Ecoflam MAIOR P 500-1 PRE Operating Instructions Manual

Add to My manuals
32 Pages

advertisement

Ecoflam MAIOR P 500-1 PRE Operating Instructions Manual | Manualzz

LIGHT OIL BURNERS

MAIOR P 500.1 PRE

MAIOR P 600.1 PRE

Technical data

Operating instructions

Electric diagrams

Spare parts list www.ecoflam­burners.com

EN

MAIOR P 500 PRE.1 TC

MAIOR P 500 PRE.1 TL S

10-01-2017

3144806

EN

INDEX

MAIOR P 500.1

MAIOR P 600.1

0

General warnings - Conformity declaration

Burner designation - Modular delivery system

Burner description

Electrical control panel

Technical data

Working diagrams

Test boiler - Flame dimension

Overall dimensions

Oil operating mode - General safety functions

1000

Installation

Fitting the burner to the boiler

Oil connection

Feeding and suction line for light oil

Electrical connections

Start-up: checking procedure

Exhaust gas test

Start-up oil side

Fuel selection - Start-up

Adjusting the max air flow rate

Firing head setting

Adjusting the max oil flow rate

Servomotor Lamtec - Air damper motor pre-setting

Adjusting the pump pressure

Adjusting the intermediate burner capacity

Maintenance program

Troubleshooting instructions

Operating troubles

Appendix

Control box - Display

Fluidics nozzle chart

Bergonzo nozzle tables

Pump and pressure regulators

Electrical diagrams

Spare parts list

2000 3000 4000 5000 6000

10

10

11

12

13

14

15

16

16

16

16

17

17

17

18

7000 kW

3

4

5

5

6

7

7

8

9

19

20

21

22

23

24

25

27

28

29

2 www.ecoflam-burners.com

420010813300

GENERAL WARNINGS - CONFORMITY DECLARATION

MAIOR burners are designed for the combustion of light oil.

The design and function of the burners meet the standard EN267. They are suitable for use with all heat generators complying with standard within their respective performance range.

Any other type of application requires the approval of ECOFLAM.

Installation, start-up and maintenance must only be carried out by authorised specialists and all applicable guidelines and regulations must be complied with.

BURNER DESCRIPTION

MAIOR burners are progressive mechanical fully automatic monoblock devices.

Emissions values may differ, depending on combustion chamber dimensions, combustion chamber load and the firing system (three-pass boilers, boilers with reverse firing).

EN 267

Automatic forced draught burners for liquid fuels.

EN 60335-1, -2-102

Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances

INSTALLATION LOCATION

The burner must not be operated in rooms containing aggressive vapours (e.g. spray, perchloroethylene, hydrocarbon tetrachloride, solvent, etc.) or tending to heavy dust formation or high air humidity.

Adequate ventilation must be provided at the place of installation of the furnace system to ensure a reliable supply with combustion air.

PACKAGING

The burner, and all the additional components are supplied in a modular system of packages according to the configuration ordered that based on the country of installation shall follow the applicable standards and the local rules and code of practise.

The following standards should be observed in order to ensure safe, environmentally sound and energy-efficient operation:

Declaration of conformity for oil burners

We ,

Ecoflam Bruciatori S.p.A.

declare under our sole responsibility that the oil burners named

MAIOR conform to the following standards:

EN 267

EN 55014-1

EN 60335-1

EN 61000-6-2

EN 50156-1

EN 55014-2

EN 60335-2-102

EN 61000-6-3

These products bear the CE mark in accordance with the stipulations of the following directives:

2014/35/UE Low Voltage Directive

2014/30/UE EMC Directive

2006/42/EC Machine directive

2011/65/EU RoHS2 directive

!

BURNER SELECTION: Type of operation and configuration must be done by professional personnel in order to grant correct working of the burner. Installation, start-up and maintenance must be carried out by authorised specialists and all applicable guidelines and regulations

(including local safety regulations and codes of practise) must be observed.

We accept no responsibility for damage arising from:

- inappropriate use;

- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts;

- non authorised modifications made on the burner.

Final delivery and instructions for use

The firing system installer must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator,

They should include the address and telephone number of the nearest customer service centre.

Notes for the operator

The system should be inspected by a specialist at least once a year.

Depending on the type of installation, shorter maintenance intervals may be necessary.

It is advisable to take out a maintenance contract to guarantee regular servicing.

EN

Ecoflam burners have been designed and built in compliance with all current regulations and directives.

All burners comply to the safety and energy saving operation regulations within the standard of their respective performance range. The quality is guaranteed by a quality and management system certified in accordance with ISO 9001:2008.

420010813300

www.ecoflam-burners.com

3

EN

BURNER DESIGNATION

MAIOR P 300.1 PR TC 230-400-50

RANGE NAME BY FUEL TYPE

MAIOR Light oil

MODEL SIZE (Gas: kW; Oil: kg/h)

MAIOR P 300.1

253 kg/h - 3000 kW

-

EMISSIONS

Standard Class 1 - OIL EN267 (<250 mg/kWh)

OPERATION TYPE

PR

MD

PRE

2 stages progressive mechanical gas / oil

2 stages modulating mechanical with PID

2 stages modulating electronic

HEAD TYPE

TC

TL

Short head

Long head

FUEL

BIODIESEL

KEROSENE

Light oil

Biodiesel

Kerosene

ELECTRICAL POWER SUPPLY

230-400-50 230-400 Volt, 50 Hz

MODULAR DELIVERY SYSTEM

Light oil burners

All light oil burners are delivered complete in one single packaging including filter and flexible hoses up to 6 MW.

Additional accessories and options shall be installed by the installer in accordance to the instruction and local safety regulations and codes of practise.

KITS - Accessories

Kits and accessories are managed and delivered separately.

