ClearWater CD-2000 Installation & Maintenance Manual
Advertisement
Advertisement
Ozone Systems
Installation & Maintenance Manual
CD-2000
Corona Discharge Ozone Generators
ClearWater Tech, LLC
Integrated Ozone Systems
850-E Capitolio Way, San Luis Obispo, Ca 93401 • 805-549-9724 • Fax: 805-549-0306 • E-mail: [email protected] • www.cwtozone.com
Copyright © 2005 - ClearWater Tech, LLC. • Reproduction of any kind is prohibited • LIT520 • REV 062005
O
3
Introduction
.............................................................................................................................
This Installation and Operation Manual is written to assist in the installation, operation and maintenance of ozone delivery systems manufactured by ClearWater Tech, LLC. The equipment has been designed using the most modern materials and technology available.
Please read this manual carefully and in its entirety before proceeding with any installation, operation or maintenance procedure associated with this equipment. Failure to follow these instructions could result in personal injury, damage to the equipment or reduced product performance.
In an ongoing effort to improve reliability and operating efficiency, ClearWater Tech may find it necessary to make changes to its products. Therefore, the information contained in this manual may not conform in every respect to earlier versions of ClearWaterTech ozone systems found in the field. If you have any questions, please contact your ClearWater Tech dealer or the
ClearWater Tech service department.
2
OVERVIEW
H
ow Ozone is Generated
Ozone is generated by exposing oxygen molecules
(O
2
) in an air stream to a controlled, high energy electrical field. As the air stream passes through the electrical field produced inside the ozone generator, some oxygen molecules are split, forming single oxygen atoms (O
1 recombine with other O
2 forming ozone (O
3
).
). These oxygen atoms then
molecules in the air stream,
Electrical Field
Oxygen (O
2
)
O
2
O
2
O
1
O
1
Ozone (O
3
)
O
3
O
3
Properties of Ozone
Ozone is the most powerful oxidizer available that can be safely used in water treatment.
1 It is used to treat drinking water, bottled water, swimming pool water, wastewater, food and beverage processing water, and in many other applications. Ozone is effective in performing the following water treatment functions:
• Disinfection – Bacterial disinfection,
inactivation of viruses and cysts.
• Oxidation of Inorganics – Precipitates iron,
manganese, sulfides, nitrites and organically-
bound heavy metals.
• Oxidation of Organics – Including organics
causing color, taste and odor problems, some
detergents and pesticides, phenols, VOCs,
turbidity control and microflocculation of soluble
organics.
Molecular weight: 48
Odor:
Color:
Gas Density:
Readily detectable at concentrations above 0.02 ppm in air
Bluish in ozone generator cell, but ozone/air mixture exiting generator is invisible – even at high ozone concentrations.
2.144 grams/liter at 32°F (approx. 150% that of oxygen).
Solubility:
Only partially soluble in water, but about 10-20 times more soluble than oxygen (at 68°F).
Benefits of Ozone Use
• Ozone is generated on site – no transportation or storage is required.
• The most powerful oxidizer commercially available – very effective for
disinfection and oxidation without handling problems.
• Ozone creates no potentially harmful by-products (such as THMs) – the only
by-product is oxygen.
• Ozone leaves no telltale taste or odor.
References
1.
Water Quality Association, “Ozone for POU, POE and Small Water System Water Treatment Applications,” Lisle, IL, 1999.
3
ThEORy Of OPERaTIOn/PROdUcT dEscRIPTIOn
ClearWater Tech ozone systems are designed for safe, effective use in a variety of water treatment applications. Each complete, integrated system includes the components required for reliable, efficient ozone production and can be divided into four general segments:
• Air preparation system • Ozone generator • Ozone injection/contacting • Ozone destruct
Ozone Injector
Booster Pump
Water Flow
Ozone
Destruct
Unit
Ball Valve
Air Preparation System
Ozone Generator
CD4000P
Water Trap
Contact Vessel
Vacuum Break
Shown: ClearWater Tech CD4000P Ozone System
air Preparation system
ClearWater Tech commercial cabinet ozone generators require a source of clean, dry, oxygen-enriched air for effective ozone production. To meet that need, the rack-mount air preparation systems built by ClearWater
Tech employ pressure swing adsorption (PSA) technology to increase the concentration of oxygen and reduce the moisture content in the feed gas (the air supplied to the ozone generator). This substantially improves the output capability of the ozone generator and prevents premature failure of key internal components. These air preparation systems deliver 90%+/-3% oxygen purity at -100°F dew point and at very low pneumatic pressures, minimizing noise and reducing compressor wear.
If “Plant Air” feed gas is to be used, in place of the ClearWater Tech air preparation system, the same air quality standards must be met to achieve the ozone output and longevity of the ozone generator. A PSI
(pounds per square inch) regulator must be installed when using plant air feed gas. The regulator must be set to a maximum of 10 PSI.
4
Theory of Operation/Product Description (continued)
Ozone Generator
ClearWater Tech pressurized ozone generators are designed to supply high concentrations of ozone gas (up to
10%) at 10 PSI. The oxygen feed gas produced by the air preparation system is supplied to the ozone generator, which flows through a built-in flow meter. A stainless steel needle valve (preset inside the ozone generator), located on the stainless steel delivery line, is used to maintain optimum pneumatic parameters inside the reaction chambers. After this point the vacuum created at the ozone injector draws the ozone gas into the water line. The ozone generator is equipped with a pressure switch, which prevents its operation of the system if the pressure within the reaction chambers drops below 9 PSI.
As the feed gas enters the fused, thermally-protected reaction chambers inside the ozone generator, some of the oxygen molecules are split while passing through the high voltage electrical field (the “corona”), forming single oxygen atoms (O
1
). These oxygen atoms then recombine with other oxygen molecules in the air stream, forming ozone. The modular, multiple reaction chamber design allows the ozone generator to keep working even if one or more of the chambers requires service.
Depending on the application, the ClearWater Tech ozone generator may be interlocked with an ORP controller, pressure switch, timer or circulation pump. The CD4000P is equipped with two three-way solenoid valves. While the valve on the right (closest to the cabinet wall) is for additional back flow prevention, the valve to the left is to depressurize and “off gas” residual ozone from the ozone reaction chambers. An internal off gas destruct
(mounted inside the ozone generator) is used to destroy this residual ozone, (see Appendix - Section B).
Other safety features are also built in, including a pressure switch and thermal protection.
a short course in fine Bubbles
LESSON 1 - The large bubble (20mm) has a volume of 4.19 cm 3
12.6 cm 2 .
and a surface area of
LESSON 2 - 296 small bubbles (3mm) could be made from the large bubble in lesson 1. They would have a total surface area of 83.6 cm 2 . This is 6.6 times the surface area of the large bubble.
LESSON 3 - Theoretically, 6.6 times as much water could be ozonated with the same amount of ozone!
Ozone Injection/contacting
The ozone injector serves two purposes: One, it creates the vacuum required to safely draw the ozone gas from the ozone generator and two, it provides a means by which the ozone gas can become dissolved in water.
A very dynamic injection process is required to effectively dissolve ozone in water.
ClearWater Tech injection systems use only Mazzei® injectors for maximum mass transfer efficiency. The injector produces a cavitation effect, enabling the ozone gas to join the water stream in the form of extremely tiny bubbles. These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water.
Depending on the application and the water treatment goals, a ClearWater Tech contacting system may also be required. Some oxidation reactions take place so quickly that they are limited only by the rate at which the ozone is dissolved in the water. Other reactions, such as disinfection, may require that a proper ozone residual be maintained for a specific amount of time. A correctly-sized contact vessel is used for this purpose.
Ozone destruct
The ClearWater Tech off-gas destruct systems consists of two components - the ozone destruct unit (a heated chamber filled with manganese dioxide and copper oxide) and a water trap. Used in conjunction with a ClearWater
Tech off gas vent, the ozone destruct system is an effective way to vent the contact vessel(s) when it is impractical to send the off gas to atmosphere or reintroduce it to the water.
5
safETy InfORMaTIOn safETy WaRnInGs
Two aspects of ClearWater Tech ozone generators represent potential dangers – ozone gas and high voltage electricity.
