Advertisement
Advertisement
Instruction
Manual Model EJA438W and EJA438N
Diaphragm Sealed Gauge
Pressure Transmitters
[Style: S2]
IM 1C22J1-01E
Yokogawa Electric Corporation
IM 1C22J1-01E
10th Edition
Blank Page
CONTENTS
CONTENTS
1.
INTRODUCTION ............................................................................................ 1-1
WARRANTY .................................................................................................. 1-2
2.
HANDLING CAUTIONS ................................................................................ 2-1
2.1
Model and Specifications Check ......................................................... 2-1
2.2
Unpacking ........................................................................................... 2-1
2.3
Storage ................................................................................................ 2-1
2.4
Selecting the Installation Location ...................................................... 2-1
2.5
Pressure Connection ........................................................................... 2-2
2.6
Waterproofing of Cable Conduit Connections .................................... 2-2
2.7
Restrictions on Use of Radio Transceiver .......................................... 2-2
2.8
Insulation Resistance and Dielectric Strength Test ............................ 2-2
2.9
Installation of Explosion Protected Type ............................................ 2-3
2.9.1
FM Approval ................................................................................. 2-3
2.9.2
CSA Certification .......................................................................... 2-4
2.9.3
SAA Certification .......................................................................... 2-6
2.9.4
CENELEC (KEMA)/IEC (KEMA) Certification .............................. 2-7
2.9.5
JIS Certification ............................................................................ 2-8
2.10 EMC Conformity Standards ................................................................ 2-9
3.
COMPONENT NAMES .................................................................................. 3-1
4.
INSTALLATION ............................................................................................. 4-1
4.1
Precautions ......................................................................................... 4-1
4.2
Mounting the Diaphragm Seals .......................................................... 4-1
4.3
Transmitter Mounting .......................................................................... 4-1
4.4
Affixing the Teflon Film ....................................................................... 4-3
4.5
Rotating Transmitter Section .............................................................. 4-3
5.
WIRING .......................................................................................................... 5-1
5.1
Wiring Precautions .............................................................................. 5-1
5.2
Selecting the Wiring Materials ............................................................ 5-1
5.3
Connections of External Wiring to Terminal Box ................................ 5-1
5.3.1
Power Supply Wiring Connection ................................................ 5-1
5.3.2
External Indicator Connection ...................................................... 5-1
5.3.3
BRAIN TERMINAL BT200 Connection ........................................ 5-2
5.3.4
Check Meter Connection .............................................................. 5-2
5.4
Wiring .................................................................................................. 5-2
5.4.1
Loop Configuration ....................................................................... 5-2
(1) General-use Type and Flameproof Type ...................................... 5-2
(2) Intrinsically Safe Type ................................................................... 5-2
5.4.2
Wiring Installation ......................................................................... 5-3
(1) General-use Type and Intrinsically Safe Type .............................. 5-3
(2) Flameproof Type (JIS) .................................................................. 5-3
5.5
Grounding ............................................................................................ 5-4
5.6
Power Supply Voltage and Load Resistance ..................................... 5-4
FD No. IM 1C22J1-01E
10th Edition: Feb. 2000(YK)
All Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation i IM 1C22J1-01E
CONTENTS
6.
OPERATION .................................................................................................. 6-1
6.1
Preparation for Starting Operation ...................................................... 6-1
6.2
Zero Point Adjustment ........................................................................ 6-2
6.2.1 When you can obtain Low Range Value from actual measured value of 0% (0 kPa, atmospheric pressure); .............. 6-2
6.2.2 When you cannot obtain Low Range Value from actual measured value of 0%; ................................................................ 6-3
6.3
Starting Operation ............................................................................... 6-3
6.4
Shutting Down Operation .................................................................... 6-3
6.5
Setting the Range Using the Range-setting Switch ........................... 6-4
7.
BRAIN TERMINAL BT200 OPERATION ..................................................... 7-1
7.1
BT200 Operation Precautions ............................................................. 7-1
7.1.1
Connecting the BT200 ................................................................. 7-1
7.1.2
Conditions of Communication Line .............................................. 7-1
7.2
BT200 Operating Procedures ............................................................. 7-1
7.2.1
Key Layout and Screen Display ................................................... 7-1
7.2.2
Operating Key Functions .............................................................. 7-2
(1) Alphanumeric Keys and Shift Keys .............................................. 7-2
(2) Function Keys ............................................................................... 7-2
7.2.3
Calling Up Menu Addresses Using the Operating Keys .............. 7-3
7.3
Setting Parameters Using the BT200 ................................................. 7-4
7.3.1
Parameter Summary .................................................................... 7-4
7.3.2
Parameter Usage and Selection .................................................. 7-6
7.3.3
Setting Parameters ....................................................................... 7-7
(1) Tag No. Setup ............................................................................... 7-7
(2) Calibration Range Setup .............................................................. 7-7
(3) Damping Time Constant Setup ..................................................... 7-8
(4) Output Signal Low Cut Mode Setup ............................................. 7-9
(5) Integral Indicator Scale Setup ...................................................... 7-9
(6) Unit Setup for Displayed Temperature ........................................ 7-11
(7) Operation Mode Setup ............................................................... 7-11
(8) Output Status Display/Setup when a CPU Failure ..................... 7-11
(9) Output Status Setup when a Hardware Error Occurs ................. 7-11
(10)Range Change while Applying Actual Inputs .............................. 7-12
(11) Zero Point Adjustment ................................................................ 7-12
(12)Test Output Setup ....................................................................... 7-14
(13)User Memo Fields ...................................................................... 7-14
7.4
Displaying Data Using the BT200 ..................................................... 7-14
7.4.1
Displaying Measured Data ......................................................... 7-14
7.4.2
Display Transmitter Model and Specifications ........................... 7-14
7.5
Self-Diagnostics ................................................................................ 7-15
7.5.1
Checking for Problems ............................................................... 7-15
(1) Identifying Problems with BT200 ................................................ 7-15
(2) Checking with Integral Indicator ................................................. 7-16
7.5.2
Errors and Countermeasures ..................................................... 7-17
8.
MAINTENANCE ............................................................................................. 8-1
8.1
Overview ............................................................................................. 8-1
8.2
Calibration Instruments Selection ....................................................... 8-1
8.3
Calibration ........................................................................................... 8-1 ii IM 1C22J1-01E
CONTENTS
8.4
Disassembly and Reassembly ............................................................ 8-3
8.4.1
Replacing the Integral Indicator ................................................... 8-3
8.4.2
Replacing the CPU Assembly ...................................................... 8-4
8.5
Troubleshooting ................................................................................... 8-5
8.5.1
Basic Troubleshooting .................................................................. 8-5
8.5.2
Troubleshooting Flow Charts ....................................................... 8-5
9.
GENERAL SPECIFICATIONS ...................................................................... 9-1
9.1
Standard Specifications ...................................................................... 9-1
9.2
Model and Suffix Codes ...................................................................... 9-3
9.3
Optional Specifications ........................................................................ 9-5
9.4
Dimensions .......................................................................................... 9-7
INSTALLATION AND OPERATING PRECAUTIONS FOR
JIS INTRINSICALLY SAFE EQUIPMENT .......................................... EX-A03E
INSTALLATION AND OPERATING PRECAUTIONS FOR
JIS FLAMEPROOF EQUIPMENT ....................................................... EX-B03E
Customer Maintenance Parts List
DPharp EJA Series Transmitter Section ............................ CMPL 1C22A1-02E
Models EJA438W and EJA438N Diaphragm Sealed
Gauge Pressure Transmitter ..................................... CMPL 1C22J3-01E
REVISION RECORD iii IM 1C22J1-01E
Blank Page
1. INTRODUCTION
1.
INTRODUCTION
Thank you for purchasing the DPharp electronic pressure transmitter.
The DPharp Pressure Transmitters are precisely calibrated at the factory before shipment. To ensure correct and efficient use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
j
Regarding This Manual
• This manual should be passed on to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.
• The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instruments.
• Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
j Safety Precautions
• For the protection and safety of the operator and the instrument or the system including the instrument, please be sure to follow the instructions on safety described in this manual when handling this instrument. In case the instrument is handled in contradiction to these instructions, Yokogawa does not guarantee safety.
• For the intrinsically safe equipment and explosionproof equipment, in case the instrument is not restored to its original condition after any repair or modification undertaken by the customer, intrinsically safe construction or explosionproof construction is damaged and may cause dangerous condition. Please contact Yokogawa for any repair or modification required to the instrument.
• The following safety symbol marks are used in this
Manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
For FOUNDATION Fieldbus and HART protocol versions, please refer to IM 1C22T2-01E and IM
1C22T1-01E respectively, in addition to this IM.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
1-1 IM 1C22J1-01E
WARRANTY
• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurred during the warranty period shall basically be repaired free of charge.
• In case of problems, the customer should contact the
Yokogawa representative from which the instrument was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• Responsible party for repair cost for the problems shall be determined by Yokogawa based on our investigation.
• The Purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by the purchaser.
- Failure or damage due to improper handling, use or storage which is out of design conditions.
- Use of the product in question in a location not conforming to the standards specified by
Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earthquakes, storms/floods, thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
1. INTRODUCTION
WARNING
• Instrument installed in the process is under pressure. Never loosen or tighten the flange bolts as it may cause dangerous spouting of process fluid.
• Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors even after dismounting the instrument from the process line for maintenance.
CAUTION
This instrument is tested and certified as intrinsically safe type or explosionproof type. Please note that the construction of the instrument, installation, external wiring, maintenance or repair is strictly restricted, and non-observance or negligence of this restriction would result in dangerous condition.
1-2 IM 1C22J1-01E
2. HANDLING CAUTIONS
2.
HANDLING CAUTIONS
This chapter describes important cautions regarding how to handle the transmitter. Read carefully before using the transmitter.
The EJA Series pressure transmitters are thoroughly tested at the factory before shipment. When the transmitter is delivered, visually check them to make sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware shown in Figure 2.1 is included. If the transmitter was ordered without the mounting bracket, the transmitter mounting hardware is not included. After checking the transmitter, repack it in the way it was delivered until installation.
Transmitter mounting bolt
U-bolt
U-bolt nut
Mounting bracket
F0201.EPS
Figure 2.1 Transmitter Mounting Hardware
2.1 Model and Specifications
Check
The model name and specifications are indicated on the name plate attached to the case. If the reverse operating mode was ordered (reverse signal), ‘ REVERSE ’ will be inscribed in field *1.
Figure 2.2 Name Plate Example of JIS Flameproof Type
2.2 Unpacking
When moving the transmitter to the installation site, keep it in its original packaging. Then, unpack the transmitter there to avoid damage on the way.
2.3 Storage
The following precautions must be observed when storing the instrument, especially for a long period.
(a) Select a storage area which meets the following conditions:
• It is not exposed to rain or water.
• It suffers minimum vibration and shock.
• It has an ambient temperature and relative humidity within the following ranges.
Ambient temperature:
–40 to 85
°
C without integral indicator
–30 to 80
°
C with integral indicator
Relative humidity:
5% to 100% R.H. (at 40
°
C)
Preferred temperature and humidity: approx. 25
°
C and 65% R.H.
(b) When storing the transmitter, repack it as nearly as possible to the way it was packed when delivered from the factory.
(c) If storing a transmitter that has been used, thoroughly clean the diaphragm surface of the diaphragm seal (pressure-detector section), so that no measured fluid remains on them. Also make sure before storing that the pressure-detector and transmitter assemblies are securely mounted.
2.4 Selecting the Installation
Location
The transmitter is designed to withstand severe environmental conditions. However, to ensure stable and accurate operation for years, observe the following precautions when selecting an installation location.
(a) Ambient Temperature
Avoid locations subject to wide temperature variations or a significant temperature gradient. If the location is exposed to radiant heat from plant equipments, provide adequate thermal insulation and/or ventilation.
2-1 IM 1C22J1-01E
2.7 Restrictions on Use of Radio
Transceiver
2. HANDLING CAUTIONS
(b) Ambient Atmosphere
Avoid installing the transmitter in a corrosive atmosphere. If the transmitter must be installed in a corrosive atmosphere, there must be adequate ventilation as well as measures to prevent intrusion or stagnation of rain water in conduits.
(c) Shock and Vibration
Select an installation site suffering minimum shock and vibration (although the transmitter is designed to be relatively resistant to shock and vibration).
(d) Installation of Explosion-protected Transmitters
Explosion-protected transmitters can be installed in hazardous areas according to the types of gases for which they are certified. See Subsection 2.9
“Installation of Explosion Protected Type Transmitters.”
2.5 Pressure Connection
IMPORTANT
Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test for such effects, bring the transceiver in use slowly from a distance of several meters from the transmitter, and observe the measurement loop for noise effects. Thereafter, always use the transceiver outside the area affected by noise.
WARNING
• Instrument installed in the process is under pressure. Never loosen or tighten the flange bolts to avoid the dangerous spouting of process fluid.
• Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the skin, eyes or body, or inhalation of vapors even after dismounting the instrument from process line for maintenance.
The following precautions must be observed in order to safely operate the transmitter under pressure.
(a) Never apply a pressure higher than the specified maximum working pressure.
(b) Never loosen or tighten the bolts securing the diaphragm seal flanges when the assembly is under pressure. Do it after releasing the process pressure if required.
2.6 Waterproofing of Cable
Conduit Connections
Apply a non-hardening sealant to the threads to waterproof the transmitter cable conduit connections.
(See Figure 5.4.2a, 5.4.2b and 5.4.2d.)
2.8 Insulation Resistance and
Dielectric Strength Test
Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required.
However, if required, observe the following precautions in the test procedures.
(a) Do not perform such tests more frequently than is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.
(b) Never apply a voltage exceeding 500 V DC (100 V
DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding
500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.
(c) Before conducting these tests, disconnect all signal lines from the transmitter terminals. Perform the tests in the following procedure:
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted
SUPPLY terminals and the minus (–) leadwire to the grounding terminal.
3) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied short as possible to verify that the insulation resistance is at least 20 M
Ω
.
2-2 IM 1C22J1-01E
4) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 k
Ω
resistor between the grounding terminal and the shortcircuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specified voltage.
4) When the specified voltage is reached, hold it for one minute.
5) After completing this test, slowly decrease the voltage to avoid any voltage surges.
2.9 Installation of Explosion
Protected Type
NOTE
For FOUNDATION Fieldbus explosion protected type, please refer to IM 1C22T2-01E.
WARNING
To pressure the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair activities. Please read the following sections very carefully.
2-3
2. HANDLING CAUTIONS
2.9.1 FM Approval
a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM012-A12 P.1 and 2.”)
Note 1. Model EJA Series pressure transmitters with optional code /FS1 are applicable for use in hazardous locations.
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D. Class II, Division 2, Groups E, F & G and
Class III, Division 1 Hazardous Locations.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –40 to 60
°
C
Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax = 30 V
Imax = 165 mA
Ci = 22.5 nF
Li = 730
µ
H
Pmax = 0.9 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc
≤
30 V
Isc
≤
165 mA
Pmax
≤
0.9W
Ca > 22.5 nF
La > 730
µ
H
• Intrinsically Safe Apparatus Parameters
[Groups C, D, E, F and G]
Vmax = 30 V
Imax = 225 mA
Pmax = 0.9 W
Ci = 22.5 nF
Li = 730
µ
H
* Associated Apparatus Parameters
(FM approved barriers)
Voc
≤
30 V
Isc
≤
225 mA
Pmax
≤
0.9 W
Ca > 22.5 nF
La > 730
µ
H
• Entity Installation Requirements
Vmax
≥
Voc or Vt, Imax
≥
Isc or It,
Pmax (IS Apparatus)
≥
Pmax (Barrier)
Ca
≥
Ci + Ccable, La
≥
Li + Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not use or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/
ISA RP12.6 “Installation of Intrinsically Safe
Systems for Hazardous (Classified) Locations” and the National Electric Code (ANSI/NFPA 70).
• The configuration of associated apparatus must be
FMRC Approved.
IM 1C22J1-01E
• Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments.
• Associated apparatus manufacturer’s installation drawing must be followed when installing this apparatus.
• The maximum power delivered from the barrier must not exceed 0.9 W.
• Note a warning label worded “SUBSTITUTION OF
COMPONENTS MAY IMPAIR INTRINSIC
SAFETY,” and “INSTALL IN ACCORDANCE
WITH DOC. No. IFM012-A12 P.1 and 2.”
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply –
Safety Barrier
+
–
+
–
General
Purpose
Equipment
+
–
[Nonincendive]
Hazardous Location Nonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.
EJA Series Pressure
Transmitters
+
General
Purpose
Equipment
+
Supply – –
Not Use
Safety Barrier
F0203.EPS
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /FF1 are applicable for use in hazardous locations.
• Explosionproof for Class I, Division 1, Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60
°
C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
2. HANDLING CAUTIONS
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NEPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
• Keep the “CAUTION” nameplate attached to the transmitter.
CAUTION: OPEN CIRCUIT BEFORE REMOV-
ING COVER. SEAL ALL CONDUITS WITHIN
18 INCHES. WHEN INSTALLED IN DIV.1,
“FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED.” INSTALL IN ACCORDANCE
WITH THE INSTRUCTION MANUAL IM 1C22.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJA Series pressure transmitters with optional code /FU1 can be selected the type of protection (FM Intrinsically Safe or FM
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
2.9.2 CSA Certification
a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe type. (Following contents refer to “DOC No. ICS003-A12 P.1-1 and P.1-2.”)
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /CS1 are applicable for use in hazardous locations
2-4 IM 1C22J1-01E
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D, Class II, Division 2, Groups F & G, and
Class III, Hazardous Locations. (not use Safety
Barrier)
• Encl. “Type 4X”
• Temperature Class: T4
• Ambient temperature: –40 to 60
°
C
• Process Temperature: 120
°
C max.
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax) = 30 V
Maximum Input Current (Imax) = 165 mA
Maximum Input Power (Pmax) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730
µ
H
* Associated apparatus (CSA certified barriers)
Maximum output voltage (Voc)
≤
30 V
Maximum output current (Isc)
≤
165 mA
Maximum output power (Pmax)
≤
0.9 W
Note 3. Installation
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Intrinsically safe and nonincendive Certification.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply –
Safety Barrier
+
–
+
–
General
Purpose
Equipment
+
–
[Nonincendive]
Hazardous Location Nonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III
EJA Series Pressure
Transmitters
+
Supply –
General
Purpose
Equipment
+
–
Not Use
Safety Barrier
F0204.EPS
2. HANDLING CAUTIONS b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /CF1 are applicable for use in hazardous locations:
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Encl “Type 4X”
• Temperature Class: T6, T5, and T4
• Process Temperature: 85
°
C (T6), 100
°
C (T5), and
120
°
C (T4)
• Ambient Temperature: –40 to 80
°
C
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the figure.
CAUTION: SEAL ALL CONDUITS
WITHIN 50 cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE
INSTALLÉ À MOINS DE 50 cm DU
BÎTIER.
• When installed in Division 2, “SEALS NOT
REQUIRED.”
Note 3. Operation
• Keep the “CAUTION” label attached to the transmitter.
CAUTION: OPEN CIRCUIT BEFORE
REMOVING COVER.
OUVRIR LE CIRCUIT AVANT
D´NLEVER LE COUVERCLE.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Explosionproof Certification.
2-5 IM 1C22J1-01E
Non-Hazardous
Locations
Hazardous Locations Division 1
Non-hazardous
Location
Equipment 50 cm Max.
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Conduit
EJA Series
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
EJA Series
F0205.EPS
c. CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJA Series pressure transmitters with optional code /CU1 can be selected the type of protection (CSA Intrinsically Safe or CSA
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
2.9.3 SAA Certification
a. SAA Intrinsically Safe Type
Caution for SAA Intrinsically safe type and Type n.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /SU1 are applicable for use in hazardous locations.
• Type of Protection and Marking Code:
Ex ia IIC T4 (Tamb = 60
°
C) IP67 Class I Zone 0
• Type of Protection and Marking Code:
Ex n IIC T4 (Tamb = 60
°
C) IP67 Class I Zone 2
• Ambient Temperature: –40 to 60
°
C
2. HANDLING CAUTIONS
Note 2. Entity Parameters
• Intrinsically safe rating of the transmitters are as follows.
Maximum Input Voltage (Ui) = 30 V
Maximum Input Current (Ii) = 165 mA
Maximum Input Power (Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 0.02
µ
F
Maximum Internal Inductance (Li) = 0.73 mH
Note 3. Wiring
• All Wiring shall comply with the Australian
Standard.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void Standards Association of Australia
Intrinsically safe and Type n Certification.
Hazardous Location
(Zone 0)
[Intrinsic Safety]
Nonhazardous Location
EJA Series
Pressure
Transmitter
–
+ +
Safety Barrier *1
–
F0206.EPS
*1: Any safety barriers used for the output current must be limited by a resistor “R” such that Imaxout-Uz/R.
[Type n]
Hazardous Location
(Zone 2)
EJA Series
Pressure
Transmitter
–
+ +
Power Supply *2
–
2-6
F0207.EPS
*2: The voltage of the power supply is not exceed 30V dc.
b. SAA Flameproof Type
Caution for SAA flameproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /SU1 are applicable for use in hazardous locations:
• Type of Protection and marking Code:
Ex d II C T* IP67 Class I Zone 1 (T* see schedule)
• Temperature Class: T6, T5, and T4
• Process Temperature:
85
°
C (T6), 100
°
C (T5), and 120
°
C (T4)
IM 1C22J1-01E
• Supply voltage: 42 V dc max.
