Honeywell HS10S-FA is a water station that consists of a backflow preventer, fine filter, and pressure reducer. It is designed for use with drinking water and has a maximum operating temperature of 65°C. The backflow preventer helps to prevent contaminated water from flowing back into the clean water supply, while the fine filter removes particles from the water. The pressure reducer helps to regulate the water pressure to a safe level for your home or business. The HS10S-FA is easy to install and maintain, and it comes with a one-year warranty.
advertisement
HS10S-FA
Einbauanleitung • Installation instruction
Anleitung zum späteren Gebrauch aufbewahren!
Keep instructions for later use!
Wasserstation
Water station
D
1. Sicherheitshinweise
1. Beachten Sie die Einbauanleitung.
2. Benutzen Sie das Gerät
•
• bestimmungsgemäß in einwandfreiem Zustand
• sicherheits- und gefahrenbewusst.
3. Beachten Sie, dass das Gerät ausschließlich für den in dieser Einbauanleitung genannten Verwendungsbereich bestimmt ist. Eine andere oder darüber hinausgehende Benutzung gilt als nicht bestimmungsgemäß.
4. Beachten Sie, dass alle Montage-, Inbetriebnahme, Wartungs- und Justagearbeiten nur durch autorisierte Fachkräfte ausgeführt werden dürfen.
5. Lassen Sie Störungen, welche die Sicherheit beeinträchtigen können, sofort beseitigen.
2. Funktionsbeschreibung
Federbelastete Rückflussverhinderer haben einen beweglichen Dichtkegel, der sich beim jeweiligen Volumenstrom mehr oder weniger vom Ventilsitz abhebt. Geht der Volumenstrom gegen Null, so wird der Dichtkegel durch die
Federkraft wieder auf den Ventilsitz zurückgeführt und liegt dort dicht auf.
Im Interesse der Funktionssicherheit des Rückflussverhinderers ist nach der
EN 1717 eine regelmäßige Inspektion und Wartung erforderlich.
Der Filtereinsatz ist in zwei Bereiche unterteilt. Beim Filtern wird nur der große untere Bereich von außen nach innen von Wasser durchströmt, der kleine obere Bereich kommt nicht mit ungefiltertem Wasser in Berührung.
Beim Öffnen des Kugelventils zum Rückspülen wird der gesamte Filtereinsatz nach unten gedrückt bis die Wasserzufuhr zur Außenseite des unteren
Bereichs unterbrochen ist. Gleichzeitig wird der Wasserdurchfluss durch den oberen Bereich geöffnet. Das für die Filterreinigung benötigte Wasser durchströmt den oberen Filterbereich, den rotierenden Impeller und anschließend den unteren Filterbereich von innen nach außen, d.h. die Rückspülung erfolgt mit gefiltertem Wasser. Dabei wird auch der obere Bereich durch den Impellerstrahl gereinigt. Durch Schließen des Kugelventils schaltet sich der Filtereinsatz automatisch in Betriebsstellung zurück.
Federbelastete Druckminderer arbeitet nach dem Kraftvergleichssystem. Der
Membrankraft wirkt die Federkraft des Regelventils entgegen. Sinkt infolge einer Wasserentnahme der Ausgangsdruck (Hinterdruck) und damit die
Membrankraft, so öffnet die nun größere Federkraft das Ventil. Der
Ausgangsdruck wird wieder höher, bis erneut ein Gleichgewichtszustand zwischen Membran- und Federkraft erreicht ist.
Der Eingangsdruck (Vordruck) hat keinen Einfluss auf das Regelventil im
Druckminderer. Druckschwankungen auf der Eingangsseite beeinflussen nicht den Hinterdruck (Vordruckkompensation).
3. Verwendung
Medium
Vordruck
Hinterdruck
Einbaulage
Anschlussgröße
Flansche eingans- und ausgangsseitig
Trinkwasser max. 16 bar
1,5 - 6,5 bar waagrecht, mit Filtertasse nach unten
DN 65 - DN 100
Flansche PN16 nach DIN86021 /
ISO 7005-2, EN 1092-2
Das Gerät wurde für den Einsatz im Trinkwasser entwickelt.
Die Verwendung in Prozesswässern ist im Einzelfall zu prüfen.
