Advertisement
Advertisement
Actuator controls
AUMA MATIC
AM 01.1/ AM 02.1
AMExB 01.1/ AMExC 01.1
Modbus
Certificate Registration No.
12 100/104 4269
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Scope of these instructions:
Operation instructions
These instructions are valid for multi-turn actuators of type ranges
SA(R) 07.1 – SA(R) 16.1 and SA(R)ExC 07.1 – SA(R)ExC 16.1 and for part-turn actuators of type ranges SG(R) 05.1 – SG(R) 12.1 and SGExC
05.1 – SGExC 12.1 with the controls AUMA MATIC AM 01.1/ AM 02.1
or AMExB 01.1 and AMExC 01.1 and Modbus interface.
2
Table of contents
1.
Safety instructions
1.1
Range of application
1.2
1.3
1.4
Commissioning (electrical connection)
Maintenance
Warnings and notes
2.
Short description
3.
Transport and storage
4.4
4.5
4.6
4.7
4.
General information about Modbus
4.1
Basic characteristics
4.2
4.3
Modbus Basic functions
Transfer mode
Bus access
Communication
Protection functions
Modbus RTU mode
5.
Technical data
6.
Design AUMA MATIC Modbus
7.8
7.9
7.10
7.11
7.12
7.13
7.14
7.15
7.4
7.5
7.6
7.7
7.
Electrical connection
7.1
Power supply (standard)
7.2
7.3
Bus connection (standard)
Fitting the cover
Remote position transmitter
AUMA MATIC on wall bracket
Test run
Mains and bus connection for Ex-version with plug/ socket connector / terminal board (KP)
Mains and bus connection for Ex-version with plug-in terminal connection (KES)
Redundant bus connection
Bus cables
Setting the Modbus interface
Setting the communication parameter
Setting parameter seating mode in end position CLOSED, parity bits and number of stop bits
Setting the Modbus address:
Setting the baud rate
8.
Commissioning with controls
8.1
Introduction
8.2
8.3
Overview over the Modbus functions for data transmission
Modbus function and corresponding offset addresses of the AUMA MATIC
9.
Input data
9.1
Reading the actuator signals from the actuator using register functions
9.2
9.3
Description of the input data
Reading the feedback signals from the actuator using status functions
10.
Process representation output
10.1
Transmitting operation commands to or reading out from the actuator using register functions
10.2
10.3
Description of the output data
Transmission of operation commands to the actuator using coil functions
24
24
26
30
23
23
23
23
32
32
32
33
7
10
21
21
21
22
17
18
19
20
14
14
14
15
11
11
12
13
Page
4
4
4
4
4
4
5
6
6
6
6
6
6
5
5
Operation instructions
11.
Operation parameters of the actuator
12.
Description of actuator functions
12.1
Operation commands for OPEN/ CLOSE operation
12.2
12.3
Positioner
Stepping mode
13.
Failure function
14.
Description Modbus interface
14.1
14.1.1
14.1.2
Indication during system start-up:
Indications of operation LEDs 7 to 0
System displays LEDs L1 to L4
14.2
14.3
Customer inputs assignment of the Modbus interface (option)
Modbus connection assignment
14.4
14.5
Assignment positioner connections
Checking/ setting the switches on the logic board
15.
Troubleshooting and corrective actions
15.1
Actuator can not be controlled via Modbus
15.2
15.3
Position feedback does not function
Actuator is not switched off by the limit switch in direction CLOSE
15.4
15.5
15.6
Index
Actuator stops immediately after having started
Actuator does not signalise reference operation, connection failure position transmitter or signal interruption position transmitter
Measuring the Modbus signals using an oscilloscope
16.
Appendix A Standard wiring diagram
16.1
Legend for standard wiring diagram
16.2
Additional information to the wiring diagram legend
17.
Appendix B Proposed external wiring diagram
18.
Appendix C Literature references
19.
Appendix D Connecting the cable shield for AUMA MATIC AMExB/ AMExC 01.1
Addresses of AUMA offices and representatives
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Page
34
41
41
41
42
43
44
44
44
45
45
46
46
47
48
48
51
51
51
54
57
57
59
60
51
51
52
53
53
3
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
1.
Safety instructions
1.1
Range of application
Operation instructions
AUMA actuators are designed for the operation of industrial valves, e.g. globe valves, gate valves, butterfly valves and ball valves.
For other applications, please consult us. The manufacturer is not liable for any possible damage resulting from use in other than the designated applications. Such risk lies entirely with the user.
Observance of these operation instructions is considered as part of the controls’ designated use.
1.2
Commissioning
(electrical connection)
1.3
Maintenance
1.4
Warnings and notes
During electrical operation, certain parts inevitably carry lethal voltages.
Work on the electrical system or equipment must only be carried out by a skilled electrician himself or by specially instructed personnel under the control and supervision of such an electrician and in accordance with the applicable electrical engineering rules.
The maintenance instructions must be strictly observed, otherwise a safe operation of the multi-turn actuator/ the controls is no longer guaranteed.
Non-observance of the warnings and notes may lead to serious injuries or damage. Qualified personnel must be thoroughly familiar with all warnings and notes in these operation instructions.
Correct transport, proper storage, mounting and installation, as well as careful commissioning are essential to ensure a trouble-free and safe operation.
The following references draw special attention to safety-relevant procedures in these operation instructions. Each is marked by the appropriate pictograph.
This pictograph means: Note!
“Note” marks activities or procedures which have major influence on the correct operation. Non-observance of these notes may lead to consequential damage.
This pictograph means: Electrostatically endangered parts!
If this pictograph is attached to a printed circuit board, it contains parts which may be damaged or destroyed by electrostatic discharges. If the boards need to be touched during setting, measurement, or for exchange, it must be assured that immediately before a discharge through contact with an earthed metallic surface (e.g. the housing) has taken place.
This pictograph means: Warning!
“Warning” marks activities or procedures which, if not carried out correctly, can affect the safety of persons or material.
2.
Short description
AUMA actuators have a modular design. Motor and gearing are mounted in a common housing.
The actuators are driven by an electric motor and controlled with the electronic controls AUMA MATIC Modbus. The electronic controls are included in the scope of delivery.
4
Operation instructions
3.
Transport and storage
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
.
.
.
.
.
.
Transport to place of installation in sturdy packing.
Do not attach ropes or hooks to the handwheel for the purpose of lifting by hoist.
Store in well-ventilated, dry room.
Cover to protect against dust and dirt.
Apply suitable corrosion protection agent to bright surfaces.
Modbus
Protect against floor dampness by storage on a shelf or on a wooden pallet.
4.
General information about Modbus
For the exchange of information among automation systems and between automation systems and the connected decentral field devices, serial fieldbuses are mainly used today as the communication system. Thousands of applications have proved impressively that cost savings of up to 40 % in wiring, commissioning, and maintenance are achieved by using fieldbus technology. Just two wires are needed to transmit all relevant information for the field devices, such as input and output signals, parameters, and diagnostics data. While in the past the fieldbuses used were often manufacturer specific and incompatible with other bus systems, the systems employed today are almost exclusively open and standardized. This means that the user is independent of individual suppliers and can choose the best product at the most competitive price.
Modbus is an open international fieldbus system which is also used successfully throughout the world. The application range includes automation in the areas of manufacturing, processing, and building.
These operation instructions cannot provide a general introduction into
Modbus. For this, please refer to the literature references in appendix C
(page 57).
4.1
Basic characteristics Modbus defines the functional features of a serial fieldbus system with which distributed digital automation devices can be interconnected. Modbus distinguishes between master and slave devices.
Master devices control the data traffic on the Bus. A master is allowed to send messages without an external request.
Slave devices such as AUMA Modbus actuators are peripheral devices.
Typical slave devices are input/ output devices, valves, actuators, and measuring transmitters. They do not have bus access, i.e. they may only ,at the request of a master, transmit messages to that master.
5
6
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
4.2
Modbus Basic functions
4.3
Transfer mode
4.4
Bus access
4.5
Communication
4.6
Protection functions
Operation instructions
Modbus uses a master-slave technique in which only the master can initiate a transaction. The slaves respond by supplying the requested data in a reply or by executing the action requested in the query.
The Modbus telegram from the master contains the slave address, a function code defining the requested action, a data field, and a CRC field. The
Modbus slaves’ response message contains fields confirming the requested action and possibly the requested data and also a CRC field.
If an error occurs during reception of the telegram or the slave is unable to perform the requested action, the slave will generate an error telegram and
.
.
.
.
.
send it as response to the master.
RS-485 twisted pair cable or fibre optic cable.
AUMA actuators support baud rates up to 38.4 kBit/s
Master-slave technique.
Mono-master system.
Master and slave devices: max. 127 devices at one bus
(the AUMA MATIC supports slave addresses from 1 to 127), without
.
.
.
.
.
.
repeater max. 32 devices.
Master-slave data exchange via query-response cycle (Polling procedure).
Modbus RTU protocol.
Parity check for each telegram byte
CRC check for each telegram
Watchdog for AUMA actuators with adjustable failure behaviour.
Query-response cycle monitoring with configurable timer interval at the master.
4.7
Modbus RTU mode Data format for a byte.
.
.
.
.
.
.
Coding system:
8 bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8 bit field of the telegram
Bits per byte:
1 start bit
8 data bits; least significant bit sent first
1 bit for even/ odd parity, no bit for no parity
1 stop bit if parity is used, 2 stop bits if no parity is used.
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
5.
Technical data
Table 1: Modbus interface for actuator controls AM/ AMExB/ AMExC
Features and functions
Power supply Standard voltages:
3-phase AC voltages/ frequencies
1-phase AC 1) voltages/ frequencies
Volt 220 230 240 380 400 415 440 460 480 500 Volt 110,115,120 220,230,240
Hz 50 50 50 50 50 50 60 60 60 50 Hz 50/60 50/60
Special voltages:
3-phase AC voltages/ frequencies
Volt 525 575
Hz 50 50
660
50
690
50
1-phase AC 1) voltages/ frequencies
208
60
External supply of the electronics
(option)
Switchgear
Control and output signals
Modbus interface with additional inputs (option)
Local controls
24 V DC + 20 % / – 15 %,
Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Standard: Reversing contactors 2) (mechanically and electrically interlocked) for motor power up to 1.5 kW
Options: Reversing contactors 2) (mechanically and electrically interlocked) for motor power up to 7.5 kW
Thyristor unit 3) (recommended for modulating actuators) for motor power up to 1.5 kW, 500 V AC, with internal fuses for motor power up to 5.5 kW, 500 V AC, external fuses required via Modbus interface
Modbus interface with 4 free 24 V DC inputs and 2 free 0/4 – 20 mA inputs. Signal transmission vial fieldbus interface.
Standard: Selector switch LOCAL – OFF – REMOTE (lockable in all three positions)
Push buttons OPEN – STOP – CLOSE
3 indication light:
End position CLOSED (yellow), collective fault signal (red),
End position OPEN (green)
Option: Protection cover, lockable
Functions
Motor protection evaluation
Standard
Standard:
Switch-off mode, adjustable
Limit or torque seating for end position CLOSED
Overload protection against excessive torque over the whole travel
Phase failure monitoring with automatic phase correction
Push-to-run operation or self-retaining in LOCAL
Positioner 4) :
Nominal position value via Modbus interface
Adjustable behaviour on loss of signal
Adjustable sensitivity (dead band) and pause time
For AM: Monitoring of motor temperature in combination with thermoswitches in actuator motor
For AMExB/ AMExC: Monitoring of the motor temperature with PTC tripping device in combination with PTC thermistors in the actuator motor
Optionen: Additional thermal overload relay in the controls in combination with thermoswitches within the actuator
PTC tripping device in combination with PTC thermistors in the actuator motor
Electrical connection Standard: For AM: AUMA plug/ socket connector with screw type connection
For AMExB/ AMExC: Ex-plug/ socket connector with terminal board
For further options and threads for cable entries, please refer to separate technical data sheets
Special threads, other than standard mentioned above, possible
Control plug gold plated 3) (sockets and pins)
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed)
Overvoltage protection 3) (option) Protection of the actuator and controls electronics against overvoltages on the fildbus cables of up to 4 kV
Wiring diagram (basic version) MSP 1B1-00-7-F18E1 KMS TP102/001
1) AC current only with AM 01.1/ AM 02.1 and AMExC 01.1 in combination with actuator SGExC
2) The lifetime guaranteed by the manufacturer amounts to min. 2 million cycles. If a higher number of switching cycles is to be expected, thyristor units with virtually unlimited lifetime should be used
3) only in combination with AM 01.1 and AM 02.1
4) Requires position transmitter (potentiometer or RWG) in actuator
7
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Settings/ programming of the Modbus interface
Setting of the Modbus interface The setting of baud rate, parity, and Modbus address is realised via the AUMA MATIC
Modbus assembly
Commands and signals of the Modbus interface
Oricess representation output
(command signals)
OPEN, STOP CLOSE, nominal position value 4)
Process representation input
(feedback signals)
End position OPEN, CLOSED
Actual position value 4)
Selector switch in position LOCAL/ REMOTE
Running indication 4) (directional)
Torque switch OPEN, CLOSED
Limit switch OPEN, CLOSED
Manual operation by handwheel 4) or local controls
Process representation input
(fault signals)
Behaviour on loss of communication
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
The behaviour of the actuator is programmable:
- operation to end position OPEN or CLOSED
- operation to any intermediate position 4)
General Modbus data
Communication protocol
Network topology
Transmission medium
Modbus interface
Transmission speed/ cable length
Modbus RTU
Linear (BUS) structure. Active bus termination on both sides.
