
36 Planning the electrical installation
Selecting the power cables
General rules
Dimension the input power and motor cables according to local regulations.
• The input power and the motor cables must be able to carry the corresponding load currents. See Electrical power network specification on page 129 and Motor output power (X1) on page 139 for the rated currents.
• The cable must be rated for at least 70 °C (US: 75 °C / 167 °F) maximum permissible temperature of the conductor in continuous use.
• The conductivity of the PE conductor must be equal to that of the phase conductor (same cross-sectional area).
• 600 V AC cable is accepted for up to 500 V AC.
• Refer to
Technical data
on page
154
for the EMC requirements.
A symmetrical shielded motor cable must be used to meet the EMC requirements of the CE and C-Tick marks; see the following diagrams.
A four-conductor system is allowed for input cabling, but a shielded symmetrical cable is recommended. Compared to a four-conductor system, the use of a symmetrical shielded cable reduces electromagnetic emission of the whole drive system as well as motor bearing currents and wear. The motor cable and its PE pigtail (twisted shield) should be kept as short as possible in order to reduce electromagnetic emission.
Planning the electrical installation 37
Alternative power cable types
Motor cables (also recommended for supply cabling):
Symmetrical shielded cable: three phase conductors and a concentric or otherwise constructed PE conductor, and a shield.
Check with local / state / country electrical codes for allowance.
Note: A separate PE conductor is required if the conductivity of the cable shield is not sufficient for the purpose.
PE conductor
Shield Shield
PE
PE
Allowed for AC power cabling
A four-conductor system: three phase conductors and a protective conductor.
Shield
PE
PE
Motor cable shield
To function as a protective conductor, the shield must have the same cross-sectional area as the phase conductors when they are made of the same metal. To effectively suppress radiated and conducted radio-frequency emissions, the shield conductivity must be at least 1/10 of the phase conductor conductivity. The requirements are easily met with a copper or aluminium shield. The minimum requirement of the motor cable shield of the drive is shown below. It consists of a concentric layer of copper wires. The better and tighter the shield, the lower the emission level and bearing currents.
4
5
1 3 2
1 Insulation jacket
2 Copper wire screen
3 Helix of copper tape or copper wire
4 Inner insulation
5 Cable core
38 Planning the electrical installation
Protecting the contacts of relay outputs and attenuating inductive loads
Inductive loads (relays, contactors, motors) cause voltage transients when switched off.
Equip inductive loads with noise attenuating circuits (varistors, RC filters [AC] or diodes [DC]) in order to minimize the EMC emission at switch-off. If not suppressed, the disturbances might connect capacitively or inductively to other conductors in the control cable and form a risk of malfunction in other parts of the system.
Install the protective component as close to the inductive load as possible. Do not install protective components at the I/O terminal block.
1 2
230 V AC
3
230 V AC
4
24 V DC
0 V DC
4
0 V DC
24 V DC
1) Relay outputs; 2) Varistor; 3) RC filter; 4) diode
Planning the electrical installation 39
Selecting the control cables
It is recommended that all control cables are shielded.
Double-shielded twisted pair cable is recommended for analog signals. For pulse encoder cabling, follow the instructions given by the encoder manufacturer. Use one individually-shielded pair for each signal. Do not use a common return for different analog signals.
Double-shielded cable is best for low-voltage digital signals but single-shielded twisted multi-pair cable (Figure b) may also be used. a b
Run the analog signal and digital signals in separate cables.
Relay-controlled signals, providing their voltage does not exceed 48 V, may be run in the same cables as digital input signals. It is recommended that the relay-controlled signals are run as twisted pairs.
Never mix 24 V DC and 115/230 V AC signals in the same cable.
Relay cable
The cable type with braided metallic screen (for example, ÖLFLEX by LAPPKABEL) has been tested and approved by ABB.
Connection of a motor temperature sensor to the drive I/O
See
Thermal switch connection
on page
57
.
Routing the cables
Route the motor cable away from other cable routes. Motor cables of several drives may be run in parallel installed next to each other. It is recommended that the motor cable, input power cable and control cables are installed on separate trays. Avoid long parallel runs of motor cables with other cables to decrease electromagnetic interference caused by the rapid changes in the drive output voltage.
Where control cables must cross power cables make sure that they are arranged at an angle as near to 90 degrees as possible.
The cable trays must have good electrical bonding to each other and to the grounding electrodes. Aluminium tray systems can be used to improve local equalizing of potential.
40 Planning the electrical installation
A diagram of the cable routing is shown below:
Power cable min. 300 mm
(12 in)
Motor cable
Drive min. 500 mm
(20 in)
Control cables
Separate control cable ducts
Route 24 V and 230 V cables in separate ducts unless the 24 V cable is insulated for
230 V or insulated with an insulation sleeving for 230 V.
24 V 230 V 24 V 230 V
Planning the electrical installation 41
Typical installation example
Installation cabinet ‘star point’
AC power from fuses or reactor
Mount AC filter and
MicroFlex e150 on the same metal panel.
CAUTION
DO NOT TOUCH!
Brake resistors can become extremely hot!
Locate away from vulnerable components and wiring.
AC power wires should be as short as possible, typically less than 0.3 m (1 ft).
Longer wires must be shielded as shown.
Wire colors can vary according to region.
Protective Earth
(PE)
Drive earth wire must be at least
10 mm 2 (7 AWG)
Connect AC power cable shield to metal panel, using conductive shield earth/ground clamps.
On painted panels, remove paint to expose bare metal.
42 Planning the electrical installation
Electrical installation: AC input, motor and brake 43
6
Electrical installation:
AC input, motor and brake
What this chapter contains
The chapter describes how to connect input power cables, motor and brake resistor.
WARNING!
The work described in this chapter may only be carried out by a qualified electrician. Follow the instructions in chapter
Safety
on page
11
.
Ignoring the safety instructions can cause injury or death.
Make sure that the drive is disconnected from the input power during installation. If the drive is already connected to the input power, wait for 5 minutes after disconnecting the input power.
See the requirements in Electrical power network specification on page 129 . Use a fixed connection to the AC power line.
44 Electrical installation: AC input, motor and brake
Checking the insulation of the assembly
Drive
Every drive has been tested for insulation between the main circuit and the chassis at the factory. If further high potential (‘hipot’) testing is performed, use only DC voltages as AC voltage hipot tests could damage the drive. It is recommended to seek advice from your ABB sales representative before performing hipot tests.
Input power cable
Check the insulation of the input power cable according to local regulations before connecting to the drive.
Motor and motor cable
Check the insulation of the motor and motor cable as follows:
1. Check that the motor cable is connected to the motor and disconnected from the drive output terminals U, V and W.
2. Measure the insulation resistance between each phase conductor and the
Protective Earth conductor using a measuring voltage of 500 V DC. The insulation resistance of the motor must exceed 100 Mohm (reference value at 25 °C or
77 °F). Please consult the manufacturer’s instructions. Moisture inside the motor casing reduces the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement.
Electrical installation: AC input, motor and brake 45
Connecting the power cables
Connection diagram: AC input
AC filter
Connect earth/ground to protective earth on top of drive AC
Supply
Line (L1)
Line (L2)
Line (L3)
Route L1, L2, L3 and earth/ground together in conduit or cable
Isolating switch
Incoming safety earth/ground (PE)
Circuit breaker or fuses
STAR POINT
To earth/ground outer shield, use 360° clamps connected to enclosure backplane.
MicroFlex e150 is designed to be powered from standard single or three-phase lines that are electrically symmetrical with respect to earth/ground. The power supply module within the MicroFlex e150 provides rectification, smoothing and current surge protection. Fuses or circuit breakers are required in the input lines for cable protection.
For three phase supplies, connect the supply to L1, L2 and L3 as shown above. For single phase supplies, connect the supply and neutral to any two line inputs, for example L1 and L2.
For CE compliance, an AC filter must be connected between the AC power supply and the MicroFlex e150. If local codes do not specify different regulations, use at least the same gauge wire for earth/ground as used for L1, L2 and L3.
The X1 mating connector is a Phoenix COMBICON MSTB 2,5HC/11-ST-5,08.
Tightening torque is 0.5-0.6 N·m (4.4-5.3 lb-in). The threaded hole in the top or bottom of the case may be used as an additional functional earth/ground connection for signals on connector X3. The threaded holes may also be used to attach shield or strain relief clamps. The holes are threaded for M4 bolts no longer than 11 mm
(0.43 in).
Earthing / grounding
A permanent earth/ground bonding point is provided on the heat sink, which must be used as the protective earth. It is labeled with the protective earth symbol in the casting and does not form any other mechanical function.
Connector X1 contains earth terminals, but these must not be used as protective earth since the connector does not guarantee earth connection first, disconnection last. Earthing methods are shown in Typical installation example on page 41 .
46 Electrical installation: AC input, motor and brake
When using unearthed/ungrounded distribution systems, an isolation transformer with an earthed/grounded secondary is recommended. This provides three-phase AC power that is symmetrical with respect to earth/ground and can prevent equipment damage.
Protection class
User protection has been achieved using Protective Class I (EN 61800-5-1), which requires an earth connection to the unit whenever hazardous voltages are applied.
The equipment provides protection against electric shock by:
• Means of connection of protective earth to accessible live conductive parts.
• Basic insulation.
Earth leakage
Maximum earth leakage from the MicroFlex e150 is 3.4 mA per phase (230 V, 50 Hz supply). This value does not include the earth leakage from the AC power filter, which could be much larger (see EMC filters on page 166 ). If the MicroFlex e150 and filter are mounted in an enclosure, it is recommended the enclosure is earthed using a
10 mm
2
conductor.
Electrical installation: AC input, motor and brake 47
Input power conditioning
Certain power line conditions must be avoided; an AC line reactor, an isolation transformer or a step up/step down transformer might be required for some power conditions:
• If the feeder or branch circuit that provides power to the MicroFlex e150 has permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer must be connected between the power factor correction capacitors and the MicroFlex e150 to limit the maximum symmetrical short circuit current to 5000 A.
• If the feeder or branch circuit that provides power to the MicroFlex e150 has power factor correction capacitors that are switched on line and off line, the capacitors must not be switched while the drive is connected to the AC power line.
If the capacitors are switched on line while the drive is still connected to the AC power line, additional protection is required. A Transient Voltage Surge
Suppressor (TVSS) of the proper rating must be installed between the AC line reactor (or isolation transformer) and the AC input to the MicroFlex e150.
Supplying input power from a variac (variable transformer)
When AC power is supplied from a variac, the MicroFlex e150's pre-charge circuit might not operate correctly. To ensure that the pre-charge circuitry operates correctly, increase the variac voltage to the desired level and then power cycle the 24 V DC control circuit supply. This will restart the pre-charge circuit and allow it to operate correctly.
48 Electrical installation: AC input, motor and brake
Power supply filters
To comply with EC directive 2004/108/EC, an AC power filter of the appropriate type must be connected. This can be supplied by ABB and will ensure that the
MicroFlex e150 complies with the CE specifications for which it has been tested.
Ideally, one filter should be provided for each MicroFlex e150; filters should not be shared between drives or other equipment.
Harmonic suppression
When operating the 3 A MicroFlex e150 (part E152A03...) on a single-phase AC supply, a 13 mH, 4 A rms (10 A peak) line reactor is required to ensure compliance with EN 61000-3-2 class A limits, when the total equipment supply load is less than
1 kW.
Reversing the filter
When using filters FI0015A00 or FI0015A02, they must be reversed to ensure that the MicroFlex e150 complies with the CE specifications for which it has been tested.
The AC power supply should be connected to the filter terminals marked as the outputs, with the MicroFlex e150 connected to the filter terminals marked as the inputs.
WARNING!
This recommendation applies only to filters FI0015A00 and
FI0015A02. Alternative filters or protection devices must be connected as specified by the manufacturer.
See
Power supply filters
on page
138
.
Electrical installation: AC input, motor and brake 49
Power disconnect and protection devices
A power disconnect should be installed between the input power supply and the
MicroFlex e150 for a fail-safe method to disconnect power. The MicroFlex e150 will remain in a powered condition until all input power is removed from the drive and the internal bus voltage has depleted.
The MicroFlex e150 must have a suitable input power protection device installed, preferably a fuse. Recommended circuit breakers are thermal magnetic devices (1 or
3 phase as required) with characteristics suitable for heavy inductive loads (C-type trip characteristic). Circuit breaker or fuses are not supplied - see
Recommended fuses, circuit breakers and wire sizes
on page
136
. For CE compliance, see
Technical data
on page
153
.
From supply
Circuit breaker From supply
Fuse
L
N
L
N
L
N
L
N
Circuit breaker and fuse, single-phase
From supply
L1
L2
L3
Circuit breaker
L1
L2
L3
From supply
L1
L2
L3
Fuse
L1
L2
L3
Circuit breaker and fuse, three-phase
NOTE: Metal conduit or shielded cable should be used. Connect conduits so the use of a line reactor or RC device does not interrupt EMI/RFI shielding.
Using 2 phases of a 3-phase supply
Power can be derived by connecting two phases of an appropriate three-phase supply (L1 and L2 for example). When supplying AC power in this way, the voltage between the two phases must not exceed the rated input voltage of the
MicroFlex e150. A two pole breaker must be used to isolate both lines. Fuses must be fitted in both lines.
50 Electrical installation: AC input, motor and brake
Drive overload protection
The MicroFlex e150 will immediately trip and disable if there is an overload condition.
The parameters for managing drive overloads are configured automatically by the
Commissioning Wizard (page 100 ). If they need to be changed, use the Parameters tool in Mint WorkBench (page 112 ).
Electrical installation: AC input, motor and brake 51
24 V control circuit supply
A 24 V DC supply must be provided to power the controlling electronics. This is useful for safety reasons where AC power is removed from the power stage, but the controlling electronics must remain powered to retain position and I/O information.
A separate fused 24 V supply should be provided for the MicroFlex e150. If other devices are powered from the same 24 V supply, a filter (part FI0014A00) should be installed to isolate the MicroFlex e150 from the rest of the system. Alternatively, a ferrite sleeve can be attached to the supply cable near connector X2.
Customer supplied
24 V DC
+24 V
GND
Fuse *
24 V filter
(optional)
Ferrite sleeve**
X2
Use a twisted pair cable, with ferrite sleeve attached close to connector X2.
Incoming safety earth/ground (PE)
STAR
POINT
* Recommended fuse: Bussman S504 20 x 5 mm anti-surge 2 A.
** Recommended ferrite sleeve: Fair-Rite part 0431164281 or similar.
52 Electrical installation: AC input, motor and brake
Motor connections
MicroFlex e150 will operate with a large number of brushless servo motors. For information on selecting servo motors please contact your local ABB representative.
The motor must be capable of being powered by an inverter PWM output. The motor can be connected directly to the MicroFlex e150 or through a motor contactor (M-
Contactor). Motors should ideally have a minimum inductance of 1 mH per winding; for motors with lower inductance an output reactor can be fitted in series with the motor.
The motor outputs are fully short circuit proof according to EN 61800-5-1. The drive trips on a motor phase short circuit and will not restart unless AC power is removed.
See page
35
.
When using a motor in the Mint WorkBench catalog, the parameters for managing motor overloads are configured automatically by the
Commissioning Wizard
(page
100
). If they need to be changed, or you are using an alternative motor, use the
Parameters tool (page 112 ).
WARNING!
Hazardous voltages can exist on the motor output connections. Do not touch the motor output connections before you first ensure there is no high voltage present.
WARNING!
The motor cables U, V and W must be connected to their corresponding U, V or W terminal on the motor. Misconnection will result in uncontrolled motor movement.
WARNING! Do not connect supply power to the MicroFlex e150 UVW outputs.
The MicroFlex e150 might be damaged.
For CE compliance, the motor earth/ground should be connected to the drive earth/ground, and the motor power cable must be shielded; see
Motor power cable shielding
on page
53
. The connector or gland used at the motor must provide 360 degree shielding. The maximum recommended cable length is 30.5 m (100 ft). See
Recommended fuses, circuit breakers and wire sizes
on page
136
for recommended wire sizes.
Electrical installation: AC input, motor and brake 53
Motor Connect motor earth/ground to protective earth on top of drive.
Earth
U
V
W
Optional motor circuit contactors.
To earth/ground outer shield, use 360° clamp connected to backplane.
Unshielded lengths should be as short as possible.
Motor power cable shielding
It is essential that the motor cable shield is correctly bonded to a functional earth, typically the same earthed metal backplane on which the MicroFlex e150 is mounted.
The motor power output cable carries a high frequency high current waveform to the motor, so the cable’s shielding must be earthed to prevent the cable radiating electromagnetic contamination into the surrounding area. Such contamination can cause spurious errors in unrelated parts of the installation, such as low voltage communication cables. To provide a low impedance path to earth and effective shielding, the conductor must provide contact with a large proportion of the cable’s circumference. The following diagram shows two possible methods.
Exposing the cable shield
1. Make a single circular cut in the cable’s outer sheath, ensuring that the cable’s braided shield is not damaged.
2. Slide the section of outer sheath towards the end of the cable to expose an area of braided shield. Carefully remove the excess sheath at the end of the cable.
3. Attach the metal P-clip or clamp to the exposed area of braided shield.
4. Ensure that the P-clip (or Motor Cable Management Bracket, OPT-CM-001) is securely attached to an unpainted area of the metal backplane.
54 Electrical installation: AC input, motor and brake
1. Make a single circular cut in the cable’s outer sheath, ensuring that the cable’s braided shield is not damaged.
2. Slide the section of outer sheath towards the end of the cable to expose an area of braided shield.
Carefully remove the excess sheath at the end of the cable.
On painted panels, remove paint to expose bare metal.
from
MicroFlex e150
Optional Motor Cable Management Bracket
OPT-CM-001 (recommended) from
MicroFlex e150
Metal P-clip
Continuation of motor power cable shielding
When using a motor contactor, or extending the motor cable through a terminal box, ensure that the motor cable shielding is continued all the way to the motor.