• Output Signal: 4 to 20 mA
• Ambient Temperature: –40 to 80
°
C
Note 2. Wiring
• All wiring shall comply with the Australian
Standard.
Note 3. Operation
• Keep the “CAUTION” label attached to the transmitter.
CAUTION: AMBIENT TEMPERATURE
ABOVE 75 DEG C SELECT SUITABLE
CABLE. DISCONNECT POWER AND
WAIT 1 MINUTE BEFORE REMAKING
COVER.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void Standards Association of Australia
Flameproof Certification.
2.9.4 CENELEC (KEMA)/IEC (KEMA)
Certification
a. CENELEC (KEMA) Intrinsically Safe Type
Caution for CENELEC (KEMA) intrinsically safe type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /KS1 for potentially explosive atmospheres:
• Type of Protection and Marking code:
EEx ia IIC T4
• Temperature Class: T4
• Process Temperature: 120
°
C max.
• Ambient Temperature: –40 to 60
°
C
Note 2. Electrical Data
• In type of explosion protection intrinsic safety EEx ia IIC only for connection to a certified intrinsically safe circuit with following maximum values:
Ui = 30 V
Ii = 165 mA
Pi = 0.9 W
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730
µ
H
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation diagram)
2. HANDLING CAUTIONS
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void KEMA Intrinsically safe Certification.
[Installation Diagram]
Hazardous Location Nonhazardous Location
Transmitter
Supply
+
–
+
–
Safety Barrier *1
F0208.EPS
*1: In any safety barriers used the output current must be limited by a resistor “R” such that Imaxout-Uz/R.
b. CENELEC (KEMA) Flameproof Type
Caution for CENELEC (KEMA) flameproof type.
Note 1. Model EJA Series differential, gauge, and absolute pressure transmitters with optional code /KF1 for potentially explosive atmospheres:
• Type of Protection and Marking Code: EEx d IIC
T6···T4
• Temperature Class: T6, T5, and T4
• Maximum Process Temperature:
85
°
C (T6), 100
°
C (T5), and 120
°
C
• Ambient Temperature: –40 to 80
°
C
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation requirement.
• The cable entry devices shall be of a certified flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “CAUTION” label to the transmitter.
CAUTION: WAIT 1 MIN. AFTER
POWER-DISCONNECTION, BEFORE
OPENING THE ENCLOSURE.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void KEMA Flameproof Certification.
2-7 IM 1C22J1-01E
c. IEC (KEMA) Type of Protection “n”
Caution for IEC (KEMA) Type of Protection “n.”
Note 1. Model EJA Series pressure transmitters with optional code /KU1 for potentially explosive atmospheres.
• Type of Protection and Marking Code:
Ex nA IIC T4
• Temperature Class: T4
• Process Temperature: 120
°
C max.
• Ambient Temperature: –40 to 60
°
C
Note 2. Electrical Data
• Supply and output circuit
≤
30 V dc, 165 mA
(terminals + and –)
Note 3. Installation
• All wiring shall comply with local installation requirements. (refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of
Yokogawa Electric Corporation is prohibited and will void KEMA Type of Protection “n” Certification.
[Installation Diagram]
Nonhazardous Location Hazardous Location
(Zone 2 only)
Transmitter
+
Supply
–
+
–
Power Supply
Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
2.9.5 JIS Certification
2. HANDLING CAUTIONS
JIS Flameproof and Intrinsically Safe Type
The model EJA Series pressure transmitters with optional code /JF1 and /JS1, which have obtained certification according to technical criteria for explosion-protected construction of electric machinery and equipment(Standards Notification No. 556 from the
Japanese Ministry of Labor) conforming to IEC standards, are designed for hazardous areas where explosive gases and/or inflammable vapors may be present. [JIS Flameproof Type(optional code /JF1) allows installation in Division 1 and 2 areas, and JIS
Intrinsically Safe Type(optional code /JS1) allows installation in Division 0, 1, and 2 areas.]
To observe the safety of flameproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair activities. Users absolutely must read
“Installation and Operating Precautions for JIS Intrinsically Safe Equipment and Flameproof Equipment” at the end of this manual.
F0209.EPS
Ratings of the Power Supply as follows;
Maximum Voltage: 30 V
Maximum Current: 165 mA d. CENELEC (KEMA) Intrinsically Safe Type/
CENELEC (KEMA) Flameproof Type/IEC
(KEMA) Type of Protection “n”
Model EJA Series pressure transmitters with optional code /KU1 can be selected the type of protection (CENELEC (KEMA) Intrinsically
Safe or CENELEC (KEMA) Flameproof or IEC
(KEMA) Type of Protection “n”) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
CAUTION
(For JIS flameproof type without integral indicator)
When the fill fluid near the sensor part moves from within, the instrument outputs a failure signal either high or low of the specific signal. In that case, generate the alarm to identify that the failure signal is output since the event may invalidate the flameproof approval.
If the optional integral indicator is equipped, the indicator identifies the alarm on its display.
Therefore, no other alarm generation is necessary.
Hazardous Location Nonhazardous Location
4 to 20 mA DC 1 to 5 V DC
Transmitter
Power
Supply
DCS
Display
F0210.EPS
Figure 2.3 Example of using DCS (Distributed Control
System)
2-8 IM 1C22J1-01E
2.10 EMC Conformity Standards
For EMI (Emission): EN55011, AS/NZS 2064 1/2
For EMS (Immunity): EN50082–2
NOTE
YOKOGAWA recommends customer to apply the Metal Conduit Wiring or to use the twisted pair Shield Cable for signal wiring to conform the requirement of EMC Regulation, when customer installs the EJA Series Transmitters to the plant.
2. HANDLING CAUTIONS
2-9 IM 1C22J1-01E
3. COMPONENT NAMES
3.
COMPONENT NAMES
Transmitter section*
*See below for details.
Cover flange
Capillary tube
Diaphragm
Flange
Diaphragm seal
Pressure-detector section
F0301.EPS
Figure 3.1.1 Component Names (Model EJA438W External View)
Transmitter section
External indicator conduit connection (Note 1)
Terminal box cover
Conduit connection
CPU assembly
Zero-adjustment screw
Integral indicator (Note 1)
Mounting screw
Pressure-detector section
Cover flange
Amplifier cover
Setting pin
(CN4)
Range-setting switch
(See Subsection 6.5)
(Note 1)
Setting pin (CN4) position (Note 2)
H
L
H
L
Burn-out direction
HIGH
LOW
Output at burn-out
110% or higher
-5% or lower
F0302.EPS
Note 1: Options depend on your order specifications. For details, see Subsection 9.2, “Model and Suffix Codes.”
Note 2: • Insert the pin (CN4) as shown in the above figure into the H or L side. The pin is set to the H side for delivery (unless option code /C1 is otherwise specified in the order).
• The setting can be confirmed by calling up parameter D52 using the BRAIN TERMINAL. Refer to Subsection. 7.3.2 (8).
Display Symbol Meaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
%, Pa, hPa, kPa, MPa, kgf/cm 2 , gf/cm 2 , mbar, bar, atm, mmHg, mmH
2
O, inH
2
O, inHg, ftH
2
O, psi, Torr
Select one of these seventeen available engineering units for the display.
T0301.EPS
Figure 3.1.2 Component Names (Transmitter Section Details)
3-1 IM 1C22J1-01E
4. INSTALLATION
4.
INSTALLATION
4.1 Precautions
j
Before installing the transmitter, read the cautionary notes in Section 2.4, “Selecting the Installation
Location.” For additional information on the ambient conditions allowed at the installation location, refer to Subsection 9.1 “Standard Specifications.”
IMPORTANT
• When welding piping during construction, take care not to allow welding currents to flow through the transmitter.
• Do not step on this instrument after installation.
IMPORTANT
• During the diaphragm seal installation, ensure as far as possible that no seal liquid head is applied to the diaphragm seal.
• Exercise care so as not to damage diaphragm surface. Since the diaphragm protrudes approx.
1mm from the flange surface, placing the diaphragm seals with its diaphragm surface facing downward may damage the diaphragm surface.
• Do not sharply bend or twist capillary tube or apply excessive stress to it.
4.2 Mounting the Diaphragm
Seals
Mount the diaphragm seals using the flanges as shown in Figure 4.2.1. Figure 4.2.2 shows how to mount the diaphragm seals on a tank. The customer should prepare the mating flange, gasket, bolts and nuts.
Diaphragm
Flange
Nut
Bolt
IMPORTANT
Install the sealed diaphragm so that the shank positions downward.
Diaphragm seal
Capillary tube
ød
Gasket
The product is shipped with these parts assembled.
Correctly install the diaphragm seals on the high and low pressure sides of the process, checking the label on each seal.
F0401.EPS
Figure 4.2.1 Mounting the Diaphragm Seals
IMPORTANT
Please use a gasket which has a bigger inside diameter than that of gasket facing (ød) on diaphragm seal. In case a gasket which has a smaller inside diameter than that of gasket facing is used, it may cause an error as the gasket prevents diaphragm from working correctly. (Refer to Subsection 9.4 ‘Dimensions’)
F0402.EPS
Figure 4.2.2 Installing the Diaphragm Seals to a Tank
4.3 Transmitter Mounting
j
The transmitter can be mounted on a nominal 50 mm (2-inch) pipe using the mounting bracket supplied, as shown in Figure 4.3.1 The transmitter can be mounted on either a horizontal or a vertical pipe.
j
When mounting the bracket on the transmitter, tighten the (four) bolts that hold the transmitter to a torque of approximately 39 N·m {4 kgf·m}.
IMPORTANT
Never loosen the four screws securing the cover flange or the screws at the joints between the capillary tube and cover flanges (if the seal liquid leaks, the transmitter cannot be used).
4-1 IM 1C22J1-01E
Vertical pipe mounting
Horizontal pipe mounting
U-bolt nut
Mounting bracket
50mm (2-inch) pipe
Figure 4.3.1 Transmitter Mounting
Transmitter mounting bolt
4. INSTALLATION
IMPORTANT
The transmitter should be installed at least 700 mm (when the model code of the material of the wetted part is H, at least 1300 mm) below the process connection to ensure a positive head pressure of fill fluid. If it can not be installed at least 700 mm below the process connection, please use the equation below: h=
(P–P0)
3 dHg ds
3
7.5
3
10 –3 [mm] h: Vertical height between the process connection and the transmitter (mm) h
≤
0: Install the transmitter at least h (mm) below the process connection h>0: Install the transmitter at most h (mm) above the process connection
P: Pressure in the tank (Pa abs)
P0: Minimum working pressure limit of the transmitter (Pa abs)
If the ambient temperature range is
–10 to 50
°
C.
5254 (Wetted parts material code S)
6980 (Wetted parts material code T)
13019 (Wetted parts material code H)
6980 (Wetted parts material code U) ds: Specific gravity of fill fluid (at 25
°
C), refer to GS 1C22J3-E.
dHg:Specific gravity of the Mercury 13.6 (at
25
°
C)
U-bolt
F0403.EPS
(+) h
0
(–)
P
4-2
F0404.EPS
Figure 4.3.2 Example of Installation to Tank (Caution on
Installation)
IM 1C22J1-01E
4.4 Affixing the Teflon Film
The FEP Teflon option includes a teflon film and fluorinated oil.
Before mounting the diaphragm seal to the process flange, affix the teflon film as follows :
IMPORTANT
(1) Position the diaphragm seal so that the diaphragm is in a upward position.
(2) Pour the fluorinated oil on the diaphragm and gasket area covering it completely and evenly. Be careful not to scratch the diaphragm or change the its shape.
(3) Affix the teflon film over the diaphragm and gasket area.
(4) Next, carefully inspect the cover and try to identify any entrapped air between the diaphragm and the teflon film. The air must be removed to ensure accuracy. If air pockets are present, use your fingers to remove the air by starting at the center of the diaphragm and work your way out.
(5) Place the gasket with the teflon film and affix to the process flange.
4. INSTALLATION
4.5 Rotating Transmitter Section
The DPharp transmitter section can be rotated in 90
° segments.
(1) Remove the two Allen screws that fasten the transmitter section and pressure-detector section, using the Allen wrench supplied with the transmitter.
(2) Rotate the transmitter section slowly in 90
° segments.
(3) Tighten the two Allen screws.
IMPORTANT
Do not rotate the transmitter section more than
180
°
.
Transmitter section
Rotate 90
°
or 180
° segments
Rotate 90
°
or 180
° segments
Conduit connection
Zero-adjustment screw
Teflon film
PART No.
F9347XA
F9347YA
Process flange size
For 3inch (80 mm)
For 2inch (50 mm)
Fluorinated oil
[PART No.: F9145YN]
Diaphragm
Gasket area
Pressure-detector section
Figure 4.5.1 Rotating Transmitter Section
F0406.EPS
Diaphragm seal
Figure 4.4.1 Affixing the Teflon Film
F0405.EPS
4-3 IM 1C22J1-01E
5. WIRING
5.
WIRING
5.1 Wiring Precautions
IMPORTANT
• Lay wiring as far as possible from electrical noise sources such as large capacity transformers, motors, and power supplies.
• Remove electrical connection dust cap before wiring.
• All threaded parts must be treated with waterproofing sealant. (A non-hardening silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal and power cables through the same ducts.
• Explosion-protected instruments must be wired in accordance with specific requirements (and, in certain countries, legal regulations) in order to preserve the effectiveness of their explosionprotected features.
• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on CENELEC,
SAA, and JIS flameproof type transmitters.
When the shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.
See Subsection 8.4 “Disassembly and Reassembly” for details.
Refer to The “Installation and Operating
Precautions for JIS Flameproof Equipment”
and “Installation and Operating Precautions
for JIS Intrinsically Safe Equipment” at the end of this manual for correct wiring.
CAUTION
If the transmitter is flameproof and the ambient temperature is 50
°
C or more, use cables having a maximum allowable heat resistance of at least
75
°
C in consideration of the instrument's generation of heat or the cables' self-heating.
(d) In environment where oils, solvents, corrosive gases or liquids may be present, use wires or cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless terminal lugs (for 4 mm screws) with insulating sleeves be used for leadwire ends.
5.3 Connections of External
Wiring to Terminal Box
5.3.1 Power Supply Wiring Connection
Connect the power supply wiring to the SUPPLY + and – terminals.
Transmitter terminal box
Power supply
+
–
F0501.EPS
Figure 5.3.1 Power Supply Wiring Connection
5.2 Selecting the Wiring Materials
(a) Use stranded leadwires or cables which are the same as or better than 600 V grade PVC insulated wire (JIS C3307) or equivalent.
(b) Use shielded wires in areas that are susceptible to electrical noise.
(c) In areas with higher or lower ambient temperatures, use appropriate wires or cables.
5.3.2 External Indicator Connection
Connect wiring for external indicators to the CHECK + and – terminals.
(Note) Use a external indicator whose internal resistance is 10
Ω
or less.
External indicator
Power supply
+
–
Transmitter terminal box
Figure 5.3.2 External Indicator Connection
F0502.EPS
5-1 IM 1C22J1-01E
5.3.3 BRAIN TERMINAL BT200 Connection
Connect the BT200 to the SUPPLY + and – terminals
(Use hooks).
BT200
Transmitter terminal box
+
Power supply
–
Ignore the polarity since the BT200 is
AC-coupled to the terminal box.
F0503.EPS
Figure 5.3.3 BT200 Connection
5.3.4 Check Meter Connection
Connect the check meter to the CHECK + and – terminals (use hooks).
• A 4 to 20 mA DC output signal from the CHECK + and – terminals.
(Note) Use a check meter whose internal resistance is 10
Ω
or less.
Power supply
+
–
Check meter
Transmitter terminal box
Figure 5.3.4 Check Meter Connection
F0504.EPS
5.4 Wiring
CAUTION
For the intrinsically safe equipment and flameproof equipment, wiring materials and wiring work for these equipment including peripherals are strictly restricted. Users absolutely must read
“Installation and Operating Precautions for JIS
Intrinsically Safe Equipment” and “Installation and Operating Precautions for JIS Flameproof
Equipment” at the end of this manual prior to the work.
5. WIRING
5.4.1 Loop Configuration
Since the DPharp uses a two-wire transmission system, signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The transmitter and distributor are connected as shown below.
For details of the power supply voltage and load resistance, see Section 5.6; for communications line requirements, see Subsection 7.1.2.
(1) General-use Type and Flameproof Type
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver instrument
Figure 5.4.1a Connection between Transmitter and
Distributor
F0505.EPS
(2) Intrinsically Safe Type
For intrinsically safe type, a safety barrier must be included in the loop.
Nonhazardous Location Hazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver instrument
Safety barrier
Figure 5.4.1b Connection between Transmitter and
Distributor
F0506.EPS
5-2 IM 1C22J1-01E
5.4.2 Wiring Installation
(1) General-use Type and Intrinsically Safe
Type
Make cable wiring using metallic conduit or waterproof glands.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the flexible metal conduit for waterproofing.
Flexible metal conduit
Wiring metal conduit
Tee
Drain plug
Apply a non-hardening sealant to the threads for waterproofing.
F0507.EPS
Figure 5.4.2a Typical Wiring Using Flexible Metal Conduit
(2) Flameproof Type (JIS)
Wire cables through a flameproof packing adapter, or using a flameproof metal conduit.
j
Wiring cable through flameproof packing adapter for only JIS flameproof type (see Figure 5.4.2b).
• Use only flameproof packing adapters approved by
Yokogawa.
• Apply a nonhardening sealant to the terminal box connection port and to the threads on the flameproof packing adapter for waterproofing.
5. WIRING
• Measure the cable outer diameter in two directions to within 1 mm.
• Calculate the average of the two diameters, and use packing with an internal diameter nearest to this value
(see Table 5.4.2).
Table 5.4.2
Flameproof Packings and Applicable Cable
Outer Diameters
Optional
Code
Wiring Port
Thread
Diameter
Applicable
Cable OD
(mm)
Identifying
Mark
Part
Number
G11
G 1/2
8 to 10
10.1 to 12
16 8-10
16 10-12
G9601AM
G12
T0501.EPS
• Mounting flameproof packing adapter body to conduit connection (see Figure 5.4.2c)
1) Screw the flameproof packing adapter into the terminal box until the O-ring touches the wiring port (at least 6 full turns), and firmly tighten the lock nut.
2) Insert the cable through the union cover, the union coupling, the clamp nut, the clamp ring, the gland, the washer, the rubber packing, and the packing box, in that order.
3) Insert the end of the cable into the terminal box.
4) Tighten the union cover to grip the cable. When tightening the union cover, tighten approximately one turn past the point where the cable will no longer move up and down.
Proper tightening is important. If it is too tight, a circuit break in the cable may occur; if not tight enough, the flameproof effectiveness will be compromised.
5) Fasten the cable by tightening the clamp nut.
6) Tighten the lock nut on the union cover.
7) Connect the cable wires to each terminal.
Flameproof packing adapter
Flexible metal conduit
Wiring metal conduit
Apply a non-hardening sealant to the threads for waterproofing.
Tee
Drain plug
F0508.EPS
Figure 5.4.2b Typical Cable Wiring Using Flameproof
Packing Adapter
Apply a non-hardnening sealant to the threads for waterproofing.
O-ring
Adapter body
Lock nut
Wrench
Packing box
Rubber packing
Washer
Gland
Clamp ring
Clamp nut
Union coupling
Lock nut
Wrench
Union cover
Cable
F0509.EPS
Figure 5.4.2c Installing Flameproof Packing Adapter
5-3 IM 1C22J1-01E
j
Flameproof metal conduit wiring
• A seal fitting must be installed near the terminal box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the terminal box connection port, flexible metal conduit and seal fitting for waterproofing.
Gas sealing device
Non-hazardous area
Flameproof flexible metal conduit
Hazardous area
Flameproof heavy-gauge steel conduit
Apply a non-hardening sealant to the threads of these fittings for waterproofing
Tee
Drain plug
Seal fitting
After wiring, impregnate the fitting with a compound to seal tubing.
F0510.EPS
Figure 5.4.2d Typical Wiring Using Flameproof Metal
Conduit
5. WIRING
5.6 Power Supply Voltage and
Load Resistance
When configuring the loop, make sure that the external load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load resistance includes safety barrier resistance.
600
External load resistance
R (
Ω
)
250
R=
E–10.5
0.0236
Communication applicable range
BRAIN and HART
,
5.5 Grounding
(a) Grounding should satisfy JIS Class 3 requirements
(grounding resistance, 100
Ω
or less). Grounding is required for JIS flameproof type and intrinsically safe type.
(Note) If equipped with built-in Lightning Protector, grounding should satisfy Special JIS class 3 requirements (grounding resistance, 10
Ω
or less).
(b) There are ground terminals on the inside and outside of the terminal box. Either of these terminals may be used.
(c) Use 600 V grade PVC insulated wires for grounding.
Transmitter terminal box
Ground terminal
0 10.5
16.4
24.7
Power supply voltage E (V DC)
42
F0512.EPS
Figure 5.6 Relationship between Power Supply Voltage and External Load Resistance
Ground terminal
Figure 5.5 Ground Terminals
F0511.EPS
5-4 IM 1C22J1-01E
6. OPERATION
6.
