AB Quality CompactLogix 1768-CNBR Installation Instructions Manual
AB Quality CompactLogix 1768-CNBR is a ControlNet interface module that allows for efficient data exchange and communication between CompactLogix controllers and other devices on a ControlNet network. It facilitates seamless integration of the CompactLogix system into larger control architectures, enabling data sharing, remote I/O access, and enhanced control capabilities.
Advertisement
Advertisement
Installation Instructions
CompactLogix ControlNet Interface Module
Catalog Numbers 1768-CNB, 1768-CNBR
Topic
North American Hazardous Location Approval
Prevent Electrostatic Discharge
Connect to a ControlNet Network
Interpreting the Status Indicators
ControlNet Network Channel-status Indicators
Page
About This Publication
Use this document as a guide to install the CompactLogix ControlNet Bridge
Interface Module.
Publication 1768-IN006A-EN-P - September 2007
2 CompactLogix ControlNet Interface Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you to identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 3
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Informations sur l'utilisation de cet
équipement en environnements dangereux.
Products marked CL I, “DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B,
C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
Les produits marqués CL I, “DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for
Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
AVERTISSEMENT
RISQUE D'EXPLOSION
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I,
Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication 1768-IN006A-EN-P - September 2007
4 CompactLogix ControlNet Interface Module
Environment and Enclosure
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
•
Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1.
•
NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 5
Prevent Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
For additional information, refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
Publication 1768-IN006A-EN-P - September 2007
6 CompactLogix ControlNet Interface Module
Before You Begin
Plan for this minimum spacing from enclosure walls, wireways, and other equipment.
Minimum Spacing
105 mm (4 in.)
90 mm
(3.54 in.)
Power
OU T
105 mm (4 in.)
31661-M
90 mm
(3.54 in.)
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 7
Required System Components
Item
1768 CompactLogix power supply
1768 CompactLogix controller
1769 end cap
Connects to the controller as either the last module:
• without any 1769 series modules attached to the controller (1768 series only).
• with a combination of 1768 series and 1769 series modules attached to the controller.
Serial cable to connect to a 1768 controller
BNC connectors
DIN rail or mounting screws
Catalog Number or Size
1768-PA3
1768-L4 x
1769-ECR
1756-CP3
See Connect to a ControlNet Network.
DIN rail
Screws
Either of these sizes:
•
35 x 7.5 mm
(EN 50 022 - 35 x 7.5)
•
35 x 15 mm
(EN 50 022 - 35 x 15)
M4 or #8 panhead screws
Publication 1768-IN006A-EN-P - September 2007
8 CompactLogix ControlNet Interface Module
Installing the Modules
ATTENTION
This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure
DIN rail to mounting surface approximately every 200 mm (7.87 in.) and use end-anchors appropriately.
IMPORTANT
Do not use screws and DIN rail to mount the modules. It is possible to break the mounting tabs off if you screw the modules to the panel while they are on DIN rail.
Mount Modules with Screws
The steps in these instructions show how to mount the modules on DIN rail.
If you are using screws instead of DIN rail, make these changes to the instructions.
1.
Follow the steps in Mount the Module on the DIN Rail on page 10 to
connect the modules together.
2.
Use the modules as a template and mark pilot holes on your panel.
3.
Drill the pilot holes for M4 or #8 screws.
ATTENTION
Do not let metal to fall into modules while drilling. This could damage the modules.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 9
4.
Use M4 or #8 screws to mount the modules to your panel with
1.16 Nm (10 lb-in) of torque.
5.
Ground the module on a ground bus with a dedicated Earth-ground stake.
6.
Connect the ground bus to a functional Earth-ground on the DIN rail or panel.
Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.
Install the DIN Rail
Mount the DIN rail in a suitable location.
