ALTV244UL3 Series
CCTV Power Supplies
Installation Guide
Models Include:
ALTV244UL3
- 24VAC @ 3.5A (85VA) or
28VAC @ 3A (85VA).
- Four (4) Fuse Protected Outputs.
- Factory installed 3-wire line cord.
ALTV244ULX3
- 24VAC @ 3.5A (85VA) or
28VAC @ 3A (85VA).
- Four (4) Fuse Protected Outputs.
- Factory installed 3-wire line cord.
ALTV244175UL3
- 24VAC @ 7A (175VA) or
28VAC @ 10A (300VA).
- Four (4) Fuse Protected Outputs.
- Factory installed 3-wire line cord.
ALTV244ULCB3
- 24VAC @ 3.5A (85VA) or
28VAC @ 3A (85VA).
- Four (4) PTC Protected Outputs.
- Factory installed 3-wire line cord.
ALTV244175ULCB3
- 24VAC @ 7A (175VA) or
28VAC @ 10A (300VA).
- Four (4) PTC Protected Outputs.
- Factory installed 3-wire line cord.
More than just power.
TM Rev. 040406
Overview:
Altronix ALTV244UL3 Series CCTV Power Supplies provide 24VAC or 28VAC distributed via four (4) fuse or
PTC protected outputs for powering CCTV cameras, heaters and other video accessories.
Four (4) Output ALTV244UL3 Reference Chart:
Altronix
Model Number
ALTV244UL3
ALTV244ULX3
ALTV244ULCB3
24VAC 3.5A
28VAC 3A
24VAC 3.5A
28VAC 3A
24VAC 3.5A
28VAC 3A
ALTV244175UL3
24VAC 7A
28VAC 6.25A
ALTV244175ULCB3
24VAC 7A
28VAC 6.25A
4
4
4
4
4
–
–
P
–
P
P
P
–
P
–
3.5A
3.5A
3.5A
3.5A
2.5A
3.5A
3.5A
2.5A
–
–
5A/
250V
5A/
250V
5A/
250V
10A/
250V
10A/
250V
3.5A/
250V
0.9A
3.5A/
250V
0.9A
3.5A/
250V
0.9A
– 1.76A
– 1.76A
Agency Listings:
• UL Listed for Commercial CCTV Equipment
(UL 2044).
CUL Listed - CSA Standard C22.2 No.1-98,
Audio, Video and Similar Equipment.
• CE European Conformity.
Input:
• 115VAC, 50/60Hz.
Output:
• Four (4) fuse or PTC protected outputs.
• 24VAC or 28VAC output.
• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
• Surge suppression.
Features:
• Power ON/OFF switch
(ALTV244UL3, ALTV244ULX3, and
ALTV244ULCB3).
Specifications:
Features
(cont’d)
:
• Illuminated power disconnect circuit breaker
with manual reset
(ALTV244175UL3 and ALTV244175ULCB3).
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates
costly labor.
• Spare fuses included (on fuse protected models).
Enclosure Dimensions
(H x W x D)
:
• ALTV244UL3, ALTV244ULCB3
8.5” x 7.5” x 3.5”
(215.9mm x 190.5mm x 88.9mm).
• ALTV244175UL3, ALTV24175ULCB3
12” x 7.5” x 4.5”
(304.8mm x 190.5mm x 114.3mm).
• ALTV244ULX3
13.5” x 13” x 3.25”
(342.9mm x 330.2mm x 82.6mm).
Installation Instructions:
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 10-12). Secure enclosure to earth ground.
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3,
ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).
- 2 - ALTV244UL3 Series
3. All units are factory set for 24VAC operation.
For 28VAC operation adjust unit prior to applying power as follows:
Remove wires marked [24V] and [28V] from terminals marked [P] and [S].
Connect wire marked [28V] to terminal marked [P] and connect wire marked [24V] to terminal marked [S].
Note: ALTV244ULCB3 set for 28VAC operation is not Class 2 Rated, not power-limited.
4. Plug in 3-wire line cord (Figs. 1-5, pgs. 4-8).
Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided. Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3,
ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
Terminals marked [1P - 4P] are of the same polarity.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage.
7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3,
ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).
8.
Connect devices to the terminals marked [1P] - [1N] through [4P] - [4N] on PD4 or PD4CB board
(Figs. 1-5, pgs. 4-8), carefully observing polarity.
9. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3,
ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).
10. Green LED will illuminate when power is present.
11. Upon completion of the wiring, secure enclosure door with screws (supplied).
Installation of a cam lock is optional.
Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical
Code and all local codes. Use 75˚C or higher rated UL insulated wiring for connecting the unit to the mains.
Replace fuses with the same type and rating (refer to Four (4) Output ALTV244UL3 Reference Chart, pg. 2).
PD4/PD4CB - Distribution Module
1P - 4P
1N - 4N
AC output.
AC output.
