Gree Fengyun KFR-80W/A22-C, Fengyun Series Manual
GREE Fengyun KFR-80W/A22-C is a powerful air conditioner that can cool and heat your home quickly and efficiently. It has a number of features that make it a great choice for any home, including: a high energy efficiency rating, a quiet operation, and a built-in air purifier. You can use it to create a more comfortable and healthy environment in your home.
Advertisement
Advertisement
Fengyun Series
Model Remarks
~
Model Remarks
208 230V
220V 240~
Fengyun Series
2 Specifications and Technical Parameters
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W/Btu/h)
Power Input (W)
Rated Input (W)
Rated Current (A)
Air Flow Volume (m
3
/h) (H/M/L)
Dehumidifying Volume (l/h)
SEER / C.O.P (Btu/W)
Energy Class
Model of Indoor Unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Indoor unit
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB
(A) (H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (W/H/D) ( mm)
Dimension of Package
(L/W/H) ( mm)
Net Weight /Gross Weight
(kg)
GWCN24C1ND1BA
COOLING
208 - 230V
60Hz
6450/22000
2000
2810
14.4
1150/1100/1050
3
11/-
/
GWCN24C1ND1BA/I
1400/1300/1200
φ
40
/
3
0.18
106 X 980
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
49/47/45
GWCN24C1NK1BA
COOLING
220-240V~
50HZ
6850
2200
3030
10.6
1150
3
3.1
/
GWCN24C1NK1BA/I
1410/1310/1260
GWCN28C1TK1AA
COOLING
220-240V~
50Hz
8000W/28000Btu/h
3200
4300
22.99
1200/1100/1000
3
2.5
/
GWCN28C1TK1AA/I
35
/
3
0.19
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
50/47/45
1410/1310/1260
φ
45
/
3
0.4
106 X 890
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
50/48/46
59/57/55
1178 X326X227
1265X417X328
17.5/24
60/57/55
1178 X326X227
1265X417X328
17.5/24
60/58/56
1178 X326X227
1265X417X333
17.5/24
Model of Outdoor Unit
Compressor
Manufacturer/trademark
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Fan Motor Speed (rpm)
Outdoor unit
Output of Fan Motor (W)
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A)
(H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (W/H/D) ( mm)
Dimension of Package (L/W/H)( mm)
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Connecti on Pipe
Gas additional charge(g/m)
Liquid Pipe (mm)
Outer Diameter
Gas Pipe (mm)
Max Distance Height (m)
Length (m)
GWCN24C1ND1BA/O
Shanghai Hitachi
SHY73MC4-U
ROTARY
56
9.7
2085
PUT-IN
Capillary
Capacitor
-7 ≤
Φ
T ≤
9.52
2-1.4
46
GWCN24C1NK1BA/O GWCN28C1TK1AA/O
HIGHLY
SHV33YE6UU
TECUMSEH
PRODUCTS INDIA PVT.
AWR5538EXC
ROTATORY
60
Hermetic motor compressor
92
10.9
15.2
2335 3200
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
-5
Capillary
Capacitor
℃≤
Φ
T ≤
9.52
2-1.4
52 ℃
730.5X673X44
815
0.27
Φ
60
3.5
/
460
/
T1
I
IP24
2.4
0.6
58
68
950X700X412
1100X755X450
65/77
R22 1.9
/
/
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
730.5X813X44
815
60
1
3.5
/
Axial fan –1
Φ 460
/
T1
I
IP24
2.4
0.6
60
70
950X840X412
1100X880X450
72/77
R22 / 2.2kg
/
/
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
1017.5X813X44
920
Φ
92
0.9
3.5
/
482
/
T3
I
IP24
2.5
0.6
62
72
950X840X412
1100X880X450
90/105
R22/2.9
/
/
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W/Btu/h)
Power Input (W)
Rated Input (W)
Rated Current (A)
Air Flow Volume (m
3
/h) (H/M/L)
Dehumidifying Volume (l/h)
SEER / C.O.P (Btu/W)
Energy Class
Model of Indoor Unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Indoor unit
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB
(A) (H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (W/H/D) ( mm)
Dimension of Package
(L/W/H) ( mm)
Net Weight /Gross Weight
(kg)
GWCN28C1NK3AA
COOLING HEATING
220-240V~
50HZ
8000
2800
4000
17.4
/
/
/
/
1200
3
2.85/3.15
4
GWCN28C1NK3AA/I
1410/1310/1260
35
-
3
0.19
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/48/47
59/57/56
1178 X326X227
1265X417X328
17.5/24
GWHN28C1NK3AA
COOLING HEATING
230V~
50HZ
8000
2800
4000
17.4
8800
2800
3600
15.7
1200
3
2.85/3.15
4
GWHN28C1NK3AA/I
1410/1310/1260
35
-
3
0.19
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/48/47
59/57/56
1178 X326X227
1265X417X328
17.5/24
Model of Outdoor Unit
Compressor
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Fan Motor Speed (rpm)
Outdoor unit
Output of Fan Motor (W)
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive
Operating Pressure for the
Permissible Excessive
(H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (W/H/D) ( mm)
Dimension of Package
Connecti
Refrigerant Charge (kg)
Length (m)
Gas additional charge(g/m) on Pipe Outer Diameter
Max Distance
Liquid Pipe
(mm)
Gas Pipe
(mm)
Height (m)
Length (m)
GWCN28C1NK3AA/O
DAIKIN
JT90G-P8V1N
Hermetic motor compressor
75.5
13.2
2950
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
1017.5X813X44
920
92
0.9
3.5
/
Axial fan –1
Φ 482
Auto defrost
T1
I
IP24
2.5
0.6
60
70
950X412X840
1100X450X880
90/105
R410A/2.6
5
30
Φ
9.52(3/8”)
Φ 16(5/8”)
10
15
GWHN28C1NK3AA/O
DAIKIN
JT90G-P8V1N
Hermetic motor compressor
75.5
13.2
2950
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
1017.5X813X44
920
92
0.9
3.5
/
Axial fan –1
Φ 482
Auto defrost
T1
I
IP24
2.5
0.6
60
70
950X412X840
1100X450X880
90/105
R410A/2.6
5
30
Φ
9.52(3/8”)
Φ 16(5/8”)
10
15
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W/Btu/h)
Power Input (W)
Rated Input (W)
Rated Current (A)
Air Flow Volume (m
3
/h) (H/M/L)
Dehumidifying Volume (l/h)
EER / C.O.P (W/W)
Energy Class
Model of Indoor Unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Indoor unit
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB (A)
(H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (L/W/H) ( mm)
Dimension of Package
(L/W/H) ( mm)
Net Weight /Gross Weight
(kg)
GWHN24C1NK1BA
COOLING
6800
2200
2810
10.6
220-240V~
50HZ
1200
3
2.95/3.2
60/57/55
HEATING
1178 X326X227
1265X417X328
7300
2250
2920
10.7
GWHN24C1NK1BA/I
1410/1310/1260
35
-
3.5
0.19
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
1.5
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
50/47/45
17.5/24
GWCN24C1ND1AA
COOLING
220V~
60HZ
7000
2450
3300
23.5
1100
3
2.86
GWCN24C1ND1AA/I
1260/1170/1080
25
——
3.5
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
46/44/41
56/54/51
1178 X326X227
1265X417X333
17.5/24
Outdoor unit
Model of Outdoor Unit
Compressor Manufacturer/trademark
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Fan Motor Speed (rpm)
Output of Fan Motor (W)
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Connecti on Pipe
Sound Power Level dB (A) (H/M/L)
Dimension (L/W/H) ( mm)
Dimension of Package (L/W/H)( mm)
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Gas additional charge(g/m)
Outer Diameter
Max Distance
GWHN24C1NK1BA/O
HIGHLY
SHV33YE6UU
ROTATORY
60
10.9
2335
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
-
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
2.4
0.6
60
70
1006X420X847
1100X450X905
72/77
R22 /2.4
/
/
Liquid Pipe
Height (m)
Length (m)
GWCN24C1ND1AA/O
C-2R170H6S
Hermetic motor compressor
66
12.2
1700
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
----
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
2.5
0.6
58
68
1006X340X847
1100X450X905
72/77
R22 / 2.5kg
/
7.5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W/Btu/h)
Power Input (W)
Rated Input (W)
Rated Current (A)
Air Flow Volume (m
3
/h) (H/M/L)**
Dehumidifying Volume (l/h)
EER / C.O.P (W/W)
Energy Class
Indoor unit
Model of Indoor Unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB
(A) (H/M/L)
Sound Power Level dB (A)
(H/M/L)***
Dimension (L/W/H) ( mm)
Dimension of Package
(L/W/H) ( mm)
Net Weight /Gross Weight
(kg)
GWCN28C1TD1AA
COOLING
220V~
60Hz
8000W/28000Btu/h
3400
4050
21.66
1200/1100/1000
3
2.35
/
GWCN28C1TD1AA/I
1400/1300/1200
35
/
3
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
50/48/46
60/58/56
1178 X326X227
1265X417X333
17.5/24
GWHN28C1TD1AA
COOLING HEATING
220V~
60Hz
8000W/28000Btu/h 8800W/30000Btu/h
3400 3300
4050
21.66
4050/3800
21.66/20.32
1200/1100/1000
3
2.35/2.67
/
GWHN28C1TD1AA/I
1400/1300/1200
35
/
3
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
50/48/46
60/58/56
1178 X326X227
1265X417X333
17.5/24
Outdoor
Unit
Model of Outdoor Unit
Compressor Manufacturer/trademark
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width
(L)
Fan Motor Speed (rpm)
Output of Fan Motor (W)
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (L/W/H) ( mm)
Dimension of Package (L/W/H)( mm)
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Gas additional charge(g/m)
Connectio n Pipe
Outer Diameter
Loading
Quantity
Max Distance
20’ Container
40’ Container
40’ High Cube Container
GWCN28C1TD1AA/O
TECUMSEH PRODUCTS INDIA
AWZ5532EXN
Hermetic motor compressor
90
14.5
3200
Internal Inherent Protector
Capillary
Capacitor
-5 ℃≤ T ≤ 52 ℃
Aluminum fin-copper tube
Φ
9.52
2-1.4
1017.5X813X44
940
92
0.9
4
/
Axial fan –1
Φ 460
Auto defrost
T3
I
IP24
2.5
0.6
GWHN28C1TD1AA/O
