DE23I4-XX/1
GENERATOR
INSTALLATION AND
OPERATORS MANUAL
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINCO generator has the same serial number as yours.
If you should ever need to contact us on this unit, it will help us to respond to your needs faster.
MODEL __________________________________________________
SERIAL NUMBER _________________________________________
PURCHASE DATE _________________________________________
DEALER NAME ___________________________________________
DEALER PHONE # ________________________________________ www.wincogen.com
TABLE OF CONTENTS
SAVE THESE INSTRUCTIONS
SAFETY INFORMATION
CALIFORNIA PROPOSITION 65
SAFETY DEFINITIONS
TESTING POLICY 3
SPECIFICATIONS 4
DE23I4 4
INTRODUCTION 5
PRODUCT DESCRIPTION
PREPARING THE UNIT
START-UP CHECK LIST
6
UNPACKING
LIFTING THE GENERATOR SET
INSTALLATION 7
GENERAL INFORMATION
ENGINE GENERATOR SET MOUNTING
VENTILATION REQUIREMENTS
EXHAUST INSTALLATION
FUEL INSTALLATION
INSTALLING THE FUEL LINE
ELECTRICAL CONNECTIONS
GENERATOR CIRCUIT BREAKER
GROUNDING
TRANSFER SWITCH
DC WIRING
INSTALLING THE BATTERY
SERVICING BATTERIES
BATTERY CHARGER
& BLOCK HEATER
12 STARTING PROCEDURE
LUBRICATION
COOLANT
PRE-START CHECK LIST
CONTROL LAYOUT
MANUAL MODE
AUTO MODE
CONTROL POWER
13
2
3
OPERATING CONDITIONS
NORMAL OPERATION
HARSH ENVIRONMENTS OPERATIONS
COLD WEATHER OPERATIONS
15
MAINTENANCE 16
CHANGING THE OIL
CHANGING OIL FILTER
CHANGING COOLANT
REFILLING COOLANT
CHANGING AIR FILTER
CHECKING WATER IN FUEL FILTER
CLEANING RADIATOR
CHANGING THE FUEL FILTER
STORAGE
MAINTENANCE SCHEDULE
TROUBLE SHOOTING TABLES
WIRING SIZE TABLE
ECM DIAGRAM
DSE7310 WIRING DIAGRAM
WIRING DIAGRAMS
19
20
21
22
23
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the generator. Read and understand all instructions in the manual before starting and operating the generator.
USING THIS MANUAL
Congratulations on your choice of a WINCO generator.
You have selected a high-quality, precision-engineered generator designed and tested to give you years of satisfactory service.
To get the best performance from your new generator, it is important that you carefully read and follow the operating instructions in this manual.
Should you experience a problem please follow the
“Troubleshooting Tables” near the end of this manual.
The warranty listed in the manual describes what you can expect from WINCO should you need service assistance in the future.
OPM-147/B 2
SAFETY INFORMATION
SAVE THESE INSTRUCTIONS
This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potentially deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
CALIFORNIA PROPOSITION 65
WARNING: This product contains crude oil, gasoline, diesel fuel and other petroleum products, Antifreeze to which can expose you to chemicals including toluene and benzene,
Ethylene glycol (ingested) which are known to the State of California to cause cancer, birth defects or other reproductive harm and developmental issues.
For more information go to www.P65Warning.ca.gov.
SAFETY DEFINITIONS
DANGER: indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
This signal word is to be limited to the most extreme situations.
WARNING: indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION: indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
1. ELECTRICAL SHOCK -
The output voltage present in this equipment can cause fatal electric shock. This equipment must be operated by a responsible person.
A. Do not allow anyone to operate the generator
without instruction.
B. Guard against electric shock.
C. Avoid contact with live terminals or receptacles.
D. Use extreme care if operating this unit in rain or
snow.
E. Use only three-pronged grounded receptacles and cords.
F. Be sure the unit is properly grounded, installation
must meet the national electrical code.
F. Follow local codes for closeness to combustible
material.
3. DEADLY EXHAUST GAS -
Exhaust fumes from any gasoline engine contain carbon monoxide, an invisible, odorless and deadly gas that must be mixed with fresh air.
A. Operate only in well ventilated areas.
B. Never operate indoors including attached garages
C. Never operate the unit in such a way as to allow
exhaust gases to seep back into closed rooms (i.e.
through windows, walls, and/or floors).
4. NOISE HAZARD -
Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
A. Use hearing protection when working around this
equipment for long periods of time.
B. Keep your neighbors in mind when using this
equipment.
5. CLEANLINESS -
Keep the generator and surrounding area clean.
A. Remove all grease, ice, snow or materials that create
slippery conditions around the unit.
B. Remove any rags or other materials that could create
a potential fire hazard.
C. Carefully clean up any gas or oil spills before starting
the
D. Do Not use the generator area as a storage closet.
6. SERVICING EQUIPMENT -
All service, including the installation or replacement of service parts, should be performed only by a qualified technician.
A. Use only factory approved repair parts.
B. Do not work on this equipment when fatigued.
C. Never remove the protective guards, covers, or
receptacle panels while the engine is running.
D. Use extreme caution when working on electrical
components. High output voltage from this
equipment can cause serious injury or death.
E. Always avoid hot mufflers, exhaust manifolds, and
engine parts. They can cause severe burns instantly.
F. The use of the engine-generator set must comply
with all national, state, and local codes.
2. FIRE HAZARD -
Gasoline and other fuels present a hazard of possible explosion and/or fire.
A. Do not refuel when the engine is running or hot.
B. Keep fuel containers out of reach of children.
C. Do not smoke or use open flame near the generator
set or fuel tank.
D. Keep a fire extinguisher nearby and know its proper
use. Fire extinguishers rated ABC by NFPA are
appropriate.
E. Store fuel only in an approved container, and only in
a well ventilated area.
TESTING POLICY
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked.
3
Rated output of generator is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of applicable engines.
OPM-147/B
SPECIFICATIONS
DE23I4
MODEL
Standby Prime
DE23I4-03 DE23I4-04 DE23I4-17 DE23I4-18 DE23I4-03 DE23I4-04 DE23I4-17 DE23I4-18
GENERATOR
Watts
Volts
22,000
120/240
Phase
PF
Single
1.0
Amps
Hertz
91
60
23,000 23,000
120/208 120/240
Three
0.8
Three
0.8
79
60
69
60
23,000
277/480
Three
0.8
34
60
19,800
120/240
Single
1.0
82
60
20,700
120/208
Three
0.8
71
60
20,700
120/240
Three
0.8
62
60
20,700
277/480
Three
0.8
31
60
GENERATOR RESISTANCE
(all value at 22 ° C)
Model
Winding Group
Rotor
Stator
Exciter Rotor
Exciter Stator
Stamford S1L2-J1
711
0.925 Ω
0.203 Ω per phase series star connected
0.207 Ω per phase
16.44 Ω
ENGINE
Model
Starting System
Fuel Consumption (full load)
Isuzu 4LE2T
12 Volt
2.1 Gal/hr
ASTM D-975 - 2D* Fuel
Oil Type
Oil Capacity
Cooling System
See Lubrication section in this manual
* See engine manual for additional fuel types and specifications
11 Quarts
50/50 mix
OPM-147/B 4
INTRODUCTION
PRODUCT DESCRIPTION
The engine-generator set consists of a multi-cylinder, liquidcooled engine nominally operating at 1800 RPM. This generator set meets current EPA regulations for standby or prime power use. The generator frequency regulation is maintained by the engine electronic governor to within
+/- 0.5 Hertz. The generator is connected to the engine flywheel via flexible drive disks. The generator set is skid mounted with isolation mounts between the engine and base.