4. Technische Daten
Betriebstemperatur
Nenndruck max. 65°C
PN16
Mindestdruckgefälle 1,0 bar
Öffnungsdruck beim
Rückflussverhinderer ca. 0,05 bar
Betriebsdruck Min. 2,0 bar
Max. 16,0 bar
Membranleistung
Anschlussgröße max. 9,0 bar
DN 65 - DN 100
•
•
5. Lieferumfang
•
Die Wasserstation besteht aus:
Rückflussverhinderer mit
- Gehäuse und Gehäusekopf mit Flanschen
- Rückflussverhinderereinsatz
- Prüf- und Entleerungsschraube
- Dichtkegel, Führungsbuchsen, Druckfeder, Lippendichtring
Feinfilter mit
- Gehäuse mit Flanschen
- Manometer
- Feinfilter in Messing-Filtertasse
- Kugelventil mit Hebel und Ablaufanschluss
Druckminderer mit
- Gehäuse mit Flanschen nach ISO 7005-2, EN 1092-2
- Federhaube mit Einstellschraube
- Sollwertfeder
- Kartuscheneinsatz
- Manometer
6. Varianten
•
•
•
•
•
HS10S-...FA = Standardausführung mit Flanschen PN16, untere/obere
Durchlassweite Filtersieb 105/135 μ m
Anschlussgröße
7. Montage
•
7.1. Einbauhinweise
Einbau in waagrechte Rohrleitung mit Prüf- und Entleerungsschraube und
Filtertasse nach unten und Federhaube nach oben
- In dieser Einbaulage ist eine optimale Entleerung und Filterwirkung gewährleistet
Absperrventile vorsehen
- Mit Absperrventilen ist ein optimaler Service gewährleistet
Auf gute Zugänglichkeit achten
- Manometer gut beobachtbar
- Vereinfacht Wartung und Inspektion
Der Einbauort muss frostsicher sein
Unmittelbar nach dem Wasserzähler einbauen
- Entsprechend DIN 1988, Teil 2
Beruhigungsstrecke von 5xDN hinter Druckminderer vorsehen (Entsprechend DIN EN806 Teil 2)
7.2. Montageanleitung
1. Rohrleitung gut durchspülen
2. Druckminderer einbauen
• Durchflussrichtung beachten
• spannungs- und biegemomentfrei einbauen
3. Manometer eindichten
7.3. Rückspülwasserabführung
Das Rückspülwasser muss so zum Ablaufkanal geführt werden, dass kein
Rückstau entstehen kann.
Dazu gibt es 3 Möglichkeiten:
1. Direkter Anschluss:
• Übergansstück DN 50/70 sowie erforderliche Rohre und Siphon (3
Bögen 90°) in DN 70.
2. Ablauf frei in vorhandenen Bodenablauf
3. Ablauf in offenen Behälter.
Filter-Größe Rückspülmenge*
DN65 - 100 15 Liter
*bei 4 bar Eingangsdruck und 25 s Rückspüldauer
Honeywell GmbH 2 MU1H-1155GE23 R0912
D
8. Inbetriebnahme
8.1. Hinterdruck einstellen
Ausgangsdruck min. 1 bar unter Eingangsdruck einstellen.
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Sechskantmutter auf Federhaube lösen
5. Druckfeder entspannen
6. Absperrarmatur eingangsseitig langsam öffnen
7. Verstellschraube drehen, bis Manometer den gewünschten Wert anzeigt
8. Sechskantmutter wieder festziehen
9. Absperrarmatur ausgangsseitig langsam öffnen
8.2. Rückspülen
Während des Rückspülens ist ein Eingangsdruck von mindestens 1,5 bar erforderlich. Das Rückspülintervall ist abhängig vom Verschmutzungsgrad des Wassers. Spätestens alle 2 Monate muss entsprechend DIN 1988, Teil
8 eine Rückspülung durchgeführt werden. Zur bequemen und regelmäßigen
Einhaltung des Rückspülintervalls empfehlen wir den Einbau einer Rückspülautomatik Z11AS.
Auch während des Rückspülens kann gefiltertes Wasser entnommen werden.
8.2.1. Manuelles Rückspülen
Erfolgt die Rückspülwasserabführung nicht durch einen direkten Anschluss, so muss vor dem Rückspülen ein Auffanggefäß untergestellt werden.