OPERATION
6.1 Preparation for Starting Operation
The Model EJA438W and EJA438N diaphragm sealed gauge pressure transmitter measures the pressure of liquids, gases, and steam. This section describes the operation procedure for the EJA438W as shown in
Figure 6.1.1 when measuring pressure in a tank.
(a) Confirm that there is no leak in the connecting part of each diaphragm seal mounting flange.
(b) Turn ON power and connect the BT200.
Open the terminal box cover and connect the
BT200 to the SUPPLY + and –terminals.
(c) Using the BT200, confirm that the transmitter is operating properly. Check parameter values or change the setpoints as necessary.
For BT200 operating procedures, see Chapter 7. If the transmitter is equipped with an integral indicator, its indication can be used to confirm that the transmitter is operating properly.
j
Confirming that Transmitter is Operating
Properly
Confirmation using the BT200
• If the wiring system is faulty, ‘communication error’ appears on the display.
• If the transmitter is faulty, ‘SELF CHECK ERROR’ appears on the display.
PARAM
C60:SELF CHECK
ERROR communication error
Communication error
(Faulty wiring)
DATA DIAG PRNT ESC
Self-diagnostic error
(Faulty transmitter)
F0602.EPS
Confirmation using the integral indicator
• If the wiring system is faulty, the display is blank.
• If the transmitter is faulty, an error number will appear on the display according to the nature of the error.
Diaphragm seal Self-diagnostic error
(Faulty transmitter)
F0603.EPS
Capillary tube
Pressure transmitter
Transmitter mounting pipe
50mm (2 inches)
F0601.EPS
Figure 6.1.1 Pressure Measurement
NOTE
If any of the error indications above appears on the display of the integral indicator or BT200, refer to Subsection 7.5.2 for corrective action.
j Verify and Change Transmitter Parameter
Setting and Values
The following parameters are the minimum settings required for operation. The transmitter has been shipped with these parameters. To confirm or change the values, see Subsection 7.3.3.
• Measuring range........See Subsection 7.3.3 (2)
• Operation mode.........See Subsection 7.3.3 (7)
6-1 IM 1C22J1-01E
6.2 Zero Point Adjustment
Adjust the zero point after operating preparation is completed.
IMPORTANT
Do not turn off the power to the transmitter immediately after a zero adjustment. Powering off within 30 seconds after a zero adjustment will return the adjustment back to the previous settings.
The zero point adjustment can be made in either way: using the zero-adjustment screw of the transmitter or the BT200 operation.
For output signal checking, display the parameter A10:
OUTPUT (%) in the BT200.
d
BT200
PARAM
A10:OUTPUT(%)
0.0 %
A11:ENGR OUTPUT
A20:AMP TEMP
Output signal (%) display
DATA DIAG PRNT ESC d
Zero-adjustment Screw
6. OPERATION
6.2.1 When you can obtain Low Range
Value from actual measured value of 0% (0 kPa, atmospheric pressure);
For pressure measurement using gauge pressure transmitters, follow the step below before zero point adjustment.
1) Close the tap valve (main valve).
2) Loosen the fill plug so that the pressure applied to the transmitter is only the head of the seal liquid.
3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and then gradually open the tap valve.
j Using the Transmitter Zero-adjustment
Screw
Before adjusting a screw, check that the parameter
J20: EXT ZERO ADJ displays ENABLE.
See
Subsection 7.3.3 (11) for the setting procedure.
Use a slotted screwdriver to turn the zero-adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of
0.01% of the setting range. Since the degree of zero adjustments varies with the screw turning speed, turn the screw slowly for fine adjustment and quickly for coarse adjustment.
Zero-adjustment screw
F0604.EPS
After reviewing this parameter you are prepared to adjust the zero point. When making the zero adjustment on a pressure transmitter, the process pressure value does not have to be set to the low limit of the measurement range (0%). In such case, adjust the transmitter output signal to the actual measured value obtained from a high-accuracy pressure measuring instrument.
j
Using the BT200
Zero point can be adjusted by simple key operation of the BT200.
Select parameter J10: ZERO ADJ, and press the
ENTER key twice. The zero point will be adjusted automatically to the output signal 0% (4 mA DC).
Confirm that the setting value displayed for the parameter is ‘ 0.0% ’ before pressing the ENTER key.
See Subsection 7.3.3 (11) for BT200 operating procedures.
SET
J10:ZERO ADJ
–0.0 %
+ 000.0
CLR ESC
A display when parameter
J10 is selected.
Press key twice for 0% output 4 mA DC.
F0605.EPS
6-2 IM 1C22J1-01E
6.2.2 When you cannot obtain Low Range
Value from actual measured value of 0%;
Convert the actual measured value obtained by a digital manometer or a glass gauge into %.
[Example]
The measuring range of 50 to 250 kPa; the actual measured value of 130 kPa.
Actual measured value=
130–50
250–50
3
100=40.0% j
Using the Transmitter Zero-Adjustment
Screw
Turn the screw to match the output signal to the actual measured value in %.
j Using the BT200
Select the parameter J10: ZERO ADJ.
Change the set point (%) displayed for the parameter to the actual measured value (%), and press the ENTER key twice.
See Subsection 7.3.3 (11) for operation details.
A display at J10 SET
J10:ZERO ADJ
–0.0 %
+ 000.0
CLR ESC
SET
J10:ZERO ADJ
–0.0 %
+ 040.0
CLR ESC
Change setting to the actually measured value (40.0%).
Press key twice for 40% output 10.4 mA DC.
F0606.EPS
6. OPERATION
6.3 Starting Operation
After completing the zero point adjustment, use the procedure below to start operation.
1) Confirm the operating status.
There will be cases in which the output signal exhibits wide fluctuations (hunting) due to periodic variation in the process pressure. In such cases,
BT200 operation can dampen the transmitter output signal. Confirm the hunting using a receiving instrument or the integral indicator, and set the optimum damping time constant. See Subsection
7.3.2 (3), “Damping Time Constant Setup.”
2) After confirming the operating status, perform the following.
IMPORTANT
• Remove the BT200 from the terminal box, and confirm that none of the terminal screws are loosened.
• Close the terminal box cover and the amplifier cover. Screw each cover in tightly until it will not turn further.
• Two covers are required to be locked on the
CENELEC, SAA, and JIS Flameproof type transmitters. An Allen head bolts (shrouding bolts) are provided under edge of the each cover for locking. When a shrouding bolts are driven counterclockwise by an Allen wrench, it is coming out and locks up a cover. (See page
8-4)
After locking, the covers shoud be confirmed not to be opened.
• Tighten the zero-adjustment cover mounting screw to fix the cover in position.
6.4 Shutting Down Operation
Turn off the power.
NOTE
Whenever shutting down the transmitter for a long period, detach the transmitter (diaphragm seals) from the tank.
6-3 IM 1C22J1-01E
6.5 Setting the Range Using the
Range-setting Switch
With actual pressure being applied to the transmitter, the range-setting switch (push-button) located on the optional integral indicator plate and the external zeroadjustment screw allow users to change (re-range) the low- and high-limit values for the measurement range
(LRV and HRV) without using BT200. However, other changes in the display settings (scale range and engineering unit) for the integral indicator requires
BT200.
Follow the procedure below to change the LRV and
HRV settings.
[Example]
Rerange LRV to 0 and HRV to 3 MPa.
1) Connect the transmitter and apparatus as shown in
Figure 8.3.1 and warm up for at least five minutes.
2) Press the range-setting push-button.
The integral indicator then displays “ LSET .”
3) Apply a pressure of 0 kPa (atmospheric pressure) to the transmitter. (Note 1)
4) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)
5) Adjust the output signal to 0% (1 V DC) by rotating the external zero-adjustment screw. Doing so completes the LRV setting.
6) Press the range-setting push-button. The integral indicator then displays “ HSET .”
7) Apply a pressure of 3 MPa to the transmitter. (Note 1)
8) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)
9) Adjust the output signal to 100% (5 V DC) by rotating the external zero-adjustment screw. Doing so completes the HRV setting.
10) Press the range-setting push-button. The transmitter then switches back to the normal operation mode with the measurement range of 0 to 3 MPa.
Note 1: Wait until the pressure inside the pressure-detector section has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the previous
LRV (or HRV), the integral indicator may display error number “Er.07” (In this case, the output signal percent and
“Er.07” are displayed alternately every two seconds).
Although “Er.07” is displayed, you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to Subsection 7.5.2,
“Errors and Countermeasures.”
6. OPERATION
IMPORTANT
• Do not turn off the power to the transmitter immediately after completion of the change in the LRV and/or HRV setting(s). Note that powering off within thirty seconds after setting will cause a return to the previous settings.
• Changing LRV automatically changes HRV to the following value.
HRV = previous HRV + (new LRV – previous LRV)
• If the range-setting push-button and external zero-adjustment screw are not touched during a range-change operation, the transmitter automatically switches back to the normal operation mode.
Integral indicator
Note : Use a thin bar which has a blunt tip, e.g., a hexagonal wrench, to press the rangesetting push-button
Range-setting switch
(Push-button)
Figure 6.5.1 Range-setting Switch
F0607.EPS
6-4 IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
7.
BRAIN TERMINAL BT200
OPERATION
The DPharp is equipped with BRAIN communications capabilities, so that range changes, Tag No.
setup, monitoring of self-diagnostic results, and zero point adjustment can be handled by remote control via BT200 BRAIN TERMINAL or CENTUM CS console. This section describes procedures for setting parameters using the BT200. For details concerning the BT200, see IM 1C0A10-E, “BT200 User’s
Manual.”
7.1 BT200 Operation Precautions
7.1.1 Connecting the BT200
The transmitter and the BT200 can be connected either to the BT200 connection hooks in the transmitter terminal box or to a relaying terminal board.
7.2 BT200 Operating Procedures
7.2.1 Key Layout and Screen Display
Figure 7.2.1a shows the arrangement of the operating keys on the BT200 keypad, and Figure 7.2.1b shows the BT200 screen component.
LCD
(21 character
×
8 lines)
Relaying terminals
Control room
Terminal board
Function keys
Movement keys
ENTER key
Power ON/OFF key
Alphanumeric keys
Distributor
Shift keys
F0703.EPS
F0701.EPS
Figure 7.2.1a BT200 Key Layout
Figure 7.1.1 Connecting the BT200
7.1.2 Conditions of Communication Line
Power supply
Cable resistance Rc cc
Load resistance R
Cable resistance Rc
DPharp d
Loop resistance = R + 2Rc
= 250 to 600
Ω d
Loop capacitance = 0.22
µ
F max.
BT200
F0702.EPS
Figure 7.1.2 Conditions of Communication Line
7-1
MENU SCREEN
MENU
A:DISPLAY
B:SENSOR TYPE
BATTERY
Screen title
HOME SET ADJ ESC
Parameters
PARAMETER SCREEN
PARAM
A10:OUTPUT
100.0 %
A11:ENGR. OUTPUT
1000 mmH20
A20:AMP TEMP
23 deg C
DATA DI AG PRNT
Messages
Menu choices
Function commands
F0704.EPS
Figure 7.2.1b BT200 Screen Component
IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
7.2.2 Operating Key Functions
(1) Alphanumeric Keys and Shift Keys
You can use the alphanumeric keys in conjunction with the shift keys to enter symbols, as well as alphanumeric keys.
Use the function key [F1] CODE to enter symbols.
The following symbols will appear in sequence, one at a time, at the cursor each time you press [F1]
CODE:
/ . – , + * ) ( ’ & % $ # ” !
To enter characters next to these symbols, press [ > ] to move the cursor.
Alphanumeric keys
Entry Key-in Sequence symbol command l/m
( I ) ( / ) ( m )
T0703.EPS
Shift keys
F0705.EPS
a. Entering Digits, Symbols, and Spaces
Simply press the alphanumeric keys.
(2) Function Keys
The functions of the function keys depend on the function commands on display.
Entry
–4
0.3
Key-in Sequence
1 –9
T0701.EPS
b. Entering Letters (A through Z)
Press an alphanumeric key following a shift key to enter the letter shown on that side which the shift key represents. You must press the shift key before entering each letter.
Left-side letter on the alphanumeric key
Entering uppercase
CODE CAPS CLR ESC
Entry
Boy
( B )
Right-side letter on the alphanumeric key
Entry
W
IC
Key-in Sequence
J. B
T0702.EPS
Use the function key [F2]
CAPS
to select between uppercase and lowercase (for letters only). The case toggles between uppercase and lowercase each time you press [F2] CAPS.
Entering lowercase
CODE caps CLR ESC
Key-in Sequence to lower case
( o ) ( y )
MENU
A:DISPLAY
B:SENSOR TYPE
HOME SET ADJ ESC Function commands
Function keys
F0708.EPS
F0706 .EPS
F0707.EPS
7-2
Function Command List
Command
ADJ
CAPS/caps
CODE
CLR
DATA
DEL
DIAG
ESC
HOME
NO
OK
PARM
SET
SLOT
UTIL
Function
Displays the ADJ menu
Selects uppercase or lowercase
Selects symbols
Erases input data or deletes all data
Updates parameter data
Deletes one character
Calls the self-check panel
Returns to the most recent display
Displays the menu panel
Quits setup and returns to the previous display
Proceeds to the next panel
Enters the parameter number setup mode
Displays the SET menu
Returns to the slot selection panel
Calls the utility panel
*COPY
*FEED
Prints out parameters on display
Paper feed
*LIST Lists all parameters in the menu
*PON/POFF Automatic printout mode on or off
*PRNT
*GO
Changes to the print mode
Starts printing
*STOP Cancels printing
* Available on BT200-P00 (with printer).
T0704.EPS
IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
7.2.3 Calling Up Menu Addresses Using the Operating Keys
––WELCOME––
BRAIN TERMINAL
ID: BT200
STARTUP
SCREEN check connection push ENTER key
UTIL FEED
INITIAL
DATA
SCREEN
PARAM
01:MODEL
EJA438W-DA
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
OK
UTILITY
1.ID
2.SECURITY CODE
3.LANGUAGE SELECT
4.LCD CONTRAST
5.PRINTER ADJUST
(UTIL) esc
The utility screen contains the following items.
1. BT200 ID settings
2. Security code settings
3. Switching language of messages
(Japanese or English)
4. LCD contrast setting
5. Adjusting printout tone
(BT200-P00 only)
(ESC)
FUNC
1.MENU
2.UPLOAD TO BT200
3.DOWNLOAD TO INST
4.PRINT ALL DATA
(SET)
(SET MENU SCREEN)
MENU
C.SETTING
D.AUX SET 1
E.AUX SET 2
H:AUTO SET
HOME SET ADJ ESC
(ADJ)
(ADJ MENU SCREEN)
MENU
J.ADJUST
K.TEST
M.MEMO
P:RECORD
HOME SET ADJ ESC HOME SET ADJ ESC
MENU
SCREEN
(HOME MENU SCREEN)
MENU
A.DISPLAY
B.SENSOR TYPE
HOME SET ADJ ESC
PARAM
A60:SELF CHECK
GOOD
PARA-
METER
SCREEN
PARAM
A21:CAPSULE TEMP
26.5 deg C
DATA DIAG PRNT
PARAM
A10:OUTPUT(%)
50.0 %
A11:ENGR, OUTPUT
20.0 M
A20:AMP TEMP
24.5 deg C
DATA DIAG PRNT
ESC
ESC
ESC
PARAM
C60:SELF CHECK
GOOD
PARAM
C22:HIGH RANGE
100 kPa
DATA DIAG PRNT ESC
PARAM
C10:TAG NO.
YOKOGAWA
C20:PRESS UNIT
PRNT
kPa
C21:LOW RANGE
0 kPa
DATA DIAG PRNT
ESC
ESC
PARAM
J60:SELF CHECK
GOOD
PARAM
J10:ZERO ADJ
0.0 %
J11:ZERO DEV
PRNT
22.2 %
J20:EXT. ZERO ADJ
ENABLE
DATA DIAG PRNT
ESC
ESC
SETUP
SCREEN
SET
C10:TAG NO.
YOKOGAWA
YOKOGAWA
CODE CAPS CLR ESC
See “BT200 Instruction Manual” for details concerning uploading and downloading parameters and printouts (BT200-P00).
F0709.EPS
7-3 IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
7.3 Setting Parameters Using the BT200
7.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters
P: Pressure transmitters
L: Liquid level transmitters
EJA110, EJA120, EJA118W, EJA118N, EJA118Y, and EJA115
EJA310, EJA430, EJA438W, and EJA438N
EJA210 and EJA220
No.
Item Description
Rewritability
Remarks Default Value
F
Applicability
P L
01
02
MODEL
TAG NO.
03 SELF CHECK
A DISPLAY
A10 OUTPUT (%)
A11 ENGR.
OUTPUT
A20 AMP TEMP
A21 CAPSULE
TEMP
A30 STATIC
PRESS
A40 INPUT
Model+capsule type
Tag number
Self-diagnostic result
Measured data display
Output (in %)
Output (in engineering units)
Amplifier temperature
Capsule temperature
Static pressure
—
—
—
—
—
—
—
—
—
16 alphanumerics
GOOD/ERROR
Menu name
–5 to 110%
–19999 to 19999
Unit specified in D30
Unit specified in D30
Unit specified in D31*
7-4
—
A60 SELF CHECK
Input (indicated in engineering DP unit)
Self-diagnostic messages
—
—
—
—
—
—
—
—
–32000 to 32000
GOOD/ERROR, CAP MODULE
FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP
RANGE*, OVER TEMP (CAP),
OVER TEMP (AMP),
OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV,
ILLEGAL SPAN, and
ZERO ADJ OVER
Menu name B
B10 MODEL
B11 STYLE NO.
B20 LRL
B21 URL
B30 MIN SPAN
B40
C
SENSOR
TYPE
MAX STAT.P.
B60 SELF CHECK
SETTING
C10 TAG. NO.
C20 PRESS UNIT
Sensor type
Model+span
Style number
Lower range-limit
Upper range-limit
Minimum span
Maximum atatic pressure
Self-diagnostic messages
Setting data
Tag number
Measurement range units
—
—
16 uppercase alphanumerics
–32000 to 32000
–32000 to 32000
–32000 to 32000
Same as A60
—
C21 LOW RANGE
C22 HIGH
RANGE
C30 AMP
DAMPING
C40 OUTPUT
MODE
Measurement range, lower range value
Measurement range, higher range value
Damping time constant
Output mode and integral indicator mode
—
Menu name
16 alphanumerics
Selected from mmH
2
O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm 2 , kgf/cm 2 , inH
2
O, inHg, ftH
2
O, psi, or atm
–32000 to 32000(but within measurement range)
–32000 to 32000(but within measurement range)
Selected from 0.2, 0.5, 1.0, 2.0,
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Same as A60
As specified when ordered.
As specified when ordered.
As specified when ordered.
As specified when ordered.
2 s
As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.
C60
D
SELF CHECK Self-diagnostic messages
AUX SET 1 Auxiliary setting data 1
D10 LOW CUT
D11 LOW CUT
MODE
D20 DISP SELECT
Low cut
Low cut mode
Display selection
—
—
Menu name
0.0 to 20.0%
LINEAR/ZERO
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
* In case of Model EJA120, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
— —
T0705.EPS
IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
No.
Item Description
D AUX SET 1
D21 DISP UNIT
D22 DISP LRV
D23 DISP HRV
D30 TEMP UNIT
D31 STAT. P. UNIT
Auxiliary setting data 1
Engineering unit for display
Engineering range, lower range value
Engineering range, higher range value
Temperature setting units
Static pressure setting units
Rewritability
— deg C/deg F
Remarks
Menu name
8 uppercase alphanumerics
–19999 to 19999
–19999 to 19999
Default Value
As specified when ordered.
As specified when ordered.
deg C
Selected from mmH
2
O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm 2 , kgf/cm 2 , inH
2
O, inHg, ftH
2
O, psi, or atm
NORMAL/REVERSE
NORMAL/REVERSE**
As specified when ordered.
If not specified, MPa.
If not specified, NORMAL.
NORMAL
D40 REV OUTPUT
D45 H/L SWAP
D52 BURN OUT
D53 ERROR OUT
D60 SELF CHECK
Output reversal
Impulse piping accessing direction
CPU error
Hardware error
Self-diagnostic messages
E AUX SET 2
E30 BI DIRE
MODE
E60 SELF CHECK
H AUTO SET
H10 AUTO LRV
Auxiliary setting data 2
Bidirectional mode
Self-diagnostic messages
Automatic setup
H11 AUTO HRV
H60 SELF CHECK
J
J10 ZERO ADJ
J11 ZERO DEV.
J20 EXT. ZERO
J60 SELF CHECK
K
ADJUST
ADJ
TEST
K10 OUTPUT in %
Automatic measurement range lower range value setup
Automatic measurement range higher range value setup
Self-diagnostic messages
Adjustment data
Automatic zero adjustment
Manual zero adjustment
External zeroadjustment screw permission
Self-diagnostic messages
Tests
Test output % setting
—
—
—
—
—
—
—
—
—
—
HIGH/LOW
HOLD/HIGH/LOW
Same as A60
Menu name
OFF/ON
Same as A60
Menu name
–32000 to 32000
–32000 to 32000
Same as A60
Menu name
–5 to 110.0%
ENABLE/INHIBIT
Same as A60
Menu name
–5 to 110.0% Displays ‘ACTIVE’ while executing
Same as A60
HIGH
HIGH
OFF
Displays the same data as
C21.
