Ecoflam MULTIFLAM 300.1 PR, MULTIFLAM 400.1 PR Manual 44 Pages
advertisement
GAS/HEAVY OIL BURNERS
MULTIFLAM 300.1 PR
MULTIFLAM 400.1 PR
Technical data
Operating instructions
Electric diagrams
Spare parts list
Gas train manual is separate www.ecoflamburners.com
EN
MULTIFLAM 300.1 PR TC GN35MBAR 400-50 BT
12-11-2014
3143961
EN
INDEX
MULTIFLAM 300.1
MULTIFLAM 400.1
0 1000
General warnings - Conformity declaration
Burner designation - Modular delivery system
Burner description
Electrical control panel
Gas train - Kit - Accessories: assembly to the burner
Technical data
Gas category by country
Working fields
Test boiler - Flame dimension
Overall dimensions
Oil operating mode - General safety functions
Gas operating mode - General safety functions
2000
Installation
Fitting the burner to the boiler
Heavy oil preparating ring
Oil connection
Heavy oil preparating ring scheme
Feeding line for heavy oil
Gas line
Pilot gas train, kit and accessories connection - Head loss diagram
Gas pressure loss diagrams
Electrical connections
Start-up: checking procedure
Exhaust gas test
Start-up oil side
Fuel selection - Start-up
Adjusting the max air flow rate
Firing head setting
GEFRAN Setting
Adjusting the max oil flow rate
Servomotor SQM50 - Air damper motor pre-setting
Adjusting the pump pressure
Adjusting the intermediate burner capacity
Servomotor SQM50 - Oil side final setting
Start-up gas side
Fuel selection - Start-up
Adjusting the max air flow rate
Firing head setting
Servomotor SQM50 - Air damper motor pre-setting
Adjusting the intermediate burner capacity
Pressure switch adjustment
Servomotor SQM50 - Gas side final setting
Maintenance program
Troubleshooting instructions
Operating troubles
Appendix
Control box - Damper actuators
Fluidics nozzle chart
Bergonzo nozzle tables
Pump and pressure regulators
Electrical diagrams
Spare parts list
2 www.ecoflam-burners.com
3000 4000 5000
22
23
24
24
24
24
25
26
26
26
27
27
12
12
13
14
15
16
17
18
19
21
6000 kW
6
7
7
8
3
4
5
5
10
11
8
9
30
32
34
35
35
36
37
40
41
44
28
28
28
28
28
29
29
29
420010601100
GENERAL WARNINGS - CONFORMITY DECLARATION
MULTIFLAM burners are designed for the combustion of natural gas and heavy oil. The design and function of the burners meet the standard EN267 and standard
EN676. They are suitable for use with all heat generators complying with standard within their respective performance range.
Any other type of application requires the approval of ECOFLAM.
Installation, start-up and maintenance must only be carried out by authorised specialists and all applicable guidelines and regulations must be complied with.
EN 267
Automatic forced draught burners for liquid fuels.
EN 676
Forced-draught gas burners.
EN 60335-1, -2-102
Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances
BURNER DESCRIPTION
MULTFLAM burners are progressive mechanical fully automatic monoblock devices.
Emissions values may differ, depending on combustion chamber dimensions, combustion chamber load and the firing system (three-pass boilers, boilers with reverse firing).
GAS LINES
When installing the gas lines and gas train, the general EN676 directives and guidelines must be observed.
EN676 compulsory kit and accessories in order to comply to the safety regulations.
Additional accessories and kits shall be installed by the installer in accordance to the local safety regulations and codes of practise.
PACKAGING
The burner, the gas train and all the additional components are supplied in a modular system of packages according to the configuration ordered that based on the country of installation shall follow the applicable standards and the local rules and code of practise.
The following standards should be observed in order to ensure safe, environmentally sound and energy-efficient operation:
INSTALLATION LOCATION
The burner must not be operated in rooms containing aggressive vapours (e.g. spray, perchloroethylene, hydrocarbon tetrachloride, solvent, etc.) or tending to heavy dust formation or high air humidity.
Adequate ventilation must be provided at the place of installation of the furnace system to ensure a reliable supply with combustion air.
Declaration of conformity for dual fuel burners
We,
Ecoflam Bruciatori S.p.A.
declare under our sole responsibility that the products:
MULTIFLAM 300.1 PR
MULTIFLAM 400.1 PR conform to the following standards:
EN 676: 2008
EN 267: 2010
EN 60335-1: 2008
EN 60335-2-30: 2006
EN 60335-2-102: 2007
EN 55014-1: 2008 + A1: 2009
EN 55014-2: 1998 + A1: 2001 + A2: 2008
These products are built in accordance with the following directives
2006/42/EC Machinery directive
2004/108/EC EMC directive
2006/95/EC Low voltage directive
2009/142/EC Gas appliances Directive
CE certification, when required, must be done at installation site by the end user
Resana, 20th December 2010
M. PANIZZON
!
BURNER SELECTION: Type of operation and configuration must be done by professional personnel in order to grant correct working of the burner. Installation, start-up and maintenance must be carried out by authorised specialists and all applicable guidelines and regulations
(including local safety regulations and codes of practise) must be observed.
We accept no responsibility for damage arising from:
- inappropriate use;
- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts;
- non authorised modifications made on the burner.
Final delivery and instructions for use
The firing system installer must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator,
They should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year.
Depending on the type of installation, shorter maintenance intervals may be necessary.
It is advisable to take out a maintenance contract to guarantee regular servicing.
EN
Ecoflam burners have been designed and built in compliance with all current regulations and directives.
All burners comply to the safety and energy saving operation regulations within the standard of their respective performance range. The quality is guaranteed by a quality and management system certified in accordance with ISO 9001:2008.
420010601100
www.ecoflam-burners.com
3
EN
BURNER DESIGNATION
MULTIFLAM 300.1 PR TC SGT 230-400-50
RANGE NAME BY FUEL TYPE
MULTIFLAM Dual fuel (Gas / Heavy oil)
MODEL SIZE (Gas: kW; Oil: kg/h)
MULTIFLAM 300.1
300 kg/h - 3000 kW
-
EMISSIONS
Standard Class 2 - GAS EN676 (<120 mg/kWh)
OPERATION TYPE
PR
MD
E
2 stages progressive mechanical gas / oil
2 stages modulating mechanical with PID
2 stages modulating electronic
HEAD TYPE
TC
TL
Short head
Long head
FUEL
LPG
Natural gas
Liquid gas
BIOGAS Biogas
EQUIPMENT
SGT Separate gas train
ELECTRICAL POWER SUPPLY
230-400V/50Hz 230-400 Volt, 50 Hz
MODULAR DELIVERY SYSTEM
Dual fuel burners
All dual fuel burners are delivered in separate set/box, i.e. burner body including combustion head and separate gas train with separate additional kit and accessories that shall complete the gas train or the burner according to the applicable standard.
Kit and accessories are delivered separately.
Gas train - GTCP - KITS - Accessories
All gas and dual fuel burners gas trains are delivered separately in different models and configuration.
Export configuration gas train completion are available but it is mandatory for the local installer in this case to comply to the local safety regulations.
For burners over 1700 kW gas train connection pipe must be ordered.
Kits and accessories are managed and delivered separately.
Component type
BBCH
GTCP
GT
Burner Body with Combustion Head (without gas train)
Gas Train Connection pipe
Gas Train (delivered separately)
4 www.ecoflam-burners.com
420010601100
BURNER DESCRIPTION
1
5
12
4
21
13
14
18
15
7
9
6
17
8
1
3
2
11
EN
20
23
19
24
Control panel
Main switch I/0
Resistor lamp
Heavy oil lamp
Gas lamp
GTCP
LEGENDA
1. Housing
2. Electrical control panel
3. Blower motor
4. Pump and pump motor
5. Hinge flange
6. Blast tube
7. Burner head
8. Burner fixing flange
9. Air flap regulation
10. Fan wheel / blower
11. Silencer
12. Lifting eyebolts
HLR
HLoil
GEFRAN
SA
I 0 II o-G
POS 0: STOP
POS 1: NAFTA
POS 2: GAS
DISPLAY BCU LAMTEC
RWF 50
HLgas
13. Mechanical cam gas
14. Mechanical cam oil
15. Servomotor for gas and air
16. Gas train
17. Pilot gas train
18. Oil pressure regulator
19. Gas filter
20. Ball valve
21. Oil coil
22. Nozzle rod
23. Antivibration coupling
24. Tightness control
GTCP. Gas train connection pipe
GEFRAN regulator
Modulating unit RWF 40 (optional)
Selector (GAS / 0 / HEAVY OIL)
Display
SABK
420010601100
www.ecoflam-burners.com
5
EN
BURNER DESCRIPTION
Gas train - Kit - Accessories: assembly to the burner
To be supplied by the installer 155
160
314
144 Gas governor
151 Gas train Landis VGD....
155 Pilot gas valve
160
Kit tightness control (optional)
313 Min.gas pressure switch
314 Max.gas pressure switch (optional)
349 Air/gas damper motor
100
144
313
143
Gas
141
142
151
150
M
349
To be supplied by the installer
Air
MATCHING GAS TRAIN WITH DIAGRAM OF PRESSURE DROPS
ARE IN THE DEDICATED SECTION OF THIS MANUAL
120
M
349
Ecoflam gas trains are delivered separately for all gas and dual fuel burners and are available in different configurations:
Double gas valves with actuators and regulator VGD Siemens and min pressure switch + ACS gas filter
1
VGD 20.503 Rp 2” / VGD 40.065 - 40.080 - 40.100 - 40.125
2 3 9 5 8
7 6
11 10
1. Main gas pipe
2. Ball valve
3. Antivibration coupling
5. Min gas pressure switch
6. Safety gas valve + 10. Actuator
7. Working gas valve + 11. Actuator
8. Gas leakage control
9. Gas filter
KIT - MAX Gas pressure switch
ACS - Gas train connection pipe
ACS
ACS
GAS TRAIN
KITTC *
ACS
KITPRES
GTCP **
!