M-Contactor Terminal box
Motor from
MicroFlex e150
Electrical installation: AC input, motor and brake 55
Motor circuit contactors
If required by local codes or for safety reasons, an M-Contactor (motor circuit contactor) can be installed to provide a physical disconnection of the motor windings from the MicroFlex e150 (see Motor connections on page 52 ). Opening the M-
Contactor ensures that the MicroFlex e150 cannot drive the motor, which might be necessary during equipment maintenance or similar operations.
If an M-Contactor is installed, the MicroFlex e150 must be disabled at least 20 ms before the M-Contactor is opened. If the M-Contactor is opened while the
MicroFlex e150 is supplying voltage and current to the motor, the MicroFlex e150 can be damaged. Incorrect installation or failure of the M-Contactor or its wiring can result in damage to the MicroFlex e150.
Ensure that shielding of the motor cable is continued on both sides of the M-
Contactor, as shown in the previous diagram.
Sinusoidal filter
A sinusoidal filter is used to provide a better quality waveform to the motor, reducing motor noise, temperature and mechanical stress. It will reduce or eliminate harmful dV/dt values (voltage rise over time) and voltage doubling effects which can damage motor insulation. This effect occurs most noticeably when using very long motor cables, for example 30.5 m (100 ft) or more. ABB servo motors intended to be used with drives are designed to withstand the effects of large dV/dt and overvoltage effects. However, if very long motor cables are unavoidable and are causing problems, then a sinusoidal filter can be beneficial.
Motor brake connection
A rotary motor might require a brake. The brake prevents the uncontrolled release of suspended or tensioned loads when power to the motor is removed or disconnected, e.g. by a motor circuit contactor. Contact your local supplier for details of appropriate brakes.
You can wire a motor's brake, via relays, to digital outputs on connector X3 or OPT1
(see
Connections - front panel
on page
23
, and
Connections - top panel
on page
24
).
This provides a way for the MicroFlex e150 to control the motor's brake. A typical circuit is shown in the following diagram:
56 Electrical installation: AC input, motor and brake
X3
DOUT1+ 13
User supply
V+
DOUT13
User supply
GND
The relay has normally open contacts and is shown deactivated
(contacts open, brake engaged).
from motor brake connections
Relay
+24 V 0 V
Separate customer supplied
24 V DC supply
The inner shield surrounding the brake wires should be earthed/grounded at one point only.
This circuit uses DOUT1 as a motor brake output. The output is configured using Mint keyword
MOTORBRAKEOUTPUT
; see the Mint help file for details. With this configuration, the following sequences can be used to control the brake.
To engage the brake:
• The motor is brought to rest under normal control;
• The relay is deactivated, causing the brake to engage;
• The drive is disabled, removing power from the motor.
To disengage the brake:
• The drive is enabled;
• The drive applies power to the motor to hold position under normal control;
• The relay is activated, causing the brake to be disengaged.
It is sometimes necessary to include a small delay after the relay has been activated, before starting motion. This delay allows time for the relay contacts to engage and the brake to release. See the
MOTORBRAKEDELAY
keyword.
WARNING! The 24 V DC power supply used to power the brake must be a separate supply as shown in the diagram. Do not use the supply that is powering the MicroFlex e150 digital outputs. The brake wires often carry noise that could cause erratic drive operation or damage. The brake contacts must never be wired directly to the digital outputs. The relay should be fitted with a protective flyback diode, as shown. The separate 24 V DC supply used for the motor brake can also be used to power the relay in the thermal switch circuit.
Electrical installation: AC input, motor and brake 57
Thermal switch connection
You can use the motor's thermal switch contacts (normally closed), to control a relay connected to a digital input on connector X3 or OPT1 (see Connections - front panel on page 23 , and Connections - top panel on page 24 ). This allows the
MicroFlex e150 to respond to motor over-temperature conditions. Using the Mint
WorkBench Digital I/O tool, the input can be configured to be the motor temperature input. The Mint keyword
MOTORTEMPERATUREINPUT
can also be used to configure a digital input for this purpose. A typical circuit, using DIN0 as the input, is shown in the following diagram.
The relay has normally open contacts and is shown deactivated
(contacts open, motor overheated).
X1
DIN0+
17 motor thermal switch
DIN0-
7
+24 V 0 V
Separate customer supplied
24 V DC supply
+24 V 0 V
Customer supplied
24 V DC supply
WARNING! The 24 V DC power supply connected to the thermal switch must be a separate supply as shown in the diagram. The thermal switch wires often carry noise that could cause erratic drive operation or damage. The thermal switch contacts must never be wired directly to a digital input. The separate 24 V DC supply used for the thermal switch can also be used for the motor brake circuit.
58 Electrical installation: AC input, motor and brake
Brake resistor (regeneration resistor)
An optional external brake resistor might be required to dissipate excess power from the internal DC-bus during motor deceleration. The brake resistor must have a resistance of at least 39 Ω , an inductance of less than 100 μ H, and a minimum power rating of 44 W. Care should be taken to select the correct resistor for the application; see the Brake (X1) section starting on page 140 . Suitable brake resistors are listed in
Resistor choice on page 143 . The brake resistor output is conditionally short circuit proof.
WARNING!
Electrical shock hazard. DC-bus voltages can be present at these terminals. Use a suitable heat sink (with fan if necessary) to cool the brake resistor. The brake resistor and heat sink (if present) can reach temperatures in excess of 80 °C (176 °F).
Brake resistor
STAR
POINT
Earth/ground outer shield, using 360° conductive clamp connected to enclosure backplane
Electrical installation: input / output 59
Electrical installation: input / output
7
What this chapter contains
The chapter describes how to connect low voltage control signals.
The following conventions will be used to refer to the inputs and outputs:
I/O . . . . . . . . . . . Input / Output
AIN . . . . . . . . . . Analog Input
AOUT . . . . . . . . Analog Output
DIN . . . . . . . . . . Digital Input
DOUT . . . . . . . . Digital Output
STO. . . . . . . . . . Safe Torque Off
WARNING!
The work described in this chapter may only be carried out by a qualified electrician. Follow the instructions in chapter Safety on page 11 .
Ignoring the safety instructions can cause injury or death.
Make sure that the drive is disconnected from the input power during installation. If the drive is already connected to the input power, wait for 5 minutes after disconnecting the input power.
60 Electrical installation: input / output
Analog I/O
The MicroFlex e150 provides:
• Two 12-bit resolution ±10 V analog inputs.
• One 12-bit resolution ±10 V analog output.
An analog input receives the torque / velocity reference signal when operating as an analog drive (see
CONTROLREFSOURCE
in the Mint help file), or it can be used as a general purpose ADC input.
Analog inputs AIN0, AIN1
Location: X4, pins 3 & 7 (AIN0), 2 & 6 (AIN1), 5 (AGND).
The analog inputs pass through a differential buffer and second order low-pass filter with a cut-off frequency of approximately 1.2 kHz.
In Mint, analog inputs can be read using the
ADC
keyword. See the Mint help file for full details of
ADC
,
ADCMODE
and other related
ADC
... keywords.
Input circuit:
X4
AIN07
AIN0+ 3
MicroFlex e150
+15V
-
+
-
+
Mint
ADC.0
-15V
AGND 5
For differential inputs connect input lines to AIN+ and AIN-. Leave AGND unconnected:
AIN0+
AIN0-
X4
3
7
5
AIN0
(
ADC.0
)
AIN0+
GND
X4
3
7
5
AIN0
(
ADC.0
)
Differential connection Single ended connection
Electrical installation: input / output 61
Typical input circuit to provide 0-10 V (approx.) input from a 24 V source
+24VDC
Nȍ:
0V
Nȍ: potentiometer
7
5
X4
3
AIN0
(
ADC.0
)
Analog output AOUT0
Location: X4, pin 1 (AOUT0), 5 (AGND)
The analog output can be used to drive loads of 4 k Ω or greater. Shielded twisted pair cable should be used. The shield connection should be made at one end only.
In Mint, the analog output can be controlled using the
DAC
keyword. See the Mint help file for full details of
DAC
and other related
DAC
... keywords.
Output circuit:
MicroFlex e 150
+15V
Demand
±100% AD5530BRUZ
X4
1
AOUT0
-15V
5
AGND
62 Electrical installation: input / output
Digital I/O
The MicroFlex e150 provides:
• 10 general purpose digital inputs.
• 2 dedicated Safe Torque Off (STO) inputs.
• 7 general purpose digital outputs.
Connector Digital input / output
X3 STO1
X3
STO2
DIN0
DIN1
DIN2
OPT 1
(top panel)
X3
DIN3
DIN4
DIN5
DIN6
DIN7
DIN8
DIN9
Status out
(DOUT0)
X3
OPT 1
(top panel)
DOUT1
DOUT2
DOUT3
DOUT4
DOUT5
DOUT6
Common connection
Purpose
SREF
To enable the drive and provide the Safe
Torque Off (STO) function (page 64 ).
(Separate) General purpose input (page 65 ).
(Separate)
General purpose 'fast' inputs (page 66 ).
(Separate)
(Separate) General purpose input (page 65 ).
CREF1
CREF0
(Separate)
(Separate)
(Separate)
USRV+
General purpose inputs (page 68 ).
General purpose inputs (page 68 ).
Status output (page 69 ).
Can also be used as a general purpose output
General purpose outputs (page 70 ).
General purpose outputs (page 71 ).
Electrical installation: input / output 63
Using a digital input as a drive enable input (optional)
A general purpose digital input can be configured as a ‘drive enable input’. This input must be activated to allow the drive to operate. This provides an additional method for stopping the drive using a hardware switch or external PLC/controller (e.g.
NextMove e100), although it does not provide any of the formal safety features of the
Safe Torque Off inputs (page 64 ). The optional drive enable input is configured using the Digital I/O tool in Mint WorkBench.
Using a digital input as a home switch input (optional)
If homing is being handled locally by the MicroFlex e150, the axis home switch (if present) must be wired directly to the home input on the MicroFlex e150, otherwise it will not be able to complete its internal homing routines. The home switch input is configured using the Digital I/O tool in Mint WorkBench, or by using the Mint
HOMEINPUT
keyword. Other
HOME
… keywords define the homing sequence.
If homing is being handled by an EtherCAT master over Ethernet, and the master is profiling the motion, there are two options. The choice depends on the accuracy required for the homing and the EtherCAT cycle-time:
• The axis home switch can be wired to an input on the MicroFlex e150, and then mapped back to the master over EtherCAT;
• The home switch can be wired directly to the EtherCAT master.
64 Electrical installation: input / output
Digital inputs - Safe Torque Off (STO)
Location: X3, pin 18 (STO1), 8 (SREF), 19 (STO2), 9 (SREF)
The two safe torque off (STO) inputs are identical. Each input directly enables part of the motor output control circuit. Both inputs must be powered to allow the
MicroFlex e150 to supply power to the motor. If an additional hardware drive enable input is used to control the MicroFlex e150, it must not be wired with the STO input circuit. The state of the STO inputs can be viewed using the Mint WorkBench Spy window's Axis tab. See the Mint help file for details.
See
Appendix: Safe Torque Off (STO)
on page
173
.
Safe Torque Off digital input - STO1:
MicroFlex e 150
Vcc
X3
STO1 18
33R 6k8 STO circuit
SREF
Shield
8
20
33R
TLP281
DGND
Safe Torque Off digital input - STO2:
MicroFlex e 150
X3
STO2 19
33R 6k8
SREF
Shield
9
20
33R
TLP281
DGND
Vcc
STO circuit
Electrical installation: input / output 65
Digital inputs - general purpose DIN0, DIN3
Location: X3, pins 17 & 7 (DIN0), 15 & 5 (DIN3)
These general purpose digital inputs are buffered by a TLP280 opto-isolator, allowing the input signals to be connected with either polarity. The inputs do not share a common reference. When the MicroFlex e150 is connected to Mint WorkBench, the digital inputs can be configured using the Digital I/O tool. Alternatively, Mint keywords including
DRIVEENABLEINPUT
,
RESETINPUT
,
ERRORINPUT
and
STOPINPUT
can be used. The state of the digital inputs can be viewed using the Mint WorkBench Spy window's Axis tab. See the Mint help file for details.
General purpose digital input - DIN0 shown:
X3
DIN0+ 17
MicroFlex e 150
33R
33R
DIN07
3k3
Vcc
Mint
TLP280
DGND
Digital input - typical connections from an ABB NextMove e100:
NextMove e100 / controller
Mint
DRIVEENABLEOUTPUT
10k
UDN2982
User supply
24 V
X11
9
USR V+
1
DOUT0
X3
10
USR GND
User supply
GND
DIN0+
17
DIN0-
7
MicroFlex e 150
TLP280
66 Electrical installation: input / output
Digital inputs - general purpose DIN1, DIN2
Location: X3, pins 16 & 6 (DIN1), 14 & 4 (DIN2)
These general purpose fast digital inputs are buffered by a TLP115 opto-isolator, allowing the input signals to be connected with either polarity. The inputs do not share a common reference. When the MicroFlex e150 is connected to Mint WorkBench, the digital inputs can be configured using the Digital I/O tool. Alternatively, Mint keywords including
DRIVEENABLEINPUT
,
RESETINPUT
,
ERRORINPUT
and
STOPINPUT
can be used. The state of the digital inputs can be viewed using the Mint WorkBench Spy window's Axis tab. See the Mint help file for details.
General purpose fast digital input - DIN1 shown:
X3
MicroFlex e 150
33R
DIN1+ 16
3k3
Vcc
Mint
DIN16
33R
TLP115
DGND
Digital input - typical connections from an ABB NextMove e100:
NextMove e100 / controller
UDN2982
Mint
OUTX(0)
10k
X11
9
USR V+
1
DOUT0
User supply
24 V
10
USR
GND
User supply
GND
X3
DIN1+
16
DIN1-
6
Shield
20
MicroFlex e 150
TLP115
Electrical installation: input / output 67
Special functions on inputs DIN1, DIN2
DIN1 and DIN2 can be configured to perform special functions.
Step (pulse) and direction inputs
DIN1 and DIN2 can be configured using the statement
ENCODERMODE(1)=4
to become step and direction inputs:
• DIN1 is used as the step input. The step frequency controls the speed of the motor.
• DIN2 is used as the direction input. The state of the direction input controls the direction of motion. An active input will result in forward motion. An inactive input will result in motion in the opposite direction.
Encoder input
DIN1 and DIN2 can be configured using the statement
ENCODERMODE(1)=0
to form an additional encoder input. The two channels are read as a quadrature (CHA, CHB) encoder input.
In Mint, the encoder input formed by digital inputs DIN1 and DIN2 is encoder 1. The primary motor feedback encoder source on connector X8 is encoder 0, and the extra incremental encoder on connector X8 is encoder 2; see pages 80 and 86 .
Fast latch input
DIN1 or DIN2 can be configured using the
LATCHTRIGGERCHANNEL
keyword to become a fast latch input. This allows the position of the axis to be captured in realtime and read using the Mint keyword
LATCHVALUE
. The input can be configured using the
LATCHTRIGGEREDGE
keyword to be triggered either on a rising or falling edge. Further control of position capture is provided by various other keywords beginning with
LATCH
.... See the Mint help file for details.
The maximum latency to read the fast position depends on the feedback device. For an incremental encoder, the latency is approximately 150 - 300 ns. For other feedback devices latency can be up to 62.5
μ s, resulting from the 16 kHz sampling frequency used for these types of feedback device. The fast interrupt will be latched on a pulse width of about 30 μ s, although a width of 100 μ s is recommended to ensure capture. The captured value is latched in software to prevent subsequent inputs causing the captured value to be overwritten.
NOTE: The fast inputs are particularly sensitive to noise, so inputs must use shielded twisted pair cable. Do not connect mechanical switches, relay contacts or other sources liable to signal ‘bounce’ directly to the fast inputs. This could cause unwanted multiple triggering.
68 Electrical installation: input / output
Digital inputs - general purpose DIN4 - DIN9
Location: OPT1, pin 3 (CREF0), pin 4 (DIN7), 5 (DIN6), 6 (DIN5), 7 (DIN4), 11 (DIN9),
12 (DIN8), 13 (CREF1)
These general purpose digital inputs are buffered by a TLP280 opto-isolator, allowing the input signals to be connected with either polarity. Inputs DIN4 and DIN5 share a common reference, CREF1. Inputs DIN6 - DIN9 share a common reference, CREF0.
When the MicroFlex e150 is connected to Mint WorkBench, the digital inputs can be configured using the Digital I/O tool. Alternatively, Mint keywords including
DRIVEENABLEINPUT
,
RESETINPUT
,
ERRORINPUT
and
STOPINPUT
can be used.
The state of the digital inputs can be viewed using the Mint WorkBench Spy window's
Axis tab. See the Mint help file for details.
General purpose digital input - DIN4 shown:
OPT1
DIN4 7
MicroFlex e 150
33R
33R
CREF1 13
3k3
Vcc
TLP280
DGND
Digital input - typical connections from an ABB NextMove e100:
NextMove e100 / controller
Mint
OUTX(0)
10k
UDN2982
User supply
24 V X11
9
USR V+
1
DOUT0
OPT1
DIN4
7
10
USR GND
User supply
GND
CREF1
13
MicroFlex e 150
TLP280
Electrical installation: input / output 69
Status output (DOUT0)
Location: X3, pins 1 (Status-), 11 (Status+)
The optically isolated status output is designed to source current from the user supply. The TLP127 has a maximum power dissipation of 200 mW at 25 °C. The output includes a self-resetting fuse that operates at approximately 200 mA. The fuse can take up to 20 seconds to reset after the load has been removed. If the output is used to directly drive a relay, a suitably rated diode must be fitted across the relay coil, observing the correct polarity. This is to protect the output from the back-EMF generated by the relay coil when it is de-energized.