OzOnE Gas
- WARNING: HIGH CONCENTRATIONS OF OZONE GAS ARE DANGEROUS
TO HUMANS. LOW CONCENTRATIONS CAN CAUSE IRRITATION TO
THE EYES, THROAT AND RESPIRATORY SYSTEM.
This ClearWater Tech corona discharge ozone generator is designed to operate under a pressure condition. While safety precautions have been taken, entering the equipment area should be avoided if ozone gas is detected.
Ozone has a very distinctive odor and is detectable at very low concentrations (0.02 ppm), which is far below OSHA’s maximum permissible exposure level of 0.1 ppm.
caUTIOn!
OzOnE
Gas hIGh VOlTaGE
- WARNING: CLEARWATER TECH OZONE GENERATORS OPERATE
AT HIGH VOLTAGES. DO NOT TAMPER WITH OR DELIBERATELY
BYPASS THE DOOR OR SAFETY SWITCHES BUILT INTO THE
OZONE GENERATOR UNLESS INSTRUCTED TO DO SO BY THIS
MANUAL. IF CONTACT IS MADE WITH OPERATING HIGH
VOLTAGE COMPONENTS, ELECTRIC SHOCK WILL OCCUR.
ClearWater Tech corona discharge ozone generators take line voltage and convert it to 48 VDC. A high voltage transformer then boosts the voltage. While each ozone generator has a door switch and other safety interlocks, proper care must be used by a qualified electrician when making any internal adjustments or performing any maintenance procedures.
6
Safety Information
(continued)
IMPORTanT safETy InsTRUcTIOns -
When installing and using this electrical equipment, basic safety precautions should always be followed, including the following:
1.
6.
7.
8.
9.
2.
3.
4.
5.
READ AND FOLLOW ALL INSTRUCTIONS.
SAVE THESE INSTRUCTIONS.
All electrical connections should be made by a licensed, qualified electrician.
Before attempting any electrical connections, be sure all power is off at the main circuit breaker.
Install all electrical equipment at least five feet from any open body of water using non-metallic plumbing.
Install check valves and a vacuum break to prevent water from contacting the electrical equipment.
The electrical supply for this product must include a suitably-rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422-20 of the National Electrical Code, ANSI/NFPA
70-1987. The disconnecting means must be readily accessible to the operator(s) but installed at least five feet from any open body of water.
Be sure to bond (ground) the system using the copper bonding lug on the bottom of the ozone generator. The system should be bonded with solid copper wire conforming with all local, state and national electrical codes.
The system should be sized appropriately for its intended use by a qualified professional familiar with the application. This equipment must be validated by the manufacturer for its intended use.
7
InsTallaTIOn PROcEdUREs - Getting Started
Unpacking
Compare the ozone system equipment received to the packing list provided.
Before beginning any installation procedures, thoroughly inspect all components for damage. If damage is noticed, promptly notify the freight carrier and request an on-site inspection. Inspect all packing materials for small parts before discarding. Inspect all plumbing, fittings and tubing for packing material that may have become lodged in openings.
Equipment Placement
• When placing the ozone system components in the equipment room, make sure to consider safety,
maintenance requirements, local building and fire codes, etc. The components should be easily
accessible by the operators, including equipment access doors and electrical hook-up boxes. All
meters, gauges, indicator lights and switches should be visible and accessible. Dimensional drawings
of each air preparation system and ozone generator are included in Section A of the Appendix.
• The air preparation system and ozone generator should be located as close as possible to the point
of ozone injection. Ozone is an unstable gas and will begin reverting back to oxygen very quickly.
To determine the most favorable ozone injection point, the following items should be considered:
• Located downstream of all other existing water system components.
• Located upstream of the residual sanitizer injection point (if so equipped).
• In a Sidestream plumbing configuration (see Figure 5-1) with recirculation, the pH adjustment
chemical injection point must be located downstream of the residual sanitizer injection point
(if so equipped).
• In a Full Flow plumbing configuration (see Figure 5-2) without recirculation, locate downstream of the pH adjustment chemical injection point
• Adequate protection from weather, dust and excessive heat.
• Like any electronic component, performance and longevity is enhanced by favorable operating
conditions. Also, since each air preparation system and ozone generator is air-cooled, a relatively
dust-free, well ventilated area is required. No caustic chemicals should be stored in the area
surrounding the equipment. A minimum clearance of six inches from the vents on either side of the
ozone generator is required.
• The equipment is heavy and requires proper support. Therefore, a clean, dry, level surface should be
provided for the air preparation system and ozone generator. These components should be securely
fastened to the surface using the mounting holes and/or tabs provided.
• The air preparation system and ozone generator are not designed to withstand outdoor elements,
including direct contact with water and/or temperature extremes. Therefore, the equipment must be
installed in an environment consistent with the following operating parameters:
• Ambient temperature range: 20°F to 85°F continuous. If the temperature around the
equipment
consistently exceeds 85°F, additional air cooling must be provided.
• Humidity: 0 – 90% relative humidity, non-condensing environment
• Line voltage: +/-10% of rated input
Note: Equipment installed in extreme environmental conditions will void manufacturer's warranty.
• Allow room for the peripheral equipment (booster pump, injector manifold, contact vessel, etc.).
8
CORONA DISCHARGE (CD) OZONE SYSTEMS
Installation Procedures (continued)
Ozone is manufactured in the CD ozone generator by drawing in air, which is composed of 20% oxygen
(O
2
), and exposing it to multiple high voltage electrical discharges. This causes a percentage of the oxygen molecules to dissociate and reassemble as ozone (O
3 way to produce large amounts of ozone.
). The corona discharge method is the most efficient
3 - O
2
2 - O
3
Chemical Formula (simplified) for Corona Discharge Ozone
In contrast to ultraviolet ozone generators, corona discharge systems produce a much higher concentration of ozone and in much larger quantities. In addition, the annual expense of replacing lamps and checking ballasts is unnecessary with corona discharge systems. Corona discharge ozone generation is the most economical and effective method to use on most water treatment applications.
ClearWater Tech manufactures high output corona discharge systems capable of producing enough ozone to oxidize iron, sulfide, manganese and act as an efficient sanitizer in a variety of applications. Ozone reacts to water-borne contaminants significantly faster than other disinfectants and the primary by-product is pure oxygen.
ClearWater Tech ozone systems are built with the finest components available. All are air cooled and are most efficient when used with a venturi injection system to create the best possible contact and mixing of ozone while maintaining a high level of safety.
UNCRATING and INSPECTION
Shipping Terms
Unless special arrangements have been made, the ozone equipment will be shipped FOB ClearWater
Tech's factory in San Luis Obispo, CA. The freight charges will be prepaid and billed or shipped freight collect. Transfer of liability to the freight company and the customer occurs as the equipment leaves the factory loading dock and is accepted by the freight line.
Freight Inspection
All equipment should be thoroughly inspected immediately upon delivery. If any damage is noticed, promptly notify the freight line and request an on-site inspection.
Unpacking
Typically, the equipment will arrive on a pallet. Compare the components with the packing list. Thoroughly inspect all packing materials prior to discarding. Inspect all plumbing fittings and tubing for packing mate rial inadvertently lodged in any openings.
Placement of Equipment
Select a location for the ozone equipment that is as close as possible to the ozone injection point. Arrange the components (ozone generator, air dryer and electrical interlock box, if so equipped) in a manner suitable for convenient electrical access. The system component enclosures are not rain proof, so it is important to choose a location that will keep the system away from direct weather and excessive heat.
Mounting holes are located on the back of all components for convenient wall mounting. Mounting hardware is not provided.
9
ClearWater Tech air preparation and ozone generation systems Models M-1500 and P-2000 are a vacuum type and will require adjustment of the air flow through the system. On the front of the electrical interlock box is a VAC/PSI
Materials Installation Procedures (continued)
Use Schedule 80 PVC for all plumbing connections whenever possible. Also, it is recommended that unions and valves are used wherever practical. Ozone rapidly deteriorates a variety of compounds; the following is a list of materials that may be used . . .
. . . with ozone in gaseous phase (at high concentrations):
Viton Teflon ® Stainless Steel EPDM
Silicon Kynar ® Hepalon
. . . with ozone in aqueous phase (at low concentrations):
Viton
Silicon
Teflon
Schedule 40 PVC
®
Kynar ®
Stainless Steel
Concrete
EPDM
Hepalon
Schedule 80 PVC
NOTE: Be sure to use good plumbing practices and install unions and isolation valves wherever the situation dictates, i.e. pump or injector removal, etc. Secure all plumbing with unistrut or similar hardware.