GTCP-...* WARNING: in order to fit the gas train, the corresponding connection pipe must be ordered (GTCP size and fitting depend on the burner and the gas train selected).
HOW TO INSTALL THE GAS TRAIN INTO THE BURNER AND CALCULATE THE OVERALL DIMENSIONS : refer to the dimension page and the gas train manual for all detailed information
!
WARNING: EN676 compulsory kit and accessories in order to comply to the safety regulations. Additional accessories and kits shall be installed by the installer in accordance to the local safety regulations and codes of practise.
Gas governor / Filter Tightness control Modulation Kit Max Pressure switch Other accessories
FGDR - FILTER
Compulsory EN676
KITTC- Model
Compulsory > 1200 kW
KITMD-RWF50
Probe-...
KITPRES50
KITPRES150
6 www.ecoflam-burners.com
420010601100
TECHNICAL DATA
MODEL
Thermal power max.
Thermal power min.
Operation mode
Regulation ratio nominal
Fuel
Emission class std
Control unit
Gas train
Gas connection
GAS natural pressure
LPG pressure
Air regulation
Air flap control with servomotor
Air pressure switch
Flame monitoring
Ignitier
Motor
Rpm
Voltage
Total power consumption operation
Weight body BBCH
Electrical panel protection level
Sound pressure level without silencer
Sound pressure level with silencer
Ambient temperature storage
Ambient temperature use
Oil pump
Oil pump motor
Nozzles
Fuel thermo regulator
Electrical pre-heater dB(A)
Lab tests
Min/Max
Model kW
Type
Type kW mbar
Type
Model kW
N°
V/Hz
Type
GT
GTCP mbar mbar
Type
Model
W
Kg
IP kW kcal/h kg/h kW kcal/h kg/h
Type
Type
Type
MULTIFLAM 300.1
3.000
2.580.000
264
630
541.800
88
MULTIFLAM 400.1
3.900
3.354.000
343
875
752.500
115
Progressive mechanical heavy oil / gas - Modulating with PID
1÷4 GAS - 1÷3 HEAVY OIL
G20 (L.C.V. 8.570 kcal/Nm 3 ), G25 (L.C.V. 7.370 kcal/Nm 3 )
G31 (L.C.V. 22.260 kcal/Nm 3 ), G30 (L.C.V. 29.320 kcal/Nm 3 )
Heavy oil (L.C.V. 9.800 kcal/kg max visc. 50°E at 50°C)
Standard Class 2 GAS EN676 (<120 mg/kWh)
LAMTEC BT340
VGD separate gas train + Filter + KIT Tightness control + Other KIT/ACS
Gas connection range RP 50 to DN 100 depending on the gas train selected
22÷700
45÷700
Air flap
30÷700
70÷700
Air flap
LAMTEC
1…10 mbar
UV cell QRA
BRAHMA
5,5
2.800
7,5
2.800
230/400 V - 50 Hz
27.000
30.000
IP55
87,3
81,8
-20°…+70° C
-10°…+60° C
TA3
1,1 kW according to the output requested
GEFRAN
18
IP55
88,3
83
TA3
1,1 kW
21
GAS CATEGORY BY COUNTRY
Gas category
II
2R , 3R
II
2H
,
3P/B
I
3R
Country
BE CH CZ DE DK ES FI FR GB GR HU IE IT LU NL PT SE EE LT LV NO PL SK SI -
AT -
CY MT -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
EN
420010601100
www.ecoflam-burners.com
7
EN mbar 16
14
12
10
8
6
4
2
0
0
0
0
WORKING FIELDS
MULTIFLAM 300.1
MULTIFLAM 400.1
500
500
50
1000
1000
100
1500
1500
150
2000
2000
200
2500 3000
2500
250
3500
3000
300
4000
3500
350
Calculation of burner output
QF = Burner output (kW)
QN = Rated boiler output(kW)
η = Boiler efficiency (%)
QF =
QN x 100
η
4500 kW kcal/h*1000
Working fields
The working field shows burner output as a function of combustion chamber pressure.
It corresponds to the maximum values specified by EN 676 measured at the test fire tube.
Boiler efficiency should be taken into consideration when selecting the burner.
kg/h
TEST BOILER - FLAME DIMENSIONS
FLAME LEN
G
H
T G
AS BURNERS
L (m) 11
10
9
8
7
6
5
4
3
2
0
1000
1000
100
2000
2000
200
3000
300
3000
4000
400
4000
5000
500
5000
6000
600
6000
7000
700
7000
8000
800
8000
9000
900
9000 10000 11000
10000
1000
11000
1100
12000
1200
13000
1300
12000
14000
1400
13000
15000
1500
14000
16000
1600
15000 kcal/h x 1000
17000
1700 kW
Nm3/h
FLAME DIAME
T
ER
G
AS BURNERS
Ø (m) 2
1,8
1,2
1
0,8
1,6
1,4
0,6
0,4
0,2
0
1000
1000
2000
2000 3000
3000
4000
4000
5000
5000
6000
100 200 300 400 500 600
6000
7000
700
7000
8000
800
9000
900
8000
10000
1000
9000
11000
1100
10000
12000
1200
11000
13000
1300
12000
14000
1400
13000
15000
1500
14000
16000
15000 kcal/h x 1000
17000 kW
1600 1700 Nm3/h
8 www.ecoflam-burners.com
The burner/boiler matching does not pose any problems if the boiler is CE typeapproved.
If the burner must be combined with a boiler that has not been CE type-approved and/or its combustion chamber dimensions are clearly smaller than those indicated in diagram, consult the manufacturer.
The firing rates were set in relation to special test boilers, according to EN676 -
EN267 regulations.
The sizes are indicative and dipend on the configuration, to the combustion chamber pressure and to the draught.
The values have been taken out from tests executed with flame tubes.
The dimensions of the flame are made in test boiler in laboratory without resistence therefore exists max and min lenght that take into account the difference in lenght that comes from the boiler backpressure.
Example:
Burner thermal output = 8000 kW;
L flame (m) = 5 m (medium value)
D flame (m) = 1 m (medium value)
WARNING: Some flame modifications can be done in our FLEXSHOP in the factory in order to shape the flame and adapt it to some special boiler or application.
420010601100
OVERALL DIMENSIONS
E D - D1
I
O
0
1
2
3
0
1
B
A
C
66 8 L
M
SUN EC
N
MULTIFLAM 300.1
MULTIFLAM 400.1
D = Short head
D1= Long head
Dimensions (mm)
A B
1288 610
1288 610
C
678
678
D
330
345
D1 E F
530 1130 290
545 1130 320
G
471
471
G1
750
750
H1
746
746
I
315
315
L M
315 M16
315 M16
N
195
195
O
250
250
EN
HOW TO INSTALL THE GAS TRAIN
INTO THE BURNER AND CALCULATE
THE OVERALL DIMENSIONS: refer to the dimension page and the gas train manual for all detailed information
420010601100
Burner-boiler mounting flange
Fixing hole dimensions are “I” and “L” as per dimension table.
Boiler hole shall be done according to the blast tube dimension “F” plus
15-25 mm in order to be able to extract it during maintenance.
315
365
WARNING: Please follow the suggested dimension for the hole on the boiler flange in order to fit the burner. Make sure that between the boiler and the blast tube proper insulation is fitted.
Packaging (only burner)
X Y Z
MULTIFLAM 300.1
1580 1630 1090
MULTIFLAM 400.1
1580 1630 1090 kg
X
Y
www.ecoflam-burners.com
9
Z
EN
OIL OPERATING MODE - GENERAL SAFETY FUNCTIONS
START-UP MODE
As soon as the furnace system is required to supply heat, the burner control circuit will close and the program flow started.
When the program has come to its end, the burner will be turned on.
An automatic test is made for the tightness of the gas valves prior to each burner start.
The air damper is in its closed position when the burner is out of operation.
The electric actuator will open the closed air damper to its full-load position so that the burner will ventilate the furnace and the exhaust hoods with the specified air rate.
Shortly after the preventilation process has been started the lack-of-air cut-out must change over to operating position within a certain time, i.e. the minimum air pressure setting must be reached and maintained until the burner is turned off. At the end of the specified pre-ventilation time the air damper will be moved into its partial-load position in a linked control concept with the gas damper. This operation will be followed by the pre-ignition procedure and the oil feed start.
The solenoid valves will open and thus allow the pressurized oil to flow to the nozzle and to the return line.
The oil will be atomized, mixed with the combustion air and ignited.
A safety period is provided to allow the flame to develop a proper and steady pattern.
On the termination of the safety period, a flame signal must have been received by the control box via the flame monitor and remain on until the regular shut-off.
The startup program of the burner has now been completed.
OIL OPERATING MODE
After the flame has developed the load regulator will be enabled which brings the burner into its operating position.
The load regulator will now control the burner automatically between its partialload and full-load stages.
Depending on the heat demand, the electric actuator of the mechanical compound control system will be fed with the OPEN or CLOSE signal via the regulator and thus increase or decrease the oil and air flow rates.
This compound control system will vary the positions of the oil control valve and air damper and thus regulate the oil flow rate in conjunction with the air flow rate. The burner can either be controlled in twostage sliding mode or, if a respective controller is provided, in stepless control mode.
The stepless control will allow the burner to be operated at any desired stage between its partial-load and full-load positions. The burner will be turned off from its partial-load position. The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney.
The interior cooling losses will be greatly minimized.
GENERAL SAFETY FUNCTIONS
In case a flame does not develop when starting the burner (fuel release) the burner will shut off at the end of the safety period (shut-off on trouble).
