User’s
Manual Model EJA210A and EJA220A
Flange Mounted Differential
Pressure Transmitters
IM 01C21C01-01E
Yokogawa Electric Corporation
IM 01C21C01-01E
10th Edition
CONTENTS
CONTENTS
Model and Specifications Check ......................................................... 2-1
Selecting the Installation Location ...................................................... 2-1
Pressure Connection ........................................................................... 2-2
Waterproofing of Cable Conduit Connections .................................... 2-2
Restrictions on Use of Radio Transceiver .......................................... 2-2
Insulation Resistance and Dielectric Strength Test ............................ 2-2
Installation of Explosion Protected Type ............................................ 2-3
FM Approval ................................................................................. 2-3
CSA Certification .......................................................................... 2-5
IECEx Certification ....................................................................... 2-6
CENELEC ATEX (KEMA) Certification ........................................ 2-8
2.10 EMC Conformity Standards .............................................................. 2-10
2.11 PED (Pressure Equipment Directive) ............................................... 2-10
Rotating Transmitter Section .............................................................. 4-1
Changing the Direction of Integral Indicator ....................................... 4-2
Affixing the Teflon Film ....................................................................... 4-2
INSTALLING IMPULSE PIPING ................................................................... 5-1
Impulse Piping Installation Precautions .............................................. 5-1
Connecting Impulse Piping to the Transmitter ............................. 5-1
Routing the Impulse Piping .......................................................... 5-1
Impulse Piping Connection Examples ................................................ 5-2
Selecting the Wiring Materials ............................................................ 6-1
Connections of External Wiring to Terminal Box ................................ 6-1
Power Supply Wiring Connection ................................................ 6-1
External Indicator Connection ...................................................... 6-1
BRAIN TERMINAL BT200 Connection ........................................ 6-1
Check Meter Connection .............................................................. 6-2
FD No. IM 01C21C01-01E
10th Edition: Jan. 2008(KP)
All Rights Reserved, Copyright © 1997, Yokogawa Electric Corporation i IM 01C21C01-01E
CONTENTS
Loop Configuration ....................................................................... 6-2
(1) General-use Type and Flameproof Type ..................................... 6-2
(2) Intrinsically Safe Type ................................................................. 6-2
Wiring Installation ......................................................................... 6-2
(1) General-use Type and Intrinsically Safe Type ............................. 6-2
(2) Flameproof Type ......................................................................... 6-3
Power Supply Voltage and Load Resistance ..................................... 6-3
Preparation for Starting Operation ...................................................... 7-1
Zero Point Adjustment ........................................................................ 7-2
Shutting Down Operation .................................................................... 7-3
Venting or Draining Transmitter Pressure-detector Section ............... 7-3
Draining Condensate .................................................................... 7-4
Venting Gas .................................................................................. 7-4
Setting the Range Using the Range-setting Switch ........................... 7-4
BRAIN TERMINAL BT200 OPERATION ..................................................... 8-1
BT200 Operation Precautions ............................................................. 8-1
Connecting the BT200 ................................................................. 8-1
Conditions of Communication Line .............................................. 8-1
BT200 Operating Procedures ............................................................. 8-1
Key Layout and Screen Display ................................................... 8-1
Operating Key Functions .............................................................. 8-2
(1) Alphanumeric Keys and Shift Keys ............................................. 8-2
(2) Function Keys ............................................................................. 8-2
Calling Up Menu Addresses Using the Operating Keys .............. 8-3
Setting Parameters Using the BT200 ................................................. 8-4
Parameter Summary .................................................................... 8-4
Parameter Usage and Selection .................................................. 8-6
Setting Parameters ....................................................................... 8-7
(1) Tag No. Setup ............................................................................. 8-7
(2) Calibration Range Setup ............................................................. 8-7
(3) Damping Time Constant Setup ................................................... 8-8
(4) Output Signal Low Cut Mode Setup ............................................ 8-9
(5) Integral Indicator Scale Setup ..................................................... 8-9
(6) Unit Setup for Displayed Temperature ...................................... 8-11
(7) Unit Setup for Displayed Static Pressure .................................. 8-11
(8) Operation Mode Setup .............................................................. 8-11
(9) Output Status Display/Setup when a CPU Failure .................... 8-12
(10) Output Status Setup when a Hardware Error Occurs ............... 8-12
(11) Range Change while Applying Actual Inputs ............................ 8-12
(12) Zero Point Adjustment ............................................................... 8-13
(13) Test Output Setup ..................................................................... 8-14
(14) User Memo Fields ..................................................................... 8-15
ii IM 01C21C01-01E
CONTENTS
Displaying Data Using the BT200 ..................................................... 8-15
Displaying Measured Data ......................................................... 8-15
Display Transmitter Model and Specifications ........................... 8-15
Checking for Problems ............................................................... 8-16
(1) Identifying Problems with BT200 .............................................. 8-16
(2) Checking with Integral Indicator ................................................ 8-17
Errors and Countermeasures ..................................................... 8-18
Calibration Instruments Selection ....................................................... 9-1
Disassembly and Reassembly ............................................................ 9-3
Replacing the Integral Indicator ................................................... 9-3
Replacing the CPU Board Assembly ........................................... 9-4
Replacing the Process Connector Gasket ................................... 9-5
Basic Troubleshooting .................................................................. 9-5
Troubleshooting Flow Charts ....................................................... 9-6
10. GENERAL SPECIFICATIONS .................................................................... 10-1
Customer Maintenance Parts List
DPharp EJA Series Transmitter Section ........................ CMPL 01C21A01-02E
Model EJA210A and EJA220A Flange Mounted
Differential Pressure Transmitter ................................... CMPL 01C21C01-01E
iii IM 01C21C01-01E
1. INTRODUCTION
1.
INTRODUCTION
Thank you for purchasing the DPharp electronic pressure transmitter.
The DPharp Pressure Transmitters are precisely calibrated at the factory before shipment. To ensure correct and efficient use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
Regarding This Manual
• This manual should be passed on to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.
• The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instruments.
• Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
NOTE
For F OUNDATION Fieldbus TM , PROFIBUS PA and
HART protocol versions, please refer to IM
01C22T02-01E, IM 01C22T03-00E and IM
01C22T01-01E respectively, in addition to this manual.
• The following safety symbol marks are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices .
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
Direct current
1-1
1.1 For Safe Use of Product
For the protection and safety of the operator and the instrument or the system including the instrument, please be sure to follow the instructions on safety described in this manual when handling this instrument. In case the instrument is handled in contradiction to these instructions, Yokogawa does not guarantee safety. Please give your attention to the followings.
(a) Installation
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about INSTALLATION are not permitted for operators.
IM 01C21C01-01E
• In case of high process temperature, care should be taken not to burn yourself because the surface of body and case reaches a high temperature.
• The instrument installed in the process is under pressure. Never loosen the process connector bolts to avoid the dangerous spouting of process fluid.
• During draining condensate from the pressuredetector section, take appropriate care to avoid contact with the skin, eyes or body, or inhalation of vapors, if the accumulated process fluid may be toxic or otherwise harmful.
• When removing the instrument from hazardous processes, avoid contact with the fluid and the interior of the meter.
• All installation shall comply with local installation requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about WIRING are not permitted for operators.
• Please confirm that voltages between the power supply and the instrument before connecting the power cables and that the cables are not powered before connecting.
(c) Operation
• Wait 10 min. after power is turned off, before opening the covers.
(d) Maintenance
• Please do not carry out except being written to a maintenance descriptions. When these procedures are needed, please contact nearest YOKOGAWA office.
• Care should be taken to prevent the build up of drift, dust or other material on the display glass and name plate. In case of its maintenance, soft and dry cloth is used.
(e) Explosion Protected Type Instrument
• Users of explosion proof instruments should refer first to section 2.9 (Installation of an Explosion
Protected Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.
1. INTRODUCTION
(f) Modification
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.
1.2 Warranty
• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurred during the warranty period shall basically be repaired free of charge.
• In case of problems, the customer should contact the
Yokogawa representative from which the instrument was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• Responsible party for repair cost for the problems shall be determined by Yokogawa based on our investigation.
• The Purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by the purchaser.
- Failure or damage due to improper handling, use or storage which is out of design conditions.
- Use of the product in question in a location not conforming to the standards specified by
Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earthquakes, storms/floods, thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
1-2 IM 01C21C01-01E
1.3 ATEX Documentation
This procedure is only applicable to the countries in
European Union.
GB
All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative.
DK
Alle brugervejledninger for produkter relateret til
ATEX Ex er tilgængelige på engelsk, tysk og fransk.
Skulle De ønske yderligere oplysninger om håndtering af Ex produkter på eget sprog, kan De rette henvendelse herom til den nærmeste Yokogawa afdeling eller forhandler.
I
Tutti i manuali operativi di prodotti ATEX contrassegnati con Ex sono disponibili in inglese, tedesco e francese. Se si desidera ricevere i manuali operativi di prodotti Ex in lingua locale, mettersi in contatto con l’ufficio Yokogawa più vicino o con un rappresentante.
E
Todos los manuales de instrucciones para los productos antiexplosivos de ATEX están disponibles en inglés, alemán y francés. Si desea solicitar las instrucciones de estos artículos antiexplosivos en su idioma local, deberá ponerse en contacto con la oficina o el representante de Yokogawa más cercano.
NL
Alle handleidingen voor producten die te maken hebben met ATEX explosiebeveiliging (Ex) zijn verkrijgbaar in het Engels, Duits en Frans. Neem, indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal, contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger.
1-3
1. INTRODUCTION
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet ovat saatavilla englannin-, saksan- ja ranskankielisinä.
Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita omalla paikallisella kielellännne, ottakaa yhteyttä lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos produtos
Ex da ATEX estão disponíveis em Inglês, Alemão e
Francês. Se necessitar de instruções na sua língua relacionadas com produtos Ex, deverá entrar em contacto com a delegação mais próxima ou com um representante da Yokogawa.
F
Tous les manuels d’instruction des produits ATEX Ex sont disponibles en langue anglaise, allemande et française. Si vous nécessitez des instructions relatives aux produits Ex dans votre langue, veuillez bien contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene
Produkte stehen in den Sprachen Englisch, Deutsch und Französisch zur Verfügung. Sollten Sie die
Betriebsanleitungen für Ex-Produkte in Ihrer
Landessprache benötigen, setzen Sie sich bitte mit
Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex (explosionssäkra) produkter är tillgängliga på engelska, tyska och franska. Om Ni behöver instruktioner för dessa explosionssäkra produkter på annat språk, skall Ni kontakta närmaste Yokogawakontor eller representant.
GR
ATEX Ex
, .
Ex
Yokogawa .
IM 01C21C01-01E
LT
LV
EST
SK
CZ
1. INTRODUCTION
PL
1-4
RO
M
SLO
H
BG
IM 01C21C01-01E
2. HANDLING CAUTIONS
2.
HANDLING CAUTIONS
This chapter describes important cautions regarding how to handle the transmitter. Read carefully before using the transmitter.
The EJA-A Series pressure transmitters are thoroughly tested at the factory before shipment. When the transmitter is delivered, visually check them to make sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware shown in Figure 2.1 is included. If the transmitter was ordered without the mounting bracket or without the process connector, the transmitter mounting hardware is not included. After checking the transmitter, repack it in the way it was delivered until installation.
Process connector
Bolt Process connector gasket
F0201.EPS
Figure 2.1 Transmitter Mounting Hardware
2.1 Model and Specifications
Check
The model name and specifications are indicated on the name plate attached to the case. If the reverse operating mode was ordered (reverse signal), ‘REVERSE’ will be inscribed in field *1.
: Refer to USER'S MANUAL
F0202.EPS
Figure 2.2 Name Plate
2.2 Unpacking
When moving the transmitter to the installation site, keep it in its original packaging. Then, unpack the transmitter there to avoid damage on the way.
2.3 Storage
The following precautions must be observed when storing the instrument, especially for a long period.
(a) Select a storage area which meets the following conditions:
• It is not exposed to rain or water.
• It suffers minimum vibration and shock.
• It has an ambient temperature and relative humidity within the following ranges.
Ambient temperature:
–40 to 85
°
C without integral indicator
–30 to 80
°
C with integral indicator
Relative humidity:
5% to 100% R.H. (at 40
°
C)
Preferred temperature and humidity: approx. 25
°
C and 65% R.H.
(b) When storing the transmitter, repack it as nearly as possible to the way it was packed when delivered from the factory.
(c) If storing a transmitter that has been used, thoroughly clean the chambers inside the cover flanges, so that no measured fluid remains in it. Also make sure before storing that the pressure-detector and transmitter section are securely mounted.
2.4 Selecting the Installation
Location
The transmitter is designed to withstand severe environmental conditions. However, to ensure stable and accurate operation for years, observe the following precautions when selecting an installation location.
(a) Ambient Temperature
Avoid locations subject to wide temperature variations or a significant temperature gradient. If the location is exposed to radiant heat from plant equipments, provide adequate thermal insulation and/or ventilation.
(b) Ambient Atmosphere
Avoid installing the transmitter in a corrosive atmosphere. If the transmitter must be installed in a corrosive atmosphere, there must be adequate ventilation as well as measures to prevent intrusion or stagnation of rain water in conduits.
IM 01C21C01-01E 2-1
(c) Shock and Vibration
Select an installation site suffering minimum shock and vibration (although the transmitter is designed to be relatively resistant to shock and vibration).
(d) Installation of Explosion-protected Transmitters
Explosion-protected transmitters can be installed in hazardous areas according to the types of gases for which they are certified. See Subsection 2.9
“Installation of Explosion Protected Type Transmitters.”
2.5 Pressure Connection
WARNING
• Instrument installed in the process is under pressure. Never loosen the process connector bolts to avoid the dangerous spouting of process fluid.
• During draining condensate from the pressuredetector section, take appropriate care to avoid contact with the skin, eyes or body, or inhalation of vapors, if the accumulated process fluid may be toxic or otherwise harmful.
The following precautions must be observed in order to safely operate the transmitter under pressure.
(a) Make sure that the two process connector bolts are tightened firmly.
(b) Make sure that there are no leaks in the impulse piping.
(c) Never apply a pressure higher than the specified maximum working pressure.
2.6 Waterproofing of Cable
Conduit Connections
Apply a non-hardening sealant to the threads to waterproof the transmitter cable conduit connections.
(See Figure 6.4.2a, 6.4.2b and 6.4.2c.)
2.7 Restrictions on Use of Radio
Transceiver
IMPORTANT
Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test for such
2. HANDLING CAUTIONS effects, bring the transceiver in use slowly from a distance of several meters from the transmitter, and observe the measurement loop for noise effects. Thereafter, always use the transceiver outside the area affected by noise.
2.8 Insulation Resistance and
Dielectric Strength Test
Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required.
However, if required, observe the following precautions in the test procedures.
(a) Do not perform such tests more frequently than is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.
(b) Never apply a voltage exceeding 500 V DC (100 V
DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding
500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.
(c) Before conducting these tests, disconnect all signal lines from the transmitter terminals. Perform the tests in the following procedure:
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted
SUPPLY terminals and the minus (–) leadwire to the grounding terminal.
3) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied short as possible to verify that the insulation resistance is at least 20 M 1 .
4) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 k 1 resistor between the grounding terminal and the shortcircuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2-2 IM 01C21C01-01E
2. HANDLING CAUTIONS
2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specified voltage.
4) When the specified voltage is reached, hold it for one minute.
5) After completing this test, slowly decrease the voltage to avoid any voltage surges.
2.9 Installation of Explosion
Protected Type
In this section, further requirements and differences and for explosionproof type instrument are described.
For explosionproof type instrument, the description in this chapter is prior to other description in this users manual.
For the intrinsically safe equipment and explosionproof equipment, in case the instrument is not restored to its original condition after any repair or modification undertaken by the customer, intrinsically safe construction or explosionproof construction is damaged and may cause dangerous condition. Please contact
Yokogawa for any repair or modification required to the instrument.
NOTE
For F OUNDATION Fieldbus and PROFIBUS PA explosion protected type, please refer to IM
01C22T02-01E and IM 01C22T03-00E respectively.
CAUTION
This instrument is tested and certified as intrinsically safe type or explosionproof type. Please note that the construction of the instrument, installation, external wiring, maintenance or repair is strictly restricted, and non-observance or negligence of this restriction would result in dangerous condition.
WARNING
To preserve the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair activities. Please read the following sections very carefully.
2.9.1 FM Approval
2-3 a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM012-A12 P.1 and 2.”)
Note 1. Model EJA Series pressure transmitters with optional code /FS1 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3610, FM3611,
FM3810, ANSI/NEMA250
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D. Class II, Division 2, Groups E, F & G and
Class III, Division 1 Hazardous Locations.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –40 to 60
°
C
Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax = 30 V
Imax = 165 mA
Ci = 22.5 nF
Li = 730
μ
H
Pmax = 0.9 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc
Isc )
) 30 V
165 mA
Ca > 22.5 nF
La > 730
μ
H
Pmax ) 0.9W
• Intrinsically Safe Apparatus Parameters
[Groups C, D, E, F and G]
Vmax = 30 V
Imax = 225 mA
Ci = 22.5 nF
Li = 730
μ
H
Pmax = 0.9 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc
Isc )
) 30 V
225 mA
Ca > 22.5 nF
La > 730
μ
H
Pmax ) 0.9 W
• Entity Installation Requirements
Vmax * Voc or Vt, Imax * Isc or It,
Pmax (IS Apparatus) * Pmax (Barrier)
Ca * Ci + Ccable, La * Li + Lcable
IM 01C21C01-01E
2. HANDLING CAUTIONS
Note 3. Installation
• Barrier must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not use or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/ISA
RP12.6 “Installation of Intrinsically Safe Systems for
Hazardous (Classified) Locations” and the National
Electric Code (ANSI/NFPA 70).
• The configuration of associated apparatus must be
FMRC Approved.
• Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments.
• Associated apparatus manufacturer’s installation drawing must be followed when installing this apparatus.
• The maximum power delivered from the barrier must not exceed 0.9 W.
• Note a warning label worded “SUBSTITUTION OF
COMPONENTS MAY IMPAIR INTRINSIC
SAFETY,” and “INSTALL IN ACCORDANCE
WITH DOC. No. IFM012-A12 P.1 and 2.”
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply –
Safety Barrier
+
–
+
–
General
Purpose
Equipment
+
– b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /FF1 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3615, FM3810,
ANSI/NEMA250
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60
°
C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NEPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
• Keep the “CAUTION” nameplate attached to the transmitter.
CAUTION: OPEN CIRCUIT BEFORE REMOV-
ING COVER. FACTORY SEALED, CONDUIT
SEAL NOT REQUIRED. INSTALL IN ACCOR-
DANCE WITH THE INSTRUCTION MANUAL
IM 1C22.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.
[Nonincendive]
Hazardous Location Nonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.
EJA Series Pressure
Transmitters
+
Supply –
General
Purpose
Equipment
+
–
Not Use
Safety Barrier
F0203.EPS
2-4 c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJA Series pressure transmitters with optional code /FU1 can be selected the type of protection (FM Intrinsically Safe or FM
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
IM 01C21C01-01E
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
2.9.2 CSA Certification
a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe type. (Following contents refer to “DOC No. ICS003-A12 P.1-1 and
P.1-2.”)
