advertisement
Operating Guide
VLT® Decentral Drive FCD 302
vlt-drives.danfoss.com
VLT® Decentral Drive FCD 302
Operating Guide
Contents
1
1.1
Purpose of this Operating Guide
1.2
1.3
1.4
1.5
1.6
1.4.1
1.4.2
1.4.3
Type Approvals and Certifications
2
2.1
3
3.1
3.1.1
3.2
3.3
3.1.2
3.3.1
3.3.2
3.3.3
Recommended Tools and Equipment
3.3.3.1
3.3.3.2
4
4.3
4.4
4.5
4.6
4.7
4.1
4.2
4.8
4.7.1
4.7.2
4.8.1
Danfoss A/S © 2021.09
Contents
AQ267036816112en-000201/130R0208 | 3
VLT® Decentral Drive FCD 302
Operating Guide
4.9
Motor and Mains Connection with Service Switch
4.10
4.10.1
4.10.2
4.10.3
4.10.4
4.10.5
Connection of Sensors/Actuators on M12 Sockets
4.10.6
4.10.7
4.10.8
4.10.8.1
Connecting and Setting Up RS485
4.11
5
5.1
5.1.1
5.2
5.3
5.4
5.5
5.6
5.7
5.3.1
5.3.2
5.3.3
5.3.4
Uploading/Downloading Data to/from the LCP
5.3.5
5.3.6
5.3.6.1
5.3.6.2
Automatic Motor Adaptation (AMA)
5.5.1
6
Maintenance, Diagnostics and Troubleshooting
6.1
6.2
6.3
6.4
6.5
6.6
4 | Danfoss A/S © 2021.09
Contents
AQ267036816112en-000201/130R0208
VLT® Decentral Drive FCD 302
Operating Guide
6.7
6.8
7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.6.6
7.6.7
7.6.8
7.6.9
7.6.2
7.6.3
7.6.4
7.6.5
7.3.1
7.3.2
7.4.1
Cable Lengths and Cross-sections
Control Input/Output and Control Data
7.6.1
STO Terminal 37 (Terminal 37 is Fixed PNP Logic)
Control Card, RS485 Serial Communication
7.6.10
Control Card, USB Serial Communication
7.6.11
7.6.12
7.6.13
7.7.1
7.7.2
Recommended Maximum Pre-fuse Size 25 A
8
8.1
Symbols, Abbreviations and Conventions
8.1.1
8.2
Danfoss A/S © 2021.09
Contents
AQ267036816112en-000201/130R0208 | 5
VLT® Decentral Drive FCD 302
Operating Guide Introduction
1 Introduction
1.1 Purpose of this Operating Guide
This Operating Guide provides information for safe installation and commissioning of the AC drive. It is intended for use by qualified personnel.
Read and follow the instructions to use the drive safely and professionally.
Pay particular attention to the safety instructions and general warnings. Always keep this Operating Guide with the drive.
VLT
®
is a registered trademark for Danfoss A/S.
1.2 Additional Resources
Other resources are available to understand advanced drive functions and programming.
•
•
The VLT® Decentral DriveFCD 302 Design Guide provides detailed information about capabilities and functionality to design motor control systems.
The VLT® AutomationDrive FC 301/302 Programming Guide provides greater detail on working with parameters and many application examples.
• Instructions for operation with optional equipment.
Supplementary publications and manuals are available at www.danfoss.com
.
1.3 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
Table 1: Manual and Software Version
Edition Remarks Software version
AQ267036816112, version 0201 Editorial update 8.5X
1.4 Product Overview
1.4.1 Intended Use
The drive is an electronic motor controller intended for:
• Regulation of motor speed in response to system feedback or to remote commands from external controllers. A power-drive system consists of the drive, the motor, and equipment driven by the motor.
System and motor status surveillance.
•
The drive can also be used for motor protection.
Depending on the configuration, the drive can be used in standalone applications or form part of a larger appliance or installation.
The VLT® Decentral Drive FCD 302 is designed for decentral mounting, for example, in the food and beverage industry, or for other material handling applications. With the FCD 302, it is possible to reduce costs by placing the power electronics decentrally. Central panels are then rendered obsolete, saving cost, space, and effort for installation and wiring. The basic design is service-friendly with a pluggable electronic part and a flexible and spacious wiring box. It is easy to change electronics without the need for rewiring.
Installation environment: The drive is allowed for use in residential, industrial, and commercial environments in accordance with local laws and standards.
N O T I C E
RADIO INTERFERENCE
-
In a residential environment, this product can cause radio interference, in which case supplementary mitigation measures can be required.
Take the necessary precautions.
Foreseeable misuse
Do not use the drive in applications which are non-compliant with specified operating conditions and environments.
Ensure compliance with the conditions specified in
.
6 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
1.4.2 Exploded Views
1
2
5
6
9
10
Illustration 1: Exploded View Small Unit
Danfoss A/S © 2021.09
8
Introduction
AQ267036816112en-000201 / 130R0208 | 7
3
4
7
VLT® Decentral Drive FCD 302
Operating Guide
3
4
1
2
5
Inverter part
Fastening screws (4 x, 1 in each corner)
Sealing gasket
Inverter part plastic cover
Ground connection pin
Introduction
8
9
6
7
10
Installation box
Display connection
Access to USB port
Service switch-motor side (alternatively, switch located on mains side, or not mounted)
Flat mounting brackets
8 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
1
2
5
6
9
10
Illustration 2: Exploded View Large Unit
Danfoss A/S © 2021.09
8
Introduction
AQ267036816112en-000201 / 130R0208 | 9
3
4
11
7
VLT® Decentral Drive FCD 302
Operating Guide Introduction
3
4
1
2
5
6
Inverter part
Fastening screws (4 x, 1 in each corner)
Sealing gasket
Inverter part plastic cover
Ground connection pin
Installation box
7
8
9
10
11
Display connection
Access to USB port
Service switch (1) motor side (alternatively, switch located on mains side, or not mounted)
Flat mounting brackets
Circuit breaker (1) (optional)
1 The unit can be configured with either service switch or circuit breaker, not both. The illustration shown is not configurable in practice, but shows the respective positions of components only.
1.4.3 Block Diagram of the Drive
Illustration 3: Block Diagram
1
2
3
4
•
Mains input
3-phase AC mains power supply to the drive.
•
Rectifier
The rectifier bridge converts the AC input to DC current to supply inverter power.
•
DC bus
Intermediate DC-bus circuit handles the DC current.
•
•
•
•
•
DC reactors
Filter the intermediate DC circuit voltage.
Prove line transient protection.
Reduce RMS current.
Raise the power factor reflected back to the line.
Reduce harmonics on the AC input.
5
6
7
8
•
•
Capacitor bank
Stores the DC power.
Proves ride-through protection for short power losses.
•
Inverter
Converts the DC into a controlled PWM AC waveform for a controlled variable output to the motor.
•
Output to motor
Regulated 3-phase output power to the motor.
•
•
•
Control circuitry
Input power, internal processing, output, and motor current are monitored to provide efficient operation and control.
User interface and external commands are monitored and performed.
Status output and control can be provided.
1.5 Type Approvals and Certifications
The following list is a selection of possible type approvals and certifications for Danfoss drives:
10 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Table 2: Type Approvals and Certifications
Introduction
089
N O T I C E
The specific approvals and certification for the drive are on the nameplate of the drive. For more information, contact the local
Danfoss office or partner.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 11
VLT® Decentral Drive FCD 302
Operating Guide
1.6 CE Declaration
Introduction
12 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Safety
2 Safety
2.1 Safety Precautions
W A R N I N G
-
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
W A R N I N G
UNINTENDED START
When the drive is connected to the AC mains, the motor may start at any time, causing risk of death, serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command, an input reference signal
-
-
from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condition.
Press [Off] on the LCP before programming parameters.
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor start.
Check that the drive, motor, and any driven equipment are in operational readiness.
W A R N I N G
-
-
-
-
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.
Stop the motor.
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The time for full discharge of the capacitors is minimum 4 minutes for VLT® Decentral Drive FCD 302, 400 V AC, 0.37–3.0 kW (0.5–4.0 hp).
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
C A U T I O N
-
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 13
VLT® Decentral Drive FCD 302
Operating Guide Mechanical Installation
3 Mechanical Installation
3.1 Unpacking
•
3.1.1 Items Supplied
The packaging contains:
Accessories bag, supplied only with order of installation box. The bag contains:
-
-
-
2 cable clamps.
Bracket for motor/loads cables.
Elevation bracket for cable clamp.
Screw 4 mm, 20 mm.
•
•
•
•
Thread forming 3.5 mm, 8 mm.
Operating Guide.
Drive.
Depending on options fitted, the box contains 1 or 2 bags and 1 or more booklets.
Make sure that the items supplied and the information on the nameplate correspond to the order confirmation.
Check the packaging and the drive visually for damage caused by inappropriate handling during shipment. File any claim for damage with the carrier. Retain damaged parts for clarification.
6
7
4
5
1
2
9
1
2
3
4
5
VLT®
Decentral Drive www.danfoss.com
Enclosure rating:
Type 4X Indoor Use Only
LISTED E134261 76X1 IND. CONT. EQ.
10
T/C: FCD302P1K5T4W66H1X1XMFCFXXXXA0BXXXXXXDX
P/N: 131Z5118 S/N: 000000G000
1.5kW(400V) / 2.0HP(460V) 3
IN: 3x380-480V 50/60Hz, 3.7/3.1A
OUT: 3x0-Vin 0-590Hz, 4.1/3.4A
IP66 Enclosure Tamb. 40 ËšC/104 ËšF
8
Danfoss A/S
6430 Nordborg
Denmark
MADE IN DENMARK
* 1 3 1 Z 5 1 1 8 0 0 0 0 0 0 G 0 0 0 *
Type code
Ordering number
Serial number
Power rating
Input voltage, frequency, and current (at low/high voltages)
6
7
8
9
10
Output voltage, frequency, and current (at low/high voltages)
Enclosure type and IP rating
Maximum ambient temperature
Certifications
Enclosure rating
N O T I C E
LOSS OF WARRANTY
Do not remove the nameplate from the drive.
14 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Mechanical Installation
3.1.2 Storage
Ensure that the requirements for storage are fulfilled, see
.
3.2 Installation Environment
N O T I C E
-
REDUCED LIFETIME
In environments with airborne liquids, particles, or corrosive gases, ensure that the IP/Type rating of the equipment matches the installation environment. Failure to meet requirements for ambient conditions can reduce lifetime of the drive.
Ensure that requirements for air humidity, temperature, and altitude are met.
Vibration and shock
The drive complies with requirements for units mounted on the walls and floors of production premises, and in panels bolted to walls or floors. For detailed ambient conditions, refer to
.
3.3 Mounting
•
•
3.3.1 Cooling
The VLT® Decentral DriveFCD 302 has no forced cooling. It relies only on natural convection for cooling using the cooling fins.
A minimum of 100 mm (4 in) top and bottom air cooling clearance must be provided.
Derating starts above 40 °C (104 °F) and 1000 m (3280 ft) elevation above sea level. See the VLT® Decentral DriveFCD 302 Design
Guide for detailed information.
100 (4)
100 (4)
100 (4)
100 (4)
Illustration 4: Top and Bottom Cooling Clearance
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 15
VLT® Decentral Drive FCD 302
Operating Guide Mechanical Installation
3.3.2 Recommended Tools and Equipment
Table 3: Recommended Tools and Equipment
Equipment Size
Screwdrivers
Socket (Hex)
–
8
Slotted
Slotted/Torx
Spanner
LCP, ordering number 130B1078
LCP cable, ordering number 130B5776
0.4x2.5
1.0x5.5/TX20
19, 24, 28
–
–
3.3.3 Mounting
The VLT® Decentral DriveFCD 302 consists of 2 parts:
•
• Installation box
Electronic part
See
Description
–
For fastening inverter screws/mounting of brackets
For spring loaded power and control terminals
For cable clamps inside the installation box
For blind-plugs
Local control panel
Connection cable for local control panel
Illustration 5: Allowed Mounting Positions - Standard Applications
16 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Mechanical Installation
Illustration 6: Allowed Mounting Positions - Hygienic Applications
3.3.3.1 Mounting the Installation Box
W A R N I N G
-
ELECTRICAL HAZARD
Applying power to the unit at this stage could result in death or serious injury.
Do not apply power before the electrical installation is complete.
W A R N I N G
-
-
PERSONAL INJURY OR PROPERTY DAMAGE
Do not switch on the mains before the 4 screws are tightened. Failure to tighten these screws can result in personal injury or material damage when the unit is loaded.
Tighten screws before switching on power.
Ensure that the strength of the mounting location can support the unit weight.
•
•
•
Use the holes on the rear of the installation box to fix mounting brackets.
Use proper mounting screws or bolts.
For hygienic versions, use cable glands designed to meet hygienic application requirements, for example Rittal HD
2410.110/120/130.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 17
VLT® Decentral Drive FCD 302
Operating Guide Mechanical Installation
1.
Example
Mount the VLT® Decentral DriveFCD 302 vertically on a wall or machine frame. For hygienic versions ensure that liquids drain off the enclosure and orient the unit so the cable glands are located at the base.
Illustration 7: FCD 302 Standalone Mounted with Mounting Brackets
3.3.3.2 Installing the Inverter Part
Procedure for compressing the gasket between the 2 parts.
