Rosslare AYC-Q54B, AYC-Q64B Installation And Programming Manual
Show HTML Add to My manuals63 Pages
Rosslare AYC-Q64B is an advanced vandal-resistant convertible reader/controller designed for access control applications. Here's a quick rundown of its capabilities:
As a reader, AYC-Q64B can read proximity cards and transmit the data to a host controller. It supports various card formats, including HID Prox, Indala Prox, and EM4102. Using a keypad, users can also enter PINs for access.
Alternatively, AYC-Q64B can operate as a standalone controller, making access decisions locally. It can store up to 500 user codes and manage two doors with independent schedules and permissions.
The device features multiple modes of operation, including normal, bypass, and secure modes, providing flexibility in access control. It also has various input and output options for interfacing with external devices like door strikes, alarms, and sensors.
advertisement
AYC-Qx4 Series
Vandal Resistant Convertible
Reader/Controllers
Installation and Programming Manual
Models:
AYC-Q54B
AYC-Q64B
AYC-Q54B AYC-Q64B
Copyright © 2017 by Rosslare. All rights reserved.
This manual and the information contained herein are proprietary to REL, RSP
Inc. and/or their related companies and/or subsidiaries (hereafter: ”ROSSLARE”).
Only ROSSLARE and its customers have the right to use the information.
No part of this manual may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of ROSSLARE.
ROSSLARE owns patents and patent applications, trademarks, copyrights, or other intellectual property rights covering the subject matter in this manual.
TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN
THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS
AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND
TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION
MAY RESULT IN LEGAL PROCEEDINGS.
The furnishing of this manual to any party does not give that party or any third party any license to these patents, trademarks, copyrights or other intellectual property rights, except as expressly provided in any written agreement of
ROSSLARE.
ROSSLARE reserves the right to revise and change this document at any time, without being obliged to announce such revisions or changes beforehand or after the fact.
Table of Contents
Table of Contents
1.
Introduction ................................................................ 9
1.1
Reader/Controller Types........................................................... 9
1.2
Box Content ......................................................................... 10
1.3
Ancillary Equipment .............................................................. 10
2.
Technical Specifications ............................................ 11
3.
Installation ................................................................ 13
3.1
Mounting ............................................................................. 13
3.2
Wiring Instructions ................................................................ 14
3.2.1
Wiring the Unit as a Reader .......................................................... 14
3.2.2
Wiring the Unit as a Controller ..................................................... 15
4.
Reader Operation ...................................................... 18
4.1
Standby Mode ...................................................................... 18
4.2
Programming as a Reader ...................................................... 18
4.2.1
Entering Programming Mode ........................................................ 20
4.2.2
Exiting Programming Mode .......................................................... 20
4.2.3
Selecting Keypad Transmission Format ......................................... 21
4.2.4
Selecting Proximity Card Transmission Format .............................. 26
4.2.5
Changing the Programming Code ................................................ 28
4.2.6
Changing the Facility Code ........................................................... 29
4.2.7
Setting the Backlight Behavior ...................................................... 29
4.2.8
Return to Factory Default Settings ................................................ 30
4.2.9
Replacing a Lost Programming Code ............................................ 31
5.
Controller Operation ................................................. 32
5.1
Normal, Secure, and Master Users .......................................... 32
AYC-Qx4 Family Installation and Programming Manual iii
Table of Contents
5.2
Modes of Operation .............................................................. 33
5.2.1
Normal Mode ............................................................................... 33
5.2.2
Bypass Mode ................................................................................ 33
5.2.3
Secure Mode ................................................................................ 34
5.2.4
Changing the Modes of Operation ............................................... 34
5.3
Auxiliary Input and Output..................................................... 35
5.4
Door Alarms ......................................................................... 35
5.5
Internal Case and Back Tamper .............................................. 36
5.6
Lockout Feature (Keypad/Card Tamper) .................................. 36
5.7
REX Function ........................................................................ 36
5.8
Secured Intelligent Power Supply ........................................... 37
5.9
Programming as a Controller ................................................. 37
5.9.1
Entering Programming Mode ........................................................ 38
5.9.2
Exiting Programming Mode .......................................................... 39
5.9.3
Changing Lock Strike Code .......................................................... 39
5.9.4
Changing Auxiliary Code .............................................................. 40
5.9.5
Changing the Programming Code ................................................ 41
5.9.6
Changing the Normal/Secure Code .............................................. 41
5.9.7
Changing the Normal/Bypass Code and Door Chime Settings ...... 42
5.9.8
Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike
Release Time ................................................................................. 43
5.9.9
Defining the Auxiliary Input and Output ....................................... 44
5.9.10
Setting the Lockout Feature .......................................................... 49
5.9.11
Setting the Backlight Behavior ...................................................... 50
5.9.12
Enrolling Primary and Secondary Codes ........................................ 51
5.9.13
Deleting Primary and Secondary Codes ......................................... 55
5.9.14
Relay Codes Assignment ............................................................... 57
5.9.15
Relay Code Assignment using Standard Method .......................... 57 iv AYC-Qx4 Family Installation and Programming Manual
Table of Contents
5.9.16
Relay Code Assignment using Search Method .............................. 58
5.9.17
PIN Code Length/Factory Default Settings ..................................... 59
5.9.18
Replacing a Lost Programming Code ............................................ 60
5.9.19
Exiting Secure Mode if Normal/Secure Code was Lost................... 60
A.
Declaration of Conformity........................................ 61
B.
Limited Warranty ...................................................... 62
AYC-Qx4 Family Installation and Programming Manual v
List of Figures
List of Figures
Figure 1: Drilling Mounting Holes .................................................................... 13
Figure 2: Controller Application Wiring Diagram ............................................. 16
Figure 3: Controller Wiring – Using the Internal Power .................................... 17
Figure 4: Controller Wiring – Using the External Power ................................... 17 vi AYC-Qx4 Family Installation and Programming Manual
List of Tables
List of Tables
Table 1: Wiring the Reader to the Controller ................................................... 14
Table 2: Wiring the Unit as a Controller........................................................... 15
Table 3: Reader Programming Menus .............................................................. 19
Table 4: Controller Programming Menu .......................................................... 37
Table 5: Quick Reference Guide for Auxiliary Mode Setting ............................. 44
AYC-Qx4 Family Installation and Programming Manual vii
Introduction
Notice and Disclaimer
This manual’s sole purpose is to assist installers and/or users in the safe and efficient installation and usage of the system and/or product, and/or software described herein.
B EFORE ATTEMPTING TO INSTALL AND / OR USE THE SYSTEM , THE INSTALLER AND THE
USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY
REQUIREMENTS AND OPERATING PROCEDURES .
The system must not be used for purposes other than those for which it was designed.
The use of the software associated with the system and/or product, if applicable, is subject to the terms of the license provided as part of the purchase documents.
ROSSLARE exclusive warranty and liability is limited to the warranty and liability statement provided in an appendix at the end of this document.
This manual describes the maximum configuration of the system with the maximum number of functions, including future options. Therefore, not all functions described in this manual may be available in the specific system and/or product configuration you purchased.
Incorrect operation or installation, or failure of the user to effectively maintain the system, relieves the manufacturer (and seller) from all or any responsibility for consequent noncompliance, damage, or injury.
The text, images and graphics contained in the manual are for the purpose of illustration and reference only.
All data contained herein subject to change without prior notice.
In no event shall manufacturer be liable for any special, direct, indirect, incidental, consequential, exemplary or punitive damages (including, without limitation, any and all damages from business interruption, loss of profits or revenue, cost of capital or loss of use of any property or capital or injury).
All graphics in this manual are for reference only, some deviation between the image(s) and the actual product may occur.
All wiring diagrams are intended for reference only, the photograph or graphic of the PCB(s) are intended for clearer illustration and understanding of the product and may differ from the actual PCB(s).
8 AYC-Qx4 Family Installation and Programming Manual
Introduction
1.
Introduction
The AYC-Qx4 series are vandal-resistant, waterproof, standalone, convertible integrated readers and controllers. These units automatically determine whether to function as a reader or as a controller. If the unit is connected to a standard access control unit, then it functions as a reader. If the unit is connected to a Rosslare secured intelligent power supply such as the PS-A25T, PS-C25T or PS-
C25TU, it functions as a secured controller.
All of the units are water resistant and suitable for indoor or outdoor mounting. As a controller, the units accept up to 500 users, and allow entry via a personal identification number (PIN) and/or by presenting a proximity card. The PIN code length for the controller has several options. The PIN code length can be a set number of 4, 5, or 6 digits or it can be a 4-8 digits option.
For information on how the unit functions as a reader, see Chapter 4.
For information on how the unit functions as a controller, see Chapter
5.