NOTICE:
A Customer supplied 12 Volt battery is required to complete the installation. Battery requirements are listed later under the battery installation section.
The generator ships with an advanced DSE7310 digital controller. The DSE7310 will electronically display useful engine and generator performance information. The controller starts and stops the generator and monitors critical operating parameters and will shut the generator down to protect the engine from damage.
GENERATOR SET:
Every WINCO generator set has its own unique identity data plate. This data plate identifies the complete unit model number, the system serial number, and has links to the individual components that form the generator set in our factory records. Several of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts. Be sure to have the main WINCO unit data plate information recorded inside the front cover of this manual for future reference and for identification whenever requesting field or factory assistance.
Primary fields needed for assistance are complete model number and serial number.
ENGINE:
This manual covers specific operation of the combined engine generator set. The basic engine information provided in this manual is not suitable for all operating conditions. Refer to the engine operators manual for more detailed operation and maintenance information.
CAUTION: EQUIPMENT DAMAGE:
Be sure to check the engine oil level frequently as specified in the engine manual.
The engine manufacturer has established an excellent worldwide engine service organization; engine service is available from a nearby authorized dealer or distributor. Go to the WINCO website for a list of engine dealers (www.
wincogen.com) or contact the WINCO Service Department.
The rated power of each engine-generator is limited by the temperature, altitude, and all other ambient conditions specified by the engine manufacturer.
Derates
Above Sea Level
6,561 FT
9,842 FT
Coolant Temperature
>104°F
10%
20%
3% per 10°F
Units should not be operated in ambient temperature greater than 125° Fahrenheit.
GENERATOR:
The nameplate includes a standby and prime/continuous rating. The standby rating is the maximum amount of power the generator set can produce. For prime power applications the load should be equal to or less than the prime power rating and the load is assumed to be variable.
It is acceptable to occasionally reach the standby rating during prime operation to start motors or other temporary surges.
WINCO generator sets use a brushless, AVR (Auto-Voltage
Regulator) controlled broad-range generator ends. The generator converts rotational mechanical energy into electrical energy. These WINCO units are equipped with generators manufactured by Cummins Generator
Technologies. Each generator ‘end’ has its own data tag. A unique serial number is on the data plate and the data label is affixed to the main frame on the generator on the left side.
5 OPM-147/B
PREPARING THE UNIT
START-UP CHECK LIST
A Start-Up Completion & Warranty Validation Form was sent along with this manual. This must be completed and returned to WINCO Inc. within 180 days of the factory invoice date. If this form is not returned, the Warranty may be voided.
UNPACKING
of the fuel can cause a shift in the balance of the fuel tank, making for a DANGEROUS, unbalanced lifting load. If the generator was shipped on the fuel tank, use the lifting points located on the fuel tank to move the entire generator set into place. DO NOT PLACE FUEL IN THE TANK PRIOR
TO LIFTING.
This generator set is equipped with integrated fork pockets on the fuel tank to allow the generator to be lifted from any side.
1. As you receive your unit, it is critical to check it for any
damage. If any damage is noted, it is always easiest to
refuse the shipment and let WINCO take care of the
freight claim. If you sign for the unit, the transfer of the
ownership requires that you file the freight claim
2. Before proceeding with the preparations of your new
generator for operation, take a couple of minutes to
ensure the unit you have received is the correct model
and review the specification pages in this manual to
ensure that this unit meets your job requirements.
CAUTION: EQUIPMENT DAMAGE:
These units are shipped with oil and a 50/50 mix of coolant.
Be sure to check all fluid levels before operating. See engine manufacturer’s instruction manual for recommended oil requirements before initial starting.
Once generator set is on-site:
1. Carefully remove the crate.
2. After inspecting the engine-generator for external,
physical damage, locate and check the following items
packed with the unit:
a. Installation and Operator’s Manual.
b. Engine manufacturer’s instruction manual.
c. Start-up and warranty validation form.
d. Battery hold-down brackets & hardware.
e. Unit components or accessory items shipped loose
for on-site installation.
f. Optional accessories.
3. Remove main frame hold-down bolts.
4. Unit can now be lifted from shipping rails.
Always use forklifts of a proper rating and with long enough forks to move the generator. As the distance from the forklift mast increases the lifting capacity for the forklift decreases. When lifting from the side the forks should extend the entire width of the unit through the opposite side frame rail.
LIFTING THE GENERATOR SET
NOTICE: PERSONAL INJURY:
To prevent injury to persons or equipment, observe the following guidelines when lifting the generator:
CAUTION:
Do not attempt to lift the generator set by the means of the lifting eyes on the engine or generator end. These lifting points are only for the use during the manufacturing process and are designed for lifting of the individual generator set components and not the complete unit.
WARNING:
NEVER attempt to lift the fuel tank filled with fuel. Sloshing
13.6” 52.4” 1.0”
CAUTION: EQUIPMENT DAMAGE
It is possible to lift the generator from the radiator side. It requires especially long forks and care should be taken to ensure that no contact is made with the radiator. Pushing the radiator will cause damage that is not covered under warranty.
OPM-147/B 6
INSTALLATION
The max continuous coolant temperature for this unit is
203°F. This unit should be installed in a well ventilated area, ensuring the exhaust air cannot be recirculated back into the engine.
CAUTION:
This unit will get hot while it is running and for some time afterward.
WARNING: PERSONAL INJURY:
Before proceeding with the installation, be sure the engine control is in the “stop” position and the emergency stop depressed. Also, be sure the generator MLCB (main line circuit breaker) is in the “off” position and the unit starting battery is disconnected.
GENERAL INFORMATION
This series of engine-generator sets are designed and built as open power units, meaning no weather protection has been provided. These units must be installed inside of an enclosure that will provide proper protection from the elements.
The WINCO installation manual OPM-112 contains additional information on indoor installations and is available electronically through our website or by requesting a copy from the factory.
Before beginning the installation process, recheck the voltage, phase, and amperage rating of the generator set. Be certain it can handle the intended load and are compatible with the intended loads. Plans for installation should be prepared with proper attention to mechanical and electrical engineering detail to assure a satisfactory system installation. The installation must comply with all national, state, and local codes.
The information in this manual is offered only as a guide to finalizing your installation plans and does not substitute for sound engineering judgment for the specific application.
VENTILATION REQUIREMENTS
WARNING: EQUIPMENT DAMAGE:
It is the installer’s responsibility to ensure that there is sufficient cooling air available to prevent the engine and generator from over heating. Damage caused by overheating is not covered by warranty.