Procedure
1.
2.
Tighten the 4 connection screws to torque 2.8–3.0 Nm (24–26 in-lb).
Tighten the 4 screws in diagonally opposite order.
3.
Tighten the 2 grounding spears to torque 3.0 (26 in-lb).
18 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
4 Electrical Installation
4.1 Safety Instructions
See 2.1 Safety Precautions for general safety instructions.
W A R N I N G
-
-
INDUCED VOLTAGE
Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned off and locked out. Failure to run output motor cables separately or to use shielded cables could result in death or serious injury.
Run output motor cables separately or use shielded cables.
Simultaneously lock out all the drives.
W A R N I N G
SHOCK HAZARD
The unit can cause a DC current in the PE conductor. Failure to use a Type B residual current-operated protective device (RCD)
may lead to the RCD not providing the intended protection and therefore may result in death or serious injury.
When an RCD is used for protection against electrical shock, only a Type B device is allowed on the supply side.
•
•
Overcurrent protection
Extra protective equipment, such as short-circuit protection or motor thermal protection between drive and motor, is required for applications with multiple motors.
Input fusing is required to provide short circuit and overcurrent protection. If not factory-supplied, the installer must provide fuses. See maximum fuse ratings in
7.7.2 Recommended Maximum Pre-fuse Size 25 A .
•
•
Wire type and ratings
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
Power connection wire recommendation: Minimum 75 °C (167 °F) rated copper wire. See wire sizes and types.
7.1 Electrical Data for recommended
4.2 EMC-compliant Installation
To obtain an EMC-compliant installation, follow the instructions provided in 4.3 Grounding
,
, and
N O T I C E
POTENTIAL EQUALIZATION
Risk of burst transient when the ground potential between the drive and the control system is different. Install equalizing cables between the system components. Recommended cable cross-section: 16 mm 2 (6 AWG).
•
•
•
•
•
•
4.3 Grounding
For electrical safety
Ground the drive in accordance with applicable standards and directives.
Use a dedicated ground wire for input power, motor power, and control wiring.
Do not ground 1 drive to another in a daisy chain fashion.
Keep the ground wire connections as short as possible.
Follow motor manufacturer's wiring requirements.
Minimum cable cross-section: 10 mm 2 (7 AWG) (or 2 rated ground wires terminated separately).
For EMC-compliant installation
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 19
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
•
•
•
Establish electrical contact between the cable shield and the drive enclosure by using metal cable glands or by using the clamps provided on the equipment.
Use high-strand wire to reduce electrical interference.
Do not use pigtails.
N O T I C E
POTENTIAL EQUALIZATION
Risk of burst transient when the ground potential between the drive and the control system is different. Install equalizing cables between the system components. Recommended cable cross-section: 16 mm 2 (6 AWG).
C A U T I O N
PE CONNECTION
The metal pins in the corners of the electronic part and the holes on the corner of the installation box are essential for the protective earth connection. Make sure that they are not loosened, removed, or violated in any way. Tightening torque requirement is
3 Nm (26.6 in-lb).
Illustration 8: PE Connection Between the Installation Box and the Electronic Part
N O T I C E
The external grounding terminal is available as an accessory (ordering number 130B5833).
20 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
4.4 Wiring Schematic
Electrical Installation
3-phase power input
Mechanical brake
+10 V DC
-10 V DC-
+10 V DC
0/4-20 mA
-10 V DC-
+10 V DC
0/4-20 mA
91 (L1)
92 (L2)
93 (L3)
95 (PE)
122(MBR+)
123(MBR-)
50 (+10 V OUT)
S201
53 (A IN)
S202
54 (A IN)
ON/I=0-20mA
OFF/U=0-10V
Switch mode power supply
10 V DC
15 mA
24 V DC
600 mA
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN/OUT)
P 5-00
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
S801
ON=Terminated
OFF=Open
(U) 96
(U) 97
(W) 98
(PE) 99
(R+) 82
(R-) 81
Relay1
03
02
Relay2
01
06
05
04
0 V
(COM A OUT) 39
(A OT) 42
5V
29 (D IN/OUT)
24V
24 V (NPN)
0 V (PNP)
32 (D IN)
33 (D IN)
37 (D IN)
OV
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
Brake resistor
240 V AC, 2A
240 V AC, 2A
400 V AC, 2A
Analog output
0/4–20 mA
RS485
Interface
S801
GX
(N RS485) 69
(P RS485) 68
(COM RS485) 61
GX
RS485
(PNP) = Source
(NPN) = Sink
Motor
VCXA
PROFIBUS interface
67
GND1
62
63
66
RS485
GND1
Illustration 9: Basic Wiring Schematic
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 21
VLT® Decentral Drive FCD 302
Operating Guide
2
1
L1
L2
L3
PE
1 L1
3 L2
5 L3
33 NO
41 NC
T1 2
T2 4
T3 6
NO 34
NC 42
L1
91
L2
92
L3
93
12
27
U
96
V
97
W
98
Illustration 10: Large Unit only: Circuit Breaker and Mains Disconnect
1
2
Looping terminals
Circuit breaker
1
L1
L2
L3
PE
1
3
5
7
2
4
6
8
L1
91
L2
92
L3
93
12
27
U
96
V
97
W
98
U
V
W
Illustration 11: Large Unit only: Service Switch at Mains with Looping Terminals
1 Looping terminals
Electrical Installation
22 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
4.5 Location of Terminals
4 2 1 3 11 12
Electrical Installation
5
13
6
13
7 8
Illustration 12: Location of Terminals (Small Unit)
1
4
5
2
3
6
7
Digital and analog inputs/outputs
Safe Torque Off (STO), LCP connection, B-option
Relay 1
Relay 12
Motor, mechanical brake, brake resistor
Mains
24 V DC back-up input
13 9
10
8
9
10
11
12
13
USB port
Standard bus/RS485
PROFIBUS
Ethernet port
Ethernet port
Protective Earth (PE)
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 23
VLT® Decentral Drive FCD 302
Operating Guide
4 2 1 3 11 12 13
5
13
Electrical Installation
6
7 8
Illustration 13: Location of Terminals (Large Unit)
13 9 10
1
4
5
2
3
6
7
Digital and analog inputs/outputs
Safe Torque Off (STO), LCP connection, B-option
Relay 1
Relay 12
Motor, mechanical brake, brake resistor
Mains
24 V DC back-up input
8
9
10
11
12
13
USB port
Standard bus/RS485
PROFIBUS
Ethernet port
Ethernet port
Protective Earth (PE)
For both small and large units, the service switch is optional. The switch is shown mounted on the motor side. Alternatively, the switch can be on the mains side or omitted.
For the large unit, the circuit breaker is optional. The large unit can be configured with either service switch or circuit breaker, not both. The illustration shown is not configurable in practice, but shows the respective positions of components only.
4.6 Terminal Types
Motor, control, and mains terminals are spring loaded (CAGE-CLAMP) type.
1.
Open the contact by inserting a small screwdriver into the slot above the contact, as shown in
2.
3.
Insert the stripped wire into the contact.
Remove the screwdriver to fasten the wire into the contact.
24 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
4.
Example
Ensure that the contact is firmly established and not loose. Loose wiring can result in equipment faults or injury.
Illustration 14: Opening the Terminals
4.7 Connecting the Motor
W A R N I N G
INDUCED VOLTAGE
Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned
-
off and locked out. Failure to run output motor cables separately or to use shielded cables could result in death or serious injury.
Run output motor cables separately or use shielded cables.
Simultaneously lock out all the drives.
U
U1
W2
U1
N O T I C E
MOTOR PROTECTION
Protection against motor overload is not included in the factory setting. If this function is desired, set parameter 1-90 Motor Ther-
mal Protection to trip or warning. Refer to the VLT® AutomationDrive FC 301/FC 302 Programming Guide for further information.
For correct dimensioning of cable cross-section, see 7.1 Electrical Data .
Table 4: Terminals 96, 97, 98
Terminal
96 97 98
V
V1
U2
V1
W
W1
V2
W1
Motor voltage 0–100% of mains voltage
3 wires out of motor
6 wires out of motor
6 wires out of motor
6 wires out of motor, star connected. Connect U2, V2, W2
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 25
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
Terminal
PE separately (optional terminal block)
Ground connection
N O T I C E
Do not install power factor correction capacitors between the drive and the motor. Do not wire a starting or pole-changing device between the drive and the motor.
1.
2.
3.
Connect the motor to terminals 96, 97, 98.
Connect ground to PE terminal.
Make sure that the shield of the motor cable is properly grounded at both ends (motor and drive).
4.7.1 Grounding Shielded Cable
Grounding clamps are provided for motor and control wiring.
Illustration 15: Grounding Clamp for Motor and Control Wiring (Small Unit)
26 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
Illustration 16: Grounding Clamp for Motor and Control Wiring (Large Unit)
Procedure
1.
Use a wire stripper to remove the insulation for proper grounding.
2.
3.
Secure the grounding clamp to the stripped portion of the wire with the screws provided.
Secure the grounding wire to the grounding clamp provided.
4.7.2 Connecting Several Motors
The drive can control several parallel-connected motors. The total current consumption of the motors must not exceed the rated output current I
M,N
for the drive.
N O T I C E
Installations with cables connected in a common joint are only recommended for short cable lengths (maximum 10 m (38.2 ft)).
When motors are connected in parallel, parameter 1-29 Automatic Motor Adaptation (AMA) cannot be used.
N O T I C E
The electronic thermal relay (ETR) of the drive cannot be used as motor protection for the individual motor in systems with parallel-connected motors. Provide further motor protection by thermistors in each motor or individual thermal relays. Circuit breakers are not suitable as protection.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 27
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
Illustration 17: Parallel Connection of Motors
•
•
Problems can arise at start-up and at low RPM values when motor sizes differ widely. Motors of low rated motor power have a relatively high ohmic resistance in the stator. This high resistance calls for a higher voltage at start and at low RPM values. To resolve such a problem:
Reduce the load during start-up on the motor of lowest rated motor power.
Configure parallel connections only between motors of comparable rated motor power.
•
•
4.8 Connecting AC Mains
Size the wiring based on the input current of the drive. For maximum wire sizes, see
.
Comply with local and national electrical codes for cable sizes.
91
L1
PE
4.8.1 Connecting the Drive to Mains
Table 5: Terminals 91, 92, and 93
Terminals
92
L2
93
L3
Mains voltage 3x380–480 V
Ground connection
Procedure
1.
2.
Connect the 3-phase AC input power wiring to terminals L1, L2, and L3.
Depending on the configuration of the equipment, connect the input power to the mains input terminals or the input disconnect.
3.
4.
Ground the cable in accordance with the grounding instructions, see
4.7.1 Grounding Shielded Cable
.
When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] Off . This setting prevents damage to the DC link and reduces ground capacity currents in accordance with IEC 61800-3.
28 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
4.9 Motor and Mains Connection with Service Switch
Electrical Installation
Illustration 18: Motor and Mains Connection with Service Switch
4.10 Control Terminals
4.10.1 Control Wiring
W A R N I N G
-
-
-
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death, serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condition.
Press [Off] on the LCP before programming parameters.
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor start.
Check that the drive, motor, and any driven equipment are in operational readiness.
•
•
•
It is recommended that control wiring is rated for 600 V.
Isolate control wiring from high-power components in the drive.
If the drive is connected to a thermistor, for PELV isolation, ensure that control wiring is reinforced/double insulated.
4.10.2 Terminal Functions
Table 6: Terminal Functions
Terminal
Number
Functions
01, 02, 03
04, 05, 06
Relay 1 output. Usable for AC or DC voltage and resistive or inductive loads.
Relay 2 output. Usable for AC or DC voltage and resistive or inductive loads.
12, 13 24 V DC digital supply voltage. Useable for digital inputs and external transducers. To use the 24 V DC for digital input common, programme parameter 5-00 Digital I/O Mode for PNP operation.
18, 19, 32, 33 Digital inputs. Selectable for NPN or PNP function in parameter 5-00 Digital I/O Mode . Default is PNP.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 29
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
35
36
37
20
Terminal
Number
27, 29
Functions
55
61
39
42
50
53, 54
68 (+), 69 (-)
62
63
66
67
B01-B12
G, R, V, N, P
Digital inputs or outputs. Program parameter 5-01 Terminal 27 Mode for terminal 27 and parameter 5-02 Terminal
29 Mode for terminal 29 for selecting the input/output functions. Default setting is input.
Common (-) for external 24 V control back-up supply. Optional.
External + 24 V control back up supply. Optional.
Safe Stop.
Common for digital inputs. To use for digital input common, programme parameter 5-00 Digital I/O Mode for
NPN operation.
Common for analog output.
Analog output. Programmable for various functions in parameter group 6-5* Analog Output 1 . The analog signal is 0–20 mA or 4–20 mA at a maximum of 500 Ω.
10 V DC analog supply voltage. 15 mA maximum commonly used for a potentiometer or thermistor.
Analog input. Selectable for voltage (0 to ±10 V) or current (0 or 4 to ± 20 mA). Closed is for current and open is for voltage. Switches are located on the drive control card.
See
.
Common for analog inputs.
Common for serial communication (RS485 interface).
