Altronix ALTV244ULCB3, ALTV244ULX3 Installation Manual

Add to my manuals
12 Pages

advertisement

Altronix ALTV244ULCB3, ALTV244ULX3 Installation Manual | Manualzz

ALTV244UL3 Series

CCTV Power Supplies

Installation Guide

Models Include:

ALTV244UL3

- 24VAC @ 3.5A (85VA) or

28VAC @ 3A (85VA).

- Four (4) Fuse Protected Outputs.

- Factory installed 3-wire line cord.

ALTV244ULX3

- 24VAC @ 3.5A (85VA) or

28VAC @ 3A (85VA).

- Four (4) Fuse Protected Outputs.

- Factory installed 3-wire line cord.

ALTV244175UL3

- 24VAC @ 7A (175VA) or

28VAC @ 10A (300VA).

- Four (4) Fuse Protected Outputs.

- Factory installed 3-wire line cord.

ALTV244ULCB3

- 24VAC @ 3.5A (85VA) or

28VAC @ 3A (85VA).

- Four (4) PTC Protected Outputs.

- Factory installed 3-wire line cord.

ALTV244175ULCB3

- 24VAC @ 7A (175VA) or

28VAC @ 10A (300VA).

- Four (4) PTC Protected Outputs.

- Factory installed 3-wire line cord.

More than just power.

TM Rev. 040406

Overview:

Altronix ALTV244UL3 Series CCTV Power Supplies provide 24VAC or 28VAC distributed via four (4) fuse or

PTC protected outputs for powering CCTV cameras, heaters and other video accessories.

Four (4) Output ALTV244UL3 Reference Chart:

Altronix

Model Number

ALTV244UL3

ALTV244ULX3

ALTV244ULCB3

24VAC 3.5A

28VAC 3A

24VAC 3.5A

28VAC 3A

24VAC 3.5A

28VAC 3A

ALTV244175UL3

24VAC 7A

28VAC 6.25A

ALTV244175ULCB3

24VAC 7A

28VAC 6.25A

4

4

4

4

4

P

P

P

P

P

3.5A

3.5A

3.5A

3.5A

2.5A

3.5A

3.5A

2.5A

5A/

250V

5A/

250V

5A/

250V

10A/

250V

10A/

250V

3.5A/

250V

0.9A

3.5A/

250V

0.9A

3.5A/

250V

0.9A

– 1.76A

– 1.76A

Agency Listings:

• UL Listed for Commercial CCTV Equipment

(UL 2044).

CUL Listed - CSA Standard C22.2 No.1-98,

Audio, Video and Similar Equipment.

• CE European Conformity.

Input:

• 115VAC, 50/60Hz.

Output:

• Four (4) fuse or PTC protected outputs.

• 24VAC or 28VAC output.

• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).

• Surge suppression.

Features:

• Power ON/OFF switch

(ALTV244UL3, ALTV244ULX3, and

ALTV244ULCB3).

Specifications:

Features

(cont’d)

:

• Illuminated power disconnect circuit breaker

with manual reset

(ALTV244175UL3 and ALTV244175ULCB3).

• Unit maintains camera synchronization.

• Ease of installation saves time & eliminates

costly labor.

• Spare fuses included (on fuse protected models).

Enclosure Dimensions

(H x W x D)

:

• ALTV244UL3, ALTV244ULCB3

8.5” x 7.5” x 3.5”

(215.9mm x 190.5mm x 88.9mm).

• ALTV244175UL3, ALTV24175ULCB3

12” x 7.5” x 4.5”

(304.8mm x 190.5mm x 114.3mm).

• ALTV244ULX3

13.5” x 13” x 3.25”

(342.9mm x 330.2mm x 82.6mm).

Installation Instructions:

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws

(Enclosure Dimensions, pgs. 10-12). Secure enclosure to earth ground.

2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3,

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).

