PVI Industries QuickDraw Water-to-Water Storage Single Wall, 150 Gallon Specification
Advertisement
Advertisement
QuickDraw
®
BOILER WATER
SINGLE-WALL
PACKAGED WATER HEATER with AquaPLEX
®
STORAGE TANK
TANK SERIES 150 GALLON
MODEL
NUMBER
STANDARD
RECOVERY
RATE
STANDARD
BOILER
WATER FLOW
40°F - 140°F 180°F (20° ∆ T)
A
COLD
INLET
NPT
B
HOT
OUTLET
NPT
C
BOILER
WATER
INLET
NPT
D
BOILER
WATER
OUTLET
NPT
E
COWLING
DEPTH
F
SKID
LENGTH
G
OVERALL
DEPTH
H
PULL
SPACE
SHIPPING
WEIGHT
LBS
300 L 150A-QW
550 L 150A-QW
800 L 150A-QW
1500 L 150A-QW
2300 L 150A-QW
2600 L 150A-QW
3300 L 150A-QW
4000 L 150A-QW
4400 L 150A-QW
7100 L 150A-QW
140
240
380
690
1020
1200
1490
1790
2540
3260 gph
12
21
32
58
87
102
126
152
215
276 gpm
2
2
2
2
2-1/2
2-1/2
2-1/2
2-1/2
2-1/2
2-1/2
2
2
2
2
2
2
2
2
2
2
3/4
1
1-1/4
1-1/2
2
2-1/2
2-1/2
3
4
4
3/4
1
1-1/4
1-1/2
2
2-1/2
2-1/2
3
4
4
42
42
53
53
53
53
53
53
53
53
* For recoveries, boiler water flows and valve sizes at different boiler water temperatures and temperature rises, refer to forms PV 6909.
Electrical requirements: 120V, 1Ø, 60 Hz., 15 amps maximum, to a single point connection.
When using 4” boiler water valve, the supply and return piping is to be field supplied and installed.
Dimensions are in inches unless otherwise noted.
For standard and optional equipment, see form PV 8163.
37-1/2
37-1/2
54-1/2
54-1/2
54-1/2
54-1/2
54-1/2
54-1/2
54-1/2
54-1/2
69
69
80
81
81
88
88
88
88
88
34
34
46
46
40
46
40
46
46
46
1050
1090
1100
1200
1290
1300
1460
1480
1590
1750
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN
AND SPECIFICATION WITHOUT NOTICE.
PV 9040 05-2019
PVI Industries, LLC
Fort Worth, TX ▪ (800) 784-8326 ▪ www.pvi.com

Download
Advertisement