ATS Module
GEN Module
Industrial Generator Set Accessories
Engine Start Circuit Monitoring System
Standard Features
D
Continually monitors the engine start circuit wiring between the generator set and automatic transfer switch (ATS) as required by NEC 2017
D
UL listed
D
Forwards engine start signals to the generator set during normal operation
D
Detects open circuits and short circuits in the engine start wiring
D
Monitors conditions, annunciates faults, and starts the generator set in accordance with Article 700.10(D)(3) of NFPA 70 d Provides two Form C contacts, one for engine start and one for alarm d
Communicates faults to an optional customer- supplied alarm, a Remote Serial
Annunciator (RSA III), or a controller input d
Automatically starts the generator set engine when a fault is detected
D
GEN module status LEDs indicate the state of each circuit/channel: d
Blue: Channel disabled (off) d
Red: Wiring fault detected d
Green: Engine start is not active, wiring is ok d
Off: Engine start is active, wiring is ok
D
Easy installation on new or existing standby power equipment d
Use one module on the generator set d
Use one module on each ATS, up to a maximum of
8 transfer switches per generator module
D GEN module can be powered by the generator set’s engine starting battery; ATS module requires no power
D
Select engine start on an open or closed contact (All
Kohler r generators start on a closed contact)
Generator
Set
GEN
Module
Battery
ATS
Modules
ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 ATS 6 ATS 7 ATS 8
G6-165 1/20
Module Dimensions
48.0
(1.9)
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Dimensions are shown in mm (inches).
95.4
(3.8)
90.2
(3.6)
100
(3.9)
83.8
(3.3)
141
(5.6)
58.1
(2.3)
36.3
(1.4)
14
(0.55)
ATS Module GEN Module
GM109872
Specifications
Parameter
DC Power
Internal Ride Through Power
Specification
GEN Module: 9- 27 VDC 15W maximum
ATS Module: No power source required
3 seconds minimum
Mounting
Operating Temperature Range
35 mm DIN rail
- 20 _ C to 70 _ C (- 4 _ F to 158 _ F)
Maximum Distance 1000 ft. (305 m) one way (2000 ft. [610 m] Loop)
Maximum Wire Loop Resistance Less than 100 ohms
Generator Start Module Contact 1A 30 VDC Form C
Generator Alarm Module Contact 1A 30 VDC Form C
Wire Gauge 12- 30 AWG stranded
DISTRIBUTED BY:
107
(4.2)
113.2
(4.5)
GM109873
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler r generator distributor for availability.
2020 Kohler Co. All rights reserved.
G6-165 1/20