Goodman AVPEC Spec Sheet

Show HTML Add to My manuals
10 Pages

advertisement

Goodman AVPEC Spec Sheet | Manualzz

AVPEC

Multi-Position, Variable-Speed,

ECM-Based Air Handler with

Internal EEV, ComfortBridge ™ and Inverter Compatible

2 to 5 Tons

Contents

Nomenclature ....................................... 2

Product Specifications .......................... 3

Dimensions ........................................... 4

Airflow Data ........................................... 5

Heat Kit Data .......................................... 6

Wiring Diagram ..................................... 8

Accessories ........................................... 9

Product Features

• Electronic Expansion Valve (EEV) for cooling and heat pump applications.

• Variable-speed ECM blower motor

• Suitable for operation with inverter-driven products

• Integrated communicating ComfortBridge ™ Technology

• Commissioning and diagnostics via on board Bluetooth with the CoolCloud™ phone and tablet application

• Provides constant CFM over a wide range of static pressure conditions independent of duct system

• CFM indicator

• Provides adjustable low CFM for efficient fan-only operation

• All-aluminum evaporator coil

• Fault recall of six most recent faults

• Improved humidity and comfort control

• 3 kW – 25 kW electric heater kits

• AHRI certified; ETL listed

• Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193

• Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193

• Horizontal or vertical configuration capabilities

• 21 " depth for easier attic access

• DecaBDE-free thermoplastic drain pan with secondary drain connections

• Screw-less sides and back helps to reduce condensation when installed in humid locations

• Foil-faced insulation covers the internal casing to reduce cabinet condensation

• Galvanized, leather grain-embossed finish

• Glue-less cabinet insulation retention

• Tool-less filter access

SS-GAVPEC

* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.

www.goodmanmfg.com

8/21

Supersedes 3/21

Nomenclature

Brand

A Single-Piece Air Handler

A

1

Unit Application

R Multi Position PSC Motor

S Multi Position EEM Motor

V Multi Position Variable-Speed

Motor - Communicating

Cabinet Finish

U Unpainted

P Painted

Expansion Device

E Electronic Expansion Valve

T Expansion Device

V Inverter Tuned Expansion Valve

V

2

P

3

E

4

C

5

Communicating

C = Yes

25

6,7

B

8

1

9

4

10

AA

11,12

Engineering*

Major/Minor Revisions

*Not used for inventory management

Refrigerant Charge

4 = R-410A

Electrical

1 208/230V, 1 Phase, 60 Hz

24 = 2 Tons

25 = 2 Tons

29 = 2 Tons

30 = 2½ Tons

Cabinet Width

B = 17½"

C = 21"

D = 24½"

Nominal Capacity @ 13 SEER

31 = 2½ Tons

36 = 3 Tons

37 = 3½ Tons

42 = 3½ Tons

48 = 4 Tons

49 =3-3½ Tons

59 = 4-5 Tons

60 = 5 Tons

61 = 4-5 Tons

2

HKS

1 2

X 03

3 4

X

5

A AA

6,7

Unit Type

HKS Heat Kit for

Air Handlers

Circuit Breaker

X No circuit breaker

C Circuit Breaker

Heating Capacity @ 240 Volts

03 3.0 kW

05 4.5 kW

15 14.4 kW

19 19.2 kW wth 150F limit

06

08

6.0 kW

8.0 kW

10 9.6 kW

20 19.2 kW with 170F limit

25 25.0 kW

Revisions

Engineering Revisions

A Single Phase 208 V

B Single Phase 240 V

Phase

E Three Phase 240 V

F Three Phase 208/240 V

C Single Phase 208/240 V G Three Phase 460 V

D Three Phase 208 V

H Special case 208 V*

Cabinet Size (MAX)

C C Cabinet

D D Cabinet

X All Cabinet Sizes www.goodmanmfg.com

*Refer S&R Plate

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

3

Product Specifications

AVPEC25

B14A*

AVPEC37

C14A*

AVPEC59

D14A*

Nominal Ratings

Cooling (BTU/h)

CFM (High range)

Blower

Diameter

Width

Coil Drain Connection FPT

Service Valve

Liquid

Suction

Electrical Data

Voltage

Electric Heat Capacity (kW)

Min Circuit Ampacity

24,000

1200/600

10⅝"

6"

¾"

⅜"

¾"

36,000

1700/800

10⅝"

10⅝"

¾"

⅜"

⅞"

48,000

1800/1350

11⅝"

10⅝"

¾"

⅜"

⅞"

208/240

3, 5, 6, 8, 10

4.9/4.9

208/240

5, 6, 8, 10, 15, 19

6.5/6.5

208/240

5, 6, 8, 10, 15, 20

8.6/8.6

Max. Overcurrent Device (Amps)

Minimum VAC

Maximum VAC

Blower Motor

Full Load Amps (FLA)

Horsepower (HP)

Ship Weight (lbs.)