Providing proper air movement during your installation planning is essential. You will need to provide a fresh air inlet as well as a hot air outlet (to the outside of protection housing) for proper engine performance. These enginegenerator sets are equipped with unit mount radiators and the engine is equipped with a pusher type fan. The hot air from the face of the radiator must be ducted out of the enclosure to ensure proper cooling. Failing to do so will allow the hot air to recirculate around the radiator causing the engine to overheat, resulting in an engine shutdown and damage. If louvers are used in front of the hot air duct to protect the unit from outside weather, the louvers should be 1½ times as large as the area of the radiator face to prevent back pressure.
This generator is equipped with a duct flange designed to make installation simpler. The flange should not be placed closer than 0.75 in. to the edge of the structure or other solid surfaces. The radiator is mounted on rubber vibration isolators that allow it to move. Placing the duct flange too close to a wall can result in contact that will damage the radiator resulting in costly repairs.
Foam or other seals can be used to form a tight lip forcing all of the air from the engine fan out of the enclosure.
In addition to a hot air discharge, you must plan a fresh air intake opposite the radiator discharge. Their fresh air inlets should be 1½ to 2 times larger than the radiator face. The extra air inlet area is required to minimize restriction and to provide combustion air for the engine. Do not block fresh air intakes with other equipment as this will result in insufficient air flow to the engine for cooling. Installing them opposite the hot air discharge will allow a sweeping flow of cooling air across the engine, preventing hot spots.
EXHAUST
THIMBLE
ENGINE GENERATOR SET MOUNTING
The unit’s main frame must be bolted securely to a solid base. The engine-generator is mounted on channels which are attached with special shock mounts to the main frame.
This allows the engine-generator free movement without affecting the base or surrounding equipment.
WARNING: EQUIPMENT DAMAGE:
Never mount these engine-generator sets to a wooden base/structure. Over time, the wood will deteriorate and the unit mountings will come loose. These units must be mounted to a steel or concrete base.
RADIATOR
DISCHARGE
FOAM SEAL
AIR INLET
DUCT
7 OPM-147/B
EXHAUST INSTALLATION
WARNING: PERSONAL INJURY
Improper exhaust installation will allow dangerous gases to seep into enclosed spaces causing a hazard to your health and/or death.
All exhaust must be piped out of the enclosure. When selecting a location to exhaust fumes make sure that the potential for contact with people is controlled. Exhaust can enter buildings through windows, ventilation systems and other openings if proper precautions are not followed.
INSTALLING THE FUEL LINE
Engine-generator sets are properly adjusted before they leave the factory. Connecting a fuel supply with adequate supply volume is critical to reliable operation. Diesel units with optional base mounted fuel tanks are pre-plumbed to the mechanical fuel pump on the engine.
Open skid mounted diesel units are often supplied with capped inlet and return lines. The use of a suitable customer supplied flexible fuel lines is essential between the engine and fuel supply to provide a vibration break between your fuel supply and the engine.
The exhaust must be isolated from the vibration of the engine. If the exhaust is connected in a rigid system it will result in damage to the engine. The generator comes equipped with an engine mounted flex pipe to aid your installation. Ensure proper alignment with the generator.
The flex can be eliminated if it is pushed to one side to make a connection.
The most direct path possible should be used to get to the outside of the enclosure. Each bend restricts the pipe and increases back pressure. It may be necessary to increase the exhaust pipe diameter in some applications.
WARNING: FIRE DANGER:
Connecting rigid fuel line (i.e. steel or copper line) directly to the inlet fuel filter or fuel pump may cause the fuel line to crack during operation creating a serious fire hazard.
The exhaust pipe is very hot. When passing through the structure it is critical that a thimble or other appropriate technique is used to dissipate the heat and prevent the structure from catching on fire.
Water in the exhaust pipe and especially the Diesel
Oxidation Catalyst (DOC) will cause damage to the engine.
It is preferable to exhaust out the side of the enclosures.
Slope the pipe slightly downward away from the engine to cause any water in the exhaust to run away from the engine. Do not exhaust near intake. Once outside the enclosure a rain cap or other technique must be used to keep water out of the exhaust. In mobile applications make sure the rain flap faces to the rear of the vehicle so that it is not blown open during transportation.
In many applications the DOC works as the muffler. If it is desired to decrease engine noise further adding a muffler to the exhaust system is possible. The muffler cannot increase back pressure to more than 0.725 psi.
NOTE: The symbol always indicates ground where shown. All wiring must be completed in accordance with the National Electric Code as well as any state and local codes.
FUEL INSTALLATION
The fuel supply should be as close to the engine as possible. This will reduce the installation cost of fuel runs and minimize line losses. The diesel fuel supply should be no more than 3 feet below the fuel inlet pump. If your fuel supply is lower than 3 feet, you may have to install an additional lift pump to bring the fuel up to the mechanical fuel pump on the engine.
Fuel Inlet
Connection
Fuel Return
Line Connection
ELECTRICAL CONNECTIONS
NOTICE: CLASS 1 WIRING METHODS ARE TO BE USED FOR
ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A
CLASS 2 CIRCUIT
You must pay particular attention to wire size requirement for the amperage of service you are dealing with. The table below provides you guidance on wire sizing based on both wire type and amperage. Wire amperages have been derated for 40° C ambient temperatures operation.
GENERATOR CIRCUIT BREAKER
This unit DOES NOT come with a circuit breaker. The circuit breaker will provide overload protection for the generator.
The information in this manual is offered to assist you in providing the proper fuel for your engine. However, this information is only provided to inform you of the engine’s requirements and assist in making you aware of the decisions you must make. In no case should the instructions or information provided be interpreted to conflict with any local, state, or national codes. If in doubt, always consult your local fire marshal or fuel supplier.
OPM-147/B 8
The following table gives you the recommended circuit breaker size specifications. See actual breaker for wire capabilities and torque specifications and restrictions.
Watts
22,000
Voltage
120/240
Phase
1
CB AMP
90-100
23,000
23,000
23,000
120/208
120/240
277/480
3
3
3
80-100
70-80
35-45
The wire must be properly sized between the generator and the load. Use the table 310-16 of the National Electrical
Code ANSI/NFPA 70. to properly size the wire to meet or exceed the amperage rating of the circuit breaker installed.
GROUNDING
Proper grounding of your generator is application dependent. Carefully evaluate your planned use of your generator to understand which grounding you require.
If you are not sure what to do, contact a competent professional to assist you. The NFPA 70 250:34-35 are good technical references.
VEHICLE-MOUNTED GENERATOR
Your WINCO generator ships with a bonded neutral.
When mounted to a vehicle to safely distribute power it is necessary that the generator frame is bonded to the vehicle frame. The generator should only supply equipment that is cord and plug connected through customer installed receptacles mounted on the generator or the vehicle.
PERMANENTLY INSTALLED GENERATORS
This WINCO portable generator ships with a bonded neutral. NFPA 70 refers to this as a “separately derived system.” When connecting it to a building a transfer switch specifically designed for GFCI and bonded neutral generators is required or the ground or the neutral to ground bond must be broken and the panel relabeled.
Lug size 10mm
U
CUSTOMER CONNECTIONS
Line 1
V
W
N
Line 2
Line 3
Neutral
Ground
The DSE 7310 controller uses current transformers (CT) to monitor the amount of load on each leg of the generator. If the wires are routed through the CT the wrong direction it will result in a negative current readings on the controllers.
This can be corrected by swapping the wires on the CT terminals in the generator end. Zip tie the wires to the CT walls after installation in order to prevent wire movement.