Displays the same data as
C22.
K60 SELF CHECK Self-diagnostic messages
Memo M MEMO
M10 MEMO 1
M20 MEMO 2
M30 MEMO 3
M40 MEMO 4
M50 MEMO 5
M60 SELF CHECK
Memo
Memo
Memo
Memo
Memo
Self-diagnostic messages
P
P10
P11
P12
P13
P60
RECORD History of the errors
ERROR REC 1 Last error
ERROR REC 2 One time before
ERROR REC 3 Two time before
ERROR REC 4 Three time before
SELF CHECK Self-diagnostic messages
** Not applicable for Model EJA115.
—
—
—
—
Menu name
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
Same as A60
Display the error
Display the error
Display the error
Display the error
Same as A60
F
Applicability
P L
—
— —
— —
T0706.EPS
7-5 IM 1C22J1-01E
7.3.2 Parameter Usage and Selection
Before describing the procedure for setting parameters, we present the following table showing how the parameters are used and in what case.
7. BRAIN TERMINAL BT200 OPERATION
IMPORTANT
If the transmitter is turned off within 30 seconds after parameters have been set, the set data will not be stored and the terminal returns to previous settings.
Table 7.3.1 Parameter Usage and Selection
Tag No. setup c
P.7-7
Calibration range setup c
P.7-7
Setup Item
Damping time constant setup c
P.7-8
Output signal low cut mode setup c
P.7-9
Integral indicator scale range and unit setup c
P.7-9
Range change (while applying actual inputs) c
P.7-12
Zero point adjustment c P.7-12
Test output (fixed current output) setup c
P.7-14
User memo fields c
P.7-14
Description
Sets the Tag No. (using 16 alphanumeric characters).
Note: Up to 8 alphanumerics (upper case letters) can be used in the BT100.
Sets the calibration range for 4 to 20 mA DC. Sets three data items: range unit, input value at 4 mA DC (LRV), and input value at 20 mA DC (HRV).
Note: LRV and HRV can be specified with range value specifications up to 5 digits
(excluding any decimal point) within the range of –32000 to 32000.
Adjusts the output response speed for 4 to 20 mA DC.
Can be set in 9 increments from 0.2 to 64 s.
Used to stabilize output near 0%: forcing output to 0% for input below a specific value.
Sets the following 5 types of integral indicator scale ranges and units:
% scale indicator, user set scale indicator, alternate indication of user set scale and % scale, input pressure display, alternate indication of input pressure and % scale
When using the user set scale, 4 types of data can be set:
user set scale setting, unit (BT200 only), display value at 4 mA DC (LRV), and display
value at 20 mA DC (HRV).
Note: LRV and HRV can be specified with range value specifications up to 5
digits (excluding any decimal point) within the range of –19999 to 19999.
Unit setup for displayed temperature c P.7-11
Operation mode (normal/reverse signal) setup c
P.7-11
Output status display/setup when a CPU failure c P.7-11
Sets a unit for temperatures displayed on the BT200.
Reverses the direction for 4 to 20 mA DC output relative to input.
Reverse mode is used for applications in which safety requires that output be driven toward 20 mA if input is lost.
Displays the status of 4 to 20 mA DC output when a CPU failure. The parameter of the standard unit is fixed to the high limit value.
Output status setup when a hardware error occurs c P.7-11
Sets the status of the 4 to 20 mA DC output when an abnormal status is detected with the capsule or the amplifier as the result of self-diagnosis. One of the following statuses; last held, high limit, and low limit values, can be selected.
Range for 4 to 20 mA DC signal is set with actual input applied. Sets 20 mA DC output precisely with respect to user’s reference instrument output. Note that DPharp is calibrated with high accuracy before shipment, so span should be set using the normal range setup.
Adjusts zero point. This can be done either using the external zero-adjustment screw on the transmitteror using the BT200.
Used for loop checks.
Output can be set freely from –5% to 110% in 1% steps.
Allows user to enter up to 5 items of any desired text in up to 8 uppercase alphanumeric characters per item.
T0707.EPS
7-6 IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
7.3.3 Setting Parameters
Set or change the parameters as necessary. After completing these, do not fail to use the “DIAG” key to confirm that “GOOD” is displayed for the selfdiagnostic result at _ 60: SELF CHECK .
(1) Tag No. Setup (C10: TAG NO)
Use the procedure below to change the Tag No. Up to 16 alphanumeric characters can be entered.
• Example: Set a Tag No. to FIC-1a
<When power is off>
Press the key to turn on the BT200.
SET
C10:TAG NO.
YOKOGAWA
FIC-1a
PRINTER OFF
F2:PRINTER ON
FEED POFF NO
SET
C10:TAG NO.
FIC-1a
FEED NO
PARAM
C10:TAG NO.
FIC-1a
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
DATA DIAG PRNT
OK
ESC
This is the panel for confirming set data. The set data items flash.
When all items have been confirmed, press the again. (To go back to the setting panel, press the (NO) key.
The DPharp TAG NO. was overwritten.
Press the (OK) key to return to the parameter panel.
Press the (NO) key to return to the setting panel.
F0711.EPS
––WELCOME––
BRAIN TERMINAL
ID: BT200 check connection push ENTER key
UTIL FEED
PARAM
01:MODEL
EJA438W-DA
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
OK
MENU
A:DISPLAY
B:SENSOR TYPE
Connect DPharp and BT200 using a communication cable and press the key.
Displays the name of connected
DPharp model, TAG NO. and diagnostics information. Press the
(OK) key after confirmation.
Press the (SET) key to display the SET menu panel.
HOME SET
MENU
C:SETTING
D:AUX SET 1
E:AUX SET 2
H:AUTO SET
ADJ ESC
HOME SET ADJ
MENU
C10:TAG NO.
YOKOGAWA
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
DATA DIAG PRNT
SET
C10:TAG NO.
YOKOGAWA
YOKOGAWA
ESC
ESC
Select C: SETTING and press the
key.
Select C10: TAG NO. and press the key.
CODE CAPS CLR ESC
SET
C10:TAG NO.
YOKOGAWA
FIC-1a _
Set the new TAG NO. (FIC-1a).
FOKOGAWA
FIKOGAWA
FICOGAWA
FIC-GAWA
FIC-1AWA
FIC-1aWA
FIC-1a
Set TAG NO. and press the
key.
CODE caps CLE ESC
When you have made an entry mistake, return the cursor using the key, then reenter.
F0710.EPS
(2) Calibration Range Setup a. Setting Calibration Range Unit
(C20: PRESS UNIT)
The unit is set at the factory before shipment if specified at the time of order. Follow the procedure below to change the unit.
• Example: Change the unit from mmH
2
O to kPa.
SET
C20:PRESS UNIT
mmH20
< mmWG >
< mmHG >
< Torr >
< kPa >
SET
C20:PRESS UNIT
kPa
ESC
Use the or key to select “kPa.”
Press the key twice to enter the setting.
Press the (OK) key.
FEED mmH
2
O mmAq mmWG mmHg
Torr kPa
MPa mbar bar gf/cm 2 kgf/cm 2 inH
2
O inHg ftH
2
O psi atm
Pa hPa
NO OK
F0712.EPS
7-7 IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION b. Setting Calibration Range Lower
Range Value and Higher Range Value
(C21: LOW RANGE, C22: HIGH
RANGE)
These range values are set as specified in the order before the instrument is shipped. Follow the procedure below to change the range.
• The measurement span is determined by the high and low range limit values. In this instrument, changing the low range value also automatically changes the high range value, keeping the span constant.
• Example 1: With present settings of 0 to 30 kPa, set the lower range value to 0.5 kPa.
SET
C21:LOW RANGE
0 kPa
+ 0.5
Set 0.5.
Press the key twice to enter the setting.
DEL CLR
SET
C21:LOW RANGE
0.5 kPa
ESC
Press the (OK) key.
• Example 2: With present settings of 0 to 30 kPa, set the Higher range value to10 kPa.
SET
C22:HIGH RANGE
30 kPa
+ 10
Set 10.
Press the key twice to enter the setting.
DEL CLR
SET
C22:HIGH RANGE
10 kPa
ESC
Press the (OK) key.
FEED NO OK
PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
C22:HIGH RANGE
10 kPa
DATA DIAG PRNT ESC
The low range value is not changed, so the span changes.
F0714.EPS
(3) Damping Time Constant Setup
(C30: AMP DAMPING)
When the instrument is shipped, the damping time constant is set at 2.0 seconds. Follow the procedure below to change the time constant.
FEED NO OK
SET
C20:PRESS UNIT
kPa
C21:LOW RANGE
0.5 kPa
C22:HIGH RANGE
30.5 kPa
DATA DIAG PRNT ESC
The higher range value is changed while the span remains constant.
Span = Higher range value – Lower range value
F0713.EPS
• Example: Change from 2.0 sec to 4.0 sec.
SET
C30:AMP DAMPING
2.0 sec
< 2.0 sec >
< 4.0 sec >
< 8.0 sec >
< 16.0 sec >
ESC
Use the or key to select 4.0 sec.
Press the key twice to enter the setting.
SET
C30:AMP DAMPING
4.0 sec
Press the (OK) key.
• Note, however, that changing the higher range value does not cause the lower range value to change.
Thus, changing the higher range value also changes the span.
• Calibration range can be specified with range value specifications up to 5 digits (excluding any decimal point) for low or high range limits within the range of –32000 to 32000.
FEED
0.2sec
0.5sec
1.0sec
2.0sec
4.0sec
8.0sec
16.0sec
32.0sec
64.0sec
NO OK
F0715.EPS
Note: The damping time constant set here is the damping time constant for the amplifier assembly. The damping time constant for the entire transmitter is the sum of the values for the amplifier assembly and for the capsule assembly. For the capsule assembly damping time constant (fixed), see the
“General Specifications” found at the end of this manual.
(See Chapter 9.)
7-8 IM 1C22J1-01E
(4) Output Signal Low Cut Mode Setup
(D10: LOW CUT, D11: LOW CUT MODE)
Low cut mode can be used to stabilize the output signal near the zero point. The low cut point can be set in a range from 0 to 20% of output. (Hysteresis of cut point:
±
1%)
Select “ ZERO ” as the low cut mode.
d
LOW CUT mode ZERO at 10%
Output (%)
50
10
0 10
Input(%)
50
• Example: Change the low cut setting range from 5% to 10%, and the low cut mode from LINEAR to ZERO.
SET
D10:LOW CUT
5.0 %
+ 10.0
Set “10.”
Press the key twice to enter the setting.
CLR ESC
SET
D10:LOW CUT
10.0 %
Press the (OK) key.
Next, the [D11: LOW CUT MODE] setting panel is displayed.
FEED NO
SET
C11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >
SET
D11:LOW CUT MODE
ZERO
OK
ESC
Use the or key to select ZERO.
Press the key twice to enter the setting.
Press the (OK) key.
F0716.EPS
7. BRAIN TERMINAL BT200 OPERATION
(5) Integral Indicator Scale Setup
The following 5 displays are available for integral indicators.
D20: DISP SELECT and Display
NORMAL %
USER SET
USER & %
INP PRES
PRES & %
Description and Related parameters
Indicates –5 to 110% range depending on the Measurement range (C21, C22).
A10:OUTPUT (%)
45.6 %
Indicates values depending on the
Engineering range (D22, D23).
( Note 1 )
Units set using Engineering unit
(D21) are not indicated.
A11:ENGR.OUTPUT
20.0 M
Indicates user set and % alternately in 3 second intervals.
A10:OUTPUT (%)
45.6 %
A11:ENGR. OUTPUT
20.0 M
Indicates input pressure. Indication limits –19999 to 19999.
A40:INPUT
456 kPa
Indicates input pressure and % alternately in 3 second intervals.
A10:OUTPUT (%)
45.6 %
A40:INPUT
456 kPa
(Note 1) Scale range can be specified with range limit specifications up to 5 digits (excluding any decimal point) for low or high range limits within the range of –19999 to 19999.
T0708.EPS
See (a.) through (c.) for each setting procedure.
FEED NO OK
PARAM
D10:LOW CUT
10.0 %
D11:LOW CUT MODE
ZERO
D20:DISP SELECT
NORMAL %
DATA DIAG PRNT ESC
F0717.EPS
7-9 IM 1C22J1-01E
% indication and input pressure indication
D20: DISP SELECT
NORMAL %
INP PRES
PRES & %
Transmitter is set for “% display” when shipped.
User-set engineering unit display
D20: DISP SELECT
USER SET
USER & %
Set for user-set engineering unit display.
D21: DISP UNIT
Set a unit to be displayed on the BT200.
7. BRAIN TERMINAL BT200 OPERATION b. Setting User-set Engineering Unit
(D21: DISP UNIT)
This parameter allows entry of the engineering units to be displayed on the BT200. When the instrument is shipped, this is set as specified in the order.
Follow the procedure below to change this setting.
Since these units are not displayed on the integral indicator, use the adhesive labels provided. This parameter need not be set for % display.
• Example: Set an engineering unit M.
SET
D21:DISP UNIT
M_
Set “M.”
Press the key twice to enter the setting.
CODE CAPS CLR ESC
SET
D21:DISP UNIT
M
Press the (OK) key.
D22: DISP LRV
Set a numeric value for engineering unit for 4 mA output (LRV).
D23: DISP HRV
Set a numeric value for engineering unit for 20 mA output (HRV).
F0718.EPS
a. Display Selection (D20: DISP SELECT)
Follow the instructions given to the below to change the range of integral indication scales.
When USER SET is selected, the user set values of integral indication and A11: ENGR. OUTPUT parameter are indicated.
• Example: Set the integral indicator scale to
SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>
SET
D20:DISP SELECT
USER SET
FEED
engineering units display.
ESC
Use the or key to select “USER SET.”
Press the key twice to enter the setting.
Press the (OK) key.
NO OK
The “%” disappears from the integral indicator display.
FEED NO OK
F0720.EPS
c. Lower and Higher Range Value Setup in Engineering Unit (D22: DISP LRV,
D23: DISP HRV)
These parameter items are used to set the lower and higher range values for the engineering unit display.
When the instrument is shipped, these are set as specified in the order. Follow the procedure below to change these settings. Note that these parameters need not be set for % display.
• Example: Set lower range value (LRV) to –50 and higher range value (HRV) to 50.
Setting LRV
SET
D22:DISP LRV
0M
- 50
Set “–50.”
Press the key twice to enter the setting.
DEL CLR ESC
Setting HRV
SET
D23:DISP HRV
100M
+ 50
Set “50.”
Press the key twice to enter the setting.
DEL
SET
D23:DISP HRV
50M
CLR ESC
Press the (OK) key.
F0719.EPS
FEED NO OK
PARAM
D21:DISP UNT
M
D22:DISP LRV
– 50M
D23:DISP HRV
50M
DATA DIAG PRNT ESC
7-10
F0721.EPS
IM 1C22J1-01E
(6) Unit Setup for Displayed Temperature
(D30: TEMP UNIT)
When the instrument is shipped, the temperature units are set to degC . Follow the procedure below to change this setting. Note that changing the unit here changes the unit for A20: AMP TEMP (amplifier temperature) and A21: CAPSULE TEMP (capsule temperature).
• Example: Change the unit for the temperature
display.
SET
D30:TEMP UNIT
deg C
< deg C >
< deg F >
ESC
Use the or key to select “deg F.”
Press the key twice to enter the setting.
F0722.EPS
(7) Operation Mode Setup
(D40: REV OUTPUT)
This parameter allows the direction of the 4 to 20 mA output to be reversed with respect to input.
Follow the procedure below to make this change.
• Example: Change 4 to 20 mA output to 20 to
4 mA output.
SET
D40:REV OUTPUT
NORMAL
< NORMAL >
< REVERSE>
ESC
Use the or key to select REVERSE.
Press the key twice to enter the setting.
F0723.EPS
7. BRAIN TERMINAL BT200 OPERATION
(8) Output Status Display/Setup when a CPU
Failure (D52: BURN OUT)
This parameter displays the status of 4 to 20 mA DC output if a CPU failure occurs. In case of a failure, communication is disabled.
Setting of HIGH or LOW is enabled. This is done with the pin (CN4) on the CPU assembly. See
Chapter 3 for details.
Standard specifications
The parameter is set to HIGH. If a failure, the transmitter outputs the signal of 110% or higher. The parameter D53: ERROR OUT is set to HIGH from the factory.
Optional code/C1
The parameter is set to LOW. If a failure, output which is –5% or lower is generated. The parameter
D53: ERROR OUT is set to LOW from the factory.
• Example: Standard specifications pin (CN4) position: H
D52: BURN OUT
HIGH
• Example: Optional code/C1
D52: BURN OUT
LOW pin (CN4) position: L
F0724.EPS
(9) Output Status Setup when a Hardware
Error Occurs (D53: ERROR OUT)
This parameter allows the setting of the output status when a hardware error occurs. The following three selections are available.
(a) HOLD; Outputs the last value held before the error occurred.
(b) HIGH; Outputs an output of 110% when an error has occurred.
(c) LOW; Outputs an output of –5% when an error has occurred.
Note: A hardware error means CAP MODULE FAULT of Er.01 or
AMP MODULE FAULT of Er. 02 which are shown in 7.5.2
“Errors and Countermeasures.”)
• Example: Set the output status to LOW when
a hardware error occurs.
SET
D53:ERROR OUT
HIGH
< HIGH>
< LOW>
< HOLD>
ESC
Use the or key to select “LOW.”
Press the key twice to enter the setting.
F0725.EPS
7-11 IM 1C22J1-01E
(10) Range Change while Applying Actual
Inputs (H10: AUTO LRV, H11: AUTO
HRV)
This feature allows the lower and higher range values to be set up automatically with the actual input applied. If the lower and higher range values are set,
C21: LOW RANGE and C22: HIGH RANGE are changed at this same time.
Follow the procedure in the figure below.
The measurement span is determined by the higher and lower range values. Changing the lower range value results in the higher range value changing automatically, keeping the span constant.
7. BRAIN TERMINAL BT200 OPERATION
Note that changing the higher range value does not cause the lower range value to change but does change the span.
• Example 2: When the higher range value is to
be changed to 10 kPa with the present setting of 0 to 30 kPa, take the following action with an input pressure of 10 kPa applied.
SET
H10:AUTO HRV
30 kPa
+ 30
Press the key twice.
The higher range value is changed to 10 kPa.
ESC
SET
H11:AUTO HRV
10.000 kPa
Press the (OK) key.
• Example 1: When changing the lower range
value to 0.5 kPa for the present setting of 0 to 30 kPa, take the following action with input pressure of 0.5 kPa applied.
SET
H10:AUTO LRV
0 kPa
+ 0
SET
H10:AUTO LRV
0.5000 kPa
ESC
Press the key twice.
The lower range value is changed to 0.5 kPa.
Press the (OK) key.
FEED NO OK
PARAM
H10:AUTO LRV
0 kPa
H11:AUTO HRV
10.000 kPa
H60:SELF CHECK
GOOD
DATA DIAG PRNT ESC
The lower range value is not changed, so the span changes.
Parameter C22 is changed at the same time.
F0727.EPS
FEED NO
PARAM
H10:AUTO LRV
0.5000 kPa
H11:AUTO HRV
30.500 kPa
H60:SELF CHEC
GOOD
DATA DIAG PRNT
OK
ESC
The higher range value is changed keeping the span constant.
Parameters C21 and C22 are changed at the same time.
F0726.EPS
(11) Zero Point Adjustment
(J10: ZERO ADJ, J11: ZERO DEV,
J20: EXT ZERO ADJ)
The DPharp supports several adjustment methods.
Select the method best suited for the conditions of your application.
Note that output signal can be checked by displaying parameter A10:OUTPUT (%) on the BT200.
Adjustment Method
Using the BT200
Using the external zero-adjustment screw
Description
Set the present input to 0%.
Adjust for 0% output at input level of
0%.
Adjust output to the reference value obtained using other means.
If the input level cannot easily be made 0% (because of tank level, etc.), adjust output to the reference value obtained using other means, such as a sight glass.
Adjust zero point using the zeroadjustment screw on the transmitter.
This permits zero adjustment without using the BT200. Accurately adjust the output current to 4 mA DC or other target output value using an ammeter that accuratly reads output currents.
T0709.EPS
7-12 IM 1C22J1-01E
(a) Follow the procedure below when setting the present output to 0% (4 mA).
7. BRAIN TERMINAL BT200 OPERATION
(b)-2 Follow the procedure below to use J11: ZERO
DEV .
A10:OUTPUT (%)
0.5 %
SET
J10:ZERO ADJ
0.0 %
+ 000.0
Output is 0.5%.
Press the key twice.
SET
J10:ZERO ADJ
0.0 %
CLR ESC
Zero adjustment is completed.
Press the (OK) key.
A10:OUTPUT (%)
41.0 %
SET
J11:ZERO DEV.
2.50 %
0
SET
J11:ZERO DEV.
2.50 %
1.50
Present output is 41.0%.
Output error = 40.0 – 41.0 = –1.0%.