1. Kugelhahn langsam öffnen
• das patentierte Rückspülsystem wird in Gang gesetzt
2. Kugelhahn nach ca. 3 Sekunden wieder schließen. Vorgang drei Mal
• wiederholen bei stark verschmutztem Filter können zusätzliche Wiederholungen erforderlich sein
8.2.2. Automatisches Rückspülen mit Z11AS
Die Rückspülautomatik Z11AS ist als Zubehör erhältlich. Die Automatik übernimmt zuverlässig das Rückspülen des Filters in einstellbaren Zeiträumen zwischen 4 Minuten und 3 Monaten.
8.2.3. Differenzdruckgesteuertes Rückspülen mit DDS76 und Z11AS
Ebenfalls als Zubehör ist der Differenzdruckschalter DDS 76 erhältlich. Er
übernimmt die vollautomatische differenzdruck-abhängige Steuerung des
Rückspülvorgangs. Er löst den Rückspülvorgang durch den Vergleich der
Drücke vor und hinter dem Filtersieb aus. Übersteigt der anstehende Differenzdruck den eingestellten Wert, sowird die Rückspülautomatik Z11AS über ihren potentialfreien Eingang ausgelöst.
9. Instandhaltung
9.1. Inspektion
Wir empfehlen einen Wartungsvertrag mit einem Installationsunternehmen abzuschließen
Entsprechend DIN 1988, Teil 8 sind folgende Maßnahmen durchzuführen:
9.1.1. Rückflussverhinderer
Intervall: einmal jährlich
1. Absperrarmatur eingangsseitig schließen
2. Prüfventil öffnen
• Bis zur Druckentlastung wird etwas Wasser am Prüfventil ausfließen.
Nach kurzer Zeit muss der Wasserausfluß aufhören. Tropft oder läuft das Wasser beständig weiter, so ist der Austausch des Rückflussverhinderers notwendig - siehe Wartung Rückflussverhinderer
3. Prüfventil wieder schließen
4. Absperrarmatur eingangsseitig langsam öffnen
9.1.2. Filter
Intervall: alle 2 Monate
•
•
•
Der Filter muss regelmäßig, spätestens alle 2 Monate, durch Rückspülen gereinigt werden
Eine Nichtbeachtung kann zu Filterverstopfung führen. Druckabfall und sinkender Wasserdurchfluss sind die Folge
Die Siebe des Filters sind aus nichtrostendem Stahl. Roter Belag infolge von Rost aus den Rohrleitungen hat keinen Einfluss auf Funktion und
Filterwirkung
Sichtkontrolle des Kugelventils nicht vergessen.
Bei Tropfenbildung auswechseln!
9.1.3. Druckminderer
Intervall: einmal jährlich
1. Absperrarmatur ausgangsseitig schließen
2. Hinterdruck mit Druckmessgerät bei Nulldurchfluss kontrollieren
• Steigt der Druck langsam an, ist die Armatur eventuell verschmutzt oder defekt. Führen Sie in diesem Fall eine Wartung und Reinigung durch
3. Absperrarmatur ausgangsseitig langsam öffnen
9.2. Wartung
Intervall: 1-3 Jahre (abhängig von den örtlichen Bedingungen)
Durchführung durch ein Installationsunternehmen.
9.2.1. Rückflussverhinderer
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Rückflussverhinderer austauschen
5. Absperrarmaturen ein- und ausgangsseitig langsam öffnen
9.2.2. Filter
9.2.2.1.Filtereinsatz wechseln
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Filtertasse abschrauben
5. Filtereinsatz entnehmen
6. Neuen Filtereinsatz einstecken
• O-Ring aufstecken
7. Neuen O-Ring auf Filtertasse stecken
8. Filtertasse aufschrauben
9. Absperrarmatur eingangsseitig langsam öffnen
10. Absperrarmatur ausgangsseitig langsam öffnen
9.2.2.2.Sieb wechseln
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Filtertasse abschrauben
5. Filtereinsatz entnehmen
6. Schraube lösen
7. Filtereinsatz demontieren
Im Filtereinsatz befindet sich eine Druckfeder. Durch Herausspringen der Druckfeder kann es zu Verletzungen kommen.
• Stellen Sie sicher, dass die Druckfeder entspannt ist!
