DETECT
Temp
Installation - Adjustment - Care
20090508
DETECT Ta
DETECT Temperature is a temperature sensor for the
WISE system and can be wired to the ADAPT products via
CONNECT Adapt.
Adjustment
DETECT Temp has fixed values which cannot be changed.
Its range scale is 10 - 30 °C with the output signal of 0-10
V DC.
Care
The DETECT Temp should be wiped or brushed to remove dust whenever necessary. If it is extremely dirty, it can be cleaned with detergent, however only using a moist cleaning cloth.
Electrical Data
Supply voltage
Power consumption
Output: 0-10 V max load
Degree of protection
24 V AC ±10%
1 VA
10 mA
IP 30
Figure 1. Mount the DETECT Temp on an appropriate wall in the room. The product must not be exposed to sunlight or draught from open doors or windows.
1
20
Master
21
Slave
22
Slave
23
Modbus
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2
5
4
6
Figure 2. The wiring of DETECT Temp to CONNECT Adapt.
1 = The interconnection card in CONNECT Adapt
2 = DETECT Temp