ESC
Since “J11: ZERO DEV.” contains the previous correction, obtain the correction value by adding –1.0% to it. 2.50% + (–1.0%) = 1.50%
Set the correction value, 1.50.
Press the key twice.
FEED NO
A10:OUTPUT (%)
0.0 %
OK
Output is 0%.
ECS
The output is changed to 40%.
A10:OUTPUT (%)
40.0 %
F0730.EPS
F0728.EPS
(b) In tank level measurement, if the actual level cannot be brought to zero for zero adjustment, then the output can be adjusted to correspond to the actual level obtained using another measuring instrument such as a glass gauge.
[Example]
Measurement range: 50 to 250 kPa, Actual value:
130 kPa.
Actual value(%)
=
Actual value
–Measurement range lower range value x 100
Measurement range higher range value
–Measurement range lower range value
=
130–50
250–50 x 100=40.0%
(b)-1 Follow the procedure below to use
ADJ .
A10:OUTPUT (%)
41.0 %
SET
J10:ZERO ADJ
0.0 %
+ 040.0
J10: ZERO
Present output is 41.0%.
Enter the present actual level, 40%.
Press the key twice.
CLR ESC
A10:OUTPUT (%)
40.0 %
The output is changed to 40%.
F0729.EPS
(c) Zero Point Adjustment Using the External Zero
Adjustment Screw
• Enabling/inhibiting of zero point adjustment using the external zero-adjustment screw on the transmitter
(J20: EXT ZERO ADJ)
Follow the procedure below to enable or inhibit zero point adjustment from the zero-adjustment screw on the transmitter.
This is set to “ENABLE” when the instrument is shipped.
• Example: Inhibiting zero adjustment by the
external zero-adjustment screw
SET
J20:EXIT ZERO ADJ
ENABLE
< ENABLE >
< INHIBIT>
ESC
Use the or key to select “INHIBIT.”
Press the key twice to enter the setting.
F0731.EPS
• Zero point adjustment using external zero-adjustment screw on the transmitter
Turn the zero-adjustment screw on the outside of the transmitter case using a slotted screwdriver. Turn the screw to the right to increase the zero point or to the left to decrease the zero output; the zero adjusts in increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point changes according to the speed at which the screw is turned. To make fine adjustments, turn the screw slowly; to make coarse adjustments, turn the screw quickly.
7-13
Note: When a zero point adjustment has been made, do not turn off the transmitter less than 30 seconds after adjustment.
IM 1C22J1-01E
(12) Test Output Setup (K10: OUTPUT X%)
This feature can be used to output a fixed current from 3.2 mA (–5%) to 21.6 mA (110%) for loop checks.
• Example: Output 12 mA (50%) fixed current.
SET
K10:OUTPUT X %
0.0 %
+ 050.0
Set “50.0%.”
Press the key twice to output a fixed current at 50%.
ESC
SET
K10:OUTPUT X %
50.0 % ACTIVE
FEED NO OK
“Active” is displayed while this is being executed.
Press the (OK) key to cancel the fixed current output.
F0732.EPS
7. BRAIN TERMINAL BT200 OPERATION
7.4 Displaying Data Using the
BT200
7.4.1 Displaying Measured Data
The BT200 can be used to display measured data.
The measured data is updated automatically every 7 seconds. In addition, the display can be updated to the present data value at any time by pressing the
(DATA) key. For parameters associated with the display of measured data, see Subsection 7.3.1,
“Parameter Summary.”
• Example: Display output.
MENU
A:DISPLAY
B:SENSOR TYPE
IMPORTANT
1. Test output is held for approximately 10 minutes, and then released automatically after the time has elapsed. Even if the BT200 power supply is turned off or the communication cable is disconnected during test output, it is held for approximately 10 minutes.
2. Press the (OK) key to release test output immediately.
HOME SET ADJ ESC
PARAM
A10:OUTPUT (%)
XX.X %
A11:ENGR.OUTPUT
YY.Y %
A20:AMP TEMP
ZZ deg C
DATA DIAG PRNT ESC
Display “A10: OUTPUT (%).”
Data is updated automatically at 7-second intervals.
PARAM
A10:OUTPUT (%)
A11:ENGR.OUTPUT
A20:AMP TEMP communi
(13) User Memo Fields (M: MEMO)
This feature provides 5 user memo fields, each holding up to 8 alphanumeric characters. Up to 5 items such as inspection date, inspector, and other information can be saved in these fields.
7.4.2 Display Transmitter Model and
Specifications
The BT200 can be used to display the model and specifications of the transmitter.
F0734.EPS
• Example: View transmitter model name.
MENU
A:DISPLAY
B:SENSOR TYPE
Press .
• Example: Save an inspection date of January
30, 1995.
PARAM
M10:MEMO 1
M20:MEMO 2
M30:MEMO 3
DATA DIAG PRNT
SET
M10:MEMO 1
95.1.30_
ESC
Set “95.1.30” in the order of year, month, and day.
Press the key twice to enter the setting.
ESC
F0733.EPS
HOME SET ADJ ESC
PARAM
B10:MODEL
EJA438W-DA
B11:STYLE NO.
S1.01
B20:LRL
– 98.07 kPa
DATA DIAG PRNT ESC
For the associated parameters, see Subsection
7.3.1, Parameter Summary.
F0735.EPS
7-14 IM 1C22J1-01E
7.5 Self-Diagnostics
7.5.1 Checking for Problems
(1) Identifying Problems with BT200
The following four areas can be checked.
(a) Whether connections are good.
(b) Whether BT200 was properly operated.
(c) Whether settings were properly entered.
(d) History of the errors.
See examples below.
• Example 1: Connection errors
––WELCOME––
BRAIN TERMINAL
ID: BT200 check connection push ENTER key
UTIL FEED
Press the key.
When the panel shown on the left appears, press the key.
communication error
ESC
Since communications will be unsuccessful if there is a problem in the connection to the BT200, the display at the left will appear.
Recheck the connection.
Press the (OK) key.
• Example 2: Setting entry errors
PARAM
01:MODEL
EJA438W-DA
02:DAG NO.
YOKOGAWA
03:SELF CHECK
ERROR
The initial data panel shows the result of current transmitter diagnostics.
OK
PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
600 kPa
C22:HIGH RANGE
600 kPa
DATA DIAG PRNT ESC
DIAG
C60:SELF CHECK
ERROR
< ERROR >
< ILLEGAL LRV >
FEED PRNT ESC
Press the (DIAG) key in the parameter panel to go to the diagnostics panel
(C60: SELF CHECK).
An error message is displayed when an error occurs in the diagnostics panel.
F0736.EPS
7. BRAIN TERMINAL BT200 OPERATION
• Example 3: Checking the history of the errors
MENU
J:ADJUST
K:TEST
M:MEMO
P:RECORD
HOME SET ADJ ESC
Connect the BT200 to the transmitter, and call item “P.”
PARAM
P10:ERROR REC 1
ERROR
P11:ERROR REC 2
ERROR
P12:ERROR REC 3
GOOD
DATA DIAG PRNT ESC
P10: “ERROR REC 1” displays the last error.
P11: “ERROR REC 2” displays the error one time before the last error occurred.
P12: “ERROR REC 3” displays the error two times before the last error occurred.
P13: “ERROR REC 4” displays the error three times before the last error occurred.
The history of up to four errors can be stored. When the 5th error has occurred, it is stored in “P10”. The error stored in
“P13” will be deleted, and then, the error in “P12” will be copied to “P13”. In this sequence, the history of the most previously occurred error will be removed from memory.
“GOOD” will be displayed if there was no previous error.
SET
P10:ERROR REC 1
ERROR
< ERROR >
< ILLEGAL LRV >
< ILLEGAL HRV >
ESC
<(a) SETUP PANEL>
Select P10: ERROR REC1 and press the key to display the error message.
For the details of the messages listed below, see Table
8.5.1 Error Message Summary.
CAP MODULE FAULT
AMP MODULE FAULT
OUT OF RANGE
OUT OF SP RANGE
OVER TEMP (CAP)
OVER TEMP (AMP)
OVER OUTPUT
OVER DISPLAY
ILLEGAL LRV
ILLEGAL HRV
ILLEGAL SPAN
ZERO ADJ OVER
Note 1: Press the key twice in the setting panel
(panel 1) to clear all error message (P10 to P13) information.
Note 2: After two hours from when an error occurs, the error message of that error will be recorded. Therefore, if you switch off the transmitter within two hours from when the error occurs, there is no history of that error stored in the transmitter, and this function is meaningless.
F0737.EPS
7-15 IM 1C22J1-01E
(2) Checking with Integral Indicator
NOTE
If an error is detected in the self-diagnostic, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at two-second intervals.
See Table 7.5.1 regarding the error numbers.
7. BRAIN TERMINAL BT200 OPERATION
F0738.EPS
Figure 7.5.1 Identifying Problems Using the Integral
Indicator
7-16 IM 1C22J1-01E
7. BRAIN TERMINAL BT200 OPERATION
7.5.2 Errors and Countermeasures
The table below shows a summary of error messages.
Table 7.5.1 Error Message Summary
Integral
Indicator
Display
None
----
Er. 01
BT200 Display
GOOD
ERROR
CAP MODULE
FAULT
Cause
Output Operation during Error
Countermeasure
Capsule problem.
Outputs the signal
(Hold, High, or Low) set with parameter
D53.
Replace capsule.
Er. 02
Er. 03
Er. 04
AMP MODULE
FAULT
OUT OF RANGE
OUT OF SP
RANGE
Amplifier problem.
Input is outside measurement range limit of capsule.
Static pressure exceeds specified range.
*1
Capsule temperature is outside range
(–50 to 130
°
C).
Outputs the signal
(Hold, High, or Low) set with parameter
D53.
Outputs high range limit value or low range limit value.
Displays present output.
Replace amplifier.
Check input.
Check line pressure
(static pressure).
Er. 05
Er. 06
Er. 07
Er. 08
OVER TEMP
(CAP)
OVER TEMP
(AMP)
OVER OUTPUT
OVER DISPLAY
Amplifier temperature is outside range
(–50 to 95
°
C).
Output is outside high or low range limit value.
Displayed value is outside high or low range limit value.
Displays present output.
Displays present output.
Outputs high or low range limit value.
Displays high or low range limit value.
Use heat insulation or make lagging to keep temperature within range.
Use heat insulation or make lagging to keep temperature within range.
Check input and range setting, and change them as needed.
Check input and display conditions and modify them as needed.
Check LRV and modify as needed.
Er. 09
Er. 10
Er. 11
Er. 12
ILLEGAL LRV
ILLEGAL HRV
ILLEGAL SPAN
LRV is outside setting range.
Holds output immediately before error occurrence.
HRV is outside setting range.
Holds output immediately before error occurrence.
SPAN is outside setting range.
Holds output immediately before error occurrence.
ZERO ADJ OVER Zero adjustment is too large.
Displays present output.
Check HRV and modify as needed.
Check SPAN and change as needed.
Readjust zero point.
*1: For Model EJA120, static pressure cannot be measured. The display is always 0 MPa, but this is
not a measured value.
T0710 .EPS
7-17 IM 1C22J1-01E
8. MAINTENANCE
8.
MAINTENANCE
8.1 Overview
WARNING
Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors during draining condensate or venting gas in transmitter pressure-detector section even after dismounting the instrument from process line for maintenance.
Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disassembly and reassembly procedures required for component replacement.
Since the transmitters are precision instruments, carefully and thoroughly read the following sections for proper handling during maintenance.
IMPORTANT
• As a rule, maintenance of this transmitter should be implemented in a maintenance service shop where the necessary tools are provided.
• The CPU assembly contains sensitive parts that may be damaged by static electricity.
Exercise care so as not to directly touch the electronic parts or circuit patterns on the board, for example, by preventing static electrification by using grounded wrist straps when handling the assembly.
Also take precautions such as placing a removed CPU assembly into a bag with an antistatic coating.
8.2 Calibration Instruments Selection
Table 8.2.1 shows the instruments required for calibration. Select instruments that will enable the transmitter to be calibrated or adjusted to the required accuracy.
The calibration instruments should be handled carefully so as to maintain the specified accuracy.
8.3 Calibration
Use the procedure below to check instrument operation and accuracy during periodic maintenance or troubleshooting.
1) Connect the instruments as shown in Figure 8.3.1
and warm up the instruments for at least five minutes.
IMPORTANT
• To adjust the transmitter for highest accuracy, make adjustments with the power supply voltage and load resistance including leadwire resistances set close to the conditions under which the transmitter is installed.
• If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure should be applied on the high pressure side, as shown in the figure. If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied using the vacuum pump.
2) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter.
Calculate the errors (differences between digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from 100% to 0%, and confirm that the errors are within the required accuracy.
8-1 IM 1C22J1-01E
8. MAINTENANCE
Table 8.2.1 Tools for Disassembly and Reassembly
Name Yokogawa-recommended Instrument Remarks
Power supply
Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor
Voltmeter
Model 2792 standard resistor [250
Ω ±
0.005%, 3 W]
Load adjustment resistor [100
Ω ±
1%, 1 W]
Model 2501 A digital multimeter
Accuracy (10V DC range):
±
(0.002% of rdg + 1 dgt)
Digital manometer
Model MT110, MT120 precision digital manometer
1) For 10 kPa class
Accuracy:
±
(0.015% of rdg + 0.015% of F.S.)
±
(0.2% of rdg + 0.1% of F.S.)
. . . . .
. . . . . . . . .
2) For 130 kPa class
Accuracy:
±
0.02% of rdg . . . . . . . . . . . . . . . . . . . . . .
±
5digits . . . . . . . . . . . . . . . . . . . . . . . . . .
±
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . .
3) For 700 kPa class
Accuracy:
±
(0.02% of rdg + 3digits)
±
5 digits
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
±
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . .
4) For 3000 kPa class
Accuracy:
±
(0.02% of rdg + 10 digits) . . . . . . . . . . .
±
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . .
5) For 130 kPa abs class
Accuracy:
±
(0.03% of rdg + 6 digits) . . . . . . . . . . . .
for 0 to 10 kPa for -10 to 0 kPa for 25 to 130 kPa for 0 to 25 kPa for -80 to 0 kPa for 100 to 700 kPa for 0 to 100 kPa for -80 to 0 kPa for 0 to 3000 kPa for -80 to 0 kPa for 0 to 130 kPa abs
Pressure generator
Model 2657 pneumatic pressure standard for 200 kPa {2 kgf/cm 2 }, 25 kPa {2500 mmH
2
Accuracy:
±
0.05% of F.S. or
±
0.1% setting (whichever is greater)
O} Requires air pressure supply.
Dead weight gauge tester 25 kPa {2500mmH
Accuracy:
±
0.03% of setting
2
O}
Select a manometer having a pressure range close to that of the transmitter.
Select a pressure generator having a pressure range close to that of the transmitter.
Pressure source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump for negative pressure ranges.
T0801.EPS
Note : The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% level, there are difficulties in calibration to this level in the field.
For calibration to the 0.1% level, contact Yokogawa representatives from which the instrument was purchased or the nearest Yokogawa office.
Mating calibration flange
Model MT110, MT120 precision digital manometer
P
If a pressure source and a manometer are combined:
Pressure source
Diaphragm seal
Reference pressure
P
Model 2657 pneumatic pressure standards
Supply pressure
If a pressure generator is used:
Figure 8.3.1 Instrument Connections
Load resistance, 250
Ω
Rc
Load adjustment resistance, 100
Ω
R
V
Digital voltmeter
Power supply
E
F0801.EPS
8-2 IM 1C22J1-01E
8.4 Disassembly and Reassembly
This section describes procedures for disassembly and reassembly for maintenance and component replacement.
Always turn OFF power and shut off and release pressures before disassembly. Use proper tools for all operations. Table 8.4.1 shows the tools required.
Table 8.4.1 Instruments Required for Calibration
Tool
Phillips screwdriver
Slotted screwdriver
Allen wrenches
Wrench
Torque wrench
Adjustable wrench
Socket wrench
Socket driver
Tweezers
Quantity
1
1
2
1
1
1
1
1
1
Remarks
JIS B4633, No. 2
JIS B4648
One each, nominal 3 and
5 mm Allen wrenches
Width across flats, 17 mm
Width across flats, 16 mm
Width across flats, 5.5 mm
T0902.EPS
8. MAINTENANCE
8.4.1 Replacing the Integral Indicator
This subsection describes the procedure for replacing an integral indicator. (See Figure 8.4.2)
CAUTION
Precautions for JIS Flameproof Type Transmitters
Users are prohibited by law from modifying the construction of a flameproof type transmitter.
Thus the user is prohibited from using a flameproof type transmitter with its integral indicator removed, or from adding an integral indicator to a transmitter. If such modification is absolutely required, contact Yokogawa.
CAUTION
Precautions for CENELEC, SAA, and JIS
Flameproof Type Transmitters
• Flameproof type transmitters must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state. For details, see
“Installation and Operating Precautions for JIS
Flameproof Equipment” later in this manual.
• Two covers are locked by each of an Allen head bolt (shrouding bolt) on the flameproof type transmitters. When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then a cover can be opened.
When a cover is closed it should be locked by a shrouding bolt without fail. Tighten the shrouding bolt to a torque of 0.7 N·m.
Shrouding bolt
Figure 8.4.1 Shrouding Bolts j Removing the Integral Indicator
1) Remove the cover.
2) Supporting the integral indicator by hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU assembly.
When doing this, carefully pull the LCD board assembly straight forward so as not to damage the connector between it and the CPU assembly.
j Attaching the Integral Indicator
1) Align both the LCD board assembly and CPU assembly connectors and engage them.
2) Insert and tighten the two mounting screws.
3) Replace the cover.
Output terminal cable
Press forward
LCD board assembly
Integral indicator
Shrouding bolt
Cover
Boss
Flat cable
CPU assembly
Bracket
(for zero-adjustment screw pin)
Zero-adjustment screw pin
Mounting screw
F0802.EPS
F0803.EPS
8-3
Figure 8.4.2 Removing and Attaching LCD Board
Assembly and CPU Assembly
IM 1C22J1-01E
8.4.2 Replacing the CPU Assembly
This subsection describes the procedure for replacing the CPU assembly. (See Figure 8.4.2) j
Removing the CPU Assembly
1) Remove the cover. If an integral indicator is mounted, refer to Subsection 8.4.1 and remove the indicator.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) shown in
Figure 8.4.2.
3) Disconnect the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage.
4) Use a socket driver (width across flats, 5.5mm) to loosen the two bosses.
5) Carefully pull the CPU assembly straight forward to remove it.
6) Disconnect the flat cable (cable with black connector at the end) that connects the CPU assembly and the capsule.
NOTE
Be careful not to apply excessive force to the
CPU assembly when removing it.
j
Mounting the CPU Assembly
1) Connect the flat cable (with black connector) between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown connector).
NOTE
Make certain that the cables are free of pinching between the case and the CPU assembly edge.
3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU board assembly straight onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is equipped with an integral indicator, refer to
Subsection 8.4.1 to mount the indicator.
8. MAINTENANCE
NOTE
Confirm that the zero-adjustment screw pin is placed properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero-adjustment mechanism will be damaged.
5) Replace the cover.
8-4 IM 1C22J1-01E
8.5 Troubleshooting
If any abnormality appears in the measured values, use the troubleshooting flow chart below to isolate and remedy the problem. Since some problems have complex causes, these flow charts may not identify all.
If you have difficulty isolating or correcting a problem, contact Yokogawa service personnel.
8.5.1 Basic Troubleshooting
First determine whether the process variable is actually abnormal or a problem exists in the measurement system.
If the problem is in the measurement system, isolate the problem and decide what corrective action to take.
This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting; see
Section 7.5 for information on using this function.
: Areas where self-diagnostic offers support
Abnormalities appear in measurement.
8. MAINTENANCE
8.5.2 Troubleshooting Flow Charts
The following sorts of symptoms indicate that transmitter may not be operating properly.
Example : • There is no output signal.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.
Connect BRAIN TERMINAL and check self-diagnostics.
Does the self-diagnostic indicate problem location?
NO
YES
Refer to error message summary in
Subsection 7.5.2 to take actions.
YES
Inspect the process system.
Is process variable itself abnormal?
NO
Measurement system problem
Isolate problem in measurement system.
YES
Inspect receiver.
Does problem exist in receiving instrument?
NO
Is power supply polarity correct?
NO
YES Refer to Section 5.3 to check/correct polarity at each terminal from power supply to the terminal box.
Are power supply voltage and load resistance correct?
YES
NO
Refer to Section 5.6 to obtain rated voltage and load resistance.
Is there continuity through the transmitter loop wiring?
Do the loop numbers match?
YES
NO
Find/correct broken conductor or wiring error.
Contact Yokogawa service personnel.
F0805.EPS
Environmental conditions Transmitter itself
Check/correct environmental conditions.
Operating conditions
Check transmitter.
Check/correct operating conditions.
Figure 8.5.1 Basic Flow and Self-Diagnostics
F0804.EPS
8-5 IM 1C22J1-01E
Output travels beyond 0% or 100%.
Connect BRAIN TERMINAL and check self-diagnostics.
Does the selfdiagnostic indicate problem location?
NO
YES
Refer to error message summary in
Subsection 7.5.2 to take actions.
