BA01205S/04/EN/02.15

Produktversion 1.00.xx

71308243

Products Solutions

Operating Instructions

WirelessHART Test Kit SWT70

Test system for WirelessHART connections

Services

WirelessHART Test Kit SWT70

Table of contents

Revision history. . . . . . . . . . . . . . . . . . . . . . . . . 5

Registered trademarks. . . . . . . . . . . . . . . . . . . 5

1 Safety instructions. . . . . . . . . . . . . . . . . . 6

1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.2 Installation, commissioning and operation . . . . . . 6

1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.4 Declaration of Conformity . . . . . . . . . . . . . . . . . . . . 7

1.5 Radio approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.6 Technical improvement . . . . . . . . . . . . . . . . . . . . . . 8

1.7 Conventions used in this manual . . . . . . . . . . . . . . 9

2 Identification . . . . . . . . . . . . . . . . . . . . . 10

2.1 Unpacking the product . . . . . . . . . . . . . . . . . . . . . 10

2.1.1 Visual inspection . . . . . . . . . . . . . . . . . . . . 10

2.1.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . 10

2.1.3 Storage and transportation . . . . . . . . . . . 10

2.2 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.3 Ordering information . . . . . . . . . . . . . . . . . . . . . . . 11

2.4 Additional radio approvals . . . . . . . . . . . . . . . . . . 11

2.5 System requirements . . . . . . . . . . . . . . . . . . . . . . . 12

2.6 Licensing agreement . . . . . . . . . . . . . . . . . . . . . . . 12

3 Function and system design . . . . . . . . 13

4 Installation . . . . . . . . . . . . . . . . . . . . . . . 14

4.1 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 14

5 Commissioning . . . . . . . . . . . . . . . . . . . 15

5.1 Display and operating elements . . . . . . . . . . . . . 15

5.2 Inserting and connecting the battery unit . . . . . . 15

5.3 Connecting the HART modem and installing the modem driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

5.4 Installing the operating program . . . . . . . . . . . . . 17

5.5 Configuring the WirelessHART Test Kit . . . . . . . 18

6 Maintenance and repair. . . . . . . . . . . . 22

6.1 Battery units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

6.1.1 Replacement . . . . . . . . . . . . . . . . . . . . . . . . 22

6.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

6.3 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

6.4 Contact addresses at Endress+Hauser . . . . . . . . . 23

7 Troubleshooting . . . . . . . . . . . . . . . . . . 24

8 Technical data . . . . . . . . . . . . . . . . . . . . 25

8.1 Output/wireless interface . . . . . . . . . . . . . . . . . . 25

8.2 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

8.3 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

8.4 Mechanical construction . . . . . . . . . . . . . . . . . . . 27

8.5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

8.6 Certificates and approvals . . . . . . . . . . . . . . . . . . 28

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Endress + Hauser 3

WirelessHART Test Kit SWT70

4 Endress + Hauser

WirelessHART Test Kit SWT70

Revision history

Product version

1.00.00

1.00.xx

Manual Changes

BA01205S/04/en/01.12 Original

BA01205S/04/en/02.15 General

Remarks

Adaption CD/CI

All information about hazardous areas removed

Registered trademarks

HART ® , WirelessHART ®

Registered trademarks of the HART Communication Foundation, Austin, USA

Microsoft ® , Windows ® , Windows XP ® , Windows Vista ® , Windows 7 are registered trademarks of the Microsoft Corporation.

® and the Microsoft logo

Acrobat Reader ® is a registered trademark of Adobe Systems Incorporated.

All other brand and product names are trademarks or registered trademarks of the individual companies and organizations in question.

Endress + Hauser 5

Safety instructions

Applications

Battery unit

WirelessHART Test Kit SWT70

1 Safety instructions

1.1

Designated use

The WirelessHART Test Kit SWT70 is a test system for individual WirelessHART connections. The WirelessHART Test Kit consists of two WirelessHART test adapters

SWA70 with special test firmware, magnetic fittings and an operating program. The two

WirelessHART test adapters can be configured as a transmitter or receiver and are used to test and measure individual wireless connections in a WirelessHART network.

The WirelessHART test adapters SWA70 in the WirelessHART Test Kit SWT70 may not be used to operate field devices. The WirelessHART test adapters SWA70 may not be permanently installed in a facility or connected to a WirelessHART network.