Component type

CB

KIT

ACS

Complete burner

Kits

Accessories

4 www.ecoflam-burners.com

420010813300

BURNER DESCRIPTION

EN

Control panel

HLF

V

HLBT

R 0: OFF

1: ON

SAL main switch I/0

HLF working lamp

HLBT thermal lock-out lamp

420010813300

www.ecoflam-burners.com

5

EN

TECHNICAL DATA

MODEL

Thermal power max.

kW kcal/h

Thermal power min.

kg/h kW kcal/h kg/h

Operation mode

Regulation ratio nominal

Fuel

Emission class

Control unit

Air regulation

Type

Type

Type std

Air flap control with servomotor

Flame monitoring

Ignitier

Motor

Rpm

Voltage

Total power consumption operation

Weight body BBCH

Electrical panel protection level

Sound pressure level without silencer

Sound pressure level with silencer

Ambient temperature storage

Ambient temperature use

Oil pump

Nozzles

Type

Type

Model

Type

Model kW

V/Hz

W

Kg

IP dB(A)

Lab tests

Min/Max

Model

Type

MAIOR P 500.1 PRE

5.000

4.300.000

422

1.200

1.032.000

101

1.290.000

126

Progressive mechanical oil - Modulating with PID

1÷3 OIL

Light oil (L.C.V. 10.200 kcal/kg max. visc 1,6÷6 mm 2 /s at 20°C) (EL) Hu = 11,86 kWh/kg

Standard Class 1 OIL EN267 (<250 mg/kWh)

LAMTEC ETAMATIC BT3xx

Air flap Air flap

LAMTEC

UV CELL

BRAHMA

MAIOR P 600.1 PRE

5.800

4.988.000

489

1.500

11

2.800

15

2.800

230/400 V - 50 Hz

12.000

16.500

IP55

91,1

85,7

TA3

-20°…+70° C

-10°…+60° C according to the output requested

IP55

92,8

86,7

TA4

6 www.ecoflam-burners.com

420010813300

WORKING DIAGRAMS mbar 25

20

15

10

5

MAIOR P 500.1

MAIOR P 600.1

7000 kW

6000 kcal/h*1000 kg/h

Calculation of burner output

QF = Burner output (kW)

QN = Rated boiler output(kW)

η = Boiler efficiency (%)

QF =

QN x 100

η

Working diagrams

The working diagram shows burner output as a function of combustion chamber pressure.

It corresponds to the maximum values specified by EN 276 measured at the test fire tube.

Boiler efficiency should be taken into consideration when selecting the burner.

0

1000

1000

100

2000

2000

200

3000

3000

300

4000

4000

400

5000 6000

5000

500

TEST BOILER - FLAME DIMENSIONS

FLAME LENGHT LIGHT OIL BURNERS

L (m) 11

10

9

8

7

6

5

4

3

2

0

1000 2000 3000 4000

1000

100

2000

200

3000

300

4000 5000

400

5000

6000

500

6000

7000

600

7000

8000

700

8000 9000 10000 11000

9000

800

10000

900

11000 12000

1000

13000

1100

12000

14000

1200

13000

15000

1300

14000

16000

1400

15000 kcal/h x 1000

17000 kW kg/h

FLAME DIAMETER LIGHT OIL BURNERS

Ø (m) 2

1,8

1,2

1

0,8

1,6

1,4

0,6

0,4

0,2

0

1000

1000

2000

2000 3000

3000

4000

4000

5000

5000

6000

100 200 300 400 500

6000

7000

600

7000

8000

700

8000 9000 10000 11000

9000

800

10000 11000

900

12000

1000

13000

1100

12000

14000

1200

13000

15000

1300

14000

16000

15000 kcal/h x 1000

17000 kW

1400 kg/h

420010813300

The burner/boiler matching does not pose any problem if the boiler is CE typeapproved.

If the burner must be combined with a boiler that has not been CE type-approved and/or its combustion chamber dimensions are clearly smaller than those indicated in diagram, consult the manufacturer.

The firing rates were set in relation to special test boilers, according to EN 267 regulations.

The sizes are indicative and dipend on the configuration, to the combustion chamber pressure and to the draught.

The values have been taken out from tests executed with flame tubes.

The dimensions of the flame are made in test boiler in laboratory without resistence therefore exists max and min lenght that take into account the difference in lenght that comes from the boiler backpressure.

Example:

Burner thermal output = 8000 kW;

L flame (m) = 5 m (medium value)

D flame (m) = 1 m (medium value)

WARNING: Some flame modifications can be done in our FLEXSHOP in the factory in order to shape the flame and adapt it to some special boiler or application.

www.ecoflam-burners.com

7

EN

EN

OVERALL DIMENSIONS

E D - D1 B

A

0

1

2

0

1

2

C

SUNTEC

M

I

D = Short head

D1= Long head

Dimensions (mm)

Model

MAIOR P 500.1 PRE

MAIOR P 500.1 PRE S

MAIOR P 600.1 PRE

A

1240

1240

1240

B

635

635

635

C

605

605

605

D

355

-

355

D1

555

835

555

E

1100

1100

1100

F

320

320

320

G

570

570

570

H1

965

965

965

I

330

330

330

L

330

330

330

M

M16

M16

M16

Burner-boiler mounting flange

Fixing hole dimensions are “I” and “L” as per dimension table.

Boiler hole shall be done according to the blast tube dimension “F” plus

15-25 mm in order to be able to extract it during maintenance.

WARNING: Please follow the suggested dimension for the hole on the boiler flange in order to fit the burner. Make sure that between the boiler and the blast tube proper insulation is fitted.

Packaging (only burner)

Model X Y Z

MAIOR P 500.1 PRE S 1750 2380 1460

MAIOR P 600.1 PRE S 1750 2380 1460 kg

330

420

X

Y

Z

8 www.ecoflam-burners.com

420010813300

OIL OPERATING MODE - GENERAL SAFETY FUNCTIONS

START-UP MODE

As soon as the furnace system is required to supply heat the burner control circuit will close and the program be started. After the program has run down the burner will start.

The air damper is closed when the burner iis out of operation.

The automatic furnace controller controls and monitors the starting function.

The electric actuator opens the closed air damper to its full-load position so that the burner will sweep the furnace compartment and exhaust ports at the required air flow rates. At the end of the specified pre-ventilation time the air damper will be moved into its partial load position. This operation will be followed by the pre-ignition procedure and the oil feed start.

The solenoid valves will open and thus allow the pressurized oil to flow to the nozzle and to the return line.

The oil will be atomized, mixed with the combustion air and ignited.