1.1
Reader/Controller Types
The different types of units described in this manual are:
AYC-Q54
AYC-Q64
Backlight Keypad Type PIN
Standard
Standard
Proximity
AYC-Qx4 Family Installation and Programming Manual 9
Introduction
1.2
Box Content
Before beginning, verify that all of the following is in the box. If anything is missing, please report the discrepancy to your nearest
Rosslare office.
One AYC-Qx4 unit
Installation kit
Installation and operating instructions
1.3
Ancillary Equipment
The following equipment is required to complete your installation:
When functioning as a reader:
Compatible host controller (not supplied ) – UL listed access control unit, such as model AC-215U
When functioning as a controller:
Secured intelligent power supply (such as the PS-A25T, PS-C25T or PS-C25TU)
The controller connects to the following:
Electric lock strike mechanism or a magnetic lock device, which implements fail safe (power to lock) or fail secure
(power to open) functions.
Request-to-Exit (REX) button – normally open type
Switch is closed when pressed.
Door monitor switch
Rosslare accessories can be found on www.rosslaresecurity.com
.
10 AYC-Qx4 Family Installation and Programming Manual
Technical Specifications
2.
Technical Specifications
Specifications
Electrical Characteristics
AYC-Q54B AYC-Q64B
Power Supply Type
Operating Voltage Range
Linear (recommended)
5 to 16 VDC (when used as a controller, provided by the secured intelligent power supply)
Input Current Standby (12 VDC) 65 mA
Maximum Input Current (16 VDC) 110 mA
90 mA
130 mA
LED Control Input Dry contact N.O.
Tamper Output Open collector, active low, 30 mA max sink current
Cable Distance to Host Controller Up to 150 m (500 ft) using an 18 AWG cable
Max. Proximity Card Read Range* N/A
Proximity Card Modulation N/A
Proximity Card Compatibility N/A
45 mm (1.8 in.)
ASK at 125 KHz
EM cards
Card Transmit Format (Reader)
Communication
N/A
Keypad Transmit Format (Reader) Programmable PIN code formats
LED Indicators Two tri-colored LEDs
Data1/C1, Data0/C2 – open collector, 5
V termination
Wiegand 26-Bit, or
Clock & Data
Environmental Characteristics
Operating Temperature Range -35°C to 66°C (-31°F to 151°F)
Operating Humidity Range 0 to 95% (non-condensing)
Outdoor Usage Weather-resistant, meets IP65, epoxy potted, suitable for outdoor use
AYC-Qx4 Family Installation and Programming Manual 11
Technical Specifications
Specifications
Physical Characteristics
Size
(Height x Width x Depth)
Weight
AYC-Q54B
480 g (1.1 lb)
AYC-Q64B
120 x 76 x 21 mm (4.7 x 3.0 x 0.8 in.)
* Measured using a Rosslare proximity card or equivalent. Range also depends on electrical environment and proximity to metal.
12 AYC-Qx4 Family Installation and Programming Manual
Installation
3.
Installation
Installation of an RFID reader adjacent to metallic surfaces might alter the reader’s specifications. To diminish this interference, use a plastic spacer when mounting the reader.
3.1
Mounting
Before starting, select the location to mount the unit. This location should be at shoulder height.
To mount the unit:
1.
Peel off the back of the self-adhesive installation template and attach the template to the required location.
2.
At the bottom of the unit’s case, remove the screw.
3.
Carefully remove the snap-off front cover of the unit to reveal the screw holes.
4.
Depending on the type of installation, gang box or panel mount, drill the respective holes in the rear cover: for gang box mounting, drill two holes marked “A”; for flat panel mount, drill four holes marked “B” (Figure 1).
Figure 1: Drilling Mounting Holes
5.
Drill a 10-mm (7/16”) hole for the cable. If the surface is metal, place a grommet or electrical tape around the edge of the hole.
6.
Insert the unit’s cable wire into the cable hole and wire the unit as described in Section 3.2.
7.
Screw the back cover to its mounting location.
AYC-Qx4 Family Installation and Programming Manual 13
Installation
8.
Carefully re-attach the front cover of the unit.
9.
Secure the front cover by using the supplied security Torx screw.
A Torx security screw tool is provided to tighten the security Torx screw.
3.2
Wiring Instructions
The unit is supplied with a 6-conductor 56-cm (22-in.) pigtail with exposed wires coated with solder.
3.2.1
Wiring the Unit as a Reader
If you connect the unit to a standard access control unit, it automatically functions as a reader.
To connect the unit as a reader (to a controller):
1.
Select the appropriate connections according to Table 1.
Table 1: Wiring the Reader to the Controller
Wire Color Function
Black/Shield
Red
Green
White
Brown
Purple
Ground (-)
Vin (+)
Data 0/Data (D0)
Data 1/Clock (D1)
LED control
Tamper
2.
Prepare the controller cable by cutting the cable jacket back 3.2 cm (1¼”) and strip the wire 1.3 cm (½”).
3.
Splice the reader’s pigtail wires to the corresponding controller wires and cover each joint with insulating tape.
4.
If the tamper output is being utilized, connect the purple wire to the correct input on the controller.
5.
Trim and cover all conductors that are not used.
14 AYC-Qx4 Family Installation and Programming Manual
Installation
• The individual wires extending from the reader are color-coded according to the required Wiegand standard.
• When using a separate power supply for the reader, this supply and the controller’s power supply must have a common ground. A linear power supply is recommended.
• Attach the cable shield wire on the reader to an earth ground (best), or to a signal ground connection at the panel or power supply end of the cable. This configuration is best for shielding the reader cable from external interference.
3.2.2
Wiring the Unit as a Controller
If you connect the unit to a Rosslare PS-x25x secured power supply, it automatically functions as a controller.
To connect the unit as a controller:
1.
Select the appropriate connections according to Table 2.
Table 2: Wiring the Unit as a Controller
Controller Wire Color Function Note
+
-
C 1
C 2
AUX. IN
N/A
Red
Black
White
Green
Brown
Purple
+DC Input
Ground
Wired to the PS-x25x
Wired to the PS-x25x
Communication Wired to the PS-x25x
Communication Wired to the PS-x25x
Auxiliary Input
Not in use
Wired to input
N/A
Attach the cable shield wire on the unit to an earth ground (best).
You can also attach it to a signal ground connection at the panel or power supply end of the cable. This configuration is best for shielding the controller cable from external interference.
2.
Prepare the PS-x25x secured power supply’s cable by cutting the cable jacket back 3.2 cm (1¼”) and strip the wire 1.3 cm (½”).
3.
Splice the controller pigtail wires to the corresponding PS-x25x secured power supply’s wires and cover each joint with insulating tape.
4.
Trim and cover all conductors not used.
AYC-Qx4 Family Installation and Programming Manual 15
Installation
5.
To connect the unit to the desired power supply option, refer to the relevant wiring diagrams that follow.
Figure 2 shows the wiring for the controller application using a dual relay secured intelligent power supply.
Figure 2: Controller Application Wiring Diagram
16 AYC-Qx4 Family Installation and Programming Manual
Installation
Figure 3 shows the auxiliary output connection using the internal power.
Figure 3: Controller Wiring – Using the Internal Power
Figure 4 shows the auxiliary output connection using the external power.
Figure 4: Controller Wiring – Using the External Power
AYC-Qx4 Family Installation and Programming Manual 17
Reader Operation
4.
Reader Operation
Upon power-on reset, the unit searches for the presence of a secured intelligent power supply. If a secured intelligent power supply is not detected, it is automatically configured as a reader, as indicated by one short beep.
The use of a proximity card is for the AYC-Q64 model only.
4.1
Standby Mode
The default mode of the reader is Standby mode. In Standby mode, the unit is ready to receive data from a presented proximity card or an entered PIN code.
When the reader is in Standby mode, the left LED is red and the right LED is off.
When a proximity card is presented or a keypad entry is being transmitted, the left LED flashes green.
Green
Keyboard data can be sent via one of eight keypad transmission formats (see Section 4.2.3).
Proximity cards presented to the reader are always sent in either
Wiegand 26-Bit, Clock & Data or, Wiegand Card + PIN format (see
Section 4.2.4).
4.2
Programming as a Reader
Programming is done solely via the unit's keypad driven Programming
Menu System. During the manufacturing process, certain codes and settings are pre-programmed. These settings are called the default factory settings.
18 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
Table 3 shows the names of all the reader programming menus.
Default factory settings are marked by a "*" sign.