Tubing Installation
1. Install braided tubing from the indicating desiccant chamber on the air dryer to the brass AIR INLET fitting on the bottom of the ozone generator (or the bottom of the electrical interlock box if so equipped). If you are not using an electrical interlock box, skip Step 2 and go to Step 3.
2.
3.
If equipped with the electrical interlock box, continue running the braided tubing from the electrical interlock box brass AIR OUTLET fitting to the brass barb AIR INLET fitting on the bottom of the ozone generator.
Install the ozone check valve assembly onto the injector. Connect the 1/4” Teflon ® tubing from the Teflon ®
OZONE OUT compression fitting on the bottom of the ozone generator to the Teflon ® compression fit ting on the check valve assembly on the injector. Secure by tightening the fitting around the 1/4” Teflon ® tubing after insertion. (If equipped with the electrical interlock box, install the 1/4” Teflon ® tubing from the
OZONE OUT fitting on the bottom of the ozone generator to the stainless steel solenoid valve located on the top of the electrical interlock box. Continue running the Teflon ® line from the solenoid valve to the check valve assembly on the injector.)
Check Valve Selection
The ozone check valve is an important component in preventing damage to the ozone generator. All ClearWater
Tech CD2000 ozone generator is equipped with a Kynar ® low pressure check valve on the ozone outlet. A second check valve should be installed on the venturi injector ozone inlet. This check valve should be matched to the application. A low pressure Kynar ® check valve is appropriate for applications where the system pressure will not exceed 40 psi. Higher line or system pressure installations require a stainless steel check valve.
Note: The cracking pressure (the pressure at which the valve opens) of any stainless steel or Kynar ® check valves not sourced through ClearWater Tech must not exceed 0.5 lb. (0.33 lb. is recommended.
10
PROdUcT dEscRIPTIOn
Ozone Generator
The ozone generator houses the ozone reaction chamber(s), power supply and all electrical components directly related to the production of ozone. Ozone is produced when the feed gas is exposed to a high voltage electrical current inside the reaction chamber.
Air Preparation
The ClearWater Tech ozone system may be equipped with a heat regenerative desiccant air dryer. Corona discharge ozone generators are much more effective, produce more ozone and require far less maintenance if an air preparation unit is included. The air preparation system lowers the dew point of the feed gas. Moist feed gas (air) will cause nitric acid to form inside the generator which decreases ozone production and if not removed, causes corrosion and eventual failure of the generator’s internal components. The ability of the ozone generator to produce ozone is drastically reduced as the dew point rises above -60°C.
Injector Manifold
The ozone gas is injected into the filtered water return line by means of the injector manifold. This allows the ozone to be injected into the water under a vacuum condition which is the safest technology available.
Contact Vessel
(optional)
To maximize the effectiveness of ozone, it must be thoroughly mixed and have adequate time to react with the contaminants in the water before being filtered or utilized. Contact vessels are designed to achieve this necessary mixing and contact time. ClearWater Tech supplies several different types of contact vessels for a variety of applications.
Booster Pump
(optional)
If excessive back pressure is created in the water line by filters, pressure tanks or other system parameters, a booster pump may be necessary to create a sufficient pressure differential across the venturi. This booster pump is used in con junction with a side stream ozone injection loop.
Electrical Interlock Box
(optional)
The electrical interlock box is a multi-function electrical enclosure. It houses the Motor Control Interlock (MCI), ORP
Interlock and the Vacuum Interlock. The enclosure also acts as the air preparation monitoring station, controlling the amount of intake air and monitoring the vacuum.
11
PlUMBInG cOnnEcTIOns
Full Flow Plumbing Connections
Refer to the ‘Full Flow Installation’ diagram on the next page and follow the instructions below if the ozone is being injected directly into the full flow of the pool’s return line:
1. Tap into the return line after the pump, filter, and heater. The ozone injection point should be the last component in line and
as far as possible from the residual sanitizer injection point.
2. Glue in the proper injector, noting the direction of flow (indicated by an arrow on the injector).
3. Once the injector is installed, the vacuum may be adjusted as described in the “ozone generator operation” section. If the
system is equipped with the optional electrical interlock box, the vacuum can be observed on the VAC/PSI gauge located
above the SCFH gauge on the electrical interlock box.
Note: The ozone generator will only energize for 15 seconds or until a vacuum is attained.
Tubing Installation
1. Install braided tubing from the air dryer to the AIR INLET fitting on the bottom of the ozone generator (or the bottom of the
electrical interlock box if so equipped). If you are not using an electrical interlock box, skip Step 2 and go to Step 3.
2. If equipped with the electrical interlock box, continue running the braided tubing from the electrical interlock box to the
brass barb fitting on the bottom of the ozone generator.
3. Install the check valve assembly into the injector. Connect the 1/4” Teflon ® tubing from the OZONE OUT fitting on the
bottom of the ozone generator to the check valve assembly on the injector. Secure by tightening the fitting around the
1/4” Teflon ® tubing after insertion. (If equipped with the electrical interlock box, install the 1/4” Teflon ® tubing from
the OZONE OUT fitting on the bottom of the ozone generator to the stainless steel solenoid valve located on the top of the
electrical interlock box. Continue running the Teflon ® line from the solenoid valve to the check valve assembly on the
injector.
Independent Ozone Loop Plumbing Connections
Refer to diagrams (pgs 7-8) and follow the instructions below if the ozone is being injected into an independent ozone loop.
If circumstances allow (new construction, pre-plumbed for an ozone loop), the ideal configuration is for the ozone loop to be completely independent from the pool’s circulation system. Otherwise, the feed water for the side stream is pulled from the main return before the circulation pump and returned at a point after the filter and heater. This is done so the booster pump is not attempting to draw water through the filter and from the circulation pump when the circulation pump is not operating. The pH adjustment point will always be the last item in this sequence.
Use Schedule 80 PVC for plumbing connections when possible. It is recommended that unions and valves are used where practical.
Ozone rapidly deteriorates many compounds; the following is a list of materials that may be used with ozone in an aqueous solution.
Viton Teflon ®
Silicon
Sch. 40 PVC Stainless Steel
Kynar
EPDM
Sch. 80 PVC Concrete Hepalon
NOTE: Be sure to use good plumbing practices and install unions and isolation valves wherever the situation dictates, i.e. pump removal, etc. Secure all plumbing with unistrut or similar hardware.
1. In the main water return line, before the circulation pump (or a pre-plumbed independent suction fitting if new construction) install a tee and an isolation valve.
2. Install the booster pump. Secure the pump on a housekeeping pad with the appropriate mounting hardware.
3. If an auxiliary control relay (i.e. flow switch) is being used, install it into the line after the ozone booster pump.
4. Install the injector manifold after the ozone booster pump, making sure to note the correct flow direction of the injector manifold. Remove the tie wraps that secure the check valve assembly to the injector manifold and thread the check valve assembly onto the opening of the venturi.
12
13
14
15
OPTIONAL VACUUM BREAK INSTALLATION
Plumbing Connections - continued
Location
Select a suitable vertical surface that is accessible and in close proximity to the ozone generator and venturi manifold on which to mount the vacuum break.
Installation Steps
1. Install the two mounting Clic
®
clamps provided on the vertical surface so that the vacuum break will be in a vertical position and
the height of the fill/drain valve fitting will be below the level of the ozone generator bulk head check valve. One clamp should
be located directly above the vacuum break’s bottom end cap and the other just below the fill/drain fitting tee.
2. Install the two reducer bushings provided into the riser tee, one into the side tapping and the other into the top tapping.
Be sure to use 2-3 wraps of Teflon
®
tape on the male threads.
3. Install the PVC ball valve provided into the reducer bushing in the side tapping on the riser tee. Be sure to use 2-3 wraps of
Teflon
®
tape on the male threads. This valve controls the amount of water that is drawn up into the riser tube by the suction
of the venturi. It can also be used to isolate the venturi should a check valve fail.
4. Install the 90º Kynar
®
fitting provided into the reducer bushing on the top tapping on the riser tee. Be sure to use 2-3
wraps of Teflon
®
tape on the male threads.