- 2 - ALTV244UL3 Series

3. All units are factory set for 24VAC operation.

For 28VAC operation adjust unit prior to applying power as follows:

Remove wires marked [24V] and [28V] from terminals marked [P] and [S].

Connect wire marked [28V] to terminal marked [P] and connect wire marked [24V] to terminal marked [S].

Note: ALTV244ULCB3 set for 28VAC operation is not Class 2 Rated, not power-limited.

4. Plug in 3-wire line cord (Figs. 1-5, pgs. 4-8).

Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring.

Minimum 0.25” spacing must be provided. Use separate knockouts.

5. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3,

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).

6. Measure output voltage before connecting devices. This helps avoiding potential damage.

Terminals marked [1P - 4P] are of the same polarity.

CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage.

7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3,

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).

8.

Connect devices to the terminals marked [1P] - [1N] through [4P] - [4N] on PD4 or PD4CB board

(Figs. 1-5, pgs. 4-8), carefully observing polarity.

9. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3,

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).

10. Green LED will illuminate when power is present.

11. Upon completion of the wiring, secure enclosure door with screws (supplied).

Installation of a cam lock is optional.

Caution: Equipment to be installed/serviced by authorized/trained personnel only.

Shut branch circuit power before installing/servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical

Code and all local codes. Use 75˚C or higher rated UL insulated wiring for connecting the unit to the mains.

Replace fuses with the same type and rating (refer to Four (4) Output ALTV244UL3 Reference Chart, pg. 2).

PD4/PD4CB - Distribution Module

1P - 4P

1N - 4N

AC output.

AC output.

Terminal Identification:

The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.

CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.

ALTV244UL3 Series - 3 -

Fig. 1 - ALTV244UL3

3.5A 250V 3.5A 250V 3.5A 250V

24VAC or 28VAC Output 1

Follow same procedure using terminals

2P & N through 4P & N for outputs 2 through 4)

LED

1P 1N 2P 2N 3P 3N 4P 4N

Class 1 Outputs

N P S

Primary

In-line

Fuse

XFMR non power- limited

Black Lead

White Lead

Green

Lead (ground)

Input 115VAC,

50/60Hz

Voltage Selection

Configuration

N P S

24VAC

Output

24V 28V

28VAC

Output

N P S

28V 24V

- 4 - ALTV244UL3 Series

Fig. 2 - ALTV244ULCB3

24VAC or 28VAC Output 1

Follow same procedure using terminals

2P & N through 4P & N for outputs 2 through 4)

LED

1P 1N 2P 2N 3P 3N 4P 4N

24VAC configuration Class 2 Not Wet/Class 3 Wet

28VAC configuration Class 1 N P S

Primary

In-line

Fuse

XFMR non power- limited

Black Lead

White Lead

Green

Lead (ground)

Input 115VAC,

50/60Hz

Voltage Selection

Configuration

N P S

24VAC

Output

24V 28V

28VAC

Output

N P S

28V 24V

ALTV244UL3 Series - 5 -

Fig. 3 - ALTV244ULX3

Class 1

Outputs

ON OFF

MAIN FUSE

Black Lead

White Lead

Primary

In-line Fuse non power- limited

Input 115VAC,

50/60Hz

Voltage Selection

Configuration

N P S

24VAC

Output

24V 28V

28VAC

Output

N P S

28V 24V

- 6 - ALTV244UL3 Series

Fig. 4 - ALTV244175UL3

3.5A 250V 3.5A 250V 3.5A 250V

24VAC or 28VAC

Output 1

Follow same procedure using terminals

2P & N through

4P & N for outputs 2 through 4)

LED

1P 1N 2P 2N 3P 3N 4P 4N

Class 1 Outputs

N P S

Illuminated Power Disconnect

Circuit Breaker with manual reset

Voltage Selection

Configuration

N P S

24VAC

Output

24V 28V

Green

Lead (ground) non power- limited

Black Lead

White

Lead

Input 115VAC,

50/60Hz

28VAC

Output

N P S

28V 24V

ALTV244UL3 Series - 7 -

Fig. 5 - ALTV244175ULCB3

24VAC or 28VAC

Output 1

Follow same procedure using terminals

2P & N through

4P & N for outputs 2 through 4)