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /CS1 are applicable for use in hazardous locations
Certificate: 1053843
• Applicable Standard: C22.2 No.0, No.0.4, No.25,
No.30, No.94, No.142, No.157, No.213
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D, Class II, Division 2, Groups F & G, and
Class III, Hazardous Locations. (not use Safety
Barrier)
• Encl. “Type 4X”
• Temperature Class: T4
• Ambient temperature: –40 to 60
°
C
• Process Temperature: 120 ° C max.
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax) = 30 V
Maximum Input Current (Imax) = 165 mA
Maximum Input Power (Pmax) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730
μ
H
* Associated apparatus (CSA certified barriers)
Maximum output voltage (Voc) ) 30 V
Maximum output current (Isc) ) 165 mA
Maximum output power (Pmax) ) 0.9 W
Note 3. Installation
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Intrinsically safe and nonincendive Certification.
2. HANDLING CAUTIONS
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply –
Safety Barrier
+
–
+
–
General
Purpose
Equipment
+
–
2-5
[Nonincendive]
Hazardous Location Nonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.
EJA Series Pressure
Transmitters
Supply
+
–
General
Purpose
Equipment
+
–
Not Use
Safety Barrier
F0204.EPS
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /CF1 are applicable for use in hazardous locations:
Certificate: 1089598
• Applicable Standard: C22.2 No.0, No.0.4, No.25,
No.30, No.94, No.142
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Encl “Type 4X”
• Temperature Class: T6, T5, and T4
• Process Temperature: 85
°
C (T6), 100
°
C (T5), and
120
°
C (T4)
• Ambient Temperature: –40 to 80
°
C
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the figure.
CAUTION: SEAL ALL CONDUITS
WITHIN 50 cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE
INSTALLÉ À MOINS DE 50 cm DU
BÎTIER.
• When installed in Division 2, “SEALS NOT
REQUIRED.”
IM 01C21C01-01E
Note 3. Operation
• Keep the “CAUTION” label attached to the transmitter.
CAUTION: OPEN CIRCUIT BEFORE
REMOVING COVER.
OUVRIR LE CIRCUIT AVANT
D´NLEVER LE COUVERCLE.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Explosionproof Certification.
Non-Hazardous
Locations
Hazardous Locations Division 1
Non-hazardous
Location
Equipment 50 cm Max.
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Conduit
EJA Series
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
Hazardous Locations Division 2
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
EJA Series
F0205.EPS
c. CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJA Series pressure transmitters with optional code /CU1 can be selected the type of protection (CSA Intrinsically Safe or CSA
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
2-6
2. HANDLING CAUTIONS
2.9.3 IECEx Certification
Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /SU2 can be selected the type of protection (IECEx Intrinsically Safe/type n or flameproof) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
a. IECEx Intrinsically Safe Type / type n
Caution for IECEx Intrinsically safe and type n.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /SU2 are applicable for use in hazardous locations.
• No. IECEx KEM 06.0007X
• Applicable Standard: IEC 60079-0:2004,
IEC 60079-11:1999, IEC 60079-15:2005,
IEC 60079-26:2004
• Type of Protection and Marking Code:
Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature :–40 to 60
°
C
• Max. Process Temp.: 120
°
C
• Enclosure: IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Ui) = 30 V
Maximum Input Current (Ii) = 165 mA
Maximum Input Power (Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730
μ
H
• Type "n" ratings are as follows:
Maximum Input Voltage (Ui) = 30 V
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730
μ
H
• Installation Requirements
Uo ) Ui, Io ) Ii, Po ) Pi,
Co * Ci + Ccable, Lo * Li + Lcable
Uo, Io, Po, Co, and Lo are parameters of barrier.
Note 3. Installation
• In any safety barreir used output current must be limited by a resistor 'R' such that Io=Uo/R.
• The safety barrier must be IECEx certified.
IM 01C21C01-01E
2. HANDLING CAUTIONS
• Input voltage of the safety barrier must be less than
250 Vrms/Vdc.
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation and will void
IECEx Intrinsically safe and type n certification.
• The cable entry devices and blanking elements for type n shall be of a certified type providing a level of ingress protection of at least IP54, suitable for the conditions of use and correctly installed.
• Electrical Connection:
The type of electrical connection is stamped near the electrical connection port according to the following marking.
Location of the marking
F0210.EPS
Note 4. Operation
• WARNING:
WHEN AMBIENT TEMPERATURE * 55
°
C,
USE THE HEAT-RESISTING CABLES * 90
°
C.
Note 5. Special Conditions for Safe Use
• WARNING:
IN THE CASE WHERE THE ENCLOSURE OF
THE PRESSURE TRANSMITTER IS MADE OF
ALUMINUM, IF IT IS MOUNTED IN AN AREA
WHERE THE USE OF ZONE 0 IS REQUIRED,
IT MUST BE INSTALLED SUCH, THAT, EVEN
IN THE EVENT OF RARE INCIDENTS, IGNI-
TION SOURCES DUE TO IMPACT AND
FRICTION SPARKS ARE EXCLUDED.
Hazardous Location
Group I/IIC, Zone 0
[Intrinsically Safe]
Nonhazardous Location
EJA Series Pressure
Transmitters
+
Supply –
IECEx certified
Safety Barrier
+ +
– –
Hazardous Location
Group IIC, Zone 2
[type n]
Nonhazardous Location
T0202.EPS
General
Purpose
Equipment
+
–
F0211.EPS
2-7
EJA Series Pressure
Transmitters
+
Supply –
Not Use
Safety Barrier
IECEx Certified
Equipment [nL]
+
–
F0212.EPS
b. IECEx Flameproof Type
Caution for IECEx flameproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /SU2 are applicable for use in hazardous locations:
• No. IECEx KEM 06.0005
• Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
• Type of Protection and Marking Code:
Ex d IIC T6...T4
• Enclosure: IP67
• Maximum Process Temperature: 120
°
C (T4),
100 ° C (T5), 85 ° C (T6)
• Ambient Temperature: –40 to 75
°
C (T4), –40 to
80
°
C (T5), –40 to 75
°
C (T6)
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
• In hazardous locations, the cable entry devices shall be of a certified flameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable flameproof certified blanking elements. (The plug attached is certificated as the flame proof IP67 as a part of this apparatus.)
• In case of ANSI 1/2 NPT plug, ANSI hexagonal wrench should be applied to screw in.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 10 MINUTES
BEFORE OPENING.
• WARNING:
WHEN AMBIENT TEMPERATURE * 70 ° C,
USE THE HEAT-RESISTING CABLES * 90
°
C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void IECEx Certification.
IM 01C21C01-01E
2. HANDLING CAUTIONS
2.9.4 CENELEC ATEX (KEMA)
Certification
(1) Technical Data a. CENELEC ATEX (KEMA) Intrinsically Safe
Type
Caution for CENELEC ATEX (KEMA) Intrinsically safe type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /KS2 for potentially explosive atmospheres:
• No. KEMA 02ATEX1030 X
• Applicable Standard: EN50014:1997,
EN50020:1994, EN50284:1999
• Type of Protection and Marking code:
EEx ia IIC T4
• Temperature Class: T4
• Enclosure: IP67
• Process Temperature: 120
°
C max.
• Ambient Temperature: –40 to 60
°
C
Note 2. Electrical Data
• In type of explosion protection intrinsic safety EEx ia IIC only for connection to a certified intrinsically safe circuit with following maximum values:
Ui = 30 V
Ii = 165 mA
Pi = 0.9 W
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730
μ
H
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void KEMA Intrinsically safe Certification.
Note 5. Special Conditions for Safe Use
• In the case where the enclosure of the Pressure
Transmitter is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
[Installation Diagram]
Hazardous Location Nonhazardous Location
Transmitter
Supply
+
–
+
–
Safety Barrier *1
F0208.EPS
*1: In any safety barriers used the output current must be limited by a resistor “R” such that Imaxout-Uz/R.
2-8 b. CENELEC ATEX (KEMA) Flameproof Type
Caution for CENELEC ATEX (KEMA) flameproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /KF2 for potentially explosive atmospheres:
• No. KEMA 02ATEX2148
• Applicable Standard: EN50014:1997,
EN50018:2000
• Type of ProteATEXction and Marking Code: EEx d IIC T6···T4
• Temperature Class: T6, T5, and T4
• Enclosure: IP67
• Maximum Process Temperature:
85 ° C (T6), 100 ° C (T5), and 120 ° C (T4)
• Ambient Temperature: T4 and T6; –40 to 75
°
C,
T5; –40 to 80
°
C
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation requirement.
• The cable entry devices shall be of a certified flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “CAUTION” label to the transmitter.
CAUTION: AFTER DE-ENERGIZING,
DELAY 10 MINUTES BEFORE OPEN-
ING. WHEN THE AMBIENT
TEMP.
70 ° C, USE HEAT-RESISTING
CABLES 90
°
C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void KEMA Flameproof Certification.
IM 01C21C01-01E
c. CENELEC ATEX (KEMA) Intrinsically Safe
Type/CENELEC ATEX (KEMA) Flameproof
Type/ CENELEC ATEX Type n
Model EJA-A Series pressure transmitters with optional code /KU2 can be selected the type of protection CENELEC ATEX (KEMA) Intrinsically
Safe, Flameproof or CENELEC ATEX Type n for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used.
The installation must be in accordance with the description about the type of protection in this user’s manual.
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
CENELEC ATEX Type of Protection “n”
WARNING
When using a power supply not having a nonincendive circuit, please pay attention not to ignite in the surrounding flammable atmosphere.
In such a case, we recommend using wiring metal conduit in order to prevent the ignition.
• Applicable Standard: EN60079-15:2003
• Referential Standard: IEC60079-0:1998, IEC60079-
11:1999
• Type of Protection and Marking Code:
EEx nL IIC T4
• Temperature Class: T4
• Enclosure: IP67
• Process Temperature: 120 ° C max.
• Ambient Temperature: –40 to 60
°
C
Note 1. Electrical Data
Ui = 30 V
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730
μ
H
Note 2. Installation
• All wiring shall comply with local installation requirements. (refer to the installation diagram)
Note 3. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void Type of Protection “n”.
2. HANDLING CAUTIONS
[Installation Diagram]
Hazardous Location
(Zone 2 only)
Transmitter
+
Supply
–
Nonhazardous Location
+
–
Power Supply
F0209.EPS
Ratings of the Power Supply as follows;
Maximum Voltage: 30 V
CENELEC ATEX Type of Protection “Dust”
• Applicable Standard: EN50281-1-1:1997
• Type of Protection and Marking Code: II 1D
• Maximum Surface Temperature:
T65
°
C (Tamb.: 40
°
C), T85
°
C (Tamb.: 60
°
C), and
T105
°
C (Tamb.: 80
°
C)
Note 1. Installation instructions
The cable entry devices and blanking elements shall be of a certificated type providing a level of ingress protection of at least IP6x, suitable for the conditions of use and correctly installed.
(2) Electrical Connection
The type of electrical connection is stamped near the electrical connection port according to the following marking.
Location of the marking
F0200.EPS
(3) Installation
WARNING
• All wiring shall comply with local installation requirement and local electrical code.
• There is no need of the conduit seal for both of
Division 1 and Division 2 hazardous locations because this product is sealed at factory.
• In case of ANSI 1/2 NPT plug, ANSI hexagonal wrench should be applied to screw in.
2-9 IM 01C21C01-01E
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical sparking when access to the instrument and peripheral devices in hazardous locations.
(5) Maintenance and Repair
WARNING
The instrument modification or parts replacement by other than authorized Representative of
Yokogawa Electric Corporation is prohibited and will void the certification.
(6) Name Plate
Name plate
2. HANDLING CAUTIONS
MWP: Maximum working pressure.
CAL RNG: Specified calibration range.
DISP MODE: Specified display mode.
OUTPUT MODE: Specified output mode.
NO.: Serial number and year of production *1 .
TOKYO 180-8750 JAPAN:
The manufacturer name and the address *2 .
*1: The third figure from the last shows the last one figure of the year of production. For example, the production year of the product engraved in “NO.” column on the name plate as follows is 2001.
12A819857 132
The year 2001
*2: “180-8750” is a zip code which represents the following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
Tag plate for flameproof type
: Refer to USER'S MANUAL
2.10 EMC Conformity Standards
EN61326, AS/NZS CISPR11
CAUTION
This instrument is a Class A product, and it is designed for use in the industrial environment.
Please use this instrument in the industrial environment only.
Tag plate for intrinsically safe type
Tag plate for type n protection
Tag plate for flameproof, intrinsically safe type,
type n protection, and Dust
D T65 C (Tamb.: 40 C), T85 C (Tamb.: 60 C), and T105 C (Tamb.: 80 C)
MODEL: Specified model code.
STYLE: Style code.
SUFFIX: Specified suffix code.
SUPPLY: Supply voltage.
OUTPUT: Output signal.
F0298.EPS
NOTE
YOKOGAWA recommends customer to apply the Metal Conduit Wiring or to use the twisted pair Shield Cable for signal wiring to conform the requirement of EMC Regulation, when customer installs the EJA Series Transmitters to the plant.
2.11 PED (Pressure Equipment
Directive)
(1) General
• EJA series of pressure transmitters are categorized as pressure accessories under the vessel section of this directive 97/23/EC, which corresponds to
Article 3, Paragraph 3 of PED, denoted as Sound
Engineering Practice (SEP).
2-10 IM 01C21C01-01E
• EJA130A, EJA440A, EJA510A, and EJA530A can be used above 200 bar and therefore considered as a part of a pressure retaining vessel where category lll, Module H applies. These models with option code /PE3 conform to that category.
(2) Technical Data
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as Sound
Engineering Practice (SEP) .
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory - Vessel
Type of Fluid: Liquid and Gas
Group of Fluid: 1 and 2
Model
EJA110A
EJA120A
EJA130A
PS(bar)
160
0.5
420
*1 V(L)
0.01
0.01
0.01
PS-V(bar-L)
1.6
0.005
4.2
Category *2
Article 3, paragraph 3
(SEP)
Article 3, paragraph 3
(SEP)
Article 3, paragraph 3
(SEP)
EJA130A
With code /PE3
420 0.01
4.2
III
EJA310A
EJA430A
EJA440A
160
160
500
0.01
0.01
0.01
1.6
1.6
50
Article 3, paragraph 3
(SEP)
Article 3, paragraph 3
(SEP)
Article 3, paragraph 3
(SEP)
EJA440A
With code /PE3
500 0.01
50 III
EJA510A 500 0.01
50
Article 3, paragraph 3
(SEP)
EJA510A
With code /PE3
500 0.01
50 III
EJA530A 500 0.01
50
Article 3, paragraph 3
(SEP)
EJA530A
With code /PE3
500 0.01
50 III
*1: PS is maximum allowable pressure for vessel itself.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
T0299.EPS
2. HANDLING CAUTIONS
(3) Operation
CAUTION
• The temperature and pressure of fluid should be applied under the normal operating condition.
• The ambient temperature should be applied under the normal operating condition.
• Please pay attention to prevent the excessive pressure like water hammer, etc. When water hammer is to be occurred, please take measures to prevent the pressure from exceeding
PS by setting the safety valve, etc. at the system and the like.
• When external fire is to be occurred, please take safety measures at the device or system not to influence the transmitters.
2.12 Low Voltage Directive
Applicable standard : EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to which a soild, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. " 2 " applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by condenstaion must be expected.
(2) Installation Category I
"Overvoltage category(Installation category)" describes a number which defines a transient overvoltage condition. It implies the regulattion for impulse withstand voltage. " I " applies to electrical equipment which is supplied from the circuit when appropriate transient overvoltage control means
(interfaces) are provided.
2-11 IM 01C21C01-01E
3. COMPONENT NAMES
3.
COMPONENT NAMES
Tramsmitter sedtion
External indicator conduit connection (Note 1)
Terminal box cover
Conduit connection
CPU assembly
Zero-adjustment screw
Integral indicator (Note 1)
Mounting screw
Amplifier Cover
Setting pin
(CN4)
Range-setting switch (Note 1)
(See Subsection 7.6)
Setting pin (CN4) position
(Note 2)
H
L
H
L
Note 1: See Subsection 10.2, “Model and Suffix Codes,” for details.
Note 2: Insert the pin (CN4) as shown in the figure above to set the burn-out direction. The pin is set to the H side for delivery (unless option code /C1 is specified in the order).
The setting can be confirmed by calling up parameter
D52 using the BRAIN TERMINAL. Refer to Subsection
8.3.3 (11).
Figure 3.1 Component Names
Burn - out direction
HIGH
Cover flange
Output at burn - out
110% or higher
Process connection
(low pressure side)
Process connector
(Note 1)
Pressure-detector section
LOW
-5% or lower
F0301.EPS
Table 3.1 Display Symbol
Display Symbol Meaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
%, kPa, Pa, MPa, kgf/cm 2 , gf/cm 2 , mbar, bar, atm, mmHg, mmH
2
O, inH
2
O, inHg, ftH
2
O, psi, Torr
Select one of these sixteen available engineering units for the display.
T0301.EPS
IM 01C21C01-01E 3-1
4. INSTALLATION
4.
INSTALLATION
4.1 Precautions
Before installing the transmitter, read the cautionary notes in Section 2.4, “Selecting the Installation
Location.” For additional information on the ambient conditions allowed at the installation location, refer to
Subsection 10.1 “Standard Specifications.”
IMPORTANT
Please use a gasket which has a bigger inside diameter than that of gasket facing (ød) on diaphragm seal. In case a gasket which has a smaller inside diameter than that of gasket facing is used, it may cause an error as the gasket prevents diaphragm from working correctly. (Refer to Subsection 10.4 ‘Dimensions’)
IMPORTANT
• When welding piping during construction, take care not to allow welding currents to flow through the transmitter.
• Do not step on this instrument after installation.
• Never loosen the four screws securing the cover flanges (if the seal liquid leaks, the transmitter cannot be used).
4.2 Mounting
The transmitter is mounted on a process using its highpressure side flange as shown in Figure 4.1. The customer should prepare the mating flange, gasket, stud bolts and nuts.
4.3 Rotating Transmitter Section
The DPharp transmitter section can be rotated in 90
° segments.
(1) Remove the two Allen screws that fasten the transmitter section and pressure-detector section, using the Allen wrench supplied with the transmitter.
(2) Rotate the transmitter section slowly in 90
° segments.
(3) Tighten the two Allen screws.
IMPORTANT
Do not rotate the transmitter section more than
180
°
.
Gasket
Transmitter section
Rotate 90
° or 180
° segments
Nut
Figure 4.1
Transmitter Mounting
Stud bolt
F0401.EPS
Conduit connection
Zero-adjustment screw
4-1
Pressure-detector section
F0402.EPS
Figure 4.2 Rotating Transmitter Section
IM 01C21C01-01E
4.4 Changing the Direction of
Integral Indicator
IMPORTANT
Always turn OFF power, release pressure and remove a transmitter to non-hazardous area before disassembling and reassmbling an indicator.
An integral indicator can be installed in the following three directions. Follow the instructions in section 9.4
for removing and attaching the integral indicator.
Figure 4.3
Integral Indicator Direction
F0404.EPS
4. INSTALLATION
4.5 Affixing the Teflon Film
IMPORTANT
The FEP Teflon option includes a teflon film and fluorinated oil. Before mounting the transmitter to the process flange, affix the teflon film as follows:
1) Position the diaphragm so that the diaphragm is in a upward position.