5. Place the two-inch diameter water reservoir into the mounting Clic
®
clamps and secure. Check to make sure the height of the
fill/drain fitting is below the level of the ozone generator bulkhead check valve.
6. Slide the riser tube into the water reservoir.
7. Attach one end of a suitable length of 1/4” Teflon
®
tubing provided to the 90º Kynar
® compression fitting on the top of
the riser tee. Attach the other end of the tubing to the bulkhead check valve on the bottom of the ozone generator. The
length of the tubing will depend on the distance between the vacuum break and the ozone generator.
8. Initiate water flow through the system (e.g., start the circulation pump or booster pump) so water is flowing through the
venturi injector. Adjust the suction at the venturi with a hand-held SCFH gauge, matching the air flow to the correct
specification as outlined on pages 17 and 18.
9. Close the PVC ball valve on the riser tee. Using the straight compression fitting provided, attach another suitable length
of 1/4” Teflon
®
tubing to the outlet of the PVC ball valve. Attach the other end of the tubing to the compression fitting on the
venturi check valve assembly.
10. Turn the fill/drain fitting so the opening faces upward and add water to the water reservoir until it begins to overflow out of the
fill/drain fitting. Now turn the fitting so the opening faces downward.
11. Slowly open the PVC ball valve on the riser tee, allowing the water level in the riser tube to rise to a level no closer than two
inches from the bottom of the riser tee.
12. Connect a suitable length of the 3/4” braided tubing provided to the barbed fitting on the fill/drain fitting. Make sure
the open end of the tubing goes to safe, proper drainage and that the tube has no flow restrictions.
13. Run the system to ensure the water level in the riser tube is stabilized.
Note: The proper water level must be maintained in the water reservoir. When full, the reservoir contains about twice the amount of water required to fill the riser tube, so it must always be kept at least half full. An insufficient water level will result in a loss of vacuum, preventing air flow through the ozone generator.
16
Plumbing Connections - continued
Vacuum Break detail
Ozone Flow
Ozone Generator
Fill Port Cap
Upper Tee
Ozone Flow
Lower Tee
Check Valve Assembly
Venturi
Ozone Injector Manifold
Drain Port
Flapper
Valve
17
Mounting Clamps
Riser Tube
Elbow
Plumbing Connections - continued
OPTIONAL CONTACT COLUMN INSTALLATION
Location
The contact column(s) should be installed after the injector manifold(s), within three (3) feet of a wall or solid mounting surface using isolation valves to facilitate cleaning the diffuser, if needed. There should be as few elbows as possible between the injector(s) and the contact column(s). Be sure to note the flow direction of the column(s).
Mounting To a Wall or Other Solid Mounting Surface Using the Hardware Kit
Refer to the diagrams on the next pages and follow these instructions:
1. Locate the following items from the hardware kit:
• ‘L’ bracket
• two 1/2” concrete anchors with nuts and washers
• unistrut and protective end cap
• 6” clamp assembly with nut and bolt
2. Mark the two holes for the ‘L’ bracket on the wall. The ‘L’ bracket should be in located above the center of the length of the contact column. A foot or so from the top is ideal. Drill two 1/2” holes where you marked, about 3 1 /
2
” to 4” deep. Insert one concrete anchor into each hole with the threaded end sticking out. Slip the ‘L’ bracket over these threaded ends and tighten down with the nuts and washers provided. This will cause the ends of the concrete anchors in the wall to expand and thus secure the ‘L’ bracket to the wall.
3. Bolt the unistrut to the ‘L’ bracket with two bolts, nuts and washers. NOTE: The unistrut may be cut to length if desired.
4. Slip the two 6” clamp pieces into the unistrut around the contact column. Tighten bolt.
5. Attach the protective end cap to the exposed end of the unistrut.
18
MOUNTING CONTACT COLUMN TO WALL USING UNISTRUT MOUNTING SYSTEM
6' Clamp Assembly with Bolt & Nut
Unistrut (may get cut to length desired)
1/2" Holes Drilled Into
Wall (3 .5" to 4" deep)
Bolts, Nuts & Washers
(2 each)
Unistrut
Protective
End Cap
Contact Column
"L" Bracket
Concrete Anchors with
Nuts & Washers (2 each)
Wall
MOUNTING TWO CONTACT COLUMNS TO WALL USING UNISTRUT MOUNTING SYSTEM
6' Clamp Assemblies
(2)with Bolt & Nut
1/2" Holes Drilled Into
Wall (3 .5" to 4" deep)
Bolts, Nuts & Washers
(2 each)
Unistrut (may get cut to length desired)
Unistrut
Protective
End Cap
Contact Columns
"L" Bracket
Concrete Anchors with
Nuts & Washers (2 each)
Wall
19
Installation of Contact Column Vent Line
1.
2.
Drill and tap a 1/4” MPT hole into the main water return line after the heater. This hole should be drilled into a location with less pressure than the ozone loop so that the contact column will continually bleed ozone gas buildup on top of the column to be mixed back into the main water line. (Do not install this vent line on the suction side of the pump.)
Install the Teflon ® vent line from the Kynar ® fitting on the top of the contact column to the location drilled into the main water line.
Vent Line Installation Detail
Compression
Elbow Fitting
Needle Valve
(may be installed anywhere along vent line)
Vent Line
Contact
Column
Compression Fitting
Water Return Line
20
ElEcTRIcal cOnnEcTIOns
GENERAL INFORMATION
Please read the following important information before making any electrical connections:
1. All electrical work should be done by a licensed electrician.
2. All local codes must be observed.
3. The M-1500, CD-1500, P-2000, and CD-2000 are available in 120 VAC and 240 VAC models. Be sure to install the proper model for each application.
4. Before attempting any electrical hook-up, be sure the power is OFF at the main circuit box.
5. Ground the ozone generator using the copper grounding lug on the bottom of the unit. Solid copper wire conforming with all local, state, and national electrical codes should be used.
The ozone generator should be wired so that the ozone comes ‘ON’ when the main circulation pump comes on for filtration. This can be accomplished by utilizing the optional elctrical interlock box to interface with a flow switch, ORP monitor, timer or motor control interlock (MCI) to the main circulation pump. If the optional electrical interlock box is not used, the ozone generator should be wired to the main circulation pump’s power source (or timer if a timer is used).
If a side stream booster pump is used, the ozone generator and the booster pump should be interlocked to the main circulation pump.
The ozone generators come standard ready to be hard wired using 1/2” liquid tight conduit.
ELECTRICAL CONNECTIONS WITH OPTIONAL ELECTRICAL INTERLOCK BOX
Note: All electrical connections should be made by a qualified electrical contractor. All local, state and national
0codes must be observed.
Inside the electrical interlock box (at the bottom, toward the center) is a terminal strip. All the peripheral equipment is wired to this block (with the exception of the air dryer). All possible pre-wiring to the terminal block has been done. Refer to the diagram on the following page for details.
A dedicated 20 AMP circuit should be run from the main electrical panel to the electrical interlock box or from the main electrical panel into a service disconnect box before wiring to the interlock box.
Terminals 1,2, and 3 : Main Power - 240 VAC systems - 240 VAC, 60 Hz, 3 AMP w/o booster pump, 11 AMP with 1 HP booster pump. Use minimum #12 AWG. Connect 240 VAC, 20 AMP service from the disconnect box or from a dedicated breaker on the main panel to the 240 VAC terminals 1 & 2 to the 240V terminals on the terminal strip in the electric interlock box. Connect the white neutral wire to terminal 3 and connect the green wire to the grounding bar in the electric interlock box. The system can be controlled by the circulation pump timer by wiring the timer to terminals 1 & 2.
120 VAC systems - 120 VAC, 60 Hz, 6 AMP w/o booster pump, 22 AMP with 1 HP booster pump. Connect 120 VAC, 10 AMP service to terminal 1 on the terminal strip. Connect the white neutral wire to terminal 2 and connect a #12 AWG jumper wire from terminal 2 to terminal 3. Connect the green wire to the grounding bar.
Terminal 4: MCI (Motor Control Interlock) - 120 VAC, 60 Hz. Use # 18 AWG. This is an interlock from the main circulation pump to the ozone system. Run a 120 VAC line from the motor starter to this terminal. Should this feature not be used, simply install a jumper from L1 to this terminal. The unit will not function without a 120 VAC signal to this location.