15/15

197

253

3.9

½

128

15/15

197

253

5.2

¾

150

15/15

197

253

6.9

1

160

Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.

AVPEC61

D14A*

60,000

2000/1600

11⅝"

10⅝"

¾"

⅜"

⅞"

208/240

5, 6, 8, 10, 15, 20, 25

8.6/8.6

15/15

197

253

6.9

1

177

2 www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

3

9

Dimensions

8 7 6 5 4 3 2 1

F F

1-1/2" (11.43 cm)

7-1/8" (18.1 cm)

E

D

5/8" (1.59 cm)

K

C

B

J

3-11/16" (9.37 cm)

1-15/16" (4.92 cm)

9-5/32" (23.26 cm)

7-17/32" (19.13 cm)

5-5/32" (13.10 cm)

3-1/16" (7.78 cm)

1-13/32" (3.57 cm)

5/8" (1.59 cm)

1-25/32" (4.52 cm)

21" (55.88 cm)

11-7/32" (28.50 cm)

21/32 (1.67 cm) 1-23/32" (4.13 cm)

1-11/32" (3.33 cm)

E

D

2-11/16" (6.83 cm)

1-11/16" (4.29 cm)

C

A

B

SEE HORIZONTAL

DRAIN PORT DETAIL

10-3/32" (25.88 cm)

SEE VERTICAL

DRAIN PORT DETAIL

G

E

D

INLET TUBE

H

1" (25.4 cm) 19.5" (49.53 cm)

(RIGHT SIDE VIEW)

17/32

1-13/16" (4.60 cm)

A

SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS)

9 8

F

(FRONT VIEW)

Model

AVPEC25B14

AVPEC37C14

AVPEC59D14

AVPEC61D14

7

A

53⁷⁄₁₆

53⁷⁄₁₆

53⁷⁄₁₆

58

1-13/16" (4.60 cm)

CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO

OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAD,

ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT

6 5 4

B

16⅜

19⅞

23⁵⁄₁₆

23⁵⁄₁₆

C

17½

21

24½

24½

D

20

21¹³⁄₁₆

21½

26⅛

E

21½

18⅝

18⁵⁄₁₆

22⅞

F

14⅛

17¹¹⁄₁₆

21³⁄₁₆

21³⁄₁₆

2-31/32" (7.46 cm)

3-25/32" (9.60 cm)

3

G

9⅛

10¹³⁄₁₆

12⅝

12⁵⁄₁₆

3-1/32" (7.70 cm)

VERTICAL DRAIN

PORT DEATIL

1-5/8" (4.13 cm)

H

7⅝

6¹³⁄₁₆

6⅞

25⅛

2

SCALE: NTS

SHEET: 1 OF 1

DWG.

NO.