Table 3: Reader Programming Menus
Menu Description Default
1 Selecting Keypad Transmission Format
Single Key, 6-Bit Wiegand (Rosslare Format)
Single Key, 6-Bit Wiegand with Nibble + Parity Bits
Single Key, 8-Bit Wiegand, Nibbles Complemented
4 Keys Binary + Facility Code, Wiegand 26-Bit
1 to 5 Keys + Facility Code, Wiegand 26-Bit
6 Keys BCD and Parity Bits, Wiegand 26-Bit
Single Key, 3x4 Matrix Keypad
1 to 8 Keys BCD, Clock & Data
Single Key, Wiegand 4-Bit
2 Selecting Card Transmission Format
Wiegand 26-Bit
Clock & Data
Wiegand Card + PIN
3 Changing the Programming Code
4 Changing the Facility Code
6 Backlight Options
Off
On (Default)
Off until key press when on for 10 seconds
Dimmed until key press when on for 10 seconds
0 Return to Factory Default Settings
*
*
1234
0
*
AYC-Qx4 Family Installation and Programming Manual 19
Reader Operation
4.2.1
Entering Programming Mode
To reach the Programming Menu System, the unit must first be placed into Programming mode.
• The factory 4-digit Programming code is 1234.
• If a Programming code is not entered within 30 seconds, the unit returns to Standby mode.
To enter Programming mode:
1.
Press # four times.
The left LED turns off and the right LED turns red.
2.
Enter your 4-digit Programming code.
If the Programming code is valid, the right LED turns green. Green
If the Programming code is invalid, you hear a long beep and the reader returns to Standby mode.
4.2.2
Exiting Programming Mode
To exit Programming mode:
1.
Press # to exit Programming mode at any time.
You hear a beep.
The left LED turns red and the right LED turns off.
Red
This indicates that the unit has returned to Standby mode.
Wrong entries may reset the reader back to Standby mode. If no key is pressed for 30 seconds while in Programming mode, the unit exits Programming mode and returns to Standby mode.
20 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
4.2.3
Selecting Keypad Transmission Format
There are nine keypad transmission formats.
• Only one keypad transmission format can be active at any one time.
• When using the keypad transmission format "1 to 8 keys BCD, Clock
& Data" (Option 8), an additional input is required to specify the number of keys in the PIN code.
To select the appropriate keypad transmission format:
1.
Enter Programming mode.
Green
2.
Press 1 to enter Menu 1.
The left LED turns red.
Red Green
3.
Enter one of the following codes:
1 – Single Key, Wiegand 6-Bit (Rosslare Format) (default)
2 – Single Key, Wiegand 6-Bit with Nibble + Parity Bits
3 – Single Key, Wiegand 8-Bit, Nibbles Complemented
4 – 4 Keys Binary + Facility Code, Wiegand 26-Bit
5 – 1 to 5 Keys + Facility Code, Wiegand 26-Bit
6 – 6 Keys BCD and Parity Bits, Wiegand 26-Bit
7 – Single Key, 3x4 Matrix Keypad
8 – 1 to 8 Keys BCD, Clock & Data Single Key
9 – Single Key, Wiegand 4-Bit
When selecting Option 8, the Program LED turns orange, awaiting an additional key input to select the number of keys.
You hear three beeps.
The system returns to Standby mode.
Red
If an incorrect option number is entered, the reader returns to
Standby mode and the keypad transmission format remains unchanged.
AYC-Qx4 Family Installation and Programming Manual 21
Reader Operation
4.2.3.1
Single Key, Wiegand 6-Bit (Rosslare Format)
Each key press immediately sends 4 bits with 2 parity bits added – even parity for the first 3 bits and odd parity for the last 3 bits.
0 = 1 1010 0 ="A" in Hexadecimal 6 = 1 0110 0
1 = 0 0001 0 7 = 1 0111 1
2 = 0 0010 0 8 = 1 1000 1
3 = 0 0011 1
4 = 1 0100 1
5 = 1 0101 0
9 = 1 1001 0
= 1 1011 1 ="B" in Hexadecimal
# = 0 1100 1 ="C" in Hexadecimal
4.2.3.2
Single Key, Wiegand 6-Bit Nibble and Parities
Each key press immediately sends 4 bits with 2 parity bits added – even parity for the first 3 bits and odd parity for the last 3 bits.
0 = 0 0000 1
1 = 0 0001 0
2 = 0 0010 0
3 = 0 0011 1
6 = 1 0110 0
7 = 1 0111 1
8 = 1 1000 1
9 = 1 1001 0
4 = 1 0100 1
5 = 1 0101 0
= 1 1010 0 = "A" in Hexadecimal
# = 1 1011 1 = "B" in Hexadecimal
4.2.3.3
Single Key, Wiegand 8-Bit Nibbles Complemented
This option inverts the most significant bits in the message leaving the least 4 significant bits as a Binary Coded Decimal (BCD) representation of the key. The host system receives an 8-bit message.
0 = 11110000
1 = 11100001
2 = 11010010
3 = 11000011
4 = 10110100
5 = 10100101
6 = 10010110
7 = 10000111
8 = 01111000
9 = 01101001
= 01011010 = "A" in Hexadecimal
# = 01001011 = "B" in Hexadecimal
22 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
4.2.3.4
4 Keys Binary + Facility Code, Wiegand 26-Bit
This option buffers 4 keys and outputs keypad data with a 3-digit
Facility code like a standard 26-Bit card output.
The Facility code is set in Programming Menu number four and can be in the range 000 to 255. The factory default setting for the Facility code is 000 (see Section 4.2.6).
The keypad PIN code is 4-digit long and can range between 0000 and
9999. On the fourth key press of the 4-digit PIN code, the data is sent across the Wiegand Data lines as binary data in the same format as a
26-Bit Card.
If or # are pressed are pressed during PIN code entry, the keypad clears the PIN code entry buffer, generate a beep and is ready to receive a new 4-digit keypad PIN code.
If the entry of the 4-digit keypad PIN code is disrupted and no number key is pressed within 5 seconds, the keypad clears the PIN code entry buffer, generate a beep and is ready to receive a new 4-digit keypad
PIN code.
(EP) FFFF FFFF AAAA AAAA AAAA AAAA (OP)
Where:
EP = Even parity for first 12 bits
OP = Odd parity for last 12 bits
F = 8-bit Facility code
A = 16-bit code generated from keyboard
4.2.3.5
1 to 5 Keys + Facility Code, Wiegand 26-Bit
Option 5 buffers up to 5 keys and outputs keypad data with a Facility code like a 26-Bit card output.
The Facility code is set in Programming Menu number four and can be in the range 000 to 255. The factory default setting for the Facility code is 000 (see Section 4.2.6).
AYC-Qx4 Family Installation and Programming Manual 23
Reader Operation
The keypad PIN code can be one to five digits in length and can range between 1 and 65,535. When entering a keypad PIN code that is less than 5 digits in length, # must be pressed to signify the end of PIN code entry. For keypad PIN codes that are 5 digits in length, on the fifth key press of the 5-digit PIN code, the data is sent across the
Wiegand Data lines as binary data in the same format as a 26-Bit card.
If is pressed during PIN code entry or a PIN code greater than
65,535 is entered, the keypad clears the PIN code entry buffer, generates a beep and is ready to receive a new 5-digit keypad PIN code.
If the entry of the 1- to 5-digit keypad PIN code is disrupted and a number key or # is not pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a medium length beep and is ready to receive a new 1- to 5-digit keypad PIN code.
(EP) FFFF FFFF AAAA AAAA AAAA AAAA (OP)
Where:
EP = Even parity for first 12 bits
OP = Odd parity for last 12 bits
F = 8-bit Facility code
A = 16-bit code generated from keyboard
4.2.3.6
6 Keys BCD and Parity Bits, Wiegand 26-Bit
Option 6 sends buffer of 6 keys, adds parity and sends a 26-Bit Binary
BCD message. Each key is a four bit equivalent of the decimal number.
The keypad PIN code must be 6 key presses long. On the sixth key press of the 6-digit PIN code, the data is sent across the Wiegand
Data lines as a BCD message.
If the entry of the 6-digit keypad PIN code is disrupted and no number key is pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a medium length beep and is ready to receive a new
6-digit keypad PIN code.
(EP) AAAA BBBB CCCC DDDD EEEE FFFF (OP)
24 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
Where:
EP = Even parity for first 12 bits
OP = Odd parity for last 12 bits
A = The first key entered D = Fourth key entered
B = Second key entered E = Fifth key entered
C = Third key entered F = Sixth key entered
4.2.3.7
Single Key, 3x4 Matrix Keypad
This unique mode is intended to let the host controller scan the keypad while still keeping the proximity card readers Wiegand 26-Bit or Clock & Data formats active.
An optional interface board must be used between the AYC-Qx4 and the host system. Each key press is immediately sent on DATA0 as an
ASCII character at a baud rate of 9600 bits per second.
When a key is pressed DATA1 is pulled "low" until the key is released at which point DATA1 is set to "high". This allows the controller to detect the duration of the key press.
The MD-P64 interface unit outputs the data received to 7 outputs emulating a keyboard. The interface unit does not affect any data that it receives from the proximity reader whether it is Wiegand 26-Bit or Clock & Data.