See
RS485 interface. When the drive is connected to an RS485 serial communication bus, a switch on the control card is provided for termination resistance. Set the switch to ON for termination and OFF for no termination.
RxD/TxD –P (red cable) for PROFIBUS. See dedicated literature for VLT® PROFIBUS DP V1 MCA 101) for details.
RxD/TxD –N (green cable) for PROFIBUS.
0 V for PROFIBUS.
+5 V for PROFIBUS.
B-option. See dedicated literature for details.
Connection of LCP.
4.10.3 Brake Resistor
Table 7: Brake Resistor Terminals
Terminal
81 (optional function)
82 (optional function)
Function
R-
R+
Brake resistor terminals
•
•
The connection cable to the brake resistor must be shielded/armored. Connect the shield to the metal cabinet of the drive and to the metal cabinet of the brake resistor with cable clamps.
Dimension the cross-section of the brake cable to match the brake torque.
30 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
4.10.4 Mechanical Brake
Table 8: Terminals 122 and 123
Number Function
122 (optional function)
123 (optional function)
MBR+
MBR-
•
•
In hoisting/lowering applications, control of electro-mechanical brake is required:
The brake is controlled using the special mechanical brake control/supply terminals 122 and 123.
Select brake.
[32] Mechanical brake control in parameter group 5-4* Relays , [1] Array, Relay 2 for applications with an electro-mechanical
•
• The brake is released when the motor current exceeds the preset value in parameter 2-20 Release Brake Current .
The brake is engaged when the output frequency is less than the frequency set in parameter 2-21 Activate Brake Speed [RPM] or parameter 2-22 Activate Brake Speed [Hz] . The brake engages only when the drive performs a stop command.
When the drive enters alarm mode or is exposed to an overvoltage situation, the mechanical brake immediately cuts in. For more detailed information, refer to the VLT® AutomationDrive FC 301/FC 302 Programming Guide.
N O T I C E
When the mechanical brake control/supply terminals 122 and 123 are set through parameter group 5–4* Relays , [1] Array , Relay 2 , only 1 relay output (Relay 1) is available for free programming.
1
3
4
4.10.5 Connection of Sensors/Actuators on M12 Sockets
Table 9: 4 x M12 Connection Input
Pin Wire color Terminal
Brown
Blue
Black
12
20
18, 19, 32, 33
Table 10: 2 x M12 Connection Output
Pin Wire color
1
3
4
Brown
Blue
Black
Terminal
Reserved (1)
20
02, 05
Function
+24 V
0 V
Digital input
Function
Reserved
0 V
N.O. (24 V)
1 When reserved wires for option are used. If not utilized, they can be cut off.
•
•
Mechanical brake
UDC = 0.45 x RMS mains voltage
Maximum current = 0.8 A
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 31
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
LCP RL2 RL1 33
FB2 FB1
USB
18 19 32
Illustration 19: Connection of Sensors/Actuators on M12 Sockets
•
•
•
•
4.10.6 DIP Switches
Analog input terminals 53 and 54 can select either voltage (0-10 V) or current (0-20 mA) input signals.
Set switches S201 (terminal 53) and S202 (terminal 54) to select the signal type. ON is for current, OFF for voltage.
Terminal 53 default is for a speed reference in open loop.
Terminal 54 default is for a feedback signal in closed loop.
1 2
3
4
Illustration 20: Location of DIP Switches
5
1
2
3
S201 - terminal 53
S202 - terminal 54
S801 - standard bus termination
4
5
PROFIBUS termination
Fieldbus address
N O T I C E
Switches 4 and 5 are only valid for units fitted with fieldbus options.
Refer to VLT® PROFIBUS DP V1 MCA 101 Programming Guide for further information.
4.10.7 Safe Torque Off (STO)
To run STO, additional wiring for the drive is required.
Refer to the VLT® Frequency Converters Safe Torque Off Operating Guide for further information.
•
•
4.10.8 RS485 Serial Communication
Use shielded serial communication cable.
for proper grounding.
32 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
•
•
•
•
-
-
2 communication protocols are internal to the drive:
Danfoss FC.
Modbus RTU.
Functions can be programmed remotely using the protocol software and RS485 connection or in parameter group 8-** Communications and Options .
Selecting a specific communication protocol changes various default parameter settings to match the specifications of that protocol and makes more protocol-specific parameters available.
Option cards for the drive are available to provide extra communication protocols. See the option card documentation for installation and operating guides.
4.10.8.1 Connecting and Setting Up RS485
Procedure
1.
Connect RS485 serial communication wiring to terminals (+)68 and (-)69.
61
68
69
+
RS485
2.
3.
4.
Illustration 21: Serial Communication Wiring Diagram
Select the protocol type in parameter 8-30 Protocol .
Set the drive address in parameter 8-31 Address .
Set the baud rate in parameter 8-32 Baud Rate .
4.11 Installation Checklist
Before completing installation of the unit, inspect the entire installation as detailed in
. Check and mark the items when completed.
Table 11: Start-up Checklist
Inspect for Description ☑
Auxiliary equipment
•
•
•
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers located on the input power side of the drive, or the output side to the motor. Examine their operational readiness and ensure that they are ready in all respects for operation at full speed.
Check function and installation of any sensors used for feedback to the drive.
Remove power factor correction caps on motor(s), if present.
Cable routing
Control wiring
Ensure that input power, motor wiring and control wiring are separated or in 3 separate metallic conduits for high-frequency noise isolation.
•
•
•
Check for broken or damaged wires and connections.
Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly at both ends.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 33
VLT® Decentral Drive FCD 302
Operating Guide Electrical Installation
Inspect for
EMC considerations
Environmental considerations
Description
Check for proper installation regarding electromagnetic compatibility.
See the equipment label for the maximum ambient operating temperature limits. Temperature is not to exceed 40°C (104°F). Humidity levels must be 5-95% non-condensing.
Cooling clearance Units require top and bottom clearance adequate to ensure proper air flow for cooling.
Fusing and circuit breakers
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are in the open position. Check for proper fusing or circuit breakers.
Input and output power wiring
•
• Check for loose connections.
Check for proper fusing or circuit breakers.
☑
Switches
Grounding
Installation box and electronics part
Cable glands and blind plugs
Vibration
Ensure that all switch and disconnect settings are in the proper position.
The equipment requires a dedicated ground wire from its chassis to the plant ground. Check for good ground connections that are tight and free of oxidation.
Ensure the installation box and the electronics part is properly closed. Check that all 4 fastening screws are tightened with the right torque.
Ensure the cable glands and blind plugs are properly tightened to guarantee that the right enclosure protection degree is achieved. Liquids and/or excessive dust ingress in the drive can cause sub-optimal performance or damage.
Ensure the equipment is not exposed to a high level of vibration. Mount the panel solidly or use shock mounts as necessary.
C A U T I O N
-
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
34 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Commissioning
5 Commissioning
5.1 Safety Instructions
See 2.1 Safety Precautions for general safety instuctions.
W A R N I N G
-
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
7.
8.
9.
4.
5.
6.
5.1.1 Before Applying Power
Procedure
1.
2.
3.
Close the safety cover properly.
Check that all cable glands are firmly tightened.
Ensure that input power to the unit is off and locked out. Do no rely on the drive disconnect switches for input power isolation.
Verify that there is no voltage on input terminals L1 (91), L2 (92), and L3 (93), phase-to-phase, and phase-to-ground.
Verify that there is no voltage on output terminals 96 (U), 97 (V), and 98 (W), phase-to-phase, and phase-to-ground.
Confirm continuity of the motor by measuring Ω values on U–V (96–97), V–W (97–98), and W–U (98–96).
Check for proper grounding of the drive and the motor.
Inspect the drive for loose connections on the terminals.
Confirm that the supply voltage matches the voltage of the drive and the motor.
5.2 Applying Power
W A R N I N G
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death, serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command,
-
-
an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condition.
Press [Off] on the LCP before programming parameters.
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor start.
Check that the drive, motor, and any driven equipment are in operational readiness.
Procedure
1.
Confirm that the input voltage is balanced within 3%. If not, correct the input voltage imbalance before proceeding. Repeat this procedure after the voltage correction.
2.
3.
Ensure that any optional equipment wiring matches the installation application.
Ensure that all operator devices are in the OFF position. Panel doors must be closed and covers securely fastened.
4.
Apply power to the unit. Do not start the drive now. For units with a disconnect switch, turn it to the ON position to apply power to the drive.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 35
VLT® Decentral Drive FCD 302
Operating Guide Commissioning
5.3 Local Control Panel Operation
•
5.3.1 Local Control Panel
The local control panel (LCP) is the combined display and keypad on the front of the unit.
LCP functions
Control drive speed in hand-on mode.
•
•
•
• Start, stop, and control speed when in local control.
Show operational data, status, warnings, and cautions.
Program drive functions.
Manually reset the drive after a fault when auto reset is inactive.
An optional numeric LCP (NLCP) is also available. The NLCP operates in a manner similar to the LCP. See the product-relevant Programming Guide for details on use of the NLCP.
N O T I C E
For commissioning via PC, install the MCT 10 Set-up Software. The software is available for download (basic version) or for ordering (advanced version, code number 130B1000). For more information and downloads, see www.danfoss.com
.
•
•
•
•
5.3.2 LCP Layout
The LCP is divided into 4 functional groups:
A: Display area
B: Display menus and keys
C: Navigation keys and indicator lights (LEDs)
D: Operation keys and reset
1
2
A
Status
799 RPM 7.83 A
0.000
53.2 %
1(1)
36.4 kW
Auto Remote Ramping 4
6
B Status
Quick
Menu
Main
Menu
Alarm
Log
7
B ack
C an ce l
10
15
16
17
C
On
Warn.
Alarm
OK
D Hand
On
Off
Auto
On
18 19
Illustration 22: Local Control Panel (LCP)
20
Reset
21
3
5
9
8
11
12
13
14
36 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Commissioning
3
4
1
2
5
Area A: Display area
The display area is activated when the drive receives power from mains voltage, a DC bus terminal, or an external 24 V DC supply.
The information shown on the LCP can be customized for user application. Select options in the Quick Menu Q3-13 Display Settings .
Table 12: Legend to Area A, Display Area
Callout Parameter Default setting
Parameter 0-20 Display Line 1.1 Small
Parameter 0-21 Display Line 1.2 Small
Parameter 0-22 Display Line 1.3 Small
Parameter 0-23 Display Line 2 Large
Parameter 0-24 Display Line 3 Large
[1617] Speed [RPM]
[1614] Motor Current
[1610] Power [kW]
[1613] Frequency
[1602] Reference %
Area B: Display menu keys
Menu keys are used for menu access for parameter set-up, toggling through status display modes during normal operation, and viewing fault log data.
Table 13: Legend to Area B, Display Menu Keys
Callout Key Function
6
7
Status Shows operational information.
Quick Menu Allows access to programming parameters for initial setup instructions and many detailed application instructions.
8
9
Main Menu Allows access to all programming parameters.
Alarm Log Shows a list of current warnings, the last 10 alarms, and the maintenance log.
12
13
10
11
14
Area C: Navigation keys and indicator lights (LEDs)
Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local (hand) operation. There are also 3 drive status indicator lights in this area.
Table 14: Legend to Area C, Navigation Keys
Callout Key Function
Back
Cancel
Info
Navigation keys
OK
Reverts to the previous step or list in the menu structure.
Cancels the last change or command as long as the display mode has not changed.
Press for a definition of the function being shown.
Press to move between items in the menu.
Press to access parameter groups or to enable a choice.
Table 15: Legend to Area C, Indicator Lights (LEDs)
Callout Indicator Light Function
15 ON
16
17
WARN
ALARM
Green The ON light activates when the drive receives power from mains voltage, a DC bus terminal, or an external 24 V DC supply.
Yellow When warning conditions are met, the yellow WARN light comes on and text appears in the display area identifying the problem.
Red A fault condition causes the red alarm light to flash and an alarm text is shown.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 37
VLT® Decentral Drive FCD 302
Operating Guide Commissioning
Area D: Operation keys and reset
Operation keys are a the bottom of the LCP.
Table 16: Legend to Area D, Operation Keys and Reset
Callout Key Function
18 Hand On Starts the drive in local control.
• An external stop signal by control input or serial communication overrides the local control.
19
20
Off Stops the motor but does not remove power to the drive.
Auto On Puts the system in remote control.
• Responds to an exteral start command by control terminals or serial communication.
21 Reset Resets the drive manually after a fault has been cleared.
N O T I C E
The display contrast can be adjusted by pressing [Status] and[ â–µ ]/[ â–¿ ] keys.
•
•
•
5.3.3 Parameter Settings
Establishing the correct programming for applications often requires setting functions in several related parameters.
Programming data are stored internally in the drive.
For back-up, upload data into the LCP memory.
To download data to another drive, connect the LCP to that unit and download the stored settings.
Restoring factory default settings does not change data stored in the LCP memory.
5.3.4 Uploading/Downloading Data to/from the LCP
Procedure
1.
Press [Off] to stop the motor before uploading or downloading data.
4.
5.
2.
3.
Press [Main Menu].
Go to parameter 0-50 LCP Copy and press [OK].
Select [1] All to LCP to upload data to the LCP, or select [2] All from LCP to download data from the LCP.
Press [OK].
6.
ï‚© A progress bar shows the uploading or downloading process.