Is the diaphragm seal correctly connected to the process?
NO
Correct the connections.
YES
Is power supply polarity correct?
YES
NO
Check/correct polarity at each terminal from power supply to the terminal box.
NO
Is the pressure as specified?
YES Use the transmitter within the measurement range shown on the data plate.
Is zero point adjusted correctly?
NO
YES Adjust the zero point.
Contact Yokogawa service personnel.
F0806.EPS
8. MAINTENANCE
Large output error.
Connect BRAIN TERMINAL and check self-diagnostics.
Does the selfdiagnostic indicate the problem location?
NO
YES
Refer to error message summary in
Subsection 7.5.2 to take actions.
Are power supply voltage and load resistance correct?
NO
YES Refer to Section 5.6 to obtain the rated voltage and load resistance.
Is external noise contained in the outout?
NO
YES
Avoid noise by providing complete grounding, or using shielded wires.
NO
Is excess capillary secured?
YES Secure it so that it is not moved by wind or vibration.
Is transmitter installed where there is marked variation in temperature?
NO
YES
Provide lagging and/or heat insulation, or allow adequate ventilation.
Were appropriate instruments used for calibration?
YES
NO
Refer to Section 8.2 when selecting instruments for calibration.
NO
Is output adjusted correctly?
YES Adjust the output.
Contact Yokogawa service personnel.
F0807.EPS
8-6 IM 1C22J1-01E
9. GENERAL SPECIFICATIONS
9.
GENERAL SPECIFICATIONS
9.1
Standard Specifications
Refer to GS 1C22T2-E for Fieldbus communication type marked with “ e
”.
d Performance Specifications
See General Specifications sheet, GS 1C22J3-E.
d Functional Specifications
Span & Range Limits
Measurement
Span and Range
Span
A
Range
MPa
0.06 to 3
–0.1 to 3
Span 0.46 to 14 psi
(/D1)
8.6 to 430
–15 to 430
66 to 2000 bar
(/D3) kgf/cm 2
(/D4)
0.6 to 30 0.6 to 30
–1 to 30 –1 to 30
4.6 to 140 4.6 to 140
B
Range –0.1 to 14 –15 to 2000
Span 0.46 to 7 66 to 1000
–1 to 140 –1 to 140
4.6 to 70 4.6 to 70
Range –0.1 to 7 –15 to 1000 –1 to 70 –1 to 70
T0901.EPS
Measurement range is within the flange rating.
Zero Adjustment Limits:
Zero can be fully elevated or suppressed, within the Lower and Upper Range Limits of the capsule.
External Zero Adjustment “ e ”:
External zero is continuously adjustable with
0.01% incremental resolution of span. Span may be adjusted locally using the digital indicator with range switch.
Output “ e ”:
Two wire 4 to 20 mA DC output with digital communications, linear or square root programmable. BRAIN or HART FSK protocol are superimposed on the 4 to 20 mA signal.
Failure Alarm:
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: –5%, 3.2 mA DC
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order):
The sum of the amplifier and capsule damping time constant must be used for the overall time constant. Amp damping time constant is adjustable from 0.2 to 64 seconds.
Capsule (Silicone Oil) A and B
Time Constant (approx. sec) 0.4
T0902.EPS
When the capillary length 3 m and the fill fluid code
A.
Ambient Temperature Limits:
* Safety approval codes may affect limits.
–40 to 60 ° C (–40 to 140 ° F),
–30 to 60
°
C (–22 to 140
°
F) with LCD Display
Note:The ambient temperature limits must be within the fill fluid operating temperature range, see Table 1.
Process Temperature Limits:
* Safety approval codes may affect limits.
See Table 1.
Working Pressure Limits:
2.7 kPa abs {20 mmHg abs} to flange rating pressure.
For atmospheric pressure or below, see Figure 1.
9-1 d Installation
Supply & Load Requirements “ e ”:
* Safety approvals can affect electrical requirements.
See Section 5.6, ‘Power Supply Voltage and Load
Resistance.’
EMC Conformity Standards: ,
For EMI (Emission): EN55011, AS/NZS 2064 1/2
For EMS (Immunity): EN50082-2
Communication Requirements “ e
”:
BRAIN
Communication Distance;
Up to 2 km (1.25 miles) when using CEV polyethylene-insulated PVC-sheathed cables.
Communication distance varies depending on type of cable used.
Load Capacitance;
0.22
µ
F or less (see note)
Load Inductance;
3.3 mH or less (see note)
Input Impedance of communicating device;
10 k
Ω
or more at 2.4 kHz.
Note: For general-use and Flameproof type.
For Intrinsically safe type, please refer to
‘Optional Specifications.’
HART
Communication Distance;
Up to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies depending on type of cable used.
Use the following formula to determine cable length for specific applications:
L=
65 x 10 6
(R x C)
-
(C f
+ 10,000)
C
Where:
L = length in meters or feet
R = resistance in
Ω
(including barrier resistance)
C = cable capacitance in pF/m or pF/ft
C f
= maximum shunt capacitance of receiving devices in pF/m or pF/ft
IM 1C22J1-01E
9. GENERAL SPECIFICATIONS d Physical Specifications
Wetted Parts Materials:
Diaphragm and other wetted parts;
Process temperature for fill fluid code B
See ‘Model and Suffix Codes’
Non-wetted Parts Materials:
Capillary tube;
SUS316
Protection tube;
SUS304, PVC-sheathed [Max. operating temperature: 100
°
C (212
°
F)]
Fill Fluid;
See Table 1.
Housing;
Low copper cast-aluminum alloy with polyurethane paint (Munsell 0.6GY3.1/2.0)
Enclosure Classification;
JIS C0920 immersion proof (equivalent to NEMA
4X and IEC IP67)
Cover O-rings;
Buna-N
Data plate and tag;
SUS304
Weight:
Transmitter ambient temperature range
(For fill fluid code A,B)
100{750}
Working pressure kPa abs
{mmHg abs}
10{75}
2.7{20}
1{7.5}
9.3 kg (20.5 lb): Model EJA438W, 2-inch ANSI
Class 150 flange, without mounting bracket. Add
1.4 kg (3.1 lb) for JIS SCS14A stainless steel amplifier housing.
Connections:
Refer to the ‘Model and Suffix Codes’ to specify the process and electrical connection type.
Process temperature for fill fluid code A
Process temperature for fill fluid code C
0.1{0.75}
-50 0 50 100 150 200 250 300
Process Temperature (
8
C)
F0901.EPS
Flange max.
working pressure
Atmospheric pressure
Figure 1. Working Pressure and Process Temperature
Table 1. Process Temperature and Ambient Temperature
Process
Temperature (Note 1)
Ambient temperature (Note 2)
Working pressure
Specific gravity (Note 3)
Fill Fluid
Code ‘A’
–10 to 250
8
C
(14 to 482
8
F)
–10 to 60
8
C
(14 to 140
8
F)
Silicone Oil
Fill Fluid
Code ‘B’
–30 to 180
8
C
(–22 to 356
8
F)
–15 to 60
8
C
(5 to 140
8
F)
See Figure 1.
Fill Fluid
Code ‘C’
10 to 300
8
C
(50 to 572
8
F)
10 to 60
8
C
(50 to 140
8
F)
Fluorinated Oil
Fill Fluid
Code ‘D’
–20 to 120
8
C
(–4 to 248
8
F )
–10 to 60
8
C
(–14 to 140
8
F )
51 kPa abs or more
{380 mmHg abs}
Ethylene Glycol
Fill Fluid
Code ‘E’
–50 to 100
8
C
(–58 to 212
8
F)
–40 to 60
8
C
(–40 to 140
8
F)
Vacuum pressure not allowed
1.07
0.94
1.09
1.90 to 1.92
1.09
T0903.EPS
Note 1: See Figure 1. ‘Working Pressure and Process Temperature.’
Note 2: This ambient temperature is the transmitter ambient temperature.
Note 3: Approximate values at a temperature of 25
°
C(77
°
F)
Note 4: The pressure transmitter should be installed at least 600 mm below the process connection.
However, this value(600 mm) may be affected by ambient temperature, operating pressure, fill fluid or material of the wetted diaphragm. Contact YOKOGAWA when the transmitter can not be installed at least 600 mm below the process connection.
<Settings When Shipped “ e
”>
Tag Number
Output Mode
Display Mode
As specified in order
‘Linear’
‘Linear’
*1
Operation Mode ‘Normal’ unless otherwise specified in order
Damping Time
Constant
‘2 sec.’
Calibration Range
Lower Range Value
Calibration Range
Higher Range Value
As specified in order
As specified in order
Calibration Range
Units
Selected from mmH
2
O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa, MPa, mbar, bar, gf/cm 2 , kgf/cm 2 , inH
2
O, inHg, ftH
2
O, psi, or atm.(Only one unit can be specified)
T0908.EPS
Note 1: If Tag No. is no more than 16 alphanumeric characters (including - and ·), it will be written into the tag plate and amplifier memory settings.
9-2 IM 1C22J1-01E
9. GENERAL SPECIFICATIONS
9.2
Model and Suffix Codes
d Model EJA438W
[Style: S2]
Model Suffix Codes Description
EJA438W
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Signal
Measurement span
(capsule)
Wetted parts material
-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Process flange rating
Process flange size / material
Cover flange bolts material
S . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H . . . . . . . . . . . . . . . . . . . . . . . . . . . .
T . . . . . . . . . . . . . . . . . . . . . . . . . . . .
U . . . . . . . . . . . . . . . . . . . . . . . . . . . .
J1 . . . . . . . . . . . . . . . . . . . . . . . . . .
J2 . . . . . . . . . . . . . . . . . . . . . . . . . .
J4 . . . . . . . . . . . . . . . . . . . . . . . . . .
J6 . . . . . . . . . . . . . . . . . . . . . . . . . .
A1 . . . . . . . . . . . . . . . . . . . . . . . . . .
A2 . . . . . . . . . . . . . . . . . . . . . . . . . .
A4 . . . . . . . . . . . . . . . . . . . . . . . . . .
D2 . . . . . . . . . . . . . . . . . . . . . . . . . .
D4 . . . . . . . . . . . . . . . . . . . . . . . . . .
D5 . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . .
Fill fluid
Capillary length (m)
Installation
Electrical connection
Integral indicator
Mounting bracket
Optional codes
Diaphragm sealed differential pressure transmitter
(Flush diaphragm type)
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol) (Note 1)
Digital communication (FOUNDATION Fieldbus protocol) (Note 3)
0.06 to 3 MPa {0.6 to 30 kgf/cm 2 }
0.46 to 14 MPa {4.6 to 140 kgf/cm 2 }
[Diaphragm] [Others]
JIS SUS316L
Hastelloy C-276
Tantalum
Titanium
JIS 10K
JIS 20K
JIS 40K
JIS SUS316L
Hastelloy C-276
Tantalum (Note 2)
Titanium
JIS 63K
ANSI class 150
ANSI class 300
ANSI class 600
DIN PN10/16
DIN PN25/40
DIN PN64
2-inch (50 mm) / JIS S25C
2-inch (50 mm) / JIS SUS304
2-inch (50 mm) / JIS SUS316
3-inch (80 mm) / JIS S25C
3-inch (80 mm) / JIS SUS304
3-inch (80 mm) / JIS SUS316
P1 . . . . . . . . . . JPI class 150
P2 . . . . . . . . . . JPI class 300
P4 . . . . . . . . . . JPI class 600
JIS SCM435
JIS SUS630
-A . . . . . . . . . . . . . . . . . . .
-B . . . . . . . . . . . . . . . . . . .
-C . . . . . . . . . . . . . . . . . . .
-D . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . .
h h . . . . . . . . . . . . .
-9 . . . . . . . . . . . . . .
[Process temp.] [Ambient temp.]
For general use (silicone oil)
For general use (silicone oil)
For high temperature use (silicone oil)
–10 to 250
8
C –10 to 60
8
C
–30 to 180 8 C –15 to 60 8 C
10 to 300
8
C 10 to 60
8
C
For oil-prohibited use (fluorinated oil) –20 to 120
8
C –10 to 60
8
C
For low temperature use (ethylene glycol) –50 to 100
8
C –40 to 60
8
C
Always A
Specify capillary length from 1 to 10 m in h h
. (Example for 2 m: 02)
Horizontal impulse piping type, left side high pressure
0 . . . . . . . . . . . . .
2 . . . . . . . . . . . . .
G1/2 female, one electrical connection
1/2 NPT female, two electrical connections without blind plug
3 . . . . . . . . . . . . . PG 13.5 female, two electrical connections without blind plug
4 . . . . . . . . . . . . .
5 . . . . . . . . . . . . .
M20 female, two electrical connections without blind plug
G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
8 . . . . . . . . . . . . .
9 . . . . . . . . . . . . .
PG 13.5 female, two electrical connections and a blind plug
M20 female, two electrical connections and a blind plug
D . . . . . . . . . .
Digital indicator
E . . . . . . . . . .
N . . . . . . . . . .
Digital indicator with the range setting switch
(None)
A . . . . . . . . .
JIS SECC 2-inch pipe mounting (flat type)
B . . . . . . . . .
JIS SUS304 2-inch pipe mounting (flat type)
N . . . . . . . . .
(None)
/ h
Optional specification
T0904.EPS
Example: EJA438W-DASA1AA-AA02-92NA/ h
Note 1: Refer to GS 1C22T1-E for HART Protocol version.
Note 2: In case of wetted parts material code T(Tantalum), maximum process temperature limits is 200
°
C.
Note 3: Refer to GS 1C22T2-E for Fieldbus communication.
9-3 IM 1C22J1-01E
9. GENERAL SPECIFICATIONS d Model EJA438N
[Style: S2]
Model Suffix Codes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description
Diaphragm sealed differential pressure transmitter
EJA438N
(Extended diaphragm type)
Output Signal
Measurement span
(capsule)
Wetted parts material
-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol) (note 1)
Digital communication (FOUNDATION Fieldbus protocol) (note 2)
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.06 to 3 MPa {0.6 to 30 kgf/cm 2 }
0.46 to 7 MPa {46 to 70 kgf/cm 2 }
[Diaphragm] [Pipe] [Others]
Process flange rating
S . . . . . . . . . . . . . . . . . . . . . . . . . . . .
J1 . . . . . . . . . . . . . . . . . . . . . . . . . .
JIS SUS316L
JIS 10K
JIS SUS316 JIS SUS316
J2 . . . . . . . . . . . . . . . . . . . . . . . . . .
J4 . . . . . . . . . . . . . . . . . . . . . . . . . .
JIS 20K
JIS 40K
A1 . . . . . . . . . . . . . . . . . . . . . . . . . . ANSI class 150
A2 . . . . . . . . . . . . . . . . . . . . . . . . . . ANSI class 300
P1 . . . . . . . . . . . . . . . . . . . . . . . . . . JIP class 150
P2 . . . . . . . . . . . . . . . . . . . . . . . . . . JIP class 300
Diaphragm extension length (X
2
)
Process flange size / material
Cover flange bolts material
D2 . . . . . . . . . . . . . . . . . . . . . . . . . .
D4 . . . . . . . . . . . . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . . . . . . . . . . . .
DIN PN10/16
DIN PN25/40
X
2
= 50 mm
4 . . . . . . . . . . . . . . . . . . . . . . . . .
6 . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . .
X
2
= 100 mm
X
2
= 150 mm
4-inch (100 mm) / JIS S25C
H . . . . . . . . . . . . . . . . . . . . . .
J . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . .
4-inch (100 mm) / JIS SUS304
4-inch (100 mm) / JIS SUS316
3-inch (80 mm) / JIS S25C
E . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . .
3-inch (80 mm) / JIS SUS304
3-inch (80 mm) / JIS SUS316
A . . . . . . . . . . . . . . . . . . . . .
JIS SCM435
B . . . . . . . . . . . . . . . . . . . . .
JIS SUS630
Fill fluid
Capillary length (m)
Installation
Electrical connection
-A . . . . . . . . . . . . . . . . . .
-B . . . . . . . . . . . . . . . . . .
-C . . . . . . . . . . . . . . . . . .
-D . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . .
h h . . . . . . . . . .
-9 . . . . . . . . . . . .
0 . . . . . . . . . . .
2 . . . . . . . . . . .
3 . . . . . . . . . . .
[Process [Ambient temperature] temperature]
For general use (silicone oil)
For general use (silicone oil)
For high temperature use (silicone oil)
–10 to 250
8
C –10 to 60
8
C
–30 to 180
8
C –15 to 60
8
C
10 to 300
8
C 10 to 60
8
C
For oil-prohibited use (fluorinated oil) –20 to 120
8
C –10 to 60
8
C
For low temperature use (ethylene glycol) –50 to 100
8
C –40 to 60
8
C
Always B
Specify capillary length from 1 to 10 m in h h
. (Example for 2 m: 02)
Horizontal impulse piping type, left side high pressure
G1/2 female, one electrical connection
1/2 NPT female, two electrical connections without blind plug
PG 13.5 female, two electrical connections without blind plug
4 . . . . . . . . . . .
5 . . . . . . . . . . .
7 . . . . . . . . . . .
8 . . . . . . . . . . .
9 . . . . . . . . . . .
M20 female, two electrical connections without blind plug
G1/2 female, two electrical connections and a blind plug
1/2 NPT female, two electrical connections and a blind plug
PG 13.5 female, two electrical connections and a blind plug
M20 female, two electrical connections and a blind plug
Integral indicator
Mounting bracket
Optional codes
D . . . . . . . . .
E . . . . . . . . .
N . . . . . . . . .
Digital indicator
Digital indicator with the range setting switch
(None)
A . . . . . . . . JIS SECC
B . . . . . . . .
JIS SUS304
N . . . . . . . . (None)
/ h
Optional specification
2-inch pipe mounting (flat type)
2-inch pipe mounting (flat type)
T0905.EPS
Example: EJA438N-DASA12GA-AB02-92NA/ h
Note 1: Refer to GS 1C22T1-E for HART Protocol version.
Note 2: Refer to GS 1C22T2-E for Fieldbus communication.
9-4 IM 1C22J1-01E
9. GENERAL SPECIFICATIONS
9.3
Optional Specifications
Item
Factory Mutual (FM)
CENELEC (KEMA)
Canadian Standards
Association (CSA)
Standards Association of
Australia (SAA)
Japanese Industrial
Standards (JIS)
Attached flameproof
Packing adapter
Description
FM Explosionproof Approval
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors ( NEMA 4X )
Temperature class: T6
Amb. Temp.:–40 to 60
8
C (–40 to 140
8
F)
Electrical connection: 1/2 NPT female
FM Intrinsically safe Approval
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60
8
C (–40 to 140
8
F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 m H
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 m H
Electrical connection: 1/2 NPT female
Combined FF1and FS1
Electrical connection: 1/2 NPT female
CENELEC (KEMA) Flameproof Approval
EExd IIC T4, T5, T6, Amb. Temp.: –40 to 80 8 C (–40 to 176 8 F)
Max. process Temp.: T4; 120
8
C (248
8
F), T5; 100
8
C (212
8
F), T6; 85
8
C (185
8
F)
Electrical connection: 1/2 NPT female, Pg 13.5 female and M20 female
CENELEC (KEMA) Intrinsically safe Approval
EEx ia IIC T4, Amb. Temp.: –40 to 60
8
C(–40 to 140
8
F)
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 m
H
Electrical connection: 1/2 NPT female, Pg 13.5 female and M20 female
Combined KF1, KS1 and Type N Approval
KEMA Type N Approval
Ex nA IIC T4, Amb. Temp.: –40 to 60
8
C(–40 to 140
8
F)
U=30 V, I=165 mA
Electrical connection: 1/2 NPT female, Pg 13.5 female and M20 female
CSA Explosionproof Approval
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 ‘SEALS NOT REQUIRED’ , Temp. Class : T4, T5, T6 Encl Type 4x
Max. Process Temp.: T4; 120
8
C (248
8
F), T5; 100
8
C (212
8
F), T6; 85
8
C (185
8
F)
Amb. Temp.:–40 to 80
8
C (–40 to 176
8
F)
Electrical connection: 1/2 NPT female
CSA Intrinsically safe Approval
Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60
8
C (–40 to 140
8
F)
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 m
H
Electrical connection: 1/2 NPT female
Combined CF1 and CS1
Electrical connection: 1/2 NPT female
SAA Flameproof, Intrinsically safe and Non-sparking Approval
Ex d IIC T4/T5/T6, IP67 class I, Zone 1, Amb. Temp. : –40 to 80 8 C (–40 to 176 8 F)
Max. Process Temp.: T4; 120
8
C (248
8
F), T5; 100
8
C (212
8
F), T6; 85
8
C (185
8
F)
Ex ia IIC T4, IP67 class I, Zone 0
Ex n IIC T4, IP67 class I, Zone 2
Ui=30 V DC, Ii=165 mA DC, Wi=0.9 W, Amb. Temp.: –40 to 60 8 C (–40 to 140 8 F)
Electrical connection: 1/2 NPT female, Pg 13.5 female and M20 female
JIS Flameproof Approval, Ex do IIC T4X
Amb. Temp. – 20 to 60 8 C, Process Temp. –20 to 120 8 C
JIS Intrinsically safe Approval, Ex ia IIC T4
Amb. Temp. – 20 to 60
8
C, Process Temp. –20 to 120
8
C
Electrical connection: G1/2 female
Applicable cable O.D.: 8 to 12 mm
1 pc.