Key pressed = ASCII Value
0 = '0' ( 0x30 hex )
1 = '1' ( 0x31 hex )
2 = '2' ( 0x32 hex )
3 = '3' ( 0x33 hex )
4 = '4' ( 0x34 hex )
5 = '5' ( 0x35 hex )
6 = '6' ( 0x36 hex )
7 = '7' ( 0x37 hex )
8 = '8' ( 0x38 hex )
9 = '9' ( 0x39 hex )
= '* ' ( 0x2A hex )
# = '#' ( 0x23 hex )
AYC-Qx4 Family Installation and Programming Manual 25
Reader Operation
4.2.3.8
1 to 8 Keys BCD, Clock & Data
Buffers up to 8 keys and outputs keypad data without a Facility code like standard Clock and Data card output.
The keypad PIN code can be one to eight digits in length. The PIN code length is selected while programming the reader for Option 8.
The reader transmits the data when it receives the last key press of the PIN code. The data is sent across the two data output lines as binary data in Clock & Data format.
If or # key are pressed during PIN code entry, the keypad clears the
PIN code entry buffer, generates a beep, and is ready to receive a new keypad PIN code.
If the entry of the digit keypad PIN code is disrupted and a number key or # is not pressed within 5 seconds, the keypad clears the PIN code entry buffer, generates a medium length beep, and is ready to receive a new keypad PIN code.
4.2.3.9
Single Key, Wiegand 4-Bit
Each key press immediately sends 4 bits of data, with no parity bits added.
0 = 0000
1 = 0001
2 = 0010
3 = 0011
4 = 0100
5 = 0101
6 = 0110
7 = 0111
8 = 1000
9 = 1001
* = 1010 ="A" in Hexadecimal
# =1011 ="B" in Hexadecimal
4.2.4
Selecting Proximity Card Transmission Format
There are three proximity card transmission formats.
To select the proximity card transmission format:
1.
Enter Programming mode.
2.
Press 2 to enter Menu 2.
Green
The left LED turns red.
Red Green
26 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
3.
Enter one of the following codes:
1 – Wiegand 26-Bit
2 – Clock & Data
3 – Wiegand Card + PIN
You hear three beeps.
The system returns to Standby mode. Red
If an incorrect option is entered, the reader returns to Standby mode and the keypad transmission format remains unchanged.
4.2.4.1
"Wiegand Card + PIN" Transmission Format
This unique mode is intended to let host controllers get card and keypad data simultaneously. This option overrules the selected
Keypad Transmission Format and sends the keypad data as described below.
After a card is presented to the unit, the program LED starts to flash in green and indicates that the unit is waiting for the PIN code. If the entry of 1- to 5-digit keypad PIN code is disturbed and a number key or # is not pressed within 5 seconds, the keypad clears the card buffer and the PIN code entry buffer, generates a medium length beep, and is ready to receive a new card.
The keypad PIN code can be one to five digits in length in the range of 0 to 99,999. When entering a keypad PIN code, # must be pressed to signify the end of the PIN entry. When pressing # , the data is sent by the Wiegand data lines. If * is pressed, the keypad clears the card buffer and the PIN code entry buffer, generates a medium length beep, and is ready to receive a new card.
AYC-Qx4 Family Installation and Programming Manual 27
Reader Operation
The AYC-QX4 output card data comes in Wiegand 26-Bit with the following keypad data in Wiegand 26-Bit format:
Card Data: (EP) AAAA AAAA AAAA BBBB BBBB BBBB (OP)
Where:
EP = Even parity for first 12 A bits
OP = Odd parity for last B 12 bits
PIN Data: (EP) 0000 AAAA BBBB CCCC DDDD EEEE (OP)
Where:
A = The first key entered
B = Second key entered
C = Third key entered
EP = Even parity for first 12 bits
D = Fourth key entered
E = Fifth key entered
OP = Odd parity for last 12 bits
If the PIN code is less than 5 digits, all the most significant nibbles are filled with 0.
Example: (EP) 0000 0000 0000 0000 AAAA BBBB (OP)
Where:
A = The first key entered
EP = Even parity for first 12 bits
B = Second key entered
OP = Odd parity for last 12 bits
4.2.5
Changing the Programming Code
• The Programming code cannot be erased; the code 0000 is invalid and does not erase the Programming code.
• The factory default 4-digit Programming code is 1234.
To change the Programming code:
1.
Enter Programming mode.
2.
Press 3 to enter Menu 3.
Green
The left LED turns red.
Red Green
28 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
3.
Enter the new 4-digit code you wish to set as the Programming code.
You hear three beeps.
The system returns to Standby mode.
4.2.6
Changing the Facility Code
• The Facility code can be in the range of 000 to 255.
• The default Facility code is 0.
To change the Facility code:
1.
Enter Programming mode.
2.
Press 4 to enter Menu 4.
Red
Green
The left LED turns red.
3.
Enter the new 3-digit code you wish to set as the Facility code.
You hear three beeps.
The system returns to Standby mode.
4.2.7
Setting the Backlight Behavior
To set the backlight behavior:
1.
Enter Programming mode.
2.
Press 6 to enter Menu 6.
Red Green
Red
Green
The left LED turns red.
Red Green
AYC-Qx4 Family Installation and Programming Manual 29
Reader Operation
3.
Enter one of the following codes:
0 – Always off
1 – Always on
2 – Backlight is off, activates for 10 seconds when a key is pressed (left LED also goes on), after which it dims until off
(left LED also goes off)
3 – Backlight is dimmed, activates for 10 seconds when a key is pressed (left LED also goes on), after which it returns to a dimmed level
You hear three beeps.
The system returns to Standby mode.
4.2.8
Return to Factory Default Settings
Red
You must be very careful before using this command! This erases the entire memory and return all codes to their factory default setting.
To return to factory default settings:
1.
Enter Programming mode.
Green
2.
Press 0 to enter Menu 0.
Both LEDs flash red.
Red Red
3.
Enter your 4-digit Programming code.
If the Programming code is valid, all memory is erased. You hear three beeps and the reader returns to Standby mode.
If the Programming code is invalid, you hear a long beep and the reader returns to Standby mode without erasing the memory of the reader
30 AYC-Qx4 Family Installation and Programming Manual
Reader Operation
4.2.9
Replacing a Lost Programming Code
In the event that the Programming code is forgotten, the unit can be reprogrammed in the field.
To replace a lost Programming code:
1.
Remove power from the reader.
2.
Activate the tamper by removing the reader from the wall or removing the reader's case.
3.
Apply power to the reader.
4.
You now have 10 seconds to enter Programming mode using the factory default Programming code 1234.
AYC-Qx4 Family Installation and Programming Manual 31
Controller Operation
5.
Controller Operation
Upon power-on reset, the unit searches for the presence of a secured intelligent power supply. If a secured intelligent power supply is detected, then the unit is automatically configured as a secure access control unit, as indicated by two short beeps.
The Lock Strike and Auxiliary outputs, as well as the REX input, are not located on the unit, eliminating the possibility of unauthorized entry to the restricted area.
The use of a proximity card is for the AYC-Q64 model only.
5.1
Normal, Secure, and Master Users
The units accept up to 500 users and provide entry via the use of PIN codes and/or Proximity cards. Each user is provided with two code memory slots, Memory Slot 1 (Primary code) and Memory Slot 2
(Secondary code).
The PIN code length has several options. The PIN code length can be a set number of 4, 5 or 6 digits or it can be a 4–8 digits option. When choosing the 4–8-digit option, please note that you should either enter zeros before the code, or press # at the end (for example, if your code is 12345, enter either 00012345 or 12345# ).
Entering a code refers to either PIN or card depending on the model you have.
The way in which the two memory slots are programmed determines a user’s access level and also determines the way in which the unit grants access in its three modes of operation. There are three user levels:
Normal
A Normal user only has a Primary code and is only granted access when the unit is in Normal or Bypass mode.
32 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
Secure
A Secure user must have a Primary and Secondary code programmed; the two codes must not be the same. The Secure user can gain access when the unit is in any of its three modes of operation. In Normal mode, the Secure user must use the Primary code to gain entry. In Secure mode, the Secure user must present both the Primary and Secondary codes to gain entry.
Master
A Master user must have both Primary and Secondary codes programmed with the same PIN code. The Master user can gain access during any mode of operation by presenting the PIN code and/or proximity card once to the controller. (The Master user is convenient but is less secure than a Secure user.)
5.2
Modes of Operation
There are three modes of operation:
5.2.1
Normal Mode
The left LED is green.
Green
Normal mode is the default mode. In Normal mode, the door is locked until a Primary code is presented to the controller. Special codes such as Lock Strike code and Auxiliary code are active in Normal mode. See Sections 5.9.3 and 5.9.4 for more information on the Lock
Strike and Auxiliary codes.