Press [Hand On] or [Auto On] to return to normal operation.
5.3.5 Changing Parameter Settings
Parameter settings can be accessed and changed via the [Quick Menu] or [Main Menu] keys. The Quick Menu only gives access to a limited number of parameters.
Procedure
1.
2.
3.
4.
5.
6.
7.
Press [Quick Menu] or [Main Menu] on the LCP.
Press [ â–µ ]/[ â–¿ ] to browse through the parameter groups, press [OK] to select a parameter group.
Press [ â–µ ]/[ â–¿ ] to browse through the parameters, press [OK] to select a parameter.
Press [ â–µ ]/[ â–¿ ] to change the value of a parameter setting.
Press [ â—ƒ ]/[ â–¹ ] to shift digit when a decimal parameter is in the editing state.
Press [OK] to accept the change.
Press either [Back] twice to enter Status , or press [Main Menu] once to enter Main Menu .
38 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Commissioning
5.3.6 Restoring Default Settings
N O T I C E
-
RISK OF LOSING DATA
When restoring default settings, there is a risk of losing programming, motor data, localization, and monitoring records.
Provide a back-up by uploading data to the LCP before initialization.
•
•
Restoring the default parameter settings is done by initialization of the drive. Initialization is carried out via parameter 14-22 Operation Mode (recommended) or manually.
Initialization via parameter 14-22 Operation Mode does not reset the drive settings such as hours run, serial communication selections, personal menu settings, fault log, alarm log, and other monitoring functions.
Manual initialization erases all motor programming, localization, and monitoring data, and restores factory default settings.
5.3.6.1 Recommended Initialization
Procedure
1.
Press [Main Menu] twice to access parameter.
4.
5.
2.
3.
Scroll to parameter 14-22 Operation Mode and press [OK].
Scroll to [2] Initialisation and press [OK].
Remove power to the unit and wait for the display to turn off.
Apply power to the unit.
6.
7.
ï‚© Default parameter settings are restored during start-up. This may take slightly longer than normal.
Alarm 80, Drive initialised is shown.
Press [Reset] to return to operating mode.
5.3.6.2 Manual Initialization
Procedure
1.
Remove power to the unit and wait for the display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at the same time while applying power to the unit (approximately 5 s or until a click is heard and the fan starts).
ï‚© Factory default parameter settings are restored during start-up. This might take slightly longer than normal.
•
•
•
•
Manual initialization resets parameter settings except for the settings in:
Parameter 15-00 Operating Hours .
Parameter 15-03 Power Up's .
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's .
.
5.4 Basic Operational Programming
Drives require basic operational programming before running for best performance. Basic operational programming requires entering motor nameplate data for the motor being operated and the minimum and maximum motor speeds. Enter the data in accordance with the following procedure. See
5.3.2 LCP Layout for detailed instructions on entering data through the LCP. Enter the data
with power ON, but before operating the drive.
1.
Press [Quick Menu] on the LCP.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 39
VLT® Decentral Drive FCD 302
Operating Guide
2.
Use the navigation keys to scroll to parameter group Q2 Quick Setup and press [OK].
Commissioning
13.7% 0.75A 1 (1)
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
3.
4.
Illustration 23: Quick Menus
-
-
-
-
-
-
Select language and press [OK].
Enter the motor data in parameter 1-20 Motor Power [kW] / parameter 1-21 Motor Power [HP] through parameter 1-25 Motor
Nominal Speed . The information can be found on the motor nameplate. The entire quick menu is shown in International/
North American default parameter settings.
Parameter 1-20 Motor Power [kW]
Parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
0.0 Hz 0.00kW 1(1)
Motor Setup Q2
1 - 21 Motor Power [kW]
2.2 kW
5.
Illustration 24: Motor Set-up
Continue set-up of Quick Menu parameters: a.
Parameter 5-12 Terminal 27 Digital Input
[0] No operation .
. If terminal default is [2] Coast inverse , it is possible to change this setting to b.
c.
d.
e.
Parameter 1-29 Automatic Motor Adaptation (AMA) . Set desired AMA function. Enable complete AMA is recommended.
Parameter 3-02 Minimum Reference . Set the minimum speed of the motor shaft.
Parameter 3-03 Maximum Reference . Set the maximum speed of the motor shaft.
Parameter 3-41 Ramp 1 Ramp Up Time . Set the ramping up time regarding synchronous motor speed, ns.
f.
g.
Parameter 3-42 Ramp 1 Ramp Down Time
Parameter 3-13 Reference Site
. Set the ramping down time regarding synchronous motor speed, ns.
. Set the site from where the reference must work.
40 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Commissioning
5.5 Automatic Motor Adaptation (AMA)
AMA is not relevant for permanent magnet motors.
N O T I C E
•
•
•
•
•
•
Automatic motor adaptation (AMA) is a procedure that optimizes compatibility between the drive and the motor.
The drive builds a mathematical model of the motor for regulating output motor current. The procedure also tests the input phase balance of electrical power. It compares the motor characteristics with the data entered in parameters 1-20 to 1-25 .
The motor shaft does not turn and no harm is done to the motor while running AMA.
Some motors may be unable to run the complete version of the test. In that case, select
If an output filter is connected to the motor, select [2] Enable reduced AMA .
[2] Enable reduced AMA .
If warnings or alarms occur, see 6.8 List of Warnings and Alarms .
Run this procedure on a cold motor for best results.
5.5.1 Running AMA
Enter the advanced motor data in parameter group 1-3* Adv. Motor Data .
Procedure
1.
Press [Main Menu] to access parameters.
2.
Scroll to parameter group 1-** Load and Motor and press [OK].
Scroll to parameter group 1-2* Motor Data and press [OK].
3.
4.
5.
6.
Scroll to parameter 1-29 Automatic Motor Adaptation (AMA) and press [OK].
Select [1] Enable complete AMA and press [OK].
Follow on-screen instructions.
ï‚© The test runs automatically and indicates when it is complete.
5.6 Local-control Test
To reset the drive after a trip, see 6.6 Warning and Alarm Types
.
Procedure
1.
Press [Hand On] to provide a local start command to the drive.
2.
Accelerate the drive by pressing [ â–µ ] to full speed. Moving the cursor left of the decimal point provides quicker input changes.
3.
4.
Note any acceleration problems.
Press [Off] and note any deceleration problems.
5.7 System Start-up
The procedure in this section requires wiring and application programming to be completed. The following procedure is recommended after application setup is completed.
If warnings or alarms occur, see
6.6 Warning and Alarm Types and
6.8 List of Warnings and Alarms .
1.
Press [Auto on].
2.
Apply an external run command.
3.
4.
5.
Adjust the speed reference throughout the speed range.
Remove the external run command.
Check the sound and vibration levels of the motor to ensure that the system is working as intended.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 41
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
6 Maintenance, Diagnostics and Troubleshooting
6.1 Maintenance and Service
Under normal operating conditions and load profiles, the drive is maintenance-free throughout its designed lifetime. To prevent breakdown, danger, and damage, examine the drive for loose terminal connections, excessive dust buildup, and so on, at regular intervals. Replace worn or damaged parts with Danfoss authorized parts. For service and support, contact the local Danfoss supplier.
W A R N I N G
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death, serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command,
-
-
an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condition.
Press [Off] on the LCP before programming parameters.
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor start.
Check that the drive, motor, and any driven equipment are in operational readiness.
6.2 Cleaning
The enclosure (IP66/NEMA type 4x indoor) provides protection against dirt and water ingress. The enclosure is suitable for cleaning methods and solvents used in food and beverage plants. Use the solvent concentration recommended by the manufacturer. Avoid high-pressure hot water cleaning at close proximity or of long duration, because this method of cleaning can damage gaskets and labels.
6.3 Frontal LEDs
The actual status can be read via 6 LEDs, which signal the actual status of the unit.
ON W ar ning A lar m
Bus MS NS1 NS2
Illustration 25: Frontal LEDs
Table 17: Description of Frontal LEDs
Name Color
ON Green
Status
On
Warning Yellow
Alarm Red
Off
On
Off
Flashing
Off
Indication, frontal LEDs
The drive receives power from mains voltage or external 24 V supply.
No power from mains voltage or external 24 V supply.
Warning situation is present.
No warning is present.
Alarm is present.
No alarm is present
42 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
Name Color Status
Bus MS Only relevant if optional fieldbus is present. See fieldbus-dedicated manuals for specific information.
Bus NS1 Only relevant if optional fieldbus is present. See fieldbus-dedicated manuals for specific information.
Bus NS2 Only relevant if optional fieldbus is present. See fieldbus-dedicated manuals for specific information.
Indication, frontal LEDs
Bus Module Status
Bus Network Status 1
Bus Network Status 2
6.4 Status Display
When the drive is in Status mode, status messages are generated automatically and appear in the bottom line of the display, see
.
Status
799RPM 7.83A 36.4kW
0.000
53.2%
1(1)
1
Auto
Hand
Off
Remote
Local
2
3
Illustration 26: Status Display
1
2
Ramping
Stop
Running
Jogging
.
.
.
Standby
Operating mode (see Table 18 )
Reference site (see
)
3 Operation status (see
)
6.5 Status Message Definitions
for definitions of the status messages.
Table 18: Operating Mode
Off The drive does not react to any control signal until [Auto On] or [Hand On] is pressed.
Auto On The drive is controlled from the control terminals and/or the serial communication.
Hand On The drive is controlled by the navigation keys on the LCP. Stop commands, reset, reversing, DC brake, and other signals applied to the control terminals override local control.
Table 19: Reference Site
Remote The speed reference is given from external signals, serial communication, or internal preset references.
Local
The drive uses [Hand On] control or reference values from the LCP.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 43
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
Table 20: Operation Status
AC Brake [2] AC brake is selected in controlled slow down.
parameter 2-10 Brake Function . The AC brake overmagnetizes the motor to achieve a
AMA finish
OK
AMA was carried out successfully.
AMA ready AMA is ready to start. Press [Hand On] to start.
AMA running
AMA process is in progress.
The brake chopper is in operation. Generative energy is absorbed by the brake resistor.
Braking
Braking max.
Coast
The brake chopper is in operation. The power limit for the brake resistor defined in
Limit (kW) has been reached.
parameter 2-12 Brake Power
•
•
Coast inverse was selected as a function for a digital input ( parameter group 5-1* Digital Inputs ). The corresponding terminal is not connected.
Coast activated by serial communication.
Ctrl. rampdown
•
•
[1] Control Ramp-down was selected in parameter 14-10 Mains Failure .
The mains voltage is below the value set in parameter 14-11 Mains Voltage at Mains Fault .
The drive ramps down the motor using a controlled ramp down.
Current
High
The drive output current is above the limit set in parameter 4-51 Warning Current High
Current Low The drive output current is below the limit set in parameter 4-52 Warning Speed Low .
.
DC Hold
DC Stop
[1] DC hold is selected in parameter 1-80 Function at Stop and a stop command is active. The motor is held by a DC current set in parameter 2-00 DC Hold/Preheat Current .
•
•
•
The motor is held with a DC current ( parameter 2-01 DC Brake Current ) for a specified time ( parameter 2-02 DC
Braking Time ).
The DC brake cut in speed is reached in parameter 2-03 DC Brake Cut In Speed [RPM] and a stop command is active.
[5] DC-brake inverse is selected as a function for a digital input ( sponding terminal is not active.
parameter group 5-1* Digital Inputs ). The corre-
The DC brake is activated via serial communication.
Feedback high
Feedback low
Freeze output
The sum of all active feedbacks is above the feedback limit set in
The sum of all active feedbacks is below the feedback limit set in parameter 4-57 Warning Feedback High parameter 4-56 Warning Feedback Low .
.
•
•
The remote reference is active, which holds the present speed.
[20] Freeze output sponding terminal is active. Speed control is only possible via the terminal options [21] Speed up and [22]
Speed down .
is selected as a function for a digital input ( parameter group 5-1* Digital Inputs ). The corre-
Hold ramp is activated via serial communication.
Freeze output request
A freeze output command was given, but the motor remains stopped until a run permissive signal is received.
44 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
Freeze ref.
[19] Freeze reference is selected as a function for a digital input ( parameter group 5-1* Digital Inputs ). The corresponding terminal is active. The drive saves the actual reference. Changing the reference is now only possible via terminal options [21] Speed up and [22] Speed down .
Jog request A jog command was given, but the motor remains stopped until a run permissive signal is received via a digital input.
Jogging
•
•
•
The motor is running as programmed in parameter 3-19 Jog Speed [RPM] .
[14] Jog was selected as a function for a digital input ( terminal (for example, terminal 29) is active.
parameter group 5-1* Digital Inputs ). The corresponding
The jog function is activated via the serial communication.
The jog function is selected as a reaction for a monitoring function (for example, for the no signal function).
The monitoring function is active.
Motor check In parameter 1-80 Function at Stop , [2] Motor Check is selected. A stop command is active. To ensure that a motor is connected to the drive, a permanent test current is applied to the motor.
OVC control Overvoltage control is activated via parameter 2-17 Over-voltage Control , [2] Enabled . The connected motor supplies the drive with generative energy. The overvoltage control adjusts the V/Hz ratio to run the motor in controlled mode and to prevent the drive from tripping.
PowerUnit
Off
Protection md
(Only drives with a 24 V external supply installed). Mains supply to the drive was removed, and the control card is supplied by the external 24 V.
