Swegon TBLZ-2-66 Electrical equipment cubicle Installation instructions
Swegon TBLZ-2-66 is a control box for controlling two parallel air handling units with a touch screen for entering settings and viewing readings for common functions. The control box can be wired to a BMS via Ethernet and transmits set points to both air handling units, allowing for separate control of each unit. It supports VAV regulation and constant duct pressure maintenance through a connected pressure sensor, and room temperature and CO2 level monitoring with external sensors.
Advertisement
Advertisement
GB.TBLZ266.180122
Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function)
GOLD RX 04-120
1. General
The TBLZ-2-66 accessory is a control system incorporated into a control box. The control box is designed for installation in connection with GOLD RX air handling units (Version E/F).
Communication cables for Modbus communication should be connected between the control box and the
GOLD air handling units.
The control box can be wired to a BMS via the Ethernet.
The control box contains a PLC system and the front panel of the box has a control terminal with touch screen.
The touch screen is used for entering settings and viewing readings for common functions.
2. Application area
The TBLZ-2-66 control box is a control system for controlling two parallel GOLD air handling units.
One GOLD air handling unit is selected as the Master, and the other unit is selected as the Slave.
The control box transmits set points to both air handling units. These set points then control each unit separately.
If the air handling units are to be regulated on a VAV basis and the duct pressure is to be kept constant, connect a standard pressure sensor to the GOLD unit that operates as the Master. The pressure readings are transmitted via the communication system to the control box and are processed there. This also applies to the external room temperature sensor and the CO
2 the system.
sensor, if one is used in
3. Installation
The control box should be installed in connection with the
GOLD unit selected as the Master.
It is advantageous if the control box touch screen and the hand-held micro terminal of the Master AHU are located in such a way that they can be operated and supervised from the same place.
Conditions
Parallel control is possible for the size 04–120 GOLD RX air handling units.
The GOLD air handling units involved must be of the same size.
The air handling units are considered parallel if they are connected to a common duct system.
Both air handling units must be equipped with the same accessories, such as an air heater, air cooler, dampers, etc.
4. Technical data
Enclosure class IP 66
Ambient temp. 0 - +50°C at relative humidity 5 - 85% (non-condensing)
Weight 7 kg
Dimensions 380x300x220
(WidthxHeightxDepth)
We reserve the right to alter specifications.
www.swegon.com 1
GB.TBLZ266.180122
5. Electrical connections
The electrical connections should be wired by a qualified electrician in accordance with local electrical safety regulations.
The supply voltage to the control box must be single-phase, 230 V, and the cable conductors must be connected to wiring terminals 101 (L) and 102 (N).
The control box must be connected to the control circuit card of the GOLD air handling unit with twisted-pair, shielded communication cables. Communication is conducted via Modbus RTU and the control circuit card of the control box is the communication Master.
The following wiring terminals must be connected as specified below:
Terminal in control box Terminal in GOLD unit
401 1 in the Master AHU
402
403
404
2 in the Master AHU
1 in the Slave AHU
2 in the Slave AHU
7.1 Temperature regulation:
ERS, Supply air and Extract air/Room regulation
ERS, supply air and extract air regulation are controlled in each GOLD unit. The settings in the control box are automatically transmitted over to the air handling units.
If room sensors are used for room regulation, this is activated in the Master unit.
Set the set points for ERS regulation in the Master AHU
(AHU 1).
7.2 Fan regulation
Flow regulation
The total flow set on the control box touch screen is split equally and is transmitted to the flow controllers of the
GOLD air handling units. The air handling units are then automatically set for flow regulation.
6. Commissioning
Energize the control box and both GOLD air handling units.
Set the Modbus addresses for communication in both
GOLD units.
In the hand-held micro terminal, scroll to Communication under Functions.
Select EIA-485 and check under Protocol that Modbus is selected.
Scroll to Settings and set the following parameters:
Modbus ID 1 for the Master AHU (AHU 1) and Modbus ID
2 (AHU 2) for the Slave AHU.