A safety period is provided to allow the flame to develop a proper and steady pattern.

On the termination of the safety period, a flame signal must have been received by the automatic furnace controller via the flame monitor and remain on until the regular shut-off.

The startup program of the burner has now been completed.

OIL OPERATING MODE

After the flame has developed the load regulator will be enabled which brings the burner into its operating position.

The load regulator will now control the burner automatically between its partialload and full-load stages.

Depending on the heat demand, the electric actuator of the mechanical compound control system will be fed with the OPEN or CLOSE signal via the regulator and thus increase or decrease the oil and air flow rates.

This compound control system will vary the positions of the oil control valve and air damper and thus regulate the oil flow rate in conjunction with the air flow rate. The burner can either be controlled in twostage sliding mode or, if a respective controller is provided, in stepless control mode.

The stepless control will allow the burner to be operated at any desired stage between its partial-load and full-load positions. The burner will be turned off from its partial-load position. The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney.

The interior cooling losses will be greatly minimized.

EN

GENERAL SAFETY FUNCTIONS

In case a flame does not develop when starting the burner (fuel release) the burner will shut off at the end of the safety period (safety lock-out).

A safety lock-out will also occur in the case of flame failure during operation, air flow failure during the pre-ventilation phase and pressure failure during the whole period of burner operation.

Any failure of the flame signal at the end of the safety period and a flame signal during the pre-ventilation phase (external light control) will result in a safety lock-out with the control box being locked.

The trouble is indicated by the trouble signal lamp lighting up.

The control box can be unlocked immediately after a safety lock-out by pressing the unlocking key. The program unit will return to its starting position and proceed with the restart of the burner.

A voltage failure will result in a regular shut-off of the burner. Upon voltage recovery there may be an automatic restart unless another interlock is provided, e.g. by the safety system. In any case of trouble the fuel oil supply will be shut off right away. The program unit will stop at the same time causing also the trouble location indicator to stop.

The symbols will indicate the kind of trouble.

420010813300

www.ecoflam-burners.com

9

EN

INSTALLATION

Fitting the burner to the boiler

!

WARNING: handling and moving operations must be carried out by specialised personnel.

Use the eyebolts to lift the burner in order that it will not overturn and fall down.

To perform the installation of the burner into the boiler drill the boiler plate according to the dimension given on this manual and place the burner towards it by lifting and moving the burner by means of eyebolts.

Place the gasket on the burner flange and install the burner into the boiler by fixing nuts into the bolts.

The space between the blast tube and the boiler lining must be sealed with appropriate insulating material.

Burner blast tube insertion depth and brickwork

Unless otherwise specified by the boiler manufacturer, heat generators without a cooled front wall require brickwork or insulation 5 as shown in the illustration.

The brickwork must not protrude beyond the leading edge of the blast tube, and should have a minimum conical angle of

60°. Gap 6 must be filled with an elastic, non-combustible insulation material. For boilers with reverse firing, the minimum burner tube insertion depth A as speci fied in the boiler manufacturer’s instructions must be observed.

On boilers the blast tube insertion depth should be observed as per the boiler manufacturer's instructions.

Reverse flame boiler :

A = 50-100 mm.

Three pass boilers :

A1 = 50-100 mm.

Exhaust system

To avoid unfavourable noise emissions, right-angled connectors should not be used on the flue gas side of the boiler.

A1

A

Position of the electrodes - nozzle installation

3

÷

4 mm

Ignition Electrode

BURNER LINING

Check before burner installation:

1. Depending on the type of boiler (reverse flame or three pass) check the burner blast tube installation depth according to the data specified by the boiler manufacturer or consult the burner producer.

2. From the factory the nozzle for progressive version must be specified from the customer according to boiler output and combustion chamber geometry, otherwise we will select the nozzle for the 80% capacity of the burner.

3. Check the ignition electrodes and the nozzle on the burner head as per factory setting (see figures).

The setting of the mixing and ignition unit according to the boiler output will be performed during commissioning procedure.

4. Check that the head is preset at 50%.

10 www.ecoflam-burners.com

5

÷

6 mm

420010813300

INSTALLATION

Oil connection

!

WARNING: make sure that the feeding line is properly dimensioned and is in compliance with the local safety rules and code of practise in the country of installation

HYDRAULIC CIRCUIT

LIGHT OIL FEEDING

176: oil pump

178: solenoid valve

184: output control valve

311: return oil pressure switch

CV: check valve

RL: return line

VL: suction line

VLO: working oil valve

V L

RL

176

CV

178

311

V LO

184

EN

OIL PRESSURE CONTROL (FEED)

The feed pressure is controlled by means of the pressure regulator installed in the pump and should be set at 25 bar. The pressure regulator is operated by turning its screw. Make sure to fill the pump with oil prior to taking into operation.

PUMP BLEEDING

Open the feed and return stop valves and ensure the ring line (if any) is in operation.

Reduce the oil pressure at the pressure regulating valve. Turn on the pump by pressing the contactor.

Check the pump for proper direction of rotation. Check for proper oil delivery and absence of leaks in the hydraulic oil system. For bleeding the pump open the pressure gauge connection, for example.

When taking the burner into operation pro ceed by gradually increasing the pressure to operating level (25 bar).

CHECKING THE PRESSURE

(OIL SUCTION PRESSURE)

The maximum permissible vacuum is 0,4 bar. At higher vacuum levels the fuel oil will tend to separate air from oil which may lead to operating trouble. In the ring line mode of operation the recommended oil pressure is 2 bar.

close to the burners as possible and to arrange them in a way that the boiler door and the burner can be swing out without any obstruction.

Refer to the technical documentation for the line dimensions for the feed and return lines from the stop valves to the tank.

OIL FILTER

A filter must be installed upstream of the pump to protect the oil pressure pump and the hydraulic system.

OIL CONNECTION

Hoses are used for connection to the oil lines and stop valves. The hoses must be installed according to the applicable standards (relieved of tensile load, free of distortion) to avoid kinking and exclude the danger of breakage. Take care when mounting the oil lines to bring their ends as

INSTALLATION OPTIONS

• Two-line installation (separate feed and return lines without delivery pump).

• Ring line system (with delivery pump and gas-air separator).