5.2.2
Bypass Mode
The left LED is orange.
Orange
In Bypass mode, access to the premises is dependent on whether the controller's Lock Strike Relay is programmed for Fail Safe Operation or
Fail Secure Operation. When the Lock Strike is programmed for Fail
Secure Operation, the door is locked until is pressed. When the
Lock Strike is programmed for Fail Safe Operation, the door is constantly unlocked.
AYC-Qx4 Family Installation and Programming Manual 33
Controller Operation
5.2.3
Secure Mode
The left LED is red.
Red
Only Secure and Master users can access the premises in Secured mode.
A Secure user must enter the Primary and Secondary codes to gain entry. After entering the Primary code, the right LED flashes green for
10 seconds, during which the Secondary code must be entered. A
Master user only needs to present the code once to gain entry.
5.2.4
Changing the Modes of Operation
5.2.4.1
Changing from Normal Mode to Secure Mode
The default factory setting for the Normal/Secure code is 3838.
To change from Normal to Secure mode:
1.
Enter the Normal/Secure code.
Green
The left LED flashes red.
Red
2.
Press # to confirm the mode change.
The left LED stops flashing.
Red
5.2.4.2
Changing from Secure Mode to Normal Mode
The default factory setting for the Normal/Secure code is 3838.
To change from Secure to Normal mode:
1.
Enter the Normal/Secure code.
The left LED flashes green.
Red
Green
2.
Press # to confirm the mode change.
The left LED stops flashing.
Green
34 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.2.4.3
Changing from Normal Mode to Bypass Mode
See Section 5.9.7 to create/modify the Normal/Bypass code.
To change from Normal to Bypass mode:
1.
Enter the 4-digit Normal/Bypass code.
Green
The left LED flashes orange.
Orange
2.
Press # to confirm the mode change.
The left LED stops flashing.
Orange
5.2.4.4
Changing from Bypass Mode to Normal Mode
See Section 5.9.7 to create/modify the Normal/Bypass code.
To change from Bypass to Normal mode:
1.
Enter the 4-digit Normal/Bypass code.
Orange
The left LED flashes green.
Green
2.
Press # to confirm the mode change.
The left LED stops flashing.
Green
5.3
Auxiliary Input and Output
For optimum usability in different applications, the controller’s auxiliary input and output can be configured in ten different modes of operation (see Section 5.9.9).
5.4
Door Alarms
Door alarms can be generated by connecting the Auxiliary Input to a
Door Position Switch. Either Door-Forced or Door-Ajar conditions are supported, as well as, a configurable delay timer for each alarm type.
Only one door alarm is enabled at any one time. Door alarms may activate auxiliary output and siren depending on the auxiliary settings.
AYC-Qx4 Family Installation and Programming Manual 35
Controller Operation
5.5
Internal Case and Back Tamper
If the unit is forcibly opened or it is removed from the wall, a tamper event is triggered. A tamper output opens sending a to the connected
Alarm system (purple wire) the event closes when the tamper is closed
(case is re-closed or re-attached to the wall).
The tamper event can also activate the auxiliary output if the controller is in Auxiliary Mode 3 (see Table 5).
5.6
Lockout Feature (Keypad/Card Tamper)
If the controller is presented with wrong codes (PIN or card) consecutively several times, the unit goes into Lockout mode.
When a lockout occurs, the controller’s reader and keypad are deactivated so no codes can be entered until the set lockout period expires.
During Lockout mode, the left LED is Off, the right LED flashes red, and the controller beeps every two seconds.
5.7
REX Function
The REX button is connected to Rosslare’s secured intelligent power supply. The REX button must be located inside the premises to be secured and is used to open the door without the use of a PIN code. It is usually located in a convenient location, such as inside the door or at a receptionist's desk. The function of the REX button depends on whether the Lock Strike Relay is programmed for Fail Safe Operation or Fail Secure Operation.
Fail Secure Operation – From the moment the REX button is pressed, the door is unlocked until the Lock Strike Release Time passes. After this time, the door is locked even if the REX button is not released.
Fail Safe Operation – From the moment the REX button is pressed, the door is unlocked until the REX button is released, plus the Lock Strike Release Time. In this case, the Lock Strike
Relay only begins its count down once the REX button is released.
36 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.8
Secured Intelligent Power Supply
Rosslare’s secured intelligent power supplies are designed for use with
Rosslare's secured standalone access control units, including the
AYC-Qx4 series. The AYC-Qx4 units are designed to operate indoors and are installed within the secured premises. The units must be used with one of Rosslare’s secured intelligent power supplies, which provides Lock Strike output and REX input. The AYC-Qx4 and the power supply communicate through a proprietary Rosslare protocol, which provides a secure link between them. This in turn activates the door lock.
Each power supply unit contains a speaker connection for all sounder abilities.
For more information, see the
PS-x25x Installation Manual
.
5.9
Programming as a Controller
Programming is done solely via the unit's keypad driven Programming
Menu System. To reach the Programming Menu System, the unit must first be put into Programming mode (see Section 5.9.1).
During the manufacturing process, certain codes and settings are preprogrammed. These settings are the called the default factory settings.
Table 4 shows the names of all the controller programming menus. It also shows of all the default factory codes and settings for the units.
Table 4: Controller Programming Menu
Menu
No.
Menu Description
4 digits
Default
5 digits
6 digits
4-8 digits
1 Changing Lock Strike Code
2 Change Auxiliary Code
2580 25802 258025 25802580
0852 08520 085208 08520852
3 Changing Program Code 1234 12341 123412 12341234
4 Changing Normal/Secure Code 3838 38383 383838 38383838
5 Changing Normal/Bypass Code N/A
AYC-Qx4 Family Installation and Programming Manual 37
Controller Operation
Menu
No.
Menu Description
6 Changing Door Release Time
Define auxiliary inputs/outputs
Set Lockout
Backlight Behavior
7 Enrolling PIN Code
8 Deleting PIN Code
9 Code assignment with strike/auxiliary
0 Return to factory defaults or change PIN code Length
4 digits
Default
5 digits
6 digits
0004
2004
4000
5100
N/A
N/A
N/A
N/A
4-8 digits
You will find a complete description and instructions for each of the above menu items on the following subsections.
5.9.1
Entering Programming Mode
• The unit must be in Normal mode to enter Programming mode.
• The factory 4-digit Programming code is 1234.
• If a Programming code is not entered within five seconds, the unit returns to Normal mode.
To enter Programming mode:
1.
Press # twice.
The left LED turns off and the right LED turns red.
2.
Enter your 4-digit Programming code.
Red
The right LED turns green.
Green
38 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.9.2
Exiting Programming Mode
To exit Programming mode:
1.
Press # twice to exit Programming mode at any time.
You hear 3 beeps.
The left LED turns green and the right LED turns off.
Green
Wrong entries reset the controller back to Normal mode.
While in Programming mode, if no key is pressed for one minute, the unit exits Programming mode and returns to Normal mode.
5.9.3
Changing Lock Strike Code
The Lock Strike code is mainly used as a method to quickly test the
Lock Strike Relay during installation.
When the first user is added to the controller, the default Lock Strike code is automatically deleted. Once the code is programmed again, it is not deleted with the entry of additional user codes.
• Lock Strike code does not work in the Secure mode.
• Wrong entries return the controller to Normal mode.
• Code 0000 erases the Lock Strike code.
• The factory default 4-digit Lock Strike code is 2580.
To change the Lock Strike code:
1.
Enter Programming mode.
2.
Press 1 to enter Menu 1.
Green
The left LED turns red.
Red Green
3.
Enter the new code you wish to set as the
Lock Strike code.
AYC-Qx4 Family Installation and Programming Manual 39
Controller Operation
You hear three beeps.
The system returns to Normal mode. Green
5.9.4
Changing Auxiliary Code
The Auxiliary code is mainly used as a method to quickly test the
Auxiliary Relay during installation.
When the first user is added to the controller, the default Auxiliary code is automatically deleted. Once the code is programmed again, it is not deleted with the entry of additional user codes.
• Auxiliary code does not work in the Secure mode.
• Wrong entries return the controller to Normal mode.
• Code 0000 erases the Auxiliary code.
• The factory default 4-digit Auxiliary code is 0852.
To change the Auxiliary code:
1.
Enter Programming mode.
2.
Press 2 to enter Menu 2.
Green
The left LED turns orange.
Orange Green
3.
Enter the new Auxiliary code.
You hear three beeps.
The system returns to Normal mode. Green
40 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.9.5
Changing the Programming Code
• The Programming code cannot be erased; the code 0000 is invalid and does not erase the Programming code.
• The factory default 4-digit Programming code is 1234.
To change the Programming code:
1.
Enter Programming mode.
2.
Press 3 to enter Menu 3.
Green
The left LED turns green.
Green Green
3.