TECUMSEH PRODUCTS INDIA
AWZ5532EXN
Hermetic motor compressor
90
14.5
3200
Internal Inherent Protector
Capillary
Capacitor
-5 ℃≤ T ≤ 52 ℃
Aluminum fin-copper tube
Φ
9.52
2-1.4
1017.5X813X44
940
92
0.9
4
/
Axial fan –1
Φ 460
Auto defrost
T3
I
IP24
2.5
0.6
62
72
950X412X840
1100X450X995
90/105
R22/2.8
Liquid Pipe (mm)
Gas Pipe (mm)
Height (m)
Length (m)
Interior Dimensions L*W*H : 5898*2352*2393 ,
Door Opening W*H : 2343*2280
Interior Dimensions L*W*H : 12032*2350*2390 ,
Door Opening W*H : 2343*2280
Interior Dimensions L*W*H : 12032*2350*2697 ,
Door Opening W*H : 2338*2585
62
72
950X412X840
1100X450X995
90/105
R22/2.8
5
30
Φ 9.52(3/8”)
Φ 16(5/8”)
10
15
43 SET
90 SET
104 SET
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W/Btu/h)
Power Input (W)
Rated Input (W)
Rated Current (A)
Air Flow Volume (m
3
/h) (H/M/L)**
Dehumidifying Volume (l/h)
EER / C.O.P (W/W)
Energy Class
Indoor unit
Model of Indoor Unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB
(A) (H/M/L)
Sound Power Level dB (A)
(H/M/L)***
Dimension (L/W/H) ( mm)
Dimension of Package
(L/W/H) ( mm)
Net Weight /Gross Weight
(kg)
GWHN24C1NK3AB
COOLING
220-240V~
HEATING
50HZ
7000
2600
3650
13.8
8000
2600
3500
13.2
1200
3
2.69/3.08
4
GWHN24C1NK3AA/I
1410/1310/1260
35
-
3
0.19
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/48/47
59/58/57
1178 X326X227
1265X417X328
17.5/24
GWHN28C1ND1AA
COOLING HEATING
220V~
60HZ
8800
3380
4600
21
9500
3350
4550
21
1200
3
2.6/2.84
/
GWHN28C1ND1AA/I
1410/1310/1260
35
——
3.5
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/47/44
59/57/54
1178 X326X227
1265X417X333
17.5/24
Outdoor
Unit
Model of Outdoor Unit
Compressor Manufacturer/trademark
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width
(L)
Fan Motor Speed (rpm)
Output of Fan Motor (W)
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (L/W/H) ( mm)
Dimension of Package (L/W/H)( mm)
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Gas additional charge(g/m)
Connectio nPipe
Outer Diameter
Max Distance
GWHN24C1NK3AB/O
SANYO
C-3RV322H1AAF
Hermetic motor compressor
74
13.2
2686
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
-
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
3.8
1.2
58
68
1006X412X840
1100X450X905
72/77
R410a / 2.45kg
Liquid Pipe (mm)
Gas Pipe (mm)
Height (m)
Length (m)
GWHN28C1ND1AA/O
/
SQ034KBA
Hermetic motor compressor
76
14
3170
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
1017.5X813X44
920
92
2.26
1.5
----
Axial fan –1
Φ 482
Auto defrost
T1
I
IP24
3.8
1.2
5
60
70
950x412x840
1100X450X995
90/100
R22X3.0kg
7.5
40
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
/
Φ 9.52(3/8”)
Φ 16(5/8”)
10
20
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity
Power Input
Rated Input
Rated Current
Air Flow Volume
Dehumidifying Volume
C.O.P / EER
Model of Indoor Unit
Indoor unit
(W)
(W)
(W)
(A)
(m
3
/h)
(L/h)
(W/W)
Fan Motor Speed (r/min) (H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width
(L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)***
Dimension (W/D/H)( mm)
Dimension of Package (W/D/H)( mm)
Net Weight /Gross Weight (kg)
GWHN24C1ND1AA
COOLING
220V~
60HZ
HEATING
7000
2450
3500
7600
2400
2750
20 15
1100
3
2.86/3.17
GWHN24C1ND1AA/I
1260/1170/1080
26
——
3.5
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ
7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
46/44/41
56/54/51
1178 X326X227
1265X417X333
17.5/24
GWCN24C1NK1AA
COOLING HEATING
220V~
60HZ
7100
2700
4000
23.5
1100
3
2.63
GWCN24C1NK1AA/I
/
/
/
/
1260/1170/1080
26
——
3
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ
7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
46/44/41
56/54/51
1178 X326X227
1265X417X333
17.5/24
Model of Outdoor Unit
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Outdoor unit
Fan Motor Speed (rpm) (H/M/L)**
Output of Fan Motor (W)
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package (W/D/H)( mm)
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Connection
Pipe
Outer
Diameter
Max
Distance
Liquid Pipe (mm)
Gas Pipe (mm)
Height (m)
Length (m)
GWHN24C1ND1AA/O
C-2R170H6S
Hermetic motor compressor
66
12.2
1700
Internal Inherent Protector
Capillary
Capacitor
-7 ≤ T ≤ 46.1
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
----
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
2.5
0.6
58
68
1006X412X847
1100X450X905
72/77
R22 / 2.4kg
7.5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
GWCN24C1NK1AA/O
LH48VBAC
Hermetic motor compressor
63
12.3
2660
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 46.1
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
----
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
2.5
0.6
58
68
1006X412X847
1100X450X905
72/77
R22 / 2.55kg
5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W)
Power Input (W) (High/Normal)
Rated Input (W) (High/Normal)
Rated Current (A) (High/Normal)
Air Flow Volume (m
3
/h) (H/M/L)
Dehumidifying Volume (l/h)
C.O.P / EER (W/W) (High/Normal*)
Model of Indoor Unit
Indoor unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB (A)
(H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package
(W/D/H)( mm)
Net Weight /Gross Weight (kg)
GWCN28C1ND1AA
COOLING
8800(30000btu)
3380
4600
21
220V~
60HZ
1200
3
2.6
HEATING
GWCN28C1ND1AA/I
1400/1300/1200
35
——
3.5
0.4
Cross flow fan – 1
φ
106 X 890
Aluminum fin-copper tube
Φ 7
2-1.3
901x25.4x381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
45
55
1178 X326X227
1265X417X333
17.5/24
GWHN24C1NK3AA
COOLING
220-240V~
HEATING
50HZ
7000
2600
3400
14.8
8000
2400
3100
13.5
1200
3
2.69/3.33
GWHN24C1NK3AA/I
1410/1310/1260
35
-
3
0.19
Cross flow fan – 1
φ
106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/48/47
59/57/56
1178 X326X227
1265X417X328
17.5/24
Model of Outdoor Unit
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Fan Motor Speed (rpm) (H/M/L)
Output of Fan Motor (W)
Outdoor unit
Fan Motor RLA(A)
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package (W/D/H)( mm)
Net Weight /Gross Weight (kg)
Connec tion
Pipe
Refrigerant Charge (kg)
Length (m)
Outer Diameter
Max Distance
Liquid Pipe (mm)
Gas Pipe (mm)
Height (m)
Length (m)
GWCN28C1ND1AA/O
SQ034KBA
Hermetic motor compressor
76
14
3170
Internal Inherent Protector
Capillary
Capacitor
18 ≤ T ≤ 46
Aluminum fin-copper tube
Φ 9.52
2-1.4
1017.5X813X44
920
92
2.26
1.5
----
Axial fan –1
Φ 482
Auto defrost
T1
I
IP24
2.5
0.6
60
70
950x412x840
1100X450X995
90/100
R22X3.0kg
7.5
Φ 9.52(3/8”)
Φ 16(5/8”)
10
20
GWHN24C1NK3AA/O
C-3RV322H1AAF
Hermetic motor compressor
74
13.2
2686
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
-
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
3.8
1.2
58
68
1006X412X840
1100X450X905
72/77
R410a / 2.45kg
5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
Fengyun Series
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W)
Power Input (W) (High/Normal)
Rated Input (W) (High/Normal)
Rated Current (A) (High/Normal)
Air Flow Volume (m
3
/h) (H/M/L)
Dehumidifying Volume (l/h)
C.O.P / EER (W/W) (High/Normal*)
Model of Indoor Unit
Indoor unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB (A)
(H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package
(W/D/H)( mm)
Net Weight /Gross Weight (kg)
GWCN24C1NK3AA
COOLING
220-240V~
HEATING
50HZ
7000
2600
3400
14.8
-
-
-
-
1200
3
2.69/3.33
GWCN24C1NK3AA/I
1410/1310/1260
35
-
3
0.19
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/48/47
59/57/56
1178 X326X227
1265X417X 333 328 ②
17.5/24
GWHN24C1NK1AA
COOLING
220-230V~
HEATING
50HZ
7100
2700
4000
23.5
8000
2700
3000
16
1100
3
2.63/2.96
GWHN24C1NK1AA/I
1260/1170/1080
26
——
3
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
46/44/41
56/54/51
1178 X326X227
1265X417X333
17.5/24
Model of Outdoor Unit
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Fan Motor Speed (rpm) (H/M/L)
Output of Fan Motor (W)
Outdoor
Fan Motor RLA(A)
Fan Motor Capacitor (uF) unit
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package (W/D/H)( mm)
Connec tion
Pipe
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Outer Diameter
Max Distance
Liquid Pipe (mm)
Gas Pipe (mm)
Height (m)
Length (m)
GWCN24C1NK3AA/O
C-3RV322H1AAF
Hermetic motor compressor
74
13.2
2686
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
-
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
3.8
1.2
58
68
1006X420X847 1006x412X840 ②
1100X450X905
72/77
R410a / 2.45kg
5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
GWHN24C1NK1AA/O
LH48VBAC
Hermetic motor compressor
63
12.3
2660
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
730.5X813X44
815
60
1
3.5
----
Axial fan –1
Φ 460
Auto defrost
T1
I
IP24
2.5
0.6
58
68
1006X340X847
1100X450X905
72/77
R22 / 2.55kg
5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
The above data are subject to change without notice. Please refer to the nameplate of the unit.