Publication 1768-IN006A-EN-P - September 2007
10 CompactLogix ControlNet Interface Module
Mount the Module on the DIN Rail
1
1768-CNB Module 1768-CNBR Module
(rear)
(front)
TIP
2
31646A-M 31646AB-M
Throughout this installation instruction the graphic used for the module is the 1768-CNBR module.
b a
(rear)
(front) c
Publication 1768-IN006A-EN-P - September 2007
31647 -M
2 b
CompactLogix ControlNet Interface Module 11 a c
(rear)
(front)
31647 -M
Publication 1768-IN006A-EN-P - September 2007
12 CompactLogix ControlNet Interface Module
Mount the Power Supply on the DIN Rail
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 13
Mount the I/O Modules on the DIN Rail
1 a b d
2 c
31649-M b c a
31 6 50-M
Publication 1768-IN006A-EN-P - September 2007
14 CompactLogix ControlNet Interface Module
Connect the Module
You can connect the module to the ControlNet network by using a tap
(catalog number 1786-TPR, 1786-TPS, 1786-TPYR, or 1786-TPYS) or a network access cable (catalog number 1786-CP).
Refer to the ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002, for additional information.
WARNING
If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
TIP
Use the 1786-CP cable for temporary connections, such as programming software. For network connections and permanent connections, we recommend taps with a straight connector
(catalog number 1786-TPS or 1786-TPYS) because of the location of the BNC connectors on the bottom of the module.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 15
Set the Network Address Switches
Use a small screwdriver to set the module’s network address switches. You must specify a unique ControlNet network address. You can select an address of 01…99.
Network Address Switches
Side of Module
NETWORK
ADDRESS
04
03
05
06
07
02
01
3
4
00
5
6
08
09
7
2
1
0
9
8
NETWORK
ADDRESS
03
04
05
02
01
00
5
3
4
2
1
0
6
7
9
8
06
07
09
08
This module’s network address is 99.
31 6 51- M
Publication 1768-IN006A-EN-P - September 2007
16 CompactLogix ControlNet Interface Module
Connect to a ControlNet Network
The 1768-CNB and 1768-CNBR modules have a network access port (NAP) available. The most common and easiest way to connect to the network is by using the a ControlNet tap. Perform the following steps to connect the module to the network by using a tap.
1.
Remove and save the dust caps from the ControlNet network taps.
ATTENTION
Do not allow any metal portions of the tap to contact any conductive material. If you disconnect the tap from the module, place the dust cap back on the straight or right-angle connector to prevent the connector from accidentally contacting a metallic grounded surface.
Segment 1 Segment 2 1768-CNB Segment 1
1768-CNBR Segments 1 and 2
Dust Cap
Dust Cap
2.
Connect the tap’s straight or right-angle connector to the module’s
BNC connector.
If your node supports Connect the tap’s connector
Nonredundant media
1768-CNB module
To the channel A connector on the module
(channel B on the 1768-CNBR module is not used)
(1)
Redundant media
•
From trunkline A to channel A on the 1768-CNBR module
•
From trunkline B to channel B on the 1768-CNBR module
(1)
While both channels are active, we recommend using channel A for non-redundant media.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 17
IMPORTANT
On 1768-CNBR installations, make sure the correct network is connected to the correct tap connection. Reversing the tap connections will result in incorrect status display.
When you are using redundant media, connect the channel of each partner to the same network segment.
NETWORK
ADDRESS
03
04 05 06
07
02
01
00
5
09
3
4
08
6
7
2 8
1 0 9
NETWORK
ADDRESS
04
03
02
01
3
4
2
05 06
07
08
00
5
09
6
7
8
1 0 9
Segment 1
A
Tap
Segment 2
Tap
A B
Tap
31653- M
Publication 1768-IN006A-EN-P - September 2007
18 CompactLogix ControlNet Interface Module
Connecting a Laptop Computer to the Network with a 1784-PCC Card
The 1784-PCC1 cable can be connected from a laptop computer with a
1784-PCC card into any ControlNet product’s network access port (NAP) to provide access to an existing ControlNet network. A laptop computer connected through this cable is counted as a node and must have a unique network address (MAC ID) less than or equal to the maximum unscheduled node (UMAX).
1768-CNBR Module
1784-PCC1 Cable
ControlNet Link
1784-PCC Card
31654a-M
WARNING
The NAP is intended for temporary local-programming purposes only and not intended for permanent connection. If you connect or disconnect the NAP cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 19
Connecting a Desktop Computer to the Network with a 1786-CP Cable
The 1786-CP cable can be connected from a desktop computer with either a
1784-PCIC or 1784-PCICS card into any ControlNet product’s network access port (NAP) to provide access to an existing ControlNet network. A desktop computer connected through this cable is counted as a node and must have a unique network address (MAC ID) less than or equal to the maximum unscheduled node (UMAX).
