Operators Manual
Operation, Maintenance and Service
Capture Ray
TM
Hoods
Model:
KVE-UV, KVC-UV, KVW-UV
INSTALLATION INSTRUCTIONS
Suspending and Mounting
Determine location of 1/2” (13mm) diameter handing rods. All thread rods are recommended for use with front support brackets provided. All hanging rods should have double nuts. Rods should be threaded 4” (102mm) minimum for verticle adjustment. See figure 1. Handing rods by installer.
Exhaust hoods are shipped in maximum lengths of 14’-0”. When installing multiple sections, we recommend hanging the section individually then fasten together as per the installation drawing. See figure 2.
Install U-channel strips provided on multiple bank sections between interior section ends at bottom. All exhaust hoods must be hung level and plumb.
Note:
Allow 100lbs (45kg) per linear foot hanging weight.
Do not lift exhaust hoods from their end panels. Lift from four corners
All exhaust hoods and control panels are fitted together and factory tested prior to shipping for alignment and operation.
Duct Connections
Duct connections meet NFPA 96 of applicable local codes. Size of connection is indicated on exhaust hood drawing. Connection to be made after exhaust hood is hung.
PROPER LOCATION IS ESSENTIAL
Locating the exhaust ventilator with sufficient overhang over the cooking equipment is manditory for proper capture and extraction of grease and smoke.
It is important that the installer check with Kitchen Equipment Contractor for accurate location of the cooking bank, exhaust hood and control panel.
Exhaust hood shop drawings show recommended mounting height from finsihed floor to underside of exhaust hood at front edge. All hanging bracket locations are also indicated. Electrical, ductwork and air requirements are also indicated on the exhaust hood show drawings.
Capture Ray TM Operation & Maintenance & Service Manual 2
FIGURE 1
HOOD INSTALLATION DETAILS
40" MIN.
16 GA. DUCT WORK
ALL WELDED PER CODE
1/2" ALL THREAD
(BY OTHERS)
HANGER BRACKETS
1/2" NUTS
(BY OTHERS)
OPTIONAL TURNBUCKLES
(BY OTHERS)
1.25"
4"
HANGER BRACKET
DETAIL
1/2" ALL THREAD
(BY OTHERS)
WELDED TO
TOP OF HOOD
18 GA.
MAT'L
1/2" THREADED NUT
(BY OTHERS)
2 "
1.25" 3 "
DROP
CEILING
CANOPY
HOOD
EXHAUST
DUCT
CONTINUOUS
LIQUID TIGHT
WELD
(ALTERNATIVE)
EXHAUST
COLLAR
78"-84"
A.F.F.
78"
(INDUSTRY STANDARD)
CONTINUOUS
LIQUID TIGHT
WELD
COOKING
EQUIPMENT
TURN BUCKLE
** IMPORTANT NOTE **
SUPPLY FIRE DAMPER
MAKE SURE THE FIRE DAMPER IS SET
IN THE OPEN POSITION BEFORE INSTALLING
SUPPLY DUCT
SEE FIGURE #7 & #6 FOR SETTING FIRE DAMPER
SUPPLY DUCT
SUPPLY DUCT MAY BE ATTACHED TO SUPPLY
COLLAR WITH SHEET METAL SCREWS OF POP
RIVOTS AND SEALED WITH DUCT TAPE.
SCREWS/RIVOTS ARE NOT TO INTERFER WITH
THE OPERATION OF THE FIRE DAMPER
HANGER
BRACKET
SUPPLY
DUCT
ALL THREAD
EXHAUST DUCT
PER CODE
Capture Ray TM Operation & Maintenance & Service Manual 3
FIGURE 2
SPLICE STRIP / U-CHANNEL ASSEMBLIES
Hoods end to end
A
= U-Channel
Holds two end panels
together
Pry U-Channel apart
at one end and insert
over the end panels
Hammer channel on
starting from one end
and going to the other
B
= Splice Strip
Insert splice strip over
bottom front edge first
then over top front of
the hood
Secure to top of the hood
by welding or sheet metal
screws (supply plenum only)
C
= U-Channel
Holds two backs together
Clamp the two backs together
Slide U-Channel up over the backs, and secure with sheet metal screws
D
= Splice Strip
Insert splice strip over
bottom sides first
then over top sides
Secure to top of the hood
by welding
D
A
A
B
D
Hoods back to back
C
B
C
Capture Ray TM Operation & Maintenance & Service Manual 4
METHOD OF OPERATION
Capture Ray TM hood systems operate properly when the KSA grease extractors and backup mech filters are properly installed, the UVC lamps are clean and the exhaust fan is turned on.
The system is engineered to reduce maintenance and keep service issues to a minimum. The unit is constructed of stainless steel with removable KSA grease extractors and GPS filters for interior inspection and cleaning.
Make-up Air Supply
Make-up air must be provided to replace the air exhausted through all kitchen exhaust systems. The
“make-up air” may be supplied through a front face discharge plenum on the Capture Ray TM hoods or from registers in the kitchen area. Velocities of “make-up air” should be kept to a minimum especially near the exhaust hood perimeter.
> CAUTION: High “make-up air” velocities will distrub smoke capture. Many codes call for a number of air changes per hour. This should be reviewed with the entire ventilation requirements of the facility.
METHOD OF DETERMINING AIRFLOWS
The air flow through the Capture RayTM hoods in determined by using the testing and balancing
(T.A.B.) port as showin in figure 3.
T.A.B.
TM
- TESTING AND BALANCING PORTS
Ps P s
The capture-jet and exhaust air flows are easily and accurately determined by matching the pressure difference from the
T.A.B. ports mounted in each plenum. Corresponding air flows, in cfm per foot of hood, can be read from the diagrams provided in this catalog.
Capture-Ray Hood Example
2.1
1.9
1.7
1.5
1.3
1.1
0.9
0.7
0.5
150 170 190 210 230 250 270 290
Airflow (cfm/ft)
(based on heat load design)
Measured Pressure
∆ P = 1.4"
Capture Ray TM Operation & Maintenance & Service Manual 5
Halton AccuFlow
Overview
The AccuFlow by Halton is a Bluetooth equipped device intended to monitor the exhaust airflow rate of Halton Capture Jet hoods and alarm kitchen staff if the hood is above or below design. The device
(shown below in Photo 1) has two taps (Photo 2) that are connected to the exhaust hood to monitor the differential pressure between ambient air and the exhaust plenum; the T.A.B Port reading.
AccuFlow installs in Capture Jet plenum for easy viewing and access. The device shares an electrical circuit with the Capture Jet fan.
Photo 1 – Halton AccuFlow
Photo 2 – AccuFlow Pressure Taps Connects to ambient (room) air
Connects to T.A.B. port
Plastic tubing connected to (-) port of
Accuflow device
Exhaust airflow rate is determined in the same fashion as other Halton Capture Jet hoods; each hood has a unique K-Factor dependent upon model. The actual airflow is compared to the design value and an alarm is enabled if airflow is above or below the specified range.
Capture Ray TM Operation & Maintenance & Service Manual 6
Operation
Each AccuFlow is programmed at a Halton Company manufacturing facility. To program the device, the Bluetooth feature is enabled and personnel input necessary parameters. Programming can be completed with a Windows Mobile enable smart-phone (PDA) or PC with the required software installed.
Programmed values include: Design Airflow, High Airflow Delta, Low Airflow Delta and K-Factor.
Design Airflow is determined using the Halton HELP software and the Low and High Airflow Delta are defined as +/- ten percent of design airflow. K-Factors have been determined by Halton Research and
Development personnel.
Bluetooth capability also allows an Authorized Service Agent to determine the airflow of an exhaust hood on site if an alarm is present. This information can be conveyed to Halton personnel for troubleshooting.
Alarms
Alarms are enabled when design airflow is above or below ten percent of design airflow. An alarm is visible on the front of the Accuflow, see Photo 3 below.
Photo 3 – AccuFlow Alarm Location
Indications of alarm status (under or over design) are printed on the device. If the LED indicator is steady, the hood is at design airflow. Alarms are differentiated by the number of blinks per second;
1 blink per second indicates the hood is under design, 2 blinks per second indicates the hood is over design.
Capture Ray TM Operation & Maintenance & Service Manual 7
Troubleshooting AccuFlow
Problem
No lights Illuminated on
AccuFlow device
Low airflow alarm
Failure
Probable Cause
Loose or improper electrical connections
-Not reaching design airflow
-Plastic tubing disconnected from Accuflow device or TAB port
-Broken plastic tubing
-Dirty or plugged TAB port in exhaust plenum
Bad Device
Solution
- Verify or reconnect electrical connections
-Increase fan speed
-Reconnect
-Replace tubing
-Clean TAB port
- Replace
Capture Ray TM Operation & Maintenance & Service Manual 8
SERVICE INSTRUCTIONS
WARNING
Removal of the UVC lamps and access to the control panel is by a Halton Factory Authorized
Trained Service Agency only.
Capture Ray TM Component Cleaning
Durning the day grease accumulates in the interior of the KSA grease extractor and the GPS (grease particle separator) filter. Therefore, they must be cleaned on a daily basis. This can be accomplished by running through a dishwasher.
> Caution: If the KSA grease extractor and GPS filter are not maintained, accumulated grease can create a fire hazzard and impair the overall performance of the hoods.
Automatic Duct Protection
Automatic fire suppression is accomplished by use of a thermal fusible link in the exhaust collar and detection line above the appliances. If the fusible link should activate, it would close the fire damper (if supplied) and automatically release the suppression agent.
NOTE: Depending on the type of cooking equipment covered, an additional surface fire protection system is typically required.
In the event of a fire, the surface fire protection system would normally activate and discharge before high temperatures would close the fire damper (if supplied). All gas, and/or some electric, cooking equipment must also be provided with a “fuel shut-off” device when the surface fire protection system is activated. Duct and plenum protection is required on Capture Ray TM hoods. Consult local authorities.
CROSS SECTION OF CAPTURE RAY
TM
HOOD
BALLAST
BOX
TOP
INTAKE
(STD)
INTERNAL
FAN
UV CASSETTE
GPS - (GREASE
PARTICLES
SEPARATOR)
S.S. KSA
FILTERS
T.A.B.
PORTS
CAPTURE-JET AIR
Capture Ray TM Operation & Maintenance & Service Manual 9
MAINTENANCE AND CARE INSTRUCTIONS
WARNING
Unauthorized access or tampering will result in serious eye damage.
CAUTION
Access and service is by a Halton Factory authorized personnel only.
You have purchased the finest kitchen ventilation equipment available anywhere. Like any fine piece of equipment, it should be given regular care and maintenance.
NOTE: It is crucial that a Preventative Maintenance Program is contracted and performed by a Halton
Factory Authorized Trained Service Agency only. Your Halton dealer is well qualified to co-ordinate this service. Periodic inspections are recommended to check the operation. When corresponding with the factory or your equipment dealer regarding service issues or replacement parts, be sure to refer to the unit by the correct model number including perfix and suffix letters and numbers and serial numbers if shown. The model plate affixed to the unit contains this information and is mounted on the inside of the hood wall.
REGULAR MAINTENANCE ENSURES PEAK PERFORMANCE.
CLEANING EXTERIOR
STAINLESS STEEL - Normal soil may be removed with a stainless steel detergent and warm water applied with a cloth.
NOTE: Remove grease build-up from fixed baffles and other interior surfaces. To remove grease that has baked on, apply cleanser to a damp cloth or sponge and rub cleanser on the metal in the direction of the polishing lines of the metal.
NEVER RUB WITH A CIRCULAR MOTION.
Soil and burnt deposits which do not respond can usually be removed by rubbing the surface with
Scotch-Brite scouring pads or stainless scouring pads.
DO NOT USE ORDINARY STEEL WOOL.
Heat tint can be removed by a vigorous scouring in the direction of the polish lines using Scotch-Brite scouring pads or a stainless scouring pad in combination with a powdered cleanser.
Capture Ray TM Operation & Maintenance & Service Manual 10
REPLACEMENT PARTS SCHEMATIC
BALLAST BOX
TOP
INTAKE
(STD)
"UV" Cassette
38"L = #2806
66"L = #2807
GPS Filter
#2804
Incandescent
Light Base
#2802
Incandescent
Light Globe
#2801
KSA Grease
Extractor#2800
Grease Cup
#2805
Replacement Part Numbers
38” UV Cassette
66” UV Cassette
GPS Filter
Grease Cup
KSA Grease Extractor
Incandescent Light Base
Incandescent Light Globe
2806
2807
2804
2805
2800
2802
2801
PREVENTATIVE MAINTENANCE
Preventative maintenance is necessary for efficient operation of your Capture Ray TM hood.
Daily - Clean exhaust hood exterior. See cleaning exterior. Wash the KSA extractor and the GPS filter.
Weekly - Make sure the unit is turned off at the control panel. Remove the KSA grease extractor and clean the interior sections of the exhaust plenum where there is any grease build-up.
Gently wipe any grease off the UV lamps.
Monthly - The Capture Ray TM hood should be inspected regulary. The UV tube frames and controls should be verified for proper operation and cleaning. Check to ensure that all indicator lights are on, and wipe down the UVC lamps with a damp cloth to remove any residue. Run a complete test of the system and alarms.
Although this is listed as monthly, it may be extended or shortened depending on the type of cooking and hours of operation.
WARNING - Removal of the UVC lamps and Control Panel is by a Halton Factory Authorized
Trained Service Agency only. It is crucial that a Preventative Maintenance Program is contracted and performed by a Halton Factory Authorized Service Agency only.
Capture Ray TM Operation & Maintenance & Service Manual 11
CONTROL PANEL OPERATION
The UV control panel is designed to operate the UV lamps only under safe conditions and warn when there are lamp failures, fan failures, the lifetime of the lamps has been exceeded or other operational failures. If these solutions do not fix the problem, refer to the Troubleshooting Guide later in this manual.
If an alarm goes off on the panel it indicates then there is a problem with the UV operation. To silence the alarm, press the “MUTE” button; however, the indicator lamps will remain lit. To reset the 10,000 hour clock, it is necessary to use the keypad to reset the timer.
DISPLAY
Error
No Fan
10,000 Hour Maintenance
CAUSE
A lamp has failed, the voltage to the lamp is too low, or the lamp ballast has failed.
Either the fan is at a lower speed or belt has broken
Either a KSA filter is not in place in the hood or the cassette access door is open.
The expected lifetime of the lamps have been reached.
SOLUTION
- Check line voltage
- Replace UV Lamp
- Replace lamp ballast if needed
- Examine and tighten or replace
fan belt if needed.
- Replace fan if needed.
- Check that all filters are
installed and the cassette
access door is closed and
fastened.
- Replace the UV lamps. Failure
to do this will cause the
system to not be efficient.
Fire The fire system has been activated.
STANDARD CONTROL PANEL
4"
10 "
Capture Ray TM Operation & Maintenance & Service Manual 12
CONTROL PANEL - INPUT - OUTPUT DESCRIPTION
Safety Switches
These switches are monitored when the unit is turned On; in Off mode, they are ignored (except for the Fire Switch.) They are listed in the order of precedence in case some happen together.
Fire Switch – Normally Open switch connected to terminals 9 and 12
• When switch is closed, UV Lamp output is shut off immediately
• Buzzer sounds, Fire LED is lit and display scrolls FIrE
• Exhaust and Makeup fans may be shut off (depending on Low-level programming)
• This particular alarm remains active even when unit is Off.
Door Switch – Normally Closed switch (stays open during operation) connected to terminals 1 and 2
• When switch is closed, UV Lamp output is shut off immediately
• Fans remain on
• Buzzer sounds, UV Door LED is lit and display scrolls door OPEn
Pressure Switch - Normally Closed switch (stays open during operation) connected to terminals 1 and 15
• When switch is closed, UV shuts off immediately without delay (UV is the only output
affected)
• After Flow Alarm Delay time, buzzer sounds and display scrolls No Fan
• If switch is open again thereafter for at least 1 second, UV lamp output resumes operation
and error is cleared. (1 second delay to avoid contactor flickering when pressure is
unstable)
UV Lamp Failure Switch - Normally Closed switch (stays open during operation) connected to terminals 1 and 5
• This switch is monitored only if option is enabled (in Low-level programming) and UV Lamp
output is on
• When switch is closed (condition must exist for 60 seconds), all outputs remain on
• Buzzer sounds and display scrolls Error
Miscellaneous Switch - Normally Open switch, can be used for any additional safety feature when needed.
• When switch is closed, UV Lamp output is shut off immediately
• Fans remain on
• Buzzer sounds, M LED is lit and display scrolls no FIL
Remote ON/OFF Switch - Used to remotely turn the system On and OFF
• If enabled (in Low-level programming), this input overrides the On/Off key
• Keypad On/Off is no longer used (except for Low-level programming)
• Remote switch cannot be used for Low-level programming
Capture Ray TM Operation & Maintenance & Service Manual 13
CONTROL PANEL - INPUT - OUTPUT DESCRIPTION
Outputs
UV output – terminals 6 and 7
AC voltage to energize contactor coil switching power to UV lamps, either 120 or 240VAC
Exhaust Fan – terminals 6 and 10
AC voltage to energize exhaust fan starter, 120 or 240VAC
Makeup Fan – terminals 6 and 11.
AC voltage to energize makeup fan starter, 120 or 240VAC
Alarm signal output – Terminal numbers to be assigned if used.
Normally Open contacts which closes on certain alarms (low level programmable) to send signal to remote monitoring system.
User Interface
There are four keys:
- I/O to turn system On and OFF and to perform low level programming
- Alarm silence to mute the alarm buzzer
- Total to display the total number of hours of UV operation
- Clean to display the number of hours of operation since last UV cleaning
There are six LEDs (from left to right):
- UV lamps ON
- UV access door open
- M lit when miscellaneous input is activated
- No Fan lit when insufficient airflow in the system is detected by pressure switch
- Fire
- Maintenance - If UV Lamp Failure option is enabled, and a failure is detected, UV Service LED
blinks every 0.5 seconds (whether the unit is On or Off)
If Total Time Since Last Cleaning reaches 420 hours (Low-level adjustable), or if Total Hours
Of Operation reaches 10,000 hours (again, Low-level adjustable), UV Service LED comes full on
(whether unit is On or Off.) This check is done also when unit is turned on
NOTE: If cleaning cycle time set at factory for 1600 hour intervals is insufficient for proper
opeartion based on usage, time should be adjusted to reflect new cleaning cycle.
Capture Ray TM Operation & Maintenance & Service Manual 14
OPERATING MODES
OFF MODE
• The unit displays OFF
• All outputs are off
• All LEDs remain off (except possibly Service and Fire icons)
• Statistics can be consulted/cleared using appropriate keys
• Press On/Off key to turn on system; turn on sequence is as follows: o both fans are turned on o when unit detects air flow, UV lamps are turned on
• If buzzer is on, Mute key disables it
ON MODE
• The unit displays ON
• Fan/UV outputs are on
• Statistics can be consulted/cleared using appropriate keys
• Press On/Off to turn off system; turn off sequence is as follows: o UV lamp is shut off o fans stay on for an extra 30 seconds to exhaust ozone from the duct (Low-level pro
grammable)
• If buzzer is on, Mute key disables it
VIEWING/CLEARING STATISTICS
• Two types of statistics are recorded: Total Hours Of Operation and Total Hours Since Last
Cleaning
• These are simply displayed as a number of hours. If this exceeds 999 hours, then the dis
play rounds to the nearest 10, and displays as kilo-hours, with a decimal. For example, 517
hours is displayed as 517, whereas 1517 hours is displayed as 1.52.
• Statistic is viewed by pressing either Total or Clean. Display returns to normal as soon as
key is released.
• Statistic can be cleared by pressing the Mute key while pressing the statistic key.
LOW-LEVEL PARAMETERS
The unit has a Low-level programming mode. These allow fine-tuning of various system parameters and is intended for the OEM factory or service technicians.
To program these parameters, follow these steps:
• First make sure the unit is Off
• Press and hold the On/Off key for 20 seconds, until the 1st parameter is displayed (PO1)
• On/Off key toggles between parameter name and value
• Total and Clean keys are to be used as Up and Down keys
Capture Ray TM Operation & Maintenance & Service Manual 15
• Use the Total and Clean keys to browse through the parameter names, and to modify the
parameter value
• 3-second long press of On/Off key to end the Low-level programming mode and exit back
to previous mode. However, there is also a 30-second timeout, so that if no key pressed
for that time, the unit resumes operation on its own.
There is a special key sequence that allows resetting the Low-level parameters to their factory defaults described here. During power-up, if the Clean key is pressed, the unit will reset all parameters to their default values.
MAXIMUM UV CLEAN TIME
Maximum time allowed (in kilo-hours) before UV Service LED lights.
Parameter name: P01
Allowed values: 0.01 to 9.99
Factory default: 1.60
MAXIMUM UV OPERATING TIME
Maximum time allowed (in kilo-hours) before UV Service LED lights.
Parameter name: P02
Allowed values: 0.01 to 9.99
Factory default: 9.99
FAN TURN-OFF DELAY
When unit is turned Off, fans remain on for a certain period (seconds) until residual ozone is evacuated.
Parameter name: P03
Allowed values: 0 (immediate) to 999
Factory default: 30
FAN OPERATION DURING FIRE
When unit detects the Fire input, it shuts off the UV Lamp output. Fans are also shut off according to this parameter.
Capture Ray TM Operation & Maintenance & Service Manual 16
Parameter name: P04
Allowed values: 0 Both fans are shut off.
1 Exhaust fan only is on.
Factory default: 0
2 Makeup fan only is on.
3 Both fans are turned on.
AIRFLOW ALARM DELAY
This sets the maximum time allowed for the pressure switch to be closed in On mode. After this delay (in seconds), the unit will sound the buzzer to alert the operator.
Parameter name: P05
Allowed values: 0 (off, never sounds alarm) to 999
Factory default: 30
REMOTE ON/OFF
Enables or disables the remote On/Off switch. If enabled, keypad On/Off no longer controls the unit
(except to program Low-level). When enabled, a remote closed contact will mean On, and an Open contact will mean Off.
Parameter name: P06
Allowed values: 0 Disabled.
1 Enabled.
Factory default: 0
UV LAMP FAILURE DETECTOR
Enables or disables the UV Lamp Failure detector. If enabled, the unit will monitor the input whenever the UV Lamp output is supposed to be on.
Parameter name: P07
Allowed values: 0 Disabled.
1 Enabled.
Factory default: 1
Capture Ray TM Operation & Maintenance & Service Manual 17
1.1 DRY CONTACT ALARM FUNCTION
A dry contact relay (Alarm Relay) can be activated in certain conditions. This is useful for connecting the control panel to a central building automation or monitoring system.
Parameter name: P08
Allowed values: 0 Relay closes only when Fire Alarm is detected
1 Relay closes only when any of the following is detected:
- UV Door alarm
- No Filter alarm
- No Fan alarm
- Any of the statistics reaches its preset value
2 Relay closes in any of the above conditions
Factory default: 0
TROUBLE SHOOTING GUIDE
INOPERATIVE
Exhaust fan and UVC lamp will not function
Control Panel Message:
No Fan or Error
Fan on but no UVC lamps
Control Panel Message:
No Fan or door OPEN
Power off within ten seconds
Control Panel Message:
No Fan
PROBLEM CAUSE
Field Wiring or Breaker
UV door open
Pressure switch malfunction
No air flow
Panel not reading air flow
UV failure lamp flashes on and off
Control Panel Message:
Error
UV lamp failure or lamp ballast failure
SOLUTION
- Verify field wiring for proper
connections
- Check fuse at control panel
- Close door
- Check wiring
- Check air tube for blockage
- Replace pressure switch if
necessary
- Check fan for proper operation
- Check pressure switch
connection and tube
- Replace pressure switch if
defective
- Replace failed cassette with a
new one.
- Replace ballast if defective.
Capture Ray TM Operation & Maintenance & Service Manual 18
EXHAUST FIRE DAMPER ASSEMBLY
1. REMOVE GREASE FILTERS
2. UNRAVEL S.S. CABLE AT CLIP (A)
3. FEED LOOSE END OF CABLE THROUGH EYEBOLT AT CLIP (B), THEN BACK
THROUGH EYEBOLT AT CLIP (C)
4. HOLD FIRE DAMPER IN MAXIMUM OPEN POSITION TO ATTACH LINK AT POINT (D)
5. CLOSE "S" HOOKS AS REQUIRED
6. FOR FINAL ADJUSTMENT OF FIRE DAMPER TO ASSURE MAXIMUM OPEN POSTION,
USE EYE BOLTS AT CLIPS (A) AND (B) TO TIGHTEN FOR SLACK
VENTILATOR TOP
INSIDE THE EXHAUST PLENUM
CLIP (C)
CLIP (A)
COLLAR
#1 LINK
(D)
#2 LINK
FIRE DAMPER
#3 LINK
CLIP (B)
EYE BOLT
12 GAUGE STEEL
12 GAUGE STEEL
COLLAR
COLLAR HAS 1/2" FLANGE ON INSIDE
PERIMETER FOR DAMPER TO REST ON
BRACKET
W/ EYEBOLT
FUSIBLE
LINKS
(3)
S.S.
CABLE
PIVOT ROD
BACKET HOLDING
DAMPER
Capture Ray TM Operation & Maintenance & Service Manual 19
HALTON LIMITED WARRANTY
Halton (“Manufacturer”). Warrants only to its direct purchasers and to no others, that all products manufactured by the Manufacturer shall be free from defect in materials and workmanship for a period of twelve (12) months from the date of the original installation and start-up or eighteen (18) months from date of shipment, whichever occurs first. All products sold but not manufactured by Manufacturer will be warranted for a period of twelve (12) months from date of shipment.
For products manufactured by the Manufacturer we agree to pay any reasonable labor costs necessary to repair or replace, at Manufacturers option, defective parts or materials for a period of twelve (12) months from date of original installation and start-up or eighteen (18) months from date of shipment, whichever occurs first. All labor costs subject hereto shall be performed during standard work hours at straight-time rates.
For products sold but not manufactured by the Manufacturer we agree to pay any reasonable labor costs necessary to repair or replace, at Manufacturers option, defective parts or materials for a period of (90) days from date of original installation and start-up or (12) months from date of shipment, whichever occurs first. All labor costs subject hereto shall be performed during standard work hours at straighttime rates.
Purchaser shall pay incurred premium labor charge, including overtime, weekends and holidays.
Travel time, service charges, miscellaneous tools, material charges, and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer.
This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the installation and Care Instruction Manuals. Purchaser shall be solely responsible for adhering to the instructions and procedures set forth in the said instruction manuals.
This LIMITED WARRANTY SHALL NOT BE APPLICABLE to any damage or defect resulting from fire, flood, freezing or any Act of God, abuse, misuse, accident, neglect or failure to adhere to all instructions set forth in the installation and Care Instruction Manuals. Furthermore, this limited warranty shall not apply to any product that has been altered, unless such alteration has been approved in writing by a duly authorized representative of the manufacturer. In no event shall the manufacturer be liable for any loss, expense, personal injury or consequential damage, of any kind or character, as may result from a defect in material, and/or workmanship, however caused.
EXCEPT AS IS EXPRESSLY SET FORTH IN THIS LIMITED WARRANTY, MANUFACTURER MAKES
NO WARRANTY OF MARKETABILITY FOR FITNESS OR ANY PARTICULAR PURPOSE. NEITHER
DOES MANUFACTURER MAKE ANY WARRANTY, EXPRESSED OR IMPLIED, WITH RESPECT TO
PRODUCTS SOLD BY MANUFACTURER OR AS TO THE USE THEREOF.
Halton Company
101 Industrial Drive, Scottsville, 42164 USA
Tel: 270-237-5600 Fax: 270-237-5700
Website address www.haltoncompany.com
Halton Indoor Climate Systems, Ltd.
1021 Brevik Place • Mississauga, ON L4W 3R7 CANADA
Tel: 905-624-0301 Fax: 905-624-0301
Website address www.haltoncanada.com