SPEAKMAN COMPANY
SE-460 Installation, Maintenance & Operation Instructions
EYESAVER
®
EYE/FACE WASH
DESCRIPTION
Emergency eye/face wash supplied with stainless steel bowl, stay-open full flow ball valve; activated by stainless steel push handle; in-line strainer, and mounted on countertops up to 1-1/2” thick. Spray pattern is a 9” x 8” (72 sq. in.) curtain of aerated water, easily controlled at any pressure for maximum protection.
SPECIFICATIONS
BOWL: 300 Series Stainless Steel. (Reference additional SE-300 I,M,O sheet)
SPRAY HEADS: (6) Brass, Chrome-Plated, Aerated.
VALVE: 1/2” NPT Female Brass, Chrome-Plated.
SHROUDS: Yellow Polypropylene.
INLET: 1/2” NPT Female.
STRAINER: Brass, Chrome-Plated, In-Line.
SHIPPING WEIGHT: 18 lb.
EMERGENCY SIGN: 7-7/8” x 7-7/8” Plastic Wall Sign.
OPTIONS
◊
◊
◊
AL1
(Air Horn Alarm)
◊
AL2
◊
AL3
FLW
(Electrical Alarm)
(Electrical Alarm)
◊
AL3-C1D2
(Flow Switch)
AL2-C1D2
(Electrical Alarm / Haz. Area)
(Electrical Alarm / Haz. Area)
◊
◊
◊
◊
FPV
(Anti-Freeze Protection Valve)
◊
SGN4
◊
SPV
PT
(Eye Wash Floor Sign)
(1-1/4” P-Trap)
(Anti-Scald Protection Valve)
SSBV2
VPL
(1/2” Stainless Steel Valve)
(Vapor Proof Light)
INSTALLATION
Use cutting/drilling instruction template (supplied) to cut and drill holes in desired location on countertop. Once bowl is mounted securely to countertop, complete assembly of ball valve and push handle. Review drawing (as shown on other side) to assure proper installation. Be sure to apply a bead of waterproof caulk along edge of bowl and countertop to prevent water draining under countertop. Connect a water supply to the unit (use pipe sealant on all joints) that is a 1/2” minimum uninterrupted source of potable water. Failure to use potable water can result in emergency units producing impure or contaminated water causing possible further injury. The drain tailpiece or waste should be connected to an adequate drain in compliance with local plumbing codes. Once water supply is connected to unit the spray pattern can be manually adjusted by using a flat head screw driver to rotate the adjusting screw, located in the front of each shroud assembly, while the unit is activated and water is flowing.
OPERATION
The eye/face wash is activated by pushing the push handle back 90°. The unit will continue to operate until the push handle is manually pulled back to the off position.
TESTING PROGRAM
MAINTENANCE
Should you need parts to repair this unit, please reference the parts list below for correct part numbers. Before any maintenance is done be sure to shut the water supply off.
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on a weekly basis to flush the line and verify proper operation. Speakman
Company furnishes a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
WARNING: Use only genuine Speakman parts when repairing or replacing components .
To order parts call 1-800-537-
2107.
SE-460 REPLACEMENT/REPAIR PARTS
ITEM PART/GROUP # DESCRIPTION
1
2
20-0953
68-0033-MO
1/2” Ball Valve Brass RNP
3
4
5
6
7
04-0523
G10-0042-RCP
03-0520
G21-0082-PC-P
92-0034
Shroud
In-Line
Template (Not Shown)
FLOW DATA
Note: All units meet existing
ANSI Z358.1 Standards and
FLOW PRESSURE PSI (BAR)
FLOW RATE GPM (LPM)
30 (2.07)
9.55 (16.6)
OSHA Rules. Product improvements may cause specification and dimensional changes without notice.
NOTE: This unit should be connected to an uninterrupted source of potable water, with a minimum flowing pressure of 20 PSI and a maximum static pressure of 125 PSI.