Model
Function
Rated Voltage
Rated Frequency
Total Capacity (W)
Power Input (W) (High/Normal)
Rated Input (W) (High/Normal)
Rated Current (A) (High/Normal)
Air Flow Volume (m
3
/h) (H/M/L)
Dehumidifying Volume (l/h)
C.O.P / EER (W/W) (High/Normal*)
Model of Indoor Unit
Indoor unit
Fan Motor Speed (r/min)
(H/M/L)
Output of Fan Motor (w)
Input of Heater (w)
Fan Motor Capacitor (uF)
Fan Motor RLA(A)
Fan Type-Piece
Diameter-Length (mm)
Evaporator
Pipe Diameter (mm)
Row-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Swing Motor Model
Output of Swing Motor (W)
Fuse (A)
Sound Pressure Level dB (A)
(H/M/L)
Sound Power Level dB (A)
(H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package
(W/D/H)( mm)
Net Weight /Gross Weight (kg)
KFR-80GW/A22-C
COOLING HEATING
8000
2800
4010
20.5
220-230V~
50HZ
1250
3
2.86
KFR-80G/A22-C
1410/1310/1260
35
——
3.5
0.4
Cross flow fan – 1
φ 106 X 890
Aluminum fin-copper tube
Φ 7
2-1.4
901.6X25.4X381
MP24GA
2
PCB 3.15A Transformer 0.4/0.1A
49/47/44
8800
2750
3600
19.5
59/57/54
1178 X326X227
1265X417X333
17.5/24
Model of Outdoor Unit
Compressor Model
Compressor Type
L.R.A. (A)
Compressor RLA(A)
Compressor Power Input(W)
Overload Protector
Throttling Method
Starting Method
Working Temp Range ( ℃ )
Condenser
Pipe Diameter (mm)
Rows-Fin Gap(mm)
Coil length (l) x height (H) x coil width (L)
Fan Motor Speed (rpm) (H/M/L)
Output of Fan Motor (W)
Fan Motor RLA(A)
Outdoor unit
Fan Motor Capacitor (uF)
Air Flow Volume of Outdoor Unit
Fan Type-Piece
Fan Diameter (mm)
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side(MPa)
Permissible Excessive Operating
Pressure for the Suction Side(MPa)
Sound Pressure Level dB (A) (H/M/L)
Sound Power Level dB (A) (H/M/L)
Dimension (W/D/H)( mm)
Dimension of Package (W/D/H)( mm)
Connec tion
Pipe
Net Weight /Gross Weight (kg)
Refrigerant Charge (kg)
Length (m)
Outer Diameter
Max Distance
Liquid Pipe (mm)
Gas Pipe (mm)
Height (m)
Length (m)
The above data are subject to change without notice. Please refer to the nameplate of the unit.
KFR-80W/A22-C
ZR36KH-PFJ-522
Hermetic motor compressor
100
17.1
2730
Internal Inherent Protector
Capillary
Capacitor
-5 ≤ T ≤ 43
Aluminum fin-copper tube
Φ 9.52
2-1.4
1017.5X813X44
920
92
2.26
3.5
----
Axial fan –1
Φ 482
Auto defrost
T1
I
IP24
2.5
0.6
60
70
950X412X840
1100X450X995
90/100
R22 / 2.75kg
5
Φ 9.52(3/8”)
Φ 16(5/8”)
15
30
Fengyun Series
3 Component Name
Indoor Unit
Front Panel
Air inlet Electrical box cover
Manual switch
Body case
Display window
Filter louver
Air out let
Manual switch
Display window
Remote controller connecting pipe and wire
Outdoor Unit
Heating Run
Cooling
Receiving
window
Air inlet
Drainage hose
Air outlet grille
Air outlet
Indoor Unit
Front Panel
Air inlet
Electrical box cover
Manual switch
Body case
Display window
Filter louver
Air out let
Manual switch
Display window
Remote controller connecting pipe and wire
Outdoor Unit
Heating
Run
Cooling
Receiving window
Air inlet
Air outlet grille Drainage hose
Air outlet
Fengyun Series
Air inlet grill
Left Tube-exit Sign
Top View
Rear View
Right
Tube
-exit Sign
Ceiling
Left Right
Air inlet grill
Left Tube-exit Sign
Top View
Rear View
Ceiling
Right
Tube
-exit Sign
Left Right
Fengyun Series
Over 6 0 0
Over 6 0 0 Over 6 0 0
UNIT:mm
Over 6 0 0
Bolt
Nut
Wrench
5 Electrical Diagram
Fengyun Series
Fengyun Series
Fengyun Series
In case of any change in the Electrical Diagram shown above, please follow the drawing on cabinet.
Fengyun Series
Controller Function Manual and Operating Instructions
Remote Controller Function Manual
Temperature Parameters
Indoor preset temperature (T preset
Indoor ambient temperature (T amb.
)
)
Basic Functions
Under each mode, once the compressor start up, it will not be stopped within 6 minutes and will be restart after 3mins later.
Cooling Mode
Cooling Conditions and Process and the indoor fan will run at preset speed. run at setting fan speed.
When Tpreset 1 Tamb Tpreset 1 , the unit will keep the original running state.
Under this mode, and the temperature can be preset preset amb Start cooling
Original operating status
Stop cooling
min. min. min.
Compressor
Outdoor fan
Indoor fan Preset speed
Run Stop
Dehumidifying mode
Dehumidifying conditions and process
When Tamb. Tpreset 2 , the unit will run under dehumidify cooling mode, in which case the compressor and outdoor fan will be
When Tpreset 2 Tamb. Tpreset 2 , the unit will run under dehumidifying mode, in which case the indoor fan will keep run at low speed, the compressor will be stopped after 6 minutes and the outdoor fan will be stopped after 30-second lag. After 4 minutes, the compressor and the outdoor fan will be restarted. The humidifying process is so repeated in cycle.
When Tamb. Tpreset 2 , the compressor, outdoor fan and indoor fan will be stopped.
Under this mode, and the temperature can be amb preset
Start cooling
Original operating status
Stop cooling preset
min.
min.
min.
min.
Compressor
Outdoor fan
Indoor fan Preset speed
Run
Low fan speed
Stop
Fan mode
Under Fan mode, the indoor fan runs at preset speed.
Auto Speed Low Speed Middle SpeedHigh Speed
The temperature can be set within a range from 16 to 30 . The initial value is 25 .
Auto mode
Under this mode, the system will automatically select its run mode (cooling, fan, heating) with the change of ambient temperature.
For protection function, same as under cooling or heating mode.
Under Auto mode, if the unit is switched from heating mode to another mode, when operate in heat mode, the OFF order only be received.
Other control
Sleep function
Setting Sleep function under COOL or DEHUMIDIFY mode, the preset temperature will automatically rise by 1 after 1 hour and rise by another 1 after 2 hours. Preset temperature will rise by 2 in total within 2 hours. After that, the unit will run at this preset temperature.
Tset
Setting Temp. Tset
Tset
Tset
1Hr.
2Hrs.
2Hrs.above
No sleep function under FAN or AUTO mode.
Timer on
Timer on function can be set when the unit is at off mode. Upon the time as set, the controller will run under preset mode. The interval of time setting is 0.5h and can be set within 0.5-24h in cycle.
Timer off
Timer Off function can be set when the unit is at on mode. Upon the time as set, the system will be stopped. The interval of time setting is 0.5h and can be set within 0.5-24h in cycle.
Swing Motor Control
Once energization, the swing motor will rotate the guide louver anticlockwise to position A to close the air outlet;
After the unit is started, the guide louver will rotate to D1 then return to Li position. If under swing status, the louver will swing between L1 and D1;
Upon stop of the unit, it will rotate anticlockwise to position A to close the air outlet.
Buzzer
When the controller is energized, pressed, or receives a signal from remote controller, the buzzer will give out a beep.
Automatic Control of Fan Speed
Under this mode, the indoor fan will automatically select high, medium or low speed with the change of ambient temperature.
Indicator
RUN Indicator (Red): When the controller is energized, it will give out a blink. Running status indication: bright upon start of the unit; black upon stop of the unit and blink during trouble.
COOLING, Dehumidifying Indicator (Green): Bright under cooling or dehumidifying mode; auto cooling or auto dehumidifying mode, otherwise, it is black.
Code Switch (AUTO, TEST, RUN, STOP)
It will run under auto mode when the code switch is put to AUTO position. If any remote control signal received, the main unit will run according to the remote control signal.
It will run under COOLING mode when the swing switch is put to TESTposition, and the indoor fan will run at high speed. If any remote control signal received, it will run according to the remote control signal. At this time, the low pressure switch is shielded, the temperature sensor’s malfunction will be checked, but don’t measure any temperatures.
Fengyun Series
When putting the swing switch to RUN position, the main unit will run as instructed by remote control signal.
When putting the swing switch to STOP position, the complete unit will be stopped and will not accept remote control signal.
Memory Function
Memory contents: Mode, Swing, Set temp., Set fan speed.
After powered off and re-power on, the unit will start to run with the memory function automatically.
Protection
Antifreeze Protection
Under heating mode, if it is detected that the pipe temp. of evaporator is too high, the outdoor fan will be stopped; When the pipe temperature resumes normal, the outdoor fan will resume running.
System high-pressure protection
Run Indicator will blink. When compressor is detected free of high-pressure protection, the shield function will be released, the
Run Indicator will keep blinking. To restore the operation, it is required to press ON/OFF key to switch off the unit and indicator before pressing ON/OFF key again.
Overcurrent protection
When the compressor is turned on, if it has detected that the current exceed the stated value, the unit will stop as the indoor ambient
temp. has arrived at the setting temp., a fter the compressor has stopped for 3mins, it will resume to run in the original running state,
if the protections is more than 6 times (If compressor has continuously work more than 6mins, the protection times will reset),
the running indicator will blink, it can not resume to run automatically, it is need to press ON/OFF button to turn off the unit, then repress ON/OF button to resume to work.
Communication malfunction
When it is detected that the indoor and outdoor units have communication malfunction , the running indicator will blink, the unit will be stopped as the indoor ambient temperature has arrived the setting temperature .
Indication display
State
H igh-pres s ure protection
Over current protection
Indicator dis play
Outdoor m alfunction indicator 1 turns on, indoor run indicator blinks
Outdoor malfunction indicator 2 turns on, indoor run indicator blinks
R em ark:
Indoor Run indicator turn off 3s and blinks once
Indoor indicator turn off 3s and blinks five times
Communication malfunction
Outdoor malfunction indicators 1, 2, 3 turn on, indoor run indicator blinks
Indoor indicator turn off 3s and blinks six times
Normal communication Outdoor indicator 4, 5 blink in turn
When there are several malfunctions existed at the same time, it will display the high level malfunction in priority by a sequence as: communication air exhaust protection over current protection high pressure protection low protection
Remote Controller Function Manual
6.1.1 Temperature Parameters
Indoor preset temperature (T preset
)
Indoor ambient temperature (T amb.