A shut-off on trouble will also occur in the case of flame failure during operation, air flow failure during the pre-ventilation phase and pressure failure during the whole period of burner operation.
Any failure of the flame signal at the end of the safety period and a flame signal during the pre-ventilation phase (external light control) will result in a shut-off on trouble with the control box being locked.
The trouble is indicated by the trouble signal lamp lighting up.
The control box can be unlocked immediately after a shut-off on trouble by pressing the unlocking key. The program unit will return to its starting position and proceed with the restart of the burner.
A voltage failure will result in a regular shut-off of the burner. Upon voltage recovery there may be an automatic restart unless another interlock is provided, e.g. by the safety system. In any case of trouble the fuel oil supply will be shut off right away. The program unit will stop at the same time causing also the trouble location indicator to stop.
The symbols will indicate the kind of trouble.
10 www.ecoflam-burners.com
420010601100
GAS OPERATING MODE - GENERAL SAFETY FUNCTIONS
START-UP MODE
As soon as the furnace system is required to supply heat, the burner control circuit will close and the program flow started.
When the program has come to its end, the burner will be turned on.
An automatic test is made for the tightness of the gas valves prior to each burner start.
The air damper is in its closed position when the burner is out of operation.
The electric actuator will open the closed air damper to its full-load position so that the burner will ventilate the furnace and the exhaust hoods with the specified air rate.
Shortly after the preventilation process has been started the lack-of-air cut-out must change over to operating position within a certain time, i.e. the minimum air pressure setting must be reached and maintained until the burner is turned off. At the end of the specified pre-ventilation time the air damper will be moved into its partial-load position in a linked control concept with the gas damper.
The ignition transformer will be started.
At the end of the pre-ignition time the ignition gas solenoid valves will be opened to allow gas to flow into the pilot burner.
The ignition electrodes incorporated in the pilot burner will ignite the ignition gas.
The ionization probe gives flame signal to control box so that the safety shut-off valves will be opened.
The gas will be fed to the gas nozzles via the gas damper while combustion air is supplied by the fan.
Gas and air will be intensively mixed in the mixing unit and ignited by the pilot flame with a specified safety period (minimum furnace heat generating rate).
After the safety period has run down the pilot burner will be turned off.
Attention:
If there are shut-off dampers in the flue gas tract they must be completely open.
Otherwise there will be a high danger of low-speed detonation or explosion!
GAS OPERATING MODE
After the flame has developed the load regulator will be enabled which brings the burner into its operating position.
The load regulator will now control the burner automatically between its partialload and full-load stages. Depending on the heat demand, the electric actuator of the compound control system will be fed with the OPEN or CLOSE command via the regulator and thus increase or decrease the gas and air flow rates.
This compound control system will vary the positions of the gas control valve and air damper and thus regulate the gas flow rate in a linked concept with the air flow rate. The burner can either be controlled by a 2-stage sliding or, if a respective controller is provided, a stepless control concept.
The stepless control will allow the burner to be operated at any desired stage between its partial-load and full-load positions.
The burner will always be turned off out of its partial-load position.
The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney.
The interior cooling losses will thus be greatly minimized.
Scheme of functioning
LEGENDA
141: ball valve
142: filter
143: antivibration coupling
150: butterfly valve
151: gas train Landis VGD
155: pilot gas valve
176: oil pump
178: solenoid valve
180: nozzle rod
184: output control valve
311: return oil pressure switch
313: min gas pressure switch
CV: check valve
RL: return line
VL: suction line
VLO: working oil valve
V
L
V L O
C
V
EN
C V
420010601100
www.ecoflam-burners.com
11
EN
INSTALLATION
Fitting the burner to the boiler
!
WARNING: handling and moving operations must be carried out by specialised personnel.
Use the eyebolts to lift the burner in order that it will not overturn and fall down.
To perform the installation of the burner into the boiler drill the boiler plate according to the dimension given on this manual and place the burner towards it by lifting and moving the burner by means of eyebolts.
Place the gasket on the burner flange and install the burner into the boiler by fixing nuts into the bolts.
The space between the blast tube and the boiler lining must be sealed with appropriate insulating material.
BURNER LINING
Check before burner installation:
1. Depending on the type of boiler (reverse flame or three pass) check the burner blast tube installation depth according to the data specified by the boiler manufacturer or consult the burner producer.
2. From the factory the nozzle for progressive version must be specified from the customer according to boiler output and combustion chamber geometry, otherwise we will select the nozzle for the 80% capacity of the burner.
3. Check the ignition electrodes and the nozzle on the burner head as per factory setting (see figures).
The setting of the mixing and ignition unit according to the boiler output will be performed during commissioning procedure.
4. Check that the head is preset at 50%.
Position of the electrodes - nozzle installation
3 ÷ 4 mm
Ignition Electrode
5 ÷ 6 mm
FUEL SELECTION MODE
0 - STOP
1 - OIL
2 - GAS 0=STOP
Standard version running on 1=OIL manual fuel selection mode and on request kit for
2=GAS automatic fuel changeover.
The automatic changeover system can be triggered by a gas pressure switch or by a timer.
12 www.ecoflam-burners.com
420010601100
INSTALLATION
Heavy oil preparation ring
!
WARNING: make sure that the feeding line is properly dimensioned and is in compliance the local safety rules and code of practise in the country of installation.
All installations using heavy oil burners have to be completed with a forced oil preparation ring in order to guarantee oil supply to the burner at suitable temperature and pressure
(temperature +/- 50° C, pressure 3 bar).
For heavy oil with more than 50°E at 50°C
Ecoflam recommends to lower the maximum output of 10-20% and work in excess of air in order to grant better operation and reduce maintenance.
STANDARD SYSTEM COMPOSITION FOR LIGHT OIL
AND HEAVY OIL HEATING AND PUMPING UNIT
I. Feeding and filtering system
II. Fuel heating system for reducing oil viscosity plus service tank
III. Forced oil supply system “RING”
Installation with heavy oil must provide to the burners:
- CONSTANT PRESSURE
- CONSTANT TEMPERATURE
To size correctly the ring for the heavy oil supply consider the diagram of the pre-heating temperature of the heavy oil according to viscosity and the pump pressure according to temperature.
Ecoflam heavy oil and dual fuel heavy oil burners do have in the electrical panel the fuel temperature device GEFRAN that adjusts the temperature of the heavy oil and grants temperature stability.
PRE-HEATER UNIT
Ecoflam heavy oil burners are delivered with electrical pre-heater assembled into the burner body or in a separate skid.
Additional Forced system “OIL RING” can be design and delivered assembled on skid/frame or offered as single component.
ACCESSORIES
Service tanks + Pumps units.
Quotation on request depending on output and configuration.
RACOMMENDED OIL SUPPLY PRESSURE b a r
6
3
2
1
0
5
4
5 0
420010601100
1 0 0
O il te m per a ture
1 5 0 C
°
www.ecoflam-burners.com
13
EN
EN
INSTALLATION
Oil connection
!
WARNING: make sure that the feeding line is properly dimensioned and is in compliance with the local safety rules and code of practise in the country of installation
HYDRAULIC CIRCUIT
HEAVY OIL FEEDING
176: oil pump
178: solenoid valve
180: nozzle rod
184: output control valve
311: return oil pressure switch
CV: check valve
RL: return line
VL: suction line
VLO: working oil valve
VL
1
76
VL O
1
78
1
80
1
84
3
11
OIL PRESSURE CONTROL (FEED)
The feed pressure is controlled by means of the pressure regulator installed in the pump and should be set at 25. The pressure regulator is operated by turning its screw. Make sure to fill the pump with oil prior to taking into operation.
PUMP BLEEDING
Open the feed and return stop valves and ensure the ring line (if any) is in operation.
Reduce the oil pressure at the pressure regulating valve. Turn on the pump by pressing the contactor.
Check the pump for proper direction of rotation. Check for proper oil delivery and absence of leaks in the hydraulic oil system. For bleeding the pump open the pressure gauge connection, for example.
When taking the burner into operation pro ceed by gradually increasing the pressure to operating level (25 bar).
CHECKING THE PRESSURE
(OIL SUCTION PRESSURE)
The maximum permissible vacuum is 0,4 bar. At higher vacuum levels the fuel oil will tend to separate air from oil which may lead to operating trouble. In the ring line mode of operation the recommended oil pressure is 2 bar.
close to the burners as possible and to arrange them in a way that the boiler door and the burner can be swing out without any obstruction.
Refer to the technical documentation for the line dimensions for the feed and return lines from the stop valves to the tank.
OIL FILTER
A filter must be installed upstream of the pump to protect the oil pressure pump and the hydraulic system.
OIL CONNECTION
Hoses are used for connection to the oil lines and stop valves. The hoses must be installed according to the applicable standards (relieved of tensile load, free of distortion) to avoid kinking and exclude the danger of breakage. Take care when mounting the oil lines to bring their ends as
INSTALLATION OPTIONS
• Two-line installation (separate feed and return lines without delivery pump).
• Ring line system (with delivery pump and gas-air separator).
10
9
LEGENDA
1. Inlet
2. Return
3. Bleed and pressure gauge port
4. Vacuum gauge port
5. Pressure adjustment
6. Nozzle outlet
7. Heater
8. Hose
9. Oil filter
10. Oil ball valve
8
8
!