Terminal Identification:
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
ALTV244UL3 Series - 3 -
Fig. 1 - ALTV244UL3
3.5A 250V 3.5A 250V 3.5A 250V
24VAC or 28VAC Output 1
Follow same procedure using terminals
2P & N through 4P & N for outputs 2 through 4)
LED
1P 1N 2P 2N 3P 3N 4P 4N
Class 1 Outputs
N P S
Primary
In-line
Fuse
XFMR non power- limited
Black Lead
White Lead
Green
Lead (ground)
Input 115VAC,
50/60Hz
Voltage Selection
Configuration
N P S
24VAC
Output
24V 28V
28VAC
Output
N P S
28V 24V
- 4 - ALTV244UL3 Series
Fig. 2 - ALTV244ULCB3
24VAC or 28VAC Output 1
Follow same procedure using terminals
2P & N through 4P & N for outputs 2 through 4)
LED
1P 1N 2P 2N 3P 3N 4P 4N
24VAC configuration Class 2 Not Wet/Class 3 Wet
28VAC configuration Class 1 N P S
Primary
In-line
Fuse
XFMR non power- limited
Black Lead
White Lead
Green
Lead (ground)
Input 115VAC,
50/60Hz
Voltage Selection
Configuration
N P S
24VAC
Output
24V 28V
28VAC
Output
N P S
28V 24V
ALTV244UL3 Series - 5 -
Fig. 3 - ALTV244ULX3
Class 1
Outputs
ON OFF
MAIN FUSE
Black Lead
White Lead
Primary
In-line Fuse non power- limited
Input 115VAC,
50/60Hz
Voltage Selection
Configuration
N P S
24VAC
Output
24V 28V
28VAC
Output
N P S
28V 24V
- 6 - ALTV244UL3 Series
Fig. 4 - ALTV244175UL3
3.5A 250V 3.5A 250V 3.5A 250V
24VAC or 28VAC
Output 1
Follow same procedure using terminals
2P & N through
4P & N for outputs 2 through 4)
LED
1P 1N 2P 2N 3P 3N 4P 4N
Class 1 Outputs
N P S
Illuminated Power Disconnect
Circuit Breaker with manual reset
Voltage Selection
Configuration
N P S
24VAC
Output
24V 28V
Green
Lead (ground) non power- limited
Black Lead
White
Lead
Input 115VAC,
50/60Hz
28VAC
Output
N P S
28V 24V
ALTV244UL3 Series - 7 -
Fig. 5 - ALTV244175ULCB3
24VAC or 28VAC
Output 1
Follow same procedure using terminals
2P & N through
4P & N for outputs 2 through 4)
LED
1P 1N 2P 2N 3P 3N 4P 4N
24VAC configuration Class 2 Not Wet/Class 3 Wet
28VAC configuration Class 1 N P S
Illuminated Power Disconnect
Circuit Breaker with manual reset
Voltage Selection
Configuration
N P S
24VAC
Output
24V 28V
Green
Lead (ground) non power- limited
Black Lead
White
Lead
Input 115VAC,
50/60Hz
28VAC
Output
N P S
28V 24V
- 8 - ALTV244UL3 Series
Notes:
ALTV244UL3 Series - 9 -
Enclosure Dimensions
(H x W x D)
for:
• ALTV244UL3
• ALTV244ULCB3
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm)
7.25”
(184.15mm)
3.625”
(184.15mm)
0.6”
(15.24mm)
1.125”
(28.575mm)
6.05”
(153.67mm)
1.25”
(31.75mm)
3.5”
(88.9mm)
0.6”
(15.24mm)
1.125”
(28.575mm)
2”
(50.8mm)
1.25”
(31.75mm)
2”
(50.8mm)
8.125”
(206.375mm)
1”
(25.4mm)
0.6”
(15.24mm)
1”
(25.4mm)
6.05”
(153.67mm)
5.25”
(133.35mm)
1”
(25.4mm)
0.6”
(15.24mm)
3.5”
(88.9mm)
1”
(25.4mm)
1”
(25.4mm)
1.25”
(31.75mm)
- 10 - ALTV244UL3 Series
Enclosure Dimensions
(H x W x D)
for:
• ALTV244ULX3
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
1.40”
(36mm)
4.85”
(123mm)
4.85”
(123mm)
1.40”
(36mm)
1.20”
(31mm)
0.75”
(19mm)
12.5”
(318mm)
11.0”
(279mm)
1.40”
(36mm)
1.20”
(31mm)
3.25”
(83mm)
0.75”
(19mm)
0.9375”
(24mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
13.0”
(330mm)
5.10”
(130mm)
6.5625”
(167mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
(25mm)
10.5”
(267mm)
0.9375”
(24mm)
1.0”
(25mm)
3.25”
(83mm)
1.0”
(25mm)
3.25”
(83mm)
ALTV244UL3 Series - 11 -
Enclosure Dimensions
(H x W x D)
for:
• ALTV244175UL3
• ALTV244175ULCB3
12” x 7.5” x 4.5” (304.8mm x 190.5mm x 114.3mm)
7.5”
(190.5mm)
4.5”
(114.3mm)
1.5”
(12.7mm)
1.25”
(31.75mm)
3.5”
(88.9mm)
12”
(304.8mm)
2.5”
(63.5mm)
3.5”
(88.9mm)
1”
(25.4mm)
0.5”
(12.7mm)
1.11”
(28.19mm)
0.5”
(12.7mm)
1.11”
(28.19mm)
4.5”
(114.3mm)
7.5”
(190.5mm)
1”
(25.4mm)
0.88”
(22.35mm)
5.75”
(146.05mm)
4.5”
(114.3mm)
0.88”
(22.35mm)
1”
(25.4mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(12.7mm)
3.5”
(88.9mm)
12”
(304.8mm)
5.88”
(149.35mm)
1.13”
(28.7mm)
Altronix is not responsible for any typographical errors.