8. Siebe austauschen
9. Filtereinsatz montieren
10. Filtereinsatz einstecken
11. Neuen O-Ring auf Filtertasse stecken
12. Filtertasse aufschrauben
13. Absperrarmatur eingangsseitig langsam öffnen
14. Absperrarmatur ausgangsseitig langsam öffnen
Honeywell GmbH 3 MU1H-1155GE23 R0912
9.2.2.3.Kugelhahn wechseln
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Ablaufanschluss abschrauben
5. Kugelhahn abschrauben
6. Neuen Kugelhahn einschrauben
7. Ablaufanschluss einschrauben
8. Absperrarmatur eingangsseitig langsam öffnen
9. Absperrarmatur ausgangsseitig langsam öffnen
9.2.3. Druckminderer
Intervall: 1-3 Jahre (abhängig von den örtlichen Bedingungen)
Durchführung durch ein Installationsunternehmen.
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Sechskantmutter auf Federhaube lösen
Vorsicht !
In der Federhaube befindet sich eine Druckfeder. Durch Herausspringen der Druckfeder kann es zu Verletzungen kommen.
• Stellen Sie sicher, dass die Druckfeder entspannt ist!
5. Druckfeder entspannen
• Verstellschraube nach links (-) bis zum Anschlag drehen
6. Federhaube abschrauben
7. Kartuscheneinsatz auf einwandfreien Zustand prüfen und ggf. austauschen, bzw. dichtende Teile ersetzen
8. Montage in umgekehrter Reihenfolge
9.3. Reinigung
9.3.1. Sieb
1. Absperrarmatur eingangsseitig schließen
2. Ausgangsseite druckentlasten (z.B. durch Wasserzapfen)
3. Absperrarmatur ausgangsseitig schließen
4. Filtertasse abschrauben
5. Filtereinsatz entnehmen
6. Sieb reinigen
7. Filtereinsatz wieder einstecken
8. Filtertasse aufschrauben
D
9. Absperrarmatur eingangsseitig langsam öffnen
10. Absperrarmatur ausgangsseitig langsam öffnen
•
•
•
10. Entsorgung
Rückflussverhinderer
- Gehäuse und Gehäusekopf aus Grauguss
- Stiftschrauben und Muttern aus nichtrostendem Stahl
- Dichtkegel aus nichtrostendem Stahl
- Druckfeder aus nichtrostendem Federstahl
- Lippendichtring aus EPDM
Feinfilter
- Gehäuse und Filterhaube aus Rotguss
- Innenteile aus nichtrostendem Stahl, Rotguss und Messing
- Feinfilter aus nichtrostendem Stahl
Druckminderer
- Gehäuse aus duktilem Guss (EN-GJS-400-15 EN1563), beschichtet mit
PA (Rilsan)
- Federhaube aus duktilem Guss (EN-GJS-400-15 EN1563), beschichtet mit PA (Rilsan)
- Kartuscheneinsatz komplett aus bleiarmen (<2,2% gem. DIN 50930 Teil
6) Messing mit Edelstahlventilspindel
- Sollwertfeder aus Federstahl
- Membrane und Dichtungen aus EPDM
- Nutring und Dichtscheibe aus hochwertigem PU
- Schrauben und Muttern aus nichtrostendem Stahl
Die örtlichen Vorschriften zur ordnungsgemäßen Abfallverwertung bzw.
Beseitigung beachten!
11. Störungen / Fehlersuche
Störung
Schlagende Geräusche
Wasseraustritt aus Federhaube
Kein oder zu wenig Wasserdruck
Ursache
Druckminderer zu groß dimensioniert
Membrane defekt
Behebung
Technische Kundenberatung anrufen
Membrane ersetzen
Federhaube nicht auf Block festgeschraubt
O-Ring in Membrankolben bei der Montage vergessen
Absperrarmaturen vor oder hinter Wasserstation nicht ganz geöffnet
Druckminderer nicht auf gewünschten Hinterdruck eingestellt
Schrauben nachziehen
O-Ring einsetzen
Absperrarmaturen ganz öffnen
Hinterdruck einstellen
Wasserstation nicht in Durchflussrichtung montiert Wasserstation in Durchflussrichtung montieren (Pfeilrichtung auf Gehäuse beachten)
Honeywell GmbH 4 MU1H-1155GE23 R0912
12. Serviceteile
2
1
4
3
4
3
5
D
Nr. Bezeichnung
1
2
Dichtkegel
Lippendichtring
3
4
Sechskant-Stopfen
Dichtring
Nennweite
DN65
DN80
DN100
DN65
DN80
DN100
DN65 - DN100
DN65 - DN100
Artikelnummer
0900376
0900377
0900378
5350000
5350300
5350400
2248700
5350500
6
8
5
7
8
Nr. Bezeichnung
5 Filtereinsatz komplett
6
Nennweite Artikelnummer
105/135 μ m
Filterfeinheit 200 μ m