)
6.1.2 Basic Functions
Under any mode, the compressor, once started, will not be stopped within 6 minutes .
Once Stopp ed, the compressor should in no way be restarted unless 3-minute lag.
6.1.2.1 Cooling Mode
6.1.2.1.1 Cooling Conditions and Process
When T amb.
≥ T preset
+1 ℃ , the unit will run under cooling mode, in which case the compressor and outdoor fan will be started, the indoor fan will run at preset speed.
When T
amb
≤ T preset
-1 , the unit will be stopped under cooling mode, in which case the compressor and outdoor fan will be stopped and the indoor fan will run at preset speed.
When T preset
-1 <T
amb.
< T preset
℃
Under this mode, the reversal
valve will be de-energized and the temperature can be set from 16 to 30 ℃ .
T preset
+ 1 ℃
T amb
Start
Cooling
Original operating status
T preset
-1 ℃
Stop cooling
6 min .
3 min .
6 min .
Compressor
Outdoor fan
Indoor fan Preset speed
6.1.2.2 Dehumidifying Mode
Run
6.1.2.2.1 Dehumidifying Cooling Conditions and Process
amb.
> T
Stop will be started and the indoor fan will run at preset speed.
When T preset
-2 ℃≤ T
amb.
≤ T preset
+2 ℃ , the unit will run under dehumidifying mode, in which case the indoor fan will run at low speed. After the compressor and outdoor fan has run 6 minutes, the compressor will be stopped, the outdoor fan will be stopped after 15-second lag and the indoor fan will be stopped after 30 seconds. After 3.5 minutes, the compressor and outdoor fan will be started, and the indoor fan will run at low speed. The dehumidifying process is so repeated in cycle.
When T amb
.< T preset
-2 ℃ , the compressor, outdoor fan and indoor fan will be stopped.
Under this mode, the reversal
valve will be de-energized and the temperature can be set from 16 to 30 ℃ .
T preset
+2 ℃
T amb
Cooling
T preset
-2 ℃
Dehumidifying
6 min .
4 min.
6
min .
4 min.
Stop cooling
Compressor
Outdoor fan
Indoor fan
Preset
Run
Low speed Low speed
Stop
Fengyun Series
6.1.2.3 Heating Mode
6.1.2.3.1 Heating Conditions and Process
When T
amb.
≤ T preset +2
, the unit will run under heating mode,in reversal valve, compressor and outdoor fan will be started simultaneously , while the indoor fan will run after 2minutes (max) delay .
If T
amb.
≥ T preset
+ 4 , the compressor and outdoor fan will be stopped, the reversal indoor fan will run at preset speed for 60s and then will stop.
When T preset +2
<T amb.
< T preset
+ 4 ℃
Under this mode, the reversal
valve will be energized and the temperature can be set from 16 to 30 ℃ .
T preset
St op heating
Original operating st atus.
T preset
Tamb
6min.
3min.
6min.
Start heating
Compressor
Outdoor fan
Indoor fan
2min.
reversal valve preset speed 2min.
preset speed
Run Stop
6.1.2.3.2 Defrosting Conditions and Process
When the condenser is detected to have frost, the system will enter into defrosting status, in which case
the outdoor fan,
4-way valve and indoor fan will be stopped and the heating indicator will blink. When it is detected that the frost in condenser is completely eliminated, the outdoor fan and 4-way valve will be started, the indoor fan will be started at most
6.1.2.3.3 The preventive liquid splash protection for the 4-way valve
If the unit is switched off under heating mode or switched from heating mode to another mode, the 4-way valve will be de-energized 2 minutes after the compressor is stopped.
6.1.2.4 Fan Mode
Under FAN mode, the indoor fan runs at preset speed. Auto Speed Low Speed Middle
Speed
Hige Speed
The temperature can be set within a range from 16 to 30 ℃ .The initial value is 25 .
6.1.2.5 Auto Mode
Under this mode, the system will automatically select its run mode (cool ing , fan , heating ) with the change of ambient temperature. For protection function, same as under cooling or heating mode.
Under Auto mode, if the unit is switched from heating mode to another mode, the reversal valve will be de-energized after 2 mins delay.(cooling only unit has not heating mode)
6.1.3 Other Control
6.1.3.1 Sleep Function run at this preset temperature.
Tset
Tset
Setting SLEEP function under HEAT mode, the preset
1Hr.
hour and decrease by another 1 after 2 hours.Preset temperature will decrease by 2 in total within 2 hours. After that, the unit will run at this preset temperature.
Tset
1Hr.
Tset
No sleep function under FAN or AUTO mode.
Tset
2Hrs.
2Hrs.
Tset
Setting temp. Tset
2Hrs. above
2Hrs. above
Setting temp. Tset
6.1.3.2 AUTO ON
AUTO
ON function can be set when the unit is at off mode . Upon the time as set , the controller will run under
preset mode. The interval of time setting is 0.5h and can be set within 0.5-24h in cycle.
6.1.3.3 AUTO OFF
AUTO
OFF function can be set when the unit is at on mode . Upon the time as set , the system will be stopped.
The interval of time setting is 0.5h and can be set within 0.5-24h in cycle.
6.1.3.4 Swing Motor Control
1.
Once
energization, the
swing motor will rotate the guide louver anticlockwise to position A to close the air outlet.
2.After the unit is started, the guide louver will rotate to D2 air outlet under heating mode and to D1 air outlet and then return to L1 position. If under swing status, the louver will swing between L1 and D1 under cooling mode and between
L and D2 under heating.
3.Under heating mode, if swing is on, the louver must be stopped at L position when the unit is at preventive cold air; blowing the residual heat and defrosting status, the louver will swing under normal heating status. If swing is off, the louver will be stopped at preset position.
4.Upon stop of the unit, it will rotate anticlockwise to position A to close the air outlet.
6.1.3.5 Buzzer
When the controller is energized, pressed, or receives a signal from remote controller, the buzzer will give out a beep.
6.1.3.6 Automatic Control of Fan Speed
Under this mode, the indoor fan will automatically select high,medium or low speed with the change of ambient temperature.
6.1.3.7 Indicator
RUN Indicator (Red): when the controller is energized, it will give out a blink. Running status indication: bright upon start of
the unit; black upon stop of the unit and blink during trouble.
COOLING,Dehumidifying
Indicator (
Green
): Bright u nder cooling or dehumidifying mode; auto cooling or auto dehumidifying mode, otherwise, it is black.
HEATING
Indicator (
Yellow
): Bright u nder heating or auto heating mode, blink during defrosting, black under other modes.
The RUN Indicator is bright under FAN mode,
6.1.3.8 Swing Switch( AUTO, TEST, RUN, STOP ) a. It will run under auto mode when the swing switch is put to AUTO position .
If any remote control signal received, the main unit will run according to the remote control signal . b . It will run under COOLING mode when the swing switch is put to TEST position, and the indoor fan will run at high speed .
If any remote control signal received,it will run according to the remote control signal. At this time, the low pressure switch is shielded, the tem. sensor`s malfunction will be checked,but don`t measure any temperatures. c . When putting the swing switch to RUN position, the main unit will run as instructed by remote control signal. d . When putting the swing switch to STOP position, the complete unit will be stopped and will not accept remote control signal
6.1.3.9 Memory function
Memory contents: Mode, Swing, Set temp, Set fan speed.
After powered off, and re-power on, the unit will start to run with the memory function automatically.
Fengyun Series
6.1.4 Protection
6.1.4.1 Antifreeze Protection
If it is detected that the system is under antifreeze protection under cooling mode, the compressor and outdoor fan will be stopped, the indoor fan and the swing motor will maintain its original operating status.. When antifreeze protection is released and the compressor has stopped for 3 minutes, the controller will run at the preset mode. It don't shielded the key signal during antifreeze protection.
6.1.4.2 Anti High-temp Protection
Undre heating mode, if it is detected that the pipe temp. of evaporator is too high, the outdoor fan will be stopped; when the pipe temp. resumes normal, the outdoor fan will resume running.
6.1.4.3 System high-pressure protection
If high-pressure protection is detected ,all loads will be turned off,all key-press and remote control signals will be shielded, and the
Run Indicator will blink. When compressor is detected free of high-pressure protection, the shield function will be released, the Run
Indicator will keep blinking.To restore the operation, it is required to press ON/OFF key to switch off the unit and indicator before pressing ON/OFF key again.
6.1.4.4 System low-pressure protection
1. After compressor has started for several minutes and started to check the low-pressure switch signal, if it has detected that the
low-pressure switch opened, that the whole unit will stop, the running indicator will blink,after 3mins and low pressure resumed, the
unit will back to run; if there are twice low-pressure protection continuously act, that the running indicator blink and will not
resume automatically, in order to remind the user there is air leakage; Only if the low pressure resumed, then press ON/
OFF button to turn off the unit, then repress ON/OFF button to resume to run;(if cooling only unit has no low-pressure switch,
connect the circuit directly.)
2. When turn to the manual switch to TEST position, it will carry out the test running, and shield the low-pressure protection;
3. When compressor stops, if it detected for 30s continuously that the low-pressure switch is opened, the whole unit will stop,the
running indicator will blink,and it can not resume automatically, it need to press ON/OFF button to turn off the unit, then repress
ON/OFF button to resume to run.
6.1.4.5 Overcurrent protection
When the compressor is turned on, if it has detected that the current exceed the stated value, the unit will stop as the indoor ambient
temp. has arrived at the setting temp., after the compressor has stopped for 3mins, it will resume to run in the original running state,
if the protections is more than 6 times (If compressor has continuously work more than 6mins, the protection times will reset),
the running indicator will blink, it can not resume to run automatically, it is need to press ON/OFF button to turn off the unit, then repress ON/OF button to resume to work.
6.1.4.6 Communication malfunction
When it is detected that the indoor and outdoor units have communication malfunction , the running indicator will blink, the unit will be stopped as the indoor ambient temperature has arrived the setting temperature .