WARNING: PERSONAL DANGER:
These units are shipped with a NEUTRAL TO GROUND
BOND INSTALLED. If your system already has a neutral to ground bond, then you must run a separate ground lead to that location and UNBOND THE JUMPER IN THE
CONNECTION PANEL. For additional information, refer to the current National Electrical Code on grounding.
WARNING: EQUIPMENT DAMAGE:
When installing a three phase 240 Volt system, be sure you know which lead is high voltage ‘wild’ leg (208 Volt to neutral). The generator normally carries the high voltage on the G2 lead.
TRANSFER SWITCH
NOTICE:
For full service switching of the entire load, the ATS must be
‘SE’ (Service Entrance) rated or must have a properly rated fusible disconnect installed before the ATS to protect the contacts.
WARNING: FIRE HAZARD:
All wiring must be done by a licensed electrician, and must conform to the National Electrical Code and comply with all the local codes and regulations. Check with the local authorities before proceeding.
INSTALLATION NOTES:
Because of many different types of service, feeder and distribution equipment, no specific wiring instructions can be provided. It is recommended that only copper wire be used. In all cases it is essential that while the load is connected to the generator, there can be absolutely no feedback from the generator to the power line or the power line to the generator. When properly installed, the normal ATS Control and safety system will eliminate all paths and feedback.
To wire the automatic transfer switch into existing wiring, first determine which circuits will be on the emergency load circuit. If the entire load is transferred, the transfer switch can be wired directly after the meter and the service entrance, providing the service entrance ampere rating is within the transfer switch’s rated capability.
If only specific circuits are to be powered under emergency power failure conditions, an additional distribution panel designated “emergency distribution panel” must be installed.
All selected emergency circuits are removed from main distribution panels and installed in the emergency
9 OPM-147/B
distribution panel. The ATS is then installed between the main panel and the emergency distribution panel.
Suggested circuits: freezer, refrigerator, furnace, emergency lights, sump pump, emergency outlet circuits, etc. Total running load must not exceed generator rating.
DC WIRING
All communication and DC wiring should be run in separate conduit from AC wiring.
To install the wires, reference the following picture. Use a small flat head screwdriver to push the release spring inside the square hole (A). While the release is being pushed, insert the wire into the larger circular hole (B). Remove the screwdriver to secure the wire into place.
E STOPS
In some applications additional emergency stops may be desired or necessary. The controller has terminals designed allowing the addition of multiple remote emergency stops.
E-stops must be normally closed to work properly in this system. The e-stop circuit supplies power to fuel solenoid and the starter circuit. Opening any switch in the series prevents the engine from cranking or from receiving fuel to run.
Battery Charge Fail Emergency Stop Emergency Stop Remote Start + Remote Start - Ground Ground Battery + Battery -
A
B
REMOTE START
The DSE7310 is able to start the generator when it receives a remote signal from any dry contact. This makes the system compatible with a wide range of control mechanisms including two-wire start automatic transfer switches. When the contact closes the controller will automatically start.
When the contact is opened the generator will go through a cool-down cycle and turn off. Connect the remote start leads to the Remote Start + and Remote Start - terminal blocks in the door behind the DSE 7310 controller.
Depending on the distance, 14 to 16 gauge stranded wire should be used. It is suggested that these wires be labeled
S1 and S23.
Note: Any relay closure can be used to start and stop this generator. As long as the contact stays closed the engine generator set will continue to run. Once the relay is opened the unit will shut down and remain in the standby mode until the remote start relay is closed again.
E-Stops
To wire additional emergency stop switches first remove the orange jumper between the two Emergency Stop terminal blocks. Failure to remove the jumper will prevent the remote switches from working properly. Add wires between the terminal block to the new switch(s). The switches must be wired in series for proper function. Test each e-stop after wiring to ensure they function properly.
SERIAL COMMUNICATION
DSE provides a series of remote accessories that can help provide useful information to operators. These accessories communicate over the DSE Net. Terminal blocks are wired to the distribution panel to aid in installation. Follow the instructions included with each accessory.
The generator controller can communicate with a variety of controls and monitoring systems, including RS232 and
RS485. The ports are wired onto the back of the DSE7310.
In order to finalize communication the program will need to be adjusted using the free DSE configuration software to enable the commutation. Contact Winco service for a list of register values.
INSTALLING THE BATTERY
CAUTION:
In the following battery installation procedure, check to be sure the engine control is in the “stop” position. This should be your last step before initial start-up.
Battery Charge Fail Emergency Stop Emergency Stop Remote S Ground Ground Battery + Battery -
Two-Wire Start Hook-Ups
A customer supplied 12 Volt battery is required to complete the installation. Installation of the highest CCA rated battery, within the correct BCI group, will increase cold weather starting performance.
BATTERY REQUIREMENTS
Model Voltage BCI Group
DE23F4 12 24
Min. CCA
Rating
650
OPM-147/B 10
WARNING: EQUIPMENT DAMAGE:
This unit is12 Volt and is negative ground. Permanent damage will occur if they are connected to a 24 Volt system or a positive ground system. If you are using the truck batteries to start these units, you may have to disable the charging system to keep it from interfering with the vehicle charging system.
DANGER: EXPLOSIVE FIRE RISK:
1. Never smoke when near batteries.
2. Do not cause a flame or spark in the battery area.
3. Always discharge static electricity from your body
before touching batteries by first touching a ground surface.
Installation and servicing of batteries must only be preformed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
When installing or replacing batteries, use the proper group/size starting battery. The battery should be a maintenance-free lead acid design. Deep cycle batteries will not work for this application.
SERVICING BATTERIES
Batteries used on these units may, over time, lose water.
This is especially true if you are using a trickle charger to maintain your battery. When refilling the battery with water, use only distilled water. Tap water will shorten the service life of the battery.
CAUTION: PERSONAL DANGER:
NEVER dispose a battery in a fire. The battery is capable of exploding.
DO NOT open or mutilate the battery. Released electrolyte is known to be harmful to the skin and eyes and to be very toxic.
These engine-generator sets are all NEGATIVE ground. Be very careful not to connect the battery in reverse polarity, as this may short circuit the battery charging system on the engine.
Never fill the battery above the fill line. Over filling above the upper level line may cause the electrolyte to overflow, resulting in corrosion to the engine or nearby parts.
Immediately wash off any spilled electrolyte following the procedure above.
NOTE: Always make sure that a new battery is fully charged before installing it on a generator set. Failure to do so can cause damage to the engine control module in the generator set.
All connections must be clean and tight. Check the electrolyte in the battery periodically to be sure it is above the plates. Never allow the battery to remain in a discharged condition.
CAUTION:
A battery presents a risk of electrical shock and high short circuit current. The following precautions must be observed when working with batteries:
1. Remove watches, rings, and other metal objects.
2. Use tools with insulated handles.
3. Check both the battery cable ends and the battery
posts to be sure they are free of corrosion.
4. Always connect the battery positive cable first and then
connect the battery negative cable. When removing
the battery cables from the battery, reverse the
procedure, disconnect the negative first and then the cable.
5. Be sure all connections are tight and coat the terminals
and cable ends with dialectic grease.