Enter the new 4-digit Programming code.
You hear three beeps.
The system returns to Normal mode. Green
5.9.6
Changing the Normal/Secure Code
• Code 0000 erases the Normal/Secure code.
• This code is disabled if the Auxiliary Input is set to toggle between
Normal and Secure access modes.
• The default Normal/Secure code is 3838.
To change the Normal/Secure code:
1.
Enter Programming mode.
2.
Press 4 to enter Menu 4.
Green
The left LED flashes red.
Red Green
3.
Enter the new Normal/Secure code.
You hear three beeps.
The system returns to Normal mode. Green
AYC-Qx4 Family Installation and Programming Manual 41
Controller Operation
5.9.7
Changing the Normal/Bypass Code and Door
Chime Settings
To change the Normal/Bypass code and door chime settings:
1.
Enter Programming mode.
Green
2.
Press 5 to enter Menu 5.
The left LED flashes orange.
Orange Green
3.
There are four different ways to program the Normal/Bypass code and door chime:
Disable both Bypass code and the door chime.
Enter the code 0000 .
Disable Bypass code and enable the door chime. Enter the code 0001 .
Enable Bypass code and disable the door chime. Enter any code ending with 0.
Enable Bypass code and enable the door chime. Enter a code not ending with 0.
You hear three beeps.
The system returns to Normal mode. Green
42 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.9.8
Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time
The default value is 0004, which corresponds to Fail Secure operation, no siren, and 4-seconds Lock Strike release time.
To set the Fail Safe/Secure Operation, Tamper Siren and Lock
Strike Release Time:
1.
Enter Programming mode.
2.
Press 6 to enter Menu 6.
Green
The left LED flashes green.
Green Green
3.
Construct a code using the following instructions:
First digit
For Fail Secure Operation, the first digit should be 0 .
For Fail Safe Operation the first digit should be 1 .
Second digit
Siren Time in minutes (1–9, 0 – disabled)
Third and fourth digits
Enter the number of seconds (from 1 to 99) that you want the Lock Strike to be released.
For example, 0312 means a Fail Secure Operation consisting of a
3-minute siren and a 12-second Lock Strike release time.
You hear three beeps.
The system returns to Normal mode. Green
AYC-Qx4 Family Installation and Programming Manual 43
Controller Operation
5.9.9
Defining the Auxiliary Input and Output
The default auxiliary setting is 2004.
To define the auxiliary input and output:
1.
Enter Programming mode.
2.
Press 6 to enter Menu 6.
Green
The left LED flashes green.
Green Green
3.
Construct a code using the following instructions:
Second digit (Auxiliary Mode)
In addition to the Lock Strike Relay and Lock Strike REX, the unit features an Auxiliary Input. The Auxiliary mode defines the function of the Auxiliary Input.
Third and fourth digits (Auxiliary Setting)
Each of the Auxiliary modes has a 2-digit setting that affects how the Auxiliary mode functions (Table 5).
You hear three beeps.
The system returns to Normal mode. Green
Table 5: Quick Reference Guide for Auxiliary Mode Setting
Aux.
Mode
0
1
Aux. Input
Function
AUX REX
Aux.
Output
Activated by
Aux.
Relay
Valid code or
AUX REX
N.O.
Valid code N.O.
Aux. Settings
(in seconds)
2
Normal/Secure switch
Normal/Secure switch
Star button
(*)
N.O.
01 to 99 Aux. relay release time
01 to 99 Aux. relay release time
01 to 99 Aux. relay release time
44 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
Aux.
Mode
3
4
5
6
7
8
9
Aux. Input
Function
Normal/Secure switch
Normal/Secure switch
Door Monitor
Door Monitor
Door Monitor
Aux.
Output
Activated by
Aux.
Relay
Tamper event
N.C.
Direct shunt N.O.
Shunt N.C.
Forced door N.C.
Door ajar N.C.
LED control – Green Valid code N.O.
LED control – Red Valid code N.O.
Aux. Settings
(in seconds)
01 to 99 Aux. relay release time
01 to 99 Shunt time
01 to 99
Maximum shunt time
01 to 99 Forced delay
01 to 99 Ajar delay
01 to 99 Aux. relay release time
01 to 99 Aux. relay release time
The following subsections describe each Auxiliary mode.
5.9.9.1
Auxiliary Mode 0
Auxiliary input function: Activates the auxiliary output
Auxiliary output activated by: Valid user code, Auxiliary code, and
Auxiliary input
For example, in Auxiliary Mode 0, the controller can function as a
2-door controller. The auxiliary relay is to be attached to the lock on the second door. The auxiliary setting defines the door open time for the second door. The auxiliary input is to be attached to the REX pushbutton for the second door. The Door Monitor input feature for the second door is not enabled when using this mode.
AYC-Qx4 Family Installation and Programming Manual 45
Controller Operation
5.9.9.2
Auxiliary Mode 1
Auxiliary input function: Toggles Normal/Secure modes
Auxiliary output activated by: Valid user code, Auxiliary code
For example, in Auxiliary Mode 1, the controller can function as a
2-door controller. The auxiliary relay is to be attached to the lock on the second door. The REX feature for the second door is not enabled when using this mode.
The auxiliary setting defines the door open time for the second door.
The auxiliary input can switch the mode of operation of the controller between Normal and Secure modes. By connecting a switch timer or alarm system output to the auxiliary input, the controller can be automatically switched from Normal mode (during office hours) to
Secure mode (after office hours).
5.9.9.3
Auxiliary Mode 2
Auxiliary input function: Toggles Normal/Secure modes
Auxiliary output activated by: Bell Button ( )
For example, in Auxiliary Mode 2, the auxiliary relay can function as a general purpose time switch that can be activated when is pressed.
The auxiliary setting establishes for how long the auxiliary relay is to be activated. The auxiliary input can switch the mode of operation of the controller between Normal and Secure modes. By connecting a switch timer or alarm system output to the auxiliary input, the controller can be automatically switched from Normal mode (during office hours) to Secure mode (after office hours).
46 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.9.9.4
Auxiliary Mode 3
Auxiliary input function: Toggles Normal/Secure modes
Auxiliary output activated by: Alarms
For example, in Auxiliary Mode 3, the auxiliary output is activated if the controller is tampered; that is, if the case is forcibly opened or removed from the wall. The auxiliary input can switch the mode of operation of the controller between Normal and Secure modes. By connecting a switch timer or alarm system output to the auxiliary input, the controller can be automatically switched from Normal mode (during office hours) to Secure mode (after office hours).
5.9.9.5
Auxiliary Mode 4
Auxiliary input function: Toggles Normal/Secure modes
Auxiliary output activated by: Direct shunt (explanation below)
For example, in Auxiliary Mode 4, the controller is capable of bypassing an alarm zone by shunting an alarm system’s door sensor.
The auxiliary output is to be wired in parallel to the door sensor output. When in use, the auxiliary output is normally open and the door sensor functions normally. When a valid code is entered, the auxiliary relay shunts the door sensor for the duration of the shunt time, as defined by the auxiliary setting. If the door is left open longer than the shunt time, an alarm is triggered.
5.9.9.6
Auxiliary Mode 5
Auxiliary input function: Door Monitor
Auxiliary output activated by: Shunt (explanation below)
For example, in Auxiliary Mode 5, the controller is capable of shunting an alarm system. In this mode, the auxiliary input is to be wired to the magnetic contact switch on the door. The auxiliary relay is wired to the alarm system. Without a valid code entered, the auxiliary relay matches the condition of the magnetic contact switch; if the door opens, the auxiliary relay opens; if the door closes, the auxiliary relay closes. When a valid code is entered, a countdown for maximum shunt time, as defined by the auxiliary setting, begins; if the door is not closed before the maximum shunt time, the alarm is triggered.
AYC-Qx4 Family Installation and Programming Manual 47
Controller Operation
5.9.9.7
Auxiliary Mode 6
Auxiliary input function: Door Monitor
Auxiliary output activated by: Forced entry
For example, in Auxiliary Mode 6, the controller can trigger the auxiliary relay if the door has been forced. If the siren settings are enabled, the siren is activated.
In this mode, the auxiliary input functions as a door monitor switch and is wired to the magnetic contact switch on the door. The auxiliary relay is to be wired to the alarm system. If the door is forced open, the controller waits for the period of the forced door delay time to elapse and then it activates the auxiliary relay. The auxiliary setting sets the forced door delay period.
5.9.9.8
Auxiliary Mode 7
Auxiliary input function: Door Monitor
Auxiliary output activated by: Door Ajar (door held open)
For example, in Auxiliary Mode 7, the controller can trigger the auxiliary relay, if it detects that the door has been held open (ajar) too long. In this mode the auxiliary input functions as a door monitor switch and is wired to the magnetic contact switch on the door. The auxiliary relay is to be wired to the alarm system. If the door is opened, the controller waits for the door ajar delay time to elapse and if the door does not close prior to the end of this period, the controller activates the auxiliary relay. The auxiliary setting defines the door-ajar time.
