Acson international WM10FW Installation Manual
Add to my manuals8 Pages
Acson international WM10FW is a wall mounted chilled water fan coil unit designed for cooling purposes. The unit is equipped with an electrostatic air purifying and deodorizing filter media and filter frame, which helps to remove microscopic dust, smoke, small invisible particles, unwanted smells, and odors from the air, keeping the room air clean and fresh. The unit also features an infrared remote control operating signal with a signal receiver on the indoor unit, which makes it easy to control the unit from a distance.
advertisement
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
WALL MOUNTED CHILLED WATER FAN COIL UNIT
MODEL
COOLING UNIT
Reference Model
WM10FW
WM15FW
WM20FW
WM25FW
Model
AWM10FW / MWM010FW / YWM10FW
AWM15FW / MWM015FW / YWM15FW
AWM20FW / MWM020FW / YWM20FW
AWM25FW / MWM025FW / YWM25FW
Part No.:A08019013031
1-1
IM-WMFW-0501
- Outline And Dimensions
- Safety Precautions
- Installation Diagram
- Installation Of Indoor Unit
- Electrical Wiring Connection
- Indicator Lights page i-ii page 2 page 3 page 3 page 4 page 5
CONTENTS
- Air Conditioner Unit Operation
- Standard Operating Conditions
- Optional : Electrostatic Filter
- Service And Maintenance
- Trouble Shooting
SAFETY PRECAUTIONS
Before installing the air conditioner unit, please read the following safety precautions carefully.
!
Warning
• Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance.
• All field wiring must be installed in accordance with the national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazards due to insulation failure.
• All electrical wiring must not touch the water piping or any moving parts of the fan motors.
• Confirm that the unit has been switched OFF before installing or servicing the unit.
page 6 page 6 page 7 page 8 page 8
IMPORTANT
DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
!
Caution
Please take note of the following important points when installing.
• Ensure that the drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
• Ensure that the units panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
1-2
Indoor Unit
Air Intake Grille
Air Discharge Louver
Air Discharge Grille
INSTALLATION DIAGRAM
Air Filters
Front Frame
Back Housing
On/Off Switch
Indicator
Lights
Signal
Receiver
Drain Hose
Water Piping
Chiller
Outdoor Unit
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it. Also, this location must be suitable for piping and drainage, and be away from doors or windows.
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for smooth drainage. Avoid situations that are likely to cause water to leak.
Water Drainage
Air Flow
Direction
Maintenance &
Servicing Space
Plate Mounting Installation
Screw Position
In The Wall
Water
Leaking
Water
Leaking
Water
Leaking
End
Dipped
Into
Water
Drain
Correct Wrong Wrong Wrong
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the installation plate (Engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate).
Ensure that the hooks are properly seated on the installation plate by moving it to the left and right.
Ø 65.0 mm Hole
In The Wall
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars.
Use the level gauge for horizontal mounting, and fix it with
4 suitable screws.
In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall
(see figure).
Hole With Cone Drill
Indoor Side Outdoor Side
1. Hook the unit onto the installation plate.
2. A unit support plate can be used to hold the unit in a slanted position (See figure) to ease piping installation work.
3. Fix the screw underneath after completing installation.
1-3
ELECTRICAL WIRING CONNECTION
Cooling unit
IMPORTANT : The figures shown in the table are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also subject to the type of installation and conductors used.
Model
Voltage range
Power supply cable size mm 2
Number of wire
Interconnection Cable size mm 2
Number of wire
Recommended Fuse A
07 / 10 / 15 20 / 25
220V – 240V
1Ph / 50Hz +
1.5
3
1.5
3
15
2.5
3
2.5
3
20
• All wires must be firmly connected.
• All wires must not touch the water piping, or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps as shown in the figure.
• The power supply cord must be equivalent to H05RN-F
(245IEC57) which is the minimum requirement.
WM 10 FW ~ 25 FW
Wire Clamp
Interconnection cable
Power Supply
Cable
1-4
Water Piping Connection
The indoor unit is equipped with water outlet and inlet bare connection. There is an air-vent for air purging that is fitted at the outlet water header.
3 ways solenoid valve is required for cycling off or bypass the chilled water.
Black steel pipe, polyethrene pipe, PVC pipe and copper tube are recommended in field installation.
All types of piping and connection must be insulated by polyurethane (ARMAFLEX type or equivalent) to avoid condensation.
Do not use contaminated or damaged pipe and fitting for installation.
Some main fitting components are needed in the system to enhance the capacity and ease of service, such as gate valve, balancing valve, 2 ways or 3 ways solenoid valve, filter, strainer etc.
INDICATOR LIGHTS
IR Signal Receiver
When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit will make a <beep> sound to confirm acceptance of the signal transmission.
IR Receiver
LED Indicator Lights
Cooling Unit
The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions.
The LED indicator lights are located at the bottom right side of the air conditioner unit.
LED Indicator Lights For Cooling Unit
Cool mode Dry mode
Fan mode Sleep mode
Heat Pump Unit
The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions.
The LED indicator lights are located at the bottom right side of the air conditioner unit.