DN 100
DN 65
DN 80
DN 100
AF76S-65A
AF76S-80A
AF76S-100A
AF76S-65D
AF76S-80D
AF76S-100D
Ersatzsieb
105/135 μ m DN 100
ES76S-65A
ES76S-80A
ES76S-100A
Filterfeinheit 200 μ m
Kugelhahn komplett
DN 100 ES76S-100D
5622100
Manometer M76K-A16
Teilung 0 - 16 bar
DN 65
DN 80
ES76S-65D
ES76S-80D
7
Honeywell GmbH 5 MU1H-1155GE23 R0912
D
Nr. Bezeichnung
9
Nennweite
Ventileinsatz komplett DN65-100
10
11
12
Artikelnummer
0904120
Dichtungssatz komplett DN65-100 0904121
Manometer M39M-A10
Teilung 0 - 10 bar
Manometer M39M-A16
Teilung 0 - 16 bar
13. Zubehör
9
12
10
11
10
FY69P
Z11AS
DDS76
FY69P
Rückspülautomatik
Zum automatischen Rückspülen des Filters in einstellbaren
Zeitintervallen
Differenzdruckschalter
Schmutzfänger
Mit feinem Doppelsieb, Gehäuse aus Grauguss, innen und außen pulverbeschichtet
A = Maschenweite ca. 0,5 mm
Z11AS
DDS76
Honeywell GmbH 6 MU1H-1155GE23 R0912
GB
1. Safety Guidelines
1. Follow the installation instructions.
2. Use the appliance
•
• according to its intended use in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the applications detailed in these installation instructions. Any other use will not be considered to comply with requirements and would invalidate the warranty.
4. Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
5. Immediately rectify any malfunctions which may influence safety.
2. Description of function
Spring loaded check valves have a moving seal disc which is lifted off the seat by a greater or lesser amount depending on the flow rate through the valve.
If the flow falls towards zero, then the spring pushes the disc back onto the seat and seals the waterway.
To ensure continuing correct function it is recommended that check valves be regularly checked and maintained (as specified in EN 1717).
The filter insert is divided into two parts. In the „filtering“ position, only the lower, larger section is rinsed through by water jets from outside to inside.
The small upper section does not come in contact with unfiltered water. When the ball valve is opened for reverse rinsing, then the whole filter insert is pushed downwards until the water supply to the outer side of the main filter is stopped. Simultaneously, the water flow is opened to the upper part of the filter. The water needed for cleaning the filter passes through the upper filter section, then the rotating impeller and the main filter from inside to outside, i.e. the filter is reverse rinsed with filtered water. In that way the upper filter is also cleaned by jets from the impeller. The filter automatically switches back to the operating position when the ball valve is closed again.
Spring loaded pressure reducing valves operate by means of a force equalising system. The force of a diaphragm operates against the force of an adjustment spring. If the outlet pressure and therefore diaphragm force fall because water is drawn, the then greater force of the spring causes the valve to open. The outlet pressure then increases until the forces between the diaphragm and the spring are equal again.
The inlet pressure has no influence in either opening or closing of the valve.
Because of this, inlet pressure fluctuation does not influence the outlet pressure, thus providing inlet pressure balancing.
3. Application
Medium
Inlet pressure
Outlet pressure
Installation position
Connection size
Flanges on inlet and outlet
Drinking water
Max. 16 bar
1.5 - 6.5 bar
Horizontal with filter bowl downwards
DN 65 - DN 100
Flanges PN16 acc. to DIN86021 /
ISO 7005-2, EN 1092-2
The filter is constructed for drinking water installations. In case of a process water application the filter has to be proven individually.