Terminals 5 & 6: Oxidation Reduction Potential (ORP) Controller - 120 VAC, 60Hz. Use #18 AWG. This is control voltage only (120 VAC) from the controller to a relay integrated into the ozone system. Note: To override the ORP control signal, simply turn the ozone switch on the electrical interlock box to the ON position.
21
Electrical Connections - continued
Terminals 7 & 8: Booster Pump - 240 VAC, 60 Hz, 8 AMP, 1 HP. Use minimum #14 AWG. 120 VAC, 60 Hz, 16 AMP, use minimum #12 AWG. Wire from the terminal strip to the booster pump as indicated. The booster pump will be controlled by the interlock box. In many cases this feature is not be used; the operation of the remaining equipment will not be affected.
Terminals 9 & 10: Ozone Generator - 240 VAC, 60 Hz, 2 AMP or 120 VAC, 60 Hz, 4 AMP. Hard wire the electrical cord on the ozone generator to the terminal strip as indicated. The ozone generator will be controlled by the electrical interlock box.
Air Dryer: 120 VAC, 60 Hz, 1 AMP. Plug the air dryer into a standard wall outlet 120 VAC, 60 Hz. The air dryer should remain energized at all times with the exception of long term shutdown for service. The air dryer can be hard wired to the electrical interlock box utilizing terminals 1 (120V) and 3 (neutral).
Using a bonding wire conforming with all local, state and national electrical codes (normally a #8 AWG), ground the components to the grounding bar on the electrical interlock box and bond the electrical interlock box to a true earth ground.
120 VAC MODELS
1. Line in 120V
2 Neutral in
3. Neutral in
4. MCI in
5. ORP Line in
6. ORP Neutral
7. Booster Pump Out 120V
8. Booster Pump Neutral
9. Ozone Generator Out 120V
10. Ozone Generator Neutral
240 VAC MODELS
1. Line in 240V
2. Line in 240V
3. Neutral In
4. MCI in
5. ORP Line in
6. ORP Neutral
7. Booster Pump Line Out 240V
8. Booster Pump Line OUt 240V
9. Ozone Generator Out 240V
10. Ozone Generator Out 240V
Grounding Bar
22
Electrical Connections - continued
ELECTRICAL SCHEMATIC WITH OPTIONAL ELECTRICAL INTERLOCK BOX
240 VAC, 60 Hz, Single Phase
M-1500: 2 Amps without Booster Pump, 7 Amps with 1/2 HP Booster Pump
P-2000: 10 Amps with 3/4 HP Booster Pump
Connections:
Electrical Wiring
Braided Air Line
Teflon ® Ozone Line
AD-40 Air Dryer, Dry air or Oxygen
Vacuum
Gauge
SCFH
Gauge
Covered
Duplex
Convenience
Outlets
Ozone Generators
Electrical
Interlock
Box
Ozone
Outlet
120 VAC signal to the ozone generator form the ORP controller
Service disconnect or from a dedicated breaker in the main panel
120 VAC signal from the motor starter of the main circulation pump
L1
L2
Neutral
23
INITIAL STARTUP AND CALIBRATION WITH OPTIONAL ELECTRICAL INTERLOCK BOX
ClearWater Tech air preparation and ozone generation system CD2000 is a vacuum type and will require adjustment of the air flow through the system. On the front of the electrical interlock box is a VAC/PSI gauge and an SCFH (Standard Cubic Feet per Hour) gauge. These two instruments are all that are required to keep the system operating within the correct parameters.
The ozone system will not function without a minimum of 3” vacuum from the venturi injector (due to an electrical vacuum interlock relay). This is a safety feature designed to prevent the ozone generator from operating without the injector drawing the gas into the water.
After all the previous electrical and plumbing connections have been completed, the system is ready for startup and calibration.
Starting Position:
1.
Water flowing in the main line.
2.
Open the valves to the ozone loop (if so equipped).
3.
Switch the main service disconnect box to the ON position.
4.
Turn the ozone generator ON at the switch located on the front of the electrical interlock box. Note: The dryer should already be ON as it is wired for continuous operation. The booster pump and ozone generator should now be operating.
5.
The injector can now be adjusted for suction. Observe the SCFH gauge and adjust the air flow using the needle valve on the SCFH gauge. Closing this valve will lower the air flow and raise the vacuum. If proper flow and vacuum cannot be achieved, readjust the bypass valve on the injector manifold until you achieve the SCFH specified for the ozone generator being installed (see chart below). Note: The system will only operate for 15 seconds without vacuum.
To reset the time sequence, turn the ‘ON OFF AUTO’ switch OFF and back to ON.
Model
CD2000
Operating SCFH
8-12
16-20
Vacuum
-5 t0 -10
-5 to -10
VAC/PSI Gauge
This gauge measures the relationship between the suction at the injector and the resistance to drawing the dry air and ozone through the system. Under ideal conditions, this gauge should show a very slight vacuum.
Safe
Operating
Range
Ideal
SCFH
Gauge
VAC
Needle
Valve
PSI
24
INITIAL START-UP WITHOUT OPTIONAL ELECTRICAL INTERLOCK BOX
The air preparation and ozone generation systems on ClearWater Tech Model CD2000 is a vacuum type and will require adjustment of the air flow through the system. An SCFH (Standard Cubic Feet per Hour) gauge is used to accurately measure the amount of air flowing through the ozone delivery line on single speed injectors (in other words, the amount of ozone being injected into the water). Follow the directions and illustration below to optimize flow through the injector:
1. With the pump running, disconnect the ozone line from the outlet on the ozone generator and connect it to the fitting on the back of the SCFH gauge provided (see drawing).
2. While holding the gauge vertically, read the amount indicated on the gauge. The optimum flow is 11 to 15 SCF for the CD2000. Note: Do not obstruct the bottom air hole on the gauge.
3. On a single pump system, the injector will have a ball valve to adjust the amount of flow. To adjust the SCFH, simply install the gauge as above and open the gate valve completely. With the pump running, begin closing the gate valve until the optimum flow is achieved on the SCFH gauge. If possible, remove the gate valve handle to prevent tampering with the setting.
Attach Ozone Line
Keep
Gauge
Vertical
Injector Manifold with check valve
Do not block lower hole
25
OzOnE GEnERaTOR OPERaTIOn
After the installation has been completed, the pool operating parameters should remain the same as before. The indicator light on the ozone generator (and on the electrical interlock box, if so equipped) will be illuminated if the units are functioning properly.
It is recommended that the pool be super-chlorinated prior to starting the ozone system to insure any organic buildup has been eliminated.
System Running Time
On residential pools, the ozone generator should operate for six to eight hours per day. Normally, the ozone system will run whenever the pool filtration system is operating. Since commercial pool and spa filtration systems normally operate 24 hours a day, the ozone system will run continuously on a commercial pool.
Understanding Your Water
If a high concentration of any mineral (such as calcium or iron) exists in the water, it is necessary to treat it before starting the ozone system. ClearWater Tech suggests a water sample be taken to your ClearWater Tech distributor for analysis. Specific recommendations will be made relative to the product(s) needed to remove these minerals from the water. Note: This should be required only when the pool is drained and refilled.
If the water is clean and clear, the ozone system may be started immediately. If the water is dirty and cloudy, it is recommended that it be drained and the filters thoroughly cleaned before refilling and starting the system. Note: It is not recommended that an in-ground pool be drained in the winter or after the first rain of a season. Use a shock treatment instead of draining to avoid the possibil ity of severe damage resulting from “floating” the pool out of the ground.
Ozone and Bromine
Ozone has a short “half-life”, which means it dissipates very quickly. Therefore, a small residual of another disinfectant must be maintained. We recommend the use of bromine in indoor pools. A bromine residual will act as a buffer when the ozone system is not operating. Bromine needs to be maintained at only 1.0 PPM (parts per million) so that the trace amount of the product in the water will not be noticed. Chlorine will also work as a residual oxidizer and may be used effectively in conjunction with the ozone system (see below and chart on following page).