5.9.9.9
Auxiliary Mode 8
This mode controls the door indicator (right LED).
The right LED is not lit when:
• A valid code is entered
• While in Secure mode when waiting for Secondary code.
Auxiliary input function: Green LED control
Auxiliary output activated by: Valid user code, Auxiliary code
48 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
For example, in Auxiliary Mode 8, the controller can function as a
2-door controller and also provide LED indicator functionality control.
The auxiliary relay is connected to the lock on the second door. The auxiliary setting defines the Door Open time for the second door. The auxiliary input is used to control the door indicator (right LED). If the auxiliary input is open, the right LED flashes green; if the auxiliary input is closed, the right LED flashes red.
5.9.9.10
Auxiliary Mode 9
This mode controls the door indicator (right LED).
The right LED is not lit when:
• A valid code is entered
• While in Secure mode when waiting for Secondary code.
Auxiliary input function: Red LED control
Auxiliary output activated by: Valid user code, Auxiliary code
For example, in Auxiliary Mode 9, the controller can function as a
2-door controller and also provide LED indicator functionality control.
The auxiliary relay is connected to the lock on the second door. The auxiliary setting defines the Door Open time for the second door. The auxiliary input is used to control the door indicator (right LED). If the auxiliary input is open, the right LED flashes red; if the auxiliary input is closed the right LED flashes green.
5.9.10
Setting the Lockout Feature
If the controller is presented with wrong codes (PIN or card) consecutively several times, the unit goes into Lockout mode.
When a lockout occurs, the controller keypad and reader are locked so no codes can be entered until the set lockout period expires.
During Lockout, the left LED is Off, the right LED flashes red, and the controller beeps every two seconds. The default setting for the
Lockout Feature is 4000 (Lockout Disabled).
Using the lockout feature is highly recommended, especially when selecting to use short PIN code length (4 or 5 digits).
AYC-Qx4 Family Installation and Programming Manual 49
Controller Operation
To set the lockout feature:
1.
Enter Programming mode.
2.
Press 6 to enter Menu 6.
Green
The left LED flashes green.
Green Green
3.
Construct a code using the following instructions:
Second digit
Sets the number of wrong code attempts, which causes a
Lockout between 0 and 9 attempts.
Third and fourth digits
Sets the Duration of the lockout, between 00 and 99; the value is multiplied by ten, resulting in 0 to 990 seconds.
5.9.11
Setting the Backlight Behavior
The controller allows you to define the way the unit’s backlight works.
To set the backlight behavior:
1.
Enter Programming mode.
2.
Press 6 to enter Menu 6.
Green
The left LED flashes green.
Green Green
50 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
3.
Enter one of the following codes:
5000 – Backlight off
5100 – Backlight on (default)
5200 – Backlight is off, activates for 10 seconds when a key is pressed, after which it dims until off
5300 – Backlight is dimmed, activates for 10 seconds when a key is pressed, after which it returns to a dimmed level
5.9.12
Enrolling Primary and Secondary Codes
5.9.12.1
Primary Codes
Primary codes can only be enrolled to an empty user slot, meaning a slot where there is no existing Primary code.
Primary codes must be unique, meaning one user’s Primary code may not be the same as other user’s Primary code.
Primary codes cannot be the same as any system codes, such as the Normal/Secure code or Lock Strike code.
Users who hold a Primary code can gain entry only during Normal mode.
5.9.12.2
Secondary Codes
Secondary codes can only be enrolled to a user slot that already has a Primary code enrolled but has no Secondary code.
Secondary codes do not have to be unique, meaning multiple users can all hold the same Secondary code.
Secondary codes cannot be the same as any system codes, such as the Normal/Secure or Lock Strike codes.
Users who hold Secondary codes can gain entry in any mode of operation.
AYC-Qx4 Family Installation and Programming Manual 51
Controller Operation
5.9.12.3
Enrolling Methods
There are two methods to enroll Primary and Secondary codes:
Standard Method
The Standard Method is mainly used when the user slot number for the user you wish to program is known. You can program both Primary and Secondary codes using the Standard method
(see Section 5.9.12.4).
Code Search Method
The Code Search Method is mainly used when enrolling a user’s
Secondary code and the User Slot code is unknown.
The Code Search method only works if a user’s Primary code is already enrolled but the Secondary code is not (see Section
5.9.12.5).
5.9.12.4
Enrolling Primary and Secondary Codes using
Standard Method
To enroll Primary and Secondary codes using the Standard method:
1.
Enter Programming mode.
2.
Press 7 to enter Menu 7.
Green
The right LED turns orange.
Orange
3.
Enter the 3-digit user slot number between
001and 500 for the slot to which you wish to enroll a Primary or Secondary code.
For example, User Slot 003 represents User #3.
If the selected slot has no Primary code, the left LED flashes green, indicating that the controller is ready to accept a Primary code.
Gree Orange
52 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
If the selected slot already has a Primary code but no Secondary code, the left LED flashes red, indicating that the controller is ready to accept a Secondary code.
Red Orange
If the selected slot already has a Primary and
Secondary code, you hear a long beep and the controller returns to Normal mode.
4.
Perform one of the following:
Green
Enter the PIN code that you want to assign as the Primary or Secondary code for this slot number.
Present your user card that you want to assign as the Primary or Secondary code for this slot number.
If the PIN or user card presented is valid, the left LED stops flashing and the controller is ready for you to enter the next
3-digit slot number (refer to Step 3) for the slot to which you want to assign a code.
5.
Do one of the following:
Press # to move to the next available user slot number.
Enter another 3-digit user slot number.
If you do not wish to continue enrolling codes, press # twice and the controller returns to Normal mode.
AYC-Qx4 Family Installation and Programming Manual 53
Controller Operation
5.9.12.5
Enrolling Secondary Codes using the Code Search
Method
The Code Search feature enables you to quickly enroll a Secondary code to a user who already has a Primary code.
To enroll secondary codes using the Code Search method:
1.
Enter Programming mode.
2.
Press 7 to enter Menu 7.
Green
The right LED turns orange.
Orange
3.
Enter 000 as the 3-digit user slot number.
The right LED flashes orange.
4.
Perform one of the following:
Orange
Enter the PIN code belonging to the user for whom you wish to add a Secondary code.
Present the user card belonging to the user for whom you wish to add a Secondary code.
The left LED flashes red.
If the Primary code entered is not valid, you hear a long beep and the unit continues to wait for a valid Primary code.
Red Orange
5.
Perform one of the following:
Enter the PIN code to be used as the
Secondary code.
Present the user card to be used as the Secondary code.
54 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
If the Secondary code is valid, the controller beeps three times and returns to Normal mode.
If the Secondary code is invalid, the controller sounds a long beep, and the unit continues to wait for a valid Secondary code to be entered.
5.9.13
Deleting Primary and Secondary Codes
There are two methods to delete Primary and Secondary codes: the
Standard Method and the Code Search Method.
When deleting a user slot, both the Primary code and the Secondary code are erased.
It is recommended that a record be kept of added and deleted users so that it is easier to keep track of which user slots are empty and which user slots are not.
5.9.13.1
Deleting Primary and Secondary Codes using Standard
Method
To delete the Primary and Secondary codes using the Standard
Method:
1.
Enter Programming mode.
2.
Press 8 to enter Menu 8.
Green
The left LED turns red and the right LED turns orange.
3.
Enter the 3-digit User Slot code you wish to delete.
Red Orange
The left LED flashes red indicating the controller is waiting for the Programming code to confirm the deletion.
Red Orange
If the user slot is empty, you hear a long beep and the unit returns to Normal mode.
AYC-Qx4 Family Installation and Programming Manual 55
Controller Operation
4.
Enter your 4-digit Programming code to confirm the deletion.
If the Programming code is valid, three beeps are heard and the controller returns to Normal mode.
If the Programming code is invalid, a long beep is heard and the controller returns to Normal mode.
5.9.13.2
Deleting Primary and Secondary Codes using Search
Method
To delete the Primary and Secondary codes using the Code
Search Method:
1.
Enter Programming mode.
2.
Press 8 to enter Menu 8.
Green
The left LED turns red and the right LED turns orange.
3.
Enter 000 as the 3-digit user slot number.
Red Orange
The right LED flashes orange.
4.
Perform one of the following:
Red Orange
Enter the PIN code of the Primary code belonging to the user you want to delete.
Present the user card of the Primary code belonging to the user you want to delete.
The left LED flashes red.
Red Orange
56 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.
Enter your 4-digit Programming code to confirm the deletion.
If the Programming code is valid, you hear three beeps and the unit returns to Normal mode.