Coupling and uncoupling of devices during operation without affecting other devices is possible.
Twisted, shielded copper cable according to EN 50 170
EIA-485 (RS485)
Baud rate (kbit/s) Max. cable length (segment length) without repeater
300
600
1,200
2,400
4,800
9,600
19,200
38,400
1,200 m
1,200 m
1,200 m
1,200 m
1,200 m
1,200 m
1,200 m
1,200 m
Possible cable length with repeater (total network cable length) approx. 10 km approx. 10 km approx. 10 km approx. 10 km approx. 10 km approx. 10 km approx. 10 km approx. 10 km
Device types
Number of devices
Bus access
Supported Modbus functions
(services)
Modbus slave, e.g. devices with digital and/ or analogue inputs and outputs, such as actuators, sensors
32 devices within each segment without repeater, with repeater expandable up to 127 5)
Polling between master and slaves (query-response)
01
02
03
Read Coil Status
Read Input Status
Read Holding Registers
04
05
Read Input Registers
Force Single Coil
15 (0FHex) Force Multiple Coils
06 Preset Single Register
16 (10Hex) Preset Multiple Registers
07 Read Exception Status
17 (11Hex) Report Slave ID
08 Diagnostics:
00 00 Loopback
00 10 (0AHex)
00 11 (0BHex)
00 12 (0CHex)
Clear Counters and Diagnostic Register
Return Bus Message Count
Return Bus Communication Error Count
00 13 (0DHex)
00 14 (0EHex)
00 15 (0FHex)
Return Bus Exception Error Count
Return Slave Message Count
Return Slave No Response Count
4) Requires position transmitter (potentiometer or RWG) in actuator
5) The highest Modbus address which can be set at the AUMA MATIC is 127
8
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Service conditions
Enclosure protection according to EN 60 529
Corrosion protection
Finish coating
Colour
Ambient temperature
Vibration resistance 7) according to IEC 60 068-2-6
Weight
Accessories
Wall bracket 8)
Other information
EU Directives
Reference documents
Standard:
Options:
Standard:
Optionen:
IP 67 (when mounted)
IP 68 6)
DS 3) Terminal compartment additionally sealed against interior (double sealed)
KN Suitable for installation in industrial units, in water or power plants with a low pollutant concentration
KS Suitable for installation in occasionally or permanently aggressive atmosphere with a moderate pollutant concentration
(e.g. wastewater treatment plants, chemical industry)
KX Suitable for installation in extremely aggressive atmosphere with high humidity and high pollutant concentration
KX-G Same as KX, however aluminium-free version (outer parts)
Two-component iron-mica combination
Special primer/special finish coat (customer’s choice)
Silver-grey (DB 701, similar to RAL 9007)
Standard:
Option:
Standard:
Option:
AMExB
Standard:
Other colours than standard colour are possible on request
AM 01.1/ AM 02.1:
Standard:
Options:
– 25 °C to + 70 °C
– 40 °C to + 70 °C, low temperature version
– 50 °C to + 70 °C, extreme low temperature version, incl. heating system
– 60 °C to + 70 °C, extreme low temperature version, incl. heating system
– 20 °C to + 40 °C
AMExC:
Standard:
Options:
– 20 °C to + 40 °C
– 40 °C to + 40 °C, low temperature version
– 50 °C to + 40 °C, extreme low temperature version, incl. heating system
1 g, for 10 to 200 Hz
(only for actuator with controls. Not valid in combination with gearboxes) approx. 7 kg (with AUMA plug/ socket connector) approx. 12 kg (with Ex-plug/ socket connector with terminal board)
AUMA MATIC mounted separately from the actuator, including plug/ socket connector.
Connecting cables on request..
Recommended for high ambient temperatures, difficult access, or in case of heavy vibrations during service.
Electromagnetic Compatibility (EMC): (89/336/EEC)
Low Voltage Directive: (73/23/EEC)
Machinery Directive: (98/37/EC)
Product description “Actuator controls AUMA MATIC”
Dimension sheets “Multi-turn actuators/ part-turn actuators with integral controls AUMA
MATIC”
3) Only in combination with AM 01.1 and AM 02.1
6) For version in enclosure protection IP 68, a higher corrosion protection KS or KX is strongly recommended
7) Resistant to vibrations during start-up or for failures of the plant. However, a fatigue strength may not be derived from this
8) Cable length between actuator and AUMA MATIC max. 100 m. Not suitable for version with potentiometer in the actuator. Instead of the potentiometer, an RWG has to be used in the actuator.
9
10
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
6.
Design AUMA MATIC Modbus
The AUMA MATIC Modbus by AUMA represents the ideal controls for connecting multi-turn actuators of the SA range and part-turn actuators of the SG range to Modbus.
Figure A: AUMA MATIC Modbus
Modbus interface
Logic board
Local controls
Modbus connection board
Electrical connection with AUMA plug/ socket connector
Power supply unit
Switchgear
Signal and control board
Selector switch
Plug/ socket connector to actuator
The integral controls AUMA MATIC Modbus consist of the following
.
.
.
modules:
Modbus interface. The interface links the Modbus data with the internal electronics.
The logic board links the signals of the actuator with the local controls and the
Modbus interface and controls the reversing contactors or the thyristors.
Local controls with selector switch, push buttons, and indication lights.
The selector switch is used to select the control devices for the local
.
.
.
.
control LOCAL – 0 – REMOTE for remote control.
The push buttons (OPEN) – Stop – (CLOSE) are used for the electric operation of the actuator on site.
Plug/ socket connectors for easy mounting of the AUMA MATIC Modbus on the actuators.
Signal and control board with primary fuses, relays for conversion of the local control commands into electrical signals, and indication lights as an option.
Switchgear: Reversing contactors or thyristors for motor controls.
Modbus connection board with terminals for the Modbus cable and the termination resistor for bus termination.
Actuators which have already been installed can be retrofitted for Modbus by exchanging the controls AUMA MATIC for controls AUMA MATIC
Modbus.
Operation instructions
7.
Electrical connection
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
.
Work on the electrical system or equipment must only be carried out by a skilled electrician himself or by specially instructed personnel under the control and supervision of
.
such an electrician and in accordance with the applicable electrical engineering rules.
Installation regulations for Modbus must be observed for the wiring.
(For literature references, please refer to appendix C)
Make sure to respect electromagnetic compatibility (EMC) when installing cables:
.
.
.
.
Signal and bus cables are susceptible to interference.
Electric power cables are interference sources.
Lay cables being susceptible to inferference or sources of interference at the highest possible distance from each other.
The interference immunity of signal and bus cables increases if the cables are laid close to the ground potential.
Avoid long cables, if possible, or make sure that they are laid in locations with low susceptibility to interference.
Avoid long parallel paths with cables being either interference sources or susceptible to interference.
7.1
Power supply (standard)
Figure B-1: Connection
50.0
50.01
51.0
51.01
Figure B-2: Parking frame (accessory)
For explosion-proof version (type designation: AMExB/ AMExC), please
.
.
.
.
.
.
refer to page 15 or page 17.
Check whether type of current, supply voltage, and frequency comply with motor data (refer to name plate at motor).
Loosen bolts (50.01) (figure B-1) and remove connection housing.
Loosen screws (51.01) and remove socket carrier (51.0) from plug cover
(50.0).
Insert cable glands suitable for connecting cables.
(The enclosure protection stated on the name plate is only ensured if suitable cable glands are used).
Seal cable entries which are not used with suitable plugs.
Connect cables according to order-related wiring diagram.
The wiring diagram applicable to the actuator is attached to the handwheel in a weather-proof bag, together with the operation instructions. In case the wiring diagram is not available, it can be obtained from
AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com).
A special parking frame (figure B-2) for protection against touching the bare contacts and against environmental influences, in case the electrical connection has been removed, is available.
Parking frame
Table 2: Technical data AUMA plug/ socket connector for bus connection
Technical data
No. of contacts max.
Motor power connections 1) Protective earth
6 (3 are used) 1 (leading contact)
Marking
Connecting voltage max.
Nominal current max.
Type of customer connection
Cross section max.
Material: Pin/ socket carrier
Contacts
U1, V1, W1, U2, V2, W2
750 V
25 A
Screws
6 mm 2
Polyamide
Brass (Ms)
–
–
Screw for ring lug
6 mm 2
Polyamide
Brass (Ms)
1)Suitable for copper wires. For aluminium wires, please contact AUMA
Control terminals
50 pins / sockets
1 to 50
250 V
16 A
Screws
2.5 mm 2
Polyamide
Brass, tin plated or gold plated (option)
11
12
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
7.2
Bus connection (standard)
Operation instructions
For explosion-proof version (type designation: AMExB/ AMExC), please refer to page 15 or page 17.
For version with FO (fibre optics), refer to separate operation instructions
.
“AUMA MATIC AM 01.1/ AM 02.1 FO connection”.
Connect bus cable. Refer to figures C-1 and C-4.
The termination resistors for channel 1 and channel 2 are switched in via switches (S1) and (S2). Both switches are supplied in position ‘OFF’.
Only switch on the termination resistors (position ‘ON’) if the actuator is the final device in the Modbus segment.
Table 3: Switch positions of S1 and S2
S1
S2
ON
OFF
ON
OFF
Bus termination channel 1 ON
Bus termination channel 1 OFF
Bus termination channel 2 ON (option)
Bus termination channel 2 OFF (option)
Figure C-1: Connection board (standard)
S1
Bus termination channel 1
Connection channel 1
Screening
S2
Bus termination channel 2
(ption)
Connection channel 2
(redundant)
Screening
Figure C-2: Connection (standard)
X1
5V P/B N/A P/B N/A GND
B A B A from previous / to next
Modbus device channel 1
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Figure C-3: Connection board (for overvoltage protection)
S1
Bus termination channel 1
S2
Bus termination channel 2
7.3
Fitting the cover
Figure C-4: Connection for overvoltage protection
X1
1 2 3 4 from previous / to next
Modbus device channel 1
Table 4: Assignment of Modbus cable
Modbus cable
A
B
AUMA labelling at the connection
N/A
P/B
.
.
.
.
.
.
After connection:
Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with screws (51.01).
Clean sealing faces at the plug cover and the housing.
Check whether O-ring is in good condition.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.
Fasten cable glands with the specified torque to ensure the required enclosure protection.
13
14
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
7.4
Remote position transmitter For the connection of remote position transmitters (potentiometer, RWG) screened cables must be used.
7.5
AUMA MATIC on wall bracket The AUMA MATIC can also be mounted separately from the actuator on a
Figure C-5: AM on wall bracket
.
wall bracket.
For the connection of actuator and AUMA MATIC on wall bracket, use suitable flexible and screened connecting cables.
.
.
.
(Preconfectioned cables can be obtained from AUMA on request)
Permissible cable distance between actuator and AUMA MATIC amounts to a max. of 100 m.
Versions with potentiometer in the actuator are not suitable. Instead of the potentiometer, an RWG has to be used in the actuator.
Connect the wires in correct phase sequence.
Check direction of rotation before switching on.
Connecting cable to actuator
The plug connection on the wall bracket is made as crimp version.
Use a suitable four indent crimp tool for crimping.
Cross sections for flexible wires:
Control cables: max. 0.75 to 1.5 mm²
Power supply: max. 2.5 to 4 mm²
The connector at the actuator is equipped with screw type connections.
Wire end sleeves have to be used.
7.6
Test run Perform test run. Please refer to the operation instructions pertaining to the actuator (multi-turn actuator SA(R) ... / part-turn actuator SG ...).