LED Indicator Lights For Heat Pump Unit
Cooling mode Dry mode
Heat / Fan mode
(red / green)
Sleep mode
1-5
LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit
Cool Dry
ON
Sleep Heat Fan
Operation / Fault Indication
Cool mode
Heat mode
Fan mode
Dry mode
Room sensor missing
Pipe sensor missing
ON or OFF
* Dry mode = Cool mode at low fan
Action
–
–
–
–
–
–
Blinking
AIR CONDITIONER UNIT OPERATION
Dry Mode
• When the air humidity is high, the unit can operate in dry mode. Press <MODE> button and choose <DRY>.
• If the room temperature is 2°C higher than the set temperature, the air conditioner will operate under cooling mode until it reaches within the 2°C range of difference compared to the set temperature before it converts to dry mode.
• If the room temperature is within the 2°C range of difference compared to the set temperature, it will directly operate under dry mode.
• The unit will operate at LOW speed under dry mode.
Horizontal Air Flow Control
• For more effective air circulation, you can manually adjust the air discharge grille to the left or right.
• During cool mode operation and dry mode operation, do not direct the air discharge louver downwards for too long. If operating continues in this way, condensation may occur on the louver, thus resulting in drippings.
Fan Speed And Rated Cooling Capacity
• The rated cooling capacity is provided at the maximum fan speed.
• The cooling capacity is lower when the unit is operating at MEDIUM and LOW fan speed.
Horizontal
Cooling Unit
Temperature
Minimum indoor temperature
Maximum indoor temperature
Minimum outdoor temperature
Maximum outdoor temperature
Ts ºC
19.4
26.7
19.4
46
STANDARD OPERATING CONDITIONS
Th °C
13.9
19.4
13.9
24
Ts: Dry bulb temperature.
Th: Wet bulb temperature.
1-6
OPTIONAL : ELECTROSTATIC FILTER
Action 1-
Dual Action Electrostatic Air Purifying And
Deodorizing Filter Media And Filter Frame
Electrostatic Air Purifying Filter
Action 2-
Deodorizing Filter
Removes microscopic dust, smoke and small invisible particles to keep the room air clean with pre-charged electrostatic polypropylene filter.
Removes unwanted smells and odors in the air and keeps the room air fresh with activated carbon filter.
A) To Open The Filter Frame
Pull Upwards To Open
How To Install
Step 1
Push This Part
C) To Close The Filter Frame
Press Downward
To Lock
B) To insert the dual action filter
Ionizer Filter Top
Electrostatic Air
Purifying Filter
(White Colour)
Deodorizing
(Black Colour)
Place Filter Into
The Filter Frame
Ionizer Filter Bottom
Insert Top First
Step 2
Open The
Front Frame
Grille
Insert The Dual Action
Electrostatic And
Deodorizing Filters Into
The Slot
Slide Out The
Original Filters
Slide Back The
Original Filter
!
Caution
1. The electrostatic air purifying and deodorizing filter should be replaced once every 6 months or when the filter changes color to brownish, whichever is sooner.
2. Used dusty filters should be disposed and shouldn't be reused, even if it has been cleaned and washed.
3. The filter is a consumable part which you can purchase from your air conditioner dealer.
4. Use the new filter immediately once it has been taken out from its sealed packing. Do not unpack the new filter too early before it is actually used as this may decrease its deodorizing effect.
1-7
!
Warning
• Disconnect from the main power supply before servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fire hazards.
Service Parts
Indoor air filter
Indoor unit
SERVICE AND MAINTENANCE
Maintenance Procedures
1. Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Do not use gasoline, volatile substances or chemicals to clean the filter.
1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40°C) and a neutral detergent solution.
2. Do not use gasoline, volatile substances or chemicals to clean the indoor unit.
Period
At least once every 2 weeks.
More frequently if necessary.
At least once every 2 weeks.
More frequently if necessary.
!
Caution
Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat.
When The Unit Is Not To Be Used For An Extended Long Period Of Time
Operate the unit for 2 hours with the following setting.
Operating mode : cool
Temperature : 30°C
Remove the power plug.
If you are using an independent electric circuit for your unit, cut off the circuit.
Remove the batteries in the remote control.
TROUBLE SHOOTING
If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit.
Check the following fault conditions and causes for some simple trouble shooting tips.
Fault
1. The air conditioner unit does not operate.
2. The air flow is too low.
3. Discharge air flow has bad odor.
4. Condensation on the front air grille of the indoor unit.
Causes / Action
– Power failure, or the fuse needs to be replaced.
– The power plug is disconnected.
– If the fault persist after all these verifications, please contact the air conditioner unit installer.
– The air filter is dirty.
– The doors or windows are open.
– The air suction and discharge are clogged.
– The regulated temperature is not high enough.
– Odors may be caused by cigarettes, smoke particles, perfume etc.
which might have adhered onto the coil.
– This is caused by air humidity after an extended long period of operation.
– The set temperature is too low, increase the temperature setting and operate the unit at high fan speed.
– Switch off unit and call dealer.
5. Water flowing out from the air conditioner unit.
If the fault persists, please call your local dealer / serviceman.
1-8