1.2

Installation, commissioning and operation

The WirelessHART Test Kit SWT70 can be operated safely in compliance with the current technical safety standards and the applicable EU guidelines.

The WirelessHART Test Kit can be a source of danger if it is not mounted correctly or if it is used in applications for which it is not intended.

The WirelessHART Test Kit may only be installed, commissioned, operated and maintained by trained, qualified specialists authorized to perform such work by the facility's owneroperator. The specialist staff must have read and understood these Operating Instructions and must follow the instructions they contain. The devices may not be modified or repaired in any way.

These specifications also apply for the battery unit.

1.3

Operational safety

The WirelessHART Test Kit SWT70 meets the requirements of the EU guidelines for the various range of applications envisaged for the device. The permitted operating conditions

must be observed. See “Technical data” on page 25.

In the WirelessHART Test Kit, power is supplied to the WirelessHART test adapters via highpower lithium-thionyl chloride battery units. This has implications for operational safety and storage. Please refer to the hazardous materials regulations provided in the accompanying Safety Data Sheet (CD-ROM folder: Safety Data Sheet).

The battery units can remain in the test adapters. Once the testing period has elapsed, the test adapters quit wireless operation and therefore no additional energy is used.

Warning!

• Any tampering with the antenna, electronics or battery unit invalidates Endress+Hauser’s warranty along with the telecommunications approval.

6 Endress + Hauser

WirelessHART Test Kit SWT70

Maintenance

EC Declaration of

Conformity

/CE mark

Electromagnetic compatibility

Safety instructions

In the case of the WirelessHART Test Kit, the battery units are the only components that may be replaced. The WirelessHART Test Kit may not be repaired.If the device is faulty or

malfunctions, return it to Endress+Hauser. Follow the instructions outlined in the “Return” auf Seite 23. The battery unit must be removed before the device is returned.

1.4

Declaration of Conformity

All the Declarations of Conformity can be found on the accompanying CD-ROM in the

"Documentation\SWT70\Certificates" folder.

The WirelessHART test adapter SWA70 meets the legal requirements of the relevant

EC guidelines. Endress+Hauser confirms that the WirelessHART test adapter SWA70 has been successfully tested by affixing to it the CE mark.

All the modules are suitable for industrial use and meet the conditions of European Directive

2004/108/EC "Electromagnetic Compatibility":

• Interference emission:

EN 61326-1: 2006, Class B

Interference immunity:

EN 61326-1: 2006 Tab. 2 (Industry)

NE21

Endress + Hauser 7

Safety instructions WirelessHART Test Kit SWT70

Brazilian approval

Chinese approval

ETSI approval

(R&TTE approval)

FCC and IC approval

(IC=Industry of Canada)

Japanese approval

R

Mexican approval

1.5

Radio approvals

Caution!

• A distance of at least 20 cm must be maintained at all times between the device antenna and the body of the user or any other person in the vicinity irrespective of the application or use.

Note!

• Changes or modifications to the WirelessHART Test Kit that have not been expressly approved by Endress+Hauser will render invalid the user’s right to operate the test kit.

ANATEL 2759-11-7311 (EAN Number: 7898994191421)

“Este produto está homologado pela ANATEL, de acordo com os procedimentos regulamentados pela Resolução 242/2000, e atende aos requisitos técnicos aplicados.”

Para maiores informações, consulte o site da ANATEL www.anatel.gov.br

This device has been granted a type approval by the SRRC (State Radio Regulatory

Commission of P. R. China): CMIIT ID 2011DJ5309

This device meets the requirements of the EC Telecommunications Directive 1999/5/EC

• EN 300 328: V1.7.1 (2006-10)

• EN 301 489-1: V1.81. (2008)

• EN 301 489-17: V2.1.1 (2009)

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

This device has been granted a designation number by the Japanese Ministry of Internal

Affairs and Communications according to the Ordinance concerning Technical Regulations

(

Conformity Certification etc. of Specified Radio Equipment

)

• Article 2 clause 1 item 19

• Approval n°: 202WW09117711

This device should not be modified (otherwise the granted designation number will be invalid).