Ozone and Chlorine
For outdoor pools, we recommend the use of chlorine to supplement the ozone. A chlorine residual will act as a buffer when the ozone system is not operating. Chlorine needs to be maintained at 1.0 to 2.0 PPM (parts per million - see below). To decide which form of chlorine to use in your pool, refer to the chart on the following page.
Water Preparation
To properly prepare the water for the ozone system, make the following adjustments and maintain the levels outlined below:
Bromine
or
Chlorine pH
Total Alkalinity
Calcium Hardness
1.0 PPM
1.0 to 2.0 PPM
7.2 - 7.6
100-150 PPM
200-350 PPM
Note: If any unusual reactions are experienced when ozone is introduced to the water (such as abnormal color or odor), please wait a few days to give the ozone and filter system time to work. If the situation continues, your ClearWater Tech distributor should be consulted.
Algae
Always maintain the recommended residual levels of bromine or chlorine (at least 1.0 PPM) to help control algae. Brushing pool sides once a week is also effective, as is any algaecide. Note: Please consult your ClearWater Tech distributor before using any algaecide.
Shock Treatment
If an unusually high bather load causes cloudiness in the water, it is recommended that a chlorine shock treatment be used to assist the ozone in cleaning the water. Routine, periodic shocking is recommended to prevent buildup of organic contaminants, especially with indoor pools. These treatments are available from your ClearWater Tech distributor. Ask for assistance in selecting the proper product.
26
Ozone Generator Operation - continued
Properties of Bromine and Various Forms of Chlorine
Type of Bromine or Chlorine
% of
Available
Oxidizer pH Stabilizer Neutralizer Fast
Required? Dissolving? Dissolving?
Bromine
Gas Chlorine
61% 7.4
100% Very
Acidic
No Yes (Muriatic No
Acid or CO
2
)
Yes Yes Yes
Liquod Chlorine
(Sodium
Hypochlorite)
Calcium
Hypochlorite
12% 13
65% 11.8
Yes
Comments
Works well in floaters or feeders-Can be used in vinyl pools
Dangerous
Yes Does not have to Can be used to
It makes HoCI superchlorinate
instantly
Yes Yes No - Must be Extreme oxidizer -
(Muriatic predissolved or Do NOT use in a vinyl
Acid) broadcast can pool - Can be used
cloud in a feeder
Sodium Dichlor
Trichlor
Lithium
Hypochlorite
56%
90%
6.8-7 No
(Built in)
No Yes - Will not
cloud water
Can be used to
superchlorinate
35%
2.8-3 No Yes No Works well in floaters
(Built in) (Soda Ash) Very slow Cannot be used to
superchlorinate
10.7 Yes Yes Yes Cannot be used in a
(Muriatic Will not cloud feeder - Can be used
Acid) in vinyl-lined pools
27
CD2000 OZONE GENERATOR DIMENSIONS AND LAYOUT
Front and Bottom Views
28
ELECTRICAL CONNECTIONS
The installation should be done by a licensed electrician. All local codes must be observed.
The units come standard ready to be hard wired, using 1/2" liquid tight conduit.
The ozone generator should be wired so that the ozone generator is on when the pump is on or when water is flowing through the venturi. This can be done by using the electrical interlock box to interface with a flow switch, ORP monitor or timer; or by using the motor control interlock (MCI) to work with a main pump.
IMPORTANT: The M-1500 & P-2000 are available in 120 volt and 240 volt models. Be sure you have the proper sys tem for your application. Before attempting any electrical hookup, be sure the power is OFF at the main circuit box!
To hard wire a 120V system, connect the black “hot” wire to terminal L1. Connect the white neutral wire to the L2 ter minal. Connect a 12 AWG jumper wire from terminals L2 to L3. Then run the green ground wire to the grounding bar.
To hard wire a 240 VAC system, connect the black wire to terminal L1 and connect the red wire to terminal L2. Con nect the white neutral to terminal L3. Connect the green wire to ground.
ELECTRICAL INTERLOCK BOX (OPTIONAL) DIMENSIONS AND LAYOUT
29
240VAC ELECTRICAL CONNECTIONS WITH OPTIONAL ELECTRICAL INTERLOCK BOX
Follow the instructions below and the wiring diagram on the previous page to wire your system. Note: All electrical connections should be made by a qualified electrical contractor. All local, state and national codes must be observed.
Inside the electrical interlock box (at the bottom, toward the center) is a terminal strip. All the peripheral equipment is wired to this block (with the exception of the air dryer, which should be wired separately for continuous operation). All possible pre-wiring to the terminal block has been done.
A dedicated 20 AMP circuit should be run from the main electrical panel to the electrical interlock box or from the main electrical panel into a service disconnect box before wiring to the interlock box.
Terminals 1 & 2: Main Power - 240 VAC, 60 Hz, 2 Amps w/o booster pump, 11 AMP with 1 HP booster pump. Use minimum #12 AWG. Connect 240 VAC, 20 AMP from the disconnect box or from a dedicated breaker on the main panel to the 240 VAC terminals 1 (L1) & 2 (L2). Connect the green ground wire to the grounding bar.
Terminal 3: System Neutral - Use minimum #12 AWG. Provide a true neutral lead for this position. A true neutral runs from this terminal to the neutral bus bar in the main breaker panel. Do not ground this terminal or jumper to the ground. Note: The unit will not function without true neutral to this location.
Terminal 4: MCI (Motor Control Interlock) - 120 VAC, 60 Hz. Use # 18 AWG. This is an interlock from the main pump to the ozone system. Run a 120 VAC line from the motor starter relay to this terminal. Should this feature not be used, simply install a jumper from L1 to this terminal. Note: The unit will not function without a 120 VAC signal to this location.
Terminals 5 & 6: Oxidation Reduction Potential (ORP) Controller - 120 VAC, 60Hz. Use #18 AWG. This is control voltage only (120 VAC) from the controller to a relay integrated into the ozone system. These terminals may also be used to operate the system using a 120V signal from a flow switch or timer. Note: To override the ORP control signal, simply turn the ozone switch on the electrical interlock box to the ON position.
Terminals 7 & 8: Booster Pump - 240 VAC, 60 Hz, 8 AMP, 1 HP. Use minimum #14 AWG. Wire from the terminal strip to the booster pump as indicated. The booster pump will be controlled by the interlock box. If you are using a pump of over 1 HP, you will need to use a magnetic starter relay with these terminals providing the control voltage to the magnetic starter relay. In many cases this feature is not be used; the operation of the remaining equipment will not be affected.
Terminals 9 & 10: Ozone Generator - 240 VAC, 60 Hz, 2 AMP. Hard wire the ozone generator to the terminal strip as indicated. The ozone generator will be controlled by the electrical interlock box.
Air Dryer: 120 VAC, 60 Hz, 1 AMP. Plug the air dryer into a standard wall outlet 120 VAC, 60 Hz. The air dryer should remain energized at all times with the exception of long term shutdown for service. The air dryer can be hard wired to the electrical interlock box utilizing terminals 1 (120V) and 3 (neutral) or can be plugged directly into the convenience outlet on the bottom of the electrical interlock box if terminals 1 & 2 are NOT timer controlled. If possible, the air dryer should be plugged in 24 hours prior to system startup in order to pre-dry the desiccant beds.
Using a bonding wire conforming with all local, state and national electrical codes (normally a #8 AWG), ground the compo nents to the grounding bar on the electrical interlock box and bond the electrical interlock box to a true earth ground.
30
Ozone Systems
Maintenance & Trouble Shooting Manual
Parts & Warranty
CD-2000
Corona Discharge Ozone Generators
31
MaInTEnancE
Ozone Generator Care
A word of caution: There is extremely high voltage inside the ozone generator. If you suspect a problem, disconnect the power to the unit at the service disconnect box or main electrical panel and immediately contact your ClearWater Tech distributor. Inspect the ozone delivery line check valves daily for water seepage and replace the injector check valve yearly.
• Clean the ozone generator cabinet air filters:
These filters must be cleaned regularly. Depending on the location of the unit, it may be necessary to clean the air filters monthly. On the bottom of the cabinet are filter elements (see illustration below). These are air intake elements for the cooling fans and may therefore require the most frequent cleaning. All elements may be cleaned with soap and water and should be dried completely before reinstalling. Note: In a clean environment, these procedures may only need to be performed every three months. IMPORTANT: CLEAN THESE FILTERS REGULARLY! FAILURE TO DO
SO WILL PROMOTE OVERHEATING AND WILL VOID THE WARRANTY!