If the Programming code is invalid, you hear a long beep and the unit returns to Normal mode.
5.9.14
Relay Codes Assignment
When a primary code is enrolled for any user, the user is authorized to activate the Lock Strike relay. However, different user codes may be set to operate the auxiliary relay instead or operate both the Lock strike and auxiliary relay. Assignment of such codes is achievable for any valid user code entered in the controller.
There are two methods to assign relay codes to users: a standard method and a search method.
5.9.15
Relay Code Assignment using Standard Method
To assign relay code using the Standard method:
1.
Enter Programming mode.
Green
2.
Press 9 to enter Menu 9.
The left LED turns green and the right LED turns orange. Green Orange
3.
Enter the 3-digit user slot for code assignment.
The left LED flashes green.
4.
Enter the assignment digit for the current user slot:
Green Orange
1 activates the Lock Strike relay only default
2 activates the Auxiliary relay only
3 activates the Lock Strike and Auxiliary relays
AYC-Qx4 Family Installation and Programming Manual 57
Controller Operation
If the assignment code is valid, the left LED stops flashing.
The controller is now waiting for another slot number.
5.
Do one of the following:
Press # to move to the next available user slot number.
Enter another 3-digit user slot number.
If you do not wish to continue enrolling codes, press # twice and the controller returns to Normal mode.
5.9.16
Relay Code Assignment using Search Method
To assign relay code using the Search method:
1.
Enter Programming mode.
2.
Press 9 to enter Menu 9.
Green
The left LED turns green and the right LED turns orange.
3.
Enter 000 for user slot access.
The right LED flashes orange.
Green Orange
Green Orange
4.
Do one of the following:
Enter the PIN code of the Primary code belonging to the user you want to delete.
Present the user card of the Primary code belonging to the user you want to delete.
The left LED flashes green.
Green Orange
58 AYC-Qx4 Family Installation and Programming Manual
Controller Operation
5.
Enter the assignment digit for the current user slot:
1 activates the Lock Strike relay only default
2 activates the Auxiliary relay only
3 activates the Lock Strike and Auxiliary relays
If the assignment digit is valid, three beeps are heard and the controller returns to Normal mode.
If the assignment digit is invalid, a long beep sounds and the controller waits for another assignment digit to be entered.
5.9.17
PIN Code Length/Factory Default Settings
You must be very careful before using this command! Changing the PIN code length also erases the entire memory contents, including all user and special codes, and return all codes to their factory default settings.
To change the PIN code length:
1.
Enter Programming mode.
Green
2.
Select the desired PIN code length as follows:
00 – Returns to factory defaults and sets a 4-digit code
05 – Returns to factory defaults and sets a 5-digit code
06 – Returns to factory defaults and sets a 6-digit code
08 – Returns to factory defaults and sets a 4-8 digit code
When choosing the 4–8 option, please note that you should either enter zeros before the code, or press # at the end (for example if your code is 12345, enter either 00012345 or
12345# ).
Both LEDs flash red.
Red Red
AYC-Qx4 Family Installation and Programming Manual 59
Controller Operation
3.
Enter your 4-digit Programming code.
If the Programming code is valid, all memory is erased. You hear three beeps and the controller returns to Normal mode.
If the Programming code is invalid, you hear a long beep and the controller returns to Normal mode without erasing the memory contents.
5.9.18
Replacing a Lost Programming Code
The unit must be in Normal mode; otherwise, this does not work. Make sure that the left LED is green before proceeding.
To replace a lost Programming code:
1.
Remove power from the power supply unit.
2.
Press the REX button on the power supply unit.
3.
Apply power to the unit with REX button pressed.
4.
Release the REX button.
5.
You now have 10 seconds to program a new Programming code into the access control unit using the initial default code 1234, before the controller reverts to the existing code.
5.9.19
Exiting Secure Mode if Normal/Secure Code was
Lost
To exit Secure mode if Normal/Secure Code was lost:
1.
Remove power from the power supply unit.
2.
Press the REX button on the power supply unit.
3.
Apply power to the unit with the REX button pressed.
4.
Release the REX button.
5.
You now have 10 seconds to exit Secure mode using the initial default Normal/Secure code 3838.
6.
Program a new Normal/Secure code as described in Section 5.9.6.
60 AYC-Qx4 Family Installation and Programming Manual
Declaration of Conformity
A.
Declaration of Conformity
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference.
This device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
AYC-Qx4 Family Installation and Programming Manual 61
Limited Warranty
B.
Limited Warranty
The full ROSSLARE Limited Warranty Statement is available in the
Quick Links section on the ROSSLARE website at www.rosslaresecurity.com
.
Rosslare considers any use of this product as agreement to the
Warranty Terms even if you do not review them.
62 AYC-Qx4 Family Installation and Programming Manual
Asia Pacific, Middle
East, Africa
Rosslare Enterprises Ltd.
Kowloon Bay, Hong Kong
Tel: +852 2795-5630
Fax: +852 2795-1508 [email protected]
United States and
Canada
Rosslare Security Products, Inc.
Southlake, TX, USA
Toll Free: +1-866-632-1101
Local: +1-817-305-0006
Fax: +1-817-305-0069 [email protected]
Europe
Rosslare Israel Ltd.
Rosh HaAyin, Israel
Tel: +972 3 938-6838
Fax: +972 3 938-6830 [email protected]
CERT
ISO 9001
ISO 14001
AYC-Qx4
Latin America
Rosslare Latin America
Buenos Aires, Argentina
Tel: +54-11-4001-3104 [email protected]
China
Rosslare Electronics (Shenzhen) Ltd.
Shenzhen, China
Tel: +86 755 8610 6842
Fax: +86 755 8610 6101 [email protected]
India
Rosslare Electronics India Pvt Ltd.
Tel/Fax: +91 20 40147830
Mobile: +91 9975768824 [email protected]
advertisement
Key Features
- Vandal-resistant construction for durability in harsh environments
- Convertible design allows for use as a reader or controller
- Supports multiple card formats and PIN entry
- Standalone controller operation for up to 500 users and two doors
- Multiple modes of operation for access control flexibility
- Auxiliary input and output for interfacing with external devices
- Door alarms for unauthorized access attempts
- Tamper detection for added security
Related manuals
Frequently Answers and Questions
How many users can the AYC-Q64B store?
Can the AYC-Q64B operate in both reader and controller modes simultaneously?
What is the maximum number of doors that the AYC-Q64B can control?
Does the AYC-Q64B have any anti-tamper features?
Can I change the programming code of the AYC-Q64B?
How do I enter programming mode on the AYC-Q64B?
What is the factory default programming code for the AYC-Q64B?
advertisement
Table of contents
- 9 Introduction
- 9 Reader/Controller Types
- 10 Box Content
- 10 Ancillary Equipment
- 11 Technical Specifications
- 13 Installation
- 13 Mounting
- 14 Wiring Instructions
- 14 Wiring the Unit as a Reader
- 15 Wiring the Unit as a Controller
- 18 Reader Operation
- 18 Standby Mode
- 18 Programming as a Reader
- 20 Entering Programming Mode
- 20 Exiting Programming Mode
- 21 Selecting Keypad Transmission Format
- 26 Selecting Proximity Card Transmission Format
- 28 Changing the Programming Code
- 29 Changing the Facility Code
- 29 Setting the Backlight Behavior
- 30 Return to Factory Default Settings
- 31 Replacing a Lost Programming Code
- 32 Controller Operation
- 32 Normal, Secure, and Master Users
- 33 Modes of Operation
- 33 Normal Mode
- 33 Bypass Mode
- 34 Secure Mode
- 34 Changing the Modes of Operation
- 35 Auxiliary Input and Output
- 35 Door Alarms
- 36 Internal Case and Back Tamper
- 36 Lockout Feature (Keypad/Card Tamper)
- 36 REX Function
- 37 Secured Intelligent Power Supply
- 37 Programming as a Controller
- 38 Entering Programming Mode
- 39 Exiting Programming Mode
- 39 Changing Lock Strike Code
- 40 Changing Auxiliary Code
- 41 Changing the Programming Code
- 41 Changing the Normal/Secure Code
- 42 Changing the Normal/Bypass Code and Door Chime Settings
- 43 Release Time
- 44 Defining the Auxiliary Input and Output
- 49 Setting the Lockout Feature
- 50 Setting the Backlight Behavior
- 51 Enrolling Primary and Secondary Codes
- 55 Deleting Primary and Secondary Codes
- 57 Relay Codes Assignment
- 57 Relay Code Assignment using Standard Method
- 58 Relay Code Assignment using Search Method
- 59 PIN Code Length/Factory Default Settings
- 60 Replacing a Lost Programming Code
- 60 Exiting Secure Mode if Normal/Secure Code was Lost
- 61 Declaration of Conformity
- 62 Limited Warranty