4. Technical data
Operating temperature
Nominal pressure
Minimum pressure drop
Opening pressure check valve
Operating pressure
Diaphragm pressure loading
Connection size
Max. 65 °C
PN16
1.0 bar ca. 0.05 bar
Min. 2.0 bar
Max. 16.0 bar
Max. 9.0 bar
DN 65 - DN 100
•
•
5. Scope of delivery
•
The water station comprises:
Check valve with
- Housing and housing end casing with flanges
- Check valve insert
- Test and drain plugs
- Disc, guide, spring, disc lip seal ring
Fine filter with
- Housing with flanges
- Pressure gauge
- Fine filter in brass filter bowl
- Ball valve with lever and drain connection
Pressure reducing valve with
- Housing with PN16 flanges per ISO7005-2, EN1092-2
- Spring bonnet with adjustment screw
- Adjustment spring
- Cartridge insert
- Pressure gauge
6. Options
HS10S-...FA = Standard version with flanges PN16, Filter mesh size 100 μ m
Connection size
•
•
•
•
•
7. Assembly
•
7.1. Installations Guidelines
Install in horizontal pipework with test and drain plugs and filter bowl downwards and spring bonnet upwards
- This position ensures optimum draining and filter efficiency
Install shutoff valves
- Shutoff valves provide optimal serviceability
Ensure good access
- Pressure gauge can be read off easily
- Simplifies maintenance and inspection
The installation location should be protected against frost
Fit immediately after water meter
- Corresponds to DIN 1988, Part 2
Provide a straight section of pipework of at least five times the nominal valve size after the pressure reducing valve (in accordance with DIN
EN806 part 2)
7.2. Assembly instructions
1. Thoroughly flush pipework
2. Install pressure reducing valve
• Note flow direction
• Install without tension or bending stresses
3. Seal in pressure gauge
7.3. Discharge of reverse rinsing water
The reverse rinsing water must be routed to the drain channel in such a way that no backwater can occur.
To do this there are 3 options:
1. Direct connection:
• Connector DN 50/70 as well as the necessary pipes and siphon (3 elbows 90°) in DN 70.
2. Discharge into floor drain
3. Drain into open container.
Filter size Reverse rinsing volume*
DN65 - 100 15 litre
*at 4 bar inlet pressure and 25 s reverse rinsing duration
Honeywell GmbH 7 MU1H-1155GE23 R0912
8. Start-up
8.1. Setting outlet pressure
Set outlet pressure min. 1 bar under inlet pressure.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen hexagon nut on spring bonnet
5. Slacken tension in compression spring
6. Slowly open shutoff valve on inlet
7. Rotate adjustment screw, until the pressure gauge shows the desired value
8. Retighten hexagon nut
9. Slowly open shutoff valve on outlet
8.2. Reverse rinsing
During reverse rinsing, an inlet pressure of at least 1.5 bar is required. The reverse rinsing interval depends on the degree of dirt in the water. At the latest every 2 months, reverse rinsing should be carried out according to DIN
1988, Part 8. To ensure convenient and regular adherence to the reverse rinsing interval, we recommend installing an automated reverse rinsing system Z11AS.
Filtered water can also be tapped during reverse rinsing.
8.2.1. Manual reverse rinsing
If reverse rinsing water is not to be discharged via a direct connection, a collecting container must be positioned beneath before reverse rinsing.
1. Slowly open the ball valve
• The patented reverse rinsing system starts
2. Close ball valve again after approx. 3 seconds. Repeat procedure three
• times
If the filter is extremely dirty, the procedure may have to be repeated additional times
8.2.2. Automatic reverse rinsing with the Z11AS
The automated reverse rinsing system Z11AS is available as an accessory.
The automated system reliably takes over reverse rinsing of the filter at intervals which can be set between 4 minutes and 3 months.
8.2.3. Differential pressure controlled reverse rinsing with the DDS76 and Z11AS
Also available as an accessory is the DDS76 differential pressure switch. It provides fully automatic operation of the reverse rinsing which is controlled by the differential pressure across the filter. It actuates a reverse rinsing cycle when the pressure differential between the inlet and outlet of the filter reaches a predetermined value. If the pressure difference exceeds the preset value, then the Z11AS reverse rinsing actuator is operated via its volt-free input.
9. Maintenance
9.1. Inspection
We recommend a planned maintenance contract with an installation company
In accordance with DIN 1988, part 8, the following measures must be taken:
9.1.1. Check valve
Interval: once a year
1. Close shutoff valve on inlet
2. Open test valve
• Until the pressure is released, some water will flow out of the test valve.
After a short period of time the water flow should stop. If the water continues to drip or run, then the check valve must be replaced - see servicing of check valve
3. Close test valve again
4. Slowly open shutoff valve on inlet
GB
9.1.2. Filter
Interval: every 2 months
•
•
•
The filter must be cleaned by reverse rinsing regularly, at the latest every
2 months
Non-compliance can lead to the filter becoming blocked This results in a drop in pressure and decreasing water flow
The filter meshes are made of stainless steel. A red coating as a consequence of rust from the pipelines has no influence on function or the way the filter works
Do not forget to do a visual check of the ball valve. Replace if it is dripping!