• Check valves:
The system is equipped with two check valves: one at the ozone generator ozone outlet and one on the venturi injector. The purpose of these check valves is to prevent water from backing up into the ozone generator. The Teflon ® ozone delivery line(s) should be inspected daily to insure water is not flowing back into the ozone generator. Check valves should be replaced yearly. Note: The only time it is possible for water to flow back toward the ozone generator is during a system shutdown. Always inspect for water seepage during this time.
Fan
Cabinet Bottom Plate
Fingerguard
Fan Filter Element
Fan Filter Grill
(snaps on and off)
• Dielectric tubes:
Dielectric tubes are located in the reaction chambers of the ozone generator. These tubes should be inspected periodically and cleaned if necessary. Once each year, remove one reaction chamber and inspect the dielectric tube for debris. If the tube is clean and free of any debris, oil or dirt, it may be replaced and no further maintenance is required. If the tube is dirty or cracked, all dielectric tubes must be inspected and cleaned. Cracked dielectrics should be replaced. Please consult your ClearWater Tech distributor, as the improper installation of the dielectric may cause safety problems!
Since the air that is introduced into the reaction chambers is high quality, the dielectric tubes should remain clean for at least one year before inspection is required.
32
Removal of the Dielectric Tubes
1. Disconnect all the power to the system, including panel breakers, service disconnect box and main circulation pump interlock.
2. Unplug the electrical terminal on the back of the drive module, disconnect the polypropylene barbed air fitting and the Kynar ® ozone fitting.
3. Remove the ozone reaction chamber(s) from the back plate.
4. Disconnect the high voltage wire from the coil. Remove the stainless steel nut and Kynar ® center rod from the center of the reaction chamber.
5. The Teflon ® end caps can now be gently removed by slowly pulling straight out. The glass dielectric will remain attached to one of the end caps.
6. If the dielectric tube is dirty, clean the glass with Isopropyl alcohol. Do not use a solvent that will leave an oily residue.
7. Clean the inside of the stainless steel reaction chamber with a wire brush as necessary, then wipe with Isopropyl alcohol.
8. Be sure all solvents have evaporated prior to reassembly.
Re-Installation of the Dielectric Tubes
1. Inspect the O-rings and replace as necessary.
2. Tighten the end caps so that they are approximately 1/8" from the aluminum extrusion.
3. Replace the reaction chambers and connect the air and ozone lines.
4. Connect the high voltage wire to the coil
5. Readjust the system as necessary (see operating instructions).
Maintenance Schedule
Yearly Service
1. Replace the cooling fan filter(s) on the ozone generator
2. Replace the air inlet particulate filter on the ozone generator
3. Replace the check valves
4. Remove and clean the glass dielectric in reaction chamber
5. Rebuild the solenoid valve on the electrical interlock box
6. Replace the flange gasket and clean the diffuser in the contact column
7. Regenerate the desiccant in the external indicating chamber on the AD-40 air dryer
Every Three Years
1. Replace the cooling fan(s) in the ozone generator
2. Disassemble and hone corona discharge reaction chamber(s), clean glass dielectric(s) and replace O-rings
Every Five Years
1. Replace the glass dielectric(s) in the reaction chamber(s) and replace O-rings
2. Replace the desiccant in the AD-40 air dryer
3. Replace the desiccant in the external indicating chamber on the AD-40 air dryer
33
CD-2000 OZONE GENERATOR COMPONENTS
SPECIFICATIONS:
Energy Required:
(120VAC models)
Energy Required:
(240 VAC models)
Dimensions:
Shipping Wt:
CD-2000
105 V min., 125 V max.
50/60 Hz, 1.6 Amps
208 V min., 240 V max.
50/60 Hz, 0.8 Amps
23" h x 20.25" w x 5.5" d
49 lbs.
34
EXPLODED VIEW OF CORONA DISCHARGE REACTION CHAMBER
35
POWER SUPPLY FOR P2000 & CD2000
Power Supply for
Multi-Cell Units
(100-120V Pt# PS300)
(208-240V Pt# PS305)
36
SOLENOID VALVE (ON OPTIONAL ELECTRICAL INTERLOCK BOX)
37
PARTS LIST FOR CD-2000
PART# DESCRIPTION
CKV20 Check valve CD 1/4" kynar - FPT, low pressure
FA40
FA41
FA42
FA43
FA44
Fan - Cooling, CD filter element only - 4"
Fan - Cooling, CD 120V 50/60 Hz - 4"
Fan - Cooling, CD 240V 50/60 Hz - 4"
Fan - Cooling, CD external finger guard - 4"
Fan - Cooling, CD internal finger guard - 4"
FLT34 Filter - inline particulate 1/4", for one to three cell CD systems
RCC6 Complete CD reaction chamber, 2” (does not include fittings)
RCC20 Cathode with heat sink and feet
RCC70 Dielectric only, all CD reaction chamber, 2”
RCC80 High voltage lead, all 2” CD reaction chambers
RCC103 High voltage end cap with O-Rings
RCC108 Non-high voltage end cap with O-Rings
ORS30 O-Ring package
DRM10 Drive Module - M-1500 or P-2000 complete, with HV transformer and mounting bracket
DRM12 Drive Module - CD-1500 or CD-2000 HO complete, with HV transformer and mounting bracket
HVT100 H.V. coil only for 2" CD reaction chamber
HWS2012 Mounting screws for reaction chamber
FTK325 Fitting, Kynar elbow for reaction chamber
FUS20 Fuse - CD, 5 Amp, slow blow
PS150 Power supply - 150 watt for M-1500 or CD-1500 100V-120V, 50/60 Hz
PS155 Power supply - 150 watt for M-1500 or CD-1500 208V-240V, 50/60 Hz
PS300 Power supply - 300 watt for P-2000 or CD-2000, 100V-120V, 50/60 Hz
PS305 Power supply - 300 watt for P-2000 or CD-2000, 208V-240V, 50/60 Hz
DES12 Desiccant, AD-40 heating chamber recharge, nonindicating
DES16 Desiccant, indicating chamber recharge, 1lb
SV200 Solenoid - 3 Way valve for air dryer w/o fittings,120V 50/60 Hz
SV500 Solenoid valve rebuild kit for Electrical Interlock Box
TM15 Timer solid state for the dryer 2” cube
ADP20 AD-40, part - heating element
ASP158 Maintenance Kit for M-1500 & CD-1500
ASP156 Maintenance Kit for P-2000 & CD-2000
38
OZONE GENERATOR TROUBLESHOOTING
PROBLEM/SYMPTOM
Unit does not turn on
Unit does not stay on
Unit cycles on and off
Individual drive indicator lights not on
POSSIBLE CAUSE
•
No power to unit
• Switch not turned on
•
Blown fuse
• Cover/door interlock not active
•
Incorrect wiring connections
•
•
SOLUTION
Check breakers
• Check switch
•
Replace fuse on bottom panel
• Check door interlock switch
replace cover
Check wiring (see manual)
•
Unit overheating
•
Clean fan filter, check fan
• Insufficient vacuum • Adjust injector vacuum, be sure
(should be -5 to -15 on SCFH gauge) check valves are properly installed
•
Defective solenoid
•
Inspect and repair/replace if necessary
• Defective check valve • Inspect and replace if necessary
•
Overheating
• Defective power
• Defective solenoid
•
No power to drive module
• Blown fuse
•
Drive module burnt out
•
Clean fan filter, check fan
• Check for constant power if not
timer controlled
• Inspect and repair/replace if necessary
•
Check drive module (see illustration)
• Replace fuse
•
Replace drive module
Unit trips circuit breaker
Water in unit or ozone delivery tubing
•
• Incorrect wiring
•
Incorrect circuit breaker
You receive an electrical shock
•
Incorrect wiring upon touching the unit
• Unit not grounded
•
Unit has been flooded
Insufficient vacuum
•
•
•
Check wiring (see manual)
•
Check and, if necessary, replace with
correct circuit breaker
Check wiring (see manual)
• Ground unit in accordance with local
codes
Return unit for major service or
completely disassemble and clean
•
Adjust injector vacuum
• Defective check valve(s) • Replace check valve(s)
•
Excessive back pressure on check valve
•
Back pressure not to exceed 40 psi -
if over 40 psi consult CWT distributor
Ozone smell present
You suspect that no ozone is being produced
•
•
Insufficient vacuum
• Loose internal fittings
•
Defective O-ring seals in
reaction chamber
•
Defective dielectrics
Defective reaction chamber
•
Drive module failure
• Dielectric failure
39
•
•
•
•
Adjust injector vacuum
• Inspect and tighten fittings
•
Check and replace if necessary
Check and replace if necessary
Check and replace if necessary
•
Touch the bottom of the coil replace if it is not warm