10

9

LEGENDA

1. Inlet

2. Return

3. Bleed and pressure gauge port

4. Vacuum gauge port

5. Pressure adjustment

6. Nozzle outlet

7. Heater

8. Hose

9. Oil filter

10. Oil ball valve

8

8

!

WARNING: Check that the pump rotation is correct and before start up it has been pre-filled

420010813300

www.ecoflam-burners.com

11

EN

INSTALLATION

Feeding and suction line for light oil

SUCTION LINE LENGTHS FOR PIPE SYSTEMS

• Two-pipe siphon feed system

• Two-pipe lift system

H

H

H

(m)

3

2,5

2

1,5

1

0,5

0

-0,5

-1

-1,5

-2

-2,5

-3

-3,5

-4

The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the side.

PIPE LENGTH (m)

TA3 TA4

ø 14 mm ø 16 mm ø 20 mm ø 20 mm ø 30 mm

10 32 115 65 150

8

7

28

25

110

100

60

55

150

150

6

5

--

--

--

--

--

22

20

17

15

10

5

--

95

85

75

65

55

45

37

50

45

40

35

28

22

12

150

150

150

150

150

150

150

--

--

--

--

--

--

--

--

--

--

30

22

9

--

--

7

--

--

--

--

150

150

123

78

38

WARNING: To calculate the length of the pipework all the straight parts, curves, up and down pipes must be taken into consideration.

The static suction height is the distance between the standing valve and the axis of the burner pump.

Negative pressure must not exceed 0,45 bar; if negative pressure is greater pump operation may become faulty, leading to an increase in mechanical noise and perhaps even breakage.

All oil ring installations must comply with the local safety rules existing in the country of installation

The pumps that are used can be installed both into single-pipe and double-pipe systems:

Single-pipe system: a single pipe drives the oil from the tank to the pump’s inlet that deliver the pressurized oil to the nozzle and part of the oil not used goes back to the pump. With this single pipe the by-pass plug must be removed and the return port must be sealed with steel plug and washer.

Double-pipe system: this is the default solution from the factory.

The return pipe send the excess oil from the pump to the tank. Depending on the type of pump used to change from a 1-pipe system to a 2-pipesystem, insert the by-pass plug (as for ccw-rotation referring to the pump shaft).

Note for commissioning: during commissioning, the filter, pipelines and pumps must be pre-filled with fuel oil and vented.

The direction of rotation of the motor should be checked. When commissioning it must be ensured that pump never run dry.

NOZZLE SELECTION

Please refer to diagram to select Ecoflam recommended nozzle for the output that is required given the output necessary in the installation.

Regular maintenance is highly recommended.

Nozzle has to be cleaned in petrol or paraffin and if filter or other parts are defective or damaged the nozzle must be replaced.

NOZZLE CHART IS AVAILABLE ON APPENDIX PAGE

SUNTEC TA

Oil under suction

Oil under pressure

Vacuum or inlet pressure gauge port

B y passed oil returned to tank, or to suction

Pressure gauge port

Intake from T ank

B y pass plug inserted

Pressure adjustment

Intake from T ank

B y pass plug removed

T o nozzle

Return

TWO PIPE

INSTALLATION

ONE PIPE

INSTALLATION

Return plugged

12 www.ecoflam-burners.com

420010813300

INSTALLATION

Electrical connections

!

WARNING: Electrical wiring must be carried out with electrical supply disconnected and with burner switch in position OFF.

Electrical supply must correspond to the one shown on the burner label.

APPLICABLE STANDARD

The electrical connection work comprising all the installation materials, terminals and earth connections must be carried out in accordance with the applicable regulations. For the electrical installation of the burner care must be taken to observe the circuit diagram made out for the furnace system.

The electrical connection of the burner and instruments shall be entrusted to authorized specialists only.

NOTE: For the installation of the connection cables care must be taken to provide cable loops of sufficient length to allow for the swing-out of the boiler door and burner.

Make sure after the completion of the electrical connection work to check the wiring of the electrical system of the burner. This should include a check of the direction of rotation of the burner motor

(fan).

GENERAL WARNINGS:

All applicable electrical safety regulations must be followed. Failure to correctly dimension the suitable input power and earth the equipment may cause damages to person and compromise the correct function of the burner therefore the electrical system shall be checked by qualifed personnel.

The manufacturer declines all responsibility for modifcations or connections different from those shown in the electrical scheme.

Adapters, multiple plugs and extension cables may not be used for the equipment’s power supply.

An omnipolar switch in accordance with current safety regulations is required for the mains supply connection.

ATTENTION: Wiring is not supplied.

The burners are produced with connections suitable for power supply

380-400 V three-phase.

The burners with electric motors of an output lower or equal to 3 kW can be adapted to 220-230 V (please follow the instructions on the backside); motors with higher output can only work 380-400 V three-phase. In case of request of burners different from the above mentioned standard, it is recommended to make specific mention in the order.

Instructions: how to adapt electric motors of an output lower or equal to 3 kW to 220-230 V power supply

It is possible to change the voltage of the burner by operating as follows:

1. change the connection inside the electric box of the motor, from star to delta

(see picture 1);

2. change the setting of the thermal relay, referring to the absorption values indicated in the motor nameplate. If necessary, replace the thermal relay with another one of suitable scale.This operation is not possible on motors above 3 kW.

For more information, please contact the

Ecoflam staff.

PROBES CONNECTION

ACTIVE PROBE CONNECTION

(FOR MODULATING VERSION) fig.1

400V

230V

9 10 11 12 13

SA

G L M U1

Q BE ....

PASSIVE PROBE CONNECTION

(FOR MODULATING VERSION)

9 10 11 12 13

S P

M

Q AE ...

B

LEGENDA

HLB: lock-out lamp

STAB: two stages thermostat

HLF: burner on flame lamp

STC: boiler thermostat

STS: safety thermostat

SA: active probe

SP: passive probe

ELECTRICAL CONNECTION

1) of the burner

- Built-in electrical cabinet

Use cable gland in order to secure the required level of protection. All the links, power and control, are connected to the terminal block of the cabinet. Provide cables in sufficient length to secure the rotation of the burner body according to the assembly.