2 pcs.
Code
FF1
FS1
FU1
KF1
KS1
KU1
CF1
CS1
CU1
SU1
JF3
JS1
G11
G12
T0906.EPS
9-5 IM 1C22J1-01E
9. GENERAL SPECIFICATIONS
Painting
Item
Color change
Coating change
Amplifier cover only
Epoxy resin-baked coating
Description Code
P h
X1
Lightning protector
Oil-prohibited use
Oil-prohibited use with dehydrating treatment
Transmitter power supply voltage: 10.5 to 32 V DC (9 to 32 V DC for Fieldbus communication type) Allowable current: Max. 6000 A (1x40
µ s),
Repeating 1000 A (1x40
µ s) 100 times
Degrease cleansing treatment
Degrease cleansing and dehydrating treatment
A
K1
K5
P calibration (psi unit) D1
Calibration units bar calibration (bar unit)
M calibration (kgf/cm 2 unit)
(See Table for Span and
Range Limits)
D3
D4
Sealing treatment to JIS
SUS630 nuts
No serration (Note 1)
Sealant (liquided silicone rubber) is coated on surfaces of JIS SUS630 nuts used for cover flange mounting.
No serration work on the flange gasket surface (for ANSI flange only)
Y
Q
Teflon film (Note 2)
Operating temperature correction (Note 3)
With FEP film and fluorinated oil
Working range: 20 to 150
°
C, 0 to 2 MPa {0 to 20 kgf/cm 2 } (Not usable under vacuum)
Adjusting range: 80 to 300
°
C
T
R
Capillary without PVC sheaths
Fast response
When ambient temperature exceeds 100
°
C, or use of PVC is prohibited V
Update time: 0.125 sec or less, see GS for the response time F1
Failure alarm down-scale
(Note 4)
Stainless steel amplifier housing (Note 5)
Gold-plate
Mill Certificate
Pressure test/Leak test
Certificate
Output status at CPU failure and hardware error: –5%, 3.2 mA DC or less.
When combining with Optional code F1, output signal is –2.5%, 3.6 mA DC or less.
Amplifier housing material: JIS SCS14A stainless steel (equivalent to JIS SUS316 cast stainless steel or ASTM CF-8M)
Gold-plated diaphragm
Process flange, Block
For model EJA438W
For model EJA438N
Process flange, Block, Pipe, Base
C1
E1
A1
M05
M06
( Flange rating )
JIS 10K
( Test Pressure )
2 MPa {20 kgf/cm 2 }
3 MPa {30 kgf/cm 2 }
(Applicable model)
T41
JIS 20K EJA438W/EJA438N T42
JIS 40K
JIS 63K
ANSI/JPI Class 150
3 MPa {30 kgf/cm 2 }
3 MPa {30 kgf/cm 2 }
3 MPa {29.8 kgf/cm 2 }
3 MPa {30 kgf/cm 2 }
EJA438W
EJA438W/EJA438N
T43
T45
T46
ANSI/JPI Class 300 T47
ANSI/JPI Class 600
JIS 10K
JIS 20K
3 MPa {30 kgf/cm 2 }
2 MPa {20 kgf/cm 2 }
5 MPa {50 kgf/cm 2 }
10 MPa {100 kgf/cm 2 }
EJA438W
EJA438W/EJA438N
Nitrogen(N
2
) Gas
Retention time:
10 minutes
T49
T31
T32
JIS 40K EJA438W T33
JIS 40K
JIS 63K
7 MPa {70 kgf/cm 2 }
14 MPa {140 kgf/cm 2 }
3 MPa {29.8 kgf/cm 2 }
EJA438N
EJA438W
T34
T35
ANSI/JPI Class 150 EJA438W/EJA438N T36
ANSI/JPI Class 300 7.7 MPa {77 kgf/cm 2 } EJA438W T37
ANSI/JPI Class 300 7 MPa {70 kgf/cm 2 } EJA438N T38
ANSI/JPI Class 600 14 MPa {140 kgf/cm 2 } EJA438W T39
T0907.EPS
Note 1: This item cannot be applied to Model EJA438W wetted parts material code H (Hastelloy C), T
(Tantalum), or U (Titanium). (In case for code H, T or U, serration work on the flange gasket surface is not possible)
Note 2: Teflon film can only be specified for model EJA438W.
Note 3: Specify the process operating temperature for zero correction.
Example: Zero correction by process temperature 90
°
C.
Note 4: The hardware error indicates faulty amplifier or capsule. Standard output status (without /C1) is up-scale of 110%, 21.6 mA DC or more.
Note 5: Applicable only for electrical connection code ‘2’, ‘3’ or ‘4’. Not applicable for optional code P h and X1. Not applicable for optional code JF1 and JS1.
9-6 IM 1C22J1-01E
9. GENERAL SPECIFICATIONS
9.4
Dimensions
d Model EJA438W [Style: S2]
ød* 1
25 (0.98) f t
34
(1.34)
Unit: mm(approx. inch) n-øh
External indicator conduit connection
(Optional)
140(5.51)
94(3.70)
Conduit connection
Internal indicator
(Optional)
110 (4.33)
12
(0.47)
Wetted parts material code U (Titanium)
Terminal side
Ground terminal
Zero adjustment
92
(3.62)
Clamps (Only for JIS
Flameproof type)
2-inch pipe
(O.D. 60.5mm)
Mounting bracket
(Flat-type, Optional)
*1: Indicates inside diameter of gasket contact surface.
Process flange size: 3-inch(80mm)
Flange Rating
JIS 10K
JIS 20K
JIS 40K
JIS 63K
ANSI Class 150
ANSI Class 300
ANSI Class 600
JPI Class 150
JPI Class 300
JPI Class 600
DIN PN 10/16
DIN PN 25/40
DIN PN 64
øD
185(7.28)
200(7.87)
210(8.27)
230(9.06)
190.5(7.50)
209.6(8.25)
209.6(8.25)
190(7.48)
210(8.27)
210(8.27)
200(7.78)
200(7.78)
215(8.46)
øC
150(5.91)
160(6.30)
170(6.69)
185(7.28)
152.4(6)
168.1(6.62)
168.1(6.62)
152.4(6)
168.1(6.62)
168.1(6.62)
160(6.30)
160(6.30)
170(6.69)
øg
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
ød
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
90(3.54)
Process flange size: 2-inch(50 mm) t
18(0.71)
22(0.87)
32(1.26)
40(1.57)
0
0
0 f *
0
23.9(0.94)
28.5(1.12)
31.8(1.25)
24(0.94)
1.6(0.06)
1.6(0.06)
6.4(0.25)
1.6(0.06)
28.5(1.12)
38.4(1.51)
20(0.79)
1.6(0.06)
6.4(0.25)
0
24(0.94)
28(1.10)
0
0
Flange Rating
JIS 10K
JIS 20K
JIS 40K
JIS 63K
ANSI Class 150
ANSI Class 300
ANSI Class 600
JPI Class 150
JPI Class 300
JPI Class 600
DIN PN 10/16
DIN PN 25/40
DIN PN 64
øD
155(6.10)
155(6.10)
165(6.50)
185(7.28)
152.4(6.00)
165.1(6.50)
165.1(6.50)
152(6.10)
165(6.50)
165(6.50)
165(6.50)
165(6.50)
180(7.09)
øC
120(4.72)
120(4.72)
130(5.12)
145(5.12)
120.7(4.75)
127.0(5.00)
127.0(5.00)
120.6(4.75)
127.0(5.00)
127.0(5.00)
125(4.92)
125(4.92)
135(5.31)
øg
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
100(3.94)
ød
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
61(2.40)
* In case where process flange material is JIS S25C, value of f is 0.
t
16(0.63)
18(0.71) f *
0
0
26(1.02)
34(1.34)
19.1(0.75)
22.4(0.88)
0
0
1.6(0.06)
1.6(0.06)
31.8(1.25)
19.5(0.77)
6.4(0.25)
1.6(0.06)
22.5(0.89) 1.6(0.06)
31.9(1.26)
18(0.71)
20(0.78)
26(1.02)
6.4(0.25)
0
0
0
4
4
8
4
8
4
8
4
8
8
8 n
4
8
8
8
8
8
8
8
4
4
8
8
8
8 n
8
Open to atmosphere
(ø5mm)
øh
19(0.75)
19(0.75)
19(0.75)
23(0.91)
19.1(0.75)
19.1(0.75)
19.1(0.75)
19(0.75)
19(0.75)
19(0.75)
18(0.71)
18(0.71)
22(0.87)
øh
19(0.75)
23(0.91)
23(0.91)
25(0.98)
19.1(0.75)
22.4(0.88)
22.4(0.88)
19(0.75)
22(0.87)
22(0.87)
18(0.71)
18(0.71)
22(0.87)
9-7
F0902.EPS
IM 1C22J1-01E
d Model EJA438N [Style: S2]
9. GENERAL SPECIFICATIONS
Unit : mm (approx. inch)
øD
øC
øg
øA
External indicator conduit connection
(Optional)
140(5.51)
94(3.70)
120
(4.72)
Conduit connection
Internal indicator
(Optional)
ø30
(1.18) n-øh
110 (4.33)
12
(0.47)
Terminal side
Ground terminal
Zero adjustment
Open to atmosphere
(ø5mm)
92
(3.62)
Clamps (Only for JIS
Flameproof type)
2-inch pipe
(O.D. 60.5mm)
Mounting bracket
(Flat-type, Optional)
Diaphramg extension length code
2 : X
2
= 50 mm (2 inch)
4 : X
2
= 100 mm (4 inch)
6 : X
2
= 150 mm (6 inch)
Process flange size : 4 inch (100 mm)
Flange Rating
JIS 10K
JIS 20K
JIS 40K
ANSI Class 150
ANSI Class 300
JPI Class 150
JPI Class 300
DIN PN 10/16
DIN PN 25/40
øD
210(8.72)
225(8.86)
250(9.84)
228.6(9.00)
254(10.00)
229(9.02)
254(10.00)
220(8.66)
235(9.25)
øC
175(6.89)
185(7.28)
205(8.07)
190.5(7.50)
200.2(7.88)
190.5(7.50)
200.2(7.88)
180(7.09)
190(7.48)
øg
155(6.10)
155(6.10)
155(6.10)
155(6.10)
155(6.10)
155(6.10)
155(6.10)
155(6.10)
155(6.10)
øA
96(3.78)
96(3.78)
96(3.78)
96(3.78)
96(3.78)
96(3.78)
96(3.78)
96(3.78)
96(3.78) t
18(0.71)
24(0.94)
36(1.42) f *
0
0
0
23.9(0.94) 1.6(0.06)
31.8(1.25)
24(0.94)
32(1.26)
20(0.79)
24(0.94)
1.6(0.06)
1.6(0.06)
1.6(0.06)
0
0 n
8
8
8
8
8
8
8
8
8
øh
19(0.75)
23(0.91)
25(0.98)
19.1(0.75)
22.4(0.88)
19(0.75)
22(0.87)
18(0.71)
22(0.87)
Process flange size : 3 inch (80 mm)
Flange Rating
JIS 10K
JIS 20K
JIS 40K
ANSI Class 150
ANSI Class 300
JPI Class 150
JPI Class 300
DIN PN 10/16
DIN PN 25/40
øD
185(7.28)
200(7.87)
210(8.27)
190.5(7.50)
209.6(8.25)
190(7.48)
210(8.27)
200(7.78)
200(7.78)
øC
150(5.91)
160(6.30)
170(6.69)
152.4(6)
168.1(6.62)
152.4(6)
168.1(6.62)
160(6.30)
160(6.30)
øg
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
130(5.12)
øA
71(2.80)
71(2.80)
71(2.80)
71(2.80)
71(2.80)
71(2.80)
71(2.80)
71(2.80)
71(2.80)
* In case where process flange material is JIS S25C, value of f is 0.
t
18(0.71)
22(0.87)
32(1.26)
23.9(0.94)
28.5(1.12)
24(0.94) f *
0
0
0
1.6(0.06)
1.6(0.06)
1.6(0.06)
28.5(1.12) 1.6(0.06)
20(0.79)
24(0.94)
0
0
8
4
8
4
8
8
8 n
8
8
øh
19(0.75)
23(0.91)
23(0.91)
19.1(0.75)
22.4(0.88)
19(0.75)
22(0.87)
18(0.71)
18(0.71)
F0903.EPS
9-8 IM 1C22J1-01E
Customer
Maintenance
Parts List
DPharp EJA Series
Transmitter Section
5
2
4
11
A
10
3
13
12
1
2
2
1
14
A
7-1
8 9
6
5
7-2
Item
1
2
3
4
5
6
7-1
7-2
8
9
10
11
12
13
14
Part No.
F9342AF
F9342AM
F9342BF
Y9406ZU
Y9612YU
Below
F9340NW
F9340NX
G9330DP
G9612EB
Bellow
F9341FM
F9341FJ
Below
F9342BL
F9342BM
F9342MK
F9300PB
Bellow
F9341RA
F9341RJ
F9341JP
Below
F9341AA
F9341AC
F9341AE
F9341AH
F9341AJ
F9341AR
F9341KA
Bellow
F9300AG
F9303JU
F9341KL
Below
F9342BB
F9342BH
F9342BJ
2
2
1
1
1
Qty
2
2
1
1
4
1
1
2
2
Description
Cover
Cast-aluminum alloy
SCS14A stainless steel
O-ring
Case Assembly
Cast-aluminum alloy for G1/2
Cast-aluminum alloy for G1/2 (two electrical connections)
Cast-aluminum alloy for 1/2 NPT (two electrical connections)
Cast-aluminum alloy for M20 (two electrical connections)
Cast-aluminum alloy for Pg13.5 (two electrical connections)
SCS14A stainless steel for 1/2 NPT (two electrical connections)
Name Plate
Screw
For cast-aluminum alloy case assembly
For SCS14A stainless steel case assembly
Tag Plate
CPU Assembly
For BRAIN protocol version (Except JIS Intrinsically safe type)
For HART protocol version (Except JIS Intrinsically safe type)
For BRAIN protocol version JIS Intrinsically safe type (Optional code /JS1)
For BRAIN protocol version (Optional code /F1)
For HART protocol version with write protection switch (Optional code /F1)
For FOUNDATION Fieldbus protocol
Cap Screw
Screw
Plug
For Pg13.5
For M20
For G1/2
For 1/2 NPT
Cover Assembly
Cast-aluminum alloy
SCS14A stainless steel
LCD Board Assembly
Without range-setting switch
With range-setting switch
Mounting Screw
Label
For integral indicator
All Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation.
CMPL 1C22A1-02E
6th Edition: Feb. 2000(YK)
Yokogawa Electric Corporation
Blank Page
2
Subject to change without notice. Printed in Japan.
CMPL 1C22A1-01E
Customer
Maintenance
Parts List
Models EJA438W and EJA438N
Diaphragm Sealed
Gauge Pressure Transmitter
(Pressure-detector Section)
Qty
Item Part No.
5
6
3
4
1
2
7
8
9
Description
F9300AJ
—
—
Below
Y9625YU
Y9630YU
Y9640YU
Y9635YU
1
1
2
2
Y9612HU
Below
F9270AW
F9300TA
D0117XL-A
1
4
1
1 1
1
1
1
1
Below
F9270AX
F9300TE
Below
F9270AY
F9273CZ
4 4
O-Ring
Flange
Bolt
Bolt
See Table 1
For JIS 10K
For JIS 20K, ANSI Class 150 and JPI Class 150
For JIS 40K, ANSI Class 300 and JPI Class 300
(for Flange Size 100 mm, 4 inch)
For JIS 40K, ANSI Class 300 and JPI Class 300
(for Flange Size 80 mm, 3 inch)
Screw, M6 x 12
Bracket Assembly
SECC Carbon Steel
SUS304 Stainless Steel
U-Bolt / Nut Assembly, SUS304 Stainless Steel
Bracket
SECC Carbon Steel
Bolt
SUS304 Stainless Steel
S15C Carbon Steel
SUS XM7 Stainless Steel
All Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation.
Yokogawa Electric Corporation
CMPL 1C22J3-01E
3rd Edition: Oct. 1999(YK)
Table 1. Flange and Bolt Parts Number
Flange Rating
50 mm JIS 10K
50 mm JIS 20K
50 mm JIS 40K
50 mm JIS 63K
2 inch ANSI Class 150
2 inch ANSI Class 300
2 inch ANSI Class 600
2 inch JPI Class 150
2 inch JPI Class 300
2 inch JPI Class 600
80 mm JIS 10K
80 mm JIS 20K
80 mm JIS 40K
80 mm JIS 63K
3 inch ANSI Class 150
3 inch ANSI Class 300
3 inch ANSI Class 600
3 inch JPI Class 150
3 inch JPI Class 300
3 inch JPI Class 600
S25C
Carbon Steel
Flange Material (Item 2)
SUS304
Stainless Steel
SUS316
Stainless Steel
F9351KP
F9351KQ
F9351KR
F9351KS
F9351KT
F9351KU
F9351KV
F9351KW
F9351KX
F9351KY
F9351KA
F9351KB
F9351KC
F9351KD
F9351KE
F9351KF
F9351KG
F9351KH
F9351KJ
F9351KK
F9351GP
F9351GQ
F9351GR
F9351GS
F9351GT
F9351GU
F9351GV
F9351GW
F9351GX
F9351GY
F9351GA
F9351GB
F9351GC
F9351GD
F9351GE
F9351GF
F9351GG
F9351GH
F9351GJ
F9351GK
F9351WA
F9351WB
F9351WC
F9351YE
F9351WG
F9351WH
F9351WJ
F9351WN
F9351WP
F9351WQ
F9351WD
F9351WE
F9351WF
F9351YF
F9351WK
F9351WL
F9351WM
F9351WR
F9351WS
F9351WT
Bolt (Item 3)
Y9520ZU
Y9525ZU
Y9530ZU
Y9540ZU
Y9525ZU
Y9530ZU
F9347VX
Y9525ZU
Y9530ZU
F9347VX
Y9525ZU
Y9530ZU
Y9540ZU
Y9545ZU
Y9530ZU
F9347VX
Y9540ZU
Y9530ZU
F9347VX
Y9540ZU
2
Oct. 1999
Subject to change without notice. Printed in Japan.
CMPL 1C22J3-01E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS INTRINSICALLY SAFE EQUIPMENT
INSTALLATION AND OPERATING PRECAUTIONS FOR
JIS INTRINSICALLY SAFE EQUIPMENT
Apparatus Certified Under Technical Criteria (IEC-compatible Standards) and from “RECOMMENDED PRACTICES for Explosion-Protected Electrical Installations in General Industries,” published in 1979
1. General
The following describes precautions on electrical apparatus of intrinsically safe construction (hereinafter referred to as intrinsically safe apparatus).
Following the Labor Safety and Health Laws of Japan, an intrinsically safe apparatus must undergo type tests in order to be certified by the Technical Institute of Industrial Safety,
Inc. These tests are required to satisfy either the technical criteria for electrical machinery and equipment in compliance with explosionproof standards involving inflammable gases or vapors and for machinery and equipment having explosionproof performance (standards notification no. 556 from the Japanese Ministry of Labor) (hereinafter referred to as technical criteria), in conformity with IEC Standards, or the “Recommended Practice for Explosion-Protected
Electrical Installations in General Industries,” published in
1979. Such a certified apparatus can be used in hazardous locations where inflammable gases or vapors may be present.
Certified apparatus includes a certification label and an equipment nameplate with the specifications necessary for explosion requirements as well as precautions on explosion protection. Please confirm these precautionary items and use them to meet specification requirements.
For electrical wiring and maintenance servicing, please refer to “Internal Wiring Rules” in the Electrical Installation
Technical Standards as well as “USER’S GUIDELINES for
Electrical Installations for Explosive Gas Atmospheres in
General Industry,” published in 1994.
To meet intrinsically safe requirements, equipment that can be termed an “intrinsically safe apparatus” must:
(1) be certified by the Technical Institute of Industrial
Safety, Inc. in accordance with the Labor Safety and
Health Laws of Japan and have the appropriate mark of certification labeled on its case, and
(2) be used in compliance with the specifications marked on its certification label, equipment nameplate and precautionary information furnished.
Note: Intrinsically safe apparatus satisfy their performance under specific conditions. They are not always absolutely safe under every operational and environmental condition. In other words, they are not safe products involved with factors such as chemical reactions, geographical changes or the like other than affected by electric energy from the equipment itself.
2. Electrical Apparatus of Intrinsic
Safety Type of Explosion-
Protected Construction
The intrinsic safety type of explosion-protected construction is a method of protection applicable to a circuit or part of a circuit in which, under prescribed test conditions, no spark or thermal effect, whether produced normally or accidentally, is capable of causing a prescribed explosive gas to ignite. In other words, electrical apparatus of this construction is intended to suppress electrical energy thereby preventing ignition of a given explosive gas atmosphere even though spark or high thermal effect occurs in the electric circuitry.
Intrinsically safe electrical apparatus generally comprise intrinsically safe apparatus installed in a hazardous location and a safety barrier (associated apparatus), installed in a nonhazardous location, aimed at preventing electrical energy from flowing into the electric circuitry of intrinsically safe apparatus.