AVPEC_DIMENSIONS

1

C

B

4 www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

5

Airflow Data

Model

AVPEC25B14A*

AVPEC37C14A*

AVPEC59D14A*

Stage

High

Low

High

Low

High

Low

0.1

700

520

1190

820

1445

880

0.2

690

505

1170

810

1440

875

AVPEC61D14A*

High

Low

1645

1080

1640

1075

Note: During cooling operation outdoor will determine the indoor airflow

795

1430

870

1640

1070

0.3

690

495

1165

785

1415

870

1635

1070

0.4

685

490

1160

Airflow CFM

0.5

680

470

1145

0.6

670

455

1130

765

1405

860

1630

1060

740

1390

845

1625

1055

730

1380

840

1620

1050

0.7

665

445

1120

720

1375

835

1620

1050

0.8

660

435

1105

710

1370

830

1615

1045

0.9

655

425

1100

Cooling/Heat Pump Airflow table

Model

Airflow

Level

High

CFM

AVPEC25B14A*

Low

High

690

495

AVPEC37C14A*

Low

High

1165

795

AVPEC59D14A*

Low

High

1430

870

AVPEC61D14A*

Low

1640

1070

4 www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

5

Heat Kit Data

Model

HKSC10XC - 240 V

AVPEC37C14AC

HKSX05XC - 208 V

HKSX06XC - 208 V

HKSX08XC - 208 V

HKSX10XC - 208 V

HKSC05XC - 208 V

HKSC08XC - 208 V

HKSC10XC - 208 V

HKSC15XA - 208 V

HKSC19CA - 208 V

HKSC15XF - 208 V ^

HKSX05XC - 240 V

HKSX06XC - 240 V

HKSX08XC - 240 V

HKSX10XC - 240 V

AVPEC25B14AC

HKSX03XC - 208 V

HKSX05XC - 208 V

HKSX06XC - 208 V

HKSX08XC - 208 V

HKSX10XC - 208 V

HKSC05XC - 208 V

HKSC08XC - 208 V

HKSC10XC - 208 V

HKSX03XC - 240 V

HKSX05XC - 240 V

HKSX06XC - 240 V

HKSX08XC - 240 V

HKSX10XC - 240 V

HKSC05XC - 240 V

HKSC08XC - 240 V

HKSC05XC - 240 V

HKSC08XC - 240 V

HKSC10XC - 240 V

HKSC15XB - 240 V

HKSC19CB - 240 V

HKSC15XF - 240 V ^

AVPEC59D14AC

HKSX05XC - 208 V

HKSX06XC - 208 V

HKSX08XC - 208 V

HKSX10XC - 208 V

See notes on page 7.

No Breaker

Breaker

No Breaker

Breaker

No Breaker

Breaker

No Breaker

Breaker

No Breaker

50

28

43

50

6.5/6.5

28

34

43

55

30

47

55

21

30

36

47

Circuit 1

MCA¹

4.9/4.9

48

27

41

48

18

27

32

41

48

57

56.5

56.5

6.5

8.6/8.6

30.3

36

38

48

57

32

49.8

49.8

6.5

32

45

52

34.7

17.3

28.9

34.7

0/0

17.3

21.7

28.9

40

20

33.3

40

12.5

20

25

33.3

Amps

0.0/0.0

34.7

17.3

28.9

34.7

10.8

17.3

21.7

28.9

0

0/0

17.3

21.7

33.3

40

40

40

25

33.3

40

20

34.7

34.7

0

20

28.9

34.7

50

30

45

50

15/15

30

35

45

60

30

50

60

25

30

40

50

MOP²

15/15

50

30

45

50

20

30

35

45

15

15/15

35

40

50

60

60

60

40

50

60

35

50

50

15

35

45

60

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

MOP²

---

---

---

---

---

---

---

---

---

45

---

---

---

25

50

---

---

---

---

---

---

25

45

40

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

Circuit 2

MCA¹

---

---

---

---

---

---

---

---

---

43

---

---

---

25

50

---

---

---

---

---

---

21.7

43.3

38

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

Amps

---

---

---

---

---

---

---

---

---

34.6

---

---

---

---

---

20

40

---

---

---

---

17.3

34.7

30

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

Single-Point Kit

MCA¹ MOP²

-----

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

81.5

107

---

---

---

---

71.5

93.2

---

---

---

---

---

---

---

---

---

---

90

110

---

---

---

---

80

100

---

---

---

---

6 www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

7

6 www.goodmanmfg.com

SS-GAVPEC

Heat Kit Data (cont.)