6.1.4.7 Indicator display
S ta te In d ica to r d is p la y R e m a rk:
H ig h -p re s s u re p ro te ctio n o n , in d o o r ru n in d ica to r blinks
O u td o o r m a lfu n ctio n in d ica to r 3 tu rn s
L o w -p re s s u re p ro te ctio n o n , in d o o r ru n in d ica to r blinks
In d o o r Run in d ica to r tu rn o ff 3 s a n d b l i n k s o n ce ind o o r R u n in d ica to r t u r n o f f 3 s a n d b l i n k s 3 t i m e s
Ove r cu rre n t p ro te ctio n
O u td o o r m a lfu n ctio n in d ica to r 2 tu rn s o n , in d o o r ru n in d ica to r blinks
O u td o o r m a lfu n ctio n in d ica to rs 1 ,2 ,3
C o m m u n ica tio n m a lfu n ctio n tu rn o n , in d o o r ru n in d ica to r b l i n k s
In d o o r in d ica to r tu rn o ff 3 s a n d blinks five tim e s
In d o o r in d ica to r tu rn o ff 3 s a n d blinks six tim e s
N o rm a l co m m u n ica tio n
O u td o o r in d ica to r 4 ,5 b l i n k i n t u r n
When there are several malfunctions existed at the same time, it will display the high level malfunction in priority by a
sequence as: communication malfunction air exhaust protection over current protection high pressure protection
low pressure protection.
7 Disassembly and Assembly Procedures
Disassembly Procedures of Indoor Unit
Operating Procedures / Photos
Disassemble Filter
Push the filter inward and then pull it upward to remove it. Twist off screws to remove the cover plate of electric box.
( refer to Figure 7 -1 )
Filter Electric Box.
Cover Plate
Screw
Figure 7 -1
Disassemble Front Panel
Pull open the front panel. Push the front panel along the front case groove fixing the front panel to remove it.
( refer to Figure 7 2 ) Front Panel Hook
Figure 7 2
Disassemble Guide Louver
Manually bend the guide louver to loose the clasp at the guide louver. Remove the guide louver.
( refer to Figure 7 3 )
Clamp Guide Louver
Figure 7 3
Fengyun Series
Operating Procedures / Photos
Disassemble Front Case
Unscrew the three screw cover at the front case, unscrew the six screws, and pull backward the front case to remove it.
( refer to Figure 7 -4 )
Screw
Figure 7 -4
Disassemble Electric Box Cover
Unscrew the screw fixing the light plate to remove the light plate. Hold the electric box cover to press it inward so that the clasps at both sides are loose. Lift the electric box cover to remove it.
( refer to Figure 7 -5 )
Screw
Disassemble Electric Box
Remove the grounding wire of evaporator. Take apart the tube sensor. Unplug the socket connecters of indoor motor and swing motor at the electric box. Use screwdriver to screw off the fixing screw of electric box. Take out the electric box.
( refer to Figure 7 -6 )
Tube Sensor
Grounding Wire
Room Sensor
Lamp board
Electric
Clasp
Box Cover
Figure 7 -5
Figure 7 -6
Operating Procedures / Photos
Disassemble Water Tray
Push open the clasp fixing the water tray, and pull the water tray upward to remove the water tray.
( refer to Figure 7 -7 )
Clasp
Water Tray
Figure 7 -7
Disassemble Evaporator
Use screwdriver to screw off the two screws at the rear pipe clamp to remove the rear pipe clamp. Screw off the screws at the left and right sides of the evaporator, and take the evaporator out, so that the side plate clasp of the evaporator is released from the groove.
( refer to Figure 7 -8, 7 -9 and 7 -10 )
Clamp Pipe clamp
Figure 7 -8
Screw
Figure 7 9
Screw
Figure 7-10
Fengyun Series
Operation Process / Photoes
Disassemble Motor clamp
Use a screwdriver to unscrew the two screws fixing the motor clamp and then remove the motor clamp. Unscrew the 3 holding screw s
on the bearing
cover
and remove the motor.
(refer to Figure 7-1 1,7-12 ) screws
Figure 7-1 1
Disassemble Cross Flow Fan
T ake out the bearing holder at the left, and remove the cross flow fan. screws motor
(refer to Figure 7-1
3
)
Cross Flow Fan
Figure 7-1 2
Bearing Holder
Cross Flow Fan screw
Figure 7-1 3
Disassembly Procedures of Outdoor Unit
Operating Procedures / Photos
Disassemble Front Side Plate
Screw off the four screws around the front side plate to remove the front side plate.
( refer to Figure 7 -14 )
Front Side Plate
Screw s
Figure 7 -14
Disassemble Top Cover
Screw off the tapping screws around the top cover, and then pull the top cover upward to remove it.
( refer to Figure 7 -15 )
Screw
Top Cover
Figure 7 -15
Remove the rear grill
Screw off the four screws around the rear grill to remove the rear grill.
( refer to Figure 7 -16 )
Screw
Rear Grill
Figure 7 -16
Fengyun Series
Operating Procedures / Photos
Disassemble Cabinet
Use screwdriver to screw off the screws around the cabinet to remove the cabinet. ( refer to
Figure 7 -17 )
Screw
Cabinet
Figure 7-17
Disassemble Electric Box
Use screwdriver to screw off the two screws fixing the electric box, and pull the electric box to remove it.
( refer to Figure 8-18 )
Screw
Electric Box
S oft startup plate
Disassemble Right Side Plate
Use screwdriver to screw off the 7 screws at the right side plat e, condenser side plate and valve suport , and then pull the right side plate sub-assy upward to remove it.
( refer to Figure 7 -19 )
Screw
Right Side Plate
Figure 7 -18
Figure 7 -1 9
Operating Procedures / Photos
Disassemble Axial Flow Fan
Use spanner to remove the nut at the fan to remove the axial flow fan.
( refer to Figure 7 -20 ) nut
A xial Flow Fan
Figure 7 -2 0
Disassemble Outdoor Motor
Screw off the four tapping screws fixing the motor, pull out the motor lead-out cable plug, and remove the motor. Screw off the two tapping screws fixing the motor support, and pull the motor support upward to remove it.
( refer to Figure 7 -21 )
Motor
Screw Fixing
the Motor
Motor Cable
Motor Support
Fixing
Screw
Disassemble 4-Way Valve
(cooling only unit has not 4-way valve)
Screw off the holding nut of the 4-way valve coil and remove the coil. Use wet cotton cloth to wrap the 4-way valve, unsold the four soldering points connecting the 4-way valve, and remove the
4-Way Valve
Soldering
4-way valve. Be quick during the unsoldering Point process, pay attention to keep the wrapping cloth wet and do not allow the soldering flame to burn the compressor lead-out cable.
( refer to Figure 7 -22 )
Figure 7 -21
Figure 7 -2 2
Fengyun Series
Operating Procedures / Photos
Disassemble Capillary
Unsold the soldering points at the capillary, the valve and the condenser to remove the capillary.
Pay attention not to allow the soldering slag to block the capillary.
( refer to Figure 7 -23 )
Capillar y
Figure 7 -23
Disassemble Valve s
Screw out the 2 bolts that fixing big valve, unsolder the soldered dot connecting big valve with gas return pipe to take off big valve.
(Note: When soldering the soldered dot, wrap big valve completely by moist cloth to prevent valve from damaging by h igh temperature.)
Screw out the 2 bolts that fixing small valve, unsolder the soldered dot that connected small valve and Y-shape pipe to take off small valve.
( refer to Figure 7 -2 4 )
Disassemble Compressor
Unsolder the pipeline that connected with compressor first,then take off the 3 nuts on feet of compressor to take offcompressor.
( refer to Figure 7 -2 5 ) small valve
Compressor bolts big valve
Figure 7 -2 4
Foot Nut
Figure 7 -2 5
Exploded View of Components and Parts of Indoor Unit
Fengyun Series
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver(up)
9 Guide Louver(down)
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support(left)
14 Filter
15 Front Case
16 Front Panel
17 Front Panel A
18 Remote Controller Y512
19 Receiver Board JD
20 Electric Box Cover
21 Switch Lever
22 Wire Clamp
23 Terminal Board T4B3A
24 Electric Box Cover
25 Main PCB
26 Transformer 48X26G
27 Fuse 3.15A 250VAC
28 Room Sensor
29 Tube Sensor
30 Sensor Insert
31 Electric Box
32 Lower Shield of Electric Box
33 Upper Shield of Electric Box
34 Stepping Motor MP24GA
35 Evaporator Support(rihgt)
36 Motor Clamp
37 Motor FN25D
38 Fixer(evaporator)
39 Pipe Clamp
40 Connecting Cable
41 Connecting Cable
Components and Parts List of Indoor Unit
GWCN24C1ND1BA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002698
22432258
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30055016
43110233
46010014
390000451
3900012128
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012107
26112071
/
400205405
Part Code
GWCN24C1NK1BA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002698
22432258
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30035302
43110233
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012105
26112071
400205235
400205405
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
3
15
3
1
1
1
1
Description
Wall-Mounting Frame
Rear Case
Fan Bearing
Screw Cover
Swing Louver
Swing Link
Water Tray
Guide Louver ( up )
Guide Louver ( down )
Cross Flow Fan
Evaporator Assy
Drainage Pipe
Evaporator Support ( left )
Filter
Front Case
Front Panel
Front Panel A
Remote Controller Y512
Receiver Board JD
Electric Box Cover
Switch Lever
Wire Clamp
Terminal Board T4B3A
Electric Box Cover
Main PCB
Transformer SC28B5
Fuse 3.15A 250VAC
Room Sensor
Tube Sensor
Sensor Insert
Electric Box
Lower Shield of Electric Box
Upper Shield of Electric Box
Stepping Motor MP24GA
Evaporator Support ( rihgt )
Motor Clamp
Motor FN25D
Fixer(evaporator)
Pipe Clamp
Connecting Cable
Connecting Cable
No
26
27
28
29
22
23
24
25
30
31
16
17
18
19
12
13
14
15
20
21
36
37
38
39
32
33
34
35
40
41
1
8
9
6
7
4
5
2
3
10
11
GWHN24C1NK1BA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002698
22432258
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30055015
43110204
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012105
02112009
26112071
400205237
400205405
Part Code
Qty
GWCN28C1TK1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002698
22432258
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30035302