Inspect and replace if necessary
OZONE GENERATOR TROUBLESHOOTING
(continued)
PROBLEM/SYMPTOM
Unit seems noisy
Flow meter will not adjust
Vacuum gauge reads on pressure side
POSSIBLE CAUSE
•
Not properly secured to wall/floor
• Shipping damage
•
Fan blocked
•
Air preparation not operating
• Defective solenoid
•
Defective check valve
• Internal regulator out of adjustment
• Insufficient vacuum
•
Output solenoid defective
• Defective vacuum gauge
•
Loose Kynar ® compression fittings
SOLUTION
•
Bolt it firmly into place
• Locate and repair
•
Check and clear obstructions
•
Make sure air prep package is
set properly
• Check and repair (use solenoid bypass
kit described in manual)
•
Check and replace
• Check and adjust regulator
• Adjust injector vacuum
•
Check and replace or rebuild
• Replace vacuum gauge
•
Tighten all Kynar ® fittings
AIR DRYER TROUBLESHOOTING
PROBLEM/SYMPTOM
Air dryer not operating
Air dryer not producing dry air flow
Air dryer cold when operating
Desiccant indicator cartridge not blue in color
Air dryer not cycling
POSSIBLE CAUSE
•
No power to air dryer
• Switch not on
•
Fuse blown
• Insufficient vacuum
• Solenoid valve defective
•
No power to air dryer
• Switch not on
•
Fuse blown
• Defective heater cartridge
• Air leak
•
Desiccant saturated in storage
•
Timer defective
•
Relay defective
• Defective vacuum gauge
•
Loose Kynar ® compression fittings
SOLUTION
•
Check power connections
• Turn switch on
•
Replace fuse
• Adjust injector vacuum
• Replace solenoid valve
•
Check power connections & breakers
• Turn switch on
•
Replace fuse
• Replace heater cartridge
• Tighten fittings
•
Reactivate desiccant (as described
in manual)
•
Replace timer
•
Replace relay
• Replace vacuum gauge
•
Tighten all Kynar ® fittings
40
ELECTRICAL INTERLOCK BOX TROUBLESHOOTING
PROBLEM/SYMPTOM
‘MAIN POWER’ light not on
‘MCI’ light not on
POSSIBLE CAUSE
•
No power to electrical interlock box
• No neutral in 120 VAC supply
•
Light burnt out
•
120 VAC signal not connected
to terminal #4
• Light burnt out
•
No neutral in 120 VAC supply
‘VACUUM SYSTEM’ light not on
‘ORP’ light not on
•
•
•
•
•
No power to electrical interlock box
No MCI
No neutral in 120 VAC supply
•
No vacuum
Light burnt out
No power to electrical interlock box
• No MCI
•
No neutral in 120 VAC supply
•
No vacuum
•
System set to “MANUAL”
• No 120 VAC power to terminals
#5 and #6
• ORP level in excess of preset level
•
Light burnt out
Flow meter ball does not adjust • No vacuum
•
Vacuum leak
•
•
•
In and out hoses reversed
Defective solenoid
Defective check valve
SOLUTION
•
Check power connections & breakers
• Hook up neutral
•
Replace light
•
Jumper terminal from #1 to #4
• Replace light
•
Hook up neutral
• Check power connections & breakers
•
Jumper terminal from #1 to #4
• Hook up neutral
•
Adjust injector vacuum, or
Check tubing for leaks, or
Check for booster pump operation, or
Turn to “OFF” and back to reset
•
Replace light
•
Check power connections & breakers
• Jumper terminal from #1 to #4
•
Hook up neutral
•
Adjust injector vacuum, or
Check tubing for leaks, or
Check for booster pump operation, or
Turn to “OFF” and back to reset
•
Switch to “AUTO”
• Hook up power to these terminals
(see manual)
• Check input signal
•
Replace light
• Adjust injector vacuum
•
Check and tighten fittings
• Switch hoses
•
Inspect and repair or replace solenoid
• Check and replace check valve
41
DRIVE MODULE WIRING FOR CD2000
42
ClearWater Tech, LLC Limited One-Year Warranty
Summary of the Warranty
ClearWater Tech, LLC (“CWT”) makes every effort to assure that its products meet high quality and durability standards and warrants the products it manufactures against defects in materials and workmanship for a period of one (1) year, commencing on the date of original shipment from CWT, with the following exceptions: 1) The warranty period shall begin on the installation date if the installation is performed within 90 days of the original shipment from CWT; 2) The warranty period shall begin on the date of the bill of sale to the end user if the installation date is more 90 days after the original shipment date. To validate the warranty, a warranty card, accompanied by a copy of the bill of sale, must be returned to CWT and must include the following information:
• End user name
Complete address, including telephone number
• Date installed
Complete model and serial number information
• Name of company from which the unit was purchased
Repairs and replacement parts provided under this warranty shall carry only the unexpired portion of this warranty or 90 days, whichever is longer.
Items Excluded from the Warranty
This warranty does not extend to any product and/or part from which the factory assigned serial number has been removed or which has been damaged or rendered defective as a result of:
•
•
• an accident, misuse, alteration or abuse an act of God such as flood, earthquake, hurricane, lightning or other disaster resulting only from the forces of nature normal wear and tear operation outside the usage parameters stated in the product user’s manual use of parts not sold by CWT service or unit modification not authorized by CWT
•
•
check valve/solenoid valve failure
damage which may occur during shipping failure to meet service requirements as outlined in the I & O manual
Obtaining Service Under the Warranty
Any product and/or part not performing satisfactorily may be returned to CWT for evaluation. A Return Goods Authorization (RGA) number must first be obtained by either calling or writing your local authorized dealer, distributor or CWT direct, prior to shipping the product. The problem experienced with the product and/or part must be clearly described. The RGA number must appear prominently on the exterior of the shipped box(es). The product and/or part must be packaged either in its original packing material or in comparable and suitable packing material, if the original is not available. You are responsible for paying shipping charges to CWT and for any damages to the product and/or part that may occur during shipment. It is recommended that you insure the shipment for the amount you originally paid for the product and/or part.
If, after the product and/or part is returned prepaid and evaluated by CWT, it proves to be defective while under warranty, CWT will, at its election, either repair or replace the defective product and/or part and will return ship at lowest cost transportation prepaid to you except for shipments going outside the 50 states of the United States of America.
If upon inspection, it is determined that there is no defect or that the damage to the product and/or part resulted from causes not within the scope of this limited warranty, then you must bear the cost of repair or replacement of damaged product and/or part and all return freight charges. Any unauthorized attempt by the end user to repair CWT manufactured products without prior permission shall void any and all warranties. For service, contact your authorized dealer or distributor or CWT direct at (805) 549-9724, extension 23.
Exclusive Warranty
There is no other expressed warranty on CWT products and/or parts. Neither this warranty, or any other warranty, expressed or implied, including any implied warranties or merchantability of fitness, shall extend beyond the warranty period. Some states do not allow limitations on how long an implied warranty lasts, so that the above limitation or exclusion may not apply to you.
Disclaimer of Incidental and Consequential Damages
No responsibility is assumed for any incidental or consequential damages; this includes any damage to another product or products resulting from such a defect. Some states do not allow the exclusion or limitation of incidental or consequential damages, so that above limitation or exclusion may not apply to you.
Legal Remedies of Purchaser
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
THIS STATEMENT OF WARRANTY SUPERSEDES ALL OTHERS PROVIDED TO YOU AT ANY PRIOR TIME.
ClearWater Tech, LLC.
850 Capitolio Way Suite E, San Luis Obispo, California 93401 • (805) 549-9724 • Fax: (805) 549-0306
43

Download
Advertisement