Status output circuit:
MicroFlex e 150
User supply
V+
X3
Fuse
200 mA
11
Status+
[Error]
TLP127
Load
(relay with diode shown)
1
Status-
User supply
GND
The status output becomes active in the event of an error, or when the STO function is activated. When the MicroFlex e150 is connected to Mint WorkBench, the active level of the output can be configured using the Digital I/O tool. Alternatively, the Mint keyword
OUTPUTACTIVELEVEL
can be used. The output’s state is displayed in the
Spy window. See the Mint help file for details.
General purpose output DOUT0
The status function must be disabled before the output can be used for other purposes. To disable the status function, the command
GLOBALERROROUTPUT=-1 must be issued from a Mint WorkBench Command window, or included in a Mint program. The command
GLOBALERROROUTPUT=0
enables the status function. See the Mint help file for details.
70 Electrical installation: input / output
Status output - typical connections to an ABB NextMove e100:
MicroFlex e 150
X3
User supply
24 V X9
NextMove e100 / controller
11
Status+
1
StatusDIN4
8
TLP127
CREF1
9
TLP280
User supply
GND
Digital outputs DOUT1, DOUT2
Location: X3, pins 13 & 3 (DOUT1), 12 & 2 (DOUT2)
The optically isolated general purpose outputs are designed to source current from an individual user supply connection. The TLP127 has a maximum power dissipation of 200 mW at 25 °C. Each output includes a self-resetting fuse that operates at approximately 200 mA. The fuse can take up to 20 seconds to reset after the load has been removed. If the output is used to directly drive a relay, a suitably rated diode must be fitted across the relay coil, observing the correct polarity. This is to protect the output from the back-EMF generated by the relay coil when it is de-energized.
Digital output circuit - DOUT1 shown:
MicroFlex e 150
User supply
V+
X3
Fuse
200 mA
13
DOUT1+
Mint
OUTX(1)
TLP127
Load
(relay with diode shown)
3
DOUT1-
User supply
GND
When the MicroFlex e150 is connected to Mint WorkBench, the active level of the outputs can be configured using the Digital I/O tool. Alternatively, the Mint keyword
OUTPUTACTIVELEVEL
can be used. The state of the outputs is displayed in the Spy window. See the Mint help file for details.
Electrical installation: input / output 71
DOUT1 - typical connections to an ABB NextMove e100:
MicroFlex e 150
TLP127
X3
13
DOUT1+
3
DOUT1-
User supply
24 V X9
DIN4
8
NextMove e100 / controller
CREF1
9
TLP280
User supply
GND
Digital outputs DOUT3 - DOUT6
Location: OPT1, pin 2 (DOUT3), 1 (DOUT4), 9 (DOUT5), 8 (DOUT6), 10 (USRV+)
The optically isolated general purpose outputs are designed to source current from a common user supply (USRV+). The TLP127 has a maximum power dissipation of
200 mW at 25 °C. Each output includes a self-resetting fuse that operates at approximately 200 mA. The fuse can take up to 20 seconds to reset after the load has been removed. If the output is used to directly drive a relay, a suitably rated diode must be fitted across the relay coil, observing the correct polarity. This is to protect the output from the back-EMF generated by the relay coil when it is de-energized.
Digital output circuit - DOUT3 shown:
MicroFlex e 150
User supply
V+
OPT1
Fuse
200 mA
10
USRV+
Mint
OUTX(3)
TLP127
Load
(relay with diode shown)
2
DOUT3
User supply
GND
72 Electrical installation: input / output
When the MicroFlex e150 is connected to Mint WorkBench, the active level of the outputs can be configured using the Digital I/O tool. Alternatively, the Mint keyword
OUTPUTACTIVELEVEL
can be used. The state of the outputs is displayed in the Spy window. See the Mint help file for details.
DOUT3 - typical connections to an ABB NextMove e100:
MicroFlex e 150
User supply
24 V X9
NextMove e100 / controller
OPT1
10
USRV+
2
DOUT3
TLP127
DIN4
8
CREF1
9
TLP280
User supply
GND
ABB AC500-eCo PLC
Electrical installation: input / output 73
USB interface
Location: U1
The USB connector is used to connect the MicroFlex e150 to a PC running Mint
WorkBench. The MicroFlex e150 is a self-powered, USB 2.0 (12 Mbps) compatible device. If it is connected to a slower USB 1.0 host PC or hub, communication speed will be limited to the USB 1.0 specification (1.5 Mbps). If it is connected to a faster
USB 2.0 ‘high-speed’ (480 Mbps) or USB 3.0 (5 Gbps) host PC or hub, communication speed will remain at the USB 2.0 specification of the MicroFlex e150.
Ideally, the MicroFlex e150 should be connected directly to a USB port on the host
PC. If it is connected to a hub shared by other USB devices, communication could be affected by the activity of the other devices. The maximum recommended cable length is 5 m (16.4 ft).
RS485 interface
Location: X6
The RS485 interface is used to connect third-party serial devices such as operator panels and PLCs. The interface can operate in 2-wire or 4-wire RS485 mode, which is selected using the Configuration tool in Mint WorkBench. The default mode is 2wire RS485, 57600 Baud, 8 data bits, 1 stop bit with no parity. MicroFlex e150 supports various protocols over the RS485 interface, such as Modbus RTU and HCP
(Host Comms Protocol), as well as simple ASCII character handling.
The 7 V supply on pin 4 is provided for future accessories, so care should be taken to ensure this supply will not damage connected devices. The RS485 port could be damaged if a USB plug is accidentally inserted while the drive is powered.
Connections to a 2-wire RS485 device - ABB AC500-eCo PLC shown:
MicroFlex e 150
COM1 X6
3
RxD/TxD-P
5
SGND
TXA(+)/RXA(+)
1
GND
3
8
RxD/TxD-N TXB(-)/RXB(-)
2
74 Electrical installation: input / output
Connections to a 4-wire RS485 device - ABB Keypad KPD202-501 shown:
ABB Keypad KPD202-501
Serial
7
TXA
8
RXA
5
GND
3
TXB
2
RXB
X6
RXA(+)
5
TXA(+)
RXB(-)
1
GND
3
6
TXB(-)
2
MicroFlex e 150
Note: The MicroFlex e150 and other ABB equipment use ‘big endian’ word order and byte order for Modbus protocols. If this is incompatible with other Modbus equipment, the word and byte order for the MicroFlex e150 can be changed in Mint WorkBench.
See the Mint WorkBench help file for details.
Electrical installation: input / output 75
Ethernet interface
The Ethernet interface supports EtherCAT® (CoE and EoE) and standard Ethernet.
Standard Ethernet
The standard Ethernet connection supports several protocols, including EtherNet/IP,
Modbus TCP, HTTP and ICMP. See the application notes at www.abbmotion.com
for details.
Ethernet port E2 is fixed in EtherCAT mode, so port E1 must be used for other
Ethernet connections. To set port E1 (OUT) to standard Ethernet mode, front panel
DIP switch 4 (page
79
) must be in the ON position.
Connecting Mint WorkBench using standard Ethernet
TCP/IP allows the MicroFlex e150 to support standard Ethernet communication with a host PC running Mint WorkBench. The connection uses a high level ‘Immediate
Command Mode’ (ICM) protocol to allow Mint commands, Mint programs and even firmware to be sent to the controller over the Ethernet network.
The host PC must be connected to the controller either directly or via a switch, as shown in the following diagram:
Connecting to drives using TCP/IP in standard Ethernet mode:
Host PC
MicroFlex e150 drives
External switch
E1 E1 E1 E1
Note: The MicroFlex e150 and other ABB equipment use ‘big endian’ word order and byte order for Modbus protocols. If this is incompatible with other Modbus equipment, the word and byte order for the MicroFlex e150 can be changed in Mint WorkBench.
See the Mint WorkBench help file for details.
76 Electrical installation: input / output
EtherCAT®
MicroFlex e150 supports the EtherCAT protocol. This protocol provides deterministic communication over a standard 100 Mbit/s (100Base-TX) Fast Ethernet (IEEE
802.3u) connection. This makes it suitable for the transmission of control and feedback signals between the MicroFlex e150 and other EtherCAT enabled controllers. EtherCAT's ‘CAN application layer over EtherCAT’ (CoE) capability allows
Mint to implement a drive protocol based on the CANopen DS402 Device Profile for
Drives and Motion Control.
MicroFlex e150 incorporates a built-in multi-port EtherCAT slave controller, providing two ports for connection to other equipment. This allows nodes to be connected in many configurations such as a ring, star, or tree, with EtherCAT's self-terminating technology automatically detecting breaks or an intended end of line.
If only one port is used for EtherCAT operation, it must be the E2 (IN) port.
Straight line topology EtherCAT network:
EtherCAT master
Machine 1:
MicroFlex e150 drives 1-9
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
1 2 3 4 5 6 7 8 9
Ring topology EtherCAT network:
EtherCAT master
Machine 1:
MicroFlex e150 drives 1-9
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
1 2 3 4 5 6 7 8 9
Electrical installation: input / output 77
Multi-branch EtherCAT network:
EtherCAT master
External switch
Machine 1:
MicroFlex e150 drives 1-9
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
1 2 3 4 5 6 7 8
Machine 2:
MicroFlex e150 drives 10-20
9
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
10 11 12 13 14 15 16 17 18 19 20
EtherCAT configuration
EtherCAT configuration is usually performed from the EtherCAT manager. To assist with configuration, the MicroFlex e150 provides an EtherCAT Slave Information (ESI) file. This .xml file describes the drive’s capabilities to the EtherCAT manager. The ESI file can be uploaded from the MicroFlex e150 using the Configuration tool in Mint
WorkBench.
78 Electrical installation: input / output
Ethernet connectors
Location: E1 & E2
Ethernet port E2 (IN) is fixed in EtherCAT mode. To set port E1 (OUT) to EtherCAT mode, front panel DIP switch 4 (page 79 ) must be in the off position. If only one port is used for EtherCAT operation, it must be the E2 (IN) port.
To connect the MicroFlex e150 to other EtherCAT devices use CAT5e Ethernet cables - either S/UTP (unshielded screened/foiled twisted pairs) or preferably S/FTP
(fully shielded screened/foiled twisted pairs). To ensure CE compliance, Ethernet cables longer than 3 m should be S/FTP cables bonded to the metal backplane at both ends using conductive clamps. Cables can be up to 100 m (328 ft) long. Two varieties of CAT5e cable are available; ‘straight’ or ‘crossed’. Straight cables have the
TX pins of the connector at one end of the cable wired to the TX pins of the RJ45 connector at the other end of the cable. Crossover cables have the TX pins of the connector at one end of the cable wired to the RX pins of the RJ45 connector at the other end of the cable.
Recommended cables are listed in Ethernet cables on page 172 . Crossover or straight cables can be used. Many Ethernet devices, including hubs and ABB e100 / e150 products, incorporate Auto-MDIX switching technology which automatically compensates for the wiring of straight cables.
The MicroFlex e150 Ethernet interface is galvanically isolated from the rest of the
MicroFlex e150 circuitry by magnetic isolation modules incorporated in each of the
Ethernet connectors. This provides protection up to 1.5 kV. The connector/cable screen is connected directly to the chassis earth of the MicroFlex e150.
The EtherCAT interface supports the 100Base-TX (100 Mbit/s) speed.
Electrical installation: input / output 79
DIP switches
Location: SW1
The MicroFlex e150 has four DIP switches which allow special settings to be selected on power up. Changing the switch positions after power up has no effect.
DIP switch settings:
Switch
4
3
2
1
Description
< OFF
E1 (OUT) port: EtherCAT mode
Normal operation
X6 port: 2-wire TX/RX (or 4-wire TX): disconnect 120 Ω termination resistor
X6 port: 4-wire RX: disconnect 120 Ω termination resistor
ON >
E1 (OUT) port: Standard Ethernet mode
Firmware recovery mode
X6 port: 2-wire TX/RX (or 4-wire TX): connect 120 Ω termination resistor
X6 port: 4-wire RX: connect 120 Ω termination resistor
80 Electrical installation: input / output
Motor feedback
Location: X8
MicroFlex e150 supports incremental encoder, encoder with BiSS (Bi-directional
Synchronous Serial Interface) or SSI (Synchronous Serial Interface), EnDat or
Smart Abs absolute encoder, or SinCos encoder feedback, for use with linear and rotary motors. There are some important considerations when wiring the feedback device:
• The inputs are not isolated.
• The feedback device wiring must be separated from power wiring.
• Where feedback device wiring runs parallel to power cables, they must be separated by at least 76 mm (3 in)
• Feedback device wiring must cross power wires at right angles only.
• To prevent contact with other conductors or earths / grounds, unearthed / ungrounded ends of shields must often be insulated.
• Linear motors use two separate cables (encoder and Hall). The cores of these two cables will need to be wired to the appropriate pins of the 15-pin D-type mating connector.
Connection summary
1
9
10
15
5
6
3
4
1
2
CHA+
CHB+
CHZ+
Sense
Hall U-
Hall U+
9
10
7
8
Hall V-
Hall V+
CHA-
CHB-
11 CHZ-
12 +5 V out
13 DGND
14
15
Hall W-
Hall W+
Pin Increment.
encoder
BiSS, SSI or
EnDat 2.2
Data+
Clock+
(NC)
Sense
(NC)
(NC)
Smart Abs
Data+
(NC)
(NC)
Sense
(NC)
(NC)
(NC)
(NC)
Data-
Clock-
(NC)
(NC)
Data-
(NC)
(NC) (NC)
+5 V out +5 V out
DGND DGND
(NC)
(NC)
(NC)
(NC)
Extra incremental encoder
-
-
-
Sense
CHA-
CHA+
CHB-
CHB+
-
-
-
+5 V out
DGND
CHZ-
CHZ+
EnDat
2.1
SinCos
Data+
Clock+
(NC)
Sense
Sin-
Sin+
(NC)
(NC)
(NC)
Sense
Sin-
Sin+
Cos-
Cos+
Data-
Clock-
Cos-
Cos+
(NC)
(NC)
(NC) (NC)
+5 V out +5 V out
DGND DGND
(NC)
(NC)
(NC)
(NC)
Electrical installation: input / output 81
When using BiSS, SSI, EnDat 2.2 or Smart Abs, an extra incremental encoder can be simultaneously connected.
Twisted pairs must be used for each complementary signal pair e.g. CHA+ and CHAor Data+ and Data-.
The overall cable shield (screen) must be connected to the metallic shell of the Dtype connector. Connector X8 includes a ‘Sense' pin, which is used to detect the voltage drop on long cable runs. This allows the MicroFlex e150 to increase the encoder supply voltage on pin 12 to maintain a 5 V supply at the encoder (400 mA max).
Incremental encoder interface
See
Connection summary
on page
80
for pin configuration.
The incremental encoder connections (ABZ channels and Hall signals) are made using the 15-pin D-type female connector X8. The encoder inputs (CHA, CHB and
CHZ) accept differential signals only. The Hall inputs can be used as differential inputs (recommended for improved noise immunity) or single ended inputs. When used as single ended inputs, leave the Hall U-, Hall V- and Hall W- pins unconnected.
Encoder channel input circuit - channel A shown:
X8
MicroFlex e 150 to encoder signal loss detection
CHA+ 1
120R
MAX3096
Differential line receiver to CPU
CHA9
13 DGND
82 Electrical installation: input / output
Hall input circuit - U phase shown:
X8
MicroFlex e 150
Hall U+ 6
Hall U5
13
+5V
DGND
MAX3096
Differential line receiver to CPU
Encoders without Halls
Incremental encoders without Hall feedback connections can be connected to the
MicroFlex e150. However, if Hall connections are not present, it will be necessary for the MicroFlex e150 to perform an automatic phase search sequence each time it is powered. This will cause motor movement of up to 1 turn on rotary motors, or one pole-pitch on linear motors.
Encoder cable connections without Halls - rotary motors:
Motor
Encoder
Feedback
Twisted pairs
X8
1
9
2
10
3
11
CHA+
CHA-
CHB+
CHB-
CHZ+ (INDEX)
CHZ- (INDEX)
12
13
4
+5 V out
DGND
Sense
Connect overall shield to connector backshells
Electrical installation: input / output 83
Halls-only feedback devices
Feedback devices using only Hall sensors can be connected to the MicroFlex e150.
However, since there are no encoder connections, the MicroFlex e150 will not be able to perform smooth speed control or accurate positioning control.
Halls-only feedback cable connections - rotary motors:
Motor
Hall
Feedback
Twisted pairs
X8
4
12
13
6
5
15
14
8
7
Sense
+5 V out
DGND
Hall U+
Hall U-
Hall W+
Hall W-
Hall V+
Hall V-
Connect overall shield to connector backshells
BiSS interface
The BiSS (Bi-directional Serial Synchronous interface) is an open-source interface that can be used with many types of absolute encoder. The BiSS interface connections are made using the 15-pin D-type female connector X8.
BiSS interface cable connections:
Absolute
Encoder
Motor
Twisted pairs
Connect overall shield to connector backshells
X8
1
9
2
10
12
13
4
Data+
Data-
Clock+
Clock-
+5V out
DGND
Sense
Chassis
Connect internal shields to pin 13.
84 Electrical installation: input / output
SSI interface
The SSI (Synchronous Serial Interface) encoder interface is specifically designed for use with Baldor SSI motors, which incorporate a custom Baumer SSI encoder.
Contact ABB technical support to confirm compatibility of other SSI devices. The SSI encoder connections are made using the 15-pin D-type female connector X8.
SSI interface cable connections:
Absolute
Encoder
Motor
Twisted pairs
Connect overall shield to connector backshells
X8
10
12
13
4
1
9
2
Data+
Data-
Clock+
Clock-
+5V out
DGND
Sense
Chassis
Connect internal shields to pin 13.