BATTERY CHARGER
& BLOCK HEATER
BATTERY CHARGER
A three-stage, on-board marine battery charger is provided standard on this unit. The charger is a 1.5 amp dual use maintainer and charger designed to keep your batteries fully charged by maintaining them automatically.
Make sure all DC battery connections are tight and clean.
Follow battery manufacturer’s recommendations.
WARNING:
The electrolyte is diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following precautions must always be taken.
This charger is mounted under the customer connection on the control side of the generator. The charger will need to be plugged to a customer’s power source, using a customer supplied heavy duty, UL approved extension cord. The receptacle is to be powered by a GFCI circuit and installed in accordance to the US National Electric Code. It is suggested that this circuit be fused to 20 Amps.
1. Always wear full eye protection and protective
clothing.
2. Where electrolyte contacts skin, wash off immediately
with water.
3. If electrolyte contacts the eyes, flush thoroughly and
immediately with water and seek immediate medical
attention
4. Spilled electrolyte is to be washed down with an acid
neutralizing agent. A common practice is to use a
solution of one pound of bicarbonate of soda (baking
soda) to one gallon of water. The bicarbonate of soda
solution is to be added until the evidence of reaction
(foaming) has ceased. The resulting liquid is to be
flushed with water and the area dried.
Low/Charge Mode:
The illuminated blue power LED and red low/charging LED.
This indicates the Low/Charge mode is in process. When completed the RED Low/Charge LED will turn off.
11
Auto Maintain Mode:
The illuminated Green auto maintain LED. This indicates your 12volt battery is fully charged. During short or long term storage periods, Auto Maintain (Energy Saver) mode will monitor and auto maintain a battery only when needed to maintain a full state of charge. This feature significantly reduces AC Power consumption, lowers operating costs and maximizes reserve power performance.
OPM-147/B
BLOCK HEATER
The block heater on this unit is a 1500 watt heater and is plugged directly to a receptacle or extension cord. The block heater is thermostatically controlled when plugged in will maintain the engine coolant temperature between 100 and 120 degrees F.
STARTING PROCEDURE
CAUTION:
For the first 10 seconds of operation all of the oil, coolant, and electrical shutdowns are disabled. This is enough time to cause catastrophic damage to the equipment if the pre-start checklist is not properly completed and proper maintenance isn’t consistently followed.
NOTE: Cold start capabilities are strongly correlated with the quality of the diesel.
LUBRICATION
Before starting the engine, check the oil level in the crankcase. If it is low, refill to the full mark with the proper weight/grade of oil as recommended by the engine manufacturer’s maintenance instructions. The necessity of using the correct oil, and keeping the crankcase full, cannot be over emphasized. Failure to use the proper oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful life.
WINCO recommends our 5W-40 fully synthetic heavy duty engine oil to give you maximum cold weather protection while maintaining excellent performance in warmer weather. We have partnered with a national lubrication oil manufacturer to give you access to Winco private branded premium oil available at comparable prices to conventional oils. See your dealer for additional information.
Qty of oil
WINCO
Broad Range
Premium
Cold Climate
Not
Authorized
SAE
Grade Base Stock
5W-40 Synthetic
10W-40
5W-30
Semi-
Synthetic
Synthetic
International specifications
API CJ-4
ACEA E6/E9
API CJ-4
ACEA E6/E9
API CJ-4
ACEA E6/E9
Monograde
Sulfur
Content In
The Fuel
< 15 ppm
< 15 ppm
<15 ppm
OPM-147/B 12
CAUTION: PERSONAL INJURY
Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns.
1. Remove the dipstick and ensure the oil level is between
the Min and Max limits.
2. If it is difficult to read the level of the oil, clean the
dipstick using a clean cloth and then put it back into
its seat. Remove the dipstick again and check the level.
3. If level is low, unscrew the cap and refill with
suitable oil using the previous table.
CONTROL LAYOUT
COOLANT
Before starting the engine, check the coolant level in the radiator. If it is low, refer to Refilling Coolant in the
Maintenance section of this manual. The radiator should be filled to about 1 inch below the filler neck. For additional information on engine coolant requirements, see engine manufacturer’s maintenance instructions.
CAUTION:
Both too high and too low of coolant temperature can cause an engine malfunction. While the engine is running, ensure the coolant temperature is within appropriate temperature (167 - 194 ° F).
PRE-START CHECK LIST
There is a Pre-Start & Warranty Form that must be filled out by an Authorized WINCO Service Center. After completing the checklist, the engine-generator set is ready for initial start-up.
WARNING: EQUIPMENT DAMAGE:
Before attempting to start this unit, complete your pre-start checklist and ensure the generator mainline circuit breaker
(if installed) is in the proper position prior to starting.
Starting this unit without it properly connected can cause serious personal injury or equipment damage.
DO NOT jump start these engine-generator sets. Starting these units on a low battery or jump starting them will cause damage to the engine control module.
STOP/RESET - This button places the module into its Stop/Reset mode. This will clear any alarm conditions for which the triggering criteria have been removed. The fuel supply de-energizes and the engine comes to a standstill. Should a remote start signal be present while operating in this mode, a remote start WILL NOT occur.
MANUAL MODE - This button places the module into its Manual Mode. Once in
Manual Mode, the model responds to the
Start button to start the generator and run it off load.
START - Pressing this button from STOP/RESET will start the engine and run the load.
AUTO MODE - This button places the module into its Auto Mode. This mode allows the module to control the function of the generator automatically.
ALARM/LAMP TEST - This button silences the audible alarm in the controller, deactivates the Audible Alarm output (if configured) and illuminates all of the LEDs on the module’s face as a lamp test function.
MENU NAVIGATION - Used for navigating the instrumentation, event log, and configuration screens.
PROTECTIONS
When an alarm is present, the common alarm LED, if
configured, will illuminate. The LCD display will show an
icon to indicate the failure.
WARNINGS
Warnings are non-critical alarm conditions. They do not
affect the operation of the generator system, they
serve to draw the operator’s attention to an undesirable
condition. Warning alarms are self-resetting when the
fault condition is removed. The icon will appear steady in
the display.
SHUTDOWN
Shutdowns are critical alarm conditions that stop the
engine and draw the operator’s attention to an
undesirable condition. Shutdown alarms are latching.
The fault must be removed and the STOP/RESET button
pressed to reset the module. The icon will be flashing in
the display.
13 OPM-147/B
MANUAL MODE
1. Press and release the MANUAL MODE button. The small
LED light next to it should come on.
Note: There is no start delay in this mode of operation.
2. Press and release the green START ENGINE button. The
DSE 7310 will send two signals to the engine. The first
signal wire #21 will engage the fuel solenoid, the second
wire, #22, will engage the starter on the engine. At this
point the DSE 7310 will start the cranking cycle (10
seconds on and 10 seconds off).
Note: Wire #93 is energized to turn on the glow plugs for
15 seconds first and then the starter and fuel solenoid are engaged.
If the engine fails to start during this cranking period, the
starter motor is disengaged and goes into a rest mode
after which a second attempt is made to start the engine.
Should this sequence continue through 3 cranking cycles
the start sequence will be stopped and the display will
show ‘FAILED TO START’.
3. During manual operation, the load will not normally be
applied to the generator. But caution must be used, if the
line power should fail or be turned off the transfer switch
during manual operation the load may be applied to the
generator.