COFETEL RCEPNSW12-0650

La operación de este equipo está sujeta a las siguientes dos condiciones: (1) es posible que este equipo o dispositivo no cause interferencia perjudicial y (2) este equipo o dispositivo debe aceptar cualquier interferencia, incluyendo la que pueda causar su operación no deseada.

1.6

Technical improvement

Endress+Hauser reserves the right to make technical improvements to the hardware and software anytime without prior notice. Such improvements are not documented if they do not affect the operation of the device. A new version of the Operating Instructions is created if the improvements affect operation.

8 Endress + Hauser

WirelessHART Test Kit SWT70

Safety instructions

Safety instructions

1.7

Conventions used in this manual

Typographical emphasis and special symbols have been used to provide a clear structure to the contents of these Operating Instructions and to highlight important information.

Pay particular attention to the safety conventions and icons used in these Operating

Instructions.

Symbol Meaning

Danger!

This symbol alerts you to dangerous situations. Failure to heed the instructions will result in a serious or fatal injury.

Warning!

This symbol alerts you to dangerous situations. Failure to heed the instructions can result in a serious or fatal injury.

Caution!

This symbol alerts you to dangerous situations. Failure to heed the instructions can result in a mild to medium injury.

Note!

This symbol refers you to procedural information and other facts that do not result in physical injury.

Electrical symbols Symbol Meaning

Direct current

A terminal to which DC voltage is applied or through which direct current flows.

Alternating current

A terminal to which alternating voltage (sine-wave) is applied or through which alternating current flows.

Ground connection

A grounded terminal which, as far as the operator is concerned, is already grounded via a grounding system.

Protective ground connection

A terminal which must be connected to ground prior to connecting any other terminals.

Equipotential connection

A connection that has to be connected to the plant grounding system: This may be a potential equalization line or a star grounding system depending on national practice or company codes of practice.

Endress + Hauser 9

Identification

Storage

Transportation

WirelessHART Test Kit SWT70

2 Identification

2.1

Unpacking the product

2.1.1

Visual inspection

When unpacking the product:

• Check the packaging for visible signs of damage in transit.

• Remove the packaging carefully in order to prevent any damage.

• Keep the documentation supplied with the adapter in a safe place.

2.1.2

Scope of delivery

Check that the delivery is undamaged and that nothing is missing before you start commissioning.

The WirelessHART Test Kit is supplied in a case. The delivery comprises:

• 1 storage medium with the operating program

• 2 modified WirelessHART test adapters SWA70 with magnetic fittings

• These Operating Instructions

Warning!

• If you discover that the battery unit is damaged, proceed as described in the Safety Data

Sheet on the CD-ROM.

• If you discover that the WirelessHART Test Kit SWT70 is damaged, the test system may not be put into operation.

In this case, contact your Endress+Hauser sales partner. Where possible, return the device to Endress+Hauser in its original packaging.

2.1.3

Storage and transportation

While the WirelessHART Test Kit is a robust device, appropriate precautions must be taken to ensure proper storage and transportation:

Condition

Temperature

Special safety measures

WirelessHART Test Kit without battery units

–40 to +85°C/–40

None

to 185°F

Separate battery unit

Maximum: < 30 °C/86 °F

Recommended

1)

: < 21 °C/70 °F

Store in a cool, well-ventilated environment away from moisture, sources of heat, naked flames, food and beverages

1) A storage temperature < 21 °C/70 °F is recommended to minimize self-discharging of the battery unit.

When transporting the WirelessHART Test Kit it must be protected against strong vibrations or shock.

Warning!

• High-power lithium-thionyl chloride batteries are classified as a Class 9 hazardous material (HAZMAT Class 9: Miscellaneous).

10 Endress + Hauser

WirelessHART Test Kit SWT70 Identification

2.2

Nameplate

The nameplate is located on the side of the WirelessHART test adapter, and contains all the important information such as the order code, serial number and radio approvals. Additional information about the radio approval is provided on a separate adhesive label. See Figure 2-

2 on page   11.

1 2

Made in Germany, D- 79689 Maulburg

SWA70-I11A1A1+IKIWZ1 Ser.No.: XXXXXXXXXXX

-40°C

Tamb

+60°C

Dat.: 2010-02

XA506F-X

NEMA4

3

1 Order code

2 Serial number

3 Radio approval

Fig. 2-1: Nameplate (example)

2.3

Ordering information

The WirelessHART Test Kit SWT70 can be ordered with the following approvals:

• 71307754

An additional sticker identifies the test adapter as an integral part of a WirelessHART Test

Kit SWT70, so it is impossible to mix the test adapter up with a normal WirelessHART adapter SWA70.