Check limit and torque switching:
Check limit and torque switching, electronic position transmitter RWG or potentiometer (option) and re-set where appropriate.
The settings are described in the operation instructions pertaining to the actuator (multi-turn actuator SA(R) ... part-turn actuator SG ... ).
For actuators with feedback signal (RWG, potentiometer), a reference oper-
.
.
ation has to be performed after having changed the setting.
Perform reference operation:
Operate actuator electrically (via the push buttons OPEN and CLOSE of the local controls) once to the end position OPEN and once to the end position CLOSED.
If no reference operation is performed after changing the limit switching, the feedback signal via the bus is not correct. The bus signals the missing reference operation as warning (see page 28).
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
7.7
Mains and bus connection for Ex-version with plug/ socket connector / terminal board (KP)
When working in potentially explosive areas, observe the
European Standards EN 60079-14 “Electrical installations in hazardous areas” and EN 60079-17 “Inspection and maintenance of electrical installations in hazardous areas”.
Figure D-1: Connection
50.0
50.01
For the Ex-plug/ socket connector (figure D-1), the electrical mains connection is made after removing the plug cover (50.0) at the EEx e terminals of the terminal board (51.0). The flameproof compartment (type of protection
.
.
EEx d) remains hereby closed.
Check whether type of current, supply voltage, and frequency correspond to motor data (refer to name plate at motor).
Loosen bolts (50.01) (figure D-1) and remove plug cover.
.
Insert cable glands with “EEx e” approval and of size suitable for connecting cables. For the recommended cable
51.0
glands refer to appendix D, page 57.
Figure D-2: Disconnection from the mains
50.0
51.0
51.02
.
.
(The enclosure protection stated on the name plate is only ensured if suitable cable glands are used).
Seal cable entries which are not used with suitable plugs.
No more than max. 2 wires with the same cross section may be connected to one terminal.
.
.
.
.
Remove cable sheathing in a length of 120 – 140 mm.
Strip wires: Controls max. 8 mm, motor max. 12 mm.
For stranded wires use end-sleeves according to DIN 46228.
Connect bus cable. Refer to figure (D-3).
The termination resistor for channel 1 is connected through linking the terminals 1 – 4 and 3 – 2 (standard).
Only connect the termination resistor if the actuator is the final device in the Modbus segment.
Connect screen largely to the cable glands. For the recommended cable glands refer to appendix D, page 57.
If the actuator must be taken from the valve, e.g. for service purposes, it can be separated from the mains without having to remove the wiring
(figure D-2). For this purpose, the screws (51.02) are removed and the plug/ socket connector is pulled off. Plug cover (50.0) and terminal board (51.0) remain together.
Flameproof enclosure! Before opening, ensure that no explosive gas and no voltage is present.
A special parking frame (figure D-2) for protection against touching the bare contacts and against environmental influences is available.
15
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Figure D-3: Bus connection for channel 1 (standard)
Another bus device follows the actuator
Operation instructions from previous
Modbus device channel 1
Actuator is final bus device to next
Modbus device channel 1
Table 5: Technical data Ex plug/ socket connector with terminal board for explosion-proof actuators
Technical data
No. of contacts max.
Marking
Connecting voltage max.
Nominal current max.
Motor power connections
3
U1, V1, W1
550 V
25 A
Type of customer connection Screws
Cross section max.
6 mm 2
1) Protective earth
1 (leading contact)
–
–
Screws
6 mm 2
Material: Pin/ socket carrier
Contacts
Araldite/ Polyamide
Brass (Ms)
Araldite/ Polyamide
Brass (Ms)
1)Suitable for copper wires. For aluminium wires, please contact AUMA
Control terminals
38 pins/ sockets
1 to 24, 31 to 50
250 V
10 A
Screws
1.5 mm 2
Araldite/ Polyamide
Brass (Ms) tin-plated
16
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
7.8
Mains and bus connection for Ex-version with plug-in terminal connection (KES)
When working in potentially explosive areas, observe the
European Standards EN 60079-14 “Electrical installations in hazardous areas” and EN 60079-17 “Inspection and maintenance of electrical installations in hazardous areas”.
Figure E-1: Plug-in terminal connection
Terminal cover
Terminals
Terminal board
The bus connection is realised via terminals (figure E-1) The terminal compartment is designed for explosion protection “EEx e” (increased
.
safety). The controls AUMA MATIC (type of protection EEx d) remain closed.
Loosen bolts (1) (figure E-1) and remove terminal cover.
.
Insert cable glands with “EEx e” approval and of size suitable for connecting cables. For the recommended cable glands refer to appendix D, page 57.
.
(The enclosure protection stated on the name plate is only ensured if suitable cable glands are used).
Seal cable entries which are not used with suitable plugs.
Cross sections for connection:
Control cables:
Motor connection: max.
2.5 mm 2 max. 10 mm 2 ,
.
.
Suitable bus cables, see page 19.
Connect bus cable to channel 1 according to configuration of the terminals (figure E-2).
The termination resistor for channel 1 is connected through linking the terminals 1 – 2 and 3 – 4.
Only connect the termination resistors if the actuator is the final device in the Modbus segment.
Figure E-2: Terminal configuration for Ex connection (KES)
Another bus device follows the actuator
Previous
Modbus device
Next
Modbus device
Actuator is last bus device
Previous
Modbus device
17
18
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
7.9
Redundant bus connection
Operation instructions
AUMA Modbus devices can be connected with a second (redundant)
Modbus cable. If the bus on channel 1 fails, e. g. through cable break, the slave automatically switches to channel 2 after a waiting time.
Thus, the change-over is realised with a time delay (see parameter 5
“Time for channel changing in 0.1s”, page 35).
Additionally, the communication cannot be carried out on both channels simultaneously.
If the redundancy is activated (see parameter 4 “Redundancy”, page 34), the AUMA MATIC transmits its data using both channels but receives the data only using the active channel.
This cable redundancy may only be applied after previous integration test using the desired process control system!
.
.
For versions with AUMA plug/ socket connector (subclause 7.2):
Connect redundant bus cable to channel 2 in the same way as channel 1
(figure C-2).
For Ex-version with plug/ socket connector / terminal board (KP)
(subclause 7.7):
Connect cable B to terminal 6, cable A to terminal 7.
.
The termination resistor for channel 2 is connected through linking the terminals 5 – 6 and 7 – 8.
For Ex-version with plug-in terminal connection (KES)
(subclause 7.8):
Connect cable B to terminal 6, cable A to terminal 7 (figure E-2).
The termination resistor for channel 2 is connected through linking the terminals 5 – 6 and 7 – 8.
The setting of the redundant bus connection is realised via the parameters
4 and 5 (refert to pages 34, 35).
Operation instructions
7.10 Bus cables
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Only cables according to the recommendations of EIA 485 standard may be used for Modbus wiring.
A maximum of up to 32 Modbus devices may be connected in one segment.
If more stations are to be connected to one Modbus network, several segments must be connected with repeaters.
The bus cable must be laid at a distance of at least 20 cm from other cables.
It should be laid in a separate, conductive, and earthed cable trunking.
It must be ensured that there are no potential differences between the individual devices on the Modbus (perform a potential compensation).
The max. cable length without repeater amounts to 1,200 m (independent of the baud rate).
Cable recommendation for Modbus
Characteristic impedance:
Cable capacity:
Core diameter
Core cross section:
Loop resistance:
Screening:
35 to 165 Ohm, at a measurement frequency of 3 to 20 MHz.
< 30 pF per metre
> 0.64 mm
> 0.34 mm², corresponds to AWG 22
< 110 Ohm per km copper shielding braid or shielding braid and shielding foil
Figure F: Example: Modbus with one secment
Controls (master)
Bus termination switched on
2-wire cable
Modbus board Bus termination switched on
Connection board
AUMA MATIC
Modbus
19
20
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
7.11 Setting the Modbus interface
Operation instructions
A correct communication is only possible if the settings of the baud rate, the parity, and the stop bits agree with the master settings.
.
The settings are realised on the Modbus interface board.
Loosen screws and remove cover (figure G-1)
Figure G-1
Screws
Modbus interface board
Figure G-2: Modbus interface board
LEDs: 7 6 5 4 3 2 1 0 green LED illuminated
ADDRESS MODE ON
L1 L2 L3 L4
Push buttons:
T1 RESET
T2 MODIFY
T3 CHANGE MODE
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
7.12 Setting the communication parameters
Push buttons:
T1 RESET
T2 MODIFY
T3 CHANGE MODE:
DEFAULT MODE: for status indication and basic programming,
ADDRESS MODE for address setting
BAUD RATE MODE for baud rate selection
Push button 3 (CHANGE MODE) is used to switch between the following modes:
1) DEFAULT MODE is characterised by LED 7 (green) being switched off.
Display and modification of type of seating in end position CLOSED, parity bits and stop bits as well as display of DataExchange, status,
BusActivity, and LocalError.
2) ADDRESS MODE is characterised by LED 7 (green) being illuminated.
The address is adjustable.
3) BAUD RATE MODE is characterised by the blinking of LED 7 (green).The baud rate is adjustable.If no push buttons are pressed for 30 seconds, the display will revert to DEFAULT MODE .
The push button MODIFY allows incrementation of the figure shown in the
LED row. The new value is immediately accepted in the DEFAULT MODE .
For ADDRESS MODE and BAUD RATE MODE , the value is only accepted when leaving these modes.
7.13 Setting parameter seating mode in end position CLOSED, parity bits and number of stop bits
When not pressing push button CHANGE MODE , you are in the DEFAULT
MODE (LED 7 is not illuminated). LED 0, LED 1, and LED 2 show the value of the three mentioned parameters:
LED
0
1
2
Parameter LED on LED off seating mode in end position CLOSED torque seating limit seating
Parity setting No Parity Even Parity
Number of stop bits 2 stop bits 1 stop bit
Push button S3 “ MODIFY ” is used to set these parameters. If, for example, type of seating in end position CLOSED = torque seating, parity setting = even parity, and number of stop bits = 1 stop bit is to be selected, the combination 001 must be illuminated for the first 3 LEDs. The push button
“ MODIFY ” is operated until this combination appears. The parameter values become immediately valid.
7.14 Setting the Modbus address The Modbus address is set using push buttons T2 and T3. This is done according to the following sequence:
(a) Press push button T1 CHANGE MODE (hold down for 1 to 2 seconds):
The green LED 7 ADRESS MODE is illuminated (not blinking); it indicates the programming mode for the Modbus address.
The actually set Modbus address is displayed as binary coding by LEDs
6 to 0 (1 to 127).
(b) Set desired bus address using push button T2 MODIFY :
(Factory setting: slave address 2)
(c) Each pressing of the push button increments the address value by one.
Address 1 will follow after address 127. If push button T2 MODIFY is held down (approx. 1/3 s), the incrementation is done automatically.
21
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
(d) After setting the required Modbus address, quit the programming mode by pressing key T3 CHANGE MODE . The newly set address now becomes valid.
Pressing the key T3 results in changing to BAUD RATE MODE ; renewed pressing of key 3 results in reverting to DEFAULT MODE .
(e) Alternatively to clause d), pressing the push button T3 may be ommitted.
After 30 s the status address mode is automatically quit and the
DEFAULT MODE is indicated. The set address is thus accepted.
7.15 Setting the baud rate
The baud rate is selected with the push buttons T2 and T3. This is done according to the following sequence:
(a) Press push button T3 CHANGE MODE (hold down for 1 to 2 seconds):
The green LED 7 is illuminated (not blinking): the ADDRESS MODE is active.
(b) Press push button T3 CHANGE MODE again (hold down for 1 to 2 seconds): The green LED 7 is blinking: now, the BAUD RATE MODE is active.
(c) Select the desired Modbus baud rate pressing push button T2 MODIFY .
(d) The baud rate setting changes each time, push button T2 is pressed.
After the setting 56,400 bit/s (1001), the setting 110 Bit/s (0000) follows again. If push button T2 MODIFY is held down (approx. 1/3 s), the incrementation is done automatically. Only the first 4 LEDs count as only
10 baud rate settings are possible.
6
7
4
5
8
2
3
0
1
9
Setting
LED 3 LED 2 LED 1 LED 0
0
0
0
0
1
0
0
0
0
0
0
0
0
1
1
1
1
0
0
0
1
1
0
0
1
1
0
0
1
0
1
0
1
0
1
0
Baud rate bit/s
110
300
600
1200
2400
4800
9600
19200
38400
1 0 0 1
56400
Notes
Default setting
Baud rate deviation
– 2.5 % !