WARNING: Check that the pump rotation is correct and before start up it has been pre-filled
14 www.ecoflam-burners.com
420010601100
INSTALLATION
Heavy oil preparation ring scheme
LEGENDA
1 - Burners
2 - Service tank
3 - Electric heaters
4 - Safety and operation thermostat
5 - Level switch (working + safety )
6 - Heating coil
7 - Self-cleaning oil filter
8 - Load pumps
9 - Ring pumps
10 - Oil ring control pressure device
11 - Heating cable
12 - Main heavy oil storage tank
13 - Heating coil
EN
H o t w ater
H o t w ater
420010601100
R eturn
12
1 3 sect io n h o t
w ater p i pe oil p i pe heat i n g cab l e h o t
w ater p i pe oil p i pe i nsu l at io n
www.ecoflam-burners.com
15
EN
INSTALLATION
Feeding line for heavy oil
The pumps that are used can be installed both into single-pipe and double-pipe systems:
Single-pipe system: a single pipe drives the oil from the tank to the pump’s inlet that deliver the pressurized oil to the nozzle and part of the oil not used goes back to the pump. With this single pipe the by-pass plug must be removed and the return port must be sealed with steel plug and washer.
Double-pipe system: this is the default solution from the factory.
The return pipe send the excess oil from the pump to the tank. Depending on the type of pump used to change from a 1-pipe system to a 2-pipesystem, insert the by-pass plug (as for ccw-rotation referring to the pump shaft).
Note for commissioning: during commissioning, the filter, pipelines and pumps must be pre-filled with fuel oil and vented.
The direction of rotation of the motor should be checked. When commissioning it must be ensured that pump never run dry.
NOZZLE SELECTION
Please refer to diagram to select Ecoflam recommended nozzle for the output that is required given the output necessary in the installation.
Regular maintenance is highly recommended.
Nozzle has to be cleaned in petrol or paraffin and if filter or other parts are defective or damaged the nozzle must be replaced.
NOZZLE CHART IS AVAILABLE ON APPENDIX PAGE
SUNTEC TA
Oi l under suction
Oi l under pressure
Vacuum or in l et pressure gauge port
By-passed oi l returned to tan k, or to suction
Pressure gauge port
I nta k e from T an k
By-pass p l ug inserted
Pressure ad j ustment
T o no zzl e
R eturn
T W O P I PE
I NS T ALLA TI ON
I nta k e from T an k
By-pass p l ug remo v ed
ONE P I PE
I NS T ALLA TI ON
R eturn p l ugged
16 www.ecoflam-burners.com
420010601100
INSTALLATION
Gas line
CONNECTION DIAGRAM FOR BURNERS WITH
SEPARATE PILOT (GAS TRAIN LANDIS VGD...)
100 Burner
To be supplied by the installer 155
160
151 Gas train Landis VGD....
155 Pilot gas valve
160 Kit tightness control (optional)
313 Min.gas pressure switch
314 Max.gas pressure switch (optional)
349 Air/gas damper motor
144
313
314
100
141
143 142 150
Gas
151 M
349
To be supplied by the installer
120
Air
GAS VALVES AND INSTRUMENTS GROUP
The gas valves and instruments group used with the furnace will be selected according to the specific requirements to be met by a burner system.
The following factors must be taken into account:
• burner output
• furnace back pressure
• gas pressure loss of the burner head
• gas pressure losses of the gas valves and instruments group
M
349
NOTE: Only gas trains assembled by the burner manufacturer and approved in accordance with the burner test specifications.
EN676 compulsory kit and accessories in order to comply to the safety regulations.
Additional accessories and kits shall be installed by the installer in accordance to the local safety regulations and codes of practise.
EN
GAS CONNECTION PRESSURE
A minimum connection pressure must be available upstream of the burner gas valve to ensure the proper functioning of the burner.
WARNING: the total gas pressure loss must always be smaller than the available gas flow pressure.
For the installation of the valves and instruments group take care to observe the mounting instructions supplied by their manufacturers (these are packed with the equipment).
The gas line installed to the burner must be dimensioned in accordance with the throughput rate and the available pressure.
For selecting the nominal bore “DN” of the gas valves and instruments group care should be taken to observe the flue resistance of the boiler and the gas pressure loss of the burner and valves and instruments group.
Take care to observe the correct order of installation and direction of flow (arrow on housing).
Check the valves and instruments and connection pieces for absence of dirt particles and foreign matter before installation and initial operation. To provide effective conditions for start-up make sure the distance between the burner and the gas stop valve is as short as possible.
LEAK TEST
The gas line upstream of the burner gas valves and instruments group must be installed in accordance with the applicable regulations, checked for absence of leaks, vented and certified accordingly by the gas installation company. The screwed unions and flanged joints must be checked for proper tightness (by making a pressure test). The leak test must be made under pressure using approved foaming agents which do not cause corrosion. For steam boiler furnaces the result of the leak test must be duly certified.
GAS VALVES AND INSTRUMENTS GROUP
The gas valves and instruments group can be connected directly to the gas feed line.
VENTING
Prior to taking the burner into operation or after any repair work make sure to vent the complete gas feed line and the gas valves and instruments group into the open atmosphere (e.g. by means of a hose) taking care to avoid any hazards.
In no case should the gas line be vented into the heating or furnace chambers.
Make use of a test burner to check the gas-carrying spaces are free from an inflammable gas mixture.
SUPPORT
The valves and instruments group must be supported with a telescopic jacking member or similar during and after installation (e.g. on filter and valve).
JOINT
It is recommended to provide an easy to disconnect joint (with planar sealing faces) to facilitate repair work on the boiler
(furnace) and allow the boiler door to be swivelled out if required.
420010601100
www.ecoflam-burners.com
17
EN
INSTALLATION
Pilot gas train, kit and accessories connection - head loss diagram
PILOT GAS TRAIN CONNECTION
The pilot gas train is already installed to the burner and shall be connected to the main gas supply line preferebly with flexible pipe.
The pilot gas train is composed of n° 2 safety valves and n°1 gas governor and filter. Max inlet pressure 1 bar.
WARNING: Pilot gas train must be connected according to the drawing of the gas line.
GAS VALVES ADJUSTMENT
Note : the pilot valves are pre-adjusted in the factory. To increase or reduce the gas flow act on the gas governor.
–
GAS GOVERNOR ADJUSTMENT
The gas governor, with built-in filter, must be installed so as to stabilise the outlet gas pressure and to avoid that eventual impurities reach the gas valve. To increase gas pressure, remove the cover of governor and turn screw C.
Unscrew screw C to reduce pressure, then fit the cover.
Note : the inlet gas pressure must not be higher than the specified max. gas pressure.
+
C
KITTC- Tightness control
Tightness control is provided as a kit and shall be assembled into the main gas train according to the instructions of the gas train separate manual.
Tightness control
KITTC- Model
Compulsory > 1200 kW
Modulation Kit
KITMD-RWF50
Probe-...
KITPRES... Maximum pressure switch assembly
Maximum pressure switch is provided as a kit and shall be assembled into the main gas train according to the instructions of the gas train separate manual.
KITMD-RWF40 PID regulator
All progressive burner can be turned modulationg with the installation of the PID that regulates the output combined with a probe.
GAS PRESSURE LOSS DIAGRAM: combustion head - platform 320
The diagram provides combustion head pressure loss. To have pressure loss combined with the different type of gas train you must refer to the pressure loss diagrams.
WARNING:
Note that the head loss diagram is only indicative and does vary depending on the setting of the head.
Max Pressure switch
KITPRES50
KITPRES150
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
60
Multiflam 300.1
Multiflam 400.1
80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400
OU T PU T - Stm3/h
18 www.ecoflam-burners.com
420010601100
INSTALLATION
Gas pressure loss diagrams
!
PRESSURE DROP includes: “COMBUSTION HEAD + GAS TRAIN + GAS GOVERNOR & FILTER” as per EN676 Standard.
Back pressure of boiler (or other applications) must be added/included in order to have the total min pressure drop.
Burner Gas train
Advisable gas governor & filter
Spring color
Inlet gas pressure
MIN [mbar]
Inlet gas pressure
MAX [mbar] no 20 700
VGD 40.100
neutral
BLU 3000.1 PR
MULTICALOR 300.1
MULTIFLAM 300.1
VGD 40.080
VGD 40.065
FILTER DN 100 no
FILTER DN 80 no
FILTER DN 65 neutral neutral
22
30
35
45
55
700
700
700
700
700
VGD 20.503
no
FILTER 2" neutral
80
100
600
600
Diagram
1C
1C.2
EN
60
55
50
45
40
35
30
25
2 0
1
5
1
0
5
100
natural gas
150 200 250 flow m 3 /h
300
VGD 40.065 + F- DN65
VGD 40.065
VGD 40.080 + F- DN80
VGD 40.080
VGD 40.100 + F- DN100
VGD 40.100
350
1C
150
140
130
120
110
100
90
80
70
60
180
170
160
50
40
30
20
10
0
100 natura l gas
150 200 250 flow m 3 /h
300
VGD 20.503 + F- 2"
VGD 20.503
350
1C.2
LEGENDA
Pf: Back pressure of furnace
Pb: Pressure of burner (combustion head + complete gas train)
Pin: Minimum inlet pressure
420010601100
www.ecoflam-burners.com
19
EN
INSTALLATION
Gas pressure loss diagrams
!
PRESSURE DROP includes: “COMBUSTION HEAD + GAS TRAIN + GAS GOVERNOR & FILTER” as per EN676 Standard.
Back pressure of boiler (or other applications) must be added/included in order to have the total min pressure drop.
Burner
BLU 4000.1 PR
MULTICALOR 400.1
MULTIFLAM 400.1
Gas train
VGD 40.100
VGD 40.080
VGD 40.065
VGD 20.503
Advisable gas governor & filter no
FILTER DN 100 no
FILTER DN 80 no
FILTER DN 65 no
FILTER 2"
Spring color neutral neutral neutral neutral
Inlet gas pressure
MIN [mbar]
27
30
40
50
75
90
135
170
Inlet gas pressure
MAX [mbar]
700
700
700
700
700
700
600
600
Diagram
2C
170
160
150 natura l gas
110
100
90
80
70
60
140
130
120
50
40
30
20
10
0
200 250 300 350 flow m 3 /h
400
VGD 20.503 + F- 2"
VGD 20.503
VGD 40.065 + F- DN 65
VGD 40.065
VGD 40.080 + F- DN 80
VGD 40.080
VGD 40.