2.4

Additional radio approvals

An adhesive label on the antenna lists additional radio approvals.

R

202WW09117711

CMMIT ID 2011DJ5309

Fig. 2-2: Location of the adhesive label that lists the additional radio approvals

Endress + Hauser 11

Identification WirelessHART Test Kit SWT70

2.5

System requirements

An operating program is supplied on a data storage medium for the WirelessHART Test Kit.

The operating program can be used with the following operating systems:

• Microsoft Windows 7 (32-bit, 64-bit)

• Microsoft Windows Vista Ultimate (32-bit)

• Microsoft Windows XP Service Pack 2 and 3 (32-bit)

Windows XP/Vista MUI packs (multilingual user interface) are not supported. If another language is required, you must install the corresponding version of Windows XP/Vista.

2.6

Licensing agreement

The complete licensing agreement can be found on the CD-ROM. The software required to read out data and commission the device is either available free of charge or is subject to the licensing conditions of the manufacturer. By installing the software on your computer you agree to accept the conditions of the specific licensing agreement.

12 Endress + Hauser

WirelessHART Test Kit SWT70 Function and system design

3 Function and system design

The WirelessHART Test Kit SWT70 is a test system for individual WirelessHART connections. The test system can either be used to solve problems in existing WirelessHART networks or used in advance for project planning. The test system works independently of existing WirelessHART networks.

The WirelessHART Test Kit SWT70 consists of two WirelessHART test adapters SWA70 with a special test firmware, magnetic fittings and an operating program. Both WirelessHART test adapters can be configured as a transmitter or receiver. The transmitter and receiver can be easily mounted at the desired position using the magnetic fittings.

The transmitter and receiver are configured one after another via the operating program.

The transmitter transmits test packets cyclically to all the configured channels. The packets received by the receiver are evaluated statistically, and the signal quality is determined in this way.

A

1

B

2

1 3

Endress + Hauser

2

1

Fig. 3-1: Structure of a WirelessHART Test Kit SWT70

Top (A): WirelessHART test adapter SWA70 configured as a transmitter

Bottom (B): WirelessHART test adapter SWA70 configured as a receiver and test phase

WirelessHART test adapter SWA70 as transmitter

2 HART modem e.g. FXA195

3 WirelessHART test adapter SWA70 as receiver

13

Installation WirelessHART Test Kit SWT70

4 Installation

The WirelessHART test adapters of the WirelessHART Test Kit are mounted on magnetic surfaces using the magnetic fitting.

4.1

Installation conditions

Note!

In order to avoid attenuation of the electromagnetic waves and any resulting impairment in the operation of the WirelessHART test adapter, the following must be observed when mounting the adapter:

• The antenna must be at least 6 cm away from a wall or post (1).

• The antenna of the WirelessHART test adapter should never be located between a wall/ post and the housing (2).

• There must be a distance of at least 6 cm between the antenna and any metal material running parallel to it (3).

• The antenna must be aligned vertically, and point upwards (4).

• Ideally, there should not be any wall or similar between the transmitter and receiver.

Wall 1 Wall 2

Post

3

Fig. 4-1: General installation instructions

4

14 Endress + Hauser

WirelessHART Test Kit SWT70 Commissioning

5 Commissioning

5.1

Display and operating elements

Note!

• To avoid any restrictions in the functions, do not press the push button.

• All the display and operating elements inside the WirelessHART test adapter do not have any function on account of the special test firmware.

5.2

Inserting and connecting the battery unit

When you put the unit into operation for the first time, you must open the test adapters in order to insert the battery units. Please pay attention to the operational safety instructions.

See “Operational safety” on page 6.

Note!

• You require a Torx T10 to open the housing.

4 3 2 1

6

5

Fig. 5-1: Battery compartment with housing open

1 Light emitting diodes (no function)

2 Push button (do not press)

3 Socket for battery connector

4 Battery compartment

5 Terminals 1 to 6 (no function)

6 Terminals (no function)

Endress + Hauser 15

Commissioning WirelessHART Test Kit SWT70

Proceed as follows to connect the battery unit:

1. Insert the battery unit into the battery compartment, making sure that the battery unit engages with a click.

2. Insert the battery connector into the socket.

3. Close the housing and tighten the housing screws.

Note!