The Baud rate should be 38,400; the parity should be
“Even”; Stop bits should be 1. This applies to both GOLD air handling units.
Start the GOLD units via the hand-held micro terminal of each air handling unit.
Pressure regulation
The pressure regulation controller is located inside the control box. The pressure controller controls how the air handling units operate by transmitting flow set points to both GOLD air handling units. The control circuit cards of the air handling units maintain constant airflow in both air handling units. The air handling units are automatically set for flow regulation.
The standard pressure sensor of the GOLD units are used as duct pressure sensors in the common ducts. The duct pressure sensors are connected to the Master AHU’s connections marked COM 1-3.
The control box controller receives pressure values from the Master AHU via the communication system.
7. Description of functions
The ordinary control circuit card in the GOLD air handling units controls its respective functions, but obtains set points for certain functions of the control circuit card in the control box.
The type of temperature and fan regulation to be used can be selected on the touch screen of the control box.
Set the time and schedule in the hand-held micro terminal of the GOLD air handling unit serving as functional Master.
The settings in the Master AHU are automatically copied over to the Slave AHU.
Demand control
If demand control is used, the Master AHU’s extract air fan is controlled via signals on wiring terminals, inputs 18-19.
The supply air fan of the Master AHU is controlled in response to the extract airflow as a Slave. The Slave AHU copies the current flow regulation values and set points from the Master air handling unit. The air handling units are then automatically set for their respective functions.
2 www.swegon.com
We reserve the right to alter specifications.
GB.TBLZ266.180122
8. Touch screen and menus
8.1 Touch screen symbols
<
Used for scrolling back to the previous menu
>
Used for scrolling ahead to the next menu
Used for navigating to the main menu
Press on the relevant action bar pull-down menu or text box to change a function or a value. The value can then be changed by selecting a new function, or by entering a new value on the keyboard.
8.2 Menus in the touch screen
8.2.1 Main menu
The uppermost text line shows the type of air handling unit, date and time of day.
The second line shows the current operational status of the Master air handling unit.
The third line shows the current operating mode of the
Master air handling unit, according to Time and schedule.
Possible common fault alarms are displayed. Alarms are displayed as common fault alarm A or B and specify which air handling unit it refers to.
Parallel GOLD RX
High speed, time channel
High speed
Common fault alarm B for AHU 1
Common fault alarm B for AHU 2
2014 03:12 15:54
>
8.2.2 Settings menu
The buttons and touch screen are used for scrolling ahead to the desired function/menu image.
Temperature: Reading/setting temperatures.
The entering of settings requires that you log in.
Flow/Pressure: Reading/setting flows/pressures.
The entering of settings requires that you log in.
Installation: Selection of temperature and flow functions. The entering of settings requires that you log in.
<
Temperature
Flow/
Pressure
Installation Log in Log Out
We reserve the right to alter specifications.
www.swegon.com 3
Log in:
Log out:
Opens the Authorization level. Requires that you enter a code.
Manual log out.
Closes the Authorization level.
8.2.3 Temperature
In order to be able to change the set points The operator must log in, See Section 8.2.6.
The appearance of the menu varies depending on the type of regulation selected. Extract air/room regulation is shown in the menu to the right.
The current temperatures can be viewed and set here.
For reading current temperatures in the Master unit (AHU
1) and Slave unit (AHU 2).
The first value for SA shows the current supply air temperature of each air handling unit, the second value shows the current supply air set point of each air handling unit.
The first value for EA shows the current extract air temperature of each air handling unit, the second value shows the current extract air set point.
The values for OUTDOORS shows the current outdoor temperature of the relevant air handling unit.
The values for Room 1-4 show the Master AHU's room temperature reading.
The room set point is displayed.
The temperature set points as well as the min. and max. limiting can be changed.
<
Temperature
SA
EA
Outdoor
Room 1
Room 2
Setp. Roo
AHU 1
12.37 °C
20.19 °C
21.18 °C
20.00 °C
Temperature set points
EA/Room
Min. limit.