Check and adjust the size of the contactors and thermal relays and the wires section according to the motor and supply voltage specs.

PE

R

S

T

N

50 Hz 400V

R S T N 1 2 3 4 5 6 7 8 9 10 11 12 13

Q

HLB

STAB

T

P

HLF

STC

T

P

STS

T

P

420010813300

www.ecoflam-burners.com

13

EN

EN

START-UP: CHECKING PROCEDURE

CHECKS BEFORE COMMISSIONING:

• That the burner is assembled in accordance with the instructions given here.

• Setting the combustion components.

• All electrical connections must be correct.

• Check the burner motor for correct direction of rotation.

• The heat generator must be ready for operation, and the operating regulations for the heat generator must be observed.

• The heat generator and heating system must be filled with water and the circulating pumps must be in operation.

• The temperature regulator, pressure regulator, low water detectors and any other safety or limiting devices that might be fitted must be connected and operational.

• The exhaust gas duct must be unobstructed and the secondary air system, if available, must be operational.

• An adequate supply of fresh air must be guaranteed.

• Check tank, lines and oil pump are filled with oil and correct oil nozzle is fitted.

• With burner in starting position check that air damper is in “CLOSED” position.

• Check that control box is unlocked and in its original position.

• A standard-compliant measuring point must be available, the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results.

OIL START-UP

Open all shut-off valves of oil supply system.

• Set fuel selector switch to its “Oil” position.

• Fill pump with oil.

• Mount pressure gauge in the feed line and return line.

• Mount the pressure gauge for checking the pump suction pressure.

• Make sure that the nozzle is size and mounted correctly.

Bleeding of oil system

Shortly start the burner and check for proper direction of rotation. Bleed the oil line and oil pump.

CAUTION: The hydraulic system has been filled with oil by the manufacturer.

This may cause ignition trouble when initially operating the system.

When starting the burner take care to increase the oil pressure slowly to the operating level.

Prior to the initial fuel feed start make a functional test of the burner program flow:

Oil system:

• Open all shut-off valves of the oil supply system.

• The oil solenoid valve in the feed line disconnect on the terminal strip (see

Circuit Diagram).

• Start burner and check program flow for correct start-up sequence:

1. Fan starts.

2. Pre-ventilating damper.

3. Air pressure check.

4. Partial-load air damper.

5. Ignition.

6. Valves open (disconnected valve remains closed).

7. Safety lock-out after expiry of safety period (see control box).

• Reconnect the valve.

• Unlock the control box.

14 www.ecoflam-burners.com

420010813300

EXHAUST GAS TEST

To ensure an economically efficient and trouble-free operation of the system it will be necessary to adjust the burner specifically in accordance with the furnace system. This is achieved by means of a fuel-combustion air compound control unit which adjusts the burner to ensure a proper combustion. Exhaust gas tests are required for this purpose.

The percentage CO2 and O2 and the exhaust gas temperature will have to be measured to determine the efficiency and combustion quality.

Prior to any measurement make sure to check the boiler and exhaust gas system for absence of leaks.

Secondary air will falsify the measured results

Check that the exhaust gases have a residual oxygen (O2) content as low as possible and a carbon dioxide (CO2) content as high as possible.

The carbon monoxide content of the exhaust gases must be below the currently applicable specifications in all load stages.

In the fuel oil combustion mode the permissible soot number in the exhaust gas is not allowed to be exceeded

Recommended combustion parameters

Fuel

Natural gas

Light oil

Heavy oil

Recommended

(%) CO2

10 ÷ 9

13 ÷ 11,5

12,5 ÷ 11

Recommended

(%) O2

3,1 ÷ 4,8

3,3 ÷ 5,3

4,2 ÷ 6,2

Ratio between O

2

- and CO

2

- for natural gas H (CO

2 max = 11,7%)

Ratio between O

2 for light oil EL (CO

- and CO

2

2

- max = 15,40%)

Ratio between O

2

- and CO

2

- for heavy oil S (CO

2 max = 15,60%)

O

2

= 21 CO 2 max - CO

2 gem = %

CO

2 max

CO

2 gem = % CO

2 measured on dry flue gases

WARNING: if the installation is above sea level the output of the burner vary base on the diagram.

The regulation of the burner in this case shall take into account the reduced power of the burner due to the missing air.

M

e

a

n

a

ir pressure vs

.

a

ltitude

a

bove se

a

-level

5000

4500

4000

3500

3000

2500

2000

1500

1000

5 00

0

0 5 10 15 20 25 30 35

F

a

n

ca

p

ac

ity redu

c

ed by [%]

40 45 50

EN

420010813300

www.ecoflam-burners.com

15

EN

START-UP OIL SIDE

Fuel selection - Start-up

Select the oil operation in order to proceed with start up on the oil side.

0

SAL

1

MAIN SWITCH

0 - OFF

1 - ON

KMV

!

KMV contactor: check the air fan motor rotation.

If the rotation if not correct invert the two phases on the power supply.

START UP THE BURNER

The control box starts the pre-purge cycle, the fan motor and the oil motor and opens the air flaps in full open positon.

At the end of pre-purging, the control box drives the servomotors into the igniton positon and starts the igniton transformer.

After a few seconds the control box opens the oil valve and starts the flame. After the flame stabilisaton the control box drives the servomotor in the low flame.

In case of faulty igniton, the control box switches the burner into safety condition, in such a case you must rearm the burner.

Gradually increase burner output from the low flame to the high flame and set oil servomotor curve in order to have a stable flame. Refer to LAMTEC manual attacched.

Adjusting the maximum air flow rate

Air and Oil adjustment are accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.

Firing head setting

The firing head is pre-adjusted at the 50% from the factory. The setting fully open enables to reach the full power of the burner and full close to reach the minimum power of the burner.

The optimal position depends on the output that we need to reach but the default setting shall be modified only when you are not able to reach the suggested combustion value by adjusting the air flow in the maximum flame.

+

– B

-+

16 www.ecoflam-burners.com

420010813300

START-UP OIL SIDE

Adjusting the maximum oil flow rate

Put the selector on the maximum operation. Adjust the oil pressure reading the value on the return manometer / pressure gauge according to the nozzle tables provided in the appendix.