Model

HKSC05XC - 208 V

HKSC08XC - 208 V

HKSC10XC - 208 V

HKSC15XB 3 - 208 V

HKSC20DH - 208 V

HKSC15XF - 208 V ^

HKSX05XC - 240 V

HKSX06XC - 240 V

HKSX08XC - 240 V

HKSX10XC - 240 V

HKSC05XC - 240 V

HKSC08XC - 240 V

HKSC10XC - 240 V

HKSC15XB - 240 V

HKSC20DB - 240 V

HKSC15XF - 240 V ^

AVPEC61D14AC

HKSX05XC - 208 V

HKSX06XC - 208 V

HKSX08XC - 208 V

HKSX10XC - 208 V

HKSC05XC - 208 V

HKSC08XC - 208 V

HKSC10XC - 208 V

HKSC15XB 3 - 208 V

HKSC20DH - 208 V

HKSC25DA - 208 V

HKSC15XF - 208 V ^

HKSC20XF - 208 V ^

HKSX05XC - 240 V

HKSX06XC - 240 V

HKSX08XC - 240 V

HKSX10XC - 240 V

HKSC05XC - 240 V

HKSC08XC - 240 V

HKSC10XC - 240 V

HKSC15XB - 240 V

HKSC20DB - 240 V

HKSC25DB - 240 V

HKSC15XF - 240 V ^

HKSC20XF - 240 V ^

Breaker

No Breaker

Breaker

No Breaker

Breaker

No Breaker

Breaker

¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25

² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps

3 Notation is correct as XB because technically the 240V heater kit application can be used here without any issues.

^ Three-phase Heater Kits (Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for Heater Kits)

--- indicates Not Required

Note: The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model.

17.3

28.9

34.7

34.7

17.3

21.7

28.9

34.7

40

40

0

0/0

40

20

33.3

40

Amps

17.3

0

20

25

33.3

28.9

34.7

34.7

34.7

0

0

40

60

20

33.3

40

40

20

25

33.3

40

34.7

52

0

0

30

45

52

52

30

36

45

52

59

34

50.3

59

58.6

58.6

8.6

8.6/8.6

Circuit 1

MCA¹

30.3

8.6

34

40

50.3

45

52

52

52

58.6

83.6

8.6

8.6

34

50.3

59

58.6

34

40

50.3

59

52

73.6

8.6

8.6

35

45

60

60

35

40

45

60

60

60

15

15/15

60

35

60

60

MOP²

35

15

35

40

60

45

60

60

60

60

90

15

15

35

60

60

60

35

40

60

60

60

80

15

15

---

---

---

17.3

---

---

---

---

20

40

34.6

---

---

---

---

---

Amps

---

---

---

30

---

---

---

17.3

34.7

40.0

40

34.6

43.3

---

---

---

20

---

---

---

---

34.7

35

30

38

Heating kW Correction Factor

Supply Voltage 240 230 220 210 208

Correction Factor 1.00

0.92 0.84 0.77 0.75

Multiply the 240-volt heating capacity by correction factors.

---

---

---

21.7

---

---

---

---

25

50

43

---

---

---

---

---

Circuit 2

MCA¹

---

38

---

---

---

---

---

21.7

43.3

50

50

43

54

---

25

---

---

---

---

---

---

43.3

43.3

38

47

---

25

---

---

---

---

---

---

25

50

45

---

---

---

---

---

MOP²

---

40

---

---

---

25

45

---

---

50

50

45

60

---

25

---

---

---

---

---

---

45

45

40

50

---

---

---

73.6

---

---

---

---

83.6

109

---

---

---

---

---

---

Single-Point Kit

MCA¹ MOP²

-----

---

---

---

---

---

---

74

95.3

---

---

---

---

---

---

80

100

---

80

---

---

---

---

---

---

90

110

---

---

---

---

---

---

109

134

---

---

---

---

---

83.6

---

---

---

---

95.3

117

---

---

110

150

---

---

---

90

---

---

---

---

---

---

100

125

---

---

SS-GAVPEC www.goodmanmfg.com

7

8

Wiring Diagram

(SEE NOTE 4)

GROUND LUG

9 8

TO

HEATER KIT

7 6 5 4

208/230

VAC

3

RD BK

2 1

PL1

PL2

(SEE NOTE 7)

ECM MOTOR

WH

BR

INSTALLING

AUX ALARM

(ALARM)

(SEE NOTE 8) ~~

J19

~~

BL

HEATER KIT

OUTPUT

RD

BK

BK

RD

BK

RD

COM

BL

208

VAC

24VAC

RD

230

VAC

BK

RD

TR2

(SEE NOTE 1)

COM

208

VAC

PU

24VAC

YL

230

VAC

TR1

(SEE NOTE 1)

FAN

MOTOR

1 2 3 4 5 6 7 8 9 10 11 12

PL3

PL4

RD

BK

THERMOSTAT OUTDOOR UNIT

RD

GR

AUX ALARM

(ALARM)

J19

W BL RD

FH1 F1U FH2

+

VR1

~

C1

D1

~

_

C2

C62 C4

Y2

DH/

Y W

G

C R

J1

R13

C R

J2

L5

R25

GYBK

FH3

F2U

FH4

J13

L1

K3

K1 PB3

K2

PB2

PB1

U6

J20

EEV

GY

J6

J6

BK

YL

RD

OR

J7

J7

THERMISTOR

(HEAT EXCHANGER 1,2)

INTEGRATION

TYPE

U7

U1

J8 J9 J16 J17

U9

B11

J18

J18

INDOOR UNIT

PCB

PRESSURE

SENSOR

BK GY BL

NOTES:

1. PLACE RED WIRES ON 208 V TERMINAL OF

2-TRANSFORMER (TR1/TR2) FOR 208 VAC

OPERATION.