•
•
•
Protection mode is active. The unit detected a critical status (overcurrent or overvoltage).
To avoid tripping, switching frequency is reduced to 4 kHz.
If possible, protection mode ends after approximately 10 s.
Protection mode can be restricted in parameter 14-26 Trip Delay at Inverter Fault .
QStop
•
•
The motor is decelerating using parameter 3-81 Quick Stop Ramp Time .
[4] Quick stop inverse is selected as a function for a digital input ( sponding terminal is not active.
parameter group 5-1* Digital Inputs ). The corre-
The quick stop function is activated via serial communication.
Ramping The motor is accelerating/decelerating using the active ramp up/down. The reference, a limit value, or a standstill is not yet reached.
The sum of all active references is above the reference limit set in parameter 4-55 Warning Reference High .
Ref. high
Ref. low
Run on ref.
The sum of all active references is below the reference limit set in parameter 4-54 Warning Reference Low .
The drive is running in the reference range. The feedback value matches the setpoint value.
Run request A start command was given, but the motor remains stopped until a run permissive signal is received via digital input.
Running The drive drives the motor.
Sleep Mode The energy-saving function is enabled. The motor has stopped, but restarts automatically when required.
Speed high Motor speed is above the value set in parameter 4-53 Warning Speed High .
Speed low Motor speed is below the value set in parameter 4-52 Warning Speed Low .
Standby
In auto-on mode, the drive starts the motor with a start signal from a digital input or serial communication.
Start delay In parameter 1-71 Start Delay , a delay starting time was set. A start command is activated, and the motor starts after the start delay time expires.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 45
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
Start fwd/rev
Stop
Trip
Trip lock
[12] Enable start forward and [13] Enable start reverse are selected as options for 2 different digital inputs ( parameter group 5-1* Digital Inputs ). The motor starts in forward or reverse direction depending on which terminal is activated.
The drive received a stop command from the LCP, digital input, or serial communication.
An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, the drive can be reset manually by pressing [Reset] or remotely by control terminals or serial communication.
An alarm occurred, and the motor is stopped. When the cause of the alarm is cleared, cycle power to the drive.
The drive can then be reset manually by pressing [Reset], or remotely by control terminals or serial communication.
N O T I C E
In auto/remote mode, the drive requires external commands to execute functions.
•
•
•
•
6.6 Warning and Alarm Types
Warnings
A warning is issued when an alarm condition is impending, or when an abnormal operating condition is present and may result in the drive issuing an alarm. A warning clears by itself when the abnormal condition ceases.
Alarms
An alarm indicates a fault that requires immediate attention. The fault always triggers a trip or a trip lock. Reset the system after an alarm.
Trip
An alarm is issued when the drive is tripped, meaning that the drive suspends operation to prevent damage to the drive or system.
The motor coasts to a stop. The drive logic continues to operate and monitor the drive status. After the fault condition is remedied, the drive can be reset. It is then ready to start operation again.
Trip lock
Input power is cycled. The motor coasts to a stop. The drive continues to monitor the drive status. Remove input power to the drive, correct the cause of the fault, and reset the drive.
Resetting the drive after a trip/trip lock
A trip can be reset in any of 4 ways:
Press [Reset] on the LCP.
Digital reset input command.
Serial communication reset input command.
Auto reset.
•
•
6.7 Warning and Alarm Displays
A warning is shown in the LCP along with the warning number.
An alarm flashes along with the alarm number.
Status
1(1)
0.0Hz 0.000kW 0.00A
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
Illustration 27: Alarm Example
46 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
In addition to the text and alarm code in the LCP there are 3 status indicator lights.
B ack
Ca nc el
Maintenance, Diagnostics and
Troubleshooting
On
Warn.
Alarm
OK
Illustration 28: Status Indicator Lights
Warning
Alarm
Trip lock
Warning indicator light
On
Off
On
Alarm indicator light
Off
On (flashing)
On (flashing)
6.8 List of Warnings and Alarms
The following warning and alarm information defines each warning or alarm condition, provides the probable cause for the condition, and entails a remedy or troubleshooting procedure.
•
6.8.1 WARNING/ALARM 4, Mains Phase Loss
Cause
A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in parameter 14-12 Function at Mains Imbalance .
Troubleshooting
Check the supply voltage and supply currents to the drive.
6.8.2 WARNING 5, DC Link Voltage High
Cause
The DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still active.
6.8.3 WARNING 6, DC Link Voltage Low
Cause
The DC-link voltage (DC) is lower than the low voltage warning limit. The limit depends on the drive voltage rating. The unit is still active.
•
•
•
6.8.4 WARNING/ALARM 8, DC Undervoltage
Cause
If the DC-link voltage drops below the undervoltage limit, the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is connected, the drive trips after a fixed time delay. The time delay varies with unit size.
Troubleshooting
Check that the supply voltage matches the drive voltage.
Perform an input voltage test.
Perform a soft-charge circuit test.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 47
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
•
•
6.8.5 WARNING/ALARM 9, Inverter Overload
Cause
The drive has run with more than 100% overload for too long and is about to cut out. The counter for electronic thermal inverter protection issues a warning at 98% and trips at 100% with an alarm. The drive cannot be reset until the counter is below 90%.
Troubleshooting
Compare the output current shown on the LCP with the drive rated current.
Compare the output current shown on the LCP with the measured motor current.
Show the thermal drive load on the LCP and monitor the value. When running above the drive continuous current rating, the counter increases. When running below the drive continuos current rating, the counter decreases.
6.8.6 WARNING/ALARM 10, Motor Overload Temperature
Cause
According to the electronic thermal protection (ETR), the motor is too hot.
Select 1 of these options:
•
•
•
The drive issues a warning or an alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options.
The drive trips when the counter reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options.
•
•
•
•
•
The fault occurs when the motor runs with more than 100% overload for too long.
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
Check that the motor current set in parameter 1-24 Motor Current is correct.
Ensure that the motor data in parameters 1-20 to 1-25 is set correctly.
If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan .
Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the drive to the motor more accurately and reduces thermal loading.
•
•
•
•
•
6.8.7 WARNING/ALARM 11, Motor Thermistor Overtemp
The motor thermistor indicates that the motor temperature is too high.
Troubleshooting
Check for motor overheating.
Check that the thermistor is securely connected.
Check if the motor is mechanically overloaded.
When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 and 54 is set for voltage. Check that parameter
1-93 Thermistor Resource selects 53 or 54.
When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. Select the terminal to use in parameter 1-93 Thermistor Resource .
•
•
•
•
6.8.8 WARNING/ALARM 12, Torque Limit
Cause
The torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator
Mode . Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an alarm.
Troubleshooting
If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
If the generator torque limit is exceeded during ramp-down time, extend the ramp-down time.
If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
Check the application for excessive current draw on the motor.
48 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
•
•
6.8.9 WARNING/ALARM 13, Overcurrent
Cause
The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts approximately 1.5 s, then the drive trips and issues an alarm. Shock loading or quick acceleration with high-inertia loads can cause this fault. If the acceleration during ramp-up is quick, the fault can also appear after kinetic back-up. If extended mechanical brake control is selected, a trip can be reset externally.
Troubleshooting
Remove power and check if the motor shaft can be turned.
Check that the motor size matches the drive.
Check that the motor data is correct in parameters 1-20 to 1-25 .
•
•
•
6.8.10 ALARM 14, Earth (Ground) Fault
Cause
There is current from the output phase to ground, either in the cable between the drive and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the drive and current going into the drive from the motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the drive must be the same as the current going into the drive.
Troubleshooting
Remove power to the drive and repair the ground fault.
Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter.
Reset any potential individual offset in the 3 current transducers in the drive. Perform a manual initialization or perform a complete AMA. This method is most relevant after changing the power card.
•
•
•
•
•
•
•
•
•
6.8.11 ALARM 15, Hardware Mismatch
Cause
A fitted option is not operational with the present control card hardware or software.
Troubleshooting
Record the value of the following parameters and contact Danfoss.
Parameter 15-40 FC Type .
Parameter 15-41 Power Section .
Parameter 15-42 Voltage .
Parameter 15-43 Software Version .
Parameter 15-45 Actual Typecode String .
Parameter 15-49 SW ID Control Card .
Parameter 15-50 SW ID Power Card .
Parameter 15-60 Option Mounted .
Parameter 15-61 Option SW Version (for each option slot).
6.8.12 ALARM 16, Short Circuit
Cause
There is short-circuiting in the motor or motor wiring.
Troubleshooting
W A R N I N G
-
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
•
• Disconnect power before proceeding.
Remove the power to the drive and repair the short circuit.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 49
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
•
•
•
6.8.13 WARNING/ALARM 17, Control Word Timeout
Cause
There is no communication to the drive. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to
[0] Off .
If parameter 8-04 Control Word Timeout Function is set to [5] Stop and trip , a warning appears, and the drive ramps down to a stop and shows an alarm.
Troubleshooting
Check the connections on the serial communication cable.
Increase parameter 8-03 Control Word Timeout Time .
Check the operation of the communication equipment.
Verify that proper EMC installation was performed.
6.8.14 WARNING/ALARM 22, Hoist Mechanical Brake
Cause
The value of this warning/alarm shows the type of warning/alarm.
0 = The torque reference was not reached before timeout ( parameter 2-27 Torque Ramp Up Time ).
1 = Expected brake feedback was not received before timeout ( parameter 2-23 Activate Brake Delay , parameter 2-25 Brake Release
Time ).
•
•
•
6.8.15 WARNING 23, Internal Fan Fault
Cause
The fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ( [0] Disabled ).
For drives with DC fans, a feedback sensor is mounted in the fan. If the fan is commanded to run and there is no feedback from the sensor, this alarm appears. For drives with AC fans, the voltage to the fan is monitored.
Troubleshooting
Check for proper fan operation.
Cycle power to the drive and check that the fan operates briefly at start-up.
Check the sensors on the control card.
•
6.8.16 WARNING 25, Brake Resistor Short Circuit
Cause
The brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled and the warning appears.
The drive is still operational, but without the brake function.
Troubleshooting
Remove the power to the drive and replace the brake resistor (refer to parameter 2-15 Brake Check ).
6.8.17 WARNING/ALARM 26, Brake Resistor Power Limit
Cause
The power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-16 AC Brake Max. Current . The warning is active when the dissipated braking power is higher than 90% of the brake resistor power. If option [2] Trip is selected in parameter 2-13 Brake Power Monitoring , the drive trips when the dissipated braking power reaches 100%.
•
6.8.18 WARNING/ALARM 27, Brake Chopper Fault
Cause
The brake transistor is monitored during operation, and if a short circuit occurs, the brake function is disabled, and a warning is issued. The drive is still operational, but since the brake transistor has short-circuited, substantial power is transmitted to the brake resistor, even if it is inactive.
Troubleshooting
Remove the power to the drive and remove the brake resistor.
50 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
6.8.19 WARNING/ALARM 28, Brake Check Failed
Cause
The brake resistor is not connected or not working.
Troubleshooting
Check parameter 2-15 Brake Check .
•
•
•
•
•
•
6.8.20 ALARM 29, Heat Sink Temp
Cause
The maximum temperature of the heat sink is exceeded. The temperature fault is not reset until the temperature drops below a defined heat sink temperature. The trip and reset points are different based on the drive power size.
Troubleshooting
Check for the following conditions:
The ambient temperature is too high.
The motor cables are too long.
Incorrect airflow clearance above and below the drive.
Blocked airflow around the drive.
Damaged heat sink fan.
Dirty heat sink.
6.8.21 ALARM 30, Motor Phase U Missing
Cause
Motor phase U between the drive and the motor is missing.
Troubleshooting
W A R N I N G
-
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
•
• Disconnect power before proceeding.
Remove the power from the drive and check motor phase U.
6.8.22 ALARM 31, Motor Phase V Missing
Cause
Motor phase V between the drive and the motor is missing.
Troubleshooting
W A R N I N G
HIGH VOLTAGE
-
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
•
• Disconnect power before proceeding.
Remove the power from the drive and check motor phase V.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 51
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
6.8.23 ALARM 32, Motor Phase W Missing
Cause
Motor phase W between the drive and the motor is missing.
Troubleshooting
W A R N I N G
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation,
start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
•
• Disconnect power before proceeding.
Remove the power from the drive and check motor phase W.
•
•
6.8.24 ALARM 33, Inrush Fault
Cause
Too many power-ups have occurred within a short time period.
Troubleshooting
Let the unit cool to operating temperature.
Check potential DC-link fault to ground.
6.8.25 WARNING/ALARM 34, Fieldbus Communication Fault
Cause
The fieldbus on the communication option card is not working.
•
6.8.26 WARNING/ALARM 36, Mains Failure
Cause
This warning/alarm is only active if the supply voltage to the drive is lost and parameter 14-10 Mains Failure is not set to [0] No Function .
Troubleshooting
Check the fuses to the drive and mains supply to the unit.
6.8.27 ALARM 37, Phase Imbalance
Cause
There is a current imbalance between the power units.
6.8.28 ALARM 38, Internal Fault
Cause
When an internal fault occurs, a code number defined in Table 21
is shown.
Troubleshooting
•
• Cycle power.
Check that the option is properly installed.
• Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting directions.