1 00 + F- DN 1 00
VGD 40.
1 00
450
2C
LEGENDA
Pf: Back pressure of furnace
Pb: Pressure of burner (combustion head + complete gas train)
Pin: Minimum inlet pressure
20 www.ecoflam-burners.com
420010601100
INSTALLATION
Electrical connections
!
WARNING: Electrical wiring must be carried out with electrical supply disconnected and with burner switch in position OFF.
Electrical supply must correspond to the one shown on the burner label.
APPLICABLE STANDARD PROBES CONNECTION
The electrical connection work comprising 2) of the gas train
ACTIVE PROBE CONNECTION all the installation materials, terminals and - Connect the plugs pending to the valve:
(FOR MODULATING VERSION) earth connections must be carried out in either on the cabinet, accordance with the applicable regulations. For the electrical installation of or on the coupling case on the body of the burner.
the burner care must be taken to observe the circuit diagram made out for the furnace system.
The electrical connection of the burner and gas valves and instruments shall be entrusted to authorized specialists only.
3) of the fuel oil motor-pump unit
- Connect the power circuit of the motor
(hanging wires) to the plugs on the fuel oil valves.
- Check the rotary direction.
9 10 11 12 13
NOTE: For the installation of the connection cables care must be taken to provide cable loops of sufficient length to allow for the swing-out of the boiler door and burner.
Make sure after the completion of the electrical connection work to check the wiring of the electrical system of the burner. This should include a check of the direction of rotation of the burner motor
(fan).
GENERAL WARNINGS:
All applicable electrical safety regulations must be followed. Failure to correctly dimension the suitable input power and earth the equipment may cause damages to person and compromise the correct function of the burner therefore the electrical system shall be checked by qualifed personnel.
The manufacturer declines all responsibility for modifcations or connections different from those shown in the electrical scheme.
Adapters, multiple plugs and extension cables may not be used for the equipment’s power supply.
An omnipolar switch in accordance with current safety regulations is required for the mains supply connection.
ELECTRICAL CONNECTION
1) of the burner
- Built-in electrical cabinet
Use cable gland in order to secure the required level of protection. All the links, power and control, are connected to the terminal block of the cabinet. Provide cables in sufficient length to secure the rotation of the burner body according to the assembly.
Check and adjust the size of the contactors and thermal relays and the wires section according to the motor and supply voltage specs.
V W
M
ATTENTION: Wiring is not supplied.
PE
R
S
T
N
50 Hz 400V
The burners are produced with connections suitable for power supply
400 V three-phase.
The burners with electric motors of an output lower or equal to 7,5 kW can be adapted to 220-230 V (please follow the instructions on the backside); motors with higher output can only work 380-400 V three-phase.
In case of request of burners different from the above mentioned standard, it is recommended to make specific mention in the order.
Instructions: how to adapt electric motors of an output lower or equal to
7,5 kW to 220-230 V power supply
It is possible to change the voltage of the burner by operating as follows:
1. change the connection inside the electric box of the motor, from star to delta
(see picture 1);
2. change the setting of the thermal relay, referring to the absorption values indicated in the motor nameplate. If necessary, replace the thermal relay with another one of suitable scale.
This operation is not possible on motors above 7.5 kW.
For more information, please contact the
Ecoflam staff.
Q
R1 S1 T1 1 2
3 4 5 6 7 8 9 10 11 13 N 21 22 25 26 29 30 32 33 34 35
HLB
STAB
T
P
50 Hz 230V
COLLEGAMENTI AUSILIARI INVERTER
INVERTER AUX ELECTRICAL CONNECTIONS lunghezza max consigliata 30 m - sez min 1 mm^2
Max leght racommend 30 mt - Min cross section 1 mm^2
RP RA
RA STC
T
P
STS
T
P
COLLEGAMENTI DI POTENZA INVERTER
INVERTER POWER ELECTRICAL CONNECTIONS lunghezza max consigliata 30 m - sez min 4 mm^2
Max leght racommend 30 mt - Min cross section 4 mm^2
SA
G L M U1
Q BE....
PASSIVE PROBE CONNECTION
(FOR MODULATING VERSION) fig.1
LEGENDA
HLB: lock-out lamp
STAB: two stages thermostat
HLF: burner on flame lamp
STC: boiler thermostat
STS: safety thermostat
SA: active probe
SP: passive probe
50 Hz 230V
400V
230V
9 10 11 12 13
1
2
3
10
11
12
13
25
26
INVERTER
(5.5 kW)
MAINS
SP
M
Q AE...
B
MOTOR Encoder sensor
Namur
U V W
3
M
MV
690V
400V
400V
230V
ATTENZIONE: COLLEGARE IL MOTORE
FACENDO RIFERIMENTO ALLA TARGHETTA MOTORE
WARNING: CONNECT MOTOR
REFERRING TO MOTOR LABEL
420010601100
www.ecoflam-burners.com
21
EN
EN
START-UP: CHECKING PROCEDURE
CHECKS BEFORE COMMISSIONING:
• That the burner is assembled in accordance with the instructions given here.
• Setting the combustion components.
• All electrical connections must be correct.
• Check the burner motor for correct direction of rotation.
• The heat generator must be ready for operation, and the operating regulations for the heat generator must be observed.
• The heat generator and heating system must be filled with water and the circulating pumps must be in operation.
• The temperature regulator, pressure regulator, low water detectors and any other safety or limiting devices that might be fitted must be connected and operational.
• The exhaust gas duct must be unobstructed and the secondary air system, if available, must be operational.
• An adequate supply of fresh air must be guaranteed.
• Make a test of the all gas-carrying elements for absence of leaks.
• Check tank, lines and oil pump are filled with oil and correct oil nozzle is fitted.
• With burner in starting position check that air damper is in “CLOSED” position.
• Check that control box is unlocked and in its original position.
• A standard-compliant measuring point must be available, the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results.
OIL START-UP
Open all shut-off valves of oil supply system.
• Set fuel selector switch to its “Oil” position.
• Fill pump with oil.
• Mount pressure gauge in the feed line and return line.
• Mount the pressure gauge for checking the pump suction pressure.
• Make sure that the nozzle is size and mounted correctly.
Bleeding of oil system
Shortly start the burner and check for proper direction of rotation. Bleed the oil line and oil pump.
Prior to the initial fuel feed start make a functional test of the burner program flow:
CAUTION: The hydraulic system has been filled with oil by the manufacturer.
This may cause ignition trouble when initially operating the system.
When starting the burner take care to increase the oil pressure slowly to the operating level.
GAS START-UP
NOTE: Adjust the gas unit according to the fuel oil unit. Set the fuel selector switch to its “Gas” position.
• Connect the measuring instruments for the gas head pressure on the test connection downstream of the gas damper and the air pressure on the burner test connection.
• Open the gas shut-off valve before the gas-armatures and test the gas pressure on the pressure gauge
• Set the “Manual-Automatic” selector switch to “Manual”.
Oil system:
• Open all shut-off valves of the oil supply system.
• The oil solenoid valve in the feed line disconnect on the terminal strip (see
Circuit Diagram).
• Start burner and check program flow for correct start-up sequence:
1. Fan starts.
2. Pre-ventilating damper.
3. Air pressure check.
4. Partial-load air damper.
5. Ignition.
6. Valves open (disconnected valve remains closed).
7. Shut-off upon trouble after expiry of safety period (see control box).
• Reconnect the valve.
• Unlock the control box.
If the gas valves are tested for absence of leaks, this should be continued until a positive result is obtained. If a valve is found to leak, the program will not step forward to the control box.
The burner will start according to the program flow of the control box.
Gas system:
• Shortly open the gas shut-off valve before the gas train until pressure is available and close again.
• Start burner and check program flow for correct start-up sequence:
1. Fan.
2. Pre-ventilation damper.
3. Check air pressure.
4. Partial-load damper.
5. Ignition.
6. Valves open.
7. Shut-off upon trouble after expiry of safety period (see control box) or shut-off because of gas supply failure.
7. The burner will either stop as the gas valves open (due to gas pressure decrease) or lock out at the end of the safety time.
• Unlock the control box.
22 www.ecoflam-burners.com
420010601100
EXHAUST GAS TEST
To ensure an economically efficient and trouble-free operation of the system it will be necessary to adjust the burner specifically in accordance with the furnace system. This is achieved by means of a fuel-combustion air compound control unit which adjusts the burner to ensure a proper combustion. Exhaust gas tests are required for this purpose.
The percentage CO2 and O2 and the exhaust gas temperature will have to be measured to determine the efficiency and combustion quality.
Prior to any measurement make sure to check the boiler and exhaust gas system for absence of leaks.
Secondary air will falsify the measured results
Check that the exhaust gases have a residual oxygen (O2) content as low as possible and a carbon dioxide (CO2) content as high as possible.
The carbon monoxide content of the exhaust gases must be below the currently applicable specifications in all load stages.
In the fuel oil combustion mode the permissible soot number in the exhaust gas is not allowed to be exceeded
DETERMINING THE VOLUMETRIC GAS
FLOW RATE
The thermal furnace output of a boiler (QF) is the amount of heat supplied with the gas in a unit of time.
When taking the burner into operation the volumetric fuel flow rate should be selected according to the nominal thermal capacity of the boiler.