1768-CNBR Module 1784-PCIC or 1784-PCICS
1786-CP Cable
ControlNet Link
31654- M
WARNING
The NAP is intended for temporary local-programming purposes only and not intended for permanent connection. If you connect or disconnect the NAP cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION
Use a 1786-CP cable when connecting a programming terminal to the network through the NAP. Using a commercially available RJ-style cable could result in network failure.
Publication 1768-IN006A-EN-P - September 2007
20 CompactLogix ControlNet Interface Module
Connecting a Desktop Computer Directly to the ControlNet Network
A 1786-TPR, 1786-TPS, 1786-TPYR, or 1786-TPYS cable can be connected from a desktop computer with either a 1784-PCIC or 1784-PCICS card directly to an existing ControlNet network. A desktop computer connected through this cable is counted as a node and must have a unique network address (MAC ID) less than or equal to the maximum unscheduled node
(UMAX).
When connecting the module to a ControlNet network, you should also refer to the following documentation:
• ControlNet Coax Taps Installation Instructions, publication
1786-IN007
• ControlNet Coax Media System Planning and Installation Manual, publication CNET-IN002
TIP
For network connections, we recommend taps with a straight connector (catalog number 1786-TPS or 1786-TPYS) because of the location of the BNC connectors on the bottom of the module.
ATTENTION
If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card, do not use the 1786-CP cable to connect the card to the ControlNet network. Instead, connect the card directly to the ControlNet network.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 21
Confirm Installation
The three bicolor (red/green) status indicators on the module provide diagnostic information about the module and its connections to the network.
See Interpreting the Status Indicators on page 24 if the lights are in other
states.
Solid or Flashing Green
Solid Green Solid Green
L 1
L 2 /N
1768-CNB and
1768-CNBR Modules
O U T
Module Status Display -
31598-G
ControlNet Channel Status
Channel A BNC Connector
Channel B BNC Connector 31657-M
Publication 1768-IN006A-EN-P - September 2007
22 CompactLogix ControlNet Interface Module
Remove a Module
To remove or slide a module, the DIN rail connectors on the module to its left must be pulled out.
c - Off
1 b d f
2 a
O UT a e c
31658-M
Power
OU T
31659-M b
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 23
Wait for the Lights to Turn Off Before Removing a Module
After you turn off the power, wait for all of the lights on the power supply and controller to turn off before you disconnect any modules.
IMPORTANT
When you turn the CompactLogix power supply off, make sure you wait for all status indicators on the power supply and controller to turn off before disconnecting any part from the system.
If you disconnect the CompactLogix system while the controller is still writing its program to memory, the program write will not be completed and you will lose your program.
• When you turn off the power, the controller writes its program to memory.
• If you don’t wait for the lights to turn off, you will lose your program.
Publication 1768-IN006A-EN-P - September 2007
24 CompactLogix ControlNet Interface Module
Interpreting the Status Indicators
Module Status Display Descriptions
Status Display
OK
Off
Red
None
Msg scrolls
BPA#
ERR
BPRX
ERR
BPIC
ERR
CNIC
ERR
Cause Action
The module is not communicating due to a power supply fault or internal fault.
The module’s network address is set to 00, an invalid ControlNet network address.
If switches are set to 00 the display scrolls: FAULT:
ADDRESS SWITCHES = 00,
ILLEGAL.
The module detected a different slot address from that latched in when you cycled power. Excessive noise on the backplane causes this error.
There are too many CRC errors being generated by the multicast backplane receiver, so the backplane multicast receivers have been shut off.
There is a hardware fault within the module.
1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is firmly seated in the chassis.
4. Replace the module if the indicator remains off.
1. Turn chassis power supply off.
2. Remove the module from the chassis.
3. Set the network address switches to a unique address, 01…99.
4. Install the module in the chassis.
5. Turn chassis power supply on if it's off.
Replace the chassis or module.
Replace the module.
Replace the module.