Baud rate deviation – 5 %
( not recommended)
(e) After setting the required Modbus baud rate, close the programming mode by pressing push button T3. The newly set baud rate becomes valid and the interface is in DEFAULT MODE .
(f) Alternatively to clause e), pressing the push button T3 CHANGE MODE may be omitted. After 30 s, the BAUD RATE MODE status is automatically quit and the DEFAULT MODE is indicated. The set baud rate is thus accepted.
22
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
8.
Commissioning with controls
8.1
Introduction To commission a Modbus slave, a special configuration of the master using a configuration file is usually not required.
The Modbus RTU transmission is based on a simple protocol containing the slave address, a function code with offset address, the process data, and a checksum.
8.2
Overview of the Modbus functions for data transmission
Description Function
Force Single Coil
Force Multiple Coils
Read Coil Status
Read Input Status
Preset Single Register
Preset Multiple Register
Read Input Register
Read Holding Register
Function code
(decimal)
05
15
01
02
06
16
04
03
Sets one single bit to ON or OFF within slave
Sets several subsequent bits to ON or OFF within slave
Reads the status of individual pieces of output bit information out of the slave.
Reads the status of individual pieces of input bit information out of the slave
Writs data into one single holding register (16 bit) of slave
Writes data into subsequent holding registers
Reads the content of input data register (16 bit) out of the slave
Reads the content of holding registers out of the slave
8.3
Modbus function and corresponding offset addresses of the AUMA MATIC
Action
Write or read process representation output data
(master outputs)
Read process representation input data (master inputs
Write or read parameters of
AUMA MATIC
Permissible function function code (decimal)
Force Single Coil (05)
Force Multiple Coils (15)
Read Coil Status (01)
Preset Single Register (06)
Preset Multiple Register (16)
Read Holding Register (03)
Read Input Status (02)
Read Input Register (04)
Preset Single Register (06)
Preset Multiple Register (16)
Read Holding Register (03)
Permissible offset addresses (decimal)
0 to 2
4096 to 4098
8192 to 8239
12288 to 12296
16384 to 16433
Permissible offset addresses (hexadecimal)
0x0000 to 0x0002
0x1000 to 0x1002
0x2000 to 0x202F
0x3000 to 0x3008
0x4000 to 0x4031
23
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
9.
Input data
9.1
Reading the actuator signals from the actuator using register functions
Functions to be used:
Read Input Register (04)
Grey bits are collective signals. They contain the results of a disjunction (OR operation) of other information.
Offset
(hexadecimal)
0x3000
Offset
(decimal)
12288
Register contents
(For the description, refer to chapter 9.2)
Register 1: Locigal signalsMeldungen
0x3001 12289
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Register 2: Actuator signals
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
0x3002
0x3003
12290
12291
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Register 3: E2 Actual position
Register 4: Fault signals
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
24
0x3004 12292
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Register 5: Warning signals
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Operation instructions
Offset
(hexadecimal)
0x3005
Offset
(decimal)
12293
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Register contents
(For the description, refer to chapter 9.2)
Register 6: Physical operation
0x3006 12294
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Register 7: Options
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
0x3007
0x3008
12295
12296
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Register 8: First analogue input (wiring diagram designation: analogue 2)
Register 9: Second analogue input (wiring diagram designation: analogue 3/4)
To ensure that the actuator gives a correct end position signal after power failure in end position CLOSED/ OPEN, we recommend to evaluate the information LSC (WSR)/
LSO (WOEL) (bit 5/4 in register 2) for the end position signal
CLOSED/ OPEN.
25
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
9.2
Description of the input data
Register 1: Logical signals
Important signals from the actuator concerning errors, warnings, operations:
Operation instructions
Bit Designation Value Description
0
OPEN position
Limit seating in end position OPEN
1
0
Limit switch in direction OPEN operated.
other
CLOSED position
Limit seating in end position CLOSED
1
0
Limit switch in direction CLOSE operated.
other
1
CLOSED position
Torque seating in end position
CLOSED
1
0
Torque switch and limit switch in direction CLOSE operated.
other
2
Setpoint reached
1
The setpoint is within max. error variable (outer dead band). Signal occurs only if Modbus master has set the Setpoint reached bit.
other
3 —
0
1
0
(reserved for extensions)
4
5
6
Running
OPEN
Running
CLOSED
Warning ind.
1
0
1
0
1
Operation command (OPEN or SETPOINT) from
Modbus in direction OPEN is executed. For operation in stepping mode, this signal is also active during an off-time, the dead time, and the reversing prevention.
No operation is carried out via Modbus.
Operation command (CLOSE or SETPOINT) from
Modbus in direction CLOSE is executed. For operation in stepping mode, this signal is also active during an off-time, the dead time, and the reversing prevention.
No operation is carried out via Modbus.
One or several warnings have occurred.
Collective signal: Contains the result of a disjunction
(OR operation) of all bits of the register “Warning signals (page 28)
7 Fault ind.
0
1
0
No warnings are active (all bits of the warnings cancelled).
One or several faults have occurred so that the actuator can no longer be controlled via Modbus (at least one bit set in fault byte).
Collective signal: Contains the result of a disjunction
(OR operation) of all bits of the register “Fault signals”
(page 27).
No faults are active (all bits are cancelled in fault register).
26
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Register 2: Actuator signals
Basic signals originating from the logic
Bit Designation Value Description
1
0 Thermal fault
A thermal fault (motor protection) has occurred.
0 No thermal fault has occurred.
1 Mains fault
1
0
A mains failure has occurred, e.g. phase error.
No mains failure has occurred.
2
3
Remote sw.
position
Local sw.
position
1
0
1
0
Selector switch in position REMOTE.
Selector switch not in position REMOTE.
Selector switch in position LOCAL.
Selector switch not in position LOCAL.
4
5
6
7
LSO (WOEL)
LSC (WSR)
TSO (DOEL)
TSC (DSR)
1
0
1
0
1
0
1
0
Limit switch OPEN left operated.
Limit switch OPEN left not operated.
Limit switch CLOSE right operated.
Limit switch CLOSE right not operated.
Torque switch OPEN left operated (storing).
Torque switch OPEN left not operated.
Torque switch CLOSE right operated (storing).
Torque switch CLOSE right not operated.
Register 3: E2 Actual position
Actual actuator position, complete value, or low register
Condition
Parameter 2 (measured data coding position transmitter) = 0
Parameter 2 (measured data coding position transmitter) = 1
Value
Value range 0..100 %
Value range 0..1000 %
Register 4: Fault signals
The actuator is not ready for remote operation. As soon as one of these signals is set, bit
7 of register 1 will also be set.
Bit Designation Value Description
0
Wrong command
1
Indicates the fact that several operation commands were received simultaneously via Modbus (e.g. Remote
OPEN and Remote CLOSE simultaneously or Remote
CLOSE/ Remote OPEN and Remote SETPOINT (nominal) simultaneously) or that the max. value for a nominal position has been exceeded (setpoint > 1000 or > 100).
1
2
Selector not remote
Thermal fault
0
1
0
1
Operation commands correct
Selector switch: position LOCAL or OFF
Selector switch: position REMOTE
Motor protection has tripped; remedy: resetting local controls via selector switch position RESET after the motor has cooled off.
other
Loss of one phase or incorrect phase sequence.
3 Mains failure
0
1
0
4
5
TSO (DOEL) fault
TSC (DSR) fault
1
0
1
0 other
Torque fault OPEN occurred (only torque or torque before limit, according to type of seating); remedy: resetting using counter command.
other
Torque fault CLOSED occurred (only torque or torque before limit, according to type of seating); remedy: resetting using counter command.
other
27
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Bit Designation Value Description
1
6 — not assigned (reserved for extensions)
0
7 —
1
0 not assigned (reserved for extensions)
Register 5: Warning signals
The warning signals serve only information purposes and do not interrupt or cancel an operation (as opposed to faults). As soon as one of these signals is set, bit 6 of register 1 will be set simultaneously.
Bit Designation Value Description
0
Failure 24 V supply
1
Failure 24 V supply voltage (internal 24 V DC supply outside the permissible range).
1
Channel 2 active
0
1
0 other
Actuator uses channel 2 for communication.
other
2
Loss of transm. signal
1
0
Signal interrupted at position transmitter RWG: For recognition purposes, parameter 1 must be set to value 3 (RWG 4 – 20 mA).
other
3
4
5
Potentiometer fault
Hardwarefault
No reference operation
1
0
1
0
1
Potentiometer fault: in end position CLOSED a value is measured being higher than the one in end position
OPEN.
other
Hardware fault: If this bit is set, the Modbus board must be checked/ replaced.
other
No reference operation: The values of the position transmitter cannot be used as long as the reference operation
(end position OPEN, en position CLOSED) has not been performed. A nominal operation is not possible.
other
6
7
—
—
0
1
0
1
0 not assigned (reserved for extensions) not assigned (reserved for extensions)
Register 6: Physical operation Bit Designation Value Description
0
Rev.prev./ dead time
1
0
1
Reversing prevention/ dead time warning: The actuator does not start as long as reversing prevention or dead time is still active. The bit is set if a operation command is available which cannot be executed immediately. The bit is cancelled as soon as the actuator starts other
1 — not assigned (reserved for extensions)
2
Operation pause
0
1
0
Operation pause other
3
Start stepping mode
1
0
Indicates that the actuator is within the stepping range during active stepping mode. Conditions: position transmitter is provided, stepping mode is active, remote operation is being performed.
other
28
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
4
5
7
Remote
OPEN
Remote
CLOSE
6 Local OPEN
Local
CLOSE
0
1
0
1
0
1
0
1
Remote operation via Modbus in direction OPEN (remote operation bit for logic board set and movement of potentiometer detected). Signalling of this bit requires a position transmitter.
other
Remote operation via Modbus in direction CLOSE (remote operation bit for logic board set and movement of potentiometer detected). Signalling of this bit requires a position transmitter.
other
Actuator runs locally in direction OPEN (local controls or handwheel).
Signalling of this bit requires a position transmitter.
other
Actuator runs locally in direction CLOSE (local controls or handwheel). Signalling of this bit requires a position transmitter.
other
Register 7: Options
Digital inputs and signal loss at analogue inputs
Bit Designation Value Description
0
Dig.
input 1
1
0
Digital input Nr. 1 = 1 (switch closed)
Digital input Nr. 1 = 0 (switch open)
1 Digital input Nr. 2 = 1 (switch closed)
1
Dig.
input 2
2
Dig.
input 3
0
1
0
Digital input Nr. 2 = 0 (switch open)
Digital input Nr. 3 = 1 (switch closed)
Digital input Nr. 3 = 0 (switch open)
3
Dig.
input 4
1
0
1
Digital input Nr. 4 = 1 (switch closed)
Digital input Nr. 4 = 0 (switch open)
4 — Not assigned (reserved for extensions)
0
5
6
Analogue 2 loss
Analogue 3/4 loss
1
0
1
Signal interrupted at analogue input 2 (first free analogue input) i.e. the measured value is more than 0.2
mA lower than the set minimum value.
no signal interruption analogue input 2 detected
Signal interrupted at analogue input 3/4 (second free analogue input) i.e. the measured value is more than
0.2 mA lower than the set minimum value.
no signal interruption analogue input 3/4 detected
7 —
0
1
0 not assigned (reserved for extensions)
Register 8: First analogue input (wiring diagram designation analogue 2)
The data content depends on parameter 22 (coding analogue 2), holding register offset: 0x4015 (hexadezimal), 16405 (dezimal)
Settings:
0: 0 to 100 percent (default value)
1: 0 to 1000 per mil
2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
29
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Register 9: Second analogue input (wiring diagram designation analogue 3/4)
The data content depends on parameter 25 (coding analogue 3/4), holding register offset: 0x4018 (hexadecimal), 16408 (decimal)
Settings:
0: 0 to 100 percent (default value)
1: 1 to 1000 per mil
2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
9.3
Reading the feedback signals from the actuator using status functions
Functions to be used:
Read Input Status (02)
Grey bits are collective signals. They contain the results of a disjunction (OR operation) of other information.
