PCE PCE-ND10 Power Display Panel for System Integration Owner's Manual
Below you will find brief information for network parameter meter ND10. The ND10 meter is a digital programmable panel meter designed for measuring 3-phase, 4-wire power network parameters in balanced and unbalanced systems. It can display measured quantities and transmit them digitally. The meter is also capable of controlling and optimizing power electronic devices, systems, and industrial installations. It measures RMS values of voltage and current, active, reactive and apparent power, active and reactive energy, power parameters, frequency, 15-, 30-, and 60-minute mean active power, and THD. It also calculates current in the neutral wire from the phase current vectors. Voltage and current values are multiplied by given voltage and current ratios of measuring transformers. Power and energy indications account for all programmed ratio values. Measured values can be sent to the master via the RS-485 interface. Relay outputs signal alarm when selected parameters exceed set limits. Impulse output can be used for consumption checks of 3-phase real energy. This meter can also detect and signal incorrect phase sequence. The meter is powered by the measuring circuit, i.e. from the voltage output. There is galvanic separation between the voltage and current inputs, the RS-485 output, and the impulse output.
Advertisement
Advertisement
METER OF NETWORK
PARAMETERS
ND10 TYPE
USER’S MANUAL
1
Contents
1. ApplicAtion ................................................................... 5
2. meter Set ...................................................................... 6
3. BASic requirementS And operAtionAl SAfety ..................... 6
4. inStAllAtion .................................................................. 7
5. meter deScription ......................................................... 8
5.1 current inputs .............................................................. 8
5.2 Voltage inputs ............................................................. 8
5.3 connection diagrams ..................................................... 9
6. nd10 meter proGrAmminG .............................................. 12
6.1 front panel ................................................................ 12
6.2 power-on messages ..................................................... 13
6.3 parameter display ........................................................ 14
6.4 operating modes ......................................................... 17
6.5 parameter settings ....................................................... 18
6.5.1 Setting of meter parameters ......................................... 19
6.5.2 Setting of output parameters ......................................... 21
6.5.3 Setting of alarm parameters ......................................... 22
6.5.4 Setting date and time ................................................. 29
7. SoftWAre upGrAdeS ...................................................... 30
8. rS-485 interfAce ........................................................... 32
9. error codeS ................................................................. 46
10. technicAl dAtA ............................................................. 48
11. orderinG codeS ............................................................ 52
12. mAintenAnce And GuArAntee ........................................... 53
1. APPLICATION
The ND10 meter is a digital programmable panel meter destined for the measurement of the 3-phase, 4-wire power network parameters in balanced and unbalanced systems. It is also capable of displaying measured quantities and their simultaneous digital transmission. The meter is also capable of controlling and optimization of the power electronic devices, systems, and industrial installations. The meter can be used for measuring: RMS value of voltage and current; active, reactive and apparent power; active and reactive energy, power parameters; frequency, 15-, 30- and 60-minute mean active power and THD. Additionally, a current in the neutral wire is calculated from the phase current vectors . Voltage and current values are multiplied by given voltage and current ratios of measuring transformers. Power and energy indications take into account all programmed ratio values. Any and all measured values can be sent to the master via the RS-485 interface.
The relay outputs signal alarm when selected parameters exceed set limits. Impulse output can be used for consumption check of the 3-phase real energy. This meter is also able to detect and signal incorrect phase sequence.
The meter is powered by the measuring circuit, i.e. from the voltage output.
There is a galvanic separation between following units of the meter:
- voltage and current inputs,
- RS-485 output,
- impulse output.
2. MeTeR SeT
Complete set of the meter includes:
- ND10 Meter
- user’s manual
- warranty card
1 pcs.
1 pcs.
1 pcs.
- seal 1 pcs.
- panel mounting bracket 4 pcs.
3. BASIC RequIReMeNTS AND
OPeRATIONAL SAfeTy
In the safety service scope, the transducer meets to requirements of the eN 61010-1 standard.
•
•
•
•
•
Observations Concerning the Operational Safety:
The meter should be installed and connected only by a qualified personnel. All relevant safety measures should be observed during installation.
Always check the connections before turning the meter on.
Removal of the meter housing during the warranty period voids the warranty.
This meter conforms to all requirements of the electromagnetic compatibility in the industrial environment.
Building power network should include switch or automatic circuit breaker positioned in the convenient vicinity of the meter. It should be properly marked and available to operator at all times.
4. INSTALLATION
ND10 Meter is adapted to be mounted to the panel with mounting brackets (see fig. 1). Meter housing is made of plastic.
Housing dimensions: 96 x 96 x 77 mm. On the outer side of the meter there are screw and tab terminal strips that can be used for connecting external wires with diameter up to 2.5 mm 2 .
Prior to installation a 92.5
+0.6
x 92.5
+0.6
mm slot must be made in the panel. The thickness of the panel material should not exceed 15 mm. The meter must be placed in the panel from the front. During installation the powering voltage must be off.
When the panel is inserted in the slot, mount it in place with provided mounting brackets.
Fig. 1. Meter fitting.
96
22
Fig. 2. Meter dimensions.
5. MeTeR DeSCRIPTION
5.1. Current inputs
All current inputs are galvanically isolated (internal current transformers). The meter is suited to operate together with external measuring current transformers. Displayed values of currents as well as their derivative values are automatically calculated using set ratio value of the external transformer. Current inputs are specified in the order as either 1 A or 5 A.
5.2 Voltage inputs
Displayed values of voltages as well as their derivative values are automatically calculated using set ratio value of the external transformer. Voltage inputs are specified in the order as either
3 x 57,7/100 V, 3 x 230/400 V or 3 x 290/500 V.
5.3 Connection diagrams
OUT
Direct measurement in a 4-wire network
10
Semi-indirect measurement in a 4-wire network
OUTimp
Indirect measurement using
3 current transformers and 3 voltage
transformers in 4-wire network
OUT
Caution: It is recommended to connect ND10 meters (RS-485) to a computer with a shielded wire. A shield should be connected to ground in a single point. Shielded wire must be used in case there are many interferences in the environment.
Fig 3. Connection diagrams of the meter in the 4‑wire network.