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 25
Module Status Display Descriptions
Status Display
OK
Red DUPL
NODE
RACK
ERR
Flashing red
BOOT
ROM
Cause Action
The module’s network address is the same as another module’s on the link.
1. Turn chassis power supply off.
2. Remove the module from the chassis.
3. Set the network address switches to a unique address, 01…99.
4. Install the module in the chassis.
5. Turn chassis power supply on if it's off.
Replace the chassis.
Cannot read backplane
EEPROM, or rack/slot address incorrect.
The module has invalid firmware.
Update module firmware with
ControlFlash Update Utility.
Flash update is in progress.
None required.
UPDT
SNGL
KPR!
Green OK
INIT
BW
>MAX
The module detected that it has been connected to a
ControlNet 1.5
(single-keeper) network.
Normal operation.
The module is initializing.
The module is receiving too much network traffic and connections are timing out.
The network bandwidth has been exceeded.
Update the module’s firmware at MAC
ID 01 and reschedule the network.
None required.
None (temporary condition).
If this happens frequently, add another
1768-CNB or 1768-CNBR module and split the traffic between them.
Publication 1768-IN006A-EN-P - September 2007
26 CompactLogix ControlNet Interface Module
Module Status Display Descriptions
Status Display
OK
Green
Flashing green
SW
ERR
CNFG
ERR
NET
ERR
Cause Action
The node address switch changed after cycling power.
None required, but we recommend that you either return switches to their original settings or replace the module, since this could indicate a hardware problem.
Recheck configuration.
ControlNet network configuration error.
Network cabling error or no other active nodes on the network.
Recheck your network cabling and make sure another node on the network is active (online).
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 27
ControlNet Network Channel-status Indicators
The ControlNet network channel-status indicators appear in one of the following states:
• Steady - indicator is on continuously in the defined state.
• Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together).
The two indicators are always in opposite states, out of phase.
• Flashing - the indicator alternates between the two defined states
(applies to each indicator viewed independent of the other). If both indicators are flashing, they must flash together, in phase.
The ControlNet Network Channel Status Indicators table summarizes the meanings of these states.
ControlNet Network Channel-status Indicators
Cause Action or
A
Off
Steady red
B
No power
Faulted unit
None or apply power.
Cycle power or reset unit.
If fault persists, contact
Allen-Bradley representative or distributor.
None.
Alternating red/green
Self-test
Alternating red/off Incorrect node configuration
Off
Steady green
Channel disabled
Normal operation
Check network address and other
ControlNet network configuration parameters.
Program network for redundant media, if required.
None.
Publication 1768-IN006A-EN-P - September 2007
28 CompactLogix ControlNet Interface Module
ControlNet Network Channel-status Indicators
Cause Action or
A B
Flashing green/off Temporary errors
Node is not configured to go on line
None; unit will self-correct.
Make sure the configuration manager node is present and working and selected address is not greater than selected UMAX
.
(1)
Flashing red/off Media fault Check media. For example, broken cables, loose connectors, missing terminators.
No other nodes present on network
Add other nodes to the network.
Flashing red/green Incorrect network configuration Cycle power or reset unit.
If fault persists, contact A-B representative or distributor.
(1)
The configuration manager node is the node responsible for distributing ControlNet network configuration data to all nodes on the network.
Specifications
CompactLogix ControlNet Interface Module - 1768-CNB and 1768-CNBR
Attribute Value
Device type Communication interface
Communication interface type Bridge
Connections supported, max 48
Dimensions (HxWxDx), approx.
132 x 56.7 x 105.1 mm (5.20 x 2.23 x 4.12 in.)
Mounting type
Mounting location
Din Rail or Panel Mount
1768 ControlLogix Chassis
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 29
CompactLogix ControlNet Interface Module - 1768-CNB and 1768-CNBR
Attribute
Din rail mount
Mounting screw torque
Weight, approx.