43110233
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012105
02112009 1
26112071 1
400205235 1
400205405 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
3
15
3
1
Exploded View of Components and Parts of Indoor Unit
Fengyun Series
Components and Parts List of Indoor Unit
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver ( up )
9 Guide Louver ( down )
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support ( left )
14 Filter
15 Front Case
16 Front Panel
17 Remote Controller Y512
18 Receiver Board JD
19 Electric Box Cover
20 Switch Lever
21 Wire Clamp
22 Terminal Board T4B3A
23 Electric Box Cover
24 Main PCB
25 Transformer 48X26G
26 Fuse 3.15A 250VAC
27 Room Sensor
28 Tube Sensor
29 Sensor Insert
30 Electric
31 Lower Shield of Electric Box
32 Upper Shield of Electric Box
33 Stepping Motor MP24GA
34 Evaporator Support ( rihgt )
35 Motor Clamp
36 Motor FN25D
37 Fixer(evaporator)
38 Pipe Clamp
39 Connecting
40 Connecting Cable
GWHN28C1NK3AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30030303
43110233
46010014
390000451
390000591
42020063
01592034
01592033
15212102
24212042
26112069
15012105
26112071
400205405
Part Code
GWCN28C1NK3AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30035302
43110233
46010014
390000451
390000591
42020063
01592034
01592033
15212102
24212042
26112069
15012105
26112071
400205405
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
3
1
1
1
3
15
1
1
1
1
1
1
1
1
GWHN24C1NK3AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041299
0523001401
24212041
11122051
20002923
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30030303
43110233
46010014
390000451
390000591
42020063
01592034
01592033
15212102
24212042
26112069
15012105
26112071
40020318
Fengyun Series
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver(up)
9 Guide Louver(down)
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support(left)
14 Filter
15 Front Case
16 Front Panel
17 Remote Controller Y512
18 Receiver Board JD
19 Electric Box Cover
20 Switch Lever
21 Wire Clamp
22 Terminal Board T4B3A
23 Electric Box Cover
24 Main PCB
25 Transformer 48X26G
26 Fuse 3.15A 250VAC
27 Room Sensor
28 Tube Sensor
29 Sensor Insert
30 Electric Box
31 Lower Shield of Electric Box
GWCN28C1TD1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30035302
43110233
46010014
390000451
390000591
42020063
20102250
01592034
32 Upper Shield of Electric Box
33 Stepping Motor MP24GA
34 Evaporator Support(rihgt)
35 Motor Clamp
36 Motor FN25C
37 Fixer(evaporator)
38 Pipe Clamp
39 Connecting Cable
40 Connecting Cable
01592033
15212102
24212042
26112069
15012107
02112009
26112071
400205235
400205405
Part Code
GWHN28C1TD1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30030303
43110233
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012107
02112009
26112071
400205235
400205405
Qty
GWHN24C1NK3AB/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
0100412910
05232411
24212041
11122051
20002572
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30030303
43110233
46010014
390000451
390000591
42020063
20102250
1
01592034
1
01592033
15212102
24212042
26112069
15012105
02112009 1
1
1
1
1
26112071 1
400205235 1
40020318 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
15
3
1
1
1
1
1
1
3
1
1
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver(up)
9 Guide Louver(down)
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support(left)
14 Filter
15 Front Case
16 Front Panel
17 Remote Controller Y512
18 Receiver Board JD
19 Electric Box Cover
20 Switch Lever
21 Wire Clamp
22 Terminal Board T4B3A
23 Electric Box Cover
24 Main PCB
25 Transformer 48X26G
26 Fuse 3.15A 250VAC
27 Room Sensor
28 Tube Sensor
29 Sensor Insert
30 Electric Box
31 Lower Shield of Electric Box
32 Upper Shield of Electric Box
33 Stepping Motor MP24GA
34 Evaporator Support(rihgt)
35 Motor Clamp
36 Motor FN25C
37 Fixer(evaporator)
38 Pipe Clamp
39 Connecting Cable
40 Connecting Cable
Part Code
GWCN24C1NK3AA/I
01252398
22202040
Qty
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041299
0523001401
24212041
11122051
20002923
20002375
305125063
30046093
20102252
10582007
71010103
42011233
20102251
30035302
43110233
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012105
02112009 1
26112071 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
15
3
1
1
1
3
1
1
400205235
40020318
1
1
Exploded View of Components and Parts of Indoor Unit
Fengyun Series
Components and Parts List of Indoor Unit
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver ( up )
9 Guide Louver ( down )
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support ( left )
14 Filter
15 Front Case
16 Front Panel
17 Remote Controller Y512
18 Receiver Board JD
19 Electric Box Cover
20 Switch Lever
21 Wire Clamp
22 Terminal Board T4B3A
23 Electric Box Cover
24 Main PCB
25 Transformer 48X26G
26 Fuse T5AL 250V
27 Room Sensor
28 Tube Sensor
29 Sensor Insert
30 Electric Box
31 Lower Shield of Electric Box
32 Upper Shield of Electric Box
33 Stepping Motor MP24GA
34 Evaporator Support ( rihgt )
35 Motor Clamp
36 Motor FN26C
37 Fixer(evaporator)
38 Pipe Clamp
39 Connecting Cable
GWCN24C1ND1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002375
30512506
30046093
20102252
10582007
71010103
42011233
30035302
43110233
46010013
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
150121072
26112071
400205237
Part Code
GWHN24C1ND1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002572
20002375
30512506
30046093
20102252
10582007
71010103
42011233
30030302
43110233
6010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
150121072
26112071
400205237
GWCN24C1NK1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
010041291
05232411
24212041
11122051
20002923
20002375
30512506
30046093
20102252
10582007
71010103
42011233
30035302
43110233
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
150121053
26112071
400205235
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Qty
1
1
1
1
1
2
1
1
1
1
1
1
1
1
3
15
3
1
1
1
1
1
Fengyun Series
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver ( up )
9 Guide Louver ( down )
10 Cross Flow Fan
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support ( left )
14 Filter
15 Front Case
16 Front Panel
17 Remote Controller Y512
18 Receiver Board JD
19 Electric Box Cover
20 Switch Lever
21 Wire Clamp
22 Terminal Board T4B3A
23 Electric Box Cover
24 Main PCB
24 Main PCB
25 Transformer 48X26G
26 Fuse T5AL 250V
27 Room Sensor
28 Tube Sensor
29 Sensor Insert
30 Electric Box
31 Lower Shield of Electric Box
32 Upper Shield of Electric Box
33 Stepping Motor MP24GA
34 Evaporator Support
35 Motor Clamp
36 Motor FN25C
37 Fixer(evaporator)
38 Pipe Clamp
39 Connecting Cable
GWCN28C1ND1AA/I
01252398
22202040
76512203
242520053
10512030
10582040
Part Code
GWHN28C1ND1AA/I
01252398
22202040
GWHN24C1NK1AA/I
01252398
22202040
76512203
20182043
10512062
10512063
10352420
10352420
010041293
05232411
24212041
11122051
20002923
20002375
30512506
30046093
20102252
10582007
71010103
42011233
20102357
30035302
30055016
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
10352420
010041293
05232411
24212041
11122051
20002923
20002370
30512506
30046093
20102252
10582007
71010103
42011233
20102357
30055015
242520053
10512030
10582040
20182043
10512062
10512063
10352420
10352420
010027302
0523001401
24212041
11122051
20002923
20002375
30512506
30046093
20102252
10582007
71010103
42011233
20102357
30030303
43110233
46010013
390000451
390000591
43110233
46010014
390000451
390000591
43110233
46010014
390000451
42020063
20102250
01592034
01592033
42020063
20102250
01592034
01592033
390000591
42020063
20102250
01592034
15212102
24212042
15212102
24212042
01592033
15212102
24212042
26112069 26112069 26112069
15012107
400205237
15012107
400205237
150121053
02112009 02112009 02112009
26112071 26112071 26112071
400205235
Qty
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
3
15
3
1
1
1
1
1
1
1
1
1
1
1
1
No Description
1 Wall-Mounting Frame
2 Rear Case
3 Fan Bearing
4 Screw Cover
5 Swing Louver
6 Swing Link
7 Water Tray
8 Guide Louver ( up )
9 Guide Louver ( down )
10 Cross Flow Fan
10 Cross Flow Fan
11 Evaporator Assy
12 Drainage Pipe
13 Evaporator Support ( left )
14 Filter
15 Front Case
16 Front Panel
17 Remote Controller Y512
18 Receiver Board JD
19 Electric Box Cover
20 Switch Lever
21 Wire Clamp
22 Terminal Board T4B3A
23 Electric Box Cover
24 Main PCB
24 Main PCB
25 Transformer 48X26G
26 Fuse T5AL 250V
27 Room Sensor
28 Tube Sensor
29 Sensor Insert
30 Electric Box
31 Lower Shield of Electric Box
32 Upper Shield of Electric Box
33 Stepping Motor MP24GA
34 Evaporator Support
35 Motor Clamp
36 Motor FN25C
37 Fixer(evaporator)
38 Pipe Clamp
39 Connecting Cable
Part Code
KFR-80G/A22-C
01252398
22202040
76512203
242520053
10512030
10582040
20182043
10512062
10512063
10352420
10352420
010041291
0523001401
24212041
11122051
20002923
20002375
30512506
30046093
20102252
10582007
71010103
42011233
20102357
30035224
30055015
43110233
46010014
390000451
390000591
42020063
20102250
01592034
01592033
15212102
24212042
26112069
15012105
02112009
26112071
400205237
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
3
15
3
1
1
1
1
1
1
1
1
1
1
1
1
1
Exploded View of Components and Parts of Outdoor Unit
Fengyun Series
Components and Parts List of Oudoor Unit
No
1
2
Description
Front Grill
Front Plate
3 Axial Flow Fan
4 Motor LW80C
5 Motor Support
6 Condenser Assy
7 Temp Sensor Support
8 Ambient Sensor
9 Top Cover
10 Rear Grill
11 upper Electric box cover
12 Electric Plate
13 Capacitor CBB65 50uF/450V
14 Capacitor CBB65 60uF/450V
15 Capacitor CBB61 3.5uF/450V
16 Main PCB
17 Soft Start Device
18 2-8
19 Transformer 57X30G
20 Terminal
21
22
23
24
25
26
4-way Valve Coil
4-way Valve
Temp Sensor
Handle