2) Pour the fluorinated oil on the diaphragm and gasket area covering it completely and evenly.
Be careful not to scratch the diaphragm or change the its shape.
3) Affix the teflon film over the diaphragm and gasket area.
4) Next, carefully inspect the cover and try to identify any entrapped air between the diaphragm and the teflon film. The air must be removed to ensure accuracy. If air pockets are present, use your fingers to remove the air by starting at the center of the diaphragm and work your way out.
5) Place the gasket with the teflon film and affix to the process flange.
Teflon film
Fluorinated oil
[PART No. : F9145YN]
Diaphragm
4-2
Gasket area
PART No.
F9347XA
F9347YD
Prosess Flange size
3 inch (80mm)
2 inch (50mm)
Figure 4.4 Affixing the Teflon Film
F0403.EPS
IM 01C21C01-01E
5. INSTALLING IMPULSE PIPING
5.
INSTALLING IMPULSE PIPING
5.1 Impulse Piping Installation
Precautions
The impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects in a liquidfilled impulse piping, or the drain of a gas-filled impulse piping becomes plugged, the impulse piping will not convey the pressure accurately. Since this will cause errors in the measurement output, select the proper piping method for the process fluid (gas, liquid, or steam). Pay careful attention to the following points when routing the impulse piping and connecting the impulse piping to the transmitter.
(2) Tightening the Process Connector Mounting Bolts
After connecting the impulse piping, tighten the process connector mounting bolts uniformly.
(3) Removing the Impulse Piping Connecting
Port Dustproof Cap
The impulse piping connecting port of the transmitter is covered with a plastic cap to exclude dust. This cap must be removed before connecting the piping. (Be careful not to damage the threads when removing this cap. Never insert a screwdriver or other tool between the cap and port threads to remove the cap.)
5.1.1 Connecting Impulse Piping to the
Transmitter
(1) Check the High and Low Pressure Connections on the Transmitter (Figure 5.1)
Symbols “H” and “L” are shown on a capsule assembly to indicate high and low pressure side. For liquid level measurement in an open tank, the ‘L’ (low pressure) side is used to refer atmosphere. For a closed tank, connect the impulse line to the low pressure side of the transmitter. This will refer the pressure in the tank.
5.1.2 Routing the Impulse Piping
(1) Impulse Piping Slope
The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes.
(2) Preventing Freezing
If there is any risk that the process fluid in the impulse piping or transmitter could freeze, use a steam jacket or heater to maintain the temperature of the fluid.
“ H ” and “ L ” are shown
Low pressure connection
Process connector
Bolt
F0501.EPS
Figure 5.1 “H” and “L” Symbols on a Capsule Assembly
NOTE
After completing the connections, close the valves on the process pressure taps ( main valves ), the valves at the transmitter ( stop valves ), and the impulse piping drain valves, so that condensate, sediment, dust and other extraneous material cannot enter the impulse piping.
5-1 IM 01C21C01-01E
5.2 Impulse Piping Connection
Examples
Figure 5.2 shows examples of typical impulse piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, and the characteristics of the process fluid (corrosiveness, toxicity, flammability, etc.), etc. and make appropriate changes and additions to the connection configurations.
Open Tank
5. INSTALLING IMPULSE PIPING
Closed Tank
Pipe (opened to atmosphere at low pressure side)
Tap valve
Union or flange
Vent plug
Tee
Drain valve
Drain plug
F0502.EPS
Figure 5.2 Impulse Piping Connection Examples
5-2 IM 01C21C01-01E
6. WIRING
6.
WIRING
6.1 Wiring Precautions
IMPORTANT
• Lay wiring as far as possible from electrical noise sources such as large capacity transformers, motors, and power supplies.
• Remove electrical connection dust cap before wiring.
• All threaded parts must be treated with waterproofing sealant. (A non-hardening silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal and power cables through the same ducts.
• Explosion-protected instruments must be wired in accordance with specific requirements (and, in certain countries, legal regulations) in order to preserve the effectiveness of their explosionprotected features.
• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on CENELEC and
IECEx flameproof type transmitters. When the shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened by hand. See Subsection 9.4 “Disassembly and
Reassembly” for details.
6.3 Connections of External
Wiring to Terminal Box
6.3.1 Power Supply Wiring Connection
Connect the power supply wiring to the SUPPLY + and – terminals.
Transmitter terminal box
Power supply
+
–
Figure 6.3.1 Power Supply Wiring Connection
F0601.EPS
6.3.2 External Indicator Connection
Connect wiring for external indicators to the CHECK + and – terminals.
(Note) Use a external indicator whose internal resistance is 10 1 or less.
External indicator
Power supply
+
–
6.2 Selecting the Wiring Materials
(a) Use stranded leadwires or cables which are the same as or better than 600 V grade PVC insulated wire (JIS C3307) or equivalent.
(b) Use shielded wires in areas that are susceptible to electrical noise.
(c) In areas with higher or lower ambient temperatures, use appropriate wires or cables.
(d) In environment where oils, solvents, corrosive gases or liquids may be present, use wires or cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless terminal lugs (for 4 mm screws) with insulating sleeves be used for leadwire ends.
Transmitter terminal box
Figure 6.3.2 External Indicator Connection
F0602.EPS
6.3.3 BRAIN TERMINAL BT200 Connection
Connect the BT200 to the SUPPLY + and – terminals
(Use hooks). The communication line requires a reception resistor of 250 to 600 1 in series.
BT200
Transmitter terminal box
+
Power supply
–
Ignore the polarity since the BT200 is
AC-coupled to the terminal box.
F0603.EPS
Figure 6.3.3 BT200 Connection
IM 01C21C01-01E 6-1
6.3.4 Check Meter Connection
Connect the check meter to the CHECK + and – terminals (use hooks).
• A 4 to 20 mA DC output signal from the CHECK + and – terminals.
(Note) Use a check meter whose internal resistance is 10 1 or less.
Power supply
+
–
Check meter
Transmitter terminal box
Figure 6.3.4 Check Meter Connection
F0604.EPS
6.4 Wiring
6.4.1 Loop Configuration
Since the DPharp uses a two-wire transmission system, signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The transmitter and distributor are connected as shown below.
For details of the power supply voltage and load resistance, see Section 6.6; for communications line requirements, see Subsection 8.1.2.
(1) General-use Type and Flameproof Type
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver instrument
+
-
Figure 6.4.1a Connection between Transmitter and
Distributor
F0605.EPS
6. WIRING
(2) Intrinsically Safe Type
For intrinsically safe type, a safety barrier must be included in the loop.
Nonhazardous Location Hazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver instrument
+
-
Safety barrier
Figure 6.4.1b Connection between Transmitter and
Distributor
F0606.EPS
6.4.2 Wiring Installation
(1) General-use Type and Intrinsically Safe
Type
Make cable wiring using metallic conduit or waterproof glands.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the flexible metal conduit for waterproofing.
Flexible metal conduit
Wiring metal conduit
Tee
Drain plug
Apply a non-hardening sealant to the threads for waterproofing.
F0607.EPS
Figure 6.4.2a Typical Wiring Using Flexible Metal Conduit
6-2 IM 01C21C01-01E
(2) Flameproof Type
Wire cables through a flameproof packing adapter, or using a flameproof metal conduit.
Wiring cable through flameproof packing adapter.
• Apply a nonhardening sealant to the terminal box connection port and to the threads on the flameproof packing adapter for waterproofing.
Flameproof packing adapter
Flexible metal conduit
Wiring metal conduit
Apply a non-hardening sealant to the threads for waterproofing.
Tee
Drain plug
Figure 6.4.2b Typical Cable Wiring Using Flameproof
Packing Adapter
F0608.EPS
Flameproof metal conduit wiring
• A seal fitting must be installed near the terminal box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the terminal box connection port, flexible metal conduit and seal fitting for waterproofing.
Gas sealing device
Non-hazardous area
Flameproof flexible metal conduit
Hazardous area
Flameproof heavy-gauge steel conduit
Apply a non-hardening sealant to the threads of these fittings for waterproofing
Tee
Drain plug
Seal fitting
After wiring, impregnate the fitting with a compound to seal tubing.
F0609.EPS
Figure 6.4.2c Typical Wiring Using Flameproof Metal
Conduit
6. WIRING
6.5 Grounding
Grounding is always required for the proper operation of transmitters. Follow the domestic electrical requirements as regulated in each country. For a transmitter with built-in lightning protector, grounding should satisfy ground resistance of 10 or less.
Ground terminals are located on the inside and outside of the terminal box. Either of these terminals may be used.
Transmitter terminal box
Ground terminal
(Inside)
Ground terminal
(Outside)
Figure 6.5 Ground Terminals
6.6 Power Supply Voltage and
Load Resistance
F0610.EPS
When configuring the loop, make sure that the external load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load resistance includes safety barrier resistance.
600
External load resistance
R ( 1 )
250
R=
E–10.5
0.0236
Communication applicable range
BRAIN and HART
6-3
0 10.5
16.4
24.7
Power supply voltage E (V DC)
42
F0611.EPS
Figure 6.6 Relationship between Power Supply Voltage and External Load Resistance
IM 01C21C01-01E
7. OPERATION
7.
OPERATION
7.1 Preparation for Starting
Operation
The Model EJA210A and EJA220A flange mounted differential pressure transmitter measures the levels or densities of liquids. This section describes the operation procedure for the EJA210A as shown in Figure 7.1
when measuring a liquid level in an open tank.
(a) Confirm that there is no leak in the connecting part of the transmitter mounting flange.
Remove the plastic dust cap placed in the process connector (low pressure side).
(b) Turn ON power and connect the BT200.
Open the terminal box cover and connect the
BT200 to the SUPPLY + and – terminals.
(c) Using the BT200, confirm that the transmitter is operating properly. Check parameter values or change the setpoints as necessary.
For BT200 operating procedures, see Chapter 8. If the transmitter is equipped with an integral indicator, its indication can be used to confirm that the transmitter is operating properly.
Open tank
Confirming that Transmitter is Operating
Properly
Using the BT200
• If the wiring system is faulty, ‘communication error’ appears on the display.
• If the transmitter is faulty, ‘SELF CHECK ERROR’ appears on the display.
PARAM
C60:SELF CHECK
ERROR communication error
DATA DIAG PRNT ESC
Communication error
(Faulty wiring)
Self-diagnostic error
(Faulty transmitter)
F0702.EPS
Using the integral indicator
• If the wiring system is faulty, the display stays blank.
• If the transmitter is faulty, an error code will appear on the display according to the nature of the error.
Self-diagnostic error on the integral indicator
(Faulty transmitter)
F0703.EPS
Figure 7.1 Liquid Level Measurement
F0701.EPS
NOTE
If any of the error indications above appears on the display of the integral indicator or BT200, refer to Subsection 8.5.2 for corrective action.
Verify and Change Transmitter Parameter
Setting and Values
The following parameters are the minimum settings required for operation. The transmitter has been shipped with these parameters. To confirm or change the values, see Subsection 8.3.3.
• Measuring range ....... See Subsection 8.3.3 (2)
• Operation mode ......... See Subsection 8.3.3 (8)
IM 01C21C01-01E 7-1
7.2 Zero Point Adjustment
Adjust the zero point after operating preparation is completed.
IMPORTANT
Do not turn off the power to the transmitter immediately after a zero adjustment. Powering off within 30 seconds after a zero adjustment will return the adjustment back to the previous settings.
The zero point adjustment can be made in either way: using the zero-adjustment screw of the transmitter or the BT200 operation.
For output signal checking, display the parameter A10:
OUTPUT (%) in the BT200.
BT200
PARAM
A10:OUTPUT(%)
0.0 %
A11:ENGR OUTPUT
A20:AMP TEMP
Output signal (%) display
DATA DIAG PRNT ESC
Zero-adjustment Screw
Zero-adjustment screw
F0704.EPS
When adjusting the transmitter zero point, the liquid level in a tank does not have to be set to the low limit
(0%) of the measuring range. In such case, match the transmitter output signal with the actual measured value using a glass gauge, for example.
7. OPERATION
7.2.1 When you can obtain Low Range
Value from actual measured value of 0% (0 kPa, atmospheric pressure);
Using the Transmitter Zero-adjustment
Screw
Before adjusting a screw, check that the parameter
J20: EXT ZERO ADJ displays ENABLE .
See
Subsection 8.3.3 (12) for the setting procedure.
Use a slotted screwdriver to turn the zero-adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of
0.01% of the setting range. Since the degree of zero adjustments varies with the screw turning speed, turn the screw slowly for fine adjustment and quickly for coarse adjustment.
Using the BT200
Zero point can be adjusted by simple key operation of the BT200.
Select parameter J10: ZERO ADJ , and press the
ENTER key twice. The zero point will be adjusted automatically to the output signal 0% (4 mA DC).
Confirm that the setting value displayed for the parameter is ‘ 0.0% ’ before pressing the ENTER key.
See Subsection 8.3.3 (12) for BT200 operating procedures.
SET
J10:ZERO ADJ
–0.0 %
+ 000.0
CLR ESC
A display when parameter
J10 is selected.
Press key twice for 0% output 4 mA DC.
F0705.EPS
7-2 IM 01C21C01-01E
7.2.2 When you cannot obtain Low Range
Value from actual measured value of 0%;
Convert the actual measured value obtained by a glass gauge into %.
[Example]
The measuring range of 0 to 2 m and the actual measured value of 0.8 m.
Actual measured value=
0.8
2 x 100=40.0%
Using the Transmitter Zero-Adjustment Screw
Turn the screw to match the output signal to the actual measured value in %.
Using the BT200
Select the parameter J10: ZERO ADJ .
Change the set point (%) displayed for the parameter to the actual measured value (%), and press the ENTER key twice.
See Subsection 8.3.3 (12) for operation details.
SET
J10:ZERO ADJ
–0.0 %
+ 000.0
A display at J10
7. OPERATION
IMPORTANT
• Remove the BT200 from the terminal box, and confirm that none of the terminal screws are loosened.
• Close the terminal box cover and the amplifier cover. Screw each cover in tightly until it will not turn further.
• Two covers are required to be locked on the
CENELEC and IECEx Flameproof type transmitters. An Allen head bolts (shrouding bolts) are provided under edge of the each cover for locking. When a shrouding bolts are driven counterclockwise by an Allen wrench, it is coming out and locks up a cover. (See page 9-
3) After locking, the covers should be confirmed not to be opened by hand.
• Tighten the zero-adjustment cover mounting screw to fix the cover in position.
7.4 Shutting Down Operation
Turn off the power.
NOTE
Whenever shutting down the transmitter for a long period, detach the transmitter from the tank.
CLR ESC
SET
J10:ZERO ADJ
–0.0 %
+ 040.0
CLR ESC
Change setting to the actually measured value (40.0%).
Press key twice for 40% output 10.4 mA DC.
F0706.EPS
7.3 Starting Operation
After completing the zero point adjustment, follow the procedure below to start operation.
1) Confirm the operating status.
The output signal may widely fluctuate (hunting state) due to process pressure periodic variation. In such case, BT200 operation can dampen the transmitter output signal. Confirm the hunting state using a receiving instrument or the integral indicator and set the optimum damping time constant. See
Subsection 8.3.3 (3) “Damping time constant setup.”
2) After confirming the operating status, perform the following:
7.5 Venting or Draining Transmitter Pressure-detector Section
Since this transmitter is designed to be self-draining and self-venting with vertical impulse piping connections, neither draining nor venting will be required if the impulse piping is configured appropriately for selfdraining or self-venting operation.
If condensate (or gas) collects in the transmitter pressure-detector section, the measured pressure may be in error. If it is not possible to configure the piping for self-draining (or self-venting) operation, you will need to loosen the drain (vent) screw on the transmitter to completely drain (vent) any stagnated liquid (gas).
However, since draining condensate or bleeding off gas gives the pressure measurement disturbance, this should not be done when the loop is in operation.
7-3 IM 01C21C01-01E
WARNING
Since the accumulated liquid (or gas) may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors.
7.5.1
Draining Condensate
1) Gradually open the drain plug and drain the transmitter pressure-detector section. (See Figure
7.5.1.)
2) When all accumulated liquid is completely removed, close the drain plug.
3) Tighten the drain plug to a torque of 34 to 39 N·m.
7.5.2
Venting Gas
1) Gradually open the vent screw to vent gas from the transmitter pressur-detector section. (See Figure
7.5.1)
2) When the transmitter is completely vented, close the vent screw.
3) Tighen the vent screw to a torque of 10 N·m.
Drain plug
Vent screw
When you loosen the drain plug or the vent screw, the accumulated liquid(or gas) will be expelled in the direction of the arrow.
F0707.EPS
Figure 7.5.1 Draining/Venting the Transmitter
7. OPERATION
7.6 Setting the Range Using the
Range-setting Switch
With actual pressure being applied to the transmitter, the range-setting switch (push-button) located on the optional integral indicator plate and the external zeroadjustment screw allow users to change (re-range) the low- and high-limit values for the measurement range
(LRV and HRV) without using BT200. However, other changes in the display settings (scale range and engineering unit) for the integral indicator requires
BT200.
Follow the procedure below to change the LRV and
HRV settings.
[Example]
Rerange LRV to 0 and HRV to 3 MPa.
1) Connect the transmitter and apparatus as shown in
Figure 9.3.1 and warm up for at least five minutes.
2) Press the range-setting push-button.
The integral indicator then displays “ LSET .”
3) Apply a pressure of 0 kPa (atmospheric pressure) to the transmitter. (Note 1)
4) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)
5) Adjust the output signal to 0% (1 V DC) by rotating the external zero-adjustment screw. Doing so completes the LRV setting.
6) Press the range-setting push-button. The integral indicator then displays “ HSET .”
7) Apply a pressure of 3 MPa to the transmitter. (Note 1)
8) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)
9) Adjust the output signal to 100% (5 V DC) by rotating the external zero-adjustment screw. Doing so completes the HRV setting.
10) Press the range-setting push-button. The transmitter then switches back to the normal operation mode with the measurement range of 0 to 3 MPa.
Note 1: Wait until the pressure inside the pressure-detector section has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the previous
LRV (or HRV), the integral indicator may display error number “Er.07” (In this case, the output signal percent and
“Er.07” are displayed alternately every two seconds).
Although “Er.07” is displayed, you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to Subsection
8.5.2, “Errors and Countermeasures.”
7-4 IM 01C21C01-01E
IMPORTANT
• Do not turn off the power to the transmitter immediately after completion of the change in the LRV and/or HRV setting(s). Note that powering off within thirty seconds after setting will cause a return to the previous settings.
• Changing LRV automatically changes HRV to the following value.
HRV = previous HRV + (new LRV – previous LRV)
• If the range-setting push-button and external zero-adjustment screw are not touched during a range-change operation, the transmitter automatically switches back to the normal operation mode.
Integral indicator
Note : Use a thin bar which has a blunt tip, e.g., a hexagonal wrench, to press the rangesetting push-button
Range-setting switch
(Push-button)
Figure 7.6
Range-setting Switch
F0708.EPS
7. OPERATION
7-5 IM 01C21C01-01E
8. BRAIN TERMINAL BT200 OPERATION
8.