9.1.3. Pressure reducing valve
Interval: once a year
1. Close shutoff valve on outlet
2. Check outlet pressure using a pressure meter when there is zero throughflow
• If the pressure is increasing slowly, the valve may be dirty or defective.
In this instance, carry out servicing and cleaning
3. Slowly open shutoff valve on outlet
9.2. Maintenance
Frequency: every 1-3 years (depending on local operating conditions)
To be carried out by an installation company
9.2.1. Check valve
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Replace check valve
5. Slowly open shut off valves on inlet and outlet
9.2.2. Filter
9.2.3.1.Replace filter insert
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
5. Remove filter cartridge
6. Insert new filter insert
• Put on the O-ring
7. Put new O-ring on filter bowl
8. Screw filter bowl in place
9. Slowly open shutoff valve on inlet
10. Slowly open shutoff valve on outlet
9.2.4.2.Replace sieve
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
5. Remove filter cartridge
6. Loosen screw
7. Remove filter insert
There is a pressure spring in the filter insert. Injuries may be caused by
• the pressure spring jumping out.
Make sure tension in compression spring is slakkened!
8. Replacing sieve
9. Mount the filter insert
10. Insert filter insert
11. Put new O-ring on filter bowl
12. Screw filter bowl in place
13. Slowly open shutoff valve on inlet
14. Slowly open shutoff valve on outlet
Honeywell GmbH 8 MU1H-1155GE23 R0912
9.2.5.3.Replace ball valve
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew discharge connection
5. Remove ball valve
6. Screw in new ball valve
7. Screw in discharge connection
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet
9.2.6. Pressure reducing valve
Frequency: every 1-3 years (depending on local operating conditions)
To be carried out by an installation company
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen hexagon nut on spring bonnet
Caution !
There is a spring in the spring bonnet. It may cause injuries if the spring is derailing.
• Make sure tension in compression spring is slakkened!
5. Slacken tension in compression spring
• Turn control adjustment screw to the left (-) until it does not move any more
6. Unscrew spring bonnet
7. Check the cartridge insert for fault-free condition and replace insert or sealing parts if necessary.
8. Reassemble in reverse order
9.3. Cleaning
9.3.1. Sieve
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
5. Remove filter cartridge
6. Clean sieve
7. Re-insert the filter insert
8. Screw filter bowl in place
9. Slowly open shutoff valve on inlet
10. Slowly open shutoff valve on outlet
GB
•
•
•
10. Disposal
Check valve
- Grey cast iron housing end and housing
- Stainless steel screws and nuts
- Stainless steel disc
- Stainless steel spring
- EPDM for lip seal ring
Fine filter
- Red bronze housing and filter bowl
- Stainless steel, red bronze and brass inner parts
- Stainless steel fine filter
Pressure reducing valve
- Housing made of ductile cast iron (EN-GJS-400-15 EN1563), coated with PA (Rilsan)
- Spring bonnet made of ductile cast iron (EN-GJS-400-15 EN1563), coated with PA (Rilsan)
- Cartridge insert made completely of low-lead (<2.2% acc. to DIN 50930 part 6) brass with stainless steel valve spindle
- Spring steel adjustment spring
- Diaphragm and seals made of EPDM
- Groove ring and sealing disc made of high-quality PU
- Stainless steel thread rod and nuts
Observe the local requirements regarding correct waste recycling/ disposal!
11. Troubleshooting
Problem
Beating sounds
Water is escaping from the spring bonnet
Too little or no water pressure
Cause
Pressure reducing valve is too large
Diaphragm is faulty
Spring bonnet not screwed flush
O-ring forgotten in the diaphragm piston during assembly
Remedy
Call our Technical Customer Services
Replace diaphragm
Retighten the screws
Insert O-ring
Shut-off valves upstream or downstream from water station not fully open
Open the shutoff valves fully
Pressure reducing valve is not set to the desired outlet pressure
Set outlet pressure
Water station not mounted in the direction of flow Fit water station in flow direction (note direction of arrow on housings)
Honeywell GmbH 9 MU1H-1155GE23 R0912
12. Spare Parts
2
1
5
4
3
7
6
4
3
GB
3
4
No. Description
1
2
Valve disc guide
Dimension
DN65
DN80
DN100
Lip seal ring DN65
DN80
DN100
Hexagonal blanking plug DN65 - DN100
Seal ring DN65 - DN100
Part No.