2. MANUFACTURER'S SPECIFIED REPLACEMENT

PARTS MUST BE USED WHEN SERVICING.

3. IF ANY OF THE ORIGINAL WIRES AS

SUPPLIED WITH THIS UNIT MUST

BE REPLACED, IT MUST BE REPLACED

WITH WIRING MATERIAL HAVING A

TEMPERATURE RATING OF AT LEAST 105°C.

USE COPPER CONDUCTORS ONLY.

4. UNIT MUST BE PERMANENTLY GROUNDED

AND CONFORM TO N.E.C ANDLOCAL CODES.

5. TO RECALL THE LAST 6 FAULTS, MOST

RECENT TO LEAST RECENT, DEPRESS

FAULT RECALL BUTTON FOR MORE THAN 2

SECONDS WHILE IN STANDBY (NO THERMOSTAT

INPUTS)

6. YELLOW STATUS LED PROVIDES NETWORK

STATUS.GREEN RX LED INDICATES NETWORK

TRAFFIC

7. DISCARD CONNECTOR PL1 WHEN

INSTALLING OPTIONAL HEAT KIT.

8. REMOVE SHORTING PLATE FROM THE AUX

SWITCH TERMINAL WHEN INSTALLING AUX

ALARM SWITCH.

9. USE N.E.C CLASS 2 WIRE.

INTEGRATED CONTROL:

LOW VOLTAGE

LOW VOLTAGE FIELD

HIGH VOLTAGE

HIGH VOLTAGE FIELD

JUNCTION

TERMINAL

INTERNAL TO

RESISTOR

OVERCURRENT

PROT. DEVICE

PLUG CONNECTION

EQUIPMENT GND

FIELD GROUND

DISCONNECT

COLOR CODES:

BL - BLUE

RD - RED

YL - YELLOW

OR - ORANGE

BK - BLACK

GY - GREY

BR - BROWN

GR - GREEN

PU - PURPLE

WH - WHITE

L1

GRND

L2

INDOOR

AIR

CIRCULATOR

BLWR

GRND

L1 208/230 VAC L2

R

FUSE 3 A

C

G

W

TO

MICRO

TH2

EH1

EH2

AUX IN

AUX OUT

Y

DEHUM

24 VAC

HEAT 1 COIL/R1

HEAT 2 COIL/ R2

CONDENSATE SWITCH

+VDC (1)

RX (2)

TX (3)

GRND (4)

TR2

COM

INTEGRATED CONTROL MODULE

INDOOR

AIR

CIRCULATOR

BLWR

GRND

COMPONENT CODES:

PL1, PL2

TL

TR

F1U, F2U

PL3, PL4

POWER/HEATER

CONNECTOR

THERMAL LIMIT

TRANSFORMER

FUSE LINK

TRANSFORMER

CONNECTOR

0140A00723-C

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

Warning

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

⚡ www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

9

Downflow Kits

DFK-B

AVPEC25B14**

DFK-C

AVPEC37C14**

DFK-D

AVPEC59D14**

AVPEC61D14**

** (DFK-B, DFK-C, DFK-D) kits need to be broken up by cabinet size

Filters

Chassis

B

C

D

Part #

ALFH16201E

ALFH1912201E

ALFH20231E

Size

16.0" x 20.0"

19.5” x 20.0”

23.0” x 20.0”

Single Point Kit **

SPW-01

Model HKR-15C

X

HKR-20C

X

HKR-21C

X

** Must be installed along with any of the above compatible heat kits. This kit will fit any AVPEC air handler as long as a compatible heat kit is installed in the unit.

Accessories

Drain Port Plug

Kit Number

DPK1

Description

Side Drain Port Plug

Application

All Models

8 www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com

9

Notes

10

Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2021 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA. www.goodmanmfg.com

SS-GAVPEC SS-GAVPEC www.goodmanmfg.com