Eaton F-frame rear fed terminal 150A Owner's Manual
Advertisement
Advertisement
Instruction Leaflet
IL012029EN
Effective November 2013
Instructions for F-Frame 4/0 AWG Terminal Kit, Catalog No.
3TA150FDRF. For Use on Series C F-Frame Circuit Breakers,
Molded Case Switches, and Motor Circuit Protectors.
Contents
Description Page
1. Kit Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Instructions For Assembly . . . . . . . . . . . . . . . . 2
Instruction Leaflet
Effective November 2013
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE
ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE
PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE
CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.
ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE
PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW
GENERALLY ACCEPTED SAFETY PROCEDURES.
EATON IS NOT LIABLE FOR THE MISAPPLICATION OR
MISINSTALLATION OF ITS PRODUCTS.
Kit Contents
IL012029EN Instructions for F-Frame 4/0 AWG Terminal Kit, Catalog No.
3TA150FDRF. For Use on Series C F-Frame Circuit Breakers,
Molded Case Switches, and Motor Circuit Protectors.
Package of 3 terminals, 3 Pan Head Sems Mounting Screws, 1
Terminal Shield, 3 Terminal Shield Mounting Screws.
Instructions for Assembly
•
•
•
•
•
If circuit breaker is installed in equipment, it must be removed from the equipment to install this kit.
Assemble collar on the top of the conductor as shown and tighten securely with Pan Head Sems screws (10-32 x 3/8” [9.5 mm] long) and washers to 60 in-lbs (6.8 N m).
Slide the terminal shield into position on the end of the circuit reaker.
Use the (6-19 x 3/8” [9.5 mm] long) high-low screws provided to secure the shield in place. The line end uses 3 screws and the load end uses 2 screws.
Apply 300 MCM terminal kit label to top of breaker.
Wire Range #14-4/0 AWG CU-AI. Tighten to 120 in-lbs (13.6 N m).
Metric Wire Range 2.1 mm 2 to 107.2 mm 2 CU-AI. Tighten to 13.6
N m (120 in-lbs).
CAUTION
HAZARDOUS VOLTAGE TERMINAL SHIELD MUST BE INSTALLED
WHEN USING THE EXTENDED LUG. TERMINAL MUST BE
MOUNTED ON TOP OF CONDUCTOR AND SCREW HEAD
UNDERNEATH THE CONDUCTOR TO MAINTAIN ELECTRICAL
CLEARANCES.
2 EATON www.eaton.com
Instructions for F-Frame 4/0 AWG Terminal Kit, Catalog No.
3TA150FDRF. For Use on Series C F-Frame Circuit Breakers,
Molded Case Switches, and Motor Circuit Protectors.
Notes:
Instruction Leaflet IL012029EN
Effective November 2013
EATON www.eaton.com
3
Instruction Leaflet
Effective November 2013
IL012029EN Instructions for F-Frame 4/0 AWG Terminal Kit, Catalog No.
3TA150FDRF. For Use on Series C F-Frame Circuit Breakers,
Molded Case Switches, and Motor Circuit Protectors.
The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applications. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility.
This Instruction Booklet is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative.
The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract.
The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS
CONTAINED HEREIN.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein.
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2013 Eaton
All Rights Reserved
Printed in USA
Publication No. IL012029EN / TBG01109
Part No. IL012029ENHO1
November 2013
Eaton is a registered trademark.
All other trademarks are property of their respective owners.

Public link updated
The public link to your chat has been updated.
Advertisement