Installation Instructions for
Honeywell ALL-SPEC Air Sampling Smoke Detection System
1
2
3
4
5
6
1
2
3
4
5
6
7
Operating indicator light
Alarm indicator light for detector module II
Alarm indicator light for detector module I
Indicator light for common fault
Pre-punched cable entries for connection to the central fire panel or power supply (input/output)
Connection pipe system I
5
8
5
8 Connection for air return
ALL-SPEC_Unit_HON.doc 07/2011 1/9
S1
6
9
10
7
8
8
4
5
4
Installation of the Detector Module
Please note:
Only the detector modules of the type ASD-TP-05, ASD-TP-01 and ASD-TP-001 that have been approved by the VdS-certification authority with the approval number G 202064 may be used.
1. Carry out the following works only if the device is powered down.
2. Open the device by carefully unlocking the housing snap-in closures by means of a screwdriver. Then lift the housing lid a little bit.
3. Carefully pull the connection cable of the display board off and remove the housing lid.
Note:
Shall the device only be provided with one detector module, please skip to point 6. Shall the device however be provided with two modules please follow the following instructions.
4. If you want to install a second detector module you have to recover carefully the ventilator cover for the second air sampling duct (self-adhesive plastic cover). Take for this if necessary a screwdriver.
5. Break carefully the clasp for the connection of the second pipe system (predetermined breaking point, marked by “II“) with a screwdriver from the housing.
Note:
The knocked clasp is to removed completely from the device.
6. Make the required settings at the detector module by setting the contacts of switch S1 accordingly (see also “Settings of the detector module”).
7. Carefully spread a bit the support clamps used to fix the detector module in the corresponding mounting position.
8. Carefully place the detector module in between them until it audibly snaps in and thus is fixed by the support clamps.
Note:
Make sure that the inserted detection module is fixed tight and save by the brackets by pressing the brackets additional by hand.
9. Connect the detector module via the ribbon cable with the connection “Head 1” (detector module I) or “Head 2” (detector module II) to the base board. Note the labelling of the base board.
10. Reconnect the display board to the base board. Note the connections and labelling of the base board.
ALL-SPEC_Unit_HON.doc 07/2011 2/9
Detector Module Settings
In the following tables the switch S1 has two positions: on off
The standard settings have a grey background.
Setting the response sensitivity
detector module
DM-TP-
50
DM-TP-
10
DM-TP-
01
1,0 %/m
0,8 %/m
0,4 %/m
0,2 %/m
0,12 %/m
0,06 %/m
0,03 %/m on on off on on off off off 0,5 %/m 0,1 %/m 0,015%/m
Setting the alarm delay
S1. 3 S1. 4
0 seconds
10 seconds off on off off
30 seconds off on
60 seconds on
Setting the activating threshold
“air flow fault”
on
S1. 5 S1. 6
I on off
II off on
III off off
IV on on
Setting the delay
“air flow fault”
0.5 minutes
2 minutes
15 minutes
60 minutes
Setting the fault signal
S1. 7 S1. 8 off on on on off off on off non-latched off
Setting LOGIC
⋅
SENS
latched on
S1.10 off off on on
ALL-SPEC_Unit_HON.doc 07/2011 3/9
JU4
X1 HEAD 1 DIAG X2 X3 HEAD 2 X4 DISPLAY X5 2 1
JU4
JU1
1 2
JU1
1 2
Choose number of the detector modules
The number of fitted detector modules are chosen with the jumper JU4. The following table shows, whether the jumper must be put or not:
X = pin pair bridge
O = pin pair open
The standard settings have a grey background.
Choose number of the detector modules
Jumper
Pin No.
JU4,
1+2
1 detector module X
2 detector module O
Setting the ventilator voltage
Jumper JU1 allows to set the ventilator voltage on the base board. The following table shows whether the jumper is set or not:
X = pin pair bridged
O = pin pair open
The standard setting has a grey background.
Setting the ventilator voltage
Jumper
Pin No.
JU1,
1+2
6,9 V X
9 V O
ALL-SPEC_Unit_HON.doc 07/2011 4/9
Setting the function of the fault contact
The contact type (break contact or make contact) of the collective fault is set using the jumper JU 2 and JU 3.
Fault contact detector module I = Jumper JU2
Fault contact detector module II = Jumper JU3
The following table shows the positioning of the jumpers:
X = pin pair bridge
O = pin pair open
The standard settings have a grey background.
Setting the collective fault contact
Jumper
Pin No.
JU2/3
1+2
JU2/3
2+3 break contact X O make contact O X
A B
Device Supports
A
B
Support type MT-1 horizontal installation
Support type MT-1 vertical installation
ALL-SPEC_Unit_HON.doc 07/2011 5/9
Installation of the device
General information:
When choosing the installation location make sure the displays of the device are clearly visible.