11
6. ND10 MeTeR PROgRAMMINg
6.1 Front panel front panel description:
1 – cancel button (eSC)
2 – move left button
3 – decrease value button
4 – increase value button
5 – move right button
6 – confirm button (eNTeR)
7 – digital data transmission symbols
8 – connection / alarm symbols
9 – unit at displaying THD and power
guard
10 – THD value display symbols
11 – power coefficient and power
tangent display symbol
1
Fig. 4. Front panel.
12 – mean active power value
display symbol
13 – menu safety symbol
14 – units of the displayed values
15 – 3-phase values display
symbol
16 – base values ratios
17 – field for displaying base
values, power, THD, date,
mean values, frequency,
time and power guard
18 – min / max value symbols
19 – symbols of value-phase
connection
20 – power and energy characte-
ristics symbol
6.2 Power-on messages
After connection of voltage inputs the meter performs a display test and displays the ND10 meter name, build and current software version.
where: r n.nn is a number of the current software version or special build number.
b n.nn is a bootloader version number.
Fig. 5. Meter start messages
Caution! If the display shows Err Cal or Err EE message, please contact the maintenance service.
1
6.3 Parameter display
In the measurement mode, values are displayed according to set tables. Pressing button or allows user to switch between displayed base values (Table 1).
Pressing button button
displays minimal value and pressing
displays maximal value. When these values are displayed, pressing the or maximal values. When buttons
button resets all minimal
and are pressed simultaneously, respective mean 3-phase values are displayed, together with minimal and maximal values (see Table 2).
RS-485 interface allows setting the values that are to be displayed.
error display is described in section 8.
When reactive power is displayed, this indication is accompanied by a symbol of the load: capacity load ( ) or inductive load ( ).
Base values displayed in the field 17 (fig. 4.). Option (parameter) shown in the Table 1 indicated that displaying of this parameter may be turned off in register 4056 via RS485. Turning this parameter off (from u to tg) disables displaying their respective mean / 3-phase values.
1
Displayed symbols row 1 row 2
L
1
, V
L
2
L
3 u1 row 3
Display u2 u3 fixed
L
1-2
, V
L
2-3
L
3-1 u12 u23 u31 optional
L
1
, A
L
2
L
3
I1
I2
I3 fixed
L
1
, W
L
2
L
3
P1
P2
P3
L
1
, Var
L
2
L
3 q1 q2 q3
L
1
, VA
L
2
L
3
S1
S2
S3
Table 1
L
1
, Pf
L
2
L
3
Pf1
Pf2
Pf3 optional
L
1
, tg
L
2
L
3 tg1 tg2 tg3 kWh
Imported active energy
Displayed symbols row 1 row 2 row 3
Display
-, kWh exported active energy kVarh reactive inductive energy
/ reactive positive energy kVarh reactive capacitive energy
/ reactive negative energy
L
L
1
2
L
3
,
,THD u
THD u1 %
THD u2 %
THD u3 % optional
L
L
1
2
L
3
, THD I
,
THD I1 %
THD I2 %
THD I3 %
Displayed symbols row 1 row 2 row 3
Display
Hz f(L3) min max
3L, W PAVg
ΩP3-phase (15, 30 or 60 min.) min max
A
I(N) min max optional
% Date/Time
Ordered power consumption
(within 15, 30 or 60 min.) year
Month. day
Hours: minutes
Mean values and corresponding minimal and maximal values
(when pressed on the first 8 base value screens, following markers are highlighted: 3L, , ) .
1
Displayed symbols row
1 row
2 row
3
3L, V uLNav.
3-phase
3L, V 3L, A
Iav.
3-phase
3L, W
P min max
Table 2
3L, Var 3L, VA 3L, Pf 3L, tg q S Pf tg
When upper limit of the indication range is exceeded, it is indicated by two horizontal lines in upper part of the display.
Conversely, when lower limit is exceeded, it is indicated by two horizontal lines in the lower part of the display. When mean power is measured ΣP
3-phase
separate measurements are made for 15-second quantum. Depending on chosen value (15 min, 30 min, 60 min) calculated mean value is based on 60, 120 or 240 measurements. After the meter is turned on or after the power is reset, the first value will be calculated in 15 seconds after turning meter on or resetting. until all probed values of the active power are acquired, mean power value is calculated from values already measured. Current in the neutral wire I(N) is calculated from phase current vectors.
When alarms are activated, symbols A1 and/or A2 are displayed.
When alarms are deactivated and alarm signalization latch is turned on, flashing symbols A1 and/or A2 are displayed.
1
6.4 Operating modes
Fig. 6. ND10 meter operating modes.
1
6.5 Parameter setting
ND10 meters are configured with the use of LPCon software available for free on the www.lumel.com.pl web site.
Fig 7. Setup menu.
Programming mode is enabled by pressing and holding button for about 3 seconds. To enable the programming user bust enter a correct access code. If there is not such a code, the program transits into the programming option. Message SET
(in the first row) and first parameter group PAr are displayed. user can view parameters at any time by pressing and holding
button for about 3 seconds.
1
6.5.1 Setting of Meter Parameters
In options menu choose PAr (using buttons) and confirm selection with the
or
button.
Table 3
1
2
3
Access code entry
Current transformer
Voltage transformer ratio
SeC tr_I tr_u off,
1 … 60000
1 … 10000
0.1 … 4000.0
0 – no code 0
1
1
4
Mean active power synchronization
Syn
15, c_15, c_30, c_60
5
6
Recording minimal and maximal values complete with errors
Method of reactive energy calculation erLi en_q off, on cAP, sIgn
Mean active power synchronization:
15 - 15-minute moving window c_15 – measurement synchr. with clock every 15 min.
c_30 – measurement synchr. with clock every 30 min.
c_60 – measurement synchr. with clock every 60 min.
off – recording only correct values (within measurement range), on – recording all errors occurring in measurements
(values in 1e20 and -1e20 registers) cAP – inductive and capacity energy sIgn – positive and negative energy
15 on cAP
1
7
Display panel illumination diSP
8
Energy counters erasing
9
Mean active power erasing
10
Ordered power
11
Default settings
PA_0
PAor dEf oFF,1…60, on no, yES
0 … 144.0
no, yES off, on, 1..60 – illumination time (in seconds) from pressing the button no – no activity,
EnP – erase active energy,
Enq – erase reactive,
ALL – erase all energies yES – erase power on no no
Power ordered to establish power consumption in % of rated power
Reverting to default (factory) group settings
100 no
The automatic erasing of energy is carried out:
- for active energy when changing: voltage or current ratio;
- for reactive energy when changing: voltage or current ratio, reactive energy calculation method;
Buttons buttons
and
and
are used for setting the values while
are used for choosing position of the number to be set. The active position is signaled by the cursor. Set value can be accepted by pressing the or canceled by pressing the
button
button. When value is to be accepted, it is checked against the acceptable value range.
If the set value falls outside the allowable range, the meter remains in parameter setting mode and the value is set to the highest possible value (when entered value is too high) or lowest possible value (when it is too low).
0
6.5.2 Setting of Output Parameters
In Options choose the out mode and confirm your choice by pressing the button.
Table 4
1 Number of impulses
2 MODBuS Network Address
Io_n
Adr
5000 …
20000
1 … 247
Number of impulses per kWh
3 Transmission mode
4 Transmission speed tryb 8n2,
8e1,
8o1, 8n1 bAud 4.8 k,
9.6 k,
19.2 k,
38.4 k reverting to default
(factory) group settings
5 Default settings def no, yeS reverting to default
(factory) group settings
5000
1
8n2
9,6 k no
1
6.5.3 Setting alarm parameters
In Options choose ALr1 or ALr2 mode and confirm your selection by pressing the button.
Table 5
1 Value on alarm output (code as in Tab. 6)
2 Alarm type
A1_n,
A2_n
3 Lower value of the input range
4 upper value of the input range
5 Time delay of the switch reaction
A1_t,
A2_t
A1of,
A2of
A1on,
A2on
A1dt,
A2dt table 6 P n-on, n-off, fig. 8.
in % of the rated quantity value in % of the rated quantity value
0…900 in seconds (for A1_n =
P_ord, delay occurs only when alarm is activated) n-on
99.0
101.0
0
6 Alarm signalization latch
7 Alarm re-activation block
8 Default settings
A1_S,
A2_S, off, on
When alarm signalization latch is enabled and the alarm state ends, alarm symbol is not turned off but begins to flash. Alarm symbol flashes until it is turned off by pressing both and
buttons (for 3 seconds). This function refers only to the alarm signalization, so the relay connectors will operate without support according to the selected alarm type.
in seconds A1_b,
A2_b, def
0 …
900 no, yeS reverting to default
(factory) group settings
0 no
The write of the value ALon lower than ALof switches the alarm off.
Selection of the monitored value:
Table 6
00
01
Displayed element off u_1 no quantity /alarm disabled/
L1 phase voltage
Value needed for calculations of percentage outputs and alarm values none un [V] *
19
20
14
15
16
17
18
05
06
02
03
04
07
08
09
10
11
12
13 tg2 u_3
I_3
P_3 q_3
S_3
Pf3
I_1
P_1 q_1
S_1
Pf1 tg1 u_2
I_2
P_2 q_2
S_2
Pf2
L1 phase wire current
L1 phase active power
L1 phase reactive power
L1 phase apparent power
L1 phase active power factor tg j factor of L1 phase
L2 phase voltage
L2 phase wire current
L2 phase active power
L2 phase reactive power
L2 phase apparent power
L2 phase active power factor tg j factor of L2 phase
L3 phase voltage
L3 phase wire current
L3 phase active power
L3 phase reactive power
L3 phase apparent power
L3 phase active power factor
In [A] * un x In x cos(0°) [W] * un x In x sin(90°) [var] * un x In [VA] *
1
1 un [V] *
In [A] * un x In x cos(0°) [W] * un x In x sin(90°) [var] * un x In [VA] *
1
1 un [V] *
In [A] * un x In x cos(0°) [W] * un x In x sin(90°) [var] * un x In [VA] *
1
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36 tg3 u_A
I_A
P tg j factor of L3 phase mean 3-phase voltage mean 3-phase current
3-phase active power
(P1+P2+P3) q
S
3-phase reactive power
(q1+q2+q3)
3-phase apparent power (S1+S2+S3)
Pf_A 3-phase active power factor tg_A freq u12 tg j factor for 3 phases frequency u23 phase-to-phase voltage
L1-L2 phase-to-phase voltage
L2-L3 u31 phase-to-phase voltage
L3-L1 u4_A mean phase-to-phase voltage
P_At mean active power
P_ord used % of the ordered active power (used energy)
I_ne neutral wire current
*un, In – voltage and current rated values
1 un [V] *
In [A] *
3 x un x In x cos(0°)
[W] *
3 x un x In x sin(90°)
[var] *
3x un x In [VA]*
3
3
3
3
1
1
100 [Hz] un [V] * un [V] * un [V] * un [V] *
3 x un x In x cos(0°) [W]*
100 [%]
In [A] *
a) n-on b) n-oFF c) On d) OFF
Fig. 8. Alarm types (x – alarm no.): a),b) normal c) off d) on.
Remaining types of the alarm:
H-on – always on;
H-off – always off.
example 1 of alarm setting:
Set n-on alarm type for monitored quantity P – 3-phase active power,
Version: 5 A; 3 x 230/400 V. Setting the alarm on after exceeding
3800 W, switching the alarm off after power drops to 3100 W.
Calculations: rated 3-phase active power: P = 3 x 230 V x 5 A
= 3450 W
3450 W – 100 %
3800 W – A1on %
3450 W – 100 %
3100 W – A1of %
In conclusion: A1on = 110,0 % A1of = 90,0 %
Set: Monitored quantity: P; type of alarm: n-on, A1on 110,0,
A1of 90,0.
example no 2 of alarm setting:
The value of ordered power consumption may be used for the purpose of prior warning that ordered power might be exceeded. Ordered power consumption is calculated according to time period set for the mean active power synchronization and value of the ordered power. Pre-emptive alarm should be set so that it indicates the possibility of exceeding ordered power of 1MW at 90 % assuming allocation of 15-minutes
(900 s). Measuring current transformer 2500: 5A, voltage 230 V.
Peak max power consumption 1,5 MW.
Calculations:
ND10 meter active rated 3-phase power: P = 3 x k u
x u n
x k
I
x I n
= 3 x 1 x 230 V x 500 x 5A = 1,725 MW g 100 %.
Ordered-to-rated power ratio = 1 MW / 1.725 ≈ MW 57,97 % of meter rated value (rounded down) - Pord ;
Alarm operation hysteresis: alarm should be activated at 90 % ordered power ( A1on ), and deactivated for e.g.: at 1 % lower
89 % ( A1of ).
Optimization of power limit function (delay at alarm activation): alarm activation delay t o
= 10 % ∗
[ 1 MW ∗ 900 s
1,5 MW
]
= 60 s ( A1dt ).
1.5 MW
A1on=90.% A1of=89.9%
Time of delay A1dt= 0 sec fig. 9 shows an example of how the consumed ordered active power parameter can be used to alarm activation. Delay time is set at 0 seconds ( A1dt ).
In presented example for the remaining 10 % of ordered power at maximum power consumption, all devices could operate for additional
60 seconds without imposing penalties. If the delay time A1dt had been set to 60 seconds, alarm would not have been activated.
Fig. 9. Measurement of used ordered 15 minutes’ active
Set alarm as following: monitored quantity: A1_n = P_ord; alarm type: A1_t = n-on; A1on = 90,0, AL1of = 89,9; delay time A1dt
= 0 or 60 s; A1_s = 0; A1_b = 0. Parameters should be set as following: tr_I = 500; Syn = 15 or c_15, and Pord = 57.9.
6.5.4 Setting Date and Time
In Options choose dAtE mode and confirm the selection with
button. Seconds are reset to 0 after hour and minute values are set.
Table 7
Item
1
Parameter name
Hour, minute
Marking t_H
Range
Manufacturer’s value
00.00
2
3
Month, day year t_d t_y
0…23,
0..59
1…12,
1…31
2001 …
2100
1.01
2001
7. SOfTWARe uPgRADe
ND10 meter (with digital output) allows for firmware upgrade via PC with LPCon software installed. LPCon software is available as freeware on the www.lumel.com.pl web site. upgrade is possible if PC is connected to RS485 to uSB converter, such as PD10 converter. a) b)
Fig. 10. Program window view: a) LPCon, b) software upgrades
Important!
Software upgrade automatically reverts meter to its default (factory) settings, so it is recommended to save meter settings with LPCon software before upgrading.
After launching LPCon program, set in Options required serial port, speed, mode and address of the meter. Next, choose
ND10 meter from Devices menu and click the Read icon to read all set parameters (required for later recovery). After choosing
D evice software upgrade option from Upgrade menu a Lumel
Updater window appears( LU ) – fig. 10 b. Press Connect .
0
The Messages information window displays information concerning upgrade process. If the port is opened correctly, a Port opened message appears. upgrade mode may be entered using either of the two methods: remotely via LU (using LPCon settings: address, mode, speed, COM port) or by switching on a meter with a button pressed (while entering bootloader mode, upgrade button is used to set default communication settings of the meter). Meter display shows the „boot” message and the software version while the LU program displays Device found message along the name and version of the software of connected device. Click the ... button and browse to the meter upgrade file. If the file is opened correctly, a File opened message is displayed. Press the Send button.
When upgrade is successfully completed, meter reverts to the default settings and begins normal operation while the information window displays Done message and upgrade elapsed time.
After the LU window is closed, click the Save icon to save all initially read parameters. Current software version can be checked by reading Device information from LPCon software.
Important! Turning the meter off during upgrade process may result in permanent damage!
1
8. RS-485 INTeRfACe
•
•
•
•
•
•
Overview of the ND10 serial port parameters.
identifier meter address
0xCB
1..247
transmission speed 4.8, 9.6, 19.2, 38.4 kbit/s, operation mode Modbus RTu, transmission mode 8N2, 8e1, 8O1, 8N1,
• max. response time 750 ms.
max. no. of registers read
in a single query
- 40 4-byte registers,
- 80 2-byte registers,
• implemented functions - 03, 04, 06,16, 17,
- 03, 04 register read,
- 06 1st register write,
- 16 register write,
- 17 device identification.
Manufacturer’s settings: address 1, speed 9.6 kbit/s, mode RTu 8N2.
ND10 meter register map
ND10 meter has data contained in 16-bit and 32-bit registers. Process variables and meter parameters are placed in the address area of registers in a way depended on the variable value type. Bits in 16-bit registers are numbered from the youngest to the oldest (b0-b15). 32-bit registers include numbers of float type in Ieee-754 standard. Sequence of 3210 bytes
– the oldest is transmitted as the first.
Range of addresses
4000
– 4057
6000
– 6319
7000
– 7319
7500
– 7659
Type of value
Integer
(16 bits) float
(2x16 bits) float
(2x16 bits) float
(32 bits)
Table 8
Description
Value set in the 16-bit register.
Register description is presented in Table 9. Read and write registers.
Value is set in the two following 16-bit registers. These registers contain the same data as 32-bit registers from
7500 – 7659 range. Readout registers.
Bit sequence (1-0-3-2).
Value is set in the two following 16-bit registers. These registers contain the same data as 32-bit registers from
7500 – 7659 range. Readout registers.
Bit sequence (3-2-1-0).
Value set in the 32-bit register.
Register description is presented in
Table 10. Readout registers.
4005 RW
4010 RW
4011 RW
4012
4013
4014
Register address
4000
4001
4002
4003
4004
Operations
RW
RW
RW
RW
RW
4006
4007
4008
4009
RW
RW
RW
RW
RW
RW
RW
Range
0 … 60000
0...1200 [ o / oo
]
1 … 10000
1 … 40000
0...3
0.1
0.1
0 … 61
0..3
0.1
0.1
Description
Protection - password
Reserved
Mean ordered power *10 nominal signals
Current transformer ratio
Voltage transformer ratio *10
Mean active power synchronization:
0 - 15-minute moving window
1 – measurement synchr. with clock every 15 minutes,
2 – measurement synchr. with clock every 30 minutes,
3 – measurement synchr. with clock every 60 minutes
Reserved
Max and min value saving method: 0 – no errors,
1 – with errors
Reserved
Reactive energy calculation method:
0 – inductive and capacity energy
1 – positive and negative energy
Display panel illumination:
0 – off,
1-60 – illumination time in seconds from pressing the button;
61 – always on energy counters erasing
0 – no changes,
1 – erase active energies,
2 – erase reactive energies,
3 – erase all energies erasing of mean active power P
AV
Reserved erasing of min. and max.
Table 9
Default
0
1000
1
10
0
0
0
61
0
0
0
4015
4016
4017
4018
4019
4020
4021
4022
4023
4024
4025
4026
4027
4028
4029
4030
4031
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
0.1...35
0..5
-1440...0...1440
[ o / oo
]
-1440...0...1440
[ o / oo
]
0...900 s
0.1
0...900 s
0.1..35
0..5
-1440...0...1440
[ o / oo
]
-1440...0...1440
[ o / oo
]
0...900 s
0.1
0...900 s
5000 … 20000
1..247
0..3
quantity on the relay output of alarm 1 (code as in Table 6)
Output type 1: 0 – n-on, 1– n-off,
2 – on, 3 – off, 4 – H-on,
5 – H-off
Lower value of the alarm 1 switch of the rated input range upper value of the alarm 1 switch of the rated input range
Alarm 1 switch delay value
(for AL_n = P_ord – register 4015
= 35, delay occurs only at alarm activation)
Alarm 1 signalization latch
Alarm 1 re-activation block quantity on the relay output of alarm 2 (code as in Table 6)
Output type 1: 0 – n-on, 1– noff, 2 – on, 3 – off, 4 – H-on,
5 – H-off
Lower value of the alarm 2 switch of the rated input range upper value of the alarm 2 switch of the rated input range
Alarm 2 switch delay value (for AL_n
= P_ord – register 4015 = 35, delay occurs only at alarm activation)
Alarm 2 signalization latch
Alarm 2 re-activation block
No. of impulses for the impulse output
MODBuS Network Address
Transmission mode: 0->8n2,
1->8e1, 2->8o1, 3->8n1
24
0
990
1010
0
0
0
24
0
990
1010
0
0
0
5000
1
0
4032
4033
4034
4035
4036
RW
RW
RW
RW
RW
4037 RW
4042
4043
4044
4045
4046
4047
4048
4049
4050
4038
4039
4040
4041
4051
4052
RW
R
R
R
RW
RW
RW
RW
R
R
0...3
0.1
0 … 2359
101 … 1231
2009 … 2100
0.1
0..15258
0..65535
0..15258
0..65535
0..15258
0..65535
0..15258
0..65535
0..65535
0..65535
Transmission speed: 0->4800,
1->9600, 2->19200, 3->38400 upgrade change of transmission parameters
Hour *100 + minutes
Month * 100 + day year
Standard parameters save
(complete with reseting energy as well as min, max and mean power to 0)
Imported active energy, two older bytes
Imported active energy, two younger bytes exported active energy, two older bytes exported active energy, two younger bytes
Reactive inductive energy, two older bytes
Reactive inductive energy, two younger bytes
Reactive capacity energy, two older bytes
Reactive capacity energy, two younger bytes
Reserved
Reserved
Reserved
Reserved
Status Register – see description below
Status Register 2 – see description below
Reserved
1
0
0
101
2009
0
0
0
0
0
0
0
0
0
4053
4054
4055
4056
4057
R
R
R
RW
0..65535
0..65535
0..65535
0..65535
Serial number two older bytes
Serial number two younger bytes
Software version (*100)
-
-
quantity parameters displayed 0xffff
Reserved
Brackets [ ] contain, respectively: resolution or unit.
energy is made available in hundreds of watt-hours (var-hours) in double 16-bit register, and for this reason, one must divide them by 10 when calculating values of particular energy from registers, e.g.:
Imported active energy = (reg. value 4038 x 65536 + reg. value 4039) / 10 [kWh] exported active energy = (reg. value 4040 x 65536 + reg. value 4041) / 10 [kWh] exported inductive energy = (reg. value 4042 x 65536 + reg. value 4043) / 10 [kVarh] exported capacity energy = (reg. value 4044 x 65536
+ reg. value 4045) / 10 [kVarh]
Status Register (address 4050, R):
Bit 15 – „1” – damage of non-volatile memory
Bit 14 – „1” – lack of calibration or invalid calibration
Bit 13 – „1” – error of parameter values
Bit 12 – „1” – error of energy values
Bit 11 – „1” – error of phase sequence
Bit 10 – current range „0” – 1 A ~; „1” – 5 A ~
Bit 9
0
Bit 8 Voltage range:
0 57.8 V ~
0 1 230 V~
Bit 7 – „1” – the interval of power averaging has not elapsed
Bit 6 – „1” – frequency for THD calculation outside ranges:
- 48 – 52 for 50 Hz,
- 58 – 62 for 60 Hz
Bit 5 – „1” – too low voltage to measure the frequency
Bit 4 – „1” – L3 phase voltage too low
Bit 3 – „1” – L2 phase voltage too low
Bit 2 – „1” – L1 phase voltage too low
Bit 1 – „1” – RTC
Bit 0 – „1” – relay output state „1” – on, „0” - off
Status Register 2 – reactive power characteristics
(address 4051, R):
Bit 15...12 - reserved
Bit 11 – „1” – capacity 3L max,
Bit 10 – „1” – capacity 3L min.
Bit 9 – „1” – capacity 3L
Bit 8 – „1” – capacity L3 max.
Bit 7 – „1” – capacity L3 min.
Bit 6 – „1” – capacity L3
Bit 5 – „1” – capacity L2 max.
Bit 4 – „1” – capacity L2 min.
Bit 3 – „1” – capacity L2
Bit 2 – „1” – capacity L1 max.
Bit 1 – „1” – capacity L1 min.
Bit 0 – „1” – capacity L1
Configuration register of displayed base quantities parameters
(address 4056, R/W):
Bit 15 – „1” – date and time display
Bit 14 – „1” – usage of ordered power display
Bit 13 – „1” – neutral wire current display
Bit 12 – „1” – mean active power display
Bit 11 – „1” – frequency display
Bit 10 – „1” – current THD display
Bit 9 – „1” – voltage THD display
Bit 8 – „1” – reactive inductive energy display
Bit 7 – „1” – reactive capacitive energy display
Bit 6 – „1” – active exported energy display
Bit 5 – „1” – active imported energy display
Bit 4 – „1” – power tangent display
Bit 3 – „1” – power factor display
Bit 2 – „1” – apparent power display
Bit 1 – „1” – reactive power display
Bit 0 – „1” – phase-to-phase volage display
Address of 16 bit registers
Address of 32 bit registers
6000/7000 7500
6002/7002 7501
6004/7004 7502
6006/7006 7503
6008/7008 7504
6010/7010 7505
6012/7012 7506
6014/7014 7507
6016/7016 7508
6018/7018 7509
6020/7020 7510
6022/7022 7511
6024/7024 7512
6026/7026 7513
6028/7028 7514
6030/7030 7515
6032/7032 7516
6034/7034 7517
6036/7036 7518
6038/7038 7519
6040/7040 7520
6042/7042 7521
6044/7044 7522
6046/7046 7523
6048/7048 7524
Description
R L1 phase voltage
R L1 phase current
R L1 phase active power
R L1 phase reactive power
R L1 phase apparent power
R L1 phase power factor (Pf)
R L1 phase reactive to active power ratio
R L2 phase voltage
R L2 phase current
R L2 phase active power
R L2 phase reactive power
R L2 phase apparent power
R L2 phase power factor (Pf)
R L2 phase reactive to active power ratio
R L3 phase voltage
R L3 phase current
R L3 phase active power
R L3 phase reactive power
R L3 phase apparent power
R L3 phase power factor (Pf)
R L3 phase reactive to active power ratio
R Mean 3-phase voltage
R Mean 3-phase current
R 3-phase active power (P1+P2+P3)
R 3-phase reactive power (q1+q2+q3)
0
Table 10
V
A
W var
VA
-
-
V
A
W var
VA
-
-
V
A
W var
VA
-
-
V
A
W var
6050/7050 7525
6052/7052 7526
6054/7054 7527
6056/7056 7528
6058/7058 7529
6060/7060 7530
6062/7062 7531
6064/7064 7532
6066/7066 7533
6068/7068 7534
6070/7070 7535
6072/7072 7536
6074/7074 7537
6076/7076 7538
6078/7078 7539
6080/7080 7540
6082/7082 7541
6084/7084 7542
6086/7086 7543
6088/7088 7544
6090/7090 7545
6092/7092 7546
6094/7094 7547
6096/7096 7548
6098/7098 7549
6100/7100 7550
6102/7102 7551
R 3-phase apparent power (S1+S2+S3)
R Mean power factor (Pf)
R Mean reactive to active power ratio
R frequency
R Phase-to-phase voltage L1-L2
R Phase-to-phase voltage L2-L3
R Phase-to-phase voltage L3-L1
R Mean phase-to-phase voltage
R THD u1
R THD u2
R THD u3
R THD I1
R THD I2
R THD I3
R Cosine of u1 and I1 angle
R Cosine of u2 and I2 angle
R Cosine of u3 and I3 angle
R Mean 3-phase cosine
R Angle between u1 and I1
R Angle between u2 and I2
R Angle between u3 and I3
R vectors)
Active 3-phase input energy (no. of register
7549 overflows, resets to 0 after reaching
99999999.9 kWh)
VA
-
-
Hz
V
V
V
V
W
-
-
%
%
%
%
%
%
-
o o o
A
100
MWh
R
Active 3-phase output energy (no. of register 7551 overflows, resets to 0 after reaching 99999999,9 kWh) kWh
100
MWh kWh
1
6104/7104 7552 R
Reactive 3-phase inductive energy (no. of register 7553 overflows, resets to 0 after reaching 99999999,9 kVarh).
100
Mvarh
6106/7106 7553
6108/7108 7554 R
Reactive 3-phase capacity energy (no. of register 7555 overflows, resets to 0 after reaching 99999999,9 kVarh)
6110/7110 7555
6112/7112 7556
6114/7114 7557
6116/7116 7558
6118/7118 7559
6120/7120 7560
6122/7122 7561
6124/7124 7562
6126/7126 7563
6128/7128 7564
6130/7130 7565
6132/7132 7566
6134/7134 7567
6136/7136 7568
6138/7138 7569
6140/7140 7570
6142/7142 7571
6144/7144 7572
6146/7146 7573
6148/7148 7574
6150/7150 7575
6152/7152 7576
6154/7154 7577
R Reserved
R Reserved
R Reserved
R Reserved
R Time – hours, minutes
R Time – month, day
R Time - year
R usage of ordered power
R Voltage L1 min
R Voltage L1 max
R Voltage L2 min
R Voltage L2 max
R Voltage L3 min
R Voltage L3 max
R Current L1 min
R Current L1 max
R Current L2 min
R Current L2 max
R Current L3 min
R Current L3 max
R Active power L1 min
R Active power L1 max kvarh
100
Mvarh kvarh
A
A
A
A
W
W
-
-
-
%
V
V
V
V
V
V
A
A
6156/7156 7578
6158/7158 7579
6160/7160 7580
6162/7162 7581
6164/7164 7582
6166/7166 7583
6168/7168 7584
6170/7170 7585
6172/7172 7586
6174/7174 7587
6176/7176 7588
6178/7178 7589
6180/7180 7590
6182/7182 7591
6184/7184 7592
6186/7186 7593
6188/7188 7594
6190/7190 7595
6192/7192 7596
6192/7194 7697
6196/7196 7698
6198/7198 7699
6200/7200 7600
6202/7202 7601
6204/7204 7602
6206/7206 7603
6208/7208 7604
6210/7210 7605
6212/7212 7606
6214/7214 7607
6216/7216 7608
6218/7218 7609
6220/7220 7610
R Active power L2 min
R Active power L2 max
R Active power L3 min
R Active power L3 max
R Reactive power L1 min
R Reactive power L1 max
R Reactive power L2 min
R Reactive power L2 max
R Reactive power L3 min
R Reactive power L3 max
R Apparent power L1 min
R Apparent power L1 max
R Apparent power L2 min
R Apparent power L2 max
R Apparent power L3 min
R Apparent power L3 max
R Power factor (Pf) L1 min
R Power factor (Pf) L1 max
R Power factor (Pf) L2 min
R Power factor (Pf) L2 max
R Power factor (Pf) L3 min
R Power factor (Pf) L3 max
R Reactive to active power ratio L1 min
R Reactive to active power ratio L1 max
R Reactive to active power ratio L2 min
R Reactive to active power ratio L2 max
R Reactive to active power ratio L3 min
R Reactive to active power ratio L3 max
R Phase-to-phase voltage L1-2 min
R Phase-to-phase voltage L1-2 max
R Phase-to-phase voltage L2-3 min
R Phase-to-phase voltage L2-3 max
R Phase-to-phase voltage L3-1 min
-
-
-
-
-
V
V
V
V
V
-
-
-
-
-
-
VA
-
VA
VA
VA
VA
VA var var var var
W
W
W
W var var
6222/7222 7611
6224/7224 7612
6226/7226 7613
6228/7228 7614
6230/7230 7615
6232/7232 7616
6234/7234 7617
6236/7236 7618
6238/7238 7619
6240/7240 7620
6242/7242 7621
6244/7244 7622
6246/7246 7623
6248/7248 7624
6250/7250 7625
6252/7252 7626
6254/7254 7627
6256/7256 7628
6258/7258 7629
6260/7260 7630
6262/7262 7631
6264/7264 7632
6266/7266 7633
6268/7268 7634
6270/7270 7635
6272/7272 7636
6274/7274 7637
6276/7276 7638
6278/7278 7639
6280/7280 7640
6282/7282 7641
6284/7284 7642
6286/7286 7643
R Phase-to-phase voltage L3-1 max
R Mean 3-phase voltage (min)
R Mean 3-phase voltage (max)
R Mean 3-phase current (min)
R Mean 3-phase current (max)
R 3-phase active power (min)
R 3-phase active power (max)
R 3-phase reactive power (min)
R 3-phase reactive power (max)
R 3-phase apparent power (min)
R 3-phase apparent power (max)
R Power factor (Pf) min
R Power factor (Pf) max
R frequency min
R frequency max
R Mean phase-to-phase voltage (min.)
R Mean phase-to-phase voltage (max.)
R Active power, 3-phase, 15, 30, 60 minutes (min.)
R Active power, 3-phase, 15, 30, 60 minutes (max.)
R harmonic u1 / THD u1 min
R harmonic u1 / THD u1 max
R harmonic u2 / THD u2 min
R harmonic u2 / THD u2 max
R harmonic u3 / THD u3 min
R harmonic u3 / THD u3 max
R harmonic I1 / THD I1 min
R harmonic I1 / THD I1 max
R harmonic I2 / THD I2 min
R harmonic I2 / THD I2 max
R harmonic I3 / THD I3 min
R harmonic I3 / THD I3 max
VA
-
-
W var var
VA
V
V
V
A
A
W
-
-
Hz
Hz
V
V
W
W
V/%
V/%
V/%
V/%
V/%
V/%
A/%
A/%
A/%
A/%
A/%
A/%
6288/7288 7644
6290/7290 7645
6292/7292 7646
6294/7294 7647
6296/7296 7648
6298/7298 7649
6300/7300 7650
6302/7302 7651
6304/7304 7652
6306/7306 7653
6308/7308 7654
6310/7310 7655
6312/7312 7656
6314/7314 7657
6316/7316 7658
6318/7318 7659
R Cos of u1 and I1 angle (min.)
R Cos of u1 and I1 angle (max.)
R Cos of u2 and I2 angle (min.)
R Cos of u2 and I2 angle (max.)
R Cos of u3 and I3 angle (min.)
R Cos of u3 and I3 angle (max.)
R Mean 3-phase cos (min.)
R Mean 3-phase cos (max.)
R u1 and I1 angle (min.)
R u1 and I1 angle (max.)
R u2 and I2 angle (min.)
R u2 and I2 angle (max.)
R u3 and I3 angle (min.)
R u3 and I3 angle (max.)
R Neutral wire current (min.)
R Neutral wire current (max.)
-
-
-
-
-
-
-
o o o o o o
A
A
When lower limit is exceeded, a -1e20 value is displayed.
Conversely, when upper limit is exceeded, a 1e20 value is displayed.
9. eRROR CODeS
During the meter operation, error messages may be displayed. following list shows causes of particular errors.
- Err1 – too low voltage or current during measurement:
- Pf
- Pf
- THD
- f
- I
(N) i i
, tg j
, tg j i i
, cos, THD less than 10% un,
, cos less than 1% In,
less than 10% In,
less than 10% un,
less than 10% In;
- bAd Freq – during THD measurement, when frequency value is outside 48 – 52 Hz range for 50Hz and outside
58 – 62 Hz range for 60 Hz;
- Err bat – internal RTC battery. The measurement is carried out after switching the supply on and every day at midnight.
Then the message may be turned off by pressing the button. Then the message will be inactive until the meter is turned off and on again;
- Err CAL, Err EE – meter memory damaged. In such case meter should be sent back to the manufacturer.
- Err PAr – incorrect operational parameters of the meter.
In such case meter should be set to default (factory) settings (from menu or via RS-485 interface). Message can be disabled by pressing button.
- Err Enrg – incorrect energy parameters. Message can be disabled by pressing button. Incorrect energy values are set to 0.
- Err L3 L2 – phase sequence error. Switch phase 2 and phase 3 connections. Message may be disabled by pressing the button. Then the message will be inactive until the meter is turned off and on again;
-
- - - -
– lower limit exceeded. Measured value is lower that the lower measuring limit for a given quantity.
-
- - - -
– upper limit exceeded. Measured value is higher that the upper measuring limit for a given quantity or measurement error occurred.
10. TeCHNICAL DATA
Measuring Ranges and Admissible Basic Errors
Table 11
L1 L2 L3 S
Current In
1 A
5 A
Voltage L-N
57.7 V
230 V
Voltage L-L
100 V
400 V
0,00 ... 1.5 kA
0,00 ... 60 kA
0,0 ... 230.8 kV
0,0 ... 1.012 MV
0,0 ... 1.200 MV
0.0 ... 440 kV
0.0 ... 1.752 MV
0.0 ... 2.000 MV
0,005 ... 1,200
A~
0,025 ... 6.000
50 ... 64 V~
195 ... 253 V~
246 ... 300 V~
85 ... 110 V~
340 ... 440 V~
425 ... 520 V~ l l l l l l l l l
±0.2% rng
±0.2% m.q.
±0.5% m.q.
frequency 47.0 ... 63.0 Hz 47,0 ... 63.0 Hz l l l
±0.2% m.q.
Active power
Reactive power
Apparent power
Power factor Pf
Tangent j
Cosinus j j
Imported active energy exported active energy
Reactive inductive energy
Reactive capacitive energy
-9999 MW ...0,00
W
-9999 Mvar ...0,00 var ... 9999 Mvar
0,00 VA ... 9999
MVA
-1 ... 0 ... 1
-1.2 ... 0 ... 1.2
-1 ... 1
-180 ... 180
0 ...99 999 999.9 kWh
0 ...99 999 999.9 kWh
0...99 999 999,9 kVarh
0...99 999 999,9 kVarh
0...100%
-1,52 kW ...1,0
W ... 1,52 kW
-1,52 kvar ...1,0 var ... 1,52 kvar l l
1,0 VA ... 1,52 kVA l
-1 ... 0 ... 1
-1,2 ... 0 ... 1.2
l l
-1 ... 1
-180 ... 180 l l l l l l l l l l l l l l l l l l l l l l l l l l
±0.5% rng
±0.5% rng
±0.5% rng
±1% rng
±1% rng
±1% rng
±0.5% rng
±0.5% rng
±0.5% rng
±0.5% rng
±0.5% rng
THD 0...100% l l l
±5% rng
*Depending on the setting of tr_u (voltage transformer ratio: 0.1 ... 4000.0
and tr_I (current transformer ratio: 1 ... 10000) m.q. - error in relation to measured quantity rng - error relevant to range value
Caution! Correct measurement requires L3 phase voltage higher than 0.85 Un.
Power consumption:
- in L1 and L2 voltage circuit
- in L3 voltage circuit
- in current circuits
0.05 VA
3 VA
0.05 VA
Display
Relay outputs dedicated 3.5” LCD display,
2 relays, volt-free NO contacts current capacity 250 V~/ 0,5 A~ (a.c.)
Serial interface /optional/ RS485 : address 1..247
mode: 8N2, 8e1, 8O1,8N1 baud rate: 4.8, 9.6, 19.2, 38,4 kbit/s transmission protocol: Modbus RTu response time: 750 ms
Energy impulse output OC (NPN) output, class A passive, compliant with eN 62053-31; supply voltage 18...27 V, current 10...27mA
Pulsing constant of OC output 5000 - 20000 pulses/kWh independently of set tr_u, tr_I ratios
Protection grade of the casing from the front from behind the panel
IP 65
IP 20
Weight
Dimensions
0.3 kg
96 x 96 x 77 mm
Reference and rated operating conditions
- supply voltage /in L3 phase measurement circuit/:
50 .. 64 V a.c. or 195 .. 253 V a.c. or 246 .. 300 V a.c.
- input signal:
- power factor
47 ...63 Hz
0...0.005...1,2In for current;
0.85..1,1un for voltage;
0...0.01...1.2In; 0..0.85..1.1un; for factors Pfi ,tg j i frequency 47...63 Hz; sinusoidal ( THD 8% )
- ambient working temperature
- storage temperature
- humidity
-1...0...1
-20...23...+55
-30...+70 o C o C
25 ... 95 % (no condensation)
- max peak factor:
- current
- voltage
2
2
- external magnetic field 0...40...400 A/m
- short-term overload (5 s) voltage inputs 2 un current inputs 10 In
- working position
- warm-up time any
5 min.
Real time clock battery: CR2032
Additional errors: in % of the base error
- from input signal frequency
- from ambient temperature changes
- for THD > 8%
0
< 50%
< 50 % / 10
< 100 % o C
ND10 meter complies with following standards:
Electromagnetic compatibility:
- interference immunity acc. to eN 61000-6-2
- interference emission acc. to eN 61000-6-4
•
•
•
•
•
Safety requirements: acc. to eN 61010-1 circuit-to-circuit insulation: installation category pollution level basic,
III,
2, max working voltage in reference to ground:
- for power and measurement circuits:
- for remaining circuits: altitude a.s.l. < 2000 m.
300 V
50 V
1
11. ORDeRINg CODeS
Table 12
ND10 - X X X XX X X
Current input In:
1 A (X/1)
5 A (X/5)
1
2
Voltage input (phase/phase-to-phase) Un:
3 x 57.7/100 V
3 x 230/400 V
3x 290 / 500 V
Digital input: wihout RS485 interface with RS485 interface
Version: standard custom-made*
Language:
Polish english
1
2
3
0
1
00
XX
Table 12 other
Acceptance tests: without extra quality requirements with an extra quality inspection certificate acc. to customer’s requirements*
* after agreeing with the manufacturer
Example of Order:
The code: ND10 - 2 2 1 00 E 0 means:
P e
X
0
1
X
ND10 – meter of network parameters of ND10 type
2 – current input In: 5 A (X/5),
2 – input voltage (phase/phase-to-phase) un = 3 x 230/400 V,
0 – digital input - without RS485
00 – standard version,
E – language: english
0 – execution without extra quality requirements.
12. MAINTeNANCe AND guARANTee
The P43 transducer does not require any periodical maintenance.
In case of some incorrect operations:
After the dispatch date and in the period stated in the guarantee card:
One should return the instrument to the Manufacturer’s quality
Inspection Dept. If the instrument has been used in compliance with the instructions, we guarantee to repair it free of charge.
The disassembling of the housing causes the cancellation of the granted guarantee.
After the guarantee period:
One should turn over the instrument to repair it in a certified service workshop.
Our policy is one of continuous improvement and we reserve the right to make changes in design and specifications of any products as engineering advances or necessity requires and revise the above specifications without notice.
Advertisement
Key features
- Measures 3-phase, 4-wire power network parameters
- Displays measured quantities and transmits them digitally
- Capable of controlling and optimizing power electronic devices
- Measures RMS values of voltage and current
- Measures active, reactive, and apparent power
- Measures active and reactive energy
- Measures power parameters, frequency, and THD
- Detects and signals incorrect phase sequence
- Powered by the measuring circuit
- Galvanic separation between inputs, outputs, and impulse output