Max. limit.
20.00 °C
14.00 °C
30.00 °C
Extract air/Room regulation.
GB.TBLZ266.180122
AHU 2
22.18 °C
12.50 °C
4 www.swegon.com
We reserve the right to alter specifications.
GB.TBLZ266.180122
8.2.4 Flow/Pressure
In order to be able to change the values, the operator must log in. See Section 8.2.6.
The appearance of the menus varies depending on the type of regulation selected. Pressure regulation and flow regulation are shown in menus to the right.
The flows and pressures of immediate importance can be viewed and set here.
The first value for SA/EA shows the current pressure or flow; the second value shows the current pressure set point or flow set point.
If the AHU is operating in the flow regulation mode, the min. and max. flows (total min. and max. flows) are specified; if the AHU is operating in the pressure regulation mode, only the max. flow is specified. The AHU's possible min. and max. flows can be found in the Operation Level section of the Operation and Maintenance instructions for the GOLD air handling unit or in the hand-held micro terminal's help texts under Functions/Airflow.
If flow regulation is used, the control system of the control box splits the total airflow into two equal airflows and transmits the set points to each air handling unit. The total airflow is displayed.
<
Flow/Pressure
SA
EA
149 Pa
191 Pa
Max.
Pressure regulation
Flow/Pressure
SA
EA
1,006 l/s
1,004 l/s
<
Total flow set points
SA
Low
High
Min.
Max.
200 Pa
2,000 l/s Max.
1,000 l/s
3,500 l/s
600 l/s
3,500 l/s
200 Pa
200 Pa
1,000 l/s
1,000 l/s
200 Pa
2,000 l/s
Total flow set points
EA
Low 1,000 l/s
High
Min.
Max.
3,500 l/s
600 l/s
3,500 l/s
>
>
Pressure regulation
The P-band and I-times can be viewed and set here when the AHU is operating in the pressure regulation mode.
Flow regulation
Flow/Pressure
<
Supply air pressure controller
P-band 50.00 %
I-time 30.0 sec.
Extract air pressure controller
P-band 50.00 %
I-time 30.0 sec.
Pressure regulation
We reserve the right to alter specifications.
www.swegon.com 5
GB.TBLZ266.180122
8.2.5 Installation
The language setting can be changed without having to log in..
In order to be able to change the functions for temperature or flow/pressure regulation, the operator must log in.
See Section 8.2.6.
Selection of temperature regulation and/or flow/ pressure regulation
The form of regulation for temperature regulation or flow/ pressure regulation can be selected in the action bar pulldown menu..
<
Swedish
Master version: 2.00
Temp. regulation
Extract air regulation
SA fan
EA fan
Flow/Pressure
Pressure regulation
Pressure regulation
>
To set the communication means with the main control system
The function must be initiated in the touch screen. After initiation, alterations can be carried out both in the touchscreen as well as on the web page.
Touch screen
Initiation:
Press on ">" under the installation menu for access.
Fill in the IP-address, subnet mask and gateway. Press on
"Read IP-address".
Web page
Access:
Fill in IP-address/start.html in a web browser
(e.g. 192.168.1.10/start.html).
Touch screen and web page
Alterations:
Press on ">" under the installation menu for access.
Fill in the IP-address, subnet mask and/or gateway. Press on "Update IP-address".
8.2.6 To log In/Out
In order to obtain authorization for making changes in the temperature and flow regulation functions, you must log in.
Enter "user" in the box for entering user and "1111" in the box for entering password. The login symbol will then change from a lock symbol to a house symbol. Press on the house symbol to log in.
Your authorization will last for 5 minutes; then you will be automatically logged out.
To log out manually, press on “Log Out”.
<
<
IP address:
Subnet mask:
Gateway:
Read IP address
192
255
192
Update IP address
168
255
168
1
255
1
10
0
1 user
Box for entering user
Box for entering password
Symbol for login
6 www.swegon.com
We reserve the right to alter specifications.