With the engine running smoothly check the no load
voltage and frequency on the digital display. The voltage
should match the nameplate and a frequency of 59.5 to
60.5 hertz (Hz).
If you have the proper voltage at the generator the next
step is to check the voltage at the generator terminals
in the Automatic Transfer Switch. The voltage between
the G1 and the G3 terminals should be the same as it
was on the generator front panel. The voltage should
also be checked between the hot terminals (G1 and G3)
and the G-N to be certain of a balanced voltage output
and a solid neutral connection. The voltage between G1
and G-N should be about 120 volts AC (277 on 480
units). The same approximate voltage should be found
between terminals G3 and G-N (120 volts AC).
On three phase panels the G2 voltage level should also
be checked. ON 240 VOLT (DELTA) SYSTEMS BE SURE
YOU KNOW WHERE THE HIGH VOLTAGE “WILD” LEG IS.
IT MUST BE IN THE SAME LOCATION ON THE LINE SIDE
AS IT IS ON THE GENERATOR SIDE. (i.e. if it’s on L-3 on
the line side it must be on G-3 on the generator side. Also
on three phase systems make sure that the rotation is the
same on the generator as it is on your line power. Failure
to insure proper rotation will cause three phase motors to
spin backwards possibly damaging them.
NOTICE:
If for any reason during the check out procedure the voltage and frequency are not correct, depress the STOP/
RESET button and correct the trouble before proceeding.
4. Stopping - There are two ways to stop the unit when it is
in the manual mode. Pressing the STOP/RESET button will
stop the unit immediately. Pressing the AUTO mode
button will stop the unit but only after the cool down
timers have timed out and there is no remote start signal
being sent to the unit.
WARNING: EQUIPMENT DAMAGE
Always make sure the generator runs under no load for five minutes before stopping to allow the engine and components to cool down. Don’t use the E-Stop as the standard.
AUTO MODE
To activate the automatic start mode you will just need to depress the AUTO button, the LED indicator beside the button confirms that the unit is in automatic mode.
To test the Automatic Transfer Switch, follow the instruction on the operator’s manual that came with the transfer switch. If you get a fault during the initial start up or prior to start up, it is most likely a false warning light. Simply reset the ATS to start over.
Once you have completed testing of the ATS, be sure you
ALWAYS leave the system in the standby mode,unless servicing the unit. For standby operation, press the AUTO button on the front of the control. The green light should light up next to the AUTO button.
NOTE: For setting the exerciser circuit, for all ATS, see the operator’s manual shipped with the ATS.
CONTROL POWER
The DSE7310 controller consumes small amounts of battery power when it is in use. The controller comes with a power switch that disconnects battery power when it is not in use.
The switch is designed with a safety relay that prevents it from removing power to the controller while the generator is operating. If the switch is turned off while the engine is running it will continue operating until the engine shuts down and then the controller will power down.
This switch should be used when the generator is not going to be used over the course of several days and the generator is not connected to a battery charger.
A solar charger kit is the easiest way to always maintain the battery during storage in mobile applications. The supplied battery charger can be plugged in to an extension cord on mobile applications.
OPM-147/B 14
OPERATING CONDITIONS
NORMAL OPERATION
This generator set is designed to be operated under load and the accumulation of operating hours without load can cause unburned fuel from the combustion chamber to build up in the exhaust system. This is called wet stacking and can result in fouled injectors and carbon buildup in the exhaust pipes, turbo and exhaust valves.
Inspect the CV filters and hoses regularly during cold operation looking for signs of freezing. If the line freezes it will cause pressure to build in the crankcase and may cause an engine seal failure. An optional CV hose heater kit is available to install and is recommended for units operating in temperatures below 14 ° F. If the engine operates below optimal temperatures for long periods of time damage may occur.
To avoid wet stacking the operating temperatures must be kept high enough. The best way to do this is to ensure that the generator set has adequate load during operation. If the engine is cold at start up run it for 2-5 minutes and then load the generator. Idling longer than this is more likely to damage the engine than extend its life
If the generator application is for emergency standby the generator should be exercised at least monthly ideally under load. Load banking the generator at least annually will help keep the engine in good condition.
HARSH ENVIRONMENTS
OPERATIONS
Some applications require the generator to operate in harsh environments. One of the most common hazards are extremely dusty conditions. In harsh conditions it is often necessary to take additional steps to keep the equipment clean and operating at its peak. Maintenance intervals on lubricant and filter changes may need to be shortened. An oil quality testing program can also provide early warnings or oil degradation. Efforts may need to be made to reduce the amount of dust and debris entering the housing and generator components.
COLD WEATHER OPERATIONS
The minimum natural starting temperature with glow plugs is -5°F. The minimum starting temperature with glow plugs and block heater is -13°F.
The degree of fluidity of the diesel oil can may be reduced at low temperatures due to the separation of the paraffin.
This results in the filters becoming clogged.
The ASTM D975 or EN590 specifications distinguish different classes of diesel fuel, identifying the characteristics of those that are best adapted to low temperatures.
Oil companies must respect these standards, which provide for the distribution of fuels adapted to the climatic and geographical conditions in various countries.
This generator-engine set needs load and should not idle for long periods of time.
If the generator set will be run in extremely cold environments it may be beneficial to provide means to reduce air circulation to increase the temperature of the enclosure.
15 OPM-147/B
MAINTENANCE
CHANGING THE OIL
CAUTION: PERSONAL INJURY
Only change oil when the engine is not running and is at a low temperature in order to avoid the risk of burns.
WINCO recommends our 5W-40 fully synthetic heavy duty engine oil to give you maximum cold weather protection while maintaining excellent performance in warmer weather. We have partnered with a national lubrication oil manufacturer to give you access to Winco private branded premium oil available at comparable prices to conventional oils. See your dealer for additional information.
1. Place a drip pan or suitable container for catching the
oil below the drain plug. WINCO has supplied a valve
to hook a customer supplied 5/8” hose to conveniently
run the oil to the drip pan.
CHANGING OIL FILTER
The filter must be replaced when the lubricant oil is changed.
Only use filters with a filtering degree equal to the original filter.
CAUTION: PERSONAL INJURY
Only change oil when the engine is not running and is at a low temperature in order to avoid the risk of burns.
1. Use an oil filter wrench to
unscrew and remove the oil
filter from the filter body and recover the gasket
2. Replace the oil filter and gasket.
3. Carefully clean the surfaces of the support that are in
contact of the gasket.
4. Moisten the gasket with a thin layer of oil and place
it in its seat on the oil filter.
5. Manually tighten the new oil filter on the mount
until it is fit up against the gasket.
6. Using the oil filter wrench, further tighten the oil filter.
CHANGING COOLANT
Usage Region
Warm region
Cold Region
Outside
Temperature
10 ° F or above
-22 ° F - 10 ° F
Long-Life Coolant
Concentration
30%
50% 2. Remove the dip stick and remove the engine
lubricant oil filter plug.
3. Drain the oil by removing the plug from the oil sump.
4. Once the sump has fully drained, close the valve.
5. Top-off through the filler cap using lubricant oil
with the suitable oil table in the LUBRICATION section
of this manual.
CAUTION: PERSONAL INJURY
Only proceed when the engine is not running and is at a low temperature in order to avoid the risk of burns.