1768-CNB
1768-CNBR
Connectors
1768-CNB
1768-CNBR
Cable
Wiring category
(1)
Number of nodes, max
Slot width
Backplane current at 5 V
Power consumption
Power dissipation
Thermal dissipation
Isolation
(continuous-voltage rating)
North American temp code
ControlNet network communication rate
Diagnostics
Value
Either of these sizes:
•
35 x 7.5 mm
(EN 50 022 - 35 x 7.5)
•
35 x 15 mm
(EN 50 022 - 35 x 15)
1.16 Nm (10 lb-in), using M4 or #8 panhead screws
0.260 kg (0.57 lb)
0.293 kg (0.64 lb)
1 BNC connector for non-redundant media operation
1 NAP (RJ45 8-pin with shield)
2 BNC connectors for redundant media operation
1 NAP (RJ45 8-pin with shield)
Quad-shield RG-6 coaxial cable
2 - on communication ports
99
1, can be connected in any slot 1…4
1 A
5.14 W
5.14 W
17.5 BTU/hr
30V, Functional Insulation Type
Tested at 710V dc for 60 s, ControlNet network to system
T4A
5 Mbps
Yes
Publication 1768-IN006A-EN-P - September 2007
30 CompactLogix ControlNet Interface Module
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications
Attribute
Temperature, operating
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
Vibration
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5…95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
Shock, operating
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
ESD immunity
Radiated RF immunity
EFT/B immunity
CISPR 11:
Group 1, Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
IEC 61000-4-4:
±2 kV at 5 kHz on communication ports
Publication 1768-IN006A-EN-P - September 2007
CompactLogix ControlNet Interface Module 31
Environmental Specifications
Attribute Value
Surge transient immunity IEC 61000-4-5:
±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Enclosure type rating None (open-style)
Certifications
Certification
(when product is marked)
(1) c-UL-us
Value
CE
C-Tick
CI
UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2004/108/EC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
ControlNet International conformance tested to ControlNet network specifications
(1)
See the Product Certification website: http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
Publication 1768-IN006A-EN-P - September 2007
32 CompactLogix ControlNet Interface Module
Additional Resources
These documents contain additional information concerning related
Rockwell Automation products.
Resource
Industrial Automation Wiring and
Grounding Guidelines, publication
1770-4.1
ControlNet Modules in Logix5000
Control Systems, publication
CNET-UM001
CompactLogix Power Supplies
Installation Instructions, publication
1768-IN001
CompactLogix Controller Installation
Instructions, publication 1768-IN004
Description
Provides general guidelines for installing a
Rockwell Automation industrial system.
Describes how you can use ControlNet with your
Logix5000 controller to communicate between your controller and various devices on the ControlNet network.
Describes how to install the 1768-PA3 and
1768-PB3 CompactLogix power supplies.
Describes how to install CompactLogix controllers.
CompactLogix Controller User
Manual, publication 1768-UM001
ControlNet Coax Taps Installation
Instructions, publication 1786-IN007
Describes the necessary tasks to install, configure, program, and operate a CompactLogix system.
Provides the procedures and specifications for the installation of ControlNet coaxial taps.
Provides the details about how to plan and install
ControlNet network coax hardware.
ControlNet Coax Media Planning and Installation Guide, publication
CNET-IN002
ControlNet Fiber Media Planning and Installation Guide, publication
CNET-IN001
Logix5000 Controllers Common
Procedures Reference Manual, publication 1756-PM001
Product Certifications website, http://ab.com
Provides the information you need to get started with the ControlNet fiber media system, offers general guidelines for fiber cable installation, and describes how to install and verify your ControlNet fiber media system.
Contains common procedures that are related to all
Logix5000 controllers.
Provides declarations of conformity, certificates, and other certification details.
Publication 1768-IN006A-EN-P - September 2007
Notes:
CompactLogix ControlNet Interface Module 33
Publication 1768-IN006A-EN-P - September 2007
34 CompactLogix ControlNet Interface Module
Notes:
Publication 1768-IN006A-EN-P - September 2007
Notes:
CompactLogix ControlNet Interface Module 35
Publication 1768-IN006A-EN-P - September 2007
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.
United States
Outside United States
1.440.646.3434 Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number
(see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for return procedure.
Allen-Bradley, Rockwell Automation, RSLinx Classic, RSLinx Enterprise, RSNetWorx for ControlNet, RSNetWorx for
DeviceNet, RSNetWorx for EtherNet/IP, CompactLogix, ControlLogix, ControlFlash, TechConnect, and Logix5000 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1768-IN006A-EN-P - September 2007 PN 953002-95
Copyright © 2007 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.