EnDat interface
The absolute encoder interface supports both incremental and absolute (multi and single turn) feedback using EnDat technology. It is possible to read and write information to the encoder. The absolute encoder connections are made using the
15-pin D-type female connector X8. Version 2.2 EnDat encoders do not use the Sin and Cos channels.
EnDat 2.1 interface cable connections:
Motor
Absolute
Encoder
Twisted pairs
X8
10
12
13
4
5
6
7
1
9
8
2
Data+
Data-
Sin-
Sin+
Cos-
Cos+
Clock+
Clock-
+5V out
DGND
Sense
Connect internal shields to pin 13.
Connect overall shield to connector backshells
Electrical installation: input / output 85
Smart Abs interface
The Smart Abs encoder connections are made using the 15-pin D-type female connector X8.
Smart Abs interface cable connections:
Absolute
Encoder
Motor
Twisted pairs
Connect overall shield to connector backshells
X8
1
9
12
13
4
Data+
Data-
+5V out
DGND
Sense
Connect internal shields to pin 13.
Chassis
SinCos interface
The SinCos connections (Sin and Cos incremental channels only) are made using the 15-pin D-type female connector X8.
SSI cable connections:
Motor
SinCos
Feedback
Twisted pairs
X8
5
6
7
8
12
13
4
Sin-
Sin+
Cos-
Cos+
+5V out
DGND
Sense
Connect internal shields to pin 13.
Chassis
Connect overall shield to connector backshells
86 Electrical installation: input / output
Extra incremental encoder interface
The extra incremental encoder becomes available when using a digital encoder type that does not require the Sin / Cos inputs (BiSS, SSI, EnDat 2.2, Smart Abs). In Mint, the main digital encoder source remains as encoder 0, and the extra incremental encoder is encoder 2. Note that encoder 1 is the input formed by digital inputs DIN1 and DIN2; see Special functions on inputs DIN1, DIN2 on page 67 .
The 5 V encoder inputs (CHA, CHB and CHZ) can be used as differential inputs
(recommended for improved noise immunity) or single ended inputs. When used as single ended inputs, leave the CHA-, CHB- and CHZ- pins unconnected.
Extra encoder input circuit - channel A shown:
MicroFlex e 150
+5V
CHA+ 6
MAX3096
Differential line receiver to CPU
CHA5
13 DGND
Installation checklist 87
8
Installation checklist
This chapter contains a list for checking the mechanical and electrical installation of the drive.
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go through the checklist together with another person.
WARNING!
Only qualified electricians are allowed to carry out the work described below. Follow the complete safety instructions of the drive. Ignoring the safety instructions can cause injury or death. Open the main disconnector of the drive and lock it to open position. Measure to ensure that the drive is not powered.
Check that …
The ambient operating conditions meet the specification in chapter Technical data .
There is an adequately sized protective earth (ground) conductor between the drive and the metal mounting surface.
There is an adequately sized protective earth (ground) conductor between the motor and the drive.
All protective earth (ground) conductors have been connected to the appropriate terminals and the terminals have been tightened (pull conductors to check).
The supply voltage matches the nominal input voltage of the drive. Check the type designation label.
The input power cable has been connected to appropriate terminals, the phase order is correct, and the terminals have been tightened (pull conductors to check).
88 Installation checklist
Check that …
Appropriate supply fuses and disconnector have been installed.
The motor cable has been connected to appropriate terminals, the phase order is correct, and the terminals have been tightened (pull conductors to check).
The brake resistor cable (if present) has been connected to appropriate terminals, and the terminals have been tightened (pull conductors to check).
The motor cable (and brake resistor cable, if present) has been routed away from other cables.
No power factor compensation capacitors have been connected to the motor cable.
All low voltage control cables have been correctly connected.
If a drive bypass connection will be used (for induction motors): The direct-on-line contactor of the motor and the drive output contactor are either mechanically or electrically interlocked (cannot be closed simultaneously).
There are no foreign objects or dust inside the drive.
Drive and motor connection box covers are in place.
Verify that all wiring conforms to applicable codes.
The motor and the driven equipment are ready for start-up.
Disconnect the load from the motor until instructed to apply a load. If this is not possible, disconnect the motor wires at connector X1.
Check no physical damage is present.
Check all instruments have been properly calibrated.
Safe Torque Off (STO) connections
The STO inputs are an intrinsic part of a safe drive installation.
The acceptance test of the safety function must be carried out by an authorized person with expertise and knowledge of the safety function. The test must be documented and signed by the authorized person.
The MicroFlex e150 will operate only when the STO inputs are powered.
See Appendix: Safe Torque Off (STO) on page 173 .
9
Start-up 89
Start-up
What this chapter contains
This chapter describes software installation and the start-up procedure of the drive.
Introduction
Before powering the MicroFlex e150 you will need to connect it to the PC using a
USB or Ethernet cable and install the Mint WorkBench software. This includes a number of applications and utilities to allow you to configure, tune and program the
MicroFlex e150. Mint WorkBench and other utilities can be found on the Mint Motion
Toolkit CD (OPT-SW-001), or downloaded from www.abbmotion.com
.
The PC must have the following minimum specification:
Processor
RAM
Hard disk space
CD-ROM
Serial port
Screen
Mouse
Operating system
Minimum specification
1 GHz
512 MB
2 GB
A CD-ROM drive
USB port or
Ethernet* port
1024 x 768, 16-bit color
A mouse or similar pointing device
Windows XP or newer, 32-bit or 64-bit
90 Start-up
Connecting the MicroFlex e150 to the PC
The MicroFlex e150 can be connected to the PC using either USB or TCP/IP.
To use USB, connect a USB cable between a PC USB port and the MicroFlex e150
USB port. Your PC must be using Windows XP, Windows Vista or Windows 7.
To use TCP/IP, connect a CAT5e Ethernet cable between the PC and the
MicroFlex e150 E1 Ethernet port, and set DIP switch 4 to the ON position.
WARNING! You cannot connect an ordinary office PC to the MicroFlex e150 without first altering the PC's Ethernet adapter configuration. However, if you have installed a second Ethernet adapter dedicated for use with the MicroFlex e150, then this adapter's configuration can be altered without affecting the PC's office
Ethernet connection. If you are unsure about making changes to your PC's Ethernet adapter configuration, or are prevented by user permission levels, ask your I.T. administrator to assist you.
Installing Mint WorkBench
The Windows user account requires administrative user rights to install Mint
WorkBench.
To install Mint WorkBench from the CD (OPT-SW-001)
1. Insert the CD into the drive.
2. After a few seconds the setup wizard should start automatically. If the setup wizard does not appear, select Run... from the Windows Start menu and type d:\start where d represents the drive letter of the CD device.
3. Follow the on-screen instructions to install Mint WorkBench.
To install Mint WorkBench from the website
To install Mint WorkBench from www.abbmotion.com, download the application and run it.
Start-up 91
Starting the MicroFlex e150
If you have followed the instructions in the previous sections, you should have now connected the power sources, your choice of inputs and outputs, and the USB cable or Ethernet cable linking the PC to the MicroFlex e150.
Preliminary checks
Before you apply power for the first time, check all items in Installation checklist , starting on page
87
.
Power on checks
See section
MicroFlex e150 indicators
on page
119
for symbols that show if the drive has detected a fault.
1. Turn on the 24 V DC supply.
2. Turn on the AC supply.
3. The drive status display shows the following test sequence, which normally takes approximately 15-20 seconds: , ( in sequence), (in sequence). The sequence ends with the symbol, or if an STO input is not powered. Startup can take more than 1 minute after downloading new firmware.
4. If the motor wires were disconnected in Preliminary checks on page 91 , turn off the AC supply and reconnect the motor wires. Turn on the AC supply.
5. To allow the Commissioning Wizard to function, the Safe Torque Off inputs (page
173 ) need to be powered to allow the MicroFlex e150 to be enabled.
6. If you do not wish to enable the MicroFlex e150 yet, the Commissioning Wizard will inform you when this step is necessary.
USB driver
The USB driver for the MicroFlex e150 is installed with Mint WorkBench.
• If you are using Windows Vista or a newer operating system, no USB driver configuration should be necessary.
• If you are using Windows XP, it will prompt for the driver. Click Next >, choose
‘Install the software automatically’, and click Next > again. Windows will locate and install the driver. The MicroFlex e150 is now ready to be configured using
Mint WorkBench. If the MicroFlex e150 is later connected to a different USB port on the host computer, Windows might report that it has found new hardware.
Either install the driver files again for the new USB port, or connect the
MicroFlex e150 to the original USB port.
92 Start-up
To confirm that the USB driver is installed, check that a Motion Control category is listed in Windows Device Manager:
Start-up 93
Configuring the TCP/IP connection (optional)
If you have connected the MicroFlex e150 to the PC using the Ethernet connection, it might be necessary to alter the PC's Ethernet adapter configuration to operate correctly with the MicroFlex e150.
By default, the MicroFlex e150 has a static IP address of 192.168.100.110. This can be changed using the Configuration tool in Mint WorkBench.
Configuring the PC network adapter
WARNING! You cannot connect an ordinary office PC to the MicroFlex e150 without first altering the PC's Ethernet adapter configuration. However, if you have installed a second Ethernet adapter dedicated for use with the MicroFlex e150, then this adapter's configuration can be altered without affecting the PC's office
Ethernet connection. If you are unsure about making changes to your PC's Ethernet adapter configuration, or are prevented by user permission levels, ask your I.T. administrator to assist you.
The following explanation assumes the PC is connected directly to the
MicroFlex e150, and not across an intermediate Ethernet network. If you wish to attempt the connection through an intermediate Ethernet network, then the network administrator must be consulted to ensure that the necessary IP address will be allowed and is not already allocated on the network.
1. On the Windows 7 Start menu, choose Control Panel, then Network and Sharing
Center. (
Windows XP: Choose Start, Settings, Control Panel, then Network
Connections
).
2. Click Local Area Connection, then click Properties. (
Windows XP: Right-click the
‘Local Area Connection' entry for the required Ethernet adapter and choose
Properties ).
3. Select the ‘Internet Protocol Version 4 (TCP/IPv4)' entry ( Windows XP: ‘Internet
Protocol Version (TCP/IP ’)) and click Properties.
4. On the General tab, make a note of the existing settings. Click Advanced... and make a note of any existing settings. Click Cancel and then click the Alternate
Configuration tab and make a note of any existing settings.
5. On the General tab, choose the ‘Use the following IP address' option.
6. In the IP address box, enter an IP address, e.g. 192.168.100.241. This is the IP address that will be assigned to the Ethernet adapter.
7. In the Subnet mask box, enter 255.255.255.0 and click OK.
8. Click Close to close the Local Area Connection Properties dialog.
94 Start-up
Mint Machine Center
The Mint Machine Center (MMC) is installed as part of the Mint WorkBench software.
It is used to view the network of connected controllers in a system. Individual controllers and drives are configured using Mint WorkBench.
If you have only a single MicroFlex e150 connected to your PC, then MMC is probably not required. See Starting Mint WorkBench on page 98 to configure the
MicroFlex e150.
Toolbars
Menu system
Controller pane
Information pane
MMC provides an overview of the controller network currently accessible by the PC.
MMC contains a controller pane on the left, and an information pane on the right. In the controller pane select the Host item, then in the information pane click Scan. This causes MMC to scan for all connected controllers. Clicking once on a controller's name causes various options to be displayed in the information pane. Double-clicking on a controller's name launches an instance of Mint WorkBench that is automatically connected to the controller.
Application View allows the layout and organization of controllers in your machine to be modelled and described on screen. Controllers can be dragged onto the
Application View icon, and renamed to give a more meaningful description, for example “Conveyor 1, Packaging Controller”. Drives that are controlled by another product, such as MicroFlex e150, can be dragged onto the MicroFlex e150 icon itself, creating a visible representation of the machine. A text description for the system and associated files can be added, and the resulting layout saved as an ‘MMC
Workspace’. When you next need to administer the system, simply loading the workspace automatically connects to all the required controllers. See the Mint help file for full details of MMC.
Start-up 95
Starting MMC
1. On the Windows Start menu, select Programs, Mint WorkBench, Mint Machine
Center.
2. In the controller pane, ensure that Host is selected. In the information pane, click
Scan.
3. When the search is complete, click once on ‘MicroFlex e150' in the controller pane to select it, then double click to open an instance of Mint WorkBench.
The MicroFlex e150 will be already connected to the instance of Mint
WorkBench, ready to configure.
Go straight to
Commissioning Wizard
on page
100
to continue the configuration in Mint WorkBench.
96 Start-up
Mint WorkBench
Mint WorkBench is a fully featured application for programming and controlling the
MicroFlex e150. The main Mint WorkBench window contains a menu system, the
Toolbox and other toolbars. Many functions can be accessed from the menu or by clicking a button - use whichever you prefer. Most buttons include a ‘tool-tip’; hold the mouse pointer over the button (don't click) and its description will appear.
Menu system
Toolbars
Toolbox
Control and test area
Start-up 97
Help file
Mint WorkBench includes a comprehensive help file that contains information about every Mint keyword, how to use Mint WorkBench and background information on motion control topics. The help file can be displayed at any time by pressing F1. On the left of the help window, the Contents tab shows the tree structure of the help file; each book contains a number of topics . The Index tab provides an alphabetic list of all topics in the file, and allows you to search for them by name. The Search tab allows you to search for words or phrases appearing anywhere in the help file. Many words and phrases are underlined and highlighted with a color (normally blue) to show that they are links. Click on the link to go to an associated keyword. Most keyword topics begin with a list of relevant
See Also
links.
For help on using Mint WorkBench, click the Contents tab, then click the small sign beside the Mint WorkBench & Mint Machine Center book icon. Double click a topic name to display it.
98 Start-up
Starting Mint WorkBench
Note: If you have already used MMC to install firmware and start an instance of Mint
WorkBench, go straight to section 6.4.3 to continue configuration.
1. On the Windows Start menu, select Programs, Mint WorkBench, Mint
WorkBench.
2. In the opening dialog box, click Start New Project...
Start-up 99
3. Click Scan to search for the MicroFlex e150.
When the search is complete, click MicroFlex e150 in the list, then click Select.
Note: If the MicroFlex e150 is not listed, check the USB or serial cable between the MicroFlex e150 and the PC. Check that the MicroFlex e150 is powered correctly. Click Scan to re-scan the ports. It can take up to 5 seconds for Mint
WorkBench to detect the MicroFlex e150.
When detection is complete, the Commissioning Wizard is displayed.
If
Launch Commissioning Wizard
was not checked, Edit & Debug mode is displayed.
100 Start-up
Commissioning Wizard
Each type of motor and drive combination has different performance characteristics.
Before the MicroFlex e150 can be used to control the motor accurately, the
MicroFlex e150 must be ‘tuned'. Tuning is the process where the MicroFlex e150 powers the motor in a series of tests. By monitoring the drive's output and the feedback from the motor's encoder, the MicroFlex e150 can make small adjustments to the way it controls the motor. This information is stored in the MicroFlex e150 and can be uploaded to a file if necessary.
The Commissioning Wizard provides a simple way to tune the MicroFlex e150 and create the necessary configuration information for your drive/motor combination, so this is the first tool that should be used. If necessary, any of the parameters set by the
Commissioning Wizard can be adjusted manually after commissioning is complete.
Using the Commissioning Wizard
Each screen of the Commissioning Wizard requires you to enter information about the motor, drive or application. Read each screen carefully and enter the required information. When you have completed a screen, click Next > to display the next screen. If you need to change something on a previous screen, click the < Back button. The Commissioning Wizard remembers information that you have entered so you will not need to re-enter everything if you go back to previous screens. If you need extra help, click Help or press F1.
Start-up 101
Select your Motor Type:
Select the type of motor that you are using; rotary or linear, brushless or induction.
Select your Motor:
Carefully enter the details of your motor. If you are using a Baldor motor, the catalog number or spec. number can be found stamped on the motor's nameplate. If you are using a motor with EnDat feedback, are using a different manufacturer’s motor, or need to enter the specification manually, select the ‘I would like to define a custom motor’ option.
Confirm Motor and Drive information:
If you entered the catalog or spec. number on the previous page, it is not necessary to change anything on this screen; all the required data will be entered already.
However, if you selected the ‘I would like to define a custom motor’ option, it will be necessary to enter the required information before continuing.
Motor Feedback:
If you entered the catalog or spec. number on the previous page, it is not necessary to change anything on this screen; the feedback resolution will be entered already.
However, if you selected the ‘I would like to define a custom motor’ option, it will be necessary to enter the feedback resolution before continuing.
Drive Setup complete:
This screen confirms that drive setup is complete.
Select Operating Mode and Source:
In the Operating Mode section, choose the required operating mode. In the
Reference Source section, it is important to select ‘Direct (Host/Mint') as the
Reference Source. This will allow the Autotune Wizard to operate correctly, and allow further initial testing to be performed using Mint WorkBench. Although the
MicroFlex e150 might eventually be controlled over EtherCAT, the ‘RT Ethernet' reference source should only be selected after the MicroFlex e150 has been commissioned and is ready to add to the EtherCAT network. This can be selected by choosing the Operating Mode tool in the Toolbox.
Application Limits:
It is not necessary to change anything on this screen. However, if you wish to adjust the application peak current (App. Peak Current) and/or application maximum speed
(App. Max. Speed), then click in the appropriate box and enter a value.
Select Scale Factor:
It is not necessary to change anything on this screen. However, it is recommended to select a user unit for position, velocity and acceleration. This allows Mint WorkBench to display distance, speed and acceleration using meaningful units, instead of encoder counts. For example, selecting a Position User Unit of Revs (r) will mean that all position values entered or displayed in Mint WorkBench will represent revolutions.