Q
F
=
Q
N n
K
=
1000
0,88
= 1136 kW
Volumetric gas flow rate at STP: v
Bn
=
H
Q
N u
*n
K
=
1000
9,1*0,88
= 125 m 3 /h
Example:
Nom. thermal output Q
N
1000 kW
Boiler efficiency n
K
0,88
Calorific value of gas Hu 9,1 kWh/m 3
Gas pressure p
U
100 mbar
980 mbar Barometer reading p amb
Gas temperature relative
Gas temperature t
T gas absolute
Standard atmosferic pressure p n
15°C
(t gas+
273)
1013 mbar
Volumetric gas flow rate in operating condition: v
BB
= v
Bn
T
= p
273 p amb n
+ p u
=
= 125
273+15 1013,25
273 980+100
= 123,9 m 3 /h
EN
Recommended combustion parameters
Fuel
Natural gas
Light oil
Heavy oil
Recommended
(%) CO2
10 ÷ 9
13 ÷ 11,5
12,5 ÷ 11
Recommended
(%) O2
3,1 ÷ 4,8
3,3 ÷ 5,3
4,2 ÷ 6,2
Ratio between O
2
- and CO
2 for natural gas H (CO
2
- max = 11,7%)
Ratio between O
2
- and CO
2
- for light oil EL (CO
2 max = 15,40%)
Ratio between O
2
- and CO
2 for heavy oil S (CO
2
- max = 15,60%)
O
2
= 21 CO 2 max - CO
2 gem = %
CO
2 max
CO
2 gem = % CO
2 measured on dry flue gases
WARNING: if the installation is above sea level the output of the burner vary base on the diagram.
The regulation of the burner in this case shall take into account the reduced power of the burner due to the missing air.
M ean air pressure v s . a l titu d e abo v e sea -l e v e l
5 000
45 00
4 000
3 5 00
3000
2 5 00
2000
1 5 00
1 000
5 00
0
0 5 1 0 1 5 20 2 5 30 3
F an capacit y re d uce d b y [%]
5 4 0 45 5 0
420010601100
www.ecoflam-burners.com
23
EN
START-UP OIL SIDE
Fuel selection - Start-up
Select the oil operation in order to proceed with start up on the oil side. On the selector put the operation on minimum capacity.
0=STOP
1=OIL
2=GAS
!
KMP - contactor: check the oil pump motor rotation and keep KMP pressed till the oil circuit is loaded.
If the rotation if not correct invert the two phases on the power supply.
KMP
START UP THE BURNER
The control box starts the pre-purge cycle, the fan motor and the oil motor and opens the air flaps in full open positon.
At the end of pre-purging, the control box drives the servomotors into the igniton positon and starts the igniton transformer.
After a few seconds the control box opens the oil valve and starts the flame. After the flame stabilisaton the control box drives the servomotor in the low flame.
In case of faulty igniton, the control box switches the burner into safety condition, in such a case you must rearm the burner.
Gradually increase burner output from the low flame to the high flame and set oil servomotor curve in order to have a stable flame. Refer to LAMTEC manual attacched.
Adjusting the maximum air flow rate
Air and Oil adjustment are accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.
Firing head setting
The firing head is pre-adjusted at the 50% from the factory. The setting fully open enables to reach the full power of the burner and full close to reach the minimum power of the burner.
The optimal position depends on the output that we need to reach but the default setting shall be modified only when you are not able to reach the suggested combustion value by adjusting the air flow in the maximum flame.
+ -
24 www.ecoflam-burners.com
420010601100
START-UP OIL SIDE
Gefran setting
D i sp l a y
I ncrease k e y
D ecrease k e y
“F unct i on ” k e y
The display shows oil temperature.
The 4 leds are related to the following functions:
• Out 1: contact driving working heaters
• Out 2: contact driving upper heaters KMRL1
• Out 3: contact driving upper heaters KMRL2
• Out 4: burner start driving contact (as the oil reaches this temp the pump is activated)
The temperatures are already properly factory setted:
• Out 1 (113°)
• Out 2 (115°)
• Out 3 (120°)
• Out 4 (105°)
WARNING: Burner will start only when the first three led of the temperature will be off so that heavy oil will be in temperature.
To modify factory temperature setting act as follow:
• press key “F”
• the led Out 1 starts to ash, if You need to modify minimum oil temperature press increase or decrease button, after confirm the new value pressing again “F”
• if you need to modify an other temperature press again “F” untill You the relevant led ashes.
Please take care: if key “F” is pressed for a too long time, you enter in “configuration level” phase 1, (see “CF1” on the display); these parameters are factory setted and they have not to be modified: if you enter this function – you see CF1 ashing on the display – wait 10 seconds until the regulator automatically goes out from “configuration level”.
ADJUSTMENT OF FUEL THERMOSTATS
Inside the electrical panel there is a safety termostat that is set up at 160°C.
Said adjustments can be slightly modified following the type of fuel and particular uses.
EN
420010601100
www.ecoflam-burners.com
25
EN
START-UP OIL SIDE
Adjusting the maximum oil flow rate
Put the selector on the maximum operation. Adjust the oil pressure reading the value on the return manometer / pressure gauge according to the nozzle tables provided in the appendix.
NOTE: the pump pressure is set from the factory at the pressure required nozzle pressure required as per table of nozzle selection in appendix. If the output required is different from the one set from the factory the pressure can be adjusted according to the instruction below.
Servomotor STE 15 - Air damper motor pre-setting
Air adjustment is accomplished through BT 340 parameters setting. Refer to BT 340 manual attacched.
Adjusting the pump pressure
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE
4
SUNTEC TA....
3
1
5
2
The pump pressure is set at a value of 22-25 bar during the testing of burners.
Before starting the burner, bleed the air in the pump through the gauge port.
Fill the piping with heavy oil to facilitate the pump priming. Start the burner and check the pump feeding pressure.
In case the pump priming does not take place during the first pre-purging, with a consequent, subsequent lock-out of the burner, rearm the burner’s lock-out to restart, by pushing the button on the control box.
If, after a successful pump priming, the burner locks-out after the prepurging, due to a fuel pressure drop in the pump, rearm the burner’s lock-out to restart the burner.
Do never allow the pump working without oil for more than three minutes.
NOTE: before starting the burner, check that the return pipe is open. An eventual obstruction could damage the pump sealing device.
6
26 www.ecoflam-burners.com
420010601100
START-UP OIL SIDE
Adjusting the intermediate burner capacity
Oil adjustment is accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.
WARNING: the variable profile of the cam shall have a normal proportional curvature in order to have good combustion values and reduce its mechanical stress breakdown.
1 80
1 76
CV
CV
3 1
1 78
1 84
1 86
1 85
I
V L
R L
1 76
V L O
CV
CV
3 1
1 78
1 84
1 8 5
I mi n
1 86
1 8
0
!
WARNING: Once the setting on the oil has been completed make sure that you close the manometer
– pressure switch tap.
LEGENDA
176: oil pump
178: solenoid valve
180: nozzle rod
184: output control valve
185: manometer
186: pressure regulator
311: return oil pressure switch
CV: check valve
RL: return line
VL: suction line
VLO: working oil valve
EN
420010601100
www.ecoflam-burners.com
27
EN
START-UP GAS SIDE
Select the gas operation in order to proceed with start up on the gas side.
0=STOP
1=OIL
2=GAS
START UP THE BURNER
The control box starts the pre-purge cycle, the fan motor and opens the air flaps in full open position.
At the end of pre-purging, the control box drives the servomotor into the ignition position and starts the ignition transformer.
After a few seconds the control box opens the pilot valves and starts the pilot flame.
After the flame stabilisation the control box opens the main valves and the burner goes in the low flame and the pilot switch off.
In case of faulty igniton, the control box switches the burner into safety condition, in such a case you must rearm the burner.
Gradually increase burner output from the low flame to the high flame and set gas servomotor curve in order to have a stable flame. Refer to LAMTEC manual attacched.
Adjusting the maximum air flow rate
Air and Gas adjustment are accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.
Firing head setting
The firing head is pre-adjusted at the 50% from the factory. The setting fully open enables to reach the full power of the burner and full close to reach the minimum power of the burner.
The optimal position depends on the output that we need to reach but the default setting shall be modified only when you are not able to reach the suggested combustion value by adjusting the air flow in the maximum flame.
+ -
Servomotor STE 15 - Air damper motor pre-setting
Air adjustment is accomplished through BT 340 parameters setting. Refer to BT 340 manual attacched.
28 www.ecoflam-burners.com
420010601100
START-UP GAS SIDE
Adjusting the intermediate burner capacity
Gas adjustment is accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.
WARNING : the variable profile of the cam shall have a normal proportional curvature in order to have good combustion values and reduce its mechanical stress breakdown.
Pressure switch adjustment
AIR PRESSURE SWITCH CALIBRATION
The air pressure switch is provided for monitoring the pressure of the combustion air fan.
Unscrew screws A and B and remove cover C.
After the air and gas setting you have to calibrate the air switch with the burner working on the low flame by slowly turning the relative knob clockwise until the burner locks out.
Read the value and then decrease it by 15%.
Set the pressure switch to the minimum by turning knob D to position 1.
Start the burner and keep in low flame running, while checking that combustion is correct. Through a small cardboard, progressively obstruct the air intake until to obtain a
CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressure port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.).
Slowly increase the adjustment value of the air pressure switch until to have the burner lockout. Remove the obstruction from the air intake, screw on the cover C and start the burner by pressing the control box rearm button.
WARNING: the air pressure switch shall prevent the air pressure to go below 80% from the adjustment value in order to prevent the CO in the fumes to exceed 1% (10000 ppm).
Using the analyser try to close the air inlet and check that the burner locks out before exceeding CO value of 1% in the fumes.
MIN GAS PRESSURE SWITCH
The gas pressure switch has the function to check that the gas pressure before the gas valve does have the minimum pressure to make the burner running correctly.