NOTE: the pump pressure is set from the factory at the pressure required nozzle pressure required as per table of nozzle selection in appendix. If the output required is different from the one set from the factory the pressure can be adjusted according to the instruction below.

Servomotor LAMTEC - Air damper motor pre-setting

Air adjustment is accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.

EN

Adjusting the pump pressure

1 - INLET

2 - RETURN

3 - BLEED AND PRESSURE GAUGE PORT

4 - VACUUM GAUGE PORT

5 - PRESSURE ADJUSTMENT

6 - TO NOZZLE

4

SUNTEC TA....

3

1

5

2

The pump pressure is set at a value of 22-25 bar during the testing of burners.

Before starting the burner, bleed the air in the pump through the gauge port.

Fill the piping with light oil to facilitate the pump priming. Start the burner and check the pump feeding pressure.

In case the pump priming does not take place during the first pre-purging, with a consequent, subsequent lock-out of the burner, rearm the burner’s lock-out to restart, by pushing the button on the control box.

If, after a successful pump priming, the burner locks-out after the prepurging, due to a fuel pressure drop in the pump, rearm the burner’s lock-out to restart the burner.

Do never allow the pump working without oil for more than three minutes.

!

NOTE: before starting the burner, check that the return pipe is open. An eventual obstruction could damage the pump sealing device.

6

420010813300

www.ecoflam-burners.com

17

EN

START-UP OIL SIDE

Adjusting the intermediate burner capacity

Oil adjustment is accomplished through LAMTEC parameters setting. Refer to LAMTEC manual attacched.

WARNING: the variable profile of the cam shall have a normal proportional curvature in order to have good combustion values and reduce its mechanical stress breakdown.

1

VS VL

A

R

3

6

I

I 7

5 ma x

4

!

WARNING: Once the setting on the oil has been completed make sure that you close the manometer

– pressure switch tap.

PR

A

R

1

VS

3 m in

VL

4

6

I

I

7

5

PR

LEGENDA

1.

Oil pump

VS. Oil safety valve

3.

Adjusting cam

4.

Check valve

VL. Working valve

PR. Pressostat (optional)

5.

Nozzle

6.

Pressure regulator

7.

Manometer – pressure gauge

18 www.ecoflam-burners.com

420010813300

MAINTENANCE PROGRAM

!

Burner and boiler servicing must only be carried out by authorised qualied personnel at least once a year.

Depending on the type of installation, shorter maintenance intervals may be necessary.

The system operator is advised to take out a maintenance contract to guarantee regular servicing.

WARNING: Use original spare parts.

SAFETY WARNINGS:

1. Turn off the power supply and protect the system from accidental start-up

2. Cut oil

3. Make sure there is no residual power in the system and that the actions in points 1 and 2 have been completed

4. Before opening the burner casing, ensure that the fan motor has stopped completely

Failure to observe any of these instructions will result in the risk of death or injury!

0

SAL

1

WORKS RECOMMENDED AS PART OF ANNUAL BURNER MAINTENANCE:

• Emergency stop button function check

• Check burner start characteristics

• Run burner test and input measurement in the boiler room

• Clean the combustion components and replace defective parts if necessary

• Check the combustion head components and make sure that all components are in good condition otherwise replace them

• Replace ignition electrodes and nozzle if necessary and check their correct position after any intervention

• Flame monitor and automatic combustion control unit function check

• Clean the fan wheel and the housing and grease rotating parts if necessary

• Clean the oil filter cartridge with gasoline periodically and check the tightening of the O rings, replace them if necessary

• Make visual inspection of the burner’s electrical components and eliminate malfunctions if necessary

• Burner safety devices function check (air pressure/switches if any)

• Commissioning the burner and correct the adjustment values if necessary

NOTES ON REASSEMBLING: Perform the described step in reverse order and make sure to refit components as they were originally assembled and the system is free from leaks. Use only original spare parts.

DRAW UP A MEASUREMENT REPORT ACCORDING TO THE LOCAL REGULATION AND CODES OF PRACTISE OF THE

COUNTRY

EN

EXHAUST GAS LOSS

Exhaust gas loss by way of free heat will occur as a result of the temperature difference between the fuel-air mixture entering the furnace chamber and the gases discharged. Any increase in the excess of air and the resultant higher exhaust gas volume will cause the exhaust gas loss to rise. The exhaust gas loss can be calculated as follows: q

A

= (t

A

- t

L

)

A

1

CO

2

+ B

A1

B

Light oil

EL

0,50

0,007

Heavy oil

S

0,490

0,007

Example

Data measured in natural gas mode:

CO

2 content of exhaust gases: 10,8%

Exhaust gas temperature: 195°C

Air intake temperature: 22°C q

A t

A t

L

CO

2

= exhaust gas loss [%]

= exhaust gas temperature [°C]

= combustion air temperature [°C]

= volumetric content of carbon dioxide [%]

The exhaust gas loss can be calculated as follows: q

Af

= (195-22)(

0,37

10,8

+ 0,009) = 7,48%

Natural gas Town gas

0,370 0,350

0,009 0,011

Data measured in fuel oil mode:

CO

2

LPG

0,420

0,008 content of exhaust gases: 12,8%

Exhaust gas temperature: 195°C

Air intake temperature: 22°C

The exhaust gas loss can be calculated as follows: q

Af

= (195-22)(

0,49

12,8

+ 0,007) = 7,83%

420010813300

www.ecoflam-burners.com

19

EN

MAINTENANCE PROGRAM

REMOVING

THE BLAST TUBE

REMOVING

THE FIRING HEAD

3

4

+

-

1

2

POSITION OF ELECTRODES

ATTENTION: to remove the nozzle use the suitable box wrench taking care to not damage the electrodes .

Check the position of the electrodes after any intervention as wrong position could cause ignition troubles.

3

÷

4 mm

Ignition Electrode

5

÷

6 mm

OIL FILTER CLEANING

ATTENTION: Periodically clean oil cartridge with gasoline and replace them if it is necessary!

20 www.ecoflam-burners.com

420010813300

TROUBLESHOOTING INSTRUCTIONS

For Setting and Error Lists refer to LAMTEC manual attacched.