The Position Scale Factor value will change automatically to represent the required scale factor (the number of quadrature counts per revolution). If you need to use an alternative unit, for example degrees, type “Degrees” in the Position User Unit box
102 Start-up and enter a suitable value in the Position Scale Factor box. Separate velocity and acceleration units can also be defined. See the Mint help file for more information about scale factors.
Profile Parameters:
It is not necessary to change anything on this screen. However, if you wish to adjust the parameters for any control method, click in the appropriate box and enter a value.
Analog input parameters:
It is not necessary to change anything on this screen. However, if you wish to adjust the analog inputs, click Common Settings to select the input range. The Tune Offset button automatically adjusts the input to compensate for any DC offset.
Operation setup complete:
This screen confirms that operation setup is complete.
Autotune Wizard
The Autotune Wizard tunes the MicroFlex e150 for optimal performance with the attached motor. This removes the need for manual fine-tuning of the system, although in some critical applications this still might be required.
Click Options... to configure optional autotuning parameters. These include Triggered
Autotune which allows the autotuning process to be delayed until the drive is enabled.
WARNING! The motor will move during autotuning. For safety it is advisable to disconnect any load from the motor during initial autotuning. The motor can be tuned with the load connected after the Commissioning Wizard has finished.
Autotune:
Click START to begin the auto-tuning process. Mint WorkBench will take measurements from the motor and then perform small test moves.
For further information about tuning with the load attached, see Further tuning - with load attached on page 105 .
NOTE: Even if you do not perform any further tuning or configuration, the STO function must be tested; see Appendix: Safe Torque Off (STO) on page 173 .
Start-up 103
Further tuning - no load attached
The Autotune Wizard calculates many parameters that allow the MicroFlex e150 to provide good control of the motor. In some applications, these parameters might need to be fine-tuned to provide the exact response that you require.
1. Click the Fine-tuning icon in the Toolbox on the left of the screen.
The Fine-tuning window is displayed at the right of the screen. This already shows some of the parameters that have been calculated by the Commissioning Wizard.
The main area of the Mint WorkBench window displays the capture window.
When further tuning tests are performed, this will display a graph representing the response.
2. The Fine-tuning window has a number of tabs the bottom.
Click on the Velocity tab.
Some tabs might not be available depending on the configuration mode you selected in the Commissioning Wizard.
3. In the Test Parameters area at the bottom of the tab, click in the Move
Type drop down box and select
Forward.
Enter values in the Velocity and
Distance boxes to create a short move. The values you enter depend on the velocity scaling factor that was selected in the Commissioning Wizard. This example assumes the velocity scaling factor was selected as Revs Per Minute (rpm), so entering a value of 1000 here will create a move with a velocity of 1000 rpm. Similarly, assuming the position scaling factor had been set to Revolutions (r), the value 10 will create a move lasting for 10 revolutions of the motor.
4. Click Go to start the test move. Mint
WorkBench will perform the test move and display a graph of the result.
5. Click on the graph labels to turn off unwanted traces. Leave just Demand
Velocity and Measured Velocity turned on.
104 Start-up
Typical autotuned response (no load):
Measured velocity
Demand velocity
Note: The graph that you see will not look exactly the same as this one! Each motor has a different response.
The graph shows that the response reaches the demand quickly and only overshoots the demand by a small amount. This can be considered an ideal response for most systems.
For further information about tuning with the load attached, see Further tuning - with load attached
on page
105
.
Start-up 105
Further tuning - with load attached
To allow Mint WorkBench to adjust the basic tuning to compensate for the intended load, it is necessary to attach the load to the motor and then perform the autotune procedure again.
1. Attach the load to the motor.
2. Click the Autotune icon in the Toolbox on the left of the screen.
3. Click the Autotune on load check box.
4. Click START to begin the auto-tuning process. Mint WorkBench will take measurements from the motor and then perform small test moves.
5. Click the Fine-tuning icon in the
Toolbox on the left of the screen.
6. In the Velocity tab's Test Parameters area, ensure the same move parameters are entered and then click Go to start the test move.
Mint WorkBench will perform the test move and display a graph of the result.
106 Start-up
Optimizing the velocity response
It might be desirable to optimize the default autotuned response to better suit your application. The following sections describe the two main tuning factors and how to correct them.
Correcting overshoot
The following graph shows a response where the measured velocity overshoots the demand by a significant amount.
1. Go to the Fine-tuning window's
Velocity tab.
To reduce the amount of overshoot, click Calculate... and increase the bandwidth using the slider control.
Alternatively, type a larger value in the Bandwidth box.
Click OK to close the Bandwidth dialog.
2. Click Go to start the test move. Mint
WorkBench will perform the test move and display a graph of the result.
Velocity overshoots demand:
Measured velocity
Demand velocity
Start-up 107
Correcting zero-speed noise in the velocity response
The following graph shows a response where there is very little overshoot but a significant amount of zero-speed noise. This can cause undesirable humming or ringing in the motor.
1. Go to the Fine-tuning window's
Velocity tab.
To reduce the amount of noise, click
Calculate... and decrease the bandwidth using the slider control.
Alternatively, type a smaller value in the Bandwidth box.
Click OK to close the Bandwidth dialog.
2. Click Go to start the test move. Mint
WorkBench will perform the test move and display a graph of the result.
Zero-speed noise:
Noise in measured velocity at zero speed
Demand velocity
108 Start-up
Ideal velocity response
Repeat the tests described in Correcting overshoot and Correcting zero-speed noise in the velocity response until the optimal response is achieved. The following graph shows an ideal velocity response. There is only a small amount of overshoot and very little zero-speed noise.
Ideal velocity response:
Measured velocity
Demand velocity
Start-up 109
Performing test moves - continuous jog
This section tests the basic operation of the drive and motor by performing a continuous jog. To stop a move in progress, click the red stop button or the drive enable button on the toolbar. Alternatively, use the Mint WorkBench ‘Red Stop Button’ feature.
1. Check that the Drive enable button is pressed (down).
2. In the Toolbox, click the Edit & Debug icon.
3. Click in the Command window.
Type:
JOG(0)=10
This will cause the motor to move continuously at 10 units per second.
In Mint WorkBench, look at the Spy window located on the right of the screen. Check that the axis tab is selected. The
Spy window's Velocity display should show 10 (approximately). If there seems to be very little motor movement, it is probably due to the scale factor. In the
Commissioning Wizard, on the Select Scale Factor page, if you did not adjust the scale factor then the current unit of movement is feedback counts per second.
Depending on the motor's feedback device, 10 feedback counts per second could equate to a very small velocity. Issue another JOG command using a larger value, or use the Operating Mode Wizard to select a suitable scale factor (e.g. 4000 if the motor has a 1000 line encoder, or 10,000 for a 2500 line encoder).
4. To stop the test, type:
STOP(0)
5. If you have finished testing click the
Drive Enable button to disable the drive.
110 Start-up
Performing test moves - relative positional move
This section tests the basic operation of the drive and motor by performing a positional move. To stop a move in progress, click the red stop button or the drive enable button on the toolbar. Alternatively, use the Mint WorkBench ‘Red Stop Button’ feature.
1. Check that the Drive enable button is pressed (down).
2. In the Toolbox, click the Edit & Debug icon.
3. Click in the Command window.
Type:
MOVER(0)=10
GO(0)=10
This will cause the motor to move to a position 10 units from its current position.
The move will stop when completed.
4. If you have finished testing click the
Drive Enable button to disable the drive.
Start-up 111
Further configuration
Mint WorkBench provides a number of other tools for testing and configuring the
MicroFlex e150. Every tool is explained fully in the help file. Press F1 to display the help file, then navigate to the Mint WorkBench book. Inside this is the Toolbox book.
Configuration tool
The Configuration tool shows the MicroFlex e150’s integrated configuration interface.
1. Click the Configuration tool icon in the Toolbox on the left of the screen.
2. Select Load configuration from the controller or Start new configuration and click the green arrow.
3. Enter a descriptive name for the controller and click the green arrow.
4. Continue through the screens making the required changes.
Click Finish at any time to go to the last screen and save the changes.
5. On the final screen, click
Finish to complete the configuration.
112 Start-up
Parameters tool
The Parameters tool can be used to view or change most of the drive's parameters.
1. Click the Parameters icon in the
Toolbox on the left of the screen.
The main area of the Mint
WorkBench window displays the
Parameters editor screen.
Items listed with a grey icon are read only so cannot be changed.
Items listed with a green icon are currently set to their factory default value.
Items listed with a yellow icon have been changed from their factory default value, either during the commissioning process or by the user.
2. In the parameters tree, scroll to the required item. Click on the small + sign beside the item's name. The list will expand to show all items in the category. Click on the item you wish to edit.
3. The adjacent table will list the chosen item. Click in the Active Table cell and enter a value. This immediately sets the parameter, which will remain in the MicroFlex e150 until another value is defined. The icon to the left of the item will become yellow to indicate that the value has been changed.
Many of the MicroFlex e150's parameters are set automatically by the
Commissioning Wizard, or when tests are performed in the fine-tuning window.
Start-up 113
Spy window
The Spy window can be used to monitor and capture parameters in real-time. If you tried the test moves in Performing test moves - continuous jog on page 109 or
Performing test moves - relative positional move on page 110 then you have already seen the Spy window, as it is displayed in conjunction with Edit & Debug mode. See the Mint help file for full details of each tab.
1. Click the Edit & Debug icon in the
Toolbox on the left of the screen.
The Spy Window is displayed on the right of the screen. Click on the tabs at the bottom of the window to select the required function.
2. The Axis tab displays the five most commonly monitored parameters, together with the state of special purpose inputs and outputs.
3. The I/O tab displays the state of all the digital inputs and outputs.
Clicking on an output LED will toggle the output on/off.
4. The Monitor tab allows up to six parameters to be selected for monitoring.
Click in a drop down box to select a parameter.
At the bottom of the Monitor tab, realtime data capture can be configured.
114 Start-up
Other tools and windows
Remember, for help on each tool press F1 to display the help file, then navigate to the
Mint WorkBench book. Inside this is the Toolbox book.
• Edit & Debug Tool
This tool provides a work area including the Command window and Output window. The Command window can be used to send immediate Mint commands to the MicroFlex e150. If you tried the test moves in
Performing test moves - continuous jog
on page
109
or
Performing test moves - relative positional move on page
110
, then you have already used Edit & Debug mode.
Press Ctrl+N to open a Mint programming window (except models ..EI
N A..).
• Scope Tool
Displays the capture screen. This screen is also shown when the Fine-tuning tool is selected.
• Digital I/O Allows you to configure the active states and special assignments for the digital inputs and outputs.
For example, a general purpose digital input can be configured as an optional ‘drive enable input’, which must be active to enable the drive; see pages 63 and 65 - 68 .
If a digital input is to be used as a home switch input, see Using a digital input as a home switch input
(optional) on page 63 for important details.
Start-up 115
Safe Torque Off (STO) acceptance test
Drive commissioning is not complete until the STO function has been tested.
The acceptance test of the safety function must be carried out by an authorized person with expertise and knowledge of the safety function. The test must be documented and signed by the authorized person.
See
Appendix: Safe Torque Off (STO)
on page
173
.
116 Start-up
Fault tracing 117
10
Fault tracing
What this chapter contains
This section explains common problems and their solutions. The LED indicators are described in
MicroFlex e150 indicators
on page
119
.
Problem diagnosis
If you have followed all the instructions in this manual in sequence, you should have few problems installing the MicroFlex e150. If you do have a problem, read this section first.
• In Mint WorkBench, use the Error Log tool to view recent errors and then check the help file.
• If you cannot solve the problem or the problem persists, the SupportMe feature can be used.
118 Fault tracing
SupportMe feature
The SupportMe feature is available from the Help menu, or by clicking the button on the motion toolbar. SupportMe can be used to gather information which can then be e-mailed, saved as a text file, or copied to another application. The PC must have e-mail facilities to use the e-mail feature. If you prefer to contact ABB technical support by telephone or fax, contact details are provided on the back cover of this manual.
Please have the following information ready:
• The serial number of your MicroFlex e150 (if known).
• Open the Help, SupportMe menu item in Mint WorkBench to view details about your system.
• The catalog and specification numbers of the motor that you are using.
• A clear description of what you are trying to do, for example trying to establish communications with Mint WorkBench or trying to perform fine-tuning.
• A clear description of the symptoms that you can observe, for example the Status
LED, error messages displayed in Mint WorkBench, or errors reported by the Mint error keywords
ERRORREADCODE
or
ERRORREADNEXT
.
• The type of motion generated in the motor shaft.
• A list of any parameters that you have setup, for example the motor data you entered/selected in the Commissioning Wizard, the gain settings generated during the tuning process and any gain settings you have entered yourself.
Power-cycling the MicroFlex e150
The term ‘power-cycle the MicroFlex e150’ is used in the Troubleshooting sections.
Remove the 24 V supply, wait for the MicroFlex e150 to power down completely (the
Status LED will turn off), then re-apply the 24 V supply.
Fault tracing 119
MicroFlex
e
150 indicators
Ethernet LEDs
The Ethernet LEDs display the overall condition of the Ethernet interface once the startup sequence has completed. The LED codes conform to the EtherCAT Technology Group (ETG) standard at the time of production.
NET ERR (Red)
Off : No errors or not powered.
Blinking :
Invalid mailbox configuration in BOOT.
Invalid mailbox configuration in
PREOP.
Invalid Sync manager configuration.
Invalid output configuration.
Invalid input configuration.
Invalid watchdog configuration.
Invalid DC Sync configuration.
Invalid DC latch configuration.
1 flash :
Unspecific error.
No memory.
Invalid request state change.
Unknown requested state.
Bootstrap not supported.
No valid firmware.
No valid inputs available.
No valid output.
Synchronisation error.
Invalid Sync manager types.
Slave needs cold start.
Slave needs INIT.
Slave needs PREOP.
Slave needs SAFEOP.
Invalid input mapping.
Invalid output mapping.
Inconsistent settings.
FreeRun not supported.
SyncMode not supported.
2 flashes : Sync manager watchdog.
FreeRun needs 3 buffer mode.
Background watchdog occurred.
No valid inputs and outputs.
Fatal sync error.
No sync error.
PLL error.
DC sync IO error.
DC sync time-out error.
Invalid DC Sync cycle time.
DC Sync0 cycle time.
DC Sync1 cycle time.
Message box EoE error.
Message box CoE error.
Message box FoE error.
Message box SoE error.
Message box VoE error.
EEPROM no access.
EEPROM error.
Slave restarted locally.
120 Fault tracing
NET RUN (Green)
Off: INITIALISATION state (or not powered).
Blinking: PRE-OPERATIONAL state.
1 flash: SAFE-OPERATIONAL state.
3 flashes: Device identification. This state can be set from the master to locate the device.
Continuously illuminated, not flashing: Node in OPERATIONAL state. EtherCAT is operating normally.
LED flash periods
The following diagram shows the definitions of the terms ‘blinking’, ‘flashing’ and
‘flickering’ used in the previous sections, as defined by the EtherCAT Technology
Group.
LED flash timing definitions:
(Not illuminated) Off
1 flash
2 flashes
Inverted 2 flashes
3 flashes, etc.
Blinking
Flickering
On
1 s
1 s
1 s
1 s
1 s
(Continuously illuminated)
200 ms
Drive status display
The drive status display indicates errors and general
MicroFlex e150 status information. When an error occurs, the drive displays a sequence starting with the symbol E, followed by the five digit error code. For example, error code 10015 is displayed:
Fault tracing 121
STO error
The decimal point to the right of the number also illuminates to indicate STO errors.
For a complete list of error codes, open Mint WorkBench, press F1, and locate the
Error Handling book. This contains topics listing the drive status display indicators and basic error codes.
The following information symbols can be displayed:
Symbol Description
Drive disabled, and one or both STO inputs are not powered. The drive must be enabled before operation can continue. Both STO inputs must be powered. If an optional drive enable input has been configured, it must also be powered.
Drive disabled. The drive must be enabled before operation can continue. If an optional drive enable input has been configured, it must also be powered.
Suspend active. The Mint SUSPEND command has been issued and is active.
Motion will be ramped to zero demand whilst active.
Firmware loading (segments are illuminated sequentially). This sequence is followed by a numerical sequence representing firmware initialization stages.
Hold to Analog (HTA) mode. The axis is in Hold To Analog mode. See the Mint keyword HTA .
Drive enabled, but idle.
Cam move. A cam profile is in progress. See the Mint keyword CAM .
Dwell. A dwell (wait) ‘move’ is in progress. See the Mint keyword
MOVEDWELL
.
Flying shear. A flying shear is in progress. See the Mint keyword FLY .
Follow move. The drive is in follow mode. See the Mint keyword FOLLOW .
122 Fault tracing
Symbol Description
Homing. The drive is currently homing. See the Mint keyword HOME .
Incremental move. An incremental linear move is in progress. See the Mint keywords INCA and INCR .
Jog. The drive is jogging. See the Mint keywords
JOG
,
JOGCOMMAND
and related topics.
Offset move. An offset move is in progress. See the Mint keyword OFFSET .
Position move. A linear move is in progress. See the Mint keywords MOVEA and
MOVER .
Torque move. The drive is in torque mode. See the Mint keywords
TORQUEREF
,
TORQUEREFSOURCE
and related commands.
Stop input active. A Mint STOP command has been issued or an optional stop input is active.
Velocity reference move. The drive is under velocity control. See the Mint keywords VELREF and related keywords.
Spline. A spline move is in progress. See the Mint keyword
SPLINE
and related keyword.
In DS402 mode (under the control of an EtherCAT master), the outer segments will rotate clockwise or counter-clockwise.
User defined symbols can be displayed using Mint keywords
LED
and
LEDDISPLAY
.
Fault tracing 123
Power
Drive does not start when applying AC power:
• Check that the motor output phases are not short circuited. The drive trips on a motor phase short circuit and will not restart unless AC power is removed.