0x2007
0x2008
0x2009
0x200A
0x200B
0x200C
0x200D
0x200E
0x200F
0x2010
0x2011
0x2012
0x2013
0x2014
0x2015
0x2016
0x2017
0x2018
0x2019
Offset
(hexadecimal)
0x2000
0x2001
0x2002
0x2003
0x2004
0x2005
0x2006
Offset
(decimal)
8192
8193
8194
8195
8196
8197
8198
8205
8206
8207
8208
8209
8210
8211
8212
8199
8200
8201
8202
8203
8204
8213
8214
8215
8216
8217
Content
(Description in subclause 9.2)
OPEN position
CLOSED position
Setpoint reached
- -
Running OPEN
Running CLOSE
Warning signals
(refer to page 28, register 5)
Error signals (refer to page 27, register 4)
Thermal fault
Mains failure (phase loss)
Selector switch REMOTE
Selector switch LOCAL
LSO (WOEL)
LSC (WSR)
TSO (DOEL)
TSC (DSR)
Wrong command
Selector switch not remote
Thermal fault
Mains failure (phase loss)
TSO (DOEL) fault
TSC (DSR) fault
- -
- -
24 V power supply failure
Channel 2 active
30
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
0x2025
0x2026
0x2027
0x2028
0x2029
0x202A
0x202B
0x202C
0x202D
0x202E
0x202F
Offset
(hexadecimal)
0x201A
0x201B
0x201C
0x201D
0x201E
0x201F
0x2020
0x2021
0x2022
0x2023
0x2024
8229
8230
8231
8232
8233
8234
8235
8236
8237
8238
8239
Offset
(decimal)
8218
8219
8220
8221
8222
8223
8224
8225
8226
8227
8228
Content
(Description in subclause 9.2)
Signal loss position transmitter
Potentiometer fault (wrong polarity)
Hardware fault
No reference operation
- -
- -
Rev.prev./ dead time
- -
Operation pause
Start stepping mode
Remote OPEN
Remote CLOSE
Local OPEN
Local CLOSE
Digital input 0
Digital input 1
Digital input 2
Digital input 3
- -
Singal loss customer analogue input 1
Signal loss customer analogue input 2
- -
31
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
10.
Process representation output
Via the process representation output, the master (controls) can control the slave (actuator).
10.1 Transmitting operation commands to or reading out from the actuator using register functions
Functions to be used:
Preset Single Register (06); Preset Multiple Register (16);
Read Holding Register (03)
Offset
(hexadecimal)
Offset
(decimal)
Register contents
Register 1: Commands
0x1000 4096
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Register 2: E1 Setpoint
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
0x1002 4098
Holding register operation commands also change the corresponding coils for operation commands.
Operation commands which cannot be executed are rejected with ILLEGAL DATA VALUE (code 03). Operation commands cannot be executed if a thermal fault or mains failure have occurred, or if the local controls are not set to remote, or if commands are contradictory.
If a thermal fault or a mains failure occurs during remote operation, or if the remote operation is switched off via the selector switch, the actuator will cancel all pending operation commands
10.2 Description of the output data
Register 1: Commands (high byte)
With the bits 0 – 2, the operation commands are transmitted to the actuator. Only one of these bits may be set at any given time.
If remote
SETPOINT is set, the value of the nominal position
(register 2) is used.
Bits 3 – 15 are reserved for future extensions and must remain set to 0.
As soon as these bits are written to via coil functions, the contents of the respective
Holding Registers for the operation commands will also change.
If the Coil Remote SETPOINT is used, the respective setpoint has to be entered on the setpoint register.
Bit Designation Value Description
0
Remote
OPEN
1 Running OPEN
0 Not running OPEN
1
2
Remote
CLOSED
Remote
SETPOINT
1 Running CLOSE
0 Not running CLOSE
1
Running to setpoint
Can only be set if a position transmitter e.g. potentiometer/ RWG (options) is available.
3
4
- -
- -
1
0
0 Not running to setpoint.
1
Not assigned (reserved for extensions)
0
Not assigned (reserved for extensions)
5
6
7
- -
- -
- -
1
0
1
0
1
0
Not assigned (reserved for extensions)
Not assigned (reserved for extensions)
Not assigned (reserved for extensions)
32
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Register 2: E1 Setpoint
The setpoint can be transmitted either as a value between
0 – 100 (percent) or 0 – 1000
(per mil). The cange-over between 0 – 100 and 0 – 1000is realised via parameter 2
“Measured data coding position transmitter”. According to this programming, different maximum values apply. When these limits are exceeded, the actuator stops and signals a fault.
Byte 2: Setpoint 0...100 or setpoint 0...1000
Condition
Parameter 2 (measured data coding position transmitter) = 0
Parameter 2 (measured data coding position transmitter) = 1
Value
Setpoint 0...100 %
Setpoint 0...1000 %
10.3 Transmission of operation commands to the actuator using coil functions
Functions to be used:
Force Single Coil (05)
Force Multiple Coils (15)
Read Coil Status (01)
Offset
(hexadecimal)
0x0000
0x0001
0x0002
0
1
Offset
(decimal)
2
Contents
(Description in page 41)
REMOTE OPEN
REMOTE CLOSED
REMOTE SETPOINT
If a Force Coil is set, the other two coils will be deleted by the actuator
(the actuator executes the last command issued).
Coil operation commands also change the corresponding holding register for the operation commands.
.
.
.
.
Operation commands which cannot be executed are rejected with ILLEGAL
DATA VALUE (code 03). Operation commands cannot be executed if: a thermal fault or a power failure have occurred.
the remote controls is not set to REMOTE.
an impermissible nominal value has been set (>100 or >1000).
commands are contradictory (coil contents at Force Multiple Coils or holding registers contradictory).
If a thermal fault or a power failure occurs during remote operation or if the remote operation is switched off, the actuator will cancel the pending operation commands.
33
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
11.
Operation parameters of the actuator
Functions to be used:
The parameters of the AUMA MATIC can be written or read using the following functions:
Preset Single Register (06),
Preset Multiple Register (16), or
Read Holding Register (03)
Parameters should only be changed as a whole parameter record in order to avoid inconsistent parameter records. The Modbus software checks the consistency of parameters and refuses inconsistent parameter records
(ILLEGAL DATA VALUE, code 03).
Parameter 1 “Position transmitter”
Holding Register Offset: 0x4000 (hex.), 16384 (decimal)
Default value (standard setting): 1
0: The actuator is not equipped with a position transmitter.
1: The actuator is equipped with a potentiometer without RWG.
Switch S1.2 on Modbus board must be switched off!
2: Actuator is equipped with an RWG 0 – 20 mA.
For this position transmitter, the signal interruption noitoring is not active.
Switch S1.2 must be switched on!
3: Actuator is equipped with an RWG 4 – 20 mA.
For this position transmitter, the signal interruption monitoring is active.
Switch S1.2 on Modbus board must be switched on!
Parameter 2 “Measured data coding position transmitter”
Holding Register Offset: 0x4001 (hexadecimal), 16385 (decimal)
Default value: 0
0: Feedback signal (register 3, E2 actual position) 0 to 100 percent, resolution is 1 %, setpoint (register 2, E1 actual position) 0 to 100 percent.
1: Feedback signal (register 3, E2 actual position) 0 to 1000 per mil, resolution is 0.1 %, setpoint (register 2, E1 actual position) 0 to 1000 per mil.
Parameter 3 “Reversing prevention in ms”
Parameter for setting the waiting time in between a change of direction.
If necessary, adjust the value to the mechanics to prevent destruction caused by excessively fast changes of direction.
Holding Register Offset: 0x4002 (hexadecimal), 16386 (decimal)
Default value: 200 lowest value: 100 (0.1s) maximum value: 1000 (1 s)
Parameter 4 “Redundancy”
Holding Register Offset: 0x4003 (hexadecimal), 16387 (decimal)
Default value 0
0: no cable redundancy (only the first channel is used for communication).
1: Cable redundancy is switched on (first and second communication channel connected).
34
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Parameter 5 “Time for channel changing in 0.1 s”
Indicates the time after which the channel is changed if no process data, i.e.
expiry of connection control time of 0.1 s, is received. This parameter is only effective if the cable redundancy (parameter 4) is switched on.
Holding Register Offset: 0x4004 (hexadecimal), 16388 (decimal)
Default value: 50 lowest value: 50 (5 s) maximum value: 6000 (10 min)
Parameter 6 “Failure behaviour”
Failure operation on failure of connection.
The parameters set in the most recent connection also apply to the failure behaviour after interruption and restoring of the voltage supply.
Holding Register Offset: 0x4005 (hexadecimal), 16389 (decimal)
Default value: 0
0: Failure behaviour switched off (parameters 7, 8, 9 insignificant)
1: Simple failure behaviour switched on.
A failure operation will only be started if a connection to the master
(process data exchange) was already available.
2: Extended failure behaviour switched on.
If extended failure behaviour is switched on, a failure operation can be initiated immediately after the actuator has been switched on.
Parameter 7 “Delay time for failure operation 0.1 s”
Delay time for failure operation in 0.1 s.
Indicates the down time of process data exchange after which a failure operation will be started. If the exchange is restored during this time, no failure operation will be performed.
Holding Register Offset: 0x4006 (hexadecimal), 16390 (decimal)
Default value: 30 lowest value: 0 (actuator reacts immediately) maximum value: 12,000 (actuator reacts after 20 minutes)
Parameter 8 “Failure operation”
Holding Register Offset: 0x4007 (hexadecimal), 16391 (decimal)
Default value 0
0: The actuator stops (STOP).
1: Actuator runs CLOSE
2: Actuator runs OPEN
3: Actuator runs to failure position.
If no position transmitter is installed (parameter 1 = 0), value 3 is not permitted. In this case, the parameter record is rejected.
Parameter 9 “Failure position in per mil”
Actuator runs to the pre-set failure position.
This parameter is only effective if parameter 8 (failure operation) is set to value 3, and if parameter 6 (failure behaviour) is not 0.
Holding Register Offset: 0x4008 (hexadecimal), 16392 (decimal)
Default value: 0 lowest value: 0 (end position CLOSED) maximum value: 1,000 (end position OPEN)
35
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Parameter 10: not used
For detailed descriptions of parameters 11 to 14, please refer to subclause 12.2
Parameter 11 “Dead time positioner in 0.1 s”
Indicates the dead time which has to be maintained between two motor starts. In case the Modbus master issues a command before that time, the
AUMA MATIC delays the actuator reaction until dead time has expired.
Holding Register Offset: 0x400A (hexadecimal), 16394 (decimal)
The Modbus master of the controls must ensure that the maximum number of motor starts of the actuator is not exceeded.
Default value: 0 minimum value: 0 (actuator reacts immediately) maximum value: 600 (actuator delays reaction by 1 minute max.)
Parameter 12 “Overrun direction OPEN in per mil”
The motor is switched off as soon as the distance between the actuator position and the nominal position reaches this value. This is only valid for operations in direction OPEN.
This parameter must be lower than the value in parameter 14 (max. error in per mil).
Holding Register Offset: 0x400B (hexadecimal), 16395 (decimal)
Default value: 5 minimum value: 0 (no overrun in direction OPEN) maximum value: 100 (10 % overrun in direction OPEN)
Parameter 13 “Overrun direction CLOSE in per mil”
The motor is switched off as soon as the distance between the actuator position and the nominal position reaches this value. This is only valid for operations in direction CLOSE.
This parameter must be smaller than the value in parameter 14 (max. error in per mil).
Holding Register Offset: 0x400C (hexadecimal), 16396 (decimal)
Default value: 5 minimum value: 0 (no overrun in direction CLOSE) maximum value: 100 (10 % overrun in direction CLOSE)
Parameter 14 “Max. error in per mil”
The actuator will only be restarted if the distance between the nominal position and the actual position is higher than this value.
Corresponds to the outer dead band.
This parameter must be higher than the value in parameter 12 (overrun in direction OPEN) and parameter 13 (overrun in direction CLOSE).
The parameter must be set sufficiently high to ensure a stable function of the positioner. If the value is set too low, the actuator moves continuously within nominal value range which will result in reducing the life time of the actuator.
Holding Register Offset: 0x400D (hexadecimal), 16397 (decimal)
Default value: 10 minimum value: 1 (0,1 % error).
maximum value: 100 (10 % error).
36
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Parameters 15 to 19 are not used
Parameter 20 “Start analogue 2 in 0.1 mA”
Current value at which the measuring range of analogue 2 input (option) begins. This value must be smaller than the value in parameter 21 (end analogue 2 in 0.1 mA). If a sensor with 4 – 20 mA signal is connected to the analogue 2 input, the value must be set to 40.
Holding Register Offset: 0x4013 (hexadecimal), 16403 (decimal)
Default value: 0 minimum value: 0 (value for sensor with 0 – 20 mA signal) maximum value: 150 important value: 40 (this corresponds to the correct value for a sensor with a
4 - 20 mA signal)
Parameter 21 “End analogue 2 in 0.1 mA”
Current value at which the measuring range of analogue 2 input (option) ends. This value must be higher than the value in parameter 20 (start analogue 2 in 0.1 mA).