Table 21: Internal Fault Codes
Number Text
0
256–258
512–519
The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss service department.
The power EEPROM data is defective or too old. Replace the power card.
Internal fault. Contact the Danfoss supplier or Danfoss service department.
52 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
Number
783
Text
Parameter value outside of minimum/maximum limits.
1024–1284 Internal fault. Contact the Danfoss supplier or Danfoss service department.
1299
1300
1302
1315
The option software in slot A is too old.
The option software in slot B is too old.
The option software in slot C1 is too old.
The option software in slot A is not supported/allowed.
1316
1318
The option software in slot B is not supported/ allowed.
The option software in slot C1 is not supported/ allowed.
1379–2819 Internal fault. Contact the Danfoss supplier or Danfoss service department.
1792 Hardware reset of digital signal processor.
1793
1794
1795
1796
Motor-derived parameters not transferred correctly to the digital signal processor.
Power data not transferred correctly at power-up to the digital signal processor.
The digital signal processor has received too many unknown SPI telegrams. The AC drive also uses this fault code if the MCO does not power up correctly. This situation can occur due to poor EMC protection or improper grounding.
RAM copy error.
2561
2820
2821
2822
Replace the control card.
LCP stack overflow.
Serial port overflow.
USB port overflow.
3072–5122 Parameter value is outside its limits.
5123 Option in slot A: Hardware incompatible with the control board hardware.
5124
5125
Option in slot B: Hardware incompatible with the control board hardware.
Option in slot C0: Hardware incompatible with the control board hardware.
5126 Option in slot C1: Hardware incompatible with the control board hardware.
5376– 6231 Internal fault. Contact the Danfoss supplier or Danfoss service department.
•
•
6.8.29 WARNING 40, Overload of Digital Output Terminal 27
Troubleshooting
Check the load connected to terminal 27 or remove the short-circuit connection.
Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode .
•
•
6.8.30 WARNING 41, Overload of Digital Output Terminal 29
Troubleshooting
Check the load connected to terminal 29 or remove the short-circuit connection.
Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode .
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 53
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
6.8.31 WARNING 42, Ovrld X30/6-7
Troubleshooting
For terminal X30/6:
•
•
•
• Check the load connected to the terminal, or remove the short-circuit connection.
Check parameter 5-32 Term X30/6 Digi out (MCB 101) (VLT® General Purpose I/O MCB 101).
For terminal X30/7:
Check the load connected to the terminal, or remove the short-circuit connection.
Check parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT® General Purpose I/O MCB 101).
•
•
6.8.32 ALARM 43, Ext. Supply
Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External
24VDC , [0] No . A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle.
Cause
VLT® Extended Relay Option MCB 113 is mounted without 24 V DC.
Troubleshooting
Choose 1 of the following:
Connect a 24 V DC external supply.
Specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC , [0] No . A change in parameter
14-80 Option Supplied by External 24VDC requires a power cycle.
•
•
•
6.8.33 ALARM 45, Earth Fault 2
Cause
Ground fault.
Troubleshooting
Check for proper grounding and loose connections.
Check for proper wire size.
Check the motor cables for short circuits or leakage currents.
•
6.8.34 ALARM 46, Power Card Supply
Cause
The supply on the power card is out of range. Another reason can be a defective heat sink fan.
There are 3 supplies generated by the switch mode supply (SMPS) on the power card:
24 V.
•
•
•
•
•
•
• 5 V.
±18 V.
When powered with VLT
®
24 V DC Supply MCB 107, only 24 V and 5 V supplies are monitored. When powered with 3-phase mains voltage, all 3 supplies are monitored.
Troubleshooting
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC supply is used, verify proper supply power.
Check for a defective heat sink fan.
6.8.35 WARNING 47, 24 V Supply Low
Cause
The supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply (SMPS) on the power card:
54 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
•
•
24 V
5 V
±18 V
•
Troubleshooting
Check for a defective power card.
•
•
6.8.36 WARNING 48, 1.8 V Supply Low
Cause
The 1.8 V DC supply used on the control card is outside of the allowed limits. The supply is measured on the control card.
Troubleshooting
Check for a defective control card.
If an option card is present, check for overvoltage.
6.8.37 WARNING 49, Speed Limit
Cause
The warning is shown when the speed is outside of the specified range in parameter 4-11 Motor Speed Low Limit [RPM] and parameter 4-13 Motor Speed High Limit [RPM] . When the speed is below the specified limit in parameter 1-86 Trip Speed Low [RPM] (except when starting or stopping), the drive trips.
•
6.8.38 ALARM 50, AMA Calibration Failed
Troubleshooting
Contact the Danfoss supplier or service department.
•
6.8.39 ALARM 51, AMA Check Unom and Inom
Cause
The settings for motor voltage, motor current, and motor power are wrong.
Troubleshooting
Check settings in parameters 1-20 to 1-25 .
•
6.8.40 ALARM 52, AMA Low Inom
Cause
The motor current is too low.
Troubleshooting
Check the settings in parameter 1-24 Motor Current .
6.8.41 ALARM 53, AMA Motor Too Big
Cause
The motor is too big for the AMA to operate.
6.8.42 ALARM 54, AMA Motor Too Small
Cause
The motor is too small for the AMA to operate.
6.8.43 ALARM 55, AMA Parameter Out of Range
Cause
The AMA cannot run because the paramenter values of the motor are out of the acceptable range.
6.8.44 ALARM 56, AMA Interrupted by User
Cause
The AMA is manually interrupted.
6.8.45 ALARM 57, AMA Internal Fault
Cause
Try to restart the AMA. Repeated restarts can overheat the motor.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 55
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
6.8.46 ALARM 58, AMA Internal Fault
Troubleshooting
Contact the Danfoss supplier.
•
•
6.8.47 WARNING 59, Current Limit
Cause
The current is higher than the value in parameter 4-18 Current Limit .
Troubleshooting
Ensure that the motor data in parameters 1-20 to 1-25 is set correctly.
Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit.
•
•
•
6.8.48 WARNING 60, External Interlock
Cause
A digital input signal indicates a fault condition external to the drive. An external interlock has commanded the drive to trip.
Troubleshooting
Clear the external fault condition.
To resume normal operation, apply 24 V DC to the terminal programmed for external interlock.
Reset the drive.
•
•
•
6.8.49 WARNING/ALARM 61, Feedback Error
Cause
An error between calculated speed and speed measurement from feedback device.
Troubleshooting
Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function .
Set the tolerable error in parameter 4-31 Motor Feedback Speed Error .
Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout.
•
6.8.50 WARNING 62, Output Frequency at Maximum Limit
Cause
The output frequency has reached the value set in parameter 4-19 Max Output Frequency .
Troubleshooting
Check the application for possible causes.
• Increase the output frequency limit. Be sure that the system can operate safely at a higher output frequency.
The warning clears when the output drops below the maximum limit.
6.8.51 ALARM 63, Mechanical Brake Low
Cause
The actual motor current has not exceeded the release brake current within the start delay time window.
6.8.52 WARNING 64, Voltage Limit
Cause
The load and speed combination demands a motor voltage higher than the actual DC-link voltage.
•
•
•
•
6.8.53 WARNING/ALARM 65, Control Card Overtemperature
Cause
The cutout temperature of the control card has exceeded the upper limit.
Troubleshooting
Check that the ambient operating temperature is within the limits.
Check for clogged filters.
Check fan operation.
Check the control card.
56 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
•
6.8.54 WARNING 66, Heat Sink Temperature Low
Cause
The drive is too cold to operate. This warning is based on the temperature sensor in the IGBT module.
Troubleshooting
Increase the ambient temperature of the unit.
Supply a trickle amount of current to the drive whenever the motor is stopped by setting parameter 2-00 DC Hold/Preheat Current to 5% and parameter 1-80 Function at Stop .
•
6.8.55 ALARM 67, Option Module Configuration has Changed
Cause
One or more options have either been added or removed since the last power-down.
Troubleshooting
Check that the configuration change is intentional and reset the unit.
•
6.8.56 ALARM 68, Safe Stop Activated
Cause
Safe Torque Off (STO) has been activated.
Troubleshooting
To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal (via bus, digital, or by pressing [Reset]).
•
6.8.57 ALARM 70, Illegal FC Configuration
Cause
The control card and power card are incompatible.
Troubleshooting
To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the cards.
•
6.8.58 ALARM 71, PTC 1 Safe Stop
Cause
Because the motor is too warm, the VLT
®
PTC Thermistor Card MCB 112 activated the Safe Torque Off (STO).
Troubleshooting
-
Once the motor temperature reaches an acceptable level and the digital input from MCB 112 is deactivated, perform 1 of the following:
Send a reset signal via bus or digital I/O.
Press [Reset].
•
•
6.8.59 ALARM 72, Dangerous Failure
Cause
Safe Torque Off (STO) with trip lock.
Troubleshooting
An unexpected combination of STO commands has occurred:
VLT
®
PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled.
MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 12 warning in parameter 5-19 Terminal 37 Safe Stop ). STO is activated, but X44/10 is not activated.
•
6.8.60 WARNING 73, Safe Stop Auto Restart
Cause
STO activated.
Troubleshooting
With automatic restart enabled, the motor can start when the fault is cleared.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 57
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
6.8.61 ALARM 74, PTC Thermistor
Cause
The PTC is not working. Alarm is related to VLT
®
PTC Thermistor Card MCB 112.
•
6.8.62 ALARM 75, Illegal Profile Sel.
Cause
Do not write the parameter value while the motor is running.
Troubleshooting
Stop the motor before writing the MCO profile to parameter 8-10 Control Word Profile .
6.8.63 WARNING 77, Reduced Power Mode
Cause
The drive is operating in reduced power mode (less than allowed number of inverter sections). The warning is generated on power cycle when the drive is set to run with fewer inverters and remains on.
•
•
•
•
6.8.64 ALARM 78, Tracking Error
Cause
The difference between setpoint value and actual value exceeds the value in parameter 4-35 Tracking Error .
Troubleshooting
Disable the function or select an alarm/warning in parameter 4-34 Tracking Error Function .
Investigate the mechanics around the load and motor. Check feedback connections from motor encoder to drive.
Select motor feedback function in parameter 4-30 Motor Feedback Loss Function .
Adjust the tracking error band in parameter 4-35 Tracking Error and parameter 4-37 Tracking Error Ramping .
6.8.65 ALARM 79, Illegal Power Section Configuration
Cause
The scaling card has an incorrect part number or is not installed. The MK102 connector on the power card could not be installed.
6.8.66 ALARM 80, Drive Initialized to Default Value
Cause
Parameter settings are initialized to default settings after a manual reset. To clear the alarm, reset the unit.
6.8.67 ALARM 81, CSIV Corrupt
Cause
The CSIV file has syntax errors.
6.8.68 ALARM 82, CSIV Parameter Error
Cause
CSIV failed to initialize a parameter.
6.8.69 ALARM 83, Illegal Option Combination
Cause
The mounted options are incompatible.
6.8.70 ALARM 84, No Safety Option
Cause
The safety option was removed without applying a general reset.
Troubleshooting
Reconnect the safety option.
58 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
•
•
6.8.71 ALARM 88, Option Detection
Cause
A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has been changed.
Troubleshooting
To apply the change, enable option layout changes in parameter 14-89 Option Detection .
Alternatively, restore the correct option configuration.
6.8.72 WARNING 89, Mechanical Brake Sliding
Cause
The hoist brake monitor detects a motor speed exceeding 10 RPM.
•
6.8.73 ALARM 90, Feedback Monitor
Troubleshooting
Check the connection to the encoder/resolver option and, if necessary, replace the VLT
®
Encoder Input MCB 102 or VLT
®
Resolver Input MCB 103.
•
6.8.74 ALARM 91, Analog Input 54 Wrong Settings
Troubleshooting
Set switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54.
•
•
•
6.8.75 ALARM 99, Locked Rotor
Cause
The rotor is blocked.
Troubleshooting
Check if the motor shaft is locked.
Check if the start current triggers the current limit set in parameter 4-18 Current Limit .
Check if it increases the value in parameter 30-23 Locked Rotor Detection Time [s] .
•
6.8.76 WARNING/ALARM 104, Mixing Fan Fault
Cause
The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The mixing fan fault can be configured as a warning or an alarm in parameter 14-53 Fan Monitor .
Troubleshooting
Cycle power to the drive to determine if the warning/alarm returns.
6.8.77 WARNING/ALARM 122, Mot. Rotat. Unexp.
Cause
The drive performs a function that requires the motor to be at standstill, for example DC hold for PM motors.
6.8.78 WARNING 163, ATEX ETR Cur.Lim.Warning
Cause
The drive has run above the characteristic curve for more than 50 s. The warning is activated at 83% and deactivated at 85% of the allowed thermal overload.
6.8.79 ALARM 164, ATEX ETR Cur.Lim.Alarm
Cause
Running above the characteristic curve for more than 60 s within a period of 600 s activates the alarm, and the drive trips.
6.8.80 WARNING 165, ATEX ETR Freq.Lim.Warning
Cause
The drive has run for more than 50 s below the allowed minimum frequency ( parameter 1-98 ATEX ETR Interpol. Points Freq.
).
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 59
VLT® Decentral Drive FCD 302
Operating Guide
Maintenance, Diagnostics and
Troubleshooting
6.8.81 ALARM 166, ATEX ETR Freq.Lim.Alarm
The drive has run for more than 60 s (in a period of 600 s) below the allowed minimum frequency ( parameter 1-98 ATEX ETR Interpol.