BRAIN TERMINAL BT200
OPERATION
The DPharp is equipped with BRAIN communications capabilities, so that range changes, Tag No. setup, monitoring of self-diagnostic results, and zero point adjustment can be handled by remote control via
BT200 BRAIN TERMINAL or CENTUM CS console.
This section describes procedures for setting parameters using the BT200. For details concerning the
BT200, see IM 01C00A11-01E, “BT200 User’s
Manual.”
8.1 BT200 Operation Precautions
8.1.1 Connecting the BT200
Connection to the transmitter with the BT200 can be made by either connecting to the BT200 connection hooks in the transmitter terminal box or by connecting to a relaying terminal board.
8.2 BT200 Operating Procedures
8.2.1 Key Layout and Screen Display
Figure 8.2.1a shows the arrangement of the operating keys on the BT200 keypad, and Figure 8.2.1b shows the BT200 screen component.
LCD
(21 character
×
8 lines)
Relaying terminals
Control room
Terminal board
Function keys
Movement keys
ENTER key
Power ON/OFF key
Alphanumeric keys
Distributor
Shift keys
F0803.EPS
Figure 8.2.1a BT200 Key Layout
F0801.EPS
Figure 8.1.1 Connecting the BT200
8.1.2
Power supply
Conditions of Communication Line
Cable resistance Rc cc
Loop resistance = R + 2Rc
= 250 to 600 1
Load resistance R
Cable resistance Rc
Loop capacitance = 0.22
μ
F max.
DPharp
BT200
F0802.EPS
Figure 8.1.2 Conditions of Communication Line
8-1
MENU SCREEN
MENU
A:DISPLAY
B:SENSOR TYPE
BATTERY
Screen title
Parameters
HOME SET ADJ ESC
PARAMETER SCREEN
PARAM
A10:OUTPUT
100.0 %
A11:ENGR. OUTPUT
1000 mmH20
A20:AMP TEMP
23 deg C
DATA DI AG PRNT
Messages
Menu choices
Function commands
F0804.EPS
Figure 8.2.1b BT200 Screen Component
IM 01C21C01-01E
8.2.2 Operating Key Functions
(1) Alphanumeric Keys and Shift Keys
You can use the alphanumeric keys in conjunction with the shift keys to enter symbols, as well as alphanumeric keys.
Alphanumeric keys
8. BRAIN TERMINAL BT200 OPERATION
Use the function key [F1]
CODE to enter symbols. The following symbols will appear in sequence, one at a time, at the cursor each time you press [F1] CODE:
/ . – , + * ) ( ’ & % $ # ” !
To enter characters next to these symbols, press [ > ] to move the cursor.
Entry Key-in Sequence symbol command l/m
( I ) ( / ) ( m )
T0803.EPS
(2) Function Keys
The functions of the function keys depend on the function commands on display.
MENU
A:DISPLAY
B:SENSOR TYPE
Shift keys a. Entering Digits, Symbols, and Spaces
Simply press the alphanumeric keys.
F0805.EPS
Entry
–4
0.3
Key-in Sequence
1 –9
T0801.EPS
b. Entering Letters (A through Z)
Press an alphanumeric key following a shift key to enter the letter shown on that side which the shift key represents. You must press the shift key before entering each letter.
Left-side letter on the alphanumeric key
Right-side letter on the alphanumeric key
F0806 .EPS
Entry
W
IC
Key-in Sequence
J. B
T0802.EPS
Use the function key [F2] CAPS to select between uppercase and lowercase (for letters only). The case toggles between uppercase and lowercase each time you press [F2] CAPS.
Entering uppercase
CODE CAPS CLR ESC
Entering lowercase
CODE caps CLR ESC
Entry
Boy
( B )
Key-in Sequence to lower case
( o ) ( y )
F0807.EPS
HOME SET ADJ ESC Function commands
Function keys
F0808.EPS
8-2
Function Command List
Command
ADJ
CAPS/caps
CODE
CLR
DATA
DEL
DIAG
ESC
HOME
NO
OK
PARM
SET
SLOT
UTIL
Function
Displays the ADJ menu
Selects uppercase or lowercase
Selects symbols
Erases input data or deletes all data
Updates parameter data
Deletes one character
Calls the self-check panel
Returns to the most recent display
Displays the menu panel
Quits setup and returns to the previous display
Proceeds to the next panel
Enters the parameter number setup mode
Displays the SET menu
Returns to the slot selection panel
Calls the utility panel
*COPY
*FEED
Prints out parameters on display
Paper feed
*LIST Lists all parameters in the menu
*PON/POFF Automatic printout mode on or off
*PRNT
*GO
Changes to the print mode
Starts printing
*STOP Cancels printing
* Available on BT200-P00 (with printer).
T0804.EPS
IM 01C21C01-01E
8.2.3 Calling Up Menu Addresses Using the Operating Keys
8. BRAIN TERMINAL BT200 OPERATION
––WELCOME––
BRAIN TERMINAL
ID: BT200
STARTUP
SCREEN check connection push ENTER key
UTIL FEED
INITIAL
DATA
SCREEN
PARAM
01:MODEL
EJA210A-DM
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
OK
UTILITY
1.ID
2.SECURITY CODE
3.LANGUAGE SELECT
4.LCD CONTRAST
5.PRINTER ADJUST
(UTIL) esc
The utility screen contains the following items.
1. BT200 ID settings
2. Security code settings
3. Switching language of messages
(Japanese or English)
4. LCD contrast setting
5. Adjusting printout tone
(BT200-P00 only)
(ESC)
FUNC
1.MENU
2.UPLOAD TO BT200
3.DOWNLOAD TO INST
4.PRINT ALL DATA
(SET)
(SET MENU SCREEN)
MENU
C.SETTING
D.AUX SET 1
E.AUX SET 2
H:AUTO SET
HOME SET ADJ ESC
(ADJ)
(ADJ MENU SCREEN)
MENU
J.ADJUST
K.TEST
M.MEMO
P:RECORD
HOME SET ADJ ESC HOME SET ADJ ESC
MENU
SCREEN
(HOME MENU SCREEN)
MENU
A.DISPLAY
B.SENSOR TYPE
HOME SET ADJ ESC
PARAM
A60:SELF CHECK
GOOD
PARA-
METER
SCREEN
PARAM
A21:CAPSULE TEMP
26.5 deg C
DATA DIAG PRNT
PARAM
A10:OUTPUT(%)
50.0 %
A11:ENGR, OUTPUT
20.0 M
A20:AMP TEMP
24.5 deg C
DATA DIAG PRNT
ESC
ESC
ESC
PARAM
C60:SELF CHECK
GOOD
PARAM
C22:HIGH RANGE
100 kPa
DATA DIAG PRNT ESC
PARAM
C10:TAG NO.
YOKOGAWA
C20:PRESS UNIT
PRNT
kPa
C21:LOW RANGE
0 kPa
DATA DIAG PRNT
ESC
ESC
PARAM
J60:SELF CHECK
GOOD
PARAM
J10:ZERO ADJ
0.0 %
J11:ZERO DEV
PRNT
22.2 %
J20:EXT. ZERO ADJ
ENABLE
DATA DIAG PRNT
ESC
ESC
SETUP
SCREEN
SET
C10:TAG NO.
YOKOGAWA
YOKOGAWA
CODE CAPS CLR ESC
See “BT200 Instruction Manual” for details concerning uploading and downloading parameters and printouts (BT200-P00).
F0809.EPS
8-3 IM 01C21C01-01E
8. BRAIN TERMINAL BT200 OPERATION
8.3 Setting Parameters Using the BT200
8.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters
P: Pressure transmitters
L: Liquid level transmitters
No.
Item
EJA110A, EJA120A, and EJA130A
EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
EJA210A and EJA220A
Description
Rewritability
Remarks
01
02
MODEL
TAG NO.
03 SELF CHECK
A DISPLAY
A10 OUTPUT (%)
A11 ENGR.
OUTPUT
A20 AMP TEMP
A21 CAPSULE
TEMP
A30 STATIC
PRESS
A40 INPUT
Model+capsule type
Tag number
Self-diagnostic result
Measured data display
Output (in %)
Output (in engineering units)
Amplifier temperature
Capsule temperature
Static pressure
A60 SELF CHECK
Input (indicated as the value after zeroing)
Self-diagnostic messages
B
B10 MODEL
B11 STYLE NO.
B20 LRL
B21 URL
B30 MIN SPAN
B40
C
SENSOR
TYPE
MAX STAT.P.
B60 SELF CHECK
SETTING
C10 TAG. NO.
C20 PRESS UNIT
Sensor type
Model+span
Style number
Lower range-limit
Upper range-limit
Minimum span
Maximum static pressure* 4
Self-diagnostic messages
Setting data
Tag number
Measurement range units
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
16 alphanumerics
GOOD/ERROR
Menu name
–5 to 110%* 3
–19999 to 19999
Unit specified in D30
Unit specified in D30
Unit specified in D31* 1
–32000 to 32000
16 uppercase alphanumerics
–32000 to 32000
–32000 to 32000
–32000 to 32000
Same as A60
Default Value
GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP RANGE* 1 , OVER TEMP (CAP),
OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and
ZERO ADJ OVER
Menu name
C21 LOW RANGE
C22 HIGH
RANGE
C30 AMP
DAMPING
C40 OUTPUT
MODE
Measurement range, lower range value
Measurement range, higher range value
Damping time constant
Output mode and integral indicator mode
—
Menu name
16 alphanumerics
Selected from mmH
2
O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm 2 , kgf/cm 2 , inH
2
O, inHg, ftH
2
O, psi, or atm
–32000 to 32000(but within measurement range)
–32000 to 32000(but within measurement range)
Selected from 0.2* 2 , 0.5, 1.0, 2.0,
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Same as A60
As specified when ordered.
As specified when ordered.
As specified when ordered.
As specified when ordered.
2.0 s
As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.
C60 SELF CHECK Self-diagnostic messages
D AUX SET 1
D10 LOW CUT
D11 LOW CUT
MODE
D20 DISP SELECT
Auxiliary setting data 1
Low cut
Low cut mode
Display selection
D21 DISP UNIT
D22 DISP LRV
D23 DISP HRV
Engineering unit for display
Engineering range, lower range value
Engineering range, higher range value
—
Menu name
0.0 to 20.0%
LINEAR/ZERO
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
8 uppercase alphanumerics
–19999 to 19999
–19999 to 19999
10.0%
LINEAR
As specified when ordered.
As specified when ordered.
As specified when ordered.
8-4
F
Applicability
P L
—
—
— —
T0805.EPS
IM 01C21C01-01E
8. BRAIN TERMINAL BT200 OPERATION
No.
Item Description
Rewritability
Remarks Default Value
F
Applicability
P L
D AUX SET 1
D30 TEMP UNIT
D31 STAT. P. UNIT
Auxiliary setting data 1
Temperature setting units
Static pressure setting units
D40 REV OUTPUT
D45 H/L SWAP
D52 BURN OUT
D53 ERROR OUT
D60 SELF CHECK
Output reversal
Impulse piping accessing direction
CPU error
Hardware error
Self-diagnostic messages
E AUX SET 2
E30 BI DIRE
MODE
E60 SELF CHECK
Auxiliary setting data 2
Bidirectional mode
H AUTO SET
Self-diagnostic messages
Automatic setup
H10 AUTO LRV
H11 AUTO HRV
H60 SELF CHECK
J
J10 ZERO ADJ
J11 ZERO DEV.
J20 EXT. ZERO
J60 SELF CHECK
K
ADJUST
ADJ
TEST
K10 OUTPUT in %
Automatic measurement range lower range value setup
Automatic measurement range higher range value setup
Self-diagnostic messages
Adjustment data
Automatic zero adjustment
Manual zero adjustment
External zeroadjustment screw permission
Self-diagnostic messages
Tests
Test output % setting
—
—
—
—
—
—
—
—
—
Menu name deg C/deg F
Selected from mmH
2
O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm 2 , kgf/cm 2 , inH
2
O, inHg, ftH
2
O, psi, or atm
NORMAL/REVERSE
NORMAL/REVERSE
HIGH/LOW, –5 to 110%*
HOLD/HIGH/LOW, –5 to 110%*
Same as A60
Menu name
OFF/ON
Same as A60
Menu name
–32000 to 32000
–32000 to 32000
Same as A60
Menu name
–5 to 110.0%* 3
ENABLE/INHIBIT
Same as A60
3
3 deg C
As specified when ordered.
If not specified, MPa.
If not specified, NORMAL.
NORMAL
HIGH
HIGH
OFF
Displays the same data as
C21.
Displays the same data as
C22.
—
—
—
—
—
—
Menu name
–5 to 110.0%* 3 Displays ‘ACTIVE’ while executing
Same as A60 K60 SELF CHECK
M MEMO
Self-diagnostic messages
Memo
P
P10
P11
P12
P13
P60
M10 MEMO 1
M20 MEMO 2
M30 MEMO 3
M40 MEMO 4
M50 MEMO 5
M60 SELF CHECK
Memo
Memo
Memo
Memo
Memo
Self-diagnostic messages
RECORD History of the errors
ERROR REC 1 Last error
ERROR REC 2 One time before
ERROR REC 3 Two time before
ERROR REC 4 Three time before
SELF CHECK Self-diagnostic messages
—
—
—
—
—
Menu name
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
Same as A60
Display the error
Display the error
Display the error
Display the error
Same as A60
*1: In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
*2: When Optional code /F1 is specified, substitute the value with 0.1.
*3: When Optional code /F1 is specified, substitute the value –5 with –2.5.
*4: See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.
T0806.EPS
8-5 IM 01C21C01-01E
8.3.2 Parameter Usage and Selection
Before describing the procedure for setting parameters, we present the following table showing how the parameters are used and in what case.
8. BRAIN TERMINAL BT200 OPERATION
IMPORTANT
If the transmitter is turned off within 30 seconds after parameters have been set, the set data will not be stored and the terminal returns to previous settings.
Table 8.3.1 Parameter Usage and Selection
Setup Item
Tag No. setup
P.8-7
Calibration range setup
P.8-7
Damping time constant setup
P.8-8
Output signal low cut mode setup
P.8-9
Integral indicator scale range and unit setup
P.8-9
Description
Sets the Tag No. (using 16 alphanumeric characters).
Note: Up to 8 alphanumerics (upper case letters) can be used in the BT100.
Sets the calibration range for 4 to 20 mA DC. Sets three data items: range unit, input value at 4 mA DC (LRV), and input value at 20 mA DC (HRV).
Note: LRV and HRV can be specified with range value specifications up to 5 digits
(excluding any decimal point) within the range of –32000 to 32000.
Adjusts the output response speed for 4 to 20 mA DC.
Can be set in 9 increments from 0.2 to 64 s.
Used mainly to stabilize output near 0% if output signal is the square root mode.
Two modes are available: forcing output to 0% for input below a specific value, or changing to proportional output for input below a specific value.
Sets the following 5 types of integral indicator scale ranges and units:
% scale indicator, user set scale indicator, alternate indication of user set scale and % scale, input pressure display, alternate indication of input pressure and % scale
When using the user set scale, 4 types of data can be set:
user set scale setting, unit (BT200 only), display value at 4 mA DC (LRV), and display
value at 20 mA DC (HRV).
Note: LRV and HRV can be specified with range value specifications up to 5
digits (excluding any decimal point) within the range of –19999 to 19999.
Unit setup for displayed temperature
P.8-11
Unit setup for displayed static pressure P.8-11
Operation mode (normal/reverse signal) setup
P.8-11
Output status display/setup when a CPU failure P.8-12
Sets a unit for temperatures displayed on the BT200.
Sets a unit for static pressure displayed on the BT200.
Reverses the direction for 4 to 20 mA DC output relative to input.
Reverse mode is used for applications in which safety requires that output be driven toward 20 mA if input is lost.
Displays the status of 4 to 20 mA DC output when a CPU failure. The parameter of the standard unit is fixed to the high limit value.
Output status setup when a hardware error occurs
P.8-12
Sets the status of the 4 to 20 mA DC output when an abnormal status is detected with the capsule or the amplifier as the result of self-diagnosis. One of the following statuses; last held, high limit, and low limit values, can be selected.
Range change (while applying actual inputs)
P.8-12
Zero point adjustment
P.8-13
Test output (fixed current output) setup P.8-14
User memo fields
P.8-15
Range for 4 to 20 mA DC signal is set with actual input applied. Sets 20 mA DC output precisely with respect to user’s reference instrument output. Note that DPharp is calibrated with high accuracy before shipment, so span should be set using the normal range setup.
Adjusts zero point. This can be done either using the external zero-adjustment screw on the transmitteror using the BT200.
Used for loop checks.
Output can be set freely from –5% to 110% in 1% steps.
Allows user to enter up to 5 items of any desired text in up to 8 uppercase alphanumeric characters per item.
T0807.EPS
8-6 IM 01C21C01-01E
8.3.3 Setting Parameters
Set or change the parameters as necessary. After completing these, do not fail to use the “DIAG” key to confirm that “GOOD” is displayed for the selfdiagnostic result at _ 60: SELF CHECK .
(1) Tag No. Setup (C10: TAG NO)
Use the procedure below to change the Tag No. Up to
16 alphanumeric characters can be entered.
• Example: Set a Tag No. to FIC-1a
Press the key to turn on the BT200.
<When power is off>
––WELCOME––
BRAIN TERMINAL
ID: BT200 check connection push ENTER key
UTIL FEED
PARAM
01:MODEL
EJA110A-DM
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
OK
MENU
A:DISPLAY
B:SENSOR TYPE
Connect DPharp and BT200 using a communication cable and press the key.
Displays the name of connected
DPharp model, TAG NO. and diagnostics information. Press the
(OK) key after confirmation.
Press the (SET) key to display the SET menu panel.
HOME SET
MENU
C:SETTING
D:AUX SET 1
E:AUX SET 2
H:AUTO SET
ADJ ESC
HOME SET ADJ
MENU
C10:TAG NO.
YOKOGAWA
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
DATA DIAG PRNT
SET
C10:TAG NO.
YOKOGAWA
YOKOGAWA
ESC
ESC
Select C: SETTING and press the
key.
Select C10: TAG NO. and press the key.
CODE CAPS CLR ESC
SET
C10:TAG NO.
YOKOGAWA
FIC-1a _
Set the new TAG NO. (FIC-1a).
F OKOGAWA
F I KOGAWA
FI C OGAWA
FIC GAWA
FIC1 AWA
FIC-1 a WA
FIC-1a
Set TAG NO. and press the
key.
CODE caps CLE ESC
When you have made an entry mistake, return the cursor using the key, then reenter.
F0810.EPS
8. BRAIN TERMINAL BT200 OPERATION
SET
C10:TAG NO.
YOKOGAWA
FIC-1a
PRINTER OFF
F2:PRINTER ON
FEED POFF NO
SET
C10:TAG NO.
FIC-1a
This is the panel for confirming set data. The set data items flash.
When all items have been confirmed, press the again. (To go back to the setting panel, press the (NO) key.
The DPharp TAG NO. was overwritten.
Press the (OK) key to return to the parameter panel.
Press the (NO) key to return to the setting panel.
FEED NO
PARAM
C10:TAG NO.
FIC-1a
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
DATA DIAG PRNT
OK
ESC
F0811.EPS
(2) Calibration Range Setup a. Setting Calibration Range Unit
(C20: PRESS UNIT)
The unit is set at the factory before shipment if specified at the time of order. Follow the procedure below to change the unit.