Unscrew off and remove cover M. - Set knob N to a value equal to 60% of gas nominal feed pressure (i.e. for natural gas nom. pressure = 20 mbar, set knob to a value of 12 mbar; for LPG nom. pressure of G30/G31- 30/37 mbar, set knob to a value of 18 mbar).
MAX GAS PRESSURE SWITCH (KIT)
The maximum gas pressure switch has the function to check that the gas pressure after the gas train and before the head does not exceed the pre-set limits.
Max gas pressure switch: it is available as a kit for different pressure.
Air pressure switch
C
A
B
Gas pressure switch
2,7
2,4
2,1
0,4
D
0,6
0,9
1,2
I
M
L
45
40
2,5
5
N
10
15
20
EN
420010601100
www.ecoflam-burners.com
29
EN
MAINTENANCE PROGRAM
!
Burner and boiler servicing must only be carried out by authorised qualied personnel at least once a year.
Depending on the type of installation, shorter maintenance intervals may be necessary.
The system operator is advised to take out a maintenance contract to guarantee regular servicing.
WARNING: Use original spare parts.
SAFETY WARNINGS:
1. Turn off the power supply and protect the system from accidental start-up
2. Cut oil and gas supply
3. Make sure there is no residual power in the system and that the actions in points 1 and 2 have been completed
4. Before opening the burner casing, ensure that the fan motor has stopped completely
Failure to observe any of these instructions will result in the risk of death or injury!
0=STOP
1=OIL
2=GAS
WORKS RECOMMENDED AS PART OF ANNUAL BURNER MAINTENANCE:
• Emergency stop button function check
• Check burner start characteristics
• Run burner test and input measurement in the boiler room
• Clean the combustion components and replace defective parts if necessary
• Check the combustion head components and make sure that all components are in good condition otherwise replace them
• Replace ignition electrodes and nozzle if necessary and check their correct position after any intervention
• Flame monitor and automatic combustion control unit function check
• Clean the fan wheel and the housing and grease rotating parts if necessary
• Clean the oil filter cartridge with gasoline periodically and check the tightening of the O rings, replace them if necessary
• Perform visual inspection of gas lines in the boiler room and check the gas flow
• Clean the gas filter cartridge with air periodically, replace it if necessary
• After the cleaning of the components of the gas train perform the leakage test
• Make visual inspection of the burner’s electrical components and eliminate malfunctions if necessary
• Burner safety devices function check (air pressure/gas pressure switches)
• Commissioning the burner and correct the adjustment values if necessary
NOTES ON REASSEMBLING: Perform the described step in reverse order and make sure to refit components as they were originally assembled and the system is free from leaks. Use only original spare parts.
DRAW UP A MEASUREMENT REPORT ACCORDING TO THE LOCAL REGULATION AND CODES OF PRACTISE OF THE
COUNTRY
EXHAUST GAS LOSS
Exhaust gas loss by way of free heat will occur as a result of the temperature difference between the fuel-air mixture entering the furnace chamber and the gases discharged. Any increase in the excess of air and the resultant higher exhaust gas volume will cause the exhaust gas loss to rise. The exhaust gas loss can be calculated as follows: q
A
= (t
A
- t
L
)
A
1
CO
2
+ B
A1
B
Light oil
EL
0,50
0,007
Heavy oil
S
0,490
0,007
Example
Data measured in natural gas mode:
CO
2 content of exhaust gases: 10,8%
Exhaust gas temperature: 195°C
Air intake temperature: 22°C q
A t
A t
L
CO
2
= exhaust gas loss [%]
= exhaust gas temperature [°C]
= combustion air temperature [°C]
= volumetric content of carbon dioxide [%]
The exhaust gas loss can be calculated as follows: q
Af
= (195-22)(
0,37
10,8
+ 0,009) = 7,48%
Natural gas Town gas
0,370 0,350
0,009 0,011
Data measured in fuel oil mode:
CO
2
LPG
0,420
0,008 content of exhaust gases: 12,8%
Exhaust gas temperature: 195°C
Air intake temperature: 22°C
The exhaust gas loss can be calculated as follows: q
Af
= (195-22)(
0,49
12,8
+ 0,007) = 7,83%
30 www.ecoflam-burners.com
420010601100
MAINTENANCE PROGRAM
REMOVING THE FIRING HEAD AND THE BLAST TUBE
EN
POSITION OF ELECTRODES
ATTENTION: to remove the nozzle use the suitable box wrench taking care to not damage the electrodes .
Check the position of the electrodes after any intervention as wrong position could cause ignition troubles.
3 ÷ 4 mm Ignition Electrode
5 ÷ 6 mm
GAS FILTER CLEANING - GAS PILOT FILTER CLEANING
ATTENTION: Periodically clean oil cartridge with gasoline and the gas filter cartridge with air and replace them if it is necessary!
420010601100
Check and clean the gas filter in the pilot gas valve
www.ecoflam-burners.com
31
EN
TROUBLESHOOTING INSTRUCTIONS
For Setting and Error Lists refer to LAMTEC manual attacched.
OPERATING TROUBLE
In case of operating trouble it should be checked whether the system is in proper working order.
Make a check for the following:
1. Availability of fuel.
Availability of gas in the line at sufficiently high pressure.
Availability of fuel oil in the tank (for dual fuel burner).
Correct position of fuel selector switch.
2. Availability of electric power in the burner system.
3. Proper functional order and setting of all control and safety instruments such as temperature controller, safety limiter, water failure cut-out, electrical limit switches, etc.
If the trouble is not found to be due to any of the above-mentioned points it will be necessary to test the burner functions very carefully.
Prevailing conditions:
The burner will be found to be out of operation and in faulty and interlocked position.
Proceed with searching for the cause of the trouble and eliminate it. Unlock the control box by pressing the fault eliminate key and start the burner.
Do not press the fault eliminate key longer than 10 seconds.
The start-up program will be initiated and should be carefully monitored.
The possible cause of the fault may be quickly found by reference to the fault indicator of the control box and watching the start-up and operating program.
APPENDIX
Control box - Damper actuators
Lamtec BT340 control and safety unit
The control and safety unit BT 3xx controls and monitors the forced draught burner.
The microprocessor-controlled program sequence ensures the maximum consistency of the cycle times involved, regardless of fluctuations in the mains voltage or ambient temperature. The control and safety unit is designed to detect power failures. Depending on the parameter assignment, the unit either switches to malfunction mode or goes into the standby position if the power supply falls below the mains voltage. In the standby position, there is an automatic restart as soon as the set threshold value is exceeded by 105%.
Manual locking and unlocking
Using the reset button , the control and safety unit can be locked manually
(interlocked) or unlocked, provided the unit is connected to the mains power supply.
This function must not be confused with automatic locking and fault acknowledgement in case of an error.
Pressing the unlocking button on the unit for
... 1 second ...
.... causes ....
... 4 seconds ...
the control unit to unlock.
he control unit to unlock.
Moves the cursor upwards.
Moves the cursor downwards.
Increases the marked value.
Reduces the marked value.
Modifies/Confirms the value shown.
!
Always switch off the power supply before installing or removing the control unit. Do not attempt to open or carry out repairs on the control unit.
Unlocks the control unit.
Red LED (flashes if a fault is present).
For damper actuators refer to STE....manual attacched.
32 www.ecoflam-burners.com
420010601100
APPENDIX
Fluidics nozzle chart
25
RETURN NOZZLE
The nozzle type Fluidics W is a by-pass nozzle with integrated spring-loaded cut-off needle.
The throughput rate is controlled by varying the return pressure while keeping the supply pressure at a constant level.
Prior to burner start, check the nozzle size against the required output.
It might be necessary to replace the nozzle (see nozzle selection diagram).
Return pressure
20
15
≤ 60 kg/h
> 60 kg/h
10
50° 70° 90° Spray angle
Supply
25 Bar
Bar 5
20 40 60 80 100 % Output
EN
420010601100
www.ecoflam-burners.com
33
EN
APPENDIX
Bergonzo nozzle tables
34 www.ecoflam-burners.com
420010601100
APPENDIX
Bergonzo nozzle tables
EN
420010601100
www.ecoflam-burners.com
35
EN
APPENDIX
Pumps and pressure regulators
PUMP SUNTEC TA TECHNICAL DATA
Note: All TA models are delivered for two-pipe system (by-pass plug fitted in vacuum gauge port).
For one-pipe system, the by-pass plug must be removed and the return port sealed by steel plug and washer.
PUMP
IDE NT IFICA T IO N
(Not a ll mode l combinations are a v ai l ab l e
Consu l t your Suntec representati v e)
T A : type
O i l under suction
O i l under pressure
V acuum or in l et pressure g au g e port
Bypassed oi l returned to tan k, or to suction
P ressure g au g e port
Gear set capacity
(see pump capacity cur v es)
Shaft rotation
(seen from shaft end)
A : c l oc kw ise rotation
C : anti c l oc kw ise rotation
I nta k e f rom T an k
Bypass p l u g inserted
P ressure ad j ustment
T o no zzl e
T A 2 A 4 0 10 5 R eturn
T
W O P
I
PE
I N S T A LL A TI O N
Pressure range :
30 : 7 30 bars
4 0 : 7 4 0 bars
Preheater faci l ity
I nta k e f rom T an k
Bypass p l u g remo v ed
R e v ision number
O N E P I PE
I N S T A LL A TI O N
R eturn p l u gg ed
G ene r al
Mounting
Connection threads
I n l et end return
T o no zzl e
Pressure gauge port
Vacuum gauge port
Shaft
By-pass p l ug
W eight
H yd r aulic da t a
F l ange mounting
Cy l indrica l according to I SO 228 / 1
G 1 / 2 "
G 1 / 2 "
G 1 / 4 "
G 1 / 4 "
Ø 12 mm
I nserted in v acuum gauge port for 2 pipe system ; to be remo v ed w ith a 3 / 16 " A ll en k ey for 1 pipe system
5 , 4 k g ( T A2) -
6 k g ( T A4) -
5
6
,
,
7
4
k
k g g
(
(
T
T
A3)
A5)
No zzl e pressure ranges 30 : 7 30 bars
40 : 7 40 bars
De l i v ery pressure setting 30 bars
Operating v iscosity 4 450 cSt
Oi l temperature
I n l et pressure
Return
Rated pressure speed
Starting tor q ue
0 140°C max.
in the pump l ight oi l : 0 , 45 bars max.
v acuum to pre v ent air separation from oi l hea v y oi l : 5 bars max.
l ight oi l : 5 bars max.
hea v y oi l : 5 bars max.