• The battery unit can remain connected. So little energy is consumed that the battery unit has a service life of maximum 10 years if the WirelessHART Test Kit is not used.

5.3

Connecting the HART modem and installing the modem driver

The WirelessHART test adapters must be connected to a HART modem for configuration and measurement purposes. The driver for the HART modem must be installed on the same computer that runs the "WirelessHART Connectivity Tester" operating program.

4

1

2

3

Fig. 5-2: Connecting a WirelessHART test adapter to a computer via a modem

1 Computer with "WirelessHART Connectivity Tester" operating program

2 Serial port e.g. USB or RS-232

3 HART modem e.g. FXA195

4 WirelessHART test adapter, transmitter or receiver of the WirelessHART Test Kit

Proceed as follows to connect the HART modem and to install the modem driver if it is not already installed:

1.

Connect the HART modem to the terminal lugs of the cable gland of the WirelessHART test adapter.

– If the modem has a built-in communication resistor, this resistor must be switched on.

– If the modem does not have a built-in communication resistor, proceed as described

in the "Troubleshooting" section. See “Troubleshooting” on page 24., Number 1.

16 Endress + Hauser

WirelessHART Test Kit SWT70 Commissioning

2.

Start the computer and then plug the connector of the HART modem into the appropriate port.

– If you use a USB port, the computer recognizes new hardware. The device driver must be installed as described in Steps 3-6.

– If you use an RS-232 port, the port is automatically connected to the COM communication port. Steps 3-7 then do not apply.

3.

Click

Ok

in the dialog box that appears to start the

Found New Hardware Wizard

.

– Select the Not this time option and press Next.

4. Insert the CD containing the modem driver into the CD drive and press Next.

5. Follow the instructions of the Wizard to install the device driver.

6. After the installation, you must unplug the USB connector and restart your computer.

7.

If you insert the USB plug back into the USB port of your computer, the computer will recognize the HART modem.

– To check the communication port, select Settings > Control Panel > System .

– In the System Properties dialog box, select the Hardware tab and click Device

Manager .

– Open Ports (COM LPT) and check the communication port that has been assigned to the HART modem.

5.4

Installing the operating program

Proceed as follows to install the operating program:

1.

Insert the CD supplied into the CD drive of your computer.

2.

A Setup Wizard starts.

– Select the WirelessHART Connectivity Tester option .

– If the Setup Wizard does not start automatically, right-click the CD drive and select

Autoplay .

3. Click Setup.

4. The Setup Wizard is started.

Endress + Hauser

– Click Next to continue the installation.

5.

The

License Agreement

is displayed. Read the license agreement carefully.

– Select I agree and click Next to continue.

– Select I Do Not Agree to reject the agreement. Click Cancel to quit the installation.

17

Commissioning WirelessHART Test Kit SWT70

6.

The

Select Installation Folder

dialog box is displayed. An installation folder is suggested in the

Folder

field.

– Click Browse to select another installation folder.

– Chose Everyone or Just me as the user.

– Click Next to continue.

7.

The

Confirm Installation

dialog box is displayed.

– Click Next to start the installation.

– A status window indicates the progress of the installation process.

8. The following dialog box appears when the installation is finished.

Starting the operating program

– Click Close to close the dialog box and complete the installation.

5.5

Configuring the WirelessHART Test Kit

1.

Mount one of the two WirelessHART test adapters at the position of the transmitter.

2. Connect the WirelessHART test adapter to the computer via the HART modem.

3. Start the WirelessHART Connectivity Tester operating program by either clicking the icon on the desktop or via the menu Start/Windows Icon > All Programs >

Endress+Hauser > WirelessHART Connectivity Tester.

4. The Select the Customer dialog box is displayed.

– Select a customer via the Customer field or enter a new customer name in the field.

– Click Ok . A folder is created for every customer. Path: My Files\WirelessHART

Connectivity Tester\[Customer Name]. All the results of the measurement are saved to this folder.

18 Endress + Hauser

WirelessHART Test Kit SWT70

5. The Start dialog box is displayed.

Commissioning

Connecting the transmitter

6.