LED

1P 1N 2P 2N 3P 3N 4P 4N

24VAC configuration Class 2 Not Wet/Class 3 Wet

28VAC configuration Class 1 N P S

Illuminated Power Disconnect

Circuit Breaker with manual reset

Voltage Selection

Configuration

N P S

24VAC

Output

24V 28V

Green

Lead (ground) non power- limited

Black Lead

White

Lead

Input 115VAC,

50/60Hz

28VAC

Output

N P S

28V 24V

- 8 - ALTV244UL3 Series

Notes:

ALTV244UL3 Series - 9 -

Enclosure Dimensions

(H x W x D)

for:

• ALTV244UL3

• ALTV244ULCB3

8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm)

7.25”

(184.15mm)

3.625”

(184.15mm)

0.6”

(15.24mm)

1.125”

(28.575mm)

6.05”

(153.67mm)

1.25”

(31.75mm)

3.5”

(88.9mm)

0.6”

(15.24mm)

1.125”

(28.575mm)

2”

(50.8mm)

1.25”

(31.75mm)

2”

(50.8mm)

8.125”

(206.375mm)

1”

(25.4mm)

0.6”

(15.24mm)

1”

(25.4mm)

6.05”

(153.67mm)

5.25”

(133.35mm)

1”

(25.4mm)

0.6”

(15.24mm)

3.5”

(88.9mm)

1”

(25.4mm)

1”

(25.4mm)

1.25”

(31.75mm)

- 10 - ALTV244UL3 Series

Enclosure Dimensions

(H x W x D)

for:

• ALTV244ULX3

13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)

1.40”

(36mm)

4.85”

(123mm)

4.85”

(123mm)

1.40”

(36mm)

1.20”

(31mm)

0.75”

(19mm)

12.5”

(318mm)

11.0”

(279mm)

1.40”

(36mm)

1.20”

(31mm)

3.25”

(83mm)

0.75”

(19mm)

0.9375”

(24mm)

1.20”

(31mm)

1.40”

(36mm)

5.10”

(130mm)

5.10”

(130mm)

13.0”

(330mm)

5.10”

(130mm)

6.5625”

(167mm)

3.25”

(83mm)

1.0”

(25mm)

1.0”

(25mm)

10.5”

(267mm)

0.9375”

(24mm)

1.0”

(25mm)

3.25”

(83mm)

1.0”

(25mm)

3.25”

(83mm)

ALTV244UL3 Series - 11 -

Enclosure Dimensions

(H x W x D)

for:

• ALTV244175UL3

• ALTV244175ULCB3

12” x 7.5” x 4.5” (304.8mm x 190.5mm x 114.3mm)

7.5”

(190.5mm)

4.5”

(114.3mm)

1.5”

(12.7mm)

1.25”

(31.75mm)

3.5”

(88.9mm)

12”

(304.8mm)

2.5”

(63.5mm)

3.5”

(88.9mm)

1”

(25.4mm)

0.5”

(12.7mm)

1.11”

(28.19mm)

0.5”

(12.7mm)

1.11”

(28.19mm)

4.5”

(114.3mm)

7.5”

(190.5mm)

1”

(25.4mm)

0.88”

(22.35mm)

5.75”

(146.05mm)

4.5”

(114.3mm)

0.88”

(22.35mm)

1”

(25.4mm)

4.5”

(114.3mm)

1.25”

(31.75mm)

1.5”

(12.7mm)

3.5”

(88.9mm)

12”

(304.8mm)

5.88”

(149.35mm)

1.13”

(28.7mm)

Altronix is not responsible for any typographical errors.

140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.