3600 rpm max.
0 , 3 N.m
P ump capaci t y
Capacity ( L/ h)
1500
1400
1300
1200
1100
1000
900
T
T
A5
A4
2850 rpm
800
700
600
500
400
T
T
A3
A2
300
200
100
0
0 5
Viscosity =
10 15 20 25 30 35 40 Pressure
(bars)
200 cSt
20 cSt
5 cSt Rated speed = 2850 rpm
Data sho w n are for ne w pumps , w ith no a ll o w ance for w ear.
C hoice of hea t e r
Cartridge
Fitting
Rating
Ø 12 mm according to D I N 40430 , NFC 68190 (N°9 e l ec.)
80-100 W
36 www.ecoflam-burners.com
420010601100
APPENDIX
Electrical diagrams
MARRONE/BROWN
BLU/BLUE ommend 30 mt oss section 4 mm^2 Min cr
Max leght rac sez min 4 mm^2 lunghezza max consigliata 30 m
X30
1
X31
1
X32 X33 X34
420010601100
TION AM WITH PROHIBITION OF USE AND REPRODUC WIRING DIAGR OF THIS THE PROPERTY WE RESERVED TERM LAWS BY
www.ecoflam-burners.com
37
EN
EN
APPENDIX
Electrical diagrams
TION
38 www.ecoflam-burners.com
RAM WITH PROHIBITION OF USE AND REPRODUC WIRING DIAG OF THIS THE PROPERTY WE RESERVED TERM LAWS BY
420010601100
APPENDIX
Electrical diagrams
EN
FIRMA
DATA
FIRMA
DATA
420010601100
O DEL PRESENTE.
TERZI IL CONTENUT COMUNICARE A TO RIPRODURRE O VIETA A TERMINE DI LEGGE E' OFLAM S.p.A.
TA EC TA DELLA DIT ' RISERVA PROPRIETA
www.ecoflam-burners.com
39
EN
APPENDIX
Spare parts
30
40 www.ecoflam-burners.com
BT3xx
420010601100
APPENDIX
Spare parts list
2
3
N° DESCRIPTION
1 AIR PRESSURE SWITCH
PRESSURE GAUGE
AIR INTAKE SET
6
7
4 WIELAND PLUG
5 GLASS
PEED WINDOM FRAME
MOTOR
8
9
FAN
AIR CONVEYOR
10 AIR INTAKE
11 AIR INTAKE PIPE
12 DISPLAY
13 CONTROL BOX
14 IGNITION TRANSFORMER
15 REMOTE CONTROL SWITCH
16 REMOTE CONTROL SWITCH (PUMP)
17 REMOTE CONTROL SWITCH
18 MOTOR THERMAL RELAY
19 MOTOR THERMAL RELAY (PUMP)
20 ADJUSTMENT OF FUEL TEMPERATURE
21 MAIN SWITCH
22 GAS/HEAVY-OIL SELECTOR
23 SELECTOR
24 LAMP
25 PUSH
26 RELÉ BASE
27 RELÉ
28 UV CELL
29 IGNITION CABLE
30 IGNITION ELECTRODES SET
31 PIPE
32 ROD
33 FIRING HEAD
34 HEAVY OIL FIRING HEAD
35 FRONT DISC
36 NOZZLE HOLDER
37 COIL
38 COIL CONNECTOR
39 RING
40 SPRING HOLDER
41 PIPE
42 ROD NOZZLE HOLDER
43 INNER ASSEMBLY
44 BLAST TUBE
45 GASKET ISOMART
46 ANTIJAMMING FILTER
47 GAS DAMPER MOTOR
LAMTEC
BT 340 667R1340-1
BRAHMA T8
AEG LS05.10
AEG LS7K.10
AEG LS4K.10
AEG 3-4,7A
GEFRAN 600-R
Comepi
Comepi a.ECX1
LYVIA 10X28 BA9S
Finder 5532
Finder 5532
LANDIS QRA 2
TC
TL
TC
TL
TC
TL
TC
TL
TC
TL
EL011
EL011
TC
TL
TC
TL
TC
TL
TC
TL
STE 4,5 BT3XX
DUNGS LGW10 A2P
6 pin
5,5 k W
7,5 k W
320 x 150
MULTIFLAM 300.1 PR MULTIFLAM 400.1 PR
65323116
65322045
65324098
65324099
-
65324100
-
65323149
65323139
65320075
65320946
65320947
65325222
65324082
65324081
65324086
65324085
65324084
65324083 code
65323047
65321341
65322346
65322072
65320487
65320488
65325357
-
65321800
65320645
65324357
65321230
342503203
14058433
65323222
-
65323132
65324097
65323133
-
65324266
65321722
65320820
65320709
65323809
65323571
65321721
65321720
65324292
65324676
65324268
65324269 code
65323047
65321341
65322346
65322072
65320487
65320488
-
65325350
-
65324100
-
65323149
65323139
65320075
65320946
65320947
65325222
65324082
65324081
65324086
65324085
65324084
65324083
65321800
65320645
65324357
65321230
342503203
14058433
65323222
-
65323132
65324097
65323133
-
65323116
65322045
65324098
65324099
65324266
65321722
65320820
65320709
65323809
65323571
65321721
65321720
65324292
65324676
65324268
65324269
65325863
65320435
65321125
65323170
14051822
65325041
65320456
65321125
65323170
TC = SHORT HEAD TL = LONG HEAD
420010601100
www.ecoflam-burners.com
41
EN
EN
APPENDIX
Spare parts list
N° DESCRIPTION
48 FAN SCOOP
49 OIL PUMP
50 COUPLING
51 HOSES
52 OIL FILTER
53 PUMP MOTOR
54 MANOMETER
55 THERMOCOUPLE
56 FILTER
57 HEATER
58 OIL TANK
59 HEATING ELEMENT
60 PILOT GAS VALVE
61 COIL
62 GAS GOVERNOR
63 CONNECTION PIPE
64 SILENCER
65 THERMOSTAT
66 ADJUSTMENT OIL PRESSURE
67 OIL PRESSURE SWITCH
68 SERVOMOTOR
69 CHECK VALVE
70 OIL TANK GASKET
71 HEATING ELEMENT
72 PREHEATED’S AUX. RESISTOR HOLDER
73 FIXING PLATE
74 THROTTLE GROUP
75 MODULATING KIT
76 INVERTER
SUNTEC TA3C40105
TN 25X1500 C/T
70501/03
1100 W
CEWAL R1/4 D50-40BAR
TC6MD2JBC
U21008/01
18000 W
21000 W
50 W
BRAHMA EG12SRGMO
BRAHMA EG12SR
IMIT TR2 40/200
B-P-PRO-2 a.070H0136
B-P-PRO-2 a.070H0138
DANFOSS KPS 39 1/4F
STE15 Q3.51/6 10Nm
NAFTA ART. FZVR10 3/8
30 W
MULTIFLAM 300.1 PR MULTIFLAM 400.1 PR code code
-
65322992
65325386
65323181
65324103
65325356
65324105
65322046
65323158
65323088
-
65324088
65323072
65323595
65323707
-
65325466
65320627
65322992
65325386
65323181
65324103
65325356
65324105
65322046
65323158
-
65323089
65324088
65323072
65323595
65323707
-
65325466
65324107
65323147
-
65323166
SIEMENS RWF 50
ABB 5,5KW MOD.ACH550
TC = SHORT HEAD TL = LONG HEAD
65324107
65323147
65323165
-
65325377
14051811
65322205
65324010
65324207
65321716
65321717
65325510
3143713
460090031600
65322205
65324010
65324207
65321716
65321717
65325510
3143713
460090031600
42 www.ecoflam-burners.com
420010601100
420010601100
www.ecoflam-burners.com
43
EN
Ecoflam Bruciatori S.p.A.
Via Roma, 64 - 31023 Resana (TV) - Italy
Tel. +39 0423 719500
Fax +39 0423 719580 http://www.ecoflam-burners.com
e-mail: [email protected]
Società soggetta alla direzione e al coordinamento di Ariston Thermo S.p.A.
Via A. Merloni, 45 - 60044 Fabriano (AN) - CF 01026940427
Ecoflam Bruciatori S.p.A. reserves the right to make any adjustments, without prior notice, which is considered necessary or useful to its products, without affecting their main features
Ecoflam Bruciatori S.p.A. si riserva il diritto di apportare ai prodotti le modifiche che riterrà necessarie o utili, senza pregiudicarne le caratteristiche principali.
La maison Ecoflam Bruciatori S.p.A. se réserve le droit d’apporter les modifications qu’elle jugera nécessaires ou utiles
à ses produits sans pour autant nuire à leurs caractéristiques principales
Ecoflam Bruciatori S.p.A. se reserva el derecho a introducir en sus productos todas las modificaciones que considere necesarias o utiles, sin prejudicar sus caracteristicas
“Ecoflam Bruciatori S.p.A.” оставляет за собой право вносить в конструкцию оборудования любые необходимые изменения без особого предупреждения
advertisement