1. Remove the cap on the radiator.
2. Open the coolant drain cock on the radiator to
discharge the coolant.
3. Loosen the water drain plug located on the left side of
the cylinder block. Discharge the coolant inside the
engine.
6. Use the dip stick to ensure the level of oil does not
exceed the “MAX” limit.
7. Insert the dipstick and close the lubricant filler cap.
8. Dispose of oil in accordance to local codes. DO NOT
dispose or allow oil to seep into the ground or sewer
systems, doing so will cause environmental damage.
OPM-147/B 16
4. Close the drain cock and the water drain plug. Refill
radiator with coolant.
REFILLING COOLANT
1. Remove radiator cap. Slowly add coolant to the filler
opening.
2. Loosen the air bleeder plug of the EGR cooler to
remove any air from the coolant.
3. Tighten the air bleeder plug when the coolant
overflows.
4. Firmly close the radiator cap.
5. Fill the reserve tank up to the specified level, close the
reserve tank cap.
4. Fully hand-tighten the plug.
5. Dispose of liquid in accordance to local codes. DO NOT
dispose or allow liquid to seep into the ground or
sewer systems, doing so will cause environmental
damage.
CHANGING AIR FILTER
CLEANING RADIATOR
The surfaces of the radiator come into contact with the outside air and can be subject to deposits and impurities.
Clean in accordance to the maintenance schedule with compressed air or steam.
Do NOT remove filter while engine is running.
1. Remove the air filter cover (4) after having released the
two quick closing hooks (3).
2. Remove the filter (5). During this operation, take care
to ensure that no dust enters the sleeve.
3. Position the filter (5) in its seat.
4. Replace the cover (4) of the air filter and lock it in place
using the two quick release hooks (3).
CHECKING WATER IN FUEL FILTER
WARNING: EQUIPMENT DAMAGE
Clean the exhaust valve prior to checking the pre-filter to reduce the risk for system contamination.
Do NOT perform while the engine is running.
1. Place a container for collecting liquids under the
pre-filter.
2. Unscrew the plug located at the bottom of the filter.
3. Drain the fluid until only fuel comes out.
CHANGING THE FUEL FILTER
1. Loosen the drain plug and air
bleeder plug to discharge the
fuel inside the filter.
2. Using a filter wrench, remove case.
3. Replace the O-ring of the case
and drain plug with the new
ones, place the new element
in the case. Thinly apply fuel
on the O-Ring and screw in the
element.
4. Remove air from the fuel.
17 OPM-147/B
STORAGE
PREPARING THE ENGINE FOR A LONG PERIOD
OF INACTIVITY
In the case of a planned period of inactivity that lasts longer than two months, to prevent the interior parts of the engine and some components of the injection system from oxidizing, prepare the engine as follows:
1. Drain the lubricant oil from the sump after heating the
engine.
2. Pour 30/M protective oil into the engine up to the
“minimum” level indicated on the oil level dipstick. Start
the engine and run it for approx. 5 min.
3. Drain the fuel from the injection circuit, from the filter
and from the injection pump channels.
4. Connect the fuel circuit to a tank containing CFB
protective liquid (ISO 4113) and introduce the liquid by
pressurizing the circuit and driving the engine for
approx. 2 min. after excluding injection system
operation.
MAINTENANCE SCHEDULE
The operation required can be completed by directly polarizing terminal 50 of the electric starter motor with positive voltage equal to that of the nominal system voltage, using the designated conductor.
NOTE: Some operating conditions may require more frequent maintenance intervals.
5. Nebulize the 30/M protective oil in a quantity of
approx. 130 g (10 g per liter of displacement) in the
turbocharger intake inlet, during the engine turning
operation described in the previous paragraph.
Checks In Period of Use Frequency
Check for water in the fuel filter Daily
Check Air-Restriction Indicator on Filter Daily
Engine Oil Level Daily/Prior to Use
Engine Coolant Level
Planned Maintenance
Tension and Condition Check of
Ancillary Belt
Engine Oil Replacement
Oil Filter Replacement
Fuel Filter Replacement
Clean Radiator
Air Filter Replacement
Extraordinary Maintenance
Ancillary Belt Replacement
Turbocharger Visual Inspection
Alternator Visual Inspection
Clean/Replace Radiator Cap
Engine Coolant Replacement
Daily/Prior to Use
Frequency
500 Hours
250 Hours
500 Hours
500 Hours
500 Hours
1250 Hours
Frequency
3000 Hours
1500 Hours
3000 Hours
3000 Hours
3000 Hours
6. Close all of the engine’s intake, discharge, ventilation
and bleeding holes with plugs or seal them with
7. Drain the residual 30/M protective oil from the sump,
which can be used for an additional 2 preparations.
8. Place warning notices of ENGINE WITHOUT OIL on the
engine and dashboard.
NOTE: When storing in cold regions, make sure the coolant and engine oil are in conditions suitable to the environment. Also, when starting the engine after it has been stored, make sure that there is no snow or foreign matter that could interfere with engine startup, and rotating parts are not frozen.
OPM-147/B 18
TROUBLE SHOOTING TABLES
Problem Possible Causes
Unit will not crank when power fails
Engine won’t crank
Engine cranks but will not start
Engine starts, then stops and alarm light comes on
Engine will not come up to speed after it starts
ATS will not transfer to Emergency Supply
(generator)
Digital genset not in AUTO
Transfer control switch not in
AUTOMATIC position
Incorrect wiring between ATS and genset
Defective control relay in ATS
Fuse(s) blown in the DSE 7310
Defective DSE 7310
Loose or dirty battery terminals
Defective starter
Defective start solenoid
Low/dead battery
Low/dead battery
Blown DC fuses
Defective DSE 7310
Defective key switch
Loose or dirty battery terminals
Defective starter
Defective start solenoid
Locked up engine genset
Defective engine harness
Improper battery voltage to start solenoid,
fuel pump, or fuel solenoid
Improper fuel delivery to the unit
Fuel supply shut off
Fuel tank empty
Air in the fuel system
Engine fuel solenoid has not opened
Defective fuel pump
Defective fuel solenoid
Defective engine harness
Improper battery voltage to fuel
pump or fuel solenoid
Engine oil pressure is low
Engine has high water temperature
Engine has overspeed
Engine has gone into overcrank
No output from AC generator
Loss of speed signal
Loss of run signal
Insufficient fuel volume getting to the unit
1. Too small of fuel line
2. Fuel racks not open properly
Governor is defective
AC short in generator components
No AC generator output
Defective ATS control board. See ATS
manual
Circuit breaker open or defective
ATS will not re-transfer to normal power
No AC output from generator
Proper power line not available at line
terminals in ATS panel
Defective ATS control board. See ATS
manual
Defective diode
Defective voltage regulator
Defective rotor
Defective stator
Defective exciter rotor
Defective exciter stator
AC short in the output leads
Defective/open generator output breaker
Wiring error
19 OPM-147/B
WIRING SIZE TABLE
The table below is based on Table 310.15 (B) (16) in the National Electric Code 2014 edition. Allowable ampacitier of insulated conductors rated 0 through
2000V, 75°C through 90°C. Not more than three current-carrying conductors in Raceway, Cable, or Earth (direct buried). Adjust for 40°C (104°F) ambient temperature.