Gas Valve Assy 5/8"
Liquid Valve Assy 3/8"
43110232
/
/
3900012128
26235253
071052521
07105256
27 Rear Side Plate
28 Valve Support
29 Capillary Assy
30 Compressor SHV33YE6UU
31 Overload Protector
32 Temp Sensor
33 Gas-liquid Separator
34 Isolation Washer C
01305026
03103317
00100150
/
/
70410523
35 Clapboard 01233024
36 Capacitor
37 AC Contactor CJX9B-25S/D
38 Metal Base
39
40 Low Pressure Switch
41
Front Side Plate
Pressure Switch
01203558
01303092
/
46020003
Part Code
GWCN24C1ND1BA/O GWCN24C1NK1BA/O GWHN24C1NK1BA/I
22415001 22265251 22265251
01433031 01435254 01435254
10335257
15013062
01703027
01103811
10335253
15013106
01705253
01103792
24215101 24215101
390002065 390002065
01255262
01473028
01255262
01475252
01413076
0140337610
01413076
0140337610
33000001 33000001
33010010
30035303
33010010
30035303
10335253
15013106
01705253
01103904
24215101
390002065
01255262
01475252
01413076
0140337612
33000001
33000039
33010010
30030302
30116036
43110232
/
/
390001921
26235253
07105252
07105256
01305260
03103300
00100144
/
/
70410523
01205105
01305247
/
46020011
430004002
43000404
390001921
26235253
07105252
07105256
01305260
03103334
00100144
/
/
07255251
70410523
01205105
01305247
/
46020011
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
43110204 1
33010603 1
1
1
1
1
1
1
1
No Description
1 Front Grill
2 Front Plate
3 Axial Flow Fan
4 Motor FW60L
5 Motor Support
6 Condenser Assy
7 Temp Sensor Support
8 Ambient Sensor
9 Top Cover
10 Rear Grill
11 upper Electric box cover
12 Electric Plate
13
14
15
Capacitor CBB65
40uF/450V
Capacitor CBB65
50uF/450V
Capacitor CBB61
3.5uF/450V
01435401
10335254
15013063
01705253
011036793
24215101
390002065
01255262
01475252
01413076
014033763
33000022
/
33010010
16 Main PCB
17 Soft Start Device
18 Terminal Board 2-8
19 Transformer 57X30G
20 Terminal
21
22
23
29
30
31
4-way Valve Coil
4-way Valve
Temp Sensor
24 Handle
25 Gas Valve Assy 5/8"
26 Liquid Valve Assy 3/8"
27 Rear Side Plate
28 Valve
Capillary Assy
Compressor C-2R170H6S
Overload Protector
30035303
/
42011103
43110232
/
/
390001921
26235253
07105252
07105256
01305260
03103220
00103001
/
32 Temp Sensor
33 Gas-liquid Separator
/
07255251
34 Isolation Washer C 70410523
35 Clapboard 01235254
36
Capacitor 88-
108uF/98uF/330VAC
37 AC Contactor CJX9B-25S/D
38 Metal Base
39 Front Side Plate
40 Low Pressure Switch
41 Pressure Switch
/
44010245
01203059
01305247
/
46020011
Part Code
GWCN24C1ND1AA/O GWHN24C1ND1AA/O
22265251 22265251
01435251
10335254
15013063
01705253
011036792
24215101
390002065
01255262
01475252
01413076
014033762
33000022
/
33010010
30035303
/
42011103
43110232
430004002
43000404
390001921
26235253
07105252
07105256
01305260
03103219
00103001
/
/
07255251
70410523
01235254
/
44010245
01203059
01305247
/
46020011
GWCN24C1NK1AA/O
22265251
01435254
10335253
15013106
01705253
011036795
24215101
390002064
01255262
01475252
01413076
01403377
33000039
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
33000039
33010010
30035303
30116036
42011103
43110232
/
/
390001921
26235253
07105252
07105256
01305260
031032021
00100417
/
/
07255251
70410523
01235254
33010603
44010245
01205203
01305247
/
46020011
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Fengyun Series
No Description
1 Front Grill
2 Front Plate
3 Axial Flow Fan
4 Motor LW92F
5 Motor Support
6 Condenser Assy
7 Temp Sensor Support
8 Ambient Sensor
9 Top Cover
10 Rear Grill
11 upper Electric box cover
12 Electric Plate
13
14
Capacitor CBB65
55uF/450V
Capacitor CBB65
50uF/450V
15
Capacitor CBB61
3.5uF/450V
16 Main PCB
17 Soft Start Device
18 Terminal Board 2-8
19 Transformer 57X30G
20 Terminal Board
21 4-way Valve Coil
22 4-way Valve
23 Temp Sensor
24 Handle
25 Gas Valve Assy 5/8"
26 Liquid Valve Assy 3/8"
27 Rear Side Plate
28 Valve Support
29 Capillary Assy
30 Compressor SQ034KBA
31 Overload Protector
32 Temp Sensor
33 Gas-liquid Separator
34 Isolation Washer C
35 Clapboard
36
Capacitor 88-
108uF/98uF/330VAC
37
AC Contactor GC6-
45S/01C3A
38 Metal Base
39 Front Side Plate
40 Low Pressure Switch
41 Pressure Switch
Part Code
GWHN28C1ND1AA/O GWCN28C1ND1AA/O GWHN24C1NK1AA/O
22265401 22265401 22265251
01435401
10335401
150154012
01705401
011032345
24215101
390002064
01255402
01475401
01413075
014033593
/
01435402
10335401
150154012
01705403
01103830
24215101
390002064
01255402
01475401
01413075
01403360
/
01435251
10335254
15013106
01705253
011036794
24215101
390002064
01255262
01475252
01413076
014033764
Qty
1
1
1
1
1
1
1
1
1
1
1
1
33000039 1
33000001 33000001 33000039 1
3301010
30055017
/
42011103
43110232
42010258
430004002
43000404
390001921
26235253
07105252
071302232
01305401
01715256
03103188
00108140
/
/
07255251
70410523
01235404
/
44010265
012054012
01305403
46020007
46020011
33010010
30055018
/
42011103
43110232
42010258
/
/
390001921
26235253
07105252
071302232
01305401
01715256
03103354
00202102
/
/
07255251
70410523
01235404
/
44010265
01203583P
01305403
46020007
46020011
33010010
30030302
/
42011103
43110232
42010258
430004002
43000404
390001921
26235253
07105251
07105255
01305260
01715256
03103198
00100417
/
/
07255251
70410523
01235254
33010603
44010245 1
01205203
01305247
/
46020011
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
No
1 Front Grill
2 Front Plate
3
4
5 Motor Support
6 Condenser Assy
7
8
9 Top Cover
10 Rear Grill
11
12
13 Capacitor CBB65 55uF/450V
14
15
16
17 Soft Start Device
18 Terminal Board 2-8
19
20
21 4-way Valve Coil
22 4-way Valve
23
24
24 Handle
25 Gas Valve Assy 5/8"
26
27
28 Valve Support
29 Capillary Assy
30
31
Description
Axial Flow Fan
Motor LW92B
Temp Sensor Support
Ambient Sensor upper Electric box cover
Electric Plate
Capacitor CBB61 3.5uF/450V
Main PCB
Transformer 57X30G
Terminal Board
Temp Sensor
Handle
Liquid Valve Assy 3/8"
Rear Side Plate
Compressor ZR36KH-PFJ-522
Overload Protector
32 Temp Sensor
33 Gas-liquid Separator
Part Code
KFR-80W/A22-C
22265401
01435401
10335401
15015401
01705401
011032341
24215101
390002064
01255402
01475401
01413075
014033591
33000038
33010010
30035222
/
42011103
43110232
42010258
430004002
43000404
390001921
26235253
26235253
07105252
071302232
01305401
01715256
03103141
00100066
/
/
07255251
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
34 Isolation Washer C 70410523 1
35 Clapboard 01235404
36 Capacitor 88-
37 AC Contactor CJX9B-25S/01#
37 AC Contactor CJX9B-25S/DL
37 AC Contactor CJX9B-25S/01#
38 Metal Base
39 Front Side Plate
/
44010222
44010263
44010222
012054012
01305403
1
1
1
1
1
1
40 Low Pressure Switch 46020007 1
41 Pressure Switch 46020003 1
41 Pressure Switch 46020011 1
Exploded View of Components and Parts of Outdoor Unit
Fengyun Series
Components and Parts List of Oudoor Unit
No
19
20
21
22
23
16
17
18
13
14
15
10
11
12
7
8
9
4
5
6
1
2
3
33
34
35
30
31
32
36
37
38
27
28
29
24
25
26
Description
Front Grill
Front Plate
Axial Flow Fan
Motor LW80C
Motor Support
Condenser Assy
Temp Sensor Support
Ambient Sensor
Top Cover
Rear Grill upper Electric box cover
Electric Plate
Capacitor CBB65 50uF/450V
Capacitor CBB61 3.5uF/450V
Main PCB
Terminal Board 2-8
Transformer 57X30G
4-way Valve Coil
4-way Valve
Temp Sensor
Handle
Gas Valve Assy 5/8"
Liquid Valve Assy 3/8"
Rear Side Plate
Part Code
GWCN28C1TK1AA/O GWCN28C1NK3AA/O GWHN28C1NK3AA/O
22265401 22265401 22265401
01435402
10335253
01435402
10335401
01435402
10335401
15015401
01705401
011032341
15015401
01705401
011032344
15015401
01705401
011032344
24215101
390002064
01255402
01475401
24215101
390002064
01255402
01475401
24215101
390002064
01255402
01475401
Qty
01413074
33000001 33010743
33010010 33010010
30055018
42011103
43110232
/
/
390001921
26235253
07105252
071302232
01305401
Capillary Assy
Compressor AWR5538EXC
Overload Protector
03103141
00103011 in set
Temp Sensor /
Gas-liquid Separator 07255251
Isolation Washer C 70410523
Clapboard 01235403
AC Contactor GC6-45S/01C3A 44010265
Metal Base 01215401
Front Side Plate
Pressure Switch
High Pressure Switch
01305403
/
46025201
01413074
30035303
42011103
43110232
/
/
390001921
26235253
07103030
07130209
01308748
03103305
00100399 in set
/
07255251
70410523
01235403
44010263
01215401
01305403
46020007
460200061
01413074
33010743
33010010
30030302
42011103
43110232
430004002
43000411
390001921
26235253
07103030
07130209
01308748
03103305
00103010 in set
/
07255251
70410523
01235403
44010263
01215401
01305403
46020007
460200061
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
No
7
8
5
6
3
4
1
2
9
10
11
12
13
25
26
27
28
21
22
23
24
14
15
16
17
18
19
20
33
34
35
36
29
30
31
32
37
38
Description
Front Grill
Front Plate
Axial Flow Fan
Motor LW92P
Motor Support
Condenser Assy
Temp Sensor Support
Ambient Sensor
Top Cover
Rear Grill upper Electric box cover
Electric Plate
GWCN28C1TD1AA/O
22265401
01435402
10335253
15015452
01705401
011032341
24215101
390002064
01255402
01475401
01413075
01413074
Capacitor CBB65
45uF/440V(450V)
Capacitor CBB61 4uF/500V
Main PCB
Terminal Board 2-8
Transformer 57X30G
Terminal Board
4-way Valve Coil
4-way Valve
Temp Sensor
Handle
Gas Valve Assy 5/8"
Liquid Valve Assy 3/8"
Rear Side Plate
Valve Support
Capillary Assy
Compressor AWZ5532EXN
Overload Protector
Temp Sensor
Gas-liquid Separator
Isolation Washer C
33010013
30055018
42011103
43110232
42010258
/
/
390001921
26235253
07105252
071302232
01305401
01715256
03103141
00103010 in set
/
07255251
70410523
Clapboard 01235403
AC Contactor GC644010265
Metal Base
Front Side Plate
01215401
01305403
Pressure Switch
High Pressure Switch
/
46025201
Part Code
GWHN28C1TD1AA/O
22265401
01435402
10335253
15015452
01705401
011032341
24215101
390002064
01255402
01475401
01413075
01413074
33010013
30055017
42011103
43110232
42010258
430004002
43000404
390001921
26235253
07105252
071302232
01305401
01715256
03103141
00103010 in set
/
07255251