Screw the air sampling smoke detection system either directly to the wall with its bottom casing or mount it by means of a special support (type
MT-1). This support allows to mount the device also to racks for example.
The air outlet of the device must not be blocked. (The distance between the air outlet and adjacent objects (e.g. wall) is to be at least 10 cm.)
The air sampling smoke detection system can be mounted with the air sampling pipe connector(s) pointing upwards or downwards (If necessary, turn the housing-lid by 180
°
). If the air sampling pipe connector(s) point downwards make sure no impurities enter the air outlet which then points upwards.
Procedure:
1. First, clearly mark the fixing points for mounting the device. If necessary, use the provided drilling jig. Fix the device using four screws (max. ∅ of 6 mm for wall mounting and max.
∅
of 4 mm for mounting by means of the device support MT-1) in order to guarantee a safe fixing and to limit vibrations which occur.
2. Fix the device by means of four screws in accordance with the mounting type to the wall or the device support. Make sure the device is not fixed under mechanical tension or the screws are not tightened too much. Otherwise the device might be damaged, or unintended. secondary noise may arise.
Note:
To balance unevenness and/or to avoid vibrations vibration dampers need to be installed.
3. Carefully break out of the housing the required cable entries (max. 5 x M20 und 2 x M25). If required, use a screwdriver.
4. Carefully equip the cable entrie(s) according to requirements with M20 or M25 glands (2x M25, 1x M20 included in the delivery) by inserting them into the corresponding cable entry/entries.
5. Pass the connection cable(s) (max. 1.5 mm²) required to wire the device through the suitable cable entry/entries into the device and cut it to the required length within the device.
6. Wire the device according to the following connection diagram.
ALL-SPEC_Unit_HON.doc 07/2011 6/9
0V
+24V
0V
+24V connection to central fire panel
DJ 1191 or
DJ 1192
X6, 6
X6, 7
X6, 8
X6, 9
X7, 1
X7, 2
X6, 1
X6, 2
X6, 3
X6, 4
X6, 5
X7,3
X7, 4
X7, 5
X7, 6
X7, 7
X7, 8
X7, 9 connection to central fire panel connection to central fire panel
DJ 1191 or
DJ 1192 connection to central fire panel
Connection contact of the first alarm relay (make contact) centre tap of first alarm relay contact of the first alarm relay (break contact)
+ external response indicator for
first detector module
– external response indicator for
first detector module
+ 24 V reset input
0 V reset input
+ 24 V supply voltage
0 V supply voltage fault contact 2 nd
detector module
(connection 1) fault contact 2 nd detector module
(connection 2) contact of the 2 nd
alarm relay
(make contact) centre tap of 2 nd alarm relay contact of the 2 nd alarm relay
+ external response indicator for 2 nd
detector module
– external response indicator for 2 nd
detector module fault contact first detector module
(connection 1) fault contact first detector module
(connection 2)
X7
9
8
7
6
5
4
3
2
1 internal connection base board
X6
7
6
5
4
3
2
1
9
8
9
6
5
8
7
4
3
2
1
_
+
_
+
_
+
24 V
9
5
4
3
8
7
6
2
1
_
+
11
6
ALL-SPEC_Unit_HON.doc 07/2011 7/9
S2
Flow-Init
Commissioning
1. Make sure first that the device has been in operation for at least 30 minutes prior to the air flow initialization in order to reach the operating temperature.
2. In order to initialize the connected pipe system, press the Flow-Init-button S2 (see figure) of the corresponding detector module until the green operating indicator light of the device starts flashing. The initialization is terminated after approx. 5 seconds. After a successful initialization the operating indicator light is lit permanently.
3. During and after initialization the pipe system must no longer be changed. Even the ventilator voltage of the device must no longer be modified after initialization. Otherwise the initialization must be carried out again:
ALL-SPEC_Unit_HON.doc 07/2011 8/9
•
•
•
Conformity certification pursuant to EU Construction Products Directive 89/106/EEC
The conformity of the „ air sampling smoke detector for fire detection and fire alarm systems in buildings “ according to DIN EN 54-20 has been established by a test at the VdS laboratory.
The EC certificate of conformity has been issued by notified product certification body (ID no. 0786, VdS).
The CE designation according to DIN EN 54-20 has been carried out.
EN 54-20: 2006
Air sampling smoke detector for fire detection and fire alarm systems in buildings
0,015 % light obscuration/m
Class: A, B and C
0,1 % light obscuration/m
Class: A, B and C
0,5 % light obscuration/m
Class: A, B and C