Remove all power from the drive, correct the short circuit and restart the drive.
Communication
Drive status display is off:
• Check that the 24 V DC control circuit supply is correctly connected at X2, and is switched on.
Drive status display shows ‘r’:
• The MicroFlex e150 is in firmware recovery mode. This means that it cannot boot fully, so will allow Mint WorkBench to download firmware from the scan controller dialog.
Mint WorkBench fails to detect the MicroFlex e150:
• Ensure that the MicroFlex e150 is powered and the drive status display is illuminated (page 121 ).
• Check that the Ethernet or USB cable is connected between the PC and
MicroFlex e150.
• For Ethernet connections, check that DIP switch 4 is in the ON position to set standard Ethernet mode. Power cycle the MicroFlex e150 after changing DIP switch 4. Check that the cable is connected to port E1 (the port nearest the front panel).
• Check that the PC's Ethernet port has been correctly configured for TCP/IP operation (see
Configuring the TCP/IP connection (optional)
on page
93
).
• Try an alternative cable or different port on the PC.
• For USB connections, check that the cable is properly connected. Check the USB connector socket pins for damage or sticking. Check that the USB device driver has been installed; a ‘ABB USB Motion Product’ device should be listed in
Windows Device Manager, and 'MicroFlex e150' should be listed in Windows
Devices and Printers (Windows 7).
Mint WorkBench
The Spy window does not update:
• The system refresh has been disabled. Go to the Tools, Options menu item, select the System tab and then choose a System Refresh Rate (500 ms is recommended).
124 Fault tracing
Cannot communicate with the controller after downloading firmware:
• After firmware download, always power cycle the MicroFlex e150.
Mint WorkBench loses contact with MicroFlex e150 while connected using
USB:
• Check that the MicroFlex e150 is powered.
• Check that a ‘ABB USB Motion Product’ device is listed in Windows Device
Manager, and 'MicroFlex e150' is listed in Windows Devices and Printers
(Windows 7). If not, there could be a problem with the PC's USB interface.
Tuning
Cannot enable the MicroFlex e150 because there is an error 10010:
• Check the drive enable input, if assigned, is connected and powered correctly.
Cannot enable the MicroFlex e150 because there is an error 10033, 10034 and/or 10035:
• Check the Safe Torque Off inputs on connector X3 pins 18 & 8 and 19 & 9 are both connected and powered correctly.
When the MicroFlex e150 is enabled the motor is unstable:
• Check that the load is firmly coupled to the motor.
• Use the Mint WorkBench Drive Setup Wizard to confirm that the correct motor data has been entered.
• Use the Mint WorkBench Autotune Wizard to retune the motor.
• If the motor is still unstable, select the Mint WorkBench Autotune Wizard once more. Click Options.... On the Bandwidth tab, move the Current and/or Position and Speed Control sliders to a slower position to select a lower bandwidth. Click
OK to exit and then start the Autotune Wizard again.
Ethernet
Cannot connect to the drive over TCP/IP:
• Check that the PC's Ethernet adapter has been correctly configured, as described in Configuring the TCP/IP connection (optional) on page 93 .
How do I configure my EtherCAT manager to operate with the MicroFlex e150?
• An EtherCAT ESI file (.xml) that describes the drive to the EtherCAT manager can be uploaded from the controller using the Mint WorkBench Configuration tool.
Fault tracing 125
I can’t control the MicroFlex e150 from my EtherCAT manager
The drive’s reference source must be set to allow the EtherCAT manager to take control of the MicroFlex e150. There are several ways to do this:
• Set the
CONTROLREFSOURCESTARTUP
parameter to '1' using the Mint
WorkBench Parameter viewer or Command window, and restart the drive. This will give control to the manager each time the MicroFlex e150 starts.
• Set the Control Ref. Source to ‘RT Ethernet (CiA402)’ in the Mint WorkBench
Operating Mode Wizard or Commissioning Wizard.
• Click the Direct button on the Mint WorkBench Motion tool bar, and select ‘RT
Ethernet (DS402)’ in the Axis 0 drop-down.
• Confirm that the reference source on all controlled nodes has been set to
EtherCAT in the Mint WorkBench Operating Mode Wizard, and that the master has been configured correctly.
126 Fault tracing
Technical data 127
11
Technical data
What this chapter contains
The chapter contains the technical specifications of the drive, for example, the ratings, sizes and technical requirements as well as provisions for fulfilling the requirements for CE and other marks.
128 Technical data
Dimension drawing (all models)
11
(0.4)
82
(3.23)
79.5
(3.13)
63.4
(2.5)
5
(0.2)
6
Dimensions shown as: mm (inches)
Depth: 157 mm (6.2 in)
Weight: 3 A: 1.45 (3.2 lb)
6 A: 1.50 kg (3.3 lb)
9 A: 1.55 kg (3.4 lb)
Technical data 129
Electrical power network specification
A 115 - 230 V AC 3-phase power source (EN 61010 over-voltage category III or less) is required. An AC power filter is required to comply with the CE directive for which the MicroFlex e150 was tested (see CE marking on page 153 ).
Description
Nominal input voltage
Minimum input voltage
Maximum input voltage
Nominal input current
@ maximum rated output current
Nominal DC-bus voltage
@ 230 V AC input
Frequency
Imbalance
Unit AC input
V AC
3 A
A 7.5
1 Φ
115 or 230
105*
250
6 A
15
9 A
22
3 A
4
3 Φ
115 or 230
105*
250
6 A
8
9 A
12
305 321
Fundamental power factor
Network type
Short circuit current protection
(UL 508C)
48 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
TN (grounded) systems.
Corner grounded TN, and IT (ungrounded) systems not allowed.
The drive is suitable for use on a circuit capable of delivering not more than 5000 A symmetrical amperes (rms) at 230 V maximum when protected by fuses given in the fuse table on page 136 .
* The MicroFlex e150 will operate at lower input voltages, although the drive will trip if the DC-bus voltage falls below 50 V or 60% of the no-load voltage, whichever occurs first.
130 Technical data
Effect of AC power supply voltage on DC-bus voltage
350
300
250
200
150
Three-phase AC supply
Single-phase AC supply
100
100 125 150 175 200
AC supply voltage (rms)
225 250
Effect of AC power supply voltage on DC-bus ripple voltage
50
40
30
20
Single-phase AC supply
10
Three-phase AC supply
0
100 125 150 175 200
AC supply voltage (rms)
225 250
Technical data 131
Effect of output current on DC-bus ripple voltage
60
50
40
30
20
Single-phase AC supply
Three-phase AC supply
10
0
20 30 40 50 60 70 80 90 100
% of drive rated current
110 120 130 140 150
132 Technical data
Temperature derating
The derating characteristics assume the MicroFlex e150 is mounted vertically on
3 mm thick (or less) metal plate. If the MicroFlex e150 is mounted on 10 mm metal plate, the current characteristics shown below can be increased by up to 7% if there is no forced air cooling, or 15% if forced air cooling is present. See also Mounting and cooling on page 29 .
Derating characteristic for 3 A models (E152A03...):
Single-phase AC supply
3
1 m/s forced air
2
Natural cooling
1
0
30 35 40 45
Ambient temperature (°C)
50
Three-phase AC supply
55
3
1 m/s forced air
2
Natural cooling
1
0
30 35 40 45
Ambient temperature (°C)
50
Notes:
Load power factor = 0.75.
Overload limit for models E152A 03 ... is 6 A.
55
Technical data 133
Derating characteristic for 6 A models (E152A06...):
Single-phase AC supply
6
5
1.5 m/s forced air
4
3
2
1
1 m/s forced air
Natural cooling
0
30 35 40 45
Ambient temperature (°C)
50 55
Three-phase AC supply
4
3
2
1
6
5
0
30 35 40 45
Ambient temperature (°C)
50
Notes:
Load power factor = 0.75.
Overload limit for models E152A 06 ... is 12 A.
55
1.5 m/s forced air
1 m/s forced air
Natural cooling
134 Technical data
Derating characteristic for 9 A models (E152A09...):
Single-phase AC supply
9
8
7
6
5
4
3
2
1
0
30 35 40 45
Ambient temperature (°C)
50 55
3.5 m/s forced air
2.5 m/s forced air
1.5 m/s forced air
1 m/s forced air
Natural cooling
Three-phase AC supply
9
8
7
6
5
4
3
2
1
0
30 35 40 45
Ambient temperature (°C)
50
Notes:
Load power factor = 0.75.
Overload limit for models E152A 09 ... is 18 A.
3.5 m/s forced air
2.5 m/s forced air
1.5 m/s forced air
1 m/s forced air
55
Natural cooling
Overtemperature trips
The MicroFlex e150 contains internal temperature sensors that will cause it to trip and disable if the temperature exceeds 80 °C (3 A model), or 75 °C (6 A and 9 A models). This limit can be read using the
TEMPERATURELIMITFATAL
keyword - see the Mint help file for details.
Heat dissipation
These figures assume drive efficiency = 95%, power factor = 0.8:
MicroFlex e150 model
Heat dissipation
(W)
3 A 50
6 A 101
9 A 151
Technical data 135
136 Technical data
Recommended fuses, circuit breakers and wire sizes
The following table describes the recommended fuses and circuit breakers for AC power connections, and suitable wires sizes for AC and motor power connections.
Drive catalog number
E152A03..
Cont.
output amps
(RMS)
3 A
AC supply type
1Ø
E152A06..
E152A09..
6 A
9 A
3Ø
1Ø
3Ø
1Ø
3Ø
Input fuse
Ferraz Shawmut:
6x32 FA series, 10 A
(W084314P) or
BS88 2.5 URGS 10 A
(N076648J)
Ferraz Shawmut:
6x32 FA series, 8 A
(V084313P) or
BS88 2.5 URGS, 7 A
(M076647J)
Ferraz Shawmut:
6x32 FA series, 20 A
(A084318P) or
BS88 2.5 URGS, 20 A
(L097507J)
Ferraz Shawmut:
6x32 FA series, 12.5 A
(X084315P) or
BS88 2.5 URGS, 12 A
(P076649J)
Ferraz Shawmut:
BS88 2.5 URGS, 25 A
(R076651J)
Ferraz Shawmut:
6x32 FA series, 20 A
(A084318P) or
BS88 2.5 URGS, 20 A
(L097507J)
Circuit breaker
(C-type)
10 A
8 A
20 A
12.5 A
25 A
20 A
Minimum wire gauge
AWG mm 2
14 2.0
14
14
14
14
14
2.0
2.0
2.0
2.5
2.0
Note: All wire sizes are based on 75 °C (167 °F) copper wire. Higher temperature smaller gauge wire can be used per National Electric Code (NEC) and local codes.
Recommended fuses are based on 25 °C (77 °F) ambient, maximum continuous control output current and no harmonic current. Earth/ground wires must be the same gauge, or larger, than the L1, L2 and L3 wires.
Technical data 137
Input power-cycling and inrush
If AC power has been removed from the MicroFlex e150, it should remain disconnected for the specified period before it is reapplied:
MicroFlex e 150 current rating
3 A
6 A
9 A
Minimum power cycle delay period
(seconds)
25
45
65
This delay allows the input surge protection circuit to perform correctly, ensuring that the inrush current (typically 1.7 A) is below the drive rated current. Power-cycling the drive more frequently could cause high inrush current and corresponding nuisance operation of circuit breakers or fuses. Repeated failure to observe the delay period could reduce the lifetime of the MicroFlex e150.
Discharge period
WARNING!
After AC power has been removed from the MicroFlex e150, high voltages (greater than 50 V DC) can remain on the brake resistor connections until the DC-bus circuitry has discharged. The high voltage can remain for the period specified in the table below.
MicroFlex e 150 current rating
3 A
6 A
9 A
Time for DC-bus to discharge to 50 V or less
(maximum, seconds)
83
166
248
138 Technical data
Power supply filters
MicroFlex e 150 current rating
3 A
6 A
9 A
230 V AC, 1Ø
FI0015A00 + line reactor * or
FI0029A00 **
FI0015A02 * or
FI0029A00 **
FI0029A00 **
230 V AC, 3Ø
FI0018A00 *
FI0018A00 *
FI0018A03 *
* See
EMC filters
starting on page
166
for further details.
** See
Foot-mount filter (single phase only)
on page
165
for further details.
Maximum earth leakage from the MicroFlex e150 is 3.4 mA per phase (230 V, 50 Hz supply). This value does not include the earth leakage from the AC power filter, which could be much larger (see EMC filters on page 166 ).
24 V control circuit supply (X2)
Description
Nominal input voltage
Minimum input voltage
Maximum input voltage
Maximum ripple
Typical input current
(not powering feedback device)
Typical input current
(powering feedback device)
Maximum continuous current
@ 24 V DC
Power on surge current (typical)
@ 24 V DC, 100 ms
Unit
V DC
V DC
V DC
%
A
A
A
A
3 A 6 A
24
20
30
±10
0.5 - 0.6
0.6 - 0.8
1
4
9 A
Technical data 139
Motor output power (X1)
Description
Nominal phase current
Peak phase current for 3 s
Nominal output
@ 230 V, 3 Φ
Output voltage (line-line)
@ V DC-bus = 320 V
Output frequency
Output dV/dt at drive, phase-phase at drive, phase-ground at motor (using 20 m cable), phase-phase at motor (using 20 m cable), phase-ground
Nominal switching frequency
Minimum motor inductance
Efficiency
Unit
A rms
A rms
VA
V rms
Hz kV/µs kHz mH
%
Motor output rating adjustment
200%, 3 s overload
3 A
3 A
300%, 3 s overload
2.5 A
200%, 3 s overload
6 A
6 A
300%, 3 s overload
5.25 A
3 A
3
6
1195
6 A
6
12
2390
0 - 230
0 - 2000
2
1.1
1.9
1.8
8.0
1
>95
9 A
9
18
3585
200%, 3 s overload
9 A
9 A
300%, 3 s overload
7.5 A
140 Technical data
Brake (X1)
Description
Nominal switching threshold
Nominal power
(10% peak power, r = 57 Ω
Peak power
(10% peak power, r = 57 Ω
Maximum brake switching current
Minimum load resistance
Minimum load inductance
Unit
V DC kW kW
A pk
Ω
µH
All models on: 388, off: 376
0.25
2.7
10
39
100
Braking capacity
The braking capacity of the MicroFlex e150 can be calculated from the following formula:
E
1
2
DC bus capacitance ×
(
( Brake switching threshold )
2
–
(
¥
2 × Supply voltage
)
2 ) where the
Brake switching threshold
is 388 V. This gives the following typical values:
MicroFlex e 150 catalog number
DC-bus capacitance ( μ F)
Braking capacity (J)
E152A03...
E152A06...
E152A09...
560
1120
1680
115 V AC supply
34.7
69.4
104.2
230 V AC supply
12.5
25
37.6
Brake resistor selection
The following calculations can be used to estimate the type of brake resistor that will be required for the application. Some basic information is required to complete the calculation. Remember to use the worst-case scenario for the application, to ensure that the braking power is not underestimated. For example, use:
• The maximum possible motor speed.
• The maximum inertia.
• The minimum deceleration time.
• The minimum cycle time.
Technical data 141
Requirement a) Initial motor speed, before deceleration begins, in radians per second.
Enter value here
Initial motor speed:
U = _____________ rad/s
Multiply RPM by 0.1047 to give radians per second.
b) Final motor speed after deceleration is complete, in radians per second.
Final motor speed:
V = _____________ rad/s
Multiply RPM by 0.1047 to get radians per second. This value will be zero if the load is going to be stopped.
c) The deceleration time from initial speed to final speed, in seconds.
Decel time:
D = _____________ s
Cycle time: d) The total cycle time (i.e. how frequently the process is repeated), in seconds.
See Duty cycle on page 144 .
e) Total inertia.
C = _____________ s
Total inertia:
This is the total inertia seen by the drive, accounting for motor inertia, load inertia and gearing. Use the Mint WorkBench Autotune tool to tune the motor, with the load attached, to determine the value. This will be displayed in kg·m 2 in the Autotune tool. If you already know the motor inertia (from the motor spec.) and the load inertia (by calculation) insert the total here.
J = _____________ kg·m 2
Multiply kg·cm
2
by 0.0001 to give kg·m
2
.
Multiply lb-ft
2
by 0.04214 to give kg·m
2
.
Multiply lb-in-s
2
by 0.113 to give kg·m
2
.
142 Technical data
Braking energy
The braking energy to be dissipated, E, is the difference between the initial energy in the system (before deceleration begins) and the final energy in the system (after deceleration has finished). If the system is brought to rest then the final energy is zero.
The energy of a rotating object is given by the formula:
E
1
J îȦ
2
2 where E is energy, J is the moment of inertia, and ω is the angular velocity.
The braking energy, which is the difference between the initial energy and the final energy, is therefore:
E =
( 1
J × U
2
2
) ( 1
J × V
2
2
)
=
1
J × ( U
2
2
– V
2 )
= ________________ J (joules)
Calculate E using the values for J, U and V entered in the table on page
141
. If E is less than the drive's braking capacity (see
Braking capacity
on page
140
), a brake resistor is not required.
If E is greater than the drive's braking capacity, then continue to the next section to calculate the braking and average power dissipation.
Braking power and average power
The braking power P r
is the rate at which the braking energy is dissipated. This rate is defined by the deceleration period, D. The shorter the deceleration period, the greater the braking power.
P r
= —
D
= ________________ W (watts)
The resistors shown in the following table can withstand brief overloads, but the average power dissipation, P av
, must not exceed the stated power rating. The average power dissipation is determined by the proportion of the application cycle time, C, spent braking. The greater the proportion of time spent braking, the greater the average power dissipation.