0900376
0900377
0900378
5350000
5350300
5350400
2248700
5350500
8
5
No. Description
5 Filter insert complete
Filter mesh 100 μ m
Dimension
DN 65
DN 80
DN 100
Filter mesh 200 μ m DN 65
DN 80
DN 100
Filter mesh 50 μ m DN 65
DN 80
DN 100
6 Replacement sieve
Filter mesh 100 μ m DN 65
DN 80
DN 100
Filter mesh 200 μ m DN 65
DN 80
DN 100
Filter mesh 50 μ m DN 65
DN 80
DN 100
Filter mesh 500 μ m DN 65
DN 80
DN 100
7
8
Ball valve
Pressure gauge
0 - 16 bar
Part No.
AF76S-65A
AF76S-80A
AF76S-100A
AF76S-65D
AF76S-80D
AF76S-100D
AF76S-65C
AF76S-80C
AF76S-100C
ES76S-65A
ES76S-80A
ES76S-100A
ES76S-65D
ES76S-80D
ES76S-100D
ES76S-65C
ES76S-80C
ES76S-100C
ES76S-65F
ES76S-80F
ES76S-100F
5622100
M76K-A16
Honeywell GmbH 10 MU1H-1155GE23 R0912
GB
No. Description
9
Dimension
Valve insert complete DN65-100
10
11
12
Set of seals complete DN65-100
Pressure gauge
Ranges 0 - 10 bar
Pressure gauge
Ranges 0 - 16 bar
Part No.
0904120
0904121
M39M-A10
M39M-A16
9
12
10
11
10
13. Accessories
FY69P
Z11AS
DDS76
FY69P
Automatic reverse rinsing actuator
For automatic reverse rinsing of the filter at presettable intervals
Differential pressure switch
Strainer
With double mesh, grey cast iron housing, powder coated inside and outside.
A = Mesh size approximately 0.5 mm
Z11AS
DDS76
Honeywell GmbH 11 MU1H-1155GE23 R0912
Automation and Control Solutions
Honeywell GmbH
Hardhofweg
74821 MOSBACH
GERMANY
Phone: (49) 6261 810
Fax: (49) 6261 81309 http://ecc.emea.honeywell.com
Manufactured for and on behalf of the Environmental and
Combustion Controls Division of Honeywell Technologies
Sàrl, Z.A. La Pièce 16, 1180 Rolle, Switzerland by its
Authorised Representative Honeywell GmbH
MU1H-1155GE23 R0912
Subject to change
© 2012 Honeywell GmbH
D
1. Sicherheitshinweise ............................................................................. 2
2. Funktionsbeschreibung ........................................................................ 2
3. Verwendung ......................................................................................... 2
4. Technische Daten ................................................................................ 2
5. Lieferumfang ........................................................................................ 2
6. Varianten .............................................................................................. 2
7. Montage ............................................................................................... 2
8. Inbetriebnahme .................................................................................... 3
9. Instandhaltung ..................................................................................... 3
10. Entsorgung ........................................................................................... 4
11. Störungen / Fehlersuche ...................................................................... 4
12. Ersatzteile ............................................................................................ 5
13. Zubehör ................................................................................................ 6
GB
1. Safety Guidelines ................................................................................. 7
2. Functional description .......................................................................... 7
3. Application ........................................................................................... 7
4. Technical data ...................................................................................... 7
5. Scope of delivery ................................................................................. 7
6. Options ................................................................................................. 7
7. Assembly ............................................................................................. 7
8. Commissioning .................................................................................... 8
9. Maintenance ........................................................................................ 8
10. Disposal ............................................................................................... 9
11. Troubleshooting ................................................................................... 9
12. Spare parts ........................................................................................ 10
13. Accessories ........................................................................................ 11
Honeywell GmbH MU1H-1155GE23 R0912
7.
8.1
4.
5.
7.3
1.
DN50/70
DN70
300
2.
8.2.1
9.2.1
3.
15 l
9.2.2.1
7.
bar
6.
7.
5.
4.
8.
8.
1.
2.
9.2.2.2
10.
11.
5.
4.
8.
12.
7.
6.
9.
9.2.2.3
3.
5.
4.
6.
7.
2.
9.2.3
4.
6.
9.3.1
5.
7.
2
2
7.
5.
4.
8.
Honeywell GmbH
advertisement