• Example: Change the unit from mmH
2
O to kPa .
SET
C20:PRESS UNIT
mmH20
< mmWG >
< mmHG >
< Torr >
< kPa >
SET
C20:PRESS UNIT
kPa
ESC
Use the or key to select “kPa.”
Press the key twice to enter the setting.
Press the (OK) key.
FEED mmH
2
O mmAq mmWG mmHg
Torr kPa
MPa mbar bar gf/cm 2 kgf/cm 2 inH
2
O inHg ftH
2
O psi atm
NO OK
F0812.EPS
8-7 IM 01C21C01-01E
b. Setting Calibration Range Lower
Range Value and Higher Range Value
(C21: LOW RANGE, C22: HIGH
RANGE)
These range values are set as specified in the order before the instrument is shipped. Follow the procedure below to change the range.
• The measurement span is determined by the high and low range limit values. In this instrument, changing the low range value also automatically changes the high range value, keeping the span constant.
• Example 1: With present settings of 0 to 30 kPa, set the lower range value to 0.5 kPa.
SET
C21:LOW RANGE
0 kPa
+ 0.5
Set 0.5
.
Press the key twice to enter the setting.
DEL CLR
SET
C21:LOW RANGE
0.5 kPa
ESC
Press the (OK) key.
FEED NO OK
SET
C20:PRESS UNIT
kPa
C21:LOW RANGE
0.5 kPa
C22:HIGH RANGE
30.5 kPa
DATA DIAG PRNT ESC
The higher range value is changed while the span remains constant.
Span = Higher range value – Lower range value
F0813.EPS
• Note, however, that changing the higher range value does not cause the lower range value to change.
Thus, changing the higher range value also changes the span.
• Calibration range can be specified with range value specifications up to 5 digits (excluding any decimal point) for low or high range limits within the range of –32000 to 32000.
8. BRAIN TERMINAL BT200 OPERATION
• Example 2: With present settings of 0 to 30 kPa, set the Higher range value to10 kPa.
SET
C22:HIGH RANGE
30 kPa
+ 10
Set 10 .
Press the key twice to enter the setting.
DEL CLR ESC
SET
C22:HIGH RANGE
10 kPa
Press the (OK) key.
FEED NO OK
PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
C22:HIGH RANGE
10 kPa
DATA DIAG PRNT ESC
The low range value is not changed, so the span changes.
F0814.EPS
(3) Damping Time Constant Setup
(C30: AMP DAMPING)
When the instrument is shipped, the damping time constant is set at 2.0 seconds. Follow the procedure below to change the time constant.
• Example: Change from 2.0 sec to 4.0 sec.
SET
C30:AMP DAMPING
2.0 sec
< 2.0 sec >
< 4.0 sec >
< 8.0 sec >
< 16.0 sec >
ESC
Use the or key to select 4.0 sec .
Press the key twice to enter the setting.
SET
C30:AMP DAMPING
4.0 sec
Press the (OK) key.
FEED
0.2sec
0.5sec
1.0sec
2.0sec
4.0sec
8.0sec
16.0sec
32.0sec
64.0sec
NO OK
F0815.EPS
Note: The damping time constant set here is the damping time constant for the amplifier assembly. The damping time constant for the entire transmitter is the sum of the values for the amplifier assembly and for the capsule assembly. For the capsule assembly damping time constant (fixed), see the
“General Specifications” found at the end of this manual.
(See Chapter 10.)
8-8 IM 01C21C01-01E
(4) Output Signal Low Cut Mode Setup
(D10: LOW CUT, D11: LOW CUT MODE)
Low cut mode can be used to stabilize the output signal near the zero point. The low cut point can be set in a range from 0 to 20% of output. (Hysteresis: ± 1%)
Select “ ZERO ” as the low cut mode.
Low cut mode “ZERO”
50
(%)
Output
20
0
Input
50 (%)
F0816.EPS
• Example: Change the low cut setting range from 10% to 20%, and the low cut mode from LINEAR to ZERO.
SET
D10:LOW CUT
10.0 %
+ 20.0
Set 20 .
Press the key twice to enter the setting.
CLR ESC
SET
D10:LOW CUT
20.0 %
Press the (OK) key.
Next, the [D11: LOW CUT MODE] setting panel is displayed.
FEED NO
SET
D11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >
SET
D11:LOW CUT MODE
ZERO
OK
ESC
Use the or key to select “ZERO.”
Press the key twice to enter the setting.
Press the (OK) key.
FEED NO OK
PARAM
D10:LOW CUT
20.0 %
D11:LOW CUT MODE
ZERO
D20:DISP SELECT
NORMAL %
DATA DIAG PRNT ESC
F0817.EPS
8. BRAIN TERMINAL BT200 OPERATION
(5) Integral Indicator Scale Setup
The following 5 displays are available for integral indicators.
D20: DISP SELECT and Display
NORMAL %
USER SET
USER & %
INP PRES
PRES & %
Description and Related parameters
Indicates –5 to 110% range depending on the Measurement range (C21, C22).
A10:OUTPUT (%)
45.6 %
Indicates values depending on the
Engineering range (D22, D23).
( Note 1 )
Units set using Engineering unit
(D21) are not indicated.
A11:ENGR.OUTPUT
20.0 M
Indicates user set and % alternately in 3 second intervals.
A10:OUTPUT (%)
45.6 %
A11:ENGR. OUTPUT
20.0 M
Indicates input pressure.
( Note 2 )
Indication limits –19999 to 19999.
A40:INPUT
456 kPa
Indicates input pressure and % alternately in 3 second intervals.
A10:OUTPUT (%)
45.6 %
A40:INPUT
456 kPa
(Note 1) Scale range can be specified with range limit specifications up to 5 digits (excluding any decimal point) for low or high range limits within the range of –19999 to 19999.
The range with decimals is available to the third decimal place.
(Note 2) It indicates the value after zeroing.
T0808.EPS
See (a.) through (c.) for each setting procedure.
8-9 IM 01C21C01-01E
% indication and input pressure indication
D20: DISP SELECT
NORMAL %
INP PRES
PRES & %
Transmitter is set for “% display” when shipped.
User-set engineering unit display
D20: DISP SELECT
USER SET
USER & %
Set for user-set engineering unit display.
D21: DISP UNIT
Set a unit to be displayed on the BT200.
D22: DISP LRV
Set a numeric value for engineering unit for 4 mA output (LRV).
D23: DISP HRV
Set a numeric value for engineering unit for 20 mA output (HRV).
F0818.EPS
a. Display Selection (D20: DISP SELECT)
Follow the instructions given to the below to change the range of integral indication scales.
When USER SET is selected, the user set values of integral indication and A11: ENGR. OUTPUT parameter are indicated.
• Example: Set the integral indicator scale to
engineering units display.
SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>
SET
D20:DISP SELECT
USER SET
ESC
Use the or key to select “USER SET.”
Press the key twice to enter the setting.
Press the (OK) key.
FEED NO OK
The “%” disappears from the integral indicator display.
F0819.EPS
8. BRAIN TERMINAL BT200 OPERATION b. Setting User-set Engineering Unit
(D21: DISP UNIT)
This parameter allows entry of the engineering units to be displayed on the BT200. When the instrument is shipped, this is set as specified in the order.
Follow the procedure below to change this setting.
This parameter need not be set for % display.
• Example: Set an engineering unit M .
SET
D21:DISP UNIT
M_
Set “M.”
Press the key twice to enter the setting.
CODE CAPS CLR ESC
SET
D21:DISP UNIT
M
Press the (OK) key.
FEED NO OK
F0820.EPS
8-10 IM 01C21C01-01E
c. Lower and Higher Range Value Setup in Engineering Unit (D22: DISP LRV,
D23: DISP HRV)
These parameter items are used to set the lower and higher range values for the engineering unit display.
When the instrument is shipped, these are set as specified in the order. Follow the procedure below to change these settings. Note that these parameters need not be set for % display.
• Example: Set lower range value (LRV) to –50 and higher range value (HRV) to 50.
Setting LRV
SET
D22:DISP LRV
0M
- 50
Set –50 .
Press the key twice to enter the setting.
DEL CLR ESC
Setting HRV
SET
D23:DISP HRV
100M
+ 50
Set 50 .
Press the key twice to enter the setting.
DEL CLR ESC
SET
D23:DISP HRV
50M
Press the (OK) key.
FEED NO OK
PARAM
D21:DISP UNT
M
D22:DISP LRV
– 50M
D23:DISP HRV
50M
DATA DIAG PRNT ESC
F0821.EPS
(6) Unit Setup for Displayed Temperature
(D30: TEMP UNIT)
When the instrument is shipped, the temperature units are set to degC . Follow the procedure below to change this setting. Note that changing the unit here changes the unit for A20: AMP TEMP (amplifier temperature) and A21: CAPSULE TEMP (capsule temperature).
• Example: Change the unit for the temperature
display.
SET
D30:TEMP UNIT
deg C
< deg C >
< deg F >
ESC
Use the or key to select “deg F.”
Press the key twice to enter the setting.
F0822.EPS
8. BRAIN TERMINAL BT200 OPERATION
(7) Unit Setup for Displayed Static Pressure
(D31: STAT.P.UNIT)
Follow the procedure below to change the static pressure units.
Changing this parameter changes the unit for the A30:
STATIC PRESS (static pressure) display.
• Example: Change the static pressure unit from
kgf/cm 2 to MPa.
SET
D31:STAT.P.UNIT
kgf/cm^2
< MPa >
< mbar >
< bar >
< gf/cm^2 >
ESC
Use the or key to select MPa .
Press the key twice to enter the setting.
mmH
2
O mmAq mmWG mmHg
Torr kPa
MPa mbar bar gf/cm 2 kgf/cm 2 inH
2
O inHg ftH
2 psi
O atm
F0823.EPS
(8) Operation Mode Setup
(D40: REV OUTPUT)
This parameter allows the direction of the 4 to 20 mA output to be reversed with respect to input. Follow the procedure below to make this change.
• Example: Change 4 to 20 mA output to 20 to
4 mA output.
SET
D40:REV OUTPUT
NORMAL
< NORMAL >
< REVERSE>
ESC
Use the or key to select REVERSE.
Press the key twice to enter the setting.
F0824.EPS
8-11 IM 01C21C01-01E
(9) Output Status Display/Setup when a CPU
Failure (D52: BURN OUT)
This parameter displays the status of 4 to 20 mA DC output if a CPU failure occurs. In case of a failure, communication is disabled.
Setting of HIGH or LOW is enabled. This is done with the pin (CN4) on the CPU assembly. See Chapter 3 for details.
Standard specifications
The parameter is set to HIGH. If a failure, the transmitter outputs the signal of 110% or higher. The parameter
D53: ERROR OUT is set to HIGH from the factory.
Optional code/C1
The parameter is set to LOW. If a failure, output which is –5% or lower is generated. The parameter D53:
ERROR OUT is set to LOW from the factory.
• Example: Standard specifications pin (CN4) position: H
D52: BURN OUT
HIGH
• Example: Optional code/C1
D52: BURN OUT
LOW pin (CN4) position: L
F0825.EPS
(10) Output Status Setup when a Hardware
Error Occurs (D53: ERROR OUT)
This parameter allows the setting of the output status when a hardware error occurs. The following three selections are available.
(a) HOLD; Outputs the last value held before the error occurred.
(b) HIGH; Outputs an output of 110% when an error has occurred.
(c) LOW; Outputs an output of –5% when an error has occurred.
Note: A hardware error means CAP MODULE FAULT of Er.01 or
AMP MODULE FAULT of Er. 02 which are shown in 8.5.2
“Errors and Countermeasures.”)
• Example: Set the output status to LOW when
a hardware error occurs.
SET
D53:ERROR OUT
HIGH
< HIGH>
< LOW>
< HOLD>
ESC
Use the or key to select LOW .
Press the key twice to enter the setting.
F0826.EPS
8. BRAIN TERMINAL BT200 OPERATION
(11) Range Change while Applying Actual
Inputs (H10: AUTO LRV, H11: AUTO
HRV)
This feature allows the lower and higher range values to be set up automatically with the actual input applied.
If the lower and higher range values are set, C21:
LOW RANGE and C22: HIGH RANGE are changed at this same time.
Follow the procedure in the figure below.
The measurement span is determined by the higher and lower range values. Changing the lower range value results in the higher range value changing automatically, keeping the span constant.
• Example 1: When changing the lower range
value to 0.5 kPa for the present setting of 0 to 30 kPa, take the following action with input pressure of 0.5 kPa applied.
SET
H10:AUTO LRV
0 kPa
+ 0
SET
H10:AUTO LRV
0.5000 kPa
ESC
Press the key twice.
The lower range value is changed to 0.5 kPa.
Press the (OK) key.
FEED NO
PARAM
H10:AUTO LRV
0.5000 kPa
H11:AUTO HRV
30.500 kPa
H60:SELF CHEC
GOOD
DATA DIAG PRNT
OK
ESC
The higher range value is changed keeping the span constant.
Parameters C21 and C22 are changed at the same time.
F0827.EPS
Note that changing the higher range value does not cause the lower range value to change but does change the span.
8-12 IM 01C21C01-01E
• Example 2: When the higher range value is to
be changed to 10 kPa with the present setting of 0 to 30 kPa, take the following action with an input pressure of 10 kPa applied.
SET
H11:AUTO HRV
30 kPa
+ 30
Press the key twice.
The higher range value is changed to 10 kPa.
ESC
SET
H11:AUTO HRV
10.000 kPa
Press the (OK) key.
FEED NO
PARAM
H10:AUTO LRV
0 kPa
H11:AUTO HRV
10.000 kPa
H60:SELF CHECK
GOOD
DATA DIAG PRNT
OK
ESC
The lower range value is not changed, so the span changes.
Parameter C22 is changed at the same time.
F0828.EPS
(12) Zero Point Adjustment
(J10: ZERO ADJ, J11: ZERO DEV,
J20: EXT ZERO ADJ)
The DPharp supports several adjustment methods.
Select the method best suited for the conditions of your application.
Note that output signal can be checked by displaying parameter A10:OUTPUT (%) on the BT200.
Adjustment Method
Using the BT200
Using the external zero-adjustment screw
Description
Set the present input to 0%.
Adjust for 0% output at input level of
0%.
Adjust output to the reference value obtained using other means.
If the input level cannot easily be made 0% (because of tank level, etc.), adjust output to the reference value obtained using other means, such as a sight glass.
Adjust zero point using the zeroadjustment screw on the transmitter.
This permits zero adjustment without using the BT200. Accurately adjust the output current to 4 mA DC or other target output value using an ammeter that accuratly reads output currents.
T0809.EPS
8. BRAIN TERMINAL BT200 OPERATION
(a) Follow the procedure below when setting the present output to 0% (4 mA).
Output is 0.5%.
A10:OUTPUT (%)
0.5 %
SET
J10:ZERO ADJ
0.0 %
+ 000.0
Press the key twice.
SET
J10:ZERO ADJ
0.0 %
CLR ESC
Zero adjustment is completed.
Press the (OK) key.
FEED NO
A10:OUTPUT (%)
0.0 %
OK
Output is 0%.
F0829.EPS
(b) In tank level measurement, if the actual level cannot be brought to zero for zero adjustment, then the output can be adjusted to correspond to the actual level obtained using another measuring instrument such as a glass gauge.
Present level: 45%
Present output: 41%
100%
Present level
45%
0%
F0830.EPS
(b)-1 Follow the procedure below to use J10: ZERO
ADJ .
Present output is 41.0%.
A10:OUTPUT (%)
41.0 %
SET
J10:ZERO ADJ
0.0 %
+ 045.0
Enter the present actual level, 45%.
Press the key twice.
CLR ESC
A10:OUTPUT (%)
45.0 %
The output is changed to 45%.
F0831.EPS
8-13 IM 01C21C01-01E
(b)-2 Follow the procedure below to use J11: ZERO
DEV .
A10:OUTPUT (%)
41.0 %
SET
J11:ZERO DEV.
2.50 %
0
SET
J11:ZERO DEV.
2.50 %
6.50
Present output is 41.0%.
Output error = 45.0 – 41.0 = 4.0%.
ESC
Since “J11: ZERO DEV.” contains the previous correction, obtain the correction value by adding 4.0% to it. (2.50% + 4.0% = 6.50%)
Set the correction value, 6.50.
Press the key twice.
ECS
The output is changed to 45%.
A10:OUTPUT (%)
45.0 %
F0832.EPS
When the zero point is adjusted, the displayed value of
A40 is as follows.
[Example]
When the zero point is shifted by 20 kPa for the actual pressure, the parameter of A40 indicates 50 kPa.
70 kPa
50 kPa
20 kPa
0 kPa
Zero adjustment volume(J11)
Zero adjustment
Actual differential pressure/pressure
Input value of A40
0 kPa
F0841.EPS
(c) Zero Point Adjustment Using the External Zero
Adjustment Screw
• Enabling/inhibiting of zero point adjustment using the external zero-adjustment screw on the transmitter
(J20: EXT ZERO ADJ)
Follow the procedure below to enable or inhibit zero point adjustment from the zero-adjustment screw on the transmitter.
This is set to “ENABLE” when the instrument is shipped.
8. BRAIN TERMINAL BT200 OPERATION
• Example: Inhibiting zero adjustment by the
external zero-adjustment screw
SET
J20:EXIT ZERO ADJ
ENABLE
< ENABLE >
< INHIBIT>
ESC
Use the or key to select INHIBIT .
Press the key twice to enter the setting.
F0833.EPS
• Zero point adjustment using external zero-adjustment screw on the transmitter
Turn the zero-adjustment screw on the outside of the transmitter case using a slotted screwdriver. Turn the screw to the right to increase the zero point or to the left to decrease the zero output; the zero adjusts in increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point changes according to the speed at which the screw is turned. To make fine adjustments, turn the screw slowly; to make coarse adjustments, turn the screw quickly.
Note: When a zero point adjustment has been made, do not turn off the transmitter less than 30 seconds after adjustment.
(13) Test Output Setup (K10: OUTPUT X%)
This feature can be used to output a fixed current from
3.2 mA (–5%) to 21.6 mA (110%) for loop checks.
• Example: Output 12 mA (50%) fixed current.
SET
K10:OUTPUT X %
0.0 %
+ 050.0
Set 50.0
%.
Press the key twice to output a fixed current at 50%.
ESC
SET
K10:OUTPUT X %
50.0 % ACTIVE
FEED NO OK
“Active” is displayed while this is being executed.
Press the (OK) key to cancel the fixed current output.
F0834.EPS
IMPORTANT
1. Test output is held for approximately 10 minutes, and then released automatically after the time has elapsed. Even if the BT200 power supply is turned off or the communication cable is disconnected during test output, it is held for approximately 10 minutes.
2. Press the (OK) key to release test output immediately.
8-14 IM 01C21C01-01E
(14) User Memo Fields (M: MEMO)
This feature provides 5 user memo fields, each holding up to 8 alphanumeric characters. Up to 5 items such as inspection date, inspector, and other information can be saved in these fields.
• Example: Save an inspection date of January
30, 1995.
PARAM
M10:MEMO 1
M20:MEMO 2
M30:MEMO 3
DATA DIAG PRNT
SET
M10:MEMO 1
95.1.30_
ESC
Set 95.1.30
in the order of year, month, and day.