Points. Freq.
).
6.8.82 WARNING 251, New Typecode
Cause
The power card or other components have been replaced, and the typecode has changed.
60 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Specifications
7 Specifications
7.1 Electrical Data
Table 22: Shaft Output, Output Current, and Input Current
Mains Supply 3x380–480 V AC
Drive
Rated shaft output [kW]
Rated shaft output [hp]
Maximum input current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Recommended maximum fuse size (non UL)
Built-in circuit breaker (large unit)
Recommended circuit breaker Danfoss CTI-25M (small and large unit) part number:
0.37, 0.55 kW
0.75, 1.1 kW
1.5, 2.2, and 3 kW
Recommended circuit breaker Danfoss CTI-45MB (small unit) part number: (1)
0.55, 0.75 kW
1.1 kW
1.5 kW
2.2 kW
Power loss at maximum load [W] (2)
Efficiency (3)
Weight, small unit [kg (lb)]
Weight, large unit [kg (lb)]
Output current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0
0.37
0.55
0.75
1.1
1.5
2.2
3.0
0.5
0.75
1.0
1.5
2.0
3.0
4.0
1.2
1.9
1.0
1.6
gG-25
1.6
2.6
1.4
2.2
2.2
3.5
1.9
3.0
2.7
4.3
2.7
4.3
CTI-25M ordering number: 047B3151
3.7
5.9
3.1
5.0
5.0
8.0
4.3
6.9
6.5
10.4
5.7
9.1
Ordering number: 047B3148
Ordering number: 047B3149
Ordering number: 047B3151
Ordering number: 047B3160
Ordering number: 047B3161
Ordering number: 047B3162
Ordering number: 047B3163
35 42 46 58 62 88 116
0.93
0.95
0.96
0.96
0.97
0.97
0.97
9.8 (21.6)
13.9 (30.6)
1.3
2.1
1.8
2.9
2.4
3.8
3.0
4.8
4.1
6.6
5.2
8.3
7.2
11.5
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 61
VLT® Decentral Drive FCD 302
Operating Guide Specifications
Mains Supply 3x380–480 V AC
Continuous (3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Continuous kVA (400 V AC) [kVA]
Continuous kVA (460 V AC) [kVA]
Maximum cable size: (mains, motor, brake) [mm 2 /AWG]
1.2
1.9
0.9
0.9
1.6
2.6
1.3
1.3
solid cable 6/10 flexible cable 4/12
2.1
3.4
1.7
1.7
3.0
4.8
2.1
2.4
3.4
5.4
2.8
2.7
4.8
7.7
3.9
3.8
6.3
10.1
5.0
5.0
1 Type CTI-45MB circuit breakers are not available for 3 kW (4 hp) units.
2 Applies to the dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumption are included. For power loss data according to EN 50598-2, refer to www.danfoss.com
.
3
Efficiency measured at nominal current. For energy efficiency class, see 7.4.1 Environment
. For part load losses see www.danfoss.com
.
7.2 Mains Supply (L1, L2, L3)
Supply voltage (1)(2)
Supply frequency
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (cos Φ)
Switching on the input supply L1, L2, L3 (power-ups)
380–480 V/500–600 V ±10%
50/60 Hz ±5%
3.0% of rated supply voltage
≥0.9 nominal at rated load
Near unity (>0.98)
Maximum 2 times per minute
1 Mains voltage low/mains drop-out: During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
2 The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/500/600/690 V maximum.
7.3 Motor Output and Motor Data
7.3.1 Motor Output (U, V, W)
Output voltage
Output frequency
Output frequency in flux mode
Switching on output
Ramp times
0–100% of supply voltage
0–590 Hz (1)
0–300 Hz
Unlimited
0.01–3600 s
1 Dependent on voltage and power.
7.3.2 Torque Characteristics
Starting torque (constant torque)
Starting torque
Overload torque (constant torque)
Starting torque (variable torque)
Overload torque (variable torque)
1 Percentage relates to the nominal torque of the drive, dependent on power size.
Maximum 160% for 60 s (1)
Maximum 180% up to 0.5 s (1)
Maximum 160% for 60 s (1)
Maximum 110% for 60 s (1)
Maximum 110% for 60 s (1)
62 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Specifications
7.4 Ambient Conditions
7.4.1 Environment
Enclosure rating
Vibration test for units without circuit breaker
Mount unit with integrated circuit breaker on a level, vibrationproof, and torsionally rigid support structure.
Maximum relative humidity
Ambient temperature (1)
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced speed performance
Temperature during storage/transport
Maximum altitude above sea level
Energy efficiency class (2)
IP66/Type 4X
1.7 g RMS
5–95% (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Maximum 40 °C (75 °F) (24-hour average maximum 35 °C (95 °F))
0 °C (32 °F)
-10 °C (14 °F)
-25 to +65/70 °C (-13 to +149/158 °F)
1000 m (3280 ft)
IE2
•
•
•
•
•
1 See Special Conditions in the design guide for:
Derating for high ambient temperature.
• Derating for high altitude.
2 Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
7.5 Cable Lengths and Cross-sections
Maximum motor cable length, shielded
Maximum motor cable length, unshielded, without fulfilling emission specification
Maximum cross-section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
Maximum cross-section to mains and motor, stranded/rigid wire
Maximum cross-section to mains and motor, flexible wire
Maximum cross-section to mains and motor, flexible with/without plastic sleeve
Maximum cross-section to mains and motor, flexible with TWIN ferrule
Minimum cross-section to mains and motor, flexible/rigid/stranded
Nominal/rated current
10 m (32.8 ft)
10 m (32.8 ft)
1.5 mm 2 /16 AWG
1.5 mm 2 /16 AWG
1.5 mm 2 /16 AWG
0.25 mm 2 /24 AWG
6 mm 2 /10 AWG
4 mm 2 /12 AWG
4 mm 2 /12 AWG
1 mm 2 /17 AWG
0.5 mm 2 /20 AWG
25 A (up to 50 A with optional looping terminals)
See electrical data tables in 7.1 Electrical Data
for more information.
It is mandatory to ground the mains connection properly using T95 (PE) of the drive. The ground connection cable cross-section must be at least 10 mm 2 (8 AWG) or 2 rated mains wires terminated separately according to EN 50178. Use unshielded cable.
See also
.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 63
VLT® Decentral Drive FCD 302
Operating Guide Specifications
7.6 Control Input/Output and Control Data
7.6.1 Digital Inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Voltage level, logic 0 NPN
Voltage level, logic 1 NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Minimum pulse width
Input resistance, R i
4 (6) (1)
18, 19, 27 (1) , 29 (1) , 32, 33
PNP or NPN
0–24 V
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
0–110 kHz
4.5 ms
Approximately 4 kΩ
1 Terminals 27 and 29 can also be programmed as output.
The digital input is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
7.6.2 STO Terminal 37 (Terminal 37 is Fixed PNP Logic)
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Typical input current at 24 V
Typical input current at 20 V
Input capacitance
0–24 V DC
<4 V DC
>20 V DC
50 mA rms
60 mA rms
400 nF
7.6.3 Analog Inputs:
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R i
Maximum voltage
Current mode
Current level
Input resistance, R i
Maximum current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
2
53, 54
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
0–10 V (scaleable)
Approximately 10 kΩ
±20 V
Switch S201/S202 = ON (I)
0/4–20 mA (scaleable)
Approximately 200 Ω
30 mA
10 bit (+ sign)
Maximum error 0.5% of full scale
200 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
64 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Specifications
2 3
+24V
18
4
5
6
37
1
RS485
Illustration 29: Analog Inputs
1
2
3
Functional isolation
Control
PELV isolation
4
5
6
Mains
High voltage
Motor
7.6.4 Pulse/Encoder Inputs
Programmable pulse/encoder inputs
Terminal number pulse/encoder
Maximum frequency at terminals 29, 32, 33
Maximum frequency at terminals 29, 32, 33
Maximum frequency at terminals 29, 32, 33
Voltage level
Maximum voltage on input
Input resistance, R i
Pulse input accuracy (0.1–1 kHz)
Encoder input accuracy (1–11 kHz)
2/1
29 (1) , 33 (2) /32 (3) , 33 (3)
110 kHz (Push-pull driven)
5 kHz (Open collector)
4 Hz
See
.
28 V DC
Approximately 4 kΩ
Maximum error: 0.1% of full scale
Maximum error: 0.05% of full scale
1 FC 302 only.
2 Pulse inputs are 29 and 33.
3 Encoder inputs: 32=A, 33=B.
The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
7.6.5 Digital Outputs
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
2
27, 29 (1)
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
Maximum error: 0.1% of full scale
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 65
VLT® Decentral Drive FCD 302
Operating Guide Specifications
Resolution of frequency outputs 12 bit
1 Terminals 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
7.6.6 Analog Output
Number of programmable outputs
Terminal number
Current range at analog output
Maximum load GND - analog output less than
Accuracy on analog output
Resolution of analog output
1
42
0/4 to 20 mA
500 Ω
Maximum error: 0.5% of full scale
12 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
7.6.7 Control Card, 24 V DC Output
Terminal number
Output voltage
Maximum load
12, 13
24 V +1, -3 V
600 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs.
7.6.8 Control Card, +10 V DC Output
Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
50
10.5 V ±0.5 V
15 mA
7.6.9 Control Card, RS485 Serial Communication
Terminal number
Terminal number 61
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV).
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
7.6.10 Control Card, USB Serial Communication
USB standard
USB plug
1.1 (full speed)
USB type B plug
Connection to the PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protective earth. Use only an isolated laptop as PC connection to the
USB connector on the drive.
7.6.11 Relay Outputs
Programmable relay outputs
Relay 01 terminal number
Maximum terminal load (AC-1) (1) on 1–3 (NC), 1–2 (NO) (resistive load)
Maximum terminal load (AC-15) (1) (inductive load @ cosφ 0.4)
2
1–3 (break), 1–2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
66 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Specifications
Maximum terminal load (DC-1) (1) load)
on 1–2 (NO), 1–3 (NC) (resistive
Maximum terminal load (DC-13) (1) (inductive load)
Relay 02 terminal number
Maximum terminal load (AC-1) (1) on 4–5 (NO) (resistive load) (2)(3)
Maximum terminal load (AC-15) (1) on 4–5 (NO) (inductive load @ cosφ 0.4)
Maximum terminal load (DC-1) (1) on 4–5 (NO) (resistive load)
Maximum terminal load (DC-13) (1) on 4–5 (NO) (inductive load)
Maximum terminal load (AC-1) (1) on 4–6 (NC) (resistive load)
Maximum terminal load (AC-15) (1) on 4–6 (NC) (inductive load @ cosφ 0.4)
Maximum terminal load (DC-1) (1) on 4–6 (NC) (resistive load)
Maximum terminal load (DC-13) (1) on 4–6 (NC) (inductive load)
Minimum terminal load on 1–3 (NC), 1–2 (NO), 4–6 (NC), 4–5 (NO)
Environment according to EN 60664-1
48 V DC, 1 A
24 V DC, 0.1 A
4–6 (break), 4–5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
48 V DC, 1 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
Overvoltage category III/pollution degree 2
1 IEC 60947 parts 4 and 5. The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2 Overvoltage Category II.
3 UL applications 300 V AC 2 A.
7.6.12 Control Card Performance
Scan interval 1 ms
7.6.13 Control Characteristics
Resolution of output frequency at 0–590 Hz
Repeat accuracy of precise start/stop (terminals 18, 19)
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed control range (closed loop)
Speed accuracy (open loop)
Speed accuracy (closed loop), depending on resolution of feedback device
Torque control accuracy (speed feedback)
All control characteristics are based on a 4-pole asynchronous motor.
±0.003 Hz
≤±0.1 ms
≤2 ms
1:100 of synchronous speed
1:1000 of synchronous speed
30–4000 RPM: Error ±8 RPM
0–6000 RPM: Error ±0.15 RPM
Maximum error ±5% of rated torque
7.7 Fuses and Circuit Breakers
•
•
•
7.7.1 Recommendations
American Wire Gauge. Maximum cable cross-section is the largest cable cross-section that can be attached to the terminals.
Always observe national and local regulations.
Type gG pre-fuses must be used. To maintain UL/cUL, use pre-fuses of these types (see Table 23 ).
Measured using a 10 m (32.8 ft) shielded/armored motor cable with a rated load and rated frequency.
Fuses
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 500 V maximum.