However, battery-operated, portable intrinsically safe apparatus or the like may be used alone.
3. Terminology
(1) Intrinsically safe apparatus: Electrical apparatus in which all the circuits are intrinsically safe circuits.
(2) Associated apparatus: Electrical apparatus in which there are both intrinsically safe circuits and non-intrinsically safe circuits that can affect the safety of intrinsically safe circuits.
(3) Safety barrier: A specific type of associated apparatus, which consists mainly of safety barrier elements, and serves to limit the flow of excessive electrical energy, which is capable of causing ignition of a given explosive gas or vapour of a non-intrinsically safe circuit into concerned intrinsically safe circuits.
(4) Apparatus of category “ia”: Intrinsically safe electrical apparatus and associated apparatus which are incapable of causing ignition of a given explosive gas or vapour with the appropriate safety factors such as:
1 EX-A03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS INTRINSICALLY SAFE EQUIPMENT
— when up to two countable faults are applied and, in addition,
— when non-countable faults produce an onerous condition.
(5) Apparatus of category “ib”: Intrinsically safe electrical apparatus and associated apparatus which are incapable of causing ignition of a given explosive gas or vapour, with the appropriate safety factors such as:
— when up to one countable fault is applied and, in addition,
— when non-countable faults produce an onerous condition.
(6) Safety rating: A rating to be designated to intrinsically safe apparatus as well as associated apparatus and is the maximum rating allowable for maintaining intrinsic safety of concerned intrinsically safe circuits.
(2) For pressure transmitters, pH transmitters, temperature detectors and the like, safety barriers that can be combined are already specified. Other safety barriers cannot be used.
Note 2: Testing Intrinsically Safe System
An assembly (as a system) in which intrinsically safe apparatus and safety barriers are combined is assessed to ensure that its safety requirements are satisfied. A tested and certified system incorporates a certification number
(intrinsically safe apparatus and safety barriers have the same certification number).
Note 3: Impossible Combinations of Apparatus Certified Under
Different Standards
Intrinsically safe apparatus certified under technical criteria and safety barriers certified under the “Recommended
Practice for Explosion-Protected Electrical Installations in
General Industries” (1979) and vice versa cannot be combined even if their combination requirements are satisfied.
4. Caution on Combining Intrinsically Safe Apparatus and
Safety Barriers
(1) A combination of certified intrinsically safe apparatus and safety barriers needs to satisfy combination requirements. If intrinsically safe apparatus specify safety barriers for combination, safety barriers other than specified cannot be used (see Note 1 for more details).
(2) Certified intrinsically safe systems specify specific safety barriers in combination with intrinsically safe apparatus.
So safety barriers other than specified cannot be used
(see Note 2 for more details).
(3) Other than limitations of combining intrinsically safe apparatus and safety barriers as given in (1) and (2) above, two or more pieces of apparatus certified under different standards cannot be combined with each other
(see Note 3 for more details). In addition, bear in mind that classifications of explosion protection such as “IIA,”
“IIB” and “IIC” and category “ia” and “ib” limit a combination of intrinsically safe apparatus and safety barriers.
For more details, see the “Type Certificate Guide for
Explosion-Protected Constructionfor Electrical
Machinery and Equipment,” issued by the Japanese
Ministry of Labour, the Research Institute of Industrial
Safety.
Note 1: Testing Apparatus
Intrinsically safe apparatus and safety barriers are assessed individually to ensure that their safety requirements are satisfied. Tested and certified intrinsically safe apparatus and safety barriers incorporate individual certification numbers.
A combination of intrinsically safe apparatus and safety barriers involves the following two limitations:
(1) A safety barrier which meets the combination requirements by referring to its safety rating and combination parameters shall be selected.
5. Installation of Intrinsically Safe
Apparatus and Safety Barriers
(1) Classification of installation location
Intrinsically safe apparatus may be installed, depending upon applicable gases, in a hazardous area in Zone 0, 1 or 2 (Note
4 below), where the specified gases are present. However, note that apparatus certified under Technical Criteria, in category “ib” shall be installed only in Zone 1 or 2. Safety barriers (associated apparatus) that are combined with these intrinsically safe apparatus shall be installed only in a nonhazardous area. In cases where safety barriers are installed in a hazardous area, they shall be enclosed, for example, in a flameproof enclosure.
Note 4: Hazardous areas are classified in zones based upon the frequency of the appearance and the duration of an explosive gas atmosphere as follows:
Zone 0: An area in which an explosive gas atmosphere is present continuously or is present for long periods.
Zone 1: An area in which an explosive gas atmosphere is likely to occur in normal operation.
Zone 2: An area in which an explosive gas atmosphere is not likely to occur in normal operation and if it does occur it will exist for a short period only.
(2) Ambient temperature limits for intrinsically safe apparatus
Intrinsically safe apparatus shall be installed in a location where the ambient temperature ranges from –20
°
to +40
°
C
(for those certified under Technical Criteria) or –10
°
to
+40
°
C (for those certified under the “Recommended Practice for Explosion-Protected Electrical Installations in General
Industries” (1979). However, some field-mounted
2 EX-A03E
intrinsically safe apparatus may be used at an ambient temperature up to 60
°
C. So, specifications should be checked before installing intrinsically safe apparatus.
If the intrinsically safe apparatus are exposed to direct sunshine or radiant heat from plant facilities, appropriate thermal protection measures shall be taken.
6. Wiring for Intrinsically Safe
Circuits
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS INTRINSICALLY SAFE EQUIPMENT
In intrinsically safe construction, safety shall be maintained as an intrinsically safe system involving intrinsically safe apparatus and safety barriers connected thereto, and electrical wiring (through intrinsically safe circuits) interconnected between them. In other words, even when safety requirements are maintained individually by intrinsically safe apparatus and safety barriers, they shall not be affected by electrical or magnetic energy caused by electrical wiring.
To make electrical wiring for intrinsically safe circuits, you must:
(a) refer to the equipment configuration diagram and make electrical wiring properly;
(b) prevent intrinsically safe wiring from being contacted with non-intrinsically safe wiring, and separate the intrinsically safe circuit from other electrical circuits;
(c) prevent intrinsically safe wiring from being electrostatically and magnetically affected by nonintrinsically safe wiring;
(d) reduce wiring inductance and capacitance produced between the intrinsically safe apparatus and safety barrier where possible, and use a shorter cable between the intrinsically safe apparatus and safety barrier than specified if the maximum permissible inductance of the cable is specified as operating conditions;
(e) conform to conditions of installation such as wiring method, earthing or the like, if any; and
(f) protect the outer sheath of cables from damage with appropriate measures.
Installations for Explosive Gas Atmospheres in General
Industry” issued in 1994 by the Japanese Ministry of Labour, the Research Institute of Industrial Safety.
(1) Requirements for maintenance personnel
Maintenance and inspection of intrinsically safe apparatus and safety barriers shall be conducted by maintenance personnel skilled in intrinsically safe construction and installation of electrical devices as well as capable of applying associated rules.
(2) Maintenance and Inspection
(a) Visual inspection
Visually inspect the external connections of intrinsically safe apparatus and safety barriers, and cables for damage or corrosion as well as other mechanical and structural defects.
(b) Adjustments
Zero, span and sensitivity adjustments shall be made with applicable adjusting potentiometers and mechanical adjustment screws.
These maintenance adjustments shall be made in a nonhazardous location.
CAUTION
If intrinsically safe apparatus and safety barriers require maintenance service and checking, a gas detector shall be used to ensure that there is no explosive gas in the location (maintenance servicing shall be conducted in a nonhazardous location).
(3) Repair
Intrinsically safe apparatus and safety barriers shall be repaired by manufacturers.
(4) Prohibition of modifications and specification changes
Do not attempt to make modifications or change specifications which may affect safety.
7. Maintenance and Inspection of
Intrinsically Safe Apparatus and Safety Barriers
Maintenance and inspection of intrinsically safe apparatus and safety barriers shall be limited to within the instructions described in applicable instruction manuals. If other than this is required, contact the manufacturers. For more information, refer to the “USER’S GUIDELINES for Electrical
3 EX-A03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
INSTALLATION AND OPERATING PRECAUTIONS FOR
JIS FLAMEPROOF EQUIPMENT
Apparatus Certified Under Technical Criteria
(IEC-compatible Standards)
1. General
The following describes precautions on electrical apparatus of flameproof construction (hereinafter referred to as flameproof apparatus) in explosion-protected apparatus.
Following the Labour Safety and Health Laws of Japan, flameproof apparatus is subjected to type tests to meet either the technical criteria for explosionproof electrical machinery and equipment (standards notification no. 556 from the
Japanese Ministry of Labour) (hereinafter referred to as technical criteria), in conformity with the IEC Standards, or the “Recommended Practice for Explosion-Protected
Electrical Installations in General Industries,” published in
1979. These certified apparatus can be used in hazardous locations where explosive or inflammable gases or vapours may be present.
Certified apparatus includes a certification label and an equipment nameplate with the specifications necessary for explosion requirements as well as precautions on explosion protection. Please confirm these precautionary items and use them to meet specification requirements.
For electrical wiring and maintenance servicing, please refer to “Internal Wiring Rules” in the Electrical Installation
Technical Standards as well as “USER’S GUIDELINES for
Electrical Installations for Explosive Gas Atmospheres in
General Industry,” published in 1994.
To meet flameproof requirements, equipment that can be termed “flameproof” must:
(1) Be certified by a Japanese public authority in accordance with the Labour Safety and Health Laws of Japan and have a certification label in an appropriate location on its case, and
(2) Be used in compliance with the specifications marked on its certification label, equipment nameplate and precautionary information furnished.
2. Electrical Apparatus of Flameproof Type of Explosion-
Protected Construction
Electrical apparatus which is of flameproof construction is subjected to a type test and certified by the Japanese Ministry of Labour aiming at preventing explosion caused by electrical apparatus in a factory or any location where inflammable gases or vapours may be present. The flameproof construction is of completely enclosed type and its enclosure shall endure explosive pressures in cases where explosive gases or vapours entering the enclosure cause explosion. In addition, the enclosure construction shall be such that flame caused by explosion does not ignite gases or vapours outside the enclosure.
In this manual, the word "flameproof" is applied to the flameproof equipment combined with the types of protection
"e", "o", "i", and "d" as well as flameproof equipment.
3. Terminology
(1) Enclosure
An outer shell of an electrical apparatus, which encloses live parts and thus is needed to configure explosion-protected construction.
(2) Shroud
A component part which is so designed that the fastening of joint surfaces cannot be loosened unless a special tool is used.
(3) Enclosure internal volume
This is indicated by:— the total internal volume of the flameproof enclosure minus the volume of the internal components essential to equipment functions.
(4) Path length of joint surface
On a joint surface, the length of the shortest path through which flame flows from the inside to outside of the flameproof enclosure. This definition cannot be applied to threaded joints.
(5) Gaps between joint surfaces
The physical distance between two mating surfaces, or differences in diameters if the mating surfaces are cylindrical.
Note: The permissible sizes of gaps between joint surfaces, the path length of a joint surface and the number of joint threads are determined by such factors as the enclosure’s internal volume, joint and mating surface construction, and the explosion classification of the specified gases and vapours.
1 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
4. Installation of Flameproof
Apparatus
(1) Installation Area
Flameproof apparatus may be installed, in accordance with applicable gases, in a hazardous area in Zone 1 or 2, where the specified gases are present. Those apparatus shall not be installed in a hazardous area in Zone 0.
Note: Hazardous areas are classified in zones based upon the frequency of the appearance and the duration of an explosive gas atmosphere as follows:
Zone 0: An area in which an explosive gas atmosphere is present continuously or is present for long periods.
Zone 1: An area in which an explosive gas atmosphere is likely to occur in normal operation.
Zone 2: An area in which an explosive gas atmosphere is not likely to occur in normal operation and if it does occur it will exist for a short period only.
(2) Environmental Conditions
The standard environmental condition for the installation of flameproof apparatus is limited to an ambient temperature range from –20
°
C to +40
°
C (for products certified under
Technical Criteria). However, some field-mounted instruments may be certified at an ambient temperature up to
+60
°
C as indicated on the instrument nameplates. If the flameproof apparatus are exposed to direct sunshine or radiant heat from plant facilities, appropriate thermal protection measures shall be taken.
5. External Wiring for Flameproof
Apparatus
Flameproof apparatus require cable wiring or flameproof metal conduits for their electrical connections. For cable wiring, cable glands (cable entry devices for flameproof type) to wiring connections shall be attached. For metal conduits, attach sealing fittings as close to wiring connections as possible and completely seal the apparatus. All non-live metal parts such as the enclosure shall be securely grounded.
For details, see the “USER’S GUIDELINES for Electrical
Installations for Explosive Gas Atmospheres in General
Industry,” published in 1994.
(1) Cable Wiring
• For cable wiring, cable glands (cable entry devices for flameproof type) specified or supplied with the apparatus shall be directly attached to the wiring connections to complete sealing of the apparatus.
• Screws that connect cable glands to the apparatus are those for G-type parallel pipe threads (JIS B 0202) with no sealing property. To protect the apparatus from corrosive gases or moisture, apply nonhardening sealant such as liquid gaskets to those threads for waterproofing.
• Specific cables shall be used as recommended by the
“USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry,” published in 1994.
• In necessary, appropriate protective pipes (conduit or flexible pipes), ducts or trays shall be used for preventing the cable run (outside the cable glands) from damage.
• To prevent explosive atmosphere from being propagated form Zone 1 or 2 hazardous location to any different location or non-hazardous location through the protective pipe or duct, apply sealing of the protective pipes in the vicinity of individual boundaries, or fill the ducts with sand appropriately.
• When branch connections of cables, or cable connections with insulated cables inside the conduit pipes are made, a flameproof or increased-safety connection box shall be used. In this case, flameproof or increased-safety cable glands meeting the type of connection box must be used for cable connections to the box.
(2) Flameproof Metal Conduit Wiring
• For the flameproof metal conduit wiring or insulated wires shall be used as recommended by the USER’S
GUIDELINES for Electrical Installations for Explosive
Gas Atmospheres in General Industry, published in
1994.
• For conduit pipes, heavy-gauge steel conduits conforming to JIS C 8305 Standard shall be used.
• Flameproof sealing fittings shall be used in the vicinity of the wiring connections, and those fittings shall be filled with sealing compounds to complete sealing of the apparatus. In addition, to prevent explosive gases, moisture, or flame caused by explosion form being propagated through the conduit, always provide sealing fittings to complete sealing of the conduit in the following locations:
(a) In the boundaries between the hazardous and nonhazardous locations.
(b) In the boundaries where there is a different classification of hazardous location.
• For the connections of the apparatus with a conduit pipe or its associated accessories, G-type parallel pipe threads
(JIS B 0202) shall be used to provide a minimum of five-thread engagement to complete tightness. In addition, since these parallel threads do not have sealing property, nonhardening sealant such as liquid gaskets shall thus be applied to those threads for ensuring waterproofness.
• If metal conduits need flexibility, use flameproof flexible fittings.
2 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
6. Maintenance of Flameproof
Apparatus
To maintain the flameproof apparatus, do the following. (For details, see Chapter 10 “MAINTENANCE OF EXPLOSION-
PROTECTED ELECTRICAL INSTALLATION” in the
USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry.)
(1) Maintenance servicing with the power on.
Flameproof apparatus shall not be maintenance-serviced with its power turned on. However, in cases where maintenance servicing is to be conducted with the power turned on, with the equipment cover removed, always use a gas detector to check that there is no explosive gas in that location. If it cannot be checked whether an explosive gas is present or not, maintenance servicing shall be limited to the following two items:
(a) Visual inspection
Visually inspect the flameproof apparatus, metal conduits, and cables for damage or corrosion, and other mechanical and structural defects.
(b) Zero and span adjustments
These adjustments should be made only to the extent that they can be conducted from the outside without opening the equipment cover. In doing this, great care must be taken not to cause mechanical sparks with tools.
(2) Repair
If the flameproof apparatus requires repair, turn off the power and transport it to a safety (non-hazardous) location. Observe the following points before attempting to repair the apparatus.
(a) Make only such electrical and mechanical repairs as will restore the apparatus to its original condition. For the flameproof apparatus, the gaps and path lengths of joints and mating surfaces, and mechanical strength of enclosures are critical factors in explosion protection.
Exercise great care not to damage the joints or shock the enclosure.
(b) If any damage occurs in threads, joints or mating surfaces, inspection windows, connections between the transmitter and terminal box, shrouds or clamps, or external wiring connections which are essential in flameproofness, contact Yokogawa Electric Corporation.
requirements for flameproof apparatus (however, bear in mind that the apparatus must always be restored to its original condition). If you attempt to repair the flameproof apparatus, company-specified components shall be used.
(d) Before starting to service the apparatus, be sure to check all parts necessary for retaining the requirements for flameproof apparatus. For this, check that all screws, bolts, nuts, and threaded connections have properly been tightened.
(3) Prohibition of specification changes and modifications
Do not attempt to change specifications or make modifications involving addition of or changes in external wiring connections.
7. Selection of Cable Entry
Devices for Flameproof Type
IMPORTANT
The cable glands (cable entry devices for flameproof type) conforming to IEC Standards are certified in combination with the flameproof apparatus. So,
Yokogawa-specified cable entry devices for flameproof type shall be used to meet this demand.
References:
(1) Type Certificate Guide for Explosion-Protected
Construction Electrical Machinery and Equipment
(relating to Technical Standards Conforming to International Standards), issued by the Technical Institution of
Industrial Safety, Japan
(2) USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry (1994), issued by the Japanese Ministry of Labour, the Research
Institute of Industrial Safet
CAUTION
Do not attempt to re-process threaded connections or refinish joints or mating surfaces.
(c) Unless otherwise specified, the electrical circuitry and internal mechanisms may be repaired by component replacement, as this will not directly affect the
3 EX-B03E
Edition
8th
9th
10th
REVISION RECORD
Date
Mar. 1998
Title: Model EJA438W and EJA438N Diaphragm Sealed Gauge Pressure
Transmitter
Manual No.: IM 1C22J1-01E
Sep. 1998
Feb. 2000
Page
1-1
5-1
10-1
10-3
10-6
2-9+
CMPL
2-14
2-15
7-19
10-3
10-4
CMPL
2
Revised Item
1
5.1
10.1.1
10.1.2
10.1.3
• Add FOUNDATION Fieldbus protcol version to ‘NOTE’ notice.
• Add Item 6 to the Wiring Precautions.
• Add FOUNDATION Fieldbus protocol.
• Add Output signal code F .
• Add Optional code A1.
• Change the figure of terminal configuration.
CMPL 1C22A1-02E 3rd 4th
Page 2 • Add Item 7-2.
2.10
2.10
7.3.2(8)
10.1.2
• Delete EMC Conformity Standards Tables and move the section to page 2-14.
• Remove Page 2-15.
• Correction made in BURN OUT figure.
• Add Process flange size/material code F and C.
• Add Electrical connection code 7, 8, and 9.
• Add Process flange size/material code F and J.
• Add Elactrical connection code 7, 8, and 9.
CMPL 1C22A1-02E 4th 5th
Page 2 • Add Part No. to Item 3 (For PG13.5 and M20).
• Add Part No. to Item 10 (For 1/2 NPT, Pg13.5, and M20).
CMPL 1C22J3-01E 1st 2nd
Page 4 • Add 80 mm / 3-inch to Flange Rating and SUS316 Stainless
Steel Part No. to Flange material in Table 1.
Changed to Electronic File Format.
Revised a book in a new format.
(The location of contents and the associated page numbers may not coincide with the one in old editions.)
Major Revised Items:
1. Explosion class and option code of JIS flameproof approval.
Explosion class: Ex ds IIC T4(old) to Ex do IIC T4X(new).
Option code: /JF1(old) to /JF3(new)
2. Option code for flameproof packing adapter for JIS flameproof approval.
Option code: /G1 and /G2(old) to /G11 and /G12(new)
3. Add “Pa” and “hPa” as the unit for calibration range.
4. Part number change for CPU Board Assembly.
2-8
2-9
5-1
5-3
7-4
–
9-6
CMPL
2.9
2.10
5.2
5.4.2
• Add Figure 2.3 Example of using DCS.
• Add AS/NZS 2064 1/2 to EMI, EMC Conformity Standards.
• Add selection in the case of JIS flameproof type.
• Change option code for flame packing adapter.
Option code: G1 and G2 G11 and G12
Change Applicable cable O.D. and Identifying mark.
Part number: G9601AH G9601AM
Change the figure of flame proof packing adapter in Figure 5.4.2c.
7.3.1
–
• Add Pa and hPa to C20 and D31.
• Installation and Operating Precautions for JIS Intrinsically Safe
9.3
and Explosionproof Equipment:
EX-A01E EX-A03E, EX-B01E EX-B03E
• Add Optional code F1.
CMPL 1C22A1-02E 5th 6th
• Change a format.
• Change and add Part No. of Item 7-1, CPU assembly:
Change; F9342BC F9342BB, F9342BK F9342BJ
Add; F9342AF, F9342AM
• Change Part No. of Item 10, Plug:
G9330DK G9330DP
CMPL 1C22J3-01E 3rd
• Change a format.
REVISION RECORD.EPS
IM 1C22J1-01E
Blank Page
Advertisement