P av
= P r
× —
C
= ________________ W (watts)
Technical data 143
Resistor choice
P av
is the value to use when assessing which brake resistor to use. However, a safety margin of 1.25 times is recommended to ensure the resistor operates well within its limits*, so:
Required resistor power rating = 1.25 × P av
________________ W (watts)
The range of suitable brake resistors is shown in the following table. Choose the resistor that has a power rating equal to or greater than the value calculated above.
Part
RGJ139
RGJ160
RGJ260
RGJ360
Resistance
39 Ω
60 Ω
60 Ω
60 Ω
Power rating
100 W
100 W
200 W
300 W
WARNING! The brake resistance must be 39 Ω or greater to ensure the drive’s maximum regeneration switching current (10 A) is not exceeded.
Failure to observe the minimum resistance could result in damage to the drive. See
Brake (X1) on page 140 .
Dimensions of brake resistors are shown in
Brake resistors
on page
169
.
* The brake resistors listed in the table above can withstand a brief overload of 10 times the rated power for 5 seconds. Please contact ABB if larger power ratings are required.
144 Technical data
Resistor derating
The brake resistors shown in the previous table can achieve their stated power rating only when mounted on a heat sink. In free air a derating must be applied.
Furthermore, in ambient temperatures greater than 25 °C (77 °F), a temperature derating must be applied.
Resistor part number
RGJ139
RGJ160
Nominal power rating
(W)
100
In free air
Derate power linearly from:
80% @ 25 °C (77 °F) to
70% @ 55 °C (113 °F)
On heat sink
Derate power linearly from:
100% @ 25 °C (77 °F) to
88% @ 55 °C (113 °F)
RGJ260
RGJ360
200
300
Derate power linearly from:
70% @ 25 °C (77 °F) to
62% @ 55 °C (113 °F)
Typical heat sink:
200 mm x 200 mm x 3 mm
Derate power linearly from:
100% @ 25 °C (77 °F) to
88% @ 55 °C (113 °F)
Typical heat sink:
400 mm x 400 mm x 3 mm
Duty cycle
The braking duty cycle is the amount of time taken braking as a proportion of the overall application cycle time. For example, the following diagram shows a system which performs a trapezoidal move profile, with braking during part of the deceleration phase.
The braking duty is 0.2 (0.5 second braking / 2.5 second cycle time): v
0.5 s
Deceleration time
0.5 s
Braking active
0.5 s
2.5 s
(Cycle time)
2.5 s
(Cycle time)
2.5 s
(Cycle time) t
Technical data 145
Input / output
Analog inputs AIN0, AIN1 (X4)
Description
Type
Common mode voltage range
Common mode rejection
Input impedance
Input ADC resolution
Equivalent resolution
Sampling interval
Unit
V DC dB k Ω bits mV
µs
All models
Differential
±10
40
60
12
(includes sign bit)
±4.9
1000 (Mint)
250 (Control loop)
Analog output AOUT0 (X4)
Description
Type
Output voltage range
Output current (max)
Output DAC resolution
Equivalent resolution
Update interval
Unit
V DC mA bits mV ms
All models
Bipolar
±10
1
12
(includes sign bit)
±4.9
1
Digital inputs STO1, STO2 (X3)
See
Technical data: Digital inputs STO1, STO2 (X3)
on page
177
.
146 Technical data
Digital inputs DIN0, DIN3 (X3)
Description
Type
Input voltage
Nominal
Minimum
Maximum
Active
Inactive
Input current (maximum, per input)
Sampling interval
Minimum pulse width
Unit
V DC mA ms
µs
Digital inputs DIN1, DIN2 - high speed (X3)
Unit Description
Type
Input voltage
Nominal
Minimum
Maximum
Active
Inactive
Input current (maximum, per input)
Sampling interval
Minimum pulse width
Minimum step time
Minimum space time
Direction input setup time
Direction input hold time
V DC ns ns ns mA ms ns ns
All models
Opto-isolated inputs
24
12
30
> 12
< 2
50
1
5
All models
Opto-isolated inputs
250
250
250
100
100
24
12
30
> 12
< 2
20
1
Technical data 147
Digital inputs DIN4 - DIN9 (OPT1)
Description
Type
Input voltage
Nominal
Minimum
Maximum
Active
Inactive
Input current (maximum, per input)
Sampling interval
Minimum pulse width
Unit
V DC mA ms
µs
All models
Opto-isolated inputs
Digital outputs DOUT0 (Status), DOUT1, DOUT2 (X3)
Description
User supply (maximum)
Output current (maximum)
Fuse:
Approximate trip current
Reset time
Update interval
Unit
V DC mA mA s ms
All models
28
100
200
< 20
1
24
12
30
> 12
< 2
50
1
5
Digital outputs DOUT3 - DOUT6 (OPT1)
Description
User supply (maximum)
Output current (maximum)
Fuse:
Approximate trip current
Reset time
Update interval
Unit
V DC mA mA s ms
All models
28
100
200
< 20
1
148 Technical data
Incremental encoder interface (X8)
Unit Description
Encoder interface
Maximum input frequency
(quadrature)
Hall inputs
Output power supply to encoder
Maximum recommended cable length
MHz
BiSS encoder interface (X8)
Description
BiSS encoder interface
Operating mode
(Baldor motors)
Unit
All models
RS422 A/B Differential, Z index
8
RS422 A/B Differential
5 V DC (±7%), 400 mA max.*
30.5 (100 ft)
Output power supply to encoder
Maximum recommended cable length
All models
Differential Data and Clock
Single or multi-turn.
A wide range of devices can be supported. Contact ABB technical support before selecting a device.
5 V DC (±7%), 400 mA max.*
30.5 (100 ft)
SSI encoder interface (X8)
Description
SSI encoder interface
Operating mode
(Baldor motors)
Output power supply to encoder
Maximum recommended cable length
Unit All models
Differential Data and Clock
Single turn.
Positioning resolution up to 262144 counts/rev (18-bit).
Contact ABB technical support before selecting a device.
5 V DC (±7%), 400 mA max.*
30.5 (100 ft)
* Total current for this encoder and extra incremental encoder, which may be connected simultaneously (see page 86 ).
Technical data 149
SinCos / EnDat encoder interface (X8)
Description
Absolute encoder interface
Unit
Operating mode
(Baldor motors)
All models
EnDat / SinCos differential inputs and data input
Single or multi-turn.
512 or 2048 Sin/Cos cycles per turn, with absolute positioning resolution of up to
65536 steps.
Output power supply to encoder
Maximum recommended cable length
(Many other encoder specifications are supported - contact ABB.)
5 V DC (±7%), 400 mA max.*
30.5 (100 ft)
Smart Abs encoder interface (X8)
Description
Smart Abs encoder interface
Operating mode
Output power supply to encoder
Maximum recommended cable length
Unit All models
Differential Data
Single or multi-turn.
A wide range of devices can be supported. Contact ABB technical support before selecting a device.
5 V DC (±7%), 400 mA max.*
30.5 (100 ft)
* Total current for this encoder and extra incremental encoder, which may be connected simultaneously (see page
86
).
Ethernet interface (E1, E2)
Description
Signal
Protocols
Bit rates
Unit
Mbit/s
All models
2 twisted pairs, magnetically isolated
EtherCAT®
& TCP/IP
100
150 Technical data
Ambient conditions
Description
Operating temperature range
Minimum
Maximum
Derate
Storage temperature range
Humidity (maximum)
Forced air cooling flow
(vertical, from bottom to top)
Maximum installation altitude
(above m.s.l.)
Shock
Vibration
Unit
V DC
All models
°C
+0
+45
See Temperature derating on page
132 .
°F
+32
+113
See Temperature derating on page
132 .
% m/s m ft
-40 to +85 -40 to +185
3 A
None required
93
6 A
1
9 A
2.5
1000
Derate 1.1% / 100 m over 1000 m
3300
Derate 1.1% / 330 ft over 3300 ft
10 G
1 G, 10-150 Hz
Technical data 151
Applicable standards
MicroFlex e150 complies with the following standards.
Design and test standards
UL508C: Power Conversion Equipment.
UL840: Insulation coordination including clearance and creepage distances for electrical equipment.
EN 61800-5-1:2007 Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
EN 60529:1991 + A1:2000 Degrees of protection provided by enclosures.
EN 61800-3:2004 Electromagnetic compatibility. When installed as directed in this manual, MicroFlex e150 conforms to the category C2 emission limits and the ‘second environment’ immunity requirements defined by this standard.
See also the
CE Declaration of Conformity
on page
156
.
Environmental test standards:
EN 60068-1:1994 Environmental testing, general and guidance.
EN 60068-2-1:2007 Environmental testing, Test A. Cold.
EN 60068-2-2:2007 Environmental testing, Test B. Dry heat.
EN 60068-2-6:2008 Environmental testing, Test Fc. Vibration (sinusoidal).
EN 60068-2-27:2009 Environmental testing, Test Ea. Shock.
EN 60068-2-30:2005 Environmental testing, Test Db. Damp heat, cyclic.
EN 60068-2-31:2008 Environmental testing, Test Ec. Rough handling shocks
EN 60068-2-78:2001 Environmental testing, Test Cab. Damp heat, steady state.
Functional safety standards:
IEC 61508:2010 Functional safety of electrical/electronic/programmable electronic safety-related systems.
IEC 61800-5-2:2007 Adjustable speed electrical power drive systems: Safety requirements, Functional.
EN ISO 13849-1:2008 Safety of machinery: Safety-related parts of control systems,
Basic principles.
IEC 62061:2005 Safety of machinery: Functional safety of safety-related electrical, electronic and programmable electronic control systems
Marks
See also CE marking on page 153 for general recommendations for CE compliance.
152 Technical data
EtherCAT Conformance Test Certificate
Technical data 153
Degree of protection
MicroFlex e150 complies with EN 60529, IP20 provided connector X1 is shrouded.
For UL purposes the MicroFlex e150 is defined as an open-type, single or three phase, single axis servo amplifier.
The drive must be installed in a cabinet to fulfil the requirements for shielding from contact. Access to the cabinet should be restricted to trained maintenance staff.
NOTE: The top surface of cabinets / enclosures which are accessible when the equipment is energized shall meet at least the requirement of protective type IP3x with regard to vertical access only.
Materials
Drive enclosure
Package
Disposal
Side cover: PC+ABS-FR Bayblend FR3010 Black
Front Cover: PC/ABS GN-5001RFH Lupoy Light grey RAL9002
Heat sink: Die cast Aluminium LM6
Cardboard.
The drive contains raw materials that should be recycled to preserve energy and natural resources. The package materials are environmentally compatible and recyclable. All metal parts can be recycled. The plastic parts can either be recycled or burned under controlled circumstances, according to local regulations.
Most recyclable parts are marked with recycling marks.
The electrolytic DC capacitors and Integrated Power Module are classified as hazardous waste within the EU and must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions, please contact your local ABB distributor.
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the
European, EMC, and machinery directives.
Compliance with the European EMC Directive
The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within the European Union. The EMC product standard EN 61800-3 covers requirements stated for drives. See section Compliance with the EN 61800-3 below.
154 Technical data
Compliance with the EN 61800-3
Definitions
EMC stands for E lectro m agnetic C ompatibility. It is the ability of electrical/electronic equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or system within its locality.
First environment
includes establishments connected to a low-voltage network which supplies buildings used for domestic purposes.
Second environment
includes establishments connected to a network not supplying domestic premises.
Drive of category C2:
drive of rated voltage less than 1000 V and intended to be installed and started up only by a professional when used in the first environment.
Note: A professional is a person or organization having necessary skills in installing and/or starting up power drive systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second environment and not intended for use in the first environment.
Category C2
The drive complies with the standard with the following provisions:
1. The drive is equipped with a suitable EMC filter; see Power supply filters on page
138 .
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. Maximum cable length is 30 meters.
WARNING!
The drive can cause radio interference if used in residential or domestic environment. The user is required to take measures to prevent interference, in association to the requirements for the CE compliance listed above, if necessary.
Category C3
The drive complies with the standard with the following provisions:
1. The drive is equipped with a suitable EMC filter; see Power supply filters on page
138 .
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. Maximum cable length is 30 meters.
Technical data 155
WARNING!
A drive of category C3 is not intended to be used on a low-voltage public network which supplies domestic premises. Radio frequency interference is expected if the drive is used on such a network.
Compliance with the European Machinery Directive
This safety related drive complies with the European Union Machinery Directive requirements for a safety component intended to be integrated into machinery.
Compliance with the machinery directive has been verified according to standards
IEC 61800-5-2:2007, EN ISO 13849-1:2008, IEC 62061:2005, and IEC 61508:2010 parts 1 & 2. The drive has been designed, constructed and equipped in such a way that when installed as instructed in this manual, all hazards of an electrical nature are, or can be, prevented. The drive complies with EN 61800-5-1 which specifies safety requirements in terms of electrical, thermal and energy.
Note: The final assembler of the machinery must take the necessary precautions to prevent all hazards of an electrical nature when integrating this equipment. General specifications for design of electrical equipment of machinery is given in EN 60204-1 and EN 60204-11. Specifications for electrical equipment are also given in many standards for specific categories of machinery.
Validating the operation of the Safe Torque Off function
See Appendix: Safe Torque Off (STO) on page 173 .
156 Technical data
CE Declaration of Conformity
EC Declaration of Conformity
(In accordance with EN ISO/IEC 17050-1: 2010 and
EC Directives 2004/108/EC & 2006/42/EC)
Address: 6 Bristol Distribution Park, Hawkley Drive, Bristol, BS32 0BF, U.K.
In accordance with the following Directive(s):
2004/108/EC Electromagnetic Compatibility Directive
2006/42/EC Machinery Directive
Hereby declare that the following safety component:
MicroFlex e150 Integrated safe-torque-off drive with type markings:
E152A (followed by additional alpha-numeric digits to signify product variant)
Is in conformity with the applicable requirements of the following documents:
Standard: Title:
EN 61800-3 Adjustable Speed Electrical Power Drive Systems Part 3:
EMC Requirements and Specific Test Methods.
EN 61800-5-1 Adjustable Speed Electrical Power Drive Systems Part 5-1:
Edition/date:
2004
2007
Safety requirements - Electrical, thermal and energy .
EN 61800-5-2 Adjustable Speed Electrical Power Drive Systems Part 5-2:
Safety requirements - Functional .
EN ISO 13849-1 Safety of machinery Safety-related parts of control systems Part 1:
General principles for design.
EN 62061 Safety of machinery Functional safety of safety-related electrical, electronic and programmable electronic control systems.
In addition the safety function is certified by EC-type examination:
TÜV NORD Systems GmbH & Co. KG
Branch South
2007
2008
2005
Halderstr. 27
86150 Augsburg, Germany
Notified Body No. 0044
Certification No. SLA-0041/2010
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications and is in accordance with the requirements of the Directive(s).
Signed: Date: 20 th
February 2012
Bob Combes
R & D Manager
ABB Ltd, Bristol, U.K
The technical documentation for the product is available from:
ABB Ltd, Bristol, BS32 0BF, U.K
Ref: DE00037-100
Technical data 157
UL marking
The MicroFlex e150 is C-UL US Listed only when used in conjunction with optional
Fan Tray (part FAN001-024, see page 164 ). The approval is valid with rated voltages.
When used without optional fan tray FAN001-024, the MicroFlex e150 is UL
Recognized.
UL checklist
• The drive is to be used in a heated, indoor controlled environment. The drive must be installed in clean air according to enclosure classification. Cooling air must be clean, free from corrosive materials and electrically conductive dust. See page
150
.
• The maximum ambient air temperature is 45 °C (113 °F) at rated current. The current is derated for 45 to 55 °C (113 to 131 °F).
• The drive is suitable for use in a circuit capable of delivering not more than
5,000 rms symmetrical amperes, 230 V maximum. The ampere rating is based on tests done according to UL 508C.
• The cables located within the motor circuit must be rated for at least 75 °C
(167 °F) in UL-compliant installations.
• Use copper conductors only.
• The input cable must be protected with fuses. Circuit breakers must not be used without fuses in the USA. Page 136 lists IEC fuses that are suitable for UL applications. For suitable circuit breakers, contact your local ABB representative.
• For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical Code (NEC) and any applicable local codes. To fulfill this requirement, use the UL classified fuses.
• For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code and any applicable provincial codes. To fulfill this requirement, use the UL classified fuses.
• The drive provides overload protection in accordance with the National Electrical
Code (NEC).
158 Technical data
Control system
The MicroFlex e150 can use two main control configurations:
• Servo (Position).
• Torque Servo (Current).
The configuration is selected using the Mint
CONFIG
keyword (object 5000h), or by using the Mint WorkBench System Configuration Wizard. Each configuration supports different control modes, selected using the Tools, Control Mode menu item or by using the
CONTROLMODE
keyword in the Command window (see the Mint help file). This sets the control mode switch (object 6060h).
Servo configuration
The servo configuration is the default configuration for the drive, allowing the motor control system to operate as a torque controller, a velocity controller or a position controller. This configuration comprises 3 nested control loops; a current control loop, a velocity control loop and a position control loop, as shown on page 159 .
The universal encoder interface reads rotor position from the encoder and estimates velocity. The commutation block uses the position to calculate the electrical angle of the rotor. The current sensor system measures U and V phase currents. These are fed into a current conversion block that converts them into quantities representing torque producing and magnetizing currents (the 'vector' currents which are locked to the rotor).
In the current control loop, a current demand and the final measured current values form the inputs to a PI (Proportional, Integral) control system. This control system generates a set of voltage demands that are fed into a PWM (pulse-width modulation) block. The PWM block uses the space-vector modulation method to convert these voltage demands into a sequence of U, V and W phase switching signals, which are applied to the output bridge of the drive. The PWM block uses the measured DC-bus voltage to compensate for variations in supply voltage.
The torque controller converts a torque demand into a current demand and compensates for various load non-linearities. A 2-stage notch or low-pass filter allows the effects of load compliance to be reduced. To avoid motor damage, a user-defined application current limit is also applied, as well as individual positive and negative torque limits.