OPERATING TROUBLE

In case of operating trouble it should be checked whether the system is in proper working order.

Make a check for the following:

1. Availability of fuel.

Availability of gas in the line at sufficiently high pressure.

Availability of fuel oil in the tank (for dual fuel burner).

Correct position of fuel selector switch.

2. Availability of electric power in the burner system.

3. Proper functional order and setting of all control and safety instruments such as temperature controller, safety limiter, water failure cut-out, electrical limit switches, etc.

If the trouble is not found to be due to any of the above-mentioned points it will be necessary to test the burner functions very carefully.

Prevailing conditions:

The burner will be found to be out of operation and in faulty and interlocked position.

Proceed with searching for the cause of the trouble and eliminate it. Unlock the control box by pressing the fault eliminate key and start the burner.

Do not press the fault eliminate key longer than 10 seconds.

The start-up program will be initiated and should be carefully monitored.

The possible cause of the fault may be quickly found by reference to the fault indicator of the control box and watching the start-up and operating program.

APPENDIX

Function - Lamtec BT3xx control and safety unit

The control and safety unit BT 3xx controls and monitors the forced draught burner.

The microprocessor-controlled program sequence ensures the maximum consistency of the cycle times involved, regardless of fluctuations in the mains voltage or ambient temperature. The control and safety unit is designed to detect power failures. Depending on the parameter assignment, the unit either switches to malfunction mode or goes into the standby position if the power supply falls below the mains voltage. In the standby position, there is an automatic restart as soon as the set threshold value is exceeded by 105%.

Manual locking and unlocking

Using the reset button , the control and safety unit can be locked manually

(interlocked) or unlocked, provided the unit is connected to the mains power supply.

This function must not be confused with automatic locking and fault acknowledgement in case of an error.

Pressing the unlocking button on the unit for

... 1 second ...

... 2 seconds ...

.... causes ....

the control unit to unlock.

the control unit to lock.

Moves the cursor upwards.

Moves the cursor downwards.

Increases the marked value.

Reduces the marked value.

!

Always switch off the power supply before installing or removing the control unit. Do not attempt to open or carry out repairs on the control unit.

Modifies/Confirms the value shown.

Unlocks the control unit.

Red LED (flashes if a fault is present).

Refer to LAMTEC manual attacched.

EN

420010813300

www.ecoflam-burners.com

21

EN

APPENDIX

Fluidics nozzle chart

25

RETURN NOZZLE

The nozzle type Fluidics W is a by-pass nozzle with integrated spring-loaded cut-off needle.

The throughput rate is controlled by varying the return pressure while keeping the supply pressure at a constant level.

Prior to burner start, check the nozzle size against the required output.

It might be necessary to replace the nozzle (see nozzle selection diagram).

Return pressure

20

15

≤ 60 kg/h

> 60 kg/h

10

50° 70° 90° Spray angle

Supply

25 Bar

Bar 5

20 40 60 80 100 % Output

22 www.ecoflam-burners.com

420010813300

APPENDIX

Bergonzo nozzle tables

EN

420010813300

www.ecoflam-burners.com

23

EN

APPENDIX

Bergonzo nozzle tables

24 www.ecoflam-burners.com

420010813300

APPENDIX

Bergonzo nozzle tables

EN

420010813300

www.ecoflam-burners.com

25

EN

APPENDIX

Pumps and pressure regulators

PUMP SUNTEC TA TECHNICAL DATA

Note: All TA models are delivered for two-pipe system (by-pass plug fitted in vacuum gauge port).

For one-pipe system, the by-pass plug must be removed and the return port sealed by steel plug and washer.

P UM P

I D EN T I F I C A T ION

( Not a ll mode l combinations are a v ai l ab l e

Consu l t y our Suntec representati v e )

T A : t y pe

Oil under suction

Oil under pressure

Vacuum or inlet pressure gauge port

B y passed oil returned to tank, or to suction

Pressure gauge port

Gear set capacit y

( see pump capacit y cur v es )

S h a f t rotation

( seen f rom s h a f t end )

A : c l oc kw ise rotation

C : anti c l oc kw ise rotation

Intake from T ank

B y pass plug inserted

Pressure adjustment

T o nozzle

T A 2 A 4 0 10 5 Return

TWO PIPE

INSTALLATION

P ressure ran g e :

30 : 7 30 bars

40 : 7 40 bars

P re h eater f aci l it y

Intake from T ank

B y pass plug removed

R e v ision number

ONE PIPE

INSTALLATION

Return plugged

General

M o u ntin g

C onn ec tion t h reads

Inl e t e n d re t ur n

T o nozzl e

P ressure g au g e p o r t

V acuum g au g e p o r t

S h a ft

B y -pass p l ug

W e i gh t

Hydraulic data

F l a n g e m o u ntin g

C ylin dr i ca l acc o rd in g to I S O 22 8/ 1

G 1 / 2 "

G 1 / 2 "

G 1 / 4 "

G 1 / 4 "

Ø 12 mm

In ser t ed in v acuum gauge p o r t fo r 2 p i pe s y s t em ; to b e rem ov ed wit h a 3/ 1 6" All e n k e y fo r 1 p i pe s y s t em

5, 4 k g ( T A 2)

6 k g ( T A 4)

-

-

5,7 k

6, 4 k g g

(

(

T

T

A3

A5

)

)

N ozzl e pressure ra n ges 3 0 : 7 3 0 b ars

40 : 7 40 b ars

De liv er y pressure se ttin g 3 0 b ars

O pera tin g vi sc o s ity 4 4 5 0 cS t

Oil t empera t ure

Inl e t pressure

Re

Ra

S t t t ar ur ed n tin pressure speed g to r q ue

0 140°C ma x. in t he pump li gh t oil : 0 , 4 5 b ars ma x. v acuum to pre v e nt a i r separa tion f r o m oil hea vy oil : 5 b ars ma x.

li gh t oil : 5 b ars ma x.

hea vy oil : 5 b ars ma x.

36 00 rpm ma x.