Copper
75°C
Copper
90°C
Aluminum
Copper Clad
Aluminum
75°C
Aluminum
Copper Clad Aluminum
90°
Wire Type:
RHW, THHW, THW,
THWN, XHHW, USE,
ZW
50
Wire Type:
TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2,
THHN, THHW, THW-2, XHH, XHHW, XHHW-
2, ZW-2
55
SIZE
AWG
OR
KCMIL
8
Wire Type:
RHW, THHW, THW,
THWN, XHHW, USE
40
Wire Type:
TBS, SA, SIS, THHN, THW-2, THWN-2,
RHH, RHW-2, USE-2, XHH, XHHW,
XHHW-2, ZW-2
45
150
175
200
230
255
285
310
335
380
65
85
100
115
130
420
460
475
490
520
475
520
535
555
585
290
320
350
380
430
75
95
115
130
145
170
195
225
260
545
590
625
650
655
615
665
705
735
750
For additional information, see table 310.15 of the National Electric Code.
340
375
385
395
425
205
230
250
270
310
445
485
520
545
560
50
65
75
90
100
120
135
155
180
600
700
750
800
900
250
300
350
400
500
3
2
6
4
1
1/0
2/0
3/0
4/0
1000
1250
1500
1750
2000
385
425
435
445
480
230
260
280
305
350
500
545
585
615
630
55
75
85
100
115
135
150
175
205
OPM-147/B 20
ECM DIAGRAM
5 6 14 3 11
EGR BR
Wire size instruction; : The number next to wire line; ISZ recommended electric wire size. The line which has no special instruction; 0.75sq is ISZ recommended size.
: This symbol shows shield wire. Please use twist wire for machine side harness too.
: This symbol shows twist wire. Please use twist wire for machine side harness too : This symbol shows the point that connects with engine harness and machine side harness.
21
U V W
OPM-147/B
6&5
$
%
%&)$,/
(6723
(6723
67$57
67$57
*1'
*1'
%$77
%$77
DSE7310 WIRING DIAGRAM
)8(/
67$57
&+$5*($/7
$1$/2*8(,1387&20021
2,/35(6685(6(1625
&22/$177(036(1625
)8(//(9(/6(1625
)/(;,%/(6(1625
)/(;,%/(6(1625
)/(;,%/(6(1625
287387'
1250$//<
&/26('5(/$<
287387&
OPM-147/B 22
WIRING DIAGRAMS
THREE PHASE AC WIRE HIGH AND LOW WYE
THREE PHASE AC WIRING- DELTA SINGLE PHASE 311 WINDING
23 OPM-147/B
ENGINE GENERATOR SET
ONE (1) YEAR, 2,000 HOUR PRIME
LIMITED WARRANTY
WINCO Inc. has been engineering and manufacturing high quality generators since 1927. WINCO Inc. warrants to the original owner that the purchased product is free from defects in materials and/or workmanship for the period of time outlined below. If the product should prove defective within the time period outlined below, it will be repaired, adjusted or replaced at the option of WINCO Inc., provided that the product, upon inspection by an authorized WINCO Inc. service center, has been found to have been properly installed, maintained and operated in accordance with WINCO Inc.’s Installation and Operating Manuals, engine manufacturer installation and operation guidelines, and National and local code. This limited warranty is not valid or enforceable unless:
1. All supporting product maintenance records are kept on file and made available upon request from WINCO Inc.
2. A copy of the WINCO Inc. Start-up Completion and Warranty Validation Checklist is properly and completely filled out and returned to
WINCO Inc. within 30 days of start-up.
3. The product is routinely exercised in accordance with operating instructions. This warranty does not apply to malfunctions caused by
physical damage, misuse, improper installation, repair or service by unauthorized persons; or normal wear and tear. The warranty is
not assignable.
WINCO Inc. Product Warranty Period:
• Engine generator set: Parts and Labor for one (1) years from the date of factory invoice or 2,000 hours (whichever occurs first).
• Accessories (installed on the product or shipped loose): Parts and Labor for one (1) year from the date of factory invoice or 2,000 hours
(whichever occurs first).
The start of the warranty period can be adjusted to the date of unit start-up (limited up to 180 days from invoice date) provided that the following information is provided to WINCO Inc. at the time of start-up:
1. A copy of the WINCO Inc. Start-up Completion and Warranty Validation Checklist is properly and completely filled out and returned to
WINCO Inc. within 30 days of start-up.
2. Some engines may require revalidation after long-term storage. The engine revalidation process if included in the manual must be
followed.
To obtain warranty service:
Contact your nearest authorized WINCO Inc. service center. For assistance in locating your nearest authorized service center, contact WINCO
Inc.’s Service Department.
Warranty service may be performed by an authorized WINCO Inc. service center only. Service work performed by unauthorized persons will void all warranties.
WINCO Inc. shall not be liable for any claim in an amount greater than the purchase price of the product. In no event shall WINCO Inc. be held liable for any special, indirect, consequential or liquidated damages.
WINCO Inc. shall not be liable for any claim that requires replacement of engine, part, or component of the product that is no longer manufactured or available.
Additionally, WINCO Inc. will not be liable for any engine replacement that may require an emissions tier-level change.
THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR
OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE.
The following items and/or circumstances are excluded from this limited warranty:
• Engine starting batteries: The battery manufacturers’ warranty applies. Consult your local battery supplier for warranty service.
• Fuel system and/or governing system adjustments performed during or after start-up.
• Normal maintenance items: Consumable items such as belts, filters and hoses.
• Damage caused by over-loading the generator and failure to adequately provide over-load protection.
• LP/NG fuel adjustments or conversion from one fuel to another.
• Any repeat or shop come-back repairs resulting from poor service work or improper diagnosis and testing. Replacement of parts as a trial-and-error
method of diagnosis will not be considered for warranty.
• Adjustments and tune–ups performed during start-up or thereafter.
• Loose connections (electrical and mechanical) not found during start-up.
• All fluid level related items including low coolant not found during start-up or checked during regular maintenance intervals.
• Equipment modifications made without the written consent of WINCO Inc. will void all warranties.
• Shipping damage of any type. All equipment is shipped F.O.B. factory and risk of loss transfers to the carrier once loaded for shipment. It is the
responsibility of the receiving party to sign for the receipt of, and note any shipping damage to the equipment. Freight damage claim filing is the
responsibility of the receiving party. In the rare event that damage occurs during shipment, WINCO Inc. will not warrant any damage to the unit
resulting from packaging material.
• Any special access fees, requirements or after hours scheduling to gain access to the equipment for warranty service purposes.
• Rental generators used while warranty work is being performed.
• Damages caused by acts of nature, such as lightning, wind, flood, wild fires, or earthquake.
• Any damage due to situations beyond the control of the manufacturing and/or workmanship of the product.
• Use of non-protected steel enclosure within 25 miles of the coast.
• Damage caused by improper installation or failure to provide adequate ventilation.
• Misapplication of the equipment such as usage outside the original design parameters as stated on the nameplate of the equipment.
• Equipment purchased at the standby rating that is being used in a prime power application(s).
• Diesel engine “Wet Stacking” due to lightly loaded diesel engines.
• Travel time or service calls unless given written authorization by WINCO Inc.
OPM-147/B