70410523
01235403
44010265
01215401
01305403
/
46025201
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Fengyun Series
Exploded View of Components and Parts of Outdoor Unit
Components and Parts List of Oudoor Unit
No
31
32
33
34
27
28
29
30
23
24
25
26
19
20
21
22
39
40
41
42
35
36
37
38
13
14
15
16
17
18
9
10
11
12
7
8
5
6
3
4
1
2
Description
Front Grill
Front Plate
Axial Flow Fan
Motor LW80C
Motor Support
Condenser Assy
Temp Sensor Support
Ambient Sensor
Part Code
GWHN24C1NK3AB/O
01473001
01433011
10335253
15013106
01705253
011036796
Top Cover
Rear Grill upper Electric box cover
Electric Plate
Capacitor CBB65 40uF/450V
Capacitor CBB61 3.5uF/450V
Main PCB
Terminal Board 2-8
Transformer 57X30G low temperature Start Device
Terminal Board
4-way Valve Coil
4-way Valve
Temp Sensor
Handle
Gas Valve Assy 5/8"
Liquid Valve Assy 3/8"
Rear Side Plate
Valve Support
Capillary Assy
Compressor C-3RV322H1AAF
Overload Protector
24215101
390002065
01255262
01475252
01413076
01403391
33000022
33010010
30030302
42011103
43110232
30116041
42010258
430004002
43000411
390001921
26235253
07103030
07130209
01303709
01715256
03103281
00103703 in set
Temp Sensor
Gas-liquid Separator
/
07255251
Isolation Washer C 70410523
Clapboard 01235254
AC Contactor CJX9B-25S/DL
Metal Base
Front Side Plate
Temperature control
Pressure Switch
Pressure sensor electrical heater for base electrical heater for
44010263
01205117
01305247
45040026
460200061
32210034
765100041
76518731
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Fengyun Series
Exploded View of Components and Parts of Outdoor Unit
No Description
1 Front Grill
2 Front Plate
3 Axial Flow Fan
4 Motor LW80C
5 Motor Support
6 Condenser Assy
7 Temp Sensor Support
8 Ambient Sensor
9 Top Cover
10 Rear Grill
11 upper Electric box cover
12 Electric Plate
13
14
Capacitor CBB65
40uF/450V
Capacitor CBB61
3.5uF/450V
15 Main PCB
16 Terminal Board 2-8
17 Transformer 57X30G
18 Terminal Board
19 4-way Valve Coil
20 4-way Valve
21 Temp Sensor
21 Temp Sensor
22 Handle
23 Gas Valve Assy 5/8"
24 Liquid Valve Assy 3/8"
25 Rear Side Plate
26 Valve Support
27 Capillary Assy
28
Compressor C-
3RV322H1AAF
29 Overload Protector
30 Temp Sensor
31 Gas-liquid Separator
32 Isolation Washer C
33 Clapboard
34 AC Contactor CJX9B-25S/D
35 Metal Base
36 Front Side Plate
37 Pressure Switch
Components and Parts List of Oudoor Unit
GWHN24C1NK3AA/O
22265251
01433011
10335253
15013106
01705253
011036796
24215101
390002064
01255262
01475252
01413076
01403377
33000022
Part Code
Qty
GWCN24C1NK3AA/O
22265251
01433011
10335253
15013106
01705253
011036797
24215101
390002064
01255262
01475252
01413076
01403377
33000022 1
1
1
1
1
1
1
1
1
1
1
1
1
33010010
30030302
42011103
43110232
42010258
430004002
43000411
390001921
390001921
26235253
07103030
07130209
01305260
01715256
03103281
00103703 in set
390002064
07255251
70410523
01235254
44010245
01203568
01305247
460200061
33010010
30035303
42011103
43110232
42010258
/
/
390001921
26235253
07103030
07130209
01303709
01715256
03103281
00103703 in set
/
07255251
70410523
01235254
44010245
01203568
01305247
460200061
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Fengyun Series
9 Trouble-Shooting
Trip of circuit breaker or burn-out of fuse
When air-conditioning unit is powered on, there is no action
(when the unit is plugged in, buzzer does not sound and there is no action after using the remote controller to start the unit)
Remote controller does not receive signal (when unit is powered on, buzzer shall sound, unless buzzer is damaged)
When set circuit breaker as “ ON ” , it trips immediately
When turning the air-conditioning unit to the “ ON ” status, trip of circuit breaker occurs several minutes later
Power voltage is too low
No power supply
Power plug is not firmly seated or connection is poor
Controller fuse burned out
Connection line of transformer is loose or suffers from poor plugging, or there is transformer failure
Controller is damaged
Batteries of remote controller are running out of power
Remote controller failure
Receiving head is loose or plug connection is poor
Receiving head is damaged
Check insulation resistance for grounding; Confirm if air-conditioning unit has electrical leakage or is short-circuited
Failure of air-conditioning unit or component insulation failure, short circuit or electrical leakage owing to insulation puncture after heating, measure insulation resistance or check the components one by one to find the ones with failure; failure of circuit breaker itself, replace it.
Check power supply line
Check and secure the plug to ensure firm contact
Replace controller fuse
Secure line connections; measure output voltage of transformer and replace transformer if it is incorrect
Replace controller
Replace battery
First press “AUTO” key of manual switch. If there is no action check according to the above method; if the operation is normal after pressing the key, recheck to see if the mounting position of receiving head and the line connections are correct; if they are correct, replace receiving head or remote controller.
Check power voltage. If the voltage is 10% than rated voltage, check the cause, and improve the power supply conditions such as adding regulated power supply.
Set temperature is not appropriate
Check if the cooling (heating) load is appropriate
Adjust the set temperature
Leakage of refrigerant or insufficient refrigerant
Check the forecasted cooling (heating) load
Check leakage, carry out vacuum-pumping after repairing leakage and charge refrigerant according to requirements
Leakage between internal high pressure and low pressure sections of compressor
Replace compressor
Failure of refrigerant flow
4-way valve failure Replace 4-way valve
Partial block in capillary Replace capillary
Poor thermal insulation of connecting pipe between indoor unit and outdoor unit
Block in cooling system
Observe the condensation condition of evaporator or the reading of high pressure meter to judge if the system is blocked; deal with the system accordingly
The thermal insulation of big pipe and small pipe shall be separate and sound; joint and bare position of copper pipe shall also have thermal insulation
Block in outdoor heat exchanger
Block in air filter
Wash away dust on surface of heat exchanger
Clean filter
Fan speed was set too low
Set fan speed as high or medium
Insufficient air circulation volume
Capacitor is damaged
Replace capacitor
Fan speed turns lower
Motor is damaged
Replace motor
Mounting position of outdoor unit is inappropriate
Outdoor unit shall be installed in a place with good ventilation
Outdoor temperature is too high
Install proper weather screen; it is suggested to replace air-conditioner unit with one of higher capacity in case the best available cooling effect does not satisfy needs
Indoor space is not sufficiently closed, or people enters or leave the room frequently, or there is heating equipment operating in the room
Keep the indoor space as closed as possible, do not use electrical appliance generating large amount of heat
When air supply mode is selected, the fan does not operate
When in cooling or heating mode, compressor operates but outdoor fan does not operate
When in cooling or heating mode, outdoor fan operates but compressor does not operate
Compressor is overheated so protector is activated
Swing louver does not run
Indoor fan motor burned out or there is wire breakage or failure of overheating protector
The internal overheating protector frequently breaks as overheating is caused by abnormity of motor
Wrong line connection
Open circuit or damage of fan capacitor
Outdoor fan motor is damaged
Wrong line connection
Outdoor fan capacitor is damaged
Compressor failure
Operating capacitor of compressor is damaged
Voltage is too low or too high
Wrong line connection
Failure of protector itself
Insufficient or too much refrigerant
Capillary is blocked so air intake temperature is too high
Compressor does not operate smoothly (seized or jammed), air discharge valve is damaged
Failure of protector itself
Torque of swing motor is insufficient
Wrong line connection
Controller is damaged (IC2003 is damaged, swing relay cannot close
Fengyun Series
Replace fan motor or components with failure
Replace fan motor
Correctly connect lines according to electrical diagram
Replace it with fan capacitor of the same model and spec
Replace fan motor
Correctly connect lines according to electrical diagram
Replace fan capacitor
Replace Compressor
Replace capacitor
It is suggested to equip voltage regulator
Correctly connect lines according to electrical diagram
Use universal meter to check if contacts of compressor not overheated are conducting; replace protector in case of non-conducting conditions
Adjust refrigerant amount
Replace capillary
Replace Compressor
Replace protector
Firstly check if line connections have fault, if no, replace components at failure position
Abnormal sound and vibration
Water leakage
Fan of indoor unit touches other positions
Foreign articles inside the indoor unit
Vibration of compressor is violent
Pipes of outdoor unit bump together
Metal plates bump together inside the unit
Indoor fan bumps cabinet
Abnormal sound from inside compressor
Abnormal electromagnetic noise from
4-way valve when in heating operation
Block or breakage of drainage pipe
The refrigerant pipe joint is not wrapped firmly
Adjust fan position
Remove foreign articles
Adjust support foot mat of compressor, tighten loose bolts
Separate bumping pipes
1. Tighten connection screws
2. Attach vibration damping gum between metal plates
Adjust fan position
Replace Compressor
Internal short circuit of solenoid valve, replace solenoid valve
Replace drainage pipe
Wrap and bind it again firmly