Press the key twice to enter the setting.
ESC
F0835.EPS
8. BRAIN TERMINAL BT200 OPERATION
8.4 Displaying Data Using the
BT200
8.4.1 Displaying Measured Data
The BT200 can be used to display measured data.
The measured data is updated automatically every 7 seconds. In addition, the display can be updated to the present data value at any time by pressing the
(DATA) key. For parameters associated with the display of measured data, see Subsection 8.3.1,
“Parameter Summary.”
• Example: Display output.
MENU
A:DISPLAY
B:SENSOR TYPE
HOME SET ADJ ESC
PARAM
A10:OUTPUT (%)
XX.X %
A11:ENGR.OUTPUT
YY.Y %
A20:AMP TEMP
ZZ deg C
DATA DIAG PRNT ESC
Display “A10: OUTPUT (%).”
Data is updated automatically at 7-second intervals.
PARAM
A10:OUTPUT (%)
A11:ENGR.OUTPUT
A20:AMP TEMP communi
8.4.2 Display Transmitter Model and
Specifications
The BT200 can be used to display the model and specifications of the transmitter.
F0836.EPS
• Example: View transmitter model name.
MENU
A:DISPLAY
B:SENSOR TYPE
Press .
HOME SET ADJ ESC
8-15
PARAM
B10:MODEL
EJA210A-DM
B11:STYLE NO.
S1.01
B20:LRL
– 98.07 kPa
DATA DIAG PRNT ESC
For the associated parameters, see Subsection
8.3.1, Parameter Summary.
F0837.EPS
IM 01C21C01-01E
8.5 Self-Diagnostics
8.5.1 Checking for Problems
(1) Identifying Problems with BT200
The following four areas can be checked.
(a) Whether connections are good.
(b) Whether BT200 was properly operated.
(c) Whether settings were properly entered.
(d) History of the errors.
See examples below.
• Example 1: Connection errors
––WELCOME––
BRAIN TERMINAL
ID: BT200 check connection push ENTER key
UTIL FEED
Press the key.
When the panel shown on the left appears, press the key.
communication error
ESC
Since communications will be unsuccessful if there is a problem in the connection to the BT200, the display at the left will appear.
Recheck the connection.
Press the (OK) key.
• Example 2: Setting entry errors
PARAM
01:MODEL
EJA210A-DM
02:TAG NO.
YOKOGAWA
03:SELF CHECK
ERROR
The initial data panel shows the result of current transmitter diagnostics.
OK
PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
600 kPa
C22:HIGH RANGE
600 kPa
DATA DIAG PRNT ESC
DIAG
C60:SELF CHECK
ERROR
< ERROR >
< ILLEGAL LRV >
Press the (DIAG) key in the parameter panel to go to the diagnostics panel
(C60: SELF CHECK).
An error message is displayed when an error occurs in the diagnostics panel.
FEED PRNT ESC
F0838.EPS
8. BRAIN TERMINAL BT200 OPERATION
• Example 3: Checking the history of the errors
MENU
J:ADJUST
K:TEST
M:MEMO
P:RECORD
Connect the BT200 to the transmitter, and call item P .
HOME SET ADJ ESC
PARAM
P10:ERROR REC 1
ERROR
P11:ERROR REC 2
ERROR
P12:ERROR REC 3
GOOD
DATA DIAG PRNT ESC
P10: “ERROR REC 1” displays the last error.
P11: “ERROR REC 2” displays the error one time before the last error occurred.
P12: “ERROR REC 3” displays the error two times before the last error occurred.
P13: “ERROR REC 4” displays the error three times before the last error occurred.
The history of up to four errors can be stored. When the 5th error has occurred, it is stored in “P10”. The error stored in
“P13” will be deleted, and then, the error in “P12” will be copied to “P13”. In this sequence, the history of the most previously occurred error will be removed from memory.
“GOOD” will be displayed if there was no previous error.
SET
P10:ERROR REC 1
ERROR
< ERROR >
< ILLEGAL LRV >
< ILLEGAL HRV >
ESC
<(a) SETUP PANEL>
Select P10: ERROR REC1 and press the key to display the error message.
For the details of the messages listed below, see Table
8.5.1 Error Message Summary.
CAP MODULE FAULT
AMP MODULE FAULT
OUT OF RANGE
OUT OF SP RANGE
OVER TEMP (CAP)
OVER TEMP (AMP)
OVER OUTPUT
OVER DISPLAY
ILLEGAL LRV
ILLEGAL HRV
ILLEGAL SPAN
ZERO ADJ OVER
Note 1: Press the key twice in the setting panel
(panel 1) to clear all error message (P10 to P13) information.
Note 2: After two hours from when an error occurs, the error message of that error will be recorded. Therefore, if you switch off the transmitter within two hours from when the error occurs, there is no history of that error stored in the transmitter, and this function is meaningless.
F0839.EPS
8-16 IM 01C21C01-01E
(2) Checking with Integral Indicator
NOTE
If an error is detected in the self-diagnostic, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at two-second intervals. See
Table 8.5.1 regarding the error numbers.
8. BRAIN TERMINAL BT200 OPERATION
F0840.EPS
Figure 8.5.1 Identifying Problems Using the Integral
Indicator
8-17 IM 01C21C01-01E
8. BRAIN TERMINAL BT200 OPERATION
8.5.2 Errors and Countermeasures
The table below shows a summary of error messages.
Table 8.5.1 Error Message Summary
Integral
Indicator
Display
None
----
Er. 01
BT200 Display
GOOD
ERROR
CAP MODULE
FAULT
Cause
Output Operation during Error
Countermeasure
Capsule problem.
*1
Outputs the signal
(Hold, High, or Low) set with parameter
D53.
Replace capsule.
*2
Er. 02
Er. 03
Er. 04
Er. 05
Er. 06
Er. 07
Er. 08
AMP MODULE
FAULT
OUT OF RANGE
OUT OF SP
RANGE
OVER TEMP
(CAP)
OVER TEMP
(AMP)
OVER OUTPUT
OVER DISPLAY
Amplifier problem.
Input is outside measurement range limit of capsule.
Static pressure exceeds specified range.
*3
Capsule temperature is outside range
(–50 to 130 ° C).
Amplifier temperature is outside range
(–50 to 95 ° C).
Output is outside high or low range limit value.
Displayed value is outside high or low range limit value.
Outputs the signal
(Hold, High, or Low) set with parameter
D53.
Outputs high range limit value or low range limit value.
Displays present output.
Displays present output.
Displays present output.
Outputs high or low range limit value.
Displays high or low range limit value.
Replace amplifier.
Check input.
Check line pressure
(static pressure).
Use heat insulation or make lagging to keep temperature within range.
Use heat insulation or make lagging to keep temperature within range.
Check input and range setting, and change them as needed.
Check input and display conditions and modify them as needed.
Check LRV and modify as needed.
Er. 09
Er. 10
Er. 11
Er. 12
ILLEGAL LRV
ILLEGAL HRV
ILLEGAL SPAN
LRV is outside setting range.
Holds output immediately before error occurrence.
HRV is outside setting range.
Holds output immediately before error occurrence.
SPAN is outside setting range.
Holds output immediately before error occurrence.
ZERO ADJ OVER Zero adjustment is too large.
Displays present output.
Check HRV and modify as needed.
Check SPAN and change as needed.
Readjust zero point.
*1: For Model EJA510A and EJA530A, this error code appears when an illegal overpressure is
applied to the pressure sensor in addition to the capsule problem. The Er. 01 will remain even if
the normal input pressure is regained.
*2: For Model EJA510A and EJA530A, restart the power to the transmitter. Then if no error code
appears, perform necessary adjustments such as zero-adjustment to continue the operation.
If the error code still exists, replace the capsule assembly.
*3: For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is
not a measured value.
T0811 .EPS
8-18 IM 01C21C01-01E
9. MAINTENANCE
9.
MAINTENANCE
9.1 Overview
WARNING
Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors during draining condensate or venting gas in transmitter pressure-detector section and even after dismounting the instrument from the process line for maintenance.
Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disassembly and reassembly procedures required for component replacement.
Since the transmitters are precision instruments, carefully and thoroughly read the following sections for proper handling during maintenance.
IMPORTANT
• As a rule, maintenance of this transmitter should be implemented in a maintenance service shop where the necessary tools are provided.
• The CPU assembly contains sensitive parts that may be damaged by static electricity.
Exercise care so as not to directly touch the electronic parts or circuit patterns on the board, for example, by preventing static electrification by using grounded wrist straps when handling the assembly. Also take precautions such as placing a removed CPU assembly into a bag with an antistatic coating.
9.2 Calibration Instruments Selection
Table 9.2.1 shows the instruments required for calibration. Select instruments that will enable the transmitter to be calibrated or adjusted to the required accuracy.
The calibration instruments should be handled carefully so as to maintain the specified accuracy.
9.3 Calibration
Use the procedure below to check instrument operation and accuracy during periodic maintenance or troubleshooting.
1) Connect the instruments as shown in Figure 9.3.1
and warm up the instruments for at least five minutes.
IMPORTANT
• To adjust the transmitter for highest accuracy, make adjustments with the power supply voltage and load resistance including leadwire resistances set close to the conditions under which the transmitter is installed.
• If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure should be applied as shown in the figure (low pressure side open to atmosphere). If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied on the low pressure side (high pressure side open to atmosphere).
2) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter. Calculate the errors (differences between digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from
100% to 0%, and confirm that the errors are within the required accuracy.
IM 01C21C01-01E 9-1
9. MAINTENANCE
Table 9.2.1 Instruments Required for Calibration
Name
Power supply
Yokogawa-recommended Instrument
Model SDBT or SDBS distributor
Remarks
4 to 20 mA DC signal
Load resistor
Voltmeter
Digital manometer
Pressure generator
Pressure source
Model 2792 standard resistor [250 1
±
0.005%, 3 W]
Load adjustment resistor [100 1
±
1%, 1 W]
Model 2501 A digital multimeter
Accuracy (10V DC range):
±
(0.002% of rdg + 1 dgt)
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy:
±
(0.015% of rdg + 0.015% of F.S.)
±
(0.2% of rdg + 0.1% of F.S.)
. . . . .
. . . . . . . . .
2) For 130 kPa class
Accuracy:
±
0.02% of rdg
±
5digits
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
±
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . .
3) For 700 kPa class
Accuracy:
±
(0.02% of rdg + 3digits)
±
5 digits
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
±
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . .
4) For 3000 kPa class
Accuracy:
±
(0.02% of rdg + 10 digits) . . . . . . . . . . .
±
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . .
5) For 130 kPa abs class
Accuracy:
±
(0.03% of rdg + 6 digits) . . . . . . . . . . . .
for 0 to 10 kPa for -10 to 0 kPa for 25 to 130 kPa for 0 to 25 kPa for -80 to 0 kPa for 100 to 700 kPa for 0 to 100 kPa for -80 to 0 kPa for 0 to 3000 kPa for -80 to 0 kPa for 0 to 130 kPa abs
Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm 2 }, 25 kPa {2500 mmH
2
O}
Accuracy:
±
0.05% of F.S.
Dead weight gauge tester 25 kPa {2500mmH
2
Accuracy:
±
0.03% of setting
O}
Select a manometer having a pressure range close to that of the transmitter.
Requires air pressure supply.
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Select the one having a pressure range close to that of the transmitter.
Prepare the vacuum pump for negative pressure ranges.
T0901.EPS
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% level, there are difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives from which the instrument was purchased or the nearest Yokogawa office.
Terminal box
Power supply
E
Load resistance, 250 1
Rc
Load adjusting resistance, 100 1
R
V
Digital voltmeter
(Note) For Model EJA220A transmitter
(diaphragm-extended type), prepare a mating calibration flange to match the diaphragm extension length and outer diameter.
Model 7674 pneumatic pressure standards
Supply pressure P
Model MT220 precision digital manometer
P
Pressure source
Reference pressure
Figure 9.3.1 Instrument Connections
Mating
(Note) calibration flange
9-2
F0901.EPS
IM 01C21C01-01E
9.4 Disassembly and Reassembly
This section describes procedures for disassembly and reassembly for maintenance and component replacement.
Always turn OFF power and shut off and release pressures before disassembly. Use proper tools for all operations. Table 9.4.1 shows the tools required.
Table 9.4.1 Tools for Disassembly and Reassembly
Tool
Phillips screwdriver
Slotted screwdriver
Allen wrenches
Quantity
1
1
2
Remarks
JIS B4633, No. 2
JIS B4648
One each, nominal 3 and
5 mm Allen wrenches
Width across flats, 17 mm Wrench
Torque wrench
Adjustable wrench
Socket wrench
Socket driver
Tweezers
1
1
1
1
1
1
Width across flats, 16 mm
Width across flats, 5.5 mm
T0902.EPS
CAUTION
Precautions for CENELEC and IECEx Flameproof Type Transmitters
• Flameproof type transmitters must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state.
• On the flameproof type transmitters the two covers are locked, each by an Allen head bolt
(shrouding bolt). When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.
When a cover is closed it should be locked by a shrouding bolt without fail. Tighten the shrouding bolt to a torque of 0.7 N·m.
9. MAINTENANCE
9.4.1 Replacing the Integral Indicator
CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the construction of a flameproof type transmitter.
This would invalidate the agency approval and the transmitter’s use in such rated area.
Thus the user is prohibited from using a flameproof type transmitter with its integral indicator removed, or from adding an integral indicator to a transmitter. If such modification is absolutely required, contact Yokogawa.
This subsection describes the procedure for replacing an integral indicator. (See Figure 9.4.2)
Removing the Integral Indicator
1) Remove the cover.
2) Supporting the integral indicator by hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU assembly.
When doing this, carefully pull the LCD board assembly straight forward so as not to damage the connector pins between it and the CPU assembly.
Shrouding Bolt
Figure 9.4 Shrouding Bolts
Shrouding Bolt
F0902.EPS
9-3 IM 01C21C01-01E
Attaching the Integral Indicator
Integral indicator can be installed in the following three directions.
Figure 9.4.1 Installation Direction of Indicator
1) Align both the LCD board assembly and CPU assembly connectors and engage them.
2) Insert and tighten the two mounting screws.
3) Replace the cover.
F0910.EPS
Output terminal cable
Press forward
LCD board assembly
Integral indicator
Cover
Mounting screw
Boss
Flat cable
CPU assembly
Bracket
(for zero-adjustment screw pin)
Zero-adjustment screw pin
F0903.EPS
Figure 9.4.2 Removing and Attaching LCD Board Assembly and CPU Assembly
9. MAINTENANCE
9.4.2 Replacing the CPU Board Assembly
This subsection describes the procedure for replacing the CPU assembly. (See Figure 9.4.2)
Removing the CPU Assembly
1) Remove the cover. If an integral indicator is mounted, refer to Subsection 9.4.1 and remove the indicator.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) as shown in Figure 9.4.2.
3) Disconnect the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage.
4) Use a socket driver (width across flats, 5.5mm) to loosen the two bosses.
5) Carefully pull the CPU assembly straight forward to remove it.
6) Disconnect the flat cable (cable with black connector at the end) that connects the CPU assembly and the capsule.
NOTE
Be careful not to apply excessive force to the
CPU assembly when removing it.
Mounting the CPU Assembly
1) Connect the flat cable (with black connector) between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown connector).
NOTE
Make certain that the cables are free of pinching between the case and the CPU assembly edge.
3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU board assembly straight onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is equipped with an integral indicator, refer to Subsection 9.4.1 to mount the indicator.
9-4 IM 01C21C01-01E
NOTE
Confirm that the zero-adjustment screw pin is placed properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero-adjustment mechanism will be damaged.
5) Replace the cover.
9.4.3 Replacing the Process Connector
Gasket
This subsection describes the procedure for replacing the process connector gasket. (See Figure 9.4.3.)
1) Loosen the two bolts and remove the process connector.
2) Replace the process connector gasket.
3) Mount the process connector. Tighten the bolts securely and uniformly to a torque of 39 to 49 N·m
{4 to 5 kgf·m}, and verify that there are no pressure leaks.
9. MAINTENANCE
9.5 Troubleshooting
If any abnormality appears in the measured values, use the troubleshooting flow chart below to isolate and remedy the problem. Since some problems have complex causes, these flow charts may not identify all.
If you have difficulty isolating or correcting a problem, contact Yokogawa service personnel.
9.5.1 Basic Troubleshooting
First determine whether the process variable is actually abnormal or a problem exists in the measurement system.
If the problem is in the measurement system, isolate the problem and decide what corrective action to take.
This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting; see
Section 8.5 for information on using this function.
: Areas where self-diagnostic offers support
Abnormalities appear in measurement.
Process connector gasket
Bolt
YES
Inspect the process system.
Is process variable itself abnormal?
NO
Measurement system problem
Isolate problem in measurement system.
Process connector
F0904.EPS
Figure 9.4.3 Replacing the Process Connector Gasket
YES
Inspect receiver.
Does problem exist in receiving instrument?
NO
9-5
Environmental conditions Transmitter itself
Check/correct environmental conditions.
Operating conditions
Check transmitter.
Check/correct operating conditions.
Figure 9.5.1 Basic Flow and Self-Diagnostics
F0905.EPS
IM 01C21C01-01E
9.5.2 Troubleshooting Flow Charts
The following sorts of symptoms indicate that transmitter may not be operating properly.
Example : • There is no output signal.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.
Connect BRAIN TERMINAL and check self-diagnostics.
Does the self-diagnostic indicate problem location?
NO
YES
Refer to error message summary in
Subsection 8.5.2 to take actions.
Is power supply polarity correct?
NO
YES Refer to Section 6.3 to check/correct polarity at each terminal from power supply to the terminal box.
Are power supply voltage and load resistance correct?
YES
NO
Refer to Section 6.6 for rated voltage and load resistance.
Are valves opened or closed correctly?
YES
NO
Fully open the low pressure valve.
YES
Is there any pressure leak?
NO Fix pressure leaks, paying particular attention to connections for impulse piping, pressure-detector section, etc.
Is there continuity through the transmitter loop wiring?
Do the loop numbers match?
YES
NO
Find/correct broken conductor or wiring error.
Contact Yokogawa service personnel.
F0906.EPS
9. MAINTENANCE
Output travels beyond 0% or 100%.
Connect BRAIN TERMINAL and check self-diagnostics.
Does the selfdiagnostic indicate problem location?
NO
YES
Refer to error message summary in
Subsection 8.5.2 to take actions.
Is power supply polarity correct?
YES
NO
Refer to Section 6.3 to check/correct polarity at each terminal from power supply to the terminal box.
Are valves opened or closed correctly?
YES
NO
Fully open the low pressure valve.
YES
Is there any pressure leak?
NO
Fix pressure leaks, paying particular attention to connections for impulse piping, pressure-detector section, etc.
Is zero point adjusted correctly?
YES
NO
Adjust the zero point.
Contact Yokogawa service personnel.
F0907.EPS
9-6 IM 01C21C01-01E
9. MAINTENANCE
Large output error.
Connect BRAIN TERMINAL and check self-diagnostics.
Does the selfdiagnostic indicate problem location?
NO
YES
Refer to error message summary in
Subsection 8.5.2 to take actions.
Are valves opened or closed correctly?
YES
NO
Fully open the low pressure valve.
Is impulse piping connected correctly?