0 ,3 N .

m

P ump capacity

Capac ity (L/ h)

1 5 00

1400

1 3 00

1200

1100

1000

9 00

T

T

A5

A4

2 85 0 rpm

8 00

7 00

6 00

5 00

400

T

T

A 3

A2

3 00

200

100

0

0 5

Vi sc o s ity =

10 1 5 20 2 5 3 0 35 40 P ressure

(b ars)

200 cS t

20 cS t

5 cS t Ra t ed speed = 2 85 0 rpm

Da t a sh own are fo r n e w pumps , wit h no a llow a n ce fo r w ear .

C hoice of heater

Car t r i dge

F ittin g

Ra tin g

Ø 12 mm acc o rd in g to D I N 404 3 0 , NFC 68 1 9 0 ( N° 9 e l ec .

)

8 0-100 W

26 www.ecoflam-burners.com

420010813300

APPENDIX

Electrical diagrams

X30

1

X31

1

X32 X33 X34

1

420010813300

WITH PROHIBITION OF USE AND REPRODUCTION GRAM THIS WIRING DIA TY OF VED THE PROPER WS WE RESER BY TERM LA

www.ecoflam-burners.com

27

EN

EN

APPENDIX

Electrical diagrams

UV CELL CELL

TION

28 www.ecoflam-burners.com

GRAM WITH PROHIBITION OF USE AND REPRODUC THIS WIRING DIA TY OF VED THE PROPER WS WE RESER BY TERM LA

420010813300

APPENDIX

Spare parts

EN

420010813300

BT3xx

L

C

M

1

00

www.ecoflam-burners.com

29

EN

APPENDIX

Spare parts list

1

2

3

4

8

9

10

11

12

13

14

15

DESCRIPTION

OIL PUMP

COIL

OIL VALVE

NIPPLE

5 HOSES

6 FILTER

7 COVER

GLASS

PEEP WINDOW FRAME

MOTOR

DISPLAY

CONTROL BOX

UV CELL

BOX

MOTOR THERMAL RELAY

16 REMOTE CONTROL SWITCH

17

18

19

20

26

27

28

29

30

31

32

33

34

35

36

37

ANTIJAMMING FILTER

MANOMETER

CABLE

ELECTRODES

21 IGNITION TRANSFORMER

22 SELECTOR

23 MAIN SELECTOR

24 FUSE SUPPORT

25 LAMP

RELAY BASE

RELAY

FAN

AIR CONVEYOR

COVER AIR INLET

AIR DAMPER MOTOR

ROD

NOZZLE HOLDER

DIFFUSER SUPPORT

DIFFUSER

BLAST TUBE

INNER ASSEMBLY

38 GASKET

39 AIR PRESSURE SWITCH

40 COUPLING

41 MOTOR PUMP

42 MOTOR THERMAL RELAY

43 REMOTE CONTROL SWITCH

44 SILENCER

45 ADJUSTMENT PRESSURE

46 CHECK VALVE

47 MODULE FOR PROBE

SUNTEC TA4C40106

LUCIFER 1/2 E321H25

LUCIFER 1/2 E321H25

TN 18X1200

TN 18X1500

70501/03

11 kW

15 kW

BCU LAMTEC

BT 330 667R13

FFS08-UV1 659D31

AEG 21-26A

AEG 24-32A

AEG LS18K.00

BF3800A230

CEWAL R1/4 D50-40 BA R

TC

TLX

Brahma T8 13000/35

ART.ECX1040

HK 520 04-1 10A

LYVIA 10x28 BA9S 240V

RED LED

360 x 135

380 x 135

STE4,5 Q3.51/6 3NM R W. PIN

TC

TLX

TC

TLX

TC

TL

65323137

-

65323170

65324105

65320944

740170016500

65325903

65323222

-

65325032

65324279

65324100

65325033

-

-

65321801

-

65324264

65324265

65311650

65325013

620190023000

65320716

65325053

65320784

65324815

840050301100

MAIOR P 500.1 PRE code

65322994

65323810

65323633

65323183

65323182

65324103

0FC09252-038

65320487

65320488

65326333

-

65326869

65325776

65312274

65325889

65324066

-

LGW10A2P

1,1 kW

AEG  3-4,7A

AEG LS05.10

ART. FZVR1

LCM100 LSB-M 667R0500-1

65321128

65323047

65325386

14100728

65323116

65323132

65074538

65324304

65325066

65311790

65325903

65323222

-

65325032

65324279

65324100

65325033

-

-

-

65321802

65324264

65324265

65311650

65325013

65320716

65325053

65320784

65324815

MAIOR P 600.1 PRE code

65322994

65323810

65323633

65323183

65323182

65324103

0FC09252-038

65320487

65320488

-

65325246

65326869

65325776

65312274

65325889

-

65323104

-

65323127

65323170

65324105

65320946

65321128

65323047

65325386

14100728

65323116

65323132

65074538

65324304

65325066

65311790

TC = SHORT HEAD TL = LONG HEAD

30 www.ecoflam-burners.com

420010813300

420010813300

www.ecoflam-burners.com

31

EN

Ecoflam Bruciatori S.p.A.

Via Roma, 64 - 31023 Resana (TV) - Italy

Tel. +39 0423 719500

Fax +39 0423 719580 http://www.ecoflam-burners.com

e-mail: [email protected]

Società soggetta alla direzione e al coordinamento di Ariston Thermo S.p.A.

Via A. Merloni, 45 - 60044 Fabriano (AN) - CF 01026940427

Ecoflam Bruciatori S.p.A. reserves the right to make any adjustments, without prior notice, which is considered necessary or useful to its products, without affecting their main features

Ecoflam Bruciatori S.p.A. si riserva il diritto di apportare ai prodotti le modifiche che riterrà necessarie o utili, senza pregiudicarne le caratteristiche principali.

La maison Ecoflam Bruciatori S.p.A. se réserve le droit d’apporter les modifications qu’elle jugera nécessaires ou utiles

à ses produits sans pour autant nuire à leurs caractéristiques principales

Ecoflam Bruciatori S.p.A. se reserva el derecho a introducir en sus productos todas las modificaciones que considere necesarias o utiles, sin prejudicar sus caracteristicas

“Ecoflam Bruciatori S.p.A.” оставляет за собой право вносить в конструкцию оборудования любые необходимые изменения без особого предупреждения

advertisement

Related manuals

Download PDF

advertisement