In the velocity control loop, a velocity demand and measured velocity form the inputs to a PI control system. The output of the control system is a torque demand which, when the drive is operating as a velocity controller, forms the input to the current control loop.
Finally, in the position control loop, a position demand and measured position form the inputs to a PID (Proportional, Integral, Differential) control system incorporating velocity feedback, velocity feed-forward and acceleration feed-forward. The output of the position control system is a velocity demand which, when the drive is operating as a position controller, forms the input to the velocity control loop.
Technical data 159
160 Technical data
Torque servo configuration
The diagram on page 161 shows the torque-servo control configuration. Here, the velocity loop has been removed and the output of the position controller is fed into the current loop via the torque filters.
The torque servo configuration is useful when the drive is operating as a closed-loop position controller and settling time must be minimized. Although the servo configuration tends to give better velocity tracking when operating in position mode, settling times can be longer.
The control mode switch allows the drive to operate in either torque or position modes, but not velocity mode.
Technical data 161
162 Technical data
Accessories 163
12
Accessories
What this chapter contains
This section describes accessories and options that you might need to use with your
MicroFlex e150. Shielded (screened) cables provide EMI / RFI shielding and are required for compliance with CE regulations. All connectors and other components must be compatible with the shielded cable.
164 Accessories
Fan tray
The fan tray (part FAN001-024) provides sufficient cooling for the 6 A and 9 A
MicroFlex e150. The fan tray might be required for the 3 A model when operating in high ambient temperatures (see Temperature derating on page 132 ). The fan tray requires 23 - 27.5 V DC at 325 mA, which can be sourced from the same filtered control circuit supply used for the MicroFlex e150. The MicroFlex e150 is UL Listed
(file NMMS.E128059) when used in conjunction with the fan tray, mounted exactly as shown in the following diagram.
Fan tray
FAN001-024
Fan tray dimensions
94 ( 3.7
)
84 ( 3.3
)
Assembled MicroFlex e150 and fan tray
66 ( 2.6
)
All dimensions shown as mm ( inches
)
Position of fan tray mounting holes relative to
MicroFlex e150
Bottom of
MicroFlex e150
Fan tray
16
( 0.63
) (
4.5
0.18
)
It is important that the fan tray is mounted in close proximity to the MicroFlex e150 as shown above. Failure to do so will result in decreased cooling efficiency.
Accessories 165
Foot-mount filter (single phase only)
The single-phase foot-mount AC power filter (part FI0029A00) provides mounting holes for the MicroFlex e150 and fan tray. This allows the filter, fan tray and
MicroFlex e150 to use minimal panel mounting space. See pages 166 and 168 for details of filter FI0029A00.
Foot-mount filter FI0029A00
MicroFlex e150 E152A0...
Fan tray FAN001-024
24 V power supplies
A range of compact 24 V DIN rail mounting power supplies are available. The supplies include short circuit, overload, over-voltage and thermal protection.
Part
DR-75-24
DR-120-24
DR-240-24
Input voltage
110-230 V AC
Output voltage
24 V DC
Output rating
75 W (3.2 A)
120 W (5 A)
240 W (10 A)
166 Accessories
EMC filters
AC filters remove high frequency noise from the AC power supply, protecting the
MicroFlex e150. These filters also prevent high frequency signals from being transmitted back onto the power lines and help meet EMC requirements. To select the correct filter, see Power supply filters on page 138 .
Part Rated volts Rated amps @
40°C
Leakage current (mA)
Weight kg (lbs)
FI0014A00
FI0015A00
FI0015A02
FI0018A00
FI0018A03
FI0029A00
250
250
250
480
480
250
3
6
12
7
16
22
0.4
0.4
0.4
33
33
33
0.27 (0.6)
0.45 (0.99)
0.73 (1.61)
0.5 (1.1)
0.8 (1.76)
3.0 (6.6)
Filter dimensions, types FI0018A00 and FI0018A03:
B
F
M5
D E
Dimension
A
B
C
F
G
D
E
A
G
C
FI0018A00
Dimensions: mm (inches)
FI0018A03
190 (7.48)
160 (6.30)
250 (9.84)
220 (8.66)
180 (7.09)
20 (0.79)
4.5 (0.18)
71 (2.80)
40 (1.57)
235 (9.25)
25 (0.98)
5.4 (0.21)
70 (2.76)
45 (1.77)
Accessories 167
Filter dimensions, types FI0014A00, FI0015A00, FI0015A02:
D E A
F
G
L
H
C
K
B
J
Dimension
A
B
C
K
L
H
J
F
G
D
E
FI0014A00
85 (3.35)
54 (2.13)
40 (1.57)
65 (2.56)
75 (2.95)
27 (1.06)
12 (0.47)
29.5 (1.16)
5.3 (0.21)
6.3 (0.25)
13.5 (0.53)
Dimensions: mm (inches)
FI0015A00
113.5 (4.47)
57.5 (2.26)
46.6 (1.83)
FI0015A02
156 (6.14)
94 (3.70)
103 (4.06)
130.5 (5.14)
143 (5.63)
25 (0.98)
12.4 (0.49)
32.4 (1.28)
4.4 (0.17) 5.3 (0.21)
6 (0.24)
15.5 (0.61)
168 Accessories
Filter dimensions, type FI0029A00:
B
D
Dimension
A
B
C
D
E
F
C A
Dimensions mm (inches)
FI0029A00
255 (10.04)
100 (3.94)
244.5 (9.63)
70 (2.76)
40 (1.57)
20 (0.79)
F
E
Mounting keyhole and slot detail
G
H
J
G
K
Accessories 169
Brake resistors
Depending on the application, MicroFlex e150 might require an external brake resistor to be connected to pins R1 and R2 of connector X1. The brake resistor dissipates energy during braking to prevent an over-voltage error occurring. See section Brake (X1) on page 140 for details about choosing the correct resistor.
WARNING!
Electrical shock hazard. DC-bus voltages can be present at these terminals. Use a suitable heat sink (with fan if necessary) to cool the brake resistor. The brake resistor and heat sink (if present) can reach temperatures in excess of 80 °C (176 °F).
Brake resistor dimensions:
B
A C
E
F
G
D
Part Power
W
RGJ139 100
Res.
Ω
39
RGJ160
RGJ260
RGJ360
100
200
300
60
60
60
A
165
(6.49)
165
(6.49)
165
(6.49)
215
(8.46)
B
41
(1.61)
41
(1.61)
60
(2.36)
60
(2.36)
Dimensions mm (inches)
C D E
22
(0.87)
152
(5.98)
12
(0.47)
22
(0.87)
30
(1.18)
30
(1.18)
152
(5.98)
146
(5.75)
196
(7.72)
12
(0.47)
17
(0.67)
17
(0.67)
F
10
(0.39)
10
(0.39)
13
(0.51)
13
(0.51)
G
4.3
(0.17)
4.3
(0.17)
5.3
(0.21)
5.3
(0.21)
170 Accessories
Encoder breakout
The Encoder breakout (part OPT-MF-200) can be used to connect motor feedback and an extra incremental encoder (see page 80 ). Alternatively, the connectors can be used together to connect a single motor that has separate cables for encoder and
Halls (e.g. a linear motor).
OPT-MF-200
OPT-MF-200 MicroFlex e150
Motor feedback Incremental encoder
Accessories 171
Cables
A wide range of motor and feedback cables are available.
Motor power cables
For easier installation, it is recommended that a color-coded motor power cable is used. The part number for a BSM rotary motor power cable is derived as follows:
CBL 025 SP -12 S m
ft
1.5
5*
2.5
8.2
3.0
10*
5.0
16.4
6.1
20*
7.5
24.6
9.1
30*
10
32.8
15
49.2
15.2
50*
20 65.6
22.9
75*
30.5
100*
* North America only
SP BSM style threaded motor connector (motor end only)
WP SDM style threaded motor connector (motor end only)
RP Raw cable
(no connector)
Current
(Amps)
6
12
20
35
50
90
-
S
Standard connector
Stainless connector
Larger motors requiring 35 A cable or greater normally use terminal box connections, so a motor power connector is not required. For this reason connectors are not available on 35 A - 90 A cable.
Examples:
A 6.1 m cable, with a CE threaded standard connector, rated for 12 A has part number CBL061SP-12 .
A 30.5 m cable, with a CE threaded stainless steel connector, rated for 20 A has part number CBL305SP-20S .
A 50 ft cable, with no connector, rated for 50 A has part number CBL152RP-50 .
172 Accessories
Feedback cables
The part number for a feedback cable is derived as follows:
CBL 020 SF -E 1 S m
0.5
1.0
2.0
2.5
5.0
7.5
10
15
20
ft
1.6
3.3
6.6
8.2
16.4
24.6
32.8
49.2
65.6
SF BSM servo motor feedback cable with at least 1 connector
WF SDM servo motor feedback cable with at least 1 connector E
B
D
DF Servo motor feedback cable with drive connector only
RF
Raw cable
(no connector)
S
A
BiSS
EnDat
SinCos
Incremental encoder
SSI
Smart Abs
-
1
2
Raw cable
Legacy controllers e100 / e150
-
S
Standard connector
Stainless steel connector
Other lengths available on request
Example:
A 2 m encoder feedback cable for a MicroFlex e150 drive, with required connectors at both ends, has part number
CBL020SF-E2.
These feedback cables have the outer shield tied to the connector housing(s). If you are using an alternative cable with your chosen feedback device, be sure to obtain a cable that is a shielded twisted pair 0.34 mm
2
(22 AWG) wire minimum, with an overall shield. Ideally, the cable should not exceed 30.5 m (100 ft). Maximum wire-towire or wire-to-shield capacitance is 50 pF per 300 mm (1 ft) length, to a maximum of
5000 pF for 30.5 m (100 ft).
Ethernet cables
The cables listed in this table connect MicroFlex e150 to other Ethernet nodes such as NextMove e100, additional MicroFlex e150s, or other Ethernet compatible hardware. The cables are standard CAT5e shielded twisted pair (S/UTP) ‘crossover’
Ethernet cables:
Cable description
CAT5e Ethernet cable
Part
CBL002CM-EXS
CBL005CM-EXS
CBL010CM-EXS
CBL020CM-EXS
CBL050CM-EXS
CBL100CM-EXS
CBL200CM-EXS m
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Length ft
0.65
1.6
3.3
6.6
16.4
32.8
65.6
Appendix: Safe Torque Off (STO) 173
13
Appendix: Safe Torque Off
(STO)
What this chapter contains
The appendix describes the basics of the Safe torque off function (STO) for the
MicroFlex e150. In addition, application features and technical data for the safety system calculation are presented.
Basics
The STO function disables the control voltage of the power semiconductors of the drive output stage, which prevents the inverter generating the voltage required to rotate the motor (see diagram below). By using this function, short-time operations
(like cleaning) and/or maintenance work on non-electrical parts of the machinery can be performed without switching off the power supply to the drive.
The drive supports the Safe Torque Off (STO) function according to standards
IEC 61800-5-2, EN 61508:2010, EN ISO 13849-1 and IEC 62061:2005.
See Safety Manual: Safe Torque Off (STO) function for MicroFlex e150 drives
(LT0313...) before using the STO function.
174 Appendix: Safe Torque Off (STO)
MicroFlex e150
PWM control circuit
Safe Torque Off connections
X3:18
X3:8
Common
X3:19
X3:9
Safety circuit
(emergency stop switch, relay etc.
PWM power circuit
Drivers
High
U+
V+
W+
Low
U-
V-
W-
Integrated
Power
Module
DC+
DC-
X1:U
Motor output (U phase shown)
+24 V
+24 V
+0 V
WARNING!
The STO function does not disconnect the voltage of the main and auxiliary circuits from the drive. Therefore maintenance work on electrical parts of the drive or the motor can only be carried out after isolating the drive system from the main supply. If the drive was connected to the input power, wait for 5 minutes after disconnecting the input power.
Appendix: Safe Torque Off (STO) 175
Operation of the STO function and diagnostics
If both STO inputs are powered, the STO function is in the standby state and the drive operates normally. If power is removed from one or both of the STO inputs the STO function is activated, the drive’s motor output power stage is disabled, and the status output (page 69 ) becomes inactive. Starting is possible only after both STO inputs have been powered, and the fault has been cleared.
The
SAFETORQUEOFF
Mint keyword reports the status of the STO hardware registers.
SAFETORQUEOFF
contains an array of values indicating the states of the
STO1 and STO2 inputs, two internal hardware fault circuits, and one internal STO status output. This array is described in the following table:
Parameter
SAFETORQUEOFF(0)
SAFETORQUEOFF(1)
SAFETORQUEOFF(2)
SAFETORQUEOFF(3)
SAFETORQUEOFF(4)
SAFETORQUEOFF(5)
SAFETORQUEOFF(6)
Meaning
The combined state of the two STO inputs:
STO1 = bit 0, STO2 = bit 1
The state of STO1 input:
0 = not powered, 1 = powered
The state of STO2 input:
0 = not powered, 1 = powered
The combined state of the two hardware fault circuits:
STO1 = bit 0, STO2 = bit 1
The state of the STO1 internal hardware fault circuit:
0 = no fault, 1 = fault
The state of the STO2 internal hardware fault circuit:
0 = no fault, 1 = fault
The state of the internal STO status output:
0 = fault, 1 = no fault
See
Safety Manual: Safe Torque Off (STO) function for MicroFlex e150 drives
(LT0313...) for full details.
Status display
When an STO error occurs, the drive displays error code 10033,
10034 or 10035 on its front panel Drive Status display. The right decimal point is always (and only) illuminated for STO errors.
STO error
176 Appendix: Safe Torque Off (STO)
Installation
Typical input connections:
MicroFlex e150
Safe
Torque Off connections
X3:18
X3:8
X3:19
X3:9
Safety circuit
(emergency stop switch, relay etc.)
24 V
External Supply
+24 V
+0 V
Common
Note: If the contacts of the safety circuit do not open/close within 1 ms of each other, then a fault in the STO circuit or wiring is assumed and the drive will become disabled. The maximum allowed cable length between the drive and the activation switch is 30 m (98 ft).
Validating the operation of the Safe Torque Off function
IEC 61508 and EN 62061 require that the final assembler of the machinery validates the operation of the safety function with an acceptance test.
The acceptance test must be performed:
• at initial start-up of the safety function
• after any changes related to the safety function (wiring, components, settings, etc.)
• after any maintenance work related to the safety function.
If you connect an external Safe Torque Off circuit to the drive, perform the acceptance test for the Safe Torque Off function as described in
Safety Manual: Safe Torque Off
(STO) function for MicroFlex e150 drives (LT0313...).
Appendix: Safe Torque Off (STO) 177
Technical data: Digital inputs STO1, STO2 (X3)
Unit Description
Type
Input voltage
Nominal
Minimum
Maximum
Active
Inactive
Input current (maximum, per input)
Sampling interval
Minimum pulse width
V DC mA ms
µs
All models
Opto-isolated inputs
24
12
30
> 12
< 2
50
1
5
STO function: data related to safety standards
SIL
3
PFH
1.12 x 10
-10
(0.112 FIT)
/h
IEC 61508
HFT SFF
1 96.48%
PTI
10
years
PFD
1.12 x 10
-5
PL CCF
EN ISO 13849-1
MTTF
D
DC* Category e 75 points
20420.9
years
90% 3
* According to the categorization defined in EN ISO 13849-1:2008.
PFD
PFH
PL
PTI
SFF
SIL
STO
Abbreviation Reference
CCF EN ISO 13849-1
Description
Common Cause Failure (%)
DC
FIT
HFT
MTTF
D
IEC 61508
IEC 61508
Failure In Time: 1E-9 hours
Hardware Fault Tolerance
EN ISO 13849-1 Mean Time To dangerous Failure: (The total number of life units) / (the number of dangerous, undetected failures) during a particular measurement interval under stated conditions
IEC 61508
IEC 61508
IEC 61508
IEC 61508
IEC 61800-5-2
Probability of Failure on Demand
Probability of Dangerous Failures per Hour
EN ISO 13849-1 Performance Level: Corresponds SIL, Levels a-e
Proof Test Interval
Safe Failure Fraction (%)
Safety Integrity Level
Safe Torque Off
178 Appendix: Safe Torque Off (STO)
STO function: TüV certificate
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/drives and selecting Sales, Support and Service network .
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Training courses .
Providing feedback on ABB Drives manuals
Your comments on our manuals are welcome. Go to www.abb.com/drives and select
Document Library
–
Manuals feedback form (LV AC drives)
.
Document library on the Internet
You can find manuals and other product documents in PDF format on the Internet.
Go to www.abb.com/drives and select
Document Library.
You can browse the library or enter selection criteria, for example a document code, in the search field.
Contact us
ABB Oy
Drives
P.O. Box 184
FI-00381 HELSINKI
FINLAND
Telephone +358 10 22 11
Fax +358 10 22 22681 www.abb.com/drives
Baldor Electric Company
(A member of the ABB group)
5711 R.S Boreham, Jr. St.
P.O. Box 2400
Fort Smith, AR 72901
USA
Telephone
Fax
+1 479 646 4711
+1 479 648 5792 www.baldor.com
ABB Inc.
Automation Technologies
Drives & Motors
16250 West Glendale Drive
New Berlin, WI 53151
USA
Telephone 262 785-3200
1-800-HELP-365
780-5135 www.abb.com/drives
ABB Ltd
Motion Control
6 Bristol Distribution Park
Hawkley Drive
Bristol, BS32 0BF
United Kingdom
Telephone +44 (0) 1454 850000
Fax +44 (0) 1454 859001 www.abb.com/drives
ABB Beijing Drive Systems Co. Ltd.
No. 1, Block D, A-10 Jiuxianqiao Beilu
Chaoyang District
Beijing, P.R. China, 100015