YES
NO
Refer to individual model user manuals and connect piping as appropriate for the measurement purpose.
Are power supply voltage and load resistance correct?
YES
NO
Refer to Section 6.6 for rated voltage and load resistance.
Is transmitter installed where there is marked variation in temperature?
NO
YES
Provide lagging and/or cooling, or allow adequate ventilation.
Were appropriate instruments used for calibration?
YES
NO
Refer to Section 9.2 when selecting instruments for calibration.
NO
Is output adjusted correctly?
YES Adjust the output.
Contact Yokogawa service personnel.
F0908.EPS
9-7 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
10. GENERAL SPECIFICATIONS
10.1
Standard Specifications
Refer to IM 01C22T02-01E for F OUNDATION
Fieldbus communication type and IM 01C22T03-
00E for PROFIBUS PA communication type marked with “ ”.
Performance Specifications
See General Specifications sheet, GS 01C21C01-
00E.
Functional Specifications
Span & Range Limits:
Measurement
Span and Range
Span
M
Range kPa
1 to 100
–100 to 100 inH
2
O
(/D1)
4 to 400
–400 to 400 mbar
(/D3)
10 to 1000
–1000 to 1000 mmH
2
(/D4)
O
100 to 10000
–10000 to 10000
Span 5 to 500 20 to 2000 50 to 5000
0.05 to
5 kgf/cm 2
H
Range
–500 to 500
–2000 to 2000
–5000 to 5000
–5 to
5 kgf/cm 2
T1001.EPS
URL is define as the Upper Range Limit from the table above.
Zero Adjustment Limits:
Zero can be fully elevated or suppressed, within the Lower and Upper Range Limits of the capsule.
External Zero Adjustment “ ”:
External zero is continuously adjustable with
0.01% incremental resolution of span. Span may be adjusted locally using the digital indicator with range switch.
Output “ ”:
Two wire 4 to 20 mA DC output with digital communications, linear or square root programmable. BRAIN or HART FSK protocol are superimposed on the 4 to 20 mA signal.
Failure Alarm:
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more(standard)
Down-scale: -5%, 3.2 mA DC or less
-2.5%, 3.6 mA DC or less(Optional code /F1)
Note: Applicable for Output signal code D and E
10-1
Damping Time Constant (1st order):
The sum of the amplifier and capsule damping time constant must be used for the overall time constant. Amp damping time constant is adjustable from 0.2 to 64 seconds.
EJA210A EJA220A
Capsule (Silicone Oil)
Time Constant (approx. sec)
M H M H
0.4 0.4 0.4 0.4
Ambient Temperature Limits:
* Safety approval codes may affect limits.
–40 to 85 ° C (–40 to 185 ° F)
–30 to 80 ° C (–22 to 176 ° F) with LCD Display
Process Temperature Limits:
* Safety approval codes may affect limits.
–40 to 120 ° C (–40 to 248 ° F)
Working Pressure Limits (Silicone Oil)
2.7 kPa abs (0.38 psia) to flange rating
(see Figure 1.)
Installation
Supply & Load Requirements “ ”:
* Safety approvals can affect electrical requirements.
See Section 6.6, ‘Power Supply Voltage and Load
Resistance.’
Supply Voltage “ ”:
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code/A)
10.5 to 30 V DC for intrinsically safe, Type n, nonincendive, or non-sparking type
Minimum voltage limited at 16.4 V DC for digital communications, BRAIN and HART
EMC Conformity Standards:
EN61326, AS/NZS CISPR11
,
Communication Requirements “ ”:
BRAIN
Communication Distance;
Up to 2 km (1.25 miles) when using CEV polyethylene-insulated PVC-sheathed cables.
Communication distance varies depending on type of cable used.
Load Capacitance;
0.22
μ F or less (see note)
Load Inductance;
3.3 mH or less (see note)
Input Impedance of communicating device;
10 k 1 or more at 2.4 kHz.
Note: For general-use and Flameproof type.
For Intrinsically safe type, please refer to
‘Optional Specifications.’
IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
HART
Communication Distance;
Up to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies depending on type of cable used.
Use the following formula to determine cable length for specific applications:
L=
65 x 10 6
(R x C)
-
(C f
+ 10,000)
C
Where:
L = length in meters or feet
R = resistance in 1 (including barrier resistance)
C = cable capacitance in pF/m or pF/ft
C f
= maximum shunt capacitance of receiving devices in pF/m or pF/ft
Physical Specifications
Wetted Parts Materials:
High side:
See ‘Model and Suffix Codes’
Low side:
Diaphragm;
Hastelloy C-276
Cover flange;
SCS14A
Process connector;
SCS14A
Capsule gasket;
Teflon-coated SUS316L
Drain/Vent plug;
SUS316
Process connector gasket;
PTFE Teflon
Non-wetted Parts Materials:
Bolting;
SCM435, SUS630, or SUH660
Housing;
Low copper cast-aluminum alloy with polyurethane paint (Munsell 0.6GY3.1/2.0)
Degrees of Protection
IP67, NEMA4X, JIS C0920 immersion proof
Cover O-rings;
Buna-N
Data plate and tag;
SUS304
Fill Fluid;
Silicone or Fluorinated oil (optional)
Weight:
EJA210A with 150# flange 11 kg(25 lb)
EJA220A with 150# flange 16 kg(35 lb)
Connections:
Refer to the ‘Model and Suffix Codes’ to specify the process and electrical connection type.
The high pressure side is a flange connected, and low side is threaded.
100{14.5}
Working pressure kPa abs
{psi abs}
10{1.4}
Applicable range
Atmospheric pressure
2.7{0.38}
1{0.14}
-40
(-40)
0
(32)
40
(104)
80
(176)
Process temperature
°
C (
°
F)
120
(248)
F1001.EPS
Figure 1. Working Pressure and Process Temperature
< Settings When Shipped > “ ”
Tag Number
Output Mode
Display Mode
Operation Mode
As specified in order *1
‘Linear’
‘Linear’
‘Normal’ unless otherwise specified in order
Damping Time
Constant
Calibration Range
Lower Range Value
‘2 sec.’
As specified in order
Calibration Range
Higher Range Value
As specified in order
Calibration Range
Units
Selected from mmH
2
O, mmAq, mmWG, mmHg, Pa, hPa, kPa, MPa, mbar, bar, gf/cm 2 , kgf/cm 2 , inH
2
O, inHg, ftH
(Only one unit can be specified)
2
O, or psi.
M1003.EPS
*1: Up to 16 alphanumeric characters (including - and
· ) will be entered in the amplifier memory.
10-2 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
10.2
Model and Suffix Codes
Model EJA210A
Model Suffix Codes
. . . . . . . . . . . . . . . . . . . . .
Description
EJA210A
Flange-mounted differential pressure transmitter
(Flush diaphragm type)
Output Signal -D . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . (Note 1)
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol)
-F . . . . . . . . . . . . . (Note 5)
-G . . . . . . . . . . . . . (Note 6)
Digital communication (F OUNDATION Fieldbus protocol)
Digital communication (PROFIBUS PA protocol)
Measurement span
(capsule)
M . . . . . . . . . . . . . . . . .
1 to 100 kPa {100 to 10000 mmH
2
O}
5 to 500 kPa {0.05 to 5 kgf/cm 2 }
H . . . . . . . . . . . . . . . . . .
High pressure side
(Process flange side) wetted parts material
(Note 2)
S . . . . . . . . . . . (Note 3)
H . . . . . . . . . . . (Note 3)
T . . . . . . . . . . . (Note 3)
W . . . . . . . . . .
(Note 4)
[Diaphragm] [Others]
SUS316L
Hastelloy C-276
Tantalum
Hastelloy C-276
SUS316
Hastelloy C-276
Tantalum
SUS316
Process flange rating
J1 . . . . . . . . . . . . . .
JIS10K
J2 . . . . . . . . . . . . . .
JIS20K
A1 . . . . . . . . . . . . . .
ANSI Class 150
A2 . . . . . . . . . . . . . .
ANSI Class 300
P1 . . . . . . . . . . . . . .
JPI Class150
P2 . . . . . . . . . . . . . .
JPI Class 300
D2 . . . . . . . . . . . . . .
DIN PN10/16
Process flange size/material
Low pressure side process connection
D4 . . . . . . . . . . . . . .
D . . . . . . . . . . . . . .
DIN PN25/40
3-inch (80 mm) /S25C
E . . . . . . . . . . . . . .
3-inch (80 mm) /SUS304
F . . . . . . . . . . . . . .
3-inch (80 mm) /SUS316
A . . . . . . . . . . . . . .
2-inch (50 mm) /SU25C
B . . . . . . . . . . . . . .
2-inch (50 mm) /SUS304
C . . . . . . . . . . . . . .
2-inch (50 mm) /SUS316
0 . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flange)
1 . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . with 1/4NPT female process connector
4 . . . . . . . . . . . . .
5 . . . . . . . . . . . . .
with 1/2NPT female process connector without process connector (1/4 NPT female on the cover flange)
Bolts and nuts material
Installation
Electrical connection
A . . . . . . . . . . .
B . . . . . . . . . . .
C . . . . . . . . . . .
-9 . . . . . . . . . .
0 . . . . . . . . .
2 . . . . . . . . .
SCM435
SUS630
SUH660
Horizontal impulse piping type, left side high pressure
G1/2 female, one electrical connection
1/2 NPT female, two electrical connections without blind plug
3 . . . . . . . . .
4 . . . . . . . . .
Pg 13.5 female, two electrical connections without blind plug
M20 female, two electrical connections without blind plug
5 . . . . . . . . .
7 . . . . . . . . .
G1/2 female, two electrical connections and a blind plug
1/2 NPT female, two electrical connections and a blind plug
8 . . . . . . . . .
9 . . . . . . . . .
Pg 13.5 female, two electrical connections and a blind plug
M20 female, two electrical connections and a blind plug
Integral indicator
D . . . . . . . .
E . . . . . . . .
Digital indicator
Digital indicator with the range setting switch
N . . . . . . . .
N . . . . . .
(None)
Always N
Optional codes
/ Optional specification
T1002.EPS
Example: EJA210A-DMSA1D5A-92NN/
Note 1: Refer to IM 01C22T01-01E for HART Protocol version.
Note 2: Low pressure side wetted parts material: Cover flange; SCS14A, Process connector; SCS14A,
Capsule; SUS316L (Diaphragm; Hastelloy C-276), Vent plug; SUS316
Note 3: Applicable only for 3-inch (80 mm) flange size (Process flange size/material codes D and E )
Note 4: Applicable only for 2-inch (50 mm) flange size (Process flange size/material codes A and B )
Note 5: Refer to IM 01C22T02-01E for Fieldbus communication.
Note 6: Refer to IM 01C22T03-00E for PROFIBUS PA communication.
10-3 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
Model EJA220A
Model
EJA220A
Output Signal
Measurement span
(capsule)
High pressure side
(Process flange side) wetted parts material
(Note 2)
Suffix Codes
. . . . . . . . . . . . . . . . . . .
Description
Flange-mounted differential pressure transmitter
(Extended diaphragm type)
-D . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . (Note 1)
-F . . . . . . . . . . . . (Note 5)
-G . . . . . . . . . . .
(Note 6)
M . . . . . . . . . . . . . . . .
H . . . . . . . . . . . . . . . .
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol)
Digital communication (F OUNDATION Fieldbus protocol)
Digital communication (PROFIBUS PA protocol)
1 to 100 kPa {100 to 10000 mmH
2
O}
5 to 500 kPa {0.05 to 5 kgf/cm 2 }
[Diaphragm] [Pipe] [Others]
S . . . . . . . . . . (Note 3)
W . . . . . . . . .
(Note 4)
Hastelloy C-276 SUS316 SUS316
Process flange rating
Diaphragm extension length (X
2
)
Process flange size/material
J1 . . . . . . . . . . . .
J2 . . . . . . . . . . . . .
A1 . . . . . . . . . . . . .
A2 . . . . . . . . . . . . .
P1 . . . . . . . . . . . . .
P2 . . . . . . . . . . . . .
D2 . . . . . . . . . . . . .
D4 . . . . . . . . . . . . .
2 . . . . . . . . . . . . .
4 . . . . . . . . . . . . .
6 . . . . . . . . . . . . .
G . . . . . . . . . . .
H . . . . . . . . . . .
J . . . . . . . . . . .
D . . . . . . . . . . .
E . . . . . . . . . . .
F . . . . . . . . . . .
JIS10K
JIS20K
ANSI Class 150
ANSI Class 300
JPI Class 150
JPI Class 300
DIN PN10/16
DIN PN25/40
X
2
=50 mm
X
2
=100 mm
X
2
=150 mm
4-inch (100 mm) / S25C
4-inch (100 mm) / SUS304
4-inch (100 mm) / SUS316
3-inch (80 mm) / S25C
3-inch (80 mm) / SUS304
3-inch (80 mm) / SUS316 without process connector (Rc1/4 female on the cover flanges) connection 1 . . . . . . . . . .
with Rc1/4 female process connector
2 . . . . . . . . . .
with Rc1/2 female process connector
3 . . . . . . . . . .
with 1/4 NPT female process connector
Bolts and nuts material
Installation
Electrical connection
Integral indicator
4 . . . . . . . . . .
5 . . . . . . . . . .
A . . . . . . . . .
with 1/2 NPT female process connector without process connector (1/4 NPT female on the cover flanges)
SCM435
B . . . . . . . . .
C . . . . . . . . .
SUS630
SUH660
-9 . . . . . . .
Horizontal impulse piping type, left side high pressure
0 . . . . . .
G1/2 female, one electrical connection
2 . . . . . .
1/2 NPT female, two electrical connections without blind plug
3 . . . . . .
Pg 13.5 female, two electrical connections without blind plug
4 . . . . . .
M20 female, two electrical connections without blind plug
5 . . . . . .
G1/2 female, two electrical connections and a blind plug
7 . . . . . .
1/2 NPT female, two electrical connections and a blind plug
8 . . . . . .
Pg 13.5 female, two electrical connections and a blind plug
9 . . . . . .
M20 female, two electrical connections and a blind plug
D . . . . .
Digital indicator
E . . . . .
Digital indicator with the range setting switch
N . . . . .
N . . . .
(None)
Always N
Optional codes / Optional specification
T1003.EPS
Example: EJA220A-DMSA12G5A-92NN/
Note 1: Refer to IM 01C22T01-01E for HART Protocol version.
Note 2: Low pressure side wetted parts material: Cover flange; SCS14A, Process connector; SCS14A,
Capsule; SUS316L (Diaphragm, Hastelloy C-276), Vent plug ; SUS316
Note 3: Applicable only for 4-inch (100 mm) flange size (Process flange size/material codes G and H ).
Note 4: Applicable only for 3-inch (80 mm) flange size (Process flange size/material codes D and E ).
Note 5: Refer to IM 01C22T02-01E for Fieldbus communication.
Note 6: Refer to IM 01C22T03-00E for PROFIBUS PA communication.
10-4 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
10.3
Optional Specifications
For F OUNDATION Fieldbus explosion protected type, see IM 01C22T02-01E.
For PROFIBUS PA explosion protected type, see IM 01C22T03-00E.
Item
Factory Mutual (FM)
CENELEC ATEX
*1:
*2:
Description
FM Explosionproof Approval *1
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
Temperature class: T6
Amb. Temp.: –40 to 60 C (–40 to 140 F)
FM Intrinsically safe Approval *1
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60 C (–40 to 140 F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 H
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 H
Combined FF1 and FS1 *1
CENELEC ATEX (KEMA) Flameproof Approval *2
Certificate: KEMA 02ATEX2148
II 2G EExd IIC T4, T5, T6
Amb. Temp.: T5; –40 to 80 C ( –40 to 176 F), T4 and T6; –40 to 75 C ( –40 to 167 F)
Max. process Temp.: T4; 120 C (248 F), T5; 100 C (212 F), T6; 85 C (185 F)
CENELEC ATEX (KEMA) Intrinsically safe Approval
Certificate: KEMA 02ATEX1030X
*2
II 1G EEx ia IIC T4, Amb. Temp.: –40 to 60 C (–40 to 140 F)
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 H
Combined KF2, KS2 and Type n *2
Type n
II 3G Ex nL IIC T4, Amb. Temp.: –40 to 60
°
C (–40 to 140
°
F)
Ui=30 V DC, Ci=22.5 nF, Li=730
μ
H
Dust
II 1D maximum surface temperature T65
°
C (149 F) {Tamb.: 40
°
C (104 F)},
T85
°
C (185 F) {Tamb.: 60
°
C (140 F)}, T105
°
C (221 F) {Tamb.: 80
°
C (176 F)}
Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
Applicable for Electrical connection code 2, 4, 7 and 9 (1/2 NPT and M20 female).
Code
FF1
FS1
FU1
KF2
KS2
KU2
T1004-1.EPS
10-5 IM 01C21C01-01E
IECEx
Scheme
Item
Canadian Standards
Association (CSA)
10. GENERAL SPECIFICATIONS
*1:
*2:
Description
CSA Explosionproof Approval *1
Certificate: 1089598
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 ‘SEALS NOT REQUIRED’ , Temp. Class: T4, T5, T6 Encl Type 4x
Max. Process Temp.: T4; 120 C (248 F), T5; 100 C (212 F), T6; 85 C (185 F)
Amb. Temp.: –40 to 80 C (–40 to 176 F)
CSA Intrinsically safe Approval *1
Certificate: 1053843
Intrinsically Safe for Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Nonincendive for Class I, Division 2, Groups A, B, C and D Class II, Division 2,
Groups F and G and Class III (not use Safety Barrier)
Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60 C (–40 to 140 F)
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 H
Combined CF1 and CS1 *1
IECEx Intrinsically safe, type n and Flameproof Approval *2
Intrinsically safe and type n
Certificate: IECEx KEM 06.0007X
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67
Amb. Temp.: –40 to 60 C (–40 to 140 F), Max. Process Temp.: 120 C (248 F)
Electrical Parameters: [Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 H
[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730 H
Flameproof
Certificate: IECEx KEM 06.0005
Ex d IIC T6...T4 Enclosure: IP67
Max.Process Temp.: T4;120 C (248 F), T5;100 C (212 F), T6; 85 C (185 F)
Amb.Temp.: –40 to 75 C (–40 to 167 F) for T4, –40 to 80 C (–40 to 176 F) for T5,
–40 to 75 C (–40 to 167 F) for T6
Code
CF1
CS1
CU1
SU2
T1004-2.EPS
Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
Applicable for Electrical connection code 2, 4 and 7 (1/2 NPT and M20 female).
10-6 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
Painting
Item
Color change
Coating change
Lightning protector
Oil-prohibited use
Oil-prohibited use with dehydrating treatment
Calibration units
Description
Amplifier cover only
Amplifier cover and terminal cover, Munsell 7.5 R4/14
Epoxy resin-baked coating
Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type, 9 to 32 V DC for F OUNDATION Fieldbus and PROFIBUS PA communication type.)
Allowable current: Max. 6000 A (1 â´›
40
μ s ), Repeating 1000 A,100 times
Degrease cleansing treatment
Degrease cleansing treatment with fluorinated oil filled capsule.
Operating temperature –20 to 80 ° C
Degrease cleansing and dehydrating treatment
Degrease cleansing and dehydrating treatment with fluorinated oil filled capsule.