Select the Start Transmitter option to configure the WirelessHART test adapter as a transmitter. Alternatively you can also choose from the following options:

– Start Receiver: configure the WirelessHART adapter as a receiver. The transmitter must have already been activated with the same computer.

– Do Maintenance: read information from the WirelessHART test adapter and confirm battery change.

7. The Connect to Transmitter dialog box is displayed.

Configuring the transmitter

– In the COM-Port field, select the port to which the HART modem is connected.

– Click Connect to establish the connection between the WirelessHART test adapter and the HART modem. The Status field displays the communication status.

Note!

• You can only establish one connection to a WirelessHART test adapter of the test system via the operating program. It is not possible to connect to other HART or WirelessHART devices.

8. Once the connection has been established successfully, the Transmitter dialog box is displayed.

Endress + Hauser 19

Commissioning WirelessHART Test Kit SWT70

Connecting the receiver

Configure the transmitter:

– Enter the location of the transmitter in the Location field.

– In the Duration of Test field, enter the total duration of the test from the current transmission position. Please note the following.

– Select or deselect the channels to be tested in the Blacklist field. Channels 1 to 15 are enabled by default. Channel 16 is generally not used by WirelessHART and is therefore disabled.

Note!

• Enter the duration of the test via the Duration of Test field. If the duration of the test is

≤  5 hours, the channel is changed every 15 seconds (short-term test). If the duration of the test is > 5 hours, the channel is changed every minute (long-term test).

9. Click Start to start the test with the configured parameters. Once the test has been started successfully, the status and the remaining operating life of the battery unit are updated in the Transmitter Status field. The transmitter is configured.

10.Click Connect to Receiver . The Connect to Receiver dialog box is displayed.

11.Disconnect the first WirelessHART test adapter (transmitter) from the HART modem.

12.Mount the other WirelessHART test adapter at the position of the receiver.

13.Connect the WirelessHART test adapter to the computer via the HART modem.

14.Make the following settings in the Connect to Receiver dialog box:

– In the Com-Port field, select the port to which the HART modem is connected. If you have not changed the port you can make the settings as explained in Step 7.

– Click Connect to establish the connection between the WirelessHART test adapter and the HART modem. The Communication Status field displays the communication status.

20 Endress + Hauser

WirelessHART Test Kit SWT70

15.The Receiver dialog box appears once you click Connect .

Commissioning

Configuring the receiver

16. Configure the receiver:

– Enter the location of the receiver in the Location field.

– Enter the number of test cycles in the No. Testcycles field.

– If necessary, enter the GPS coordinates in the GPS field. Alternatively you can load the coordinates by clicking the Load GPS Coordinates button if your computer supports this function.

17.Click Start to start the connection test.

18.You can stop the connection test any time you wish. To do so, click Stop.

Note!

• The receiver must remain connected to the modem during the connection test.

Displaying the results of the connection test

The results of the connection test are saved to a log file. Path: My Files\Wireless HART Connectivity

Tester\ [Customer Name]\[Transmitter Location]_[Receiver_Location]_[Date and Time]\

The results are also displayed in the Receiver dialog box:

• The Receiver Status field displays the current status of the receiver and the remaining operating hours with the installed battery.

• The Transmitter Status field displays the current status of the transmitter and the remaining transmission time.

• The Results field graphically and numerically displays the number of test packets received per channel and on average.

• The progress bar displays the time until the next evaluation of the measurement results.

Endress + Hauser 21

Maintenance and repair WirelessHART Test Kit SWT70

6 Maintenance and repair

With the exception of replacing the battery unit, no special maintenance work is required for the WirelessHART test adapter.

6.1

Battery units

The battery unit is protected against short circuiting. Following a short-circuit, the battery unit does not supply any more power and must be replaced.

Note!

• A low ambient temperature causes a voltage drop within the battery unit.

• A high ambient temperature causes the energy of the battery unit to be limited by selfdischarge.

• See the "Ambient temperature range" section on page   25.

6.1.1

Replacement

You can order the battery units from your local Endress+Hauser sales partner using order number

71092238.

Note!

• You must first open the housing to replace the battery unit.

Proceed as follows to replace the battery unit:

1.

Open the housing of the WirelessHART test adapter by unscrewing and removing the four housing screws.

