advertisement
AVPEC
Multi-Position, Variable-Speed,
ECM-Based Air Handler with
Internal EEV, ComfortBridge ™ and Inverter Compatible
2 to 5 Tons
Contents
Nomenclature ....................................... 2
Product Specifications .......................... 3
Dimensions ........................................... 4
Airflow Data ........................................... 5
Heat Kit Data .......................................... 6
Wiring Diagram ..................................... 8
Accessories ........................................... 9
Product Features
• Electronic Expansion Valve (EEV) for cooling and heat pump applications.
• Variable-speed ECM blower motor
• Suitable for operation with inverter-driven products
• Integrated communicating ComfortBridge ™ Technology
• Commissioning and diagnostics via on board Bluetooth with the CoolCloud™ phone and tablet application
• Provides constant CFM over a wide range of static pressure conditions independent of duct system
• CFM indicator
• Provides adjustable low CFM for efficient fan-only operation
• All-aluminum evaporator coil
• Fault recall of six most recent faults
• Improved humidity and comfort control
• 3 kW – 25 kW electric heater kits
• AHRI certified; ETL listed
• Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193
• Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193
• Horizontal or vertical configuration capabilities
• 21 " depth for easier attic access
• DecaBDE-free thermoplastic drain pan with secondary drain connections
• Screw-less sides and back helps to reduce condensation when installed in humid locations
• Foil-faced insulation covers the internal casing to reduce cabinet condensation
• Galvanized, leather grain-embossed finish
• Glue-less cabinet insulation retention
• Tool-less filter access
SS-GAVPEC
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.
www.goodmanmfg.com
8/21
Supersedes 3/21
Nomenclature
Brand
A Single-Piece Air Handler
A
1
Unit Application
R Multi Position PSC Motor
S Multi Position EEM Motor
V Multi Position Variable-Speed
Motor - Communicating
Cabinet Finish
U Unpainted
P Painted
Expansion Device
E Electronic Expansion Valve
T Expansion Device
V Inverter Tuned Expansion Valve
V
2
P
3
E
4
C
5
Communicating
C = Yes
25
6,7
B
8
1
9
4
10
AA
11,12
Engineering*
Major/Minor Revisions
*Not used for inventory management
Refrigerant Charge
4 = R-410A
Electrical
1 208/230V, 1 Phase, 60 Hz
24 = 2 Tons
25 = 2 Tons
29 = 2 Tons
30 = 2½ Tons
Cabinet Width
B = 17½"
C = 21"
D = 24½"
Nominal Capacity @ 13 SEER
31 = 2½ Tons
36 = 3 Tons
37 = 3½ Tons
42 = 3½ Tons
48 = 4 Tons
49 =3-3½ Tons
59 = 4-5 Tons
60 = 5 Tons
61 = 4-5 Tons
2
HKS
1 2
X 03
3 4
X
5
A AA
6,7
Unit Type
HKS Heat Kit for
Air Handlers
Circuit Breaker
X No circuit breaker
C Circuit Breaker
Heating Capacity @ 240 Volts
03 3.0 kW
05 4.5 kW
15 14.4 kW
19 19.2 kW wth 150F limit
06
08
6.0 kW
8.0 kW
10 9.6 kW
20 19.2 kW with 170F limit
25 25.0 kW
Revisions
Engineering Revisions
A Single Phase 208 V
B Single Phase 240 V
Phase
E Three Phase 240 V
F Three Phase 208/240 V
C Single Phase 208/240 V G Three Phase 460 V
D Three Phase 208 V
H Special case 208 V*
Cabinet Size (MAX)
C C Cabinet
D D Cabinet
X All Cabinet Sizes www.goodmanmfg.com
*Refer S&R Plate
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
3
Product Specifications
AVPEC25
B14A*
AVPEC37
C14A*
AVPEC59
D14A*
Nominal Ratings
Cooling (BTU/h)
CFM (High range)
Blower
Diameter
Width
Coil Drain Connection FPT
Service Valve
Liquid
Suction
Electrical Data
Voltage
Electric Heat Capacity (kW)
Min Circuit Ampacity
24,000
1200/600
10⅝"
6"
¾"
⅜"
¾"
36,000
1700/800
10⅝"
10⅝"
¾"
⅜"
⅞"
48,000
1800/1350
11⅝"
10⅝"
¾"
⅜"
⅞"
208/240
3, 5, 6, 8, 10
4.9/4.9
208/240
5, 6, 8, 10, 15, 19
6.5/6.5
208/240
5, 6, 8, 10, 15, 20
8.6/8.6
Max. Overcurrent Device (Amps)
Minimum VAC
Maximum VAC
Blower Motor
Full Load Amps (FLA)
Horsepower (HP)
Ship Weight (lbs.)
15/15
197
253
3.9
½
128
15/15
197
253
5.2
¾
150
15/15
197
253
6.9
1
160
Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.
AVPEC61
D14A*
60,000
2000/1600
11⅝"
10⅝"
¾"
⅜"
⅞"
208/240
5, 6, 8, 10, 15, 20, 25
8.6/8.6
15/15
197
253
6.9
1
177
2 www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
3
9
Dimensions
8 7 6 5 4 3 2 1
F F
1-1/2" (11.43 cm)
7-1/8" (18.1 cm)
E
D
5/8" (1.59 cm)
K
C
B
J
3-11/16" (9.37 cm)
1-15/16" (4.92 cm)
9-5/32" (23.26 cm)
7-17/32" (19.13 cm)
5-5/32" (13.10 cm)
3-1/16" (7.78 cm)
1-13/32" (3.57 cm)
5/8" (1.59 cm)
1-25/32" (4.52 cm)
21" (55.88 cm)
11-7/32" (28.50 cm)
21/32 (1.67 cm) 1-23/32" (4.13 cm)
1-11/32" (3.33 cm)
E
D
2-11/16" (6.83 cm)
1-11/16" (4.29 cm)
C
A
B
SEE HORIZONTAL
DRAIN PORT DETAIL
10-3/32" (25.88 cm)
SEE VERTICAL
DRAIN PORT DETAIL
G
E
D
INLET TUBE
H
1" (25.4 cm) 19.5" (49.53 cm)
(RIGHT SIDE VIEW)
17/32
1-13/16" (4.60 cm)
A
SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS)
9 8
F
(FRONT VIEW)
Model
AVPEC25B14
AVPEC37C14
AVPEC59D14
AVPEC61D14
7
A
53⁷⁄₁₆
53⁷⁄₁₆
53⁷⁄₁₆
58
1-13/16" (4.60 cm)
CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO
OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAD,
ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT
6 5 4
B
16⅜
19⅞
23⁵⁄₁₆
23⁵⁄₁₆
C
17½
21
24½
24½
D
20
21¹³⁄₁₆
21½
26⅛
E
21½
18⅝
18⁵⁄₁₆
22⅞
F
14⅛
17¹¹⁄₁₆
21³⁄₁₆
21³⁄₁₆
2-31/32" (7.46 cm)
3-25/32" (9.60 cm)
3
G
9⅛
10¹³⁄₁₆
12⅝
12⁵⁄₁₆
3-1/32" (7.70 cm)
VERTICAL DRAIN
PORT DEATIL
1-5/8" (4.13 cm)
H
7⅝
6¹³⁄₁₆
6⅞
25⅛
2
SCALE: NTS
SHEET: 1 OF 1
DWG.
NO.
AVPEC_DIMENSIONS
1
C
B
4 www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
5
Airflow Data
Model
AVPEC25B14A*
AVPEC37C14A*
AVPEC59D14A*
Stage
High
Low
High
Low
High
Low
0.1
700
520
1190
820
1445
880
0.2
690
505
1170
810
1440
875
AVPEC61D14A*
High
Low
1645
1080
1640
1075
Note: During cooling operation outdoor will determine the indoor airflow
795
1430
870
1640
1070
0.3
690
495
1165
785
1415
870
1635
1070
0.4
685
490
1160
Airflow CFM
0.5
680
470
1145
0.6
670
455
1130
765
1405
860
1630
1060
740
1390
845
1625
1055
730
1380
840
1620
1050
0.7
665
445
1120
720
1375
835
1620
1050
0.8
660
435
1105
710
1370
830
1615
1045
0.9
655
425
1100
Cooling/Heat Pump Airflow table
Model
Airflow
Level
High
CFM
AVPEC25B14A*
Low
High
690
495
AVPEC37C14A*
Low
High
1165
795
AVPEC59D14A*
Low
High
1430
870
AVPEC61D14A*
Low
1640
1070
4 www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
5
Heat Kit Data
Model
HKSC10XC - 240 V
AVPEC37C14AC
HKSX05XC - 208 V
HKSX06XC - 208 V
HKSX08XC - 208 V
HKSX10XC - 208 V
HKSC05XC - 208 V
HKSC08XC - 208 V
HKSC10XC - 208 V
HKSC15XA - 208 V
HKSC19CA - 208 V
HKSC15XF - 208 V ^
HKSX05XC - 240 V
HKSX06XC - 240 V
HKSX08XC - 240 V
HKSX10XC - 240 V
AVPEC25B14AC
HKSX03XC - 208 V
HKSX05XC - 208 V
HKSX06XC - 208 V
HKSX08XC - 208 V
HKSX10XC - 208 V
HKSC05XC - 208 V
HKSC08XC - 208 V
HKSC10XC - 208 V
HKSX03XC - 240 V
HKSX05XC - 240 V
HKSX06XC - 240 V
HKSX08XC - 240 V
HKSX10XC - 240 V
HKSC05XC - 240 V
HKSC08XC - 240 V
HKSC05XC - 240 V
HKSC08XC - 240 V
HKSC10XC - 240 V
HKSC15XB - 240 V
HKSC19CB - 240 V
HKSC15XF - 240 V ^
AVPEC59D14AC
HKSX05XC - 208 V
HKSX06XC - 208 V
HKSX08XC - 208 V
HKSX10XC - 208 V
See notes on page 7.
No Breaker
Breaker
No Breaker
Breaker
No Breaker
Breaker
No Breaker
Breaker
No Breaker
50
28
43
50
6.5/6.5
28
34
43
55
30
47
55
21
30
36
47
Circuit 1
MCA¹
4.9/4.9
48
27
41
48
18
27
32
41
48
57
56.5
56.5
6.5
8.6/8.6
30.3
36
38
48
57
32
49.8
49.8
6.5
32
45
52
34.7
17.3
28.9
34.7
0/0
17.3
21.7
28.9
40
20
33.3
40
12.5
20
25
33.3
Amps
0.0/0.0
34.7
17.3
28.9
34.7
10.8
17.3
21.7
28.9
0
0/0
17.3
21.7
33.3
40
40
40
25
33.3
40
20
34.7
34.7
0
20
28.9
34.7
50
30
45
50
15/15
30
35
45
60
30
50
60
25
30
40
50
MOP²
15/15
50
30
45
50
20
30
35
45
15
15/15
35
40
50
60
60
60
40
50
60
35
50
50
15
35
45
60
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
MOP²
---
---
---
---
---
---
---
---
---
45
---
---
---
25
50
---
---
---
---
---
---
25
45
40
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Circuit 2
MCA¹
---
---
---
---
---
---
---
---
---
43
---
---
---
25
50
---
---
---
---
---
---
21.7
43.3
38
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Amps
---
---
---
---
---
---
---
---
---
34.6
---
---
---
---
---
20
40
---
---
---
---
17.3
34.7
30
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Single-Point Kit
MCA¹ MOP²
-----
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
81.5
107
---
---
---
---
71.5
93.2
---
---
---
---
---
---
---
---
---
---
90
110
---
---
---
---
80
100
---
---
---
---
6 www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
7
6 www.goodmanmfg.com
SS-GAVPEC
Heat Kit Data (cont.)
Model
HKSC05XC - 208 V
HKSC08XC - 208 V
HKSC10XC - 208 V
HKSC15XB 3 - 208 V
HKSC20DH - 208 V
HKSC15XF - 208 V ^
HKSX05XC - 240 V
HKSX06XC - 240 V
HKSX08XC - 240 V
HKSX10XC - 240 V
HKSC05XC - 240 V
HKSC08XC - 240 V
HKSC10XC - 240 V
HKSC15XB - 240 V
HKSC20DB - 240 V
HKSC15XF - 240 V ^
AVPEC61D14AC
HKSX05XC - 208 V
HKSX06XC - 208 V
HKSX08XC - 208 V
HKSX10XC - 208 V
HKSC05XC - 208 V
HKSC08XC - 208 V
HKSC10XC - 208 V
HKSC15XB 3 - 208 V
HKSC20DH - 208 V
HKSC25DA - 208 V
HKSC15XF - 208 V ^
HKSC20XF - 208 V ^
HKSX05XC - 240 V
HKSX06XC - 240 V
HKSX08XC - 240 V
HKSX10XC - 240 V
HKSC05XC - 240 V
HKSC08XC - 240 V
HKSC10XC - 240 V
HKSC15XB - 240 V
HKSC20DB - 240 V
HKSC25DB - 240 V
HKSC15XF - 240 V ^
HKSC20XF - 240 V ^
Breaker
No Breaker
Breaker
No Breaker
Breaker
No Breaker
Breaker
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
3 Notation is correct as XB because technically the 240V heater kit application can be used here without any issues.
^ Three-phase Heater Kits (Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for Heater Kits)
--- indicates Not Required
Note: The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model.
17.3
28.9
34.7
34.7
17.3
21.7
28.9
34.7
40
40
0
0/0
40
20
33.3
40
Amps
17.3
0
20
25
33.3
28.9
34.7
34.7
34.7
0
0
40
60
20
33.3
40
40
20
25
33.3
40
34.7
52
0
0
30
45
52
52
30
36
45
52
59
34
50.3
59
58.6
58.6
8.6
8.6/8.6
Circuit 1
MCA¹
30.3
8.6
34
40
50.3
45
52
52
52
58.6
83.6
8.6
8.6
34
50.3
59
58.6
34
40
50.3
59
52
73.6
8.6
8.6
35
45
60
60
35
40
45
60
60
60
15
15/15
60
35
60
60
MOP²
35
15
35
40
60
45
60
60
60
60
90
15
15
35
60
60
60
35
40
60
60
60
80
15
15
---
---
---
17.3
---
---
---
---
20
40
34.6
---
---
---
---
---
Amps
---
---
---
30
---
---
---
17.3
34.7
40.0
40
34.6
43.3
---
---
---
20
---
---
---
---
34.7
35
30
38
Heating kW Correction Factor
Supply Voltage 240 230 220 210 208
Correction Factor 1.00
0.92 0.84 0.77 0.75
Multiply the 240-volt heating capacity by correction factors.
---
---
---
21.7
---
---
---
---
25
50
43
---
---
---
---
---
Circuit 2
MCA¹
---
38
---
---
---
---
---
21.7
43.3
50
50
43
54
---
25
---
---
---
---
---
---
43.3
43.3
38
47
---
25
---
---
---
---
---
---
25
50
45
---
---
---
---
---
MOP²
---
40
---
---
---
25
45
---
---
50
50
45
60
---
25
---
---
---
---
---
---
45
45
40
50
---
---
---
73.6
---
---
---
---
83.6
109
---
---
---
---
---
---
Single-Point Kit
MCA¹ MOP²
-----
---
---
---
---
---
---
74
95.3
---
---
---
---
---
---
80
100
---
80
---
---
---
---
---
---
90
110
---
---
---
---
---
---
109
134
---
---
---
---
---
83.6
---
---
---
---
95.3
117
---
---
110
150
---
---
---
90
---
---
---
---
---
---
100
125
---
---
SS-GAVPEC www.goodmanmfg.com
7
8
Wiring Diagram
(SEE NOTE 4)
GROUND LUG
9 8
TO
HEATER KIT
7 6 5 4
208/230
VAC
3
RD BK
2 1
PL1
PL2
(SEE NOTE 7)
ECM MOTOR
WH
BR
INSTALLING
AUX ALARM
(ALARM)
(SEE NOTE 8) ~~
J19
~~
BL
HEATER KIT
OUTPUT
RD
BK
BK
RD
BK
RD
COM
BL
208
VAC
24VAC
RD
230
VAC
BK
RD
TR2
(SEE NOTE 1)
COM
208
VAC
PU
24VAC
YL
230
VAC
TR1
(SEE NOTE 1)
FAN
MOTOR
1 2 3 4 5 6 7 8 9 10 11 12
PL3
PL4
RD
BK
THERMOSTAT OUTDOOR UNIT
RD
GR
AUX ALARM
(ALARM)
J19
W BL RD
FH1 F1U FH2
+
VR1
~
C1
D1
~
_
C2
C62 C4
Y2
DH/
Y W
G
C R
J1
R13
C R
J2
L5
R25
GYBK
FH3
F2U
FH4
J13
L1
K3
K1 PB3
K2
PB2
PB1
U6
J20
EEV
GY
J6
J6
BK
YL
RD
OR
J7
J7
THERMISTOR
(HEAT EXCHANGER 1,2)
INTEGRATION
TYPE
U7
U1
J8 J9 J16 J17
U9
B11
J18
J18
INDOOR UNIT
PCB
PRESSURE
SENSOR
BK GY BL
NOTES:
1. PLACE RED WIRES ON 208 V TERMINAL OF
2-TRANSFORMER (TR1/TR2) FOR 208 VAC
OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT
PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS
SUPPLIED WITH THIS UNIT MUST
BE REPLACED, IT MUST BE REPLACED
WITH WIRING MATERIAL HAVING A
TEMPERATURE RATING OF AT LEAST 105°C.
USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED
AND CONFORM TO N.E.C ANDLOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, MOST
RECENT TO LEAST RECENT, DEPRESS
FAULT RECALL BUTTON FOR MORE THAN 2
SECONDS WHILE IN STANDBY (NO THERMOSTAT
INPUTS)
6. YELLOW STATUS LED PROVIDES NETWORK
STATUS.GREEN RX LED INDICATES NETWORK
TRAFFIC
7. DISCARD CONNECTOR PL1 WHEN
INSTALLING OPTIONAL HEAT KIT.
8. REMOVE SHORTING PLATE FROM THE AUX
SWITCH TERMINAL WHEN INSTALLING AUX
ALARM SWITCH.
9. USE N.E.C CLASS 2 WIRE.
INTEGRATED CONTROL:
LOW VOLTAGE
LOW VOLTAGE FIELD
HIGH VOLTAGE
HIGH VOLTAGE FIELD
JUNCTION
TERMINAL
INTERNAL TO
RESISTOR
OVERCURRENT
PROT. DEVICE
PLUG CONNECTION
EQUIPMENT GND
FIELD GROUND
DISCONNECT
COLOR CODES:
BL - BLUE
RD - RED
YL - YELLOW
OR - ORANGE
BK - BLACK
GY - GREY
BR - BROWN
GR - GREEN
PU - PURPLE
WH - WHITE
L1
GRND
L2
INDOOR
AIR
CIRCULATOR
BLWR
GRND
L1 208/230 VAC L2
R
FUSE 3 A
C
G
W
TO
MICRO
TH2
EH1
EH2
AUX IN
AUX OUT
Y
DEHUM
24 VAC
HEAT 1 COIL/R1
HEAT 2 COIL/ R2
CONDENSATE SWITCH
+VDC (1)
RX (2)
TX (3)
GRND (4)
TR2
COM
INTEGRATED CONTROL MODULE
INDOOR
AIR
CIRCULATOR
BLWR
GRND
COMPONENT CODES:
PL1, PL2
TL
TR
F1U, F2U
PL3, PL4
POWER/HEATER
CONNECTOR
THERMAL LIMIT
TRANSFORMER
FUSE LINK
TRANSFORMER
CONNECTOR
0140A00723-C
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
⚠
Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡ www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
9
Downflow Kits
DFK-B
AVPEC25B14**
DFK-C
AVPEC37C14**
DFK-D
AVPEC59D14**
AVPEC61D14**
** (DFK-B, DFK-C, DFK-D) kits need to be broken up by cabinet size
Filters
Chassis
B
C
D
Part #
ALFH16201E
ALFH1912201E
ALFH20231E
Size
16.0" x 20.0"
19.5” x 20.0”
23.0” x 20.0”
Single Point Kit **
SPW-01
Model HKR-15C
X
HKR-20C
X
HKR-21C
X
** Must be installed along with any of the above compatible heat kits. This kit will fit any AVPEC air handler as long as a compatible heat kit is installed in the unit.
Accessories
Drain Port Plug
Kit Number
DPK1
Description
Side Drain Port Plug
Application
All Models
8 www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
9
Notes
10
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2021 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA. www.goodmanmfg.com
SS-GAVPEC SS-GAVPEC www.goodmanmfg.com
PB