Operating temperature –20 to 80
°
C
P calibration (psi unit ) bar calibration (bar unit )
( See Table for Span and Range Limits. )
M calibration ( kgf/cm 2 unit )
Code
P
PR
X1
A
K1
K2
K5
K6
D1
D3
D4
Sealing treatment to
SUS630 nuts
No serration
Teflon film
Fast response * 2
Failure alarm down-scale * 1
NAMUR NE43 compliant * 1
Stainless steel amplifier housing
Gold-plate
Stainless steel tag plate
Mill Certificate
Pressure test/
Leak test
Certificate
Sealant ( liquid silicone rubber ) Y
No serration work on the flange gasket surface ( for ANSI flange only )
With FEP film and fluorinated oil. Working range: 20 to 120
°
C, 0 to 2 MPa {0 to 20 kgf/cm 2 }
(Not usable under vacuum )
Update time: 0.125 sec or less, see GS for response time
Output status at CPU failure and hardware error is –5%, 3.2 mA or less.
Output signal limits:
3.8 mA to 20.5 mA
Failure alarm down-scale: output status at CPU failure and hardware error is –5%, 3.2 mA or less.
Failure alarm up-scale: output status at CPU failure and hardware error is 110%, 21.6 mA or more.
Amplifier housing material: SCS14A stainless steel
(equivalent to SUS316 cast stainless steel or ASTM CF-8M)
Q
T
F1
C1
C2
C3
E1
* 1:
* 2:
Gold-plated diaphragm for high pressure side (process flange side)
JIS SUS304 stainless steel tag plate wired onto transmitter
High pressure side: Process flange, Block
Low pressure side: Cover flange
High pressure side: Process flange, Block
Low pressure side: Cover flange, Process connector
High pressure side: Process flange, Block, Pipe, Base
Low pressure side: Cover flange
For model
EJA210A
A1
N4
M03
M13
High pressure side: Process flange, Block, Pipe, Base
Low pressure side: Cover flange, Process connector
( Flange rating )
JIS 10K
JIS 20K
ANSI/JPI class 150
ANSI/JPI class 300
ANSI/JPI class 300
( Test Pressure )
2MPa {20 kgf/cm
2
}
5MPa {50 kgf/cm 2 }
3MPa {29.8 kgf/cm 2 }
7.7MPa {77 kgf/cm 2 }
7MPa {70 kgf/cm 2 }
For model
EJA220A
Nitrogen ( N
2
) Gas
Retention time: 10 minutes
M04
M14
T31
T32
T36
T37
T38
Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or
T1005.EPS
capsule. When combining with Optional code F1, output status for down-scale is –2.5%,
3.6 mA DC or less.
Applicable for Output signal code D and E. Write protection switch is attached for Output code E.
10-7 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
10.4
Dimensions
Model EJA210A
External indicator conduit connection
Blind plug
(Optional)
25
(0.98) t
174 (6.85)
133 (5.24)
30 (1.18)
Conduit connection
Internal indicator
(Optional)
163
(6.42)
Shrouding bolt *
2
Zero adjustment
ø78
(3.07)
110 (4.33)
35
(1.38)
Terminal side
146
(5.75)
Ground terminal
øD øC øg ød*
1
46
(1.81)
Process flange
Process connector
(Optional) n- øh
54
(2.13)
*1 Indicates inside diameter of gasket contact surface.
*2 Applicable only for ATEX and IECEx Flameproof type.
Flange size: 3-inch (80 mm)
Flange Nominal
Diameter and
Rating
øD øC øg ød t
Bolt Holes
No.(N) Dia.(øh)
80 mm JIS 10K
80 mm JIS 20K
185(7.28)
200(7.87)
150(5.91) 130(5.12) 90(3.54)
160(6.30) 130(5.12) 90(3.54)
18(0.71)
22(0.87)
3-inch ANSI Class150 190.5(7.50) 152.4(6.00) 130(5.12) 90(3.54) 23.9(0.94)
3-inch ANSI Class300 209.6(8.25) 168.1(6.62) 130(5.12) 90(3.54) 28.5(1.12)
3-inch JPI Class150
3-inch JPI Class300
190(7.48) 152.4(6.00) 130(5.12) 90(3.54) 24(0.44)
210(8.27) 168.1(6.62) 130(5.12) 90(3.54) 28.5(1.12)
20(0.79) 3-inch DIN PN 10/16
3-inch DIN PN 25/40
200(7.87)
200(7.87)
Flange size: 2-inch (50 mm)
Flange Nominal
Diameter and
Rating
øD
160(6.30) 130(5.12) 90(3.54)
160(6.30) 130(5.12) 90(3.54)
øC øg ød
24(0.44) t
8
8
8
4
8
8
4
8
19(0.75)
23(0.91)
19.1(0.75)
22.4(0.88)
19(0.75)
22(0.87)
18(0.71)
18(0.71)
Bolt Holes
No.(N) Dia.(øh)
50 mm JIS 10K
50 mm JIS 20K
155(6.10)
155(6.10)
120(4.72) 100(3.94) 61(2.40)
120(4.72) 100(3.94) 61(2.40)
16(0.63)
18(0.71)
2-inch ANSI Class150 152.4(6.00) 120.7(4.75) 100(3.94) 61(2.40) 19.1(0.75)
2-inch ANSI Class300 165.1(6.50) 127(5.00) 100(3.94) 61(2.40) 22.4(0.88)
2-inch JPI Class150
2-inch JPI Class300
2-inch DIN PN 10/16
152(5.98) 120.6(4.75) 100(3.94) 61(2.40) 19.5(0.71)
165.1(6.50) 127(5.00) 100(3.94) 61(2.40) 22.5(0.89)
165(6.50) 125(4.92) 100(3.94) 61(2.40) 18(0.71)
2-inch DIN PN 25/40 165(6.50) 125(4.92) 100(3.94) 61(2.40) 20(0.79)
4
4
4
8
4
8
4
8
19(0.75)
19(0.75)
19.1(0.75)
19.1(0.75)
19(0.75)
19(0.75)
18(0.71)
18(0.71)
Vent plug
Drain plug
F1003.EPS
10-8 IM 01C21C01-01E
10. GENERAL SPECIFICATIONS
Model EJA220A
External indicator conduit connection
Blind plug
(Optional)
174 (6.85)
133 (5.24)
30 (1.18)
Conduit connection
Internal indicator
(Optional)
163
(6.42)
Shrouding bolt *
1
Zero adjustment
ø78
(3.07)
110 (4.33)
35
(1.38)
øD øC øg øA
X
2 t
Process connection
46
(1.81)
Process flange
Process connector
(Optional)
25 (0.98) n- øh
54
(2.13)
*1 Applicable only for ATEX and IECEx Flameproof type.
Flange size: 4-inch (100 mm)
Flange Nominal
Diameter and
Rating
4-inch JPI Class150
4-inch JPI Class300
4-inch DIN PN 10/16
4-inch DIN PN 25/40
øD øC øg øA
229(9.02) 190.5(7.50) 155(6.10) 96(3.78)
254(10.00) 200.2(7.88) 155(6.10) 96(3.78)
220(8.66) 180(7.09) 155(6.10) 96(3.78)
235(9.25) 190(7.50) 155(6.10) 96(3.78) t
100 mm JIS 10K
100 mm JIS 20K
210(8.27) 175(6.89) 155(6.10) 96(3.78)
225(8.86) 185(7.28) 155(6.10) 96(3.78)
18(0.71)
24(0.94)
4-inch ANSI Class150 228.6(9.00) 190.5(7.50) 155(6.10) 96(3.78) 23.9(0.94)
4-inch ANSI Class300 254(10.00) 200(7.87) 155(6.10) 96(3.78) 31.8(1.25)
24(0.94)
32(1.26)
20(0.79)
24(0.94)
Bolt Holes
No.(N) Dia.(øh)
8 19(0.75)
8
8
8
8
8
8
8
23(0.91)
19.1(0.75)
22.4(0.88)
19(0.75)
22(0.87)
18(0.71)
22(0.87)
Flange size: 3-inch (80 mm)
Flange Nominal
Diameter and
Rating
80 mm JIS 10K
øD øC øg øA
185(7.28) 150(5.91) 130(5.12) 71(2.80) t
18(0.71)
80 mm JIS 20K 200(7.87) 160(6.30) 130(5.12) 71(2.80) 22(0.87)
3-inch ANSI Class150 190.5(7.50) 152.4(6.00) 130(5.12) 71(2.80) 23.9(0.94)
3-inch ANSI Class300 209.6(8.25) 168.1(6.62) 130(5.12) 71(2.80) 28.5(1.12)
3-inch JPI Class150 190(7.48) 152.4(6.00) 130(5.12) 71(2.80) 24(0.94)
3-inch JPI Class300
3-inch DIN PN 10/16
3-inch DIN PN 25/40
210(8.27) 168.1(6.62) 130(5.12) 71(2.80) 28.5(1.12)
200(7.88)
200(7.87)
160(6.30) 130(5.12) 71(2.80)
160(6.30) 130(5.12) 71(2.80)
20(0.79)
24(0.94)
Bolt Holes
No.(N) Dia.(øh)
8
8
4
8
4
8
8
8
19(0.75)
23(0.91)
19.1(0.75)
22.4(0.88)
19(0.75)
22(0.87)
18(0.71)
18(0.71)
Terminal side
146
(5.75)
Ground terminal
Vent plug
Drain plug
Diaphragm Extension Length Code
2
4
6
X
2
1.97 inch (50 mm)
3.94 inch (100 mm)
5.91 inch (150 mm)
F1004.EPS
10-9 IM 01C21C01-01E
Customer
Maintenance
Parts List
DPharp EJA Series
Transmitter Section
2
5
11
A
3
4
10
13
12
1
2
2
1
14
A
7-1
8 9
6
5
7-2
Item Part No.
Qty Description
1
2
3
4
5
6
7-1
Bellow
F9341RA
F9341RJ
F9341JP
Below
F9341AA
F9341AC
F9341AE
F9341AH
F9341AJ
F9341AR
—
Bellow
F9300AG
Y9303JU
F9341KL
Below
F9342AB
F9342AL
F9342AF
2
2
1
1
4
1
1
Cover
Cast-aluminum alloy
SCS14A stainless steel
O-ring
Case Assembly (Note 1)
Cast-aluminum alloy for G1/2
Cast-aluminum alloy for G1/2 (two electrical connections)
Cast-aluminum alloy for 1/2 NPT (two electrical connections)
Cast-aluminum alloy for M20 (two electrical connections)
Cast-aluminum alloy for Pg13.5 (two electrical connections)
SCS14A stainless steel for 1/2 NPT (two electrical connections)
Name Plate
Screw
For cast-aluminum alloy case assembly
For SCS14A stainless steel case assembly
Tag Plate
CPU Assembly
For BRAIN protocol version
For HART protocol version
For BRAIN protocol version(Optional code /F1)
7-2
8
9
10
F9342AM
F9342BF
F9342BG
Y9406ZU
Y9612YU
Below
F9340NW
F9340NX
G9330DP
G9612EB
1
2
2
1
For HART protocol version with write protection switch (Optional code /F1)
For F
OUNDATION
Fieldbus protocol version
For F OUNDATION Fieldbus protocol version with PID/LM function (Optional code /LC1)
Cap Screw
Screw
Plug
For Pg13.5
For M20
For G1/2
For 1/2 NPT
11
12
Bellow
F9341FM
F9341FJ
Below
F9342BL
1
1
Cover Assembly
Cast-aluminum alloy
SCS14A stainless steel
LCD Board Assembly
Without range-setting switch For integral indicator
13
14
F9342BM
F9342MK
F9300PB
2
2
With range-setting switch
Mounting Screw
Label
(Note 1) Applicable for BRAIN and HART protocol versions (Output signal code D and E). For F
OUNDATION
Fieldbus protocol version (Output signal code F), consult Yokogawa local office.
All Rights Reserved, Copyright © 1997, Yokogawa Electric Corporation.
Subject to change without notice. Printed in Japan.
CMPL 01C21A01-02E
10th Edition: Jan. 2008(KP)
Yokogawa Electric Corporation
Customer
Maintenance
Parts List
Model EJA210A and EJA220A
Flange Mounted Differential
Pressure Transmitter
(Pressure-detector Section)
1
EJA210A EJA220A
4
3
5
8
9
2
10
7
6
Item Part No.
Qty Description
1
2
3
4
5
6
7
F9300AJ
Below
D0114RB
U0102XC
Below
F9340XY
F9340XW
F9340XZ
F9340XX
Below
X0100MN
F9273DZ
F9340AZ
Below
F9340SA
F9340SB
D0114PB
Below
F9200CS
D0114RZ
1
1
1
2
1
1
1
O-Ring
Gasket
PTFE Teflon
PTFE Teflon (degreased)
Process Connector, SCS14A Stainless Steel (Note 1)
Rc 1/4
Rc 1/2
1/4 NPT
Bolt
1/2 NPT
SCM435 Chrome Molybdenum Steel
SUS630 Stainless Steel
SUH660 Stainless Steel
Vent Plug, SUS316 Stainless Steel
R 1/4
1/4 NPT
Vent Screw, SUS316 Stainless Steel
Drain Plug, SUS316 Stainless Steel (Note 1)
R 1/4
1/4 NPT
8
9
10
Below
F9275EC
F9275ED
F9275EE
Y9625YU
1
1
2
Vent Plug (degreased), SUS316 Stainless Steel
R 1/4
1/4 NPT
Needle Assembly (degreased), SUS316 Stainless Steel
Bolt
(Note 1) In case of degrease cleansing treatment (Optional Code/K1, K2, K5 and K6), consult YOKOGAWA local office.
Yokogawa Electric Corporation
All Rights Reserved, Copyright © 1997, Yokogawa Electric Corporation.
Subject to change without notice. Printed in Japan.
CMPL 01C21C01-01E
4th Edition: July 2001(YK)
Edition
1st
2nd
3rd
4th
5th
6th
Date
Jun. 1997
Mar. 1998
Sep. 1998
Oct. 1999
Sep. 2000
July 2001
REVISION RECORD
Title: Model EJA210A, EJA220A Flange Mounted Differential Pressure Transmitter
Manual No.: IM 01C21C01-01E
Page
–
CONTENTS
1-1
6-1
11-1
11-3
11-6
2-9+
CMPL
–
2-13
8-17
11-3
11-4
CMPL
-
2-8
8-4
CMPL
2-8
2-9
8-5
10-2
10-3
10-4
10-5
10-6
CMPL
2-10
8-4, 8-5
CMPL
Revised Item
New publication
Page 3
1
• Add REVISION RECORD.
• Add ‘NOTE’ notice for F OUNDATION Fieldbus and HART
protcol versions.
• Add Item to the Wiring Precautions.
6.1
11.1
11.2
11.3
• Add FOUNDATOIN Fieldbus protocol.
• Add Output signal code F.
• Add Optional code A1.
• Change the figure of terminal configuration.
CMPL 1C21A1-02E 1st 2nd
Page 2 • Add item 7-2.
Changed to Electronic File Format.
2.10
• Delete EMC Conformity Standards Tables.
8.3.2(9)
11.2
• Correction made in BURN OUT figure.
• Add Process flange size / material code F and C.
• Add Electrical connection code 7, 8, and 9.
• Add Process flange size / material code F and J.
• Add Electrical connection code 7, 8, and 9.
CMPL 1C21A1-02E 2nd 3rd
Page 2 • Add Part No. to Item 3 (For PG13.5 and M20).
• Add Part No. to Item 10 (For 1/2NPT, PG13.5, and M20).
Revised a book in a new format.
(The location of contents and the associated page numbers may
2.10
8.3.1
not coincide with the one in old editions.)
• Add AS/NZS 2064 1/2 to EMI, EMC Conformity Standards.
• Move Parameter Summary table to Chapter 8.
CMPL 1C21A1-02E 3rd 4th
• Change a format.
CMPL 1C21C1-01E 1st 2nd
• Change a format.
2.9.4b
2.9.4b
8.3.1
10.1
10.2
10.3
• Change contents of NOTE 1.
• Change contents of NOTE 4.
• Add footnote 2 and 3.
• Add calibration units of Pa and hPa.
• Add Bolts and nuts material code C.
• Add Bolts and nuts material code C.
• Add Amb. Temp. for T6: –40 to 75
°
C
• Add Optional code /F1 and /N4.
CMPL 1C21A1-02E 4th 5th(Manual Change)
• Add part numbers to 7-1 CPU Assembly.
F9342AF and F9342AM
CMPL 1C21A1-02E 5th 6th
• Add part numbers to 7-2 CPU Assembly.
F9342BG
• Change part number of 7-1 CPU Assembly.
F9342BC A F9342BB
• Change part number of 10 Plug
G9330DK A G9330DP
CMPL 1C21C1-01E 2nd 3rd
• Add part number to 4 Bolt.
F9340AZ
2.10
8.3.1
• Change EMC Conformity number.
• Add footnote (*4) to B40, Maximum static pressure in Parameter
Summary.
CMPL 1C21A1-02E 6th 7th(Manual Change)
• Change Part No. of 7-1 CPU Assembly for BRAIN protocol.
F9342BB A F9342AB
REVISION RECORD.EPS
IM 01C21C01-01E
Edition
6th
(Continued)
7th
8th
9th
Date
July 2001
May 2002
Apr. 2003
Apr. 2006
10th Jan. 2008
Page
CMPL
1-2
2-7
10-5
10-6
2-8
2-10
10-5
1-2
1-3
2-6
2-11
10-5, 10-6
10-6
10-7
1-1
1-4
2-3+
2-10
4-2
8-14
9-3
10-1+
10-5, -6
CMPL
Revised Item
CMPL 1C21A1-02E 7th 8th(Manual Change)
• Change Part No. of 7-1 CPU Assembly for HART protocol.
F9342BH A F9342AL
CMPL 1C21A1-02E 8th CMPL 01C21A01-02E 9th
• Delete Part No. of 4 Name Plate.
• Change Part No. of 5 Screw.
F9303JU A Y9303JU
CMPL 1C21C1-01E 3rd CMPL 01C21C01-01E 4th
1.1
2.9.4
10.3
• Add “1.1 For Safety Using.”
• Add descriptions based on ATEX directive.
• Add Optional code K 2.
• Add Optional code C2 and C3.
2.9.4
2.11
10.3
• Add Option code KU2.
• Add PED (Pressure Equipment Directive).
• Add Option code KU2.
1.1
1.3
2.9.3
2.12
10.3
• Add (e) Explosion Protected Type Instrument and (f) Modification
• Add “1.3 ATEX Document”
• Add “IECEx Certification” and delete “SAA Certification”
• Add Low Voltage Directive
• Add Certificate numbers and Applicable standards
• Add option code /SU2 and delete option code /SU1
• Add option code /PR
2.9.1
2.10
4.4
8.3.3 (12)
• Add direct current symbol.
• Add 11 European languages for ATEX documentation.
• Add applicable standard and certificate number for appovals.
• Add EMC caution note.
• Add section of changing the direction of integral indicator.
• Add figure for A40.
9.4.1
10.1, 10.2
• Add figure of integral indicator direction.
• Add PROFIBUS PA communication type.
10.3
• Delete applicable standard from the table.
CMPL 01C21A01-02E 9th CMPL 01C21A01-02E 10th
• Delete logo from the tag plate.
REVISION RECORD.EPS
IM 01C21C01-01E