2. Remove the connecting cable for the battery unit from the socket on the PCB cover.

3. Simultaneously press the two clips of the battery unit towards the middle of the battery unit and remove the unit.

4. Insert the new battery unit into the compartment. In doing so, ensure that the two clips of the battery unit make an audible click when engaging in the indentations at the top and bottom of the compartment.

5. Insert the connecting cable for the battery unit into the socket on the PCB cover.

22 Endress + Hauser

WirelessHART Test Kit SWT70 Maintenance and repair

6.2

Disposal

The WirelessHART Test Kit is equipped with a non-rechargeable, high-power lithiumthionyl chloride battery unit. The battery unit is non-hazardous when used according to the recommendations of the manufacturer. It does, however, contain hazardous substances.

Please observe national regulations, particularly those governing the disposal of lithiumthionyl chloride high-power batteries in your country, and pay attention to the accompanying Safety Data Sheet (CD-ROM folder: Material Safety Data Sheet).

In Germany there is a law that regulates the return of used batteries. You can return your battery unit to Batterien-Montage-Zentrum GmbH (BMZ), a company specializing in batteries

(www.bmz-gmbh.de). Please observe the German regulations when returning battery units in Germany. The sender bears the costs incurred.

6.3

Return

The measuring device must be returned if repairs or a factory calibration are required, or if the wrong measuring device has been ordered or delivered.

According to legal regulations Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with the medium.

To ensure the safe, professional and swift return of your device, please refer to the applicable procedures and basic conditions on the Endress+Hauser website: www.services.endress.com/return-material

In the case of devices with a battery unit, the battery unit must be removed before the device is returned.

Warning!

• If Endress+Hauser requests you to return the battery unit, please pay attention to the accompanying Safety Data Sheet and the local transportation conditions.

6.4

Contact addresses at Endress+Hauser

Contact addresses can be found on our homepage: www.addresses.endress.com. If you have any questions, please contact your Endress+Hauser branch office.

Endress + Hauser 23

Troubleshooting WirelessHART Test Kit SWT70

7 Troubleshooting

The table below lists problems which might occur during commissioning and operation of the WirelessHART Test Kit.

Problem

1 The "WirelessHART Connectivity Tester" operating program communicates with the test adapter via a HART modem. The operating program cannot find the WirelessHART test adapter.

Solution

• The modem's output signal is too high.

– Connect a resistor parallel to the modem as indicated in the diagram. For this purpose, you can, for example, use the communication resistor that is built into many modems.

HART modem

250 Ω

Terminals of the

WirelessHART test adapter

2 The WirelessHART test adapter cannot connect to the operating program.

3 The WirelessHART test adapters of the

WirelessHART Test Kit cannot communicate with one another. No results are displayed in the

"Receiver" dialog box of the "WirelessHART

Connectivity Tester" operating program.

• The battery unit is empty or not plugged in.

– Check the "power" connector and replace the battery unit if necessary.

– A simple check is to shake the battery unit: if you hear liquid this means that the battery unit still has life. Following a short-circuit, however, the battery no longer works even if liquid can be heard.

• The WirelessHART test adapters are not mounted correctly.

– Check that the WirelessHART test adapters are

mounted correctly. See “Installation” on page 14.

24 Endress + Hauser

WirelessHART Test Kit SWT70

8 Technical data

8.1

Output/wireless interface

Technical data

Communication interface WirelessHART communication interface

Transmission rate Nominal 250 kBits/s

2.4 GHz (ISM band) Frequency band

Transmission range Under reference operating conditions: outdoor 250 m, indoor 50 m

8.2

Power supply

Power supply

Battery power

Battery life

Special high-power lithium-thionyl battery unit, long battery life

19 Ah nominal capacity at 20°C

• up to 10 years, depending on the testing frequency and the environmental conditions

• The battery unit can remain connected. So little energy is consumed that the battery unit has a service life of maximum 10 years if the WirelessHART Test Kit is not used.

8.3

Environment

Climate class

Ambient temperature range

Storage temperature

Vibration resistance

Shock resistance

EN 60721-3-4: 4K4H, suitable for stationary use in locations exposed to weather conditions

• –40 to +80 °C/-40 to +176 °F

• The battery unit capacity decreases rapidly at temperatures below –30 °C/-22 °F.