Circuit breaker
The unit is suitable for use on a circuit capable of delivering not more than 10000 RMS symmetrical Amperes, 500 V maximum.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 67
VLT® Decentral Drive FCD 302
Operating Guide Specifications
7.7.2 Recommended Maximum Pre-fuse Size 25 A
Table 23: FCD 302 Pre-fuses Meeting UL/cUL Requirements
Brand Fuse type (1) UL file number
Bussmann
Bussmann
FWH-
KTS-R
E91958
E4273
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
SIBA
Little Fuse
Ferraz-Shawmut
Ferraz-Shawmut
Ferraz-Shawmut
JKS-
JJS-
FNQ-R-
KTK-R-
LP-CC-
5017906-
KLS-R
ATM-R
A6K-R
HSJ
E4273
E4273
E4273
E4273
E4273
E180276
E81895
E2137
E2137
E2137
UL category (CCN code)
JFHR2
RK1/JDDZ
J/JDDZ
T/JDDZ
CC/JDDZ
CC/JDDZ
CC/JDDZ
RK1/JDDZ
RK1/JDDZ
CC/JDDZ
RK1/JDDZ
J/HSJ
1 5 A (0.37 kW (0.5 hp)), 7 A (0.55 kW (0.75 hp)), 9 A (0.75 kW (1.0 hp)), 12 A (1.1 kW (1.5 hp)), 15 A (1.5 kW (2.0 hp)), 20 A (2.2 kW (3.0 hp)), 25 A (3 kW
(4.0 hp))
Table 24: FCD 302 DC Voltage Level
DC voltage level 380–480 V units (V DC)
Inverter undervoltage disable
Undervoltage warning
Inverter undervoltage re-enable (warning reset)
Overvoltage warning (without brake)
Dynamic brake turn on
Inverter overvoltage re-enable (warning reset)
Overvoltage warning (with brake)
Overvoltage trip
373
410
398
778
778
795
810
820
7.8 Mechanical Dimensions
68 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
331.5 mm (13.05 in)
280 mm (11.02 in)
6.5 mm
(0.25 in)
Ø13 mm
(0,51 in)
41 mm
(1.61 in) 315 mm (12.4 in)
349.5 mm (13.75 in)
ON
WARNING ALARM
Bus MS NS1 NS2
Illustration 30: Cable Entries and Hole Sizes (Small Unit)
Specifications
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 69
VLT® Decentral Drive FCD 302
Operating Guide
431.5 mm (16.98 in)
380 mm (14.96 in)
6.5 mm
(0.25 in)
Ø13 mm
(0,51 in)
32 mm
(1.25 in) 415 mm (16.33 in)
449.5 mm (17.69 in)
Illustration 31: Cable Entries and Hole Sizes (Large Unit)
Table 25: Mechanical Dimensions
Motor side
Control side
Mains side
1 Also used for 4xM12/6xM12 sensor/actuator sockets.
1xM20, 1xM25
2xM20, 9xM16 (1)
2xM25
Specifications
70 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide
8 Appendix
8.1 Symbols, Abbreviations and Conventions
8.1.1 Symbols and Abbreviations
°C Degrees Celsius
°F
AC
AEO
AWG
Degrees Fahrenheit
Alternating current
Automatic energy optimization
American wire gauge
LCP
MCT n s
P
M,N
PELV
AMA
DC
EMC
ETR f
M,N
I
INV
I
LIM
I
M,N
I
VLT,MAX
I
VLT,N
IP
PCB
PM motor
PWM
RPM
Automatic motor adaptation
Direct current
Electro-magnetic compatibility
Electronic thermal relay
Nominal motor frequency
Rated inverter output current
Current limit
Nominal motor current
Maximum output current
Rated output current supplied by the drive
Ingress protection
Local control panel
Motion control tool
Synchronous motor speed
Nominal motor power
Protective extra low voltage
Printed circuit board
Permanent magnet motor
Pulse width motor
Revolutions per minute
Danfoss A/S © 2021.09
Appendix
AQ267036816112en-000201 / 130R0208 | 71
VLT® Decentral Drive FCD 302
Operating Guide Appendix
Regen
T
LIM
U
M,N
Regenerative terminals
Torque limit
Nominal motor voltage
8.2 Quick Menu Parameters
Table 26: Parameter 0-01 Language
Option Function
Defines the language. The drive is delivered with 4 different language packages. English and German are included in all packages. English cannot be erased or manipulated.
[0]* English
[1] Deutsch
[2] Français
[3] Dansk
[4] Spanish
[5] Italiano
[6] Svenska
[7] Nederlands
[10] Chinese
[20] Suomi
[22] English US
[27] Greek
[28] Bras.Port
[36] Slovenian
[39] Korean
[40] Japanese
[41] Turkish
[42] Trad. Chinese
[43] Bulgarian
[44] Srpski
[45] Romanian
[46] Magyar
[47] Czech
[48] Polski
[49] Russian
Part of language packages 1–4
Part of language packages 1–4
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 2
Part of language package 1
Part of language package 4
Part of language package 4
Part of language package 4
Part of language package 3
Part of language package 2
Part of language package 2
Part of language package 4
Part of language package 2
Part of language package 3
Part of language package 3
Part of language package 3
Part of language package 3
Part of language package 3
Part of language package 4
Part of language package 3
72 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Appendix
Option
[50] Thai
Function
Part of language package 2
[51] Bahasa Indonesia Part of language package 2
[52] Hrvatski Part of language package 3
Table 27: Parameter 1-20 Motor Power [kW]
Range Function
Size related*
[0.09 -
3000.00 kW] N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the nominal motor power in kW according to the motor nameplate data. The default value corresponds to the nominal rated output of the drive. This parameter is visible in the LCP if parameter 0-03 Regional Settings is set to [0] International .
Table 28: Parameter 1-22 Motor Voltage
Range Function
Size related* [10 - 1000 V] Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the nominal rated output of the drive.
Table 29: Parameter 1-23 Motor Frequency
Range Function
Size related*
[20 -
1000 Hz] N O T I C E
From software version 6.72 onwards, the output frequency of the drive is limited to 590 Hz.
Select the motor frequency value form the motor nameplate data. If a value other than 50 Hz or 60 Hz is selected, adapt the load-independent settings in parameter 1-50 Motor Magnetization at Zero Speed to parameter 1-53 Model Shift Frequency . For 87 Hz, adapt parameter 4-13 Motor Speed High Limit [RPM] and parameter 3-03 Maximum Reference .
Table 30: Parameter 1-24 Motor Current
Range Function
Size related*
[0.10 -
10000.00 A] N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the nominal motor current value from the motor nameplate data. The data is used for calculating motor torque, motor thermal protection, and so on.
Table 31: Parameter 1-25 Motor Nominal Speed
Range Function
Size related*
[100 -
60000 RPM] N O T I C E
This parameter cannot be adjusted while the motor is running.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 73
VLT® Decentral Drive FCD 302
Operating Guide Appendix
Range Function
Enter the nominal motor speed value from the motor nameplate data. The data is used for calculating automatic motor compensations.
Latched start
Reversing
Start reversing
Enable start forward
Enable start reverse
Jog
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Speed down
Setup select bit 0
Setup select bit 1
Catch up
Slow down
Pulse input
Ramp bit 0
Ramp bit 1
[22]
[23]
[24]
[28]
[18]
[19]
[20]
[21]
[29]
[32]
[34]
[35]
[13]
[14]
[16]
[17]
[9]
[10]
[11]
[12]
Table 32: Parameter 5-12 Terminal 27 Digital Input
Option Function
Select the function from the available digital input range.
[4]
[5]
[6]
[8]
[0]
[1]
[2]
[3]
No operation
Reset
Coast inverse
Coast and reset inverse
Quick stop inverse
DC-brake inverse
Stop inverse
Start
74 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Appendix
[56]
[57]
[62]
[65]
Option
[36] Mains failure inverse
[55] DigiPot increase
DigiPot decrease
DigiPot clear
Reset Counter A
Reset Counter B
Function
Table 33: Parameter 1-29 Automatic Motor Adaptation (AMA)
Option Function
N O T I C E
This parameter cannot be adjusted while the motor is running.
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor parameters ( parameter 1-30 Stator Resistance (Rs) to parameter 1-35 Main Reactance (Xh) ) at motor standstill.
Activate the AMA function by pressing [Hand On] after selecting [1] Enable complete AMA or [2] Enable reduced AMA . After a normal sequence, the display reads Press [OK] to finish AMA . After pressing [OK], the drive is ready for operation.
[0]* OFF
[1] Enable complete
AMA
[2] Enable reduced
AMA
Performs AMA of the stator resistance R s
, the rotor resistance R r leakage reactance X
2
, and the main reactance X h
.
, the stator leakage reactance X
1
, the rotor
Performs a reduced AMA of the stator resistance R between the drive and the motor.
s
in the system only. Select this option if an LC filter is used
N O T I C E
For the best adaptation of the drive, run AMA on a cold motor.
AMA cannot be performed while the motor is running.
N O T I C E
N O T I C E
AMA cannot be performed on permanent magnet motors.
N O T I C E
It is important to set parameter group 1-* Motor Data correctly since these parameters form part of the AMA algorithm. An AMA must be performed to achieve optimum dynamic motor performance. Depending on the power rating of the motor, it takes up to 10 minutes.
N O T I C E
To avoid generating external torque during AMA, disconnect the motor shaft from the application.
Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208 | 75
VLT® Decentral Drive FCD 302
Operating Guide Appendix
N O T I C E
If 1 of the settings in parameter group 1-2* Motor Data is changed, parameter 1-30 Stator Resistance (Rs) to parameter 1-39 Motor
Poles , the Advanced Motor parameters return to their default settings.
Table 34: Parameter 3-02 Minimum Reference
Range Function
Size related*
[-999999.999 - parameter 3-03 ReferenceFeedbackUnit ]
•
Enter the minimum reference. The minimum reference is the lowest value obtainable by summing all references. Minimum reference is active only when parameter 3-00 Reference Range is set to [0] Min.–Max .The minimum reference unit matches:
The configuration of parameter 1-00 Configuration Mode and for [2] Torque set to Nm.
for [1] Speed closed loop set to RPM
• The unit selected in parameter 3-01 Reference/Feedback Unit .
If option [10] Synchronization is selected in parameter 1-00 Configuration Mode , this parameter defines the maximum speed deviation when performing the position offset defined in parameter
3-26 Master Offset .
Table 35: Parameter 3-03 Maximum Reference
Range Function
Size related*
[parameter 3-02 -
999999.999 ReferenceFeedbackUnit]
•
•
Enter the maximum reference. The maximum reference is the highest value obtainable by summing all references. The maximum reference unit matches:
The configuration of parameter 1-00 Configuration Mode and for [2] Torque set to Nm.
for [1] Speed closed loop set to RPM
The unit selected in parameter 3-00 Reference Range .
If option [9] Positioning is selected in parameter 1-00 Configuration Mode , this parameter defines the default speed for positioning.
Table 36: Parameter 3-41 Ramp 1 Ramp Up Time
Range Function
Size related*
[0.01 -
3600 s]
Enter the ramp-up time, that is, the acceleration time from 0 RPM to the synchronous motor speed n s
.
Select a ramp-up time which prevents the output current from exceeding the current limit in parameter
4-18 Current Limit during ramping. The value 0.00 corresponds to 0.01 s in speed mode. See ramp-down time in parameter 3-42 Ramp 1 Ramp Down Time .
Table 37: Parameter 3-42 Ramp 1 Ramp Down Time
Range Function
Size related*
[0.01 -
3600 s]
Enter the ramp-down time, that is, the deceleration time from the synchronous motor speed n s
to 0 RPM.
Select a ramp-down time such that no overvoltage occurs in the inverter due to regenerative operation of the motor, and such that the generated current does not exceed the current limit in parameter 4-18
Current Limit . The value 0.00 corresponds to 0.01 s in speed mode. See ramp-up time in parameter 3-41
Ramp 1 Ramp Up Time .
76 | Danfoss A/S © 2021.09
AQ267036816112en-000201 / 130R0208
VLT® Decentral Drive FCD 302
Operating Guide Index
Index
+
2
External command.........................................................................10, 10, 46
A
Approvals and certifications.....................................................................10
Automatic motor adaptation.....................................................41, 48, 55
F
Fans
Fieldbus
G
B
H
C
Cable length, control cables.....................................................................63
Control card performance.........................................................................67
Cross-section, control cable..................................................................... 63
I
Initialization, recommended....................................................................39
Input power..........................................................10, 19, 22, 28, 33, 35, 46
D
Downloading data from the LCP............................................................38
L
List of warnings and alarms......................................................................47
E
EMC-compliant installation...................................................................... 19
M
Mains
Mains connection................................................................................28
Mains voltage................................................................................. 37,44
Danfoss A/S © 2021.09
AQ267036816112en-000201/130R0208 | 77
VLT® Decentral Drive FCD 302
Operating Guide Index
Mechanical brake control..........................................................................49
Motor
Motor current......................................................................10,10,37,41
Thermal protection.............................................................................19
Warning.......................................................................... 48,48,51,51,52
N
P
S
See STO
Serial communication.....................................................38, 43, 44, 45, 46
Short circuit
Switches
Disconnect...........................................................................13,29,35,42
O
T
Thermistor
Torque
Q
U
Unintended start..................................................................... 13, 29, 35, 42
Uploading data to the LCP........................................................................38
USB serial communication........................................................................66
R
Recommended initialization....................................................................39
Reset.................................................................36, 36, 38, 39, 46, 46, 46, 57
RS485 serial communication....................................................................66
V
Voltage
Safety warning........................................................13,35,49,51,51,52
W
78 | Danfoss A/S © 2021.09
AQ267036816112en-000201/130R0208
VLT® Decentral Drive FCD 302
Operating Guide Index
Danfoss A/S © 2021.09
AQ267036816112en-000201/130R0208 | 79
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten vlt-drives.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
*130R0208*
Danfoss A/S © 2021.09
*M0012401* AQ267036816112en-000201 / 130R0208
advertisement