Holding Register Offset: 0x4014 (hexadecimal), 16404 (decimal)
Default value: 200 minimum value: 50 maximum value: 200 (value for sensor with 0 – 20 or 4 – 20 mA signal)
Parameter 22 "Coding analogue 2"
Holding Register Offset: 0x4015 (hexadecimal), 16405 (decimal)
Default value: 0
0: 0 to 100 percent
1: 0 to 1000 per mil
2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
Parameter 23 “Start analogue 3/4 in 0.1 mA”
Current value at which the measuring range of analogue 3/4 input begins.
This value must be smaller than the value in parameter 24 (end analogue 3/4).
If a sensor with a 4 – 20 mA signal is connected to analogue 3/4, the value must be set to 40.
Holding Register Offset: 0x4016 (hexadecimal), 16406 (decimal)
Default value 0 minimum value: 0 (value for sensor with 0 – 20 mA output) maximum value: 150 important value: 40 (this corresponds to the correct value for a sensor with a
4 – 20 mA signal)
Parameter 24 “End analogue 3/4 in 0.1 mA”
Current value at which the measuring range of analogue 3/4 input ends.
This value must be higher than the value in parameter 23 (start analogue 3/4).
Holding Register Offset: 0x4017 (hexadecimal), 16407 (decimal)
Default value: 200 minimum value: 50 maximum value: 200 (value for sensor with 0 – 20 mA or 4 – 20 mA output)
37
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Parameter 25 “Coding analogue 3/4”
Holding Register Offset: 0x4018 (hexadecimal), 16408 (decimal)
Default value: 0
0: 0 to 100 percent
1: 0 to 1000 per mil
2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
The stepping mode increases the number of starts of the actuator. It must be ensured that the maximum number of starts will equally not be exceeded when operating in stepping mode.
Parameter 26 “Stepping direction OPEN active”
This parameter is only effective if parameter 1 (position transmitter) is not 0.
Otherwise, the parameter record will be rejected.
Holding Register Offset: 0x4019 (hexadecimal), 16409 (decimal)
Default value: 0
0: Stepping mode in direction OPEN switched off
1: Stepping mode in direction OPEN switched on
Parameter 27 “Stepping operating time OPEN in 0.1 s”
Stepping operating time direction OPEN in 0.1 s
This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Holding Register Offset: 0x401A (hexadecimal), 16410 (decimal)
Default value: 10 minimum value: 1 (actuator runs 0.1 s per stepping period) maximum value: 36,000 (actuator runs 1 hour per stepping period)
Parameter 28 “Stepping pause time OPEN in 0.1 s”
Stepping pause time direction OPEN in 0.1 s
This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Holding Register Offset: 0x401B (hexadecimal), 16411 (decimal)
Default value 50
Default value: 50 minimum value: 1 (actuator stationary 0.1 s per stepping period) maximum value: 36,000 (actuator stationary 1 hour per stepping period)
Parameter 29 “Stepping start OPEN in per mil”
Start stepping range in direction OPEN with indication of position in per mil.
This value must be smaller than the value in parameter 30 (stepping end
OPEN in per mil). Otherwise, the parameter record will be rejected.
This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Holding Register Offset: 0x401C (hexadecimal), 16412 (decimal)
Default value: 0 minimum value: 0 (stepping mode in direction OPEN begins at position 0, end position CLOSED) maximum value: 999
38
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Parameter 30 “Stepping end OPEN in per mil”
End stepping range in direction OPEN with indication of position in per mil.
This value must be higher than the value in parameter 29 (stepping start
OPEN in per mil). Otherwise, the parameter record will be rejected. This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Holding Register Offset: 0x401D (hexadecimal), 16413 (decimal)
Default value: 1000 minimum value: 1 maximum value: 1,000 (Stepping mode in direction OPEN ends at position
1,000, end position OPEN)
Parameter 31 “Stepping direction CLOSE active”
This parameter is only effective if parameter 1 (position transmitter) is not 0.
Otherwise, the parameter record will be rejected.
Holding Register Offset: 0x401E (hexadecimal), 16414 (decimal)
Default value: 0
0: Stepping mode in direction CLOSE switched off
1: Stepping mode in direction CLOSE switched on
Parameter 32 “Stepping operating time CLOSE in 0.1 s”
Operating time for stepping mode in direction CLOSE. Indication in 0.1
seconds.
This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0.
Holding Register Offset: 0x401F (hexadecimal), 16415 (decimal)
Default value: 10 minimum value: 1 (actuator runs 0.1 s per stepping period) maximum value: 36,000 (actuator runs 1 hour per stepping period)
Parameter 33 “Stepping pause time CLOSE in 0.1 s”
Pause time for stepping mode in direction CLOSE. Indication in 0.1 seconds
This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0. Otherwise, the parameter record will be rejected.
Holding Register Offset: 0x4020 (hexadecimal), 16416 (decimal)
Default value: 50 minimum value: 1 (actuator stationary 0.1 s per stepping period) maximum value: 36,000 (actuator stationary 1 hour per stepping period)
Parameter 34 “Stepping start CLOSE in per mil”
Start stepping range in direction CLOSE with indication of position in per mil.
This value must be higher than the value in parameter 35 (stepping end
CLOSE in per mil). Otherwise, the parameter record will be rejected.
This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0.
Holding Register Offset: 0x4021 (hexadecimal), 16417 (decimal)
Default value: 1000 minimum value: 1 maximum value: 1,000 (Stepping mode in direction CLOSE starts at position
1,000, end position OPEN)
39
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Parameter 35 “Stepping end CLOSED in per mil”
End stepping range in direction CLOSE with indication of position in per mil.
This value must be higher than the value in parameter 34 (stepping start
CLOSE in per mil). This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0. Otherwise, the total parameter record will be rejected.
Holding Register Offset: 0x4022 (hexadecimal), 16418 (decimal)
Default value: 0 minimum value: 0 (stepping mode in direction CLOSE ends at position 0, end position CLOSED) maximum value: 999
Parameters 36 to 50 are spare parameters
They are reserved for extensions.
Default value: 0
Value range: 0 to 65535
40
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
12.
Description of actuator functions
12.1 Operation commands for OPEN/ CLOSE operation
Operation commands are determined by the operation command bits and the nominal value (setpoint) of the Modbus process representation output.
Only one command bit may be set at any given time. If several command bits are set, no operation is performed and the fault signal ‘Wrong command’ is given.
To avoid placing too much strain on the mechanics the actuator is equipped with a (programmable) delay when changing direction (reversing prevention).
The following operation command bits are required for OPEN/ CLOSE operation :
Remote OPEN
Remote CLOSE
Remote operation OPEN / STOP
Remote OPEN = 1 The actuator runs in direction OPEN.
Remote OPEN = 0 The actuator stops.
The actuator is switched off automatically if the end position OPEN
(limit switch LSO [WOEL]) is reached.
Occurring faults (thermal protection, phase failure, torque failure) stop the operation.
Remote operation CLOSE/ STOP
Remote CLOSED = 1 The actuator runs to position CLOSED.
Remote CLOSED = 0 The actuator stops.
The actuator is switched off automatically if the end position CLOSED is reached (limit switch LSC [WSR] for limit seating or LSC [WSR] and TSC
[DSR] for torque seating). Occurring faults (thermal failure, phase failure, torque failure) stop the operation.
Remote operation to setpoint position/ STOP
The positioner can only function if the actuator is equipped with a position transmitter, e.g. potentiometer/ RWG (option).
Remote SETPOINT = 1 The actuator moves to the set nominal value.
Remote SETPOINT = 0 The actuator stops.
The setpoint must be indicated in % or in ‰ (depending on the AUMA user parameter 2 “Measured data coding position transmitter”.
Occurring faults (thermal failure, phase failure, torque failure) stop an operation via the positioner.
With a setpoint of 0 % (0 ‰), the actuator runs to the end position CLOSED.
With a setpoint of 100 % (1000 ‰), the actuator runs to the end position
OPEN. In case the setpoint is more than 100 % (1,000 ‰) , no operation is performed and the fault signal “Wrong command” is given.
12.2 Positioner The positioner is activated via the bit ‘Remote SETPOINT’.
The positioner is a three-position controller. Via the setpoint E1 in the process representation output, the nominal value of the position is transmitted to the actuator as nominal variable.
The positioner integrated in the actuator controls AUMA MATIC provides the position signal for controlling the motor depending on the nominal and actual position value. The feedback signal (actual position E2) is produced internally within the actuator.
The position transmitter compares the nominal value of the position set in the controls to the locally measured actual value of the position. If the difference between nominal value and actual value is higher than the max. error
(parameter 14), the positioner drives the motor, depending on the error, either in direction OPEN or direction CLOSE.
41
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
Figure H: Modulating duty: nominal operation to 50 %
OPEN
100 %
Overrun (inner dead band)
51 %
50,5 %
Setpoint
50 %
49,5 %
49 %
Overrun
Setpoint reached
Max.
error
= 1 %
Motor is switched off
CLOSED 0 % t
The inner dead band determines the switching-off point of the actuator.
The tripping point in both directions can be set via the parameters 12 and
13 (page 35), so that the actuator stops as close as possible to the nominal value.
Max. error (outer dead band)
Dead time
12.3 Stepping mode
The outer dead band determines the switching-on point of the actuator.
If the actual position or a change in nominal value is higher than the max.
permissible error set with parameter 14 (page 36), the motor is started.
The parameter must be set sufficiently high to ensure a stable function of the positioner. If the value is set too low, the number of starts is likely to be increased. Thus, the end of the lifetime of the actuator and valve will be reached sooner.
The dead time prevents the operation to a new nominal position within a pre-defined time period. The time can be between
0 and 1 minute and is set in parameter 11.
The controls must ensure that the maximum number of motor starts of the actuator is not exceeded. This can be achieved by setting the parameter 11 to a sufficiently high value.
For further information on the positioner, please refer to the operation instructions pertaining to the actuator (multi-turn actuator SA(R).../ part-turn actuator SG... with AUMA MATIC AM...).
Stepping mode requires a position transmitter (option).
The stepping mode lengthens the operating time for part of or for the whole travel.
Setting operation and pause times as well as stepping ranges
The operation and pause times (stepping times) in opening or closing direction are set with the parameters 27, 28 and 32, 33. An individual operation and pause time can be set for each direction.
The stepping ranges can be set separately in direction OPEN and CLOSE
(parameter 29, 30 and 34, 35).
Indication of operation in stepping mode
The states of the operation in stepping mode are indicated by the bits 2 and
3 in register 6 of the process representation input.
42
Operation instructions
13.
Failure function
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
The failure function allows the start of failure operations in case of special events, e.g. when the communication between the actuator and the master is interrupted. This function is set with the parameters 6 to 9.
If the actuator is in the failure function, the set failure position is approached via a failure operation.
If the actuator is then moved to another position (e.g. by manual operation), it will try to perform the set failure action while the selector switch is in position REMOTE.
To prevent a new approach to the failure position during manual operation, the selector switch (local controls) must be switched to position ‘LOCAL’ or ‘OFF’ before operating the handwheel.
.
.
The following events can trigger the failure function:
The connection to the master is interrupted.
The master sends no telegrams to the actuator.
As soon as the cause for triggering the failure function is eliminated
(connection restored, master in Operate state), the operation commands from the master can be executed again.
The last operation command having been transmitted to the actuator prior to the connection failure is deleted within the actuator. To ensure a defined behaviour, a valid operation command must be transmitted to the actuator upon resuming communication.
Time behaviour of the failure function
The internal connection control time (1 s) is started with the last Modbus query-response cycle prior to communication failure.
If no valid Modbus telegram was received within this connection control time, the failure function will be initiated with the start of the delay time. At the end of the delay time, the failure action will be executed:
Last Modbus
Query-response cycle
End of the connection control time (1s)
Start of the failure function delay time
End of the failure function delay time
(Parameter 7)
Executing the failure action
43
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
14.
Description Modbus interface
Figure J: Modbus interface board
LEDs: 7 6 5 4 3 2 1 0
Operation instructions
L1 L2 L3 L4
Switch S1
(below cover plate)
1
2
1 6 1
Taster
T1
T2
T3
6 1 1 4
X7
X8 Modbus X11 X12 X10
S1.1
When using the external analogue input X11 AI 3/4, the switch S1.1 must be in position On.
S1.2
Switch for setting the position feedback via position transmitter potentiometers/ RWG (option).
S1.2 = OFF: The actuator is equipped with a potentiometer.
S1.2 = ON: Switch may only be in this position if an RWG (0/4 – 20 mA) is installed in the actuator.
14.1 Indication during system start-up
When starting the system, the LEDs 0 to 7 will be illuminated. LEDs L1 to L4 are switched off. This signifies that the board is correctly started.
After a short time (approx. 1/4 s), the LED L1 (round red LED) will be illuminated and the LEDs 0 to LED 7 will be switched off one after the other. This means that the microcontroller is now operating. If LED L1 is switched off and the LEDs 0 to 7 are still illuminated, then the system is in the reset status (this situation can also be reproduced by constantly pressing push button T1).
14.1.1 Indications of operation LEDs 7 to 0
Indications of operation
LED Default Mode
0 (red)
1 (red)
2 (red)
3 (red)
4 (red)
5 (red)
6 (red)
7 (red)
LED on LED is off torque seating no parity
2 stop bits data exchange bus active local error limit seating even parity
1 stop bit no data exchange state (blinking) no bus active no local error off
Significance
Address
Mode
1
2
4
8
16
32
64 on
Baud rate
Mode
1
2
4
–
–
8
– blinking
LED 0 Indicates torque or limit switching in end position CLOSED
(illuminated for torque switching)
LED 1 Indicates the quantity of the parity bits from the Modbus protocol
(illuminated for No Parity). Only No Parity and Even Parity are supported, Odd paritiy is not supported
44
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
Indicates the quantity of stop bits - 1 or 2 - (illuminated for 2 stop bits)
Is blinking for each incoming telegram which is assigned to the actuator.
Applications LED:
- is blinking in 1 s intervals for normal service
(0.5 s illumination, 0.5 s pause)
- is permanently illuminated in case of initialisation failure
- is blinking twice while Fail Safe status is active.
Is blinking for each telegram which has been recognized at the bus.
Local actuator signal:
- blinking once:
- blinking twice:
Thermal fault
Power failure
- blinking 3 times: TSO (DOEL) fault
- blinking 4 times: TSC (DSR) fault
- blinking 5 times: 24 V power supply > 28.3 V or <18 V indicates the setting mode:
Off:
On:
DEFAULT MODE
ADDRESS MODE
Blinking: BAUD RATE MODE
14.1.2 System displays LEDs L1 to L4
LED L1 indicates the actuator status. If L1 is illuminated, the actuator is ready for operation.
System indications
L1 (red) System is Ok (CPU working)
L2 (red)
L3 (red)
L4 (red)
Actuator runs OPEN
Actuator runs CLOSE not assigned
LEDs L2 to L4 are illuminated if the actuator has received and processed a feasible operation command via the bus. The following combinations are valid:
Operation indications
LED 4 off off off
LED 3 off off on
LED 2 on on on
Signification no operation operation direction OPEN operation direction CLOSE
14.2 Customer input assignment of the Modbus interface (option)
X7 Digital inputs This plug provides pins for 4 digital customer inputs.
Table 6: Digital inputs (galvanically isolated)
4
5
6
Pin
1
2
3
Description
Digital input 1
Digital input 2
Digital input 3
Digital input 4
+ 24 V DC
+ 24 V DC
These signals are freely available inputs which the microcontroller transmits into the process representation input (register 7, bits 0 – 3). The inputs are galvanically isolated and internally connected to 0 V via pull-down resistors.
In an unconnected state, a logical zero is transmitted. To set an input to logical one, + 24 V DC must be applied (pins 5 or 6).
.
For these signals, proposed external wiring diagrams .
(appendix B) must be observed.
The bounce time of the connected switches should not be more than 1 ms.
45
46
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
X11 Second analogue input (analogue 3/4)
An external 0/4 – 20mA sensor for transmitting the measured values via the
Modbus can be connected to this input.
Table 7: Analogue inputs at plug X11
4
5
6
Pin
1
2
3
Description
+ 24 V DC
GND (system ground)
GND (system ground)
AN 3+: analogue signal 0 – 20 mA (plus)
AN 4–: analog signal 0 – 20 mA (minus)
GND (system ground)
If switch S1.1 is set to position ON, then pin 5 (AN 3/4+) is connected to
GND and input AN 3/4– can be used in the same way as AN 2.
If the switch is set to position OFF, a differential measurement between AN
3/4+ and AN 3/4– can be performed.
X12 First analogue input (analogue 2).
An external 0/4 – 20mA sensor for transmitting the measured values via the
Modbus can be connected to this input.
Table 8: Analogue inputs at plug X12 AI 2
Pin
1
2
Description
AN 2: analogue signal (0 – 20 mA)
GND (system ground)
.
.
.
Potential-free differential measurement is not possible due to the presence of a permanent ground (GND) connection.
For these signals, proposed external wiring diagrams
(appendix B) must be observed.
The inputs AN2, AN3, and AN4 do not have galvanic isolation via opto-isolator. The maximum load of the 24 V DC voltage source applied by the sensors must not exceed
40 mA altogether.
14.3 Modbus connection assignment
X8 MODBUS The bus signals and the galvanically isolated power supply for the bus termination are allocated to this plug.
Table 9: Assignment for plug X8
4
5
6
2
3
Pin Description
1 Channel 1: B cable Modbus
Channel 1: A cable Modbus
Channel 2: A cable Modbus (redundant channel)
Channel 2: B cable Modbus (redundant channel)
GND float (Modbus ground)
+ 5 V float (Modbus + 5 V)
14.4 Assignment positioner connections
X10 The signals required for the position transmitter with potentiometer or with
RWG are allocated to this plug.
Table 10: Assignment for plug X10 AI 1
2
3
4
Pin Description
1 + 5 V for potentiometer
AN 1: analogue signal from position transmitter
GND (system ground)
+ 24V for RWG
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
14.5 Checking/ setting the switches on the logic board
The settings on the logic board are already made in the factory, according to the order details.
The logic board is located below the Modbus board.
Figure K: Logic board
S3-2:
Switching-off in end position OPEN.
Switch position has no influence.
When controlling via Profibus DP, switching-off is always realised by limit seating in end position OPEN
S3-2
S2-2
S1-2
Position 1:
Switching-off by limit seating in end position CLOSED
Position 2:
Switching-off by torque seating in end position CLOSED
The setting of the end position seating in end position
CLOSED must be the same on the Modbus board (LED 0 in default mode, figure J, page 44) and on the logic board
(switch S1-2).
Table 11
DIP switch S2-2 Programming
(ON = pressed)
Direction CLOSE Direction OPEN
Self-retaining REMOTE may not be used!
Self-retaining REMOTE
Push-to-run operation REMOTE
Self-retaining LOCAL
Push-to-run operation LOCAL
Blinker transmitter (option)
Torque error: torque switch tripping
(in mid-travel) contained in collective fault signal (insignificant for fieldbus interface)
Blinker transmitter must be deactivated!
Blinker transm. deact.
included not included
47
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
15.
Troubleshooting and corrective actions
15.1 Actuator can not be controlled via Modbus
Operation instructions
1
Actuator cannot be controlled via Modbus continuously illuminated
Modbus board defective
LED ‘SYSTEM OK’ (V1) ?
is blinking is not illuminated
Modbus board not supplied with voltage
Yes EPROM installed on board?
No
Exchange
Modbus board
Install
Modbus EPROM
Yes Operation via local controls possible?
No
Exchange
Modbus board
Check voltage supply of AUMA MATIC
Check fuses
Voltage supply of
Modbus board correct
48
Operation instructions
Yes
Modbus communication correct
1
Voltage supply of Modbus board correct
‘Data Ex.’ illuminated?
(LED 3)
No
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Modbus slave not in Data Exchange mode
Yes
LED 5 illuminated?
(bus active)
No
Master poss. sends data to the wrong slave address
- check master or change slave address of AUMA MATIC
- Baud rate setting, check parity and number of stop bits
- Check RS485 wiring
- Baud rate setting, check parity and number of stop bits
- poss. exchange of
Modbus interface
2
49
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
2
Modbus communication correct blinking once LED 4
(State)
?
blinking twice
Operation instructions
Slave is in failure mode 1) is not illuminated blinking once blinking twice
LED 5 (LocErr) ?
blinking three times blinking four times blinking five times
Thermal fault
Motor overheating
Power failure: mains failure/ overcurrent/ phase loss
TSO (DOEL) fault:
Torque in direction OPEN
TSC (DSR) fault:
Torque in direction CLOSE
Let motor cool off. Eliminate cause of overheating
Check mains connection
Eliminate cause of torque fault
Eliminate cause of torque fault
24 DC power supply fault
Check mains voltage. Poss.
exchange PSU
Modbus board does not signal any fault
Check
Yes
Modbus board
Check logic board
Yes
Operation possible via controls?
Illumination of LED or if operation command is sent via Modbus ?
No
No
No operation command issued by master
Check prgram of controls
Check logic board, motor control and/ or motor
1) refer to setting of application parameters 6, 7, 8, and 9
50
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
15.2 Position feedback does not function .
Check if the voltage at plug (X1) on the Modbus board, pin 3 (-) and pin 2
(+) is subject ot linear incrementation when running open and linear decrement when running close.
The value for position CLOSED should be within the range of 0 to 2 V.
The value for position OPEN should be within the range of 3 to 5 V. The voltage difference between CLOSED and OPEN should be superior to 3V.
15.3 Actuator is not switched off by the limit switch in direction CLOSE
The actuator is set to torque seating.
.
.
Set actuator to limit seating:
Set switch S4 (see figure H, page 44) on the Modbus board to position
‘LIMIT’.
Adjust switch S1-2 on the logic board (see page 47) to position 1.
15.4 Actuator stops immediately after having started .
Set switch S2-2 (blinker transmitter) on the logic board to position ‘ON’.
15.5 Actuator does not signal reference operation, connection failure position transmitter or signal interruption position transmitter
.
.
.
The position transmitter (potentiometer, RWG) is faulty.
Check position transmitter wiring and connection
Check the setting of parameter 1 “Position transmitter”
If the actuator is not equipped with a position transmitter, parameter 1 has to be set to value 0 (no position transmitter)
15.6 Measuring the Modbus signals using an oscilloscope
On the Modbus board, the signal from Modbus channel 1 on the plug (X8
Modbus, refer to page 46) pin 1 (P/B) and pin 2 (N/A) can be checked using a digital oscilloscope.
The off-load voltage between pin 1 (+) and pin 2 (-) must be positive and within the range of 0.8 V and 1.4 V.
Example for correct Modbus signal: Example for incorrect Modbus signal
(Bus only terminated on one side):
51
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
16.
Appendix A Standard wiring diagram
Legend page 53
Original wiring diagram and legend are delivered together with the actuator.
52
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions
16.1 Legend for standard wiring diagram
S 1
S 2
S 3
S 4
F 1, F 2
F 3, F 4
H 1
H 2
H 3
K 1, K 2
K 3, K4
S 11
S 12.1
S 12.2
S 12.3
R 2
F 1
R 1
A 1.8
A 2
A 8
A 13
A 20
TSC
(DSR)
TSO
(DOEL)
Torque switch, closing, clockwise rotation
Torque switch, opening, counterclockwise rotation
LSC
(WSR)
Limit switch, closing, clockwise rotation
LSO
(WOEL)
Limit switch, opening, counterclockwise rotation
Th
H
Potentiometer
Thermoswitch (motor protection)
Heater
Modbus board
Logic board
Power supply board
Bus connection board
Signal and control board
Primary fuses for power supply unit
Secondary fuses
Indication light end position CLOSED
Indication light end position OPEN
Indication light FAULT
Reversing contactors
Control relays for reversing contactors
Selector switch LOCAL – OFF – REMOTE
Push button OPEN
Pusbutton STOP
Push button CLOSE
16.2 Additional information to the wiring diagram legend
Information B:
Local controls
Information F:
Power supply board
Information H:
Modbus board
Modbus
53
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus Operation instructions
17.
Appendix B Proposed external wiring diagram
Digital and analogue inputs are optional.
The two analogue customer connections (AI 3/4 and AI 2) as well as the four digital customer inputs (Dig 1 ...4) are only provided (wired) by the factory if explicitly mentioned in the order.
The 5th digit of the MSP number (refer to name plate) indicates if analogue connections are available.
If the 5th digit is assigned to ‘0’, no external connections are available.
If the 5th digit is assigned to ‘L’, the connections are provided.
Connection of external sensors, 2-wire technology
54
Operation instructions
Connection of external sensors, 3-wire technology
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
55
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Connection of external sensors, 4-wire technology
Operation instructions
56
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
18.
Appendix C Literature references
1. Modicon protocol:
Reference Guide PI-MBUS-300
2. http:/ www.modbus.org
Modbus Application Protocol Specification
Modbus over serial line specification and implementation guide
19.
Appendix D Connecting the cable shield for AUMA MATIC AMExB/ AMExC 01.1
The shield of the fieldbus cable should be largely connected with the respective threads.
Recommended threads e.g. WAZU-EMV/EX supplied by Hugro (refer to www.hugro-gmbh.de).
57
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
Notes
Operation instructions
58
Operation instructions
Index
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus
C
Cable capacity
Cable recommendation
Characteristic impedance
Collective fault signal
Commissioning
Communication
Connection board
Controls
Core cross section (bus cable 19
Core diameter (bus cable) 19
Corrosion protection 5
23
6
10,12
10
19
19
19
47
D
Dead band
Dead time
26,42
26,42
E
Electrical connection
Error
Error variable
F
Failure function
Fault signals
Faults
H
Handwheel
4,11
26
26
43
27
26,48
43
I
Indication lights
L
Limit seating
Literature
Local controls
Loop resistance
10
M
Maintenance 4
Measuring the Modbus signals 51
Motor connection
Motor protection
17
27
N
Name plate 15
26
57
10
19
O
Operating time
Overrun
Overvoltage protection
42
36,42
13
P
Parameter
Coding
Coding analogue 3/4
Dead time positioner
37
38
36
Delay time for failure operation 35
End analogue 37
End analogue 3/4 in 0.1 mA 37
Failure behaviour
Failure operation
Failure position
Max. error
35
35
35
36
Measured data coding
Overrun direction CLOSE
Overrun direction OPEN
Position transmitter
Redundancy
Reversing prevention
Stepping
Stepping direction
34
34
Start analogue 37
Start analogue 3/4 in 0.1 mA 37
38
34
36
36
34
CLOSE active
Stepping end CLOSED
39 in per mil 40
Stepping end OPEN in per mil 39
Stepping operating time
CLOSE in 0.1 s
Stepping operating time
OPEN in 0.1 s
39
38
Stepping pause time
CLOSE in 0.1 s
Stepping pause time
OPEN in 0.1 s
39
38
Stepping start
CLOSE in per mil 39
Stepping start
OPEN in per mil 38
Time for channel changing 35
Parking frame
Part-turn actuators
15
10
Phase failure 41
Plug/ socket connector 10,15,16
Position transmitter
Position transmitter RWG
Positioner
Power supply
41
14
41
11
Process representation
Protective functions
Push-to-run operation
32
6
47
R
Reversing contactors
S
Safety instructions
Screening (bus cable)
Seating
Selector switch
Self-retaining
Signals
Stepping mode
Storage
Switching-off point
10
T
Technical data
Termination resistors
Thyristors
Torque switching
Transfer mode
Transport
7,8,9,16
10,12
10
14
6
5
Trouble shooting and corrective actions 48
W
Wall bracket
Warning signals
Warnings
Wiring diagram
14
28
4,26
52
47
26
38,42
5
42
4
19
47
10
Information also available on the Internet:
Wiring diagram, inspection records and further actuator information can be downloaded directly from the Internet by entering the order no. or
COMM. no (refer to name plate).
Our website: http://www.auma.com
59
Europe
AUMA Riester GmbH & Co. KG
Factory Müllheim
DE-79373 Müllheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 250 [email protected]
www.auma.com
Factory Ostfildern-Nellingen
DE-73747 Ostfildern
Tel +49 711 34803 - 3000
Fax +49 711 34803 - 3034 [email protected]
Service Centre Cologne
DE-50858 Köln
Tel +49 2234 20379 - 00
Fax +49 2234 20379 - 99
Service Centre Magdeburg
DE-39167 Niederndodeleben
Tel +49 39204 759 - 0
Fax +49 39204 759 - 19
Service Centre Bavaria
DE-85748 Garching-Hochbrück
Tel +49 89 329885 - 0
Fax +49 89 329885 - 18
North Office, Ship building sector
DE-21079 Hamburg
Tel +49 40 791 40285
Fax +49 40 791 40286
North Office, Industry
DE-29664 Walsrode
Tel +49 5167 504
Fax +49 5167 565
East Office
DE-39167 Niederndodeleben
Tel +49 39204 75980
Fax +49 39204 75989
West Office
DE-45549 Sprockhövel
Tel +49 2339 9212 - 0
Fax +49 2339 9212 - 15
SoutheWest Office
DE-69488 Birkenau
Tel +49 6201 373149
Fax +49 6201 373150
Württemberg Office
DE-73747 Ostfildern
Tel +49 711 34803 80
Fax +49 711 34803 81
Baden Office
DE-76764 Rheinzabern
Tel +49 7272 76 07 - 23
Fax +49 7272 76 07 - 24
Power plant sector
DE-79373 Müllheim
Tel +49 7631 809 192
Fax +49 7631 809 294
Büro Bavaria
DE-93356 Teugn/Niederbayern
Tel +49 9405 9410 24
Fax +49 9405 9410 25
AUMA Armaturenantriebe GmbH
AT-2512 Tribuswinkel
Tel +43 2252 82540
Fax +43 2252 8254050 [email protected]
AUMA (Schweiz) AG
CH-8965 Berikon
Tel +41 566 400945
Fax +41 566 400948
AUMA Servopohony spol. s.r.o.
CZ-10200 Praha 10
Tel +420 272 700056
Fax +420 272 704125 [email protected]
OY AUMATOR AB
FI-02270 Espoo
Tel +35 895 84022
Fax +35 895 8402300 [email protected]
AUMA France
FR-95157 Taverny Cédex
Tel +33 1 39327272
Fax +33 1 39321755 [email protected]
www.auma.fr
AUMA ACTUATORS Ltd.
GB- Clevedon North Somerset BS21 6QH
Tel +44 1275 871141
Fax +44 1275 875492 [email protected]
AUMA ITALIANA S.R.L.
IT-20023 Cerro Maggiore Milano
Tel +39 0331-51351
Fax +39 0331-517606 [email protected]
www.auma.it
AUMA BENELUX B.V.
NL-2314 XT Leiden
Tel +31 71 581 40 40
Fax +31 71 581 40 49 [email protected]
Fax +351 2 1910 95 99 [email protected]
MEGA Endüstri Kontrol Sistemieri Tic. Ltd. Sti.
TR-06460 Övecler Ankara
Tel +90 312 472 62 70
Fax +90 312 472 62 74 [email protected]
CTS Control Limited Liability Company
UA-02099 Kiyiv
Tel +38 044 566-9971, -8427
Fax +38 044 566-9384 [email protected]
Africa
AUMA South Africa (Pty) Ltd.
ZA-1560 Springs
Tel +27 11 3632880
Fax +27 11 8185248 [email protected]
A.T.E.C.
EG- Cairo
Tel +20 2 3599680 - 3590861
Fax +20 2 3586621 [email protected]
America
AUMA ACTUATORS INC.
US-PA 15317 Canonsburg
Tel +1 724-743-AUMA (2862)
Fax +1 724-743-4711 [email protected]
www.auma-usa.com
AUMA Chile Respresentative Office
CL- La Reina Santiago de Chile
Tel +56 2 821 4108
Fax +56 2 281 9252 [email protected]
AUMA Polska
PL-41-310 Dabrowa Górnicza
Tel +48 32 26156 68
Fax +48 32 26148 23
www.auma.com.pl
AUMA Priwody OOO
RU-141400 Moscow region
Tel +7 095 221 64 28
Fax +7 095 221 64 38 [email protected]
www.auma.ru
ERICHS ARMATUR AB
SE-20039 Malmö
Tel +46 40 311550
Fax +46 40 945515 [email protected]
www.erichsarmatur.se
GRØNBECH & SØNNER A/S
DK-2450 København SV
Tel +45 33 26 63 00
Fax +45 33 26 63 21
www.g-s.dk
IBEROPLAN S.A.
ES-28027 Madrid
Tel +34 91 3717130
Fax +34 91 7427126 [email protected]
D. G. Bellos & Co. O.E.
GR-13671 Acharnai Athens
Tel +30 210 2409485
Fax +30 210 2409486 [email protected]
SIGURD SØRUM A. S.
NO-1301 Sandvika
Tel +47 67572600
Fax +47 67572610 [email protected]
INDUSTRA
PT-2710-297 Sintra
Tel +351 2 1910 95 00
LOOP S. A.
AR-C1140ABP Buenos Aires
Tel +54 11 4307 2141
Fax +54 11 4307 8612 [email protected]
Asvotec Termoindustrial Ltda.
BR-13190-000 Monte Mor/ SP.
Tel +55 19 3879 8735
Fax +55 19 3879 8738 [email protected]
TROY-ONTOR Inc.
CA-L4N 5E9 Barrie Ontario
Tel +1 705 721-8246
Fax +1 705 721-5851 [email protected]
MAN Ferrostaal de Colombia Ltda.
CO- Bogotá D.C.
Tel +57 1 4 011 300
Fax +57 1 4 131 806 [email protected]
www.manferrostaal.com
PROCONTIC Procesos y Control Automático
EC- Quito
Tel +593 2 292 0431
Fax +593 2 292 2343 [email protected]
IESS DE MEXICO S. A. de C. V.
MX-C.P. 02900 Mexico D.F.
Tel +52 55 55 561 701
Fax +52 55 53 563 337 [email protected]
Multi-Valve Latin America S. A.
PE- San Isidro Lima 27
Tel +511 222 1313
Fax +511 222 1880 [email protected]
PASSCO Inc.
PR-00936-4153 San Juan
Tel +18 09 78 77 20 87 85
Fax +18 09 78 77 31 72 77
2005-04-11
Suplibarca
VE- Maracaibo Estado, Zulia
Tel +58 261 7 555 667
Fax +58 261 7 532 259 [email protected]
Asia
AUMA (INDIA) PRIVATE LIMITED
IN-560 058 Bangalore
Tel +91 80 2839 4655
Fax +91 80 2839 2809 [email protected]
www.auma.co.in
AUMA JAPAN Co., Ltd.
JP-210-0848 Kawasaki-ku, Kawasaki-shi Kanagawa
Tel +81 44 329 1061
Fax +81 44 366 2472 [email protected]
AUMA ACTUATORS (Singapore) Pte Ltd.
SG-569551 Singapore
Tel +65 6 4818750
Fax +65 6 4818269 [email protected]
www.auma.com.sg
AUMA Middle East Rep. Office
AE- Dubai
Tel +971 4 3682720
Fax +971 4 3682721 [email protected]
PERFECT CONTROLS Ltd.
HK- Tsuen Wan, Kowloon
Tel +852 2493 7726
Fax +852 2416 3763 [email protected]
DW Controls Co., Ltd.
KR-153-803 Seoul Korea
Tel +82 2 2113 1100
Fax +82 2 2113 1088/1089 [email protected]
www.actuatorbank.com
AL-ARFAJ Eng. Company W. L. L.
KW-22004 Salmiyah
Tel +965 4817448
Fax +965 4817442 [email protected]
BEHZAD Trading Enterprises
QA- Doha
Tel +974 4433 236
Fax +974 4433 237 [email protected]
Sunny Valves and Intertrade Corp. Ltd.
TH-10120 Yannawa Bangkok
Tel +66 2 2400656
Fax +66 2 2401095 [email protected]
Top Advance Enterprises Ltd.
TW- Jhonghe City Taipei Hsien (235)
Tel +886 2 2225 1718
Fax +886 2 8228 1975 [email protected]
www.auma-taiwan.com.tw
AUMA Beijing Representative Office
CN-100029 Beijing
Tel +86 10 8225 3933
Fax +86 10 8225 2496 [email protected]
www.auma-china.com
Australia
BARRON GJM Pty. Ltd.
AU-NSW 1570 Artarmon
Tel +61 294361088
Fax +61 294393413 [email protected]
www.barron.com.au
AUMA Riester GmbH & Co. KG
P. O. Box 1362
D - 79373 Müllheim
Tel +49 (0)7631/809-0
Fax +49 (0)7631/809 250 [email protected]
www.auma.com
AUMA Riester GmbH & Co. KG
P. O. Box 1151
D - 73747 Ostfildern
Tel +49 (0)711 / 34803 0
Fax +49 (0)711 / 34803 34 [email protected]
www.auma.com
For detailed information on AUMA products, please refer to the Internet: www.auma.com
Certificate Registration No.
12 100/104 4269
Y003.953/003/en/1.05
Advertisement