• Without battery unit:

–40 to +85°C/ -40 to +185 °F

• With battery unit: below +21°C/+70°F (recommended to minimize self discharging)

EN 60068-2-64: 20 Hz  f  2000 Hz: 0.01g²/Hz

EN 60068-2-27: 15 g, 11 ms

Endress + Hauser 25

Technical data

Electromagnetic compatibility

Telecommunication approval

WirelessHART Test Kit SWT70

All the modules are suitable for industrial use and meet the conditions of the European

Directive 2004/108/EU "Electromagnetic Compatibility":

• EN 61326:

– Interference immunity: EN 61326-1, 2006, Tab. 2 (Industry)

– Interference emission: EN 61326-1, 2006, Class B

• NAMUR recommendation EMC (NE 21), "B" ESD behavior

The WirelessHART test adapter meets the requirements of the EU Directive 99/5/EC

"Telecommunications"

• EN 300 328: V1.7.1 (2006-10)

• EN 301 489-17: V1.8.1 (2008)

• EN 301 489-17: V2.1.1 (2009)

26 Endress + Hauser

WirelessHART Test Kit SWT70

Design/dimensions

Technical data

8.4

Mechanical construction

With antenna pointing vertically upwards (B x H x D): 111.5 x 189.9 x 92.8 (mm)

Dimensions in mm

25.4 mm = 1 inch

8

Weight

Material

Degree of protection

Antenna

92.8

21.9

26.1

92

111.5

Fig. 8-1: Housing dimensions of the WirelessHART test adapter SWA70

0.785 kg with battery unit

• Housing: polyester

• Color: pale-gray, RAL 7035 with blue logo

F32 polyester housing: IP65/IP66; NEMA Type 4

• Omnidirectional dipole antenna

• The antenna must be aligned vertically, and point upwards.

Endress + Hauser 27

Technical data

Configuration

CE mark

Telecommunication approval

WirelessHART Test Kit SWT70

8.5

Operation

Operating program: WirelessHART Connectivity Tester

8.6

Certificates and approvals

The WirelessHART test adapter SWA70 meets the legal requirements of the relevant

EC guidelines. Endress+Hauser confirms that the WirelessHART test adapter SWA70 has been successfully tested by affixing to it the CE mark.

See “Radio approvals” on page 8.

• Brazil: ANATEL 2759-11-7311 (EAN Number: 7898994191421)

• China: CMIIT ID (SRRC)

• ETSI (R&TTE)

• FCC Part 15.247 for wireless applications in the 2.4 GHz frequency band

• Japan: Ministry of internal affairs and communication

• Mexico: COFETEL RCEPNSW12-0650

• Other national certificates are available on request.

Please pay attention to the following additional national regulations:

Country

Bulgaria

Italy

Norway

Romania

Latvia

Regulation

General authorization is required for use outdoors and in public

General authorization is required if using outside own premises

Use can be restricted within a 20 km radius of the center of Ny-Alesund

Use as auxiliary device; special license is required

Outside use of the 2.4 GHz frequency band requires national approval

28 Endress + Hauser

Index

Index

A

Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . 25

Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

B

Battery compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Battery connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Battery life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Battery power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Battery unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Inserting and connecting . . . . . . . . . . . . . . . . . . . . . . 15

Replacing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Brazilian approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

C

CE mark. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 28

Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Chinese approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Climate class. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 15

Communication interface . . . . . . . . . . . . . . . . . . . . . . . . . 25

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Contact addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

D

Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . 7

Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Designated use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Disposal

Battery unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

E

EC Declaration of Conformity. . . . . . . . . . . . . . . . . . . . . . . 7

Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . 7, 26

Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

ETSI approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

F

FCC and IC approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Frequency band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

H

HART modem

Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Endress + Hauser

I

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 14

Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

J

Japanese approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

L

Licensing agreement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Light emitting diodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

M

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 22

Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . . . 27

Mexican approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

N

Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

O

Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 28

Operational safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

P

Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Push button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

R

R&TTE approval. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Radio approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 11

Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Replacing

Battery unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

S

Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 9

Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

T

Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Telecommunication approval . . . . . . . . . . . . . . . . . . 26, 28

Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Transmission range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Transmission rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Transportation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Type of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

29

Index

U

Unpacking the product . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

V

Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Visual inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

W

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

WirelessHART Test Kit

Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

30 Endress + Hauser

www.addresses.endress.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals